Alarm System Inspection Report Form
Alarm System Inspection Report Form
YES NO N/A
E The fire alarm system documentation is on site and includes a description of the system √
G The fire alarm system has deficiencies noted on the attached pages √
H Comments:
All devices now in good working order, however, Vipond to change the location descriptions as the room #'s have been changed.
Once complete a letter from Vipond verifying this has been completed & tested should be forwarded and added to this file.
The information on this form (and the documents attached here-to) attest to the fact that the equipment listed here-in was tested/inspected in
conformance with applicable codes, bylaws, standards, and the manufacturer's requirements by a qualified technician. The equipment was left in
an operational condition except as noted in the spaces marked "comments". A copy should be maintained on the premises for examination by the
Fire Marshall or Inspector at their request.
Technician #1 Technician #2
YES NO N/A
Output circuits for selective voice paging, including visual indication operates √
Output circuits for selective voice paging trouble operation, including visual indication operates √
Operation of voice paging does not interfere with entitled inhibit time of alert signal and alarm signal √
Circuits for emergency telephone call in operation, including audible and visual indication operates √
Circuits for emergency telephone for operation, including two-way voice communication operates √
YES NO N/A
Control unit or transponder location Main Entrance and above ceiling tile
EMERGENCY POWER SUPPLY TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.3, 5.3.2, 5.33]
YES NO N/A
Correct battery rating as determined by battery calculations based on full system load √
Adequately ventilated √
Generator provides power to the AC circuit serving the fire alarm system. √
Trouble condition at the emergency generator results in an audible common trouble signal and a visual indication at the required
annunciator. √
Battery voltage not less than 85% of its rated capacity after tests completed √
Battery manufacturer and part number FACP- NP7-12T BPS- SLA12-7
Battery manufacturer's date code or ins service date Date 2013 2015
Battery Voltage (main power supply 'ON') is Voltage 27.71 24.30
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 26.39 N/A
in supervisory condition Current (A) 0.201 N/A
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 25.19 N/A
in full load condition Current (A) 0.274 N/A
The charging current is Current (mA) 809 N/A
YES NO N/A
(i) Required supervisory load for 24 h followed by the required full load operation; √
(ii) Silent test using load resistor method for full duration test. √
(v) Replace the batteries with a new set having a current date code/capacity/type √
Reco AH 12 7
Record the battery terminal voltage after tests are completed. VDC 27.01 N/A
ANNUNCIATOR AND REMOTE TROUBLE SIGNAL UNIT TEST & INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.1]
YES NO N/A
Individual alarm and supervisory input zone clearly indicated and separately designated √
Individual alarm and supervisory input zone designation labels are properly identified √
YES NO N/A
Minimum of one alarm zone and one supervisory zone tested per annunciator or sequential display to confirm operation √
Individual alarm and supervisory input zone designation labels are properly identified. √
REMOTE TROUBLE SIGNAL UNIT TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.3]
YES NO N/A
YES NO N/A
Operates as per design and specification, or in accordance with documentation provided in Appendix E. √
DATA COMMUNICATION LINK TEST [Ref. CAN/ULC-S536-04, Clauses 5.1.5, 5.6 Note]
YES NO N/A
Confirm that a trouble signal is received at the control unit or transponder under an open loop fault for each data communication
link (DCL) √
Where fault isolation modules are installed in data communication links serving field devices, wiring shorted on the isolated side,
annunciation of the fault confirmed, and then a device on the source side operated, and activation confirmed at the control unit or √
Where fault isolation in data communication links is provided between control units or transponders and between transponders,
introduce a short circuit fault and confirm annunciation of the fault and operation outside the shorted section between each pair of: √
YES NO N/A
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 9th, 2016
Building Name: Wallaceburg Board Office Address: 420 Creek Street, Wallaceburg Page 1 of 3
By 118 H/S √ √
By 112 H/S √ √
By 108 H/S √ √
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 9th, 2016
Building Name: Wallaceburg Board Office Address: 420 Creek Street, Wallaceburg Page 2 of 3
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 9th, 2016
Building Name: Wallaceburg Board Office Address: 420 Creek Street, Wallaceburg Page 3 of 3
CAN/ULC
EMERGENCY LIGHTING
INDIVIDUAL DEVICE RECORD
Date: August 9th, 2016
Building Name: Wallaceburg Board Office Address: 420 Creek Street, Wallaceburg
1st Floor
Front Entrance RG 36 LER PA-6V7.2 (14) 2 7.10 12:16 276
Mail Room SLC12 250 PA-12V32 (15) 2 13.97 12:12 283
Board Room East RG 36 LER PA-6V7.2 (14) 2 6.89 12:14 294
Entrance to Parking Lot RG 36 LER PA-6V7.2 (09) 2 6.87 12:16 256 X See Repairs List
Centre Doors To Lobby RG 36 LER PA-6V7.2 (11) 4 7.01 12:17 293
By Coatroom RG 36 LER PA-6V7.2 (09) 2 6.87 12:18 286
Northwest Corner RG 36 LER PA-6V7.2 (08) 4 6.92 12:19 287 X See Repairs List
Southwest Corner RG 36 LER PA-6V7.2 (11) 2 6.84 12:20 254
By South Stair RG 36 LER PA-6V7.2 (10) 2 6.83 12:21 261
South Exit RG 36 LER PA-6V7.2 (12) 2 6.89 12:22 271 X See Repairs List
Back of Computer Room RG 36 PA-6V7.2 (12) 3 6.78 12:50 283
Southeast Corner Hall RG 36 LER PA-6V7.2 (12) 4 6.97 12:23 286
Northeast Corner Hall RG 36 LER PA-6V7.2 (11) 2 6.89 12:24 239 X See Repairs List
REPAIRS
# LOCATION DEVICE REPAIR COMPLETED
Fire Alarm Devices
Vipond to reprogram the device locations as the facility has changed their room #'s during construction.
To be completed. All devices have been tested and are in good working order.
Booster Power supply not supervised, upon arrival we found the BPS in trouble as the charger had failed .
Vipond has now corrected, checked by AEI October 12th, 2016.
Emergency Lighting
1 Top Of North Stair RG 36 Replaced battery w/(1) Panasonic LCR067R2P 08/31/2016
2 Exit From Stair RG 36 LER Replaced battery w/(1) Panasonic LCR067R2P 08/31/2016
3 By Elevator RG 36 LER Replaced battery w/(1) Panasonic LCR067R2P 08/31/2016
4 End Of South East Hall RG 36 LER Replaced battery w/(1) Panasonic LCR067R2P 08/31/2016
5 Entrance to Parking Lot RG 36 LER Replaced battery w/(1) Panasonic LCR067R2P 08/31/2016
6 Northwest Corner RG 36 LER Replaced battery w/(1) Panasonic LCR067R2P 08/31/2016
7 South Exit RG 36 LER Replaced battery w/(1) Panasonic LCR067R2P 08/31/2016
8 Northeast Corner Hall RG 36 LER Replaced battery w/(1) Panasonic LCR067R2P 08/31/2016
Additional Comments:
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
DEVICE LEGEND
DEVICE DESCRIPTION
ANN Annunciator
AD Ancillary Device (Note 4)
B Bell
BZ Buzzer
C Chime
CR Control Relay
CT1 Single Input Module (for supervised Class B signal or audio circuits)
CT2 Double Input Module (for supervised Class B signal or audio circuits)
DH Door Hold Open Device
DS Duct Smoke Detector
ET Emergency Telephone
FACP Fire Alarm Control Panel
FH Firefighters Handset
FS Sprinkler Flow Switch
GA 2nd Stage of 2-Stage Pull Station
H Horn
H/S Horn Strobe
HSP Horn Loudspeaker
HT Heat Detector, Fixed Temperature
HT-RES Resetable Heat Detector
K Horn, Klaxon Type
M Manual Pull Station
MAG LOCK Magnetic Door Lock
PS Pressure Switch
RHT Heat Detector, Rate-of-Rise
S Smoke Detector
SA Smoke Alarm, Single Station Type (Note 3)
SP Loudspeaker
SS Sprinkler Supervisory Switch
SV Sprinkler Valve
TS Sprinkler Tamper Switch (Note 2)
V Visual Alarm Appliance
Note 1: Confirmation of wiring supervision to each individual device is only required during installation verification or a complete building audit
of the system and is not required on the annual test.
Note 2: Sprinkler tamper switches cause trouble condition to be annunciated but not an alarm condition.
Note 3: Single station smoke alarms are not part of the fire alarm system but testing of such devices may be required by the authority
having jurisdiction.
Note 4: Identify the specific ancillary devices in the Remark column of Fire Alarm System Device Test and Inspection Record form
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
YES NO N/A
E The fire alarm system documentation is on site and includes a description of the system √
G The fire alarm system has deficiencies noted on the attached pages √
H Comments:
Building is under construction (wire demolition), therefore we could only complete the inspection of emergency lighting.
The information on this form (and the documents attached here-to) attest to the fact that the equipment listed here-in was tested/inspected in
conformance with applicable codes, bylaws, standards, and the manufacturer's requirements by a qualified technician. The equipment was left
in an operational condition except as noted in the spaces marked "comments". A copy should be maintained on the premises for examination
by the Fire Marshall or Inspector at their request.
Technician #1 Technician #2
YES NO N/A
Output circuits for selective voice paging, including visual indication operates √
Output circuits for selective voice paging trouble operation, including visual indication operates √
Operation of voice paging does not interfere with entitled inhibit time of alert signal and alarm signal √
Circuits for emergency telephone call in operation, including audible and visual indication operates √
Circuits for emergency telephone for operation, including two-way voice communication operates √
YES NO N/A
YES NO N/A
EMERGENCY POWER SUPPLY TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.3, 5.3.2, 5.33]
YES NO N/A
Correct battery rating as determined by battery calculations based on full system load √
Adequately ventilated √
Generator provides power to the AC circuit serving the fire alarm system. √
Trouble condition at the emergency generator results in an audible common trouble signal and a visual indication at the required
annunciator. √
Battery voltage not less than 85% of its rated capacity after tests completed √
Battery manufacturer and part number (2) Enersys NP5-12
Battery manufacturer's date code or ins service date Date 2010
Battery Voltage (main power supply 'ON') is Voltage N/A
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage N/A
in supervisory condition Current (A) N/A
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage N/A
in full load condition Current (A) N/A
The charging current is Current (mA) N/A
INDICATE TYPE OF BATTERY TEST PERFORMED (must choose 1 of 5 methods)
YES NO N/A
(i) Required supervisory load for 24 h followed by the required full load operation; √
(ii) Silent test using load resistor method for full duration test. √
(v) Replace the batteries with a new set having a current date code/capacity/type √
Record battery capacity AH N/A
Record the battery terminal voltage after tests are completed. VDC N/A
ANNUNCIATOR AND REMOTE TROUBLE SIGNAL UNIT TEST & INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.1]
YES NO N/A
Individual alarm and supervisory input zone clearly indicated and separately designated √
Individual alarm and supervisory input zone designation labels are properly identified √
YES NO N/A
Minimum of one alarm zone and one supervisory zone tested per annunciator or sequential display to confirm operation √
Individual alarm and supervisory input zone designation labels are properly identified. √
REMOTE TROUBLE SIGNAL UNIT TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.3]
YES NO N/A
YES NO N/A
Operates as per design and specification, or in accordance with documentation provided in Appendix E. √
DATA COMMUNICATION LINK TEST [Ref. CAN/ULC-S536-04, Clauses 5.1.5, 5.6 Note]
YES NO N/A
Confirm that a trouble signal is received at the control unit or transponder under an open loop fault for each data communication link
(DCL) √
Where fault isolation modules are installed in data communication links serving field devices, wiring shorted on the isolated side,
annunciation of the fault confirmed, and then a device on the source side operated, and activation confirmed at the control unit or √
Where fault isolation in data communication links is provided between control units or transponders and between transponders,
introduce a short circuit fault and confirm annunciation of the fault and operation outside the shorted section between each pair of: √
YES NO N/A
Door Holders √
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 8th, 2016
Building Name: Christ the King Address: 227 Thomas Street, Wallaceburg Page 1 of 3
Gym SE Exit M 4
Gym H S-1
Boy's Change Room RHT 4
Girl's Change Room RHT 4
Gym Storage- 1 RHT 4 High
NW Exit M 4
Under Stage HT Under Construction 4
Hall By Gym S (C2M PDI) 4
Exit By Gym M 4
Kitchen By Gym RHT 4
West Exit To Gym M 1 EOL
Hall @ 108 B S-1
Hall West By Room 108 S (C2M PDI) 1
Room 108 RHT (281C) 4
Room 108 M 4
Room 108 B S-1
Hall Centre By Room 106 S (C2M PDI) 1
Room 106 RHT (281C) 4
Room 106 B S-1
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 8th, 2016
Building Name: Christ the King Address: 227 Thomas Street, Wallaceburg Page 2 of 3
Library Exit M 3
Hall By Library B S-1
Staff Room # 122 RHT 1
Slop Sink Room # 124 HT 1
Hall by Room # 109 S (C2M-PDI) 1
Furnace HT 1
Hall By Furnace M 1
Furnace Room M 1
Furnace Room Storage HT 2
100 A B S-1
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 8th, 2016
Building Name: Christ the King Address: 227 Thomas Street, Wallaceburg Page 3 of 3
At Hall To Gym DH
Under Construction
At Hall To Gym AUX Relay S-1
CAN/ULC
EMERGENCY LIGHTING
INDIVIDUAL DEVICE RECORD
Date: August 8th, 2016
By 102 Enerwatt PA-6V12 (10) 2 N/A 11:37 .120 X See Repairs List
Room 108 NV12100 (2) C-Cell 6V12 (11) 6 13.71 11:40 1.141
Gym SE Exit RG 36 LE 450 PA6V7.2 AH (09) 2 N/A 11:50 .800 X See Repairs List
Gym SW Wall RG 36 (2) PA-6V4.5 (10) 2 13.61 11:50 .390
Gym- RightStage RG 36 PA6V7.2 AH (09) 2 N/A 11:50 .100 X See Repairs List
Gym- Left Stage RG 36 Lumacell 6V7 2 7.00 11:50 .270
REPAIRS
# LOCATION DEVICE REPAIR COMPLETED
Fire Alarm
Under Construction- To Be Tested By Others
Emergency Lighting
1 By 102 Enerwatt Replaced Battery w/ (1) Panasonic PA-6V12 08/05/2016
2 Gym SE Exit RG 36 LE 450 Replaced Battery w/ (1) Panasonic PA-6V7.2 08/05/2016
3 Gym- RightStage RG 36 Replaced Battery w/ (1) Panasonic PA-6V7.2 08/05/2016
Additional Comments:
Please note that we were unable to test the fire alarm system due to the building being under construction (wire demolition
A verification of the work preformed by Vince Ferro Construction LTD. will be required.
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
DEVICE LEGEND
DEVICE DESCRIPTION
ANN Annunciator
AD Ancillary Device (Note 4)
B Bell
BZ Buzzer
C Chime
CR Control Relay
CT1 Single Input Module (for supervised Class B signal or audio circuits)
CT2 Double Input Module (for supervised Class B signal or audio circuits)
DH Door Hold Open Device
DS Duct Smoke Detector
ET Emergency Telephone
FACP Fire Alarm Control Panel
FH Firefighters Handset
FS Sprinkler Flow Switch
GA 2nd Stage of 2-Stage Pull Station
H Horn
H/S Horn Strobe
HSP Horn Loudspeaker
HT Heat Detector, Fixed Temperature
HT-RES Resetable Heat Detector
K Horn, Klaxon Type
M Manual Pull Station
MAG LOCK Magnetic Door Lock
PS Pressure Switch
RHT Heat Detector, Rate-of-Rise
S Smoke Detector
SA Smoke Alarm, Single Station Type (Note 3)
SP Loudspeaker
SS Sprinkler Supervisory Switch
SV Sprinkler Valve
TS Sprinkler Tamper Switch (Note 2)
V Visual Alarm Appliance
Note 1: Confirmation of wiring supervision to each individual device is only required during installation verification or a complete building audit
of the system and is not required on the annual test.
Note 2: Sprinkler tamper switches cause trouble condition to be annunciated but not an alarm condition.
Note 3: Single station smoke alarms are not part of the fire alarm system but testing of such devices may be required by the authority
having jurisdiction.
Note 4: Identify the specific ancillary devices in the Remark column of Fire Alarm System Device Test and Inspection Record form
ANNUAL FIRE ALARM SYSTEM TESTING CERTIFICATE
THIS DOCUMENT CERTIFIES THAT THE EMERGENCY LIGHTING AT THE FOLLOWING LOCATION:
HAS BEEN TESTED & INSPECTED IN ACCORDANCE WITH CANADIAN ULC CODES AND DESIGN CRITERIA
DESIGNATED BY MANUFACTURER'S SPECIFICATIONS.
Alert the management of the building that the fire alarm system is being tested and that alternate measures under the Fire
Safety Plan should be implemented.
Check that an alternative plan has been established to alert occupants and the local fire department should an actual fire
condition occur during testing.
Check the Technicians' responsibilities, if any, under that alternative measures of the Fire Safety Plan.
If there is a remote connection to a central station or fire department take necessary steps to alert central station or fire
department.
N/A Are there ancillary functions that can impair building functions such as elevator capture, fan shutdown, door holders, etc.?
N/A Can these be disabled and tested by groups?
√ Have building occupants been made aware of fire alarm testing?
√ Has a pre-determined time been established for testing signalling devices?
√ Have provisions been made for acquiring access to the secured areas of the building?
√ Are there spare reset and panel keys available?
Technician #1 Technician #2
Signature:__________________________ Signature:__________________________
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
CAN/ULC S536-04
SMOKE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 2nd, 2016
Building Name: Maintenance Warehouse Address: 525 Baldoon Road, Chatham Page 1 of 1
CAN/ULC
EMERGENCY LIGHTING
INDIVIDUAL DEVICE RECORD
Date: August 2nd, 2016
Building Name: Maintenance Warehouse Address: 525 Baldoon Road, Chatham Page 1 of 1
1 Wood Shop (West End) 12 MSL360 PA-1233 (10) 2 13.41 1:00 Panel D cct #36
2 Metal Shop @ Mezzanine RG-36 PA-6V12 (14) 2 6.91 1:00 Panel A cct #24
4 Main Entrance 12 MSL360 PA-1233 (08) 2 13.67 1:00 Brk #29 Panel C
REPAIRS
# LOCATION DEVICE REPAIR COMPLETED
Smoke Alarm Devices
1 Library North SA (12V) Replaced Device w/ (1) System Sensor 2012HA 08/31/2016
2 Library South SA (12V) Replaced Device w/ (1) System Sensor 2012HA 08/31/2016
Additional Comments:
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
DEVICE LEGEND
DEVICE DESCRIPTION
ANN Annunciator
AD Ancillary Device (Note 4)
B Bell
BZ Buzzer
C Chime
CR Control Relay
CT1 Single Input Module (for supervised Class B signal or audio circuits)
CT2 Double Input Module (for supervised Class B signal or audio circuits)
DH Door Hold Open Device
DS Duct Smoke Detector
ET Emergency Telephone
FACP Fire Alarm Control Panel
FH Firefighters Handset
FS Sprinkler Flow Switch
GA 2nd Stage of 2-Stage Pull Station
H Horn
H/S Horn Strobe
HSP Horn Loudspeaker
HT Heat Detector, Fixed Temperature
HT-RES Resetable Heat Detector
K Horn, Klaxon Type
M Manual Pull Station
MAG LOCK Magnetic Door Lock
PS Pressure Switch
RHT Heat Detector, Rate-of-Rise
S Smoke Detector
SA Smoke Alarm, Single Station Type (Note 3)
SP Loudspeaker
SS Sprinkler Supervisory Switch
SV Sprinkler Valve
TS Sprinkler Tamper Switch (Note 2)
V Visual Alarm Appliance
Note 1: Confirmation of wiring supervision to each individual device is only required during installation verification or a complete building audit
of the system and is not required on the annual test.
Note 2: Sprinkler tamper switches cause trouble condition to be annunciated but not an alarm condition.
Note 3: Single station smoke alarms are not part of the fire alarm system but testing of such devices may be required by the authority
having jurisdiction.
Note 4: Identify the specific ancillary devices in the Remark column of Fire Alarm System Device Test and Inspection Record form
ANNUAL FIRE ALARM SYSTEM TESTING CERTIFICATE
THIS DOCUMENT CERTIFIES THAT THE SMOKE ALARM SYSTEM AT THE FOLLOWING LOCATION;
BUILDING SERVICES~ 525 BALDOON ROAD, CHATHAM
HAS BEEN TESTED & INSPECTED IN ACCORDANCE WITH THE STANDARD FOR THE INSPECTION AND TESTING
OF FIRE ALARM SYSTEMS, CAN/ULC-S536-04.
A TEST OF ALL EMERGENCY LIGHTING EQUIPMENT WAS ALSO COMPLETED IN ACCORDANCE WITH CANADIAN
ULC CODES AND DESIGN CRITERIA DESIGNATED BY MANUFACTURER'S SPECIFICATIONS.
Alert the management of the building that the fire alarm system is being tested and that alternate measures under the Fire
Safety Plan should be implemented.
Check that an alternative plan has been established to alert occupants and the local fire department should an actual fire
condition occur during testing.
Check the Technicians' responsibilities, if any, under that alternative measures of the Fire Safety Plan.
If there is a remote connection to a central station or fire department take necessary steps to alert central station or fire
department.
N/A Are there ancillary functions that can impair building functions such as elevator capture, fan shutdown, door holders, etc.?
N/A Can these be disabled and tested by groups?
√ Have building occupants been made aware of fire alarm testing?
√ Has a pre-determined time been established for testing signalling devices?
√ Have provisions been made for acquiring access to the secured areas of the building?
N/A Are there spare reset and panel keys available?
Technician #1 Technician #2
Signature:__________________________ Signature:__________________________
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
CAN/ULC S536-04
SMOKE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 18th, 2016
Building Name: Building Services Address: 245 Tecumseh Street, Sarnia Page 1 of 1
DATE
LOCATION DEVICE A B C D E F CODE REMARKS
Office Area Cubicles SA (110V) √ √ 2010
Shop West Wall SA (110V) √ √ 2014
Open Area By Records SA (9V) X 2006 See Repairs List
Records Area SA (9V) X 2006 See Repairs List
Metal Shop SA (9V) X 2006 See Repairs List
Wood Shop SA (9V) X 2006 See Repairs List
Northeast Storage SA (9V) X 2006 See Repairs List
CAN/ULC
EMERGENCY LIGHTING
INDIVIDUAL DEVICE RECORD
Date: July 18th, 2016
REPAIRS
# LOCATION DEVICE REPAIR COMPLETED
Fire Alarm Devices
1 Open Area By Records SA (9V) Replaced Device w/ (1) Kidde 0916 Smoke Detector 07/18/2016
2 Records Area SA (9V) Replaced Device w/ (1) Kidde 0916 Smoke Detector 07/18/2016
3 Metal Shop SA (9V) Replaced Device w/ (1) Kidde 0916 Smoke Detector 07/18/2016
4 Wood Shop SA (9V) Replaced Device w/ (1) Kidde 0916 Smoke Detector 07/18/2016
5 Northeast Storage SA (9V) Replaced Device w/ (1) Kidde 0916 Smoke Detector 07/18/2016
Emergency Lighting
1 Wall at Back of Offices RG36 Replaced Battery w/ (1) Panasonic PA-6V7.2 07/18/2016
2 Wood Shop RG36 Replaced Battery w/ (1) Panasonic PA-6V7.2 07/18/2016
Additional Comments:
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
DEVICE LEGEND
DEVICE DESCRIPTION
ANN Annunciator
AD Ancillary Device (Note 4)
B Bell
BZ Buzzer
C Chime
CR Control Relay
CT1 Single Input Module (for supervised Class B signal or audio circuits)
CT2 Double Input Module (for supervised Class B signal or audio circuits)
DH Door Hold Open Device
DS Duct Smoke Detector
ET Emergency Telephone
FACP Fire Alarm Control Panel
FH Firefighters Handset
FS Sprinkler Flow Switch
GA 2nd Stage of 2-Stage Pull Station
H Horn
H/S Horn Strobe
HSP Horn Loudspeaker
HT Heat Detector, Fixed Temperature
HT-RES Resetable Heat Detector
K Horn, Klaxon Type
M Manual Pull Station
MAG LOCK Magnetic Door Lock
PS Pressure Switch
RHT Heat Detector, Rate-of-Rise
S Smoke Detector
SA Smoke Alarm, Single Station Type (Note 3)
SP Loudspeaker
SS Sprinkler Supervisory Switch
SV Sprinkler Valve
TS Sprinkler Tamper Switch (Note 2)
V Visual Alarm Appliance
Note 1: Confirmation of wiring supervision to each individual device is only required during installation verification or a complete building audit
of the system and is not required on the annual test.
Note 2: Sprinkler tamper switches cause trouble condition to be annunciated but not an alarm condition.
Note 3: Single station smoke alarms are not part of the fire alarm system but testing of such devices may be required by the authority
having jurisdiction.
Note 4: Identify the specific ancillary devices in the Remark column of Fire Alarm System Device Test and Inspection Record form
ANNUAL FIRE ALARM SYSTEM TESTING CERTIFICATE
THIS DOCUMENT CERTIFIES THAT THE SMOKE ALARM SYSTEM AT THE FOLLOWING LOCATION;
FACILITY SERVICES BUILDING~ 245 TECUMSEH ST, SARNIA
HAS BEEN TESTED & INSPECTED IN ACCORDANCE WITH THE STANDARD FOR THE INSPECTION AND TESTING
OF FIRE ALARM SYSTEMS, CAN/ULC-S536-04.
A TEST OF ALL EMERGENCY LIGHTING EQUIPMENT WAS ALSO COMPLETED IN ACCORDANCE WITH CANADIAN
ULC CODES AND DESIGN CRITERIA DESIGNATED BY MANUFACTURER'S SPECIFICATIONS.
YES NO N/A
E The fire alarm system documentation is on site and includes a description of the system √
G The fire alarm system has deficiencies noted on the attached pages √
H Comments:
I A copy of this report has been given to: SCCDSB- Paul Lernout
The information on this form (and the documents attached here-to) attest to the fact that the equipment listed here-in was tested/inspected in
conformance with applicable codes, bylaws, standards, and the manufacturer's requirements by a qualified technician. The equipment was
left in an operational condition except as noted in the spaces marked "comments". A copy should be maintained on the premises for
examination by the Fire Marshall or Inspector at their request.
Technician #1 Technician #2
YES NO NA
Power 'ON' visual indicator √
Common visual trouble signal √
Common audible trouble signal √
Trouble signal silence switch √
Main power supply failure trouble signal operates √
Ground fault tested on positive and negative trouble signal √
Alert signal operation √
Alarm signal operation √
Automatic transfer from alert signal to alarm signal √
Manual transfer from alert signal to alarm signal cancel (acknowledge) feature operates on a two-stage system √
Automatic transfer from alert signal to alarm signal cancel (acknowledge) feature operates on a two-stage system √
Alarm signal silence inhibit function operates √
Alarm signal manual silence operational √
Alarm signal silence visual indication operates √
Alarm signals, when silenced automatically reinitiate upon subsequent alarm √
Alarm signal silence automatic cut-out timer Time: √
Audible and visual alert signals and alarm signals programmed and operate per design and specification; or documentation as detailed
in Appendix C - Description of Fire Alarm System for Inspection and Test Procedures √
Input circuit, alarm and supervisory operation, including audible and visual indication operates √
Input circuit supervision fault causes a trouble indication √
Output circuit alarm indicates operational √
Output circuit supervision fault causes a trouble indication √
Visual indicator test (lamp test) √
Coded Signal sequences operate not less than the required number of times and the correct alarm signal operates thereafter √
Coded signal sequences are not interrupted by subsequent alarm √
Ancillary device by-pass will result in a trouble signal √
Input circuit to output circuit operation, including ancillary device circuits, for correct program operation, as per design and
specification, or documentation as detailed in Appendix C - Description of Fire Alarm System for Inspection and Testing Procedures √
Fire alarm system reset operation √
Main power supply to emergency power supply transfer operates √
Status change confirmation (smoke detectors only) verified [Refer Subsection 5.7.4.3, Status Change Confirmation (Alarm Verification
Feature)] √
Receipt of alarm transmission to the fire signal receiving centre √
Receipt of the supervisory transmission to the fire signal receiving centre √
Receipt of the trouble transmission to the fire signal receiving centre √
Operation of the fire signal receiving centre disconnect means results in a specific trouble at the control unit or transponder and
transmits a trouble to the fire signal receiving centre
√
Record the name and telephone number of the fire signal receiving centre √
Name DAMAR-114650 Gryphons
Phone Number (519) 336-7111
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
YES NO N/A
Output circuits for selective voice paging, including visual indication operates √
Output circuits for selective voice paging trouble operation, including visual indication operates √
Operation of voice paging does not interfere with entitled inhibit time of alert signal and alarm signal √
Circuits for emergency telephone call in operation, including audible and visual indication operates √
Circuits for emergency telephone for operation, including two-way voice communication operates √
YES NO N/A
EMERGENCY POWER SUPPLY TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.3, 5.3.2, 5.33]
YES NO N/A
Correct battery rating as determined by battery calculations based on full system load √
Adequately ventilated √
Generator provides power to the AC circuit serving the fire alarm system. √
Trouble condition at the emergency generator results in an audible common trouble signal and a visual indication at the required
annunciator. √
Battery voltage not less than 85% of its rated capacity after tests completed √
Battery manufacturer and part number (2) Enersys NP12-12 (2) Enersys NP7.2-12
Battery manufacturer's date code or ins service date Date 2015 2015
Battery Voltage (main power supply 'ON') is Voltage 26.90 26.40
Battery voltage and current with main power supply 'OFF' and fire alarm system in Voltage 25.50 26.10
supervisory condition Current (A) 0.430 0.06
Battery voltage and current with main power supply 'OFF' and fire alarm system in Voltage 25.10 24.80
full load condition Current (A) 0.325 1.214
The charging current is Current (mA) 480 920
YES NO N/A
(i) Required supervisory load for 24 h followed by the required full load operation;
(ii) Silent test using load resistor method for full duration test.
(v) Replace the batteries with a new set having a current date code/capacity/type
Record battery capacity AH
Record the battery terminal voltage after tests are completed. VDC
ANNUNCIATOR AND REMOTE TROUBLE SIGNAL UNIT TEST & INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.1]
YES NO N/A
Individual alarm and supervisory input zone clearly indicated and separately designated √
Individual alarm and supervisory input zone designation labels are properly identified √
YES NO N/A
Minimum of one alarm zone and one supervisory zone tested per annunciator or sequential display to confirm operation √
Individual alarm and supervisory input zone designation labels are properly identified. √
REMOTE TROUBLE SIGNAL UNIT TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.3]
YES NO N/A
YES NO N/A
Operates as per design and specification, or in accordance with documentation provided in Appendix E. √
DATA COMMUNICATION LINK TEST [Ref. CAN/ULC-S536-04, Clauses 5.1.5, 5.6 Note]
YES NO N/A
Confirm that a trouble signal is received at the control unit or transponder under an open loop fault for each data communication
link (DCL) √
Where fault isolation modules are installed in data communication links serving field devices, wiring shorted on the isolated side,
annunciation of the fault confirmed, and then a device on the source side operated, and activation confirmed at the control unit or √
Where fault isolation in data communication links is provided between control units or transponders and between transponders,
introduce a short circuit fault and confirm annunciation of the fault and operation outside the shorted section between each pair of: √
YES NO N/A
Door Holders √
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 9th, 2016
Address: 1825 Hogan Drive, Sarnia Building Name: Gregory A. Hogan Page 1 of 4
Room 129B M √ √ 1
Room 129 H √ √ S-B
By 127 H/S √ √ 1
By 127 EOL √ √ 1
Room 127 H/S √ √ S-B
By 127 S (C2M PDI) √ √ 1
By 127 H/S √ √ S-B
By 136 S (C2M PDI) √ √ 1
Room 134 RHT √ √ 1
Room 134 RHT √ √ 1
By 132 H/S √ √ S-A
By 123 S (C2M PDI) √ √ 1
Room 123 H √ √ S-B
Room 121B S (C2M PDI) √ √ 1
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 9th, 2016
Address: 1825 Hogan Drive, Sarnia Building Name: Gregory A. Hogan Page 2 of 4
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 9th, 2016
Address: 1825 Hogan Drive, Sarnia Building Name: Gregory A. Hogan Page 3 of 4
Exit By 114 M √ √ 3
Exit By Scoreboard EOL √ √ 3
Exit By Scoreboard M √ √ 3
Room 114 RHT √ √ 3
Room 114 RHT √ √ 3
By 101 H/S √ √ S-A
By 110 RHT √ √ 3
By 103 S (1400A) √ √ 3
Barrier Free Washroom HT √ √ 3
By 105 S (C2M PDI) √ √ 3
Sink Room RHT √ √ 3
Room Across from 105 RHT √ √ 3
Room 105 RHT √ √ 3
Room 105A RHT √ √ 3
By 105 H/S √ √ S-B
By 105/114 S (C2W BA) √ √ 2
Exit By 114 S (C2M PDI) √ √ 2
Exit By 114 M √ √ 2
Room 105 RHT √ √ 2
By 105 H/S √ √ S-A
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 9th, 2016
Address: 1825 Hogan Drive, Sarnia Building Name: Gregory A. Hogan Page 4 of 4
CAN/ULC
EMERGENCY LIGHTING
INDIVIDUAL DEVICE RECORD
Date: August 9th, 2016
REPAIRS
# LOCATION DEVICE REPAIR COMPLETED
Fire Alarm Devices
Repairs not Required
Emergency Lighting
1 Gym Exit to Hall RG12S36 Replaced Battery w/ (1) Panasonic PA-12V33 08/09/2016
2 Gym Exit By 229-240 RG36LMC Replaced Battery w/ (1) Panasonic PA-6V7.2 08/09/2016
3 Gym Exit Left RG36LMC Replaced Battery w/ (1) Panasonic PA-6V7.2 08/09/2016
4 Gym Exit Right RG36LMC Replaced Battery w/ (1) Panasonic PA-6V7.2 08/09/2016
Hydrant Inspection
Repairs Not Required
Additional Comments:
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
DEVICE LEGEND
DEVICE DESCRIPTION
ANN Annunciator
AD Ancillary Device (Note 4)
B Bell
BZ Buzzer
C Chime
CR Control Relay
CT1 Single Input Module (for supervised Class B signal or audio circuits)
CT2 Double Input Module (for supervised Class B signal or audio circuits)
DH Door Hold Open Device
DS Duct Smoke Detector
ET Emergency Telephone
FACP Fire Alarm Control Panel
FH Firefighters Handset
FS Sprinkler Flow Switch
GA 2nd Stage of 2-Stage Pull Station
H Horn
H/S Horn Strobe
HSP Horn Loudspeaker
HT Heat Detector, Fixed Temperature
HT-RES Resetable Heat Detector
K Horn, Klaxon Type
M Manual Pull Station
MAG LOCK Magnetic Door Lock
PS Pressure Switch
RHT Heat Detector, Rate-of-Rise
S Smoke Detector
SA Smoke Alarm, Single Station Type (Note 3)
SP Loudspeaker
SS Sprinkler Supervisory Switch
SV Sprinkler Valve
TS Sprinkler Tamper Switch (Note 2)
V Visual Alarm Appliance
Note 1: Confirmation of wiring supervision to each individual device is only required during installation verification or a complete building audit
of the system and is not required on the annual test.
Note 2: Sprinkler tamper switches cause trouble condition to be annunciated but not an alarm condition.
Note 3: Single station smoke alarms are not part of the fire alarm system but testing of such devices may be required by the authority
having jurisdiction.
Note 4: Identify the specific ancillary devices in the Remark column of Fire Alarm System Device Test and Inspection Record form
183 Exeter Road, Unit A
London, Ontario
PHONE (519) 652-5086
FAX (519) 652-8719
1. GENERAL:
a) Are the hydrant(s) free from obstructions and accessible? YES
b) Are the hydrant(s) visible and clearly marked? YES
2. WATER SUPPLIES:
a) Was a flow test done? YES
b) Was water flowed from the hydrant for a minimum time of one minute with the valve fully open? YES
c) Was the water free of debris? YES
d) Type of water supply? City Water Supply
3. FIRE HYDRANTS:
a) Was the hydrant valve found? YES
b) Was the hydrant valve open? YES
c) Did the fire hydrant open & operate properly? YES
d) Was the bonnet “O ” ring lubricated? YES
e) Were the outlet caps in place and tight? YES
f) Was water flowed from the hydrant? YES
g) Did the water drain from the barrel properly? YES
h) Was a flow test done? YES
South Hydrant:
i) The static pressure was? 65
k) The pitot reading from an engineered playpipe was 16 Using an outlet size of 2.5
l) The USGPM results are? 671
North Hydrant:
i) The static pressure was? 63
k) The pitot reading from an engineered playpipe was 16 Using an outlet size of 2.5
l) The USGPM results are? 671
NONE
NONE
6. The following items are deficient as per The Ontario Fire Code and need to be corrected immediately:
NONE
The certificate of inspection cannot be issued until all items under section #6 have been completed.
NONE
NOTE: This inspection/test was performed in accordance with The Ontario Fire Code. This inspection does NOT
certify that the fire hydrant installation complies with NFPA, OBC or Ontario Retrofit Reg. #627/92 (an engineer’s
report would be required to certify this).
As per the requirements of The Ontario Fire Codes, the inspecting company must submit this report to the
local Fire Prevention office
THIS DOCUMENT CERTIFIES THAT THE FIRE ALARM SYSTEM AT THE FOLLOWING LOCATION;
GREGORY A. HOGAN 1825 HOGAN DRIVE, SARNIA
HAS BEEN TESTED & INSPECTED IN ACCORDANCE WITH THE STANDARD FOR THE INSPECTION AND TESTING OF
FIRE ALARM SYSTEMS, CAN/ULC-S536-04. THE FIRE HYDRANT HAS ALSO BEEN INSPECTED AT THIS LOCATION.
A TEST OF ALL EMERGENCY LIGHTING EQUIPMENT WAS COMPLETED IN ACCORDANCE WITH CANADIAN
ULC CODES AND DESIGN CRITERIA DESIGNATED BY MANUFACTURER'S SPECIFICATIONS.
YES NO N/A
E The fire alarm system documentation is on site and includes a description of the system √
G The fire alarm system has deficiencies noted on the attached pages √
H Comments:
The information on this form (and the documents attached here-to) attest to the fact that the equipment listed here-in was tested/inspected in
conformance with applicable codes, bylaws, standards, and the manufacturer's requirements by a qualified technician. The equipment was left in
an operational condition except as noted in the spaces marked "comments". A copy should be maintained on the premises for examination by the
Fire Marshall or Inspector at their request.
