Solis 4G Single Phase Inverter: PV Grid Tie Inverter - US Version
Solis 4G Single Phase Inverter: PV Grid Tie Inverter - US Version
Solis 4G Single Phase Inverter: PV Grid Tie Inverter - US Version
Ver 1.1
Contents
1. Introduction ……………………………………………… 3
1.1 Product Description ………………………………… 3
1.2 Packaging ………………………………………… 4
2. Safety Instructions ……………………………………… 5
2.1 Safety Symbols …………………………………… 5
2.2 General Safety Instructions ……………………… 5
2.3 Notice For Use ……………………………………… 6
3. Overview ……………………………………………… 7
3.1 Front Panel Display ……………………………… 7
3.2 LED Status Indicator Lights ……………………… 7
3.3 Keypad …………………………………………… 8
3.4 LCD ………………………………………………… 8
4. Installation ……………………………………………… 9
4.1 Select Location for the Inverter ………………… 9
4.2 Mounting the Inverter ………………………………… 11
4.3 Electrical Connections …………………………… 14
4.3.1 Terminal connections ……………………… 14
4.3.2 Connect PV side of inverter ……………… 15
4.3.3 Connect grid side of inverter ……………… 16
4.3.4 Ground connection ………………………… 17
4.3.5 Max. overcurrent protection device (OCPD)… 18
4.3.6 Inverter monitoring connection …………… 18
5. Start & Stop ……………………………………… 20
5.1 Start the Inverter ……………………………… 20
5.2 Stop the Inverter ………………………………… 20
6. Operation ……………………………………………… 21
6.1 Main Menu ………………………………………… 21
.1.
Contents 1. Introduction
6.2 Information ……………………………………… 21 1.1 Product Description
6.2.1 Lock screen …………………………………… 23 Solis single phase US series inverters can transfer DC power from PV panels into AC
power and feed into grid.
6.3 Settings ……………………………………………… 23 Solis single phase US series inverters contain 8 models which are listed below:
6.3.1 Set Time ……………………………………… 23 Solis-1P6K-4G-US, Solis-1P7K-4G-US, Solis-1P7.6K-4G-US, Solis-1P7.6K4-4G-US,
Solis-1P8K-4G-US, Solis-1P8.6K-4G-US, Solis-1P9K-4G-US, Solis-1P10K-4G-US
6.3.2 Set Address …………………………………… 23
6.4 Advanced Info. ……………………………………… 24
6.4.1 Alarm Message ……………………………… 24 LED lights
6.4.2 Running Message …………………………… 25
LCD display
6.4.3 Version ………………………………………… 25
6.4.4 Daily Energy …………………………………… 25 4 buttons
.3.
1. Introduction 2.Safety Instructions
Improper use may result in potential electric shock hazards or burns. This manual
1.2 Packaging
contains important instructions that should be followed during installation and
When you receive the inverter, ensure that all the parts listed below are included:
maintenance. Please read these instructions carefully before use and keep them for
future reference.
WARNING:
WARNING symbol indicates important safety instructions, which if not
correctly followed, could result in serious injury or death.
2 3 4
NOTE:
NOTE symbol indicates important safety instructions, which if not correctly
PV Grid Tie Inverter
CAUTION:
CAUTION, RISK OF ELECTRIC SHOCK symbol indicates important safety
1 instructions, which if not correctly followed, could result in electric shock.
C 2016, Ningbo Ginlong Technologies Co., Ltd.
Ver 1.1
CAUTION:
5
CAUTION, HOT SURFACE symbol indicates safety instructions, which if not
correctly followed, could result in burns.
2 Wall mounting bracket 1 Please don’t connect PV array positive(+) or negative(-) to ground, it could
4 Grounding screw 1
WARNING:
5 Manual 1
Electrical installations must be done in accordance with the local and national
electrical safety standards.
Table 1.1 Parts list
.4. .5.
