Siemens Mammomat 300 Installation and Startup Instructions

Download as pdf or txt
Download as pdf or txt
You are on page 1of 93

Ins ta lla tiona nd Sta rt-Up Ins tru ctions

Reg is ter 3
RXB7-120 .0 33.0 1.10 .0 2 eng lis h
Repla ces :RX B7-120 .0 33.0 1.0 9.0 2 0 5.98

W eiterg a be sow ie Vervielfä ltig u ng dieser Unterla g e, Verw ertu ng u nd Proprietry da ta , com pa ny confidentia l. Allrig hts reserved.
M itteilu ng ihres Inha lts nichtg es ta ttet, s ow eitnicht a u sdrü ck lich zu g e- Confié a titre de s ecret d'enterprise. Tou s droits réservés .
s ta nden. Zu w iderha ndlu ng verpflichtenzu Scha deners a tz. Alle Confia do com o s ecreto indu s tria l. Nos reserva m os todos los derechos .
Rechte fü r denFa llder Pa tenterteilu ng oder G M -Eintra g u ng vorbeha lten.
Installation and Start-Up Instructions 0-1
Table of contents, Revision status

Page

1 Prerequisites 1-1
Meters and appliances, tools, notes
Meters and appliances required 1-1
Tools required 1-1
Start-up, DHHS and X-ray decree area of application 1-2
Important notes on start-up 1-2
Checking and recording for the area of application of the
X-ray decree (§16 Germany) 1-2
Checking and recording for the DHHS area of application 1-3
Note on delivery state 1-4

2 Protective measures 2-1


Protective measures 2-1

3 Preparatory work 3-1


General 3-1
Scope of delivery 3-1
Unpacking the stand 3-2
Unpacking 3-2
Removing the transport safeguards 3-3
Removing the swivel-arm system transport safeguard 3-3
Transport safeguard for the lifting carriage 3-3
Transport safeguard for the rotary motion 3-4
Protective strips for the metal curtain 3-4
Unpacking the generator and mounting the radiation field 3-5

4 Installing the generator and the stand 4-1


Arranging the components 4-1
Removing the generator cover 4-2
Installing the cable ducts 4-3
Laying the cable harness 4-4
Aligning the stand 4-5

5 Cable connections 5-1


EMC measures 5-1
EMC measures at the cable entry 5-1
Fitting the hose clamps and ferrite sleeves 5-1
EMC measures on the bottom plate 5-3
Fitting the cables X1, X8 and X9 on the bottom plate 5-3
Connecting the stand cable-harness 5-4
The high-voltage connectors, alternative types 5-4
Connecting the high-voltage connector 5-5

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
0-2 Installation and Start-Up Instructions
Table of contents, Revision status

Connecting the cable harness to the generator 5-6


Mains connection 5-8
Connecting the incoming mains to the
stand (400 V, 2-phase) 5-8
400 V 2-phase connection 5-8
Connecting the mains supply to the generator 5-9
Measures for changing from 2-phase to 1-phase connection 5-10

6 Modifying the object tables 6-1


Modifying the object tables 18 cm x 24 cm for thick cassettes 6-1
Modifying the object tables 24 cm x 30 cm for thick cassettes 6-2

7 Mains connection and power supply 7-1


Checks before powering up the generator 7-1
Measuring the line resistance 7-1
Checking the line voltage in the generator 7-2
Checking the supply voltages 7-3

8 Attaching the swivel-arm covers 8-1


Attaching the swivel-arm covers 8-1
Arranging the swivel-arm system 8-1
Connecting the cables to control-button board and
patient handles 8-1
Attaching the covers 8-2

9 Checking the microprocessors 9-1


Microprocessors 9-1

10 Checks without high voltage 10-1


Checks without high voltage 10-1

11 Checks with high voltage 11-1


Preparation 11-1
Checking x-ray tube high voltage, tube current and
mAs values 11-2
Tube current reduction 11-2
Oscilloscope diagrams 11-3

12 Start-up and functional test of the IONTOMAT 12-1


Checking and programming with the service PC 12-1
Sensitivity 12-1
Sensitivity correction 12-2
Correction curve 12-2

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
Installation and Start-Up Instructions 0-3

Other film/screen combinations 12-3


Correction curve diagrams 12-4
Checking the film density 12-8
Checking the automatic transparency adaption 12-9
Checking cut-off dose and resolution (§16 Germany) 12-10
Output values of constancy testing (§16 Germany) 12-11

13 Further programming 13-1


Setting the real time clock 13-1
Prerequisite 13-1
Setting the time in the mammomat 13-1
Setting the tube-current reduction 13-1
Reducing the generator power 13-2

14 Checking the swivel-arm system 14-1


Rotary motion 14-1
Vertical adjustment 14-2
Emergency stop 14-3

15 Field light 15-1


Checking and adjusting the field light time 15-1
Checking the field light time 15-1
Adjusting the field light time 15-2

16 Checking the compression device and OPCOMP 16-1


Checking the compression device 16-1
Checking the OPCOMP 16-3

17 Checking the exposure blocking 17-1


Checking the exposure blocking 17-1

18 Checking the radiation field limitation 18-1


Checking the radiation field limitation 18-1
General 18-1
Measuring procedure 18-1
Evaluation 18-2

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
0-4 Installation and Start-Up Instructions

19 Final procedures 19-1


Service PC and measuring instruments 19-1
Recording the programmed values 19-1
Reading the exposure counter and deleting the
error memory 19-1
Removing the measuring instruments 19-2
Checking the protective grounding resistance 19-2
Mounting the cable duct covers 19-2
Mounting the stand covers 19-3
Mammomat stand with separate rear side covers 19-3
Mammomat with single rear cover 19-4
Fitting the cable outlet cover 19-5
Mounting the front cover onto the generator 19-5
Final protective grounding resistance test 19-6
Face shield 19-6
Warning label on control panel 19-7

20 Options 20-1
Bolting the stand/generator to the floor 20-1

21 Appendix 21-1
Working with the service PC 21-1
Description of the syntax used in these instructions 21-1
Connecting the service PC 21-2
Measuring protocol 21-3

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
Prerequisites 1-1

Meters and appliances, tools, notes


Meters and appliances required
NOTE!
Calibrated instruments are required.

• Line resistance meter 44 15 733 RV090.


• Protective ground-wire tester 44 15 899 RV090.
• Oscilloscope, e.g TEKTRONIX 314.
• Digital multimeter incl. mAs meter.
• Densitometer e.g PDA 81.
• Service PC (e.g Siemens-Nixdorf PCD 3NSX/20 or similar) with connecting cable
(PC-Generator), part no. 96 00 440 RE999.
• Normi 7 test body (provided by the customer) or SIB phantom Type 42 001 (PTW or
INAK).
• Centring cross, part no. 96 60 051 RE 999.
• Plexiglass plates, three plates measuring150 mm x 150 mm x 20 mm and one plate
measuring 150 mm x 150 mm x 10 mm, part no. 85 49 438 and 97 88 423 respective-
ly.

WARNING!
For safety reasons, the existing protective ground conductor in the power cord must un-
der no circumstances be disconnected when operating the oscilloscope. For those mea-
surements, in which any resulting ground loop may falsify the measuring result, use the
differential amplifier (difference measurement).

Tools required
• Standard installation tool kit.
• Torque wrench for bolting the stand/generator to the floor (optional).
• Electrical screwdriver with adjustable torque is recommended.

NOTE!
Checks and /or adjustments, which must be made with X-ray radiation switched on, are
marked with the radiation warning symbol:

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
1-2 Prerequisites

Start-up, DHHS and X-ray decree area of application


Important notes on start-up
The MAMMOMAT 300 is adjusted, programmed and tested in the factory, leaving only
the adaption to the on-site mains voltage and the functional tests to be performed.

When the measurements to be made (kV, mAs, etc.) are within the tolerances stated in
these instructions, this confirms that the settings made in the factory have not changed and
the equipment is fully serviceable.

The measured values marked with >> in section 11 shall be entered in the test certificate
provided.

The service PC is required only for programming according to:


• Section 11, Checks with high voltage
• Section 12, Start-up and functional test of the Iontomat
Programming the "Correction curve"
Setting the "sensitivity" (film density)
Setting the "sensitivity correction" (adaption to different exposure techniques)
• Section 13, Further programming
• Section 19, Final procedures
Recording the programmed values.
Reading the exposure counter and deleting the error memory.

NOTE!
If the generator is switched off with the Service PC connected, wait approximately 5 sec-
onds before switching it on again.

Checking and recording for the area of application of the X-ray decree
(§16 Germany)
In the area of application of the X-ray decree, an acceptance test certificate is supplied,
with most of the data filled in by the factory.