Technician #1 Technician #2
YES NO N/A
Output circuits for selective voice paging, including visual indication operates √
Output circuits for selective voice paging trouble operation, including visual indication operates √
Operation of voice paging does not interfere with entitled inhibit time of alert signal and alarm signal √
Circuits for emergency telephone call in operation, including audible and visual indication operates √
Circuits for emergency telephone for operation, including two-way voice communication operates √
YES NO N/A
YES NO N/A
EMERGENCY POWER SUPPLY TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.3, 5.3.2, 5.33]
YES NO N/A
Correct battery rating as determined by battery calculations based on full system load √
Adequately ventilated √
Generator provides power to the AC circuit serving the fire alarm system. √
Trouble condition at the emergency generator results in an audible common trouble signal and a visual indication at the required
annunciator. √
Battery voltage not less than 85% of its rated capacity after tests completed √
Battery manufacturer and part number Panasonic LCR1212P
Battery manufacturer's date code or ins service date Date 2012
Battery Voltage (main power supply 'ON') is Voltage 27.49
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 25.45
in supervisory condition Current (A) 0.180
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 24.80
in full load condition Current (A) 1.62
The charging current is Current (mA) 220
YES NO N/A
(i) Required supervisory load for 24 h followed by the required full load operation; √
(ii) Silent test using load resistor method for full duration test. √
(v) Replace the batteries with a new set having a current date code/capacity/type √
Record battery capacity. AH 12
Record the battery terminal voltage after tests are completed. VDC 25.60
ANNUNCIATOR AND REMOTE TROUBLE SIGNAL UNIT TEST & INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.1]
YES NO N/A
Individual alarm and supervisory input zone clearly indicated and separately designated √
Individual alarm and supervisory input zone designation labels are properly identified √
YES NO N/A
Minimum of one alarm zone and one supervisory zone tested per annunciator or sequential display to confirm operation √
Individual alarm and supervisory input zone designation labels are properly identified. √
REMOTE TROUBLE SIGNAL UNIT TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.3]
YES NO N/A
YES NO N/A
Operates as per design and specification, or in accordance with documentation provided in Appendix E. √
DATA COMMUNICATION LINK TEST [Ref. CAN/ULC-S536-04, Clauses 5.1.5, 5.6 Note]
YES NO N/A
Confirm that a trouble signal is received at the control unit or transponder under an open loop fault for each data communication link
(DCL) √
Where fault isolation modules are installed in data communication links serving field devices, wiring shorted on the isolated side,
annunciation of the fault confirmed, and then a device on the source side operated, and activation confirmed at the control unit or √
Where fault isolation in data communication links is provided between control units or transponders and between transponders,
introduce a short circuit fault and confirm annunciation of the fault and operation outside the shorted section between each pair of: √
YES NO N/A
Door Holders √
Tie to Security √
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 25th, 2016
Main Lobby M √ √ 1
Main Lobby Aux Relay √ √ 1
Entrance to Library DH √ √ 1
NAC
Library H/S √ √ 1
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 25th, 2016
Custodian Hallway S √ √ 1
Custodian Storage RHT √ √ 1
Custodian Electrical RHT √ √ 1
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 25th, 2016
East Exit M √ √ 1
Garbage Storage HT √ √ 1
Hall By Girls Changeroom S √ √ 1
Hall By Gym S √ √ 2
Exit By Gym M √ √ 2
NAC
Storage in Room 120 H √ √ 2
Room Coat Room 120 RHT √ √ 1
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 25th, 2016
CAN/ULC
EMERGENCY LIGHTING
INDIVIDUAL DEVICE RECORD
Date: July 25th, 2016
REPAIRS
# LOCATION DEVICE REPAIR COMPLETED
Fire Alarm Devices
No Repairs Required
Emergency Lighting
1 Hall @ Resource SPEXS636 Replaced Batteries w/ (2) Panasonic PA-6V4.5 07/25/2016
2 Library Classroom RG-36 Replaced Battery w/ (1) Panasonic PA-6V7.2 07/25/2016
3 Hall @ Office SPEXS636 Replaced Batteries w/ (2) Panasonic PA-6V4.5 07/25/2016
4 Hall Intersection to Gym SPEXS636 Replaced Batteries w/ (2) Panasonic PA-6V4.5 07/25/2016
5 Hall @ Boys Changeroom SPEXS636 Replaced Batteries w/ (2) Panasonic PA-6V4.5 07/25/2016
6 Exit By Gym Entrance SPEXS636 Replaced Batteries w/ (2) Panasonic PA-6V4.5 07/25/2016
Additional Comments:
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
DEVICE LEGEND
DEVICE DESCRIPTION
ANN Annunciator
AD Ancillary Device (Note 4)
B Bell
BZ Buzzer
C Chime
CR Control Relay
CT1 Single Input Module (for supervised Class B signal or audio circuits)
CT2 Double Input Module (for supervised Class B signal or audio circuits)
DH Door Hold Open Device
DS Duct Smoke Detector
ET Emergency Telephone
FACP Fire Alarm Control Panel
FH Firefighters Handset
FS Sprinkler Flow Switch
GA 2nd Stage of 2-Stage Pull Station
H Horn
H/S Horn Strobe
HSP Horn Loudspeaker
HT Heat Detector, Fixed Temperature
HT-RES Resetable Heat Detector
K Horn, Klaxon Type
M Manual Pull Station
MAG LOCK Magnetic Door Lock
PS Pressure Switch
RHT Heat Detector, Rate-of-Rise
S Smoke Detector
SA Smoke Alarm, Single Station Type (Note 3)
SP Loudspeaker
SS Sprinkler Supervisory Switch
SV Sprinkler Valve
TS Sprinkler Tamper Switch (Note 2)
V Visual Alarm Appliance
Note 1: Confirmation of wiring supervision to each individual device is only required during installation verification or a complete building audit
of the system and is not required on the annual test.
Note 2: Sprinkler tamper switches cause trouble condition to be annunciated but not an alarm condition.
Note 3: Single station smoke alarms are not part of the fire alarm system but testing of such devices may be required by the authority
having jurisdiction.
Note 4: Identify the specific ancillary devices in the Remark column of Fire Alarm System Device Test and Inspection Record form
ANNUAL FIRE ALARM SYSTEM TESTING CERTIFICATE
THIS DOCUMENT CERTIFIES THAT THE FIRE ALARM SYSTEM AT THE FOLLOWING LOCATION;
GEORGE P VANIER~ 20 CECILE AVENUE, CHATHAM
HAS BEEN TESTED & INSPECTED IN ACCORDANCE WITH THE STANDARD FOR THE INSPECTION AND TESTING
OF FIRE ALARM SYSTEMS, CAN/ULC-S536-04.
A TEST OF ALL EMERGENCY LIGHTING EQUIPMENT WAS ALSO COMPLETED IN ACCORDANCE WITH CANADIAN
ULC CODES AND DESIGN CRITERIA DESIGNATED BY MANUFACTURER'S SPECIFICATIONS.
YES NO N/A
E The fire alarm system documentation is on site and includes a description of the system √
G The fire alarm system has deficiencies noted on the attached pages √
H Comments:
The information on this form (and the documents attached here-to) attest to the fact that the equipment listed here-in was tested/inspected in
conformance with applicable codes, bylaws, standards, and the manufacturer's requirements by a qualified technician. The equipment was
left in an operational condition except as noted in the spaces marked "comments". A copy should be maintained on the premises for
examination by the Fire Marshall or Inspector at their request.
Technician #1 Technician #2
YES NO N/A
Output circuits for selective voice paging, including visual indication operates √
Output circuits for selective voice paging trouble operation, including visual indication operates √
Operation of voice paging does not interfere with entitled inhibit time of alert signal and alarm signal √
Circuits for emergency telephone call in operation, including audible and visual indication operates √
Circuits for emergency telephone for operation, including two-way voice communication operates √
YES NO N/A
YES NO N/A
EMERGENCY POWER SUPPLY TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.3, 5.3.2, 5.33]
YES NO N/A
Correct battery rating as determined by battery calculations based on full system load √
Adequately ventilated √
Generator provides power to the AC circuit serving the fire alarm system. √
Trouble condition at the emergency generator results in an audible common trouble signal and a visual indication at the required
annunciator. √
Battery voltage not less than 85% of its rated capacity after tests completed √
Battery manufacturer and part number Main- (2) Enersys NP7-12T
Battery manufacturer's date code or ins service date Date 2013
Battery Voltage (main power supply 'ON') is Voltage 26.70
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 25.20
in supervisory condition Current (A) 0.162
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 25.00
in full load condition Current (A) 0.225
The charging current is Current (mA) 298
INDICATE TYPE OF BATTERY TEST PERFORMED (must choose 1 of 5 methods)
YES NO N/A
(i) Required supervisory load for 24 h followed by the required full load operation; √
(ii) Silent test using load resistor method for full duration test. √
(v) Replace the batteries with a new set having a current date code/capacity/type √
Record battery capacity AH 7
Record the battery terminal voltage after tests are completed. VDC 26.00
YES NO N/A
EMERGENCY POWER SUPPLY TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.3, 5.3.2, 5.33]
YES NO N/A
Correct battery rating as determined by battery calculations based on full system load √
Adequately ventilated √
Generator provides power to the AC circuit serving the fire alarm system. √
Trouble condition at the emergency generator results in an audible common trouble signal and a visual indication at the required
annunciator. √
Battery voltage not less than 85% of its rated capacity after tests completed √
Battery manufacturer and part number Booster- (2) Enersys NP7-12T
Battery manufacturer's date code or ins service date Date 2014
Battery Voltage (main power supply 'ON') is Voltage 26.30
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 25.50
in supervisory condition Current (A) 0.410
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 25.00
in full load condition Current (A) 0.460
The charging current is Current (mA) 292
INDICATE TYPE OF BATTERY TEST PERFORMED (must choose 1 of 5 methods)
YES NO N/A
(i) Required supervisory load for 24 h followed by the required full load operation; √
(ii) Silent test using load resistor method for full duration test. √
(v) Replace the batteries with a new set having a current date code/capacity/type √
Record battery capacity AH 7
Record the battery terminal voltage after tests are completed. VDC 25.70
ANNUNCIATOR AND REMOTE TROUBLE SIGNAL UNIT TEST & INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.1]
YES NO N/A
Individual alarm and supervisory input zone clearly indicated and separately designated √
Individual alarm and supervisory input zone designation labels are properly identified √
YES NO N/A
Minimum of one alarm zone and one supervisory zone tested per annunciator or sequential display to confirm operation √
Individual alarm and supervisory input zone designation labels are properly identified. √
REMOTE TROUBLE SIGNAL UNIT TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.3]
YES NO N/A
YES NO N/A
Operates as per design and specification, or in accordance with documentation provided in Appendix E. √
DATA COMMUNICATION LINK TEST [Ref. CAN/ULC-S536-04, Clauses 5.1.5, 5.6 Note]
YES NO N/A
Confirm that a trouble signal is received at the control unit or transponder under an open loop fault for each data communication link
(DCL) √
Where fault isolation modules are installed in data communication links serving field devices, wiring shorted on the isolated side,
annunciation of the fault confirmed, and then a device on the source side operated, and activation confirmed at the control unit or √
Where fault isolation in data communication links is provided between control units or transponders and between transponders,
introduce a short circuit fault and confirm annunciation of the fault and operation outside the shorted section between each pair of: √
YES NO N/A
Fan Shutdown √
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 4th, 2016
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 4th, 2016
118 S √ √ 037 2
Library H √ √ NAC 2
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 4th, 2016
CAN/ULC
EMERGENCY LIGHTING
INDIVIDUAL DEVICE RECORD
Date: August 4th, 2016
Emergency Lighting
Repairs not Required
Additional Comments:
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
DEVICE LEGEND
DEVICE DESCRIPTION
ANN Annunciator
AD Ancillary Device (Note 4)
B Bell
BZ Buzzer
C Chime
CR Control Relay
CT1 Single Input Module (for supervised Class B signal or audio circuits)
CT2 Double Input Module (for supervised Class B signal or audio circuits)
DH Door Hold Open Device
DS Duct Smoke Detector
ET Emergency Telephone
FACP Fire Alarm Control Panel
FH Firefighters Handset
FS Sprinkler Flow Switch
GA 2nd Stage of 2-Stage Pull Station
H Horn
H/S Horn Strobe
HSP Horn Loudspeaker
HT Heat Detector, Fixed Temperature
HT-RES Resetable Heat Detector
K Horn, Klaxon Type
M Manual Pull Station
MAG LOCK Magnetic Door Lock
PS Pressure Switch
RHT Heat Detector, Rate-of-Rise
S Smoke Detector
SA Smoke Alarm, Single Station Type (Note 3)
SP Loudspeaker
SS Sprinkler Supervisory Switch
SV Sprinkler Valve
TS Sprinkler Tamper Switch (Note 2)
V Visual Alarm Appliance
Note 1: Confirmation of wiring supervision to each individual device is only required during installation verification or a complete building audit
of the system and is not required on the annual test.
Note 2: Sprinkler tamper switches cause trouble condition to be annunciated but not an alarm condition.
Note 3: Single station smoke alarms are not part of the fire alarm system but testing of such devices may be required by the authority
having jurisdiction.
Note 4: Identify the specific ancillary devices in the Remark column of Fire Alarm System Device Test and Inspection Record form
ANNUAL FIRE ALARM SYSTEM TESTING CERTIFICATE
THIS DOCUMENT CERTIFIES THAT THE FIRE ALARM SYSTEM AT THE FOLLOWING LOCATION;
GOOD SHEPHERD~ 4 EDITH STREET, THAMESVILLE
HAS BEEN TESTED & INSPECTED IN ACCORDANCE WITH THE STANDARD FOR THE INSPECTION AND TESTING
OF FIRE ALARM SYSTEMS, CAN/ULC-S536-04.
A TEST OF ALL EMERGENCY LIGHTING EQUIPMENT WAS ALSO COMPLETED IN ACCORDANCE WITH CANADIAN
ULC CODES AND DESIGN CRITERIA DESIGNATED BY MANUFACTURER'S SPECIFICATIONS.
YES NO N/A
E The fire alarm system documentation is on site and includes a description of the system √
G The fire alarm system has deficiencies noted on the attached pages √
H Comments:
I A copy of this report has been given to: St. Clair Catholic District School Board
The information on this form (and the documents attached here-to) attest to the fact that the equipment listed here-in was tested/inspected in
conformance with applicable codes, bylaws, standards, and the manufacturer's requirements by a qualified technician. The equipment was left
in an operational condition except as noted in the spaces marked "comments". A copy should be maintained on the premises for examination
by the Fire Marshall or Inspector at their request.
Technician #1 Technician #2
YES NO N/A
Output circuits for selective voice paging, including visual indication operates √
Output circuits for selective voice paging trouble operation, including visual indication operates √
Operation of voice paging does not interfere with entitled inhibit time of alert signal and alarm signal √
Circuits for emergency telephone call in operation, including audible and visual indication operates √
Circuits for emergency telephone for operation, including two-way voice communication operates √
YES NO N/A
EMERGENCY POWER SUPPLY TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.3, 5.3.2, 5.33]
YES NO N/A
Correct battery rating as determined by battery calculations based on full system load √
Adequately ventilated √
Generator provides power to the AC circuit serving the fire alarm system. √
Trouble condition at the emergency generator results in an audible common trouble signal and a visual indication at the required
annunciator. √
Battery voltage not less than 85% of its rated capacity after tests completed √
Battery manufacturer and part number (4) Panasonic LCR0612P
Battery manufacturer's date code or ins service date Date 2013
Battery Voltage (main power supply 'ON') is Voltage 26.30
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 25.00
in supervisory condition Current (A) 0.255
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 24.90
in full load condition Current (A) 0.76
The charging current is Current (mA) 333
INDICATE TYPE OF BATTERY TEST PERFORMED (must choose 1 of 5 methods)
YES NO N/A
(i) Required supervisory load for 24 h followed by the required full load operation; √
(ii) Silent test using load resistor method for full duration test. √
(v) Replace the batteries with a new set having a current date code/capacity/type √
Record battery capacity AH 12
Record the battery terminal voltage after tests are completed. VDC 25.50
ANNUNCIATOR AND REMOTE TROUBLE SIGNAL UNIT TEST & INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.1]
YES NO N/A
Individual alarm and supervisory input zone clearly indicated and separately designated √
Individual alarm and supervisory input zone designation labels are properly identified √
YES NO N/A
Minimum of one alarm zone and one supervisory zone tested per annunciator or sequential display to confirm operation √
Individual alarm and supervisory input zone designation labels are properly identified. √
REMOTE TROUBLE SIGNAL UNIT TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.3]
YES NO N/A
YES NO N/A
Operates as per design and specification, or in accordance with documentation provided in Appendix E. √
DATA COMMUNICATION LINK TEST [Ref. CAN/ULC-S536-04, Clauses 5.1.5, 5.6 Note]
YES NO N/A
Confirm that a trouble signal is received at the control unit or transponder under an open loop fault for each data communication link
(DCL) √
Where fault isolation modules are installed in data communication links serving field devices, wiring shorted on the isolated side,
annunciation of the fault confirmed, and then a device on the source side operated, and activation confirmed at the control unit or √
Where fault isolation in data communication links is provided between control units or transponders and between transponders,
introduce a short circuit fault and confirm annunciation of the fault and operation outside the shorted section between each pair of: √
YES NO N/A
Door Holders √
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 8th, 2016
Building Name: Holy Family Address: 649 Murray Street, Wallaceburg Page 1 of 4
Gym HT √ √ 3 High
Gym HT √ √ 3 High
Gym HT √ √ 3 High
Gym Exit M √ √ 3
Gym B √ √ S-1
Gym Stage HT √ √ 3
Exit By Gym M √ √ 2
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 8th, 2016
Building Name: Holy Family Address: 649 Murray Street, Wallaceburg Page 2 of 4
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 8th, 2016
Building Name: Holy Family Address: 649 Murray Street, Wallaceburg Page 3 of 4
Side Lobby M √ √ 1
Front Door M √ √ 1
Office RHT √ √ 1
Office Storage RHT √ √ 1
Front Door ANN √ √
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 8th, 2016
Building Name: Holy Family Address: 649 Murray Street, Wallaceburg Page 4 of 4
CAN/ULC
EMERGENCY LIGHTING
INDIVIDUAL DEVICE RECORD
Date: August 8th, 2016
REPAIRS
# LOCATION DEVICE REPAIR COMPLETED
Fire Alarm
1 Fire panel buzzer failed, replaced panel w/ system as other issues were found. 08/24/2016
2 (2) valves not in use, have been disconnected from system. Other valves were not supervised, are 08/24/2016
now supervised upon installation of the new panel
Emergency Lighting
Repairs Not Required
Additional Comments:
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
DEVICE LEGEND
DEVICE DESCRIPTION
ANN Annunciator
AD Ancillary Device (Note 4)
B Bell
BZ Buzzer
C Chime
CR Control Relay
CT1 Single Input Module (for supervised Class B signal or audio circuits)
CT2 Double Input Module (for supervised Class B signal or audio circuits)
DH Door Hold Open Device
DS Duct Smoke Detector
ET Emergency Telephone
FACP Fire Alarm Control Panel
FH Firefighters Handset
FS Sprinkler Flow Switch
GA 2nd Stage of 2-Stage Pull Station
H Horn
H/S Horn Strobe
HSP Horn Loudspeaker
HT Heat Detector, Fixed Temperature
HT-RES Resetable Heat Detector
K Horn, Klaxon Type
M Manual Pull Station
MAG LOCK Magnetic Door Lock
PS Pressure Switch
RHT Heat Detector, Rate-of-Rise
S Smoke Detector
SA Smoke Alarm, Single Station Type (Note 3)
SP Loudspeaker
SS Sprinkler Supervisory Switch
SV Sprinkler Valve
TS Sprinkler Tamper Switch (Note 2)
V Visual Alarm Appliance
Note 1: Confirmation of wiring supervision to each individual device is only required during installation verification or a complete building audit
of the system and is not required on the annual test.
Note 2: Sprinkler tamper switches cause trouble condition to be annunciated but not an alarm condition.
Note 3: Single station smoke alarms are not part of the fire alarm system but testing of such devices may be required by the authority
having jurisdiction.
Note 4: Identify the specific ancillary devices in the Remark column of Fire Alarm System Device Test and Inspection Record form
183 Exeter Road, Unit A
London, Ontario
PHONE (519) 652-5086
FAX (519) 652-8719
1. GENERAL:
a) Are the hydrant(s) free from obstructions and accessible? YES
b) Are the hydrant(s) visible and clearly marked? YES
2. WATER SUPPLIES:
a) Was a flow test done? YES
b) Was water flowed from the hydrant for a minimum time of one minute with the valve fully open? YES
c) Was the water free of debris? YES
d) Type of water supply? City Water Supply
3. FIRE HYDRANTS:
a) Was the hydrant valve found? YES
b) Was the hydrant valve open? YES
c) Did the fire hydrant open & operate properly? YES
d) Was the bonnet “O ” ring lubricated? YES
e) Were the outlet caps in place and tight? YES
f) Was water flowed from the hydrant? YES
g) Did the water drain from the barrel properly? YES
h) Was a flow test done? YES
i) The static pressure was? 72
k) The pitot reading from an engineered playpipe was 12 Using an outlet size of 2.5
l) The USGPM results are? 581
NONE
NONE
6. The following items are deficient as per The Ontario Fire Code and need to be corrected immediately:
NONE
The certificate of inspection cannot be issued until all items under section #7 have been completed.
NONE
NOTE: This inspection/test was performed in accordance with The Ontario Fire Code. This inspection does NOT
certify that the fire hydrant installation complies with NFPA, OBC or Ontario Retrofit Reg. #627/92 (an engineer’s
report would be required to certify this).
LIMITATION OF LIABILITY: It is understood and agreed that the INSPECTOR is NOT an insurer and is NOT
warranting or guaranteeing the adequacy, performance or life expectancy of any structure, item,
component or system in the building. Further, it is mutually agreed that the maximum amount of joint and
several liability the INSPECTOR can incur for any error, mistakes, omissions, breach of contract, breach of
warrantee, negligent hiring, or any other theory of liability including violation of a statue or consumer
protection act is strictly limited to the FEE PAID for the inspection report.
As per the requirements of The Ontario Fire Codes, the inspecting company must submit this report to the
local Fire Prevention office
Notes:
Hydrant @ back of the property.
THIS DOCUMENT CERTIFIES THAT THE FIRE ALARM SYSTEM AT THE FOLLOWING LOCATION;
HOLY FAMILY~ 649 MURRAY STREET, WALLACEBURG
HAS BEEN TESTED & INSPECTED IN ACCORDANCE WITH THE STANDARD FOR THE INSPECTION AND TESTING OF
FIRE ALARM SYSTEMS, CAN/ULC-S536-04. THE FIRE HYDRANT HAS ALSO BEEN INSPECTED AT THIS LOCATION.
A TEST OF ALL EMERGENCY LIGHTING EQUIPMENT WAS COMPLETED IN ACCORDANCE WITH CANADIAN
ULC CODES AND DESIGN CRITERIA DESIGNATED BY MANUFACTURER'S SPECIFICATIONS.
YES NO N/A
E The fire alarm system documentation is on site and includes a description of the system √
G The fire alarm system has deficiencies noted on the attached pages √
H Comments:
I A copy of this report has been given to: Paul Lernout- SCCDSB
The information on this form (and the documents attached here-to) attest to the fact that the equipment listed here-in was tested/inspected in
conformance with applicable codes, bylaws, standards, and the manufacturer's requirements by a qualified technician. The equipment was left in
an operational condition except as noted in the spaces marked "comments". A copy should be maintained on the premises for examination by the
Fire Marshall or Inspector at their request.
Technician #1 Technician #2
Signature:______________________ Signature:______________________
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
YES NO N/A
Output circuits for selective voice paging, including visual indication operates √
Output circuits for selective voice paging trouble operation, including visual indication operates √
Operation of voice paging does not interfere with entitled inhibit time of alert signal and alarm signal √
Circuits for emergency telephone call in operation, including audible and visual indication operates √
Circuits for emergency telephone for operation, including two-way voice communication operates √
YES NO N/A
EMERGENCY POWER SUPPLY TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.3, 5.3.2, 5.33]
YES NO N/A
Correct battery rating as determined by battery calculations based on full system load √
Adequately ventilated √
Generator provides power to the AC circuit serving the fire alarm system. √
Trouble condition at the emergency generator results in an audible common trouble signal and a visual indication at the required
annunciator. √
Battery voltage not less than 85% of its rated capacity after tests completed
Battery manufacturer and part number DSW12-18
Battery manufacturer's date code or ins service date Date 2010
Battery Voltage (main power supply 'ON') is Voltage 27.26
Battery voltage and current with main power supply 'OFF' and fire alarm system in Voltage 25.40
supervisory condition Current (A) 0.43
Battery voltage and current with main power supply 'OFF' and fire alarm system in Voltage 24.70
full load condition Current (A) 1.82
The charging current is Current (mA) 0.45
INDICATE TYPE OF BATTERY TEST PERFORMED (must choose 1 of 5 methods)
YES NO N/A
(i) Required supervisory load for 24 h followed by the required full load operation; √
(ii) Silent test using load resistor method for full duration test. √
(v) Replace the batteries with a new set having a current date code/capacity/type √
Record battery capacity. AH 18
Record the battery terminal voltage after tests are completed. VDC 26.80
ANNUNCIATOR AND REMOTE TROUBLE SIGNAL UNIT TEST & INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.1]
YES NO N/A
Individual alarm and supervisory input zone clearly indicated and separately designated √
Individual alarm and supervisory input zone designation labels are properly identified √
YES NO N/A
Minimum of one alarm zone and one supervisory zone tested per annunciator or sequential display to confirm operation √
Individual alarm and supervisory input zone designation labels are properly identified. √
REMOTE TROUBLE SIGNAL UNIT TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.3]
YES NO N/A
YES NO N/A
Operates as per design and specification, or in accordance with documentation provided in Appendix E. √
DATA COMMUNICATION LINK TEST [Ref. CAN/ULC-S536-04, Clauses 5.1.5, 5.6 Note]
YES NO N/A
Confirm that a trouble signal is received at the control unit or transponder under an open loop fault for each data communication link
(DCL) √
Where fault isolation modules are installed in data communication links serving field devices, wiring shorted on the isolated side,
annunciation of the fault confirmed, and then a device on the source side operated, and activation confirmed at the control unit or √
Where fault isolation in data communication links is provided between control units or transponders and between transponders,
introduce a short circuit fault and confirm annunciation of the fault and operation outside the shorted section between each pair of: √
YES NO N/A
Door Holders √
Fan Shutdown √
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 11th, 2016
Address: 715 London Road, Wyoming Building Name: Holy Rosary Page 1 of 3
Rm 101 H √ √ S-2
Rm 102 H √ √ S-2
105 H √ √ S-2
107 H √ √ S-2
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 11th, 2016
Address: 715 London Road, Wyoming Building Name: Holy Rosary Page 2 of 3
Rm 117 H √ √ S-2
Rm 108 H √ √ S-2
Rm 108 SA (110V) √ √ 2011 Not wired to Fire Panel
Corner by 106 (108) S (SIGA) √ √ 1 016
Rm 121 H √ √ S-2
Rm 121 RHT √ √ 2 022
Rm 110 H √ √ S-2
Rm 112 H √ √ S-2
Hall By 110 H/S √ √ S-1
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 11th, 2016
Address: 715 London Road, Wyoming Building Name: Holy Rosary Page 3 of 3
Rm 129 H √ √ S-2
By Room 129 M √ √ 2 130
CAN/ULC
EMERGENCY LIGHTING
INDIVIDUAL DEVICE RECORD
Date: July 11th, 2016
REPAIRS
# LOCATION DEVICE REPAIR COMPLETED
Fire Alarm Devices
1 Edwards EST Quickstart FA Panel Replace batteries w/(2) Enersys NP18-12 07/11/2016
Emergency Lighting
Repairs not Required
Additional Comments:
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
DEVICE LEGEND
DEVICE DESCRIPTION
ANN Annunciator
AD Ancillary Device (Note 4)
B Bell
BZ Buzzer
C Chime
CR Control Relay
CT1 Single Input Module (for supervised Class B signal or audio circuits)
CT2 Double Input Module (for supervised Class B signal or audio circuits)
DH Door Hold Open Device
DS Duct Smoke Detector
ET Emergency Telephone
FACP Fire Alarm Control Panel
FH Firefighters Handset
FS Sprinkler Flow Switch
GA 2nd Stage of 2-Stage Pull Station
H Horn
H/S Horn Strobe
HSP Horn Loudspeaker
HT Heat Detector, Fixed Temperature
HT-RES Resetable Heat Detector
K Horn, Klaxon Type
M Manual Pull Station
MAG LOCK Magnetic Door Lock
PS Pressure Switch
RHT Heat Detector, Rate-of-Rise
S Smoke Detector
SA Smoke Alarm, Single Station Type (Note 3)
SP Loudspeaker
SS Sprinkler Supervisory Switch
SV Sprinkler Valve
TS Sprinkler Tamper Switch (Note 2)
V Visual Alarm Appliance
Note 1: Confirmation of wiring supervision to each individual device is only required during installation verification or a complete
building audit of the system and is not required on the annual test.
Note 2: Sprinkler tamper switches cause trouble condition to be annunciated but not an alarm condition.
Note 3: Single station smoke alarms are not part of the fire alarm system but testing of such devices may be required by the
authority having jurisdiction.
Note 4: Identify the specific ancillary devices in the Remark column of Fire Alarm System Device Test and Inspection Record form
ANNUAL FIRE ALARM SYSTEM TESTING CERTIFICATE
THIS DOCUMENT CERTIFIES THAT THE FIRE ALARM SYSTEM AT THE FOLLOWING LOCATION;
HOLY ROSARY, 715 LONDON STREET, WYOMING
HAS BEEN TESTED & INSPECTED IN ACCORDANCE WITH THE STANDARD FOR THE INSPECTION AND TESTING
OF FIRE ALARM SYSTEMS, CAN/ULC-S536-04.
A TEST OF ALL EMERGENCY LIGHTING EQUIPMENT WAS ALSO COMPLETED IN ACCORDANCE WITH CANADIAN
ULC CODES AND DESIGN CRITERIA DESIGNATED BY MANUFACTURER'S SPECIFICATIONS.
YES NO N/A
E The fire alarm system documentation is on site and includes a description of the system √
G The fire alarm system has deficiencies noted on the attached pages √
H Comments:
I A copy of this report has been given to: St. Clair Catholic District School Board
The information on this form (and the documents attached here-to) attest to the fact that the equipment listed here-in was tested/inspected in
conformance with applicable codes, bylaws, standards, and the manufacturer's requirements by a qualified technician. The equipment was left
in an operational condition except as noted in the spaces marked "comments". A copy should be maintained on the premises for examination
by the Fire Marshall or Inspector at their request.
Technician #1 Technician #2
YES NO NA
Power 'ON' visual indicator √
Common visual trouble signal √
Common audible trouble signal √
Trouble signal silence switch √
Main power supply failure trouble signal operates √
Ground fault tested on positive and negative trouble signal √
Alert signal operation √
Alarm signal operation √
Automatic transfer from alert signal to alarm signal √
Manual transfer from alert signal to alarm signal cancel (acknowledge) feature operates on a two-stage system √
Automatic transfer from alert signal to alarm signal cancel (acknowledge) feature operates on a two-stage system √
Alarm signal silence inhibit function operates √
Alarm signal manual silence operational √
Alarm signal silence visual indication operates √
Alarm signals, when silenced automatically reinitiate upon subsequent alarm √
Alarm signal silence automatic cut-out timer Time: √
Audible and visual alert signals and alarm signals programmed and operate per design and specification; or documentation as detailed
in Appendix C - Description of Fire Alarm System for Inspection and Test Procedures √
Input circuit, alarm and supervisory operation, including audible and visual indication operates √
Input circuit supervision fault causes a trouble indication √
Output circuit alarm indicates operational √
Output circuit supervision fault causes a trouble indication √
Visual indicator test (lamp test) √
Coded Signal sequences operate not less than the required number of times and the correct alarm signal operates thereafter √
Coded signal sequences are not interrupted by subsequent alarm √
Ancillary device by-pass will result in a trouble signal √
Input circuit to output circuit operation, including ancillary device circuits, for correct program operation, as per design and specification,
or documentation as detailed in Appendix C - Description of Fire Alarm System for Inspection and Testing Procedures √
Fire alarm system reset operation √
Main power supply to emergency power supply transfer operates √
Status change confirmation (smoke detectors only) verified [Refer Subsection 5.7.4.3, Status Change Confirmation (Alarm Verification
Feature)] √
Receipt of alarm transmission to the fire signal receiving centre √
Receipt of the supervisory transmission to the fire signal receiving centre √
Receipt of the trouble transmission to the fire signal receiving centre √
Operation of the fire signal receiving centre disconnect means results in a specific trouble at the control unit or transponder and
transmits a trouble to the fire signal receiving centre
√
Record the name and telephone number of the fire signal receiving centre √
Name DAMAR- 114623- Tigers
Phone Number (800) 265-7562
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
YES NO N/A
Output circuits for selective voice paging, including visual indication operates √
Output circuits for selective voice paging trouble operation, including visual indication operates √
Operation of voice paging does not interfere with entitled inhibit time of alert signal and alarm signal √
Circuits for emergency telephone call in operation, including audible and visual indication operates √
Circuits for emergency telephone for operation, including two-way voice communication operates √
YES NO N/A
YES NO N/A
EMERGENCY POWER SUPPLY TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.3, 5.3.2, 5.33]
YES NO N/A
Correct battery rating as determined by battery calculations based on full system load √
Adequately ventilated √
Generator provides power to the AC circuit serving the fire alarm system. √
Trouble condition at the emergency generator results in an audible common trouble signal and a visual indication at the required
annunciator. √
Battery voltage not less than 85% of its rated capacity after tests completed √
Battery manufacturer and part number FACP -Enersys NP18-12 Booster- Enersys NP7-12
Battery manufacturer's date code or ins service date Date 2015 2015
Battery Voltage (main power supply 'ON') is Voltage 27.30 26.89
Battery voltage and current with main power supply 'OFF' and fire alarm Voltage 25.59 25.79
system in supervisory condition Current (A) 0.13 0.27
Battery voltage and current with main power supply 'OFF' and fire alarm Voltage 24.78 25.66
system in full load condition Current (A) 2.620 0.95
The charging current is Current (mA) 0.99 0.30
INDICATE TYPE OF BATTERY TEST PERFORMED (must choose 1 of 5 methods)
YES NO N/A
(i) Required supervisory load for 24 h followed by the required full load operation; √
(ii) Silent test using load resistor method for full duration test. √
(v) Replace the batteries with a new set having a current date code/capacity/type √
Record battery capacity AH FACP - 18 Booster- 7
Record the battery terminal voltage after tests are completed. VDC 26.9 26.6
ANNUNCIATOR AND REMOTE TROUBLE SIGNAL UNIT TEST & INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.1]
YES NO N/A
Individual alarm and supervisory input zone clearly indicated and separately designated √
Individual alarm and supervisory input zone designation labels are properly identified √
YES NO N/A
Minimum of one alarm zone and one supervisory zone tested per annunciator or sequential display to confirm operation √
Individual alarm and supervisory input zone designation labels are properly identified. √
REMOTE TROUBLE SIGNAL UNIT TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.3]
YES NO N/A
YES NO N/A
Operates as per design and specification, or in accordance with documentation provided in Appendix E. √
DATA COMMUNICATION LINK TEST [Ref. CAN/ULC-S536-04, Clauses 5.1.5, 5.6 Note]
YES NO N/A
Confirm that a trouble signal is received at the control unit or transponder under an open loop fault for each data communication link
(DCL) √
Where fault isolation modules are installed in data communication links serving field devices, wiring shorted on the isolated side,
annunciation of the fault confirmed, and then a device on the source side operated, and activation confirmed at the control unit or √
Where fault isolation in data communication links is provided between control units or transponders and between transponders,
introduce a short circuit fault and confirm annunciation of the fault and operation outside the shorted section between each pair of: √
YES NO N/A
Door Holders √
Fan Shutdown √
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 8th, 2016
Room 107 CR √ √
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 8th, 2016
CAN/ULC S536-04
FIRE ALARM- Other Devices
INDIVIDUAL DEVICE RECORD
Date: July 8th, 2016
Kitchen IM √ √ 036
Kitchen IM √ √ 037
Penthouse IM √ √ 049
Penthouse IM √ √ 050
Kitchen CR √ √ 134
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 8th, 2016
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 8th, 2016
CAN/ULC S536-04
FIRE ALARM- Sprinkler
INDIVIDUAL DEVICE RECORD
Date: July 8th, 2016
CAN/ULC
EMERGENCY LIGHTING
INDIVIDUAL DEVICE RECORD
Date: July 8th, 2016
2 Room 125B Stage Storage RG12S250 (4) PA-6V12 (14) 14.01 3:15 Panel C
3 Penthouse (ST 1.1) RG12S250 (4) PA-6V12 (14) 13.49 3:15 Panel M4
4 Custodian Room 115 RG12S250 (4) PA-6V12 (15) 13.78 3:15 Panel E
5 Staffroom By Washrooms 106 RG12S250 (4) PA-6V12 (15) 13.72 3:15 Panel A
6 Elect. Rm 105A @ Front Door RG12S250 (4) PA-6V12 (15) 14.00 3:15 Panel A
*Panel Locations*
By 135-Panel D 54
By 125B- Panel C 60
Rm 115- Panel E 10
Penthouse-Panel M4 7
Rm 105A-Panel A 46/1
Penthouse-Panel DP2
REPAIRS
# LOCATION DEVICE REPAIR COMPLETED
Fire Alarm Devices
Repairs Not Required
Emergency Lighting
Repairs Not Required
Additional Comments:
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
DEVICE LEGEND
DEVICE DESCRIPTION
ANN Annunciator
AD Ancillary Device (Note 4)
B Bell
BZ Buzzer
C Chime
CR Control Relay
CT1 Single Input Module (for supervised Class B signal or audio circuits)
CT2 Double Input Module (for supervised Class B signal or audio circuits)
DH Door Hold Open Device
DS Duct Smoke Detector
ET Emergency Telephone
FACP Fire Alarm Control Panel
FH Firefighters Handset
FS Sprinkler Flow Switch
GA 2nd Stage of 2-Stage Pull Station
H Horn
H/S Horn Strobe
HSP Horn Loudspeaker
HT Heat Detector, Fixed Temperature
HT-RES Resetable Heat Detector
IM/ISO Isolator Module
K Horn, Klaxon Type
M Manual Pull Station
MAG LOCK Magnetic Door Lock
PS Pressure Switch
RHT Heat Detector, Rate-of-Rise
S Smoke Detector
SA Smoke Alarm, Single Station Type (Note 3)
SP Loudspeaker
SS Sprinkler Supervisory Switch
SV Sprinkler Valve
TS Sprinkler Tamper Switch (Note 2)
V Visual Alarm Appliance
Note 1: Confirmation of wiring supervision to each individual device is only required during installation verification or a complete building audit
of the system and is not required on the annual test.
Note 2: Sprinkler tamper switches cause trouble condition to be annunciated but not an alarm condition.
Note 3: Single station smoke alarms are not part of the fire alarm system but testing of such devices may be required by the authority
having jurisdiction.
Note 4: Identify the specific ancillary devices in the Remark column of Fire Alarm System Device Test and Inspection Record form
183 Exeter Road, Unit A
London, Ontario
PHONE (519) 652-5086
FAX (519) 652-8719
1. GENERAL:
2. CONTROL VALVES:
3. WATER SUPPLIES:
a) Are siamese connections in good condition, couplings spin freely, caps in place and ball drips open? Yes
(Chrome)
Hydrant # 1:
i) The static pressure was? 68
j) The pitot reading from an engineered playpipe was 34 Using an outlet size of 2.5
k) The USGPM results are? 978
6. WET SYSTEMS:
a) Are all sprinklers in good condition, free from obstruction, corrosion and loading? Yes
b) Are the sprinklers less than 50 years old? (2009) Yes
c) Are there spare sprinklers and a wrench in the head cabinet? Yes
d) Is the condition of the piping, drain valves, hangers and gauges in good condition? Yes
e) Have the sprinklers been checked for the proper temperature rating in various locations where possible? Yes
13. LISTED ARE RECENT CHANGES IN THE BUILDING OCCUPANCY OR FIRE PROTECTION EQUIPMENT:
NONE
NONE
NONE
The above items are deficient as per The Ontario Fire Code and need to be corrected immediately. A certificate of inspection
cannot be issued until all items under section #15 have been addressed. Consultation with the local fire prevention office is
suggested, if discrepancies occur
NONE
NOTE: This inspection/test was performed in accordance with The Ontario Fire Code. This inspection does NOT certify that the
sprinkler system installation complies with NFPA, OBC or Ontario Retrofit Reg. #627/92 (an engineer’s report would be required to
certify this).
• LIMITATION OF LIABILITY: It is understood and agreed that the INSPECTOR is NOT an insurer and is NOT warranting or
guaranteeing the adequacy, performance or life expectancy of any structure, item, component or system in the building.
Further, it is mutually agreed that the maximum amount of joint and several liability the INSPECTOR can incur for any error,
mistakes, omissions, breach of contract, breach of warrantee, negligent hiring, or any other theory of liability including violation
of a statute or consumer protection act is strictly limited to the FEE PAID for the inspection report.
THIS DOCUMENT CERTIFIES THAT THE FIRE ALARM SYSTEM AT THE FOLLOWING LOCATION;
HOLY TRINITY~ 60 LORNE CRESCENT, SARNIA
HAS BEEN TESTED & INSPECTED IN ACCORDANCE WITH THE STANDARD FOR THE INSPECTION AND TESTING OF
FIRE ALARM SYSTEMS, CAN/ULC-S536-04. THE FIRE HYDRANT AND SPRINKLER SYSTEM HAVE ALSO BEEN
INSPECTED AT THIS LOCATION.
