Micomho P446: Technical Manual
Micomho P446: Technical Manual
Micomho P446: Technical Manual
Technical Manual
Fast Multifunction Distance Protection Relay
Platform Hardware Version: M
Platform Software Version: 71
Publication Reference: P446/EN/TM/E
P446/EN/TM/E © 2011. ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and service marks of ALSTOM. The other names mentioned,
registered or not, are the property of their respective companies. The technical and other data contained in this document is provided for information only. Neither
ALSTOM, its officers or employees accept responsibility for, or should be taken as making any representation or warranty (whether express or implied), as to the
accuracy or completeness of such data or the achievement of any projected performance criteria where these are indicated. ALSTOM reserves the right to revise or
GRID
change this data at any time without further notice.
MiCOMho P446 1 Introduction
INTRODUCTION
CHAPTER 1
P446/EN/TM/E 1-1
1 Introduction MiCOMho P446
1-2 P446/EN/TM/E
MiCOMho P446 1 Introduction
1 FOREWORD
This technical manual provides a functional and technical description of Alstom Grid’s MiCOMho P446
range of IEDs, as well as a comprehensive set of instructions for using the device.
1.2 Conventions
The names for special keys and function keys appear in capital letters.
For example: ENTER
When describing software applications, menu items, buttons, labels etc as they appear on the
screen are written in bold type.
For example: Select Save from the file menu.
Menu hierarchies in documentation describing software applications use the > sign to indicate
the next level
For example: Select File > Save
Filenames and paths use the courier font
For example: Example\File.text
Special terminology is written with leading capitals
For example: Sensitive Earth Fault
When reference is made to Alstom Grid's Courier database, the column text is written in upper
case
For example: The SYSTEM DATA column
When reference is made to Alstom Grid's Courier database, the cell text is written in bold type
For example: The Language cell in the SYSTEM DATA column
When reference is made to Alstom Grid's Courier database, the value of a cell's content is
enclosed in single quotation marks
For example: The Language cell in the SYSTEM DATA column contains the value 'English'
1.2.2 Nomenclature
Due to the technical nature of this manual, many special terms, abbreviations and acronyms are used
throughout the manual. Some of these terms are well-known industry-specific terms while others may
be special product-specific terms used by Alstom Grid. A glossary at the back of this manual provides
a complete description of all special terms used throughout the manual.
We would like to highlight the following changes of nomenclature however:
P446/EN/TM/E 1-3
1 Introduction MiCOMho P446
The word 'relay' is no longer used for the device itself. Instead, the device is referred to as an
'IED' (Intelligent Electronic Device), the 'device', the 'product', or the 'unit'. The word 'relay' is
used purely to describe the electromechanical components within the device, i.e. the output
relays.
British English is used throughout this manual.
The British term 'Earth' is used in favour of the American term 'Ground'.
Chapter 1: Introduction
Chapter 2: Safety Information
Chapter 3: Hardware Design
Chapter 4: Software Design
Chapter 5: Configuration
Chapter 6: Settings and Records
Chapter 7: Operation
Chapter 8: Application Examples
Chapter 9: SCADA Communications
Chapter 10: Cyber Security
Chapter 11: PSL Editor
Chapter 12: PSL Schemes
Chapter 13: Installation
Chapter 14: Commissioning Instructions
Chapter 15: Maintenance & Troubleshooting
Chapter 16: Technical Specifications
Chapter 17: Symbols and Glossary
Chapter 18: Wiring Diagrams
Appendix A: Commissioning Record Forms
Appendix B: P59x Commissioning Instructions
Appendix C: DDB Signals
1-4 P446/EN/TM/E
MiCOMho P446 1 Introduction
Protection Features
Feature IEC61850 ANSI
Tripping Mode (1 & 3 pole) PTRC
ABC and ACB phase rotation
Phase overcurrent stages, with optional directionality (4) OcpPTOC/RDIR 50/51/67
Earth/Ground overcurrent stages, with optional directionality (4) EfdPTOC/RDIR 50N/51N/ 67N
Sensitive earth fault (SEF) (4) SenPTOC/RDIR 50N/51N/67N
High impedance restricted earth fault (REF) SenRefPDIF 64
Negative sequence overcurrent stages, with optional directionality (4) NgcPTOC/RDIR 67/46
Broken conductor (open jumper), used to detect open circuit faults 46
Thermal overload protection ThmPTTR 49
Undervoltage protection stages (2) VtpPhsPTUV 27
Overvoltage protection stages (2) VtpPhsPTOV 59
Remote overvoltage protection stages (2) VtpCmpPTOV 59R
Residual voltage stages (neutral displacement) (2) VtpResPTOV 59N
P446/EN/TM/E 1-5
1 Introduction MiCOMho P446
Communication Features
Feature IEC61850 ANSI
Front RS232 serial communication port for configuration 16S
Rear serial RS485 communication port for SCADA control 16S
2 Additional rear serial communication ports for SCADA control and
16S
teleprotection (fibre and copper) (optional)
Ethernet communication (optional) 16E
Redundant Ethernet communication (optional) 16E
Courier 16S
IEC61850 (optional) 16E
IEC60870-5-103 (optional) 16S
DNP3.0 over serial link (optional) 16S
DNP3.0 over Ethernet (optional) 16E
IRIG-B time synchronization (optional) CLK
Table 4: Communication features
General Features
Feature IEC61850 ANSI
NERC compliant cybersecurity
Multiple password access control levels
Function keys (10) FnkGGIO
Programmable LEDs (18) LedGGIO
Programmable hotkeys (2)
Programmable allocation of digital inputs and outputs
Fully customizable menu texts
Measurement of all instantaneous & integrated values MET
Circuit breaker control, status & condition monitoring XCBR 52
Trip circuit and coil supervision
Control inputs PloGGIO1
Power-up diagnostics and continuous self-monitoring
Dual rated 1A and 5A CT inputs
1-6 P446/EN/TM/E
MiCOMho P446 1 Introduction
P446/EN/TM/E 1-7
1 Introduction MiCOMho P446
2 COMPLIANCE
The unit has undergone a range of extensive testing and certification processes to ensure and prove
compatibility with all target markets. Table 6 summarizes a list of standards with which the device is
compliant. A detailed description of these criteria can be found in the Technical Specifications chapter.
Condition Compliance
EMC compliance (compulsory) 2004/108/EC (demonstrated by EN50263:2000)
Product safety (compulsory) 2006/95/EC (demonstrated by EN60255-27:2005)
R&TTE Compliance (compulsory) 99/5/EC
EN50263, IEC 60255-22-1/2/3/4, IEC 61000-4-5/6/8/9/10, EN61000-
EMC
4-3/18, IEEE/ANSI C37.90.1/2, ENV50204, EN55022
Product Safety for North America UL/CL File No. UL/CUL E202519
Environmental conditions IEC 60068-2-1/30/60/78
Power supply interruption IEC 60255-11, IEC 61000-4-11
Type tests for Insulation, creepage distance and clearances, high
IEC 60255-27:2005
voltage dielectric withstand, and impulse voltage withstand
Enclosure protection IEC 60529:1992 – IP10, IP30, IP52
Mechanical robustness IEC 60255-21-1/2/3
Table 6: Compliance standards
1-8 P446/EN/TM/E
MiCOMho P446 1 Introduction
3 APPLICATION OVERVIEW
P446/EN/TM/E 1-9
1 Introduction MiCOMho P446
4 ORDERING OPTIONS
Variants Order No.
Distance Protection P446 P446 **
Distance & Autoreclose for 2 Circuit Breakers
In/Vn rating
In = 1A/5A ; Vn = 100-120Vac 1
Protocol
Hardware options Compatibilty
Nothing 1, 3 & 4 1
IRIG-B Only (Modulated) 1, 3 & 4 2
Fibre Optic Converter Only 1, 3 & 4 3
IRIG-B (Modulated) & Fibre Optic Converter 1, 3 & 4 4
Ethernet (100Mbit/s) 6, 7 & 8 6
Ethernet (100Mbit/s) plus IRIG-B (Modulated) 6, 7 & 8 A
Ethernet (100Mbit/s) plus IRIG-B (De-modulated) 6, 7 & 8 B
IRIG-B (De-modulated) 1, 3 & 4 C
InterMiCOM + Courier Rear Port 1, 3 & 4 E
InterMiCOM + Courier Rear Port + IRIG-B modulated 1, 3 & 4 F
Redundant Ethernet Self-Healing Ring, 2 multi-mode fibre ports + Modulated IRIG-B 6, 7 & 8 G
Redundant Ethernet Self-Healing Ring, 2 multi-mode fibre ports + Un-modulated IRIG-B 6, 7 & 8 H
Redundant Ethernet RSTP, 2 multi-mode fibre ports + Modulated IRIG-B 6, 7 & 8 J
Redundant Ethernet RSTP, 2 multi-mode fibre ports + Un-modulated IRIG-B 6, 7 & 8 K
Redundant Ethernet Dual-Homing Star, 2 multi-mode fibre ports + Modulated IRIG-B 6, 7 & 8 L
Redundant Ethernet Dual-Homing Star, 2 multi-mode fibre ports + Un-modulated IRIG-B 6, 7 & 8 M
Product Options
24 inputs and 32-standard outputs B
24 inputs and 8 standard plus 12 high break outputs C
24 inputs and 16 standard plus 8 high break outputs D
As B + 850nm dual channel F
As C + 850nm dual channel G
As D + 850nm dual channel H
As B + 1300nm SM single channel J
As C + 1300nm SM single channel K
As D + 1300nm SM single channel L
As B + 1300nm SM dual channel N
As C + 1300nm SM dual channel O
As D + 1300nm SM dual channel P
As B + 1300nm MM single channel R
As C + 1300nm MM single channel S
As D + 1300nm MM single channel T
As B + 1300nm MM dual channel V
As C + 1300nm MM dual channel W
As D + 1300nm MM dual channel X
As B + 850nm MM + 1300mn SM Z
As D + 850nm MM + 1300mn SM 1
As B + 1300mn SM + 850nm MM 2
As D + 1300mn SM + 850nm MM 3
As B + 850nm MM + 1300mn MM 4
As D + 850nm MM + 1300mn MM 5
As B + 1300mn MM + 850nm MM 6
As D + 1300mn MM + 850nm MM 7
Mounting
Flush/Panel mounting M
19" Rack mounting N
Flush/panel mounting with harsh environment coating P
19" Rack mounting with harsh environmental coating Q
Language
English, French, German, Spanish 0
English, French, German, Russian 5
Chinese, English or French via HMI, with English or French only via Communications port C
Software version
Date and application dependant **
Hardware version
Extended main processor (XCPU2) With Function Keys & Tri-colour LEDs K
As K plus increased main processor memory (XCPU3), Cyber Security M
1-10 P446/EN/TM/E
MiCOMho P446 2 Safety Information
SAFETY INFORMATION
CHAPTER 2
P446/EN/TM/E 2-1
2 Safety Information MiCOMho P446
2-2 P446/EN/TM/E
MiCOMho P446 2 Safety Information
1 CHAPTER OVERVIEW
The Safety Information chapter provides information for the safe handling of the equipment. You must
be familiar with information contained in this chapter before unpacking, installing, commissioning, or
servicing the equipment.
The chapter contains the following sections
1 Chapter Overview
2 Health and Safety
3 Symbols
4 Installation, Commissioning and Servicing
4.1 General Safety Guidelines
4.1.1 Lifting Hazards
4.1.2 Electrical Hazards
4.2 UL/CSA/CUL Requirements
4.3 Equipment Connections
4.4 Protection Class 1 Equipment Requirements
4.5 Pre-energization Checklist
4.6 Peripheral Circuitry
4.7 Upgrading/Servicing
P446/EN/TM/E 2-3
2 Safety Information MiCOMho P446
Are familiar with the installation, commissioning, and operation of the equipment and the system
to which it is being connected.
Are familiar with accepted safety engineering practices and are authorized to energize and de-
energize equipment in the correct manner.
Are trained in the care and use of safety apparatus in accordance with safety engineering
practices
Are trained in emergency procedures (first aid).
Although the documentation provides instructions for installing, commissioning and operating the
equipment, it cannot cover all conceivable circumstances nor include detailed information on all topics.
In the event of questions or problems, do not take any action without proper authorization. Please
contact the appropriate Alstom Grid technical sales office and request the necessary information.
2-4 P446/EN/TM/E
MiCOMho P446 2 Safety Information
3 SYMBOLS
Throughout this chapter you may come across the following symbols. You will also see these symbols
on parts of the equipment.
Caution: refer to equipment documentation. Failure to do so could result in damage to the equipment
P446/EN/TM/E 2-5
2 Safety Information MiCOMho P446
Follow the Health and Safety at Work, etc Act 1974, and the Management of Health and Safety at
Work Regulations 1999.
All personnel involved in installing, commissioning, or servicing of this equipment must be familiar with the
correct working procedures.
Consult the equipment documentation before installing, commissioning, or servicing the equipment.
Always use the equipment in a manner specified by the manufacturer. Failure to do will jeopardize the
protection provided by the equipment.
Removal of equipment panels or covers may expose hazardous live parts, which must not be touched until the
electrical power is removed. Take extra care when there is unlocked access to the rear of the equipment.
A suitable protective barrier should be provided for areas with restricted space, where there is a risk of electric
shock due to exposed terminals.
Disconnect power before disassembling. Disassembly of the equipment may expose sensitive electronic
circuitry. Take suitable precautions against electrostatic voltage discharge (ESD) to avoid damage to the
equipment.
Where fiber optic communication devices are fitted, these should not be viewed directly. Optical power meters
should be used to determine the operation or signal level of the device.
Insulation testing may leave capacitors charged up to a hazardous voltage. At the end of each part of the test,
the voltage should be gradually reduced to zero, to discharge capacitors, before the test leads are disconnected.
2-6 P446/EN/TM/E
MiCOMho P446 2 Safety Information
To maintain compliance with UL and CSA/CUL, the equipment should be installed using UL/CSA-recognized
parts for: connection cables, protective fuses, fuse holders and circuit breakers, insulation crimp terminals, and
replacement internal batteries.
For external fuse protection, a UL or CSA Listed fuse must be used. The listed protective fuse type is: Class J
time delay fuse, with a maximum current rating of 15 A and a minimum DC rating of 250 V dc (for example type
AJT15).
Where UL/CSA listing of the equipment is not required, a high rupture capacity (HRC) fuse type with a maximum
current rating of 16 Amps and a minimum dc rating of 250 V dc may be used (for example Red Spot type NIT or
TIA.
M4 (#8) clamping screws of heavy duty terminal block connectors used for CT and VT wiring must be tightened
to a nominal torque of 1.3 Nm.
M3.5 (#6) clamping screws of medium duty terminal block connectors used for binary I/O and power supply
wiring must be tightened to a nominal torque of 0.8 Nm.
Pin terminal screws of terminal block connectors used for field wiring must be tightened to a nominal torque of
0.25 Nm.
Always use insulated crimp terminations for voltage and current connections.
Always use the correct crimp terminal and tool according to the wire size.
Watchdog (self-monitoring) contacts are provided to indicate the health of the device. Alstom Grid strongly
recommends that you hardwire these contacts into the substation's automation system, for alarm purposes.
Ground the equipment with the supplied PCT (Protective Conductor Terminal).
The PCT is sometimes used to terminate cable screens. Always check the PCT’s integrity after adding or
removing such functional ground connections.
The recommended minimum PCT wire size is 2.5 mm² for countries whose mains supply is 230 V (e.g. Europe)
and 3.3 mm² for countries whose mains supply is 110 V (e.g. North America). This may be superseded by local
or country wiring regulations.
P446/EN/TM/E 2-7
2 Safety Information MiCOMho P446
All connections to the equipment must have a defined potential. Connections that are pre-wired, but not used,
should be grounded when binary inputs and output relays are isolated. When binary inputs and output relays
are connected to a common potential, unused, pre-wired connections should be connected to the common
potential of the grouped connections.
Check voltage and current rating of external wiring, ensuring it is appropriate for the application.
Where external components, such as resistors or voltage dependent resistors (VDRs), are used, these may
present a risk of electric shock or burns, if touched.
Take extreme care when using external test blocks and test plugs such as the MMLG, MMLB and MiCOM
ALSTOM P990, as hazardous voltages may be exposed. CT shorting links must be in place before inserting or
removing MMLB test plugs, to avoid potentially lethal voltages.
4.7 Upgrading/Servicing
Modules, PCBs, or expansion boards must not be inserted into or withdrawn from the equipment while
energized, as this may result in damage to the equipment. Hazardous live voltages would also be exposed,
thus endangering personnel.
2-8 P446/EN/TM/E
MiCOMho P446 2 Safety Information
Avoid incineration or disposal to water courses. The equipment should be disposed of in a safe, responsible, in
an environmentally friendly manner, and if applicable, in accordance with country-specific regulations.
P446/EN/TM/E 2-9
2 Safety Information MiCOMho P446
2-10 P446/EN/TM/E
MiCOMho P446 3 Hardware Design
HARDWARE DESIGN
CHAPTER 3
P446/EN/TM/E 3-1
3 Hardware Design MiCOMho P446
3-2 P446/EN/TM/E
MiCOMho P446 3 Hardware Design
1 CHAPTER OVERVIEW
The Hardware Design chapter describes the design of the product's hardware platform. It consists of
the following sections:
1 Chapter Overview
2 Hardware Design
3 Housing Variants
4 Front Panel
4.1 Front panel ports
5 Rear Panel
6 Boards and modules
6.1 Main Processor Board
6.2 Power Supply Board
6.3 Standard Output Relay Board
6.4 Input Module
6.4.1 Transformer Board
6.4.2 Input board
6.5 Coprocessor board
6.6 IRIG-B board
6.7 Ethernet board
6.8 Redundant Ethernet with IRIG-B input
6.9 Rear Communications Board
6.10 Fibre Board
6.11 High Break Relay Output Board
P446/EN/TM/E 3-3
3 Hardware Design MiCOMho P446
2 HARDWARE DESIGN
All products based on the Px40 platform have common hardware architecture. The unit’s hardware is
based on a modular design philosophy and is made up of several modules drawn from a standard
range.
The exact specification and number of hardware modules used depends on the model number and the
variant, but the product will consists of a combination of the following boards:
Board Part No.
Power supply board 24/54 V DC ZN0021 001
Power supply board 48/125 V DC ZN0021 002
Power supply board 110/250 V DC ZN0021 003
Relay output board with 8 outputs ZN0019 001
Transformer board ZN0004 001
Input board ZN0017 011
Input board with opto-inputs ZN0017 012
Processor board ZN0069 001
IRIG-B board ZN0007 001
Fibre ZN0007 002
Fibre + IRIG-B ZN0007 003
2nd rear communications board ZN0025 001
2nd rear communications board with IRIG-B input ZN0025 002
100 MhZ Ethernet board ZN0049 001
100 MhZ Ethernet board with IRIG-B modulated input ZN0049 002
100 MhZ Ethernet board with IRIG-B demodulated input ZN0049 003
IRIG-B demodulated input ZN0049 004
High-break output relay board ZN0042 001
Coprocessor board ZN0020 002
Coprocessor board ZN0020 003
Redundant Ethernet SHP, 2 multi-mode fibre ports + modulated IRIG-B ZN0071 001
Redundant Ethernet SHP, 2 multi-mode fibre ports + demodulated IRIG-B ZN0071 002
Redundant Ethernet RSTP, 2 multi-mode fibre ports + modulated IRIG-B ZN0071 005
Redundant Ethernet RSTP, 2 multi-mode fibre ports + demodulated IRIG-B ZN0071 006
Redundant Ethernet DHP, 2 multi-mode fibre ports + modulated IRIG-B ZN0071 007
Redundant Ethernet DHP, 2 multi-mode fibre ports + demodulated IRIG-B ZN0071 008
Table 1 Board options
All modules are connected by a parallel data and address bus, which allows the processor board to
send and receive information to and from the other modules as required. There is also a separate
serial data bus for conveying sampled data from the input module to the processors. The figure below
shows the modules and the flow of information between them.
3-4 P446/EN/TM/E
MiCOMho P446 3 Hardware Design
P446/EN/TM/E 3-5
3 Hardware Design MiCOMho P446
3 HOUSING VARIANTS
The products of the MiCOM Px40 series can be implemented in a range of case sizes and types.
There are two main housing categories: standalone and rack-mounted. Each product can be
implemented in either case type.
Case dimensions for industrial products usually follow modular measurement units based on rack
sizes. These are: U for height and TE for width, where:
1U = 1.75" = 44.45 mm
1TE = 0.2 inches = 5.08 mm
The Px40 series of products are available in rack-mount or standalone versions. All products are
nominally 4U high to allow mounting in an IEC 60297 compliant 19” rack. The height of the front
panels are such that no significant gaps can be seen when they are mounted one above another in
the rack.
The case width depends on the product type and its hardware options. There are three different case
widths for the PX40 series of products: 40TE, 60TE and 80TE.
The widths in millimeters and inches for these case variants are shown below.
Case width (TE) Case width (mm) Case width (inches)
40TE 203.2 8
60TE 304.8 12
80TE 406.4 16
Table 2 Case Widths
The cases are pre-finished steel with a conductive covering of aluminum and zinc. This provides good
grounding at all joints, providing a low impedance path to earth that is essential for performance in the
presence of external noise.
3-6 P446/EN/TM/E
MiCOMho P446 3 Hardware Design
4 FRONT PANEL
Figure 2 shows the front panel of a typical 60TE unit. The front panels of the products based on 40TE and 80TE
cases have a lot of commonality, and differ only in the number of hotkeys and user-programmable
light-emitting diodes (LEDs). The hinged covers at the top and bottom of the front panel are shown
open. An optional transparent front cover physically protects the front panel.
Serial number
Current and voltage ratings.
A compartment for a 1/2 AA size backup battery (used for the real time clock and event, fault,
and disturbance records).
A 9-pin female D-type front port for an EIA(RS)232 serial connection to a PC.
A 25-pin female D-type parallel port for monitoring internal signals and downloading high-speed
local software and language text.
P446/EN/TM/E 3-7
3 Hardware Design MiCOMho P446
A Keypad
The keypad consists of the following keys:
Function keys to
Depending on the model, up to ten programmable function keys are available for custom use.
The function keys are associated with programmable LEDs for local control. Factory default settings
associate specific functions with these direct-action keys and LEDs, but by using programmable
scheme logic, you can change the default functions of the keys and LEDs to fit specific needs.
Trip (Red) switches ON when the IED issues a trip signal. It is reset when the associated fault
record is cleared from the front display. Also the trip LED can be configured as self-resetting.
Alarm (Yellow) flashes when the IED registers an alarm. This may be triggered by a fault, event
or maintenance record. The LED flashes until the alarms have been accepted (read), then
changes to constantly ON. When the alarms are cleared, the LED switches OFF.
Out of service (Yellow) is ON when the IED's protection is unavailable.
Healthy (Green) is ON when the IED is in correct working order, and should be ON at all times.
It goes OFF if the unit’s self-tests show there is an error in the hardware or software. The state
of the healthy LED is reflected by the watchdog contacts at the back of the unit.
3-8 P446/EN/TM/E
MiCOMho P446 3 Hardware Design
proprietary communication protocol to allow communication with a range of protection equipment, and
between the device and the Windows-based support software package.
You can connect the unit to a PC with a serial cable up to 15 m in length.
The port pin-out follows the standard for Data Communication Equipment (DCE) device with the
following pin connections on a 9-pin connector.
Pin number Description
2 Tx Transmit data
3 Rx Receive data
5 0 V Zero volts common
Table 3 DCE 9-pin serial port connections
You must use the correct serial cable, or the communication will not work. A straight-through serial
cable is required, connecting pin 2 to pin 2, pin 3 to pin 3, and pin 5 to pin 5.
Once the physical connection from the unit to the PC is made, the PC’s communication settings must
be set to match those of the IED. The following table shows the unit’s communication settings for the
front port.
Protocol Courier
Baud rate 19,200 bps
Courier address 1
Message format 11 bit - 1 start bit, 8 data bits, 1 parity bit (even parity), 1 stop bit
Table 4 RS232 communication settings
The inactivity timer for the front port is set to 15 minutes. This controls how long the unit maintains its
level of password access on the front port. If no messages are received on the front port for 15
minutes, any password access level that has been enabled is cancelled.
The front communication port supports the Courier protocol for one-to-one communication. It is
designed to be used for installing, commissioning or maintaining the unit and is not intended for
permanent connection.
P446/EN/TM/E 3-9
3 Hardware Design MiCOMho P446
Note: The front serial port does not support automatic extraction of event and disturbance records,
although this data can be accessed manually.
3-10 P446/EN/TM/E
MiCOMho P446 3 Hardware Design
5 REAR PANEL
The MiCOM Px40 series is of a modular construction, most of the internal workings being
implemented on boards and modules, which fit into slots. Some of the boards plug into terminal
blocks, which are bolted onto the rear of the unit, whilst some boards such as the communications
boards have their own connectors. The rear panel consists of these terminal blocks, plus the rears of
the communications boards.
The back panel cut-outs and slot allocations vary according to the product and the type of boards and
terminal blocks needed to populate the case. The following figure shows a typical rear view of an
80TE case populated with various boards.
Note: This diagram is just an example and may not show the exact product described in this manual. It
also does not show the full range of available boards, just a typical arrangement.
Not all slots are the same size. The slot width depends on the type of board or terminal block. For
example, HD (heavy duty) terminal blocks, as required for the analogue inputs, require a wider slot
size than MD (medium duty) terminal blocks. The board positions are not generally interchangeable.
Each slot is designed to house a particular type of board. Again this is model-dependent.
There are four types of terminal block: RTD/CLIO, MIDOS, HD and MD. The terminal blocks are
fastened to the rear panel with screws.
P446/EN/TM/E 3-11
3 Hardware Design MiCOMho P446
HD Terminal Block MD Terminal Block Midos Terminal Block RTD/CLIO Terminal Block
P4522ENa .
Figure 5: Terminal block types
Note: Not all products use all types of terminal blocks. The product described in this manual may use one
or more of the above types.
3-12 P446/EN/TM/E
MiCOMho P446 3 Hardware Design
PCBs
Each PCB is assigned a 9 character part number beginning with 'ZN'. This is followed by a 7-digit
number split into two parts as follows:
ZN<4digit number> <3 digit number>
where the 4-digit number is the main part number and the 3 digit number is the variation of that part
number. This is best illustrated by an example; in this case, the 3 power supply variations:
Component Description Part Number
Power Supply Module: 24/54 V DC ZN0021 001
Power Supply Module: 48/125 V DC ZN0021 002
Power Supply Module: 110/250 V DC ZN0021 003
Table 5 PCB numbering
A PCB typically consists of the components, a front connector for connecting into the main system
parallel bus via a ribbon cable, and an interface to the rear. This rear interface may be:
Directly presented to the outside world (as is the case for communication boards such as
Ethernet Boards)
Presented to a connector, which in turn connects into a terminal block bolted onto the rear of
the case (as is the case for most of the other board types)
P446/EN/TM/E 3-13
3 Hardware Design MiCOMho P446
Subassemblies
A sub-assembly consists of two or more boards connected together physically (bolted together with
spacers) and electrically (via electrical connectors). It may also have other special requirements such
as being encased in a metal housing for shielding against electromagnet radiation.
Boards are designated by a part number beginning with ZN, whereas preassembled sub-assemblies
are designated with a part number beginning with GN. Subassemblies, which are put together at the
production stage, do not have a separate part number.
The products in the Px40 series typically contain two subassemblies:
The input module is preassembled and is therefore assigned a GN number, whereas the power supply
module is assembled at production stage and does not therefore have an individual part number.
Connections
HD or MIDOS terminal blocks are used at the rear of the unit for the current and voltage signal
connections. MD terminal blocks are used for the digital logic input signals, the output relay contacts,
the power supply and the rear communication port.
3-14 P446/EN/TM/E
MiCOMho P446 3 Hardware Design
Grounding
The boards and modules use multi-point grounding to improve the immunity to external noise and
minimize the effect of circuit noise. Ground planes are used on boards to reduce impedance paths and
spring clips are used to ground the module metalwork.
The main processor board is based around a floating point, 32-bit Digital Signal Processor (DSP). It
performs all calculations and controls the operation of all other modules in the IED, including the data
communication and user interfaces. This board is the only board that does not fit into one of the slots.
It resides in the front panel and is connected to the rest of the system via an internal ribbon cable.
The LCD and LEDs are mounted on the processor board along with the front panel communication
ports. All serial communication is handled using a Field Programmable Gate Array (FPGA).
The memory provided on the main processor board is split into two categories, volatile and non-
volatile: the volatile memory is fast access SRAM which is used for the storage and execution of the
processor software, and data storage as required during the processor’s calculations. The non-
volatile memory is sub-divided into two groups:
Flash memory for non-volatile storage of software code, text and configuration data including
the present setting values
Battery-backed SRAM for the storage of disturbance, event, fault and maintenance record data
P446/EN/TM/E 3-15
3 Hardware Design MiCOMho P446
The power supply board provides power to the unit. One of three different configurations of the power
supply board can be fitted to the unit. This will be specified at the time of order and depends on the
nature of the supply voltage that will be connected to it.
The three board versions are:
The power supply board connector plugs into a medium duty terminal block sliding in from the front of
the unit to the rear. This terminal block is always positioned on the right hand side of the unit looking
from the rear.
The power supply board is usually assembled together with the relay output board to form a complete
subassembly, as shown below.
3-16 P446/EN/TM/E
MiCOMho P446 3 Hardware Design
P4551ENa
The power supply outputs are used to provide isolated power supply rails to the various modules
within the unit. Three voltage levels are used by the unit’s modules:
All power supply voltages including the 0 V earth line are distributed around the unit by means of the
64-way ribbon cable.
An additional 48 V supply is provided by the power supply board for the field voltage. This is brought
out to terminals on the back of the unit so that it can be used to drive the optically isolated digital
inputs.
The power supply board incorporates inrush current limiting. This limits the peak inrush current to
approximately 10 A.
Power is applied to pins 1 and 2 of the terminal block, where pin 1 is negative and pin 2 is positive.
The pin numbers are clearly marked on the terminal block as show below.
P446/EN/TM/E 3-17
3 Hardware Design MiCOMho P446
Power: Terminals 1 + 2 of
PSU terminal block.
1 T1 = -ve
2
T2 = +ve
16
17
18
P4538ENa
Watchdog Facility
The power supply board also provides a Watchdog facility. This Watchdog facility provides two output
relay contacts, one normally open and one normally closed. These are used to indicate the health of
the unit processor board. They are driven by the main processor board.
1
2
P4550ENa
3-18 P446/EN/TM/E
MiCOMho P446 3 Hardware Design
Note: The polarity independent K-bus can only be used for the Courier data protocol. The polarity
conscious MODBUS, IEC60870-5-103 and DNP3.0 protocols need RS485.
The rear serial port is shown in Figure 13. The pin assignments are as follows:
1
2
Note: An additional serial port with D-type presentation is available as an optional board, if required.
The power supply board also provides a rear serial port. The rear serial port (RP1) is an EIA(RS)485
interface, which provides SCADA communication. The interface supports half-duplex communication
and provides optical isolation for the serial data being transmitted and received.
P446/EN/TM/E 3-19
3 Hardware Design MiCOMho P446
P4527ENa
ZN0019 xxx: 8 relays with 6 Normally Open contacts and 2 Changeover contacts
ZN0031 xxx: 7 relays with 3 Normally Open contacts and 4 Changeover contacts
3-20 P446/EN/TM/E
MiCOMho P446 3 Hardware Design
Terminal Number
Terminal 8 Relay 4 NO
Terminal 9 Relay 5 NO
Terminal 10 Relay 5 NO
Terminal 11 Relay 6 NO
Terminal 12 Relay 6 NO
Terminal 13 Relay 7 changeover
Terminal 14 Relay 7 common
Terminal 15 Relay 7 changeover
Terminal 16 Relay 8 changeover
Terminal 17 Relay 8 common
Terminal 18 Relay 8 changeover
Table 6: Pin-out of 8-relay board
P446/EN/TM/E 3-21
3 Hardware Design MiCOMho P446
The input module consists of two or three PCBs; the main input board and one or two transformer
boards, depending on the model chosen. The transformer board contains the voltage and current
transformers, which isolate and scale the analogue input signals delivered by the system transformers.
The input board contains the A/D conversion and digital processing circuitry, as well as eight digital
optically isolated inputs (opto-inputs).
The boards are connected together physically (bolted together with spacers) and electrically (via
electrical connectors). The module is encased in a metal housing for shielding against electromagnet
radiation.
3-22 P446/EN/TM/E
MiCOMho P446 3 Hardware Design
The transformer board hosts the current and voltage transformers, which are used to step down the
currents and voltages originating from the power systems' current and voltage transformers to levels,
which can be used by the unit’s electronic circuitry. In addition to this, the on-board CT and VT
transformers provide electrical isolation between the unit and the power system.
The transformer board is connected physically and electrically to the input board to form a complete
input module.
Transformer Inputs
The CT and VT secondary windings provide differential input signals to the input board to reduce
noise. Up to 5 current transformers and 4 voltage transformers can be populated on one transformer
board. The current inputs will accept either 1 A or 5 A nominal current, depending on the tapping
chosen. The CT and VT inputs are presented to a HD or MiDOS terminal block.
The exact pin out is dependent on the model and its variant, but generally it follows a standard theme.
The following table shows a typical pin out of the first transformer board. The exact pin out details are
provided in the wiring diagrams in the Wiring Diagrams section near the end of this manual
Terminal Number
Terminal 1 IA 5A tapping
Terminal 2 IA common
Terminal 3 IA 1A tapping
Terminal 4 IB 5A tapping
Terminal 5 IB common
Terminal 6 IB 1A tapping
Terminal 7 IC 5A tapping
Terminal 8 IC common
Terminal 9 IC 1A tapping
P446/EN/TM/E 3-23
3 Hardware Design MiCOMho P446
Terminal Number
Terminal 10 IN 5A tapping
Terminal 11 IN common
Terminal 12 IN 1A tapping
Terminal 13 IN sen 5A tapping
Terminal 14 IN sen common
Terminal 15 IN sen 1A tapping
Terminal 16
Terminal 17
Terminal 18
Terminal 19 VA
Terminal 20 VB
Terminal 21 VC
Terminal 22 VN
Terminal 23 VCS1
Terminal 24 VCS2
Table 8: Transformer input pin-out
The input board is used to convert the analogue signals delivered by the current and voltage
transformers into digital quantities used by the IED. This input board also has on-board opto-input
circuitry, providing eight optically-isolated digital inputs and associated noise filtering and buffering.
These opto-inputs are presented to the user by means of a MD terminal block, which sits adjacent to
the analogue inputs terminal block.
3-24 P446/EN/TM/E
MiCOMho P446 3 Hardware Design
The input board is connected physically and electrically to the transformer board to form a complete
input module.
A schematic of the input module comprising two boards is shown in Figure 19 .
Noise Noise
filter filter
Parallel Bus
Buffer
Transformer
board
VT Low
or pass
CT filter
VT Low
or pass
CT filter
P4552ENa
A/D Conversion
The differential analogue inputs from the unit’s CT and VT transformers are presented to the main
input board as shown. Each differential input is first converted to a single input quantity referenced to
the input board’s ground potential. The signals are then passed through low pass filters to attenuate
the high frequency components before being presented to a multiplexer. The sample stream output
from the multiplexer is buffered before being presented to the 16 bit ADC, where the samples are
converted into digital quantities with 16 bit resolution. The digital sample stream is passed through a
serial interface module and then presented to the unit’s processing boards in the form of a serial
sample data bus.