Only:
• the cut-off dose
• the resolution of the film/screen systems used, and
• the output values of the constancy test

must be determined by the owner of the equipment and recorded in the acceptance test
certificate. Furthermore, the front page of the acceptance test certificate must also be com-
pleted with the operator´s data.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
Prerequisites 1-3

Checking and recording for the DHHS area of application


In the area of application of the DHHS regulations, maintenance measurements must be
made according to the instructions "DHHS Maintenance Schedule and User´s Spot
Checks" RX B7-120.101... (included in the "DHHS Supplements to the operating instruc-
tions" RX B7-120.203...).

Sections
• Required labels.
• Radiation ON indicators.
• Manual termination of exposure.
• Checking the maximum adjustable mAs with the following kV-values.
• Filters in beam limiting device (BLD).
• Reproducibility.
• kVp-accuracy.
• mAs-accuracy.
• Automatic exposure control (AEC).
• Coincidence of radiation field/image receptor.
• Alignment of light field/x-ray field.
• Illuminance of light localizer (light field).
• Shut-down of motor-driven compression movement.

The result must be recorded in "Measurement certificate" RX B7-120.037...

Some of the values to be determined can be taken from the acceptance test certificate.

The radiation-field limitation is set at the factory and recorded in the acceptance test cer-
tificate.

If the measurements to be made concerning the radiation-field limitation are within the
tolerances stated in these instructions, this confirms that the settings made at the factory
have not changed.

Note on delivery state


The MAMMOMAT 300 has been tested and adjusted at the factory, and should therefore
be ready for operation after completion of the installation.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
1-4 Prerequisites

This page intentionally left blank.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
Protective measures 2-1

Protective measures
Prior to any intervention in the equipment, disconnect it from the power
supply with the main circuit-breaker.

WARNING!
If the system is only switched off at the control panel or with S2/D711, line voltage will
still be present at the generator line connection, line filter Z1, Z2, transformer T1, trans-
former T10 and p.c. board D711 (see wiring diagram).

To prevent accidental triggering of high voltage cable and radiation, set the switch S2 (SS)
on p.c board D702 to "OFF" (lower position) (no triggering of the SS relay).

WARNING!
After shut-down of the system, there may still be about 380 V DC present on the interme-
diate circuit. This will be indicated by LED V24 on p.c. board D 710. The voltage will
drop to less than 30 V within about 3 minutes, the LED goes out at about 30 V.

CAUTION!
The p.c. boards contain electrostatic highly sensitive components requiring particular
care in their handling (ground before making contact and place only on a conductive sur-
face, see Technical Information TI 219).

Before removing or inserting a p.c. board, switch off the equipment.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
2-2 Protective measures

This page intentionally left blank.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
Preparatory work 3-1

General
Scope of delivery
The MAMMOMAT 300 is packed in one crate and one cardboard box:

Crate (length 2140 mm, width 800 mm, height 1375 mm)

The crate contains:

• Compression plate.


Object table (Bucky).

Diaphragm
} packed together in a separate box

• Stand with X-ray tube assembly and base plate.

• Cover panels

• Installation material

• Miscellaneous small parts

• Stanchions for the lead-glass pane (radiation shield).

• Cable ducts

• Technical documents

Cardboard box (lenght 1210 mm, width 820 mm, height 700 mm)
The cardboard box contains:

• Generator with integrated control panel, high-voltage generator and base plate.

• Lead-glass pane

Unpacking

As a general rule, the directional marks on the crates should be observed during transport,
storage and unpacking.

The stand crate is bolted together, while the cardboard box is secured with plastic straps.

CAUTION!
Wear safety footwear.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
3-2 Preparatory work

Unpacking the stand

4
1
1

3 2

MAM00080
Figure 1 Unpacking the stand

Unpacking
1 Open the stand crate by removing the top (1) and then the side wall (2).
2 Take out all enclosed packages (accessories, installation material, cover panels etc.)
from the crate.
3 Remove the wooden supports.
4 Remove the remaining walls (3).
5 Upend the stand (4) , with pallet (5) (two persons are required).
6 Loosen the four bolts (6) and remove the pallet (5).

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
Preparatory work 3-3

Removing the transport safeguards


Removing the swivel-arm system transport safeguard

1
2

MAM00081
3

Figure 2 Swivel-arm system transport safeguard

1 Loosen the transport safeguard nuts (1) and remove the tube head screws (2).
2 Push the red transport safeguard (3) inwards, away from the tube head.

NOTE!
Removal of the swivel-arm system transport safeguard is done after the equipment has
been powered up, see further section "Attaching the swivel-arm covers", page 8-1.

Transport safeguard for the lifting carriage

1
MAM00082

Figure 3 Transport safeguard for the lifting carriage

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
3-4 Preparatory work

1 Loosen the two screws (1) and remove the red transport safeguard (2).

NOTE!
The lifting carriage transport safeguard shall be kept for service purposes.

2 Cut and remove the cable tie securing the balancing spring during transport.

Transport safeguard for the rotary motion

MAM00083
Figure 4 Transport safeguard for the rotary motion

1 Remove the transport safeguard screw (1) to enable rotary motion.


The screw (1) should be kept for future need.

Protective strips for the metal curtain

2
MAM00084

Figure 5 Protective strips for the metal curtain

The edges of the metal curtain are very sharp and are therefore provided with protective
strips (1) on delivery. These strips must always be applied onto the edges of the metal cur-
tain during service and maintenance work.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
Preparatory work 3-5

CAUTION!
The protective strips must be removed from the metal curtain before any vertical adjust-
ment of the swivel-arm system is performed.

Holders (2) for storing the protective strips when not in use, are provided on both sides of
the curtain, see Figure 5.

Unpacking the generator and mounting the radiation


shield

1 MAM00085

Figure 6 Unpacking the generator

1 Open the cardboard box by cutting the plastic straps.


2 Lift out the lead-glass pane and put it away in a safe place.
3 Remove the protective cover from the generator.
4 Upend the generator (1) and lift it off the pallet (2) (two persons are required).
5 Mount one stanchion (3) for the lead-glass pane (4) onto the generator.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
3-6 Preparatory work

6 4 3 7

MAM00086
6 Insert sheet-metal strip (5) (additional radiation protection) and vibration absorbing
strip (6) into both stanchions.
7 Fit the lead-glass pane (4) into the groove of the stanchion and keep it in position
while mounting the other stanchion onto the generator.
8 Cover the holes with plastic caps (7).

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
Installing the generator and the stand 4-1

Arranging the components


1 Position the stand and the generator in accordance with installation plan and Figure
1 below.
640

150
1
2
3
1091

90

708

MAM00088
700 700 700 700
1400
540

Figure 1 Installation, top view

Cable duct (1) and generator (3) with radiation shield (2) can be installed optionally
to the left or to the right of the the stand. Maximum cable length between stand and
generator is approximately 3.5 meter.
Radiation shield (2) perpendicular to visual line between generator and focus of the
tube head (4) according to Figure 1.
Recommended minimum distance to wall and generator base plate respectively is 700
mm (shorter distances may be used at the customer´s desire, if in compliance with lo-
cal regulations).
For the installation of the cable duct, a minimum distance of 150 mm between wall
and stands is required.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
4-2 Installing the generator and the stand

Removing the generator cover


1 Pry loose the plastic strip (1) and remove the sixteen screws (2), eight on each side.

NOTE!
Pay special attention to the contact washers (there are four contact washers on either
side). They are needed again when reassembling the front cover to establish protective
ground connection and to fulfil EMC (Electro Magnetic Compatibility) requirements.

2 Remove the front cover (3) from the generator.

MAM00091
3
1

Figure 2 Removing the generator cover

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
Installing the generator and the stand 4-3

Installing the cable ducts


1 Position the cable ducts (1) to the stand and the generator respectively.
2 Leave sufficient space, approx 10 mm between the cable ducts (1) and the base plate
of the stand (3) to allow for the mounting of the cable outlet cover (4).
3 Check that the cable duct (1) is slightly overlapped by the cable outlet cover (4).

4 1
5

10 mm
6

MAM00089
7

Figure 3 Installing the cable ducts (top view)

4 Mark the outlines of the cable ducts (1) on the floor.


5 Cut the bottom of the cable ducts (6) and the cable duct cover (5) to proper length.

NOTE!
Figure 3 shows a right- angled installation of the cable ducts. If the generator is to be in-
stalled at an other angle to the stand, you just have to cut the cable ducts correspondingly.

6 Fasten the bottom plate of the cable ducts (6) to the floor according to marking, using
double-sided adhesive tape.
7 Cover the cable entry at the generator that is not used with the enclosed cover plate
(7).