A TEST OF ALL EMERGENCY LIGHTING EQUIPMENT WAS COMPLETED IN ACCORDANCE WITH CANADIAN
ULC CODES AND DESIGN CRITERIA DESIGNATED BY MANUFACTURER'S SPECIFICATIONS.
YES NO N/A
E The fire alarm system documentation is on site and includes a description of the system √
G The fire alarm system has deficiencies noted on the attached pages √
H Comments:
I A copy of this report has been given to: Paul Lernout - SCCDSB
The information on this form (and the documents attached here-to) attest to the fact that the equipment listed here-in was tested/inspected in
conformance with applicable codes, bylaws, standards, and the manufacturer's requirements by a qualified technician. The equipment was left in
an operational condition except as noted in the spaces marked "comments". A copy should be maintained on the premises for examination by
the Fire Marshall or Inspector at their request.
Technician #1 Technician #2
YES NO NA
YES NO N/A
Output circuits for selective voice paging, including visual indication operates √
Output circuits for selective voice paging trouble operation, including visual indication operates √
Operation of voice paging does not interfere with entitled inhibit time of alert signal and alarm signal √
Circuits for emergency telephone call in operation, including audible and visual indication operates √
Circuits for emergency telephone for operation, including two-way voice communication operates √
YES NO N/A
EMERGENCY POWER SUPPLY TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.3, 5.3.2, 5.33]
YES NO N/A
Correct battery rating as determined by battery calculations based on full system load √
Adequately ventilated √
Generator provides power to the AC circuit serving the fire alarm system. √
Trouble condition at the emergency generator results in an audible common trouble signal and a visual indication at the required
annunciator. √
Battery voltage not less than 85% of its rated capacity after tests completed √
Battery manufacturer and part number (2) Enersys NP18-12B
Battery manufacturer's date code or ins service date Date 2013
Battery Voltage (main power supply 'ON') is Voltage 26.40
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 25.60
in supervisory condition Current (A) 0.158
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 25.30
in full load condition Current (A) 1.661
The charging current is Current (mA) 451
(i) Required supervisory load for 24 h followed by the required full load operation; √
(ii) Silent test using load resistor method for full duration test. √
(v) Replace the batteries with a new set having a current date code/capacity/type √
Record the battery terminal voltage after tests are completed. VDC 25.90
ANNUNCIATOR AND REMOTE TROUBLE SIGNAL UNIT TEST & INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.1]
YES NO N/A
Individual alarm and supervisory input zone clearly indicated and separately designated √
Individual alarm and supervisory input zone designation labels are properly identified √
YES NO N/A
Minimum of one alarm zone and one supervisory zone tested per annunciator or sequential display to confirm operation √
Individual alarm and supervisory input zone designation labels are properly identified. √
REMOTE TROUBLE SIGNAL UNIT TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.3]
YES NO N/A
YES NO N/A
Operates as per design and specification, or in accordance with documentation provided in Appendix E. √
DATA COMMUNICATION LINK TEST [Ref. CAN/ULC-S536-04, Clauses 5.1.5, 5.6 Note]
YES NO √
Confirm that a trouble signal is received at the control unit or transponder under an open loop fault for each data communication link
(DCL) √
Where fault isolation modules are installed in data communication links serving field devices, wiring shorted on the isolated side,
annunciation of the fault confirmed, and then a device on the source side operated, and activation confirmed at the control unit or √
Where fault isolation in data communication links is provided between control units or transponders and between transponders, introduce
a short circuit fault and confirm annunciation of the fault and operation outside the shorted section between each pair of: √
YES NO N/A
Doorholders √
√
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 18th, 2016
Building Name: Monsignor John Uyen Address: 255 Lark Street, Chatham Page 1 of 3
Front Entrance M √ √ 1
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 18th, 2016
Building Name: Monsignor John Uyen Address: 255 Lark Street, Chatham Page 2 of 3
In 127 M √ √ 2
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 18th, 2016
Building Name: Monsignor John Uyen Address: 255 Lark Street, Chatham Page 3 of 3
CAN/ULC
EMERGENCY LIGHTING
INDIVIDUAL DEVICE RECORD
Date: August 18th, 2016
Building Name: Monsignor John Uyen Address: 255 Lark Street, Chatham
Gym Exit Right SPEXS10721 (2) Enerwatt 6V4.5 (12) 2 13.60 12:30 .670
Gym Exit to Hall SPEXS10721 (2) PA-6V4.5 (14) 3 13.70 12:30 .801
Hall By Office by Boys W/C SPEXS10721 (2) Enerwatt 6V4.5 (13) 3 13.75 12:30 .551
Hall By Principal SPEXS10721 (2) PA-6V4.5 (09) 2 13.88 12:30 .501 X See Repairs List
Hall By Locker 39 SPEXS10721 (2) Enerwatt 6V4.5 (11) 2 13.76 12:30 .675
Exit By Stage Exit SPEXS10721 (2) Enerwatt 6V4.5 (12) 2 13.70 12:30 .781
Hall By Room 1 SPEXS10721 (2) Enerwatt 6V4.5 (13) 4 13.81 12:30 .741
Hall By Library SPEXS10721 (2) Enerwatt 6V4.5 (11) 2 13.65 12:30 .691
Library Left Exit SPEXS10721 (2) Enerwatt 6V4.5 (12) 2 13.75 12:30 .801
Library Left By Theatre SPEXS10721 (2) PA-6V4.5 (12) 3 13.69 12:30 .767
Library Rear SPEXS10721 (2) PA-6V4.5 (09) 2 13.56 12:30 .681 X See Repairs List
Exit By Washroom SPEXS10721 (2) PA-6V4.5 (15) 2 14.01 12:30 .900
Library Right By Theatre SPEXS10721 (2) PA-6V4.5 (14) 3 13.49 12:30 .850
Library Right Exit SPEXS10721 (2) PA-6V4.5 (12) 3 13.98 12:30 .775
Library Room Exit SPEXS10721 (2) PA-6V4.5 (09) 2 13.75 12:30 .881
Boiler Room Exit SPEXS10721 (2) PA-6V4.5 (11) 3 13.81 12:30 .681
Portapac Hallway Exit SPEXS10721 (2) Enerwatt 6V4.5 (12) 2 13.78 12:30 .781
REPAIRS
# LOCATION DEVICE REPAIR COMPLETED
Fire Alarm
1 Library at 132 RHT Remounted (1) 5601A Heat Detector 08/18/2016
2 Custodian Room RHT Replaced Device w/ (1) 5601A Heat Detector 08/18/2016
Emergency Lighting
1 Hall By Principal SPEXS10721 Replaced Batteries w/ (2) Panasonic PA-6V4.5 08/18/2016
2 Library Rear SPEXS10721 Replaced Batteries w/ (2) Panasonic PA-6V4.5 08/18/2016
Additional Comments:
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
DEVICE LEGEND
DEVICE DESCRIPTION
ANN Annunciator
AD Ancillary Device (Note 4)
B Bell
BZ Buzzer
C Chime
CR Control Relay
CT1 Single Input Module (for supervised Class B signal or audio circuits)
CT2 Double Input Module (for supervised Class B signal or audio circuits)
DH Door Hold Open Device
DS Duct Smoke Detector
ET Emergency Telephone
FACP Fire Alarm Control Panel
FH Firefighters Handset
FS Sprinkler Flow Switch
GA 2nd Stage of 2-Stage Pull Station
H Horn
H/S Horn Strobe
HSP Horn Loudspeaker
HT Heat Detector, Fixed Temperature
HT-RES Resetable Heat Detector
K Horn, Klaxon Type
M Manual Pull Station
MAG LOCK Magnetic Door Lock
PS Pressure Switch
RHT Heat Detector, Rate-of-Rise
S Smoke Detector
SA Smoke Alarm, Single Station Type (Note 3)
SP Loudspeaker
SS Sprinkler Supervisory Switch
SV Sprinkler Valve
TS Sprinkler Tamper Switch (Note 2)
V Visual Alarm Appliance
Note 1: Confirmation of wiring supervision to each individual device is only required during installation verification or a complete building audit
of the system and is not required on the annual test.
Note 2: Sprinkler tamper switches cause trouble condition to be annunciated but not an alarm condition.
Note 3: Single station smoke alarms are not part of the fire alarm system but testing of such devices may be required by the authority
having jurisdiction.
Note 4: Identify the specific ancillary devices in the Remark column of Fire Alarm System Device Test and Inspection Record form
ANNUAL FIRE ALARM SYSTEM TESTING CERTIFICATE
THIS DOCUMENT CERTIFIES THAT THE FIRE ALARM SYSTEM AT THE FOLLOWING LOCATION;
MONSIGNOR JOHN UYEN~ 255 LARK ROAD, CHATHAM
HAS BEEN TESTED & INSPECTED IN ACCORDANCE WITH THE STANDARD FOR THE INSPECTION AND TESTING OF
FIRE ALARM SYSTEMS, CAN/ULC-S536-04.
A TEST OF ALL EMERGENCY LIGHTING EQUIPMENT WAS COMPLETED IN ACCORDANCE WITH CANADIAN
ULC CODES AND DESIGN CRITERIA DESIGNATED BY MANUFACTURER'S SPECIFICATIONS.
YES NO N/A
E The fire alarm system documentation is on site and includes a description of the system √
G The fire alarm system has deficiencies noted on the attached pages √
H Comments:
The information on this form (and the documents attached here-to) attest to the fact that the equipment listed here-in was tested/inspected in
conformance with applicable codes, bylaws, standards, and the manufacturer's requirements by a qualified technician. The equipment was left
in an operational condition except as noted in the spaces marked "comments". A copy should be maintained on the premises for examination
by the Fire Marshall or Inspector at their request.
Technician #1 Technician #2
YES NO N/A
Output circuits for selective voice paging, including visual indication operates √
Output circuits for selective voice paging trouble operation, including visual indication operates √
Operation of voice paging does not interfere with entitled inhibit time of alert signal and alarm signal √
Circuits for emergency telephone call in operation, including audible and visual indication operates √
Circuits for emergency telephone for operation, including two-way voice communication operates √
YES NO N/A
EMERGENCY POWER SUPPLY TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.3, 5.3.2, 5.33]
YES NO N/A
Correct battery rating as determined by battery calculations based on full system load √
Adequately ventilated √
Generator provides power to the AC circuit serving the fire alarm system. √
Trouble condition at the emergency generator results in an audible common trouble signal and a visual indication at the required
annunciator. √
Battery voltage not less than 85% of its rated capacity after tests completed √
Battery manufacturer and part number Enersys NP7-12
Battery manufacturer's date code or ins service date Date 2013
Battery Voltage (main power supply 'ON') is Voltage 26.80
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 25.80
in supervisory condition Current (A) 0.59
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 25.00
in full load condition Current (A) 0.612
The charging current is Current (mA) 760
INDICATE TYPE OF BATTERY TEST PERFORMED (must choose 1 of 5 methods)
YES NO N/A
(i) Required supervisory load for 24 h followed by the required full load operation; √
(ii) Silent test using load resistor method for full duration test. √
(v) Replace the batteries with a new set having a current date code/capacity/type √
Record battery capacity AH 7
Record the battery terminal voltage after tests are completed. VDC 25.8
EMERGENCY POWER SUPPLY TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.3, 5.3.2, 5.33]
YES NO N/A
Correct battery rating as determined by battery calculations based on full system load √
Adequately ventilated √
Generator provides power to the AC circuit serving the fire alarm system. √
Trouble condition at the emergency generator results in an audible common trouble signal and a visual indication at the required
annunciator. √
Battery voltage not less than 85% of its rated capacity after tests completed √
Battery manufacturer and part number Enersys NP18-12
Battery manufacturer's date code or ins service date Date 2013
Battery Voltage (main power supply 'ON') is Voltage 26.50
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 26.50
in supervisory condition Current (A) 0.970
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 25.50
in full load condition Current (A) 2.70
The charging current is Current (mA) 1200
INDICATE TYPE OF BATTERY TEST PERFORMED (must choose 1 of 5 methods)
YES NO N/A
(i) Required supervisory load for 24 h followed by the required full load operation; √
(ii) Silent test using load resistor method for full duration test. √
(v) Replace the batteries with a new set having a current date code/capacity/type √
Record battery capacity AH 18
Record the battery terminal voltage after tests are completed. VDC 25.5
ANNUNCIATOR AND REMOTE TROUBLE SIGNAL UNIT TEST & INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.1]
YES NO N/A
Individual alarm and supervisory input zone clearly indicated and separately designated √
Individual alarm and supervisory input zone designation labels are properly identified √
YES NO N/A
Minimum of one alarm zone and one supervisory zone tested per annunciator or sequential display to confirm operation √
Individual alarm and supervisory input zone designation labels are properly identified. √
REMOTE TROUBLE SIGNAL UNIT TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.3]
YES NO N/A
YES NO N/A
Operates as per design and specification, or in accordance with documentation provided in Appendix E. √
DATA COMMUNICATION LINK TEST [Ref. CAN/ULC-S536-04, Clauses 5.1.5, 5.6 Note]
YES NO N/A
Confirm that a trouble signal is received at the control unit or transponder under an open loop fault for each data communication link
(DCL) √
Where fault isolation modules are installed in data communication links serving field devices, wiring shorted on the isolated side,
annunciation of the fault confirmed, and then a device on the source side operated, and activation confirmed at the control unit or √
Where fault isolation in data communication links is provided between control units or transponders and between transponders,
introduce a short circuit fault and confirm annunciation of the fault and operation outside the shorted section between each pair of: √
YES NO N/A
Door Holders √
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 27th, 2016
Address: 545 Baldoon Road, Chatham Building Name: Our Lady of Fatima Page 1 of 6
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 27th, 2016
Address: 545 Baldoon Road, Chatham Building Name: Our Lady of Fatima Page 2 of 6
Storage 4 RHT √ √ 1
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 27th, 2016
Address: 545 Baldoon Road, Chatham Building Name: Our Lady of Fatima Page 3 of 6
Library H/S √ √ A
French Room off Library RHT √ √ 1
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 27th, 2016
Address: 545 Baldoon Road, Chatham Building Name: Our Lady of Fatima Page 4 of 6
Gym H/S √ √ A
Gym H/S √ √ B
Gym (Left) RHT √ √ 3
Gym (Right) RHT √ √ 3
Equipment Room RHT √ √ 3
Exit 6 off Gym M (8) √ √ 3 126
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 27th, 2016
Address: 545 Baldoon Road, Chatham Building Name: Our Lady of Fatima Page 5 of 6
Storage RHT √ √ 3
Room 18 Storage RHT √ √ 3
Hall By Room 18- SE Hall S √ √ 3 019
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 27th, 2016
Address: 545 Baldoon Road, Chatham Building Name: Our Lady of Fatima Page 6 of 6
Chapel DS √ √ 1 0040
CAN/ULC
EMERGENCY LIGHTING
INDIVIDUAL DEVICE RECORD
Date: July 27th, 2016
Address: 545 Baldoon Road, Chatham Building Name: Our Lady of Fatima
Board Office
By Room 158 SLC12200 (2) PA-12V7.2 (08) 2 12.85 11:00 300 Ok
Storage Room 156 SLC12200 (2) NP7-12 (14) 2 13.00 11:00 297 Ok
Storage Room 123 RG 72 PA-6V12 (10) 2 13.95 11:05 280 Ok
Daycare Entrance SLC12200 (2) NP7-12 (14) 2 6.65 11:05 300 Ok
Boiler Room Exit (Room 150) 8 LMC Combo CSB 6V4.5 (11) 2 6.60 11:05 295 Ok
REPAIRS
# LOCATION DEVICE REPAIR COMPLETED
Fire Alarm Devices
Repairs Not Required
Emergency Lighting
Repairs Not Required
Additional Comments:
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
DEVICE LEGEND
DEVICE DESCRIPTION
ANN Annunciator
AD Ancillary Device (Note 4)
B Bell
BZ Buzzer
C Chime
CR Control Relay
CT1 Single Input Module (for supervised Class B signal or audio circuits)
CT2 Double Input Module (for supervised Class B signal or audio circuits)
DH Door Hold Open Device
DS Duct Smoke Detector
ET Emergency Telephone
FACP Fire Alarm Control Panel
FH Firefighters Handset
FS Sprinkler Flow Switch
GA 2nd Stage of 2-Stage Pull Station
H Horn
H/S Horn Strobe
HSP Horn Loudspeaker
HT Heat Detector, Fixed Temperature
HT-RES Resetable Heat Detector
K Horn, Klaxon Type
M Manual Pull Station
MAG LOCK Magnetic Door Lock
PS Pressure Switch
RHT Heat Detector, Rate-of-Rise
S Smoke Detector
SA Smoke Alarm, Single Station Type (Note 3)
SP Loudspeaker
SS Sprinkler Supervisory Switch
SV Sprinkler Valve
TS Sprinkler Tamper Switch (Note 2)
V Visual Alarm Appliance
Note 1: Confirmation of wiring supervision to each individual device is only required during installation verification or a
complete building audit of the system and is not required on the annual test.
Note 2: Sprinkler tamper switches cause trouble condition to be annunciated but not an alarm condition.
Note 3: Single station smoke alarms are not part of the fire alarm system but testing of such devices may be required by the
authority having jurisdiction.
Note 4: Identify the specific ancillary devices in the Remark column of Fire Alarm System Device Test and Inspection Record
183 Exeter Road, Unit A
London, Ontario
PHONE (519) 652-5086
FAX (519) 652-8719
1. GENERAL:
2. WATER SUPPLIES:
3. FIRE HYDRANTS:
NONE
NONE
6. The following items are deficient as per The Ontario Fire Code and need to be corrected immediately:
NONE
The certificate of inspection cannot be issued until all items under section #6 have been completed.
NONE
NOTE: This inspection/test was performed in accordance with The Ontario Fire Code. This inspection does NOT
certify that the fire hydrant installation complies with NFPA, OBC or Ontario Retrofit Reg. #627/92 (an engineer’s
report would be required to certify this).
LIMITATION OF LIABILITY: It is understood and agreed that the INSPECTOR is NOT an insurer and is NOT
warranting or guaranteeing the adequacy, performance or life expectancy of any structure, item,
component or system in the building. Further, it is mutually agreed that the maximum amount of joint and
several liability the INSPECTOR can incur for any error, mistakes, omissions, breach of contract, breach of
warrantee, negligent hiring, or any other theory of liability including violation of a statue or consumer
protection act is strictly limited to the FEE PAID for the inspection report.
As per the requirements of The Ontario Fire Codes, the inspecting company must submit this report to the
local Fire Prevention office
THIS DOCUMENT CERTIFIES THAT THE FIRE ALARM SYSTEM AT THE FOLLOWING LOCATION;
OUR LADY OF FATIMA~ 545 BALDOON ROAD, CHATHAM
HAS BEEN TESTED & INSPECTED IN ACCORDANCE WITH THE STANDARD FOR THE INSPECTION AND TESTING OF
FIRE ALARM SYSTEMS, CAN/ULC-S536-04. THE FIRE HYDRANT HAS ALSO BEEN INSPECTED AT THIS LOCATION.
A TEST OF ALL EMERGENCY LIGHTING EQUIPMENT WAS COMPLETED IN ACCORDANCE WITH CANADIAN
ULC CODES AND DESIGN CRITERIA DESIGNATED BY MANUFACTURER'S SPECIFICATIONS.
YES NO N/A
E The fire alarm system documentation is on site and includes a description of the system √
G The fire alarm system has deficiencies noted on the attached pages √
H Comments:
The information on this form (and the documents attached here-to) attest to the fact that the equipment listed here-in was tested/inspected in
conformance with applicable codes, bylaws, standards, and the manufacturer's requirements by a qualified technician. The equipment was left in
an operational condition except as noted in the spaces marked "comments". A copy should be maintained on the premises for examination by
the Fire Marshall or Inspector at their request.
Technician #1 Technician #2
YES NO NA
Power 'ON' visual indicator √
Common visual trouble signal √
Common audible trouble signal √
Trouble signal silence switch √
Main power supply failure trouble signal operates √
Ground fault tested on positive and negative trouble signal √
Alert signal operation √
Alarm signal operation √
Automatic transfer from alert signal to alarm signal √
Manual transfer from alert signal to alarm signal cancel (acknowledge) feature operates on a two-stage system √
Automatic transfer from alert signal to alarm signal cancel (acknowledge) feature operates on a two-stage system √
Alarm signal silence inhibit function operates √
Alarm signal manual silence operational √
Alarm signal silence visual indication operates √
Alarm signals, when silenced automatically reinitiate upon subsequent alarm √
Alarm signal silence automatic cut-out timer Time: √
Audible and visual alert signals and alarm signals programmed and operate per design and specification; or documentation as detailed
in Appendix C - Description of Fire Alarm System for Inspection and Test Procedures √
Input circuit, alarm and supervisory operation, including audible and visual indication operates √
Input circuit supervision fault causes a trouble indication √
Output circuit alarm indicates operational √
Output circuit supervision fault causes a trouble indication √
Visual indicator test (lamp test) √
Coded Signal sequences operate not less than the required number of times and the correct alarm signal operates thereafter √
Coded signal sequences are not interrupted by subsequent alarm √
Ancillary device by-pass will result in a trouble signal √
Input circuit to output circuit operation, including ancillary device circuits, for correct program operation, as per design and specification,
or documentation as detailed in Appendix C - Description of Fire Alarm System for Inspection and Testing Procedures √
Fire alarm system reset operation √
Main power supply to emergency power supply transfer operates √
Status change confirmation (smoke detectors only) verified [Refer Subsection 5.7.4.3, Status Change Confirmation (Alarm Verification
Feature)] √
Receipt of alarm transmission to the fire signal receiving centre √
Receipt of the supervisory transmission to the fire signal receiving centre √
Receipt of the trouble transmission to the fire signal receiving centre √
Operation of the fire signal receiving centre disconnect means results in a specific trouble at the control unit or transponder and
transmits a trouble to the fire signal receiving centre
√
Record the name and telephone number of the fire signal receiving centre √
Name DAMAR- 883331 Gators
Phone Number 1 (800) 265-7562
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
YES NO N/A
Output circuits for selective voice paging, including visual indication operates √
Output circuits for selective voice paging trouble operation, including visual indication operates √
Operation of voice paging does not interfere with entitled inhibit time of alert signal and alarm signal √
Circuits for emergency telephone call in operation, including audible and visual indication operates √
Circuits for emergency telephone for operation, including two-way voice communication operates √
YES NO N/A
EMERGENCY POWER SUPPLY TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.3, 5.3.2, 5.33]
YES NO N/A
Correct battery rating as determined by battery calculations based on full system load √
Adequately ventilated √
Generator provides power to the AC circuit serving the fire alarm system. √
Trouble condition at the emergency generator results in an audible common trouble signal and a visual indication at the required
annunciator. √
Battery voltage not less than 85% of its rated capacity after tests completed √
Battery manufacturer and part number (2) Enersys NP7-12
Battery manufacturer's date code or ins service date Date 2012
Battery Voltage (main power supply 'ON') is Voltage 26.68
Battery voltage and current with main power supply 'OFF' and fire alarm Voltage 25.56
system in supervisory condition Current (A) 80.00
Battery voltage and current with main power supply 'OFF' and fire alarm Voltage 25.20
system in full load condition Current (A) 480.00
The charging current is Current (mA) 240
INDICATE TYPE OF BATTERY TEST PERFORMED (must choose 1 of 5 methods)
YES NO N/A
(i) Required supervisory load for 24 h followed by the required full load operation; √
(ii) Silent test using load resistor method for full duration test. √
(v) Replace the batteries with a new set having a current date code/capacity/type √
Record battery capacity. AH 7
Record the battery terminal voltage after tests are completed. VDC 25.60
ANNUNCIATOR AND REMOTE TROUBLE SIGNAL UNIT TEST & INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.1]
YES NO N/A
Individual alarm and supervisory input zone clearly indicated and separately designated √
Individual alarm and supervisory input zone designation labels are properly identified √
YES NO N/A
Minimum of one alarm zone and one supervisory zone tested per annunciator or sequential display to confirm operation √
Individual alarm and supervisory input zone designation labels are properly identified. √
REMOTE TROUBLE SIGNAL UNIT TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.3]
YES NO N/A
YES NO N/A
Operates as per design and specification, or in accordance with documentation provided in Appendix E. √
DATA COMMUNICATION LINK TEST [Ref. CAN/ULC-S536-04, Clauses 5.1.5, 5.6 Note]
YES NO N/A
Confirm that a trouble signal is received at the control unit or transponder under an open loop fault for each data communication link
(DCL) √
Where fault isolation modules are installed in data communication links serving field devices, wiring shorted on the isolated side,
annunciation of the fault confirmed, and then a device on the source side operated, and activation confirmed at the control unit or √
Where fault isolation in data communication links is provided between control units or transponders and between transponders,
introduce a short circuit fault and confirm annunciation of the fault and operation outside the shorted section between each pair of: √
YES NO N/A
Door Holders (x 3) √
Tie to Security √
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 25th, 2016
Hall By Office M √ √ 1
Hall By Room 4 M √ √ 1
Workroom RHT √ √ 1
East Exit M √ √ 1
Hall By Change Rm M √ √ 1
Hall By Change Rm M √ √ 1
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 25th, 2016
Infirmary RHT √ √ 1
Gym NW B √ √ NAC-1
Gym SE B √ √ NAC-1
Exit By Stage M √ √ 2
Hall By Rm 107 DH √ √
CAN/ULC
EMERGENCY LIGHTING
INDIVIDUAL DEVICE RECORD
Date: July 25th, 2016
Boy’s Change Room Rear COM 36 (2) PA-6V4.5 (13) 2 11.00 9:16 X See Repairs List
Girl’s Change Room Rear COM 36 (2) NP5-12 (15) 2 14.20 9:20
REPAIRS
# LOCATION DEVICE REPAIR COMPLETED
Fire Alarm Devices
Repairs Not Required
Emergency Lighting
1 Hall By Gym RG 36 Replaced Battery w/ (1) Panasonic PA-6V12 07/25/2016
2 Gym Exit To Hall CLT VRW 36 Replaced Battery w/ (1) Panasonic PA-6V4.5 07/25/2016
3 Gym Left CLT VRW 36 Replaced Battery w/ (1) Panasonic PA-6V4.5 07/25/2016
4 Boy’s Change Room Rear COM 36 Replaced Batteries w/ (2) Panasonic PA-6V4.5 07/25/2016
Additional Comments:
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
DEVICE LEGEND
DEVICE DESCRIPTION
ANN Annunciator
AD Ancillary Device (Note 4)
B Bell
BZ Buzzer
C Chime
CR Control Relay
CT1 Single Input Module (for supervised Class B signal or audio circuits)
CT2 Double Input Module (for supervised Class B signal or audio circuits)
DH Door Hold Open Device
DS Duct Smoke Detector
ET Emergency Telephone
FACP Fire Alarm Control Panel
FH Firefighters Handset
FS Sprinkler Flow Switch
GA 2nd Stage of 2-Stage Pull Station
H Horn
H/S Horn Strobe
HSP Horn Loudspeaker
HT Heat Detector, Fixed Temperature
HT-RES Resetable Heat Detector
K Horn, Klaxon Type
M Manual Pull Station
MAG LOCK Magnetic Door Lock
PS Pressure Switch
RHT Heat Detector, Rate-of-Rise
S Smoke Detector
SA Smoke Alarm, Single Station Type (Note 3)
SP Loudspeaker
SS Sprinkler Supervisory Switch
SV Sprinkler Valve
TS Sprinkler Tamper Switch (Note 2)
V Visual Alarm Appliance
Note 1: Confirmation of wiring supervision to each individual device is only required during installation verification or a complete building audit
of the system and is not required on the annual test.
Note 2: Sprinkler tamper switches cause trouble condition to be annunciated but not an alarm condition.
Note 3: Single station smoke alarms are not part of the fire alarm system but testing of such devices may be required by the authority
having jurisdiction.
Note 4: Identify the specific ancillary devices in the Remark column of Fire Alarm System Device Test and Inspection Record form
ANNUAL FIRE ALARM SYSTEM TESTING CERTIFICATE
THIS DOCUMENT CERTIFIES THAT THE FIRE ALARM SYSTEM AT THE FOLLOWING LOCATION;
ST. AGNES, 55 CROYDON STREET, CHATHAM
HAS BEEN TESTED & INSPECTED IN ACCORDANCE WITH THE STANDARD FOR THE INSPECTION AND TESTING
OF FIRE ALARM SYSTEMS, CAN/ULC-S536-04.
A TEST OF ALL EMERGENCY LIGHTING EQUIPMENT WAS ALSO COMPLETED IN ACCORDANCE WITH CANADIAN
ULC CODES AND DESIGN CRITERIA DESIGNATED BY MANUFACTURER'S SPECIFICATIONS.
YES NO N/A
E The fire alarm system documentation is on site and includes a description of the system √
G The fire alarm system has deficiencies noted on the attached pages √
H Comments:
I A copy of this report has been given to: St. Clair Catholic District School Board
The information on this form (and the documents attached here-to) attest to the fact that the equipment listed here-in was tested/inspected in
conformance with applicable codes, bylaws, standards, and the manufacturer's requirements by a qualified technician. The equipment was
left in an operational condition except as noted in the spaces marked "comments". A copy should be maintained on the premises for
examination by the Fire Marshall or Inspector at their request.
Technician #1 Technician #2
YES NO N/A
Output circuits for selective voice paging, including visual indication operates √
Output circuits for selective voice paging trouble operation, including visual indication operates √
Operation of voice paging does not interfere with entitled inhibit time of alert signal and alarm signal √
Circuits for emergency telephone call in operation, including audible and visual indication operates √
Circuits for emergency telephone for operation, including two-way voice communication operates √
YES NO N/A
EMERGENCY POWER SUPPLY TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.3, 5.3.2, 5.33]
YES NO N/A
Correct battery rating as determined by battery calculations based on full system load √
Adequately ventilated √
Generator provides power to the AC circuit serving the fire alarm system. √
Trouble condition at the emergency generator results in an audible common trouble signal and a visual indication at the required
annunciator. √
Battery voltage not less than 85% of its rated capacity after tests completed √
Battery manufacturer and part number Enersys NP7-12
Battery manufacturer's date code or ins service date Date 2013
Battery Voltage (main power supply 'ON') is Voltage 26.52
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 25.6
in supervisory condition Current (A) 0.24
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 25.13
in full load condition Current (A) 1.52
The charging current is Current (mA) 0.72
YES NO N/A
(i) Required supervisory load for 24 h followed by the required full load operation; √
(ii) Silent test using load resistor method for full duration test. √
(v) Replace the batteries with a new set having a current date code/capacity/type √
Record battery capacity AH 7
Record the battery terminal voltage after tests are completed. VDC 26.40
ANNUNCIATOR AND REMOTE TROUBLE SIGNAL UNIT TEST & INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.1]
YES NO N/A
Individual alarm and supervisory input zone clearly indicated and separately designated √
Individual alarm and supervisory input zone designation labels are properly identified √
YES NO N/A
Minimum of one alarm zone and one supervisory zone tested per annunciator or sequential display to confirm operation √
Individual alarm and supervisory input zone designation labels are properly identified. √
REMOTE TROUBLE SIGNAL UNIT TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.3]
YES NO N/A
YES NO N/A
Operates as per design and specification, or in accordance with documentation provided in Appendix E. √
DATA COMMUNICATION LINK TEST [Ref. CAN/ULC-S536-04, Clauses 5.1.5, 5.6 Note]
YES NO N/A
Confirm that a trouble signal is received at the control unit or transponder under an open loop fault for each data communication link
(DCL) √
Where fault isolation modules are installed in data communication links serving field devices, wiring shorted on the isolated side,
annunciation of the fault confirmed, and then a device on the source side operated, and activation confirmed at the control unit or √
Where fault isolation in data communication links is provided between control units or transponders and between transponders,
introduce a short circuit fault and confirm annunciation of the fault and operation outside the shorted section between each pair of: √
YES NO N/A
Door Holders √
Fan Shutdown √
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 19th, 2016
Building Name: St. Anne Address: 183 Snow Ave, Blenheim Page 1 of 7
Kitchen HT-R √ √ 5
Kitchen B √ √ 5-1
Front Door M √ √ 5
Coat Room M √ √ 5
School
Exit By Mechanical Room # 133 M √ √ 4
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 19th, 2016
Building Name: St. Anne Address: 183 Snow Ave, Blenheim Page 2 of 7
Classroom 140 M √ √ 4
Classroom 142 M √ √ 4
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 19th, 2016
Building Name: St. Anne Address: 183 Snow Ave, Blenheim Page 3 of 7
Classroom 7 RHT √ √ 3
Classroom 6 RHT √ √ 3
Library A Rm 101 M √ √ 3
Library B Rm 101 M √ √ 3
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 19th, 2016
Building Name: St. Anne Address: 183 Snow Ave, Blenheim Page 4 of 7
Lobby M √ √ 3
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 19th, 2016
Building Name: St. Anne Address: 183 Snow Ave, Blenheim Page 5 of 7
Gym RHT √ √ 1
Gym RHT √ √ 1
Gym RHT √ √ 1
Gym RHT √ √ 1
Gym Stage HT √ √ 1
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 19th, 2016
Building Name: St. Anne Address: 183 Snow Ave, Blenheim Page 6 of 7
Room 124 HT √ √ 4
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 19th, 2016
Building Name: St. Anne Address: 183 Snow Ave, Blenheim Page 7 of 7
Room 124 HT √ √ 4
CAN/ULC
EMERGENCY LIGHTING
INDIVIDUAL DEVICE RECORD
Date: August 19th, 2016
REPAIRS
# LOCATION DEVICE REPAIR COMPLETED
Fire Alarm
1 Hall By Storage Room 132 S (6249C) Replaced Smoke w/(1) C2W-BA Detector 08/19/2016
Emergency Lighting
1 Mechanical Room 134 RG 12S360 Replaced Battery w/ (1) Enersys NP33-12 08/19/2016
2 Electrical Room 115A Unit #6 RG 12S360 Replaced Battery w/ (1) Enersys NP33-12 08/19/2016
Hydrant Inspection
Repairs not Required
Additional Comments:
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
DEVICE LEGEND
DEVICE DESCRIPTION
ANN Annunciator
AD Ancillary Device (Note 4)
B Bell
BZ Buzzer
C Chime
CR Control Relay
CT1 Single Input Module (for supervised Class B signal or audio circuits)
CT2 Double Input Module (for supervised Class B signal or audio circuits)
DH Door Hold Open Device
DS Duct Smoke Detector
ET Emergency Telephone
FACP Fire Alarm Control Panel
FH Firefighters Handset
FS Sprinkler Flow Switch
GA 2nd Stage of 2-Stage Pull Station
H Horn
H/S Horn Strobe
HSP Horn Loudspeaker
HT Heat Detector, Fixed Temperature
HT-RES Resetable Heat Detector
K Horn, Klaxon Type
M Manual Pull Station
MAG LOCK Magnetic Door Lock
PS Pressure Switch
RHT Heat Detector, Rate-of-Rise
S Smoke Detector
SA Smoke Alarm, Single Station Type (Note 3)
SP Loudspeaker
SS Sprinkler Supervisory Switch
SV Sprinkler Valve
TS Sprinkler Tamper Switch (Note 2)
V Visual Alarm Appliance
Note 1: Confirmation of wiring supervision to each individual device is only required during installation verification or a complete building audit
of the system and is not required on the annual test.
Note 2: Sprinkler tamper switches cause trouble condition to be annunciated but not an alarm condition.
Note 3: Single station smoke alarms are not part of the fire alarm system but testing of such devices may be required by the authority
having jurisdiction.
Note 4: Identify the specific ancillary devices in the Remark column of Fire Alarm System Device Test and Inspection Record form
183 Exeter Road, Unit A
London, Ontario
PHONE (519) 652-5086
FAX (519) 652-8719
1. GENERAL:
2. WATER SUPPLIES:
3. FIRE HYDRANTS:
NONE
NONE
6. The following items are deficient as per The Ontario Fire Code and need to be corrected immediately:
NONE
The certificate of inspection cannot be issued until all items under section #6 have been completed.
NONE
NOTE: This inspection/test was performed in accordance with The Ontario Fire Code. This inspection does NOT
certify that the fire hydrant installation complies with NFPA, OBC or Ontario Retrofit Reg. #627/92 (an engineer’s
report would be required to certify this).
LIMITATION OF LIABILITY: It is understood and agreed that the INSPECTOR is NOT an insurer and is NOT
warranting or guaranteeing the adequacy, performance or life expectancy of any structure, item,
component or system in the building. Further, it is mutually agreed that the maximum amount of joint and
several liability the INSPECTOR can incur for any error, mistakes, omissions, breach of contract, breach of
warrantee, negligent hiring, or any other theory of liability including violation of a statue or consumer
protection act is strictly limited to the FEE PAID for the inspection report.
As per the requirements of The Ontario Fire Codes, the inspecting company must submit this report to the
local Fire Prevention office
THIS DOCUMENT CERTIFIES THAT THE FIRE ALARM SYSTEM AT THE FOLLOWING LOCATION;
ST. ANNE~ 183 SNOW AVENUE, BLENHEIM
HAS BEEN TESTED & INSPECTED IN ACCORDANCE WITH THE STANDARD FOR THE INSPECTION AND TESTING OF
FIRE ALARM SYSTEMS, CAN/ULC-S536-04. THE FIRE HYDRANT HAS ALSO BEEN INSPECTED AT THIS LOCATION.
A TEST OF ALL EMERGENCY LIGHTING EQUIPMENT WAS COMPLETED IN ACCORDANCE WITH CANADIAN
ULC CODES AND DESIGN CRITERIA DESIGNATED BY MANUFACTURER'S SPECIFICATIONS.
YES NO N/A
E The fire alarm system documentation is on site and includes a description of the system √
G The fire alarm system has deficiencies noted on the attached pages √
H Comments:
The information on this form (and the documents attached here-to) attest to the fact that the equipment listed here-in was tested/inspected in
conformance with applicable codes, bylaws, standards, and the manufacturer's requirements by a qualified technician. The equipment was left in
an operational condition except as noted in the spaces marked "comments". A copy should be maintained on the premises for examination by
the Fire Marshall or Inspector at their request.