The calibration coefficients are stored in non-volatile memory. These are used by the processor board
to correct for any amplitude or phase errors introduced by the transformers and analogue circuitry.
Opto-isolated inputs
The other function of the input board is to read in the digital inputs. As with the analogue inputs, the
digital inputs must be electrically isolated from the power system. This is achieved by means of the 8
on-board optical isolators for connection of up to 8 digital signals. The digital signals are passed
P446/EN/TM/E 3-25
3 Hardware Design MiCOMho P446
through an optional noise filter before being buffered and presented to the unit’s processing boards in
the form of a parallel data bus.
This selectable filtering allows the use of a pre-set filter of ½ cycle which renders the input immune to
induced power-system noise on the wiring. Although this method is secure it can be slow, particularly
for inter-tripping. This can be improved by switching off the ½ cycle filter in which case one of the
following methods to reduce ac noise should be considered.
The opto-isolated logic inputs can be programmed for the nominal battery voltage of the circuit of
which they are a part, allowing different voltages for different circuits such as signaling and tripping.
They can also be programmed to 60% - 80% or 50% - 70% pickup to dropoff ratio of the nominal
battery voltage in order to satisfy different operating constraints.
The threshold levels are as follows:
Nominal Battery voltage Logic levels: 60-80% DO/PU Logic Levels: 50-70% DO/PU
24/27 V Logic 0 < 16.2 V : Logic 1 > 19.2 V Logic 0 <12.0 V : Logic 1 > 16.8
30/34 Logic 0 < 20.4 V : Logic 1 > 24.0 V Logic 0 < 15.0 V : Logic 1 > 21.0 V
48/54 Logic 0 < 32.4 V : Logic 1 > 38.4 V Logic 0 < 24.0 V : Logic 1 > 33.6 V
110/125 Logic 0 < 75.0 V : Logic 1 > 88.0 V Logic 0 < 55.0 V : Logic 1 > 77.0 V
220/250 Logic 0 < 150 V : Logic 1 > 176.0 V Logic 0 < 110 V : Logic 1 > 154.0 V
Table 9: Opto-input thresholds
The lower value eliminates fleeting pickups that may occur during a battery earth fault, when stray
capacitance may present up to 50% of battery voltage across an input.
Note: The opto-input circuitry can be provided without the A/D circuitry as a separate board, which can
provide supplementary opto-inputs. The board number for this separate opto-input board is
ZN0017-012.
Opto-Inputs
The pin-out of the opto-inputs are shown in the table below.
Terminal Number
Terminal 1 Opto 1 -ve
Terminal 2 Opto 1 +ve
Terminal 3 Opto 2 -ve
Terminal 4 Opto 2 +ve
Terminal 5 Opto 3 -ve
Terminal 6 Opto 3 +ve
Terminal 7 Opto 4 -ve
Terminal 8 Opto 4 +ve
Terminal 9 Opto 5 -ve
Terminal 10 Opto 5 +ve
Terminal 11 Opto 6 -ve
Terminal 12 Opto 6 +ve
Terminal 13 Opto 7 –ve
Terminal 14 Opto 7 +ve
Terminal 15 Opto 8 –ve
3-26 P446/EN/TM/E
MiCOMho P446 3 Hardware Design
Terminal Number
Terminal 16 Opto 8 +ve
Terminal 17 Common
Terminal 18 Common
Table 10: Opto-input pin-out
Note: The above figure shows a coprocessor complete with GPS input and 2 fibre-optic serial data
interfaces. These interfaces will not be present on boards that do not require them.
Where applicable, a second processor board is used to process the special algorithms associated with
the device. This second processor board provides fast access (zero wait state) SRAM for use with
both program and data memory storage. This memory can be accessed by the main processor board
via the parallel bus. This is how the software is transferred from the flash memory on the main
processor board to the coprocessor board on power up. Further communication between the two
processor boards is achieved via interrupts and the shared SRAM. The serial bus carrying the sample
data is also connected to the co-processor board, using the processor’s built-in serial port, as on the
main processor board.
P446/EN/TM/E 3-27
3 Hardware Design MiCOMho P446
The IRIG-B board can be fitted to provide an accurate timing reference for the device. The IRIG-B
signal is connected to the board via a BNC connector. The timing information is used to synchronize
the IED's internal real-time clock to an accuracy of 1 ms. The internal clock is then used for time
tagging events, fault maintenance and disturbance records.
The IRIG-B interface is available in modulated or demodulated formats. The two board variants are as
follows:
Due to slot limitations the IRIG-B facility is also provided in combination with other functionality on a
number of additional boards, such as:
Each of these boards is also available with either modulated or demodulated IRIG-B.
The IRIG-B signal is used for setting the IEDs internal real time clock. It is not used to time
synchronize devices.
3-28 P446/EN/TM/E
MiCOMho P446 3 Hardware Design
This is a communications board that provides a standard 100-Base Ethernet interface. This board
supports one electrical copper connection and one fibre-pair connection.
There are three variants for this product as follows:
Two of the variants provide an IRIG-B interface. IRIG-B provides a timing reference for the unit – one
board for modulated IRIG-B and one for demodulated. The IRIG B signal is connected to the board
with a BNC connector.
P446/EN/TM/E 3-29
3 Hardware Design MiCOMho P446
This board provides dual redundant Ethernet (supported by two fibre pairs) together with an IRIG-B
interface for timing.
Alstom Grid supply six different board variants depending on the redundancy protocol and the type of
IRIG-B signal (demodulated or modulated). The available redundancy protocols are:
ZN0071 001: 100 MHz redundant Ethernet running RSTP, with on-board modulated IRIG-B
ZN0071 002: 100 MHz redundant Ethernet running RSTP, with on-board demodulated IRIG-B
ZN0071 005: 100 MHz redundant Ethernet running SHP, with on-board modulated IRIG-B
ZN0071 006: 100 MHz redundant Ethernet running SHP, with on-board demodulated IRIG-B
ZN0071 007: 100 MHz redundant Ethernet running DHP, with on-board modulated IRIG-B
ZN0071 008: 100 MHz redundant Ethernet running DHP, with on-board demodulated IRIG-B
3-30 P446/EN/TM/E
MiCOMho P446 3 Hardware Design
P4547ENa
The optional communications board containing the secondary communication ports provide two serial
interfaces presented on 9 pin D-type connectors. These interfaces are known as SK4 and SK5.
SK4 can be used with RS232 RS485 and K-bus.
SK5 can only be used with RS232 and is used for InterMiCOM communication.
The second rear communications board and IRIG-B board are mutually exclusive since they use the
same hardware slot. For this reason two versions of the second rear communications board are
available; one with an IRIG-B input and one without:
The board comes in two varieties; one with an IRIG-B input and one without:
P446/EN/TM/E 3-31
3 Hardware Design MiCOMho P446
This board provides an interface for communicating with a master station. This communication link can
use all compatible protocols (Courier, IEC 60870-5-103, MODBUS and DNP 3.0). It is a fibre-optic
alternative to the metallic RS485 port presented on the power supply terminal block, and as such is
mutually exclusive with it.
It uses BFOC 2.5 ST connectors
The board comes in two varieties; one with an IRIG-B input and one without:
3-32 P446/EN/TM/E
MiCOMho P446 3 Hardware Design
P4554ENa
A High Break output relay board is available as an option. It comprises four normally open output
contacts, which are suitable for high breaking loads.
A High Break contact consists of a high capacity relay with a MOSFET in parallel with it. The
MOSFET has a varistor placed across it to provide protection, which is required when switching off
inductive loads. This is because the stored energy in the inductor causes a high reverse voltage that
could damage the MOSFET, if not protected.
When there is a control input command to operate an output contact the miniature relay is operated at
the same time as the MOSFET. The miniature relay contact closes in nominally 3.5 ms and is used to
carry the continuous load current. The MOSFET operates in less than 0.2 ms, but is switched off after
7.5 ms.
When the control input is reset, the MOSFET is again turned on for 7.5 mS. The miniature relay
resets in nominally 3.5 ms before the MOSFET. This means the MOSFET is used to break the load.
The MOSFET absorbs the energy when breaking inductive loads and so limits the resulting voltage
surge. This contact arrangement is for switching DC circuits only.
The following figure shows the timing diagram for High Break contact operation
P446/EN/TM/E 3-33
3 Hardware Design MiCOMho P446
databus on off
control input
MOSFET reset
relay contact
closed
load current
Breaker fail
In the event of failure of the local circuit breaker (stuck breaker), or defective auxiliary contacts
(stuck contacts), it is incorrect to use 52a contact action. The interrupting duty at the local
breaker then falls on the relay output contacts, which may not be rated to perform this duty.
High Break contacts should be used in this case to avoid the risk of burning out relay contacts.
Initiation of teleprotection
The High Break contacts also offer fast making, which results in faster tripping. In addition, fast
keying of teleprotection is a benefit. Fast keying bypasses the usual contact operation time,
such that permissive, blocking and intertrip commands can be routed faster.
Warning: These relay contacts are POLARITY SENSITIVE. External wiring must comply with the
polarity requirements described in the external connection diagram to ensure correct
operation.
3-34 P446/EN/TM/E
MiCOMho P446 4 Software Design
SOFTWARE DESIGN
CHAPTER 4
P446/EN/TM/E 4-1
4 Software Design MiCOMho P446
4-2 P446/EN/TM/E
MiCOMho P446 4 Software Design
1 CHAPTER OVERVIEW
The Software Design chapter describes the design of the product's software platform. It consists of the
following sections:
1 Chapter Overview
2 Software Design Overview
3 System Level Software
3.1 Real Time Operating system
3.2 System Services Software
3.3 Self-diagnostic Software
3.3.1 Start-up Self-Testing
3.3.1.1 System Boot
3.3.1.2 Initialization Software
3.3.1.3 Platform Software Initialization & Monitoring
3.3.2 Continuous Self-testing
4 Platform Software
4.1 Record Logging
4.2 Settings Database
4.3 Interfaces
6 Coprocessor Software
6.1 Distance Protection
P446/EN/TM/E 4-3
4 Software Design MiCOMho P446
These elements are not distinguishable to the user, and the distinction is made purely for the purposes
of explanation. Figure 1 shows the software structure.
Settings database
Control of output
contacts and
Sampling programmable LEDs
function Front panel Local
interface communications
(LCD + Keypad) interfaces
Hardware
P4553ENa
The software, which executes on the main processor, can be divided into a number of functions as
illustrated above. Each function is further broken down into a number of separate tasks. These tasks
are then run according to a scheduler. They are run at either a fixed rate or they are event driven. The
tasks communicate with each other as required.
4-4 P446/EN/TM/E
MiCOMho P446 4 Software Design
P446/EN/TM/E 4-5
4 Software Design MiCOMho P446
At the conclusion of the initialization software the supervisor task begins the process of starting the
platform software.
For products using a coprocessor, the startup checks are as follows:
A check is made for the presence of the co-processor board, and if present a valid response
The SRAM on the co-processor board is checked with a test bit pattern before the co-processor
code is transferred from the flash EPROM
If any of these checks produce an error, the co-processor board remains out of service.
Note: A coprocessor board is used only in products with Distance, phase comparison, or current
differential functionality.
At the successful conclusion of all of these tests the unit is entered into service and the application
software is started up.
The flash EPROM containing all program code and language text is verified by a checksum
The code and constant data held in SRAM is checked against the corresponding data in flash
EPROM to check for data corruption
The SRAM containing all data other than the code and constant data is verified with a
checksum
The battery status
The level of the 48 V field voltage
The integrity of the digital signal I/O data from the opto-isolated inputs and the output relay coils
is checked by the data acquisition function every time it is executed.
4-6 P446/EN/TM/E
MiCOMho P446 4 Software Design
The operation of the analogue data acquisition system is continuously checked by the
acquisition function every time it is executed. This is done by sampling the reference voltages
The operation of the optional Ethernet board is checked by the software on the main processor
card. If the Ethernet board fails to respond an alarm is raised and the card is reset in an
attempt to resolve the problem.
The operation of the optional IRIG-B function is checked by the software that reads the time and
date from the board
In the event that one of the checks detects an error in any of the unit’s subsystems, the platform
software is notified and it attempts to log a maintenance record in battery-backed SRAM.
If the problem is with the battery status or the IRIG-B board, the unit continues in operation. For
problems detected in any other area, the unit initiates a shutdown and re-boot, resulting in a period of
up to 10 seconds when the functionality is unavailable.
The complete restart of the unit including all initializations should clear most problems that may occur.
If, however, the diagnostic self-check detects the same problem that caused the unit to restart, it is
clear that the restart has not cleared the problem, and the unit takes itself permanently out of service.
This is indicated by the ‘’health-state’ LED on the front of the unit, which switches OFF, and the
watchdog contact which switches ON.
The start-up and continuous self test logic diagrams are shown below.
P446/EN/TM/E 4-7
4 Software Design MiCOMho P446
4-8 P446/EN/TM/E
MiCOMho P446 4 Software Design
P446/EN/TM/E 4-9
4 Software Design MiCOMho P446
4 PLATFORM SOFTWARE
The platform software has three main functions:
To control the logging of records generated by the protection software, including alarms, events,
faults, and maintenance records
To store and maintain a database of all of the settings in non-volatile memory
To provide the internal interface between the Settings database and the unit’s user interfaces,
using the front panel interface and the front and rear communication ports.
Alarms
Event records
Fault records
Security records
Maintenance records
The logs are maintained such that the oldest record is overwritten with the newest record. The logging
function can be initiated from the protection software. The platform software is responsible for logging
a maintenance record in the event of an IED failure. This includes errors that have been detected by
the platform software itself or errors that are detected by either the system services or the protection
software function. See the Settings and Records chapter for further details on record logging.
4.3 Interfaces
The settings and measurements database must be accessible from all of the interfaces to allow read
and modify operations. The platform software presents the data in the appropriate format for each of
the interfaces (LCD display, keypad and all the communications interfaces).
4-10 P446/EN/TM/E
MiCOMho P446 4 Software Design
P446/EN/TM/E 4-11
4 Software Design MiCOMho P446
1.2
Power frequency (eg 50/60 Hz)
Ma gnitude (per unit)
1
Combined response of fourier
and anti-aliasing filters
0.8
0.6
Anti-aliasing filter response
0.4
0.2
0
0 5 10 15 20 25
Harmonic
P4563ENa
The Fourier components of the input current and voltage signals are stored in memory so that they
can be accessed by all of the protection elements’ algorithms. The disturbance recorder also uses the
samples from the input module, in an unprocessed form. This is for waveform recording and the
calculation of true RMS values of current, voltage and power for metering purposes.
Digital input signals (from the opto-isolated inputs on the input board)
Outputs of the protection elements (for example, protection starts and trips)
Outputs of the fixed protection scheme logic (the fixed scheme logic is the standard set of
protection schemes provided by default)
InterMiCOM (IM), InterMiCOM64 (IM64) signals and Control Inputs
IEC61850 GOOSE inputs (optional)
Function keys (this option is not applicable to all products)
The PSL consists of programmable logic gates, latches and delay timers. The logic gates can be
programmed to perform a range of different logic functions and can accept any number of inputs. The
timers are used either to create a programmable delay, or to condition the logic outputs such as
creating pulses of fixed duration. The outputs of the PSL are the LEDs on the front panel, the output
contacts at the rear of the unit, IM and IM64 signals and GOOSE outputs.
The execution of the PSL logic is event driven, i.e. it only runs when an input changes state. This
reduces the amount of processing time used by the PSL. The output of the latches, timers and relay
contacts are updated at the end of the protection and control task.
4-12 P446/EN/TM/E
MiCOMho P446 4 Software Design
The PSL allows you to design your own logic scheme. This means that it can be configured to form
very complex systems. Because of this, the PSL can only be configured using the PSL Editor, which
is a component of the PC support package MiCOM S1 Studio.
When you transfer a PSL file from the PSL editor to the IED, you can specify the Group to which it is
downloaded, together with a 32-character reference description. This PSL reference is shown in the
Grp1/2/3/4 PSL Ref cell in the PSL DATA column. The download date and time and file checksum for
each of the group’s PSL file is also shown in the cells Date/Time and Grp 1/2/3/4 PSL ID in the PSL
DATA column. The PSL data can be used to indicate whether a PSL has been changed and thus be
useful in providing information for version control of PSL files.
The default PSL Reference description is Default PSL followed by the model number, for example,
“Default PSL PXXX??????0yy0?” where XXX refers to the product and yy refers to the software
version. This is the same for all protection setting groups since the default PSL is the same for all
groups. Since the LCD display (bottom line) only has space for 16 characters the display must be
scrolled to see all 32 characters of the PSL Reference description.
Note: The PSL DATA column information is visible using the front panel interface or over the Courier
communications protocol.
P446/EN/TM/E 4-13
4 Software Design MiCOMho P446
during relay power up thus allowing the function key state to be reinstated after power-up, should
power be inadvertently lost.
4-14 P446/EN/TM/E
MiCOMho P446 4 Software Design
6 COPROCESSOR SOFTWARE
For distance protection, phase comparison and differential protection functionality, a coprocessor
software module, which runs on a coprocessor board, is required. There are three types, depending
on the required functionality:
All of the processing for the Differential, Phase Comparison, Distance and DEF protection algorithms
is performed on the co-processor board.
The co-processor is also responsible for managing inter-tripping commands IM64 via the
communication link.
Data exchange between the co-processor board and the main processor board is achieved through
the use of shared memory on the co-processor board. When the main processor accesses this
memory, the co-processor is temporarily halted. After the co-processor code has been copied onto
the board at initialization, the main traffic between the two boards consists of setting change
information, commands from the main processor, differential protection measurements and output
data.
Note: The protection elements perform additional filtering, for example implemented by the trip count
strategy.
Figure 5 shows the frequency response of the 12, 24 and 48 coefficient filters, noting that all have a
gain of unity at the fundamental.
P446/EN/TM/E 4-15
4 Software Design MiCOMho P446
4-16 P446/EN/TM/E
MiCOMho P446 5 Configuration
CONFIGURATION
CHAPTER 5
P446/EN/TM/E 5-1
5 Configuration MiCOMho P446
5-2 P446/EN/TM/E
MiCOMho P446 5 Configuration
1 OVERVIEW
Each product has different configuration parameters according to the functions it has been designed to
perform. There is, however, a common methodology used across the entire Px40 product series to set
these parameters.
This chapter describes an overview of this common methodology, as well as providing concise
instructions of how to configure the device.
This chapter consists of the following sections:
1 Overview
2 Using the HMI Panel
2.1 Navigating the HMI Panel
2.2 Getting started
2.3 Default display
2.4 Password Entry
2.5 Reading and Clearing of Alarms and Fault Records
2.6 Menu Structure
2.7 Changing the Settings
2.8 Direct Access (The Hotkey Menu)
2.9 Function keys
P446/EN/TM/E 5-3
5 Configuration MiCOMho P446
The keypad provides full access to the device functionality by means of a range of menu options. The
information is displayed on the LCD.
Keys Description Function
C Cancel key
To return to column header from any
menu cell
F1
For executing user programmable
Function keys
functions
Note: As the LCD display has a resolution of 16 characters by 3 lines, some of the information is in a
condensed mnemonic form.
5-4 P446/EN/TM/E
MiCOMho P446 5 Configuration
The cursor keys are used to navigate the menus. These keys have an auto-repeat function if held
down continuously. This can be used to speed up both setting value changes and menu navigation.
The longer the key is held pressed, the faster the rate of change or movement.
Figure 1 shows how to navigate the menu items in the form of a menu navigation map.
Alarm message
P4565ENa
If there are alarms present, the yellow Alarms LED will be flashing and the menu display will read as
follows:
P446/EN/TM/E 5-5
5 Configuration MiCOMho P446
Alarms / Faults
Present
HOTKEY
Even though the device itself should be in full working order when you first start it, an alarm could still
be present, for example, if there is no network connection for a device fitted with a network card. If this
is the case, you can read the alarm by pressing the 'Read' key.
ALARMS
NIC Link Fail
The only way you will be able to completely clear this alarm will be by connecting the device into an
Ethernet network. This is also the only way you will be able to get into the default display menu.
If there are other alarms present, these must also be cleared before you can get into the default
display menu options
11:09:15
23 Nov 2010
HOTKEY
Description (user-defined)
For example:
Description
MiCOM P543
HOTKEY
5-6 P446/EN/TM/E
MiCOMho P446 5 Configuration
Plant Reference
MiCOM
HOTKEY
Access Level
For example:
Access Level
3
HOTKEY
In addition to the above, there are also displays for the system voltages, currents, power and
frequency.
Figure 2 depicts the navigation between default displays.
The right cursor key takes you to the next menu option in a clockwise direction, whereas the left cursor
key takes you to the next menu option in an anti-clockwise direction.
If the device is not yet configured for NERC compliance (see cyber Security chapter) a warning will
appear when moving from the "NERC compliant" banner. The warning message is as follows:
P446/EN/TM/E 5-7
5 Configuration MiCOMho P446
You will have to confirm with the ENTER button before you can go any further.
Note: The unit is delivered with the NERC-compliant default display. Please see the Cyber Security
chapter for further details
Note: Whenever the unit has an uncleared alarm the default display is replaced by the text Alarms/ Faults
present. You cannot override this default display. However, you can enter the menu structure from
the default display, even if the display shows the Alarms/Faults present message.
Enter Password
1. A flashing cursor shows which character field of the password can be changed. Press the up
or down cursor keys to change each character (tip: pressing the up arrow once will return an
upper case "A" as required by the default level 3 password).
2. Use the left and right cursor keys to move between the character fields of the password.
3. Press the Enter key to confirm the password. If you enter an incorrect password, an invalid
password message is displayed then the display reverts to Enter password. Upon entering a
valid password a message appears indicating that the password is correct and if so what level
of access has been unlocked. If this level is sufficient to edit the selected setting, the display
returns to the setting page to allow the edit to continue. If the correct level of password has not
been entered, the password prompt page appears again.
4. To escape from this prompt press the Clear key. Alternatively, enter the password using
System data > Password. If the keypad is inactive for 15 minutes, the password protection of
the front panel user interface reverts to the default access level.
5. To manually reset the password protection to the default level, select System data >
Password, then press the clear key instead of entering a password.
1. To view the alarm messages, press the "Read" key. When all alarms have been viewed but
not cleared, the alarm LED changes from flashing to constantly on, and the latest fault record
appears (if there is one).
2. Scroll through the pages of the latest fault record, using the cursor keys. When all pages of the
fault record have been viewed, the following prompt appears.
5-8 P446/EN/TM/E
MiCOMho P446 5 Configuration
Press Clear To
Reset Alarms
3. To clear all alarm messages, press the Clear key. To return to the display showing alarms or
faults present, and leave the alarms uncleared, press the "Read" key.
4. Depending on the password configuration settings, you may need to enter a password before
the alarm messages can be cleared.
5. When all alarms are cleared, the yellow alarm LED switches off. If the red LED was on, this
will also be switched off.
Note: To speed up the procedure, you can enter the alarm viewer using the Read key and subsequently
pressing the Clear key. This goes straight to the fault record display. Press the Clear key again to
move straight to the alarm reset prompt, then press the Clear key again to clear all alarms.
Note: Sometimes the term "Setting" is used generically to describe all of the three types
It is more convenient to specify all the settings in a single column, detailing the complete Courier
address for each setting. The above table may therefore be represented as follows:
Setting Column Row Description
SYSTEM DATA 00 00 First Column definition
Language (Row 01) 00 01 First setting within first column
P446/EN/TM/E 5-9
5 Configuration MiCOMho P446
The first three column headers are common throughout the entire Px40 series. However the rows
within each of these column headers may differ according to the product type. Many of the column
headers are the same for all products within the Px40 series. However, there is no guarantee that the
addresses will be the same for a particular column header. Therefore you should always refer to the
product documentation and not make any assumptions
5-10 P446/EN/TM/E
MiCOMho P446 5 Configuration
Update settings
ENTER or CLEAR
10. Press the Enter key to accept the new settings or press the Clear key to discard the new
settings.
Notes: If the menu time-out occurs before the setting changes have been confirmed, the setting values are
also discarded.
Control and support settings are updated immediately after they are entered, without the Update
settings prompt
Control Inputs
The control inputs are user-assignable functions. You can use the CTRL I/P CONFIG column to
configure the control inputs for the hotkey menu. In order to do this, use the first setting Hotkey
Enabled cell to enable or disable any of the 32 control inputs. You can then set each control
input to latched or pulsed and set its command to 'On/Off', 'Set/Reset', 'In/Out', or
'Enabled/Disabled'.
By default, the hotkey is enabled for all 32 control inputs and they are set to "Set/Reset" and are
"Latched".
CB Control
You can open and close the controlled circuit breaker with the direct access key to the right, if
enabled as described above. By default direct access to the circuit breakers is disabled.
The availability of the above three functions is controlled by the Direct Access cell in the
CONFIGURATION column. There are four options: 'Disabled', 'Enabled', 'CB Ctrl only' and 'Hotkey
only'.
For the Setting Group selection and Control inputs, this cell must be set to either 'Enabled' or 'Hotkey
only'.
For CB Control functions, the cell must be set to 'Enabled' or 'CB Ctrl only'.
Hotkey display
In general, the layout of a typical display of the hotkey menu is as follows:
P446/EN/TM/E 5-11
5 Configuration MiCOMho P446
The top line shows the contents of the previous and next cells for easy menu navigation
The centre line shows the function
The bottom line shows the options assigned to the direct access keys
HOTKEY MENU
EXIT
Use the left and right cursor keys to scroll between the other available options, then use the hotkeys to
control the function currently displayed. If neither of the cursor keys is pressed within 20 seconds of
entering a hotkey sub menu, the unit reverts to the default display.
Press Clear key to return to the default menu from any page of the hotkey menu.
Note: More detailed information about the above three functions is available in the Operations chapter.
Plant Reference
MiCOM
HOTKEY CLOSE
To Close the circuit breaker (in this case), press the key directly below CLOSE. You will be given an
option to cancel or confirm
Execute
CB CLOSE
Cancel Confirm
5-12 P446/EN/TM/E
MiCOMho P446 5 Configuration
FUNCTION KEYS
Fn Key Status
0000000000
The next cell down (Fn Key 1) allows you to activate or disable the first function key (1). The Lock
setting allows a function key to be locked. This allows function keys that are set to ‘Toggled’ mode
and their DDB signal active ‘high’, to be locked in their active state, preventing any further key presses
from deactivating the associated function. Locking a function key that is set to the Normal mode
causes the associated DDB signals to be permanently off. This safety feature prevents any
inadvertent function key presses from activating or deactivating critical relay functions
FUNCTION KEYS
Fn Key 1
Unlocked
The next cell down (Fn Key 1 Mode) allows you to set the function key to 'Normal' or 'Toggled'. In the
Toggle mode the function key DDB signal output stays in the set state until a reset command is given,
by activating the function key on the next key press. In the Normal mode, the function key DDB signal
stays energized for as long as the function key is pressed then resets automatically. If required, a
minimum pulse width can be programmed by adding a minimum pulse timer to the function key DDB
output signal.
FUNCTION KEYS
Fn Key 1 Mode
Toggled
The next cell down (Fn Key 1 Label) allows you to change the label of the function. The default label is
"Function key 1" in this case. To change the label you need to press the enter key and then change
the text on the bottom line, character by character. This text is displayed when a function key is
accessed in the function key menu, or it can be displayed in the PSL
FUNCTION KEYS
Fn Key 1 Label
Function Key 1
Subsequent cells allow you to carry out the same procedure as above for the other function keys.
The status of the function keys is stored in battery backed memory. If the auxiliary supply is
interrupted, the status of all the function keys is restored. If the battery is missing or discharged, the
function key DDB signals are set to logic 0 once the auxiliary supply is restored. The IED only
recognizes a single function key press at a time and a minimum key press duration of approximately
200 ms is required before the key press is recognized in PSL. This feature avoids accidental double
presses.
P446/EN/TM/E 5-13
5 Configuration MiCOMho P446
Minimum
1 GHz processor
256 MB RAM
WindowsTM XP
Resolution 800 x 600 (256 colors)
1 GB free hard disk space
Recommended
2 GHz processor
1 GB RAM
WindowsTM XP
Resolution 1024 x 768
5 GB free hard disk space
1. Connect a serial cable between the port on the front panel of the IED and the PC.
2. To start MiCOM S1 Studio, select Programs > MiCOM S1 Studio > MiCOM S1 Studio.
3. Click Quick Connect and select Create a New System.
4. The new system file is placed in a default path in the Path to System field. You can change
this path if desired.
5. Enter the name of the system in the Name field (you can add a brief description of the system
using the Comment field, if required).
6. Click OK.
7. Select the device type Px40 Series
8. Select the communications port Front port, Rear port or Ethernet port.
9. Once connected, select the language for the settings file, the device name, then click Finish.
The configuration is updated.
10. In the Studio Explorer window, select Device > Supervise Device… to control the unit
functions directly.
5-14 P446/EN/TM/E
MiCOMho P446 5 Configuration
1. If creating a new system, in the Studio Explorer, select Create new system.
2. Right click the new system and select New substation.
3. Right-click the new substation and select New voltage level.
4. Right-click the new voltage level and select New bay.
5. Right-click the new bay and select New device.
6. Select a device type from the list, and enter the unit type. Click Next.
7. Enter the full model number and click Next.
8. Select the Language and Model, then click Next.
9. Enter a unique device name, then click Finish.
10. Right-click the Settings folder and select New File. A default file 000 is added.
11. Right-click file 000 and select click Open. You can now edit the settings.
Notes: You can add a device at any level, whether it is a system, substation, voltage or bay.
If the device type you want doesn’t appear in the list, you will have to import a device data model.
Refer to section 3.4 for details.
1. Before running the Data Model Manager, you must close MiCOM S1 Studio.
2. To start the Data Model Manager, select Programs > Alstom Grid > MiCOM S1 Studio >
Data Model Manager.
3. You will be prompted to add data models. A dialog provides a list of locations from where the
data models are to be retrieved.
4. You must now re-start MiCOM S1 Studio to use the new data models.
Note: Each product version has a number of data models, all of which are large, and hence download
times can be lengthy. We recommend that you select only the data models you need in order to
keep download times reasonable.
P446/EN/TM/E 5-15
5 Configuration MiCOMho P446
5-16 P446/EN/TM/E
MiCOMho P446 5 Configuration
9. To change the address values, select View > Enter Manual Editing Mode
10. Enter the required IP configuration and select the green download button:
P446/EN/TM/E 5-17
5 Configuration MiCOMho P446
13. Set the values, save them, and then send the DNP3.0 file to the device
5-18 P446/EN/TM/E
MiCOMho P446 5 Configuration
Note: IP1 and IP2 are different but use the same subnet mask.
Note: In the IED Configurator, ensure that the port type is set to "Copper" (even if redundant fibres
are being used)
P446/EN/TM/E 5-19
5 Configuration MiCOMho P446
Example address
decimal 85 1 + 4 + 16 + 64 = 85
1
2
4
8
16
32
64
Unused
ON
P4389ENb
SW2 Top view
Details of how to access the switches on the REB are provided in the Installation chapter.
Caution This hardware configuration should ideally take place before the unit is
installed. If this is not possible, this must be carried out by authorized
installation engineers.
5-20 P446/EN/TM/E
MiCOMho P446 5 Configuration
Device Identification
1. To configure the REB, go to the main window and click Identify Device.
2. The REB connected to the PC is identified and its details are listed as shown below.
Device address
P446/EN/TM/E 5-21
5 Configuration MiCOMho P446
MAC address
Version number of the firmware
SNTP IP address
Date & time of the real-time clock, from the board.
Note: Due to the time needed to establish the RSTP protocol, it is necessary to wait 25 seconds between
connecting the PC to the IED and clicking the Identify Device button.
IP Address Configuration
1. To change the network address component of the IP address, go to the main window and click
the IP Config button. The Device setup screen appears. The first three octets of the board IP
address can be configured. Note: the last octet is set using the DIP switches (SW2) next to
the ribbon connector.
2. Enter the required board IP address and click OK. The board network address is updated and
displayed in the main window.
Equipment
1. To view the MAC addresses learned by the switch, go to the main window and click the
Identify Device button. The selected device MAC address then appears highlighted.
2. Click the Equipment button. The list of MAC addresses learned by the switch and the
corresponding port number are displayed.
5-22 P446/EN/TM/E
MiCOMho P446 5 Configuration
RSTP Parameters
1. To view or configure the RSTP Bridge Parameters, go to the main window and click the device
address to select the device. The selected device MAC address appears highlighted.
2. Click the RSTP Config button. The RSTP Config screen appears.
3. To view the available parameters in the board that is connected, click the Get RSTP
Parameters button.
P446/EN/TM/E 5-23
5 Configuration MiCOMho P446
4. To set the configurable parameters such as Bridge Max Age, Bridge Hello Time, Bridge
Forward Delay, and Bridge Priority, modify the parameter values and click Set RSTP
Parameters as below:
Default value Minimum value Maximum value
S.No Parameter
(seconds) (seconds) (seconds)
1 Bridge Max Age 20 6 40
2 Bridge Hello Time 2 1 10
3 Bridge Forward Delay 15 4 30
4 Bridge Priority 32768 0 61440
Bridge Parameters
1. To read the RSTP bridge parameters from the board, go to the main window and click the
device address to select the device. The RSTP Config window appears and the default tab is
Bridge Parameters.
2. Click the Get RSTP Parameters button. This displays all the RSTP bridge parameters from
the Ethernet board.
3. To modify the RSTP parameters, enter the values and click Set RSTP Parameters.
4. To restore the default values, click Restore Default and click Set RSTP Parameters.
5. The grayed parameters are read-only and cannot be modified.
Port Parameters
This function is useful if you need to view the parameters of each port.
1. From the main window, click the device address to select the device and the RSTP Config
window appears.
2. Select the Port Parameters tab, then click Get Parameters to read the port parameters.
3. Alternatively, select the port numbers to read the parameters.
5-24 P446/EN/TM/E
MiCOMho P446 5 Configuration
Port States
This is used to see which ports of the board are enabled or disabled.
1. From the main window, click the device address to select the device. The RSTP Config
window appears.
2. Select the Port States tab then click the Get Port States button. This lists the ports of the
Ethernet board. A tick shows they are enabled.
P446/EN/TM/E 5-25
5 Configuration MiCOMho P446
1. Select the CONFIGURATION column and check that the Comms settings cell is set to
Visible.
2. Select the COMMUNICATIONS column.
3. Move to the first cell down (RP1 protocol). This is a non settable cell, which shows the chosen
communication protocol – in this case Courier.
COMMUNICATIONS
RP1 Protocol
Courier
4. Move down to the next cell (RP1 Address). This cell controls the address of the IED. Up to 32
IEDs can be connected to one spur. It is therefore necessary for each IED to have a unique
address so that messages from the master control station are accepted by one IED only.
Courier uses an integer number between 0 and 254 for the IED address. It is important that
no two IEDs have the same address.
COMMUNICATIONS
RP1 Address
255
5. Move down to the next cell (RP1 InactivTimer). This cell controls the inactivity timer. The
inactivity timer controls how long the IED waits without receiving any messages on the rear
port before it reverts to its default state, including revoking any password access that was
enabled. For the rear port this can be set between 1 and 30 minutes.