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
4-4 Installing the generator and the stand

Laying the cable harness


NOTE!
Remove the transport safeguards which consists of cable ties (four around the cable har-
ness and one around each shield cable end).

1 Separate the cable harness.


2 Lay the stand cable harness in the cable duct, as shown in Figure 4, all the way to the
generator.

1 2
3
4

MAM00092
5

MAM00087
1
4
2
3

Figure 4 Laying the cable harness

The cable harness consists of four shield cables, see Figure 4.

Pos in fig. 4 Description

1 High voltage cable H1.


2 IONTOMAT signal cable X11.
Unit control cable X1.
Power supply cable X14.
3 Anode rotation cable X9.
Filament cable X8.
4 Mains supply cables:
L1
L2
Protective ground.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
Installing the generator and the stand 4-5

3 Fit the cable duct cover (5) on the cable ducts.

Aligning the stand


1 Align the stand vertically by means of the levelling screws (1) .
For adjustment of the levelling screws, use a ratchet spanner 1/2" with extension
(without socket).

NOTE!
It is important that all six levelling screws bear against the floor to ensure optimum sta-
bility of the stand.

2 Cover the levelling screws with the cover discs supplied.

Figure 5 Levelling screws MAM00090

NOTE!
If bolting to the floor is required, please refer to section 20 page 1.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
4-6 Installing the generator and the stand

This page intentionally left blank.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
Cable connections 5-1

EMC measures
The following measures are required to ensure electromagnetic compatibility of the
equipment.

EMC measures at the cable entry


Fitting the hose clamps and ferrite sleeves
3cm

MAM00100
Figure 1 Cables from the stand

1 Lay the cable harness from the stand to the generator and leave approximately 3 cm
of the shielding at the U-bracket, see Figure 1.
If the cable harness is too long put away free cable length as ahown in Figure 2.
2 Fit on a hose clamp (3) on each cable.
Hose clamps are included in the delivery.
3 Fold the shield braid (1) backwards over the U-bracket (2) on each cable and clamp
with a hose clamp (3).

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
5-2 Cable connections

2
4 3

3
2 1

MAM00098
Figure 2 Ferrite sleeves and hose clamps

4 Provide each incoming cable with a ferrite sleeve (4) except for mains supply cables
L1 and L2 and the ground wire which shall be laid together in one and same ferrite
sleeve. Ferrite sleeves are included in the delivery.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
Cable connections 5-3

EMC measures on the bottom plate


Fitting the cables X1, X8 and X9 on the bottom plate

3 4 2

MAM00099
Figure 3 Bottom plate

1 Fit the bottom plate at the bottom of the generator stand as shown in Figure 3.
2 Carfully cut away the insulation on cables X1, X8 and X9 to lay bare the shield braid
(1).
3 Select proper clamps (2) with regard to the thickness of the cables, cable clamps in
different sizes are provided on the bottom plate.
4 Fit the clamp (2) over the shield braid and screw tight to ensure satisfactory contact
between shield braid and clamp.
5 Install and tighten the four screws (3) and contact washers (4) at the bottom plate.

NOTE!
Cable X9 shall be clamped to the side wall of the cabinets, if this is not already done see
Figure 7 in this section.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
5-4 Cable connections

Connecting the stand cable-harness


The high-voltage connector, alternative types

3
3

1
1

2
2
MAM00161

MAM00093
Type A Type B

Figure 4 The high-voltage connectors, alternative types

NOTE!
The high-voltage connector (1) is factory-adjusted for correct fit. Mount the angular ca-
ble-sleeve halves and sleeve nut (Type B only). The high-voltage connector shall be in-
serted with silicone oil, silicone-rubber ring (2) and silicone-rubber disc (3). Lubricate
the silicone-rubber disc and the pins with silicon oil before mounting the disc. Make sure
that there aren’t any air bubbles between the disc and the connector.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
Cable connections 5-5

Connecting the high-voltage connector

3 3
1

2 2

4 4
1

MAM00243
MAM00162

tillf00162
Type A Type B

Figure 5 Connecting the high-voltage connector

Type A
1 Plug in the high-voltage connector (1) at H1.
2 Tighten the sleeve nut (2) by hand.
3 Tighten the stop screws on the sleeve nut.
4 Position the high-voltage cable (3) to the right in the generator and fasten with cable
ties (4).

Type B
1 Plug in the high-voltage connector (1) at H1.
2 Tighten the sleeve nut (2) by hand.
3 Position the high-voltage cable (3) to the right in the generator and fasten with cable
ties (4).

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
5-6 Cable connections

Connecting the cable harness to the generator


NOTE!
Required EMC measures are described on page 1 in this section.

F1 F2 F3 F4 F5
2

4
1

F10 F20

MAM00102
X32 X5 T3/X30

Figure 6 Cable harness at the generator

Unit control cable X1


1 Connect the unit control cable X1 to D700 X1 (1).
Filament cable X8
1 Connect the filament cable X8 to D700 X8 (2).

Power supply cable X14


1 Connect the power supply cable X14 to D711 X14 (3).
2 Strain relieve it on the side with a cable tie (4).

IONTOMAT signal cable X11


1 Connect the IONTOMAT signal cable connector X11, to D700 X11 (5).

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
Cable connections 5-7

Rotating anode cable X9

2 4

MAM00163
Figure 7 Connecting X9 to the generator

1 Connect the rotating anode cable X9 to D711 X9 (1).


2 Connect the two blue free wires from connector D711 X9 (1) to capacitor C51 (2).
3 Fit the cable to the chassis by using a cable clamp (3).

CAUTION!
When fitting the cable clamp, ensure satisfactory contact between shield braid (4) and
chassis.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
5-8 Cable connections

Mains connection
The equipment has been set to 400 V, 2-phase, in the factory (see test certificate). Ad-
justment to the line frequency is not needed. If the mains voltage is not 400 V, 2-phase at
the installation site a reconnection of the mains is necessary.

Should a reconnection for the mains voltage be necessary, this must be done at transform-
er T10 as well as p.c. board D711 (insertion or removal of fuses and labeling is specified
in the wiring diagram, see Line Input page 5-3).

Change the rated voltage labels to the correct voltage (there are two labels on the genera-
tor and one on the stand). Labels are included in the installation material.

NOTE!
For more details about changing mains, removal of short circuit, fuses and labeling, etc
see Wiring Diagram.

Connecting the incoming mains to the stand (400 V,


2-phase)
400 V 2-phase connection
L1
N

L2

L3

1
2

1
1
MAM00097

4
3

Figure 8 Incoming main cable

1 Connect the incoming mains cable (1) to X899 (2) in the stand as shown in Figure 8
and Figure 9.
2 Fit plastic tubes (4) on the plates.
3 Strain-relieve (3) the incoming mains cable.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
Cable connections 5-9

TWO-PHASE

GENERATOR STAND
Incoming mains
208, 230, 240, 277 or 400 VAC
P.E N L1 L2 L3
X899

F10

F20

X881

MAM00095
Figure 9 Incoming mains 2-phase

Connecting the mains supply to the generator (400 V, 2-phase)

F1 F2 F3 F4F5

3
F10 F20
MAM00103

Figure 10 Mains supply to the generator

1 Check that there is no wire jumper at F20 (1) and no brass plug at F5 (2).
Fuses must be inserted into fuse holders F20 and F5.
2 Connect the mains supply cables between stand and generator to fuses F10 and F20
on the generator.
Wire marked L1 to F10 and L2/N to F20.
3 Connect the protective ground wire from the stand to the generator (3).

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
5-10 Cable connections

Measures for changing from 2-phase to 1-phase connec-


tion
SINGLE PHASE

GENERATOR STAND
Incoming mains
110, 208, 230, 240 or 277 VAC
P.E N L1 L2 L3
X899

F10

X881

MAM00096
Figure 11 Incoming mains 1-phase

1 Move wire marked N/L2 from X899 L2 to X899 N (stand).


2 Connect incoming phase of the power supply to L1 and the neutral conductor of the
power supply (0 V) to N and fuse F20.
3 Strain-relieve the incoming mains cable as shown in Figure 8.
4 Short circuit F20 (1) and F5 (2) in Figure 10 with the jumper and brass plug included
in the service bag.

CAUTION!
For single-phase mains connection, make sure that the neutral conductor of the power
supply (0V) is connected to terminal N and fuse F20.