Technician #1 Technician #2
YES NO NA
Power 'ON' visual indicator √
Common visual trouble signal √
Common audible trouble signal √
Trouble signal silence switch √
Main power supply failure trouble signal operates √
Ground fault tested on positive and negative trouble signal √
Alert signal operation √
Alarm signal operation √
Automatic transfer from alert signal to alarm signal √
Manual transfer from alert signal to alarm signal cancel (acknowledge) feature operates on a two-stage system √
Automatic transfer from alert signal to alarm signal cancel (acknowledge) feature operates on a two-stage system √
Alarm signal silence inhibit function operates √
Alarm signal manual silence operational √
Alarm signal silence visual indication operates √
Alarm signals, when silenced automatically reinitiate upon subsequent alarm √
Alarm signal silence automatic cut-out timer Time: √
Audible and visual alert signals and alarm signals programmed and operate per design and specification; or documentation as detailed
in Appendix C - Description of Fire Alarm System for Inspection and Test Procedures √
Input circuit, alarm and supervisory operation, including audible and visual indication operates √
Input circuit supervision fault causes a trouble indication √
Output circuit alarm indicates operational √
Output circuit supervision fault causes a trouble indication √
Visual indicator test (lamp test) √
Coded Signal sequences operate not less than the required number of times and the correct alarm signal operates thereafter √
Coded signal sequences are not interrupted by subsequent alarm √
Ancillary device by-pass will result in a trouble signal √
Input circuit to output circuit operation, including ancillary device circuits, for correct program operation, as per design and specification,
or documentation as detailed in Appendix C - Description of Fire Alarm System for Inspection and Testing Procedures √
Fire alarm system reset operation √
Main power supply to emergency power supply transfer operates √
Status change confirmation (smoke detectors only) verified [Refer Subsection 5.7.4.3, Status Change Confirmation (Alarm Verification
Feature)] √
Receipt of alarm transmission to the fire signal receiving centre √
Receipt of the supervisory transmission to the fire signal receiving centre √
Receipt of the trouble transmission to the fire signal receiving centre √
Operation of the fire signal receiving centre disconnect means results in a specific trouble at the control unit or transponder and
transmits a trouble to the fire signal receiving centre √
Record the name and telephone number of the fire signal receiving centre √
Name DAMAR- 114653 Gators
Phone Number (800) 265-7562
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
YES NO N/A
Output circuits for selective voice paging, including visual indication operates √
Output circuits for selective voice paging trouble operation, including visual indication operates √
Operation of voice paging does not interfere with entitled inhibit time of alert signal and alarm signal √
Circuits for emergency telephone call in operation, including audible and visual indication operates √
Circuits for emergency telephone for operation, including two-way voice communication operates √
YES NO N/A
YES NO N/A
EMERGENCY POWER SUPPLY TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.3, 5.3.2, 5.33]
YES NO N/A
Correct battery rating as determined by battery calculations based on full system load √
Adequately ventilated √
Generator provides power to the AC circuit serving the fire alarm system. √
Trouble condition at the emergency generator results in an audible common trouble signal and a visual indication at the required
annunciator. √
Battery voltage not less than 85% of its rated capacity after tests completed √
Battery manufacturer and part number (2) Enersys NP12-12
Battery manufacturer's date code or ins service date Date 2014
Battery Voltage (main power supply 'ON') is Voltage 27.50
Battery voltage and current with main power supply 'OFF' and fire alarm Voltage 25.20
system in supervisory condition Current (A) 0.364
Battery voltage and current with main power supply 'OFF' and fire alarm Voltage 24.90
system in full load condition Current (A) 1.508
The charging current is Current (mA) 2150
INDICATE TYPE OF BATTERY TEST PERFORMED (must choose 1 of 5 methods)
YES NO N/A
(i) Required supervisory load for 24 h followed by the required full load operation; √
(ii) Silent test using load resistor method for full duration test. √
(v) Replace the batteries with a new set having a current date code/capacity/type √
Record battery capacity AH 12
Record the battery terminal voltage after tests are completed. VDC 26.40
ANNUNCIATOR AND REMOTE TROUBLE SIGNAL UNIT TEST & INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.1]
YES NO N/A
Individual alarm and supervisory input zone clearly indicated and separately designated √
Individual alarm and supervisory input zone designation labels are properly identified √
YES NO N/A
Minimum of one alarm zone and one supervisory zone tested per annunciator or sequential display to confirm operation √
Individual alarm and supervisory input zone designation labels are properly identified. √
REMOTE TROUBLE SIGNAL UNIT TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.3]
YES NO N/A
YES NO N/A
Operates as per design and specification, or in accordance with documentation provided in Appendix E. √
DATA COMMUNICATION LINK TEST [Ref. CAN/ULC-S536-04, Clauses 5.1.5, 5.6 Note]
YES NO N/A
Confirm that a trouble signal is received at the control unit or transponder under an open loop fault for each data communication link
(DCL) √
Where fault isolation modules are installed in data communication links serving field devices, wiring shorted on the isolated side,
annunciation of the fault confirmed, and then a device on the source side operated, and activation confirmed at the control unit or √
Where fault isolation in data communication links is provided between control units or transponders and between transponders,
introduce a short circuit fault and confirm annunciation of the fault and operation outside the shorted section between each pair of: √
YES NO N/A
Fans √
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 20th, 2016
Building Name: St. Anne Address: 1000 Rapids Parkway, Sarnia Page 1 of 4
201A DS (1451A) √ √ 10
201A DS (1451A) √ √ 10 EOL
201A M √ √ 8 EOL
201A RHT √ √ 8
201A H √ √ S-2
Stairs By 201A S (1451A) √ √ 9 EOL
Room 150A M √ √ 1
Exit By 147A M √ √ 1
By 146A H √ √ S-2
133 M √ √ 5
133 Electricial Room S (1451A) √ √ 5 EOL
By 146A S (2451A) √ √ 1
By 134 S (2451A) √ √ 1
By 134 V √ √ S-2
By 135 H √ √ S-2
Gym Exit M √ √ 1
Gym East Wall H √ √ S-2
Gym By 146B H √ √ S-2
Exit By 136 M √ √ 1
Room 137B RHT √ √ 7
Room 137B M √ √ 7
By 123 S (2451A) √ √ 2
In 123A H √ √ S-2
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 20th, 2016
Building Name: St. Anne Address: 1000 Rapids Parkway, Sarnia Page 2 of 4
By D04 H √ √ S-1
By D02B H √ √ S-1
D01A M √ √ 4
Exit By D02B S (1400A) √ √ 4
By D11 H √ √ S-1
By D02C S (1400A) √ √ 4
By D02D M √ √ 4
By 112A H √ √ S-1
By 108 S (2451A) √ √ 2
By 108 V √ √ S-1
By 109C H √ √ S-1
By 125 S (2451A) √ √ 2
By 104 V √ √ S-1
In 104 H √ √ S-1
By Front Door M √ √ 2
By Front Door S (2451A) √ √ 2
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 20th, 2016
Building Name: St. Anne Address: 1000 Rapids Parkway, Sarnia Page 3 of 4
CAN/ULC S536-04
FIRE ALARM- SPRINKLER
INDIVIDUAL DEVICE RECORD
Date: July 20th, 2016
Building Name: St. Anne Address: 1000 Rapids Parkway, Sarnia Page 4 of 4
Monitor SV #1 SV √ 23 √
Monitor SV #2 SV √ 24 √
Monitor SV #3 SV √ 25 √
Monitor SV #4 SV √ 26 √
Monitor SV #5 SV √ 27 √
Monitor SV #6 SV √ 28 √
CAN/ULC
EMERGENCY LIGHTING
INDIVIDUAL DEVICE RECORD
Date: July 20th, 2016
REPAIRS
# LOCATION DEVICE REPAIR COMPLETED
Fire Alarm Devices
Repairs Not Required
We were required to return and test the remaining smokes as they had been covered by a contractor during renovations
Emergency Lighting
Repairs Not Required
Additional Comments:
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
DEVICE LEGEND
DEVICE DESCRIPTION
ANN Annunciator
AD Ancillary Device (Note 4)
B Bell
BZ Buzzer
C Chime
CR Control Relay
CT1 Single Input Module (for supervised Class B signal or audio circuits)
CT2 Double Input Module (for supervised Class B signal or audio circuits)
DH Door Hold Open Device
DS Duct Smoke Detector
ET Emergency Telephone
FACP Fire Alarm Control Panel
FH Firefighters Handset
FS Sprinkler Flow Switch
GA 2nd Stage of 2-Stage Pull Station
H Horn
H/S Horn Strobe
HSP Horn Loudspeaker
HT Heat Detector, Fixed Temperature
HT-RES Resetable Heat Detector
K Horn, Klaxon Type
M Manual Pull Station
MAG LOCK Magnetic Door Lock
PS Pressure Switch
RHT Heat Detector, Rate-of-Rise
S Smoke Detector
SA Smoke Alarm, Single Station Type (Note 3)
SP Loudspeaker
SS Sprinkler Supervisory Switch
SV Sprinkler Valve
TS Sprinkler Tamper Switch (Note 2)
V Visual Alarm Appliance
Note 1: Confirmation of wiring supervision to each individual device is only required during installation verification or a complete building audit
of the system and is not required on the annual test.
Note 2: Sprinkler tamper switches cause trouble condition to be annunciated but not an alarm condition.
Note 3: Single station smoke alarms are not part of the fire alarm system but testing of such devices may be required by the authority
having jurisdiction.
Note 4: Identify the specific ancillary devices in the Remark column of Fire Alarm System Device Test and Inspection Record form
183 Exeter Road, Unit A
London, Ontario
PHONE (519) 652-5086
FAX (519) 652-8719
1. GENERAL:
2. CONTROL VALVES:
3. WATER SUPPLIES:
a) Are siamese connections in good condition, couplings free, caps in place and ball drips open? YES
5. FIRE HYDRANTS:
N/A
6. WET SYSTEMS:
7. DRY SYSTEMS:
N/A
8. ANTI-FREEZE SYSTEMS:
N/A
9. SPECIAL SYSTEMS:
N/A
N/A
11. ALARMS:
a) Are all sprinklers in good condition, free from obstruction, corrosion and loading? YES
b) Are the sprinklers less than 50 years old? (1996) YES
c) Are there spare sprinklers and a wrench in the head cabinet? No
d) Is the condition of the piping, drain valves, hangers and gauges in good condition? YES
e) Have the sprinklers been checked for the proper temperature rating? YES
14. Listed are recent changes in the building occupancy or fire protection equipment.
NONE
NONE
NONE
NONE
• LIMITATION OF LIABILITY: It is understood and agreed that the INSPECTOR is NOT an insurer and is NOT
warranting or guaranteeing the adequacy, performance or life expectancy of any structure, item, component or
system in the building. Further, it is mutually agreed that the maximum amount of joint and several liability the
INSPECTOR can incur for any error, mistakes, omissions, breach of contract, breach of warrantee, negligent
hiring, or any other theory of liability including violation of a statute or consumer protection act is strictly limited
to the FEE PAID for the inspection report.
NOTE: This inspection/test was performed in accordance with The Ontario Fire Code. This inspection does NOT certify
that the sprinkler system installation complies with NFPA, OBC or Ontario Retrofit Reg. #627/92 (an engineer’s report
would be required to certify this).
As per the requirements of The Ontario Fire Codes, the inspecting company must submit this report to the local
Fire Prevention office
THIS DOCUMENT CERTIFIES THAT THE FIRE ALARM SYSTEM AT THE FOLLOWING LOCATION;
ST. ANNE- 1000 THE RAPIDS PARKWAY, SARNIA
HAS BEEN TESTED & INSPECTED IN ACCORDANCE WITH THE STANDARD FOR THE INSPECTION AND TESTING OF
FIRE ALARM SYSTEMS, CAN/ULC-S536-04. THE SPRINKLER SYSTEM HAS ALSO BEEN INSPECTED AT THIS LOCATION.
A TEST OF ALL EMERGENCY LIGHTING EQUIPMENT WAS COMPLETED IN ACCORDANCE WITH CANADIAN ULC
CODES AND DESIGN CRITERIA DESIGNATED BY MANUFACTURER'S SPECIFICATIONS.
YES NO N/A
E The fire alarm system documentation is on site and includes a description of the system √
G The fire alarm system has deficiencies noted on the attached pages √
H Comments:
The information on this form (and the documents attached here-to) attest to the fact that the equipment listed here-in was tested/inspected in
conformance with applicable codes, bylaws, standards, and the manufacturer's requirements by a qualified technician. The equipment was left
in an operational condition except as noted in the spaces marked "comments". A copy should be maintained on the premises for examination
by the Fire Marshall or Inspector at their request.
Technician #1 Technician #2
YES NO N/A
Output circuits for selective voice paging, including visual indication operates √
Output circuits for selective voice paging trouble operation, including visual indication operates √
Operation of voice paging does not interfere with entitled inhibit time of alert signal and alarm signal √
Circuits for emergency telephone call in operation, including audible and visual indication operates √
Circuits for emergency telephone for operation, including two-way voice communication operates √
YES NO N/A
YES NO N/A
EMERGENCY POWER SUPPLY TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.3, 5.3.2, 5.33]
YES NO N/A
Correct battery rating as determined by battery calculations based on full system load √
Adequately ventilated √
Generator provides power to the AC circuit serving the fire alarm system. √
Trouble condition at the emergency generator results in an audible common trouble signal and a visual indication at the required
annunciator. √
Battery voltage not less than 85% of its rated capacity after tests completed √
Battery manufacturer and part number NP7-12
Battery manufacturer's date code or ins service date Date 2014
Battery Voltage (main power supply 'ON') is Voltage 27.20
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 25.20
in supervisory condition Current (A) 0.200
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 24.80
in full load condition Current (A) 1.39
The charging current is Current (mA) 398
INDICATE TYPE OF BATTERY TEST PERFORMED (must choose 1 of 5 methods)
YES NO N/A
(i) Required supervisory load for 24 h followed by the required full load operation; √
(ii) Silent test using load resistor method for full duration test. √
(v) Replace the batteries with a new set having a current date code/capacity/type √
Record battery capacity AH 12
Record the battery terminal voltage after tests are completed. VDC 25.80
ANNUNCIATOR AND REMOTE TROUBLE SIGNAL UNIT TEST & INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.1]
YES NO N/A
Individual alarm and supervisory input zone clearly indicated and separately designated √
Individual alarm and supervisory input zone designation labels are properly identified √
YES NO N/A
Minimum of one alarm zone and one supervisory zone tested per annunciator or sequential display to confirm operation √
Individual alarm and supervisory input zone designation labels are properly identified. √
REMOTE TROUBLE SIGNAL UNIT TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.3]
YES NO N/A
YES NO N/A
Operates as per design and specification, or in accordance with documentation provided in Appendix E. √
DATA COMMUNICATION LINK TEST [Ref. CAN/ULC-S536-04, Clauses 5.1.5, 5.6 Note]
YES NO N/A
Confirm that a trouble signal is received at the control unit or transponder under an open loop fault for each data communication
link (DCL) √
Where fault isolation modules are installed in data communication links serving field devices, wiring shorted on the isolated side,
annunciation of the fault confirmed, and then a device on the source side operated, and activation confirmed at the control unit or √
Where fault isolation in data communication links is provided between control units or transponders and between transponders,
introduce a short circuit fault and confirm annunciation of the fault and operation outside the shorted section between each pair of: √
YES NO N/A
Door Holders √
Tie to Security √
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 8th, 2016
Building Name: St. Elizabeth Address: 1350 Bertha Street, Wallaceburg Page 1 of 3
Gym Exit M √ √ 1
Gym B √ √ S-1 EOL
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 8th, 2016
Building Name: St. Elizabeth Address: 1350 Bertha Street, Wallaceburg Page 2 of 3
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 8th, 2016
Building Name: St. Elizabeth Address: 1350 Bertha Street, Wallaceburg Page 3 of 3
CAN/ULC
EMERGENCY LIGHTING
INDIVIDUAL DEVICE RECORD
Date: August 8th, 2016
REPAIRS
# LOCATION DEVICE REPAIR COMPLETED
Fire Alarm
Repairs Not Required
Emergency Lighting
Repairs Not Required
Additional Comments:
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
DEVICE LEGEND
DEVICE DESCRIPTION
ANN Annunciator
AD Ancillary Device (Note 4)
B Bell
BZ Buzzer
C Chime
CR Control Relay
CT1 Single Input Module (for supervised Class B signal or audio circuits)
CT2 Double Input Module (for supervised Class B signal or audio circuits)
DH Door Hold Open Device
DS Duct Smoke Detector
ET Emergency Telephone
FACP Fire Alarm Control Panel
FH Firefighters Handset
FS Sprinkler Flow Switch
GA 2nd Stage of 2-Stage Pull Station
H Horn
H/S Horn Strobe
HSP Horn Loudspeaker
HT Heat Detector, Fixed Temperature
HT-RES Resetable Heat Detector
K Horn, Klaxon Type
M Manual Pull Station
MAG LOCK Magnetic Door Lock
PS Pressure Switch
RHT Heat Detector, Rate-of-Rise
S Smoke Detector
SA Smoke Alarm, Single Station Type (Note 3)
SP Loudspeaker
SS Sprinkler Supervisory Switch
SV Sprinkler Valve
TS Sprinkler Tamper Switch (Note 2)
V Visual Alarm Appliance
Note 1: Confirmation of wiring supervision to each individual device is only required during installation verification or a complete building audit
of the system and is not required on the annual test.
Note 2: Sprinkler tamper switches cause trouble condition to be annunciated but not an alarm condition.
Note 3: Single station smoke alarms are not part of the fire alarm system but testing of such devices may be required by the authority
having jurisdiction.
Note 4: Identify the specific ancillary devices in the Remark column of Fire Alarm System Device Test and Inspection Record form
ANNUAL FIRE ALARM SYSTEM TESTING CERTIFICATE
THIS DOCUMENT CERTIFIES THAT THE FIRE ALARM SYSTEM AT THE FOLLOWING LOCATION;
ST. ELIZABETH~ 1350 BERTHA STREET, WALLACEBURG
HAS BEEN TESTED & INSPECTED IN ACCORDANCE WITH THE STANDARD FOR THE INSPECTION AND TESTING
OF FIRE ALARM SYSTEMS, CAN/ULC-S536-04.
A TEST OF ALL EMERGENCY LIGHTING EQUIPMENT WAS ALSO COMPLETED IN ACCORDANCE WITH CANADIAN
ULC CODES AND DESIGN CRITERIA DESIGNATED BY MANUFACTURER'S SPECIFICATIONS.
YES NO N/A
E The fire alarm system documentation is on site and includes a description of the system √
G The fire alarm system has deficiencies noted on the attached pages √
H Comments:
The information on this form (and the documents attached here-to) attest to the fact that the equipment listed here-in was tested/inspected in
conformance with applicable codes, bylaws, standards, and the manufacturer's requirements by a qualified technician. The equipment was left
in an operational condition except as noted in the spaces marked "comments". A copy should be maintained on the premises for examination
by the Fire Marshall or Inspector at their request.
Technician #1 Technician #2
YES NO NA
Power 'ON' visual indicator √
Common visual trouble signal √
Common audible trouble signal √
Trouble signal silence switch √
Main power supply failure trouble signal operates √
Ground fault tested on positive and negative trouble signal √
Alert signal operation √
Alarm signal operation √
Automatic transfer from alert signal to alarm signal √
Manual transfer from alert signal to alarm signal cancel (acknowledge) feature operates on a two-stage system √
Automatic transfer from alert signal to alarm signal cancel (acknowledge) feature operates on a two-stage system √
Alarm signal silence inhibit function operates √
Alarm signal manual silence operational √
Alarm signal silence visual indication operates √
Alarm signals, when silenced automatically reinitiate upon subsequent alarm √
Alarm signal silence automatic cut-out timer Time: √
Audible and visual alert signals and alarm signals programmed and operate per design and specification; or documentation as detailed
in Appendix C - Description of Fire Alarm System for Inspection and Test Procedures
√
Input circuit, alarm and supervisory operation, including audible and visual indication operates √
Input circuit supervision fault causes a trouble indication √
Output circuit alarm indicates operational √
Output circuit supervision fault causes a trouble indication √
Visual indicator test (lamp test) √
Coded Signal sequences operate not less than the required number of times and the correct alarm signal operates thereafter √
Coded signal sequences are not interrupted by subsequent alarm √
Ancillary device by-pass will result in a trouble signal √
Input circuit to output circuit operation, including ancillary device circuits, for correct program operation, as per design and specification,
or documentation as detailed in Appendix C - Description of Fire Alarm System for Inspection and Testing Procedures
√
Fire alarm system reset operation √
Main power supply to emergency power supply transfer operates √
Status change confirmation (smoke detectors only) verified [Refer Subsection 5.7.4.3, Status Change Confirmation (Alarm Verification
Feature)]
√
Receipt of alarm transmission to the fire signal receiving centre √
Receipt of the supervisory transmission to the fire signal receiving centre √
Receipt of the trouble transmission to the fire signal receiving centre √
Operation of the fire signal receiving centre disconnect means results in a specific trouble at the control unit or transponder and
√
transmits a trouble to the fire signal receiving centre
Record the name and telephone number of the fire signal receiving centre √
Name DAMAR- 883330 (Gaels)
Phone Number (519) 336-7111
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
YES NO N/A
Output circuits for selective voice paging, including visual indication operates √
Output circuits for selective voice paging trouble operation, including visual indication operates √
Operation of voice paging does not interfere with entitled inhibit time of alert signal and alarm signal √
Circuits for emergency telephone call in operation, including audible and visual indication operates √
Circuits for emergency telephone for operation, including two-way voice communication operates √
YES NO N/A
EMERGENCY POWER SUPPLY TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.3, 5.3.2, 5.33]
YES NO N/A
Correct battery rating as determined by battery calculations based on full system load √
Adequately ventilated √
Generator provides power to the AC circuit serving the fire alarm system. √
Trouble condition at the emergency generator results in an audible common trouble signal and a visual indication at the required
annunciator. √
Battery voltage not less than 85% of its rated capacity after tests completed √
Battery manufacturer and part number Enersys (2) NP12-12
Battery manufacturer's date code or ins service date Date 2012
Battery Voltage (main power supply 'ON') is Voltage 27.17
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 25.82
in supervisory condition Current (A) 0.336
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 25.66
in full load condition Current (A) 1.788
The charging current is Current (mA) 420
INDICATE TYPE OF BATTERY TEST PERFORMED (must choose 1 of 5 methods)
YES NO N/A
(i) Required supervisory load for 24 h followed by the required full load operation; √
(ii) Silent test using load resistor method for full duration test. √
(v) Replace the batteries with a new set having a current date code/capacity/type √
Record battery capacity AH 12
Record the battery terminal voltage after tests are completed. VDC 27.02
ANNUNCIATOR AND REMOTE TROUBLE SIGNAL UNIT TEST & INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.1]
YES NO N/A
Individual alarm and supervisory input zone clearly indicated and separately designated √
Individual alarm and supervisory input zone designation labels are properly identified √
YES NO N/A
Minimum of one alarm zone and one supervisory zone tested per annunciator or sequential display to confirm operation √
Individual alarm and supervisory input zone designation labels are properly identified. √
REMOTE TROUBLE SIGNAL UNIT TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.3]
YES NO N/A
YES NO N/A
Operates as per design and specification, or in accordance with documentation provided in Appendix E. √
DATA COMMUNICATION LINK TEST [Ref. CAN/ULC-S536-04, Clauses 5.1.5, 5.6 Note]
YES NO N/A
Confirm that a trouble signal is received at the control unit or transponder under an open loop fault for each data communication link
(DCL) √
Where fault isolation modules are installed in data communication links serving field devices, wiring shorted on the isolated side,
annunciation of the fault confirmed, and then a device on the source side operated, and activation confirmed at the control unit or √
Where fault isolation in data communication links is provided between control units or transponders and between transponders,
introduce a short circuit fault and confirm annunciation of the fault and operation outside the shorted section between each pair of: √
YES NO N/A
Door Holders √
Fan Shutdown √
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 9th, 2016
Address: 434 John Street, Port Lambton Building Name: Sacred Heart Page 1 of 3
By Room 118 H √ √
Portapak Entrance E M √ √ 2
Portapak Entrance W M √ √ 2
Portapak Entrance E S (C2M PDI) √ √ 2 5
Portapak Entrance W S (C2M PDI) √ √ 2 6
By Portapak Entrance S (C2M PDI) √ √ 1 5
By Portapak Entrance H/S √ √
By Portapak Entrance DS √ √ 3
Room 116 H √ √
By 116 M √ √ 1
By 116 EOL √ √ 2
By 116 EOL √ √ 3
By 116 EOL √ √ 1
Room 113 H √ √
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 9th, 2016
Building Name: Sacred Heart Address: 434 John Street, Port Lambton Page 2 of 3
Room 108 H √ √
Hall By 108 DS √ √ 3
By 108A S (C2M PDI) √ √ 1 5
By 108A S (C2M PDI) √ √ 1 5
By 108A H/S √ √
Room 108A H √ √
Room 106 H √ √
Room 109 M √ √ 1
Room 109 H √ √
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 9th, 2016
Building Name: Sacred Heart Address: 434 John Street, Port Lambton Page 3 of 3
Room 124 H √ √
128 Gym M √ √ 1
128 Gym M √ √ 1
128 Gym RHT √ √ 1
128 Gym RHT √ √ 1
Room 128B H √ √
CAN/ULC
EMERGENCY LIGHTING
INDIVIDUAL DEVICE RECORD
Date: August 9th, 2016
Address: 434 John Street, Port Lambton Building Name: Sacred Heart
REPAIRS
# LOCATION DEVICE REPAIR COMPLETED
Fire Alarm Devices
1 Room 126 Kitchen HT Replaced Device w/ (1) C2W BA Heat Detector 08/09/2016
Emergency Lighting
1 Room 124 Furnace Room SLD 24 720 Replaced w/ (2) EnerSys NP33-12 Batteries 08/18/2016
Additional Comments:
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
DEVICE LEGEND
DEVICE DESCRIPTION
ANN Annunciator
AD Ancillary Device (Note 4)
B Bell
BZ Buzzer
C Chime
CR Control Relay
CT1 Single Input Module (for supervised Class B signal or audio circuits)
CT2 Double Input Module (for supervised Class B signal or audio circuits)
DH Door Hold Open Device
DS Duct Smoke Detector
ET Emergency Telephone
FACP Fire Alarm Control Panel
FH Firefighters Handset
FS Sprinkler Flow Switch
GA 2nd Stage of 2-Stage Pull Station
H Horn
H/S Horn Strobe
HSP Horn Loudspeaker
HT Heat Detector, Fixed Temperature
HT-RES Resetable Heat Detector
K Horn, Klaxon Type
M Manual Pull Station
MAG LOCK Magnetic Door Lock
PS Pressure Switch
RHT Heat Detector, Rate-of-Rise
S Smoke Detector
SA Smoke Alarm, Single Station Type (Note 3)
SP Loudspeaker
SS Sprinkler Supervisory Switch
SV Sprinkler Valve
TS Sprinkler Tamper Switch (Note 2)
V Visual Alarm Appliance
Note 1: Confirmation of wiring supervision to each individual device is only required during installation verification or a complete building audit
of the system and is not required on the annual test.
Note 2: Sprinkler tamper switches cause trouble condition to be annunciated but not an alarm condition.
Note 3: Single station smoke alarms are not part of the fire alarm system but testing of such devices may be required by the authority
having jurisdiction.
Note 4: Identify the specific ancillary devices in the Remark column of Fire Alarm System Device Test and Inspection Record form
ANNUAL FIRE ALARM SYSTEM TESTING CERTIFICATE
THIS DOCUMENT CERTIFIES THAT THE FIRE ALARM SYSTEM AT THE FOLLOWING LOCATION;
SACRED HEART~ 434 JOHN STREET, PORT LAMBTON
HAS BEEN TESTED & INSPECTED IN ACCORDANCE WITH THE STANDARD FOR THE INSPECTION AND TESTING
OF FIRE ALARM SYSTEMS, CAN/ULC-S536-04.
A TEST OF ALL EMERGENCY LIGHTING EQUIPMENT WAS ALSO COMPLETED IN ACCORDANCE WITH CANADIAN
ULC CODES AND DESIGN CRITERIA DESIGNATED BY MANUFACTURER'S SPECIFICATIONS.
YES NO N/A
E The fire alarm system documentation is on site and includes a description of the system √
G √
H Comments:
I A copy of this report has been given to: SCCDSB- Paul Lernout
The information on this form (and the documents attached here-to) attest to the fact that the equipment listed here-in was tested/inspected in
conformance with applicable codes, bylaws, standards, and the manufacturer's requirements by a qualified technician. The equipment was left in
an operational condition except as noted in the spaces marked "comments". A copy should be maintained on the premises for examination by the
Fire Marshall or Inspector at their request.
Technician #1 Technician #2
YES NO N/A
Output circuits for selective voice paging, including visual indication operates √
Output circuits for selective voice paging trouble operation, including visual indication operates √
Operation of voice paging does not interfere with entitled inhibit time of alert signal and alarm signal √
Circuits for emergency telephone call in operation, including audible and visual indication operates √
Circuits for emergency telephone for operation, including two-way voice communication operates √
YES NO N/A
YES NO N/A
EMERGENCY POWER SUPPLY TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.3, 5.3.2, 5.33]
YES NO N/A
Correct battery rating as determined by battery calculations based on full system load √
Adequately ventilated √
Generator provides power to the AC circuit serving the fire alarm system. √
Trouble condition at the emergency generator results in an audible common trouble signal and a visual indication at the required
annunciator. √
Battery voltage not less than 85% of its rated capacity after tests completed √
Battery manufacturer and part number NP12-12
Battery manufacturer's date code or ins service date Date 2014
Battery Voltage (main power supply 'ON') is Voltage 26.90
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 26.00
in supervisory condition Current (A) 0.371
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 24.90
in full load condition Current (A) 1.388
The charging current is Current (mA) 388
INDICATE TYPE OF BATTERY TEST PERFORMED (must choose 1 of 5 methods)
YES NO N/A
(i) Required supervisory load for 24 h followed by the required full load operation; √
(ii) Silent test using load resistor method for full duration test. √
(v) Replace the batteries with a new set having a current date code/capacity/type √
Record battery capacity AH 12
Record the battery terminal voltage after tests are completed. VDC 25.90
ANNUNCIATOR AND REMOTE TROUBLE SIGNAL UNIT TEST & INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.1]
YES NO N/A
Individual alarm and supervisory input zone clearly indicated and separately designated √
Individual alarm and supervisory input zone designation labels are properly identified √
YES NO N/A
Minimum of one alarm zone and one supervisory zone tested per annunciator or sequential display to confirm operation √
Individual alarm and supervisory input zone designation labels are properly identified. √
REMOTE TROUBLE SIGNAL UNIT TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.3]
YES NO N/A
YES NO N/A
Operates as per design and specification, or in accordance with documentation provided in Appendix E. √
DATA COMMUNICATION LINK TEST [Ref. CAN/ULC-S536-04, Clauses 5.1.5, 5.6 Note]
YES NO N/A
Confirm that a trouble signal is received at the control unit or transponder under an open loop fault for each data communication link
(DCL) √
Where fault isolation modules are installed in data communication links serving field devices, wiring shorted on the isolated side,
annunciation of the fault confirmed, and then a device on the source side operated, and activation confirmed at the control unit or √
Where fault isolation in data communication links is provided between control units or transponders and between transponders,
introduce a short circuit fault and confirm annunciation of the fault and operation outside the shorted section between each pair of: √
YES NO N/A
Door Holders √
Tie to Security √
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 20th, 2016
Building Name: Sacred Heart Address: 1411 LeCaron Ave., Sarnia Page 1 of 3
By 523 S √ √ 2 2M-34
NAC-
By 524-A H/S √ √
1
By 515-A S √ √ 2 M2-31
By 525-A S √ √ 2 M2-30
NAC-
By 525-A H/S √ √
2
513 RHT √ √ 2 M2-29
By 501-A S √ √ 3 M2-44
NAC-
By 514-A H/S √ √
1
By Electrical Room S √ √ 3 M2-47
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 20th, 2016
Building Name: Sacred Heart Address: 1411 LeCaron Ave., Sarnia Page 2 of 3
By 508 S √ √ 3 M2-60
By 532-A M √ √ 2 M2-22
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 20th, 2016
Building Name: Sacred Heart Address: 1411 LeCaron Ave., Sarnia Page 3 of 3
Rm 535 HT √ √ 1 M2-13
CAN/ULC
EMERGENCY LIGHTING
INDIVIDUAL DEVICE RECORD
Date: July 20th, 2016
REPAIRS
# LOCATION DEVICE REPAIR COMPLETED
Fire Alarm Devices
Repairs Not Required
Emergency Lighting
Repairs Not Required
Additional Comments:
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
DEVICE LEGEND
DEVICE DESCRIPTION
ANN Annunciator
AD Ancillary Device (Note 4)
B Bell
BZ Buzzer
C Chime
CR Control Relay
CT1 Single Input Module (for supervised Class B signal or audio circuits)
CT2 Double Input Module (for supervised Class B signal or audio circuits)
DH Door Hold Open Device
DS Duct Smoke Detector
ET Emergency Telephone
FACP Fire Alarm Control Panel
FH Firefighters Handset
FS Sprinkler Flow Switch
GA 2nd Stage of 2-Stage Pull Station
H Horn
H/S Horn Strobe
HSP Horn Loudspeaker
HT Heat Detector, Fixed Temperature
HT-RES Resetable Heat Detector
K Horn, Klaxon Type
M Manual Pull Station
MAG LOCK Magnetic Door Lock
PS Pressure Switch
RHT Heat Detector, Rate-of-Rise
S Smoke Detector
SA Smoke Alarm, Single Station Type (Note 3)
SP Loudspeaker
SS Sprinkler Supervisory Switch
SV Sprinkler Valve
TS Sprinkler Tamper Switch (Note 2)
V Visual Alarm Appliance
Note 1: Confirmation of wiring supervision to each individual device is only required during installation verification or a complete building audit
of the system and is not required on the annual test.
Note 2: Sprinkler tamper switches cause trouble condition to be annunciated but not an alarm condition.
Note 3: Single station smoke alarms are not part of the fire alarm system but testing of such devices may be required by the authority
having jurisdiction.
Note 4: Identify the specific ancillary devices in the Remark column of Fire Alarm System Device Test and Inspection Record form
ANNUAL FIRE ALARM SYSTEM TESTING CERTIFICATE
THIS DOCUMENT CERTIFIES THAT THE FIRE ALARM SYSTEM AT THE FOLLOWING LOCATION;
SACRED HEART, 1411 CARON AVENUE, SARNIA
HAS BEEN TESTED & INSPECTED IN ACCORDANCE WITH THE STANDARD FOR THE INSPECTION AND TESTING
OF FIRE ALARM SYSTEMS, CAN/ULC-S536-04.
A TEST OF ALL EMERGENCY LIGHTING EQUIPMENT WAS ALSO COMPLETED IN ACCORDANCE WITH CANADIAN
ULC CODES AND DESIGN CRITERIA DESIGNATED BY MANUFACTURER'S SPECIFICATIONS.
YES NO N/A
E The fire alarm system documentation is on site and includes a description of the system √
G The fire alarm system has deficiencies noted on the attached pages √
H Comments:
The information on this form (and the documents attached here-to) attest to the fact that the equipment listed here-in was tested/inspected in
conformance with applicable codes, bylaws, standards, and the manufacturer's requirements by a qualified technician. The equipment was left in
an operational condition except as noted in the spaces marked "comments". A copy should be maintained on the premises for examination by
the Fire Marshall or Inspector at their request.
Technician #1 Technician #2
YES NO NA
Power 'ON' visual indicator √
Common visual trouble signal √
Common audible trouble signal √
Trouble signal silence switch √
Main power supply failure trouble signal operates √
Ground fault tested on positive and negative trouble signal √
Alert signal operation √
Alarm signal operation √
Automatic transfer from alert signal to alarm signal √
Manual transfer from alert signal to alarm signal cancel (acknowledge) feature operates on a two-stage system √
Automatic transfer from alert signal to alarm signal cancel (acknowledge) feature operates on a two-stage system √
Alarm signal silence inhibit function operates √
Alarm signal manual silence operational √
Alarm signal silence visual indication operates √
Alarm signals, when silenced automatically reinitiate upon subsequent alarm √
Alarm signal silence automatic cut-out timer Time: √
Audible and visual alert signals and alarm signals programmed and operate per design and specification; or documentation as detailed
in Appendix C - Description of Fire Alarm System for Inspection and Test Procedures √
Input circuit, alarm and supervisory operation, including audible and visual indication operates √
Input circuit supervision fault causes a trouble indication √
Output circuit alarm indicates operational √
Output circuit supervision fault causes a trouble indication √
Visual indicator test (lamp test) √
Coded Signal sequences operate not less than the required number of times and the correct alarm signal operates thereafter √
Coded signal sequences are not interrupted by subsequent alarm √
Ancillary device by-pass will result in a trouble signal √
Input circuit to output circuit operation, including ancillary device circuits, for correct program operation, as per design and specification,
or documentation as detailed in Appendix C - Description of Fire Alarm System for Inspection and Testing Procedures √
Fire alarm system reset operation √
Main power supply to emergency power supply transfer operates √
Status change confirmation (smoke detectors only) verified [Refer Subsection 5.7.4.3, Status Change Confirmation (Alarm Verification
Feature)] √
Receipt of alarm transmission to the fire signal receiving centre √
Receipt of the supervisory transmission to the fire signal receiving centre √
Receipt of the trouble transmission to the fire signal receiving centre √
Operation of the fire signal receiving centre disconnect means results in a specific trouble at the control unit or transponder and
transmits a trouble to the fire signal receiving centre
√
Record the name and telephone number of the fire signal receiving centre √
Name DAMAR- 883335 Crusaders
Phone Number 1 (800) 265-7562
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
YES NO N/A
Output circuits for selective voice paging, including visual indication operates √
Output circuits for selective voice paging trouble operation, including visual indication operates √
Operation of voice paging does not interfere with entitled inhibit time of alert signal and alarm signal √
Circuits for emergency telephone call in operation, including audible and visual indication operates √
Circuits for emergency telephone for operation, including two-way voice communication operates √
YES NO N/A
YES NO N/A
EMERGENCY POWER SUPPLY TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.3, 5.3.2, 5.33]
YES NO N/A
Correct battery rating as determined by battery calculations based on full system load √
Adequately ventilated √
Generator provides power to the AC circuit serving the fire alarm system. √
Trouble condition at the emergency generator results in an audible common trouble signal and a visual indication at the required
annunciator. √
Battery voltage not less than 85% of its rated capacity after tests completed √
Battery manufacturer and part number NP12-12
Battery manufacturer's date code or ins service date Date 2015
Battery Voltage (main power supply 'ON') is Voltage 26.28
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 25.50
in supervisory condition Current (A) 0.300
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 25.33
in full load condition Current (A) 0.920
The charging current is Current (mA) 810
INDICATE TYPE OF BATTERY TEST PERFORMED (must choose 1 of 5 methods)
YES NO N/A
(i) Required supervisory load for 24 h followed by the required full load operation; √
(ii) Silent test using load resistor method for full duration test. √
(v) Replace the batteries with a new set having a current date code/capacity/type √
Record battery capacity. AH 12
Record the battery terminal voltage after tests are completed. VDC 25.60
ANNUNCIATOR AND REMOTE TROUBLE SIGNAL UNIT TEST & INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.1]
YES NO N/A
Individual alarm and supervisory input zone clearly indicated and separately designated √
Individual alarm and supervisory input zone designation labels are properly identified √
YES NO N/A
Minimum of one alarm zone and one supervisory zone tested per annunciator or sequential display to confirm operation √
Individual alarm and supervisory input zone designation labels are properly identified. √
REMOTE TROUBLE SIGNAL UNIT TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.3]
YES NO N/A
YES NO N/A
Operates as per design and specification, or in accordance with documentation provided in Appendix E. √
DATA COMMUNICATION LINK TEST [Ref. CAN/ULC-S536-04, Clauses 5.1.5, 5.6 Note]
YES NO N/A
Confirm that a trouble signal is received at the control unit or transponder under an open loop fault for each data communication link
(DCL) √
Where fault isolation modules are installed in data communication links serving field devices, wiring shorted on the isolated side,
annunciation of the fault confirmed, and then a device on the source side operated, and activation confirmed at the control unit or √
Where fault isolation in data communication links is provided between control units or transponders and between transponders,
introduce a short circuit fault and confirm annunciation of the fault and operation outside the shorted section between each pair of: √
YES NO N/A
Door Holders (x 3) √
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 26th, 2016
1st Floor
Electrical Room Back Stair S (C2M PDI) √ √ 15 5
Hall By Room 4 S (C2M PDI) √ √ 13 5 EOL
2nd Floor
Health Rm French Office RHT √ √ 1
Hall By Staff Room M √ √ 1
Staff Lounge- Kitchen RHT √ √ 1
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 26th, 2016
Hall By Room 6 M √ √ 1
1st Floor
Hall By Room 4 M √ √ 1
Hall By Room 1 B √ √ NAC-1
Janitors Closet HT √ √ 1
Principal’s Office RHT √ √ 1
Office RHT √ √ 1
Office Closet RHT √ √ 1
Hall By Front Entrance M √ √ 1
Gym Exit To Hall M √ √ 1
Gym Exit M √ √ 1
Servery off Gym RHT √ √ 1
Gym Exit Hall M √ √ 1
Gym Storage RHT √ √ 1
Gym Stage RHT √ √ 1 High
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 26th, 2016
Gym B √ √ NAC-1
Hall To Gym M √ √ 1
Room Across from Locker 35 RHT √ √ 1
Hall To Rm 9 Coat Room RHT √ √ 1
Room 9 RHT √ √ 1
Room 9 Right RHT √ √ 1
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 26th, 2016
CAN/ULC
EMERGENCY LIGHTING
INDIVIDUAL DEVICE RECORD
Date: July 26th, 2016
Gym SE Exit To Hall RG 36 LMC PA-6V7.2 (08) 2 3.00 8:36 X √ See Repairs List
Gym NE Exit RG 36 LMC PA-6V12 (10) 2 7.00 8:38 X √ See Repairs List
Hall By Gym RG 36 4 PA-6V12 (14 2 6.92 8:40
Basement By Stair RG 36A PA-6V12 (10) 2 6.81 8:42 X √ See Repairs List
Basement Custodian Room RG 36 PA-6V7.2 (12) 2 7.09 8:44
REPAIRS
# LOCATION DEVICE REPAIR COMPLETED
Fire Alarm Devices
Repairs Not Required
Emergency Lighting
1 Gym SE Exit To Hall RG 36 LMC Replaced Battery w/ (1) Panasonic PA-6V7.2 07/26/2016
2 Gym NE Exit RG 36 LMC Replaced Battery w/ (1) Panasonic PA-6V7.2 07/26/2016
3 Basement By Stair RG 36A Replaced Battery w/ (1) Panasonic PA-6V12 07/26/2016
Additional Comments:
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
DEVICE LEGEND
DEVICE DESCRIPTION
ANN Annunciator
AD Ancillary Device (Note 4)
B Bell
BZ Buzzer
C Chime
CR Control Relay
CT1 Single Input Module (for supervised Class B signal or audio circuits)
CT2 Double Input Module (for supervised Class B signal or audio circuits)
DH Door Hold Open Device
DS Duct Smoke Detector
ET Emergency Telephone
FACP Fire Alarm Control Panel
FH Firefighters Handset
FS Sprinkler Flow Switch
GA 2nd Stage of 2-Stage Pull Station
H Horn
H/S Horn Strobe
HSP Horn Loudspeaker
HT Heat Detector, Fixed Temperature
HT-RES Resetable Heat Detector
K Horn, Klaxon Type
M Manual Pull Station
MAG LOCK Magnetic Door Lock
PS Pressure Switch
RHT Heat Detector, Rate-of-Rise
S Smoke Detector
SA Smoke Alarm, Single Station Type (Note 3)
SP Loudspeaker
SS Sprinkler Supervisory Switch
SV Sprinkler Valve
TS Sprinkler Tamper Switch (Note 2)
V Visual Alarm Appliance
Note 1: Confirmation of wiring supervision to each individual device is only required during installation verification or a complete
building audit of the system and is not required on the annual test.