COMMUNICATIONS
RP1 Inactivtimer
10.00 mins.
6. If the optional fibre optic connectors are fitted, the RP1 PhysicalLink cell is visible. This cell
controls the physical media used for the communication (Copper or Fibre optic).
COMMUNICATIONS
RP1 PhysicalLink
Copper
7. Move down to the next cell (RP1 Card Status). This cell is not settable. It just displays the
status of the chosen physical layer protocol for RP1.
5-26 P446/EN/TM/E
MiCOMho P446 5 Configuration
COMMUNICATIONS
RP1 Card Status
K-Bus OK
8. Move down to the next cell (RP1 Port Config). This cell controls the type of serial connection.
Select between K-Bus or RS485.
COMMUNICATIONS
RP1 Port Config
K-Bus
9. If using EIA(RS)485, the next cell selects the communication mode. The choice is either
IEC 60870 FT1.2 for normal operation with 11-bit modems, or 10-bit no parity. If using K-Bus
this cell will not appear.
COMMUNICATIONS
RP1 Comms Mode
IEC 60870 FT1.2
10. If using EIA(RS)485, the next cell down controls the baud rate. Three baud rates are
supported; 9600, 19200 and 38400. If using K-Bus this cell will not appear as the baud rate is
fixed at 64kbps.
COMMUNICATIONS
RP1 Baud rate
19200
Note: If you modify protection and disturbance recorder settings using an on-line editor such as PAS&T,
you must confirm them. To do this, from the Configuration column select the Save changes cell.
Off-line editors such as MiCOM S1 Studio do not need this action for the setting changes to take
effect.
1. Select the CONFIGURATION column and check that the Comms settings cell is set to
Visible.
2. Select the COMMUNICATIONS column.
3. Move to the first cell down (RP1 protocol). This is a non settable cell, which shows the chosen
communication protocol – in this case DNP3.0.
COMMUNICATIONS
RP1 Protocol
DNP3.0
4. Move down to the next cell (RP1 Address). This cell controls the DNP3.0 address of the IED.
Up to 32 IEDs can be connected to one spur, therefore it is necessary for each IED to have a
unique address so that messages from the master control station are accepted by only one
IED. DNP3.0 uses a decimal number between 1 and 65519 for the IED address. It is
important that no two IEDs have the same address.
P446/EN/TM/E 5-27
5 Configuration MiCOMho P446
COMMUNICATIONS
RP1 Address
1
5. Move down to the next cell (RP1 Baud Rate). This cell controls the baud rate to be used. Six
baud rates are supported by the IED 1200bits/s, 2400bits/s, 4800bits/s, 9600bits/s,
19200bits/s and 38400bits/s. Make sure that the baud rate selected on the IED is the same as
that set on the master station.
COMMUNICATIONS
RP1 Baud rate
9600 bits/s
6. Move down to the next cell (RP1 Parity). This cell controls the parity format used in the data
frames. The parity can be set to be one of None, Odd or Even. Make sure that the parity
format selected on the IED is the same as that set on the master station.
COMMUNICATIONS
RP1 Parity
None
7. If the optional fibre optic connectors are fitted, the RP1 PhysicalLink cell is visible. This cell
controls the physical media used for the communication (Copper or Fibre optic).
COMMUNICATIONS
RP1 PhysicalLink
Copper
8. Move down to the next cell (RP1 Time Sync). This cell sets the time synchronization request
from the master by the IED. It can be set to enabled or disabled. If enabled it allows the
DNP3.0 master to synchronize the time.
COMMUNICATIONS
RP1 Time sync
Enabled
1. Select the CONFIGURATION column and check that the Comms settings cell is set to
Visible.
2. Select the COMMUNICATIONS column.
3. Move to the first cell down (RP1 protocol). This is a non settable cell, which shows the chosen
communication protocol – in this case IEC 60870-5-103.
COMMUNICATIONS
RP1 Protocol
IEC 60870-5-103
4. Move down to the next cell (RP1 Address). This cell controls the IEC 60870-5-103 address of
the IED. Up to 32 IEDs can be connected to one spur. It is therefore necessary for each IED to
5-28 P446/EN/TM/E
MiCOMho P446 5 Configuration
have a unique address so that messages from the master control station are accepted by one
IED only. IEC 60870-5-103 uses an integer number between 0 and 254 for the IED address.
It is important that no two IEDs have the same IEC 60870 5 103 address. The IEC 60870-5-
103 address is then used by the master station to communicate with the IED.
COMMUNICATIONS
RP1 address
162
5. Move down to the next cell (RP1 Baud Rate). This cell controls the baud rate to be used. Two
baud rates are supported by the IED, ‘9600 bits/s’ and ‘19200 bits/s’. Make sure that the baud
rate selected on the IED is the same as that set on the master station.
COMMUNICATIONS
RP1 Baud rate
9600 bits/s
6. Move down to the next cell (RP1 Meas. period). The next cell down controls the period
between IEC 60870-5-103 measurements. The IEC 60870-5-103 protocol allows the IED to
supply measurements at regular intervals. The interval between measurements is controlled
by this cell, and can be set between 1 and 60 seconds.
COMMUNICATIONS
RP1 Meas. Period
30.00 s
7. If the optional fibre optic connectors are fitted, the RP1 PhysicalLink cell is visible. This cell
controls the physical media used for the communication (Copper or Fibre optic).
COMMUNICATIONS
RP1 PhysicalLink
Copper
8. The next cell down can be used for monitor or command blocking.
COMMUNICATIONS
RP1 CS103Blcking
Disabled
9. There are three settings associated with this cell; these are:
Setting: Description:
Disabled No blocking selected.
When the monitor blocking DDB Signal is active high, either by energizing an opto
input or control input, reading of the status information and disturbance records is
Monitor Blocking
not permitted. When in this mode the device returns a “Termination of general
interrogation” message to the master station.
When the command blocking DDB signal is active high, either by energizing an
opto input or control input, all remote commands will be ignored (i.e. CB
Command Blocking
Trip/Close, change setting group etc.). When in this mode the device returns a
“negative acknowledgement of command” message to the master station.
P446/EN/TM/E 5-29
5 Configuration MiCOMho P446
Note: To help the user, some configuration data is available in the IED CONFIGURATOR column,
allowing read-only access to basic configuration data.
5-30 P446/EN/TM/E
MiCOMho P446 5 Configuration
P446/EN/TM/E 5-31
5 Configuration MiCOMho P446
5-32 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
CHAPTER 6
P446/EN/TM/E 6-1
6 Settings and Records MiCOMho P446
6-2 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
1 OVERVIEW
The product is an intelligent electronic device (IED) that must be configured to the system and
application using appropriate settings. The IED is supplied preconfigured with factory default settings,
but you need to set the parameters according to your application. The IED also supplies
measurements of system parameters, which are not settable.
This chapter contains tables and descriptions of all the unit’s settings and measurement parameters.
It consists of the following sections:
1 Overview
2 Settings Descriptions
2.1 Setting Categories
2.2 Menu Structure
2.3 Rationalizing the Unit Configuration
P446/EN/TM/E 6-3
6 Settings and Records MiCOMho P446
6-4 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
2 SETTINGS DESCRIPTIONS
Wit the exception of the Disturbance Recorder, Control and Support settings are stored and used by
the unit immediately after they are entered.
For Protection Group Settings and the Disturbance Recorder, the IED stores the new setting values in
a temporary ‘scratchpad’ memory. Once the new settings have been confirmed, the device activates
all the new settings together. This provides extra security so that several setting changes, made in a
group of protection settings, all take effect at the same time.
Note: Sometimes the term "Setting" is used generically to describe all of the three types
It is more convenient to specify all the settings in a single column, detailing the complete Courier
address for each setting. The above table may therefore be represented as follows:
P446/EN/TM/E 6-5
6 Settings and Records MiCOMho P446
The first three column headers are common throughout the entire Px40 series. However the rows
within each of these column headers may differ according to the product type. Many of the column
headers are the same for all products within the Px40 series. However, there is no guarantee that the
addresses will be the same for a particular column header. Therefore you should always refer to the
product documentation and not make any assumptions
6-6 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-7
6 Settings and Records MiCOMho P446
6-8 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-9
6 Settings and Records MiCOMho P446
6-10 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-11
6 Settings and Records MiCOMho P446
6-12 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-13
6 Settings and Records MiCOMho P446
6-14 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-15
6 Settings and Records MiCOMho P446
6-16 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-17
6 Settings and Records MiCOMho P446
6-18 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
3.3 Measurements 1
The MEASUREMENTS 1 column lets you view the measurement quantities. These may include
various Magnitudes, Phase Angles, RMS values and Frequencies.
MENU TEXT Col Row Default Setting Available Setting
Description
MEASUREMENTS 1 2 0 0
This column contains measurement parameters
IA Magnitude 2 1 0 Not Settable
IA Magnitude
IA Phase Angle 2 2 0 Not Settable
IA Phase Angle
IB Magnitude 2 3 0 Not Settable
IB Magnitude
IB Phase Angle 2 4 0 Not Settable
IB Phase Angle
IC Magnitude 2 5 0 Not Settable
IC Magnitude
IC Phase Angle 2 6 0 Not Settable
IC Phase Angle
IN Derived Mag 2 9 0 Not Settable
IN Derived Mag
IN Derived Angle 2 0A 0 Not Settable
IN Derived Angle
ISEF Magnitude 2 0B 0 Not Settable
ISEF Magnitude
ISEF Angle 2 0C 0 Not Settable
ISEF Angle
I1 Magnitude 2 0D 0 Not Settable
I1 Magnitude
I2 Magnitude 2 0E 0 Not Settable
I2 Magnitude
I0 Magnitude 2 0F 0 Not Settable
I0 Magnitude
IA RMS 2 10 0 Not Settable
IA RMS
IB RMS 2 11 0 Not Settable
IB RMS
P446/EN/TM/E 6-19
6 Settings and Records MiCOMho P446
6-20 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-21
6 Settings and Records MiCOMho P446
3.4 Measurements 2
The MEASUREMENTS 2 column works in a similar manner to the Measurements 1 settings, but may
provide a different choice of measurement settings.
6-22 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-23
6 Settings and Records MiCOMho P446
3.5 Measurements 4
The MEASUREMENTS 4 column works in a similar manner to the Measurements 1 settings, but may
provide a different choice of measurement settings.
6-24 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-25
6 Settings and Records MiCOMho P446
6-26 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-27
6 Settings and Records MiCOMho P446
6-28 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-29
6 Settings and Records MiCOMho P446
6-30 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-31
6 Settings and Records MiCOMho P446
3.9 Configuration
The settings in this column are mainly concerned with switching on or off the protection functions. If a
protection function is enabled, the settings associated with this function will appear in the HMI panel
menu. If it is disabled, the settings associated with that function are not shown in the HMI panel menu.
The CONFIGURATION column is also used to enabling, disabling and activating Protection Setting
Groups and controlling the visibility/invisibility of columns such as Control Inputs in order to simplify the
menu.
MENU TEXT Col Row Default Setting Available Setting
Description
CONFIGURATION 9 0 0
This column contains all the general configuration options
0 = No Operation, 1 = All Settings, 2 = Setting Group 1,
Restore Defaults 9 1 No Operation 3 = Setting Group 2, 4 = Setting Group 3, 5 = Setting
Group 4
Setting to restore a setting group to factory default settings.
To restore the default values to the settings in any Group settings, set the ‘restore defaults’ cell to the relevant Group number. Alternatively it is possible to
set the ‘restore defaults’ cell to ‘all settings’ to restore the default values to all of the IED’s settings, not just the Group settings.
The default settings will initially be placed in the scratchpad and will only be used by the IED after they have been confirmed by the user.
Note: Restoring defaults to all settings includes the rear communication port settings, which may result in communication via the rear port being disrupted if
the new (default) settings do not match those of the master station.
Setting Group 9 2 Select via Menu 0 = Select via Menu or 1 = Select via PSL
Allows setting group changes to be initiated via Opto Input or via Menu
6-32 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-33
6 Settings and Records MiCOMho P446
6-34 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
Note: When you select 'restore defaults to all settings', this includes the rear communication port settings.
This will result disrupt communication via the rear port if the new (default) settings do not match
those of the master station.
P446/EN/TM/E 6-35
6 Settings and Records MiCOMho P446
6-36 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-37
6 Settings and Records MiCOMho P446
6-38 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-39
6 Settings and Records MiCOMho P446
6-40 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-41
6 Settings and Records MiCOMho P446
6-42 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-43
6 Settings and Records MiCOMho P446
6-44 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-45
6 Settings and Records MiCOMho P446
6-46 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-47
6 Settings and Records MiCOMho P446
6-48 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-49
6 Settings and Records MiCOMho P446
6-50 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-51
6 Settings and Records MiCOMho P446
6-52 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-53
6 Settings and Records MiCOMho P446
6-54 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-55
6 Settings and Records MiCOMho P446
6-56 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-57
6 Settings and Records MiCOMho P446
6-58 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-59
6 Settings and Records MiCOMho P446
6-60 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-61
6 Settings and Records MiCOMho P446
6-62 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-63
6 Settings and Records MiCOMho P446
6-64 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-65
6 Settings and Records MiCOMho P446
6-66 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-67
6 Settings and Records MiCOMho P446
6-68 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-69
6 Settings and Records MiCOMho P446
6-70 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-71
6 Settings and Records MiCOMho P446
6-72 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
Fn Key Status 17 1 0
Displays the status of each function key.
Fn Key 1 17 2 Unlocked 0 = Disabled, 1 = Unlocked (Enabled), 2 = Locked
Setting to activate function key. The ‘Lock’ setting allows a function key output that is set to toggle mode to be locked in its current active state.
P446/EN/TM/E 6-73
6 Settings and Records MiCOMho P446
6-74 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-75
6 Settings and Records MiCOMho P446
6-76 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-77
6 Settings and Records MiCOMho P446
6-78 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-79
6 Settings and Records MiCOMho P446
6-80 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-81
6 Settings and Records MiCOMho P446
6-82 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-83
6 Settings and Records MiCOMho P446
6-84 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-85
6 Settings and Records MiCOMho P446
6-86 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
The above columns are also applicable to Settings Groups 2, 3 and 4 but with the addresses as
follows:
P446/EN/TM/E 6-87
6 Settings and Records MiCOMho P446
6-88 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-89
6 Settings and Records MiCOMho P446
6-90 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-91
6 Settings and Records MiCOMho P446
6-92 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-93
6 Settings and Records MiCOMho P446
6-94 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-95
6 Settings and Records MiCOMho P446
6-96 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-97
6 Settings and Records MiCOMho P446
• Set operating mode and associated timers for each distance zone when distance operates in
the basic scheme
• Select aided schemes via one or two available signalling channels
• Define operating zones during Trip On Close (TOC)
6-98 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-99
6 Settings and Records MiCOMho P446
6-100 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-101
6 Settings and Records MiCOMho P446
6-102 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-103
6 Settings and Records MiCOMho P446
6-104 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-105
6 Settings and Records MiCOMho P446
6-106 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-107
6 Settings and Records MiCOMho P446
6-108 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-109
6 Settings and Records MiCOMho P446
Note: As this configuration merely assigns pick-up at the local end only, they need to be further configured
to a selected Aided channel scheme under GROUP 1 SCHEME LOGIC to provide unit protection.
6-110 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-111
6 Settings and Records MiCOMho P446
6-112 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-113
6 Settings and Records MiCOMho P446
6-114 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-115
6 Settings and Records MiCOMho P446
6-116 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-117
6 Settings and Records MiCOMho P446
6-118 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-119
6 Settings and Records MiCOMho P446
6-120 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-121
6 Settings and Records MiCOMho P446
6-122 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
4.17 Supervision
The GROUP 1 SUPERVISION column is used to set the parameters for the Supervision functions.
The Supervision column includes Voltage Transformer Supervision (VTS), Current Transformer
Supervision (CTS), Inrush Detection and special Weak Infeed Blocking.
P446/EN/TM/E 6-123
6 Settings and Records MiCOMho P446
6-124 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-125
6 Settings and Records MiCOMho P446
6-126 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-127
6 Settings and Records MiCOMho P446
6-128 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-129
6 Settings and Records MiCOMho P446
6-130 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-131
6 Settings and Records MiCOMho P446
6-132 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-133
6 Settings and Records MiCOMho P446
6-134 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-135
6 Settings and Records MiCOMho P446
6-136 P446/EN/TM/E
MiCOMho P446 6 Settings and Records
P446/EN/TM/E 6-137
6 Settings and Records MiCOMho P446
6-138 P446/EN/TM/E
MiCOMho P446 7 Operation
OPERATION
CHAPTER 7
P446/EN/TM/E 7-1
7 Operation MiCOMho P446
7-2 P446/EN/TM/E
MiCOMho P446 7 Operation
1 OVERVIEW
This chapter explains the principles of the IED’s individual protection functions. It
consists of the following sections:
1 Overview
2 Setting Groups
2.1 Setting groups selection
3 Line Parameters
3.1 Tripping mode - selection of single- or three-pole tripping
3.2 Residual compensation for earth faults
3.3 Mutual compensation for parallel lines
4 Distance Protection
4.1 Distance protection introduction
4.2 Phase selection
4.2.1 Theory of operation
4.2.2 Cross-country override logic
4.3 Biased neutral current detector
4.4 Measuring zones – theory of operation
4.4.1 Mho characteristic
4.4.1.1 Phase elements
4.4.1.2 Ground elements
4.4.1.3 Memory- or cross-polarisation
4.4.2 Quadrilateral characteristic
4.4.2.1 Phase elements
4.4.2.2 Ground elements
4.5 Distance elements zone settings
4.5.1 Directionality – Delta and Conventional
4.5.2 Phase fault zone settings
4.5.3 Ground fault zone settings
4.5.4 Distance zone sensitivities
4.6 Conventional voltage transformer and capacitor VT applications
4.6.1 CVTs with passive suppression of ferroresonance
4.6.2 CVTs with active suppression of ferroresonance
4.7 Load blinding (load avoidance)
4.8 Distance elements basic scheme setting
10 Broken Conductor
10.1 Broken conductor detection
11 Earth Fault
11.1 Earth fault, Sensitive Earth Fault (SEF) and Restricted Earth
Fault (REF) protection
11.1.1 IDG curve
11.2 Directional earth fault protection
11.2.1 Residual voltage polarization
11.2.2 Negative sequence polarization (Not for SEF)
12 Aided DEF
12.1 Directional function - setup of DEF and directional comparison
elements
12.1.1 DEF zero sequence polarization with virtual current polarizing
12.1.2 DEF negative sequence polarization
17 Voltage Protection
17.1 Undervoltage protection
17.2 Overvoltage protection
17.2.1 Compensated overvoltage
18 Frequency Protection
18.1 Frequency protection
18.2 Independent rate of change of frequency protection [81R]
18.2.1 Basic functionality
P446/EN/TM/E 7-5
7 Operation MiCOMho P446
21 System Checks
21.1 System voltage checks
21.1.1 System checks overview
21.1.2 System voltage checks logic diagrams
21.1.3 System voltage checks VT selection
21.1.4 System voltage synchronism checks
21.1.4.1 Slip control by timer
21.1.4.2 Check sync. 2
21.1.4.3 Predictive closure of circuit breaker
21.1.4.4 Voltage and phase angle correction
23 Measurements
23.1 Fault locator
23.1.1 Basic theory for ground faults
23.1.2 Data acquisition and buffer processing
23.1.3 Faulted phase selection
23.1.4 The fault location calculation
23.1.5 Obtaining the vectors
23.1.6 Solving the equation for the fault location
23.1.7 Mutual compensation
24 Communications Settings
24.1 Read Only mode
24.1.1 IEC 60870-5-103 protocol on rear port 1
24.1.2 Courier protocol on rear port 1 or 2 and Ethernet
24.1.3 IEC 61850
24.1.4 Courier database support
24.1.5 New DDB signals
P446/EN/TM/E 7-7
7 Operation MiCOMho P446
7-8 P446/EN/TM/E
MiCOMho P446 7 Operation
2 SETTING GROUPS
There are four groups of protection settings, each group contains the same setting cells.
This allows four different sets of settings and PSL configurations. Only one group of
protection settings can be selected as the active group. The active group is the group
currently used by all protection elements. GROUP 1 is the default active group.
Note: Each setting group has its own PSL. Once a PSL has been designed it can be sent to
any one of 4 setting groups in the IED. When downloading a PSL to the IED, enter
the setting group to which it will be sent. This is also the case when extracting a PSL
from the IED.
P446/EN/TM/E 7-9
7 Operation MiCOMho P446
3 LINE PARAMETERS
VA
Z F1
I A k ZN I N
where
I N is the residual current (derived from phase currents),
I N I A I B IC Equation 1
Z L 0 Z L1
k ZN Equation 2
3Z L1
where
Z L1 is the total positive sequence impedance of the line (a complex value),
Z L 0 is total zero sequence impedance of the line (a complex value).
The complex residual compensation coefficient is defined by two settings: kZN Res
Comp (the absolute value) and kZN Res Angle (the angle in degrees).
Caution: The kZN Res Angle is different to previous LFZP, SHNB, and LFZR IEDs:
When importing settings from these older products, subtract angle Z L1 .
If the ratio I M I N is less than the Mutual Cut Off setting, the mutual
compensation is applied to all distance zones and the fault locator.
If the ratio I M I N is greater than the Mutual Cut Off setting, no mutual
compensation is applied.
P446/EN/TM/E 7-11
7 Operation MiCOMho P446
4 DISTANCE PROTECTION
The phase selector needs to identify the faulted phases and ensure that only the
correct distance measuring zones can issue a trip. Possible phase selections are
AN, BN, CN, AB, BC, CA, ABC. For double phase to ground faults, the selection is
AB, BC or CA, with N (neutral) for indication only.
For the selected phase-to-ground elements the phase and the neutral currents
must exceed the minimum sensitivity threshold. For the selected phase-to-phase
elements the loop current must exceed the minimum sensitivity threshold. The
biased neutral current detector should be picked up for any ground fault distance
element to operate.
The faulted phase impedance must appear within a tripping (measuring) zone,
corresponding to the phase selection. Five independent protection zones are
provided. The tripping zones are mho circles or quadrilateral and are selected
independently for phase-to-phase and phase-to-ground faults. The ground fault
distance elements always uses residual compensation and mutual compensation if
one is enabled (see sections 3.2 and 3.3).
For directional zones, the directionality element (see section 4.5.1) must agree with
the tripping zone. Zones 1, 2, 4 are always directional whereas Zone P and 3 are
only directional if set as directional. In directional zones the directionality element
must agree with the tripping zone. For example, Zone 1 is a forward directional
zone and must not trip for reverse faults. Therefore a Zone 1 trip is only allowed if
the directionality element issues a forward decision. Zone 4 is reverse-looking so
needs a reverse decision by the directionality element.
The set time delay for the measuring zone must expire, with the fault impedance
measured inside the zone characteristic for the duration. Typically, Zone 1 has no
time delay (instantaneous), all other zones have time delays. Where channel-
aided distance schemes are used, the time delay tZ2 for overreaching Zone 2 may
be bypassed under certain conditions.
To achieve fast, sub-cycle operation, the phase selection, measuring zones and
directionality algorithms run in parallel, with their outputs combined with an AND-gate.
This helps to avoid sequential measurement which would slow the operation of the
protection.
7-12 P446/EN/TM/E
MiCOMho P446 7 Operation
Note: Zone 1 can be extended to Zone 1X when required in zone 1 extension schemes.
Line Angle
+jX
Z3
(offset)
ZP
(forward)
Z2
Z1 Forward
+R
Reverse Directionality
(simplified)
Z4
P4900ENa
P446/EN/TM/E 7-13
7 Operation MiCOMho P446
Line Angle
+jX
Z3 (offset)
ZP (forward)
Z2
Z1
Forward
+R
Reverse
Directionality
(simplified)
Z4
P4901ENa
Note: Any existing trip decision is not reset under this condition. After the first cycle
following a selection, the phase selector is only permitted to change to a selection
involving additional phases.
On double phase to ground faults, only appropriate phase-phase elements are enabled.
This is because they are generally more accurate under these conditions than ground
elements. A biased neutral current level detector operates to indicate the involvement of
ground.
7-14 P446/EN/TM/E
MiCOMho P446 7 Operation
No
Change!
AB
Change!
BC
Change!
CA
Ground Fault,
P1134ENa P1179ENa
1 Cycle 1 Cycle Phase C
Comparison Comparison
P446/EN/TM/E 7-15
7 Operation MiCOMho P446
The cross-country override logic applies when the IED makes a multiple phase selection
(more than one phase is involved in the fault) and exactly one Zone 1 ground element
picks up, with no other ground elements. Only on-angle operation of the Zone 1 ground
element can activate the cross-country logic, which prevents incorrect operation due to
impedance encroachment.
The cross-country logic also only allows Zone 1 ground elements to operate for one of
the phases that were selected previously. For example, if the original phase selection
was A and B phases, it would only allow the override for Zone 1 AN or BN elements.
I N I A I B IC
Neutral current
K 10%
I BIAS max I A I B , I B I C , I C I A
The neutral current detector uses maximum of three phase current differences as a
biasing value. The slope of the characteristic is fixed at 10%.
Biasing the neutral current detector has distinct advantages. The detector is sensitive
enough to operate for any single-phase fault, without the risk of picking up on neutral spill
current during phase-to-phase faults. The neutral spill current might arise from
mismatched current transformers or CT saturation.
The biasing also ensures that the ground distance elements are generally disabled for
double-phase-to-ground faults with high resistance in the neutral. Such faults can occur in
resistively grounded systems, or in solidly grounded systems due to high arc resistance.
Given that these conditions are very similar to pure phase-to-phase faults, the ground
distance elements can exhibit high measuring errors.
7-16 P446/EN/TM/E
MiCOMho P446 7 Operation
Note: The directional self-polarised mho characteristic is not used in the IED because it is
unable to operate for close-up zero voltage faults. The IED always uses partial
memory or cross-polarisation, see section 4.4.1.3. The self-polarised characteristic is
described here to show the concept of the mho angle comparators and
impedance/voltage domains for phase distance elements.
jX
V IZ
V IZ
Z
IZ
R I
V I
The above condition can be converted into the voltage domain by multiplying all
parameters by the distance protection current I , see Figure 5.
S2 V I Z . Equation 8
P446/EN/TM/E 7-17
7 Operation MiCOMho P446
Operation occurs when the angle between the signals is greater than 90°:
90 S1 S 2 90 . Equation 9
jX
V IZ V IZ
Z
IZ
V I
V
V I Z V I Z
R I
Z I Z
where
Z is the forward impedance reach setting,
Z is the reverse impedance reach setting.
Note: The directional self-polarised mho characteristic is not actually used in the IED
because it is unable to operate for close-up zero voltage faults. The IED always uses
partial memory- or cross-polarisation, see section 4.4.1.3. The self-polarised
characteristic is described to show the concept of the mho angle comparator and Z1 /
ZLP -plane representations in the context of the ground distance elements.
7-18 P446/EN/TM/E
MiCOMho P446 7 Operation
representation is often more convenient, especially if an injection test kit is used which
can not apply the residual compensation to the impedance plot.
Directional mho
Z LP -plane
Z1 -plane jX Z k ZN I N I ph
jX
V ph I ph Z replica
V IZ
Z Z
Z replica
90°
90°
R R
V I V ph I ph
P4905ENa
I is the distance protection current (i.e. I I A kZN I N for A-N fault, see section 3.2,
or I I A kZN I N kZm I M if the mutual compensation is enabled, see section 3.3),
S2 V ph I ph Z 1 kZN I N I ph .
Z replica Z 1 kZN I N I ph
or, if the mutual compensation is enabled,
Z replica Z 1 kZN I N I ph kZm I M I ph .
where
kZN is the residual compensation coefficient,
I N is the residual current (derived),
k Zm is the mutual compensation coefficient,
I M is the residual current of the parallel line,
V ph is the faulty phase voltage ( VA for AN fault),
If healthy phase currents are much less then the current of the faulty phase and the
mutual compensation is disabled,
I N I ph (faulty phase current) and Z replica Z 1 k ZN
jX Z1 -plane
V IZ
Z
90°
V I
V I Z
R
Z
P4906ENa
Where:
Z is the forward impedance reach setting,
Z is the reverse impedance reach setting,
V is the distance protection voltage (i.e. V VA for AN fault),
I is the distance protection current ( I I A kZN I N for A-N fault),
7-20 P446/EN/TM/E
MiCOMho P446 7 Operation
Z LP -plane
jX Z k ZN I N I ph
V ph I ph Z replica
Z Z replica
90°
I ph
V ph
Z replica R
Z
V ph I ph Z replica
Z k ZN I N I ph
P4907ENa
Z replica Z 1 kZN I N I ph ,
where Z replica - replica reverse reach,
Z replica
Z 1 kZN I N I ph .
Note that if the healthy phase currents are much less then the current of the faulty phase,
then I N I ph (faulty phase current) and Z replica Z 1 k ZN , Z replica
Z 1 k ZN .
P446/EN/TM/E 7-21
7 Operation MiCOMho P446
voltage faults, where there would be no polarising voltage. To ensure correct mho
element response for zero-voltage faults the IED adds a percentage of voltage from the
memory to the main polarising voltage as a substitute phase reference.
This technique is called memory-polarising and it has the advantage of preserving and
enhancing the directional properties of the mho characteristic.
The IED does not allow directional mho characteristics to be purely self polarized or
purely memory polarized. The polarising voltage always contains the directly measured
self-polarized voltage, onto which a percentage of the prefault memory voltage is added.
The setting Dist. Polarising ( p ) defines the proportion between self-polarising voltage
V (i.e. V AB for AB fault or VA for AN fault) and memory-polarising voltage Vmem (the
prefault value of the same voltage). This percentage of additional memory can be set
from 0.2 (20%) to 5 (500%).
S1 V p Vmem .
If p 1 the characteristic is 50%-self and 50%-memory polarised. If p 5 the
characteristic is 16.7%-self and 83.3%-memory polarised.
The memory algorithm works as follows:
The cross-polarisation voltage is generated using a phase or phases not otherwise used
for the particular Distance or Directional measurement. While one pole is dead, and the
memory is not available, the elements associated with the remaining phases are
polarised as shown in Table 2 and the remaining elements are disabled.
The following table shows the Vmem calculations for each loop under various operating
conditions:
Cross (memory Cross (memory Cross (memory
Loop Memory Valid invalid, no poles invalid, lagging invalid, leading
dead) pole dead) pole dead)
7-22 P446/EN/TM/E
MiCOMho P446 7 Operation
In the table, and 2 denote phase rotation of 120° and 240° respectively, while e j 90
denotes phase rotation of -90°. The values of a and a 2 are interchanged when reverse
phase rotation (ACB) is selected, to provide the correct cross polarising voltages and
negative sequence volts and current. If voltage transformer is at the line side and the
memory is invalid, phase-to-phase elements are self-polarised during single pole dead
condition.
The IED does not operate the distance elements if the polarising signal magnitude is less
than 1V, except for Zone 1 following breaker closure, which is allowed to operate as a
Mho characteristic with a reverse offset of 25%. This ensures operation when closing on
to a close-up three phase fault (SOTF/TOR condition). Also Z4 reverse operation is held
if it operates while memory is valid. Other zones may have their zone time delays
bypassed for SOTF/TOR condition, as detailed in the application notes.
One of the additional benefits of adding memory into the polarizing mix is that mho
characteristics offer dynamic expansion in the event of a forward fault, therefore covering
greater fault arc resistance.
The memory voltage Vmem is a pre-fault voltage, and the pre-fault voltage at the relaying
point is equal to the source voltage (assuming the pre-fault current is zero):
Vmem VS
P446/EN/TM/E 7-23
7 Operation MiCOMho P446
IED
Dist
VS Bus I
Line
ZS ZF
V
P4908ENa
Z S V I Z 90
p
90 V I
1 p
jX
V IZ
Z
V I
R
p
ZS p
1 p V I ZS
1 p
For the phase-to-ground loops, Figure 11 shows the impedance characteristic in the Z1 -
plane.
I VS
ZF ZL ZS
V
7-24 P446/EN/TM/E
MiCOMho P446 7 Operation
VS V I ( Z S Z L )
( Z S Z L ) V I Z 90
p
90 V I
1 p
p
V I (ZS ZL )
1 p
jX
90°
V IZ
p
(Z S Z L )
1 p
V I
R
Self-polarised
P4911ENa
For the phase-to-ground loops, Figure 13 shows the impedance characteristic in the Z1 -
plane.
From Figure 11 and Figure 13 the mho-expansion and mho-contraction is defined as
follows:
For forward faults:
p
MhoExpansion ZS
1 p
where Z S is the impedance of the source behind the relaying point.
Using the source and line impedances is a simple way of representing the mho-
expansion and mho-contraction on the impedance plot. The IED does not calculate Z S
or Z S Z L internally, it only deals with the signals S1 and S 2 provided to mho-
comparators. In some cases the source and line impedances in Figure 11 and Figure 13
are different to their actual values used in various power system studies. This is mainly
P446/EN/TM/E 7-25
7 Operation MiCOMho P446
due to pre-fault current and the residual compensation for phase-to-ground loops. To plot
an accurate impedance characteristic, calculate the values of Z S or Z S Z L as follows:
Directional quadrilateral
This characteristic is used for Zones 1, 2, 3 (optionally reversed), P (optionally reversed),
and 4 (reversed).
+jX
Top reactance line
0.25 R R
Forward
+R
Reverse Directionality
0.25 Z (simplified)
The directional quadrilateral is formed from two parallel reactance lines, two parallel
resistive reach blinders, and is controlled by the delta or conventional directional line.
The bottom reactance line and the left hand reach blinder are automatically set to 25% of
the reactance reach and the right hand blinder respectively. The reactance line is
arranged to operate for faults below the line, the blinders for faults within the resistive
reach limits and the delta directional line for forward faults. The counter increments when
all of these conditions are satisfied.
Offset quadrilateral
This characteristic is used for Zone 3, Zone P when the offset is enabled.
7-26 P446/EN/TM/E
MiCOMho P446 7 Operation
R R
Z
The offset quadrilateral is formed from two reactance lines and two resistive reach
blinders. The upper reactance line is arranged to operate for faults below it and the lower
for faults above it. The right hand blinder is arranged to operate for faults to its left and
the left hand blinder for faults to its right.
Note: When Zone 3 or Zone P is set to offset in the Simple setting mode, the left hand
blinder and lower reactance line equal the offset percentage setting of the line
impedance and fault resistance respectively. In the advanced setting mode, both
lines can be set independently.
+jX
V IZ
Z V I
+R
P4914ENa
P446/EN/TM/E 7-27
7 Operation MiCOMho P446
For all V I vectors below the top reactance line the following condition is true:
V I Z .
The same condition in the voltage domain is:
V I Z I e j ,
S 2 I e j .
The impedance below the top reactance line is detected when the angle between the
signals is less than 0°:
S1 S 2 0 .
Z V I
3
V I Z
For an offset zone Z is a settable reverse reach . For a directional zone Z is 25% of
the forward reach Z :
Z 0.25 Z
The signals provided to the comparator are:
S1 V I Z ,
S2 I e j 3 ,
7-28 P446/EN/TM/E
MiCOMho P446 7 Operation
The impedance above the bottom reactance line is detected when the angle between the
signals is greater than 0°:
S1 S 2 0 .
