Beijing Ameco: Training Manual Jet Fundamentals Aircraft Maintenance
Beijing Ameco: Training Manual Jet Fundamentals Aircraft Maintenance
Beijing Ameco: Training Manual Jet Fundamentals Aircraft Maintenance
Aviation College
Training Manual
Jet
Aircraft
Maintenance
Fundamentals
ATA 24
Electrical Power
JAR-66
Page 1
Lufthansa Technical Training
ELECTRICAL POWER
INTRODUCTION TO ELECTRICAL POWER
Ameco Beijing FUNDAMENTALS
POWER DISTRIBUTION
We have now added more details to the AC and DC power distribution, so that
we can divide it into three parts.
First, the main power distribution provides electrical power to all main
consumers.
Second, the essential power distribution supplies all consumers that are
essential to operate the aircraft safely, and third, the emergency power
distribution system supplies the consumers that are necessary to land the
aircraft safely.
Each part of the distribution system can be supplied with electrical power from
a normal source and, in case of loss of this source, from an alternate source.
The essential power distribution is normally supplied by the main power
distribution system.
In the event of a failure in the main power distribution or its power sources, the
essential power is supplied by the remaining power source as long as any part
of it is available, due to various switching functions.
The emergency power distribution is normally supplied by the main power
sources via the essential power distribution.
In case of total loss of the normal power sources, emergency power distribution
is switched to its alternate power source which is an emergency generator or
the battery.
For Training Purposes Only
ELECTRICAL MONITORING
The control of the electrical power system in modern aircraft is mainly
automatic, but some switching must be performed manually.
This is primarily done from the electrical power control panel located on the
overhead panel of the cockpit.
Here you can see an example of the Boeing 747-400 and of the Airbus A320.
In order to display all the important system data, the ECAM or EICAS system
is used. These two system pages of the EICAS and ECAM system present the
main information necessary to monitor the system operation.
You have probably noticed that the EICAS display on the left shows no
operating parameters, such as voltage or current. This data is available on the
maintenance display page, selecteable via the CMC.
For Training Purposes Only
LOAD SHEDDING
These large loads must be shed or switched off before we switch any power
source on or off on the ground.
This load shedding improves the reliability of the power relays and prevents an
overload of the power source.
Manual load shedding is achieved via a pushbutton on the electrical control
panel.
The pushbutton is called GALLEY on the A320 panel and UTILITY on the 747
panel.
Automatic load shedding is also available if an overload of generators is
detected or must be prevented by the system. This is covered later in this
lesson.
For Training Purposes Only
OK, the generator is now switched off manually by the generator pushbutton,
even if the engine is still running.
TRANSFER BUSSES
In this segment we look at another type of essential power distribution, which is
often used in boeing aircraft.
It comprises two transfer busses, and the associated switching.
The name transfer bus is used, because the bus is automatically transfered-
from the normal power source to the alternate power source by the switching.
Try to find the solution to this challenge.
The captains transfer bus usually supplies the same equipment as an AC
essential bus, such as instruments, navigation and communication systems of
the captain and the FO transfer bus supplies redundant equipment for the first
officer.
The power sources for the two pilots are usually independent.
Only if AC BUS 2 and 3 fail, do both pilots use AC BUS 1 as the common
alternate power source.
There is no DC essential or DC transfer bus in this electrical power system.
They are unnecessary because of the 4 TR Units which make the main DC
power redundant.
For Training Purposes Only
OPERATION EXAMPLE # 1
In our example of the four engine aircraft the AC emergency distribution is
called AC standby bus.
Normally, the AC standby this bus has the same power source as the Captain’s
transfer bus.
But if no main power source is available, the standby bus is switched
automatically to the Static inverter. However, the transfer bus is lost.
If Standby power switch is in the off position the standby AC bus is completely
deenergized. This isolates the bus in case of smoke due to a short circuit and
prevents a battery discharge on the ground when the main power sources are
switched off.
In the battery position the AC standby bus and the battery bus are connected
to the battery, despite the availability of the main power sources. This overrides
the automatic switching if it is not working or allows you to test whether the
battery and static inverter are alright on the ground.
The AUTO position is the normal position during flight. This allows automatic
switching as we have described.
The DC emergency power in this aircraft is provided by a Battery bus.
The Battery Bus is supplied by its normal power source as long as any of the
TR units are working and supplied by a main AC power source .
The Battery bus is automatically switched to the Battery output if normal power
is lost.
For Training Purposes Only
Figure 30 OPERATION
HAM US / kl August 1998 Page 61
Lufthansa Technical Training
ELECTRICAL POWER
MAIN DC, ESSENTIAL AND EMERGENCY
Ameco Beijing FUNDAMENTALS
OPERATION EXAMPLE # 2
Now let’s have a look at the similarities and differences in our two engined
aircraft example.
Here the emergency power consists of two emergency busses which are
powered as long as the main power sources are available.
In case of total loss of main power sources in this aircraft two different
emergency power sources are available. This is as in our previous example,
the battery power, here provided by two individual batteries, and in addition, an
emergency generator.
For Training Purposes Only
DISTRIBUTION COMPONENTS
INTRODUCTION
The main components are the power relays which are used as the switching
devices, the circuit breakers and fuses which are used as safety devices and
current transformers which are used as current measuring devices.
For Training Purposes Only
AC POWER RELAY
For AC switching, two different types of power relays are used: The breaker has two advantages over the contactor. One is that the coil can be
One type is called a contactor and the other type is called a breaker. smaller, because no heat is produced in the coil during the closed state.