Note 2: Sprinkler tamper switches cause trouble condition to be annunciated but not an alarm condition.
Note 3: Single station smoke alarms are not part of the fire alarm system but testing of such devices may be required by the
authority having jurisdiction.
Note 4: Identify the specific ancillary devices in the Remark column of Fire Alarm System Device Test and Inspection Record form
ANNUAL FIRE ALARM SYSTEM TESTING CERTIFICATE
THIS DOCUMENT CERTIFIES THAT THE FIRE ALARM SYSTEM AT THE FOLLOWING LOCATION;
ST. JOSEPH~ 25-35 RALEIGH ST. CHATHAM
HAS BEEN TESTED & INSPECTED IN ACCORDANCE WITH THE STANDARD FOR THE INSPECTION AND TESTING OF
FIRE ALARM SYSTEMS, CAN/ULC-S536-04. THE FIRE HYDRANT HAS ALSO BEEN INSPECTED AT THIS LOCATION.
A TEST OF ALL EMERGENCY LIGHTING EQUIPMENT WAS COMPLETED IN ACCORDANCE WITH CANADIAN
ULC CODES AND DESIGN CRITERIA DESIGNATED BY MANUFACTURER'S SPECIFICATIONS.
YES NO N/A
E The fire alarm system documentation is on site and includes a description of the system √
G The fire alarm system has deficiencies noted on the attached pages √
H Comments:
I A copy of this report has been given to: Paul Lernout - SCCDSB
The information on this form (and the documents attached here-to) attest to the fact that the equipment listed here-in was tested/inspected in
conformance with applicable codes, bylaws, standards, and the manufacturer's requirements by a qualified technician. The equipment was left in
an operational condition except as noted in the spaces marked "comments". A copy should be maintained on the premises for examination by the
Fire Marshall or Inspector at their request.
Technician #1 Technician #2
YES NO NA
Power 'ON' visual indicator √
Common visual trouble signal √
Common audible trouble signal √
Trouble signal silence switch √
Main power supply failure trouble signal operates √
Ground fault tested on positive and negative trouble signal √
Alert signal operation √
Alarm signal operation √
Automatic transfer from alert signal to alarm signal √
Manual transfer from alert signal to alarm signal cancel (acknowledge) feature operates on a two-stage system √
Automatic transfer from alert signal to alarm signal cancel (acknowledge) feature operates on a two-stage system √
Alarm signal silence inhibit function operates √
Alarm signal manual silence operational √
Alarm signal silence visual indication operates √
Alarm signals, when silenced automatically reinitiate upon subsequent alarm √
Alarm signal silence automatic cut-out timer Time: √
Audible and visual alert signals and alarm signals programmed and operate per design and specification; or documentation as detailed
in Appendix C - Description of Fire Alarm System for Inspection and Test Procedures √
Input circuit, alarm and supervisory operation, including audible and visual indication operates √
Input circuit supervision fault causes a trouble indication √
Output circuit alarm indicates operational √
Output circuit supervision fault causes a trouble indication √
Visual indicator test (lamp test) √
Coded Signal sequences operate not less than the required number of times and the correct alarm signal operates thereafter √
Coded signal sequences are not interrupted by subsequent alarm √
Ancillary device by-pass will result in a trouble signal √
Input circuit to output circuit operation, including ancillary device circuits, for correct program operation, as per design and specification,
or documentation as detailed in Appendix C - Description of Fire Alarm System for Inspection and Testing Procedures √
Fire alarm system reset operation √
Main power supply to emergency power supply transfer operates √
Status change confirmation (smoke detectors only) verified [Refer Subsection 5.7.4.3, Status Change Confirmation (Alarm Verification
Feature)] √
Receipt of alarm transmission to the fire signal receiving centre √
Receipt of the supervisory transmission to the fire signal receiving centre √
Receipt of the trouble transmission to the fire signal receiving centre √
Operation of the fire signal receiving centre disconnect means results in a specific trouble at the control unit or transponder and
transmits a trouble to the fire signal receiving centre
√
Record the name and telephone number of the fire signal receiving centre √
Name DAMAR- 114657 Saints
Phone Number 1 (800) 265-7562
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
YES NO N/A
Output circuits for selective voice paging, including visual indication operates √
Output circuits for selective voice paging trouble operation, including visual indication operates √
Operation of voice paging does not interfere with entitled inhibit time of alert signal and alarm signal √
Circuits for emergency telephone call in operation, including audible and visual indication operates √
Circuits for emergency telephone for operation, including two-way voice communication operates √
YES NO N/A
EMERGENCY POWER SUPPLY TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.3, 5.3.2, 5.33]
YES NO N/A
Correct battery rating as determined by battery calculations based on full system load √
Adequately ventilated √
Generator provides power to the AC circuit serving the fire alarm system. √
Trouble condition at the emergency generator results in an audible common trouble signal and a visual indication at the required
annunciator. √
Battery voltage not less than 85% of its rated capacity after tests completed √
Battery manufacturer and part number (2) BB EP28-12
Battery manufacturer's date code or ins service date Date 2011
Battery Voltage (main power supply 'ON') is Voltage 27.00
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 25.20
in supervisory condition Current (A) 0.650
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 24.90
in full load condition Current (A) 0.992
The charging current is Current (mA) 1820
(i) Required supervisory load for 24 h followed by the required full load operation; √
(ii) Silent test using load resistor method for full duration test. √
(v) Replace the batteries with a new set having a current date code/capacity/type √
Record battery capacity AH 12
Record the battery terminal voltage after tests are completed. VDC 25.60
ANNUNCIATOR AND REMOTE TROUBLE SIGNAL UNIT TEST & INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.1]
YES NO N/A
Individual alarm and supervisory input zone clearly indicated and separately designated √
Individual alarm and supervisory input zone designation labels are properly identified √
YES NO N/A
Minimum of one alarm zone and one supervisory zone tested per annunciator or sequential display to confirm operation √
Individual alarm and supervisory input zone designation labels are properly identified. √
REMOTE TROUBLE SIGNAL UNIT TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.3]
YES NO N/A
YES NO N/A
Operates as per design and specification, or in accordance with documentation provided in Appendix E. √
DATA COMMUNICATION LINK TEST [Ref. CAN/ULC-S536-04, Clauses 5.1.5, 5.6 Note]
YES NO N/A
Confirm that a trouble signal is received at the control unit or transponder under an open loop fault for each data communication link
(DCL) √
Where fault isolation modules are installed in data communication links serving field devices, wiring shorted on the isolated side,
annunciation of the fault confirmed, and then a device on the source side operated, and activation confirmed at the control unit or √
Where fault isolation in data communication links is provided between control units or transponders and between transponders,
introduce a short circuit fault and confirm annunciation of the fault and operation outside the shorted section between each pair of: √
YES NO N/A
Door Holders √
Tie to Security √
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 21st, 2016
860 S (1400A) √ √ 1
Exit Door 860 M X 1 See Repairs List
NAC-
By 743 H √ √ 1
By 744 M √ √ 2
741 RHT √ √ 3 EOL
NAC-
By 736 H √ √ 1
By Front Door M √ √ 4
NAC-
By 705 H √ √ 1
Exit By 723 M √ √ 7
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 21st, 2016
Stage RHT √ √ 8
NAC-
Back Stage Wall H √ √ 2
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 21st, 2016
Sprinkler Room
East Zone FS √ √ 12 EOL
CAN/ULC
EMERGENCY LIGHTING
INDIVIDUAL DEVICE RECORD
Date: July 21st, 2016
Gym (Storage) RG 12S 144 (2) PA-6V12 (14) 7 13.25 11:03 545 Panel H CCT#27
Ceiling (Kitchen) RG 12S 72 PA-12V7.2 (14) 3 13.20 11:05 671 Panel A Cir #3
Custodian Room RG 12S 72 (2) PA-6V7.2 (14) 3 13.21 11:07 691 Panel A Cir #3
W / C Ceiling Rm 142C RG 12S 72 (2) PA-6V7.2 (12) 3 13.19 11:20 621 Panel A Cir #3
Outside Rm 140 Elect. (In 705P) RG 36 (2) PA-6V7.2 (12) 3 13.92 11:21 591 Panel B CCT#13
Electrical Room 140A RG 12S 72 (1) PA-6V7.2 (10) 1 6.79 11:22 582 Panel B CCT#13
Library Office Ceiling RG 12S 72 (2) PA-6V7.2 (13) 4 N/A 11:24 N/A X Panel B CCT#13
736A Ceiling RG 12S 72 (2) PA-6V7.2 (14) 3 13.20 11:25 591 Panel B CCT#3
Custodian Room RG 12S 72 (2) PA-6V12 (14) 4 13.25 11:27 630 Panel D CCT #3
Storage RG 12S 100 (2) PA-6V7.2 (13) 3 13.20 11:29 633 Panel D CCT #3
83 Ceiling (860 First Rm on Left) RG 12S 100 (2) PA-6V7.2 (10) 4 13.34 11:30 692 Panel C CCT #1
YMCA Area- West Exit RG 442MTSW (1) PA-6V12 (14) 4 6.89 11:32 643 Panel T CCT #3
REPAIRS
# LOCATION DEVICE REPAIR COMPLETED
Fire Alarm Devices
1 Exit Door 860 M Replaced (1) Manual Pull Station Glass Rod 07/21/2016
2 Exit Off 709 M Replaced (1) Manual Pull Station Glass Rod 07/21/2016
3 Gym Right Side M Replaced (1) Manual Pull Station Glass Rod 07/21/2016
Emergency Lighting
1 Library Office Ceiling RG 12S 72 Replaced Batteries w/ (2) Panasonic PA-6V7.2 07/21/2016
Sprinkler System
Repairs not Required
Additional Comments:
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
DEVICE LEGEND
DEVICE DESCRIPTION
ANN Annunciator
AD Ancillary Device (Note 4)
B Bell
BZ Buzzer
C Chime
CR Control Relay
CT1 Single Input Module (for supervised Class B signal or audio circuits)
CT2 Double Input Module (for supervised Class B signal or audio circuits)
DH Door Hold Open Device
DS Duct Smoke Detector
ET Emergency Telephone
FACP Fire Alarm Control Panel
FH Firefighters Handset
FS Sprinkler Flow Switch
GA 2nd Stage of 2-Stage Pull Station
H Horn
H/S Horn Strobe
HSP Horn Loudspeaker
HT Heat Detector, Fixed Temperature
HT-RES Resetable Heat Detector
K Horn, Klaxon Type
M Manual Pull Station
MAG LOCK Magnetic Door Lock
PS Pressure Switch
RHT Heat Detector, Rate-of-Rise
S Smoke Detector
SA Smoke Alarm, Single Station Type (Note 3)
SP Loudspeaker
SS Sprinkler Supervisory Switch
SV Sprinkler Valve
TS Sprinkler Tamper Switch (Note 2)
V Visual Alarm Appliance
Note 1: Confirmation of wiring supervision to each individual device is only required during installation verification or a complete building audit
of the system and is not required on the annual test.
Note 2: Sprinkler tamper switches cause trouble condition to be annunciated but not an alarm condition.
Note 3: Single station smoke alarms are not part of the fire alarm system but testing of such devices may be required by the authority
having jurisdiction.
Note 4: Identify the specific ancillary devices in the Remark column of Fire Alarm System Device Test and Inspection Record form
183 Exeter Road, Unit A
London, Ontario
PHONE (519) 652-5086
FAX (519) 652-8719
1. GENERAL:
2. CONTROL VALVES:
3. WATER SUPPLIES:
a) Are siamese connections in good condition, couplings free, caps in place and ball drips open? YES
(Brass)
6. WET SYSTEMS:
7. DRY SYSTEMS:
N/A
8. ANTI-FREEZE SYSTEMS:
N/A
9. SPECIAL SYSTEMS:
N/A
N/A
11. ALARMS:
a) Are all sprinklers in good condition, free from obstruction, corrosion and loading? YES
b) Are the sprinklers less than 50 years old? (1995) YES
c) Are there spare sprinklers and a wrench in the head cabinet? YES
d) Is the condition of the piping, drain valves, hangers and gauges in good condition? YES
e) Have the sprinklers been checked for the proper temperature rating? YES
14. Listed are recent changes in the building occupancy or fire protection equipment.
NONE
NONE
NONE
The above items are deficient as per The Ontario Fire Code and need to be corrected immediately.
A certificate of inspection cannot be issued until all items under section #16 have been addressed.
Consultation with the local fire prevention office is suggested, if discrepancies occur
NONE
NOTE: This inspection/test was performed in accordance with The Ontario Fire Code. This inspection does NOT certify
that the fire hydrant installation complies with NFPA, OBC or Ontario Retrofit Reg. #627/92 (an engineer’s report would be
required to certify this).
LIMITATION OF LIABILITY: It is understood and agreed that the INSPECTOR is NOT an insurer and is NOT
warranting or guaranteeing the adequacy, performance or life expectancy of any structure, item,
component or system in the building. Further, it is mutually agreed that the maximum amount of joint and
several liability the INSPECTOR can incur for any error, mistakes, omissions, breach of contract, breach of
warrantee, negligent hiring, or any other theory of liability including violation of a statue or consumer
protection act is strictly limited to the FEE PAID for the inspection report.
As per the requirements of The Ontario Fire Codes, the inspecting company must submit this report to the
local Fire Prevention office
Notes:
West Zone Insp.Test in 751A (Ceiling)
East Zone Insp.Test in Gym (Chair Storage)
THIS DOCUMENT CERTIFIES THAT THE FIRE ALARM SYSTEM AT THE FOLLOWING LOCATION;
ST. JOSEPH- 535 BIRCHBANK DRIVE, CORUNNA
HAS BEEN TESTED & INSPECTED IN ACCORDANCE WITH THE STANDARD FOR THE INSPECTION AND TESTING OF
FIRE ALARM SYSTEMS, CAN/ULC-S536-04. THE SPRINKLER SYSTEM & FIRE HYDRANT HAVE ALSO BEEN INSPECTED
AT THIS LOCATION.
A TEST OF ALL EMERGENCY LIGHTING EQUIPMENT WAS ALSO COMPLETED IN ACCORDANCE WITH CANADIAN
ULC CODES AND DESIGN CRITERIA DESIGNATED BY MANUFACTURER'S SPECIFICATIONS.
YES NO N/A
E The fire alarm system documentation is on site and includes a description of the system √
G The fire alarm system has deficiencies noted on the attached pages √
H Comments:
I A copy of this report has been given to: Paul Lernout - SCCDSB
The information on this form (and the documents attached here-to) attest to the fact that the equipment listed here-in was tested/inspected in
conformance with applicable codes, bylaws, standards, and the manufacturer's requirements by a qualified technician. The equipment was left
in an operational condition except as noted in the spaces marked "comments". A copy should be maintained on the premises for examination
by the Fire Marshall or Inspector at their request.
Technician #1 Technician #2
YES NO NA
Power 'ON' visual indicator √
Common visual trouble signal √
Common audible trouble signal √
Trouble signal silence switch √
Main power supply failure trouble signal operates √
Ground fault tested on positive and negative trouble signal √
Alert signal operation √
Alarm signal operation √
Automatic transfer from alert signal to alarm signal √
Manual transfer from alert signal to alarm signal cancel (acknowledge) feature operates on a two-stage system √
Automatic transfer from alert signal to alarm signal cancel (acknowledge) feature operates on a two-stage system √
Alarm signal silence inhibit function operates √
Alarm signal manual silence operational √
Alarm signal silence visual indication operates √
Alarm signals, when silenced automatically reinitiate upon subsequent alarm √
Alarm signal silence automatic cut-out timer Time: √
Audible and visual alert signals and alarm signals programmed and operate per design and specification; or documentation as detailed
in Appendix C - Description of Fire Alarm System for Inspection and Test Procedures √
Input circuit, alarm and supervisory operation, including audible and visual indication operates √
Input circuit supervision fault causes a trouble indication √
Output circuit alarm indicates operational √
Output circuit supervision fault causes a trouble indication √
Visual indicator test (lamp test) √
Coded Signal sequences operate not less than the required number of times and the correct alarm signal operates thereafter √
Coded signal sequences are not interrupted by subsequent alarm √
Ancillary device by-pass will result in a trouble signal √
Input circuit to output circuit operation, including ancillary device circuits, for correct program operation, as per design and
specification, or documentation as detailed in Appendix C - Description of Fire Alarm System for Inspection and Testing Procedures √
Fire alarm system reset operation √
Main power supply to emergency power supply transfer operates √
Status change confirmation (smoke detectors only) verified [Refer Subsection 5.7.4.3, Status Change Confirmation (Alarm Verification
Feature)] √
Receipt of alarm transmission to the fire signal receiving centre √
Receipt of the supervisory transmission to the fire signal receiving centre √
Receipt of the trouble transmission to the fire signal receiving centre √
Operation of the fire signal receiving centre disconnect means results in a specific trouble at the control unit or transponder and
transmits a trouble to the fire signal receiving centre
√
Record the name and telephone number of the fire signal receiving centre √
Name DAMAR- 114656-Lakers
Phone Number (800) 265-7562
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
YES NO N/A
Output circuits for selective voice paging, including visual indication operates √
Output circuits for selective voice paging trouble operation, including visual indication operates √
Operation of voice paging does not interfere with entitled inhibit time of alert signal and alarm signal √
Circuits for emergency telephone call in operation, including audible and visual indication operates √
Circuits for emergency telephone for operation, including two-way voice communication operates √
YES NO N/A
EMERGENCY POWER SUPPLY TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.3, 5.3.2, 5.33]
YES NO N/A
Correct battery rating as determined by battery calculations based on full system load √
Adequately ventilated √
Generator provides power to the AC circuit serving the fire alarm system. √
Trouble condition at the emergency generator results in an audible common trouble signal and a visual indication at the required
annunciator. √
Battery voltage not less than 85% of its rated capacity after tests completed √
Battery manufacturer and part number (2) Enersys NP7-12
Battery manufacturer's date code or ins service date Date 2014
Battery Voltage (main power supply 'ON') is Voltage 26.60
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 25.500
in supervisory condition Current (A) 0.340
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 25.20
in full load condition Current (A) 1.201
The charging current is Current (mA) 770
YES NO N/A
(i) Required supervisory load for 24 h followed by the required full load operation; √
(ii) Silent test using load resistor method for full duration test. √
(v) Replace the batteries with a new set having a current date code/capacity/type √
Record battery capacity AH 7
Record the battery terminal voltage after tests are completed. VDC 25.80
ANNUNCIATOR AND REMOTE TROUBLE SIGNAL UNIT TEST & INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.1]
YES NO N/A
Individual alarm and supervisory input zone clearly indicated and separately designated √
Individual alarm and supervisory input zone designation labels are properly identified √
YES NO N/A
Minimum of one alarm zone and one supervisory zone tested per annunciator or sequential display to confirm operation √
Individual alarm and supervisory input zone designation labels are properly identified. √
REMOTE TROUBLE SIGNAL UNIT TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.3]
YES NO N/A
YES NO N/A
Operates as per design and specification, or in accordance with documentation provided in Appendix E. √
DATA COMMUNICATION LINK TEST [Ref. CAN/ULC-S536-04, Clauses 5.1.5, 5.6 Note]
YES NO N/A
Confirm that a trouble signal is received at the control unit or transponder under an open loop fault for each data communication
link (DCL) √
Where fault isolation modules are installed in data communication links serving field devices, wiring shorted on the isolated side,
annunciation of the fault confirmed, and then a device on the source side operated, and activation confirmed at the control unit or √
Where fault isolation in data communication links is provided between control units or transponders and between transponders,
introduce a short circuit fault and confirm annunciation of the fault and operation outside the shorted section between each pair of: √
YES NO N/A
Door Holders √
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 24th, 2016
Building Name: St. John Fisher Address: 44 Main Street, Forest Page 1 of 4
In 101A RHT √ √ 2
In 101B Exit M √ √ 2
In 101B RHT √ √ 2
In 101B H √ √ 2
Hall at 103 H √ √ 2
In 103 RHT √ √ 2
103 Exit M √ √ 2
104 Custodial M √ √ 2
In 105 RHT √ √ 2
In 110 RHT √ √ 2
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 24th, 2016
Building Name: St. John Fisher Address: 44 Main Street, Forest Page 2 of 4
Hall at 110 H √ √ 2
In 112 RHT √ √ 2
At 112C RHT √ √ 2
In 112 Exit M √ √ 2
112A RHT √ √ 2
112B RHT √ √ 2
112C RHT √ √ 2
112D RHT √ √ 1
Room 113 H √ √ 1
Exit at 115 M √ √ 1
In Room 114 DS √ √ 3
In 115 RHT √ √ 1
In 117 RHT √ √ 1
In 117 H √ √ S-1
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 24th, 2016
Building Name: St. John Fisher Address: 44 Main Street, Forest Page 3 of 4
In 121 Daycare 2 H √ √ 1
Exit at 122 M √ √ 1
In 122 M √ √ 1
In 122 RHT √ √ 1
In Room 122 H √ √ 1
Room 127 FS √ √ 5
Room 127 TS √ √ 5
Hall at 133 H √ √ 2
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 24th, 2016
Building Name: St. John Fisher Address: 44 Main Street, Forest Page 4 of 4
137 Kitchen HT √ √ 2
Exit at 137 M √ √ 2
139D RHT √ √ 2
139E RHT √ √ 2
CAN/ULC
EMERGENCY LIGHTING
INDIVIDUAL DEVICE RECORD
Date: August 24th, 2016
Room 104 SLD 24550 (2) PA-12V33 (09) 22 27.69 11:50 1310
Room 112D SLD 24550 (2) PA-12V33 (09) 10 - 11:52 - X See Repairs List
REPAIRS
# LOCATION DEVICE REPAIR COMPLETED
Fire Alarm Devices
1 In 107 Boys Washroom RHT Replaced Device w/ (1) 5601A Heat Detector 08/24/2016
2 Edwards Fire Alarm Panel Edwards 6616 Replaced Batteries w/ (2) EnerSys NP33-12 08/29/2016
Emergency Lighting
1 Room 112D SLD 24 550 Replaced (1) 24 Volt PC Board 08/29/2016
Additional Comments:
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
DEVICE LEGEND
DEVICE DESCRIPTION
ANN Annunciator
AD Ancillary Device (Note 4)
B Bell
BZ Buzzer
C Chime
CR Control Relay
CT1 Single Input Module (for supervised Class B signal or audio circuits)
CT2 Double Input Module (for supervised Class B signal or audio circuits)
DH Door Hold Open Device
DS Duct Smoke Detector
ET Emergency Telephone
FACP Fire Alarm Control Panel
FH Firefighters Handset
FS Sprinkler Flow Switch
GA 2nd Stage of 2-Stage Pull Station
H Horn
H/S Horn Strobe
HSP Horn Loudspeaker
HT Heat Detector, Fixed Temperature
HT-RES Resetable Heat Detector
K Horn, Klaxon Type
M Manual Pull Station
MAG LOCK Magnetic Door Lock
PS Pressure Switch
RHT Heat Detector, Rate-of-Rise
S Smoke Detector
SA Smoke Alarm, Single Station Type (Note 3)
SP Loudspeaker
SS Sprinkler Supervisory Switch
SV Sprinkler Valve
TS Sprinkler Tamper Switch (Note 2)
V Visual Alarm Appliance
Note 1: Confirmation of wiring supervision to each individual device is only required during installation verification or a complete building audit
of the system and is not required on the annual test.
Note 2: Sprinkler tamper switches cause trouble condition to be annunciated but not an alarm condition.
Note 3: Single station smoke alarms are not part of the fire alarm system but testing of such devices may be required by the authority
having jurisdiction.
Note 4: Identify the specific ancillary devices in the Remark column of Fire Alarm System Device Test and Inspection Record form
ANNUAL FIRE ALARM SYSTEM TESTING CERTIFICATE
THIS DOCUMENT CERTIFIES THAT THE FIRE ALARM SYSTEM AT THE FOLLOWING LOCATION;
ST. JOHN FISHER~ 44 MAIN STREET NORTH, FOREST
HAS BEEN TESTED & INSPECTED IN ACCORDANCE WITH THE STANDARD FOR THE INSPECTION AND TESTING
OF FIRE ALARM SYSTEMS, CAN/ULC-S536-04.
A TEST OF ALL EMERGENCY LIGHTING EQUIPMENT WAS ALSO COMPLETED IN ACCORDANCE WITH CANADIAN
ULC CODES AND DESIGN CRITERIA DESIGNATED BY MANUFACTURER'S SPECIFICATIONS.
YES NO N/A
E The fire alarm system documentation is on site and includes a description of the system √
G The fire alarm system has deficiencies noted on the attached pages √
H Comments:
The information on this form (and the documents attached here-to) attest to the fact that the equipment listed here-in was tested/inspected in
conformance with applicable codes, bylaws, standards, and the manufacturer's requirements by a qualified technician. The equipment was
left in an operational condition except as noted in the spaces marked "comments". A copy should be maintained on the premises for
examination by the Fire Marshall or Inspector at their request.
Technician #1 Technician #2
YES NO NA
Power 'ON' visual indicator √
Common visual trouble signal √
Common audible trouble signal √
Trouble signal silence switch √
Main power supply failure trouble signal operates √
Ground fault tested on positive and negative trouble signal √
Alert signal operation √
Alarm signal operation √
Automatic transfer from alert signal to alarm signal √
Manual transfer from alert signal to alarm signal cancel (acknowledge) feature operates on a two-stage system √
Automatic transfer from alert signal to alarm signal cancel (acknowledge) feature operates on a two-stage system √
Alarm signal silence inhibit function operates √
Alarm signal manual silence operational √
Alarm signal silence visual indication operates √
Alarm signals, when silenced automatically reinitiate upon subsequent alarm √
Alarm signal silence automatic cut-out timer Time: √
Audible and visual alert signals and alarm signals programmed and operate per design and specification; or documentation as detailed
in Appendix C - Description of Fire Alarm System for Inspection and Test Procedures √
Input circuit, alarm and supervisory operation, including audible and visual indication operates √
Input circuit supervision fault causes a trouble indication √
Output circuit alarm indicates operational √
Output circuit supervision fault causes a trouble indication √
Visual indicator test (lamp test) √
Coded Signal sequences operate not less than the required number of times and the correct alarm signal operates thereafter √
Coded signal sequences are not interrupted by subsequent alarm √
Ancillary device by-pass will result in a trouble signal √
Input circuit to output circuit operation, including ancillary device circuits, for correct program operation, as per design and
specification, or documentation as detailed in Appendix C - Description of Fire Alarm System for Inspection and Testing Procedures √
Fire alarm system reset operation √
Main power supply to emergency power supply transfer operates √
Status change confirmation (smoke detectors only) verified [Refer Subsection 5.7.4.3, Status Change Confirmation (Alarm Verification
Feature)] √
Receipt of alarm transmission to the fire signal receiving centre √
Receipt of the supervisory transmission to the fire signal receiving centre √
Receipt of the trouble transmission to the fire signal receiving centre √
Operation of the fire signal receiving centre disconnect means results in a specific trouble at the control unit or transponder and
transmits a trouble to the fire signal receiving centre √
Record the name and telephone number of the fire signal receiving centre √
Name DAMAR- 883334 Black Knights
Phone Number (800) 265-7562
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
YES NO N/A
Output circuits for selective voice paging, including visual indication operates √
Output circuits for selective voice paging trouble operation, including visual indication operates √
Operation of voice paging does not interfere with entitled inhibit time of alert signal and alarm signal √
Circuits for emergency telephone call in operation, including audible and visual indication operates √
Circuits for emergency telephone for operation, including two-way voice communication operates √
YES NO N/A
EMERGENCY POWER SUPPLY TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.3, 5.3.2, 5.33]
YES NO N/A
Correct battery rating as determined by battery calculations based on full system load √
Adequately ventilated √
Generator provides power to the AC circuit serving the fire alarm system. √
Trouble condition at the emergency generator results in an audible common trouble signal and a visual indication at the required
annunciator. √
Battery voltage not less than 85% of its rated capacity after tests completed √
Battery manufacturer and part number (2) Leoch 12V18
Battery manufacturer's date code or ins service date Date 2014
Battery Voltage (main power supply 'ON') is Voltage 27.20
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 25.30
in supervisory condition Current (A) 0.325
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 25.00
in full load condition Current (A) 2.20
The charging current is Current (mA) 900
YES NO N/A
(i) Required supervisory load for 24 h followed by the required full load operation; √
(ii) Silent test using load resistor method for full duration test. √
(v) Replace the batteries with a new set having a current date code/capacity/type √
Record battery capacity AH 18
Record the battery terminal voltage after tests are completed. VDC 26.80
ANNUNCIATOR AND REMOTE TROUBLE SIGNAL UNIT TEST & INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.1]
YES NO N/A
Individual alarm and supervisory input zone clearly indicated and separately designated √
Individual alarm and supervisory input zone designation labels are properly identified √
YES NO N/A
Minimum of one alarm zone and one supervisory zone tested per annunciator or sequential display to confirm operation √
Individual alarm and supervisory input zone designation labels are properly identified. √
REMOTE TROUBLE SIGNAL UNIT TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.3]
YES NO N/A
YES NO N/A
Operates as per design and specification, or in accordance with documentation provided in Appendix E. √
DATA COMMUNICATION LINK TEST [Ref. CAN/ULC-S536-04, Clauses 5.1.5, 5.6 Note]
YES NO N/A
Confirm that a trouble signal is received at the control unit or transponder under an open loop fault for each data communication
link (DCL) √
Where fault isolation modules are installed in data communication links serving field devices, wiring shorted on the isolated side,
annunciation of the fault confirmed, and then a device on the source side operated, and activation confirmed at the control unit or √
Where fault isolation in data communication links is provided between control units or transponders and between transponders,
introduce a short circuit fault and confirm annunciation of the fault and operation outside the shorted section between each pair of: √
YES NO N/A
Door Holders (x 2) √
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: September 1st, 2016
Building Name: St. Joseph Address: 43 St. Clair Street, Tilbury Page 1 of 5
Hall By 140 S √ √ 3
Hall at A RHT √ √ 3
Hall By 129 S √ √ 3
Room 129 A H √ √ 3
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: September 1st, 2016
Building Name: St. Joseph Address: 43 St. Clair Street, Tilbury Page 2 of 5
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: September 1st, 2016
Building Name: St. Joseph Address: 43 St. Clair Street, Tilbury Page 3 of 5
Room 136 S √ √ 1
Hall By 136 M √ √ 1
Exit By Gym M √ √ 1
Exit By 140 M √ √ 1
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: September 1st, 2016
Building Name: St. Joseph Address: 43 St. Clair Street, Tilbury Page 4 of 5
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: September 1st, 2016
Building Name: St. Joseph Address: 43 St. Clair Street, Tilbury Page 5 of 5
CAN/ULC
EMERGENCY LIGHTING
INDIVIDUAL DEVICE RECORD
Date: September 1st, 2016
REPAIRS
# LOCATION DEVICE REPAIR COMPLETED
Fire Alarm Devices
1 Staff Room Closet 132 A RHT Replaced Device w/ (1) 5601A Heat Detector 09/01/2016
Emergency Lighting
1 Hall By Room 140 RGC 442 MT 9W Replaced Battery w/ (1) Panasonic PA-6V7.2 09/01/2016
2 Hall By Room 129 RGC 442 MT 9W Replaced Battery w/ (1) Panasonic PA-6V7.2 09/01/2016
3 Hall by Room 122 3 LER Replaced Battery w/ (1) Panasonic PA-6V7.2 09/01/2016
4 Hall by Exit #3 3 LER Replaced Battery w/ (1) Panasonic PA-6V7.2 09/01/2016
5 Hall by Room 119 Storage RGC442 MT 9W Replaced Battery w/ (1) Panasonic PA-6V7.2 09/01/2016
6 Hall by Room 113 RGC 442 MT 9W Replaced Battery w/ (1) Panasonic PA-6V7.2 09/01/2016
7 Hall by 107 Photocopy Rm RGC 442 MT 9W Replaced Battery w/ (1) Panasonic PA-6V7.2 09/01/2016
8 Hall by Exit #5 3 LER Replaced Battery w/ (1) Panasonic PA-6V7.2 09/01/2016
9 Hall by 100 Office 3 LER Replaced Battery w/ (1) Panasonic PA-6V7.2 09/01/2016
10 Library Exit 3 LER Replaced Battery w/ (1) Panasonic PA-6V7.2 09/01/2016
11 Library Exit to Hall 3 LER Replaced Battery w/ (1) Panasonic PA-6V7.2 09/01/2016
12 Hall by Room 136 3 LER Replaced Battery w/ (1) Panasonic PA-6V7.2 09/01/2016
13 Hall at Exit # 6 3 LER Replaced Battery w/ (1) Panasonic PA-6V7.2 09/01/2016
14 Hall by Exit # 6 RGC 442 MT 9W Replaced Battery w/ (1) Panasonic PA-6V7.2 09/01/2016
15 Gym Exit to Hall 3 LER Replaced Battery w/ (1) Panasonic PA-6V7.2 09/01/2016
16 Gym NW Exit 3 LER Replaced Battery w/ (1) Panasonic PA-6V7.2 09/01/2016
17 Gym NE Exit 3 LER Replaced Battery w/ (1) Panasonic PA-6V7.2 09/01/2016
Additional Comments:
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
DEVICE LEGEND
DEVICE DESCRIPTION
ANN Annunciator
AD Ancillary Device (Note 4)
B Bell
BZ Buzzer
C Chime
CR Control Relay
CT1 Single Input Module (for supervised Class B signal or audio circuits)
CT2 Double Input Module (for supervised Class B signal or audio circuits)
DH Door Hold Open Device
DS Duct Smoke Detector
ET Emergency Telephone
FACP Fire Alarm Control Panel
FH Firefighters Handset
FS Sprinkler Flow Switch
GA 2nd Stage of 2-Stage Pull Station
H Horn
H/S Horn Strobe
HSP Horn Loudspeaker
HT Heat Detector, Fixed Temperature
HT-RES Resetable Heat Detector
K Horn, Klaxon Type
M Manual Pull Station
MAG LOCK Magnetic Door Lock
PS Pressure Switch
RHT Heat Detector, Rate-of-Rise
S Smoke Detector
SA Smoke Alarm, Single Station Type (Note 3)
SP Loudspeaker
SS Sprinkler Supervisory Switch
SV Sprinkler Valve
TS Sprinkler Tamper Switch (Note 2)
V Visual Alarm Appliance
Note 1: Confirmation of wiring supervision to each individual device is only required during installation verification or a complete building audit
of the system and is not required on the annual test.
Note 2: Sprinkler tamper switches cause trouble condition to be annunciated but not an alarm condition.
Note 3: Single station smoke alarms are not part of the fire alarm system but testing of such devices may be required by the authority
having jurisdiction.
Note 4: Identify the specific ancillary devices in the Remark column of Fire Alarm System Device Test and Inspection Record form
ANNUAL FIRE ALARM SYSTEM TESTING CERTIFICATE
THIS DOCUMENT CERTIFIES THAT THE FIRE ALARM SYSTEM AT THE FOLLOWING LOCATION;
SAINT JOSEPH, 43 ST. CLAIR STREET, TILBURY
HAS BEEN TESTED & INSPECTED IN ACCORDANCE WITH THE STANDARD FOR THE INSPECTION AND TESTING
OF FIRE ALARM SYSTEMS, CAN/ULC-S536-04.
A TEST OF ALL EMERGENCY LIGHTING EQUIPMENT WAS ALSO COMPLETED IN ACCORDANCE WITH CANADIAN
ULC CODES AND DESIGN CRITERIA DESIGNATED BY MANUFACTURER'S SPECIFICATIONS.
YES NO N/A
E The fire alarm system documentation is on site and includes a description of the system √
G The fire alarm system has deficiencies noted on the attached pages √
H Comments:
The information on this form (and the documents attached here-to) attest to the fact that the equipment listed here-in was tested/inspected in
conformance with applicable codes, bylaws, standards, and the manufacturer's requirements by a qualified technician. The equipment was
left in an operational condition except as noted in the spaces marked "comments". A copy should be maintained on the premises for
examination by the Fire Marshall or Inspector at their request.
Technician #1 Technician #2
YES NO NA
Power 'ON' visual indicator √
Common visual trouble signal √
Common audible trouble signal √
Trouble signal silence switch √
Main power supply failure trouble signal operates √
Ground fault tested on positive and negative trouble signal √
Alert signal operation √
Alarm signal operation √
Automatic transfer from alert signal to alarm signal √
Manual transfer from alert signal to alarm signal cancel (acknowledge) feature operates on a two-stage system √
Automatic transfer from alert signal to alarm signal cancel (acknowledge) feature operates on a two-stage system √
Alarm signal silence inhibit function operates √
Alarm signal manual silence operational √
Alarm signal silence visual indication operates √
Alarm signals, when silenced automatically reinitiate upon subsequent alarm √
Alarm signal silence automatic cut-out timer Time: √
Audible and visual alert signals and alarm signals programmed and operate per design and specification; or documentation as detailed
in Appendix C - Description of Fire Alarm System for Inspection and Test Procedures √
Input circuit, alarm and supervisory operation, including audible and visual indication operates √
Input circuit supervision fault causes a trouble indication √
Output circuit alarm indicates operational √
Output circuit supervision fault causes a trouble indication √
Visual indicator test (lamp test) √
Coded Signal sequences operate not less than the required number of times and the correct alarm signal operates thereafter √
Coded signal sequences are not interrupted by subsequent alarm √
Ancillary device by-pass will result in a trouble signal √
Input circuit to output circuit operation, including ancillary device circuits, for correct program operation, as per design and specification,
or documentation as detailed in Appendix C - Description of Fire Alarm System for Inspection and Testing Procedures √
Fire alarm system reset operation √
Main power supply to emergency power supply transfer operates √
Status change confirmation (smoke detectors only) verified [Refer Subsection 5.7.4.3, Status Change Confirmation (Alarm Verification
Feature)] √
Receipt of alarm transmission to the fire signal receiving centre √
Receipt of the supervisory transmission to the fire signal receiving centre √
Receipt of the trouble transmission to the fire signal receiving centre √
Operation of the fire signal receiving centre disconnect means results in a specific trouble at the control unit or transponder and
transmits a trouble to the fire signal receiving centre
√
Record the name and telephone number of the fire signal receiving centre √
Name DAMAR- 114625 Meteors
Phone Number 1 (800) 265-7562
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
YES NO N/A
Output circuits for selective voice paging, including visual indication operates √
Output circuits for selective voice paging trouble operation, including visual indication operates √
Operation of voice paging does not interfere with entitled inhibit time of alert signal and alarm signal √
Circuits for emergency telephone call in operation, including audible and visual indication operates √
Circuits for emergency telephone for operation, including two-way voice communication operates √
YES NO N/A
EMERGENCY POWER SUPPLY TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.3, 5.3.2, 5.33]
YES NO N/A
Correct battery rating as determined by battery calculations based on full system load √
Adequately ventilated √
Generator provides power to the AC circuit serving the fire alarm system. √
Trouble condition at the emergency generator results in an audible common trouble signal and a visual indication at the required
annunciator.