2.Safety Instructions 3. Overview
WARNING: 3.1 Front Panel Display
To reduce the risk of fire, over-current protective devices (OCPD) are
required for circuits connected to the Inverter.
The DC OCPD shall be installed per local requirements. All photovoltaic source
and output circuit conductors shall have disconnects that comply with the NEC
Article 690, Part II. All Solis single phase inverters feature an integrated
DC switch.
CAUTION:
Risk of electric shock. Do not remove cover. There is no user serviceable
parts inside. Refer servicing to qualified and accredited service technicians.
CAUTION:
The PV array (Solar panels) supplies a DC voltage when they are exposed to
sunlight.
CAUTION: There are three LED status indicator lights in the front panel of the inverter. Left LED:
The surface temperature of the inverter can reach up to 75℃ (167 F). POWER LED (red) indicates the power status of the inverter. Middle LED: OPERATION
To avoid risk of burns, do not touch the surface of the inverter while it’s operating. LED (green) indicates the operation status. Right LED: ALARM LED (yellow) indicates
Inverter must be installed out of the reach of children. the alarm status. Please see Table 3.1 for details
.8. .9.
4. Installation 4. Installation
Install on a wall or strong structure capable of bearing the weight.
4.2 Mounting the Inverter
Install vertically with a maximum incline of +/- 5°.If the mounted inverter is tilted to an
angle greater than the maximum noted, heat dissipation can be inhibited, and may result Dimensions of mounting bracket:
in less than expected output power. 5.16
2. 1 7 2 . 17
When 1 or more inverters are installed in one location, a minimum 12inchs clearance
should be kept between each inverter or other object. The bottom of the inverter should
be 20inchs clearance to the ground.
1.1
1.57
12in
12in
4.92
12in 12in 12in Please see Figure 4.4 and Figure 4.5 for instruction on mounting the inverter to a wall or pillar.
The inverter shall be mounted vertically. The steps to mount the inverter are listed below:
1. According to the figure 4.2, select the mounting height of the bracket and mark the
mounting holes. For brick walls, the position of the holes should be suitable for the
20in
20in
expansion bolts.
Suitable fixing screws
Visibility of the LED status indicator lights and the LCD located at the front panel of
Bracket
the inverter should be considered.
NOTE:
Nothing should be stored on or placed against the inverter.
Locking screw
.10. .11.
4. Installation 4. Installation
2.Make sure the bracket is horizontal and the mounting holes (in Figure 4.4 and Figure 4.5)
are marked correctly. Drill the holes into the wall or pillar at your marks.
WARNING: 5. Use M4*9 screws to fix the bottom of the inverter to the mount bracket.
The inverter must be mounted vertically.
4.Lift up the inverter (be careful to avoid body strain), and align the back bracket on the
inverter with the convex section of the mounting bracket. Hang the inverter on the
mounting bracket and make sure the inverter is secure (see Figure 4.6)
The are two holes at the bottom of bracket, one to fix the inverter, another for the
lock. The diameter of the lock should be less than 0.27in (7mm).
.12. .13.
4. Installation 4. Installation
4.3 Electrical Connections
Before marking wire connections, unscrew the four screws on both sides of the wiring box, Terminal A
then remove the cover
Terminal B
Press on the wiring box cover while loosening the screws. This action will help to
avoid damaging the screw threads.
Before connection, please make sure the polarity of the output voltage of PV array
Please see figure 4.6,there are four knockouts in the wiring box. The two knockouts on the
matches the“DC+”and “DC-”symbols.
left (bottom and side) are for the DC conduit entry. The two knockouts on the right (bottom
and side) are for the AC conduit entry. All knockouts in the wiring box can accept trade size
1 inch or 1¼ inch (ID) conduit.. Please use qualified DC cable for PV system.