+jX
V I
V IR
R Z +R
P4916ENa
For all V I vectors which are on the left side of the right blinder the following condition is
true:
V I R Z .
The same condition in the voltage domain is:
V I R I Z ,
The conversion from the impedance domain into the voltage domain is done in the same
way as for the Mho characteristic, see Figure 5.
Finally, the two signals provided to the comparator are:
S1 V I R ,
S2 I Z .
The impedance on the left side of the right hand resistive line is detected when the angle
between the signals is greater than 0°:
S1 S 2 0 .
P446/EN/TM/E 7-29
7 Operation MiCOMho P446
IED
Dist V I Half of the loop
Bus
A
ZF
R LP B
Network Line
P4917ENa
Since any phase-to-phase distance element measures half of the loop, the right-hand
resistive reach R of the characteristic shown in Figure 18 is equal to half of the setting:
1
R Rx Ph. Resistive
2
+jX
Z
V I
V I R +R
R
P4918ENa
For an offset zone R is a settable reverse resistive reach …. For a directional zone R
is 25% of the forward resistive reach R :
R 0.25 R .
The two signals provided to the comparator are:
S1 V I R ,
S2 I Z .
The impedance on the right side of the left hand resistive line is detected when the angle
between the signals is less than 0°:
7-30 P446/EN/TM/E
MiCOMho P446 7 Operation
S1 S 2 0 .
+jX
Z
V I
R R +R
Z
3
P4919ENa
Comparators:
Reverse Zone
Line S1 S2 Condition
Parameters
Parameter Forward or Reverse Zone Offset Zone
Zx Ph. Reach Zx Ph. Reach
Z
Zx Ph. Angle Zx Ph. Angle
P446/EN/TM/E 7-31
7 Operation MiCOMho P446
I fault I
fault e j ,
I I
The distance protection can not measure the fault current directly because of the
unknown infeed from the remote end. Therefore one of two methods is used to estimate
the angle of I fault :
6. The “fixed” tilting, when the angle of I fault is assumed to be close to the angle of
I ph (the local phase current):
I fault I ph
I
7. The “dynamic” tilting, when the angle of fault is assumed to be close to the angle
of I 2 (the local negative sequence current):
I fault I 2
For both fixed and dynamic tilting the validity of current polarisation is controlled by the
following condition:
I 2 I ph 45 .
If this condition is not fulfilled, assumptions () and () are possibly too far from reality and
the current polarisation is considered invalid. Since the quad characteristic can
significantly over- or under-reach under such conditions, the IED automatically switches
from quad to mho characteristics to provide better stability.
FIXED TILTING (the setting Zx Dynamic Tilt is disabled):
7-32 P446/EN/TM/E
MiCOMho P446 7 Operation
Z1-plane
Iph j
+jX e
I
V IZ
Z V I
+R
P4920ENa
For all V I vectors below the top reactance line, the following condition is true:
I ph j
V I Z e .
I
The same condition in the voltage domain is:
V I Z ( I ph e j )
S 2 I ph e j ,
Z replica Z 1 kZN I N I ph ,
The impedance below the top reactance line is detected when the angle between the
signals is less than 0°:
S1 S 2 0 .
If the mutual compensation is enabled, then
Z replica Z 1 k ZN I N I ph k Zm I M I ph .
The following figure shows the Z LP -plane representation of the characteristic:
P446/EN/TM/E 7-33
7 Operation MiCOMho P446
Z LP -plane
+jX Z k ZN I N I ph V ph I ph Z replica
Z replica
Z
V ph I ph
+R
P4921ENa
8. The top line tilting angle in Z LP -plane characteristic is fixed at setting (Zx Tilt
Top Line).
9. The top line tilting angle in Z1 -plane characteristic is defined as follows:
I ph I ph
TiltAngle
I ph k ZN I N
I
If the healthy phase currents are much less than the current of the faulty phase, then
I N I ph . The tilting angle in this case is fixed at the following value:
1
TiltAngle
1 k ZN
If the mutual compensation is enabled, the tilting angle is:
I ph
TiltAngle
I ph k ZN I N k ZM I M
Z replica Z 1 k ZN .
7-34 P446/EN/TM/E
MiCOMho P446 7 Operation
+jX Z LP -plane
Z replica
V ph I ph
RLP RLP
+R
3
ica
Z repl
P4922ENa
Comparators:
Forward or Offset Zone
Line S1 S2 Condition
Bottom Line
V ph I ph Z replica I ph e j 3 S1 S 2 0
Left Line
V ph I ph RLP I ph Z replica S1 S 2 0
Reverse Zone
Line S1 S2 Condition
Bottom Line
V ph I ph Z replica I ph e j 3 S1 S 2 0
Left Line
V ph I ph RLP I ph Z replica S1 S 2 0
P446/EN/TM/E 7-35
7 Operation MiCOMho P446
Z replica Z 1 k ZN I N I ph k Zm I M I ph ,
Z replica Z 1 k ZN I N I ph k Zm I M I ph
Parameters
Parameter Forward or Reverse Zone Offset Zone
Zx Gnd. Reach Zx Gnd. Reach
Z
Zx Gnd. Angle Zx Gnd. Angle
0.25 * Zx Gnd. Reach Zx' Gnd Rev Rch
Z
Zx Gnd. Angle + 180° Zx Gnd. Angle + 180°
Rx Gnd Resistive Rx Gnd Resistive
RLP
0° 0°
0.25 * Rx Gnd Resistive Rx' Gnd Res. Rev
RLP
180° 180°
Zx Tilt Top Line Zx Tilt Top Line
+jX Z1 -plane
( I ph I )
Z
V I
R
+R
Z R
( I ph I ) 3
P4923ENa
I ph I ph
R RLP , R RLP
I I
I I ph k ZN I N
If the healthy phase currents are much less than the current of the faulty phase and the
mutual compensation is disabled, then I N I ph (the faulty phase current) and the
characteristic in the Z1 -plane is simplified:
7-36 P446/EN/TM/E
MiCOMho P446 7 Operation
+jX Z1 -plane
1
1 k ZN
Z
1
RLP
1 k ZN 1
RLP
1 k ZN
Rreach Rreach +R
Z
1
3
1 k ZN
P4924ENa
1
where is the angle of :
1 k ZN
1
.
1 k ZN
Example:
k ZN 0.58 e j 6 , Z 84
1
j 6
2 .2
1 0.58 e
sin Z sin 84 2.2
1.0033 Equation 10
sin Z sin 84
RLP
Rreach 1.0033
1 k ZN
RLP
Rreach 1.0033
1 k ZN
In typical cases the sine ratio coefficient (Equation 10) is close to unity so the simplified
equations can be used:
RLP
Rreach
1 k ZN
P446/EN/TM/E 7-37
7 Operation MiCOMho P446
RLP
Rreach
1 k ZN
DYNAMIC TILTING (the setting Zx Dynamic Tilt is enabled):
When the user selects the Dynamic tilting, the top line of the ground distance
quadrilateral characteristic in Z1 -plane tilts for the angle difference between the negative
sequence current and the distance protection current plus the user-settable angle (default
angle is -3°):
I
TiltAngle 2
I
The default starting (initial) tilt angle of -3° is introduced to reduce the possibility of
overreach caused by any small differences between the negative sequence source
impedances, and general CT/VT angle tolerances.
Negative sequence current is used as a reference for ground faults since it provides a
better estimate of the current in the fault than either the faulted phase current or zero
sequence current (used in previous models). Therefore the reactance line follows the
fault resistance impedance and tilts up or down, starting from the set initial tilt angle to
avoid underreach or overreach.
The following additional constraints also exist to ensure the top/bottom line does not tilt
too far:
The Zone 1 reactance top line can only dynamically tilt down to ensure that Zone 1
does not overreach. This maintains grading/selectivity with downstream protection.
The Zones 1X, 2, 3, P, 4 reactance top lines can only dynamically tilt up to ensure
that these zones do not underreach. This is particularly important for Zone 2 or
other zones used to key channel-aided distance schemes.
The reactance bottom line for all zones can only dynamically tilt down.
If any circuit breaker pole is open, the internal pole dead logic is used. The Dynamic
Tilting is disabled automatically and the IED uses the Fixed Tilting algorithm.
The IED uses the following algorithm for dynamic tilting:
11. If the angle between I 2 and I ph is more than 45°, the quadrilateral
characteristics are disabled and the mho characteristics are used instead.
12. The leading and lagging polarising currents are detected based on phase
relations between I 2 and I ph :
I LEAD I ph I ph I LEAD I 2
I LAG I 2 I LAG I ph
I2
I ph
I2
Figure 27: Phase relations between I 2 and I ph for lead and lag polarising currents
13. The comparators used for Zone 1 top and bottom lines are:
7-38 P446/EN/TM/E
MiCOMho P446 7 Operation
Line S1 S2 Condition
Bottom Line
V ph I ph Z replica I LAG e j 3 S1 S 2 0
If the lagging current I LAG is equal to the negative sequence current I 2 , the top and
bottom lines are dynamically tilted down.
If the lagging current I LAG is equal to the phase fault current I ph , the characteristic is the
same as for the Fixed Tilt.
14. The comparators used for Zones 1X, 2, 3, P, 4, top and bottom lines are:
Forward or Offset Zone
Line S1 S2 Condition
Bottom Line
V ph I ph Z replica I LAG e j 3 S1 S 2 0
Reverse Zone
Line S1 S2 Condition
Bottom Line
V ph I ph Z replica I LAG e j 3 S1 S 2 0
Possible cases:
If the leading current I LEAD is equal to the negative sequence current I 2 , the top lines
are dynamically tilted up.
If the leading current I LEAD is equal to the phase fault current I ph , the top lines are the
same as for the Fixed Tilt.
If the lagging current I LAG is equal to the negative sequence current I 2 , the bottom lines
are dynamically tilted down.
If the lagging current I LAG is equal to the phase fault current I ph , the bottom lines are
the same as for the Fixed Tilt.
15. The left and right resistive reach lines are the same as for the Fixed Tilting.
If the dynamic tilting by the negative sequence current I 2 is used for both top and bottom
lines, the characteristic in the Z LP -plane is as follows (Zone 1 example):
P446/EN/TM/E 7-39
7 Operation MiCOMho P446
+jX Z LP -plane
( I 2 I ph )
Z replica
V ph I ph
+R
Z replica
( I 2 I ph ) 3
P4926ENa
+jX Z1 -plane
(I2 I )
Z
V I
+R
Z
( I 2 I ) 3
P4927ENa
7-40 P446/EN/TM/E
MiCOMho P446 7 Operation
Note: Distance zones are directionalized (where applicable) by a delta directional decision.
The characteristic angle for this decision is set along with the Delta Directional
configuration, in the GROUP x DISTANCE SETUP menu column. The default setting
is 60o.
S 2 I e j 60 .
A forward fault is detected if the following condition is true:
90 S1 S 2 90 .
The RCA (Relay Characteristic Angle) of the Conventional Directional element is fixed at
60°.
By factory defaults, the top line of quadrilateral characteristics is not fixed as a horizontal
reactance line. To account for phase angle tolerances in the line CT, VT and IED, the
line is tilted downwards at a droop of -3o. This tilt down helps to prevent zone 1
overreach.
In Advanced setting mode, the top line tilt is settable.
The current sensitivity setting for each zone is used to set the minimum current that must
flow in each of the faulted phases before a trip can occur. For example, if a phase A-B
line fault is present, the IED must measure both currents Ia and Ib above the minimum
set sensitivity.
The default setting is 7.5% In for Zones 1 and 2, 5% In for other zones, ensuring that
distance element operation is not constrained, right through to an SIR ratio of 60.
P446/EN/TM/E 7-41
7 Operation MiCOMho P446
The top line of ground quadrilateral characteristics is not fixed as a horizontal reactance
line. To account for phase angle tolerances in the line CT, VT and the IED, the line is
tilted downwards at a “droop” of -3o. This tilt down helps to prevent zone 1 overreach. To
further improve performance this line incorporates an additional dynamic tilt, which
changes according to the phase angle between the faulted phase current and the
negative sequence current:
Zone 1 is allowed to tilt down to avoid overreaching for prefault power export;
Zones 2 and 3 are allowed to tilt up to avoid underreaching for prefault power
import.
For lines with an impedance of less than 5 Ω the Zone reach term dominates and the
sensitivity is greater than 5% In. Above this line impedance the sensitivity is 5% In.
In Advanced mode the same restrictions as minimum sensitivity should be applied to
ensure distance element accuracy.
P446/EN/TM/E 7-43
7 Operation MiCOMho P446
Operate
Blind
Radius
Z
Load
Blind
b R
Blind
Blind
Operate
P1134ENa P1232ENa
In Figure 30:
Z denotes the Load/B Impedance setting. This sets the radius of the
underimpedance circle.
denotes the Load/B Angle setting. This sets the angle of the two blinder
boundary lines - the gradient of the rise or fall with respect to the resistive axis.
MiCOMho P446 can allow the load blinder to be bypassed any time the measured
voltage for the phase in question falls below an undervoltage V< setting. Under such
circumstances, the low voltage could not be explained by normal voltage excursion
tolerances on-load. A fault is definitely present on the phase in question, and it is
acceptable to override the blinder action and allow the distance zones to trip according to
the entire zone shape. The benefit is that the resistive coverage for faults near to the IED
location can be higher.
7-44 P446/EN/TM/E
MiCOMho P446 7 Operation
The Alternative mode is epecially suitable for evolving faults where the ground timers
could reset and phase timers start.
tGroundZ1
DDB Zone x Gnd Scheme block tPhaseZ1 DDB Any Dist Start
1
Phase Elements Zone 1
t
SET Zone x Gnd Scheme Enabled
tGroundZ2 tGroundZx
DDB Zone x AN & t
Ground Elements Zone 2
Ground Elements
DDB Zone x Trip
& 1 Zone x
tPhaseZ2 & 1
DDB Zone x BN
& Note:
tGroundZP In below, Zone x refers to
DDB Zone x AB & t zone 1,2,3,4,p.
Ground Elements Zone P
Phase Elements
Zone x
DDB Zone x BC & 1 tPhaseZP
By default distance start events are controlled by the inputs to the basic scheme,DDB
960-989. DDB 741-760 can also produce events but these are blocked by settings in the
P446/EN/TM/E 7-45
7 Operation MiCOMho P446
RECORD CONTROL column. The source of these start events can be referred
depending on the customer's preference.
Note: The numbers in the table represent the DDB signals available in the PSL.
7-46 P446/EN/TM/E
MiCOMho P446 7 Operation
Note: The characteristic angle set in this section is also used by the DISTANCE
PROTECTION. This is because distance zones are directionalized by the delta
decision.
Delta directional comparison looks at the relative phase angle of the superimposed
current I compared to the superimposed voltage V, at the instant of fault inception.
The delta is only present when a fault occurs and a step change from the prefault steady-
state load is generated by the fault. The element issues a forward or reverse decision
which can be input into an aided channel unit protection scheme.
Under healthy network conditions the system voltage is close to Vn nominal and load
current flows. Under such steady-state conditions, if the voltage measured on each
phase now is compared with a stored memory from exactly two power system cycles
previously (equal to 96 samples), the difference between them is zero. Zero voltage
change (V = 0) and zero current change (I = 0), except when there are changes in load
current.
When a fault occurs on the system, the delta changes measured are:
V = fault voltage (time “t”) - prefault healthy voltage (t-96 samples)
I = fault current (time “t”) - prefault load current (t-96 samples)
The delta measurements are a vector difference, resulting in a delta magnitude and
angle. Under healthy system conditions the prefault values are those measured 2 cycles
earlier. When a fault is detected the prefault values are retained for the duration of the
fault.
The changes in magnitude are used to detect the presence of the fault and the angles are
used to determine whether the fault is in the Forward or Reverse direction.
Figure 33 shows a single phase to ground fault.
P446/EN/TM/E 7-47
7 Operation MiCOMho P446
IF1
ZS1 I1 ZL1 ZR1
V1
IF/3
IF2
ZS2 I2 ZL2 ZR2
E
V2
voltage
generator
represents
IF0 voltage
change
ZS0 I0 ZL0 ZR0 at fault
location
V0
P1134ENa P1239ENa
The fault is shown near to the busbar at end R of the line, and results in a connection of
the positive, negative, and zero sequence networks in series. The delta diagram shows
that any fault is a generator of , connected at the location of the fault inception. The
characteristics are:
The I generated by the fault is equal to the total fault arc current.
The I splits into parallel paths, with part contribution from source “S” and part from
remote end “R” of the line. Therefore each IED measures a lower proportion of
delta I. Must be verified for all fault types Ph-G, Ph-Ph, Ph-Ph-G, and 3-phase.
The V generated by the fault is equal to the fault arc voltage minus the prefault
voltage, so it is in antiphase with the prefault voltage.
The V is generally smaller, measured at the IED location because the voltage
collapse is smaller near to the source than at the fault. The delta V measured by
an IED is the voltage drop across the source impedance behind the IED location.
Must be verified for all fault types Ph-G, Ph-Ph, Ph-Ph-G, and 3-phase.
If a fault occurs at any point on the protected line, the resulting I and V as measured at
the IED location must be greater than the Delta I Fwd and Delta V Fwd settings, so the
fault can be detected.
7-48 P446/EN/TM/E
MiCOMho P446 7 Operation
Note: Distance zone directionalizing shares the same characteristic angle setting used for
Delta directional comparison protection but uses fixed operating thresholds: V=0.5 V
and I=5%In. In distance applications, if the fault V is below the setting of 0.5 V, a
conventional distance line ensures correct forward/reverse polarizing. This is not true
for Delta directional aided schemes where sufficient V must be present for tripping to
occur.
Directional forward
-90o < (angle(I) – angle(V+180o) – RCA) < 90o
Directional reverse
-90o > (angle(I) – angle(V+180o) – RCA) > 90o
To facilitate testing of the distance elements using test sets, which do not provide a
dynamic model to generate true fault delta conditions, select COMMISSIONING TESTS >
Static Test Mode. When set, this disables phase selector control and forces the IED to
use a conventional (non-delta) directional line.
P446/EN/TM/E 7-49
7 Operation MiCOMho P446
6.1 InterMiCOM
7-50 P446/EN/TM/E
MiCOMho P446 7 Operation
Provided the correct hardware options have been specified, it is possible to configure the
P446 to operate using either InterMiCOM64 or MODEM InterMiCOM, or both. The
selection is made under the CONFIGURATION column of the menu software.
P446/EN/TM/E 7-51
7 Operation MiCOMho P446
Speed
Permissive
faster
Blocking
slower
low
high
This diagram shows that a blocking signal should be fast and dependable; a direct
intertrip signal should be very secure; and a permissive signal is an intermediate
compromise of speed, security and dependability.
In MODEM InterMiCOM applications, selected signaling bits within each message can be
conditioned to provide optimal characteristics for each of the three teleprotection
command types.
In InterMiCOM64 applications, the framing and error checking of a single command
message is sufficient to meet the security of a permissive application, while the speed is
sufficiently fast to meet the needs of a blocking scheme. Accordingly in InterMiCOM64
applications, there is no differentiation between blocking commands or permissive
commands, so that only signals being used for direct intertripping with higher security
requirements need to be differentiated from those in permissive (or blocking) schemes.
Direct Intertrip mode provides the most secure signaling (available on commands 1 - 8)
and Permissive mode provides secure, dependable signaling (available on commands 5
- 8). Each command can also be disabled so that it has no effect in the logic of the relay.
Since many applications involve commands being sent over a multiplexed
communications channel, it is necessary to ensure that only data from the correct relay is
used. The relays in the scheme must be programmed with a unique pair of addresses
that correspond with each other in the Source Address and Receive Address cells. For
example, at the local end relay, if the Source Address is set to 1, the Receive Address
at the remote end relay must also be set to 1. Similarly, if the remote end relay has a
Source Address set to 2, the Receive Address at the local end must also be set to 2.
The two pairs of addresses should be set to be different in any scheme to avoid the
possibility of incorrect operation during inadvertent loopback connections, and any
schemes sharing the same communications services should be set to have different
address pairs to avoid any problems caused by inadvertent cross-channel connections.
Noise on the communications should not be interpreted as valid commands by the relay.
For this reason, InterMiCOM uses a combination of unique pair addressing described
above, basic signal format checking and an 8-bit Cyclic Redundancy Check (CRC)
according to the security requirements of the commands. The CRC calculation is
performed at both the sending and receiving end relays for each message and both must
match to assure the security of the Direct Intertrip commands.
An alarm is provided if noise on the communications channel becomes excessive.
During periods of excessive noise, it is possible that the synchronization of the message
structure will be lost and accurate decoding of the messages may not be possible.
Predictable operation of InterMiCOM is assured during such noisy periods by means of
the IM# FallBackMode cell. The status of the last received valid command can be
maintained until a new valid message is received by setting the IM# FallBackMode cell
to Latched. Alternatively, a known fallback state can be assigned to the command by
setting the IM# FallBackMode cell to Default. In this latter case, the time period
between communication disruption and the default state being restored will need to be
set in the IM# FrameSynTim cell and the default value will need to be set in
IM# DefaultValue cell. Upon subsequent receipt of a valid message, all the timer periods
will be reset and the new valid command states will be used.
If there is a total communications failure, the relay will use the fallback (failsafe) strategy
as described above. Total failure of the channel is considered when no message data is
received for four power system cycles or if there is a loss of the DCD line.
P446/EN/TM/E 7-53
7 Operation MiCOMho P446
Depending on whether a direct or modem connection between the two relays in the
scheme is being used, the required pin connections are described as follows.
The connection configuration shown in Figure 47 should also be used when connecting
to equipment that does not implement control the DCD line.
This type of connection should be used when connecting to multiplexers which provide an
EIA(RS)232 channel with the ability to control the DCD line. With this type of connection
it should be noted that the maximum distance between the Px40 relay and the modem
should not exceed 15m, and that a baud rate suitable for the communications path used
should be selected.
7-54 P446/EN/TM/E
MiCOMho P446 7 Operation
P446/EN/TM/E 7-55
7 Operation MiCOMho P446
The overall fiber length that can be achieved depends on the converter performance.
In this case, the maximum distance between the Px40 relay and the converter should not
exceed 15m.
7-56 P446/EN/TM/E
MiCOMho P446 7 Operation
Note: when an InterMiCOM signal is sent from the local relay, only the remote end relay will
react to this command. The local end relay will only react to InterMiCOM commands
initiated at the remote end and received locally, and vice-versa. Therefore
InterMiCOM can be described as a duplex teleprotection system.
Note: InterMiCOM64 Channel 1 and 2 references are not the same as references to
communications Channels 1 and 2 and this can cause some confusion.
InterMiCOM64 communications can run using two different user settable Baud rates: 56
and 64 kbits/s, for ease of interfacing with standard public and private telecommunication
networks.
InterMiCOM64 also supports the IEEE C37.94 standard for direct optical fiber connection
to appropriately equipped multiplexers. In this case the data rate is matched to one of the
Nx64 channels supported by the multiplexer.
P446/EN/TM/E 7-57
7 Operation MiCOMho P446
The MiCOMho P446 can be equipped with either one or two fiber communications ports
to support InterMiCOM64. For the purposes of setting, labeling, etc., these
communications ports are referenced as protection communications Channels 1 and 2.
Although there is some association of the InterMiCOM64 signal groupings referenced
Channels 1 and 2, with communications Channels 1 and 2, they have subtly different
meanings and care needs to be taken to avoid confusion.
P1735ENa
64
Figure 40: Triangulated InterMiCOM application
When one leg of the communication triangle fails, for example, channel A-C becomes
unavailable, the InterMiCOM64 will continue to provide the full teleprotection scheme
between all three ends in a degraded chain topology because of the way the 8 Channel 2
7-58 P446/EN/TM/E
MiCOMho P446 7 Operation
InterMiCOM64 commands are passed on via the scheme logic. In this degraded ‘Chain’
topology, relays A and C will receive and transmit teleprotection commands via relay B.
The retransmitting done by relay B (A-B-C and C-B-A) provides the self-healing for the
lost links A-C and C-A).
This Chain topology may be employed as a means to save cost in implementing a
three-terminal scheme, since two legs may be cheaper to install than full triangulation, or
if a suitable communication link is not available between two of the line ends. It should
be noted, however, that the operating speed of teleprotection commands will increase by
approximately 7 ms (plus communications channel signaling delay) when retransmitted in
Chain topology, due to the extended path length.
Relay A Relay B
Address Group 25 25-A 25-B
Address Group 26 26-A 26-B
Address Group 27 27-A 27-B
Address Group 28 28-A 28-B
Address Group 29 29-A 29-B
Address Group 30 30-A 30-B
Address Group 31 31-A 31-B
Address Group 32 32-A 32-B
For two relays to communicate with one another, their addresses need to be in the same
address group. One relay should be assigned with address A and the other with address
B. For example, if the group 1 address is used, one relay should be given the address 1-
A, and the other relay should be given the address 1-B. The relay with address 1-A will
only accept messages with the 1-A address and will send out messages carrying address
1-B. The relay assigned with address 1-B will only accept messages with address 1-B
and will send out messages carrying address 1-A.
The groups of addresses available when a three-terminal InterMiCOM64 scheme is
selected are as follows:
Relay A Relay B Relay C
Address Group 1 1-A 1-B 1-C
Address Group 2 2-A 2-B 2-C
Address Group 3 3-A 3-B 3-C
Address Group 4 4-A 4-B 4-C
Address Group 5 5-A 5-B 5-C
Address Group 6 6-A 6-B 6-C
Address Group 7 7-A 7-B 7-C
Address Group 8 8-A 8-B 8-C
Address Group 9 9-A 9-B 9-C
Address Group 10 10-A 10-B 10-C
Address Group 11 11-A 11-B 11-C
Address Group 12 12-A 12-B 12-C
Address Group 13 13-A 13-B 13-C
Address Group 14 14-A 14-B 14-C
Address Group 15 15-A 15-B 15-C
Address Group 16 16-A 16-B 16-C
Address Group 17 17-A 17-B 17-C
Address Group 18 18-A 18-B 18-C
Address Group 19 19-A 19-B 19-C
Address Group 20 20-A 20-B 20-C
Address Group 21 21-A 21-B 21-C
Address Group 22 22-A 22-B 22-C
Address Group 23 23-A 23-B 23-C
Address Group 24 24-A 24-B 24-C
Address Group 25 25-A 25-B 25-C
Address Group 26 26-A 26-B 26-C
Address Group 27 27-A 27-B 27-C
Address Group 28 28-A 28-B 28-C
7-60 P446/EN/TM/E
MiCOMho P446 7 Operation
For three relays to work together as a protection system, their addresses must be in the
same group and they should be assigned separately with addresses A, B and C. They
must also have a fixed connection configuration, as shown in 0, in which channel 1 of one
relay is connected to channel 2 of another relay.
For example, if the group 1 address is used, addresses 1-A, 1-B and 1-C should be
assigned to relays A, B and C respectively. Relay A will only accept messages with
address 1-A and will send messages carrying addresses 1-B and 1-C to channel 1 and
channel 2 respectively. Relay B will only accept messages with address 1-B and will
send messages carrying addresses 1-C and 1-A to channel 1 and to channel 2
respectively. Similarly relay C will only accept messages with address 1-C and will send
messages carrying addresses 1-A and 1-B to channel 1 and to channel 2 respectively.
P446/EN/TM/E 7-61
7 Operation MiCOMho P446
Note: There are 8 of these settings, one for each of eight InterMiCOM64 commands. The 8
settings are applied the same to the 8 InterMiCOM64 commands on Channel 1 as to
the 8 InterMiCOM64 commands on Channel 2, so that if “IM1 Cmd Type” is set to
“Direct”, then IM1 channel 1 and IM1 channel2 with both be conditioned for direct
transfer tripping.
Note: There are 8 of each of these settings, one for each of eight InterMiCOM64 commands.
The 8 settings are applied the same to the 8 InterMiCOM64 commands on Channel 1
as to the 8 InterMiCOM64 commands on Channel 2.
7-62 P446/EN/TM/E
MiCOMho P446 7 Operation
P446/EN/TM/E 7-63
7 Operation MiCOMho P446
7-64 P446/EN/TM/E
MiCOMho P446 7 Operation
Figure 41: InterMiCOM64 channel fail and scheme fail conceptual logic
The messages received on each channel are individually assessed for quality to ensure
that the InterMiCOM64 signaling scheme is available for use. In the event of no messages
being received for a period equal to the “Channel Timeout” setting, or the signal quality
falling below a defined value then DDB signals will be activated as shown in the figure.
Poor quality is indicated if the percentage of incomplete messages exceeds the “IM Msg
Alarm Lvl” setting within a 100 ms period (rolling window), or if the communications
propagation time of the InterMiCOM64 message exceeds the “Ch Max PropDelay” (if the
“Prop DelayStats” setting is enabled), or if (in IEEE C37.94 configuration only, and not
shown on the diagram) the “Ch Mux Clk” flag is set to indicate an incorrect baud rate.
If either the “Ch Timeout”, or the “Ch Degraded” signal persists in the alarmed state for
more than the duration of the “Comm Fail Timer” setting, then the “Signaling Fail” signal
will be raised and indicated on the relay according to the conditions set in the “Comm
Fail Mode” setting of the relay.
In the case of two-ended schemes (including dual redundant schemes), the “IM64
Scheme Fail” signal will be generated at the same time as the “Signaling Fail” signal.
However, for three-terminal applications, the “IM64 Scheme Fail” signal gives an
indication of when the full set of signaling bits cannot be processed by the scheme. Due
to the self-healing nature of the three-terminal application, this occurs when both
channels at any one end are not receiving good signals. This will generate a flag within
the InterMiCOM64 message structure which is passed to both remote ends, as well as
generating the local “IM64 Scheme Fail” signal. By this method, in three-terminal
applications the scheme fail indication will be raised at all three ends.
It should be noted that the scheme fail signaling is generated by the inability of the relays
to receive messages through communication failure. That is to say that a transmitting
relay will only know that its communication to a remote relay is in a failed state if it
receives notification from the remote relay that that is the case. If a relay in the scheme
is put into test mode, the communication failure information is not passed on to the
remote ends. In this instance then it might be that the communications are in a failed
state, but that there is no indication to the remote relays that this is the case. Should this
cause operational issues then it may be necessary to include other signals to enable
more precise indication of scheme failure, as described in the Application Examples
chapter.
In addition to the main InterMiCOM64 channel fail and scheme fail conceptual logic in the
figure above, there are number of additional alarm DDB signals associated with test
P446/EN/TM/E 7-65
7 Operation MiCOMho P446
modes, reconfiguration for 3-terminal schemes, and the communication mode (standard
vs IEEE C37.94). These are outlined in the two figures below:
Figure 43: InterMiCOM64 communications mode and IEEE C37.94 alarm signals
The majority of signals described in 0 are associated with the IEEE C37.94
communications mode and will not be activated if the standard communication mode is
selected. As can be seen from the “Comms Changed DDB” logic, switching between
the different communication modes requires a power-cycle to be performed.
7-66 P446/EN/TM/E
MiCOMho P446 7 Operation
P446/EN/TM/E 7-67
7 Operation MiCOMho P446
In this example if both channels at any one end fail to receive information, then this will
be communicated to the other ends with an alarm raised and aided scheme switched out
of service. The example above takes into account the test modes and local switching,
such that the scheme will be signaled out of service at all ends if one end is locally
disabled.
The logic presented above is intended only as an example. It is likely that some
customization would be required to suit actual application requirements.
In any configuration, except the IEEE C37.94, the data rate may be selected as either
64 kbit/sec or 56 kbit/sec.
7-68 P446/EN/TM/E
MiCOMho P446 7 Operation
P2265ENd
The relays are connected directly using two 1300nm single-mode fibers, type 9/125m for
each signaling channel. BFOC/2.5 type fiber optic connectors are used.
P2265ENd
Note: The relay must be powered off and on before this setting change becomes effective.
The IEEE C37.94 standard defines an N*64 kbits/s standard where N can be 1 - 12.
N can be selected on the relay or alternatively set to Auto in which case the relay will
configure itself to match the multiplexer.
P446/EN/TM/E 7-69
7 Operation MiCOMho P446
6.3.3.2 InterMiCOM64 connection via P590 series optical fiber to electrical interface units
To connect the relays via a pulse code modulation (PCM) multiplexer network or digital
communication channel, Type P590 type interface units are required. The following
interface units are available:
The data rate for each unit can be 56 kbits/s or 64 kbits/s as required for the data
communications link.
One P590 unit is required per relay per data channel (i.e. for each transmit and receive
signal pair). It provides optical to electrical and electrical to optical signal conversion
between the MiCOMho P446 relay and the multiplexer. The interface unit should be
located as close to the PCM multiplexer as possible, to minimize any effects on the data
of electromagnetic noise or interference. The units are housed in a 20TE MiCOM case.
Fiber optic connections to the unit are made through BFOC/2.5 type connectors, more
commonly known as ‘ST’ connectors. The optical characteristics are similar to the
MiCOMho P446 850 nm multi-mode fiber optic interface.
6.3.3.2.1 Multiplexer link with G.703 using type P591 interface
A relay with 850 nm short haul optical interface is connected to a P591 unit by two cores
of 850 nm multi-mode optical fiber. Multi-mode fiber type 50/125 m or 62.5/125 m is
suitable. BFOC/2.5 type fiber optic connectors are used. The P591 unit converts the
data between optical fiber and ITU-T compatible G.703 co-directional electrical interface.
The G.703 output must be connected to an ITU-T compatible G.703 co-directional
channel on the multiplexer.
P2266ENe
7-70 P446/EN/TM/E
MiCOMho P446 7 Operation
P2267ENc
Connections of V.35 signals to the P592 unit are made via a standard female 34 pin ‘M’
block connector. Since the V.35 signals are either of ±0.55 V or ±12 V magnitude, the
cable connecting the unit to the multiplexer must be properly screened against
electromagnetic noise and interference. The interface cable should consist of twisted
pairs of wires which are shielded, and have a characteristic impedance of about 100 . It
is generally recommended that the interface cable shield is connected to the multiplexer
frame ground. The choice of grounding depends however on local codes and practices.
The P592 front panel consists of five indicating LEDs and six DIL (dual in line) switches.
The switch labeled ‘Clockswitch’ is provided to invert the V.35 transmit timing clock
signal if required.
The switch labeled ‘Fiber-optic Loopback’ is provided to allow a test loopback of the
communication signal across the fiber optic terminals. When switched on, the red LED
labeled 'Fiber-optic Loopback' is illuminated.
The switch labeled ‘V.35 Loopback’ is provided to allow a test loopback of the
communication signal across the V.35 terminals. It loops the incoming V.35 ‘Rx’ data
lines internally back to the outgoing V.35 ‘Tx’ data lines. When switched on, the red LED
labeled ‘V.35 Loopback’ is illuminated.
The switch labeled ‘DSR’ is provided to select/ignore the DSR (Data Set Ready)
handshaking control signal. The red LED labeled DSR Off is extinguished either when
DSR is asserted or when overridden by setting the DSR switch On.
The switch labeled ‘CTS’ is provided to select/ignore the CTS (Clear To Send)
handshaking control signal. The red LED labeled CTS Off is extinguished either when
CTS is asserted or when overridden by setting the CTS switch On.
The switch labeled ‘Data Rate’ is provided to allow the selection of 56 or 64k bits/s data
rate, as required by the PCM multiplexing equipment.