The generator power relay number one connects the engine driven generator The second advantage is that the breaker stays closed even when no electrical
number one with the distribution. power is available.
All AC power relays have the same function, independent of their location in
the distribution. This function is to switch the three phase main AC power to
specific parts of the distribution.
Because they perform the same function all AC power relays are basically
similar. They consist primarily of the three high power main contacts which are
operated by an electro magnetic device.
In addition, several auxiliary contacts monitor the switching state for indication,
regulation and protection.
The electromagnetic operating device of a contactor consists of a coil and the
iron armature.
When a current is switched on for the coil, a magnetic field is generated which
moves the armature and the contacts.
The contacts are operated for as long as the current flows. You can see that it
is similar to a standard relay.
The electromagnetic operating device of the breaker type power relay works in
a different way. It needs only a short current pulse to close the contacts and a
second pulse to open or trip the contacts again.
To hold the contacts in the closed state, no current is necessary. This is
because a latching device, normally a permanent magnet, is used to hold the
armature in the operated position.
Here you can compare the three steps in the operation of the breaker type
power relay with the operation of the contactor which we previously explained.
For Training Purposes Only
The first step is identical for both types because the close current in the coil
must generate the magnetic field.
In the second step, the coil current of the breaker is interrupted by auxiliary
contacts and the magnetic field of the permanent magnet holds the armature
down.
To open the power relay contacts again, the magnetic field of the permanent
magnet must be weakened. This is performed by a trip current which flows in
the opposite direction.
FUSE
Fuses and circuit breakers are used to prevent currents that are higher than
the maximum allowed for the cross section of the wire.
A higher current is caused by a short circuit or faulty consumer and can
overheat the wire and generate a fire.
Therefore, when a wire cross section is reduced, such as on busses or
terminals, a circuit breaker or fuse is always installed.
Only the generator feeder lines are not protected by fuses or circuit breakers.
This area is protected by the specific circuits of the GCU.
A fuse is the easiest method of overcurrent protection. It consists mainly of a
metal strip with a cross section smaller than that of the wire it must protect.
When the current exceeds the maximum allowed value for the specific wire, the
metal strip melts and the electric circuit is interrupted before it damages the
wiring. This means that it works like a shear pin in an mechanical linkage, by
acting as the weakest link in the wiring.
When a fuse is blown, it must be replaced after repairing the affected circuit.
For this task spare fuses must be available in the aircraft in a sufficient number.
Replacement of blown fuses is time consuming, therefore, in nearly all aircraft,
circuit breakers are used instead of fuses.
Fuses are only used when the permitted current exceeds 125 amperes and this
is only possible in the DC distribution. In this current range, fuses are also
called current limiters.
For Training Purposes Only
The not to be exceeded current of the wire is labeled as the nominal current of The same type of tag is also used to identify switches or other cockpit controls
the circuit breaker on the front face of the control knob. for the same reason.
The values range from a half ampere for control circuits to 125 amperes for
connections between busses.
The time that is needed to release a circuit breaker depends on the current that
exceeds the nominal value.
On the graph presented here, you can identify the time which is allowed to
release the circuit breaker used in this example.
Figure 37 CB MONITORING
HAM US / kl August 1998 Page 75
Lufthansa Technical Training
ELECTRICAL POWER
DISTRIBUTION COMPONENTS
Ameco Beijing FUNDAMENTALS
CURRENT TRANSFORMER
From the distribution, the generator control unit needs operational parameters
for control, protection and indication.
Whereas, the voltage is directly derived from the measuring point, the current
needs special measuring component. In the AC distribution current
transformers or CTs in short, are used for this task.
Current transformers are available as single phase or three phase components
as shown here.
All current transformers have a hole for each measuring phase. The wires
which carry the current to be be measured are put through these holes.
An iron core is located around each hole which carries a coil wire.
For Training Purposes Only
AC GENERATION
INTRODUCTION
All of these AC power sources generate AC electrical power with a voltage of
115 V and a frequency of 400 Hz.
AC power is generated using two different methods; the first uses a constant
speed generator and the second uses a static inverter.
The constant speed AC generator converts the mechanical input power from
the engine, the APU or the emergency hydraulic motor into the required
electrical power.
For Training Purposes Only
Figure 42 AC POWER
HAM US / kl August 1998 Page 85
Lufthansa Technical Training
ELECTRICAL POWER
AC GENERATION
Ameco Beijing FUNDAMENTALS
Figure 43 AC GENERATION
HAM US / kl August 1998 Page 87
Lufthansa Technical Training
ELECTRICAL POWER
AC GENERATION
Ameco Beijing FUNDAMENTALS
BRUSHLESS GENERATOR
To transfer the exciter current into the rotating part of the generator classical
generators use sliprings and brushes.
However this method is not used on aircraft generators because it has a low
MTBF and produces sparks.
To prevent the disadvantages of using brushes and sliprings all aircraft
generators are brushless generators. Brushless generators consist of the main
generator and an additional generator called the exciter generator.
The exciter generator is an external pole generator. This means that the coils
which produce the magnetic field are located in the fixed part called the stator.
This magnetic field induces an alternating current in the rotating coil of the
exciter generator.
The alternating current is then rectified by diodes to the necessary exciter
direct current for the main generator.
The diodes are located in the rotating part of the generator and form the
rotating rectifier.
For Training Purposes Only
GCU
For Training Purposes Only
GENERATOR COOLING
You already know that the engine driven generator uses a constant speed drive
to change the variable engine speed into a constant input speed.
