Cable Sizing Sheet - Final
Cable Sizing Sheet - Final
Maximum permissible length during motor running condition is given by: Maximum permissible length during motor starting condition is given by:
Notes:
Specifications
1) Refer Oman cable catelouge for continuous current carrying
Supply Voltage 415 V capacity of the cable.
2) Motor full load current have been considered based on typical
System Frequency 50 Hz motor manufacturer catelouge.
sinØr 0.53
sinØs 0.98
Data For Cable Type XLPE Insulated Copper Conductor armoured Cable
Cross section in mm 2
3/C-4 3/C-6 3/C-10 3/C-16 3/C-25 3/C-35 3/C-50 3/C-70 3/C-95 3/C-120 3/C-150 3/C-185 3/C-240 3/C-300 3/C-400 2#3/C-95 2#3/C-120 2#3/C-150 2#3/C-185 2#3/C-240 2#3/C-300 2#3/C-400 3#3/C-240 3#3/C-300 3#3/C-400
Approximate voltage drop per
10.200 6.752 4.047 2.500 1.650 1.150 0.870 0.600 0.450 0.370 0.300 0.260 0.210 0.190 0.170 0.225 0.185 0.150 0.130 0.105 0.095 0.085 0.070 0.063 0.057
ampere per m (mV)
AC Resistance at 900C Ohm/km 5.88 3.93 2.33 1.47 0.927 0.668 0.494 0.343 0.248 0.197 0.16 0.129 0.100 0.082 0.066 0.124 0.099 0.080 0.065 0.050 0.041 0.033 0.033 0.027 0.022
Reactance at 50Hz in Ohm/km 0.093 0.089 0.084 0.081 0.081 0.079 0.078 0.074 0.072 0.072 0.073 0.072 0.071 0.071 0.070 0.036 0.036 0.037 0.036 0.036 0.036 0.035 0.024 0.024 0.023
Nominal Current Rating in amps. 39 48 65 83 107 128 152 187 226 258 291 329 380 427 490 452 516 582 658 760 854 980 1140 1281 1470
Installed Current Rating in amps. 24.76 30.48 40.81 51.53 66.43 78.56 93.29 113.45 137.12 154.71 174.50 194.96 225.19 250.03 286.91 274.23 309.42 349.00 389.93 450.37 500.05 573.83 675.56 750.08 860.74
0.55 1.20 657 953 1517 2228 3142 3943 4748 5896 6924 7567 8036 8635 9289 9689 10172 13849 15134 16072 17270 18577 19378 20345 27866 29067 30517
1.1 2.39 330 478 762 1119 1578 1980 2384 2960 3477 3799 4035 4336 4664 4865 5107 6953 7599 8070 8671 9328 9729 10215 13991 14594 15322
1.5 3.26 242 351 559 820 1157 1451 1748 2170 2549 2785 2958 3179 3419 3566 3744 5098 5571 5916 6357 6838 7133 7489 10257 10699 11233
2.2 4.78 165 239 381 559 789 990 1192 1480 1738 1900 2017 2168 2332 2432 2554 3477 3799 4035 4336 4664 4865 5107 6996 7297 7661
3 6.52 121 175 279 410 578 726 874 1085 1274 1393 1479 1589 1710 1783 1872 2549 2785 2958 3179 3419 3566 3744 5129 5350 5617
4 8.70 91 131 209 307 433 544 655 813 955 1044 1108 1191 1281 1336 1403 1910 2087 2217 2382 2562 2673 2806 3844 4009 4209
5.5 11.96 66 96 152 224 315 396 476 592 695 759 806 866 932 972 1021 1390 1518 1613 1733 1864 1944 2041 2796 2916 3062
7.5 16.30 48 70 112 164 231 290 350 434 510 557 592 636 684 713 749 1020 1114 1183 1271 1368 1427 1498 2051 2140 2247
11 20.23 39 57 90 132 186 234 282 350 411 449 477 512 551 575 603 821 898 953 1024 1102 1149 1207 1653 1724 1810
15 27.59 - 41 66 97 137 171 207 256 301 329 350 376 404 421 442 602 658 699 751 808 843 885 1212 1264 1327
18.5 34.02 - - 54 79 111 139 167 208 244 267 283 305 328 342 359 489 534 567 609 655 684 718 983 1025 1076
22 40.46 - - 45 66 93 117 141 175 205 224 238 256 275 287 302 411 449 477 512 551 575 603 826 862 905
30 55.17 - - - - 68 86 103 128 151 165 175 188 202 211 221 301 329 350 376 404 421 443 606 632 664
37 68.05 - - - - - 70 84 104 122 133 142 152 164 171 179 244 267 283 305 328 342 359 491 513 538
45 78.28 - - - - - 60 73 90 106 116 123 132 142 149 156 212 232 246 265 285 297 312 427 446 468
55 95.67 - - - - - - - 74 87 95 101 108 117 122 128 174 190 202 217 233 243 255 350 365 383
Appendix-1
TABLE 1a: CABLE SIZES FOR 415V MOTOR FEEDER (THREE CORE CABLE LAID IN UNDERGROUND DUCT BANK)
Maximum permissible length during motor running condition is given by: Maximum permissible length during motor starting condition is given by:
Notes:
Specifications
1) Refer Oman cable catelouge for continuous current carrying
Supply Voltage 415 V capacity of the cable.
2) Motor full load current have been considered based on typical
System Frequency 50 Hz motor manufacturer catelouge.
sinØr 0.53
sinØs 0.98
Data For Cable Type XLPE Insulated Copper Conductor armoured Cable
Cross section in mm 2
3/C-4 3/C-6 3/C-10 3/C-16 3/C-25 3/C-35 3/C-50 3/C-70 3/C-95 3/C-120 3/C-150 3/C-185 3/C-240 3/C-300 3/C-400 2#3/C-95 2#3/C-120 2#3/C-150 2#3/C-185 2#3/C-240 2#3/C-300 2#3/C-400 3#3/C-240 3#3/C-300 3#3/C-400
Approximate voltage drop per
10.200 6.752 4.047 2.500 1.650 1.150 0.870 0.600 0.450 0.370 0.300 0.260 0.210 0.190 0.170 0.225 0.185 0.150 0.130 0.105 0.095 0.085 0.070 0.063 0.057
ampere per m (mV)
AC Resistance at 900C Ohm/km 5.88 3.93 2.33 1.47 0.927 0.668 0.494 0.343 0.248 0.197 0.16 0.129 0.100 0.082 0.066 0.124 0.099 0.080 0.065 0.050 0.041 0.033 0.033 0.027 0.022
Reactance at 50Hz in Ohm/km 0.093 0.089 0.084 0.081 0.081 0.079 0.078 0.074 0.072 0.072 0.073 0.072 0.071 0.071 0.070 0.036 0.036 0.037 0.036 0.036 0.036 0.035 0.024 0.024 0.023
Nominal Current Rating in amps. 39 48 65 83 107 128 152 187 226 258 291 329 380 427 490 452 516 582 658 760 854 980 1140 1281 1470
Installed Current Rating in amps. 24.76 30.48 40.81 51.53 66.43 78.56 93.29 113.45 137.12 154.71 174.50 194.96 225.19 250.03 286.91 274.23 309.42 349.00 389.93 450.37 500.05 573.83 675.56 750.08 860.74
75 130.46 - - - - - - - - 64 70 74 79 85 89 94 127 139 148 159 171 178 187 256 267 281
90 156.55 - - - - - - - - - - 62 66 71 74 78 106 116 123 132 142 149 156 214 223 234
110 191.34 - - - - - - - - - - - 54 58 61 64 87 95 101 108 117 122 128 175 182 191
132 229.61 - - - - - - - - - - - - - 51 53 72 79 84 90 97 101 106 146 152 159
160 272.19 - - - - - - - - - - - - - - 45 61 67 71 76 82 85 90 123 128 135
250 457.65 - - - - - - - - - - - - - - - - - - - - 51 53 73 76 80
Appendix-1
TABLE 1b: CABLE SIZES FOR 415V MOTOR FEEDER (THREE CORE CABLE LAID ON CABLE TRAY/LADDER IN AIR)
Maximum permissible length during motor running condition is given by: Maximum permissible length during motor starting condition is given by:
𝐿_(𝑀𝑎𝑥−𝑃𝑒𝑟𝑚𝑖𝑠𝑠𝑖𝑏𝑙𝑒)=(𝑉_𝑑𝑠.𝑉.1000)/(√3.𝐼_𝑆.(𝑅.𝑐𝑜𝑠∅_𝑆+𝑋.𝑠𝑖𝑛∅_𝑆 ).100)
𝐿_(𝑀𝑎𝑥−𝑃𝑒𝑟𝑚𝑖𝑠𝑠𝑖𝑏𝑙𝑒)=(𝑉_𝑑𝑟.𝑉.1000)/(√3.𝐼_𝐿.(𝑅.𝑐𝑜𝑠∅_𝐿+𝑋.𝑠𝑖𝑛∅_𝐿 ).100)
Notes:
Specifications
1) Refer Oman cable catelouge for continuous current carrying
Supply Voltage 415 V capacity of the cable.