The LED labeled ‘Supply Healthy’ is green and provides indication that the unit is
correctly powered.
See the Wiring Diagrams chapter for External Connection Diagrams. The timing for the
InterMiCOM64 communication channel may be set either with Clock Source as ‘External’
for a multiplexer network which is supplying a master clock signal, or with Clock Source
as ‘Internal’ for a multiplexer network recovering signal timing from the equipment.
6.3.3.2.3 Multiplexer link with X.21 using type P593 interface
The P593 unit supports the ITU-T Recommendation X.21 interface. It is approved as line
interface equipment by the British Approvals Board for Telecommunications (BABT) for
connection to the services described in this section; License Certificate Number
NS/1423/1/T/605362.
A relay with 850 nm short haul optical interface is connected to a P593 unit by two cores
of 850 nm multi-mode optical fiber. Multi-mode fiber type 50/125 m or 62.5/125 m is
suitable. BFOC/2.5 type fiber optic connectors are used. The P593 unit converts the
data between optical fiber and ITU-T compatible X.21 electrical interface. The X.21
output must be connected to an ITU-T compatible X.21 channel on the multiplexer or
ISDN digital data transmission link.
P446/EN/TM/E 7-71
7 Operation MiCOMho P446
P2268ENe
Connections of X.21 signals to the P593 unit are made via a standard male 15 way D-
type connector, wired as a DTE device. The interface cable should consist of twisted
pairs of 24 AWG, overall shielded, and have a characteristic impedance of about 100 .
It is generally recommended that the interface cable shield is connected to the multiplexer
frame ground. The choice of grounding depends however on local codes and practices.
Please see the Wiring Diagrams chapter for the External Connection Diagrams.
The timing for the InterMiCOM64 communication channel must be set with Clock Source
as ‘External’.
The P593 front panel consists of four indicating LEDs and two switches.
The LED labeled ‘Supply healthy’ is green and provides indication that the unit is
correctly powered.
The LED labeled ‘Clock’ is green and provides indication that an appropriate X.21 signal
element timing signal is presented to the unit.
One of the switches is labeled ‘Fiber Optic Loopback’. This is provided to allow a test
loopback of the communication signal across the fiber optic terminals. When switched
on, the red LED labeled ‘Fiber Optic Loopback’ is illuminated.
The second switch is labeled ‘X.21 Loopback’. This is provided to allow a test loopback
of the communication signal across the X.21 terminals. It loops the incoming X.21 ‘Rx’
data lines internally back to the outgoing X.21 ‘Tx’ data lines, and also loops the incoming
fiber optic ‘Rx’ data line (via the X.21 signal conversion circuitry) back to the outgoing
fiber optic ‘Tx’ data line. When switched on, the red LED labeled ‘X.21 Loopback’ is
illuminated.
7-72 P446/EN/TM/E
MiCOMho P446 7 Operation
Note: The PCM-FLÜ isolating transformer has “a”, “m” and “b” taps on both primary and
secondary windings. For all InterMiCOM64 applications, connection must be made
between taps ‘a’ and ‘m’, since the frequency range of this winding extends to 2 MHz.
Connection between ‘a’ and ‘b’ may result in unreliable communications as the
maximum frequency for this tap configuration is 6 kHz. Connection to ‘a’ and ‘m’ taps
must be adhered to on both primary and secondary so as to maintain a 1:1 ratio.
For maximum security and performance it is strongly recommended that the pilots use
screened twisted pairs of conductors.
The Campus modem should be specified with a G.703 interface and should be used in
conjunction with a MiCOM P591.
6.3.3.3.3 Baseband modem propagation delay
The use of a baseband modem will bring an additional propagation delay time that needs
to be taken into account. For a 2-wire connection to the Campus modem the additional
delay will be 1.02 ms. For a 4-wire connection to the Campus modem the additional
delay will be 1.08 ms.
6.3.3.3.4 Baseband modem and relay configuration
A scheme configuration using 2-wire connection without additional isolation is shown in
the figure below:
The MiCOMho P446 relays should have their “IM64 Comms Mode” set to “standard”,
their data rates set to 64 kbits/s, and their clock sources set to external.
One of the Campus modems on the pilot wire should be assigned as a “master” and the
other assigned as “slave”. The “master” should be set to generate an internal clock, and
the “slave” should be set for “receive recovery”. This is achieved by means of setting
dual in-line (DIL) switches inside the modem. To implement these settings, the switches
should be set as per the following tables:
MASTER
S1 (on the bottom side of the modem)
Pin no. 1 2 3 4 5 6 7 8
Setting 1 0 1 0 0 1 1 1
Setting 0 0 0 0 0 1 0 0
Setting 1 0 1 1
7-74 P446/EN/TM/E
MiCOMho P446 7 Operation
SLAVE
S1 (on the bottom side of the modem)
Pin no. 1 2 3 4 5 6 7 8
Setting 1 0 1 0 0 1 0 1
Setting 0 0 0 0 0 1 0 0
Setting 1 0 1 1
The MiCOM P591 communications interface units do not require any special setting up and
the scheme should be now operational.
P446/EN/TM/E 7-75
7 Operation MiCOMho P446
The SOTF and TOR functions are known as Trip on Close logic. Figure 46 shows the
Trip On Close function in relation to the Distance zones. Figure 47 shows the Trip On
Close driven by Current No Volt level detectors. Both methods operate in parallel if
mapped to the SOTF and TOR Tripping matrix in the setting file.
The Current No Volt (CNV) level detectors can be set in the menu GROUP X CB FAIL &
P.DEAD The same settings are used for pole dead logic detection. The 20 ms time
delay in Figure 47 avoids a possible race between very fast overvoltage and undercurrent
level detectors.
7-76 P446/EN/TM/E
MiCOMho P446 7 Operation
SET: TOR_En
Pick-up =
DDB: Any PD (891)
TOC Delay
S
DDB: TOC_Active (877)
Drop-off = t TOC
Reset dly R
&
DDB: All PD (890)
& Pick-up = tSOTF
S
Enable dly
R
SET: TOR_Z2_En
& DDB: Trip_TOR_Z2 (705)
SET: TOR_ZP_En
& DDB: Trip_TOR_ZP(708)
SET: SOTF_Z1_En
SET: SOTF_Z2_En
& DDB: Trip_SOTF_Z2 (710)
P4039ENb
Enabled using pole dead detection logic. If an All Pole Dead condition is detected,
the SOTF Delay timer starts. Once this timer expires, SOTF is enabled and stays
active for the period set in the TOC Reset Delay setting.
Enabled by an external pulse. SOTF is enabled after an external pulse linked to
DDB Set SOTF (DDB 488) is ON. The external pulse could be a circuit breaker
close command, for example. The function stays active for the duration of the
SOTF Pulse setting.
Enabled using both pole dead detection logic and an external pulse.
Three pole instantaneous tripping (and auto-reclose blocking) occurs for any fault
detected by the selected zones or Current No Volt level detectors when in SOTF mode.
Whether this feature is enabled or disabled, the normal time delayed elements or aided
channel scheme continues to function and can trip the circuit.
SOTF Delay. The SOTF Delay is a pick up time delay that starts after opening all three
poles of a CB. If the CB is then closed after the set time delay has expired, SOTF
protection is active. SOTF provides enhanced protection for manual closure of the
breaker (not for auto-reclosure).
This setting is visible only if Pole Dead or Pdead + Pulse are selected to enable SOTF.
SOTF Tripping. While the Switch on to Fault Mode is active, the IED trips
instantaneously for pick up of any zone selected in these links. To operate for faults on
the entire circuit length, at least Zone 1 and Zone 2 should be selected. If no elements
are selected, the normal time delayed elements and aided scheme provide the protection.
SOTF Pulse. A user settable time window during which the SOTF protection is available.
This setting is visible only if ExtPulse or Pdead + Pulse are selected to enable SOTF.
7-78 P446/EN/TM/E
MiCOMho P446 7 Operation
With this feature Enabled, for a period following circuit breaker closure, the IED operates
in Trip on Reclose mode. Three pole instantaneous tripping occurs for any fault
detected by the selected zones or Current No Volt level detectors. Whether this feature
is enabled or disabled, the normal time delayed elements or aided channel scheme
continue to function and can trip the circuit.
TOC Reset Delay. The SOTF and TOR features stay in service for the duration of the
TOC Reset Delay once the circuit is energized. The delay timer starts on CB closure and
is common for SOTF and TOR protection. Once this timer expires after successful
closure, all protection reverts to normal.
TOC Delay. A user settable time delay that starts when the CB opens, after which TOR
is enabled. The time delay must not exceed the minimum Dead Time setting of the auto-
reclose because both times start simultaneously and TOR protection must be ready by
the the CB closes on potentially persistent faults.
TOR Tripping. While the Trip on Reclose Mode is active, the IED trips instantaneously
for pick up of any selected Distance zone. For example, Zone 2 could operate without
waiting for the usual time delay if a fault is in Zone 2 on CB closure. Also Current No
Volts can be mapped for fast fault clearance on line reclosure on a permanent fault. To
operate for faults on the entire circuit length, at least Zone 1 and Zone 2 should be
selected. If no elements are selected, the normal time delayed elements and aided
scheme provide the protection. TOR tripping is 3 phase and auto-reclose is blocked.
Distance POR with DEF POR scheme operating over a common shared channel…
Select both in AIDED SCHEME 1 only, with AIDED SCHEME 2 Disabled.
Distance PUR with DEF BLOCKING operating over separate channels due to the
dissimilar scheme types. Assign Distance to AIDED SCHEME 1, and DEF to
AIDED SCHEME 2.
Directional Comparison BLOCKING scheme with a second channel for a distance
with DEF BLOCKING scheme operating in unison… Assign Delta to AIDED
SCHEME 1, and both Distance/DEF to AIDED SCHEME 2.
Note: Where schemes share a common channel, the signal send and signal receive logic
operates in a logical “OR” mode.
P446/EN/TM/E 7-79
7 Operation MiCOMho P446
Aided Scheme 1 and Aided Scheme 2 are two instances of the same logic. Each of
these schemes provides the same options and can be independently applied. The
scheme logic is split into three sections defined in the following diagram: send logic,
receive logic, and aided tripping logic, as shown in Figure 48. Detailed scheme
descriptions follow later. As there are two instances of the aided scheme, any internal
logic signals which are specific to the instance of the scheme are shown in the diagrams
with two DDB numbers relating to the first and second instance, respectively.
Protection:
Distance
Signal Send (CTx)
DEF Send Logic
Delta Dir
Local Send
Feedback Echo
Aided Trip En
Protection:
Distance
Aided Tripping Aided Tripping
DEF Logic
Delta Dir
P1590ENa
The full logic of Send, Receive and Aided Trip are shown in the following diagrams.
7-80 P446/EN/TM/E
MiCOMho P446 7 Operation
MASK:Zone 1 En
SET: Dist Ph En
MASK:Zone 2 En
Aided 1 - 497
SET:Delta En Aided 2 - 513
DDB: Custom Send
MASK:Delta Fwd En
MASK:Custom En &
DDB:Delta Fwd AN(998)
&
DDB: Delta Fwd BN(999)
MASK:Delta Rev En
SET:DEF En
MASK:DEF Fwd En
&
DDB: DEF FWD(996)
MASK:DEF Rev En
& P1591ENd
P446/EN/TM/E 7-81
7 Operation MiCOMho P446
t
DR
&
200ms
&
t
& & DW
t
1 PR
1 &
150ms
& &
Aided 1:317
Aided 1:492 Aided 2:318
CRx Int
DDB: CRx Ext 1
& Aided 1:494
Aided 2:508
Aided 1:493
Aided 2:507
Unblocking
Scheme Selected
P1592ENb
7-82 P446/EN/TM/E
MiCOMho P446 7 Operation
P446/EN/TM/E 7-83
7 Operation MiCOMho P446
for a PUR scheme is keyed by operation of the underreaching zone 1 elements of the
IED. If the remote IED detects a forward fault on receipt of this signal, the IED operates
with no additional delay. Faults in the last 20% (Note 1) of the protected line are
therefore cleared with no intentional time delay.
Note: Assuming a 20% typical “end-zone” when Zone 1 is set to 80% of the protected line.
The following are some of the main features and requirements for a permissive
underreaching scheme.
Zone 3
Zone 2
Zone 1
A B
Z
Z
Zone 1
Zone 2
Zone 3
CRx CRx
CTx CTx
& &
Z1 TZ1 Z1
TZ1
Trip A Trip B
1 1
Zp Zp
TZp TZp
Z2 TZ2 Z2
TZ2
Z3 Z3
TZ3 TZ3
Z4 Z4
TZ4 TZ4
P1134ENa P1145ENb
Optional features of scheme
7-84 P446/EN/TM/E
MiCOMho P446 7 Operation
Note: Assuming a 20% typical “end-zone” when Zone 1 is set to 80% of the protected line.
The following are some of the main features and requirements for a permissive
overreaching scheme:
Note: The POR scheme also uses the reverse looking zone 4 of the IED as a reverse fault
detector. This is used in the current reversal logic and in the optional weak infeed
echo feature, shown dotted in Figure 54.
P446/EN/TM/E 7-85
7 Operation MiCOMho P446
Zone 4
Zone 3
Zone 2
Zone 1
A Z B
Z
Zone 1
Zone 2
Zone 3
Zone 4
CRx CRx
Zone 4 & & Zone 4
CTx CTx
1 1
& &
Z1 Z1
TZ1 TZ1
1 Trip A Trip B 1
ZP ZP
TZP TZP
Z2 Z2
TZ2 TZ2
Z3 Z3
TZ3 TZ3
Z4 Z4
TZ4 TZ4
P1134ENa P1149ENb
Optional features of scheme
Note: The DDB Any Trip (522) feeds into a 100 ms delay on drop-off timer, which in turn
leads to signal sending. This is a principle similar to the logic which results in a signal
send for weak infeed and breaker open echoing.
7-86 P446/EN/TM/E
MiCOMho P446 7 Operation
DDB:CRx Int
(494,508)
SET: POR Selected &
Any Z4 Element DDB: Aided Trip En
&
DEF Rev Element 1 1 (501,517)
tRGD
IntSig: BIK Send
DDB:Any Trip (522) SET:Reversal Guard
DDB:Trip_3Ph (529)
&
SETTING Send on
Trip = Any Trip
1 &
100ms
SETTING Send on
Trip = Aided/ZI
&
SETTING Aided x
Distance = Disabled
&
ZI TRIP
1
AIDED x DIST TRIP
DDB: CB Open 3 ph
250ms &
Pole (903)
P1582ENi
P446/EN/TM/E 7-87
7 Operation MiCOMho P446
Echo Send
No Distance Zone Operation, plus Channel Received.
Weak Infeed Tripping
Weak infeed echo logic ensures an aided trip at the strong infeed terminal but not at the
weak infeed. The IED also has a setting option to allow tripping of the weak infeed circuit
breaker of a faulted line. Three undervoltage elements, Va<, Vb< and Vc< are used to
detect the line fault at the weak infeed terminal. This voltage check prevents tripping
during spurious operations of the channel or during channel testing.
The additional weak infeed trip logic is as follows.
7-88 P446/EN/TM/E
MiCOMho P446 7 Operation
The window of time during which the unblocking logic is enabled starts
10 ms after the guard signal is lost, and continues for 150 ms. The 10 ms delay gives
time for the signaling equipment to change frequency, as in normal operation. For the
duration of any alarm condition, zone 1 extension logic is invoked if Z1 Ext on Chan. Fail
is Enabled.
P446/EN/TM/E 7-89
7 Operation MiCOMho P446
Zone 4
Zone 3
Zone 2
Zone 1
A Z B
Z
Zone 1
Zone 2
Zone 3
Zone 4
CRx CRx
Fast Z4 Fast Z4
& CTx CTx &
& &
Z1 Z1
TZ1 TZ1
1 Trip A Trip B 1
ZP ZP
TZP TZP
Z2 Z2
TZ2 TZ2
Z3 Z3
TZ3
TZ3
Z4 Z4
TZ4 TZ4
7-90 P446/EN/TM/E
MiCOMho P446 7 Operation
t2(C) t2(D)
Fault Fault
A L1 B A L1 B
Strong Weak
source C L2 D source C L2 D
P1134ENa
Note how after circuit breaker B on line L1 opens P1157ENa
the direction of current flow in line L2 is reversed.
The difference in the receive logic is shown in Logic Diagrams, Figure 58 and Figure 59
below:
P1584ENc
SET: Reversal
Guard
DDB: CTx (498,514)
1
tRGD
DDB: CRx Int (494,508)
The relative merits of Blocking 1 and Blocking 2 are discussed in Application Examples.
P446/EN/TM/E 7-91
7 Operation MiCOMho P446
ZL
A B
P1306ENa
The scheme has the same features/requirements as the corresponding distance scheme
and provides sensitive protection for high resistance earth faults.
CRx CRx
DEF-R & & DEF-R
CTx CTx
1 1
P1134ENa P1154ENa
Optional features of scheme
Trip logic: IN> Forward, plus Channel NOT Received, with small set delay
P1307ENa
The scheme has the same features/requirements as the corresponding distance scheme
and provides sensitive protection for high resistance earth faults.
Where t is shown in the diagram this signifies the time delay associated with an element.
To allow time for a blocking signal to arrive, a short time delay on aided tripping must be
used.
CRx CRx
DEF-R Start Start DEF-R
CTx
Stop CTx
Stop
This scheme is similar to that used in the LFDC IED, and is shown in Figure 64.
Send logic: Fault Forward
Permissive trip logic: Fault Forward plus Channel Received.
R R
Z (T)
CRX CRX
CB CB
Open & Signalling Signalling & Open
Equipment Equipment
Trip G Trip H
1 1
TZ(T) TZ(T)
END G END H
Z t t Z
0 0
P1234ENa
P1019ENa
7-94 P446/EN/TM/E
MiCOMho P446 7 Operation
Fast tripping occurs at a strong source line end for faults along the protected line
section, even if there is weak or zero infeed at the other end of the protected line.
If a line terminal is open, fast tripping still occurs for faults along the whole of the
protected line length.
A current reversal guard timer in the signal send logic prevents unwanted IED trips
on the healthy circuit during current reversal situations on a parallel circuit.
To allow time for a blocking signal to arrive, a short time delay on aided tripping
Delta dly must be used.
This scheme is similar to that used in the LFDC IED, and is shown in Figure 64.
Send logic: Fault Reverse
Trip logic: Fault Forward, plus Channel NOT Recieved, delayed by Tp.
R R
Z (T)
CRX CRX
Signalling Signalling
Equipment Equipment
Trip G Trip H
1 1
TZ(T) TZ(T)
END G END H
Z t t Z
P1019ENa
0 0 P1233ENa
Z1 Extension (A)
ZL
A Z1A B
Z1 Extension (B)
P1308ENa
In this scheme Zone 1X is enabled and set to overreach the protected line. A fault on the
line, including one in the end 20% not covered by zone 1, results in instantaneous
tripping followed by auto-reclosure. Zone 1X has resistive reaches and residual
compensation similar to Zone 1. The auto-recloser in the IED is used to inhibit tripping
from zone 1X so that on reclosure the IED operates with Basic scheme logic only, to co-
ordinate with downstream protection for permanent faults. Therefore transient faults on
the line are cleared instantaneously, which reduces the probability of a transient fault
becoming permanent. However, the scheme can operate for some faults on an adjacent
line, although this is followed by auto-reclosure with correct protection discrimination.
Increased circuit breaker operations would occur, together with transient loss of supply to
a substation.
Fault trip Z1X time delay
First fault trip = tZ1
Fault trip for persistent fault on auto-reclose = tZ2
Table 5: Time delays associated with extended zone Z1X
The Zone 1X reach is set as a percentage of the Zone 1 reach, as a reach multiplier.
The Zone 1 extension scheme can be Disabled, permanently Enabled or just brought into
service when the communication channel fails and the aided scheme is inoperative. It
can be set to be enabled when Ch 1 or Ch 2 fails, or when all channels fail, or when any
channel fails. See Figure 67.
1
SET Z1X on Ch 1 Fail
&
SET Z1X on Ch 2 Fail
&
SET Z1X on Ch 1 AND 2 Fail
&
SET Z1X on Ch 1 OR 2 Fail
&
DDB Channel 1 Fail (317)
P1548ENb
7-96 P446/EN/TM/E
MiCOMho P446 7 Operation
Any fault in the reach of Zone 1 results in fast tripping of the local circuit breaker. For an
end zone fault with remote infeed, the remote breaker is tripped in Zone 1 by the remote
IED. The local IED can recognize this by detecting the loss of load current in the healthy
phases. This, coupled with operation of a Zone 2 comparator, causes tripping of the local
circuit breaker.
Before an accelerated trip can occur, load current must be detected before the fault. The
loss of load current opens a window during which time a trip occurs if a Zone 2
comparator operates. A typical setting for this window is 40 ms as shown in Figure 68,
although this can be altered in the LoL Window setting. The accelerated trip is delayed
by 18 ms to prevent initiation of a loss of load trip due to circuit breaker pole discrepancy
occurring for clearance of an external fault. The local fault clearance time can be
deduced as follows:
t = Z1d + 2CB + LDr + 18 ms
Where:
Z1d = Maximum downstream zone 1 trip time
CB = Breaker operating time
LDr = Upstream level detector (LoL: I<) reset time
Z2
Z1
Z1 Z1
Z1
Z2
LOL-A
LOL-B
LOL-C &
1 P1146ENa
For circuits with load tapped off the protected line, care must be taken in setting the loss
of load feature to ensure that the I< level detector setting is above the tapped load
current. When selected, the loss of load feature operates with the main distance scheme
that is selected. This provides high speed clearance for end zone faults when the Basic
scheme is selected or, with permissive signal aided tripping schemes, it provides high
speed back-up clearance for end zone faults if the channel fails.
Note: Loss of load tripping is only available where 3 pole tripping is used. The detailed
Logic Diagram is shown in Figure 69.
P446/EN/TM/E 7-97
7 Operation MiCOMho P446
7-98 P446/EN/TM/E
MiCOMho P446 7 Operation
Permanently disabled
Permanently enabled
Enabled only in case of VT fuse/MCB failure
In addition, each stage may be disabled by a DDB (463, 464, 465 or 466) Inhibit I > x (x =
1, 2, 3 or 4)
Phase overcurrent protection is phase segregated, but the operation of any phase is
mapped to 3 phase tripping in the default PSL.
The VTS element of the IED can be selected to either block the directional element or
simply remove the directional control.
Note: The IEEE and US curves are set differently to the IEC/UK curves, with regard to the
time setting. A time multiplier setting (TMS) is used to adjust the operating time of the
IEC curves, whereas a time dial setting is used for the IEEE/US curves. The menu is
arranged so that if an IEC/UK curve is selected, the > Time Dial cell is not visible and
vice versa for the TMS setting.
Where:
TD = Time dial setting for IEEE curves
S = Constant
M = /s
Curve description Standard S constant
Moderately Inverse IEEE 4.85
Very Inverse IEEE 21.6
Extremely Inverse IEEE 29.1
Inverse US 5.95
Short Time Inverse US 2.261
Table 7: Reset characteristics
Under system fault conditions, the fault current vector lags its nominal phase voltage by
an angle depending on the system X/R ratio. The IED must therefore operate with
maximum sensitivity for currents lying in this region. This is done using the IED
characteristic angle (RCA) setting. The RCA is the angle by which the current applied to
the IED must be displaced from the voltage applied to the IED to obtain maximum
sensitivity. This is set in cell >Char Angle in the overcurrent menu. It is possible to set
characteristic angles anywhere in the range –95° to +95°.
Figure 70 shows the functional logic block diagram for directional overcurrent.
The overcurrent block is a level detector that detects if the current magnitude is above the
threshold, and together with the respective polarizing voltage, a directional check is
performed based on the following criteria:
7-100 P446/EN/TM/E
MiCOMho P446 7 Operation
Directional forward
-90° < (angle(I) - angle(V) - RCA) < 90°
Directional reverse
-90° > (angle(I) - angle(V) - RCA) > 90°
A Phase
Overcurrent A Phase Start
Directional
VBC Polarizing
Voltage
Check & IDMT/DT A Phase Trip
1 &
VBC Polarizing
Memory
B Phase
Overcurrent B Phase Start
Directional
VCA Polarizing
Voltage
Check & IDMT/DT B Phase Trip
1 &
VCA Polarizing
Memory
C Phase
Overcurrent C Phase Start
Directional
VAB Polarizing
Voltage
Check & IDMT/DT C Phase Trip
1 &
VAB Polarizing
Memory
Fast VTS
Block
AR Timer Block
(3rd & 4th stages only)
Any of the four overcurrent stages may be configured to be directional noting that IDMT
characteristics are only selectable on the first two stages. When the element is selected
as directional, a VTS Block option is available. When the relevant bit is set to 1,
operation of the Voltage Transformer Supervision (VTS), blocks the stage if
directionalized. When set to 0, the stage reverts to non-directional when the VTS
operates.
P446/EN/TM/E 7-101
7 Operation MiCOMho P446
CTS Block n = 1, 2, 3, 4
P1604ENa
CTS Block
&
Slow VTS Block
P1605ENb
P446/EN/TM/E 7-103
7 Operation MiCOMho P446
10 BROKEN CONDUCTOR
I1
I2/I1 Above Delay Timer
Threshold &
Broken
I2 Conductor Trip
CTS Block
P1639ENa
7-104 P446/EN/TM/E
MiCOMho P446 7 Operation
11 EARTH FAULT
11.1 Earth fault, Sensitive Earth Fault (SEF) and Restricted Earth Fault
(REF) protection
The IED includes backup earth fault protection. Two elements are available:
A derived earth fault element, where the residual current to operate the element is
derived from the addition of the three line CT currents.
A sensitive earth fault element where low current settings are required.
The sensitive earth fault element has a separate CT input and would normally be
connected to a core balance CT. The derived and sensitive earth fault elements both
have four stages of protection. The first two stages can be set to either inverse time or
definite time only. The third and fourth stages have a DT characteristic only. Each stage
can be configured to be directional forward, directional reverse or non-directional.
Note: The input CT which is designed specifically to operate at low current magnitudes is
common to both the Sensitive Earth Fault (SEF) and high impedance Restricted Earth
Fault (REF) protection, so these features are treated as mutually exclusive in the IED
menu.
Protection also can be enabled if the differential protection communication channel fails
(not applicable to SEF and REF Functions).
Earth fault Overcurrent IN> can be set to:
Permanently disabled
Permanently enabled
Enabled only if VT fuse/MCB fails
Also each stage of EF can be disabled using a DDB (467,468,469 and 470)
Inhibit IN > x and each stage of SEF by DDB (1724,1725,1726 and 1727)
Inhibit ISEF > x (where x = 1, 2, 3 or 4).
The VTS element of the IED can be selected to either block the directional element or
simply remove the directional control.
The N> and ISEF> Function Links settings have the following effect:
VTS Block - When the relevant setting is 1, operation of the Voltage Transformer
Supervision (VTS) blocks the stage if it is directionalized. When set to 0 the stage reverts
to non-directional when the VTS is operated`.
The inverse time characteristics available for the earth fault protection are the same as
those for the phase overcurrent elements, but with the addition of an IDG curve
characteristic.
t = 5.8 - 1.35 loge in seconds
N > Setting
P446/EN/TM/E 7-105
7 Operation MiCOMho P446
Where:
= Measured current
N>Setting = An adjustable setting which defines the start point of the
characteristic
Although the start point of the characteristic is defined by the N> setting, the actual IED
current threshold is a different setting called “IDG s”. The IDG s setting is a multiple of
N>.
An additional setting IDG Time is also used to set the minimum operating time at high
levels of fault current.
Figure 74 shows how the IDG characteristic is implemented.
10
3
IDG Time Setting Range
2
0
1 10 100
I/IN>
P2242ENa
Note: Residual voltage is nominally 180 out of phase with residual current. Therefore the
DEF elements are polarized from the -Vres quantity. This 180 phase shift is
automatically introduced in the IED.
The following directional criteria are with zero sequence (residual voltage) polarization.
7-106 P446/EN/TM/E
MiCOMho P446 7 Operation
Directional forward
-90o < (angle(IN) - angle(VN+180o) - RCA) < 90o
Directional reverse
-90o > (angle(IN) - angle(VN+180o) - RCA) > 90o
The virtual current polarizing feature is used exclusively in DEF aided schemes only and
is not available for use with the backup earth fault elements.
CTS Block
IN> Protection
Inhibit
&
IN Derived/Measured
> Setting
EF Start
Directional
VN Polarizing Check & IDMT/DT EF Trip
Voltage VN Pol> &
Slow VTS
Block
Figure 75: Directional Earth Fault overcurrent with neutral voltage polarization
(single stage)
P446/EN/TM/E 7-107
7 Operation MiCOMho P446
CTS Block
IN> Protection
Inhibit
&
IN Derived/Measured
> Setting
EF Start
NPS Polarizing
Current I2> Directional &
Check & IDMT/DT EF Trip
NPS Polarizing
Voltage V2> &
Slow VTS
Block
Directional forward
-90° < (angle(I2) - angle(V2 + 180°) - RCA) < 90°
Directional reverse
-90° > (angle(I2) - angle(V2 + 180°) - RCA) > 90°
7-108 P446/EN/TM/E
MiCOMho P446 7 Operation
12 AIDED DEF
If Virtual I Pol is set to Disabled it prevents checking of the faulted phase and
subsequent removal of the faulted phase voltage. The DEF protection is then polarized
by the residual voltage only.
The directional criteria with zero sequence (virtual current) polarization are as follows.
Directional forward
-90 < (angle(IN) - angle(VNpol+180) - RCA) < 90
Directional reverse
-90 > (angle(IN) - angle(VNpol+180) - RCA) > 90
P446/EN/TM/E 7-109
7 Operation MiCOMho P446
Directional forward
-90o < (angle(I2) - angle(V2+180o) - RCA) < 90o
Directional reverse
-90o > (angle(I2) - angle(V2+180o) - RCA) > 90o
7-110 P446/EN/TM/E
MiCOMho P446 7 Operation
Healthy CT Saturated CT
Protected
circuit
Zm Zm AG
R CT1 R CT2
IF
R L1 R L3
VS R ST
R L2 R R L4
If the IED circuit is considered to be very high impedance, the secondary current
produced by the healthy CT flows through the saturated CT. If CT magnetizing
impedance of the saturated CT is considered to be negligible, the maximum voltage
across the IED circuit is equal to the secondary fault current multiplied by the connected
impedance, (RL3 + RL4 + RCT2).
The IED can be made stable for this maximum applied voltage by increasing the overall
impedance of the IED circuit, so that the resulting current through the IED is less than its
current setting. As the impedance of the IED input alone is relatively low, a series
connected external resistor is required. The value of this resistor, RST, is calculated by
the formula shown in Figure 77. An additional non-linear metrosil may be required to limit
the peak secondary circuit voltage during internal fault conditions.
To ensure that the protection operates quickly during an internal fault, the CTs used to
operate the protection must have a kneepoint voltage of at least 4 Vs.
The necessary IED connections for high impedance REF are shown in Figure 78.
P446/EN/TM/E 7-111
7 Operation MiCOMho P446
C
RSTAB
SEF Input
P2044ENc
7-112 P446/EN/TM/E
MiCOMho P446 7 Operation
VTS Block
Each stage of Residual Overvoltage protection may be disabled by a DDB (475 or 476)
Inhibit VN>x (x = 1, 2).
P446/EN/TM/E 7-113
7 Operation MiCOMho P446
2 - (K. 2
FLC)
t = - loge
(2 - p2)
Where:
t = Time to trip, following application of the overload current, ;
= Heating and cooling time constant of the protected plant;
= Largest phase current;
FLC = Full load current rating (IED setting ‘Thermal Trip’);
k = 1.05 constant, allows continuous operation up to <1.05 FLC;
P = Steady state preloading before application of the overload.
The time to trip varies depending on the load current carried before application of the
overload, therefore whether the overload was applied from 'hot” or “cold”.
The thermal time constant characteristic may be rewritten as:
- p
e(-t/)=
-1
Where:
= 2/k2 FLC2
and
p = p2/k2 FLC2
Where is the thermal state and is p the prefault thermal state.
7-114 P446/EN/TM/E
MiCOMho P446 7 Operation
Note: A current of 105%s (kFLC) has to be applied for several time constants to cause a
thermal state measurement of 100%.
15.1.2 Dual time constant characteristic (typically not applied for P446)
This characteristic is used to protect oil-filled transformers with natural air cooling, such
as the ONAN (Oil Natural Air Natural) type. The thermal model is similar to that of the
single time constant, except that two time constants must be set.
When there is marginal overloading, heat flows from the windings into the bulk of the
insulating oil. Therefore at low current the replica curve is dominated by the long time
constant for the oil. This protects against a general rise in oil temperature.
When there is severe overloading, heat accumulates in the transformer windings with
little opportunity for dissipation into the surrounding insulating oil. Therefore at high
current the replica curve is dominated by the short time constant for the windings. This
protects against hot spots developing in the transformer windings.
Overall, the dual time constant characteristic provided in the IED protects the winding
insulation from ageing, and to minimize gas production by overheated oil.
Note: The thermal model does not compensate for the effects of ambient temperature
change.
2 - (k.FLC)2
0.4e(-t/) + 0.6e(-t/) =
2 - p2
Where:
1 = Heating and cooling time constant of the transformer windings;
2 = Heating and cooling time constant for the insulating oil.
A graphical solution using a spreadsheet is recommended to solve this equation to give
the operating time (t). The spreadsheet can be set to calculate the current to give a
chosen operating time. The equation to calculate the current is:
Thermal State
Current IA Measurement
Thermal Start Thermal
Current IB 1 Trip Characteristic Thermal Alarm
Current IC Thermal Trip
Reset
Thermal State
Measurerment P1629ENa
Figure 80 shows how the magnitudes of the three phase input currents are compared and
the largest magnitude taken as the input to the thermal overload function. If this current
exceeds the thermal trip threshold setting, a start condition is asserted.
P446/EN/TM/E 7-115
7 Operation MiCOMho P446
Power Fault
swing
3
cycles
PH1
PSB active PSB removed
& minimum including
3Æ faults
threshold
increased P1181ENa
PH2
7-116 P446/EN/TM/E
MiCOMho P446 7 Operation
Both Zone 7 and Zone 8 characteristics are based on the positive sequence impedance
measurement:
V1
Z1 ,
I1
where
V1 is the positive sequence voltage,
+jX
Z8
t
Z7
V1
Z1
I1
R8 R 7 R7
R8 +R
Z 7
Z 8
P446/EN/TM/E 7-117
7 Operation MiCOMho P446
Inital
State :Idle
State :
PSB_Zone.CurrentZone = ZONE8
DDB Disabled: Slow Zone 8 Entered
Power Swing
DeltaT Expired
PSB_Zone.CurrentZone = OUT_OF_ZONE
PSB_Zone.CurrentZone = OUT_OF_ZONE
State :
Zone 7 Entered
State :
PSB_Zone.CurrentZone = ZONE7
DeltaT Expired
DDB Enabled: Slow
Power Swing
Each line of the quadrilateral characteristic uses a comparator to determine the measured
impedance relative to the line.
impedance that may naturally be passing through Zone 1, and could otherwise cause a
spurious trip if all zones were unblocked on fault inception. Any measuring zone that
picks up beyond the two cycle window remains blocked. This minimizes the risk of
tripping for a continued swing that may pass through Zone 1, and could otherwise cause
a spurious trip if all zones were allowed to unblock together.