You also know that in modern aircraft the CSD and the brushless generator are
located in a common component called the integrated drive generator or IDG.
The oil is used mainly for the CSD operation as you will learn later, but it is also
used by the generator.
Oil cooling is always used where practicable because it is very efficient. Oil
cooled generators are smaller and lighter than generators cooled by air.
In addition to the IDG, oil cooling is also used in the emergency generator.
Here the oil from the hydraulic motor which drives the generator can easily be
used.
In some aircraft the APU generator is also cooled by oil, using the APU oil.
Air must be used for generator cooling, if oil cooling is not practicable. This is
true for older aircraft where the generator and the CSD are separate
components and also for most APU generators.
The cooling air is taken from the air inlet of the engine or APU and is available
as long as the engine or APU is running.
Generally the generator cooling reduces the heat that is produced by the load
current in the windings and diodes.
To prevent damage to the generator due to overheat the load current must be
limited. The better the cooling conditions the higher the load current limit
allowed.
For instance oil cooled generators have a higher load limit than air--cooled
ones, and the load limit for some APU generators is lower on ground than in
flight.
For Training Purposes Only
GENERATOR CONNECTIONS
Two types of electrical connections are used.
One is a conventional connector, which provides all low current connections,
like exciter and PMG and the other is a terminal block which we will now look at
in more detail.
The terminal block consists of three bolts, T1, T2 and T3, to connect the three
generator feeder lines and normally one bolt, N, for the connection to neutral.
Some generators, mainly in older aircraft, have three bolts for the connection to
neutral. You will learn the reason for this later.
As all bolts are the same size you must always ensure that the power cables
are connected to the correct terminal bolt. This means that phase A must be
connected to T1, phase B to T2, phase C to T3 and neutral to N.
Aircraft manufacture minimizes the risk of working error, by using a fixed
spacer connecting the cables in the correct sequence or by using color coding.
For Training Purposes Only
STATIC INVERTER
A static inverter converts DC power into AC power without any moving parts.
It is always necessary when only DC power is available but AC power is
required.
One application you should know about already is the emergency static
inverter.
Additional applications of the static inverter on aircraft are the towing inverter
and the VSCF generator.
A towing inverter is used on some aircraft types to provide AC power during
towing of the aircraft. You will see this in the ground power lesson.
VSCF stands for variable speed constant frequency and the VSCF generator is
a new type of engine driven generator.
All static inverters consist, basically, of a transformer and a switch.
The switch contact switches continuously between the two possible positions.
In the upper position, the contact allows a current flow from the plus pole of the
DC power source, via the upper part of the transformer and back to the minus
pole of the power source.
In the lower position, the contact allows a current flow from the plus pole of the
DC power source, via the lower part of the transformer and back to the minus
pole of the power source.
When the current in the primary winding of the transformer changes its
direction, an alternating magnetic field is produced which induces an alternating
current into the secondary winding of the transformer.
The type of static inverter used on aircraft functions in generally the same way
as the basic one, but needs more parts and is more complex.
A filter network is added in the output circuit to get an accurate sine wave AC
power and the switch contact is replaced by solid state switches to achieve
For Training Purposes Only
high reliability.
A beat generator closes the solid state switches at the right time in order to get
the correct output frequency.
Oil System
For Training Purposes Only
CSD COMPONENTS
The real constant speed drive contains the following components for speed
conversion:
A differential gear that is able to add or subtract speeds, an hydraulic
motor -- pump combination to produce the additional speed and a speed control
circuit, to control the speed conversion.
In addition to the components for speed conversion, the CSD contains three
main parts: First an oil circuit, which provides oil for the hydraulic components
and for cooling and lubrication.
Then a disconnect device that allows you to interrupt the CSD input shaft
during flight, and finally several components for system monitoring.
As you have already seen in the previous lesson, modern CSDs are combined
with the generator in one component. This component is called the integrated
drive generator or IDG.
The integreated drive generator or the constant speed drive is mounted on the
engine gear box with a quick attach and detach, or Q-A-D, ring.
The Q-A-D ring, which is also used for other components, allows a quick
replacement of the IDG.
The main component of the speed conversion is the axial differential gear,
therefore constant speed drives are also named AGD drives, for axial gear
differential.
The differential gear transfers the torque from the input to the output and adds
the input speed with an additional speed of an hydraulic motor.
The additional speed, that is added by the differential gear, is produced by an
hydraulic motor. It’s speed and the direction of rotation is controlled by the
hydraulic pressure which is produced by a pump.
In the IDG cutaway you can identify two identical sets of hydraulic
For Training Purposes Only
motor-- pump units. That two small units work together like one big unit , but
with a higher efficiency.
OIL CIRCUIT
The oil is used in the internal oil circuit as the hydraulic fluid for the
motor -- pump unit and for cooling and lubrication.
In the external oil circuit the oil is cooled by an oil cooler.
Here all the main components of the CSD oil circuit are added to our basic
diagram.
The charge pressure pump pressurizes the oil against the charge relief valve to
supply all components that need the oil.
The scavenge pump pumps the oil from the oil sump via a filter to the oil cooler
and back into the CSD oil reservoir.
The charge pressure relief valve controls the working pressure to about
250 psi.
Filters are used in the internal and external oil circuit to clean the oil. Some
filters are equipped with a popout indicator that indicates filter clogging. When a
filter element needs changing, replacement is carried out by following the
corresponding maintenance manual procedures.