Cross section
Cable type Recommended
4.3.1 Terminal connections Range value
Industry generic PV cable 4.0~6.0
(model:PV1-F) 4.0(12AWG)
(12~10AWG)
The Ginlong Solis 6-10kW Single Phase inverters can be connected to a 208V or 240V grid.
The default setting is for a 240VAC single phase grid. Since the inverter monitors voltage
between L1 and L2, the Neutral conductor can be connected or not connected when tying the
inverter to a 240V grid. Ground must be connect to the PE terminal.
Figure 4.10 Grounding terminal on heat-sink
Cross section
Cable type Recommended External ground connection point
Range value
An external ground connection is provided at the right side of inverter.
Industry generic 4.0~25.0mm² 10-25mm²
grid cable (12~4AWG) (8-4AWG) Prepare OT terminals: M4. Use proper tooling to crimp the lug to the terminal.
Connect the OT terminal with ground cable to the right side of inverter. The torque is
Table 4.2 Grid cable size
20 in-lbs (2Nm).
L1 L1
STANDARD
N
GRID
L3 L2 L2
208V~ 240V~
3PH-△- 3W SPLIT-PHASE
TERMINAL L1 L2 N L1 L2 N
To protect the inverter's AC grid connection conductors, Ginlong Solis recommends installing Smart phone monitoring
breakers that will protect against overcurrent. The following table defines OCPD ratings for
the Ginlong Solis 6-10kW single phase inverters.
GPRS monitoring
Wi-Fi box
Solis-1P7.6K4-4G-US 240V/208V 7.6/7.6 40/50 Wi-Fi monitoring
The inverter can be monitored via Wi-Fi or GPRS. All Ginlong Solis communication
devices are optional (Figure 4.9). For connection instructions, please refer to the Ginlong
Solis Monitoring Device installation manuals.
.18. .19.
5. Start & Stop 6. Operation
During normal operation, the display alternately shows the power and the operation
5.1 Start the Inverter
status with each screen lasting for 10 seconds (see Figure 6.1). Screens can also be
To start up the Inverter, it is important that the following steps are strictly followed: scrolled manually by pressing the UP and DOWN keys. Press the ENTER key to
1. Switch the grid supply main Switch (AC) ON first. access to the Main Menu.
2. Switch the DC switch ON. If the voltage of PV arrays are higher than start up voltage,
the inverter will turn on. The red LED power will light, and the LCD shows the company's Pressing the
ESC key Main Menu
name and the inverter model. calls back the
previous menu.
Information
Ginlong Power 3424W UP/DOWN
Solis-1P7.6K4-4G-US 01-01-2014 12:04
Settings
5 sec
Figure 5.1 Company Name and Inverter Model on LCD Manufacturer
UP/DOWN or
Start Model name auto-scroll UP/DOWN
(10 sec)
Advanced Info.
3. When both the DC and the AC sides supply to the inverter, it will be ready to generate
Status: Generating
power. Initially, the inverter will check both its internal parameters and the parameters 01-01-2014 12:04 UP/DOWN
of the AC grid, to ensure that they are within the acceptable limits. At the same time, Pressing the Advanced settings
ENTER key
the green LED will flash and the LCD displays the information of INITIALIZING. gives access to
the main menu.
4. After 30-300 seconds (depending on local requirement), the inverter will start to
generate power. The green LED will be on continually and the LCD displays
Figure 6.1 Operation Overview
GENERATING.
.20. .21.
6. Operation 6. Operation
Display Duration Description 6.2.1 Lock screen
V_DC1 350.8V V_DC1: Shows input 01 voltage value. Pressing the ESC key returns to the Main Menu. Pressing the ENTER key locks
I_DC1 5.1A 10 sec
I_DC1: Shows input 01 current value. (Figure 6.2(a)) or unlocks (Figure 6.2 (b)) the screen.
Total Energy
10 sec Total generated energy value 6.3.1 Set Time
0258458 kwh
This function allows time and date setting. When this function is selected, the LCD will
This Month: 0123kwh This Month: Total energy generated this month. display a screen as shown in Figure 6.3.