NOTE!
Connections on transformer T10 must be adjusted according to actual voltage, for details
see Wiring Diagram.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
Modifying the object tables 6-1

Modifying the 18 cm x 24 cm object table for thick


cassettes
If thick cassettes are to be used, the 18 cm x 24 cm object table must be modified as fol-
lows (see also separate instructions enclosed with the object table).
9
2
1

8
7

3
,,,
4

MAM00104
5

6 5

10

Figure 1 Modifying the object table

1 Remove the carbon-fibre plate (1) by unscrew four long screws (2) on the top side
and four short screws (3) on the front side.
2 Remove the four screws (4), two on each side.
3 Withdraw the steel bottom plate (5) and the spacing plate (6).
4 Install the new steel bottom plate and spacing plate included in the package.
Be careful with the switch and wire (7). Make sure that the switch actuator (8) is in
proper position.
5 Fasten with screws (4), two on each side.

NOTE!
It is recommended that the spacing plate and bottom plate not in use be kept for future
need.

6 Mount the carbon fibre-plate (1) and pay attention to the brass grounding strap (9).

NOTE!
Before mounting the carbon-fibre plate, make sure that the grid is properly positioned on
the support (10).

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
6-2 Modifying the object tables

Modifying the 24 cm x 30 cm object table for thick


cassettes
If thick cassettes are to be used, the 24 cm x 30 cm object table must be modified as fol-
lows (see also separate instructions enclosed with the object table).

10
1 2

8
7

3
9

4
5
,,,
6 5

MAM00105
11

Figure 2 Modifying the object table

1 Remove the carbon-fibre plate (1) by unscrewing four long screws (2) on the top side
and four short screws (3) on the front side.
2 Remove the six nuts (4) on the underside.
3 Withdraw the steel bottom plate (5) and spacing plate (6).
4 Re-insert the steel bottom plate (5) with the new spacing plate included in the package
into the object table.
Be careful with the switch and wire (7). Make sure that the switch actuator (8) is in
proper position.
5 Secure the assembly with the six nuts (4).
Be sure the grounding spring (9) is in place.

NOTE!
It is recommended that the spacing plate not in use be kept for future need.

6 Mount the carbon-fibre plate (1) and pay attention to the brass grounding strap (10).

NOTE!
Before mounting the carbon-fibre plate, make sure that the grid (11) is properly posi-
tioned on the support.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
Mains connection and power supply 7-1

Checks before powering up the generator


On p.c. board D702:
1 Set switch S1(UZW) to "OFF" (lower position).
2 Set switch S2 (SS) to "OFF" (lower position).
3 Set switch S3 (TEST) to "ON" (upper position- output service PC).

UZW S1 J39 J50

SS S2

TEST S3

V6
V7

ZBL V1
AR V2
KVE V3
BRAKE V4
STATUS V5
VH X967 X965
NSE1 X980
NSE2 X981
DS X982 X966
X962 IHREG
SS X983
X968
BS X984
GND X985 X964 X961 X969
MAREG
X960

X990 X963
X702

R13

R11

MAM00106
R43

Figure 1 P.C. board D702

Measuring the line resistance


See Figure 2
1 Remove fuses F10 (1) and F20 (2) or, when single-phase supply, fuse F10 (1).
2 Connect line resistance meter to fuse holders F10 and F20.
3 Mains supply "ON".
4 Carry out measurement.
5 Mains supply "OFF".

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
7-2 Mains connection and power supply

To achieve the full output, the resistance measured must not exceed the following values:

• 0.25 Ohm at 110 V (1-phase)

• 0.45 Ohm at 208 V

• 0.50 Ohm at 230 V

• 0.60 Ohm at 240 V

• 0.65 Ohm at 277 V

• 0.85 Ohm at 400 V (2-phase)

If the above values are exceeded, reduce the generator power in accordance with section
13 in this manual.

Checking the line voltage in the generator


1 If not already done, remove fuses F10 (1) and F20 (2) or, when single-phase supply,
fuse F10 (1).

2
MAM00107

Figure 2 Line voltage in the generator

2 Mains supply "ON".


3 Measure the voltage at fuse holders F10 (1) and F20 (2).
4 Check that the mains voltage agrees with the voltage plugged on transformer T10 (3)
and p.c. board D711 (4), located above line filter Z1 (5).
5 Mains supply "OFF".
6 Reinsert fuses F10 (1) and F20 (2).

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
Mains connection and power supply 7-3

7 Mains supply "ON" (Do not switch the system on yet).


8 Measure the voltage at transformer T1 (6) terminals 1 and 3, transformer T1 is located
under the line filter Z1 (5). There must be 195 V- 253 V between the terminals.
9 Measure the voltage at the output of line filter Z1 it must lie within 195 V- 264 V.

Checking the supply voltages


The correct supply voltages +5 V, +15 V and +24 V have already been tested in the fac-
tory. Only a visual check of the function is therefore needed.
1 System "ON".
2 Check that the following orange diodes are "ON" on p.c. board D704:
• V39 (+15 V)
• V38 (-15 V)
• V41 (+5 V)
• V40 (+24 V)

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
7-4 Mains connection and power supply

This page intentionally left blank.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
Attaching the swivel-arm covers 8-1

Attaching the swivel-arm covers


Arranging the swivel-arm system
1 Install object table, no compression force (swivel-arm system still upside down).
2 Rotate the swivel-arm system to 0 degrees by pressing one of the switches for clock-
wise rotation on the supporting arm.

CAUTION!
Do not perform any vertical adjustment of the swivel-arm system, before the protective
strips have been removed from the metal curtain

3 System and mains "OFF".


4 Remove the swivel-arm system transport safeguard, see section 3.

Connecting the cables to control-button board and patient handles


4
3
2 1

MAM00108
2 1
3
4

Figure 1 Connecting the cables

Before installing side covers, cables are to be connected.


1 Connect cables X807 (1) to control-button circuit boards D807 (2).
2 Connect ground wires to patient handles (3).

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
8-2 Attaching the swivel-arm covers

Attaching the covers


Screws in different size are included in the delivery.

5 2
3

MAM00109
Figure 2 Covers and sign

1 Mount the side covers (1) with six screws (2) on each side.

NOTE!
Don’t forget to fit the sign (3) when mounting the side covers. Use the two longer screws.

2 Mount the front cover (4) over the side covers by engaging the bottom end first, and
fasten with two short screws (5).

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
Checking the microprocessors 9-1

Microprocessors
The following LED displays on the processor p.c. boards indicate whether the relevant
microprocessors are operating correctly.
1 Mains and system "ON".
Following conditions must be indicated after not more than 15 s.

Microprocessors for: LED displays


Must be off.
Master: P.c. board D702
Flashing rapidly.

IONTOMAT PM: P.c. board D701 Must be off.

MAM00110
Must be flashing
(2-3 Hz).

P.C. board D711:


• V9 "ON" (line voltage on).
• V13 "OFF" (system stand-by).
• V11 "ON" (system on).
• V16 "ON" (intermediate circuit - filament).

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
9-2 Checking the microprocessors

This page intentionally left blank.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
Checks without high voltage 10-1

Checks without high voltage


1 System "OFF".
2 On p.c. board D702 set switch S1 (UZW) to "ON" (upper position) and switch S2
(SS) to "OFF" (lower position).
3 System "ON".
4 Press the exposure buttons on the control panel. The rotating anode shall start up. At
the end of the limit time, the rotating anode is braked.
5 Release the exposure buttons.

NOTE!
If the exposure buttons are prematurely released, "Limit" will be indicated.

6 System "OFF".

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
10-2 Checks without high voltage

This page intentionally left blank.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
Checks with high voltage 11-1

Preparation
This section describes how to check:

• Radiographic voltage.

• Tube current.

• mAs values.

CAUTION!
Radiation

NOTE!
Check that the high-voltage plug is plugged into H1 and locked.

kV>17 V39
kV>50 V41

WR_AUS V40

MASOLL X706
MAIST X707
IHSOLL X705
IHIST X704
UZIST X713
ISCHWING X710
KVSOLL X712
KVIST X711
0VA X708

KVE X714
KVA X715
ZBL X716
BRAKE X717
0VD X709

X703
R136
MAM00111

Figure 1 P.C. board D705

1 Set the switch S2 (SS) to "ON" (upper position) on p.c. board D702.
2 Remove the jumper and connect the mAs meter to mAs measuring sockets X3 and
X4 on p.c. board D710.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
11-2 Checks with high voltage

3 Connect oscilloscope to p.c. board D705 as follows:


• Channel 1 to measuring point "KVIST(actual value)" (1 V= 5 kV).
• Channel 2 to measuring point "MAIST(actual value)" (1 V= 40 mA).
• Trigger at measuring point "KVE" (start with high voltage "ON"), rising edge.
• Twist the measuring leads and connect their grounding braids to measuring point
"0VA".
4 Connect service PC to circuit board D702 using the connection cable.