The reservoir ensures that enough oil is available for the user in all attitude
conditions. Sight glasses or an oil level indicator allow checking of the correct
oil level. This must be checked periodically to ensure that the oil level is neither
too low nor too high.
The oil pressure switch provides a signal to the monitoring circuit when the
charge pressure drops below 50% of the normal pressure.
The two temperature bulbs provide the oil in and the oil out temperature signals
for monitoring.
Oil coolers use either air or fuel for cooling. Both types are used, one after the
other, in some aircraft.
A pressure fill port is used for oil servicing. Here the oil is pumped into the oil
For Training Purposes Only
circuit until the correct level is reached. This is normally fulfilled when oil leaves
the CSD at an overfill port.
A too low indication together with a high absolute temperature means that the
cooling is not sufficient.
DISCONNECT
The last part of the constant speed drive we have to look at is the disconnect
device.
It consists of four main parts.
These are:
S a clutch
S a worm gear mechanism
S a solenoid
S a reset mechanism.
The clutch of the disconnect device is named a dog clutch, it is normally closed
by a spring and transfers the speed from the gearbox input to the differential
gear.
The CSD must always be disconnected if an overheat or pressure loss in the
oil circuit occurs. This is necessary to prevent damage to the engine gearbox,
the CSD and generator and all other components installed in that area.
The overheat or pressure loss causes the fault light in the IDG pushbutton to
illuminate. The fault light indicates, that this pushbutton must be pressed to
disconnect the CSD.
When the push button is pressed, the solenoid is energized and the lower part
of the worm gear mechanism is released. The lower part is moved up by a
spring and joins the worm gear.
Because of the rotation of the worm gear, the right part of the clutch is moved
against the spring force.
When the clutch is open, the worm gear is no longer driven, but it continues
turning, for a short time, due to the centrifugal force. This is necessary to
achieve a complete disconnect.
For Training Purposes Only
When the disconnect is performed, the input drive shaft and the left part of the
clutch are the only parts of the constant speed drive that still run.
If the input speed is too low, the centrifugal force cannot open the clutch
completely, this can lead to a clutch damage, such as broken teeth.
Consequently, a disconnect must only be performed, if the engine runs with a
minimum of idle speed.
DISCONNECT VERIFICATION
After the disconnect, the result can be checked on the ECAM or EICAS
system.
Here you see the ECAM page as an example.
The only reliable indication, is the voltage and frequency, because they show
absolute zero, if the disconnect was successful.
Any voltage and frequency above zero show that the generator is still running
and therefore the disconnect was not complete.
The label DISC only shows that the disconnect has been performed, it does
not indicate if it has been successfully completed.
When the disconnect pushbutton is pressed with a stopped engine, for
instance, to perform a check, you must reset the CSD immediately before the
engine is started. This is necessary, because if the engine spools up with an
activated disconnect mechanism, the worm gear opens the clutch slowly. This
results in the same condition as when disconnect is performed with engine
speed too low.
The clutch will not open completely and probably be damaged.
For Training Purposes Only
DISCONNECT RESET
The constant speed drive reset is performed when the engine is completely
stopped, by pulling the ring on the CSD housing.
This moves down the lower part of the worm gear mechanism until it is locked
into the solenoid shaft again.
A click sound indicates to you that the worm gear mechanism is locked into the
solenoid shaft. In the same moment the spring closes the clutch again.
As a reset is only possible on ground, inadvertent operation of the disconnect
pushbutton during flight must be prevented. This is performed by a guard that
normally covers the pushbutton.
In some aircraft the IDG pushbutton guard is secured with a thin copper wire.
This wire always breaks when the guard is lifted. This shows you, that the
disconnect pushbutton was probably pressed.
If there is no flight crew report from the last flight present, you can assume that
this happened during the ground time.
To prevent a damage to the IDG during the next engine start, a reset must be
performed.
Other aircraft types use no safety wire. In this case the disconnect circuit is
electrically inhibited as long as the engine is stopped.
There is one final important point you must know concerning the operation of
the disconnect push button. You are not allowed to press the button for longer
than three seconds and for more than once in 60 sec.
For Training Purposes Only
POWER SUPPLY
For Training Purposes Only
Figure 66 GCU
HAM US / kl August 1998 Page 133
Lufthansa Technical Training
ELECTRICAL POWER
GENERAL CONTROL AND PROTECTION
Ameco Beijing FUNDAMENTALS
POWER
RELAYS
VOLTAGE REGULATIONS
In this segment we will start by discussing the regulation functions of the GCU.
These functions can be divided into the regulation functions for generators
working in isolated operation and the regulation functions for generators
working in parallel operation.
There are two regulation functions for isolated generators available.
These are the voltage and frequency regulation. The purpose of these
regulation functions is to control the corresponding generator output parameter
to the specified value.
The voltage regulation controls the voltage for the AC distribution to a constant
value of 115 V. This compensates for the voltage drop on the feeder lines and
inside the generator.
For Training Purposes Only
--Paralled Generator
Switching
Protection
For Training Purposes Only
POR
FREQUENCY REGULATION
The second regulation for isolated generators is the frequency regulation.
It only exists when the frequency of the generator is not already controlled by
the speed regulation of the generator drive.
A frequency regulation loop is necessary for IDG s that use an
electromechanical speed control circuit and for CSMG emergency generators.
In addition, the VSCF uses a comparable regulation loop.
The closed loop circuit compares the actual frequency from the PMG output
with the 400 Hz reference frequency.