Last Month: 0123kwh 10 sec
Last Month: Total energy generated last month.
.22. .23.
6. Operation 6. Operation
YES=<ENT> NO=<ESC>
6.4.2 Running Message
Set Address: 01 This function is for maintaince person to get running message such as internal temperature,
Standard NO. etc.
Figure 6.4 Set Address
Screens can be scrolled manually by pressing the UP/DOWN keys.
Press the UP/DOWN keys to set the address. Press the ENTER key to save the settings.
Press the ESC key to cancel the change and return to the previous menu.
6.4.3 Version
The screen shows the model version and the software version of the Inverter
6.4 Advanced Info - Technicians Only
(see Figure 6.7).
NOTE: Model: 08
To access to this area is for fully qualified and accredited technicians only. Software Version: D20001
Enter menu “Advanced Info.” and “Advanced settings” (need password).
Figure 6.7 Model Version and Software Version
Select “Advanced Info.” from the Main Menu. The screen will require the password as below
6.4.4 Daily Energy
YES=<ENT> NO=<ESC>
Password:0000 The function is for checking the energy generation for selected day.
Press UP/DOWN key to move one date from another. inverter without AFCI module, UL-240V-A and UL-208V-A are the settings for inverter
integrate with AFCI module. The default grid setting is 240V.
6.4.6 Daily record
NOTE:
The screen shows history of changing settings. Only for maintance personel. The default setting is 240V split phase “UL-240V” or “UL-240V-A”, if it’s
different please select 208V single phase “UL-208V” or “UL-208V-A” or
220V split phase “MEX-CFE”. Other standards are for 50Hz grid, please
6.4.7 Communication Data
don’t select.
The screen shows the internal data of the Inverter (see Figure 6.14), which is for service
NOTE:
technicians only. This function is for technicians use only.
01-05: 01 25 E4 9D AA
06-10: C2 B5 E4 9D 55 Selecting the “User-Def” menu will access to the following submenu (see Figure 6.16),
This function is used to select the grid's reference standard (see Figure 6.11). UN-G-V1: 90---210V UN-G-F1: 47-49.5Hz(56-59.8Hz)
UN-G-V1-T: 0.1---9S UN-G-F1-T: 0.1---9S
YES=<ENT> NO=<ESC> UN-G-V2: 90---210V UN-G-F2: 47-49Hz(56-59.8Hz)
Standard:UL-240V-A
UN-G-V2-T: 0.1---1S UN-G-F2-T: 0.1---9S
Figure 6.15
.26. .27.
6. Operation 6. Operation
Press the UP/DOWN keys to scroll through items. Press the ENTER key to edit the
highlighted item. Press the UP/DOWN keys again to change the setting. Press the ENTER This function is applicable by maintenance personnel only, wrong operation
key to save the setting. Press the ESC key to cancel changes and returns to the previous will prevent the inverter from reaching maximum power.
menu.
6.5.6 Calibrate Energy
6.5.2 Grid ON/OFF Maintenance or replacement could clear or cause a different value of total energy. Use this
This function is used to start up or stop the power generation of Solis Single Phase function could allow user to revise the value of total energy to the same value as before. If
Inverter (see Figure 6.17). the monitoring website is used the data will be synchronous with this setting automatically.
Grid ON (see Figure 6.19).
Grid OFF
YES=<ENT> NO=<ESC>
Figure 6.17 Set Grid ON/OFF Energy:0000000kWh
Screens can be scrolled manually by pressing the UP/DOWN keys. Press the ENTER key Figure 6.19 Calibrate energy
to save the setting. Press the ESC key to return to the previous menu.
