Wind Load For Building With All Height

This document provides an analysis of wind loading on a main wind-force resisting system (MWFRS) of an enclosed building per the ASCE 7-02 code. It includes input data for the building dimensions and wind parameters. It then lists resulting wind pressure coefficients and calculates design net external wind pressures at different heights on walls and the roof. Gust effects are considered to determine the gust factor G. The analysis is presented in tables and notes.

Uploaded by

dantevarias
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
379 views4 pages

Wind Load For Building With All Height

This document provides an analysis of wind loading on a main wind-force resisting system (MWFRS) of an enclosed building per the ASCE 7-02 code. It includes input data for the building dimensions and wind parameters. It then lists resulting wind pressure coefficients and calculates design net external wind pressures at different heights on walls and the roof. Gust effects are considered to determine the gust factor G. The analysis is presented in tables and notes.

Uploaded by

dantevarias
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

"ASCE702W.

xls" Program
Version 1.7

WIND LOADING ANALYSIS - Main Wind-Force Resisting System


Per ASCE 7-02 Code for Enclosed or Partially Enclosed Buildings
Using Method 2: Analytical Procedure (Section 6.5) for Buildings of Any Height
Job Name: Subject:
Job Number: Originator: Checker:

Input Data:

Wind Direction = Normal (Normal or Parallel to building ridge)


Wind Speed, V = 120 mph (Wind Map, Figure 6-1) Wind
Bldg. Classification = II (Table 1-1) B
Exposure Category = B (Sect. 6.5.6)
Ridge Height, hr = 157.00 ft. (hr >= he)
Eave Height, he = 157.00 ft. (he <= hr)
Building Width = 100.00 ft. (Normal to Building Ridge) L
Building Length = 200.00 ft. (Parallel to Building Ridge)
Plan
Roof Type = Monoslope (Gable or Monoslope)
Topo. Factor, Kzt = 1.00 (Sect. 6.5.7 & Figure 6-4)
Direct. Factor, Kd = 0.85 (Table 6-4)
Enclosed? (Y/N) Y (Sect. 6.2 & Figure 6-5) qo
Damping Ratio, b = 0.030 (Suggested Range = 0.010-0.070)
Period Coef., Ct = 0.0200 (Suggested Range = 0.020-0.035) hr
h
(Assume: T = Ct*h^(3/4) , and f = 1/T) he

Resulting Parameters and Coefficients: L


Elevation
Roof Angle, q = 0.00 deg.
Mean Roof Ht., h = 157.00 ft. (h = he, for roof angle <=10 deg.) L = 100 ft.
Windward Wall Cp = 0.80 (Fig. 6-6) B = 200 ft.
Leeward Wall Cp = -0.50 (Fig. 6-6)
Side Walls Cp = -0.70 (Fig. 6-6)
Roof Cp (zone #1) = -1.04 -0.18 (Fig. 6-6) (zone #1 for 0 to h/2)
Roof Cp (zone #2) = -0.70 -0.18 (Fig. 6-6) (zone #2 for h/2 to h)
Roof Cp (zone #3) = N.A. N.A. (Fig. 6-6) (zone #3 for h to 2*h)
Roof Cp (zone #4) = N.A. N.A. (Fig. 6-6) (zone #4 for > 2*h)
+GCpi Coef. = 0.18 (Figure 6-5) (positive internal pressure)
-GCpi Coef. = -0.18 (Figure 6-5) (negative internal pressure)