Any difference in this comparison is sent to the generator drive, in order to
adjust the generator input speed. You will see this circuit in more detail in the
following segments, because it is also needed for generator parallel operation .
For Training Purposes Only
-Paralled Generator
Switching
Protection
For Training Purposes Only
PARALLELING CONDITIONS
Before a generator can be switched into parallel to another power source,
either for permanent parallel operation or just for a few seconds in the case of
the ”No power break transfer” function, it must be synchronized
The correct voltage is guaranteed by the voltage regulation of each individual
power source and the correct frequency is ensured by the frequency regulation.
However, this is not enough, because, even with identical frequency and
voltage a difference of up to 320 V is present between two power sources if the
phase angle is 180_ apart.
I think you can imagine what would happen if the generator power relay closes
in this situation -- high currents and torques would probably damage the
system. This serious situation can only be solved if, in addition to voltage and
frequency, the phase angle difference is reduced to zero before the generator
is switched on. This is performed by providing a synchronization signal to the
frequency regulation, derived from the voltage differences of the new power
source and the already active power source supplying the main AC bus. This
correction signal produces a small frequency difference between the two power
sources, that will shift the phase angle permanently.
For Training Purposes Only
FUNCTIONS GENERAL
We have already seen that the generator control relay and generator power
relay can be tripped automatically by certain system failures.
The system failures are detected by protection circuits.
These circuits can be divided into circuits which detect failures in the AC
generation, and circuits that detect failures in the distribution. Both groups of
protection circuits are present in all generator control units.
A third group of protection circuits detect failures in parallel operation and,
therefore, are only available in GCU’s used in these systems.
The failure types that are presented here on the left, are detected in all AC
generation systems.
In some aircraft types additional protection circuits are used.
For Training Purposes Only
Figure 82 OVERVOLTAGE
HAM US / kl August 1998 Page 165
Lufthansa Technical Training
ELECTRICAL POWER
GENERAL CONTROL AND PROTECTION
Ameco Beijing FUNDAMENTALS
Figure 83 OVERFREQUENCY
HAM US / kl August 1998 Page 167
Lufthansa Technical Training
ELECTRICAL POWER
GENERAL CONTROL AND PROTECTION
Ameco Beijing FUNDAMENTALS
Figure 84 UNDERVOLTAGE
HAM US / kl August 1998 Page 169
Lufthansa Technical Training
ELECTRICAL POWER
GENERAL CONTROL AND PROTECTION
Ameco Beijing FUNDAMENTALS
Figure 85 UNDERFREQUENCY
HAM US / kl August 1998 Page 171
Lufthansa Technical Training
ELECTRICAL POWER
GENERAL CONTROL AND PROTECTION
Ameco Beijing FUNDAMENTALS
Figure 86 UNDERSPEED
HAM US / kl August 1998 Page 173
Lufthansa Technical Training
ELECTRICAL POWER
GENERAL CONTROL AND PROTECTION
Ameco Beijing FUNDAMENTALS
Figure 87 OVERLOAD
HAM US / kl August 1998 Page 175
Lufthansa Technical Training
ELECTRICAL POWER
GENERAL CONTROL AND PROTECTION
Ameco Beijing FUNDAMENTALS
DIFFERENTIAL PROTECTION
The area of differential protection is located between each generator and the
main distribution center.
Both ends of the area have one set of current transformers. One set for each
generator is located in the distribution and one set is located in the neutral line
of the generator.
For Training Purposes Only
DC GENERATION
INTRODUCTION
Two different components are used for DC power generation. First, the TR
units which are the normal DC power source and second the battery.
Several TR units are installed in the electrical compartment, generally one for
each main DC bus.
The TR unit converts the three phase 115 V AC from the AC power distribution
into 28 V DC for the DC power distribution.
of current transformers.
The value is directly dependent on the current which is needed by the
connected consumers.
The maximum value which is allowed depends on the type of TR unit. This-
maximum value ranges from up to 200 Amp. for continuous operation to
1000 Amp. for a limited time of 1 second.
Figure 97 TR UNITS
HAM US / kl AUGUST 1998 Page 195
Lufthansa Technical Training
ELECTRICAL POWER
DC GENERATION
Ameco Beijing FUNDAMENTALS
AIRCRAFT BATTERY
In the distribution lessons you have learned already that the aircraft battery is
used to supply the emergency power in certain cases and to supply the APU
starter motor for APU start.
These tasks can be performed by two different types of battery installation.
One is shown in this example of a two engine aircraft.
Most aircraft use this type of battery installation. They have one two or even
three batteries which work together to supply either emergency power or the
APU starter motor.
The number of batteries depends mainly on the amount of electrical energy
that must be stored.
For Training Purposes Only
EMERGENCY APU
POWER STARTER MOTOR
NICD BATTERY
All batteries in jet aircraft are of the nickel cadmium type. These tasks cannot be performed in the aircraft, but the line maintenance
This battery type has many advantages over the lead acid type battery which is personnel must check some important items to ensure reliable battery
used in small aircraft and cars. operation until the next workshop visit.
The two main advantages of the nickel cadmium battery are that it causes less The first important item that the line maintenance must observe is to never
maintenance costs and has a better performance at low temperatures. overheat a battery by too many APU start attempts immediately after each
other.
However, special care is necessary during charge and discharge of a nickel
cadmium aircraft battery to guarantee safe and reliable operation. A battery cell overheat reduces the electrolyte level and can melt the plastic
separator. This damages the battery and the cell will probably look like this.
