Air Conditioning Specifications: Eeb/Esd
Air Conditioning Specifications: Eeb/Esd
EEB/ESD
12-20-2020
2.3.1.1 For new design associated to shelters BTU calculations should cover the following;
sensible heat gain, solar gain, trans gain through partitions, infiltration and by-
passed air and CFM calculations at summer season.
2.3.1.2 Cooling and heating load estimates must only be carried out by experienced
personnel, or under the supervision of experienced personnel, and include
appropriate allowances for internal loads, infiltration, fan gains and duct heat
gain/loss.
2.3.1.3 Equipment selection must be based on the design indoor and outdoor
conditions, adjusted if necessary, to account for the installed plant
configuration (e.g. heat gain from surroundings, recirculation). Unit capacity
must be capable of achieving both the calculated sensible and total loads.
The Contractor shall select and furnish dual redundant (Package Unit or Wall Mounted
Package type depending on shelter size) (three Air conditioning systems for remote
sites*) air condition system for the equipment shelters, provided with control panel,
automatic thermal control system. Load calculation sheet shall be submitted along with
the proposed A/C type and capacity.
HVAC outdoor units (Package Unit type) must be equipped with spring mount
vibration isolators.
3 Purpose
HVAC system shall satisfy the requirements that needed for safe operation of the
system. The active system shall be sized to maintain the conditioned space at 75°F dry
bulb and 50% relative humidity at the actual outdoor dry bulb and wet bulb
temperature, with not less than 20 percent spare capacity of the design load. The air
conditioning load shall be (enough for load requirements) and even bigger if required
based on the CDR based on the internal heat loads of the electronic equipment in the
normal mode of operation as well as any mechanical heat loads that might be within the
conditioned space. Use shelter orientation which yields largest solar heat design
conditions.