2) Motor full load current have been considered based on typical
System Frequency 50 Hz motor manufacturer catelouge.
sinØr 0.53
sinØs 0.98
Data For Cable Type XLPE Insulated Copper Conductor Armoured Cable
Cross section in mm2 3/C-4 3/C-6 3/C-10 3/C-16 3/C-25 3/C-35 3/C-50 3/C-70 3/C-95 3/C-120 3/C-150 3/C-185 3/C-240 3/C-300 3/C-400 2#3/C-95 2#3/C-120 2#3/C-150 2#3/C-185 2#3/C-240 2#3/C-300 2#3/C-400 3#3/C-240 3#3/C-300 3#3/C-400
Approximate voltage drop per
10.2 6.8 4.0 2.5 1.65 1.15 0.87 0.60 0.45 0.37 0.30 0.26 0.21 0.19 0.17 0.225 0.185 0.15 0.13 0.105 0.095 0.085 0.070 0.063 0.057
ampere per metre (mV)
AC Resistance at 900C
5.88 3.93 2.33 1.47 0.927 0.668 0.494 0.343 0.248 0.197 0.16 0.129 0.100 0.082 0.066 0.124 0.099 0.080 0.065 0.050 0.041 0.033 0.033 0.027 0.022
Ohm/km
Reactance at 50Hz in Ohm/km 0.093 0.089 0.084 0.081 0.081 0.079 0.078 0.074 0.072 0.072 0.073 0.072 0.071 0.071 0.070 0.036 0.036 0.037 0.036 0.036 0.036 0.035 0.024 0.024 0.023
0.55 1.20 657 953 1517 2228 3142 3943 4748 5896 6924 7567 8036 8635 9289 9689 10172 13849 15134 16072 17270 18577 19378 20345 27866 29067 30517
1.1 2.39 330 478 762 1119 1578 1980 2384 2960 3477 3799 4035 4336 4664 4865 5107 6953 7599 8070 8671 9328 9729 10215 13991 14594 15322
1.5 3.26 242 351 559 820 1157 1451 1748 2170 2549 2785 2958 3179 3419 3566 3744 5098 5571 5916 6357 6838 7133 7489 10257 10699 11233
2.2 4.78 165 239 381 559 789 990 1192 1480 1738 1900 2017 2168 2332 2432 2554 3477 3799 4035 4336 4664 4865 5107 6996 7297 7661
3 6.52 121 175 279 410 578 726 874 1085 1274 1393 1479 1589 1710 1783 1872 2549 2785 2958 3179 3419 3566 3744 5129 5350 5617
4 8.70 91 131 209 307 433 544 655 813 955 1044 1108 1191 1281 1336 1403 1910 2087 2217 2382 2562 2673 2806 3844 4009 4209
5.5 11.96 66 96 152 224 315 396 476 592 695 759 806 866 932 972 1021 1390 1518 1613 1733 1864 1944 2041 2796 2916 3062
7.5 16.30 48 70 112 164 231 290 350 434 510 557 592 636 684 713 749 1020 1114 1183 1271 1368 1427 1498 2051 2140 2247
11 20.23 39 57 90 132 186 234 282 350 411 449 477 512 551 575 603 821 898 953 1024 1102 1149 1207 1653 1724 1810
15 27.59 - 41 66 97 137 171 207 256 301 329 350 376 404 421 442 602 658 699 751 808 843 885 1212 1264 1327
18.5 34.02 - - 54 79 111 139 167 208 244 267 283 305 328 342 359 489 534 567 609 655 684 718 983 1025 1076
22 40.46 - - 45 66 93 117 141 175 205 224 238 256 275 287 302 411 449 477 512 551 575 603 826 862 905
30 55.17 - - - 48 68 86 103 128 151 165 175 188 202 211 221 301 329 350 376 404 421 443 606 632 664
37 68.05 - - - - 55 70 84 104 122 133 142 152 164 171 179 244 267 283 305 328 342 359 491 513 538
45 78.28 - - - - 48 60 73 90 106 116 123 132 142 149 156 212 232 246 265 285 297 312 427 446 468
Appendix-1
TABLE 1b: CABLE SIZES FOR 415V MOTOR FEEDER (THREE CORE CABLE LAID ON CABLE TRAY/LADDER IN AIR)
Maximum permissible length during motor running condition is given by: Maximum permissible length during motor starting condition is given by:
𝐿_(𝑀𝑎𝑥−𝑃𝑒𝑟𝑚𝑖𝑠𝑠𝑖𝑏𝑙𝑒)=(𝑉_𝑑𝑠.𝑉.1000)/(√3.𝐼_𝑆.(𝑅.𝑐𝑜𝑠∅_𝑆+𝑋.𝑠𝑖𝑛∅_𝑆 ).100)
𝐿_(𝑀𝑎𝑥−𝑃𝑒𝑟𝑚𝑖𝑠𝑠𝑖𝑏𝑙𝑒)=(𝑉_𝑑𝑟.𝑉.1000)/(√3.𝐼_𝐿.(𝑅.𝑐𝑜𝑠∅_𝐿+𝑋.𝑠𝑖𝑛∅_𝐿 ).100)
Notes:
Specifications
1) Refer Oman cable catelouge for continuous current carrying
Supply Voltage 415 V capacity of the cable.
2) Motor full load current have been considered based on typical
System Frequency 50 Hz motor manufacturer catelouge.
sinØr 0.53
sinØs 0.98
Data For Cable Type XLPE Insulated Copper Conductor Armoured Cable
Cross section in mm2 3/C-4 3/C-6 3/C-10 3/C-16 3/C-25 3/C-35 3/C-50 3/C-70 3/C-95 3/C-120 3/C-150 3/C-185 3/C-240 3/C-300 3/C-400 2#3/C-95 2#3/C-120 2#3/C-150 2#3/C-185 2#3/C-240 2#3/C-300 2#3/C-400 3#3/C-240 3#3/C-300 3#3/C-400
Approximate voltage drop per
10.2 6.8 4.0 2.5 1.65 1.15 0.87 0.60 0.45 0.37 0.30 0.26 0.21 0.19 0.17 0.225 0.185 0.15 0.13 0.105 0.095 0.085 0.070 0.063 0.057
ampere per metre (mV)
AC Resistance at 900C
5.88 3.93 2.33 1.47 0.927 0.668 0.494 0.343 0.248 0.197 0.16 0.129 0.100 0.082 0.066 0.124 0.099 0.080 0.065 0.050 0.041 0.033 0.033 0.027 0.022
Ohm/km
Reactance at 50Hz in Ohm/km 0.093 0.089 0.084 0.081 0.081 0.079 0.078 0.074 0.072 0.072 0.073 0.072 0.071 0.071 0.070 0.036 0.036 0.037 0.036 0.036 0.036 0.035 0.024 0.024 0.023
Appendix-1
TABLE 2a: CABLE SIZES FOR 415V POWER FEEDER (FOUR CORE CABLE LAID IN UNDERGROUND DUCT BANK)
Maximum permissible length during motor running condition is given by: Maximum permissible length during motor starting condition is given by:
𝐿_(𝑀𝑎𝑥−𝑃𝑒𝑟𝑚𝑖𝑠𝑠𝑖𝑏𝑙𝑒)=(𝑉_𝑑𝑟.𝑉.1000)/(√3.𝐼_𝐿.(𝑅.𝑐𝑜𝑠∅_𝐿+𝑋.𝑠𝑖𝑛∅_𝐿 ).100) 𝐿_(𝑀𝑎𝑥−𝑃𝑒𝑟𝑚𝑖𝑠𝑠𝑖𝑏𝑙𝑒)=(𝑉_𝑑𝑠.𝑉.1000)/(√3.𝐼_𝑆.(𝑅.𝑐𝑜𝑠∅_𝑆+𝑋.𝑠𝑖𝑛∅_𝑆 ).100)
Specifications Notes:
1) Refer Oman cable catelouge for continuous current
Supply Voltage 415 V carrying capacity of the cable.
System Frequency 50 Hz
sinØr 0.52678269
Data For Cable Type XLPE Insulated Copper Conductor Armoured Cable
Cross section in mm2 4/C-4 4/C-6 4/C-10 4/C-16 4/C-25 4/C-35 4/C-50 4/C-70 4/C-95 4/C-120 4/C-150 4/C-185 4/C-240 4/C-300 4/C-400 2#4/C-95 2#4/C-120 2#4/C-150 2#4/C-185 2#4/C-240 2#4/C-300 2#4/C-400 3#4/C-240 3#4/C-300 3#4/C-400 4#4/C-300 4#4/C-400 6#4/C-300 7#4/C-400 8#4/C-400
Approximate voltage drop per
10.2 6.8 4.0 2.5 1.65 1.15 0.87 0.60 0.45 0.37 0.30 0.26 0.21 0.19 0.17 0.225 0.185 0.15 0.13 0.105 0.095 0.085 0.070 0.063 0.057 0.048 0.043 0.032 0.024 0.021
ampere per metre (mV)
AC Resistance at 900C
5.88 3.93 2.33 1.47 0.927 0.668 0.494 0.343 0.248 0.197 0.16 0.129 0.100 0.082 0.066 0.124 0.099 0.080 0.065 0.050 0.041 0.033 0.033 0.027 0.022 0.020 0.017 0.014 0.009 0.008
Ohm/km
Reactance at 50Hz in
0.093 0.089 0.084 0.081 0.081 0.079 0.078 0.074 0.072 0.072 0.073 0.072 0.071 0.071 0.070 0.036 0.036 0.037 0.036 0.036 0.036 0.035 0.024 0.024 0.023 0.018 0.018 0.012 0.010 0.009
Ohm/km
Nominal Current Rating in
39 48 65 83 107 128 152 187 226 258 291 329 380 427 490 452 516 582 658 760 854 980 1140 1281 1470 1708 1960 2562 3430 3920
amps.