NOTE!
Switch S3 on circuit board D702 must be set to upper position.

5 Start service program, see section 21 "Appendix".

Checking X-ray tube high voltage, tube currrent and mAs


values
1 System "ON".
2 Set the "cassette loaded" switch to "0" with the service PC program: Stand configu-
ration - Stand installation - Cassette loaded check (0=function deactivated).
3 Trigger test exposures with the following exposure values and check the kV values
and tube current characteristic on the oscilloscope (se oscillograms).
The accuracy of the kV is +/- 5% plus +/- 1.5 kV during the first 5 ms of the exposure.
For mA values < 50 mA, the accuracy of the kV is +/- 5% plus +/- 2 kV during the
first 5 ms.
The tube current must rise quickly to set value at the beginning of the exposure and
run linearly during the exposure, however not when TCR is running.
The accuracy of the mAs product must be +/- 10%.
4 Replace the jumper previously removed.

Tube current reduction


NOTE!
In MAMMOMAT 300, the tube current reduction is factory set to "ON" (see section 13
and test certificate). In this way, the tube current is reduced to approximately 50 mA at
the start of the exposure during the time programmed in section 13.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
Checks with high voltage 11-3

Oscilloscope diagrams
• MAMMOMAT 300 in mAs mode, see Figure 2-Figure 5.

• MAMMOMAT 300 with tube current reduction switched on, Iontomat mode
with Bucky, see Figure 6.

• MAMMOMAT 300 in Iontomat mode with tube current reduction switched


off, see Figure 7.

Tube P49 Mo,


molybdenum anode 0.3

30 kV 20 mAs (P = 3.75 kW)

MAM00112

Figure 2

30 kV 1 V/T (1 V = 5 kV)
125 mA 1 V/T (1 V = 40 mA)
20 ms/T

NOTE!
Record the measured kV and mAs value in the measuring protocol page 21-3.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
11-4 Checks with high voltage

Tube P49 Mo,


molybdenum anode 0.3

35 kV 100 mAs(P = 3.75 kW)

MAM00113
Figure 3

35 kV 2 V/T (1 V = 10 kV)
107 mA 1 V/T (1 V = 40 mA)
0.2 sec/T

25 kV 100 mAs(P = 3.75 kW)


MAM00114

Figure 4
25 kV 1 V/T (1 V= 5 kV)
150 mA 2 V/T (1 V = 80 mA)
0.1 sec/T

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
Checks with high voltage 11-5

Tube P49 Mo,


molybdenum anode 0.15

30 kV 10 mAs (P = 0.70 kW) >>

MAM00115
Figure 5
30 kV 1 V/T (1 V = 5 kV)
23 mA 0.5 V/T (1 V = 20 mA)
100 ms/T

NOTE!
Small focus is selected by attaching a magnification table.

NOTE!
Record the measured kV and mAs value in the measuring protocol page 21-3.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
11-6 Checks with high voltage

Tube P49 Mo,


molybdenum anode 0.3

30 kV Iontomat w. grid (P = 3.75 kW)


40 mm plexiglass

MAM00116
Figure 6
30 kV 1 V/T (1 V = 10 kV)
125 mA 1 V/T (1 V = 40 mA)
100 ms/T (total exposure time depending
on programmed sensitivity.)

30 kV Iontomat (P = 3.75 kW) >>


40 mm plexiglass
MAM00117

Figure 7
30 kV 1 V/T (1 V = 5 kV)
125 mA 1 V/T (1 V = 40 mA)
100 ms/T (total exposure time depending on
programmed sensitivity.)

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
Start-up and functional test of the IONTOMAT 12-1

Checking and programming with the service PC


Use the service PC to check and program the IONTOMAT. Operation of the service PC
is described in section 21.

The tables are optimized for the following four film/screen combinations. Curve x1 is
used for magnification tables and curve x2 for other object tables (with or without grid).

Table 1
Correction curve
Film Screen Cassette Sensi-
tivity Magni- Non-mag-
fication nification
Kodak Min-RE Kodak Min-R Kodak Min-R2 11 A1 A2
Fuji UM-MA HC Fuji HR Mammo Fine Fuji EC-MA 9 B1 B2

MAM00129
Agfa Mamoray MR6 Agfa MR Detail S Agfa MR Detail S 6.5 C1 C2
Dupont Microvision C Dupont Quantavision ME Dupont Quantavision 12 D1 D2

Program the IONTOMAT values as follows:

Sensitivity
Start with the sensitvity listed in the table for channel B, both H ( ) and D
( ), see also M300 Service Instructions. If the film/screen combination used by the
customer is not listed in table 1, start with sensitivity 11.

NOTE!
Be sure to use the same type of cassette, screen and film in each object table as the
customer uses.

Indicates the sensitivity for the IONTOMAT channel for contact exposure tables
(H) and magnification tables (D).

Values from 0 to 31 can be entered.

Channel A is not used, the sensitivity is therefore set 0.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
12-2 Start-up and functional test of the IONTOMAT

Sensitivity correction
Program "Sensitivity correction" to 0 for "without grid" and 0 for "magnification".

IONTOMAT PM - Sens. correction


24 x 30
Without grid _.0

With grid .0

Magnification .0

Valid entries from -8 to 8 in 1/2 E.P.


For pos entries 1 st digit is < space >, for neg entries type < - >.
Input of decimal point not required!

MAM00127
1 Help 2 Save 3 4 5 6 7 8 9 10 Quit

Indicates the sensitivity correction for different types of object tables.

The position "without grid" applies to tables with as well as without grid.

Factory set "0", "0", "0".

Different film-density corrections can be programmed for the different tables with the
"Sens-cor" module.

Correction curve
Program "Correction curve" according to table 1 above (see also M300 Service Instruc-
tions). If the customer uses another combination or mixture of those listed in tale 1, please
refer to page 12-3.

IONTOMAT PM - Correction curve

Curve number
Speed H _A2

Speed D A1

Press space to change the correction-curve table.


MAM00128

1 Help 2 Save 3 4 5 6 7 8 9 10 Quit

Indicates which correction curve shall be used for contact exposure tables (H)
and magnification tables (D). Values shown as delivered.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
Start-up and functional test of the IONTOMAT 12-3

Other film/screen combinations


In case the customer uses another film/screen combination than those the correction
curves are optimized for, see table 1 of correction curves on page 12-1, proceed as fol-
lows:
1 Begin with curve C2 and make test exposures using a grid table at 25 kV, 2 and 6 cm
plexi (5 cm if limit (ER550) or ER 013 occurs, due to insufficient dose rate). If the
image from 6 cm plexi (O.D.-6 cm) is lighter than one from 2 cm plexi (O.D.-2 cm),
choose correction curve A2 or B2 (A2 makes images from thick objects darker than
B2 does, i.e. A2 corrects more than B2). On the other hand, if O.D.-6 cm is darker
than O.D.-2 cm, choose curve D2. Repeat the test with the chosen curve. The differ-
ence between O.D.-6 cm and O.D.-2 cm (∆ Ο.D.) should be less than 0.30 O.D.
2 Now test 27 kV, 2 and 6 cm. Try even 30 and 35 kV if these kV´s are of interest for
the customer. If this ∆ Ο.D. is ≤ 0.30 O.D., go to 3. If not, it is necessary to test an-
other curve (choose between A2, B2, C2 and D2) at 27 kV. Choose the best one and
repeat the test at 25 kV. Continue in this manner until the result is as good as possible
for the kV´s of interest for the customer. Diagrams 1, 3, 5 and 7 on the following pag-
es can be of help. Note that the steeper the curve is, the more the thicker objects are
corrected (they will be darker).
3 Check also the correction with 2 cm plexi between the different kV values of interest.
If this ∆ Ο.D. is ≤ 0.30 O.D., an acceptable curve has been chosen. It may not be pos-
sible to reach the specified O.D. corrections, choose then the best compromise for the
customer´s needs.
4 Do the same tests with magnification table, but use 2 and 5 cm plexi instead. The pe-
missible ∆ Ο.D. for magnification tables is ≤ 0.40 O.D. Choose between correction
curves A1, B1, C1 and D1. Diagrams 2, 4, 6, and 8 on the following pages can be of
help.

NOTE!
When necessary, curve A2, B2, C2 and D2 can be used for magnification tables and/or
A1, B1, C1 and D1 for grid tables. In general, the X1-curves (magnification) correct more
than the X2-curves.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
12-4 Start-up and functional test of the IONTOMAT

Correction curve diagrams


The following diagrams approximately show the families of correction curves. The axes
"Quotient" and "Transparency correction" are the values shown in "Normal mode, Ion-
tomat data" with the service program.