Press the DOWN key to move the cursor, Press the UP key to revise the value. Press the
6.5.3 Clear Energy ENTER key to execute the setting. Press the ESC key to return to the previous menu.
There are 5 item for this sub menu: Figure 6.21 Arc fault
1. Set output power 2. Set Reactive Power 3. Out_P With Restore
Please check DC cables and connections to identify the source of possible arcing. Then
4. Rea_P With Restore 5. Select PF Curve
press <ESC> for 3 seconds, the inverter will restart.
.28. .29.
7. Maintenance 8. Trouble Shooting
7.Maintenance Alarm Message Failure description Solution
Solis Single Phase Inverter does not require any regular maintenance. However, cleaning 1.Check PV input connections
Inverter no power 2.Check DC input voltage
the dust on heat-sink will help the inverter to dissipate the heat and increase its life time. No power
on LCD (single phase >120V, three phase >350V)
The dust can be removed with a soft brush. 3.Check if PV+/- is reversed
8. Troubleshooting
OV-DC01/02/03/04 Over DC voltage 1.Reduce the module number in series
OV-BUS Over DC bus voltage 1.Check inverter inductor connection
UN-BUS01/02 Under DC bus voltage 2.Check driver connection
The inverter is designed in accordance with the most important international grid-tied
GRID-INTF01/02 Grid interference
standards and safety and electromagnetic compatibility requirements. Before delivering to Over grid current
1.Restart inverter
OV-G-I 2.Change power board
the customer, the inverter has been subjected to several tests to ensure its optimal operation IGBT-OV-I Over IGBT current
and reliability. 1.Restart inverter
DC-INTF DC input overcurrent 2.Identify and remove the string to the fault MPPT
OV-DCA-I 2.Change power board
In case of failure, the LCD screen will display an alarm message. In this case, the inverter
IGFOL-F Grid current tracking fail 1.Restart inverter or contact installer.
may stop feeding into the grid. The failure descriptions and their corresponding alarm
IG-AD Grid current sampling fail
messages are listed in Table 8.1:
1.Check inverter surrounding ventilation.
OV-TEM Over Temperature 2.Check if there’s sunshine direct on
inverter in hot weather.
.30. .31.
8. Trouble Shooting
Alarm Message Failure description Solution
9.1 Technical data
Model Solis-1P6K-4G-US Solis-1P7K-4G-US
ILeak-FAULT High Grid leakage current 1.Check AC and DC connection
01/02/03/04 2.Check inverter inside cable connection. Max power per MPPT (Watts) 4000
Relay check fault 1.Restart inverter or contact installer. Max voltage (Volts) 600
Relay-FAULT
Startup voltage (Volts) 120
DCinj-FAULT High DC injection current 1.Restart inverter or contact installer.
Full power MPPT voltage range (Volts) 200-500 233-500
AFCI Check FAULT AFCI module self check fault 1.Restart inverter or contact installer. Operating MPPT voltage range (Volts) 100-500
ARC-FAULT ARC detected in DC circuit 1.Check if there’s arc in PV connection Max usable input current per MPPT (Amps) 10
and restart inverter. Max short circuit input current (Amps) 15.6
Number of MPPT 3
Table 8.1 Fault message and description
Inputs per MPPT 1
Nominal output power 240V grid (Watts) 6000 7000
Nominal output power 208V grid (Watts) 6000 7000
NOTE: Nominal grid voltage (Volts) 240/208
If the inverter displays any alarm message as listed in Table 8.1; please Operating voltage range (Volts) 183-228(for 208V rated)/211-264(for 240V rated)
turn off the inverter (refer to Section 5.2 to stop your inverter) and wait for 5 Max. overcurrent protection device 240/208V(Amps) 40/40
minutes before restarting it (refer to Section 5.1 to start your inverter). If the Max.output current for 208V grid (Amps) 28.8 33.7
failure persists, please contact your local distributor or the service center. Max.output current for 240V grid (Amps) 25 29.2
Please keep ready with you the following information before contacting us. Output power factor range 0.8leading~0.8lagging
Grid current THD <1.5%
1. Serial number of Solis Single Phase Inverter;
Nominal grid frequency (Hertz) 60
2. The distributor/dealer of Solis Single Phase Inverter (if available); Operating frequency range (Hertz) 59.5-60.5
3. Installation date. Peak efficiency 97.8%
CEC weighted efficiency 97.5%
4. The description of problem (i.e. the alarm message displayed on the LCD and the status
MPPT efficiency >99.5%
of the LED status indicator lights. Other readings obtained from the Information submenu
Integrated AFCI(DC arc-fault circuit protection) Yes
(refer to Section 6.2) will also be helpful.); Rapid shutdown Optional
5. The PV array configuration (e.g. number of panels, capacity of panels, number of strings Dimensions(inch / cm) 13.1*25.8H*9.8in / 33.3*65.5*24.9 cm
.34. .35.