Installed Current Rating in
24.76 30.48 40.81 51.53 66.43 78.56 93.29 113.45 137.12 154.71 174.50 194.96 225.19 250.03 286.91 274.23 309.42 349.00 389.93 450.37 500.05 573.83 675.56 750.08 860.74 1000.10 1147.66 1500.15 2008.40 2295.32
amps.
Appendix-1
TABLE 2b: CABLE SIZES FOR 415V POWER FEEDER (FOUR CORE CABLE LAID DIRECT BURRIED IN GROUND)
Maximum permissible length during motor running condition is given by: Maximum permissible length during motor starting condition is given by:
𝐿_(𝑀𝑎𝑥−𝑃𝑒𝑟𝑚𝑖𝑠𝑠𝑖𝑏𝑙𝑒)=(𝑉_𝑑𝑟.𝑉.1000)/(√3.𝐼_𝐿.(𝑅.𝑐𝑜𝑠∅_𝐿+𝑋.𝑠𝑖𝑛∅_𝐿 ).100) 𝐿_(𝑀𝑎𝑥−𝑃𝑒𝑟𝑚𝑖𝑠𝑠𝑖𝑏𝑙𝑒)=(𝑉_𝑑𝑠.𝑉.1000)/(√3.𝐼_𝑆.(𝑅.𝑐𝑜𝑠∅_𝑆+𝑋.𝑠𝑖𝑛∅_𝑆 ).100)
Specifications Notes:
1) Refer Oman cable catelouge for continuous current
Supply Voltage 415 V carrying capacity of the cable.
System Frequency 50 Hz
sinØr 0.52678269
Data For Cable Type XLPE Insulated Copper Conductor Armoured Cable
Cross section in mm2 4/C-4 4/C-6 4/C-10 4/C-16 4/C-25 4/C-35 4/C-50 4/C-70 4/C-95 4/C-120 4/C-150 4/C-185 4/C-240 4/C-300 4/C-400 2#4/C-95 2#4/C-120 2#4/C-150 2#4/C-185 2#4/C-240 2#4/C-300 2#4/C-400 3#4/C-240 3#4/C-300 3#4/C-400 4#4/C-300 4#4/C-400 6#4/C-300 7#4/C-400 8#4/C-400
Approximate voltage drop per
10.2 6.8 4.0 2.5 1.65 1.15 0.87 0.60 0.45 0.37 0.30 0.26 0.21 0.19 0.17 0.225 0.185 0.15 0.13 0.105 0.095 0.085 0.070 0.063 0.057 0.048 0.043 0.032 0.024 0.021
ampere per metre (mV)
AC Resistance at 900C
5.88 3.93 2.33 1.47 0.927 0.668 0.494 0.343 0.248 0.197 0.16 0.129 0.100 0.082 0.066 0.124 0.099 0.080 0.065 0.050 0.041 0.033 0.033 0.027 0.022 0.020 0.017 0.014 0.009 0.008
Ohm/km
Reactance at 50Hz in
0.093 0.089 0.084 0.081 0.081 0.079 0.078 0.074 0.072 0.072 0.073 0.072 0.071 0.071 0.070 0.036 0.036 0.037 0.036 0.036 0.036 0.035 0.024 0.024 0.023 0.018 0.018 0.012 0.010 0.009
Ohm/km
Nominal Current Rating in
47 59 79 102 131 157 187 229 274 312 349 394 455 509 574 548 624 698 788 910 1018 1148 1365 1527 1722 2036 2296 3054 4018 4592
amps.
Installed Current Rating in
24.98 31.35 41.45 52.83 67.85 80.27 95.60 114.34 136.81 155.79 174.26 194.11 224.16 250.77 276.90 273.63 311.58 348.53 388.22 448.32 501.53 553.79 672.48 752.30 830.69 1003.06 1107.59 1504.59 1938.28 2215.17
amps.
Appendix-1
TABLE 2c: CABLE SIZES FOR 415V POWER FEEDER (FOUR CORE CABLE LAID ON CABLE TRAY/LADDER IN AIR)
Maximum permissible length during motor running condition is given by: Maximum permissible length during motor starting condition is given by:
𝐿_(𝑀𝑎𝑥−𝑃𝑒𝑟𝑚𝑖𝑠𝑠𝑖𝑏𝑙𝑒)=(𝑉_𝑑𝑟.𝑉.1000)/(√3.𝐼_𝐿.(𝑅.𝑐𝑜𝑠∅_𝐿+𝑋.𝑠𝑖𝑛∅_𝐿 ).100) 𝐿_(𝑀𝑎𝑥−𝑃𝑒𝑟𝑚𝑖𝑠𝑠𝑖𝑏𝑙𝑒)=(𝑉_𝑑𝑠.𝑉.1000)/(√3.𝐼_𝑆.(𝑅.𝑐𝑜𝑠∅_𝑆+𝑋.𝑠𝑖𝑛∅_𝑆 ).100)
Specifications
Supply Voltage 415 V
System Frequency 50 Hz
sinØr 0.52678269
Data For Cable Type XLPE Insulated Copper Conductor Armoured Cable
Cross section in mm2 4/C-4 4/C-6 4/C-10 4/C-16 4/C-25 4/C-35 4/C-50 4/C-70 4/C-95 4/C-120 4/C-150 4/C-185 4/C-240 4/C-300 4/C-400 2#4/C-95 2#4/C-120 2#4/C-150 2#4/C-185 2#4/C-240 2#4/C-300 2#4/C-400 3#4/C-240 3#4/C-300 3#4/C-400 4#4/C-300 4#4/C-400 6#4/C-300 7#4/C-400 8#4/C-400
Approximate voltage drop
10.2 6.8 4.0 2.5 1.65 1.15 0.87 0.60 0.45 0.37 0.30 0.26 0.21 0.19 0.17 0.225 0.185 0.15 0.13 0.105 0.095 0.085 0.070 0.063 0.057 0.048 0.043 0.032 0.024 0.021
per ampere per metre (mV)
AC Resistance at 900C
5.88 3.93 2.33 1.47 0.927 0.668 0.494 0.343 0.248 0.197 0.16 0.129 0.100 0.082 0.066 0.124 0.099 0.080 0.065 0.050 0.041 0.033 0.033 0.027 0.022 0.020 0.017 0.014 0.009 0.008
Ohm/km
Reactance at 50Hz in
0.093 0.089 0.084 0.081 0.081 0.079 0.078 0.074 0.072 0.072 0.073 0.072 0.071 0.071 0.070 0.036 0.036 0.037 0.036 0.036 0.036 0.035 0.024 0.024 0.023 0.018 0.018 0.012 0.010 0.009
Ohm/km
Nominal Current Rating in
37 46 64 83 109 134 163 205 253 293 335 386 456 519 597 506 586 670 772 912 1038 1194 1368 1557 1791 2076 2388 3114 4179 4776
amps.
Installed Current Rating in
27.01 33.58 46.72 60.59 79.57 97.82 118.99 149.65 184.69 213.89 244.55 281.78 332.88 378.87 435.81 369.38 427.78 489.10 563.56 665.76 757.74 871.62 998.64 1136.61 1307.43 1515.48 1743.24 2273.22 3050.67 3486.48
amps.