If z <= 15 then: Kz = 2.01*(15/zg)^(2/a) , If z > 15 then: Kz = 2.01*(z/zg)^(2/a) (Table 6-3, Case 2a)
a= 7.00 zg = 1200 (Table 6-2)
Kh = 1.12 (Kh = Kz evaluated at z = h)
I= 1.00 (Table 6-1) (Importance factor)
Velocity Pressure: qz = 0.00256*Kz*Kzt*Kd*V^2*I (Sect. 6.5.10, Eq. 6-15)
qh = 35.23 psf qh = 0.00256*Kh*Kzt*Kd*V^2*I (qz evaluated at z = h)
Ratio h/L = 1.570 freq., f = 1.127 hz. (f >= 1, Rigid structure)
Gust Factor, G = 0.818 (Sect. 6.5.8)
Design Net External Wind Pressures (Sect. 6.5.12.2):
p = qz*G*Cp - qi*(+/-GCpi) for windward wall (psf), where: qi =qh (Eq. 6-17, Sect. 6.5.12.2.1)
p = qh*G*Cp - qi*(+/-GCpi) for leeward wall, sidewalls, and roof (psf), where: qi = qh (Sect. 6.5.12.2.1)

1 of 4 08/04/2021 11:48 am
"ASCE702W.xls" Program
Version 1.7

Normal to Ridge Wind Load Tabulation for MWFRS - Buildings of Any Height
Surface z Kz qz Cp p = Net Design Press. (psf)
(ft.) (psf) (w/ +GCpi) (w/ -GCpi)
Windward Wall 0 0.57 18.01 0.80 5.45 18.13
15.00 0.57 18.01 0.80 5.45 18.13
20.00 0.62 19.55 0.80 6.46 19.14
25.00 0.67 20.84 0.80 7.30 19.98
30.00 0.70 21.95 0.80 8.03 20.71
35.00 0.73 22.94 0.80 8.68 21.36
40.00 0.76 23.83 0.80 9.26 21.94
45.00 0.79 24.65 0.80 9.80 22.48
50.00 0.81 25.40 0.80 10.29 22.97
55.00 0.83 26.10 0.80 10.75 23.43
60.00 0.85 26.76 0.80 11.18 23.86
70.00 0.89 27.97 0.80 11.97 24.65
80.00 0.93 29.05 0.80 12.68 25.36
90.00 0.96 30.05 0.80 13.33 26.01
100.00 0.99 30.97 0.80 13.93 26.61
120.00 1.04 32.62 0.80 15.01 27.70
140.00 1.09 34.09 0.80 15.98 28.66
For z = hr: 157.00 1.12 35.23 0.80 16.72 29.40

For z = he: 157.00 1.12 35.23 0.80 16.72 29.40


For z = h: 157.00 1.12 35.23 0.80 16.72 29.40
Leeward Wall All - - -0.50 -20.75 -8.07
Side Walls All - - -0.70 -26.52 -13.84
Roof (zone #1) cond. 1 - - - -1.04 -36.32 -23.64
Roof (zone #1) cond. 2 - - - -0.18 -11.53 1.15
Roof (zone #2) cond. 1 - - - -0.70 -26.52 -13.84
Roof (zone #2) cond. 2 - - - -0.18 -11.53 1.15

Notes: 1. (+) and (-) signs signify wind pressures acting toward & away from respective surfaces.
2. Per Code Section 6.1.4.1, the minimum wind load for MWFRS shall not be less than 10 psf.
3. References : a. ASCE 7-02, "Minimum Design Loads for Buildings and Other Structures".
b. "Guide to the Use of the Wind Load Provisions of ASCE 7-02"
by: Kishor C. Mehta and James M. Delahay (2004).
4. Roof zone #1 is applied for horizontal distance of 0 to h/2 from windward edge.
5. Roof zone #2 is applied for horizontal distance of h/2 to h from windward edge.

2 of 4 08/04/2021 11:48 am
"ASCE702W.xls" Program
Version 1.7

Determination of Gust Effect Factor, G:

Is Building Flexible? No f >=1 Hz.

1: Simplified Method for Rigid Building


G= 0.850

Parameters Used in Both Item #2 and Item #3 Calculations (from Table 6-2):
a^ = 0.143
b^ = 0.84
a(bar) = 0.250
b(bar) = 0.45
c= 0.30
l= 320 ft.
e(bar) = 0.333
z(min) = 30 ft.