The nickel cadmium battery in electrical power systems contain 20 individual
cells. The second important item to remember is do not discharge a battery below
22 V, because this can inverse the polarity of the weakest cell in the battery.
Normally, each individual cell produces a voltage of about 1.2 V. Because all
cells are connected in series, the complete battery has a nominal voltage If this happens, the battery can’t be recharged in the aircraft. It must be
of 24 V. replaced and recharged in the workshop.
During charging, the voltage of an individual cell rises to 1.5 V. During The line maintenance personnel must also check at certain intervals that the
discharge the voltage drops to 1.0 V when the cell is completely discharged. battery is fully charged.
The voltage in a charged battery cell is produced by the chemical reaction
which occurs between two plates made of different material. These plates are
covered by an electrolyte fluid.
The electrolyte fluid is a strong alkaline solution. Its level rises during charging,
but its specific gravity is not changed.
If the fluid comes into contact with the aircraft structure or human skin, you
must rinse it off immediately with water or an acid solution to prevent corrosion
or injury.
The vent cap can be removed to adjust the electrolyte level in the workshop.
Within the vent cap is a valve which releases any gas overpressure which is
sometimes produced during charging.
The positive and negative plates get a large surface area of active material,
For Training Purposes Only
BATTERY INDICATION
To allow monitoring of battery operation and to check the charging level, two
battery parameters are indicated -- the voltage and the current.
On this example of an airbus aircraft you see that the voltage is displayed on
the ECAM display and the electric panel and the current is shown only on the
ECAM display.
The battery voltage is measured on the hot battery bus and the current is
measured by a shunt located in the battery cable to ground.
A shunt is a small resistor that produces a voltage proportional to the current.
For Training Purposes Only
For instance it switches off the battery contactor when the battery is fully
charged or during discharge on the ground when the battery voltage drops
below 23 V.
GROUND POWER
INTRODUCTION
Normally, one external power source or one APU generator is sufficient to
supply all the consumers needs on the ground.
In our example of the two engine airbus, both power sources can be switched
to the whole network.
Either the APU generator or external power can supply the complete electrical
power distribution.
External power should be used for environmental and economic reasons. On
modern airbus aircraft, external power has automatic priority for ground supply.
For Training Purposes Only
TOWING POWER
Let us now have a look at a different situation where external power and
probably also the APU generator are not available. This is the towing of the
aircraft.
During this aircraft operation, some equipment must be available. This is
primarily the navigation lights, cockpit lights and the indication of the brake
pressure.
The only power source that is left to supply this equipment is the aircraft
battery.
The battery provides 24 V DC but some of the named equipment needs AC
power. Therefore, an additional component must be installed. This component
converts the battery power to 115 V AC.
The AC consumers needed during towing are connected to a towing bus which
is normally supplied by the main AC power distribution.
If this normal AC power distribution is not supplied, the towing static inverter
For Training Purposes Only
When this happens the batteries and the static inverter supply the emergency
power distribution for about five seconds and then the emergency generator
automatically takes over.
This is also a completely automatic function. It’s only in the event of the emer-
gency generator not taking over that the MANual ON push button on the emer-
gency electrical power panel must be pressed by the pilot.
To ensure that the emergency power supply works reliably, an emergency gen-
erator test must be performed on ground on a regular basis.
Figure 119 2 ENGINE AIRCRAFT NORMAL AND FAILURE OPERATION AND SIMULATION
HAM US / kl June 2000 Page 239
Lufthansa Technical Training
ELECTRICAL POWER
SIMULATION
Ameco Beijing FUNDAMENTALS
Figure 120 4 ENGINE AIRCRAFT NORMAL AND FAILURE OPERATION AND SIMULATION
HAM US / kl June 2000 Page 241
Lufthansa Technical Training
ELECTRICAL POWER
SIMULATION
Ameco Beijing FUNDAMENTALS
Figure 121 4 ENGINE AIRCRAFT NORMAL AND FAILURE OPERATION AND SIMULATION
HAM US / kl June 2000 Page 243
Lufthansa Technical Training
ELECTRICAL POWER
SIMULATION
Ameco Beijing FUNDAMENTALS
Page: ccxlv
Ameco Beijing
Aviation College
TABLE OF FIGURES
GENERATOR CONTROL RELAY
SWITCHING FUNCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . 156
GENERATOR POWER RELAY
SWITCHING FUNCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . 158
FUNCTIONS GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162
DIFFERENTIAL PROTECTION . . . . . . . . . . . . . . . . . . . . . . 180
PROTECTION & SWITCHING
IN PARALLEL OPERATION . . . . . . . . . . . . . . . . . . . . 190
DC GENERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194
TR UNIT NORMAL OPERATION . . . . . . . . . . . . . . . . . . . . 194
TR UNIT PROTECTION FUNCTION . . . . . . . . . . . . . . . . . 196