√
Battery voltage not less than 85% of its rated capacity after tests completed √
Battery manufacturer and part number FACP - Enersys NP18-12B BPS- Enersys NP7-12
Battery manufacturer's date code or ins service date Date 2013 2013
Battery Voltage (main power supply 'ON') is Voltage 27.20 26.40
Battery voltage and current with main power supply 'OFF' and fire alarm system in Voltage 25.60 25.70
supervisory condition Current (A) 0.296 0.048
Battery voltage and current with main power supply 'OFF' and fire alarm system in Voltage 25.30 24.40
full load condition Current (A) 0.44 3.143
The charging current is Current (mA) 471 597
(i) Required supervisory load for 24 h followed by the required full load operation; √
(ii) Silent test using load resistor method for full duration test. √
(v) Replace the batteries with a new set having a current date code/capacity/type √
Record battery capacity. AH 17.2 7
Record the battery terminal voltage after tests are completed. VDC 27.00 26.50
ANNUNCIATOR AND REMOTE TROUBLE SIGNAL UNIT TEST & INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.1]
YES NO N/A
Individual alarm and supervisory input zone clearly indicated and separately designated √
Individual alarm and supervisory input zone designation labels are properly identified √
YES NO N/A
Minimum of one alarm zone and one supervisory zone tested per annunciator or sequential display to confirm operation √
Individual alarm and supervisory input zone designation labels are properly identified. √
REMOTE TROUBLE SIGNAL UNIT TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.3]
YES NO N/A
YES NO N/A
Operates as per design and specification, or in accordance with documentation provided in Appendix E. √
DATA COMMUNICATION LINK TEST [Ref. CAN/ULC-S536-04, Clauses 5.1.5, 5.6 Note]
YES NO N/A
Confirm that a trouble signal is received at the control unit or transponder under an open loop fault for each data communication link
(DCL) √
Where fault isolation modules are installed in data communication links serving field devices, wiring shorted on the isolated side,
annunciation of the fault confirmed, and then a device on the source side operated, and activation confirmed at the control unit or √
Where fault isolation in data communication links is provided between control units or transponders and between transponders,
introduce a short circuit fault and confirm annunciation of the fault and operation outside the shorted section between each pair of: √
YES NO N/A
Fan Shutdown √
Door Holders √
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 8th, 2016
Address: 720 Elm Avenue, Sarnia Building Name: St. Matthews Page 1 of 3
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 8th, 2016
Address: 720 Elm Avenue, Sarnia Building Name: St. Matthews Page 2 of 3
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 8th, 2016
Address: 720 Elm Avenue, Sarnia Building Name: St. Matthews Page 3 of 3
CAN/ULC S536-04
FIRE ALARM- AUDIBLES
INDIVIDUAL DEVICE RECORD
Date: July 8th, 2016
Address: 720 Elm Avenue, Sarnia Building Name: St. Matthews Page 1 of 2
Stage H/S √ √
Office H/S √ √
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 8th, 2016
Address: 720 Elm Avenue, Sarnia Building Name: St. Matthews Page 2 of 2
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 8th, 2016
Address: 720 Elm Avenue, Sarnia Building Name: St. Matthews Page 1 of 3
Penthouse SV √ 1.3 √
Zone SV-2.1
Penthouse SV √ 2.1 √
Zone SV-3
Penthouse CT-1 √ 3 √ 147
Penthouse EOL √ 3 √
Penthouse SV √ 3 √
Zone FS 1.1
1st Floor Sprinkler Rm (105A) CT2 √ 1.1 √
Zone FS 1.2
1st Floor Sprinkler Rm (105A) CT2 √ 1.2 √
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 8th, 2016
Address: 720 Elm Avenue, Sarnia Building Name: St. Matthews Page 2 of 3
Zone SV 2
1st Floor Sprinkler Rm (105A) CT2 √ 2
Main Incoming #3 SV √ 2 √ 137
Zone SV 1.1
1st Floor Sprinkler Rm (105A) CT2 √ 1.1
East Wing SV √ 1.1 √ 139
Zone SV 1.2
1st Floor Sprinkler Rm (105A) CT2 √ 1.2
West Wing SV √ 1.2 √ 140
Zone FS 1.3
Penthouse CT2 √ 1.3
Penthouse FS √ √ 1.3 148
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 8th, 2016
Address: 720 Elm Avenue, Sarnia Building Name: St. Matthews Page 3 of 3
Isolators
In Storage 135 ISO √ 038
Control Relays
Daycare Kitchen CR √ 126
Learning/Resource CR √ 134
Office CR √ 135
In Penthouse CR √ 144
CAN/ULC
EMERGENCY LIGHTING
INDIVIDUAL DEVICE RECORD
Date: July 8th, 2016
Stroller Storage- Room 157 RG12S250 (4) PA-6V12 (15) 15 13.75 12:12 EB-2 Panel B CCT 42
Room 125B- off Room 125 RG12S250 (4) PA-6V12 (15) 20 13.91 12:14 EB-3 Panel C CCT 60
Room 135 Storage RG12S250 (4) PA-6V12 (15) 20 13.81 12:15 EB-4 Panel D CCT 10
Custodian- Room 115 RG12S250 (4) PA-6V12 (15) 20 13.97 12:10 EB-5 Panel E CCT 10
Mechanical Room- 2nd Floor RG12S250 (4) PA-6V12 (15) 8 13.86 12:13 M4 Panel
Coat Room # 140, Exit # 14 5LER4502MT9W (2) PA-6V12 (15) 4 13.87 12:09
Coat Room # 150, Exit # 15 5LER4502MT9W (2) PA-6V12 (15) 4 13.89 12:11
Room 106 By W/C RG125250 (4) PA-6V12 (15) 8 13.92 12:13 EB-6 Panel A CCT 3
REPAIRS
# LOCATION DEVICE REPAIR COMPLETED
Fire Alarm Devices
Repairs Not Required
Emergency Lighting
Repairs Not Required
Additional Comments:
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
DEVICE LEGEND
DEVICE DESCRIPTION
ANN Annunciator
AD Ancillary Device (Note 4)
B Bell
BZ Buzzer
C Chime
CR Control Relay
CT1 Single Input Module (for supervised Class B signal or audio circuits)
CT2 Double Input Module (for supervised Class B signal or audio circuits)
DH Door Hold Open Device
DS Duct Smoke Detector
ET Emergency Telephone
FACP Fire Alarm Control Panel
FH Firefighters Handset
FS Sprinkler Flow Switch
GA 2nd Stage of 2-Stage Pull Station
H Horn
H/S Horn Strobe
HSP Horn Loudspeaker
HT Heat Detector, Fixed Temperature
HT-RES Resetable Heat Detector
K Horn, Klaxon Type
M Manual Pull Station
MAG LOCK Magnetic Door Lock
PS Pressure Switch
RHT Heat Detector, Rate-of-Rise
S Smoke Detector
SA Smoke Alarm, Single Station Type (Note 3)
SP Loudspeaker
SS Sprinkler Supervisory Switch
SV Sprinkler Valve
TS Sprinkler Tamper Switch (Note 2)
V Visual Alarm Appliance
Note 1: Confirmation of wiring supervision to each individual device is only required during installation verification or a complete building audit
of the system and is not required on the annual test.
Note 2: Sprinkler tamper switches cause trouble condition to be annunciated but not an alarm condition.
Note 3: Single station smoke alarms are not part of the fire alarm system but testing of such devices may be required by the authority
having jurisdiction.
Note 4: Identify the specific ancillary devices in the Remark column of Fire Alarm System Device Test and Inspection Record form
183 Exeter Road, Unit A
London, Ontario
PHONE (519) 652-5086
FAX (519) 652-8719
1. GENERAL:
2. CONTROL VALVES:
3. WATER SUPPLIES:
a) Are siamese connections in good condition, couplings spin freely, caps in place and ball drips open? Yes
(Chrome)
Hydrant # 1:
i) The static pressure was? 70
j) The pitot reading from an engineered playpipe was 39 Using an outlet size of 2.5
k) The USGPM results are? 1048
6. WET SYSTEMS:
a) Are all sprinklers in good condition, free from obstruction, corrosion and loading? Yes
b) Are the sprinklers less than 50 years old? Yes
c) Are there spare sprinklers and a wrench in the head cabinet? Yes
d) Is the condition of the piping, drain valves, hangers and gauges in good condition? Yes
e) Have the sprinklers been checked for the proper temperature rating in various locations where possible? Yes
13. LISTED ARE RECENT CHANGES IN THE BUILDING OCCUPANCY OR FIRE PROTECTION EQUIPMENT:
NONE
NONE
NONE
The above items are deficient as per The Ontario Fire Code and need to be corrected immediately. A certificate of inspection
cannot be issued until all items under section #15 have been addressed. Consultation with the local fire prevention office is
suggested, if discrepancies occur
NONE
NOTE: This inspection/test was performed in accordance with The Ontario Fire Code. This inspection does NOT certify that the
sprinkler system installation complies with NFPA, OBC or Ontario Retrofit Reg. #627/92 (an engineer’s report would be required to
certify this).
• LIMITATION OF LIABILITY: It is understood and agreed that the INSPECTOR is NOT an insurer and is NOT warranting or
guaranteeing the adequacy, performance or life expectancy of any structure, item, component or system in the building.
Further, it is mutually agreed that the maximum amount of joint and several liability the INSPECTOR can incur for any error,
mistakes, omissions, breach of contract, breach of warrantee, negligent hiring, or any other theory of liability including violation
of a statute or consumer protection act is strictly limited to the FEE PAID for the inspection report.
THIS DOCUMENT CERTIFIES THAT THE FIRE ALARM SYSTEM AT THE FOLLOWING LOCATION;
SAINT MATTHEWS CATHOLIC SCHOOL, 720 ELM STREET, SARNIA
HAS BEEN TESTED & INSPECTED IN ACCORDANCE WITH THE STANDARD FOR THE INSPECTION AND TESTING OF
FIRE ALARM SYSTEMS, CAN/ULC-S536-04. THE SPRINKLER SYSTEM & FIRE HYDRANT HAVE ALSO BEEN INSPECTED
AT THIS LOCATION.
A TEST OF ALL EMERGENCY LIGHTING EQUIPMENT WAS ALSO COMPLETED IN ACCORDANCE WITH CANADIAN
ULC CODES AND DESIGN CRITERIA DESIGNATED BY MANUFACTURER'S SPECIFICATIONS.
YES NO N/A
E The fire alarm system documentation is on site and includes a description of the system √
G The fire alarm system has deficiencies noted on the attached pages √
H Comments:
I A copy of this report has been given to: Paul Lernout @ SCCDSB
The information on this form (and the documents attached here-to) attest to the fact that the equipment listed here-in was tested/inspected in
conformance with applicable codes, bylaws, standards, and the manufacturer's requirements by a qualified technician. The equipment was left in
an operational condition except as noted in the spaces marked "comments". A copy should be maintained on the premises for examination by the
Fire Marshall or Inspector at their request.
Technician #1 Technician #2
YES NO N/A
Output circuits for selective voice paging, including visual indication operates √
Output circuits for selective voice paging trouble operation, including visual indication operates √
Operation of voice paging does not interfere with entitled inhibit time of alert signal and alarm signal √
Circuits for emergency telephone call in operation, including audible and visual indication operates √
Circuits for emergency telephone for operation, including two-way voice communication operates √
YES NO N/A
EMERGENCY POWER SUPPLY TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.3, 5.3.2, 5.33]
YES NO N/A
Correct battery rating as determined by battery calculations based on full system load √
Adequately ventilated √
Generator provides power to the AC circuit serving the fire alarm system. √
Trouble condition at the emergency generator results in an audible common trouble signal and a visual indication at the required
annunciator. √
Battery voltage not less than 85% of its rated capacity after tests completed √
Battery manufacturer and part number (4) Panasonic LCR0612
Battery manufacturer's date code or ins service date Date 2013
Battery Voltage (main power supply 'ON') is Voltage 26.90
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 25.30
in supervisory condition Current (A) 0.170
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 25.00
in full load condition Current (A) 0.360
The charging current is Current (mA) 180
YES NO N/A
(i) Required supervisory load for 24 h followed by the required full load operation; √
(ii) Silent test using load resistor method for full duration test. √
(v) Replace the batteries with a new set having a current date code/capacity/type √
Record battery capacity AH 6
Record the battery terminal voltage after tests are completed. VDC 26.00
ANNUNCIATOR AND REMOTE TROUBLE SIGNAL UNIT TEST & INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.1]
YES NO N/A
Individual alarm and supervisory input zone clearly indicated and separately designated √
Individual alarm and supervisory input zone designation labels are properly identified √
YES NO N/A
Minimum of one alarm zone and one supervisory zone tested per annunciator or sequential display to confirm operation √
Individual alarm and supervisory input zone designation labels are properly identified. √
REMOTE TROUBLE SIGNAL UNIT TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.3]
YES NO N/A
YES NO N/A
Operates as per design and specification, or in accordance with documentation provided in Appendix E. √
DATA COMMUNICATION LINK TEST [Ref. CAN/ULC-S536-04, Clauses 5.1.5, 5.6 Note]
YES NO N/A
Confirm that a trouble signal is received at the control unit or transponder under an open loop fault for each data communication link
(DCL) √
Where fault isolation modules are installed in data communication links serving field devices, wiring shorted on the isolated side,
annunciation of the fault confirmed, and then a device on the source side operated, and activation confirmed at the control unit or √
Where fault isolation in data communication links is provided between control units or transponders and between transponders,
introduce a short circuit fault and confirm annunciation of the fault and operation outside the shorted section between each pair of: √
YES NO N/A
Door Holders √
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 16th, 2016
Building Name: St. Michael's Address: 1930 Wildwood Drive, Brights Grove
Page 1 of 3
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 16th, 2016
Building Name: St. Michael's Address: 1930 Wildwood Drive, Brights Grove
Page 2 of 3
124 Exit # 9 M √ √ 2
Exit By 947 M √ √ 6
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 16th, 2016
Building Name: St. Michael's Address: 1930 Wildwood Drive, Brights Grove
Page 3 of 3
Hall at 118 M √ √ 2
Hall at 118 S √ √ 2 RB
CAN/ULC
EMERGENCY LIGHTING
INDIVIDUAL DEVICE RECORD
Date: August , 2016
Building Name: St. Michael's Address: 1930 Wildwood Drive, Brights Grove
REPAIRS
# LOCATION DEVICE REPAIR COMPLETED
Fire Alarm Devices
1 100B at 100C Office Meeting RHT Replaced Device w/ (1) 5601A Heat Detector 08/16/2016
Emergency Lighting
1 By 908 RG 36 A – 4 Replaced Battery w/ (1) Panasonic PA-6V12 08/16/2016
2 In 929 off 927 (Girls Changeroom) RG 36 A – 3 Replaced Battery w/ (1) Panasonic PA-6V12 08/16/2016
3 By 926 (Gym Entrance) RG 36 A – 4 Replaced Battery w/ (1) Panasonic PA-6V12 08/16/2016
4 Gym Right by Exit 9 PXM 36 – 2 Replaced Battery w/ (1) Panasonic PA-6V7.2 08/16/2016
Additional Comments:
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
DEVICE LEGEND
DEVICE DESCRIPTION
ANN Annunciator
AD Ancillary Device (Note 4)
B Bell
BZ Buzzer
C Chime
CR Control Relay
CT1 Single Input Module (for supervised Class B signal or audio circuits)
CT2 Double Input Module (for supervised Class B signal or audio circuits)
DH Door Hold Open Device
DS Duct Smoke Detector
ET Emergency Telephone
FACP Fire Alarm Control Panel
FH Firefighters Handset
FS Sprinkler Flow Switch
GA 2nd Stage of 2-Stage Pull Station
H Horn
H/S Horn Strobe
HSP Horn Loudspeaker
HT Heat Detector, Fixed Temperature
HT-RES Resetable Heat Detector
K Horn, Klaxon Type
M Manual Pull Station
MAG LOCK Magnetic Door Lock
PS Pressure Switch
RHT Heat Detector, Rate-of-Rise
S Smoke Detector
SA Smoke Alarm, Single Station Type (Note 3)
SP Loudspeaker
SS Sprinkler Supervisory Switch
SV Sprinkler Valve
TS Sprinkler Tamper Switch (Note 2)
V Visual Alarm Appliance
Note 1: Confirmation of wiring supervision to each individual device is only required during installation verification or a complete building audit
of the system and is not required on the annual test.
Note 2: Sprinkler tamper switches cause trouble condition to be annunciated but not an alarm condition.
Note 3: Single station smoke alarms are not part of the fire alarm system but testing of such devices may be required by the authority
having jurisdiction.
Note 4: Identify the specific ancillary devices in the Remark column of Fire Alarm System Device Test and Inspection Record form
183 Exeter Road, Unit A
London, Ontario
PHONE (519) 652-5086
FAX (519) 652-8719
1. GENERAL:
2. WATER SUPPLIES:
3. FIRE HYDRANTS:
NONE
NONE
6. The following items are deficient as per The Ontario Fire Code and need to be corrected immediately:
NONE
The certificate of inspection cannot be issued until all items under section #6 have been completed.
NONE
LIMITATION OF LIABILITY: It is understood and agreed that the INSPECTOR is NOT an insurer and is NOT
warranting or guaranteeing the adequacy, performance or life expectancy of any structure, item,
component or system in the building. Further, it is mutually agreed that the maximum amount of joint and
several liability the INSPECTOR can incur for any error, mistakes, omissions, breach of contract, breach of
warrantee, negligent hiring, or any other theory of liability including violation of a statue or consumer
protection act is strictly limited to the FEE PAID for the inspection report.
NOTE: This inspection/test was performed in accordance with The Ontario Fire Code. This inspection does NOT
certify that the fire hydrant installation complies with NFPA, OBC or Ontario Retrofit Reg. #627/92 (an engineer’s
report would be required to certify this).
As per the requirements of The Ontario Fire Codes, the inspecting company must submit this report to the
local Fire Prevention office
THIS DOCUMENT CERTIFIES THAT THE FIRE ALARM SYSTEM AT THE FOLLOWING LOCATION;
ST. MICHAEL, 1930 WILDWOOD DRIVE, BRIGHTS GROVE
HAS BEEN TESTED & INSPECTED IN ACCORDANCE WITH THE STANDARD FOR THE INSPECTION AND TESTING
OF FIRE ALARM SYSTEMS, CAN/ULC-S536-04. THE FIRE HYDRANT AT THIS LOCATION WAS ALSO TESTED.
A TEST OF ALL EMERGENCY LIGHTING EQUIPMENT WAS COMPLETED IN ACCORDANCE WITH CANADIAN ULC
CODES AND DESIGN CRITERIA DESIGNATED BY MANUFACTURER'S SPECIFICATIONS.
YES NO N/A
E The fire alarm system documentation is on site and includes a description of the system √
G The fire alarm system has deficiencies noted on the attached pages √
H Comments:
The information on this form (and the documents attached here-to) attest to the fact that the equipment listed here-in was tested/inspected in
conformance with applicable codes, bylaws, standards, and the manufacturer's requirements by a qualified technician. The equipment was left in
an operational condition except as noted in the spaces marked "comments". A copy should be maintained on the premises for examination by
the Fire Marshall or Inspector at their request.
Technician #1 Technician #2
YES NO N/A
Output circuits for selective voice paging, including visual indication operates √
Output circuits for selective voice paging trouble operation, including visual indication operates √
Operation of voice paging does not interfere with entitled inhibit time of alert signal and alarm signal √
Circuits for emergency telephone call in operation, including audible and visual indication operates √
Circuits for emergency telephone for operation, including two-way voice communication operates √
YES NO N/A
EMERGENCY POWER SUPPLY TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.3, 5.3.2, 5.33]
YES NO N/A
Correct battery rating as determined by battery calculations based on full system load √
Adequately ventilated √
Generator provides power to the AC circuit serving the fire alarm system. √
Trouble condition at the emergency generator results in an audible common trouble signal and a visual indication at the required
annunciator. √
Battery voltage not less than 85% of its rated capacity after tests completed √
Battery manufacturer and part number Panasonic LCR0612P
Battery manufacturer's date code or ins service date Date 2013
Battery Voltage (main power supply 'ON') is Voltage 27.30
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 25.20
in supervisory condition Current (A) 0.303
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 24.90
in full load condition Current (A) 0.834
The charging current is Current (mA) 1351
YES NO N/A
(i) Required supervisory load for 24 h followed by the required full load operation; √
(ii) Silent test using load resistor method for full duration test. √
(v) Replace the batteries with a new set having a current date code/capacity/type √
Record battery capacity. AH 12
Record the battery terminal voltage after tests are completed. VDC 26.40
ANNUNCIATOR AND REMOTE TROUBLE SIGNAL UNIT TEST & INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.1]
YES NO N/A
Individual alarm and supervisory input zone clearly indicated and separately designated √
Individual alarm and supervisory input zone designation labels are properly identified √
YES NO N/A
Minimum of one alarm zone and one supervisory zone tested per annunciator or sequential display to confirm operation √
Individual alarm and supervisory input zone designation labels are properly identified. √
REMOTE TROUBLE SIGNAL UNIT TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.3]
YES NO N/A
YES NO N/A
Operates as per design and specification, or in accordance with documentation provided in Appendix E. √
DATA COMMUNICATION LINK TEST [Ref. CAN/ULC-S536-04, Clauses 5.1.5, 5.6 Note]
YES NO N/A
Confirm that a trouble signal is received at the control unit or transponder under an open loop fault for each data communication link
(DCL) √
Where fault isolation modules are installed in data communication links serving field devices, wiring shorted on the isolated side,
annunciation of the fault confirmed, and then a device on the source side operated, and activation confirmed at the control unit or √
Where fault isolation in data communication links is provided between control units or transponders and between transponders,
introduce a short circuit fault and confirm annunciation of the fault and operation outside the shorted section between each pair of: √
YES NO N/A
Door Holders √
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 29th, 2016
Building Name: St. Michael Address: 25 Maple Street South, Ridgetown Page 1 of 4
Hall by 14 B √ √ S-1
Hall by 14 S √ √ 2 1028
Room 14 B √ √ S-1
Room 22 (15) RHT √ √ 3 1010
In Library B √ √ S-1
Library Office 58 RHT √ √ 3 1009
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 29th, 2016
Building Name: St. Michael Address: 25 Maple Street South, Ridgetown Page 2 of 4
Gym B √ √ S-1
Stage 19 S √ √ 2 1033
Class 9 B √ √ S-1
Boys C/R Hall 17 S √ √ 2 1035
Room 8 B √ √ S-1
Corridor @ 8 B √ √ S-1
Staff Room RHT √ √ 3 1027
Room 5 B √ √ S-1
Hall @ 5 S √ √ 2 1038
Hall @ 5 B √ √ S-1
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 29th, 2016
Building Name: St. Michael Address: 25 Maple Street South, Ridgetown Page 3 of 4
Class 6 B √ √ S-1
Nurse Room RHT √ √ 3 1048
Class 5 B √ √ S-1
Custodian Room 42 RHT √ √ 3 1018
Hall @ 4 B √ √ S-1
Resource Room 40 RHT √ √ 3 1023
Hall @ 3 B √ √ S-1
Hall @ 3 S √ √ 2 1040
Class 4 B √ √ S-1
Class 3 B √ √ S-1
Supply Room RHT √ √ 3 1026
Class 2 B √ √ S-1
Hall @ 1 B √ √ S-1
Class 1 B √ √ S-1
Hall @ #1 S √ √ 2 1041
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 29th, 2016
Building Name: St. Michael Address: 25 Maple Street South, Ridgetown Page 4 of 4
Daycare B √ √ S-1
CAN/ULC
EMERGENCY LIGHTING
INDIVIDUAL DEVICE RECORD
Date: August 29th, 2016
REPAIRS
# LOCATION DEVICE REPAIR COMPLETED
Fire Alarm Devices
Repairs Not Required
Emergency Lighting
1 PortaPak Hall RG 36 Replaced Battery w/ (1) Panasonic PA-6V12 08/29/2016
2 Hall By Nurses Office RG 36 Replaced Batteries w/ (2) Panasonic PA-6V7.2 08/29/2016
Additional Comments:
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
DEVICE LEGEND
DEVICE DESCRIPTION
ANN Annunciator
AD Ancillary Device (Note 4)
B Bell
BZ Buzzer
C Chime
CR Control Relay
CT1 Single Input Module (for supervised Class B signal or audio circuits)
CT2 Double Input Module (for supervised Class B signal or audio circuits)
DH Door Hold Open Device
DS Duct Smoke Detector
ET Emergency Telephone
FACP Fire Alarm Control Panel
FH Firefighters Handset
FS Sprinkler Flow Switch
GA 2nd Stage of 2-Stage Pull Station
H Horn
H/S Horn Strobe
HSP Horn Loudspeaker
HT Heat Detector, Fixed Temperature
HT-RES Resetable Heat Detector
K Horn, Klaxon Type
M Manual Pull Station
MAG LOCK Magnetic Door Lock
PS Pressure Switch
RHT Heat Detector, Rate-of-Rise
S Smoke Detector
SA Smoke Alarm, Single Station Type (Note 3)
SP Loudspeaker
SS Sprinkler Supervisory Switch
SV Sprinkler Valve
TS Sprinkler Tamper Switch (Note 2)
V Visual Alarm Appliance
Note 1: Confirmation of wiring supervision to each individual device is only required during installation verification or a complete building audit
of the system and is not required on the annual test.
Note 2: Sprinkler tamper switches cause trouble condition to be annunciated but not an alarm condition.
Note 3: Single station smoke alarms are not part of the fire alarm system but testing of such devices may be required by the authority
having jurisdiction.
Note 4: Identify the specific ancillary devices in the Remark column of Fire Alarm System Device Test and Inspection Record form
ANNUAL FIRE ALARM SYSTEM TESTING CERTIFICATE
THIS DOCUMENT CERTIFIES THAT THE FIRE ALARM SYSTEM AT THE FOLLOWING LOCATION;
ST. MICHAELS, 25 MAPLE ROAD SOUTH, RIDGETOWN
HAS BEEN TESTED & INSPECTED IN ACCORDANCE WITH THE STANDARD FOR THE INSPECTION AND TESTING
OF FIRE ALARM SYSTEMS, CAN/ULC-S536-04.
A TEST OF ALL EMERGENCY LIGHTING EQUIPMENT WAS ALSO COMPLETED IN ACCORDANCE WITH CANADIAN
ULC CODES AND DESIGN CRITERIA DESIGNATED BY MANUFACTURER'S SPECIFICATIONS.
YES NO N/A
E The fire alarm system documentation is on site and includes a description of the system √
G The fire alarm system has deficiencies noted on the attached pages √
H Comments:
I A copy of this report has been given to: SCCDSB- Paul Lernout
The information on this form (and the documents attached here-to) attest to the fact that the equipment listed here-in was tested/inspected in
conformance with applicable codes, bylaws, standards, and the manufacturer's requirements by a qualified technician. The equipment was left in
an operational condition except as noted in the spaces marked "comments". A copy should be maintained on the premises for examination by
the Fire Marshall or Inspector at their request.
Technician #1 Technician #2
Signature:______________________ Signature:______________________
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
YES NO NA
Power 'ON' visual indicator √
Common visual trouble signal √
Common audible trouble signal √
Trouble signal silence switch √
Main power supply failure trouble signal operates √
Ground fault tested on positive and negative trouble signal √
Alert signal operation √
Alarm signal operation √
Automatic transfer from alert signal to alarm signal √
Manual transfer from alert signal to alarm signal cancel (acknowledge) feature operates on a two-stage system √
Automatic transfer from alert signal to alarm signal cancel (acknowledge) feature operates on a two-stage system √
Alarm signal silence inhibit function operates √
Alarm signal manual silence operational √
Alarm signal silence visual indication operates √
Alarm signals, when silenced automatically reinitiate upon subsequent alarm √
Alarm signal silence automatic cut-out timer Time: √
Audible and visual alert signals and alarm signals programmed and operate per design and specification; or documentation as detailed
in Appendix C - Description of Fire Alarm System for Inspection and Test Procedures √
Input circuit, alarm and supervisory operation, including audible and visual indication operates √
Input circuit supervision fault causes a trouble indication √
Output circuit alarm indicates operational √
Output circuit supervision fault causes a trouble indication √
Visual indicator test (lamp test) √
Coded Signal sequences operate not less than the required number of times and the correct alarm signal operates thereafter √
Coded signal sequences are not interrupted by subsequent alarm √
Ancillary device by-pass will result in a trouble signal √
Input circuit to output circuit operation, including ancillary device circuits, for correct program operation, as per design and
specification, or documentation as detailed in Appendix C - Description of Fire Alarm System for Inspection and Testing Procedures √
Fire alarm system reset operation √
Main power supply to emergency power supply transfer operates √
Status change confirmation (smoke detectors only) verified [Refer Subsection 5.7.4.3, Status Change Confirmation (Alarm Verification
Feature)] √
Receipt of alarm transmission to the fire signal receiving centre √
Receipt of the supervisory transmission to the fire signal receiving centre √
Receipt of the trouble transmission to the fire signal receiving centre √
Operation of the fire signal receiving centre disconnect means results in a specific trouble at the control unit or transponder and
transmits a trouble to the fire signal receiving centre
√
Record the name and telephone number of the fire signal receiving centre √
Name DAMAR- 114661 Cougars
Phone Number (800) 265-7562
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
YES NO N/A
Output circuits for selective voice paging, including visual indication operates √
Output circuits for selective voice paging trouble operation, including visual indication operates √
Operation of voice paging does not interfere with entitled inhibit time of alert signal and alarm signal √
Circuits for emergency telephone call in operation, including audible and visual indication operates √
Circuits for emergency telephone for operation, including two-way voice communication operates √
YES NO N/A
EMERGENCY POWER SUPPLY TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.3, 5.3.2, 5.33]
YES NO N/A
Correct battery rating as determined by battery calculations based on full system load √
Adequately ventilated √
Generator provides power to the AC circuit serving the fire alarm system. √
Trouble condition at the emergency generator results in an audible common trouble signal and a visual indication at the required
annunciator. √
Battery voltage not less than 85% of its rated capacity after tests completed √
Battery manufacturer and part number (2) 12V7.2
Battery manufacturer's date code or ins service date Date 2013
Battery Voltage (main power supply 'ON') is Voltage 26.80
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 25.30
in supervisory condition Current (A) 0.130
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 25.20
in full load condition Current (A) 0.490
The charging current is Current (mA) 1.20
(i) Required supervisory load for 24 h followed by the required full load operation; √
(ii) Silent test using load resistor method for full duration test. √
(v) Replace the batteries with a new set having a current date code/capacity/type. √
Record battery capacity . AH 7.2
Record the battery terminal voltage after tests are completed. VDC 25.48
ANNUNCIATOR AND REMOTE TROUBLE SIGNAL UNIT TEST & INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.1]
YES NO N/A
Individual alarm and supervisory input zone clearly indicated and separately designated √
Individual alarm and supervisory input zone designation labels are properly identified √
YES NO N/A
Minimum of one alarm zone and one supervisory zone tested per annunciator or sequential display to confirm operation √
Individual alarm and supervisory input zone designation labels are properly identified. √
REMOTE TROUBLE SIGNAL UNIT TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.3]
YES NO N/A
YES NO N/A
Operates as per design and specification, or in accordance with documentation provided in Appendix E. √
DATA COMMUNICATION LINK TEST [Ref. CAN/ULC-S536-04, Clauses 5.1.5, 5.6 Note]
YES NO N/A
Confirm that a trouble signal is received at the control unit or transponder under an open loop fault for each data communication link
(DCL) √
Where fault isolation modules are installed in data communication links serving field devices, wiring shorted on the isolated side,
annunciation of the fault confirmed, and then a device on the source side operated, and activation confirmed at the control unit or √
Where fault isolation in data communication links is provided between control units or transponders and between transponders,
introduce a short circuit fault and confirm annunciation of the fault and operation outside the shorted section between each pair of: √
YES NO N/A
Door Holders √
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 11th, 2016
Building Name: St. Peter Canisius Address: 424 Victoria Street, Watford Page 1 of 3
By 127 H √ √ NAC-1
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 11th, 2016
Building Name: St. Peter Canisius Address: 424 Victoria Street, Watford Page 2 of 3
Exit By 129 M √ √ 2
Hall By 131 S (1400A) √ √ 2
By 109 H √ √ NAC-1
By 101 S (4098-9601) √ √ 1
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 11th, 2016
Building Name: St. Peter Canisius Address: 424 Victoria Street, Watford Page 3 of 3
Hall @ 207 DH √ √
Hall @ 207 DH √ √
Hall @ Gym DH √ √
Hall @ Gym DH √ √
Hall @ Office DH √ √
Hall @ Office DH √ √
Newer Section
In Room 101 EXP-HT √ √ 1 Elect. Tested
By 135 S (4098-9601) √ √ 2
CAN/ULC
EMERGENCY LIGHTING
INDIVIDUAL DEVICE RECORD
Date: July 11th, 2016
Building Name: St. Peter Canisius Address: 424 Victoria Street, Watford
Exit By 129 PXM 36 PA-6V7.2 (08) 2 3.50 10:12 0.21 X See Reps List
By 130 SPEXX10361 (2) 6V4.5 (13) 2 13.71 10:13 0.26
Room 135 Exit SPEXX10361 (2) PA-6V4.5 (13) 2 13.82 10:14 0.25 X See Reps List
Room 100C SLA 1272 12V33 (13) 8 13.57 10:15 0.33
REPAIRS
# LOCATION DEVICE REPAIR COMPLETED
Emergency Lighting
1 By 117 PXM 36 Replaced battery w/ (1) Panasonic PA-6V7.2 07/11/2016
2 Exit By 129 PXM 36 Replaced battery w/ (1) Panasonic PA-6V7.2 07/11/2016
3 Room 135 Exit SPEXX10361 Replaced battery w/ (2) Panasonic PA-6V4.5 07/11/2016
Additional Comments:
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
DEVICE LEGEND
DEVICE DESCRIPTION
ANN Annunciator
AD Ancillary Device (Note 4)
B Bell
BZ Buzzer
C Chime
CR Control Relay
CT1 Single Input Module (for supervised Class B signal or audio circuits)
CT2 Double Input Module (for supervised Class B signal or audio circuits)
DH Door Hold Open Device
DS Duct Smoke Detector
ET Emergency Telephone
FACP Fire Alarm Control Panel
FH Firefighters Handset
FS Sprinkler Flow Switch
GA 2nd Stage of 2-Stage Pull Station
H Horn
H/S Horn Strobe
HSP Horn Loudspeaker
HT Heat Detector, Fixed Temperature
HT-RES Resetable Heat Detector
K Horn, Klaxon Type
M Manual Pull Station
MAG LOCK Magnetic Door Lock
PS Pressure Switch
RHT Heat Detector, Rate-of-Rise
S Smoke Detector
SA Smoke Alarm, Single Station Type (Note 3)
SP Loudspeaker
SS Sprinkler Supervisory Switch
SV Sprinkler Valve
TS Sprinkler Tamper Switch (Note 2)
V Visual Alarm Appliance
Note 1: Confirmation of wiring supervision to each individual device is only required during installation verification or a complete building audit
of the system and is not required on the annual test.
Note 2: Sprinkler tamper switches cause trouble condition to be annunciated but not an alarm condition.
Note 3: Single station smoke alarms are not part of the fire alarm system but testing of such devices may be required by the authority
having jurisdiction.
Note 4: Identify the specific ancillary devices in the Remark column of Fire Alarm System Device Test and Inspection Record form
ANNUAL FIRE ALARM SYSTEM TESTING CERTIFICATE
THIS DOCUMENT CERTIFIES THAT THE FIRE ALARM SYSTEM AT THE FOLLOWING LOCATION;
ST. PETER CANISIUS, 424 VICTORIA STREET, WATFORD
HAS BEEN TESTED & INSPECTED IN ACCORDANCE WITH THE STANDARD FOR THE INSPECTION AND TESTING
OF FIRE ALARM SYSTEMS, CAN/ULC-S536-04.
A TEST OF ALL EMERGENCY LIGHTING EQUIPMENT WAS ALSO COMPLETED IN ACCORDANCE WITH CANADIAN
ULC CODES AND DESIGN CRITERIA DESIGNATED BY MANUFACTURER'S SPECIFICATIONS.
YES NO N/A
E The fire alarm system documentation is on site and includes a description of the system √
G The fire alarm system has deficiencies noted on the attached pages √
H Comments:
I A copy of this report has been given to: Paul Lernout - SCCDSB
The information on this form (and the documents attached here-to) attest to the fact that the equipment listed here-in was tested/inspected in
conformance with applicable codes, bylaws, standards, and the manufacturer's requirements by a qualified technician. The equipment was left in
an operational condition except as noted in the spaces marked "comments". A copy should be maintained on the premises for examination by
the Fire Marshall or Inspector at their request.