Allow Trip If a power swing locus stays in a trip zone characteristic for a duration
equal to the zone time delay, the trip is allowed to happen.
Blocking Keeps stability for that zone, even if a power swing locus enters it.
Delayed Unblock Maintains the block for a set duration. If the swing is still
present after the PSB Timeout Set window has expired, tripping is allowed as
normal.
Selection of PSB as Indication only raises an alarm, without blocking any zones.
The PSB Unblock Dly function allows for any power swing block to be removed
after a set period. For a persistent swing that does not stabilize, any blocked
zones are made free to trip once the timer has elapsed. When setting which IEDs
will unblock, consider which IED locations are natural split points for islanding the
power system.
The PSB Reset Delay is a time delay on drop-off timer, which maintains the PSB
detection even after the swing has apparently stabilized. It is used to ensure that
where the swing current passes through a natural minimum and delta I detection
might reset, that the detection does not drop out or chatter. It can therefore be
used to ensure a continual power swing indication when pole slipping (an unstable
out of step condition) is in progress.
0
& selected
distance
zones
P1654ENa
Predictive OST. Splits the system in advance. It minimizes the angle shift
between two ends and aids stability in the split areas.
OST. Splits the system when an out of step condition is detected, which is when a
pole slip occurs.
Predictive OST or OST. Splits the system in advance or when an out of step
condition is detected.
16.2.1.1 Characteristic
Both polygon characteristics are independent and have independent settings for their
respective reactance and resistive reaches.
+jX
Z6
Z5
Predictive Out of
step trip
ZL
Recoverable swing
Z5'
Z6'
Both the inner Zone 5 (Z5) and outer Zone 6 (Z6) positive sequence impedance can be
set to ensure correct Out of Step detection during open pole swing conditions. Therefore
there is only one Z5 and Z6 positive sequence impedance polygon characteristic instead
of six characteristics for each measured loop. The measured positive sequence
impedance is calculated as:
V1
Z1 ,
I1
where V1 and I1 are the positive sequence voltage and current derived from the
measured phase quantities.
During symmetrical power oscillations, there is no difference between phase impedance
loops and positive sequence impedance loops, whereas for the open pole oscillations the
phase and positive sequence impedances are different. This must be taken into account
during testing or commissioning.
All four resistive blinders are parallel, using the common angle setting ‘α’ that
corresponds to the angle of the total system impedance ZT (= ZS + ZL + ZR), where ZS
and ZR are equivalent positive sequence impedances at the sending and receiving ends
7-120 P446/EN/TM/E
MiCOMho P446 7 Operation
and ZL positive sequence line impedance. Tilting of the reactance line and residual
compensation is not implemented.
In Figure 85, the solid impedance trajectory represents the locus for the non-recoverable
power oscillation, also known as pole slip or out of step condition. The dotted impedance
trajectory represents a recoverable power oscillation, usually called swings.
If the resistive part of the positive sequence impedance leaves Z5 with the same
polarity as previously recorded on entering Zone 5, it is considered to be a
recoverable swing. No tripping is issued.
If the resistive part of the positive sequence impedance has the opposite polarity
when exiting Zone 5 to that of the recorded polarity on entering Zone 5, an Out of
Step condition is recognized. This is followed by the tripping if setting option 3 or 4
is selected. If the DeltaT timer did not expire and setting option 3 is selected, the
Out of Step condition is detected, followed by OST operation.
As the tripping mode for the detected Out of Step condition is always 3 ph trip, the
Predictive OST and OST DDB signals are mapped to the 3ph tripping in the default PSL.
Also Out of Step operation blocks the auto-reclose function. The Out of Step tripping
time delay TOST delays the OST tripping command until the angle between internal
voltages between two ends are at 240 deg closing towards 360 deg. This limits the
voltage stress across the circuit breaker. If a fault occurs during the swing condition, the
out of step tripping function is blocked.
The Out of Step algorithm is completely independent from the distance elements and the
setting-free power swing detection function. The load blinder does not have any effect on
the OST characteristics. For the Out of Step operation, the minimum positive sequence
current of 5%In must be present.
P446/EN/TM/E 7-121
7 Operation MiCOMho P446
7-122 P446/EN/TM/E
MiCOMho P446 7 Operation
17 VOLTAGE PROTECTION
P446/EN/TM/E 7-123
7 Operation MiCOMho P446
Figure 87: First stage undervoltage function - single and three phase tripping
mode
Note: Undervoltage protection is phase segregated but the operation of any phase is
mapped to 3 phase tripping in the default PSL.
Each stage of Undervoltage protection can be disabled by a DDB (471 or 472) Inhibit
Vx<.
Figure 88: Overvoltage - single and three phase tripping mode (single stage)
Note: Phase overvoltage protection is phase segregated, but the operation of any phase is
mapped to 3 phase tripping in the default PSL.
Each stage of Overvoltage protection may be disabled by a DDB (473 or 474) Inhibit Vx>
(x = 1, 2).
P446/EN/TM/E 7-125
7 Operation MiCOMho P446
The Compensated overvoltage protection function can be found in the IED menu Volt
Protection. The line impedance settings together with the line charging admittance in
IED menu Line Parameters is used to calculate the remote voltage.
The IED uses the {A,B,C,D] transmission line equivalent model given the following
parameters:
Total Impedance Z z and
Total Susceptance Y y 90 and
Line Length l
The remote voltage is calculated using the following equations:
V r D C V s
I r BA I s
where
Vr, Ir - Voltage and Current at the receiving end.
Vs, Is - Measured (IED) Voltage and Current at the sending end.
A D cosh l
B Zc sinh l
C Yc sinh l
l ZY
1 Z
Zc
Yc Y
Y = Total Line Capacitive Charging Susceptance
Zc = Characteristic Impedance of the line (Surge Impedance).
There are two stages to provide both alarm and trip stages where required.
Both stages are independently settable where Stage 1 may be selected as either IDMT,
DT or Disabled, in the V1>1 Cmp Funct cell. Stage 2 is DT only and is enabled/disabled
in the V1>Cmp Status cell.
The IDMT characteristic on the first stage is defined by the following formula:
t = K/(M - 1)
Where:
K = Time multiplier setting
t = Operating time in seconds
M = Remote Calculated voltage / IED setting voltage (PH-)
7-126 P446/EN/TM/E
MiCOMho P446 7 Operation
18 FREQUENCY PROTECTION
1 Underfrequency
Start
Underfrequency
& & (DT) Underfrequency
Trip
Underfrequency
Timer Block P1640ENa
The functional logic diagram is for the overfrequency function as shown in Figure 90.
Only a single stage is shown as the other stages are identical in functionality. If the
frequency is above the setting and not blocked the DT timer is started and after this has
timed out the trip is produced. Blocking may come from the All_Poledead signal
(selectively enabled for each stage) or the overfrequency timer block.
1 Overfrequency
Start
Overfrequency
& & Definite Time Overfrequency
Trip
Overfrequency
Timer Block P1641ENa
When enabled, the following signals are set by the under/overfrequency logic according
to the status of the monitored functions.
F<1 Timer Block (DDB 1149) - Block Underfrequency Stage 1 Timer
P446/EN/TM/E 7-127
7 Operation MiCOMho P446
7-128 P446/EN/TM/E
MiCOMho P446 7 Operation
Frequency
fn
f1
Slow decay
f2
Rapid decay
Time
P4008ENc
P446/EN/TM/E 7-129
7 Operation MiCOMho P446
Simple CBF, where only CB Fail 1 Timer is enabled. For any protection trip, the
CB Fail 1 Timer is started, and normally reset when the circuit breaker opens to
isolate the fault. If breaker opening is not detected, CB Fail 1 Timer times out and
closes an output contact assigned to breaker fail (using the programmable scheme
logic). This contact is used to backtrip upstream switchgear, generally tripping all
infeeds connected to the same busbar section.
A retripping scheme, plus delayed backtripping. CB Fail 1 Timer is used to route a
trip to a second trip circuit of the same circuit breaker. This requires duplicated
circuit breaker trip coils and is known as retripping. If retripping fails to open the
circuit breaker, a backtrip may be issued following an additional time delay. The
backtrip uses CB Fail 2 Timer, which is also started at the instant of the initial
protection element trip.
CBF elements CB Fail 1 Timer and CB Fail 2 Timer can be configured to operate for
trips triggered by protection elements in the IED or using an external protection trip. The
latter is done by allocating one of the IED opto-isolated inputs to External Trip using the
programmable scheme logic.
Three-phase and phase-segregated outputs of CB Fail 1 Timer and CB Fail 2 Timer are
in PSL.
Independent CB Fail settings are provided for CB1 and CB2.
Where circuit breaker auxiliary contacts are defective, or cannot be relied upon to
definitely indicate that the breaker has tripped.
Where a circuit breaker has started to open but has become jammed. This may
result in continued arcing at the primary contacts, with an additional arcing
resistance in the fault current path. Should this resistance severely limit fault
current, the initiating protection element may reset. Therefore resetting the
element may not give a reliable indication that the circuit breaker has opened fully.
For any protection function that needs current to operate, the IED uses operation of
undercurrent elements (I<) to detect that the necessary circuit breaker poles have tripped
and reset the CB fail timers. However, the undercurrent elements may not be reliable
methods of resetting circuit breaker fail in some applications. For example:
7-130 P446/EN/TM/E
MiCOMho P446 7 Operation
Resetting of the CBF is possible from a breaker open indication (from the IED’s pole dead
logic) or from a protection reset. In these cases resetting is only allowed provided the
undercurrent elements have also reset.
If the CBF protection is initiated by an external protection trip, then two resetting options
are provided which doesn’t necessarily require undercurrent elements (I<) operation: Prot
Reset OR I< and ProtRstOrCBOp&I< (see the table below). These options can be
especially useful if re-tripping is not implemented, since they allow avoiding back-tripping
due to spurious short-time energization of External Trip opto-inputs.
Important Note: If Prot Reset OR I< or ProtRstOrCBOp&I< options is used, External Trip
inputs MUST NOT be connected to Trip Conversion logic inputs in PSL.
P446/EN/TM/E 7-131
7 Operation MiCOMho P446
7-132 P446/EN/TM/E
MiCOMho P446 7 Operation
Setting CB1
3 Ext Trip Reset
0 I < Only
1 CB Open & I <
2 Prot Reset & I <
3 Prot Reset OR I<1
4 Prot Reset OR ( CB
CB1 Open A ph (904) Open & I< )
P4946ENa
‘0’
P446/EN/TM/E 7-133
7 Operation MiCOMho P446
7-134 P446/EN/TM/E
MiCOMho P446 7 Operation
P446/EN/TM/E 7-135
7 Operation MiCOMho P446
SET: Enable
CB1 Fail 1 DDB CB1 Fail2 Trip (835)
Status Disable
SET: Enable
CB1 Fail 2
Status Disable
SET:CB Fail 2
Timer
t DDB CB1 Fail2 Trip A (1675)
0
SET:CB Fail 2
Timer
t DDB CB1 Fail2 Trip B (1676)
0
SET:CB Fail 2
Timer
t DDB CB1 Fail2 Trip C (1677)
0
INTSIG ZCDStateSEF
SET:CB Fail 1 Timer
INTSIG TripStateSEF t
SET:CB Fail 2
Timer t
P4952ENb
0
7-136 P446/EN/TM/E
MiCOMho P446 7 Operation
Setting CB2
3 Ext Trip Reset
0 I < Only
1 CB Open & I <
2 Prot Reset & I <
3 Prot Reset OR I<1
4 Prot Reset OR ( CB
CB2 Open A ph (912) Open & I< )
P4946ENc
‘0’
P446/EN/TM/E 7-137
7 Operation MiCOMho P446
7-138 P446/EN/TM/E
MiCOMho P446 7 Operation
P446/EN/TM/E 7-139
7 Operation MiCOMho P446
7-140 P446/EN/TM/E
MiCOMho P446 7 Operation
Note: If the VT is connected at the busbar side, auxiliary contacts (52a or 52b) must be
connected to the IED for a correct pole dead indication.
P446/EN/TM/E 7-141
7 Operation MiCOMho P446
The VTS > Inhibit or VTS 2> Inhibit elements are used to override a VTS block if a
fault occurs on the system which could trigger the VTS logic. However, once the VTS
block is set, subsequent system faults must not override the block. Therefore the VTS
block is latched after a user settable time delay VTS Time Delay. Once the signal has
latched there are two methods of resetting. The first is manually using the front panel
interface or remote communications, if the VTS condition has been removed. The
second is in Auto mode, by restoring the 3 phase voltages above the phase level detector
settings mentioned previously.
VTS Status can be set to Disabled, Blocking or Indication.
A VTS indication is given after the VTS Time Delay has expired. If the VTS is set to
indicate only, the IED may maloperate, depending on which protection elements are
enabled. In this case the VTS indication is given before the VTS time delay expires, if a
trip signal is given.
P446/EN/TM/E 7-143
7 Operation MiCOMho P446
This scheme can also correctly operate under very low load or even no load conditions,
by the combination of time delayed signals derived from the DDB signals VTS Fast block
and all Poles Dead, to generate the Block Distance DDB.
Note: All non-distance voltage-dependent elements are blocked by the “VTS Fast Block”
DDB.
If a miniature circuit breaker (MCB) is used to protect the voltage transformer ac output
circuits, MCB auxiliary contacts can be used to indicate a three phase output
disconnection. As previously described, it is possible for the VTS logic to operate
correctly without this input. However, this facility has been provided for compatibility with
the current practices of various utilities. Energizing an opto-isolated input assigned to
DDB: MCB/VTS on the IED therefore providess the necessary block.
7-144 P446/EN/TM/E
MiCOMho P446 7 Operation
CTS block
I N>
& Time delay t CTS alarm
V N<
P2130ENa
Operation of the element produces a time-delayed alarm visible on the LCD, an event
record and a DDB 294: CT Fail Alarm, with an instantaneous block (DDB 928: CTS
Block) for inhibition of protection elements. See Figure 106 above.
P446/EN/TM/E 7-145
7 Operation MiCOMho P446
Blocking functions can then be assigned in the PSL as necessary because this detector
does not route directly into the IED’s fixed logic.
20.4 Special weak infeed logic for stub end transformer terminals
The true weak infeed condition is when no current based protection element is sensitive
enough to operate. This is the case when zero or minimal generation is connected at that
terminal, and the prospective level of fault current flowing through the CT is insufficient for
any forward or reverse protection operation. In such cases, the fault is cleared using
either POR or Blocking schemes and by enabling WI Echo + Trip.
However, there could be a specific configuration as shown in Figure 108 that may not be
detected by the IED as a weak infeed condition, even if there is no generation at that end
(left side - IED2).
Figure 108: Weak infeed configuration on stub-fed radial circuit (parallel line is out
of service)
The reason is a star earthed transformer which, in the case of phase to ground and
double phase to ground faults, imposes a very low zero sequence impedance and almost
infinite positive and negative sequence impedance, behaving as a source of zero
sequence current only. In this case the zero sequence current Io dominates I1 and I2 at
the weak end, where all three phase currents approximately equal Io (all in phase and
equal in magnitude). This is true for F1 earth faults at IED2, and for F2 earth faults at
IED1 and IED2. The phase currents are sufficient to the pickup current level detectors in
the IED, aso a true weak infeed condition is not seen by the IED.
In such a stub-end feeding case, IED2 may experience some overreach in the case of
double-phase to ground faults. This is caused by the unusual current distribution making
the IED detect a single-phase fault condition (and potential single pole tripping only in
single pole tripping applications).
For this unusual feeding arrangement, the IED uses a zero sequence stabilizing feature
which measures the dominance of zero sequence current over negative sequence
current (Io/2). It promotes stability by forcing the IED to recognize the above
configuration as a WI condition. It then blocks all distance elements, once the measured
Io/2 ratio exceeds the setting.
7-146 P446/EN/TM/E
MiCOMho P446 7 Operation
21 SYSTEM CHECKS
P446/EN/TM/E 7-147
7 Operation MiCOMho P446
as the line, one from the bus side of CB1, and the third from the bus side of CB2. In most
cases the line VT input is three phase, whereas the bus VTs are single phase.
The bus VT inputs are normally single phase so the system voltage checks are made on
single phases. Also the VT can be connected to either a phase to phase or phase to
neutral voltage. Therefore for correct synchronism check operation, the IED must be
programmed with the appropriate connection. The CS Input setting in the CT AND VT
RATIOS can be set to A-N, B-N, C-N, A-B, B-C or C-A according to the application.
The single phase Bus1 VT and Bus 2 VT inputs each have associated phase shift and
voltage magnitude compensation settings CB1 CS VT PhShft, CB1 CS VT Mag., CB2 CS
VT PhShft and CB2 CS VT Mag., to compensate for healthy voltage angle and magnitude
differences between the Bus VT input and the selected line VT reference phase. This
allows the bus VT inputs to be taken from VT windings with different rated voltages or
phase connections to the reference voltage (for example, they could be taken from VTs
on opposite sides of a transformer). Any voltage measurements or comparisons using
bus VT inputs are made using the compensated values.
The system checks logic comprises two modules, one to monitor the voltages, and one to
check for synchronism.
The voltage monitor determines the voltage magnitudes, frequencies and relative phase
angles of the VT inputs using the same VT inputs as the check sync reference phase
voltage setting CS Input, The Live Line, Dead Line, etc., outputs from the voltage monitor
are qualified by blocking inputs from the P544/P546, external VT supervision, VT
secondary MCB auxiliary switch contacts, and by external inputs mapped in the PSL to
DDBs (1522, etc.) to individually inhibit the output DDBs (888, etc.) for each function.
7-148 P446/EN/TM/E
MiCOMho P446 7 Operation
Two stages of system synchronism check supervision are provided for each circuit
breaker. When required, they control the manual closing and/or auto-reclosing of the
associated circuit breaker. CB1 CS1 and CB1 CS2 supervise CB1, while CB2 CS1 and
CB2 CS2 supervise CB2.
The functionality of the first two stages (CB1 CS1 and CB2 CS1) is the same for each,
but each circuit breaker has individual settings.
The functionality of the second two stages (CB1 CS2 and CB2 CS2) is the same for
each, with each circuit breaker having individual settings, and the functionality is similar to
the first stages, but the second stages have an additional “adaptive” setting.
The synchronism check function can be set to provide appropriate synchronism check
supervision of circuit breaker closing for either synchronous or asynchronous systems.
The overall Check Sync. functionality is shown in Figure 109.
Two independently settable synchronism check functions are provided for each circuit
breaker controlled by the IED. CB1 CS1 or CB1 CS2, or both, can be applied to
supervise closing of circuit breaker CB1. CB2 CS1 or CB2 CS2, or both, can be applied
to supervise closing of circuit breaker CB2.
CB1 CS1 and CB2 CS1 are designed to be applied for synchronism check on
synchronous systems, while CB1 CS2 and CB2 CS2 provide additional features which
may be required for synchronism check on asynchronous systems. In situations where it
is possible for the voltages on either side of a circuit breaker to be either synchronous or
asynchronous depending on plant connections elsewhere on the system, both CBx CS1
and CBx CS2 can be enabled, to provide a permissive close signal if either set of
permitted closing conditions is satisfied.
Each synchronism check function, as well as having the basic maximum phase angle
difference and slip frequency settings, can also be set to inhibit circuit breaker closing if
selected “blocking” conditions such as overvoltage, undervoltage or excessive voltage
magnitude difference are detected. In addition, CB1 CS2 and CB2 CS2 each require the
phase angle difference to be decreasing in magnitude to permit circuit breaker closing,
and each has an optional “Adaptive” closing feature to issue the permissive close signal
P446/EN/TM/E 7-149
7 Operation MiCOMho P446
when the predicted phase angle difference immediately prior to the instant of circuit
breaker main contacts closing (after CB Close time) is as close as practicable to zero.
Slip frequency can be defined as the difference between the voltage signals on either
side of the circuit breaker, and represents a measure of the rate of change of phase
between the two signals.
There are two system synchronism check stages for each circuit breaker. This allows the
circuit breaker closing to be enabled under different system conditions, for example, low
slip / moderate phase angle, or moderate slip / small phase angle.
When the check synchronism criteria is satisfied, a DDB signal CBx CSy OK is set
(x = 1 or 2, y = 1 or 2).
For CB1 CS1 OK DDB (883) to be set, the following conditions are necessary:
Settings Sys Checks CB1 and CB1 CS1 Status must both be Enabled;
AND
Live Line and Live Bus 1 signals are both set;
AND
None of the selected CB1 CS1 Volt. Blk conditions (V<, V>, VDiff) are true;
AND
The measured phase angle magnitude is less than the CB1 CS1 Angle setting;
AND
If CB1 CS1 SlipCtrl setting is Enabled, the measured slip frequency between the
line VT and Bus1 VT is less than the CB1 CS1 SlipFreq setting.
For signal CB1 CS2 OK DDB (884) to be set, the following conditions are necessary:
Settings Sys Checks CB1 and CB1 CS2 Status must both be Enabled;
AND
Live Line and Live Bus 1 signals are both set;
AND
None of the selected CB1 CS1 Volt. Blk conditions (V<, V>, VDiff) are true;
AND
If CB1 CS2 SlipCtrl setting is Enabled, the measured slip frequency between the
line VT and Bus1 VTs is less than the CB1 CS2 SlipFreq setting;
AND
The measured phase angle magnitude is decreasing;
AND
If the CB1 CS2 Adaptive setting is Disabled, the measured phase angle magnitude
is less than the CB1 CS2 Angle setting;
OR
If the CB1 CS2 Adaptive setting is Enabled, AND if the predicted phase angle
when CB1 closes (after CB1 Cl Time setting) is less than the CB1 CS2 Angle
setting AND as close as possible to zero AND still decreasing in magnitude.
For CB2 CS1 OK DDB (1577) to be set, the following conditions are necessary:
Settings Sys Checks CB2 and CB2 CS1 Status must both be Enabled;
AND
Live Line and Live Bus 2 signals are both set;
AND
None of the selected CB2 CS1 Volt. Blk conditions (V<, V>, VDiff) are true;
AND
7-150 P446/EN/TM/E
MiCOMho P446 7 Operation
The measured phase angle magnitude is less than the CB2 CS1 Angle setting;
AND
If CB2 CS1 SlipCtrl setting is Enabled, the measured slip frequency between the
line VT and Bus1 VT is less than the CB2 CS1 SlipFreq setting.
For signal CB2 CS2 OK DDB (1463) to be set, the following conditions are necessary:
Settings Sys Checks CB2 and CB2 CS2 Status must both be Enabled;
AND
Live Line and Live Bus 2 signals are both set;
AND
None of the selected CB2 CS1 Volt. Blk conditions (V<, V>, VDiff) are true;
AND
If CB2 CS2 SlipCtrl setting is Enabled, the measured slip frequency between the
line VT and Bus1 VTs is less than the CB2 CS2 SlipFreqsetting;
AND
In most situations where synchronism check is required, the Check Sync. 1 function
alone provides the necessary functionality and the Check Sync. 2 signals can be ignored.
A
T x 360 Hz. for Check Sync. 2
P446/EN/TM/E 7-151
7 Operation MiCOMho P446
If Slip Control by Frequency + Timer is selected, for an output to be given, the slip
frequency must be less than BOTH the set Slip Freq. value and the value determined by
the Phase Angle and Timer settings.
By enabling both Check Sync. 1, set for condition 1, and Check Sync. 2, set for condition
2, the P446 can be configured to allow CB closure if either of the two conditions is
detected.
For manual circuit breaker closing with synchro check, some utilities might prefer to
arrange the logic to check initially for condition 1 only.
Important note:
Setting the right VT ratios will not adjust the k factors and will have no impact on the
check synch functionality, check synch will only take into account the k factors setting.
The CS voltage settings in system check column are all referenced by the Main VT
ratios.
The Bus-Line Ang [0230] measurement takes into account the C/S Phase kSA
setting.
Following are various possible application scenarios, wherein voltage correction factor
and angular correction factors are applied to match different VT ratios:
Physical Ratio’s CS Correction
Relay Setting Ratio’s
(ph-N Values) Factors
Main VT Ratio
Scenario Main VT Ratio CS VT Ratio CS VT Ratio
(ph-ph) Always kSM kSA
Pri Sec Pri Sec [0A01] [0A02] [0A03] [0A04] [0A14] [0A15]
(kV) (V) (kV) (V) Pri (kV) Sec (V) Pri (kV) Sec (V)
1 220/√3 110/√3 132/√3 100/√3 220 110 132 100 1.1 30º
2 220/√3 110/√3 220/√3 110 220 110 127 110 0.577 0º
3 220/√3 110/√3 220/√3 110/3 220 110 381 110 1.732 0º
In the above examples, the CS VT ratio settings in the relay are so adjusted to a value such
that they are within the acceptable range of the relay inputs and by multiplying a voltage
correction factor, kSA, they are corrected and made equal to the physical ratios. This does
not directly match the physical ratios. It can be phase - phase, phase - neutral or any ratio
which can match the physical VT ratio.
P446/EN/TM/E 7-153
7 Operation MiCOMho P446
22.1 INTRODUCTION
The circuit breaker control and monitoring in the dual-breaker P446 provides single phase
or three phase switching of a feeder controlled by two circuit breakers at a line end, for
example in a one and a half switch configuration or at a mesh type (ring bus) installation.
It can also be set to manage switching of a feeder controlled by a single circuit breaker
This section introduces the operation of the circuit breaker scheme. It describes the
circuit breaker state monitoring, condition monitoring, circuit breaker control, and the
circuit breaker auto-reclose operation.
The control logic for dual circuit breaker switching sequences is complex. For detailed
information see the logic diagrams in the“Circuit Breaker Control and Auto-Reclose
Figures (AR Figures) section at the end of this chapter. Diagrams not included in this
chapter are in the AR figures section and are clearly indicated.
The inputs and outputs of the logic described are, in many cases, DDB signals that are
available to the programmable scheme logic (PSL). These signals are described in
Appendix C of this manual. Other signals are used but are internal to the circuit breaker
control logic. Unlike the DDB signals, these internal signals cannot be accessed using
the programmable scheme logic. They are hard-coded into the application software. A
second supplementary section lists these signals and provides a brief description.
Note: If the menu text does not state which CB, it should be assumed to be CB1 (for
example, CB Operations in the circuit breaker monitoring features). CBx is either CB1
or CB2.
If both sets of contacts are closed, it indicates one of the following conditions:
7-154 P446/EN/TM/E
MiCOMho P446 7 Operation
If any of these conditions exist, an alarm is issued after a time delay. This delay is set in
CB CONTROL settings > CB Status time. A normally open or normally closed output
contact can be assigned to this function using the programmable scheme logic (PSL).
The time delay avoids the alarm tripping due to noise or contact bounce during normal
switching.
Note: The CB Status time setting is applied equally to both controlled circuit breakers.
Under CB CONTROL there are two settings: CB1 Status Input and CB2 Status Input.
Each can be set at one of the following seven options to control CB1 and CB2:
CB Status Description
None
52A 3 pole
52B 3 pole
52A & 52B 3 pole
52A 1 pole
52B 1 pole
52A & 52B 1 pole
If None is selected, no circuit breaker status is available. This directly affects any
function in the IED that uses this signal such as circuit breaker control or auto-reclose.
If only 52A is used (open when the circuit breaker is open, closed when the circuit
breaker is closed), the IED assumes a 52B signal from the absence of the 52A signal.
Circuit breaker status information is available but no discrepancy alarm is issued. This is
also true where only a 52B is used (closed when the circuit breaker is open, open when
the circuit breaker is closed).
If both 52A and 52B are used, status information is available and a discrepancy alarm
CBx Status Alarm (x = 1 or 2) is available, according to the following table. 52A and 52B
inputs are assigned to IED opto-isolated inputs using the PSL.
Auxiliary contact position CB state detected Action
52A 52B
Open Closed Breaker Open Circuit breaker healthy
Closed Open Breaker Closed Circuit breaker healthy
Alarm raised if the condition
Closed Closed CB Failure persists for greater than “CB
Status time”
Alarm raised if the condition
Open Open State Unknown persists for greater than “CB
Status time”
In the internal logic of the P446, the breaker position used in the algorithm is considered
to be open when the CB State Detected is Breaker Open. In all others cases the breaker
position is considered to be closed. Therefore during operation of the circuit breaker, if
the condition 52A=52B=0 or 52A=52B=1 is encountered, the circuit breaker is considered
to be closed.
If single pole tripping is used, an open breaker condition is only given if all three phases
indicate an open condition. Similarly for a closed breaker condition, indication that all
P446/EN/TM/E 7-155
7 Operation MiCOMho P446
three phases are closed must be given. For single pole tripping applications 52A-a, 52A-
b and 52A-c or 52B-a, 52B-b and 52B-c inputs should be used. The circuit breaker state
monitoring logic diagrams for CB1 & CB2 are shown in AR Figure 1 and AR Figure 2.
If inputs relevant to each of the circuit breakers (CB1 and CB2) are available to the IED
using the opto isolated inputs, the logic can determine the state of each circuit breaker.
7-156 P446/EN/TM/E
MiCOMho P446 7 Operation
Note: When in Commissioning Test Mode the circuit breaker condition monitoring counters
are not updated.
The measurement of circuit breaker broken current, operating time and the overall circuit
breaker monitoring logic diagram, are shown in Figure 110, Figure 111, Figure 112,
Figure 113, Figure 114 and Figure 115.
1 t 1
DDB CB1 ExternalTrip A (535)
0
1 cycle
DDB CB1 Trip Output B (524)
1 t 1
DDB CB1 Ext Trip B (536)
0
1 cycle
DDB CB1 Trip Output C (525)
1 t 1
1
DDB CB1 Ext Trip C (537) 0
1 cycle
1
DDB Rst CB1 Data (447)
NOTE: Broken current totals shall not be incremented if the relay is in test mode
P1113ENf
P446/EN/TM/E 7-157
7 Operation MiCOMho P446
1 t 1
DDB CB2 ExtTrip A (539)
0
1 cycle
DDB CB2 Trip OutputB (1602)
1 t 1
DDB CB2 ExtTrip B (540)
0
1 cycle
DDB CB2 Trip OutputC (1603)
1 t 1
1
DDB CB2 ExtTrip C (541) 0
1 cycle
1
DDB Rst CB2 Data (1597)
NOTE: Broken current totals shall not be incremented if the relay is in test mode
P1113ENg
7-158 P446/EN/TM/E
MiCOMho P446 7 Operation
&
1
DDB External Trip3Ph (534)
1 Start
DDB External Trip A (535)
1 Stop
DDB Pole Dead A (892)
1 Start
DDB External Trip B (536)
1 Stop
1 Stop
DDB Pole Dead C (894)
1
DDB Rst CB1 Data (447)
Note: CB Operating Time shall not be produced if the relay P1114ENh
is in test mode
P446/EN/TM/E 7-159
7 Operation MiCOMho P446
&
1
DDB CB2 Ext Trip3Ph (538)
1 Start
DDB CB2 Ext Trip A (539)
1 Stop
DDB Pole Dead A (892)
1 Start
DDB CB2 Ext Trip B (540)
1 Stop
1 Stop
DDB Pole Dead C (894)
1
DDB Rst CB2 Data (1597)
Note: CB Operating Time shall not be produced if the relay P1114ENi
is in test mode
Command : Yes 1
Clear Alarms No
Quiescent State
Command: Yes
CB mon LO reset No
1
Quiescent State
Command: Clear
Clear Alarms
No Operation
Quiescent State
P1115ENh
7-160 P446/EN/TM/E
MiCOMho P446 7 Operation
Reset
Command : Yes 1 DDB CB2 I^ Lockout (1114)
Phase C Broken Current > I^ Lockout Enable &
Reset CB Data
No Setting
Quiescent State Disable
Opto Input DDB Rst CB2 data (1597) 1 1 DDB CB2 Monitor Alm (321)
> I^ lockout Alarm
Command : Yes 1
Clear Alarms No
Quiescent State
Enable
SET: Fault Freq & S Q DDB CB2 FaultFreqLock (1119)
Lock Alarm Disable R
Command: Yes
CB mon LO reset
No
1
Quiescent State
Command: Clear
Clear Alarms
No Operation
Quiescent State
P1115ENi
It is recommended that separate IED output contacts are allocated for remote circuit
breaker control and protection tripping. This enables the control outputs to be selected
using a local/remote selector switch as shown in Figure 116. Where this feature is not
required, the same output contact(s) can be used for both protection and remote tripping.
For the P446, the two circuit breakers can be selectively controlled both locally and
remotely if IED contacts are assigned to allow a separate control trip contact and a
separate control close for each circuit breaker. Therefore there are four output IED
contacts.
P446/EN/TM/E 7-161
7 Operation MiCOMho P446
+ ve
Protection
trip
Trip
Remote 0
control trip Close
Remote
control close
Local
Remote
Trip Close
ve
P0123ENa
A manual trip will be permitted provided that the circuit breaker is initially closed.
Likewise, a close command can only be issued if the circuit breaker is initially open. To
confirm these states it will be necessary to use the circuit breaker 52A and/or 52B
contacts (the different selection options are given from the CBx Status Input cell above).
If no circuit breaker auxiliary contacts are available then this cell should be set to None.
Under these circumstances no circuit breaker control (manual or auto) will be possible.
A circuit breaker close command (Close CB1 for CB1 or Close CB2 for CB2) will initiate
closing of the circuit breaker. The output contact, however, can be set to operate
following a user defined time delay (‘Man Close Delay’). This is designed to give
personnel time to retreat from the circuit breaker following the close command. This time
delay applies to all manual circuit breaker close commands.
The control close cycle can be cancelled at any time before the output contact operates
by any appropriate trip signal, or by activating DDB (443): Rst CB1 CloseDly for CB1 or
by DDB (1419): Rst CB2 CloseDly for CB2.
An Auto Close CB1 or Auto Close CB2 signal from the Auto close logic bypasses the
Man Close Delay time, and the CB1 Close or CB2 Close outputs operate immediately to
close the circuit breaker.
The length of the trip or close control pulse is set using the Trip Pulse Timeand Close
Pulse Time settings respectively. These should be set long enough to ensure the
breaker has completed its open or close cycle before the pulse has elapsed.
Note: The manual trip and close commands are found in the SYSTEM DATA column and
the hotkey menu.
If an attempt to close the circuit breaker is being made and a protection trip signal is
generated, the protection trip command overrides the close command.
If the system check synchronism function is set, this can be enabled to supervise manual
circuit breaker close commands. A circuit breaker close output will only be issued if the
check synchronism criteria are satisfied. Different system check criteria can be selected
for control closing CB1 and CB2. A user settable time delay (Check Sync Time) is
7-162 P446/EN/TM/E
MiCOMho P446 7 Operation
included to supervise manual closure with check synchronizing criteria. If the check
synchronism criteria are not satisfied in this time period following a close command the
IED will lockout and alarm.
Before manual reclosure, in addition to a synchronism check, there is also a circuit
breaker healthy check, CB Healthy, which requires the circuit breaker to be capable of
closing safely (for example, having its closing spring fully charged and/or gas pressure
sufficient for a close and immediate fault trip), as indicated by DDB input CBx Healthy (x
= 1 or 2). A user settable time delay CB Healthy Time is included for manual closure
with this check. If the circuit breaker does not indicate a healthy condition in this time
period following a close command (DDB input is still low when the set time has elapsed)
then the IED will lockout the relevant circuit breaker and set an alarm. This check can be
disabled by not allocating an opto input for DDB “CB Healthy". The signal defaults to high
if no logic is mapped to a DDB in the PSL in the IED.