AIRCRAFT BATTERY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 198
NICD BATTERY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
BATTERY INDICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . 204
BATTERY CHARGING PART 1 . . . . . . . . . . . . . . . . . . . . . . 206
BATTERY CHARGING PART 2 . . . . . . . . . . . . . . . . . . . . . . 212
BATTERY CHARGING PART 3 . . . . . . . . . . . . . . . . . . . . . . 214
GROUND POWER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 216
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 216
EXTERNAL POWER CONNECTION . . . . . . . . . . . . . . . . . 220
EXTERNAL POWER AVAILIABILITY . . . . . . . . . . . . . . . . . 220
EXTERNAL POWER ACTIVATION . . . . . . . . . . . . . . . . . . . 222
EXTERNAL POWER DEACTIVATION . . . . . . . . . . . . . . . . 228
GROUND SERVICE POWER 1 . . . . . . . . . . . . . . . . . . . . . . 230
GROUND SERVICE POWER 2 . . . . . . . . . . . . . . . . . . . . . . 236
TOWING POWER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 236
SIMULATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 238
NORMAL OPERATION 2 ENGINE AIRCRAFT . . . . . . . . 238
FAILURE SIMULATION 2 ENGINE AIRCRAFT . . . . . . . . 238
4 ENGINE AIRCRAFT SIMULATION . . . . . . . . . . . . . . . . . 240
FAILURE SIMULATION 4 ENGINE AIRCRAFT . . . . . . . . 240
Page: ccxlvi
Ameco Beijing
Aviation College
TABLE OF FIGURES
Figure 1 SYTEMS NEED ELECTRICAL POWER . . . . . . . . . . . . . . 3 Figure 36 CIRCUT BREAKER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Figure 2 ELECRICAL ENERGY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Figure 37 CB MONITORING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Figure 3 AC + DC POWER DISTRIBUTION . . . . . . . . . . . . . . . . . . 7 Figure 38 RC CIRCUT BREAKER . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Figure 4 ELECTRICAL POWER SOURCES . . . . . . . . . . . . . . . . . . 9 Figure 39 RC CIRCUT BREAKER . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Figure 5 BASIC POWER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Figure 40 CURRENT TRANSFORMER . . . . . . . . . . . . . . . . . . . . . . 81
Figure 6 POWER DISTRIBUTION . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Figure 41 CURRENT TRANSFORMER . . . . . . . . . . . . . . . . . . . . . . 83
Figure 7 ELECRICAL MONITORING . . . . . . . . . . . . . . . . . . . . . . . . 15 Figure 42 AC POWER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Figure 8 MAIN AC POWER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Figure 43 AC GENERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Figure 9 MULTI ENGINE AIRCRAFT . . . . . . . . . . . . . . . . . . . . . . . . 19 Figure 44 THREE PHASE GENERATOR . . . . . . . . . . . . . . . . . . . . . 89
Figure 10 BUS FUNCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Figure 45 3 PHASE CIRCUITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Figure 11 CONSUMERS OF AC POWER . . . . . . . . . . . . . . . . . . . . 23 Figure 46 GENERATOR CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . 93
Figure 12 LOAD SHEDDING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Figure 47 GENERATOR SLIP RINGS AND BRUSHES . . . . . . . . . 95
Figure 13 POWER SOURCE SWITCHING . . . . . . . . . . . . . . . . . . . 27 Figure 48 BRUSHLESS GENERATOR . . . . . . . . . . . . . . . . . . . . . . . 97
Figure 14 BUS TIE SWITCHING . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Figure 49 GENERATOR COOLING . . . . . . . . . . . . . . . . . . . . . . . . . 99
Figure 15 MANUAL BUS TIE SWITCHING . . . . . . . . . . . . . . . . . . 31 Figure 50 ELECTRICAL CONNECTION . . . . . . . . . . . . . . . . . . . . . 101
Figure 16 MAIN POWER 747 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Figure 51 STATIC INVERTER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Figure 17 4 GENERATORS WORK PARALLEL . . . . . . . . . . . . . . . 35 Figure 52 VSCF GENERATOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Figure 18 BUS TIE POWER RELAYS . . . . . . . . . . . . . . . . . . . . . . . . 37 Figure 53 GENERATOR DRIVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Figure 19 EXTERNAL POWER CONTROL . . . . . . . . . . . . . . . . . . . 39 Figure 54 CSD MAIN PARTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Figure 20 EXTERNAL POWER 1+2 . . . . . . . . . . . . . . . . . . . . . . . . . 41 Figure 55 CSD CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Figure 21 POWER SOURCE SWITCHING . . . . . . . . . . . . . . . . . . . 43 Figure 56 FREQUENCY ADJUSTMENT . . . . . . . . . . . . . . . . . . . . . 113
Figure 22 DC POWER SWITCHING . . . . . . . . . . . . . . . . . . . . . . . . . 45 Figure 57 MECHANICAL SPEED CONTROL CIRCUT . . . . . . . . . 115
Figure 23 DC BUS ISOLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 Figure 58 OIL CIRCUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Figure 24 DC POWER SWITCHING . . . . . . . . . . . . . . . . . . . . . . . . . 49 Figure 59 TEMPERATURE INDICATIONS . . . . . . . . . . . . . . . . . . . 119
Figure 25 AC ESSENTIAL POWER DISTRIBUTION . . . . . . . . . . . 51 Figure 60 ABNORMAL SITUATION . . . . . . . . . . . . . . . . . . . . . . . . . 121
