ASM720PE Series: Selectable 'Energise To Run' or 'Energise To Stop'
ASM720PE Series: Selectable 'Energise To Run' or 'Energise To Stop'
com
Specialist Controls for Engine Applications
Designed & Manufactured in England
NEW
Tel: +44 (0) 1295 272 360
Fax: +44 (0) 1295 264 766
ASM720PE series
[email protected] Micro-processor based -- Auto Start Module
ASM720P_E
Inputs are shown ‘close on fault’ with the engine stationary Fuel control shown for ‘Energise to Run’
TERMINAL CONNECTIONS
4 Batt +Ve via Emergency Stop Button 14 -Ve Output to Alarm Relay
5 +Ve Output to Fuel / Fuel Hold Relay 15 Reserved .. .DO NOT CONNECT
8 Warning Light & Charge Alternator Excitation 18 Frequency Sense (110/250V 50/60Hz Main Alternator)
9 +Ve Output to Pre-Heat Relay 19 Frequency Sense (110/250V 50/60Hz Main Alternator)
NOTES
ii A wide range of Accessories are available from stock, including high grade Automotive Relays
iii Pre-Heat Output is active before cranking for time set by VR1 and also during the multiple attempt start sequences
iv Energise to Stop …
> Remove / do not connect ‘Pulse’ and ‘Fuel’ Relays as shown above
> Connect ‘Energise to Stop’ Relay coil to Term.10 and Control +Ve.
> Connect ’Energise to Stop’ Solenoid to Batt-Ve and VIA the normally open Contacts of the Relay to Batt+Ve
Note: Fuel output on Term.5 remains active in ‘Energise to Stop’ mode as it is often used to power ancillary equipment.
v Fusing is omitted for clarity
ASM720PHE
REAR CONTROLS
S_ OFF S_ ON Comment
IP rating IP67 from front of controller, conditional on correct fitting and with panel gasket
Fault Inputs, sensitivity 7K Ohm at 12Vdc & 25K Ohm at 24Vdc (fault channel input to Batt-Ve)
Load-On Delay 3 sec from Crank Disconnect (Reinstatement = 3 sec from Remote Start Input)
Energise to Stop Timer 20 sec Stop solenoid energised for this time