25 kV Grid

35
dark

A2
30

25
B2
20
transp. corr.

15
C2
10

5
D2
light

0
70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85

MAM00118
thin object quotient thick object

Diagram 1

25 kV Magnification

40
dark

35 A2

30

B2
transp. corr.

25

20

15 C2

10

5 D2
light

0
75 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80
MAM00119

thin object quotient thick object

Diagram 2

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
Start-up and functional test of the IONTOMAT 12-5

27 kV Grid
30
dark

A2

25

20
B2
transp. corr.

15

10 C2

5
light

D2

MAM00120
96
93
91

97

98
94

99
81

92
87

88

89
80

85

100
83

84

95
90
82

86

thin object quotient thick object

Diagram 3

27 kV Magnification

40
dark

A2
35

30

25 B2
transp. corr.

20

15 C2

10

5
light

D2

0
MAM00121
75

78
76

77

88
86

92

93
85

89

94

95
81

87
82

83

84
80
79

90

91

thin object quotient thick object

Diagram 4

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
12-6 Start-up and functional test of the IONTOMAT

30 kV Grid

35

30 A2
dark

25

B2
transp. corr.

20

15
C2
10
llight

5
D2

0
91
89
87
85

99

105
97

119

121
117
109
93

125
111

113
107

123
115
103
95

101

MAM00122
thin object quotient thick object

Diagram 5

30 kV Magnification

40
dark

A2
35

30

B2
25
transp. corr.

20

15 C2

10

5
D2
light

0
101
97
91
89
87
85

99
95

105

119
117
109
93

111

113
107

115
103

MAM00123

thin object quotient thick object

Diagram 6

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
Start-up and functional test of the IONTOMAT 12-7

35 kV Grid

30
dark

A2
25

20
B2
transp. corr.

15
C2
10

5 D2
light

0
100 105 110 115 120 125 130 135 140 145 150

MAM00124
thin object quotient thick object

Diagram 7

35 kV Magnification

35
dark

A2
30

25

B2
transp. corr.

20

15
C2

10

5
D2
light

0
95 100 105 110 115 120 125 130 135 140 145
MAM00125

thin object quotient thick object

Diagram 8

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
12-8 Start-up and functional test of the IONTOMAT

Checking the film density


The sensitivity to be programmed must be determined by means of test exposures at 25
kV, or kV preferred by the customer, and 20 mm plexiglass.

The plexi must extend at least 30 mm behind the rear edge of the detector marking on the
compression plate and 10 mm beyond the chest wall edge of the table.

The detector shall be nearest the chest wall.

When making test exposures, ensure correct positioning of the plexiglass plates.

Object table

Plexiglass plate

Measuring Minimum projecting


point
Length: 10 mm

approx 40 mm

NOTE!
Detector nearest chest wall. Place the plexi plates in the same position for all exposures
and measure the density as shown above on the emulsion side of the film.

Button D ( ) should be used for magnifcation tables and button H ( ) for


other object tables (with or without grid).
Start with the sensitivity listed in table 1 and adjust a density of approx. 1.5 for non-mag-
nification tables ("Sensitivity H").

Change to magnification table, if used, and program "Sensitivity D" for the density as
above.

The final values are dependent on the type of cassette used and desired optical density.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
Start-up and functional test of the IONTOMAT 12-9

Checking the automatic transparency adaption


Check the automatic transparency adaption with a grid table with 20, 40 and 60 mm plexi
at the voltage(s) preferred by the customer (within 25-35 kV). If the dose rate is too low
(error 013 or "Limit"), use 50 mm plexi instead of 60 mm.

Tolerance:

≤ 0.3 density difference at constant voltage and thickness 20-60 mm.

≤ 0.3 at constant thickness and 25-35 kV.

NOTE!
Tolerance valid for grid tables and film/screen combination according to table 1.

These limits apply for film with max. gamma 4.0 measured at the density chosen.

NOTE!
The film density levels may vary from cassette to cassette. Therefore, be sure to use the
same cassette for all test exposures.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
12-10 Start-up and functional test of the IONTOMAT

Checking cut-off dose and resolution (§16 Germany)


This test is only required in the Federal Republic of Germany in the area of application of
the X-ray decree. The result must be entered in page 9 of the acceptance test certificate
supplied. Both tables must be checked.

Ascertain the cut-off dose (KB) and resolution (Rg) with the NORMI 7 test body

Test arrangement (front view)


1st exposure 2nd exposure

NORMI 7 NORMI 7
test body test body

Radiographic system Radiographic system

Film cassette Dosimeter chamber

Double detector Double detector

Procedure:
1 Select 30 kV and AEC (Iontomat) on the control panel.
2 Place the NORMI 7 test body on the object table flush with the chest wall side.
3 Slide film cassette into the object table.
4 Trigger the first exposure.
5 Note the mAs reading (QG(1)) shown on the control panel.
6 Develop the film. Measure the resolution (Rg) and the density (D) and enter in the
form.
7 Position the dosimeter chamber in the cassette slot.
8 Select 250 mAs on the control panel.
9 Trigger second exposure.
10 Record the dose value (KB(2)) measured as well as the associated mAs reading
(QG(2))
11 Calculate and record the cut-off dose as follows:

QG( 1)
K B = K B ( 2 ) ⋅ -------------
Qg( 2 )

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
Start-up and functional test of the IONTOMAT 12-11

Output values of constancy testing (§16 Germany)


Determine the output values of the constancy testing at approx. 30 kV with the customer´s
own constancy test body (NORMI 7 test body etc.) and enter them in the form stapled to
the acceptance test certificate.
Test arrangement
(Front view) (Top view)

NORMI 7 Radiographic
Pen dosimeter test body system

NORMI 7
test body
Pen dosimeter
A B
Radiographic system D C
Film cassette

Double detector
1 2 3 4
Steel balls

Plexiglass steps: Woven steel wire:

1 = 40 mm A = 100 µm
2 = 43 mm B = 80 µm
3 = 49 mm C = 63 µm
4 = 46 mm D = 40 µm

Procedure:
1 On the control panel, select a value of approx. 30 kV and AEC.
2 Place the test body on the object table flush with the chest wall side.
3 Slide film cassette into the object table.
4 Trigger the exposure and develop the film.
5 Measure the resolution (A-D), density (1-4) and the over-radiation on the chest wall
side and enter in the form (steel balls).
6 Read off the pen dosimeter and record the dose value.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
12-12 Start-up and functional test of the IONTOMAT

This page intentionally left blank.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
Further programming 13-1

Setting the real time clock


Prerequisite
The correct date and time must be set in the service PC. If not set date at C:\> date and
time at C:\> time.

Setting the time in the mammomat


Main menu:
1 Select Configuration <↑> <↓> < ENTER>.
2 Select Clock <↑> <↓> < ENTER>.
3 Press <F2>.
With <F2> the date and time set in the service PC are taken over by the Mammomat.

Setting the tube-current reduction


In Mammomat 300, the tube-current reduction is factory-set to "ON", which means that
the tube current is reduced to approx. 50 mA during the first 100 ms of the exposure. In
this way, possible grid lines are avoided.

If the tube-current reduction is set to "OFF", grid lines may occur at short exposure times
(< 100 ms).

NOTE!
The tube-current reduction is effective only in Iontomat mode.

Main menu
1 Select Configuration <↑> <↓> < ENTER>.
2 Select Miscellaneous <↑> <↓> < ENTER>.
3 Select Tube mA red. <↑> <↓> < ENTER>.
Tube-current reduction (TCR) at short exposure times.
TCR switch is ON/OFF.
Exposure time with 50 mA tube current is 100 ms.
4 Switch ON or OFF with <↓>.
5 Save the programmed values with <F2>.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
13-2 Further programming

Reducing the generator power


To achieve full power, the measured resistance must not exceed the following values:

• 0.25 Ohm at 110 V (1-phase)

• 0.45 Ohm at 208 V

• 0.50 Ohm at 230 V

• 0.60 Ohm at 240 V

• 0.65 Ohm at 277 V

• 0.85 Ohm at 400 V (2-phase)

If the above values are exceeded, reduce the generator power as follows:

Main menu
1 Select Configuration <↑> <↓> < ENTER>.
2 Select Miscellaneous <↑> <↓> < ENTER>.
3 Select Red. of power <↑> <↓> < ENTER>.
Reduction of power depending on line quality.
Tube is P 49 Mo 03.
4 Select nominal line voltage ____ V with cursor keys <↑> <↓> and < ENTER>.
5 Type in line impedance ____ Ω. Enter the measured line impedance.
Calculated power is ___ kW. Max. possible tube power is displayed.
6 Save the programmed values with <F2>.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
Checking the swivel-arm system 14-1

Rotary motion
1 System "OFF".
The rotary motion and the vertical adjustment of the swivel-arm system shall be
blocked.