Technician #1 Technician #2
Signature:______________________ Signature:______________________
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
YES NO NA
Power 'ON' visual indicator √
Common visual trouble signal √
Common audible trouble signal √
Trouble signal silence switch √
Main power supply failure trouble signal operates √
Ground fault tested on positive and negative trouble signal √
Alert signal operation √
Alarm signal operation √
Automatic transfer from alert signal to alarm signal √
Manual transfer from alert signal to alarm signal cancel (acknowledge) feature operates on a two-stage system √
Automatic transfer from alert signal to alarm signal cancel (acknowledge) feature operates on a two-stage system √
Alarm signal silence inhibit function operates √
Alarm signal manual silence operational √
Alarm signal silence visual indication operates √
Alarm signals, when silenced automatically reinitiate upon subsequent alarm √
Alarm signal silence automatic cut-out timer Time: √
Audible and visual alert signals and alarm signals programmed and operate per design and specification; or documentation as detailed
in Appendix C - Description of Fire Alarm System for Inspection and Test Procedures
√
Input circuit, alarm and supervisory operation, including audible and visual indication operates √
Input circuit supervision fault causes a trouble indication √
Output circuit alarm indicates operational √
Output circuit supervision fault causes a trouble indication √
Visual indicator test (lamp test) √
Coded Signal sequences operate not less than the required number of times and the correct alarm signal operates thereafter √
Coded signal sequences are not interrupted by subsequent alarm √
Ancillary device by-pass will result in a trouble signal √
Input circuit to output circuit operation, including ancillary device circuits, for correct program operation, as per design and specification,
or documentation as detailed in Appendix C - Description of Fire Alarm System for Inspection and Testing Procedures
√
Fire alarm system reset operation √
Main power supply to emergency power supply transfer operates √
Status change confirmation (smoke detectors only) verified [Refer Subsection 5.7.4.3, Status Change Confirmation (Alarm Verification
Feature)]
√
Receipt of alarm transmission to the fire signal receiving centre √
Receipt of the supervisory transmission to the fire signal receiving centre √
Receipt of the trouble transmission to the fire signal receiving centre √
Operation of the fire signal receiving centre disconnect means results in a specific trouble at the control unit or transponder and
√
transmits a trouble to the fire signal receiving centre
Record the name and telephone number of the fire signal receiving centre √
Name DAMAR- 114663 Vikings
Phone Number (800) 265-7562
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
YES NO N/A
Output circuits for selective voice paging, including visual indication operates √
Output circuits for selective voice paging trouble operation, including visual indication operates √
Operation of voice paging does not interfere with entitled inhibit time of alert signal and alarm signal √
Circuits for emergency telephone call in operation, including audible and visual indication operates √
Circuits for emergency telephone for operation, including two-way voice communication operates √
YES NO N/A
YES NO N/A
EMERGENCY POWER SUPPLY TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.3, 5.3.2, 5.33]
YES NO N/A
Correct battery rating as determined by battery calculations based on full system load √
Adequately ventilated √
Generator provides power to the AC circuit serving the fire alarm system. √
Trouble condition at the emergency generator results in an audible common trouble signal and a visual indication at the required
annunciator. √
Battery voltage not less than 85% of its rated capacity after tests completed √
Battery manufacturer and part number (2) Enersys NP7-12
Battery manufacturer's date code or ins service date Date 2012
Battery Voltage (main power supply 'ON') is Voltage 27.66
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 25.80
in supervisory condition Current (A) 0.120
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 25.25
in full load condition Current (A) 0.43
The charging current is Current (mA) 0.84
YES NO N/A
(i) Required supervisory load for 24 h followed by the required full load operation; √
(ii) Silent test using load resistor method for full duration test. (Refer to Appendix F1); √
(v) Replace the batteries with a new set having a current date code/capacity/type √
Record battery capacity (refer to Appendix D3.1-C). AH 7
Record the battery terminal voltage after tests are completed. VDC 27.30
ANNUNCIATOR AND REMOTE TROUBLE SIGNAL UNIT TEST & INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.1]
YES NO N/A
Individual alarm and supervisory input zone clearly indicated and separately designated √
Individual alarm and supervisory input zone designation labels are properly identified √
YES NO N/A
Minimum of one alarm zone and one supervisory zone tested per annunciator or sequential display to confirm operation √
Individual alarm and supervisory input zone designation labels are properly identified. √
REMOTE TROUBLE SIGNAL UNIT TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.3]
YES NO N/A
YES NO N/A
Operates as per design and specification, or in accordance with documentation provided in Appendix E. √
DATA COMMUNICATION LINK TEST [Ref. CAN/ULC-S536-04, Clauses 5.1.5, 5.6 Note]
YES NO N/A
Confirm that a trouble signal is received at the control unit or transponder under an open loop fault for each data communication link
(DCL) √
Where fault isolation modules are installed in data communication links serving field devices, wiring shorted on the isolated side,
annunciation of the fault confirmed, and then a device on the source side operated, and activation confirmed at the control unit or √
Where fault isolation in data communication links is provided between control units or transponders and between transponders, introduce
a short circuit fault and confirm annunciation of the fault and operation outside the shorted section between each pair of: √
YES NO N/A
Fan Shutdown √
Door Holders √
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 11th, 2016
Building Name: St. Philip Address: 420 Queen Street, Petrolia Page 1 of 3
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 11th, 2016
Building Name: St. Philip Address: 420 Queen Street, Petrolia Page 2 of 3
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 11th, 2016
Building Name: St. Philip Address: 420 Queen Street, Petrolia Page 3 of 3
By 127A M √ √ 4
Girls Change Room RHT √ √ 4
Boys Change Room RHT √ √ 4
Gym H √ √ S-2
Gym Exit M √ √ 4
Gym Storage # 2 M √ √ 4
Class 8110D S (1400A) √ √ 4 1.59
CAN/ULC
EMERGENCY LIGHTING
INDIVIDUAL DEVICE RECORD
Date: July 11th, 2016
REPAIRS
# LOCATION DEVICE REPAIR COMPLETED
Fire Alarm Devices
Repairs not Required
Emergency Lighting
1 Gym Storage RG 12S 360 Replaced battery w/(1) Enersys 12V33 07/11/2016
2 117A RG 12S 144 Replaced battery w/(1) Panasonic 6V12 07/11/2016
Additional Comments:
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
DEVICE LEGEND
DEVICE DESCRIPTION
ANN Annunciator
AD Ancillary Device (Note 4)
B Bell
BZ Buzzer
C Chime
CR Control Relay
CT1 Single Input Module (for supervised Class B signal or audio circuits)
CT2 Double Input Module (for supervised Class B signal or audio circuits)
DH Door Hold Open Device
DS Duct Smoke Detector
ET Emergency Telephone
FACP Fire Alarm Control Panel
FH Firefighters Handset
FS Sprinkler Flow Switch
GA 2nd Stage of 2-Stage Pull Station
H Horn
H/S Horn Strobe
HSP Horn Loudspeaker
HT Heat Detector, Fixed Temperature
HT-RES Resetable Heat Detector
K Horn, Klaxon Type
M Manual Pull Station
MAG LOCK Magnetic Door Lock
PS Pressure Switch
RHT Heat Detector, Rate-of-Rise
S Smoke Detector
SA Smoke Alarm, Single Station Type (Note 3)
SP Loudspeaker
SS Sprinkler Supervisory Switch
SV Sprinkler Valve
TS Sprinkler Tamper Switch (Note 2)
V Visual Alarm Appliance
Note 1: Confirmation of wiring supervision to each individual device is only required during installation verification or a complete building audit
of the system and is not required on the annual test.
Note 2: Sprinkler tamper switches cause trouble condition to be annunciated but not an alarm condition.
Note 3: Single station smoke alarms are not part of the fire alarm system but testing of such devices may be required by the authority
having jurisdiction.
Note 4: Identify the specific ancillary devices in the Remark column of Fire Alarm System Device Test and Inspection Record form
ANNUAL FIRE ALARM SYSTEM TESTING CERTIFICATE
THIS DOCUMENT CERTIFIES THAT THE FIRE ALARM SYSTEM AT THE FOLLOWING LOCATION;
ST. PHILIP, 420 QUEEN STREET, PETROLIA
HAS BEEN TESTED & INSPECTED IN ACCORDANCE WITH THE STANDARD FOR THE INSPECTION AND TESTING
OF FIRE ALARM SYSTEMS, CAN/ULC-S536-04.
A TEST OF ALL EMERGENCY LIGHTING EQUIPMENT WAS ALSO COMPLETED IN ACCORDANCE WITH CANADIAN
ULC CODES AND DESIGN CRITERIA DESIGNATED BY MANUFACTURER'S SPECIFICATIONS.
YES NO N/A
E The fire alarm system documentation is on site and includes a description of the system √
G The fire alarm system has deficiencies noted on the attached pages √
H Comments:
The information on this form (and the documents attached here-to) attest to the fact that the equipment listed here-in was tested/inspected in
conformance with applicable codes, bylaws, standards, and the manufacturer's requirements by a qualified technician. The equipment was left
in an operational condition except as noted in the spaces marked "comments". A copy should be maintained on the premises for examination
by the Fire Marshall or Inspector at their request.
Technician #1 Technician #2
YES NO NA
Power 'ON' visual indicator √
Common visual trouble signal √
Common audible trouble signal √
Trouble signal silence switch √
Main power supply failure trouble signal operates √
Ground fault tested on positive and negative trouble signal √
Alert signal operation √
Alarm signal operation √
Automatic transfer from alert signal to alarm signal √
Manual transfer from alert signal to alarm signal cancel (acknowledge) feature operates on a two-stage system √
Automatic transfer from alert signal to alarm signal cancel (acknowledge) feature operates on a two-stage system √
Alarm signal silence inhibit function operates √
Alarm signal manual silence operational √
Alarm signal silence visual indication operates √
Alarm signals, when silenced automatically reinitiate upon subsequent alarm √
Alarm signal silence automatic cut-out timer Time: √
Audible and visual alert signals and alarm signals programmed and operate per design and specification; or documentation as detailed
in Appendix C - Description of Fire Alarm System for Inspection and Test Procedures
√
Input circuit, alarm and supervisory operation, including audible and visual indication operates √
Input circuit supervision fault causes a trouble indication √
Output circuit alarm indicates operational √
Output circuit supervision fault causes a trouble indication √
Visual indicator test (lamp test) √
Coded Signal sequences operate not less than the required number of times and the correct alarm signal operates thereafter √
Coded signal sequences are not interrupted by subsequent alarm √
Ancillary device by-pass will result in a trouble signal √
Input circuit to output circuit operation, including ancillary device circuits, for correct program operation, as per design and
specification, or documentation as detailed in Appendix C - Description of Fire Alarm System for Inspection and Testing Procedures
√
Fire alarm system reset operation √
Main power supply to emergency power supply transfer operates √
Status change confirmation (smoke detectors only) verified [Refer Subsection 5.7.4.3, Status Change Confirmation (Alarm Verification
Feature)]
√
Receipt of alarm transmission to the fire signal receiving centre √
Receipt of the supervisory transmission to the fire signal receiving centre √
Receipt of the trouble transmission to the fire signal receiving centre √
Operation of the fire signal receiving centre disconnect means results in a specific trouble at the control unit or transponder and
√
transmits a trouble to the fire signal receiving centre
Record the name and telephone number of the fire signal receiving centre √
Name DAMAR- 114655 Irish
Phone Number (519) 336-7111
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
YES NO N/A
Output circuits for selective voice paging, including visual indication operates √
Output circuits for selective voice paging trouble operation, including visual indication operates √
Operation of voice paging does not interfere with entitled inhibit time of alert signal and alarm signal √
Circuits for emergency telephone call in operation, including audible and visual indication operates √
Circuits for emergency telephone for operation, including two-way voice communication operates √
YES NO N/A
EMERGENCY POWER SUPPLY TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.3, 5.3.2, 5.33]
YES NO N/A
Correct battery rating as determined by battery calculations based on full system load √
Adequately ventilated √
Generator provides power to the AC circuit serving the fire alarm system. √
Trouble condition at the emergency generator results in an audible common trouble signal and a visual indication at the required
annunciator. √
Battery voltage not less than 85% of its rated capacity after tests completed √
Battery manufacturer and part number 12V26
Battery manufacturer's date code or ins service date Date 2014
Battery Voltage (main power supply 'ON') is Voltage 26.90
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 26.30
in supervisory condition Current (A) 0.684
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 25.20
in full load condition Current (A) 0.763
The charging current is Current (mA) 1246
INDICATE TYPE OF BATTERY TEST PERFORMED (must choose 1 of 5 methods)
YES NO N/A
(i) Required supervisory load for 24 h followed by the required full load operation. √
(ii) Silent test using load resistor method for full duration test. √
(v) Replace the batteries with a new set having a current date code/capacity/type √
Record battery capacity AH 26
Record the battery terminal voltage after tests are completed. VDC 26.70
EMERGENCY POWER SUPPLY TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.3, 5.3.2, 5.33]
YES NO N/A
Correct battery rating as determined by battery calculations based on full system load √
Adequately ventilated √
Generator provides power to the AC circuit serving the fire alarm system. √
Trouble condition at the emergency generator results in an audible common trouble signal and a visual indication at the required
annunciator. √
Battery voltage not less than 85% of its rated capacity after tests completed √
Battery manufacturer and part number 12V7.2
Battery manufacturer's date code or ins service date Date 2014
Battery Voltage (main power supply 'ON') is Voltage 26.40
Battery voltage and current with main power supply 'OFF' and fire alarm system in Voltage 26.00
supervisory condition Current (A) 0.076
Battery voltage and current with main power supply 'OFF' and fire alarm system in Voltage 25.10
full load condition Current (A) 3.554
The charging current is Current (mA) 1638
INDICATE TYPE OF BATTERY TEST PERFORMED (must choose 1 of 5 methods)
YES NO N/A
(i) Required supervisory load for 24 h followed by the required full load operation. √
(ii) Silent test using load resistor method for full duration test. √
(v) Replace the batteries with a new set having a current date code/capacity/type √
Record battery capacity AH 7.2
Record the battery terminal voltage after tests are completed. VDC 26.10
EMERGENCY POWER SUPPLY TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.3, 5.3.2, 5.33]
YES NO N/A
Correct battery rating as determined by battery calculations based on full system load √
Adequately ventilated √
Generator provides power to the AC circuit serving the fire alarm system. √
Trouble condition at the emergency generator results in an audible common trouble signal and a visual indication at the required
annunciator. √
Battery voltage not less than 85% of its rated capacity after tests completed √
Battery manufacturer and part number 12V7.2
Battery manufacturer's date code or ins service date Date 2014
Battery Voltage (main power supply 'ON') is Voltage 26.40
Battery voltage and current with main power supply 'OFF' and fire alarm system in Voltage 26.10
supervisory condition Current (A) 0.050
Battery voltage and current with main power supply 'OFF' and fire alarm system in Voltage 25.40
full load condition Current (A) 1.959
The charging current is Current (mA) 786
INDICATE TYPE OF BATTERY TEST PERFORMED (must choose 1 of 5 methods)
YES NO N/A
(i) Required supervisory load for 24 h followed by the required full load operation. √
(ii) Silent test using load resistor method for full duration test. √
(v) Replace the batteries with a new set having a current date code/capacity/type √
Record battery capacity AH 7.2
Record the battery terminal voltage after tests are completed. VDC 26.30
EMERGENCY POWER SUPPLY TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.3, 5.3.2, 5.33]
YES NO N/A
Correct battery rating as determined by battery calculations based on full system load √
Adequately ventilated √
Generator provides power to the AC circuit serving the fire alarm system. √
Trouble condition at the emergency generator results in an audible common trouble signal and a visual indication at the required
annunciator. √
Battery voltage not less than 85% of its rated capacity after tests completed √
Battery manufacturer and part number 12V7.2
Battery manufacturer's date code or ins service date Date 2014
Battery Voltage (main power supply 'ON') is Voltage 26.30
Battery voltage and current with main power supply 'OFF' and fire alarm system in Voltage 26.10
supervisory condition Current (A) 0.105
Battery voltage and current with main power supply 'OFF' and fire alarm system in Voltage 25.00
full load condition Current (A) 3.096
The charging current is Current (mA) 1414
INDICATE TYPE OF BATTERY TEST PERFORMED (must choose 1 of 5 methods)
YES NO N/A
(i) Required supervisory load for 24 h followed by the required full load operation. √
(ii) Silent test using load resistor method for full duration test. √
(v) Replace the batteries with a new set having a current date code/capacity/type √
Record battery capacity AH 7.2
Record the battery terminal voltage after tests are completed. VDC 26.10
EMERGENCY POWER SUPPLY TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.3, 5.3.2, 5.33]
YES NO N/A
Correct battery rating as determined by battery calculations based on full system load √
Adequately ventilated √
Generator provides power to the AC circuit serving the fire alarm system. √
Trouble condition at the emergency generator results in an audible common trouble signal and a visual indication at the required
annunciator. √
Battery voltage not less than 85% of its rated capacity after tests completed √
Battery manufacturer and part number 12V7.2
Battery manufacturer's date code or ins service date Date 2014
Battery Voltage (main power supply 'ON') is Voltage 26.50
Battery voltage and current with main power supply 'OFF' and fire alarm system in Voltage 26.10
supervisory condition Current (A) 0.029
Battery voltage and current with main power supply 'OFF' and fire alarm system in Voltage 26.00
full load condition Current (A) 3.333
The charging current is Current (mA) 1600
INDICATE TYPE OF BATTERY TEST PERFORMED (must choose 1 of 5 methods)
YES NO N/A
(i) Required supervisory load for 24 h followed by the required full load operation. √
(ii) Silent test using load resistor method for full duration test. √
(v) Replace the batteries with a new set having a current date code/capacity/type √
Record battery capacity AH 7.2
Record the battery terminal voltage after tests are completed. VDC 26.30
EMERGENCY POWER SUPPLY TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.3, 5.3.2, 5.33]
YES NO N/A
Correct battery rating as determined by battery calculations based on full system load √
Adequately ventilated √
Generator provides power to the AC circuit serving the fire alarm system. √
Trouble condition at the emergency generator results in an audible common trouble signal and a visual indication at the required
annunciator. √
Battery voltage not less than 85% of its rated capacity after tests completed √
Battery manufacturer and part number 12V7.2
Battery manufacturer's date code or ins service date Date 2014
Battery Voltage (main power supply 'ON') is Voltage 26.60
Battery voltage and current with main power supply 'OFF' and fire alarm system in Voltage 26.10
supervisory condition Current (A) 0.123
Battery voltage and current with main power supply 'OFF' and fire alarm system in Voltage 25.30
full load condition Current (A) 3.060
The charging current is Current (mA) 1936
INDICATE TYPE OF BATTERY TEST PERFORMED (must choose 1 of 5 methods)
YES NO N/A
(i) Required supervisory load for 24 h followed by the required full load operation. √
(ii) Silent test using load resistor method for full duration test. √
(v) Replace the batteries with a new set having a current date code/capacity/type √
Record battery capacity AH 7.2
Record the battery terminal voltage after tests are completed. VDC 26.40
ANNUNCIATOR AND REMOTE TROUBLE SIGNAL UNIT TEST & INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.1]
YES NO N/A
Individual alarm and supervisory input zone clearly indicated and separately designated √
Individual alarm and supervisory input zone designation labels are properly identified √
YES NO N/A
Minimum of one alarm zone and one supervisory zone tested per annunciator or sequential display to confirm operation √
Individual alarm and supervisory input zone designation labels are properly identified. √
REMOTE TROUBLE SIGNAL UNIT TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.3]
YES NO N/A
YES NO N/A
Operates as per design and specification, or in accordance with documentation provided in Appendix E. √
DATA COMMUNICATION LINK TEST [Ref. CAN/ULC-S536-04, Clauses 5.1.5, 5.6 Note]
YES NO N/A
Confirm that a trouble signal is received at the control unit or transponder under an open loop fault for each data communication link
(DCL) √
Where fault isolation modules are installed in data communication links serving field devices, wiring shorted on the isolated side,
annunciation of the fault confirmed, and then a device on the source side operated, and activation confirmed at the control unit or √
Where fault isolation in data communication links is provided between control units or transponders and between transponders,
introduce a short circuit fault and confirm annunciation of the fault and operation outside the shorted section between each pair of: √
YES NO N/A
Fan Shutdown √
Elevator Recall √
BAS Relay √
Aux. Relay √
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 6th & 7th, 2016
Building Name: St. Patrick's High School Address: 1001 Rapids Parkway, Sarnia Page 1 of 9
By Stairwell 2D H/S √ √
By 228 H/S √ √
By 224 H/S √ √
By 218 H/S √ √
By 203 H/S √ √
By 208 H/S √ √
By 208 EOL √ √
Stairwell 2C H √ √
Stairwell 2C EOL √ √
By 206 H/S √ √
By 206 EOL √ √
By 206 EOL √ √
By 201-A H/S √ √
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 6th & 7th, 2016
Building Name: St. Patrick's High School Address: 1001 Rapids Parkway, Sarnia Page 2 of 9
By 280 H/S √ √
By 278 H/S √ √
Stairwell 2A H √ √
By 243 EOL √ √
By 241 H/S √ √
By 276 H/S √ √
By 239 H/S √ √
By 235 H/S √ √
By 236 H/S √ √
By 234 H/S √ √
By 230 H/S √ √
By 201F H/S √ √
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 6th & 7th, 2016
Building Name: St. Patrick's High School Address: 1001 Rapids Parkway, Sarnia Page 3 of 9
By 266 H/S √ √
By 264 H/S √ √
By Stairwell 2E H/S √ √
By Stairwell 2E EOL √ √
By Stairwell 2E EOL √ √
Stairwell 2E H √ √
By 215 H/S √ √
By 221 H/S √ √
By 248 H/S √ √
By 252 H/S √ √
By Stairwell 2F H/S √ √
By 256 H/S √ √
By 229 H/S √ √
By 233 H/S √ √
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 6th & 7th, 2016
Building Name: St. Patrick's High School Address: 1001 Rapids Parkway, Sarnia Page 4 of 9
By 258 H/S √ √
By 258 H/S √ √
By 210 EOL √ √
By 210 EOL √ √
By 128 H/S √ √
By 139 H/S √ √
By 134 H/S √ √
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 6th & 7th, 2016
Building Name: St. Patrick's High School Address: 1001 Rapids Parkway, Sarnia Page 5 of 9
By 143 H/S √ √
By 100H H/S √ √
By 107 H/S √ √
By 180 H/S √ √
By 100J H/S √ √
By 100 H/S √ √
By 100 H/S √ √
100 H/S √ √
Chapel H/S √ √
By 108 H/S √ √
By 112-Cafeteria H/S √ √
By 112-Cafeteria H/S √ √
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 6th & 7th, 2016
Building Name: St. Patrick's High School Address: 1001 Rapids Parkway, Sarnia Page 6 of 9
By 107F H/S √ √
By 107M H/S √ √
By 107C H/S √ √
By 112G H/S √ √
Servery H/S √ √
By 116 H/S √ √
By 127A H/S √ √
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 6th & 7th, 2016
Building Name: St. Patrick's High School Address: 1001 Rapids Parkway, Sarnia Page 7 of 9
By 135E H/S √ √
By 135E H/S √ √
By 115 H/S √ √
By 118 H/S √ √
By 124 H/S √ √
By 125 H/S √ √
125 H/S √ √
By 127 H/S √ √
By 176 EOL √ √
By 176 EOL √ √
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 6th & 7th, 2016
Building Name: St. Patrick's High School Address: 1001 Rapids Parkway, Sarnia Page 8 of 9
By 174 H/S √ √
By 140 H/S √ √
By 140 EOL √ √
By140 EOL √ √
By 149 H/S √ √
By 152 H/S √ √
By 142 H/S √ √
By 159 H/S √ √
By 148 H/S √ √
By 163 H/S √ √
By 158 H/S √ √
By 160 H/S √ √
By 165 H/S √ √
By 166 H/S √ √
By 168 H/S √ √
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 6th & 7th, 2016
Building Name: St. Patrick's High School Address: 1001 Rapids Parkway, Sarnia Page 9 of 9
By 170 H/S √ √
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 6th & 7th, 2016
Building Name: St. Patrick's High School Address: 1001 Rapids Parkway, Sarnia Page 1 of 3
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 6th & 7th, 2016
Building Name: St. Patrick's High School Address: 1001 Rapids Parkway, Sarnia Page 2 of 3
2nd Floor
Room 220 IM √ √ 257
At NW Intersection Zone 14 CT2 √ √ 223
At NW Intersection Zone 17 CT2 √ √ 224
At NW Stair #3 (in) IM √ √ 225
At NW Stair #3 (out) IM √ √ 226
Upper Lobby Stair #2 (in) IM √ √ 227
Upper Lobby Stair #2 (out) IM √ √ 228
Room 276 IM √ √ 229
At Stair #1 North Corridor IM √ √ 230
Chapel Northeast Corridor CTI √ √ 231
Chapel Mechanical Room CTI √ √ 232
Chapel Mechanical Room IM √ √ 233
East Corridor at North Intersection IM √ √ 234
North Corridor at Elevator IM √ √ 235
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 6th & 7th, 2016
Building Name: St. Patrick's High School Address: 1001 Rapids Parkway, Sarnia Page 3 of 3
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 6th & 7th, 2016
Building Name: St. Patrick's High School Address: 1001 Rapids Parkway, Sarnia Page 1 of 5
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 6th & 7th, 2016
Building Name: St. Patrick's High School Address: 1001 Rapids Parkway, Sarnia Page 2 of 5
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 6th & 7th, 2016
Building Name: St. Patrick's High School Address: 1001 Rapids Parkway, Sarnia Page 3 of 5
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 6th & 7th, 2016
Building Name: St. Patrick's High School Address: 1001 Rapids Parkway, Sarnia Page 4 of 5
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 6th & 7th, 2016
Building Name: St. Patrick's High School Address: 1001 Rapids Parkway, Sarnia Page 5 of 5
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 6th & 7th, 2016
Building Name: St. Patrick's High School Address: 1001 Rapids Parkway, Sarnia Page 1 of 4
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 6th & 7th, 2016
Building Name: St. Patrick's High School Address: 1001 Rapids Parkway, Sarnia Page 2 of 4
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 6th & 7th, 2016
Building Name: St. Patrick's High School Address: 1001 Rapids Parkway, Sarnia Page 3 of 4
CAN/ULC S536-04
FIRE ALARoom
INDIVIDUAL DEVICE RECORD
Date: July 6th & 7th, 2016
Building Name: St. Patrick's High School Address: 1001 Rapids Parkway, Sarnia Page 4 of 4
CAN/ULC
EMERGENCY LIGHTING
INDIVIDUAL DEVICE RECORD
Date: July 6th & 7th, 2016
Building Name: St. Patrick's High School Address: 1001 Rapids Parkway, Sarnia
CAN/ULC S536-04
SPRINKLERS
INDIVIDUAL DEVICE RECORD
Date: July 6th & 7th, 2016
Building Name: St. Patrick's High School Address: 1001 Rapids Parkway, Sarnia Page 1 of 2
CAN/ULC S536-04
SPRINKLERS
INDIVIDUAL DEVICE RECORD
Date: July 6th & 7th, 2016
Building Name: St. Patrick's High School Address: 1001 Rapids Parkway, Sarnia Page 2 of 2
REPAIRS
# LOCATION DEVICE REPAIR COMPLETED
Fire Alarm
1 North Right Exit from Cafeteria Room # 112 M Replaced (1) Manual Pull Station Glass Rod 08/24/2016
2 Men's Washroom - Room 220 H/S Replaced Device w/ (1) GIR-HDVM Horn Strobe 08/24/2016
3 By 213 H/S Replaced Device w/ (1) GIR-HDVM Horn Strobe 08/24/2016
Obstruction Removed, Found Device Damaged. Required
4 Room 114 H/S replacement 08/24/2016
Emergency Lighting
1 Room 222 RG12S360 Replaced Battery w/ (1) Enersys NP33-12 08/24/2016
2 Hall By 176 RG12S360 Replaced w/ (1) Enersys NP33-12, (1) 12V Bipin Lamp 08/24/2016
3 Room 134 Exit Right 5LER4502 Replaced PC Board w/ (1) CB-093 08/24/2016
4 Room 124E- Gym Storage RG12S360 Replaced Battery w/ (1) Enersys NP33-12 08/24/2016
5 Room 124G- Gym Storage RG12S360 Replaced Battery w/ (1) Enersys NP33-12 08/24/2016
6 Room 107E off of 107 RG12S360 Replaced w/ 12 Volt Single Remote Head 08/24/2016
7 Safe Room 100L RG12S250 Replaced w/ (1) 12V Bipin Lamp 08/24/2016
Sprinkler Repairs
1 Sprinkler Repairs Completed. See Report.
Additional Comments:
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
DEVICE LEGEND
DEVICE DESCRIPTION
ANN Annunciator
AD Ancillary Device (Note 4)
B Bell
BZ Buzzer
C Chime
CR Control Relay
CT1 Single Input Module (for supervised Class B signal or audio circuits)
CT2 Double Input Module (for supervised Class B signal or audio circuits)
DH Door Hold Open Device
DS Duct Smoke Detector
ET Emergency Telephone
FACP Fire Alarm Control Panel
FH Firefighters Handset
FS Sprinkler Flow Switch
GA 2nd Stage of 2-Stage Pull Station
H Horn
H/S Horn Strobe
HSP Horn Loudspeaker
HT Heat Detector, Fixed Temperature
HT-RES Resetable Heat Detector
K Horn, Klaxon Type
M Manual Pull Station
MAG LOCK Magnetic Door Lock
PS Pressure Switch
RHT Heat Detector, Rate-of-Rise
S Smoke Detector
SA Smoke Alarm, Single Station Type (Note 3)
SP Loudspeaker
SS Sprinkler Supervisory Switch
SV Sprinkler Valve
TS Sprinkler Tamper Switch (Note 2)
V Visual Alarm Appliance
Note 1: Confirmation of wiring supervision to each individual device is only required during installation verification or a
complete building audit of the system and is not required on the annual test.
Note 2: Sprinkler tamper switches cause trouble condition to be annunciated but not an alarm condition.
Note 3: Single station smoke alarms are not part of the fire alarm system but testing of such devices may be required by the
authority having jurisdiction.
Note 4: Identify the specific ancillary devices in the Remark column of Fire Alarm System Device Test and Inspection Record
183 Exeter Rd., Unit 183
London, Ontario
PHONE (519) 652-5086
FAX (519) 652-8719
1. GENERAL:
2. CONTROL VALVES:
3. WATER SUPPLIES:
a) Are siamese connections in good condition, couplings free, caps in place and ball drips open? YES
(chrome)
5. FIRE HYDRANTS:
N/A
6. WET SYSTEMS:
7. DRY SYSTEMS:
9. SPECIAL SYSTEMS:
N/A
N/A
11. ALARMS:
a) Are all sprinklers in good condition, free from obstruction, corrosion and loading? YES
b) Are the sprinklers less than 50 years old? YES
c) Are there spare sprinklers and a wrench in the head cabinet? No
d) Is the condition of the piping, drain valves, hangers and gauges in good condition? YES
e) Have the sprinklers been checked for the proper temperature rating? YES
NONE
NONE
*No spare sprinkler head wrench in head box.** Installed Aug. 24th, 2016
*Room 116 Mech. Rm. Re-install removed sprinkler head and piping.**Installed Aug. 24th, 2016
The above items are deficient as per The Ontario Fire Code and need to be corrected immediately.
A certificate of inspection cannot be issued until all items under section #16 have been addressed.
Consultation with the local fire prevention office is suggested, if discrepancies occur
NONE
• LIMITATION OF LIABILITY: It is understood and agreed that the INSPECTOR is NOT an insurer and is NOT
warranting or guaranteeing the adequacy, performance or life expectancy of any structure, item, component or
system in the building. Further, it is mutually agreed that the maximum amount of joint and several liability the
INSPECTOR can incur for any error, mistakes, omissions, breach of contract, breach of warrantee, negligent
hiring, or any other theory of liability including violation of a statute or consumer protection act is strictly limited
to the FEE PAID for the inspection report.
NOTE: This inspection/test was performed in accordance with The Ontario Fire Code. This inspection does NOT certify
that the sprinkler system installation complies with NFPA, OBC or Ontario Retrofit Reg. #627/92 (an engineer’s report
would be required to certify this).
As per the requirements of The Ontario Fire Codes, the inspecting company must submit this report to the local
Fire Prevention office
THIS DOCUMENT CERTIFIES THAT THE FIRE ALARM SYSTEM AT THE FOLLOWING LOCATION;
ST. PATRICKS CATHOLIC HIGH SCHOOL, 101 THE RAPIDS PARKWAY, SARNIA
HAS BEEN TESTED & INSPECTED IN ACCORDANCE WITH THE STANDARD FOR THE INSPECTION AND TESTING OF
FIRE ALARM SYSTEMS, CAN/ULC-S536-04. THE SPRINKLER SYSTEM & FIRE HYDRANT HAVE ALSO BEEN INSPECTED
AT THIS LOCATION.
A TEST OF ALL EMERGENCY LIGHTING EQUIPMENT WAS ALSO COMPLETED IN ACCORDANCE WITH CANADIAN
ULC CODES AND DESIGN CRITERIA DESIGNATED BY MANUFACTURER'S SPECIFICATIONS.
YES NO N/A
E The fire alarm system documentation is on site and includes a description of the system √
G The fire alarm system has deficiencies noted on the attached pages √
H Comments:
The information on this form (and the documents attached here-to) attest to the fact that the equipment listed here-in was tested/inspected in
conformance with applicable codes, bylaws, standards, and the manufacturer's requirements by a qualified technician. The equipment was left in
an operational condition except as noted in the spaces marked "comments". A copy should be maintained on the premises for examination by
the Fire Marshall or Inspector at their request.
Technician #1 Technician #2
YES NO N/A
Output circuits for selective voice paging, including visual indication operates √
Output circuits for selective voice paging trouble operation, including visual indication operates √
Operation of voice paging does not interfere with entitled inhibit time of alert signal and alarm signal √
Circuits for emergency telephone call in operation, including audible and visual indication operates √
Circuits for emergency telephone for operation, including two-way voice communication operates √
YES NO N/A
Control unit or transponder location Electrical Room 121A off of Boiler Room 121
EMERGENCY POWER SUPPLY TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.3, 5.3.2, 5.33]
YES NO N/A
Correct battery rating as determined by battery calculations based on full system load √
Adequately ventilated √
Generator provides power to the AC circuit serving the fire alarm system. √
Trouble condition at the emergency generator results in an audible common trouble signal and a visual indication at the required
annunciator. √
Battery voltage not less than 85% of its rated capacity after tests completed √
Battery manufacturer and part number NP-1212
Battery manufacturer's date code or ins service date Date 2015
Battery Voltage (main power supply 'ON') is Voltage 26.10
Battery voltage and current with main power supply 'OFF' and fire alarm Voltage 25.50
system in supervisory condition Current (A) 0.22
Battery voltage and current with main power supply 'OFF' and fire alarm Voltage 24.90
system in full load condition Current (A) 0.95
The charging current is Current (mA) 1349
(i) Required supervisory load for 24 h followed by the required full load operation; √
(ii) Silent test using load resistor method for full duration test. √
(v) Replace the batteries with a new set having a current date code/capacity/type √
Record battery capacity AH 12
Record the battery terminal voltage after tests are completed. VDC 25.80
ANNUNCIATOR AND REMOTE TROUBLE SIGNAL UNIT TEST & INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.1]
YES NO N/A
Individual alarm and supervisory input zone clearly indicated and separately designated √
Individual alarm and supervisory input zone designation labels are properly identified √
YES NO N/A
Minimum of one alarm zone and one supervisory zone tested per annunciator or sequential display to confirm operation √
Individual alarm and supervisory input zone designation labels are properly identified. √
REMOTE TROUBLE SIGNAL UNIT TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.3]
YES NO N/A
YES NO N/A
Operates as per design and specification, or in accordance with documentation provided in Appendix E. √
DATA COMMUNICATION LINK TEST [Ref. CAN/ULC-S536-04, Clauses 5.1.5, 5.6 Note]
YES NO N/A
Confirm that a trouble signal is received at the control unit or transponder under an open loop fault for each data communication link
(DCL) √
Where fault isolation modules are installed in data communication links serving field devices, wiring shorted on the isolated side,
annunciation of the fault confirmed, and then a device on the source side operated, and activation confirmed at the control unit or √
Where fault isolation in data communication links is provided between control units or transponders and between transponders,
introduce a short circuit fault and confirm annunciation of the fault and operation outside the shorted section between each pair of: √
YES NO N/A
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 2nd, 2016
Building Name: St. Ursula Address: 426 Lacroix Street, Chatham Page 1 of 3
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 2nd, 2016
Building Name: St. Ursula Address: 426 Lacroix Street, Chatham Page 2 of 3
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 2nd, 2016
Building Name: St. Ursula Address: 426 Lacroix Street, Chatham Page 3 of 3
Gym B √ √ S-1
CAN/ULC
EMERGENCY LIGHTING
INDIVIDUAL DEVICE RECORD
Date: August 2nd, 2016
Gym East Wall SLA-36 PA-6V7.2 (14) N/A N/A 2:00 Panel LPA cct 39
REPAIRS
# LOCATION DEVICE REPAIR COMPLETED
Fire Alarm Devices
1 Store Room By Staff W/C 110 RHT Replaced Device w/ (1) Mircom 5601A Detector 03/02/2016
Emergency Lighting
No Repairs Required
Additional Comments:
Portable Zone Has Been Re-Labelled To Correct Zone # 5
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
DEVICE LEGEND
DEVICE DESCRIPTION
ANN Annunciator
AD Ancillary Device (Note 4)
B Bell
BZ Buzzer
C Chime
CR Control Relay
CT1 Single Input Module (for supervised Class B signal or audio circuits)
CT2 Double Input Module (for supervised Class B signal or audio circuits)
DH Door Hold Open Device
DS Duct Smoke Detector
ET Emergency Telephone
FACP Fire Alarm Control Panel
FH Firefighters Handset
FS Sprinkler Flow Switch
GA 2nd Stage of 2-Stage Pull Station
H Horn
H/S Horn Strobe
HSP Horn Loudspeaker
HT Heat Detector, Fixed Temperature
HT-RES Resetable Heat Detector
K Horn, Klaxon Type
M Manual Pull Station
MAG LOCK Magnetic Door Lock
PS Pressure Switch
RHT Heat Detector, Rate-of-Rise
S Smoke Detector
SA Smoke Alarm, Single Station Type (Note 3)
SP Loudspeaker
SS Sprinkler Supervisory Switch
SV Sprinkler Valve
TS Sprinkler Tamper Switch (Note 2)
V Visual Alarm Appliance
Note 1: Confirmation of wiring supervision to each individual device is only required during installation verification or a complete building audit
of the system and is not required on the annual test.
Note 2: Sprinkler tamper switches cause trouble condition to be annunciated but not an alarm condition.
Note 3: Single station smoke alarms are not part of the fire alarm system but testing of such devices may be required by the authority
having jurisdiction.
Note 4: Identify the specific ancillary devices in the Remark column of Fire Alarm System Device Test and Inspection Record form
183 Exeter Road, Unit A
London, Ontario
PHONE (519) 652-5086
FAX (519) 652-8719
1. GENERAL:
a) Are the hydrant(s) free from obstructions and accessible? YES
b) Are the hydrant(s) visible and clearly marked? YES
2. WATER SUPPLIES:
a) Was a flow test done? YES
b) Was water flowed from the hydrant for a minimum time of one minute with the valve fully open? YES
c) Was the water free of debris? YES
d) Type of water supply? City Water Supply
3. FIRE HYDRANTS:
NONE
NONE
6. The following items are deficient as per The Ontario Fire Code and need to be corrected immediately:
NONE
The certificate of inspection cannot be issued until all items under section #6 have been completed.
NONE
NOTE: This inspection/test was performed in accordance with The Ontario Fire Code. This inspection does NOT
certify that the fire hydrant installation complies with NFPA, OBC or Ontario Retrofit Reg. #627/92 (an engineer’s
report would be required to certify this).
LIMITATION OF LIABILITY: It is understood and agreed that the INSPECTOR is NOT an insurer and is NOT
warranting or guaranteeing the adequacy, performance or life expectancy of any structure, item,
component or system in the building. Further, it is mutually agreed that the maximum amount of joint and
several liability the INSPECTOR can incur for any error, mistakes, omissions, breach of contract, breach of
warrantee, negligent hiring, or any other theory of liability including violation of a statue or consumer
protection act is strictly limited to the FEE PAID for the inspection report.
As per the requirements of The Ontario Fire Codes, the inspecting company must submit this report to the
local Fire Prevention office
THIS DOCUMENT CERTIFIES THAT THE FIRE ALARM SYSTEM AT THE FOLLOWING LOCATION;
ST. URSULA~ 426 LACROIX STREET, CHATHAM
HAS BEEN TESTED & INSPECTED IN ACCORDANCE WITH THE STANDARD FOR THE INSPECTION AND TESTING
OF FIRE ALARM SYSTEMS, CAN/ULC-S536-04. THE FIRE HYDRANT HAVE ALSO BEEN INSPECTED AT THIS LOCATION.
A TEST OF ALL EMERGENCY LIGHTING EQUIPMENT WAS ALSO COMPLETED IN ACCORDANCE WITH CANADIAN
ULC CODES AND DESIGN CRITERIA DESIGNATED BY MANUFACTURER'S SPECIFICATIONS.
YES NO N/A
E The fire alarm system documentation is on site and includes a description of the system √
G The fire alarm system has deficiencies noted on the attached pages √
H Comments:
The information on this form (and the documents attached here-to) attest to the fact that the equipment listed here-in was tested/inspected in
conformance with applicable codes, bylaws, standards, and the manufacturer's requirements by a qualified technician. The equipment was left in
an operational condition except as noted in the spaces marked "comments". A copy should be maintained on the premises for examination by
the Fire Marshall or Inspector at their request.
