Harmonic Power Flow Analysis For The Measurement of The Electric Power Quality
Harmonic Power Flow Analysis For The Measurement of The Electric Power Quality
Harmonic Power Flow Analysis For The Measurement of The Electric Power Quality
3, “E 1995 683
Absh.acf-The number and power of loads that pollute, from single sinusoidal generator with nonzero source impedance
an electric point of view, the electric network are constantly was widely discussed in [3] for single-phase and balanced
increasing. Their connection to the electric network causes a three-phase systems. This discussion leads to two important
significant distortion in the line current and, when their overall
power is no longer negligible with respect to the network power, conclusions.
also some distortion in the line voltage, thus deteriorating the 1) If only one polluting load is C O M I X ~ ~to~ the bus-bar,
electric supply quality. The paper proposes a method, based on it delivers a distorted current into the bus-bar, so that
the evaluation of the harmonic powers, to identify whether the the active power associated with each current harmonic
source producing harmonic distortion in the line currents and
voltages of a three-phase system is a polluting load C O M W ~ ~ component is always flowing out of the load branch into
after the metering section or is the distortion of the line voltages. the bus-bar.
Some parameters are also dehed in order to quantify the effects 2) If several polluting loads are connected to the bus-bar,
of the polluting load on the power quality. A V i Instrument each load delivers a distorted current into the bus-bar and
is also described, realized to implement the proposed method and also consumes a distorted current injected by the other
to verify it experimentally. The instrument accuracy is discussed.
polluting loads. The active power associated with each
current harmonic component and measured on each load
I. INTRODUCTION
branch is hence a function of the net current delivered by
11. METHODFUNDAMENTALS
The practical situation of different loads (linear and non- The voltage €‘ark Vector v(t> = wud -k jvq and the Current
linear) connected in parallel to the same bus-bar fed by a park Vector i ( t ) = i d -!- j i q describe the three-phase System
completely if the zero sequence components w, and io are nil
Manuscript received May 10, 1994; revised February 9, 1995. [4]. If this is not true, they describe the “pure” three-phase
The authors are with the Dipartimento di Elettrotecnica, Politecnico di
Milano, 20133 Milano, Italy. component of the system, that can still be used for the correct
IEEE Log Number 9411478. identification of polluting loads [2].
001&9456/95$04.00 0 1995 IEEE
684 IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT. VOL. 44, NO. 3, JUNE 1595
TABLE I
MEASUREMENT
UNCERTAINTIFS FOR THE DEFERENT MEASUREMENTS P!3FORMED BY THE REALIZED hSTRUhENT
IV. MEASUREMENT
ACCURACY
The behavior of the realized instrument was tested by insert- [l] All papers in ETEP, no. 1, Jan./Feb. 1993: dedicated issue to the First
ing it in a three-phase test circuit with two loads connected International Workshop on Power Definitions and Measurements under
Nonsinusoidal Conditions, Como, Italy, Sept. 10-12, 1991.
to the same bus-bar fed by a three-phase sinusoidal gener- [2] L. Cristaldi and A. Ferrero, “A digital method for the identification of
ator with 4 R balanced series resistors, 50 Hz fundamental the source of distortion in electric power systems,” IEEE Trans. Instnun.
Meas., vol. 44, no. 2, pp. 14-18, Feb. 1995.
frequency and selectable line-to-ground voltages up to 220 V. [3] P. H. Swart, M. J. Case, and J. D. van Wyk, “On techniques for
Linear, balanced and unbalanced, nonlinear and periodic time- localization of sources producing distortion in electric power networks,
variant loads have been connected to the bus-bar, in order ETEP, no. 6, pp.485490, Nov.lDec. 1994.
[4] A. Ferrero and G. Superti-Furga, “A new approach to the definition of
to reproduce different operating conditions. The instrument power components in three-phase systems under nonsinusoidal condi-
was inserted in a metering section placed in the load branch, tions.” IEEE Tram. Instrum. Meas., vol. 40,pp. 568-577, June 1991.
immediately before the load itself. [5] A. Ferrero and R. Ottoboni, “High-accuracy Fourier analysis based on
synchronous sampling techniques,” IEEE Trans. Instrum. Meas., vol.
The measurement results were always found in agreement 41, pp. 780-785, Dec. 1992.
with the results of the theoretical discussion reported in the
previous sections. In particular, the E; energy was counted
only when the load connected after the metering section was Loredma Cristaldi (S’93) was born in Catania,
a nonlinear or periodic time-variant load, and the E; energy Italy. She received the M.S. degree in electrical
was counted only when the load connected after the metering engineering from the University of Catania in 1992.
She is now working towards the Ph.D. degree in
section was an unbalanced load. electrical engineering at the Dipartimento di Elet-
The accuracy of the realized instrument was determined trotecnica of the “Politecnico di Milano” University.
experimentally by evaluating the measurement uncertainties Her current research interests are in the field of
the measurement of the power components under
introduced by the single steps of the measurement procedure. nonsinusoidal conditions.
The results in Table I have been attained.