3 1

4 1

MAM00140
Figure 1 Swivel-arm system
2 System "ON", object table installed and set projection angle to minimum with preset-
ting knob (2).
3 Check the rotary motion of the swivel-arm system by pressing buttons (1) one by one.
The rotation of the swivel-arm system shall stop when the button is released or when
end position is reached (+135 degrees clockwise and -180 degrees counter-
clockwise). The projection angle is shown on the display at the lower part of the
stand.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
14-2 Checking the swivel-arm system

mm
F o
OC

MAM00145
Figure 2 Display at the lower part of the stand

4 Set the projection angle to 60 degrees with presetting knob (2).


The preset angle is displayed for approx. 3 sec.
5 Press one of buttons (1).
The rotary motion of the swivel-arm system shall stop automatically when the preset
projection angle (both + and -) is reached and at 0 degrees.

NOTE!
All eight rotary motion buttons (four on either side) must be checked. After the button has
been released, the swivel-arm system shall remain in the position set.

Vertical adjustment
CAUTION!
Before vertical adjustment of the swivel-arm system is performed, be sure to remove the
protective strips from the metal curtain, see page 3-4.

See Figure 1
1 Press buttons for upward and downward movement (3) of the swivel-arm system.
The movement shall stop automatically when either end position is reached or when
the buttons are released.

NOTE!
All eight vertical adjustments buttons (four on either side) must be checked. The switching
off in upper and lower end position is effected by switches S881 and S884 respectively.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
Checking the swivel-arm system 14-3

Emergency stop
See Figure 1
1 Press the emergency stop button (4).
The button shall latch and all motorized movements of the equipment shall be
blocked ("Er 824" shall appear). To reset the emergency-stop button, turn it clock-
wise.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
14-4 Checking the swivel-arm system

This page intentionally left blank.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
Field light 15-1

Checking and adjusting the field light time


Checking the field light time
1

MAM00141
Figure 1 Tube head

1 Switch on the field light by pressing switch (1) or by pressing the compression foot
switch (2).
The field light shall go out automatically after a preset period of time (normally 20
sec.).

2
MAM00133

Figure 2 Foot switch

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
15-2 Field light

Adjusting the field light time


The illumination time of the field light can be adjusted according to the customer´s desire
within a certain range.

NOTE!
Shorter illumination time means increased life time of the lamp.

1 Connect the service PC to the generator and start the program as described in section
21.
2 Program according to the following:
Main menu
1 Select Stand configuration <↑> <↓> < ENTER>.
2 Select Stand installation <↑> <↓> <ENTER>.
3 Type in illumination time and save with < F2>.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
Checking the compression device and OPCOMP 16-1

Checking the compression device


5
3

MAM00142
Figure 1 Swivel arm system

1 Attach compression plate (1) if it is not already done.


2 Check that the compression plate can not be removed without pressing the compres-
sion plate release button (2).
3 Check the function of the knobs for manual compression/decompression (3).
4 Place a piece of soft material on the object table, for example a rolled up towel or a
piece of foam-rubber (4).
5 Check the function of the foot switch for motorized compression/decompression (1)
and (2) in Figure 2.

2
MAM00132

Figure 2 Foot switch

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
16-2 Checking the compression device and OPCOMP

6 Press the foot switch for motorized decompression to move the compression plate up-
wards while at the same time pressing the compression plate in the opposite direction
by hand.
The upward movement of the compression plate shall now stop (safety switch).
7 Set the compression to 7 kg by using the presetting knob (5) in Figure 1.
The preset compression force appears on the display at the lower part of the stand(1)
in Figure 3.

mm
F o
OC

MAM00134
Figure 3 Display at the lower part of the stand

NOTE!
The display (1) switches over to the actual compression-force value, when the compres-
sion plate comes in contact with the breast. The compressed thickness is shown on the dis-
play (2).

8 Press the foot switch for motorized compression to move the compression plate
downwards while simultaneously pressing the compression plate in the opposite di-
rection by hand.
The compression plate shall now slow down and stop, when the preset compression
force is reached.

NOTE!
During compression, the motorized vertical adjustment as well as the rotary motion of the
swivel-arm system shall be blocked.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
Checking the compression device and OPCOMP 16-3

Checking the OPCOMP (Option)


See Figure 1
1 Decompress.
2 Set the compression force to 20 kg by using the presetting knob (5) and compress.
The compression movement must be interrupted by OPCOMP before 20 kg is
reached, i.e. at 5-15 kg depending on the material (4) used.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
16-4 Checking the compression device and OPCOMP

This page intentionally left blank.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
Checking the exposure blocking 17-1

Checking the exposure blocking

MAM00143
Figure 1 Tube head

1 Check that the exposure release is blocked during the following conditions.
• No film cassette inserted.
• No object table installed.
• No external diaphragm (1) used with an magnification table installed.

NOTE!
The "cassette loaded" switch must be set to "ON" with the service PC program: Stand
configuration - Stand installation - Cassette loaded check (1=function activated).

NOTE!
The film cassette must be exchanged after each exposure. A second exposure before ex-
changing the cassette is not possible (exposure release is blocked).

Siemens-Elema AB SRX-MK RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
17-2 Checking the exposure blocking

This page intentionally left blank.

Siemens-Elema AB SRX-MK RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
Checking the radiation field limitation 18-1

Checking the radiation field limitation


General
The radiation field must not fall outside the edges of the image receptor, except for the
chest-wall side, where an over-radiation of maximum 1.0 % of the SID (= 6.5 mm) is al-
lowed. The light field must coincide with the radiation field.

Maximum tolerance:

2 % of the SID | left | + | right | ≤ 13 mm

| back | + | front | ≤ 13 mm

Measuring procedure

4
2
3

MAM00135
5
1

Figure 1 Checking the radiation field

1 Put film into the cassette (1).


2 Insert cassette into the object table (2).
3 Place filmbag (3) on the object table.
If no corresponding film bag is available, you can place two film cassettes side by
side on the object table.
4 Place a lead-cross (4) on the film bag/cassettes.
5 Switch on light field and mark the edges of the light field with four coins (5).
6 Release exposure.
7 Develop exposed films.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
18-2 Checking the radiation field limitation

Evaluation
Ligth field

* left + right 13 mm

Max. 13 mm *

Max. over-radiation
Lead-cross allowed

Chest-wall side Radiation field


Overlap 6,5 mm
Cassette film

MAM00136
Figure 2 Field limitation

1 Place the films over each other according to the position markings.
As shown in Figure 2, the film must be completely exposed on the side facing the
chest wall. The maximum allowed over-radiation is 6.5 mm (1.0 % of SID).
No over-radiation is allowed on the other three sides.
The maximum divergence between radiation field and light field of 13 mm (2 % of
SID) must not be exceeded.
Correction, see Service Instructions.

Repeat this check with all object tables.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
Final procedures 19-1

Service PC and measuring instruments


Recording the programmed values
Save the programmed values at menu command "SAve config.file".

Main menu:
1 Select Configuration<↑> <↓> < ENTER>.
2 Select SAve config.file <↑> <↓> < ENTER>.
3 Press <F2>.
Save data with <F2>.

NOTE!
No write protection on the diskette !

Reading the exposure counter and deleting the error memory


Read the exposure counter and delete the error memory after putting the stand into ser-
vice.

A/ Reading the exposure counter

Main menu:
1 Select Service <↑> <↓> < ENTER>.
2 Select Show exposure counter <↑> <↓> < ENTER>.
3 Enter the current counter reading in the certificate.

B/ Deleting the error memory

Main menu:
1 Select Service <↑> <↓> < ENTER>.
2 Select Delete error buffer <↑> <↓> < ENTER>.
3 Delete the error memory with <Y>.
4 Leave the program with <F10>.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
19-2 Final procedures

Removing the measuring instruments


1 Turn OFF the generator.
2 Remove the service PC.
3 Remove connected measuring instruments.

Checking the protective grounding resistance


Using the protective ground-wire tester, measure the resistance between the protective
ground terminal in the stand (X899, see Section 5) and all metallic parts of the equipment
which the patient/operator may come in contact with, incl. all object tables. The protective
ground resistance must not exceed 0.1Ω.

Mounting the cable duct covers


If it´s not already done mount the cable duct covers, see section 4.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
Final procedures 19-3

Mounting the stand covers


The Mammomat stand covers exist in two versions, one with separate rear side covers
and one with a single rear cover that also covers the rear sides.