Appendix-1
TABLE 2c: CABLE SIZES FOR 415V POWER FEEDER (FOUR CORE CABLE LAID ON CABLE TRAY/LADDER IN AIR)
Maximum permissible length during motor running condition is given by: Maximum permissible length during motor starting condition is given by:
𝐿_(𝑀𝑎𝑥−𝑃𝑒𝑟𝑚𝑖𝑠𝑠𝑖𝑏𝑙𝑒)=(𝑉_𝑑𝑟.𝑉.1000)/(√3.𝐼_𝐿.(𝑅.𝑐𝑜𝑠∅_𝐿+𝑋.𝑠𝑖𝑛∅_𝐿 ).100)𝐿_(𝑀𝑎𝑥−𝑃𝑒𝑟𝑚𝑖𝑠𝑠𝑖𝑏𝑙𝑒)=(𝑉_𝑑𝑠.𝑉.1000)/(√3.𝐼_𝑆.(𝑅.𝑐𝑜𝑠∅_𝑆+𝑋.𝑠𝑖𝑛∅_𝑆 ).100)
Specifications
Supply Voltage 415 V
System Frequency 50 Hz
sinØr 0.5268
Data For Cable Type XLPE Insulated Copper Conductor Armoured Cable
Cross section in mm2 4/C-4 4/C-6 4/C-10 4/C-16 4/C-25 4/C-35 4/C-50 4/C-70 4/C-95 4/C-120 4/C-150 4/C-185 4/C-240 4/C-300 4/C-400 2#4/C-95 2#4/C-120 2#4/C-150 2#4/C-185 2#4/C-240 2#4/C-300 2#4/C-400 3#4/C-240 3#4/C-300 3#4/C-400 4#4/C-300 4#4/C-400 6#4/C-300 7#4/C-400 8#4/C-400
Approximate voltage drop per
10.2 6.8 4.0 2.5 1.65 1.15 0.87 0.60 0.45 0.37 0.30 0.26 0.21 0.19 0.17 0.225 0.185 0.15 0.13 0.105 0.095 0.085 0.070 0.063 0.057 0.048 0.043 0.032 0.024 0.021
ampere per metre (mV)
AC Resistance at 900C
5.88 3.93 2.33 1.47 0.927 0.668 0.494 0.343 0.248 0.197 0.16 0.129 0.100 0.082 0.066 0.124 0.099 0.080 0.065 0.050 0.041 0.033 0.033 0.027 0.022 0.020 0.017 0.014 0.009 0.008
Ohm/km
Reactance at 50Hz in Ohm/km 0.093 0.089 0.084 0.081 0.081 0.079 0.078 0.074 0.072 0.072 0.073 0.072 0.071 0.071 0.070 0.036 0.036 0.037 0.036 0.036 0.036 0.035 0.024 0.024 0.023 0.018 0.018 0.012 0.010 0.009
Nominal Current Rating in
37 46 64 83 109 134 163 205 253 293 335 386 456 519 597 506 586 670 772 912 1038 1194 1368 1557 1791 2076 2388 3114 4179 4776
amps.
Installed Current Rating in
27.01 33.58 46.72 60.59 79.57 97.82 118.99 149.7 184.7 213.89 244.55 281.78 332.88 378.87 435.81 369.38 427.78 489.10 563.56 665.76 757.74 871.62 998.64 1136.61 1307.43 1515.48 1743.24 2273.22 3050.67 3486.48
amps.
Appendix-1
TABLE 3a: CABLE SIZES FOR 380V POWER FEEDER (FOUR CORE CABLE LAID IN UNDERGROUND DUCT BANK)
Maximum permissible length during motor running condition is given by: Maximum permissible length during motor starting condition is given by:
𝐿_(𝑀𝑎𝑥−𝑃𝑒𝑟𝑚𝑖𝑠𝑠𝑖𝑏𝑙𝑒)=(𝑉_𝑑𝑟.𝑉.1000)/(√3.𝐼_𝐿.(𝑅.𝑐𝑜𝑠∅_𝐿+𝑋.𝑠𝑖𝑛∅_𝐿 ).100) 𝐿_(𝑀𝑎𝑥−𝑃𝑒𝑟𝑚𝑖𝑠𝑠𝑖𝑏𝑙𝑒)=(𝑉_𝑑𝑠.𝑉.1000)/(√3.𝐼_𝑆.(𝑅.𝑐𝑜𝑠∅_𝑆+𝑋.𝑠𝑖𝑛∅_𝑆 ).100)
Specifications
Supply Voltage 380 V
System Frequency 50 Hz
sinØr 0.6
Data For Cable Type XLPE Insulated Copper Conductor Armoured Cable
Cross section in mm2 4/C-4 4/C-6 4/C-10 4/C-16 4/C-25 4/C-35 4/C-50 4/C-70 4/C-95 4/C-120 4/C-150 4/C-185 4/C-240 4/C-300 4/C-400 2#4/C-95 2#4/C-120 2#4/C-150 2#4/C-185 2#4/C-240 2#4/C-300 2#4/C-400 3#4/C-150 3#4/C-185 3#4/C-240 3#4/C-300 3#4/C-400 4#4/C-185 4#4/C-240 4#4/C-300 4#4/C-400 5#4/C-240 6#4/C-300 7#4/C-400 8#4/C-400
Approximate voltage drop per
10.2 6.8 4.0 2.5 1.65 1.15 0.87 0.60 0.45 0.37 0.30 0.26 0.21 0.19 0.17 0.225 0.185 0.15 0.13 0.10500 0.09500 0.08500 0.1 0.08666667 0.070 0.063 0.057 0.065 0.053 0.048 0.043 0.042 0.032 0.024 0.021
ampere per metre (mV)
AC Resistance at 900C
5.88 3.93 2.33 1.47 0.927 0.668 0.494 0.343 0.248 0.197 0.16 0.129 0.100 0.082 0.066 0.124 0.099 0.080 0.065 0.050 0.041 0.033 0.053 0.043 0.033 0.027 0.022 0.032 0.025 0.020 0.017 0.020 0.014 0.009 0.008
Ohm/km
Reactance at 50Hz in
0.093 0.089 0.084 0.081 0.081 0.079 0.078 0.074 0.072 0.072 0.073 0.072 0.071 0.071 0.070 0.036 0.036 0.037 0.036 0.036 0.036 0.035 0.024 0.024 0.024 0.024 0.023 0.018 0.018 0.018 0.018 0.014 0.012 0.010 0.009
Ohm/km
Nominal Current Rating in
39 48 65 83 107 128 152 187 226 258 291 329 380 427 490 452 516 582 658 760 854 980 873 987 1140 1281 1470 1316 1520 1708 1960 1900 2562 3430 3920
amps.
Installed Current Rating in
24.76 30.48 40.81 51.53 66.43 78.56 93.29 113.45 137.12 154.71 174.50 194.96 225.19 250.03 286.91 274.23 309.42 349.00 389.93 450.37 500.05 573.83 523.49 584.89 675.56 750.08 860.74 779.85 900.74 1000.10 1147.66 1125.93 1500.15 2008.40 2295.32
amps.
5.0 230 343 573 896 1388 1885 2482 3441 4540 5463 6385 7493 8948 10176 11571 9081 10926 12770 14986 17895 20352 23143 19155 22479 26843 30528 34714 29972 35790 40704 46285 44738 61056 81000 92571
10.0 115 172 287 448 694 943 1241 1720 2270 2731 3193 3746 4474 5088 5786 4540 5463 6385 7493 8948 10176 11571 9578 11239 13421 15264 17357 14986 17895 20352 23143 22369 30528 40500 46285
15.0 77 114 191 299 463 628 827 1147 1513 1821 2128 2498 2983 3392 3857 3027 3642 4257 4995 5965 6784 7714 6385 7493 8948 10176 11571 9991 11930 13568 15428 14913 20352 27000 30857
25.0 - 69 115 179 278 377 496 688 908 1093 1277 1499 1790 2035 2314 1816 2185 2554 2997 3579 4070 4629 3831 4496 5369 6106 6943 5994 7158 8141 9257 8948 12211 16200 18514
30.0 - 57 96 149 231 314 414 573 757 910 1064 1249 1491 1696 1929 1513 1821 2128 2498 2983 3392 3857 3193 3746 4474 5088 5786 4995 5965 6784 7714 7456 10176 13500 15428
40.0 - - 72 112 174 236 310 430 568 683 798 937 1118 1272 1446 1135 1366 1596 1873 2237 2544 2893 2394 2810 3355 3816 4339 3746 4474 5088 5786 5592 7632 10125 11571
50.0 - - - 90 139 189 248 344 454 546 639 749 895 1018 1157 908 1093 1277 1499 1790 2035 2314 1916 2248 2684 3053 3471 2997 3579 4070 4629 4474 6106 8100 9257
75.0 - - - - - 126 165 229 303 364 426 500 597 678 771 605 728 851 999 1193 1357 1543 1277 1499 1790 2035 2314 1998 2386 2714 3086 2983 4070 5400 6171
100.0 - - - - - - - 172 227 273 319 375 447 509 579 454 546 639 749 895 1018 1157 958 1124 1342 1526 1736 1499 1790 2035 2314 2237 3053 4050 4629
125.0 - - - - - - - - 182 219 255 300 358 407 463 363 437 511 599 716 814 926 766 899 1074 1221 1389 1199 1432 1628 1851 1790 2442 3240 3703
150.0 - - - - - - - - - 182 213 250 298 339 386 303 364 426 500 597 678 771 639 749 895 1018 1157 999 1193 1357 1543 1491 2035 2700 3086
200.0 - - - - - - - - - - - - 224 254 289 227 273 319 375 447 509 579 479 562 671 763 868 749 895 1018 1157 1118 1526 2025 2314
225.0 - - - - - - - - - - - - 199 226 257 202 243 284 333 398 452 514 426 500 597 678 771 666 795 905 1029 994 1357 1800 2057
250.0 - - - - - - - - - - - - - 204 231 182 219 255 300 358 407 463 383 450 537 611 694 599 716 814 926 895 1221 1620 1851
300.0 - - - - - - - - - - - - - - - - 182 213 250 298 339 386 319 375 447 509 579 500 597 678 771 746 1018 1350 1543
350.0 - - - - - - - - - - - - - - - - - - 214 256 291 331 274 321 383 436 496 428 511 581 661 639 872 1157 1322
400.0 - - - - - - - - - - - - - - - - - - - 224 254 289 239 281 336 382 434 375 447 509 579 559 763 1012 1157
500.0 - - - - - - - - - - - - - - - - - - - - 204 231 192 225 268 305 347 300 358 407 463 447 611 810 926
600.0 - - - - - - - - - - - - - - - - - - - - - - - - 224 254 289 250 298 339 386 373 509 675 771
650.0 - - - - - - - - - - - - - - - - - - - - - - - - 206 235 267 231 275 313 356 344 470 623 712
800.0 - - - - - - - - - - - - - - - - - - - - - - - - - - 217 - 224 254 289 280 382 506 579
1000.0 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 204 231 224 305 405 463
