Powercommand Digital Master Control: Features
Powercommand Digital Master Control: Features
Powercommand Digital Master Control: Features
PowerCommand®
Digital Master Control
Common bus:
System consists of a utility main breaker, but no generator main breaker (only individual generator set
paralleling breakers). The system controls utility main breaker and generator set paralleling breakers.
Operation sequences are configurable for open transition transfer and ramping closed transition transfer.
The system is suitable for use in peak-shaving and base-loading applications. (Fast closed transition is
not available with common bus configurations). Utility interconnection relay and DC station battery system
provided with closed transition transfer applications.
Transfer Pair:
System consists of a breaker pair including a generator bus main and a utility main. DMC 1500 control
both breakers in open transition, fast closed transition, or ramping closed transition modes. It can also be
programmed to exercise the generator set bus in parallel with the utility in either peak-shave or base-load
modes.
NOTE 1: Current transformer (CT) sizing and location must be considered as part of the design and
physical layout of the power section. The generator bus CT connection presented in the one-line diagrams
above represents totalized generator bus current output.
Protective functions
The control provides the following system close signal, the fail-to-close warning will be
protective functions for each breaker or bus. initiated. If the utility main breaker fails to
Note that each protective function will cause the close, the controller starts the generators
control to take intelligent corrective action to best and transfers load to them until the operator
resolve the problem until an operator can resets the fault condition and resolves the
address it. problem.
Breaker position contact warning: The
Any alarm on any generator set or in the system controller will monitor both A and B position
will cause the ALARM icon to appear at the contacts from the breaker. If the contacts
center-bottom of the touch-screen. Click on the disagree as to the breaker position, the
icon to navigate to the Alarm screen that breaker position contact warning will be
describes the equipment where the fault has initiated. If this warning and breaker fail-to-
occurred, and the name of the fault. The screen open warning register, then the controller will
allows the operator to attempt to reset the fault check for current above a threshold on all
from the HMI. three phases. If criteria are met, the
controller will remain on the source. If not,
Breaker fail-to-close warning: When the the controller will attempt to transfer to the
controller signals a circuit breaker to close, it alternate source.
will monitor the breaker auxiliary contacts
and verify that the breaker has closed. If the
control does not sense a breaker closure
within an adjustable time period after the
Breaker fail-to-open warning: The control Bus overload warning: The control
system monitors the operation of breakers monitors bus frequency and generator bus
that have been signaled to open. If the load relative to the online capacity. When
breaker does not open within an adjustable configured, the control will initiate a bus
time delay, a breaker fail to open warning is overload warning if the bus kW load exceeds
initiated. an adjustable threshold (80-140%) for an
Breaker tripped warning: The control adjustable delay (0-120 sec), or both.
accepts inputs to monitor breaker trip/bell Maximum parallel time warning: During
alarm contact and will initiate a breaker closed transition load transfers, the
tripped warning if it should activate. controller independently monitors the time
Fail to disconnect warning: If the controller the utility and generator sources are
is unable to open either breaker, a fail to connected. If time is exceeded, warning is
disconnect warning is initiated. initiated and the generator bus is
Fail to synchronize warning: Indicates that disconnected.
the generator bus could not be brought to Generator set main breaker fail-to-close
synchronization with the system bus. warning: Returns to the utility source and
Configurable for adjustable time delay of 10- will not retry until the operator resets the
120 seconds. If the control is trying to fault condition and resolves the problem
perform a closed transition re-transfer, but
fail-to-sync occurs, the control can be
configured to perform the re-transfer using
open transition.
Operator panel
A full color high-resolution (1024x768) 15-inch One-line diagram
touch-screen operator interface panel (HMI) is The ONE-LINE DIAGRAM screen displays system
provided to allow the operator to monitor and status using a combination of animation,
control the onsite power system. The operator changing screen color, text messages, and
panel provides the user with a complete indicators.
package of easy- to-view and useful HELP and
INFORMATION screens.
Generator set summary
All data is configurable for the display in either The GENERATOR SET SUMMARY provides an
Imperial standard or metric indications. Screen analog and graphical display of critical generator
navigation icons are located along the bottom of set operating parameters. The screen includes
the screen with the MAIN MENU icon always in the generator set state display (stopped, time delay
lower left corner. start, idle speed state, rated volts/hertz,
synchronizing, load share or load govern);
The standard viewing and basic control operator analog AC metering for generator set (3-phase,
screens include: AC volts and current, frequency, kW and power
MAIN MENU factor ); and 3-phase AC bus voltage and
ONE-LINE DIAGRAM frequency. The screen provides a complete
GENERATOR SET SUMMARY
display of all engine and alternator data present
in the generator set control. The screen also
GENERATOR SET GAUGES
shows status of the bus and generator set
METERING breaker.
TRENDING
ALARMS Load control
EVENT LOG The LOAD CONTROL screen provides a digital
SCHEDULER display of system load as a percent of available
capacity of the generator sets that are operating
Languages in parallel on the bus. The screen provides an
alphanumeric display of this data. It also
The HMI is configurable for up to seven displays the name, status and priority of each
languages, including: load block (whether on or off) and the total load
English of that block. The screen allows the operator to
Brazilian Portuguese manually add and shed loads in any sequence
Chinese desired.
