Grundfos Isolutions: We Bring More Than Pumps
Grundfos Isolutions: We Bring More Than Pumps
iSOLUTIONS
GRUNDFOS iSOLUTIONS
WE BRING MORE
THAN PUMPS…
JSX 2016 1
LCC (Life Cycle Costs)
Energy Consumption:
85%
Maintenence:10%
Investments: 5%
2
Why speed control
4
H
System
Pressure at Fixed speed
pump solution = 5 bar
Fixed
Excess speed
pressure
Required pressure = 3 bar
Reduced Nominal
Q
flow flow Qnom
Why speed control
By changing speed of the pump
the performance can be changed
and energy can be saved.
n 1450
Qx Qn x 12 6 [m3/h]
n
n 2900
2
n
2
1450
H x H n x 40 10 [m]
n
n 2900
3
n
3
1450
Px Pn x 11 1,37 [kW]
n
n 2900
5
Why speed control
Set point
An example: (constant pressure)
• A speed controlled pump automatically adapt
PI
the pump performance to the actual need. Controller
• The flow is reduced by lowering the speed of the pump
• The pressure is constant 3 bar
Freq.
conv.
H
System
Pressure at Fixed speed
pump solution = 5 bar
M
Fixed
Excess speed
pressure
Pressure at Variable speed Required pressure = 3 bar
pump solution = 3 bar
Variable speed
Reduced Nominal
Q
flow flow Qnom
Why speed control
An example
If the pump is a CRE 5-8:
By reduced flow
the power consumption is
reduced with 43%!
1.34 kW
Reduced 0.75 kW
with 43%
0.43 kW
Grundfos motors achieve highest energy
efficiency rating worldwide
CR15-4 w/MG Motor
Dutypoint: Q = 20 m3/h, H = 60 m
Energy consumption
10774 kWh/Year
Energy consumption
8484 kWh/Year
Energy consumption
7662 kWh/Year
100
79
71
9%
GRUNDFOS
iSOLUTIONS Which products are in the iSOLUTIONS range?
• Intelligent pumps – like e.g. Magna3 and MGE with built-in control features
• Intelligent controllers – e.g. the CU 352 and CU 362 with multi pump functions and much
more…
• Communication modules/units for communication to overall systems, like PLC’s and
SCADA systems
• A wide range of sensors to provide the measurements in the process and enabling us to
optimize the application, e.g. power, flow, specific energy etc.
• Intelligent motor protection and drives – for surveillance and optimization of
pumps/speed.
Pumps Controls
JSX 2016 14
GRUNDFOS
iSOLUTIONS
Alarm!
I am
stopped
JSX 2016 16
Communication
GRUNDFOS
iSOLUTIONS
JSX 2016 18
External setpoint function
Setpoint
Resulting setpoint
19
Settings – External setpoint influence
• Six different influence functions are available. The influence table can have up to 8 points
Inverse with MIN/STOP Influence table Influence table with STOP at MIN/MAX
20
External setpoint influence - Example
Setpoint influence H
100%
- 50 ºC
50 ºC
Temp [ºC] 21
External setpoint influence
Benefits!
• Avoiding external controller for doing the wanted function
• Improve functionality by influencing the setpoint
• Energy saving due to improved control of controlled parameter
22
Settings – Predefined setpoint
Predefined setpoint
Normal setpoint
STOP
23
Predefined setpoint – Application
example
Benefits!
• In wash and cleaning applications different tasks like “Foam dispensing”, “Flushing” and
“High pressure jets” requires different pressure from the cleaning pump.
By means of a switch the operator can change the setpoint of the constant pressure pump.
24
Settings – Limit exceed function 1 and 2
• Can monitor one of the Analog inputs, Pt100/1000 inputs or some selected internal values
such as Speed or Motor load. By Limit exceeded actions like Warning or Alarm + Stop can be
selected.
26
Limit exceed function?
Benefits!
• Cost saving - No need for a PLC to do this function
• Can supervise parameters which can cause damage to the pump or system and give a
warning or stop the pump if needed
• Can be used for making control of one of the relays or digital outputs
Application example
Pump running Constant differential
pressure. If a Pump differential pressure
are going below “Limit 1”, a Warning will
be generated.
Limit 1
Risk of
cavitation
27
Examples of Limit exceed function
A client wants to integrate a CRE 5-5 pump into a filtration system in order to achieve a constant
volume flow of 6 m3/h. The filter resistance may lead to 15–40m pressure drop.
The temperature should not exceed 25°C. By a lasting exceeding of the temperature (> 10s), an alarm
light should be activated.
Feed balance
tank
VFS 0,6–12
0.5–3.5V
Filter unit delta p = 15–40m
Operating
range
70 100
Transfer medium = water
Medium temperature = 20°C
Density = 998.2 kg/m3
29
30
m3/h
Electrical plug-
connection
PIN number
Example
Temperature
signal
Flow Pipeline
signal
AUTOMATIC CLEANING FILTER
Requirments:
- 30 bar on membrane inlet.
- Max. Flow 25 m3/h throw membrane.
33