1250.0 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 244 324 370
1600.0 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 253 289
2000.0 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 202 231
Appendix-1
TABLE 3b: CABLE SIZES FOR 380V POWER FEEDER (FOUR CORE CABLE LAID IN AIR)
Maximum permissible length during motor running condition is given by: Maximum permissible length during motor starting condition is given by:
𝐿_(𝑀𝑎𝑥−𝑃𝑒𝑟𝑚𝑖𝑠𝑠𝑖𝑏𝑙𝑒)=(𝑉_𝑑𝑟.𝑉.1000)/(√3.𝐼_𝐿.(𝑅.𝑐𝑜𝑠∅_𝐿+𝑋.𝑠𝑖𝑛∅_𝐿 ).100) 𝐿_(𝑀𝑎𝑥−𝑃𝑒𝑟𝑚𝑖𝑠𝑠𝑖𝑏𝑙𝑒)=(𝑉_𝑑𝑠.𝑉.1000)/(√3.𝐼_𝑆.(𝑅.𝑐𝑜𝑠∅_𝑆+𝑋.𝑠𝑖𝑛∅_𝑆 ).100)
Specifications
Supply Voltage 380 V
System Frequency 50 Hz
sinØr 0.6
Data For Cable Type XLPE Insulated Copper Conductor Armoured Cable
Cross section in mm2 4/C-4 4/C-6 4/C-10 4/C-16 4/C-25 4/C-35 4/C-50 4/C-70 4/C-95 4/C-120 4/C-150 4/C-185 4/C-240 4/C-300 4/C-400 2#4/C-95 2#4/C-120 2#4/C-150 2#4/C-185 2#4/C-240 2#4/C-300 2#4/C-400 3#4/C-240 3#4/C-300 3#4/C-400 4#4/C-300 4#4/C-400 6#4/C-300 7#4/C-400 8#4/C-400
Approximate voltage drop per
10.2 6.8 4.0 2.5 1.65 1.15 0.87 0.60 0.45 0.37 0.30 0.26 0.21 0.19 0.17 0.225 0.185 0.15 0.13 0.10500 0.09500 0.08500 0.070 0.063 0.057 0.048 0.043 0.032 0.024 0.021
ampere per metre (mV)
AC Resistance at 900C
5.88 3.93 2.33 1.47 0.927 0.668 0.494 0.343 0.248 0.197 0.16 0.129 0.100 0.082 0.066 0.124 0.099 0.080 0.065 0.050 0.041 0.033 0.033 0.027 0.022 0.020 0.017 0.014 0.009 0.008
Ohm/km
Reactance at 50Hz in
0.093 0.089 0.084 0.081 0.081 0.079 0.078 0.074 0.072 0.072 0.073 0.072 0.071 0.071 0.070 0.036 0.036 0.037 0.036 0.036 0.036 0.035 0.024 0.024 0.023 0.018 0.018 0.012 0.010 0.009
Ohm/km
Nominal Current Rating in
37 46 64 83 109 134 163 205 253 293 335 386 456 519 597 506 586 670 772 912 1038 1194 1368 1557 1791 2076 2388 3114 4179 4776
amps.
Installed Current Rating in
27.01 33.58 46.72 60.59 79.57 97.82 118.99 149.65 184.69 213.89 244.55 281.78 332.88 378.87 435.81 369.38 427.78 489.10 563.56 665.76 757.74 871.62 998.64 1136.61 1307.43 1515.48 1743.24 2273.22 3050.67 3486.48
amps.
5.0 230 343 573 896 1388 1885 2482 3441 4540 5463 6385 7493 8948 10176 11571 9081 10926 12770 14986 17895 20352 23143 26843 30528 34714 40704 46285 61056 81000 92571
10.0 115 172 287 448 694 943 1241 1720 2270 2731 3193 3746 4474 5088 5786 4540 5463 6385 7493 8948 10176 11571 13421 15264 17357 20352 23143 30528 40500 46285
15.0 77 114 191 299 463 628 827 1147 1513 1821 2128 2498 2983 3392 3857 3027 3642 4257 4995 5965 6784 7714 8948 10176 11571 13568 15428 20352 27000 30857
25.0 46 69 115 179 278 377 496 688 908 1093 1277 1499 1790 2035 2314 1816 2185 2554 2997 3579 4070 4629 5369 6106 6943 8141 9257 12211 16200 18514
30.0 - 57 96 149 231 314 414 573 757 910 1064 1249 1491 1696 1929 1513 1821 2128 2498 2983 3392 3857 4474 5088 5786 6784 7714 10176 13500 15428
40.0 - - 72 112 174 236 310 430 568 683 798 937 1118 1272 1446 1135 1366 1596 1873 2237 2544 2893 3355 3816 4339 5088 5786 7632 10125 11571
50.0 - - - 90 139 189 248 344 454 546 639 749 895 1018 1157 908 1093 1277 1499 1790 2035 2314 2684 3053 3471 4070 4629 6106 8100 9257
75.0 - - - - 93 126 165 229 303 364 426 500 597 678 771 605 728 851 999 1193 1357 1543 1790 2035 2314 2714 3086 4070 5400 6171
100.0 - - - - - - 124 172 227 273 319 375 447 509 579 454 546 639 749 895 1018 1157 1342 1526 1736 2035 2314 3053 4050 4629
125.0 - - - - - - - 138 182 219 255 300 358 407 463 363 437 511 599 716 814 926 1074 1221 1389 1628 1851 2442 3240 3703
150.0 - - - - - - - - 151 182 213 250 298 339 386 303 364 426 500 597 678 771 895 1018 1157 1357 1543 2035 2700 3086
200.0 - - - - - - - - - 137 160 187 224 254 289 227 273 319 375 447 509 579 671 763 868 1018 1157 1526 2025 2314
225.0 - - - - - - - - - - 142 167 199 226 257 202 243 284 333 398 452 514 597 678 771 905 1029 1357 1800 2057
250.0 - - - - - - - - - - - 150 179 204 231 182 219 255 300 358 407 463 537 611 694 814 926 1221 1620 1851
300.0 - - - - - - - - - - - - 149 170 193 151 182 213 250 298 339 386 447 509 579 678 771 1018 1350 1543
350.0 - - - - - - - - - - - - - 145 165 130 156 182 214 256 291 331 383 436 496 581 661 872 1157 1322
400.0 - - - - - - - - - - - - - - 145 - 137 160 187 224 254 289 336 382 434 509 579 763 1012 1157
500.0 - - - - - - - - - - - - - - - - - - 150 179 204 231 268 305 347 407 463 611 810 926
600.0 - - - - - - - - - - - - - - - - - - - 149 170 193 224 254 289 339 386 509 675 771
650.0 - - - - - - - - - - - - - - - - - - - 138 157 178 206 235 267 313 356 470 623 712
800.0 - - - - - - - - - - - - - - - - - - - - - 145 168 191 217 254 289 382 506 579
1000.0 - - - - - - - - - - - - - - - - - - - - - - - 153 174 204 231 305 405 463
1250.0 - - - - - - - - - - - - - - - - - - - - - - - - 139 163 185 244 324 370
1600.0 - - - - - - - - - - - - - - - - - - - - - - - - - - 145 191 253 289
2000.0 - - - - - - - - - - - - - - - - - - - - - - - - - - - 153 202 231
Appendix-1
TABLE 4a: CABLE SIZES FOR 440V POWER FEEDER (FOUR CORE CABLE LAID IN UNDERGROUND DUCT BANK)
Maximum permissible length during motor running condition is given by: Maximum permissible length during motor starting condition is given by:
𝐿_(𝑀𝑎𝑥−𝑃𝑒𝑟𝑚𝑖𝑠𝑠𝑖𝑏𝑙𝑒)=(𝑉_𝑑𝑟.𝑉.1000)/(√3.𝐼_𝐿.(𝑅.𝑐𝑜𝑠∅_𝐿+𝑋.𝑠𝑖𝑛∅_𝐿 ).100) 𝐿_(𝑀𝑎𝑥−𝑃𝑒𝑟𝑚𝑖𝑠𝑠𝑖𝑏𝑙𝑒)=(𝑉_𝑑𝑠.𝑉.1000)/(√3.𝐼_𝑆.(𝑅.𝑐𝑜𝑠∅_𝑆+𝑋.𝑠𝑖𝑛∅_𝑆 ).100)
Specifications
Supply Voltage 440 V
System Frequency 60 Hz
sinØr 0.6
Data For Cable Type XLPE Insulated Copper Conductor Armoured Cable
Cross section in mm2 4/C-4 4/C-6 4/C-10 4/C-16 4/C-25 4/C-35 4/C-50 4/C-70 4/C-95 4/C-120 4/C-150 4/C-185 4/C-240 4/C-300 4/C-400 2#4/C-95 2#4/C-120 2#4/C-150 2#4/C-185 2#4/C-240 2#4/C-300 2#4/C-400 3#4/C-185 3#4/C-240 3#4/C-300 3#4/C-400 4#4/C-300 4#4/C-400 5#4/C-300 6#4/C-240 6#4/C-300 6#4/C-185 7#4/C-400 8#4/C-400
Approximate voltage drop per
10.2 6.8 4.0 2.5 1.65 1.15 0.87 0.60 0.45 0.37 0.30 0.26 0.21 0.19 0.17 0.225 0.185 0.15 0.13 0.105 0.095 0.085 0.08666667 0.070 0.063 0.057 0.048 0.043 0.038 0.035 0.032 0.04333333 0.024 0.021
ampere per metre (mV)
AC Resistance at 900C
5.88 3.93 2.33 1.47 0.927 0.668 0.494 0.343 0.248 0.197 0.16 0.129 0.100 0.082 0.066 0.124 0.099 0.080 0.065 0.050 0.041 0.033 0.043 0.033 0.027 0.022 0.020 0.017 0.016 0.017 0.014 0.022 0.009 0.008
Ohm/km
Reactance at 50Hz in
0.093 0.089 0.084 0.081 0.081 0.079 0.078 0.074 0.072 0.072 0.073 0.072 0.071 0.071 0.070 0.036 0.036 0.037 0.036 0.036 0.036 0.035 0.024 0.024 0.024 0.023 0.018 0.018 0.014 0.012 0.012 0.012 0.010 0.009
Ohm/km
Reactance at 60Hz in
0.112 0.107 0.101 0.097 0.097 0.095 0.094 0.089 0.086 0.086 0.088 0.086 0.085 0.085 0.084 0.043 0.043 0.044 0.043 0.043 0.043 0.042 0.029 0.028 0.028 0.028 0.021 0.021 0.017 0.014 0.014 0.014 0.012 0.011
Ohm/km
Nominal Current Rating in
39 48 65 83 107 128 152 187 226 258 291 329 380 427 490 452 516 582 658 760 854 980 987 1140 1281 1470 1708 1960 2135 2280 2562 1974 3430 3920
amps.