Figure 26 DC ESSENTIAL BUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53 Figure 61 UNDER SPEED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Figure 27 AC TRANSFER BUS (BOEING) . . . . . . . . . . . . . . . . . . . 55 Figure 62 DISCONNECT DEVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Figure 28 EMERGENCY POWER . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 Figure 63 ECAM DISPLAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Figure 29 MANUAL SWITCHUNG . . . . . . . . . . . . . . . . . . . . . . . . . . . 59 Figure 64 CSD RESET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Figure 30 OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61 Figure 65 GCU FUNCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Figure 31 EMERGENCY POWER DISTRIBUTION . . . . . . . . . . . . 63 Figure 66 GCU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
Figure 32 EMERGENCY POWER SWITCHING . . . . . . . . . . . . . . . 65 Figure 67 GCU POWER SUPPLY . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
Figure 33 MAIN DISTRIBUTION COMPONENTS . . . . . . . . . . . . . 67 Figure 68 POINT OF REGULATION . . . . . . . . . . . . . . . . . . . . . . . . . 137
Figure 34 AC POWER RELAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69 Figure 69 VOLTAGE REGULATION . . . . . . . . . . . . . . . . . . . . . . . . . 139
Figure 35 FUSES AND CIRCUT BREAKERS . . . . . . . . . . . . . . . . 71 Figure 70 FREQUENCY REGULATION . . . . . . . . . . . . . . . . . . . . . . 141
Page: ccxlvii
Ameco Beijing
Aviation College
TABLE OF FIGURES
Figure 71 LOAD REGULATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143 Figure 106 THERMAL RUNAWAY . . . . . . . . . . . . . . . . . . . . . . . . . . . 213
Figure 72 LOAD DIVISION LOOP BALANCED . . . . . . . . . . . . . . . . 145 Figure 107 BATTERY PROTECTION . . . . . . . . . . . . . . . . . . . . . . . . 215
Figure 73 LOAD DIVISION LOOP UNBALANCED 1 . . . . . . . . . . . 147 Figure 108 2 ENGINE AIRBUS GROUND POWER . . . . . . . . . . . . 217
Figure 74 LOAD DIVISION LOOP UNBALANCED 2 . . . . . . . . . . . 149 Figure 109 BOEING 747 GROUND POWER . . . . . . . . . . . . . . . . . 219
Figure 75 UNBALANCED LOAD DIVISION . . . . . . . . . . . . . . . . . . . 151 Figure 110 GROUND POWER SWITCHING . . . . . . . . . . . . . . . . . . 221
Figure 76 FREQUENCY REGULATION . . . . . . . . . . . . . . . . . . . . . . 153 Figure 111 CHECK LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223
Figure 77 GENERATOR SYNCHRONIZATION . . . . . . . . . . . . . . . . 155 Figure 112 EXTERNAL POWER ENERGIZED . . . . . . . . . . . . . . . . 225
Figure 78 GCR CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157 Figure 113 EXTERNAL POWER INTERLOCK CIRCUIT . . . . . . . 227
Figure 79 GCB CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159 Figure 114 DEENERGIZING ELECTRICAL NETWORK . . . . . . . . 229
Figure 80 GENERATOR POWER RELAY . . . . . . . . . . . . . . . . . . . . 161 Figure 115 GROUND SERVICE BUSSES . . . . . . . . . . . . . . . . . . . . 231
Figure 81 GENERATOR PROTECTION CIRCUTS . . . . . . . . . . . . 163 Figure 116 GROUND SERVICE SWITCH . . . . . . . . . . . . . . . . . . . . 233
Figure 82 OVERVOLTAGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165 Figure 117 EXTERNAL POWER NOT IN USE . . . . . . . . . . . . . . . . 235
Figure 83 OVERFREQUENCY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167 Figure 118 GROUND SERVICE AND TOWING POWER . . . . . . . 237
Figure 84 UNDERVOLTAGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169 Figure 119 2 ENGINE AIRCRAFT NORMAL AND FAILURE
Figure 85 UNDERFREQUENCY . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171 OPERATION AND SIMULATION . . . . . . . . . . . . . . . . . . . . 239
Figure 86 UNDERSPEED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173 Figure 120 4 ENGINE AIRCRAFT NORMAL AND FAILURE
OPERATION AND SIMULATION . . . . . . . . . . . . . . . . . . . . 241
Figure 87 OVERLOAD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175
Figure 121 4 ENGINE AIRCRAFT NORMAL AND FAILURE
Figure 88 OPEN PHASE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177 OPERATION AND SIMULATION . . . . . . . . . . . . . . . . . . . . 243
Figure 89 DIFFERENTIAL PROTECTION . . . . . . . . . . . . . . . . . . . . 179
Figure 90 DIFFERENTIAL PROTECTION . . . . . . . . . . . . . . . . . . . . 181
Figure 91 NEUTRAL POINT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183
Figure 92 CURRENT TRANSFORMER . . . . . . . . . . . . . . . . . . . . . . 185
Figure 93 SHORT CIRCUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187
Figure 94 WRONG WIRE ROUTING . . . . . . . . . . . . . . . . . . . . . . . . 189
Figure 95 BTR SWITCHING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191
Figure 96 BTR SWITCHING STEP 2 . . . . . . . . . . . . . . . . . . . . . . . . 193
Figure 97 TR UNITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
Figure 98 PROTECTION CIRCUTS . . . . . . . . . . . . . . . . . . . . . . . . . 197
Figure 99 BATTERY INSTALLATION 1 . . . . . . . . . . . . . . . . . . . . . . . 199
Figure 100 BATTERY INSTALLATION 2 . . . . . . . . . . . . . . . . . . . . . 201
Figure 101 Ni Cd BATTERY CELL . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
Figure 102 BATTERY MONITORING . . . . . . . . . . . . . . . . . . . . . . . . 205
Figure 103 BATTERY CHARGING . . . . . . . . . . . . . . . . . . . . . . . . . . 207
Figure 104 BATTERY CHARGER . . . . . . . . . . . . . . . . . . . . . . . . . . . 209
Figure 105 BATT: CHARGER USED AS TR-UNIT . . . . . . . . . . . . . 211
Page: ccxlviii