If auto-reclose is used it may be desirable to block its operation when performing a
manual close. In general, the majority of faults following a manual closure will be
permanent faults and it will be undesirable to allow auto-reclose.
To ensure that auto-reclosing is not initiated for a manual circuit breaker closure on to a
pre-existing fault (switch on to fault), the AUTO-RECLOSE menu setting CB IS Time
(circuit breaker in service time) should be set for the desired time window. This setting
ensures that auto-reclose initiation is inhibited for a period equal to setting “CB IS Time”
following a manual circuit breaker closure. If a protection operation occurs during the
inhibit period, auto-reclosing is not initiated.
Following manual circuit breaker closure, if either a single phase or a three phase fault
occurs during the inhibit period, the circuit breaker is tripped three phase, but auto-
reclose is not locked out for this condition.
If the circuit breaker fails to respond to the control command (indicated by no change in
the state of CBx Status inputs) a ‘CBx Trip Fail’ or ‘CBx Close Fail’ alarm (x = 1 or 2) is
generated after the relevant ‘Trip pulse Time’ or ‘Close Pulse Time’ has expired. These
alarms can be viewed on the IED LCD display, remotely using the IED communications,
or can be assigned to operate output contacts using the IEDs programmable scheme
logic (PSL).
Note: CB Healthy Time timer and Check Sync Time timer described in this menu section are
applicable to manual circuit breaker operations only. These settings are duplicated in
the auto-reclose menu for auto-reclose applications.
For the description of settings and commands related to the various methods for resetting
circuit breaker lockouts, refer to section 22.6.6.23 - Reset CB Lockout.
P446/EN/TM/E 7-163
7 Operation MiCOMho P446
displaying the circuit breaker status screen, the P446 will revert to the default IED screen.
Figure 117 shows the hotkey menu associated with circuit breaker control functionality.
To avoid accidental operation of the trip and close functionality, the hotkey circuit breaker
control commands are disabled for 10 seconds after exiting the hotkey menu.
Figure 118: Circuit breaker control using function keys default PSL
Function key 2 and function key 3 are both enabled and set to Normal Mode and the
associated DDB signals (1097) and (1098) are active high ‘1’ on a key press.
The following DDB signals must be mapped to the relevant function key:
Init Trip CB1 (DDB 439) - Initiate manual circuit breaker CB1 trip
7-164 P446/EN/TM/E
MiCOMho P446 7 Operation
Init Close CB1 (DDB 440) - Initiate manual circuit breaker CB1 close
The programmable function key LEDs are mapped so the LEDs are yellow while the keys
are activated.
The diagram shows the control of CB1 only for simplicity. CB2 can be controlled in a
similar way and the relevant DDB signals are (441) Init Trip CB2, and (442) Init Close
CB2.
If 1Ph or 1/3Ph follower auto-reclose mode is selected, the follower can perform single
phase auto-reclose only if the leader circuit breaker has performed single phase auto-
reclose. If the leader has tripped and reclosed three phase, the follower is also forced to
trip three phase, and will then reclose three phase provided three phase auto-reclose is
permitted for the follower circuit breaker. If the follower circuit breaker trips three phase,
and three phase auto-reclose is not permitted for the follower, then the follower circuit
breaker will lock out without reclosing.
Single phase reclosing is permitted only for the first shot of an auto-reclose cycle. If two
or more shots are enabled, then in a multi-shot auto-reclose cycle the second and
subsequent trips and reclosures will be three phase.
The scheme can be configured to control a single circuit breaker installation. If the menu
setting Num CBs is set to CB1 Only, all menu settings and indications relating to CB2 are
redundant and hidden, and the scheme controls only CB1. If the menu setting Num CBs
is set to CB2 Only, all menu settings and indications relating to CB1 are redundant and
hidden, and the scheme controls only CB2. In these single circuit-breaker configurations,
the selected circuit-breaker auto-reclose can be selected to 1Ph, 3Ph or 1/3Ph AR mode
indicating single phase, three phase, or single/three phase operation.
P446/EN/TM/E 7-165
7 Operation MiCOMho P446
Note 1: Dead Time denotes the open (dead) interval delay of the CB
If asserted, the Block CB AR input blocks the operation of the auto-reclose cycle. If auto-
reclose is in progress, it forces the circuit breaker to lockout.
Typically it is used where auto-reclose may be required. An example is on a transformer
feeder, where auto-reclosing can be initiated from the feeder protection but blocked from
the transformer protection.
Block CB AR can also be used if the auto-reclose cycle is likely to fail due to conditions
associated with the protected circuit. For example, the input can be used if a circuit
breaker indicates, anywhere during the dead time, that it can not switch. This may be
due to low gas pressure or loss of vacuum alarm.
P446/EN/TM/E 7-167
7 Operation MiCOMho P446
Note: These signals are not used to trip the circuit breaker but do initiate auto-reclose. To
trip the circuit breaker directly they could be assigned to the trip contacts of the IED in
the PSL.
To initiate auto-reclosing, the following DDB signals can be mapped from opto inputs
using the PSL.
DDB (535): CB1 Ext Trip A
DDB (536): CB1 Ext Trip B
DDB (537): CB1 Ext Trip C
DDB (534): CB1 Ext Trip 3Ph
DDB (539): CB2 Ext Trip A
DDB (540): CB2 Ext Trip B
DDB (541): CB2 Ext Trip C
DDB (538): CB2 Ext Trip 3Ph
Note: For single phase auto-reclose these signals must be mapped in the PSL as shown in
the default.
1571) and CB2 Succ 1P AR (DDB 1451) generated by the logic for CB1 and CB2
respectively.
The CB1 AR 3p InProg (DDB 844) and CB2 AR 3p InProg (DDB 1411) output signals
indicate that three phase auto-reclose is in progress. The outputs remain high from
protection initiation until lockout, or successful reclosure of the circuit breaker which is
indicated by the circuit breaker successful auto-reclose signals, CB1 Succ 3P AR (DDB
852) and CB2 Succ 3P AR (DDB 1452) for generated by the logic for CB1 and CB2
respectively.
Any ‘auto-reclose lockout’ condition resets all ‘auto-reclose in progress’ signals
associated with that circuit breaker, such as ARIP.
Note: In a dual circuit breaker application, the settings describing single and three phase
auto-reclose AR 1P AR 3P and AR 1/3P below would change in the dual breaker case
to reflect the mode of the leader circuit breaker L1P, L3P, L1/3P.
The single phase auto-reclose in progress signal CB1 AR 1p InProg (DDB 845) is reset,
the three phase auto-reclose in progress signal CB1 AR 3p InProg (DDB 844) is set, and
the three phase dead timer 3P AR DT Shot 1 is started.
At the end of the relevant dead time, provided system conditions are suitable, a circuit
breaker close signal is given. The system conditions to be met for closing are that the
system voltages are in synchronism or that the dead line/live bus or live line/dead bus
conditions exist, indicated by the internal system check synchronizing element, and that
the circuit breaker closing spring, or other energy source, is fully charged as indicated by
the CB Healthy input. The circuit breaker close signal is cut-off when the circuit breaker
closes. For single phase auto-reclose no voltage or synchronism check is required as
synchronizing power is flowing in the two healthy phases. For three phase auto-
reclosing, for the first shot only, auto-reclose can be performed without checking that the
voltages are in synchronism using a setting. This setting, CBxL SC Shot 1, can be set to
Enabled to perform synch-checks on shot 1 for CB1 or CB2, or Disabled to not perform
the checks.
When the circuit breaker has closed, the Set CB1 Close (DDB 1565) signal from the CB
autoclose logic goes high and the Reclaim Time starts. If the circuit breaker has
remained closed and not tripped again when the reclaim timer expires, the auto-reclose
cycle is complete. Signal CB1 Succ 1P AR (DDB1571) or CB1 Succ 3P AR (DDB 852) is
generated to indicate the successful reclosure. These signals also increment the relevant
circuit breaker successful auto-reclose shot counters CB1 SUCC SPAR, CB1 SUCC
3PAR Shot1, CB1 SUCC 3PAR Shot2, CB1 SUCC 3PAR Shot3 and CB1 SUCC 3PAR
Shot4, as well as resetting the circuit breaker auto-reclose in progress CB1 ARIP signal.
If the protection operates and circuit breaker trips during the reclaim time the IED either
advances to the next shot in the programmed auto-reclose cycle, or, if all programmed
reclose attempts have been made, the circuit breaker goes to lockout. Every time the IED
trips the sequence counter is incremented by 1 and the reclaim time starts again after
each shot, following the Set CB1 Close signal going high again.
For multi-phase faults the auto-reclose logic can be set to allow auto-reclose block for 2
and 3 phase faults or to allow auto-reclose block for 3 phase faults only using the setting
Multi Phase AR in the AUTORECLOSE settings, where the options are Allow Autoclose ,
BAR 2 & 3 ph and BAR 3 Phase.
7-170 P446/EN/TM/E
MiCOMho P446 7 Operation
CB1/CB2 AR 1p in
Progress
CB1/CB2 AR 3p in
Progress
Follower Time(1p)
P4352ENa
P446/EN/TM/E 7-171
7 Operation MiCOMho P446
7-172 P446/EN/TM/E
MiCOMho P446 7 Operation
P446/EN/TM/E 7-173
7 Operation MiCOMho P446
The auto-recloser is enabled when the AR In Service DDB (1385) goes high. To achieve
this, as well as enabling the CONFIGURATION > Auto-reclose setting, the following
conditions must be met.
Auto-reclose must be enabled for at least one of the circuit breakers (CB1/CB2).
This is done by enabling DDB input AR Enable CB1 (1609) for CB1 or AR Enable
CB2 (1605), or both, for CB2. Both of these DDB signals default to high if not
mapped in the PSL. If they are not mapped, this part of the logic is always
satisfied.
Auto-reclosing needs to be enabled from an opto input mapped to the AR Enable
DDB (1384), or one of the following conditions must be met.
A menu command from CB CONTROL > HMI Auto-reclose Mode is used to
bring the auto-recloser into service.
For a P446 with IEC 60870-5-103 communications, a standardised enable auto-
reclose command is received through the communications link.
The auto-recloser is brought into service by pulsing the AR Pulse On DDB
(1382).
The auto-reclose status is shown in CB CONTROL > AR Status as either In Service or
Out of Service.
7-174 P446/EN/TM/E
MiCOMho P446 7 Operation
Single phase reclosing is permitted only for the first shot of an auto-reclose cycle. If two
or more shots are enabled, then, in a multi-shot auto-reclose cycle, the second and
subsequent trips and reclosures will always be three phase.
The settings for the reclosing modes are affected by the number of circuit breakers, Num
CBs, setting in the AUTO-RECLOSE column of the menu.
Where the selected follower auto-reclose mode supports single phase tripping, the
follower can perform single phase auto-reclose only if the leader circuit breaker has
performed single phase auto-reclose. If the leader has tripped and reclosed three phase,
the follower is also forced to trip three phase. The follower will reclose three phase
provided three phase auto-reclose is permitted for the follower circuit breaker. If the
follower circuit breaker trips three phase and three phase auto-reclose is not permitted for
the follower, then the follower circuit breaker locks out without reclosing.
Auto-reclose initiation will start an auto-reclose for any circuit breaker that is in service
and enabled for auto-reclose: CB1 auto-reclose will start if CB1 is in service and enabled
for auto-reclose; CB2 auto-reclose will start if CB2 is in service and enabled for auto-
reclose.
When an auto-reclose cycle is started, the relevant circuit breaker auto-reclose in
progress CB1 ARIP and/or CB2 ARIP signal is set, and remains set until the end of the
cycle for the associated circuit breaker. The end of the cycle is signified by successful
reclosure, or by lockout.
7-176 P446/EN/TM/E
MiCOMho P446 7 Operation
P446/EN/TM/E 7-177
7 Operation MiCOMho P446
Single phase reclose as Follower (provided the leader is also selected to single
phase auto-reclose);
Three phase reclose as Leader (with or without follower);
Three phase reclose as Follower;
DT Start by Prot
3PDTStart WhenLD
DTStart by CB Op.
The DT Start by Prot setting is always visible and has three options Protection Reset,
Protection Op, and Disable. These options set the basic conditions for starting the dead
time.
The ‘dead time started by protection operation’ condition can, optionally, be qualified by a
check that the line is dead.
The ‘dead time started by protection reset’ condition can, optionally, be qualified by a
check, that the circuit breaker is open, as well as by an optional check that the line is
dead (note*).
If the DT Start by Prot is set to Disable, the circuit breaker must be open for the dead time
to start. This condition can, optionally be qualified by a check that the line is dead
(note*).
The qualification to check that the ‘line is dead’ is provided by setting 3PDTStart WhenLD
to Enabled.
The qualification to check that the ‘circuit breaker is open’ is provided by setting DTStart
by CB Op to Enabled.
In a dual circuit breaker scheme (Num CBs set to Both CB1 & CB2) if the DTStart by CB
Op is set to enabled, both circuit breakers must be tripped to enable the dead time to
start. For a single phase auto-reclose cycle, the leader circuit breaker has to be tripped
single phase. For a three phase auto-reclose cycle, both circuit breakers have to be
tripped three phase.
7-178 P446/EN/TM/E
MiCOMho P446 7 Operation
If the menu setting BF if LFail Cls is set to Disabled, the follower circuit breaker will
reclose even if the leader circuit breaker fails to reclose (for example, due to the absence
of a CB Healthy signal). When BF if LFail Cls is set to Disabled, an additional menu
setting Dynamic F/L becomes visible to further control the operation of the follower circuit
breaker. If the setting Dynamic F/L is set to Enabled, the follower circuit breaker will
reclose with no deliberate additional delay, i.e. at approximately the same instant that the
leader circuit breaker would have closed if it had been healthy. If the menu setting
Dynamic F/L is set to Disabled, the follower circuit breaker will reclose after an additional
delay equal to the set Follower Time.
If the menu setting BF if LFail Cls is set to Enabled then, if the leader circuit breaker fails
to reclose, the follower circuit breaker cycle is cancelled and auto-reclosing of both circuit
breakers is locked out.
The follower circuit breaker must be open for the follower delay time to start. For a single
phase follower auto-reclose cycle, the follower circuit breaker has to be open single
phase. For a three phase follower auto-reclose cycle, the follower circuit breaker has to
be open three phase.
When the follower delay time has timed out, the relevant internal signal CBxSPFTCOMP
or CBx3PFTCOMP (x = 1 or 2) is applied to the CB AutoClose logic, described later in
section 22.6.6.16 to indicate that the follower time is complete.
CB1 SPDTCOMP
CB1 3PDTCOMP
CB2 SPDTCOMP
CB2 3PDTCOMP
CB1 SPFTCOMP
CB1 3PFTCOMP
CB2 SPFTCOMP
CB2 3PFTCOMP
The auto close logic checks that all necessary conditions are satisfied before issuing a
AutoClose CB1 or AutoClose CB2 signal to the CB1 and CB2 overall control scheme as
shown in the AR Figure 43 and AR Figure 44. (logic diagram supplement) described in
section 22.5.
For any reclosure, the circuit breaker must be healthy (mechanism OK to close, and retrip
if necessary) and it should not be in a lockout state.
For any single phase reclosure, the circuit breaker must be open on one phase. For any
three phase reclosure, the circuit breaker must be open on all three phases and the
appropriate system check conditions (live bus/dead line, synch check etc) must be
satisfied. The system check conditions for CB1 leader reclose, CB2 leader reclose, CB1
follower reclose and CB2 follower reclose are independently selectable by menu settings
and are described in section 22.6.6.20.
The auto close signals (AutoClose CB1, AutoClose CB2) sent to the circuit breaker
control scheme are pulses lasting 100 milliseconds. Another pair of signals Set CB1
Close & Set CB2 Close, DDBs (1565/1449) are set in conjunction with the auto close
signals, but these remain set until either the end of the auto-reclose cycle, or the next
P446/EN/TM/E 7-179
7 Operation MiCOMho P446
protection operation. These signals are used to initiate the Reclaim timing logic and the
CB AR Shots Counters logic, described in sections 22.6.6.17 to 22.6.6.19.
7-180 P446/EN/TM/E
MiCOMho P446 7 Operation
For either circuit breaker, at the completion of any dead time or follower time, the logic
starts an AR CBHealthy timer. If the CB Healthy signal (DDB 436 or 437) becomes high
before the set time is complete, the timer stops and, if all other relevant circuit breaker
closing conditions are satisfied the scheme issues the CB AutoClose signal. If the CB
Healthy signal, (DDB 436 or 437) signal stays low, then at the end of the set AR
CBHealthy time an AR CB Unhealthy alarm signal (DDB 307 or 329) is set. This forces
the circuit breaker auto-reclose sequence to be cancelled.
Additionally, for either circuit breaker, at the completion of any three phase dead time or
three phase follower time, the logic starts an AR CheckSync Time. If the circuit breaker
synchro-check OK signal {“CB L SCOK “ (DDB 1573 or1455) or CB F SCOK (DDB1491
or1456)} goes high before the set time is complete, the timer stops and, if all other
relevant circuit breaker closing conditions are satisfied, the scheme issues the CB
AutoClose signal. If the System check OK signal stays low, then at the end of the AR
CheckSync Time an alarm AR CB No C/S (DDB 308 or 330) is set which informs that the
check synchronism is not satisfied for that circuit breaker and forces the auto-reclose
sequence to be cancelled.
All the counter contents are accessible through the CB CONTROL column of the menu.
For each individual circuit breaker, these counters can be reset either by user commands
Reset CB1 Shots or Reset CB2 Shots from the CB CONTROL settings column, or by
activation of the relevant input Ext Rst CB1 Shots or Ext Rst CB2 Shots (DDB 1518 or
1418) mapped in the PSL.
For three phase auto-reclosing and control closing of the circuit breakers, system voltage
checks are separately selectable for :-
In the AUTORECLOSE settings, if the Num CBs is set to CB1 Only or CB2 Only, then the
operation of the circuit breaker will be the same as described for the corresponding
leader circuit breaker (for example CB1 operation will be the same as described by CB1L
in the diagrams and descriptions.
The system check options for each circuit breaker are enabled or disabled in the CBx SC
all setting (x = 1L, 2L, 1F, 2F) in the AUTORECLOSE column of the menu. If set to
Disabled, then no system checks are required on any shot, and the relevant settings are
invisible. Otherwise, the system check options that can be enabled for each breaker (as
leader or follower) are:-
System check option Setting
System checks not required for first shot of auto-
CBx SC Shot1
reclose
Fast synchronism check (note 2) CBx SC ClsNoDly
Check synchronism stage 1 (note 1) CBx SC CS1
Check synchronism stage 2 (note 1) CBx SC CS2
Dead line / Live Bus CBx SC DLLB
Live Line / Dead bus CBx SC LLDB
Dead line / Dead bus CBx SC DLDB
Note 1: Two separate (independent) system synchronism check stages are available for each
circuit breaker. Each stage has different slip frequency and phase angle settings as
described in section 21.1.
Note 2: A fast synchronism check auto-reclose option is available for the three phase auto-
reclose as leader circuit breaker, by menu setting CBx SC ClsNoDly. When the
setting is enabled, then if the line and bus come into synchronism (i.e. line energised
from remote end) at any time after the three phase dead time has started, a
AutoClose CB signal is issued immediately without waiting for the dead time to
elapse. This option is sometimes required for the second line end to reclose on a line
with delayed auto-reclosing (typical cycle: first line end reclose after dead time with
live bus & dead line, then second line end reclose immediately with live bus & live line
in synchronism).
Manual reclosing for each circuit breaker is controlled according to the settings in the
SYSTEM CHECKS column of the menu. The system check options for each circuit
breaker are enabled or disabled in the CBxM SC all setting (x = 1 or 2) in the SYSTEM
CHECKS column of the menu. If set to Disabled, then no system checks are required for
manual closure, and the relevant settings are invisible. Otherwise, the system check
options that can be enabled for each breaker (as leader or follower) are:-
System check option Setting
Check synchronism stage 1
CBxM SC CS1
(refer note 1 above)
7-182 P446/EN/TM/E
MiCOMho P446 7 Operation
Protection operation during reclaim time. If, following the final reclose attempt, the
protection operates during the reclaim time, the IED will be driven to lockout and
the auto-reclose function will be disabled until the lockout condition is reset.
Persistent fault. A fault is considered persistent if the protection re-operates after
the last permitted shot.
Block auto-reclose. The block auto-reclose logic can cause a lockout if auto-
reclose is in progress. If asserted, the Block CBx AR input (DDB 448 /1421)
mapped in the PSL will, if auto-reclose is in progress, block auto-reclose and cause
a lockout.
Multi phase faults. The logic can be set to block auto-reclose either for two phase
or three phase faults, or to block auto-reclose for three phase faults only. For this,
the setting Multi Phase AR applies, where the options are Allow AR, BAR 2&3
Phase & BAR 3 Phase in the AUTORECLOSE column of the menu.
Protection function selection. The protection functions can be individually selected
to block auto-reclose and force lockout. If enabled, the protection functions in the
AUTORECLOSE column of the menu can be set to “Initiate AR”, “No Action” or
“Block AR”. Selecting Block AR blocks auto-reclose and forces lockout if the
protection function operates.
Circuit breaker failure to close. If the circuit breaker fails to close because, for
example, the circuit breaker springs are not charged, the gas pressure is low, or
there is no synchronism between the system voltages indicated by the AR CBx
Unhealthy and
AR CBx No Checksync alarms, auto-reclose will be blocked and forced to lockout.
Circuit breaker open at the end of the reclaim time. An auto-reclose lockout is
forced if the circuit breaker is open at the end of the reclaim time.
P446/EN/TM/E 7-183
7 Operation MiCOMho P446
If CB1 or CB2 is locked out, the logic generates the alarms CBx AR Lockout (DDB 306
/328) for the corresponding circuit breaker. In this condition, auto-reclose of the circuit
breaker cannot be initiated until the corresponding lockout has been reset. The methods
of resetting from the lockout state are discussed in the next section.
Circuit breaker lockout, can also be caused by the circuit breaker condition monitoring
functions:-
Maintenance lockout,
Excessive fault frequency lockout,
Broken current lockout,
Circuit breaker failed to trip,
Circuit breaker failed to close,
Manual close failure - no check synchronism / circuit breaker unhealthy situation.
These lockout alarms are mapped to a signals CBx mon LO Alarm (DDBs 300 & 322 for
CB1 and CB2 respectively) and CBx LO Alarm. (DDBs 860 & 1599 for CB1 and CB2
respectively).
7-184 P446/EN/TM/E
MiCOMho P446 7 Operation
P446/EN/TM/E 7-185
7 Operation MiCOMho P446
23 MEASUREMENTS
Ip mZr (1m)Z Iq
Zsp Zsq
Vp Rf
Ep Eq
If
P0124ENa
7-186 P446/EN/TM/E
MiCOMho P446 7 Operation
P446/EN/TM/E 7-187
7 Operation MiCOMho P446
IpZr
Vp
If = 0
Vp IpZr
P0125ENa
i.e.:
Phase advanced vector Vp
= Vp [cos(s) + jsin(s) ] * [ sin(d) + jcos(d) ]
= Vp [-sin(s-d) + jcos(s-d) ]
Phase advanced vector pZr
= pZr [cos (e) + jsin (e) ] * [sin (d) + jcos (d) ]
= pZr [-sin(e-d) + jcos(e-d) ]
Therefore, from equation 1:
m = Vp ÷ (p * Zr) at f = 0
= Vp sin(s-d) / (pZr * sin(e-d))
Where:
d = Angle of fault current f
s = Angle of Vp
e = Angle of pZr
Therefore the IED evaluates m which is the fault location as a percentage of the fault
locator line impedance setting and then calculates the output fault location by multiplying
this by the line length setting. When calculated the fault location can be found in the fault
record under the VIEW RECORDS column in the Fault Location cells. Distance to fault is
available in kilometers, miles, impedance or percentage of line length.
compensation is achieved by taking an input to the IED from the residual circuit of the
current transformers in the parallel line.
P446 provides mutual compensation for both the fault locator function, AND the distance
protection zones.
P446/EN/TM/E 7-189
7 Operation MiCOMho P446
24 COMMUNICATIONS SETTINGS
Allowed:
Poll Class 1 (read spontaneous events)
Poll Class 2 (read measurands)
GI sequence (ASDU7 'Start GI', Poll Class 1)
Transmission of Disturbance Records sequence (ASDU24, ASDU25, Poll Class 1)
Time Synchronization (ASDU6)
General Commands (ASDU20), namely:
INF23 activate characteristic 1
INF24 activate characteristic 2
INF25 activate characteristic 3
INF26 activate characteristic 4
Blocked:
Write parameter (=change setting) (private ASDUs)
General Commands (ASDU20), namely:
INF16 auto-recloser on/off
INF19 LED reset
Private INFs (e.g. CB open/close, control inputs)
Allowed:
Read settings, statuses, measurands
Read records (event, fault, disturbance)
Time Synchronization
Change active setting group
Blocked:
Write settings
All controls, including:
Reset Indication (Trip LED)
Operate control inputs
7-190 P446/EN/TM/E
MiCOMho P446 7 Operation
CB operations
Auto-reclose operations
Reset demands
Test LEDs & contacts
Allowed:
Read statuses, measurands
Generate reports
Extract disturbance records
Time synchronization
Change active setting group
Blocked:
All controls, including:
Enable/disable protection
Operate control inputs
CB operations (Close/Trip, Lock)
Reset LEDs
Through careful scheme logic design, the activations of these read only signals can be
facilitated via Opto Inputs, Control Inputs and Function Keys.
These DDBs are available in every build, however they are effective only in Courier, IEC
60870-5-103 build and in latest IEC 61850 (firmware version 57 onwards). The setting
cells are not available in DNP3.0.
P446/EN/TM/E 7-191
7 Operation MiCOMho P446
To avoid the event buffer from being filled with unnecessary time sync. events, it is
possible to ignore any event that is generated by the time sync. opto input. This can be
done by applying the following settings:
Menu Text Value
RECORD CONTROL
Opto Input Event Enabled
Protection Event Enabled
DDB 63 - 32 (Opto Inputs) Set “Time Sync.” associated opto to 0
To improve the recognition time of the time sync. opto input by approximately 10 ms, the
opto input filtering could be disabled. This is achieved by setting the appropriate bit to 0
in the Opto Filter Cntl. cell (OPTO CONFIG. column). Disabling the filtering may make
the opto input more susceptible to induced noise. Fortunately the effects of induced
noise can be minimized by using the methods described in the Software Design chapter.
7-192 P446/EN/TM/E
MiCOMho P446 7 Operation
26 CONTROL INPUTS
The control inputs function as software switches that can be set or reset either locally or
remotely. These inputs can be used to trigger any function that they are connected to as
part of the PSL. There are three setting columns associated with the control inputs that
are: CONTROL INPUTS, CTRL. I/P CONFIG. and CTRL. I/P LABELS. The function of
these columns is described below:
Menu text Default setting Setting range Step size
CONTROL INPUTS
Ctrl I/P Status 00000000000000000000000000000000
Control Input 1 No Operation No Operation, Set, Reset
Control Input 2 to 32 No Operation No Operation, Set, Reset
The Control Input commands can be found in the ‘Control Input’ menu. In the ‘Ctrl. /P
status’ menu cell there is a 32 bit word which represent the 32 control input commands.
The status of the 32 control inputs can be read from this 32-bit word. The 32 control
inputs can also be set and reset from this cell by setting a 1 to set or 0 to reset a
particular control input. Alternatively, each of the 32 Control Inputs can be set and reset
using the individual menu setting cells ‘Control Input 1, 2, 3’ etc. The Control Inputs are
available through the IED menu as described above and also via the rear
communications.
In the programmable scheme logic editor 32 Control Input signals, DDB 191 - 223, which
can be set to a logic 1 or On state, as described above, are available to perform control
functions defined by the user.
Menu text Default setting Setting range Step size
CTRL. I/P CONFIG.
Hotkey Enabled 11111111111111111111111111111111
Control Input 1 Latched Latched, Pulsed
Ctrl Command 1 Set/Reset Set/Reset, In/Out, Enabled/Disabled, On/Off
Control Input 2 to 32 Latched Latched, Pulsed
Ctrl Command 2 to 32 Set/Reset Set/Reset, In/Out, Enabled/Disabled, On/Off
]
Menu text Default setting Setting range Step size
CTRL. I/P LABELS
Control Input 1 Control Input 1 16 character text
Control Input 2 to 32 Control Input 2 to 32 16 character text
The CTRL. I/P CONFIG. column has several functions one of which allows the user to
configure the control inputs as either ‘latched’ or ‘pulsed’. A latched control input remains
in the set state until a reset command is given, either by the menu or the serial
communications. A pulsed control input, however, remains energized for 10 ms after the
set command is given and then resets automatically (no reset command required).
In addition to the latched/pulsed option this column also allows the control inputs to be
individually assigned to the Hotkey menu by setting ‘1’ in the appropriate bit in the Hotkey
Enabled cell. The hotkey menu allows the control inputs to be set, reset or pulsed
without the need to enter the CONTROL INPUTS column. The Ctrl. Command cell also
allows the SET/RESET text, displayed in the hotkey menu, to be changed to something
more suitable for the application of an individual control input, such as ON/OFF, IN/OUT
etc.
P446/EN/TM/E 7-193
7 Operation MiCOMho P446
The CTRL. I/P LABELS column makes it possible to change the text associated with
each individual control input. This text is displayed when a control input is accessed by
the hotkey menu, or it can be displayed in the PSL.
Note: Except for pulsed operation, the status of the control inputs is stored in non
volatile memory. If the auxiliary supply is interrupted, the status of all inputs is
recorded. Once the auxiliary supply is restored, the status of the control inputs is
restored to that of before the supply failure. If the battery is missing or discharged,
the control inputs are set to logic 0 once the auxiliary supply is restored.
7-194 P446/EN/TM/E
MiCOMho P446 7 Operation
Fig 1
52A&52B 1Pole
&
&
& &
XOR &
&
&
&
XOR &
&
P446/EN/TM/E 7-195
7 Operation MiCOMho P446
Fig 2
&
1 DDB:CB2 Open Aph(912)
& 1
&
& &
XOR &
&
&
&
XOR &
&
1 DDB:CB2 Open Cph(914)
& 1
CB Status time
&
1 t DDB:CB2 Status Alm(323)
0
&
7-196 P446/EN/TM/E
MiCOMho P446 7 Operation
Fig 3
2 Fig 16,21,24,28,36
2 Fig 17,21,24,28,36
P4098ENa
Fig 4
Setting:
NUM CBs : CB1 Only
CB1 Only/
CB2 Only/ 1
Both CB1 BothCB1&CB2 & CBIST
&CB2 CBISMT
Logic 1 & S
Q DDB: CB1 In Service(1526)
R
Fig 8,55,56
1
Fig 16 DDB: CB1 ARIP(1544)
P4099ENa
P446/EN/TM/E 7-197
7 Operation MiCOMho P446
Fig 5
Config Setting:
AutoReclose: Enable
Enable/Disable & IntSig: AR DISABLED
Fig 6
Setting:
Leader by Menu
Leader Select by:
Leader by Menu/
Leader by Opto
Leader by Opto/ &
Leader by Control
Leader by Control
Setting: &
Sel LeaderCB1
Select Leader:
Sel LeaderCB1/
Sel LeaderCB2 Sel LeaderCB2
Setting:
NUM CBs : CB1 Only
CB1 Only/ &
CB2 Only/ BothCB1&CB2
Both CB1
&CB2 CB2 Only
7-198 P446/EN/TM/E
MiCOMho P446 7 Operation
Fig 7
&
&
SD
Int Sig: Pref LCB2 Q
Fig 6 R
& 1 Int Sig: SETLCB2
Fig 8
Fig 8 DDB: CB1 NOAR(1528)
&
&
P446/EN/TM/E 7-199
7 Operation MiCOMho P446
7-200 P446/EN/TM/E
MiCOMho P446 7 Operation
Setting:
NUM CBs :
CB 1 Only Fig 9
CB 2 Only
Both CB1&CB2
&
&
Note
1
When Leader/Follower AR Mode is
set via optos there are 7 invalid
& combinations of optos that can be
selected. This logic detects these
combinations and on a trip forces
Setting: both CB1 & CB2 to lockout.