French
Russian True RMS bus metering
Spanish Full-function true RMS bus AC metering
(generator bus and utility bus).
Transfer pair: System consists of a breaker pair Load demand: Will attempt to match generating
including a generator bus main and a utility capacity to load, typically for the conservation of
main. The DMC 1500 controls both breakers in fuel or optimizing of generator set life. The load
open transition, fast closed transition or ramping demand function will support from two to eight
closed transition modes. Configurable for open generator sets. Shutdown sequence can either
transition, fast closed transition (less than 100ms be a fixed sequence or can be based on running
interconnect time) or soft closed transition (load hours. With fixed sequence method, the
ramping) sequences of operation. Utility source sequence can be changed while the system is in
failure will automatically start generators and operation. Running hours method will attempt to
transfer load, re-transferring when utility source equalize generator set hours over time by
returns. exchanging stopped and running generator sets.
To protect system integrity, load demand will
Test will start generator sets and transfer load if restart all generator sets whenever an overload
test with load is enabled. condition is detected. The minimum amount of
capacity to maintain online is adjustable. Initial
Breaker control: Utility main and generator set delay for load demand to begin operation is
main breaker interfaces include separate relays adjustable from 1-60 minutes. Shutdown
for opening and closing breaker, as well as threshold is adjustable from 20-100% of online
inputs for both a and b breaker position contacts capacity minus one. Shutdown delay is
and tripped status. Breaker diagnostics include adjustable from 1-60 minutes. Re-start threshold
contact failure, fail-to-close, fail-to-open, fail-to- is adjustable from 20-100% of online capacity.
disconnect, and tripped. If a breaker fails, Run hours differential is adjustable from 1-500
appropriate control action is taken to maintain hours.
system integrity (max 30 VDC, 10 amp, or
250VAC, 10 amp). Load add/shed: Will control and monitor up to
10 loads step levels (such as feeder breaker or
Extended paralleling: Starts generator sets and automatic transfer switches) in any combination.
parallels to a utility source, then governs the real Up to 10 levels of load-add, and up to 9 levels of
and reactive power output. The control point for load-shed may be defined. The load add/shed
the real power (kW) can be configured for either function will support up to eight generator sets.
the generator set bus metering point (base-load) Loads can be added as generator sets come
or the utility metering point (peak-shave). The online, as well as on a timed basis. Loads are
control point for the reactive power (kVAR or shed on a timed basis when an overload
power factor) can be independently configured condition is detected, protecting system integrity.
for either the generator set bus metering point or Shed loads can be restored through operator
the utility metering point. Allows base kW load action. Manual load-add and shed is also
from the generator sets while maintaining the provided. Load-add delay is adjustable from 1-
utility power factor at a reasonable value to 60 sec. Load-shed delay is adjustable from 1-10
avoid penalties due to low power factor. The sec.
system always operates within generator set
ratings. The control point can be changed while Neutral earth relay control: Used to restrict
the system is in operation. Set points can be earth fault protection for multiple operating
adjusted via operator panel display or service power generation sources. This option provides
tool. control of the contactor in the neutral (neutral
contactor) to earth of each generator. Neutral
Scheduler: Allows the system to be operated at contactors are interlocked so that only one
preset times in test without load, test with load, contactor can remain closed during parallel
or extended parallel mode. A real-time clock is operation. During independent operation of any
built in. Up to 12 different programs can be set generator, its neutral contactor will be closed.
for day of week, time of day, duration, repeat
interval and mode. Up to six different exceptions
can be set up to block a program from running
during a specific time period.
Specifications
IEC configuration
Approval CE marked
BS EN ISO 60439-1
Listings
BS EN 61439-1 EN 61000-6-2
BS EN 61439-2 EN 61000-6-4
Certifications
All DMC 1500 master controls PowerCommand control systems
bear the CE mark. are designed and manufactured in
ISO 9001 certified facilities
Enclosure
Depth
Weight
Height Width Door closed Door open
mm mm mm mm kg
1962 810 605 1415 295
Elevations
Submittal detail
System capacity System load quantity
T970-7 4 Generator sets T781-7 0 Load add/shed devices
T971-7 8 Generator sets T787-7 6 Load add/shed devices
T791-7 10 Load add/shed devices
System certification
T722-7 IEC System distribution type
T801-7 ATS only
System voltage type T802-7 ATS and/or breaker type
T891-7 Low voltage (≤600VAC)
T892-7 Medium voltage (>600VAC) System HMI data options
T811-7 ATS network data
Language T812-7 Generator set manual control and
L050-7 English plant test report
L051-7 Spanish T814-7 BMS Connectivity MB TCPIP
L052-7 French T815-7 BMS Connectivity MB RTU
L057-7 Chinese
L073-7 Russian System protection options
L100-7 Brazilian Portuguese T831-7 Neutral earth control
T833-7 G59 relay (IEC only)
System application
T731-7 Isolated bus System wire
T732-7 Isolated bus with generator main T871-7 Three-wire
T733-7 Single utility common bus T872-7 Four-wire
T734-7 Single utility transfer pair
System frequency
System transition mode A045-7 50Hz
T741-7 Open transition A044-7 60Hz
T742-7 Closed hard transition
T743-7 Closed soft loading or System secondary CT ratio
extended parallel T931-7 1 Amp secondary CT ratio
T932-7 5 Amp secondary CT ratio