WARNING When mounting the stand covers, make sure that the screws at
the top of the stand are securely tightened and have functioning
contact washers (1). These screws are used to establish protec-
tive ground connections. Before mounting the front covers, be
sure to remove the protective strips from the metal curtain (2).
Store the strips in the holders provided on both sides of the cur-
tain.

Mammomat stand with separate rear side covers.


1
4 5

3
9

MAM00146
6 7
2
11

10

12 8
ST_COV1

Figure 1 Mounting the stand covers on a stand with separate rear side covers.

1. Fit the rear cover (3) to the stand and fasten it with screws (4) and contact
washers (1).
Be careful not to damage the cables at the cable outlet!

2. Fit left and right front covers (8) to the stand and fasten with screws and contact
washers (9).

3. Fit left and right rear side covers (5) (6) to the stand and fasten with screws and
contact washers (7).

4. Fit inner plastic strip (10) to the front and side covers and fasten with screws (11),
eight on either side.

5. Press on the outer plastic strip (12).

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
19-4 Final procedures

Mammomat stand with single rear cover.

1
4

3
5
6

7 2

ST_COV2
Figure 2 Mounting the stand covers on a stand with single rear cover.
The Covers are delivered with a protective plastic film, which shall be removed and
discarded.

1. Fit left, right and middle front covers (6) to the stand and fasten with screws and
contact washers (5).

2. Fit the rear cover (3) to the stand and fasten it with screws (4) and contact
washers (1).
Be careful not to damage the cables at the cable outlet!

3. Fit inner plastic strip (7) to the front and side covers and fasten with screws (8),
eight on either side.

4. Press on the outer plastic strip (9).

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
Final procedures 19-5

Fitting the cable outlet cover

3
2

MAM00130
Figure 3 Cable outlet cover

1 Fit the cable outlet cover (1) to the stand and fasten with screws (2) and contact wash-
ers (3).

Mounting the front cover onto the generator

2
MAM00131

3
1

Figure 4 Mounting the front cover

1 Fit the front cover (3) to the generator and fasten it with the sixteen screws (2).

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
19-6 Final procedures

WARNING!
When attaching the front cover, make sure that all eight contact washers (four on either
side) are used again as in the original assembly (under the screws with clearance holes
in the plastic strips). The screws must be securely tightened and the washers must be func-
tional. This is necessary to establish protective ground connection.

2 Press on the outer cover strip (1).

Final protective grounding resistance test


Using the protective ground wire tester, measure the resistance between the mains
grounding connection (incl. mains cable) and any metallic part of the stand and generator
which the patient/operator may come in contact with.

The protective ground resistance must not exceed 0.2 Ω.

Face shield

1
MAM00144

Figure 5 Face shield

1 Slide the face shield (1) onto the holder for external diaphragms.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
Final procedures 19-7

Warning label on control panel


The control-panel warning label comes in eleven languages; English, German, French,
Spanish, Italian, Dutch, Danish, Norwegian, Finnish, Greek, and Swedish. The warning
labels are found in a plastic bag under thumb index 3 in the Technical Manual.

Note!
Warning label in english is provided on delivery.

Choose appropriate language and affix the label over the existing label on the control
panel, see Fig. 5. Be sure to position the label properly before affixing it. The label sticks
immediately.

kV mAs AEC Lim. PRE.

H D

Figure 6 Warning label on control panel

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
19-8 Final procedures

This page intentionally left blank.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
Options 20-1

Bolting the stand/generator to the floor


Should a permanent fastening to the floor be required due to local regulations (for exam-
ple in earthquake areas) or due to the quality of the floor covering, the stand/generator can
be secured to the floor by means of the levelling screws (1) of the stand or the fixing holes
(2) of the generator.

MAM00138
Figure 1 Base plate for the stand

2 2

MAM00139

Figure 2 Base plate for the generator

1 Position the stand/generator and mark out appropriate fixing holes on the floor, using
the base plate as a template.

NOTE!
The base plates shall be secured with at least four screws each (two on each side).

2 Drill the holes and insert dowels and screws use Liebig safety dowel M6 S10/35 and
washer DIN 9021B, ISO 7093 or equal.Tighten the screws to 10 Nm.

NOTE!
Make sure that the screws don’t come in contact with any conductive material such as re-
inforcing iron.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
20-2 Options

This page intentionally left blank.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
Appendix 21-1

Working with the service PC


Description of the syntax used in these instructions

< ..... > The indication of which function keys to press is given between
these characters, for example <ENTER>, <ESC> etc.
CAPITALS Capital letters indicate data which must be entered unchanged, for
example the name of a register, files etc.
Italics Italics represent data in which a value should be entered, e.g. for
user name, the name of the technician should be entered.
[ ..... ] Square brackets enclose additions to commands which may be
optionally entered.
Bold Data relating to formats, user entries etc., which is important for
the following entry, is shown in bold as it appears on the monitor
screen.
This character indicates that at this point the space key must be
pressed.
xx yy zz Data can be entered in place of "x, y, z"
(e.g. day´s date).
{...} Curved brackets indicate that out of several terms listed one below
the other, one must be selected.
Notes! Important remarks are indicated with this box.
***** When the password is entered, only these characters are shown.
Menu Selection: When several menus, programs, files etc. are presented for selec-
tion, they are shown in a box (program window).
Selection is made with the <↓> and <↑> keys.
The module selected is highlighted in the display.
<ENTER> Every entry must be confirmed with the <ENTER> key.
<ESC> ESC allows paging back through the program.
<xx> + <y> Some functions are selected by pressing two keys
simultaneously. Procedure: Press, for example, the <Shift> key
and keep it depressed, press the <*> key and then release both
keys.
<F1> Key <F1> calls up a selective help text.
<F10> Key <F10> exits the program.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
21-2 Appendix

XXX - - XXX - - By this means, the way is shown how to call up a particular sub-
XXX - - XXX routine (display windows).

For example:

Main menu 
Configuration 
Iontomat 
Corr. curve 

Note: S3 on D702 in upper position

Connecting the service PC


The service PC must be connected with connecting cable part no. 99 00 440 RE999 to p.c.
board D702 in the generator (do not insert the diskette in the drive yet). Use port COM
1 on the service PC.

Starting up and using the service PC


1 Switch on generator and service PC.
After initialization, the service PC shows: C:\>
2 Now insert the diskette with the service program.
{A:}
3 Select the appropriate drive {B:} and then press <ENTER>.
The screen shows: A:\> or B:\>
4 Select the service program required, for example SERVICE, then press <ENTER>.
The program asks for user name: User name
Enter the name of the technician, for example NN, and then press <ENTER>.
5 The program asks for the password: Password
Enter the password (********) and then press <ENTER>.
The display window shows: Main menu
6 Select the program part to be used with keys <↑> and/or <↓>, then press <ENTER>.
The program part selected is shown with a background: Configuration
If necessary, additional subroutines can be similarly selected here.
7 Make the necessary entries in the appropriate part of the program.
Save the entered data with <F2>. Page back in the program with <ESC>.
The appropriate instructions are shown on the monitor.
8 End the procedure with the service PC with <F10>.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
Appendix 21-3

Measuring protocol
Values recorded during installation of Mammomat 300:

Tube P49 Mo, molybdenum anode 0.3


Calculated values Required values
______V x 5 kV/V = _____kV 30 kV +/- 5 %
______V x ____ s x 40 mA/V = ____ mAs 20 mAs +/- 10 %

Date:______________
Sign:______________

Tube P49 Mo, molybdenum anode 0.15


Calculated values Required values
______V x 5 kV/V = _____kV 30 kV +/- 5 %
______V x ____ s x 40 mA/V = ____ mAs 10 mAs +/- 10 %

Date:______________
Sign:____________

Keep measuring protocol in technical documentation.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186
21-4 Appendix

Tube P49 Mo, molybdenum anode 0.3


40 mm plexiglass
Calculated values Required values
______V x 5 kV/V = _____kV 30 kV +/- 5 %
______V x 40 mA/V = ____ mA 125 mA +/- 10 %

Date:______________
Sign:____________

Tube P49 Mo, molybdenum anode 0.3


40 mm plexiglass
Calculated values Required values
______V x 5 kV/V = _____kV 30 kV +/- 5 %
______V x 40 mA/V = ____ mA 125 mA +/- 10 %

Date:______________
Sign:____________

Keep measuring protocol in technical documentation.

Siemens-Elema AB SPS-UD RX B7-120.033.01.10.02 MAMMOMAT 300


Solna, Sweden 05.98 65 02 186

You might also like