Installed Current Rating in
24.76 30.48 40.81 51.53 66.43 78.56 93.29 113.45 137.12 154.71 174.50 194.96 225.19 250.03 286.91 274.23 309.42 349.00 389.93 450.37 500.05 573.83 584.89 675.56 750.08 860.74 1000.10 1147.66 1250.13 1351.12 1500.15 1169.78 2008.40 2295.32
amps.
5.0 266 396 660 1029 1588 2148 2814 3876 5076 6065 7035 8193 9687 10920 12308 10152 12129 14069 16385 19374 21839 24616 24578 29061 32759 36924 43678 49231 54598 58123 65518 49155 86155 98463
10.0 133 198 330 515 794 1074 1407 1938 2538 3032 3517 4096 4844 5460 6154 5076 6065 7035 8193 9687 10920 12308 12289 14531 16379 18462 21839 24616 27299 29061 32759 24578 43077 49231
15.0 89 132 220 343 529 716 938 1292 1692 2022 2345 2731 3229 3640 4103 3384 4043 4690 5462 6458 7280 8205 8193 9687 10920 12308 14559 16410 18199 19374 21839 16385 28718 32821
25.0 - 79 132 206 318 430 563 775 1015 1213 1407 1639 1937 2184 2462 2030 2426 2814 3277 3875 4368 4923 4916 5812 6552 7385 8736 9846 10920 11625 13104 9831 17231 19693
30.0 - 66 110 172 265 358 469 646 846 1011 1172 1365 1615 1820 2051 1692 2022 2345 2731 3229 3640 4103 4096 4844 5460 6154 7280 8205 9100 9687 10920 8193 14359 16410
40.0 - - 83 129 198 269 352 485 634 758 879 1024 1211 1365 1538 1269 1516 1759 2048 2422 2730 3077 3072 3633 4095 4615 5460 6154 6825 7265 8190 6144 10769 12308
50.0 - - - 103 159 215 281 388 508 606 703 819 969 1092 1231 1015 1213 1407 1639 1937 2184 2462 2458 2906 3276 3692 4368 4923 5460 5812 6552 4916 8615 9846
75.0 - - - - - 143 188 258 338 404 469 546 646 728 821 677 809 938 1092 1292 1456 1641 1639 1937 2184 2462 2912 3282 3640 3875 4368 3277 5744 6564
100.0 - - - - - - - 194 254 303 352 410 484 546 615 508 606 703 819 969 1092 1231 1229 1453 1638 1846 2184 2462 2730 2906 3276 2458 4308 4923
125.0 - - - - - - - - 203 243 281 328 387 437 492 406 485 563 655 775 874 985 983 1162 1310 1477 1747 1969 2184 2325 2621 1966 3446 3939
150.0 - - - - - - - - - 202 234 273 323 364 410 338 404 469 546 646 728 821 819 969 1092 1231 1456 1641 1820 1937 2184 1639 2872 3282
200.0 - - - - - - - - - - - - 242 273 308 254 303 352 410 484 546 615 614 727 819 923 1092 1231 1365 1453 1638 1229 2154 2462
225.0 - - - - - - - - - - - - 215 243 274 226 270 313 364 431 485 547 546 646 728 821 971 1094 1213 1292 1456 1092 1915 2188
250.0 - - - - - - - - - - - - - 218 246 203 243 281 328 387 437 492 492 581 655 738 874 985 1092 1162 1310 983 1723 1969
300.0 - - - - - - - - - - - - - - - - 202 234 273 323 364 410 410 484 546 615 728 821 910 969 1092 819 1436 1641
350.0 - - - - - - - - - - - - - - - - - - 234 277 312 352 351 415 468 527 624 703 780 830 936 702 1231 1407
400.0 - - - - - - - - - - - - - - - - - - - 242 273 308 307 363 409 462 546 615 682 727 819 614 1077 1231
500.0 - - - - - - - - - - - - - - - - - - - - 218 246 246 291 328 369 437 492 546 581 655 492 862 985
600.0 - - - - - - - - - - - - - - - - - - - - - - - 242 273 308 364 410 455 484 546 410 718 821
630.0 - - - - - - - - - - - - - - - - - - - - - - - 231 260 293 347 391 433 461 520 390 684 781
800.0 - - - - - - - - - - - - - - - - - - - - - - - - - 231 273 308 341 363 409 307 538 615
1000.0 - - - - - - - - - - - - - - - - - - - - - - - - - - 218 246 273 291 328 246 431 492
1250.0 - - - - - - - - - - - - - - - - - - - - - - - - - - - - 218 232 262 - 345 394
1600.0 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 269 308
2000.0 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 215 246
Appendix-1
TABLE 4b: CABLE SIZES FOR 440V POWER FEEDER (FOUR CORE CABLE LAID IN AIR)
Maximum permissible length during motor running condition is given by: Maximum permissible length during motor starting condition is given by:
𝐿_(𝑀𝑎𝑥−𝑃𝑒𝑟𝑚𝑖𝑠𝑠𝑖𝑏𝑙𝑒)=(𝑉_𝑑𝑟.𝑉.1000)/(√3.𝐼_𝐿.(𝑅.𝑐𝑜𝑠∅_𝐿+𝑋.𝑠𝑖𝑛∅_𝐿 ).100) 𝐿_(𝑀𝑎𝑥−𝑃𝑒𝑟𝑚𝑖𝑠𝑠𝑖𝑏𝑙𝑒)=(𝑉_𝑑𝑠.𝑉.1000)/(√3.𝐼_𝑆.(𝑅.𝑐𝑜𝑠∅_𝑆+𝑋.𝑠𝑖𝑛∅_𝑆 ).100)
Specifications
Supply Voltage 440 V
System Frequency 60 Hz
sinØr 0.6
Data For Cable Type XLPE Insulated Copper Conductor Armoured Cable
Cross section in mm2 4/C-4 4/C-6 4/C-10 4/C-16 4/C-25 4/C-35 4/C-50 4/C-70 4/C-95 4/C-120 4/C-150 4/C-185 4/C-240 4/C-300 4/C-400 2#4/C-95 2#4/C-120 2#4/C-150 2#4/C-185 2#4/C-240 2#4/C-300 2#4/C-400 3#4/C-240 3#4/C-300 3#4/C-400 4#4/C-300 4#4/C-400 6#4/C-300 7#4/C-400 8#4/C-400
Approximate voltage drop per
10.2 6.8 4.0 2.5 1.65 1.15 0.87 0.60 0.45 0.37 0.30 0.26 0.21 0.19 0.17 0.225 0.185 0.15 0.13 0.105 0.095 0.085 0.070 0.063 0.057 0.048 0.043 0.032 0.024 0.021
ampere per metre (mV)
AC Resistance at 900C
5.88 3.93 2.33 1.47 0.927 0.668 0.494 0.343 0.248 0.197 0.16 0.129 0.100 0.082 0.066 0.124 0.099 0.080 0.065 0.050 0.041 0.033 0.033 0.027 0.022 0.020 0.017 0.014 0.009 0.008
Ohm/km
Reactance at 50Hz in
0.093 0.089 0.084 0.081 0.081 0.079 0.078 0.074 0.072 0.072 0.073 0.072 0.071 0.071 0.070 0.036 0.036 0.037 0.036 0.036 0.036 0.035 0.024 0.024 0.023 0.018 0.018 0.012 0.010 0.009
Ohm/km
Reactance at 60Hz in
0.112 0.107 0.101 0.097 0.097 0.095 0.094 0.089 0.086 0.086 0.088 0.086 0.085 0.085 0.084 0.043 0.043 0.044 0.043 0.043 0.043 0.042 0.028 0.028 0.028 0.021 0.021 0.014 0.012 0.011
Ohm/km
Nominal Current Rating in
37 46 64 83 109 134 163 205 253 293 335 386 456 519 597 506 586 670 772 912 1038 1194 1368 1557 1791 2076 2388 3114 4179 4776
amps.