Model Solis-1P8.6K-4G-US Model Solis-1P9K-4G-US
Max power per MPPT (Watts) 4000 Max power per MPPT (Watts) 4000
Max voltage (Volts) 600 Max voltage (Volts) 600
Startup voltage (Volts) 120 Startup voltage (Volts) 120
Full power MPPT voltage range (Volts) 215-500 Full power MPPT voltage range (Volts) 225-500
Operating MPPT voltage range (Volts) 100-500 Operating MPPT voltage range (Volts) 100-500
Max usable input current per MPPT (Amps) 10 Max usable input current per MPPT (Amps) 10
Max short circuit input current (Amps) 15.6 Max short circuit input current (Amps) 15.6
Number of MPPT 4 Number of MPPT 4
Inputs per MPPT 1 Inputs per MPPT 1
Nominal output power 240V grid (Watts) 8600 Nominal output power 240V grid (Watts) 9000
Nominal output power 208V grid (Watts) 8200 Nominal output power 208V grid (Watts) 8600
Nominal grid voltage (Volts) 240/208 Nominal grid voltage (Volts) 240/208
Operating voltage range (Volts) 183-228(for 208V rated)/211-264(for 240V rated) Operating voltage range (Volts) 183-228(for 208V rated)/211-264(for 240V rated)
Max. overcurrent protection device 240/208V(Amps) 50/50 Max. overcurrent protection device 240/208V(Amps) 50/50
Max.output current for 208V grid (Amps) 39.4 Max.output current for 208V grid (Amps) 41.3
Max.output current for 240V grid (Amps) 35.8 Max.output current for 240V grid (Amps) 37.5
Output power factor range 0.8leading~0.8lagging Output power factor range 0.8leading~0.8lagging
Grid current THD <1.5% Grid current THD <1.5%
Nominal grid frequency (Hertz) 60 Nominal grid frequency (Hertz) 60
Operating frequency range (Hertz) 59.5-60.5 Operating frequency range (Hertz) 59.5-60.5
Peak efficiency 97.8% Peak efficiency 97.8%
CEC weighted efficiency 97.5% CEC weighted efficiency 97.5%
MPPT efficiency >99.5% MPPT efficiency >99.5%
Integrated AFCI(DC arc-fault circuit protection) Yes Integrated AFCI(DC arc-fault circuit protection) Yes
Rapid shutdown Optional Rapid shutdown Optional
Dimensions(inch / cm) 13.1*25.8H*9.8in / 33.3*65.5*24.9 cm Dimensions(inch / cm) 13.1*25.8H*9.8in / 33.3*65.5*24.9 cm
Weight(lbs / kg) 43.7lb (19.8kg) Weight(lbs / kg) 43.7lb (19.8kg)
Topology Transformerless Topology Transformerless
Ambient operating temperature range -25℃~60℃/-13℉-140℉ Ambient operating temperature range -25℃~60℃/-13℉-140℉
Enclosure type NEMA 4X Enclosure type NEMA 4X
Noise emission(typical) <30 dBA Noise emission(typical) <30 dBA
Cooling concept Natural convection Cooling concept Natural convection
Max. operating altitude without derating 13120ft (4000m) Max. operating altitude without derating 13120ft (4000m)
Designed lifetime >20 years Designed lifetime >20 years
UL 1741, UL 1998, UL 1699B, IEEE 1547, UL 1741, UL 1998, UL 1699B, IEEE 1547,
Comliance Comliance
FCC Part 15 (Class A & B), CAN/CSA C22.2 107.1-1 FCC Part 15 (Class A & B), CAN/CSA C22.2 107.1-1
Operating surroundings humidity 0~100% Condensing Operating surroundings humidity 0~100% Condensing
2 knockout for 1" and 11/4 " conduit at bottom, 2 knockout for 1" and1/4
1 " conduit at bottom,
Conduit connention Conduit connention
side and back side and back
Display LCD, 2×20 Z. Display LCD, 2×20 Z.