Calculated Parameters Used in Both Rigid and/or Flexible Building Calculations:


z(bar) = 94.20 = 0.6*h , but not < z(min) , ft.
Iz(bar) = 0.252 = c*(33/z(bar))^(1/6) , Eq. 6-5
Lz(bar) = 453.94 = l*(z(bar)/33)^(e(bar)) , Eq. 6-7
gq = 3.4 (3.4, per Sect. 6.5.8.1)
gv = 3.4 (3.4, per Sect. 6.5.8.1)
gr = 4.218 = (2*(LN(3600*f)))^(1/2)+0.577/(2*LN(3600*f))^(1/2) , Eq. 6-9
Q= 0.805 = (1/(1+0.63*((B+h)/Lz(bar))^0.63))^(1/2) , Eq. 6-6

2: Calculation of G for Rigid Building


G= 0.818 = 0.925*((1+1.7*gq*Iz(bar)*Q)/(1+1.7*gv*Iz(bar))) , Eq. 6-4

3: Calculation of Gf for Flexible Building


b= 0.030 Damping Ratio
Ct = 0.020 Period Coefficient
T= 0.887 = Ct*h^(3/4) , sec. (Period)
f= 1.127 = 1/T , Hz. (Natural Frequency)
V(fps) = N.A. = V(mph)*(88/60) , ft./sec.
V(bar,zbar) = N.A. = b(bar)*(z(bar)/33)^(a(bar))*V*(88/60) , ft./sec. , Eq. 6-14
N1 = N.A. = f*Lz(bar)/(V(bar,zbar)) , Eq. 6-12
Rn = N.A. = 7.47*N1/(1+10.3*N1)^(5/3) , Eq. 6-11
hh = N.A. = 4.6*f*h/(V(bar,zbar))
Rh = N.A. = (1/hh)-1/(2*hh^2)*(1-e^(-2*hh)) for hh > 0, or = 1 for hh = 0 ,Eq. 6-13
hB = N.A. = 4.6*f*B/(V(bar,zbar))
RB = N.A. = (1/hB)-1/(2*hB^2)*(1-e^(-2*hB)) for hB > 0, or = 1 for hB = 0,Eq. 6-13
hL = N.A. = 15.4*f*L/(V(bar,zbar))
RL = N.A. = (1/hL)-1/(2*hL^2)*(1-e^(-2*hL)) for hL > 0, or = 1 for hL = 0 ,Eq. 6-13
R= N.A. = ((1/b)*Rn*Rh*RB*(0.53+0.47*RL))^(1/2) , Eq. 6-10
Gf = N.A. = 0.925*(1+1.7*Iz(bar)*(gq^2*Q^2+gr^2*R^2)^(1/2))/(1+1.7*gv*Iz(bar)) ,
Use: G = 0.818 Eq. 6-8

3 of 4 08/04/2021 11:48 am
"ASCE702W.xls" Program
Version 1.7

Figure 6-9 - Design Wind Load Cases of MWFRS for Buildings of All Heights

Case 1: Full design wind pressure acting on the projected area perpendicular to each principal axis of
the structure, considered separately along each principal axis.
Case 2: Three quarters of the design wind pressure acting on the projected area perpendicular to each
principal axis of the structure in conjunction with a torsional moment as shown, considered
separately for each principal axis.
Case 3: Wind pressure as defined in Case 1, but considered to act simultaneously at 75% of the
specified value.
Case 4: Wind pressure as defined in Case 2, but considered to act simultaneously at 75% of the
specified value.

Notes: 1. Design wind pressures for windward (Pw) and leeward (PL) faces shall be determined in
accordance with the provisions of Section 6.5.12.2.1 and 6.5.12.2.3 as applicable for buildings
of all heights.
2. Above diagrams show plan views of building.
3. Notation:
Pwx, Pwy = Windward face pressure acting in the X, Y principal axis, respectively.
PLx, PLy = Leeward face pressure acting in the X, Y principal axis, respectively.
e (ex, ey) = Eccentricity for the X, Y principal axis of the structure, respectively.
MT = Torsional moment per unit height acting about a vertical axis of the building.

4 of 4 08/04/2021 11:48 am