Installed Current Rating in
27.01 33.58 46.72 60.59 79.57 97.82 118.99 149.65 184.69 213.89 244.55 281.78 332.88 378.87 435.81 369.38 427.78 489.10 563.56 665.76 757.74 871.62 998.64 1136.61 1307.43 1515.48 1743.24 2273.22 3050.67 3486.48
amps.
5.0 266 396 660 1029 1588 2148 2814 3876 5076 6065 7035 8193 9687 10920 12308 10152 12129 14069 16385 19374 21839 24616 29061 32759 36924 43678 49231 65518 86155 98463
10.0 133 198 330 515 794 1074 1407 1938 2538 3032 3517 4096 4844 5460 6154 5076 6065 7035 8193 9687 10920 12308 14531 16379 18462 21839 24616 32759 43077 49231
15.0 89 132 220 343 529 716 938 1292 1692 2022 2345 2731 3229 3640 4103 3384 4043 4690 5462 6458 7280 8205 9687 10920 12308 14559 16410 21839 28718 32821
25.0 53 79 132 206 318 430 563 775 1015 1213 1407 1639 1937 2184 2462 2030 2426 2814 3277 3875 4368 4923 5812 6552 7385 8736 9846 13104 17231 19693
30.0 - 66 110 172 265 358 469 646 846 1011 1172 1365 1615 1820 2051 1692 2022 2345 2731 3229 3640 4103 4844 5460 6154 7280 8205 10920 14359 16410
40.0 - - 83 129 198 269 352 485 634 758 879 1024 1211 1365 1538 1269 1516 1759 2048 2422 2730 3077 3633 4095 4615 5460 6154 8190 10769 12308
50.0 - - - 103 159 215 281 388 508 606 703 819 969 1092 1231 1015 1213 1407 1639 1937 2184 2462 2906 3276 3692 4368 4923 6552 8615 9846
75.0 - - - - 106 143 188 258 338 404 469 546 646 728 821 677 809 938 1092 1292 1456 1641 1937 2184 2462 2912 3282 4368 5744 6564
100.0 - - - - - - 141 194 254 303 352 410 484 546 615 508 606 703 819 969 1092 1231 1453 1638 1846 2184 2462 3276 4308 4923
125.0 - - - - - - - 155 203 243 281 328 387 437 492 406 485 563 655 775 874 985 1162 1310 1477 1747 1969 2621 3446 3939
150.0 - - - - - - - - 169 202 234 273 323 364 410 338 404 469 546 646 728 821 969 1092 1231 1456 1641 2184 2872 3282
200.0 - - - - - - - - - 152 176 205 242 273 308 254 303 352 410 484 546 615 727 819 923 1092 1231 1638 2154 2462
225.0 - - - - - - - - - - 156 182 215 243 274 226 270 313 364 431 485 547 646 728 821 971 1094 1456 1915 2188
250.0 - - - - - - - - - - - 164 194 218 246 203 243 281 328 387 437 492 581 655 738 874 985 1310 1723 1969
300.0 - - - - - - - - - - - - 161 182 205 169 202 234 273 323 364 410 484 546 615 728 821 1092 1436 1641
350.0 - - - - - - - - - - - - - 156 176 145 173 201 234 277 312 352 415 468 527 624 703 936 1231 1407
400.0 - - - - - - - - - - - - - - 154 - 152 176 205 242 273 308 363 409 462 546 615 819 1077 1231
500.0 - - - - - - - - - - - - - - - - - - 164 194 218 246 291 328 369 437 492 655 862 985
600.0 - - - - - - - - - - - - - - - - - - - 161 182 205 242 273 308 364 410 546 718 821
630.0 - - - - - - - - - - - - - - - - - - - 154 173 195 231 260 293 347 391 520 684 781
800.0 - - - - - - - - - - - - - - - - - - - - - 154 182 205 231 273 308 409 538 615
1000.0 - - - - - - - - - - - - - - - - - - - - - - - 164 185 218 246 328 431 492
1250.0 - - - - - - - - - - - - - - - - - - - - - - - - 148 175 197 262 345 394
1600.0 - - - - - - - - - - - - - - - - - - - - - - - - - - 154 205 269 308
2000.0 - - - - - - - - - - - - - - - - - - - - - - - - - - - 164 215 246
Appendix-1
TABLE 5: TRANSFORMER SECONDARY FEEDER CABLES - SIZING CHART FOR SINGLE CORE CABLES FOR
TRANSFORMERS SECONDARY
Derating Factor
Specifications
Supply Voltage 415 V Overall Derating Factor 0.90
System Frequency 50 Hz
Data For Cable Type XLPE Insulated Copper Conductor Armoured Cable
Cross section 1/C-120 1/C-150 1/C-185 1/C-240 1/C-300 1/C-400 1/C-500 1/C-630 1/C-800 1/C1000
Nominal Current Rating in amps. 328 377 433 510 581 664 751 846 919 997
Installed Current Rating in amps. 295 339 390 459 523 598 676 761 827 897
Transformer Full
Transformer
Load Current in No. of conductors per phase
Rating in kVA
Amps.
315 460 2 2 2 2 1 1 1 1 1 1
400 584 3 2 2 2 2 2 1 1 1 1
500 730 3 3 2 2 2 2 2 2 1 1
630 920 4 3 3 3 2 2 2 2 2 2
800 1169 5 4 4 3 3 3 2 2 2 2
1000 1461 6 5 4 4 3 3 3 3 2 2
1333 1947 7 7 6 5 4 4 4 3 3 3
1600 2337 9 8 7 6 5 5 4 4 3 3
2000 2922 11 10 8 7 6 6 5 5 4 4
2128 3109 12 10 9 8 7 6 5 5 4 4
2500 3652 13 12 10 9 8 7 6 6 5 5
System Frequency 50 Hz
Appendix-1
TABLE 5: TRANSFORMER SECONDARY FEEDER CABLES - SIZING CHART FOR SINGLE CORE CABLES FOR
TRANSFORMERS SECONDARY
Data For Cable Type XLPE Insulated Copper Conductor Armoured Cable
Cross section 1/C-120 1/C-150 1/C-185 1/C-240 1/C-300 1/C-400 1/C-500 1/C-630 1/C-800 1/C1000
Nominal Current Rating in amps. 328 377 433 510 581 664 751 846 919 997
Installed Current Rating in amps. 295 339 390 459 523 598 676 761 827 897
Transformer Full
Transformer
Load Current in No. of conductors per phase
Rating in kVA
Amps.
315 503 2 2 2 2 2 1 1 1 1 1
400 638 3 2 2 2 2 2 1 1 1 1
500 798 3 3 3 2 2 2 2 2 2 1
630 1005 4 4 3 3 3 2 2 2 2 2
800 1276 5 4 4 3 3 3 2 2 2 2
1000 1595 6 5 5 4 4 3 3 3 3 2
1333 2127 8 7 6 5 5 4 4 3 3 3
1600 2553 10 8 7 6 6 5 4 4 4 3
2000 3191 12 10 9 8 7 6 5 5 5 4
2128 3395 13 11 10 8 7 6 6 5 5 4
2500 3988 15 13 11 10 9 8 7 6 6 5
Derating Factor
Specifications
Supply Voltage 440 V Overall Derating Factor 0.90
System Frequency 50 Hz
Appendix-1
TABLE 5: TRANSFORMER SECONDARY FEEDER CABLES - SIZING CHART FOR SINGLE CORE CABLES FOR
TRANSFORMERS SECONDARY
Data For Cable Type XLPE Insulated Copper Conductor Armoured Cable
Cross section 1/C-120 1/C-150 1/C-185 1/C-240 1/C-300 1/C-400 1/C-500 1/C-630 1/C-800 1/C1000
Nominal Current Rating in amps. 328 377 433 510 581 664 751 846 919 997
Installed Current Rating in amps. 295 339 390 459 523 598 676 761 827 897
Transformer Full
Transformer
Load Current in No. of conductors per phase
Rating in kVA
Amps.
