TESTING Armature Windings
TESTING Armature Windings
TESTING Armature Windings
To check the condition of the armature windings, the armature will probably have
to be removed from the motor. However, if the motor design has external brush
holders, you can unscrew the brush caps and remove the brushes. Depending
upon brush size, this may allow access to the commutator without removing the
armature from the motor.
The first check to see if your armature windings are shorted is the 180°
Resistancetest. A volt/ohm meter can be used to check the resistance of the
series windings connected between the two commutator bars of each coil. Set the
meter to measure resistance (Ohms) and then measure the resistance from two
commutator bars 180° across from each other. Rotate the armature and check
the resistance between every pair of bars on the commutator. Figure 3 depicts a
32 bar commutator, so this check must be done between each of the 16 pairs.
The resistance you will measure is dependent upon the number of turns in each
coil and the gauge of wire used. It is also dependant upon the operating voltage
for which the motor is designed. For example, a 90 Vdc motor will have smaller
conductors and more turns per coil to raise resistance, whereas, a 12 Vdc motor
will have larger conductors and less turns per coil to lower resistance. Though you
probably will not know the armatures intended resistance value, each
measurement should read about the same. If the resistance drastically varies,
there could be a problem with the
windings. A drop in resistance could indicate a short between wires in the coil. A
huge spike in resistance could indicate that a wire is burned through or broken,
interrupting the circuit.
Test #2
Test #3
The third and final test is to measure the resistance of every commutator bar to
the iron armature stack. If the motor armature stack is directly pressed onto the
armature shaft, you can use the armature shaft for the measurement. However,
in some cases, even the armature shaft is insulated from the armature stack. In
that case, you will have to measure from each commutator bar to the iron
armature stack directly. In either case, the commutator bars should never have
electrical continuity to the armature stack and/or the armature shaft.
If any of these measurements fail, it can be assumed that the armature is
damaged.