This document provides an analysis of wind loading on roof components and cladding according to the ASCE 7-02 code. It includes input data for a building such as wind speed, building dimensions, and roof properties. The results section calculates pressure coefficients, velocity pressures, and design wind pressures for various zones on the roof based on the code requirements. Notes provide additional information on applying the results.

Uploaded by

dantevarias
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
266 views3 pages

WIND LOADING ANALYSIS - Roof Components and Cladding

This document provides an analysis of wind loading on roof components and cladding according to the ASCE 7-02 code. It includes input data for a building such as wind speed, building dimensions, and roof properties. The results section calculates pressure coefficients, velocity pressures, and design wind pressures for various zones on the roof based on the code requirements. Notes provide additional information on applying the results.

Uploaded by

dantevarias
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

"ASCE702W.

xls" Program
Version 1.7

WIND LOADING ANALYSIS - Roof Components and Cladding


Per ASCE 7-02 Code for Bldgs. of Any Height with Gable Roof q <= 45o or Monoslope Roof q <= 3o
Using Method 2: Analytical Procedure (Section 6.5)
Job Name: Subject:
Job Number: Originator: Checker:

Input Data:

Wind Speed, V = 90 mph (Wind Map, Figure 6-1)


Bldg. Classification = II (Table 1-1)
Exposure Category = C (Sect. 6.5.6) B
Ridge Height, hr = 53.33 ft. (hr >= he)
Eave Height, he = 20.00 ft. (he <= hr)
Building Width = 200.00 ft. (Normal to Building Ridge)
Building Length = 250.00 ft. (Parallel to Building Ridge) L
Roof Type = Gable (Gable or Monoslope)
Plan
Topo. Factor, Kzt = 1.00 (Sect. 6.5.7 & Figure 6-4)
Direct. Factor, Kd = 0.85 (Table 6-4)
Enclosed? (Y/N) Y (Sect. 6.2 & Figure 6-5)
Component Name = Joist (Purlin, Joist, Decking, or Fastener) qo
Effective Area, Ae = 208 ft.^2 (Area Tributary to C&C) hr
h
Overhangs? (Y/N) N (if used, overhangs on all sides) he

L
Resulting Parameters and Coefficients: Elevation

Roof Angle, q = 18.43 deg.


Mean Roof Ht., h = 36.67 ft. (h = (hr+he)/2, for roof angle >10 deg.)

Roof External Pressure Coefficients, GCp:


GCp Zone 1-3 Pos. = 0.30 (Fig. 6-11B thru 6-11D)
GCp Zone 1 Neg. = -0.80 (Fig. 6-11B thru 6-11D)
GCp Zone 2 Neg. = -1.20 (Fig. 6-11B thru 6-11D)
GCp Zone 3 Neg. = -2.00 (Fig. 6-11B thru 6-11D)
Positive & Negative Internal Pressure Coefficients, GCpi (Figure 6-5):
+GCpi Coef. = 0.18 (positive internal pressure)
-GCpi Coef. = -0.18 (negative internal pressure)
If z <= 15 then: Kz = 2.01*(15/zg)^(2/a) , If z > 15 then: Kz = 2.01*(z/zg)^(2/a) (Table 6-3, Case 1a)
a= 9.50
zg = 900 (Table 6-2)
Kh = 1.02 (Kh = Kz evaluated at z = h)
I= 1.00 (Table 6-1) (Importance factor)
Velocity Pressure: qz = 0.00256*Kz*Kzt*Kd*V^2*I (Sect. 6.5.10, Eq. 6-15)
qh = 18.06 psf qh = 0.00256*Kh*Kzt*Kd*V^2*I (qz evaluated at z = h)

Design Net External Wind Pressures (Sect. 6.5.12.4):


For h <= 60 ft.: p = qh*((GCp) - (+/-GCpi)) (psf)
For h > 60 ft.: p = q*(GCp) - qi*(+/-GCpi) (psf)
where: q = qh for roof
qi = qh for roof (conservatively assumed per Sect. 6.5.12.4.2)

1 of 3 08/04/2021 11:49 am
"ASCE702W.xls" Program
Version 1.7

Wind Load Tabulation for Roof Components & Cladding


Component z Kh qh p = Net Design Pressures (psf)
(ft.) (psf) Zone 1,2,3 (+) Zone 1 (-) Zone 2 (-) Zone 3 (-)
Joist 0 1.02 18.06 8.67 -17.70 -24.92 -39.37
15.00 1.02 18.06 8.67 -17.70 -24.92 -39.37
20.00 1.02 18.06 8.67 -17.70 -24.92 -39.37
25.00 1.02 18.06 8.67 -17.70 -24.92 -39.37
30.00 1.02 18.06 8.67 -17.70 -24.92 -39.37
35.00 1.02 18.06 8.67 -17.70 -24.92 -39.37
40.00 1.02 18.06 8.67 -17.70 -24.92 -39.37
45.00 1.02 18.06 8.67 -17.70 -24.92 -39.37
50.00 1.02 18.06 8.67 -17.70 -24.92 -39.37
For z = hr: 53.33 1.02 18.06 8.67 -17.70 -24.92 -39.37

For z = he: 20.00 1.02 18.06 8.67 -17.70 -24.92 -39.37


For z = h: 36.67 1.02 18.06 8.67 -17.70 -24.92 -39.37

Notes: 1. (+) and (-) signs signify wind pressures acting toward & away from respective surfaces.
2. Width of Zone 2 (edge), 'a' = 14.67 ft.
3. Width of Zone 3 (corner), 'a' = 14.67 ft.
4. For monoslope roofs with q <= 3 degrees, use Fig. 6-5B for 'GCp' values with 'qh'.
5. For buildings with h > 60' and q > 10 degrees, use Fig. 6-5B for 'GCpi' values with 'qh'.
6. For all buildings with overhangs, use Fig. 6-5B for 'GCp' values per Sect. 6.5.11.4.2.
7. If a parapet >= 3' in height is provided around perimeter of roof with q <= 10 degrees,
Zone 3 shall be treated as Zone 2.
8. Per Code Section 6.1.4.2, the minimum wind load for C&C shall not be less than 10 psf.
9. References : a. ASCE 7-02, "Minimum Design Loads for Buildings and Other Structures".
b. "Guide to the Use of the Wind Load Provisions of ASCE 7-02"
by: Kishor C. Mehta and James M. Delahay (2004).

2 of 3 08/04/2021 11:49 am
"ASCE702W.xls" Program
Version 1.7

Roof Components and Cladding:

Roof Zones for Buildings with h <= 60 ft.


(for Gable Roofs <= 45o and Monoslope Roofs <= 3o)

Roof Zones for Buildings with h > 60 ft.


(for Gable Roofs <= 10o and Monoslope Roofs <= 3o)

3 of 3 08/04/2021 11:49 am