315 434 2 2 2 1 1 1 1 1 1 1
400 551 2 2 2 2 2 1 1 1 1 1
500 689 3 3 2 2 2 2 2 1 1 1
630 868 4 3 3 2 2 2 2 2 2 2
800 1102 4 4 3 3 3 2 2 2 2 2
1000 1378 5 5 4 4 3 3 3 2 2 2
1333 1837 7 6 5 5 4 4 3 3 3 3
1600 2204 8 7 6 6 5 4 4 4 3 3
2000 2756 10 9 8 7 6 5 5 4 4 4
2128 2932 11 10 8 7 6 6 5 5 4 4
2500 3445 13 11 10 8 7 7 6 5 5 5
Note
1) Transformer FL current = (kVA x 1000)/(1.732 x 415/380/440) amp
2) Refer Doha cable catelouge for continuous current carrying capacity of the
cables in air.
4D
PHASE CONDUCTOR
NEUTRAL CONDUCTOR
Appendix-1
TABLE 6: CABLE SIZES FOR 110V DC FEEDER (CABLES LAID ON TRAY/LADDER IN AIR)
Formula Vd x V x 1000
L Max-Permissable =
2 x IFLC x R x 100
Specifications Notes
1) Refer Oman cable catelouge for continuous current carrying
capacity of the cables in air.
Supply Voltage 110 V
Data For Cable Type XLPE Insulated Copper Conductor Armoured Cable
Cross section in mm2 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240
Cable Resistance at
7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754
200Cin Ω/km
Cable Resistance at
9.45 5.88 3.93 2.33 1.47 0.93 0.67 0.49 0.34 0.25 0.20 0.16 0.13 0.10
900Cin Ω/km
Nominal Current Rating
32.00 43.00 55.00 74.00 98.00 128.00 158.00 190.00 239.00 295.00 341.00 389.00 449.00 530.00
in amps.
Installed Current Rating
23.36 31.39 40.15 54.02 71.54 93.44 115.34 138.70 174.47 215.35 248.93 283.97 327.77 386.90
in amps
Feeder Rating in
Maximum Permissible Route Length (m)
Amps.
1.0 58 94 140 236 375 593 823 1115 1610 2235 2819 3479 4353 5721
3.0 19 31 47 79 125 198 274 372 537 745 940 1160 1451 1907
6.0 10 16 23 39 63 99 137 186 268 373 470 580 725 953
10.0 6 9 14 24 38 59 82 111 161 224 282 348 435 572
15.0 4 6 9 16 25 40 55 74 107 149 188 232 290 381
20.0 3 5 7 12 19 30 41 56 80 112 141 174 218 286
25.0 - 4 6 9 15 24 33 45 64 89 113 139 174 229
35.0 - - 4 7 11 17 24 32 46 64 81 99 124 163
45.0 - - - 5 8 13 18 25 36 50 63 77 97 127
60.0 - - - - 6 10 14 19 27 37 47 58 73 95
75.0 - - - - - 8 11 15 21 30 38 46 58 76
90.0 - - - - - 7 9 12 18 25 31 39 48 64
100.0 - - - - - - 8 11 16 22 28 35 44 57
145.0 - - - - - - - - 11 15 19 24 30 39
160.0 - - - - - - - - 10 14 18 22 27 36
200.0 - - - - - - - - - 11 14 17 22 29
Appendix-1
TABLE 6: CABLE SIZES FOR 110V DC FEEDER (CABLES LAID ON TRAY/LADDER IN AIR)
Formula Vd x V x 1000
L Max-Permissable =
2 x IFLC x R x 100
Specifications Notes
1) Refer Oman cable catelouge for continuous current carrying
capacity of the cables in air.
Supply Voltage 110 V
Data For Cable Type XLPE Insulated Copper Conductor Armoured Cable
Cross section in mm2 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240
Cable Resistance at
7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754
200Cin Ω/km
Cable Resistance at
9.45 5.88 3.93 2.33 1.47 0.93 0.67 0.49 0.34 0.25 0.20 0.16 0.13 0.10
900Cin Ω/km
Nominal Current Rating
32.00 43.00 55.00 74.00 98.00 128.00 158.00 190.00 239.00 295.00 341.00 389.00 449.00 530.00
in amps
Installed Current Rating
23.36 31.39 40.15 54.02 71.54 93.44 115.34 138.70 174.47 215.35 248.93 283.97 327.77 386.90
in amps
Feeder Rating in
Maximum Permissible Route Length (m)
Amps.
1.0 116 187 280 471 750 1187 1646 2229 3219 4470 5639 6957 8705 11442
3.0 39 62 93 157 250 396 549 743 1073 1490 1880 2319 2902 3814
6.0 19 31 47 79 125 198 274 372 537 745 940 1160 1451 1907
10.0 12 19 28 47 75 119 165 223 322 447 564 696 871 1144
15.0 8 12 19 31 50 79 110 149 215 298 376 464 580 763
20.0 6 9 14 24 38 59 82 111 161 224 282 348 435 572
25.0 - 7 11 19 30 47 66 89 129 179 226 278 348 458
35.0 - - 8 13 21 34 47 64 92 128 161 199 249 327
45.0 - - - 10 17 26 37 50 72 99 125 155 193 254
60.0 - - - - 13 20 27 37 54 75 94 116 145 191
75.0 - - - - - 16 22 30 43 60 75 93 116 153
90.0 - - - - - 13 18 25 36 50 63 77 97 127
125.0 - - - - - - - 18 26 36 45 56 70 92
145.0 - - - - - - - - 22 31 39 48 60 79
160.0 - - - - - - - - 20 28 35 43 54 72
200.0 - - - - - - - - - 22 28 35 44 57
Appendix-1
TABLE 8: CABLE SIZES FOR 240V AC FEEDER (CABLES LAID ON TRAY/LADDER IN AIR)
Formula Vd x V x 1000
L Max-Permissable =
2 x IFLC x mV x 100
Specifications Notes
1) Refer Oman cable catelouge for continuous current carrying
capacity of the cables in air.
Supply Voltage 240 V
System Frequency 50 Hz
Data For Cable Type XLPE Insulated Copper Conductor Armoured Cable
Cross section in mm2 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240
Approximate voltage drop per
18.9 11.8 7.9 4.7 2.9 1.9 1.35 1 0.7 0.52 0.42 0.35 0.29 0.24
ampere per metre (mV)
Nominal Current Rating in
32.00 43.00 55.00 74.00 98.00 128.00 158.00 190.00 239.00 295.00 341.00 389.00 449.00 530.00
amps.
Installed Current Rating in
23.36 31.39 40.15 54.02 71.54 93.44 115.34 138.70 174.47 215.35 248.93 283.97 327.77 386.90
amps.
Appendix-1
TABLE 7: CABLE SIZES FOR 240V AC FEEDER (CABLES LAID ON TRAY/LADDER IN AIR)
Formula Vd x V x 1000
L Max-Permissable =
2 x IFLC x mV x 100
Specifications Notes
1) Refer Oman cable catelouge for continuous current carrying
capacity of the cables in air.
Supply Voltage 240 V
System Frequency 50 Hz
Data For Cable Type XLPE Insulated Copper Conductor Armoured Cable
Cross section in mm2 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240
Approximate voltage drop per
18.9 11.8 7.9 4.7 2.9 1.9 1.35 1 0.7 0.52 0.42 0.35 0.29 0.24
ampere per metre (mV)
Nominal Current Rating in
32.00 43.00 55.00 74.00 98.00 128.00 158.00 190.00 239.00 295.00 341.00 289.00 449.00 530.00
amps.
Installed Current Rating in
23.36 31.39 40.15 54.02 71.54 93.44 115.34 138.70 174.47 215.35 248.93 210.97 327.77 386.90
amps.
Appendix-1
APPENDIX 2
9254-03-EL-CAL-2042
0.79 0.79 0.79 0.79 0.79 0.79 0.79 0.79 0.79 0.79 0.79 0.79 0.79 0.79 0.79
300mm
Depth of Laying (1.5 m) (Fd) 0.940 0.940 0.940 0.940 0.940 0.940 0.940 0.940 0.940 0.940 0.940 0.940 0.940 0.940 0.940
Variation in Thermal Resistivity of soil:
2.5Km/W (Fr) 0.90 0.90 0.89 0.880 0.880 0.870 0.870 0.860 0.860 0.850 0.850 0.840 0.840 0.830 0.830
0.73 0.73 0.73 0.73 0.73 0.73 0.73 0.73 0.73 0.73 0.73 0.73 0.73 0.73 0.73
300mm
Depth of Laying (0.8 m) (Fd) 0.970 0.970 0.970 0.970 0.970 0.970 0.970 0.960 0.960 0.960 0.960 0.960 0.960 0.960 0.940
Variation in Thermal Resistivity of soil:
2.5Km/W (Fr) 0.79 0.79 0.78 0.770 0.770 0.760 0.760 0.750 0.750 0.750 0.750 0.740 0.740 0.740 0.740
APPENDIX 2
9254-03-EL-CAL-2042
Overall Derating Factor (Fa x Fg x Fd x
0.53 0.53 0.52 0.52 0.52 0.51 0.51 0.50 0.50 0.50 0.50 0.49 0.49 0.49 0.48
Fr)
APPENDIX 2
9254-03-EL-CAL-2042
Rating factors for ambient air temperature (Fa) 1 Air Temperature 500C 300mm
Group rating factors for multicore cable laid on tray (Fg)0.73 6 numbers of multicore cables touching each others 300mm
20mm 3D
600mm
PHASE
CONDUCTORS NEUTRAL
CONDUCTOR