Interface RS 485, WIFI/GPRS (optional) Interface RS 485, WIFI/GPRS (optional)
Warranty Terms 10 Years STD (Extendable to 20 Years) Warranty Terms 10 Years STD (Extendable to 20 Years)
.36. .37.
Model Solis-1P10K-4G-US 9.2 Power Derating
Max power per MPPT (Watts) 4000
Max voltage (Volts) 600 Power derating due to input voltage change.
Startup voltage (Volts) 120
Full power MPPT voltage range (Volts) 250-500 P/V curve for Solis-1P7.6K-4G-US
Operating MPPT voltage range (Volts) 100-500
Power(W)
Max usable input current per MPPT (Amps) 10
Max short circuit input current (Amps) 15.6
Number of MPPT 4 7600 Full load
Inputs per MPPT 1 under test
condition
Nominal output power 240V grid (Watts) 10000
Nominal output power 208V grid (Watts) 9500
Nominal grid voltage (Volts) 240/208
Operating voltage range (Volts) 183-228(for 208V rated)/211-264(for 240V rated) 3000
Max. overcurrent protection device 240/208V(Amps) 50/60
Max.output current for 208V grid (Amps) 45.9
Max.output current for 240V grid (Amps) 41.7
Output power factor range 0.8leading~0.8lagging
Grid current THD <1.5%
Nominal grid frequency (Hertz) 60
Operating frequency range (Hertz) 59.5-60.5 100 253 500 580 600 Voltage(V)
Peak efficiency 97.8%
CEC weighted efficiency 97.5%
MPPT efficiency >99.5% P/V curve for Solis-1P10K-4G-US
Integrated AFCI(DC arc-fault circuit protection) Yes
Power(W)
Rapid shutdown Optional
Dimensions(inch / cm) 13.1*25.8H*9.8in / 33.3*65.5*24.9 cm
Weight(lbs / kg) 43.7lb (19.8kg) 10000 Full load
Topology Transformerless under test
condition
Ambient operating temperature range -25℃~60℃/-13℉-140℉
Enclosure type NEMA 4X
Noise emission(typical) <30 dBA
Cooling concept 4000
Natural convection
Max. operating altitude without derating 13120ft (4000m)
Designed lifetime >20 years
UL 1741, UL 1998, UL 1699B, IEEE 1547,
Comliance
FCC Part 15 (Class A & B), CAN/CSA C22.2 107.1-1
Operating surroundings humidity 0~100% Condensing
2 knockout for 1" and1/4
1 " conduit at bottom,
Conduit connention
side and back 100 200 500 580 600 Voltage(V)
Display LCD, 2×20 Z.
Comments:
Interface RS 485, WIFI/GPRS (optional) There will be DC over voltage alarm when DC input voltage between 580-
Warranty Terms 10 Years STD (Extendable to 20 Years) 600V. Inverter could be damaged when the input voltage higher than 600V.
.38. .39.
Power derating due to ambient temperature condition (For all 6-10kW models):
P(%)
100%
60%
0 T(℉)
113 140
.40.