Addressable Photoelectric Smoke Detectors: FSP-951 Series
Addressable Photoelectric Smoke Detectors: FSP-951 Series
Addressable Photoelectric Smoke Detectors: FSP-951 Series
Features
SLC LOOP: • Separate base allows interchange of photoelectric, ionization and
• Two-wire SLC loop connection thermal sensors
• Unit uses base for wiring OPTIONS:
• Compatible with FlashScan® and CLIP protocol systems • Optional relay, isolator, and sounder bases
• Stable communication technique with noise immunity
Installation
ADDRESSING:
FSP-951 Series plug-in intelligent smoke detectors use a detach-
• Addressable by device able base to simplify installation, service and maintenance. Installa-
• Rotary, decimal addressing tion instructions are shipped with each detector.
(Refer to the NOTIFIER panel manuals for device capacity.) Mount detector base (all base types) on an electrical backbox which
ARCHITECTURE: is at least 1.5" (3.81 cm) deep. For a chart of compatible junction
boxes, see DN-60054.
• Sleek, low-profile, stylish design
NOTE: Because of the inherent supervision provided by the SLC loop,
• Unique single-source design to respond quickly and dependably
end-of-line resistors are not required. Wiring “T-taps” or branches are
to a broad range of fires
permitted for Class “B” wiring only.
• Integral communications and built-in device-type identification When using relay or sounder bases, consult the ISO-X(A) installation
• Built-in tamper resistant feature sheet I56-1380 for device limitations between isolator modules and isola-
tor bases.
• Remote test feature from the panel
• Walk test with address display (an address on 121 will blink the Construction
detector LED: 12-[pause]-1(FlashScan systems only)
These detectors are constructed of fire-resistant plastic. The FSP-
• Built-in functional test switch activated by external magnet 951 Series plug-in intelligent smoke detectors are designed to com-
• Removable cover and insect-resistant screen for simple field mercial standards and offer an attractive appearance.
cleaning
• Expanded color options Operation
OPERATION: Each FSP-951 Series detector uses one of the panel’s addresses
(total limit is panel dependent) on the NOTIFIER Signaling Line Cir-
• Designed to meet UL 268 7th Edition cuit (SLC). It responds to regular polls from the control panel and
• Factory preset at 1.5% nominal sensitivity for panel alarm thresh- reports its type and the status. If it receives a test command from the
old level panel (or a local magnet test), it stimulates its electronics and
• LED “blinks” when the unit is polled (communicating with the fire reports an alarm. It blinks its LEDs when polled and turns the LEDs
panel) and latches in alarm. on when commanded by the panel. The FSP-951 Series offers fea-
• Low standby current tures and performance that represent the latest in smoke detector
technology.
MECHANICALS:
• Sealed against back pressure Product Line Information
• SEMS screws for wiring of the separate base NOTE: “-IV” suffix indicates CLIP and FlashScan device.
• Designed for direct-surface or electrical-box mounting FSP-951: White, low-profile intelligent photoelectric sensor, FlashS-
• Plugs into separate base for ease of installation and maintenance can only
FSP-951A: Same as FSP-951 but with ULC listing
B224RB-IV: Ivory, relay base (CSFM: 7300-1653:0216) CK300-IV: Color Kit (includes cover and trim ring), ivory, 10-pack
B224RBA-WH: White, relay base, ULC listing CK300-BL: Color Kit (includes cover and trim ring), black, 10-pack