Technician #1 Technician #2
YES NO NA
Power 'ON' visual indicator √
Common visual trouble signal √
Common audible trouble signal √
Trouble signal silence switch √
Main power supply failure trouble signal operates √
Ground fault tested on positive and negative trouble signal √
Alert signal operation √
Alarm signal operation √
Automatic transfer from alert signal to alarm signal √
Manual transfer from alert signal to alarm signal cancel (acknowledge) feature operates on a two-stage system √
Automatic transfer from alert signal to alarm signal cancel (acknowledge) feature operates on a two-stage system √
Alarm signal silence inhibit function operates √
Alarm signal manual silence operational √
Alarm signal silence visual indication operates √
Alarm signals, when silenced automatically reinitiate upon subsequent alarm √
Alarm signal silence automatic cut-out timer Time: √
Audible and visual alert signals and alarm signals programmed and operate per design and specification; or documentation as detailed
in Appendix C - Description of Fire Alarm System for Inspection and Test Procedures √
Input circuit, alarm and supervisory operation, including audible and visual indication operates √
Input circuit supervision fault causes a trouble indication √
Output circuit alarm indicates operational √
Output circuit supervision fault causes a trouble indication √
Visual indicator test (lamp test) √
Coded Signal sequences operate not less than the required number of times and the correct alarm signal operates thereafter √
Coded signal sequences are not interrupted by subsequent alarm √
Ancillary device by-pass will result in a trouble signal √
Input circuit to output circuit operation, including ancillary device circuits, for correct program operation, as per design and specification,
or documentation as detailed in Appendix C - Description of Fire Alarm System for Inspection and Testing Procedures √
Fire alarm system reset operation √
Main power supply to emergency power supply transfer operates √
Status change confirmation (smoke detectors only) verified [Refer Subsection 5.7.4.3, Status Change Confirmation (Alarm Verification
Feature)] √
Receipt of alarm transmission to the fire signal receiving centre √
Receipt of the supervisory transmission to the fire signal receiving centre √
Receipt of the trouble transmission to the fire signal receiving centre √
Operation of the fire signal receiving centre disconnect means results in a specific trouble at the control unit or transponder and
transmits a trouble to the fire signal receiving centre √
Record the name and telephone number of the fire signal receiving centre √
Name DAMAR- 883341 Vikings
Phone Number 1 (800) 265-7562
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
YES NO N/A
Output circuits for selective voice paging, including visual indication operates √
Output circuits for selective voice paging trouble operation, including visual indication operates √
Operation of voice paging does not interfere with entitled inhibit time of alert signal and alarm signal √
Circuits for emergency telephone call in operation, including audible and visual indication operates √
Circuits for emergency telephone for operation, including two-way voice communication operates √
YES NO N/A
YES NO N/A
EMERGENCY POWER SUPPLY TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.3, 5.3.2, 5.33]
YES NO N/A
Correct battery rating as determined by battery calculations based on full system load √
Adequately ventilated √
Generator provides power to the AC circuit serving the fire alarm system. √
Trouble condition at the emergency generator results in an audible common trouble signal and a visual indication at the required
annunciator. √
Battery voltage not less than 85% of its rated capacity after tests completed √
Battery manufacturer and part number (2) Enersys NP7-12
Battery manufacturer's date code or ins service date Date 2011
Battery Voltage (main power supply 'ON') is Voltage 26.60
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 25.50
in supervisory condition Current (A) 0.066
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 25.20
in full load condition Current (A) 0.585
The charging current is Current (mA) 0.89
YES NO N/A
(i) Required supervisory load for 24 h followed by the required full load operation; √
(ii) Silent test using load resistor method for full duration test. √
(v) Replace the batteries with a new set having a current date code/capacity/type √
Record battery capacity AH 7
Record the battery terminal voltage after tests are completed. VDC 25.40
ANNUNCIATOR AND REMOTE TROUBLE SIGNAL UNIT TEST & INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.1]
YES NO N/A
Individual alarm and supervisory input zone clearly indicated and separately designated √
Individual alarm and supervisory input zone designation labels are properly identified √
YES NO N/A
Minimum of one alarm zone and one supervisory zone tested per annunciator or sequential display to confirm operation √
Individual alarm and supervisory input zone designation labels are properly identified. √
REMOTE TROUBLE SIGNAL UNIT TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.3]
YES NO N/A
YES NO N/A
Operates as per design and specification, or in accordance with documentation provided in Appendix E. √
DATA COMMUNICATION LINK TEST [Ref. CAN/ULC-S536-04, Clauses 5.1.5, 5.6 Note]
YES NO N/A
Confirm that a trouble signal is received at the control unit or transponder under an open loop fault for each data communication link
(DCL) √
Where fault isolation modules are installed in data communication links serving field devices, wiring shorted on the isolated side,
annunciation of the fault confirmed, and then a device on the source side operated, and activation confirmed at the control unit or √
Where fault isolation in data communication links is provided between control units or transponders and between transponders,
introduce a short circuit fault and confirm annunciation of the fault and operation outside the shorted section between each pair of: √
YES NO N/A
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 12th, 2016
Building Name: St. Vincent Address: 9399 Mc Naughton Line E., Chatham Page 1 of 3
Gym B √ √ NAC-1
East Exit M √ √ 1
Hall By Office M √ √ 1
French Computer M √ √ 1
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 12th, 2016
Building Name: St. Vincent Address: 9399 Mc Naughton Line E., Chatham Page 2 of 3
Boiler Room M √ √ 1
Room 4 RHT √ √ 1
Library RHT √ √ 1
NW Exit M √ √ 1
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: August 12th, 2016
Building Name: St. Vincent Address: 9399 Mc Naughton Line E., Chatham Page 3 of 3
Room 36 RHT √ √ 1
Room 35 RHT √ √ 1
Room 33 RHT √ √ 1
NE Exit M √ √ 1 EOL
Hall By NE Exit RHT √ √ 1
CAN/ULC
EMERGENCY LIGHTING
INDIVIDUAL DEVICE RECORD
Date: August 12th, 2016
Building Name: St. Vincent Address: 9399 Mc Naughton Line E., Chatham
REPAIRS
# LOCATION DEVICE REPAIR COMPLETED
Fire Alarm Devices
1 Mircom Fire Alarm Panel FA-101T Replaced Batteries w/ (2) EnerSys NP7-12 08/12/2016
2 Slop Sink In Boys Washroom 111A RHT Replaced Device w/ (1) 5601A Heat Detector 08/12/2016
3 Paint Storage 115 RHT Replaced Device w/ (1) 5601A Heat Detector 08/12/2016
4 Room 106 RHT Replaced Device w/ (1) 5601A Heat Detector 08/12/2016
Emergency Lighting
1 Gym Exit Out RG 36 REI Replaced Battery w/ (1) Panasonic PA-6V7.2 08/12/2016
2 Hall By Resource, Unit # 6 RG 36 Replaced Battery w/ (1) Panasonic PA-6V7.2 08/12/2016
3 Hall By Library, Unit # 5 RG 36 Replaced Battery w/ (1) Panasonic PA-6V7.2 08/12/2016
4 NE Exit, Unit # 1 RG 36 Replaced Battery w/ (1) Panasonic PA-6V7.2 08/12/2016
Additional Comments:
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
DEVICE LEGEND
DEVICE DESCRIPTION
ANN Annunciator
AD Ancillary Device (Note 4)
B Bell
BZ Buzzer
C Chime
CR Control Relay
CT1 Single Input Module (for supervised Class B signal or audio circuits)
CT2 Double Input Module (for supervised Class B signal or audio circuits)
DH Door Hold Open Device
DS Duct Smoke Detector
ET Emergency Telephone
FACP Fire Alarm Control Panel
FH Firefighters Handset
FS Sprinkler Flow Switch
GA 2nd Stage of 2-Stage Pull Station
H Horn
H/S Horn Strobe
HSP Horn Loudspeaker
HT Heat Detector, Fixed Temperature
HT-RES Resetable Heat Detector
K Horn, Klaxon Type
M Manual Pull Station
MAG LOCK Magnetic Door Lock
PS Pressure Switch
RHT Heat Detector, Rate-of-Rise
S Smoke Detector
SA Smoke Alarm, Single Station Type (Note 3)
SP Loudspeaker
SS Sprinkler Supervisory Switch
SV Sprinkler Valve
TS Sprinkler Tamper Switch (Note 2)
V Visual Alarm Appliance
Note 1: Confirmation of wiring supervision to each individual device is only required during installation verification or a complete building audit
of the system and is not required on the annual test.
Note 2: Sprinkler tamper switches cause trouble condition to be annunciated but not an alarm condition.
Note 3: Single station smoke alarms are not part of the fire alarm system but testing of such devices may be required by the authority
having jurisdiction.
Note 4: Identify the specific ancillary devices in the Remark column of Fire Alarm System Device Test and Inspection Record form
ANNUAL FIRE ALARM SYSTEM TESTING CERTIFICATE
THIS DOCUMENT CERTIFIES THAT THE FIRE ALARM SYSTEM AT THE FOLLOWING LOCATION;
ST. VINCENT~ 9399 MC NAUGHTON LINE, CHATHAM
HAS BEEN TESTED & INSPECTED IN ACCORDANCE WITH THE STANDARD FOR THE INSPECTION AND TESTING
OF FIRE ALARM SYSTEMS, CAN/ULC-S536-04.
A TEST OF ALL EMERGENCY LIGHTING EQUIPMENT WAS ALSO COMPLETED IN ACCORDANCE WITH CANADIAN
ULC CODES AND DESIGN CRITERIA DESIGNATED BY MANUFACTURER'S SPECIFICATIONS.
YES NO N/A
E The fire alarm system documentation is on site and includes a description of the system √
G The fire alarm system has deficiencies noted on the attached pages √
H Comments:
I A copy of this report has been given to: Paul Lernout - SCCDSB
The information on this form (and the documents attached here-to) attest to the fact that the equipment listed here-in was tested/inspected in
conformance with applicable codes, bylaws, standards, and the manufacturer's requirements by a qualified technician. The equipment was left in
an operational condition except as noted in the spaces marked "comments". A copy should be maintained on the premises for examination by
the Fire Marshall or Inspector at their request.
Technician #1 Technician #2
YES NO N/A
Output circuits for selective voice paging, including visual indication operates √
Output circuits for selective voice paging trouble operation, including visual indication operates √
Operation of voice paging does not interfere with entitled inhibit time of alert signal and alarm signal √
Circuits for emergency telephone call in operation, including audible and visual indication operates √
Circuits for emergency telephone for operation, including two-way voice communication operates √
YES NO N/A
YES NO N/A
EMERGENCY POWER SUPPLY TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.3, 5.3.2, 5.33]
YES NO N/A
Correct battery rating as determined by battery calculations based on full system load √
Adequately ventilated √
Generator provides power to the AC circuit serving the fire alarm system. √
Trouble condition at the emergency generator results in an audible common trouble signal and a visual indication at the required
annunciator. √
Battery voltage not less than 85% of its rated capacity after tests completed √
Battery manufacturer and part number NP38-12B
Battery manufacturer's date code or ins service date Date 2015
Battery Voltage (main power supply 'ON') is Voltage 26.30
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 26.00
in supervisory condition Current (A) 1.14
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 25.90
in full load condition Current (A) 1.71
The charging current is Current (mA) 1112
INDICATE TYPE OF BATTERY TEST PERFORMED (must choose 1 of 5 methods)
YES NO N/A
(i) Required supervisory load for 24 h followed by the required full load operation; √
(ii) Silent test using load resistor method for full duration test. √
(v) Replace the batteries with a new set having a current date code/capacity/type √
Record battery capacity AH 38
Record the battery terminal voltage after tests are completed. VDC 26.00
YES NO N/A
EMERGENCY POWER SUPPLY TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.3, 5.3.2, 5.33]
YES NO N/A
Correct battery rating as determined by battery calculations based on full system load √
Adequately ventilated √
Generator provides power to the AC circuit serving the fire alarm system. √
Trouble condition at the emergency generator results in an audible common trouble signal and a visual indication at the required
annunciator. √
Battery voltage not less than 85% of its rated capacity after tests completed √
Battery manufacturer and part number PK-12V13
Battery manufacturer's date code or ins service date Date 2012
Battery Voltage (main power supply 'ON') is Voltage 26.20
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 25.70
in supervisory condition Current (A) 0.05
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 25.40
in full load condition Current (A) 1.19
The charging current is Current (mA) 505
INDICATE TYPE OF BATTERY TEST PERFORMED (must choose 1 of 5 methods)
YES NO N/A
(i) Required supervisory load for 24 h followed by the required full load operation; √
(ii) Silent test using load resistor method for full duration test. √
(v) Replace the batteries with a new set having a current date code/capacity/type √
Record battery capacity AH 13
Record the battery terminal voltage after tests are completed. VDC 26.10
YES NO N/A
EMERGENCY POWER SUPPLY TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.3, 5.3.2, 5.33]
YES NO N/A
Correct battery rating as determined by battery calculations based on full system load √
Adequately ventilated √
Generator provides power to the AC circuit serving the fire alarm system. √
Trouble condition at the emergency generator results in an audible common trouble signal and a visual indication at the required
annunciator. √
Battery voltage not less than 85% of its rated capacity after tests completed √
Battery manufacturer and part number PK-12V13
Battery manufacturer's date code or ins service date Date 2012
Battery Voltage (main power supply 'ON') is Voltage 26.30
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 26.00
in supervisory condition Current (A) 0.06
Battery voltage and current with main power supply 'OFF' and fire alarm system Voltage 25.70
in full load condition Current (A) 0.97
The charging current is Current (mA) 356
INDICATE TYPE OF BATTERY TEST PERFORMED (must choose 1 of 5 methods)
YES NO N/A
(i) Required supervisory load for 24 h followed by the required full load operation; √
(ii) Silent test using load resistor method for full duration test. √
(v) Replace the batteries with a new set having a current date code/capacity/type √
Record battery capacity AH 13
Record the battery terminal voltage after tests are completed. VDC 26.00
ANNUNCIATOR AND REMOTE TROUBLE SIGNAL UNIT TEST & INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.1]
YES NO N/A
Individual alarm and supervisory input zone clearly indicated and separately designated √
Individual alarm and supervisory input zone designation labels are properly identified √
YES NO N/A
Minimum of one alarm zone and one supervisory zone tested per annunciator or sequential display to confirm operation √
Individual alarm and supervisory input zone designation labels are properly identified. √
REMOTE TROUBLE SIGNAL UNIT TEST AND INSPECTION [Ref. CAN/ULC-S536-04, Clauses 5.1.4, 5.4.3]
YES NO N/A
YES NO N/A
Operates as per design and specification, or in accordance with documentation provided in Appendix E. √
DATA COMMUNICATION LINK TEST [Ref. CAN/ULC-S536-04, Clauses 5.1.5, 5.6 Note]
YES NO N/A
Confirm that a trouble signal is received at the control unit or transponder under an open loop fault for each data communication link
(DCL) √
Where fault isolation modules are installed in data communication links serving field devices, wiring shorted on the isolated side,
annunciation of the fault confirmed, and then a device on the source side operated, and activation confirmed at the control unit or √
Where fault isolation in data communication links is provided between control units or transponders and between transponders,
introduce a short circuit fault and confirm annunciation of the fault and operation outside the shorted section between each pair of: √
YES NO N/A
Door Holders √
Pager Transmitter √
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 20th & 21st, 2016
Building Name: Ursuline College Address: 85 Grand Ave West, Chatham Page 1 of 17
Denomy W
0104
Top of Stairs By Room 921 S √ √ A2.3 0014
0104
Exit By 921 M √ √ A2.1 0044
0104
921 Back Hall S √ √ A2.1 0029
By Room 920 H √ √ LB 4
0104
Back Hall off 919 S √ √ A2.1 0027 NL
By Room 918 H √ √ UB 1
0103
Top of Stairs By 918 S √ √ D2.1 0011
0103
Exit By Top of Stairs by 918 M √ √ D2.1 0130
0103
Room 915 RHT √ √ D2.1 0073
0103
Back Room off 915 HT (284-C) √ √ D2.1 0131 Elect. Tested
0103
By Room 916 S √ √ D2.1 0039
By 914 H √ √ UB 1
0104
Top of Stairs to Mech. Rm (Penthouse) S √ √ D3.2 0160
A- Correctly Installed
B- Requires Service, Repairs, Missing or Cleaning UB Upper Booster
C- Alarm Operation Confirmed LB Lower Booster
D- Annunciation Indication Confirmed
E- Circuit Number or Address
F- Supervision and Ground Fault Detection of Wiring to Device Confirmed
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 20th & 21st, 2016
Building Name: Ursuline College Address: 85 Grand Ave West, Chatham Page 2 of 17
By 909 H √ √ NAC-2
0103
By 909 S √ √ D2.1 0037
0103
Chem Lab 908 RHT √ √ D2.1 0030
0103
Room 907 (Prep Room) RHT √ √ D2.1 0031
0103
Back Room off 907 (Prep Room) RHT √ √ D2.1 0032
By 908 H √ √ UB 1
0104
Top of Elevator Shaft RHT Tested By Edwards D2.4 0046
0103
Bio Lab 905 RHT √ √ D2.1 0034
0103
Prep Room 906 RHT √ √ D2.1 0035
0103
Back Room off 906 RHT √ √ D2.1 0041
0103
Room 904 RHT √ √ D2.1 0042
0103
By Room 904 S √ √ D2.1 0036
0103
Top of Stairs at 901 M √ √ D2.1 0032
By 901 H √ √ NAC-2
A- Correctly Installed
B- Requires Service, Repairs, Missing or Cleaning UB Upper Booster
C- Alarm Operation Confirmed LB Lower Booster
D- Annunciation Indication Confirmed
E- Circuit Number or Address
F- Supervision and Ground Fault Detection of Wiring to Device Confirmed
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 20th & 21st, 2016
Building Name: Ursuline College Address: 85 Grand Ave West, Chatham Page 3 of 17
Hall By 804 H √ √ UB 1
0103
Room 805 Main Left RHT √ √ D1.1 0080
0103
Room 805 Main Right RHT √ √ D1.1 0087
0103
Room 805 Back Area RHT √ √ D1.1 0082
0103
Office off Back Area RHT √ √ D1.1 0183
0103
Office By Exit RHT √ √ D1.1 0184
0103
Bottom of Stairs By 801/802 M √ √ D1.1 0184
0103
Bottom of Stairs By 801/802 S √ √ D1.1 0088
0103
Room 805 Rear H √ √ D1.1 0088
A- Correctly Installed
B- Requires Service, Repairs, Missing or Cleaning UB Upper Booster
C- Alarm Operation Confirmed LB Lower Booster
D- Annunciation Indication Confirmed
E- Circuit Number or Address
F- Supervision and Ground Fault Detection of Wiring to Device Confirmed
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 20th & 21st, 2016
Building Name: Ursuline College Address: 85 Grand Ave West, Chatham Page 4 of 17
Prep Room H √ √ UB 1
By 807 H √ √ UB 1
0103
Hall By 808 (Atrium) S √ √ D1.2 0017 NL
0103
Room 808 M √ √ D1.2
0127
0103
Elevator Room RHT √ √ D1.2 0020
0103
Room 809 RHT √ √ D1.2 0018
Custodial Rm By 813 (Main Water Rm) ESV 136 Fire Pump Run
A- Correctly Installed
B- Requires Service, Repairs, Missing or Cleaning UB Upper Booster
C- Alarm Operation Confirmed LB Lower Booster
D- Annunciation Indication Confirmed
E- Circuit Number or Address
F- Supervision and Ground Fault Detection of Wiring to Device Confirmed
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 20th & 21st, 2016
Building Name: Ursuline College Address: 85 Grand Ave West, Chatham Page 5 of 17
Custodial Rm By 813 (Main Water Rm) ESV Tested By C&H 126 2nd Arts
Custodial Rm By 813 (Main Water Rm) FS (Main Water) 409 Denomy Ground
Custodial Rm By 813 (Main Water Rm) ESV 132 Arts Main ESV
By 816 H √ √ LB 3
Hall By Exit H √ √ LB 3
0104
By 815 S √ √ A1.1 0021
A- Correctly Installed
B- Requires Service, Repairs, Missing or Cleaning UB Upper Booster
C- Alarm Operation Confirmed LB Lower Booster
D- Annunciation Indication Confirmed
E- Circuit Number or Address
F- Supervision and Ground Fault Detection of Wiring to Device Confirmed
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 20th & 21st, 2016
Building Name: Ursuline College Address: 85 Grand Ave West, Chatham Page 6 of 17
Stage Left H √ √ LB 3
Stage Right H √ √ LB 3
0104
Auditorium Exit Right South M √ √ A1.1 0140
Auditorium Right H √ √ LB 3
Auditorium Left H √ √ LB 3
0104
Entrance to Orchestra Pit S √ √ A1.1 0015 High
0104
Ramp Off Auditorium Left (West Corridor) S √ √ A1.1 0016
0104
Ramp Exit Near Room 816 S √ √ A1.1 0017
Lobby Northwest H √ √ LB 3
0104
Lobby Northwest M √ √ A1.1 0143
0104
Lobby Northwest- Foyer North S √ √ A1.1 0025
0104
Lobby Southwest M √ √ A1.1 0141
Lobby Southwest H √ √ LB 3
0104
Lobby Southwest- Foyer Centre S √ √ A1.1 0024
0104
Lobby Southwest by W/C- Foyer South S √ √ A1.1 0023
Administration Hallway
0103
Staff W/C RHT √ √ A1.1 0021
0103
By Handicap W/C H √ √ NAC-2
0021
A- Correctly Installed
B- Requires Service, Repairs, Missing or Cleaning UB Upper Booster
C- Alarm Operation Confirmed LB Lower Booster
D- Annunciation Indication Confirmed
E- Circuit Number or Address
F- Supervision and Ground Fault Detection of Wiring to Device Confirmed
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 20th & 21st, 2016
Building Name: Ursuline College Address: 85 Grand Ave West, Chatham Page 7 of 17
Hall By 705 H √ √ UB 1
0103
Hall Doors By 705 M √ √ D1.3 0145
0104
Main Gym Entrance- East M √ √ G1.1 0145
Hall to Changeroom H √ √ UB 1
0104
Boy's Changeroom (West) RHT √ √ G1.2 0043
0104
Boy's Storage Room RHT √ √ G1.2 0044
0104
Girl's Changeroom (East) RHT √ √ G1.2 0041
0104
Girl's Storage Room RHT √ √ G1.1 0042
0103
Boys Change Room Exit M √ √ G1.2 0141
A- Correctly Installed
B- Requires Service, Repairs, Missing or Cleaning UB Upper Booster
C- Alarm Operation Confirmed LB Lower Booster
D- Annunciation Indication Confirmed
E- Circuit Number or Address
F- Supervision and Ground Fault Detection of Wiring to Device Confirmed
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 20th & 21st, 2016
Building Name: Ursuline College Address: 85 Grand Ave West, Chatham Page 8 of 17
Greenhouse H √ √ NAC-2
0103
Greenhouse Exit to # 10 M √ √ C1.1 0405
0104
Hall to Merici @ East Storage S √ √ M1.2 0063 RB
0104
Storage @ Merici Stair (SE) RHT √ √ M1.2 0058
A- Correctly Installed
B- Requires Service, Repairs, Missing or Cleaning UB Upper Booster
C- Alarm Operation Confirmed LB Lower Booster
D- Annunciation Indication Confirmed
E- Circuit Number or Address
F- Supervision and Ground Fault Detection of Wiring to Device Confirmed
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 20th & 21st, 2016
Building Name: Ursuline College Address: 85 Grand Ave West, Chatham Page 9 of 17
Hall By 507 H √ √ UB 1
0104
Hall By 508/ Merici W. Centre Exit S √ √ M1.2 0165
0104
Exit By 508/ Merici Centre W. Exit M √ √ M1.2 0153
Fitness Room H √ √ UB 1
0104
Fitness Room/ Merici NW Exit #4 M √ √ M1.2 0152
A- Correctly Installed
B- Requires Service, Repairs, Missing or Cleaning UB Upper Booster
C- Alarm Operation Confirmed LB Lower Booster
D- Annunciation Indication Confirmed
E- Circuit Number or Address
F- Supervision and Ground Fault Detection of Wiring to Device Confirmed
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 20th & 21st, 2016
Building Name: Ursuline College Address: 85 Grand Ave West, Chatham Page 10 of 17
Hall By 610 H √ √ LB 2
0103
Hall By 609 S √ √ M2.1 0276
Hall By W/C H √ √ LB 2
0103
Sink Room By W/C RHT √ √ M2.1 0267
0103
Hall By 608 S √ √ M2.1 0272
0103
Room 608 Storage RHT √ √ M2.1 0273
0103
Hall By 607 S √ √ M2.1 0271
Hall By 606 H √ √ LB 2
0104
Top of Elevator Shaft RHT √ √ M2.4 -
0067
0103
Hall By Storage/Computer Storage S √ √ M2.1 0270
0103
Hall on Ramp at Stair S √ √ M2.1 0268
0103
Top of Stairs at 601/ Centre Stair S √ √ M2.2 0262
0103
Exit By 601/ Merici @ Centre Stair M √ √ M2.1 0377
0103
Custodial Rm RHT √ √ M2.1 0267
Exit By 601 H √ √ LB 2
0103
Hall By 601 S √ √ M2.1 0263
0103
In Room 602 DS √ √ M2.8 0266 (above tile)
0103
Hall By 605/ Merici at South Stair S √ √ M2.2 0258
0103
In Room 604 DS √ √ M2.7 0265 (above tile)
A- Correctly Installed
B- Requires Service, Repairs, Missing or Cleaning UB Upper Booster
C- Alarm Operation Confirmed LB Lower Booster
D- Annunciation Indication Confirmed
E- Circuit Number or Address
F- Supervision and Ground Fault Detection of Wiring to Device Confirmed
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 20th & 21st, 2016
Building Name: Ursuline College Address: 85 Grand Ave West, Chatham Page 11 of 17
Exit By 503 H √ √ LB 1
0104
Hall By Chapel/ 505 S √ √ M1.1 0061
0104
Hall By 501 S √ √ M1.1 0060
0104
Custodial Room RHT √ √ M1.1 0062
0104
Exit By 501 M √ √ M1.1 0151
Exit By 501 H √ √ LB 2
Exit By 403 H √ √ LB 1
0104
Stairwell Storage South RHT √ √ M2.2 0068
0104
Staff Room Exit to Hall M √ √ M1.3 0158
A- Correctly Installed
B- Requires Service, Repairs, Missing or Cleaning UB Upper Booster
C- Alarm Operation Confirmed LB Lower Booster
D- Annunciation Indication Confirmed
E- Circuit Number or Address
F- Supervision and Ground Fault Detection of Wiring to Device Confirmed
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 20th & 21st, 2016
Building Name: Ursuline College Address: 85 Grand Ave West, Chatham Page 12 of 17
Old Gym H √ √ UB 3
0103
Servery HT √ √ C1.1 0300 Elect. Tested
0103
Servery HT √ √ C1.1 0300 Elect. Tested
A- Correctly Installed
B- Requires Service, Repairs, Missing or Cleaning UB Upper Booster
C- Alarm Operation Confirmed LB Lower Booster
D- Annunciation Indication Confirmed
E- Circuit Number or Address
F- Supervision and Ground Fault Detection of Wiring to Device Confirmed
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 20th & 21st, 2016
Building Name: Ursuline College Address: 85 Grand Ave West, Chatham Page 13 of 17
By 302 H √ √ LB 2
A- Correctly Installed
B- Requires Service, Repairs, Missing or Cleaning UB Upper Booster
C- Alarm Operation Confirmed LB Lower Booster
D- Annunciation Indication Confirmed
E- Circuit Number or Address
F- Supervision and Ground Fault Detection of Wiring to Device Confirmed
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 20th & 21st, 2016
Building Name: Ursuline College Address: 85 Grand Ave West, Chatham Page 14 of 17
By 304 H √ √ UB 2
0103
By 304/ South Stair M √ √ X2.1 0383
0103
Top of Stairs By 304 S √ √ X2.3 0047
294/ 0103
Hall By Exit # 13/ Student Services S √ √ X1.2 0794 Xavier Lobby
0103
Entrance to Student Services M √ √ X1.1 0390
0103
Custodial Room RHT √ √ 293 0293
Copy Room H √ √ UB 3
Exit to # 12 H √ √ UB 2
0103
Exit to # 12 M √ √ X1.2 0391
By 204 H √ √ UB 2
0103
By 204 M √ √ X1.1 0389
0103
By 205 S √ √ X1.1 0390
0103
By Custodial Supplies/ 207 S √ √ X1.1 0287
0103
Custodial Supplies RHT √ √ X1.1 0289
A- Correctly Installed
B- Requires Service, Repairs, Missing or Cleaning UB Upper Booster
C- Alarm Operation Confirmed LB Lower Booster
D- Annunciation Indication Confirmed
E- Circuit Number or Address
F- Supervision and Ground Fault Detection of Wiring to Device Confirmed
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 20th & 21st, 2016
Building Name: Ursuline College Address: 85 Grand Ave West, Chatham Page 15 of 17
A- Correctly Installed
B- Requires Service, Repairs, Missing or Cleaning UB Upper Booster
C- Alarm Operation Confirmed LB Lower Booster
D- Annunciation Indication Confirmed
E- Circuit Number or Address
F- Supervision and Ground Fault Detection of Wiring to Device Confirmed
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 20th & 21st, 2016
Building Name: Ursuline College Address: 85 Grand Ave West, Chatham Page 16 of 17
Isolators
Tub Beside Fire Alarm Panel ISO √ √
A- Correctly Installed
B- Requires Service, Repairs, Missing or Cleaning UB Upper Booster
C- Alarm Operation Confirmed LB Lower Booster
D- Annunciation Indication Confirmed
E- Circuit Number or Address
F- Supervision and Ground Fault Detection of Wiring to Device Confirmed
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
CAN/ULC S536-04
FIRE ALARM
INDIVIDUAL DEVICE RECORD
Date: July 20th & 21st, 2016
Building Name: Ursuline College Address: 85 Grand Ave West, Chatham Page 17 of 17
A- Correctly Installed
B- Requires Service, Repairs, Missing or Cleaning UB Upper Booster
C- Alarm Operation Confirmed LB Lower Booster
D- Annunciation Indication Confirmed
E- Circuit Number or Address
F- Supervision and Ground Fault Detection of Wiring to Device Confirmed
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
CAN/ULC
EMERGENCY LIGHTING
INDIVIDUAL DEVICE RECORD
Date: July 20th & 21st, 2016
CAN/ULC
EMERGENCY LIGHTING
INDIVIDUAL DEVICE RECORD
Date: July 20th & 21st, 2016
CAN/ULC
EMERGENCY LIGHTING
INDIVIDUAL DEVICE RECORD
Date: July 20th & 21st, 2016
CAN/ULC
EMERGENCY LIGHTING
INDIVIDUAL DEVICE RECORD
Date: July 20th & 21st, 2016
Xavier Wing
94 Exit @ 301 Magnavolt (2) PA-6V4.5 (15) 2 14.02 10:14 267
95 Wheelchair Elevator Hall SPEX 36 (2) PA-6V4.5 (08) 2 13.98 10:16 361 X See Repairs List
96 Hall By 305 SPEX 36 (2) BB 6V4.5 (09) 2 14.10 10:18 271 X See Repairs List
97 Exit By 304 Magnavolt (2) SLA 6V4.5 (15) 2 13.89 10:20 280
98 Stair Exit to Student Serv. Standpro (2) BB 6V4.5 (13) 2 13.86 10:22 289
99 Student Service Entrance SPEX 36 (2) PA-6V4.5 (12) 2 14.06 10:24 291
100 Student Serv. Entrance-Rear Hall SPEX 36 (2) PA-6V4.5 (11) 2 14.07 10:26 259
101 Student Service Back Hall Exit Standpro (2) PA-6V4.5 (11) 2 13.98 10:28 300
102 Stud. Serv. Back Hall Rear Exit #12 SPEX 36 (2) PA 6V4.5 (12) 2 14.01 10:30 298
103 Exit By 204 SPEX 36 (2) PA 6V4.5 (12) 2 13.96 10:32 260
104 Hall By 205 SPEX 36 (2) PA-6V4.5 (13) 2 13.89 10:34 269
105 Centre Hall Mechanical Room 12 ESL 144 (2) PA-6V12 (12) 2 13.81 10:36 296
106 Hall to Wheelchair Elevator SPEX 36 (2) PA 6V4.5 (12) 2 13.80 10:38 280
107 Exit By 201 SPEX 36 (2) BB 6V4.5 (09) 2 14.06 10:40 260 X See Repairs List
108 Exit By 101 SPEX 36 (2) BB 6V4.5 (13) 2 14.13 10:42 290
109 Exit from Wheelchair Ramp SPEX 36 (2) PA 6V4.5 (09) 2 13.82 10:44 280 X See Repairs List
CAN/ULC
EMERGENCY LIGHTING
INDIVIDUAL DEVICE RECORD
Date: July 20th & 21st, 2016
113 Hall @ 105 SPEX 36 (2) PA 6V4.5 (09) 2 14.08 10:52 295 X See Repairs List
114 Exit # 14 (# 6) RG 36 PA-6V7.2 (11) 2 13.99 10:54 257
115 Exit By 104 SPEX 36 (2) PA-6V4.5 (09) 2 13.94 10:56 287
EMERGENCY LIGHTING
REPAIRS LIST
REPAIRS
# LOCATION DEVICE REPAIR COMPLETED
1 Back Hall off 919 C12-72 Replaced Batteries w/ (2) Panasonic PA-6V4.5 08/24/2016
2 Mechanical Rm East (# 31) 12 MSL 360 Replaced Battery w/ (1) EnerSys NP33-12 08/24/2016
3 Mechanical Rm Rear (# 32) 12 MSL 360 Replaced Lamp w/ (1) HR-915 12V Wedge Lamp 08/24/2016
4 Men's W/C (Aud. Hall) C12-72 Replaced (2) PA-6V4.5, (1) 12V9W Remote Head 08/24/2016
5 Hall By Gym SPEX-36 Replaced (1) 202T 12V PC Board 08/24/2016
6 Phys-ed Office (Gym) (# 25) 12 MSL 360 Replaced (2) 12V9W Remote Heads, (1) T6 Lamp 08/24/2016
7 Fitness Mechanical Room (# 21) 12 PCH 350 Replaced Battery w/ (1) EnerSys NP33-12 08/24/2016
8 Fitness Mechanical Room (# 20) RG 36 Replaced Battery w/ (1) Panasonic PA-6V12 08/24/2016
9 Gym SW Exit RG 36 REI Replaced Battery w/ (1) PA-6V7.2 & (1) T6-Lamp 08/24/2016
10 Gym SW Exit By Stage HXSW 36 Replaced w/ (1) 6V9W Double Remote Head 08/24/2016
11 Hall @ Greenhouse Merici SPEX-36 Replaced Batteries w/ (2) Panasonic PA-6V4.5 08/24/2016
12 Hall to Wheelchair Elev. By Exit 9 SPEX-36 Replaced Batteries w/ (2) Panasonic PA-6V4.5 08/24/2016
13 Behind TV & Photocopier RH (x3) Replaced Lamps w/ (3) HR-915 12V Wedge Lamp 08/24/2016
14 Hall By 601 SPEX-36 Replaced (1) Stanpro 202T12V PC Board 08/24/2016
15 Exit By 501 SPEX-36 Replaced PA-6V4.5 & (1) 202T 12V PC Board 08/24/2016
16 Stairwell to Hall (Ground Level) SPEX-36 Replaced Batteries w/ (2) Panasonic PA-6V4.5 08/24/2016
17 Staffroom Exit SPEX-36 Replaced Batteries w/ (2) Panasonic PA-6V4.5 08/24/2016
18 Exit 11 (Near Cafeteria) SPEX-36 Replaced Batteries w/ (2) Panasonic PA-6V4.5 08/24/2016
19 Exit from Wheelchair Lift Standpro Replaced Batteries w/ (2) Panasonic PA-6V4.5 08/24/2016
20 Hall By Cafeteria Kitchen SPEX-36 Replaced Batteries w/ (2) Panasonic PA-6V4.5 08/24/2016
21 Cafeteria Entrance SPEX-36 Replaced Batteries w/ (2) Panasonic PA-6V4.5 08/24/2016
22 By 601 RH (x2) Re-wired remote heads & installed (2) 12V Double 08/24/2016
Remote Heads
23 By Café Exit # 15 RH (x2) 08/24/2016
24 Hall By Exit 15 SPEX 36 Replaced Board w/ (1) Stanpro 202T 08/24/2016
25 310- Dance Entrance SPEX 36 Replaced w/ (2) PA-6V4.5, (1) 202T 12V PC Bd. 08/24/2016
26 Wheelchair Elevator Hall SPEX 36 Replaced Batteries w/ (2) Panasonic PA-6V4.5 09/01/2016
REPAIRS
# LOCATION DEVICE REPAIR COMPLETED
Fire Alarm Devices
1 Fire Alarm Booster Booster 1 Replaced Batteries w/ (2) EnerSys NP12-12 08/24/2016
2 Fire Alarm Booster Booster 2 Replaced Batteries w/ (2) EnerSys NP12-12 08/24/2016
3 By 814 H Replaced Device w/ (1) GIR-HD Genesis Horn 08/24/2016
4 Gym SE H Replaced Device w/ (1) GIR-HD Genesis Horn 08/24/2016
5 Hall By Men's W/C H Replaced Device w/ (1) GIR-HD Genesis Horn 08/24/2016
Additional Comments:
2018 Mallard Road, Unit #1
London, Ontario N6H 5L8
Phone: (519) 657-2063
Fax: (519) 657-2696
DEVICE LEGEND
DEVICE DESCRIPTION
ANN Annunciator
AD Ancillary Device (Note 4)
B Bell
BZ Buzzer
C Chime
CR Control Relay
CT1 Single Input Module (for supervised Class B signal or audio circuits)
CT2 Double Input Module (for supervised Class B signal or audio circuits)
DH Door Hold Open Device
DS Duct Smoke Detector
ET Emergency Telephone
FACP Fire Alarm Control Panel
FH Firefighters Handset
FS Sprinkler Flow Switch
GA 2nd Stage of 2-Stage Pull Station
H Horn
H/S Horn Strobe
HSP Horn Loudspeaker
HT Heat Detector, Fixed Temperature
HT-RES Resetable Heat Detector
K Horn, Klaxon Type
M Manual Pull Station
MAG LOCK Magnetic Door Lock
PS Pressure Switch
RHT Heat Detector, Rate-of-Rise
S Smoke Detector
SA Smoke Alarm, Single Station Type (Note 3)
SP Loudspeaker
SS Sprinkler Supervisory Switch
SV Sprinkler Valve
TS Sprinkler Tamper Switch (Note 2)
V Visual Alarm Appliance
Note 1: Confirmation of wiring supervision to each individual device is only required during installation verification or a complete building audit
of the system and is not required on the annual test.
Note 2: Sprinkler tamper switches cause trouble condition to be annunciated but not an alarm condition.
Note 3: Single station smoke alarms are not part of the fire alarm system but testing of such devices may be required by the authority
having jurisdiction.
Note 4: Identify the specific ancillary devices in the Remark column of Fire Alarm System Device Test and Inspection Record form
183 Exeter Road, Unit A
London, Ontario
PHONE (519) 652-5086
FAX (519) 652-8719
1. GENERAL:
2. CONTROL VALVES:
3. WATER SUPPLIES:
a) Are fire pumps, reservoirs and pressure tanks in good condition? YES
b) Pump rating:
psi boost 50
usgpm 100
5. FIRE HYDRANTS:
11. ALARMS:
a) Are all sprinklers in good condition, free from obstruction, corrosion and loading? YES
b) Are the sprinklers less than 50 years old? (2002) YES
c) Are there spare sprinklers and a wrench in the head cabinet? YES
d) Is the condition of the piping, drain valves, hangers and gauges in good condition? YES
e) Have the sprinklers been checked for the proper temperature rating? YES
NONE
NONE
*Low pressure switch failed. **Requires replacement. Replaced Aug. 24, 2016
The above items are deficient as per The Ontario Fire Code and need to be corrected immediately.
A certificate of inspection cannot be issued until all items under section #16 have been addressed.
Consultation with the local fire prevention office is suggested, if discrepancies occur
NONE
• LIMITATION OF LIABILITY: It is understood and agreed that the INSPECTOR is NOT an insurer and is NOT warranting or
guaranteeing the adequacy, performance or life expectancy of any structure, item, component or system in the building. Further, it is
mutually agreed that the maximum amount of joint and several liability the INSPECTOR can incur for any error, mistakes, omissions,
breach of contract, breach of warrantee, negligent hiring, or any other theory of liability including violation of a statute or consumer
protection act is strictly limited to the FEE PAID for the inspection report.
NOTE: This inspection/test was performed in accordance with The Ontario Fire Code. This inspection does NOT certify that the sprinkler
system installation complies with NFPA, OBC or Ontario Retrofit Reg. #627/92 (an engineer’s report would be required to certify this).
As per the requirements of The Ontario Fire Codes, the inspecting company must submit this report to the local Fire Prevention office
THIS DOCUMENT CERTIFIES THAT THE FIRE ALARM SYSTEM AT THE FOLLOWING LOCATION;
URSULINE COLLEGE~ 85 GRAND AVENUE WEST, CHATHAM
HAS BEEN TESTED & INSPECTED IN ACCORDANCE WITH THE STANDARD FOR THE INSPECTION AND TESTING OF
FIRE ALARM SYSTEMS, CAN/ULC-S536-04. THE SPRINKLER SYSTEM & FIRE HYDRANT HAVE ALSO BEEN INSPECTED
AT THIS LOCATION.
A TEST OF ALL EMERGENCY LIGHTING EQUIPMENT WAS ALSO COMPLETED IN ACCORDANCE WITH CANADIAN
ULC CODES AND DESIGN CRITERIA DESIGNATED BY MANUFACTURER'S SPECIFICATIONS.