AR Mode &
AR 1P 1
AR 1/3P
AR 3P &
AR Opto 1
&
DDB: Lead AR 3P(1498) 5.0s DDB: Invalid AR Mode(331)
0
&
DDB: Follower AR 1P(1409) See
Int Sig: InvalidAR Mode
Note
& Fig 55,56
DDB: Follower AR 3P(1410)
P446/EN/TM/E 7-201
7 Operation MiCOMho P446
Fig 10
&
Fig 18 DDB:Seq Counter =1( 847) 1 & 1
& DDB: AR Force CB1 3P( 858)
Fig 18 DDB:Seq Counter =2( 848)
Setting:
CB2 TripMode
3P 3P
1/3P &
&
Fig 18 DDB: Seq Counter =1(847) 1 & 1 DDB: AR Force CB2 3P( 1485)
&
Fig 18 DDB: Seq Counter =2(848)
Fig 63
Fig 18 DDB: Seq Counter =3(849)
Setting: 1 P4105ENa
NUM CBs:
CB1 Only
CB2 Only
Both CB1&CB 2 1
7-202 P446/EN/TM/E
MiCOMho P446 7 Operation
Fig 11
Setting:
PrFunct1 Trip:
PrFunct1 Trip Initiate AR
No Action
Block AR
1 IntSig:Prot AR Block
Fig 55,56
Setting:
PrFunct2 Trip:
PrFunct2 Trip Initiate AR
1 S
No Action Q
Block AR R 1 IntSig: INIT AR
Fig 13,14,16,17
&
Setting:
PrFunct ‘n’ Trip:
Initiate AR
PrFunct3 Trip
No Action
Block AR
P446/EN/TM/E 7-203
7 Operation MiCOMho P446
Setting:
NUM CBs : CB1 Only
CB1 Only/ 1
CB2 Only/ BothCB1&CB2 2 Int Sig:TAR2/3 PH
Both CB1
&CB2 Fig 53
S
Q
R
1
Fig 13 Int Sig: TARANY
P4108ENa
7-204 P446/EN/TM/E
MiCOMho P446 7 Operation
Fig 14
Setting:
NUM CBs : CB2 Only
CB1 Only/ 1
CB2 Only/ BothCB1&CB2
Both CB1
&CB2
Fig 15
Fig 16 DDB: AR Start(1541)
P446/EN/TM/E 7-205
7 Operation MiCOMho P446
Fig 16
7-206 P446/EN/TM/E
MiCOMho P446 7 Operation
Fig 17
Fig 11 Int Sig: Init AR
Fig 19,21,35,56
Fig 8 DDB: Leader CB2( 1431)
1
& Int Sig: CB 2 FARIP
Fig 8 DDB: Follower CB2( 1433)
Fig 19,21,35, 56
P4112Ena
Fig 18
SEQUENCE COUNTER
Fig 10,26,41,42
DDB: Seq Counter=3(849)
Fig 10,26,41,42
& S
Int Sig:Prot Re-op Q Int Sig: LastShot
Fig 20 R
Fig 20,55,56
Fig 16 DDB: AR START(1541)
P4113Ena
P446/EN/TM/E 7-207
7 Operation MiCOMho P446
P4114Ena
Fig 20
Fig 20 Int Sig: Prot Re-Op & Int Sig: Evolve Lock
Fig 55,56
Fig 18 DDB: Seq Counter=1(847)
Fig 21,55,56
& S
Fig 18 Int Sig:LastShot 0 Q
0.02 R
7-208 P446/EN/TM/E
MiCOMho P446 7 Operation
Fig 21
&
Fig 9 Int Sig: CB1F SPAROK
&
Fig 9 Int Sig: CB2F SPAROK
P446/EN/TM/E 7-209
7 Operation MiCOMho P446
Fig 22
Setting: Pr AR Disable
DT Start by Prot: 1
& DDB: DTOK All(1551)
Pr AR Disable/Pr Pr ProtOp
ProtOp/Pr ProtRes Fig 24,25
Pr ProtRes
&
Setting:
3PDT Start When LD: Disabled
Enabled/Disabled 1
Enabled
&
1
DDB: Dead Line(889)
&
DDB: CB1 AR 1p InProg(845)
&
DDB: CB2 AR 1p InProg(855)
Setting:
DT Start by CB Op : &
Disabled
Enabled/Disabled 1
Fig 3 Enabled
Setting:
NUM CBs :
CB 1 Only
CB 2 Only
Both CB1&CB2
P4117Ena
7-210 P446/EN/TM/E
MiCOMho P446 7 Operation
Fig 24
&
Fig 16 DDB: AR START(1541)
Logic 1
&
Fig 19 Int Sig: CB1LSPAR 1
Logic 1
&
Fig 19 Int Sig: CB2LSPAR
1PDTIME
t Int Sig: SPDTCOMP
0
Fig 24
&
Fig 19 Int Sig: CB1LSPAR
1 DDB:1P DTime(1554)
&
Fig 18,20
Fig 19 Int Sig: CB2LSPAR
Fig 33,34,40
P4119ENa
P446/EN/TM/E 7-211
7 Operation MiCOMho P446
Fig 25
&
Fig 16 DDB: AR START(1541) 1
Logic 1
&
Fig 21 Int Sig: CB1L3PAR 1
Logic 1
&
Fig 21 Int Sig: CB2L3PAR
P4120ENa
Fig 26
1 Int Sig: 3PDTCOMP
Fig 25,26
Fig 25 DDB: OKTIME3P(1555) 3PDTIME1
& t
Fig 18 DDB: Seq Counter=1(847) 0
& t DTIME2
Fig 18 DDB: Seq Counter=2(848) 0
& t DTIME3
Fig 18 DDB: Seq Counter=3(849) 0
DTIME4
& t
Fig 18 DDB: Seq Counter=4(850) 0
P4121ENa
7-212 P446/EN/TM/E
MiCOMho P446 7 Operation
Setting: Fig 27
BF if Lfail Cls: Disabled
Enabled/Disabled
Logic 1
&
Fig 19 Int Sig: CB2FSPAR
1
Logic 1
&
Fig 21 Int Sig: CB2F3PAR
Logic 1
&
Int Sig: CB1FSPAR 1
Fig 19
Logic 1
&
Fig 21 Int Sig: CB1F3PAR
Fig 28
Setting:
Dynamic F/L : Enabled
Enabled/Disable &
Int Sig: CB1 LFRC
1
Int Sig: CB2 LFRC
&
1 DDB:1PF TComp(1561)
Fig 3 Int Sig: CB2OP1P
Fig 28
Fig 19 Int Sig: CB2FSPAR
FOLL Time
S t
Q
Fig 16 DDB: AR START(1541) 1 R 0
&
Fig 19 Int Sig: CB1FSPAR
&
Fig 19 Int Sig: CB2FSPAR
P4123ENa
P446/EN/TM/E 7-213
7 Operation MiCOMho P446
Setting: Fig 29
Dynamic F/L : Enabled
Enabled/Disable &
Fig 29
DDB: CB2 Open 3ph(911)
&
Fig 21 Int Sig: CB1F3PAR
Int Sig: CB13PFTCOMP
& Fig 32,34,39
&
Fig 21 Int Sig: CB2F3PAR
P4124ENa
7-214 P446/EN/TM/E
MiCOMho P446 7 Operation
Logic 1 &
PULSE 0.1S
S
Fig 55 DDB: CB1 AR Lockout(306) Q DDB:Auto Close CB1(854)
1 R
Fig 20 IntSig: PROTREOP Fig 35,43
Fig 16 DDB: ARIP(1542) DDB:Set CB1 Close(1565)
Fig 16,20,34,41,55,56
Fig 16 DDB: CB1 ARIP(1544) & DDB:CB1CONTROL(1566)
DDB: CB1 Closed 3ph(907)
P4127ENa
P446/EN/TM/E 7-215
7 Operation MiCOMho P446
&
Logic 1
PULSE 0.1S
S
Fig 56 DDB: CB2 AR Lockout(328) Q DDB: Auto Close CB2(1448)
1 R
Fig 20 IntSig: PROTREOP Fig 35,44
Fig 16 DDB: ARIP(1542) DDB: Set CB2 Close(1449)
Fig 17,20,34,42,55,56
Fig 17 DDB: CB2 ARIP(1435) & DDB: CB2CONTROL(1450)
DDB: CB2 Closed 3ph(915)
7-216 P446/EN/TM/E
MiCOMho P446 7 Operation
Fig 34
Fig 24 IntSig: CB1SPDTCOMP
&
Fig 32 DDB: Set CB1 Close(1565)
S
Q IntSig: SETCB1SPCL
Fig 26 IntSig: CB13PDTCOMP R
& Fig 35,36
Fig 45 DDB: CB1LSCOK(1573)
Fig 45 DDB: CB1FASTSCOK(1572)
&
Fig 25 DDB: OKTIME3P(1555) &
1
Fig 29 IntSig: CB13PFTCOMP S
& Q IntSig: SETCB13PCL
Fig 47 DDB: CB1F SCOK(1491) R
Fig 35,36
P4129ENa
P446/EN/TM/E 7-217
7 Operation MiCOMho P446
Fig 35
Setting:
Dynamic F/L : Enabled
Enabled/Disable
Fig 16,17
DDB: CB1 Closed 3ph(907) &
Fig 16 DDB: CB1 ARIP(1544)
1
P4130ENa
7-218 P446/EN/TM/E
MiCOMho P446 7 Operation
Fig 35 Fig 36
DDB: 3P Reclaim TComp(1570)
1
Fig 35 DDB: 1P Reclaim TComp(1568)
1 IntSig: CB1ARSUCC
Fig 37 IntSig: RESCB1ARSUCC
Fig 16,37
Fig 35 DDB: 3P Reclaim TComp(1570)
Fig 35 1
DDB: 1P Reclaim TComp(1568)
Fig 17,38
Fig 35 DDB: 3P Reclaim TComp(1570)
1
DDB: 1P Reclaim TComp(1568)
Fig 35
P4131ENa
P446/EN/TM/E 7-219
7 Operation MiCOMho P446
7-220 P446/EN/TM/E
MiCOMho P446 7 Operation
Fig 38
Fig 3 IntSig: CB2OPANY
Setting: Enabled
Res AROKby UI:
Enabled/Disabled Disabled
&
Yes
COMMAND:
Reset AROK Ind
No
Setting: Enabled
Res AROK by NoAR:
Enabled/Disabled Disabled
1 IntSig: RESCB2ARSUCC
Fig 5 IntSig: AR DISABLED &
1
Fig 36
Setting:
NUM CBs :
CB 1 Only
CB 2 Only
Both CB1&CB2
Enabled
Setting:
Res AROK by Ext
Enabled/Disabled Disabled
&
DDB: Ext Rst CB2 AROK(1417)
Enabled
Setting:
Res AROK by TDly:
Enabled/Disabled Disabled
Fig 39
Fig 21 IntSig: CB1L3PAR
Fig 25 DDB: OK Time 3P(1555) &
*Note
Fig 45 DDB: CB1 Fast SCOK(1572) If not mapped in PSL
are defaulted high.
Fig 24 IntSig: CB1SPDTCOMP
Fig 28 IntSig: CB1SPFTCOMP
1 CB Healthy Time
Fig 26 IntSig: CB13PDTCOMP
& S t
Fig 29 IntSig: CB13PFTCOMP Q DDB: AR CB1 Unhealthy(307)
RD 0
Fig 7,10,55
DDB: CB1HEALTHY(436)*
P4134ENa
P446/EN/TM/E 7-221
7 Operation MiCOMho P446
Fig 40
Fig 21 IntSig: CB2L3 PAR
Fig 25 DDB: OK Time3P( 1555) & * Note
DDB: CB2 Fast SCOK( 1454) If not mapped in PSL
Fig 46
are defaulted high
.
Fig 24 IntSig: CB2 SPDTCOMP
1
Fig 28 IntSig: CB2 SPFTCOMP
AR CBHealthy Time
Fig 26 IntSig: CB23 PDTCOMP
& S t
Fig 29 IntSig: CB23 PFTCOMP DDB: AR CB2 Unhealthy( 329)
Q
RD 0
Fig 7,10,56
P4135ENa
7-222 P446/EN/TM/E
MiCOMho P446 7 Operation
Fig 41
CB 1 TOTAL SHOTS
Fig 32 DDB: Set CB1 Close(1565) INC
COUNTER
RES
CB 1 SUCCESSFUL
Fig 36 DDB: CB1 Succ 1P AR(1571) INC
SPAR SHOT 1 COUNTER
RES
CB 1 SUCCESSFUL
& INC
Fig 18 DDB: Seq Counter=1(847) 3 PAR SHOT1 COUNTER
RES
CB 1 SUCCESSFUL
& INC
Fig 18 DDB: Seq Counter=2(848) 3 PAR SHOT2 COUNTER
RES
CB 1 SUCCESSFUL
& INC
Fig 18 DDB: Seq Counter=3(849) 3 PAR SHOT3 COUNTER
RES
CB 1 SUCCESSFUL
& INC
Fig 18 DDB: Seq Counter=4(850)
3 PAR SHOT4 COUNTER
RES
COMMAND:
Reset CB1shots Yes
Yes /No
P446/EN/TM/E 7-223
7 Operation MiCOMho P446
Fig 42
CB 2 TOTAL SHOTS
Fig 33 DDB: Set CB2 Close(1449) INC
COUNTER
RES
CB 2 SUCCESSFUL
Fig 36 DDB: CB2 Succ 1P AR(1451) INC
SPAR SHOT 1 COUNTER
RES
CB 2 SUCCESSFUL
& INC
Fig 18 DDB: Seq Counter=1(847) 3 PAR SHOT1 COUNTER
RES
CB 2 SUCCESSFUL
& INC
Fig 18 DDB: Seq Counter=2(848) 3 PAR SHOT2 COUNTER
RES
CB 2 SUCCESSFUL
& INC
Fig 18 DDB: Seq Counter=3(849) 3 PAR SHOT3 COUNTER
RES
CB 2 SUCCESSFUL
& INC
Fig 18 DDB: Seq Counter=4(850) 3 PAR SHOT4 COUNTER
RES
COMMAND:
Reset CB2shots Yes
Yes /No
7-224 P446/EN/TM/E
MiCOMho P446 7 Operation
Disable
Settings: Local Fig 43
CB Control by
Remote
Local & Remote *Note
If not mapped in PSL
Opto are defaulted high.
Enable opto
Local & Opto
1 initiated
Remote & Opto CB trip and close
Local & Remote & Opto DDB: Control TripCB1(838)
Reset
COMMAND:
Dominont SET: Trip
UI Trip CB1 Pulse Time
Latch
1
& S t
& Q
DDB: Init Trip CB1(439) 0
R & DDB:CB1 Trip Fail(302)
t
& DDB: NoCS CB1ManClose(305)
DDB: CB1 Man SCOK(1574) 0
Fig 51
SET: Check Sync Time
P4138ENa
P446/EN/TM/E 7-225
7 Operation MiCOMho P446
Disable
SET: Local Fig 44
CB Control by
Remote
*No te
Local & Remote
If not mapped in PSL
Opto are defaulted high.
Local & Opto
1 Enable opto initiated
Remote & Opto CB trip and close
Local & Remote & Opto DDB: ControlTripCB2(840)
Reset
COMMAND: Dominont SET: Trip
UI Trip CB2 Latch Pulse Time
1
& S t
& Q
DDB: Init Trip CB2(441) 0
R & DDB: CB2 Trip Fail(324)
t
& DDB: NoCS CB2ManClose(327)
DDB: CB2 Man SCOK(1458) 0
Fig 52
SET: Check Sync Time
P4139ENa
7-226 P446/EN/TM/E
MiCOMho P446 7 Operation
Fig 45
Setting:
CB1L SC ClsNoDly: Enabled
Enabled/Disabled DDB: CB1FASTSCOK(1572)
&
Fig 32,34,39
Setting: 1
CB1L SC CS1: Enabled
Enabled/Disabled
&
DDB:CB1 CS1 OK(883)
Setting:
CB1L SC CS2 Enabled
Enabled/Disabled
&
DDB:CB1 CS2 OK(884)
Setting:
CB1L SC DLLB: Enabled
Enabled/Disabled
&
DDB: Live Bus1(886)
Setting:
CB1L SC LLDB: Enabled
Enabled/Disabled
&
DDB:Dead Bus1(887) 1 DDB: CB1LSCOK(1573)
Fig 32,34,39
Setting:
CB1L SC DLDB: Enabled
Enabled/Disabled
&
DDB:Dead Bus1(887)
Setting:
CB1L SC Shot1: Disabled
Enabled/Disabled
& *Note
Fig 18 DDB: Seq Counter=1(847) If not mapped in PSL
are defaulted high.
Setting:
CB1L SC all: Disabled
Enabled/Disabled &
P446/EN/TM/E 7-227
7 Operation MiCOMho P446
Fig 46
Setting:
CB2L SC ClsNoDly: Enabled
Enabled/Disabled & DDB: CB2FASTSCOK(1454)
Fig 33,34,40
Setting: 1
CB2L SC CS1: Enabled
Enabled/Disabled
&
DDB:CB2 CS1 OK(1577)
Setting:
CB2L SC CS2 Enabled
Enabled/Disabled
&
DDB:CB2 CS2 OK(1463)
Setting:
CB2L SC DLLB: Enabled
Enabled/Disabled
Setting:
CB2L SC LLDB: Enabled
Enabled/Disabled
Setting:
CB2L SC DLDB: Enabled
Enabled/Disabled
Setting:
CB2L SC Shot1: Disabled *Note
Enabled/Disabled If not mapped in PSL
are defaulted high.
&
Fig 18 DDB: Seq Counter=1(847)
Setting:
CB2L SC all: Disabled
Enabled/Disabled &
7-228 P446/EN/TM/E
MiCOMho P446 7 Operation
Fig 47
Setting:
CB1F SC CS1: Enabled
Enabled/Disabled
&
DDB:CB1 CS1 OK(883)
Setting:
CB1F SC CS2 Enabled
Enabled/Disabled
&
DDB:CB1 CS2 OK(884)
Setting:
CB1F SC DLLB: Enabled
Enabled/Disabled
&
DDB: Live Bus1(886)
Setting:
CB1F SC LLDB: Enabled
Enabled/Disabled
Setting:
CB1F SC DLDB: Enabled
Enabled/Disabled
Setting:
CB1F SC Shot1: Disabled
Enabled/Disabled
&
Fig 18 DDB: Seq Counter=1(847)
*Note
Setting: If not mapped in PSL
CB1F SC all: Disabled are defaulted high.
Enabled/Disabled &
P446/EN/TM/E 7-229
7 Operation MiCOMho P446
Fig 48
Setting:
CB2F SC CS1: Enabled
Enabled/Disabled
&
DDB:CB2 CS1 OK(1577)
Setting:
CB2F SC CS2 Enabled
Enabled/Disabled
&
DDB:CB2 CS2 OK(1463)
Setting:
CB2F SC DLLB: Enabled
Enabled/Disabled
&
DDB: Live Bus2(1461)
Setting:
CB2F SC LLDB: Enabled
Enabled/Disabled
Setting:
CB2F SC DLDB: Enabled
Enabled/Disabled
&
DDB: Dead Bus2(1462)
Setting:
CB2F SC Shot1: Disabled
Enabled/Disabled
&
Fig 18 DDB: Seq Counter=1(847)
*Note
Setting: If not mapped in PSL
CB2F SC all: Disabled are defaulted high.
Enabled/Disabled &
P4143ENa
7-230 P446/EN/TM/E
MiCOMho P446 7 Operation
Setting:
Enabled Fig 51
CB1M SC CS1:
Enabled/Disabled
&
DDB:CB1 CS1 OK(883)
Setting:
CB1M SC CS2 Enabled
Enabled/Disabled
&
DDB:CB1 CS2 OK(884)
Setting:
CB1M SC DLLB: Enabled
Enabled/Disabled
Setting:
CB1M SC LLDB: Enabled
Enabled/Disabled
Setting:
CB1M SC DLDB: Enabled
Enabled/Disabled
*Note
Setting:
CB1M SC Required: Disabled If not mapped in PSL
are defaulted high.
Enabled/Disabled &
P446/EN/TM/E 7-231
7 Operation MiCOMho P446
Setting:
CB2M SC CS1: Enabled Fig 52
Enabled/Disabled
&
DDB:CB2 CS1 OK(1577)
Setting:
CB2M SC CS2 Enabled
Enabled/Disabled
&
DDB:CB2 CS2 OK(1463)
Setting:
CB2M SC DLLB: Enabled
Enabled/Disabled
&
DDB: Live Bus2(1461)
Setting:
CB2M SC LLDB: Enabled
Enabled/Disabled
Setting:
CB2M SC DLDB: Enabled
Enabled/Disabled
&
DDB: Dead Bus2(1462)
*Note
Setting: If not mapped in PSL
CB2M SC Required: Disabled are defaulted high.
Enabled/Disabled &
7-232 P446/EN/TM/E
MiCOMho P446 7 Operation
Fig 53
Trip Pulse Time
Fig 13 IntSig: TAR2/3Ph S t
Q
RD 0
& S
DDB:CB1 Open Aph(904)
Q
DDB: CB1 Closed 3ph(907) RD 1
DDB: CB1FailPrTrip(1575)
Fig 55,56
Fig 13 IntSig: TARB
& S
Fig 13 IntSig: TMEM2/3Ph Q
RD
& S
DDB:CB1 Open Bph(905)
Q
DDB: CB1 Closed 3ph(907) RD 1
P4148ENa
P446/EN/TM/E 7-233
7 Operation MiCOMho P446
Fig 54
& S
DDB: CB2 Open 3ph(911)
Q
DDB: CB2 Closed 3ph(915) RD
& S
DDB:CB2 Open Aph(912)
Q
DDB: CB2 Closed 3ph(915) RD 1
DDB: CB2FailPrTrip(1459)
Fig 55,56
Fig 14 IntSig: CB2 TARB
& S
Fig 14 IntSig: CB2 TMEM2/3Ph Q
RD
& S
DDB:CB2 Open Bph(913)
Q
DDB: CB2 Closed 3ph(915) RD
1
& S
DDB:CB2 Open Cph(914)
Q
DDB: CB2 Closed 3ph(915) RD
1
7-234 P446/EN/TM/E
MiCOMho P446 7 Operation
Fig 55
&
Fig 15 IntSig: FLTMEM2P
Fig 43 DDB: CB1 CloseFail (303)
Setting:
BF if Lfail Cls: Enabled
Enabled/ Disabled
Fig 4 &
DDB: CB 1 In Service(1526)
Fig 4 DDB: CB 2 In Service(1428)
DDB: CB2 FailPrTrip(1459) &
Fig 54
P4150ENa
Fig 22 Int Sig: DeadLineLockout
P446/EN/TM/E 7-235
7 Operation MiCOMho P446
Fig 55a
P4151ENa
7-236 P446/EN/TM/E
MiCOMho P446 7 Operation
Fig 56
Fig 15 IntSig: FLTMEM3P
&
Setting: BAR3Ph
Multi Phase AR: 1
Allow Autoclose/BAR BAR2and3Ph
2and3 Ph/BAR 3Phase
Setting:
BF if Lfail Cls: Enabled
Enabled/Disabled
DDB: BlockCB2AR(1421)
Setting: &
NUM CBs :
CB1 Only/
CB2 Only/
Both CB1
&CB2 BothCB1&CB2
Fig 4 &
DDB: CB1 In Service(1526)
Fig 4 DDB: CB2 In Service(1428)
DDB: CB1FailPrTrip(1575) &
Fig 54
P446/EN/TM/E 7-237
7 Operation MiCOMho P446
Fig 56a
Fig 57
Setting:
Res LO by CB IS: Enabled
Enabled/Disabled
&
Fig 4 IntSig: CB1CRLO
Setting:
Res LO by UI: Enabled
Enabled/Disabled
COMMAND:
ResetCB1LO: Yes &
Yes/No
Setting:
Res LO by NoAR: Enabled
Enabled/Disabled
Setting:
Res LO by ExtDDB: Enabled
Enabled/Disabled
&
DDB: Rst CB1 Lockout(446)
Setting:
Res LO by T Delay: Enabled
Enabled/Disabled
LO Reset Time
t &
Fig 55 DDB: CB1AR Lockout(306)
0
P4154ENa
7-238 P446/EN/TM/E
MiCOMho P446 7 Operation
Fig 58
Setting:
Res LO by CB IS: Enabled
Enabled/Disabled
&
Fig 4 IntSig: CB2CRLO
Setting:
Res LO by UI: Enabled
Enabled/Disabled
COMMAND: &
ResetCB2LO: Yes
Yes/No
Setting:
Res LO by NoAR: Enabled
Enabled/Disabled
Setting:
Res LO by ExtDDB: Enabled
Enabled/Disabled
&
DDB: Rst CB2 Lockout(1422)
Setting:
Res LO by T Delay: Enabled
Enabled/Disabled
LO Reset Time
t &
Fig 56 DDB: CB2 AR Lockout(328)
0
P446/EN/TM/E 7-239
7 Operation MiCOMho P446
7-240 P446/EN/TM/E
MiCOMho P446 7 Operation
Fig 60
ConfigurationSetting: Enabled
System Checks:
Enabled/Disabled Disabled 1 DDB:SchkslnactiveCB1(880)
Setting: Enabled
&
System Checks CB1:
Enabled/Disabled Disabled
CB1 CS1CriteriaOK
&
CSVline<
& DDB: CSVline<(1580)
CSVBus1<
& DDB: CSVBus1<(1582)
Check synch settings CSVLine>
BUS1 VT CS1 and operation criteria & DDB: CSVLine>(1581)
are shown
CSVBus1>
& DDB: CSVBus1>(1583)
CB1 CS1VL>VB1
& DDB: CB1 CS1 VL>VB(1586)
CB1 CS1VL<VB1
& DDB: CB1 CS1 VL<VB(1588)
CB1 CS1FL>FB1
& DDB: CB1 CS1 FL>FB(1590)
CB1 CS1FL<FB1
& DDB: CB1 CS1 FL<FB(1591)
CB1 CS2FL>FB1
& DDB: CB1 CS2 FL>FB(1493)
CB1 CS2FL<FB1
& DDB: CB1 CS2 FL<FB(1494)
CB1 CS2AngHigh+
& DDB: CB1 CS2AngHigh+(1495)
CB1 CS2AngHigh-
& DDB: CB1 CS2AngHigh-(1496)
CS1AngRotACW
& DDB: CB1 CS AngRotACW(1594)
CS1AngRotCW
& DDB: CB1 CS AngRotCW(1595)
P446/EN/TM/E 7-241
7 Operation MiCOMho P446
7-242 P446/EN/TM/E
MiCOMho P446 7 Operation
Fig 62
DDB: CB1 AR Lockout(306)
&
&
P446/EN/TM/E 7-243
7 Operation MiCOMho P446
Fig 63
1 S
Q DDB: CB2 Trip Output A (1601)
R
1 S
Setting: Q DDB: CB2Trip Output B (1602)
R
CB2 TripMode
3P 3P 1 S
1 /3P Q DDB: CB2 Trip Output C (1603)
R
S
DDB: PoledeadA(892) & Q DDB: 2/3Ph Fault(527)
1 R
& 1 S
DDB: PoledeadB(893) 1 Q DDB: 3Ph Fault(528)
R
&
1
DDB: PoledeadC(894)
&
P4160ENa
7-244 P446/EN/TM/E
MiCOMho P446 7 Operation
P446/EN/TM/E 7-245
7 Operation MiCOMho P446
Name Description
CB1LFRC Int Sig from “Leader/Follower Logic – 1”
CB1LSPAR Int Sig from “Single Phase AR Cycle Selection”
CB1LSPAROK Int Sig: CB1 OK to SP AR as leader
CB1SPDTCOMP Int Sig: CB1 SP dead time complete
CB1SPFTCOMP Int Sig: CB1 SP follower time complete
CB2 3PDTCOMP Int Sig: CB2 3PAR dead time complete
CB2 3PFTCOMP Int Sig: CB2 3PAR follower time complete
CB2 3POK Int Sig: CB2 OK for 3P AR (leader or follower)
CB2 ARSUCC Int Sig: CB2 auto-reclose sucessful
Int Sig + DDB: Line/Bus2 phase angle in range:
CB2 CS1 AngHigh-
-CB2 CS1 Angle to -180deg
Int Sig + DDB: Line/Bus2 phase angle in range:
CB2 CS1 AngHigh+
+CB2 CS1 Angle to +180deg
CB2 CS1 FL<FB Int Sig + DDB: Bus2 F > (Line F + “CB2 CS1 SlipFreqf”)
CB2 CS1 FL>FB Int Sig + DDB: Line F > (Bus2 F + “CB2 CS1 SlipFreqf”)
Int Sig + DDB: CB2 CS1 is enabled and Line and Bus 2 voltages
CB2 CS1 OK
meet CB2 CS1 settings
CB2 CS1 SlipF< Int Sig + DDB: Line-Bus 2 slip freq < CB2 CS1 SlipFreq setting
CB2 CS1 SlipF> Int Sig + DDB: Line-Bus 2 slip freq > CB2 CS1 SlipFreq setting
CB2 CS1 VL<VB Int Sig + DDB: Bus2 V > (Line V + “CB2 CS1 VDiff”)
CB2 CS1 VL>VB Int Sig + DDB: Line V > (Bus2 V + “CB2 CS1 VDiff”)
Int Sig + DDB: Line/Bus2 phase angle in range:
CB2 CS2AngHigh-
-CB2 CS2 Angle to -180deg
Int Sig + DDB: Line/Bus2 phase angle in range:
CB2 CS2AngHigh+
+CB2 CS2 Angle to +180deg
CB2 CS2FL<FB Int Sig + DDB: Bus2 F > (Line F + “CB2 CS2 SlipFreqf”)
CB2 CS2FL>FB Int Sig + DDB: Line F > (Bus2 F + “CB2 CS2 SlipFreqf”)
Int Sig + DDB: CB2 CS2 is enabled and Line and Bus 2 voltages
CB2 CS2OK
meet CB2 CS2 settings
CB2 CS2SlipF< Int Sig + DDB: Line-Bus 2 slip freq < CB2 CS2 SlipFreq setting
CB2 CS2SlipF> Int Sig + DDB: Line-Bus 2 slip freq > CB2 CS2 SlipFreq setting
CB2 CS2VL<VB Int Sig + DDB: Bus2 V > (Line V + “CB2 CS2 VDiff”)
CB2 CS2VL>VB Int Sig + DDB: Line V > (Bus2 V + “CB2 CS2 VDiff”)
CB2 FARIP Int Sig: CB2 ARIP as follower
CB2 LARIP Int Sig: CB2 ARIP as leader
CB2 Op1P Int Sig: CB2 open single phase
CB2 Op2/3P Int Sig: CB2 open on 2 or 3 phases
CB2 OpAny Int Sig: CB2 open on 1, 2 or 3 phases
CB2 SPOK Int Sig: CB2 OK for SP AR (leader or follower)
CB2 SysCh Off Int Sig + DDB: CB2 CS1 & CB2 CS2checks disabled
CB2 TAR 2/3Ph Int Sig: 2Ph or 3Ph trip & AR initiation CB2
CB2 TARA Int Sig: A Ph trip & AR initiation CB2
CB2 TARB Int Sig: B Ph trip & AR initiation CB2
CB2 TARC Int Sig: C Ph trip & AR initiation CB2
CB2 TMEM 1Ph Int Sig: CB1 1Ph trip +AR AR initiation memory CB2
CB2 TMEM 2/3Ph Int Sig: CB1 2Ph trip +AR AR initiation memory CB2
CB2 TMEM 3Ph Int Sig: CB1 3Ph trip +AR AR initiation memory CB2
CB2CRLO Int Sig: CB2 in service – reset CB2 lockout
7-246 P446/EN/TM/E
MiCOMho P446 7 Operation
Name Description
CB2F3PAR Int Sig from “Three Phase AR Cycle Selection”
CB2F3PAROK Int Sig: CB2 OK to 3Ph AR as follower
CB2FSPAR Int Sig: CB2 SPAR in progress as follower
CB2FSPAROK Int Sig: CB2 OK to SP AR as follower
CB2L3PAR Int Sig from “Three Phase AR Cycle Selection”
CB2L3PAROK Int Sig: CB2 OK to 3Ph AR as leader
CB2LFRC Int Sig: CB2 failed to reclose as leader
CB2LFRC Int Sig from “Leader/Follower Logic – 1”
CB2LSPAR Int Sig from “Single Phase AR Cycle Selection”
CB2LSPAROK Int Sig: CB2 OK to SP AR as leader
CB2SPDTCOMP Int Sig: CB2 SP dead time complete
CB2SPFTCOMP Int Sig: CB2 SP follower time complete
CBARCancel Int Sig: Stop and reset CB1 and CB2 AR In progress
CS VBus1< Int Sig + DDB: Bus1 Volts < CS UV setting
CS VBus1> Int Sig + DDB: Bus1 Volts > CS OV setting
CS VBus2< Int Sig + DDB: Bus2 Volts < CS UV setting
CS VBus2> Int Sig + DDB: Bus2 Volts > CS OV setting
CS VLine< Int Sig + DDB: Line Volts < CS UV setting
CS VLine> Int Sig + DDB: Line Volts > CS OV setting
Int Sig + DDB: Line freq > (Bus1 freq + 0.001Hz)
CS1 Ang Rot ACW
(CS1 Angle Rotating Anticlockwise)
Int Sig + DDB: Bus1 freq > (Line freq + 0.001Hz)
CS1 Ang Rot CW
(CS1 Angle Rotating Clockwise)
Int Sig + DDB: Line freq > (Bus2 freq + 0.001Hz)
CS2 Ang Rot ACW
(CS2 Angle Rotating Anticlockwise)
Int Sig + DDB: Bus2 freq > (Line freq + 0.001Hz)
CS2 Ang Rot CW
(CS2 Angle Rotating Clockwise)
Dead Bus 1 Int Sig + DDB: CS1 V magnitude < Dead Bus 1 setting
Dead Bus 2 Int Sig + DDB: CS2 V magnitude < Dead Bus 2 setting
Dead Line Int Sig + DDB: Line V magnitude < Dead Line setting
Int Sig: When setting “3PDT Start When LD” is set to Enabled and
DeadLineLockout the line does not go dead for a time set by “Dead Line Time” then
this signal will force the auto-reclose sequence to lockout.
ENABLE CB13PDT Int Sig: Enable dead time for CB1 3PAR
ENABLE CB1SPDT Int Sig: Enable dead time for CB1 SPAR
ENABLE CB23PDT Int Sig: Enable dead time for CB2 3PAR
ENABLE CB2SPDT Int Sig: Enable dead time for CB2 SPAR
EVOLVE LOCK Int Sig: Lockout for 2nd trip after Discrim Tim
F Out of Range Int Sig from frequency tracking logic
FLTMEM 2P Int Sig: 2 Ph fault memory
FLTMEM 3P Int Sig: 3 Ph fault memory
Foll CB1 Int Sig from “Leader & Follower Logic – 2”
Foll CB2 Int Sig from “Leader & Follower Logic – 2”
Foll3PAROK Int Sig from “Leader & Follower AR Modes Enable”
FollSPAROK Int Sig from “Leader & Follower AR Modes Enable”
INIT AR Int Sig: Host protection required to initiate AR
Int Sig: An invalid state is being indicated by the logic that
Invalid AR Mode
determines AR mode by opto.
P446/EN/TM/E 7-247
7 Operation MiCOMho P446
Name Description
Last Shot Int Sig: the last shot
Live Bus 1 Int Sig + DDB: CS1 V magnitude >= Live Bus 1 setting
Live Bus 2 Int Sig + DDB: CS2 V magnitude >= Live Bus 2 setting
Live Line Int Sig + DDB: Line V magnitude >= Live Line setting
OK Time SP Int Sig from “Single Phase AR Lead CB Dead Time”
PrefLCB1 Int Sig: CB1 is the preferred leader
PrefLCB2 Int Sig: CB2 is the preferred leader
Prot AR Block* Int Sig: Host protection required to block AR
Prot Re-op Int Sig from “Protection Re-operation + Evolving Fault”
RESCB1ARSUCC Int Sig from “Reset CB1 Successful AR Indication
RESCB1LO Int Sig from “Reset CB1 Lockout”
RESCB2ARSUCC Int Sig from “Reset CB2 Successful AR Indication
RESCB2LO Int Sig from “Reset CB2 Lockout”
Reset L-F Int Sig: From “Protection Re-operation + Evolving fault”
RESPRMEM Int Sig: Reset “trip & AR” memory
SC Increment Int Sig: Increment the sequence counter
SCCountoveqShots Int Sig: Sequence counter has exceeded setting
SET CB1CL Int Sig from “CB1 Auto Close”
SET CB2CL Int Sig from “CB2 Auto Close”
SET LCB1 Int Sig: CB1 selected leader
SET LCB1 Int Sig from “Leader/Follower Logic – 1”
SET LCB2 Int Sig: CB2 selected leader
SET LCB2 Int Sig from “Leader/Follower Logic – 1”
SETCB13PCL Int Sig: CB1 three phase close given
SETCB1SPCL Int Sig: CB1 single phase close given
SETCB23PCL Int Sig: CB2 three phase close given
SETCB2SPCL Int Sig: CB2 single phase close given
SPDTCOMP Int Sig: Single phase dead time complete
TAR 2/3Ph Int Sig: 2Ph or 3Ph trip & AR initiation
TARA Int Sig: A Ph trip & AR initiation
TARANY Int Sig from “CB1 1 Pole / 3 Pole Trip + AR Initiation”
TARANY Int Sig: Any trip & AR initiation
TARB Int Sig: B Ph trip & AR initiation
TARC Int Sig: C Ph trip & AR initiation
TMEM 1Ph Int Sig: CB1 1Ph trip +AR AR initiation memory
TMEM 2/3Ph Int Sig: CB1 2Ph trip +AR AR initiation memory
TMEM 3Ph Int Sig: CB1 3Ph trip +AR AR initiation memory
TMEM ANY Int Sig: Any Ph trip & AR initiation memory
7-248 P446/EN/TM/E
MiCOMho P446 8 Application Examples
APPLICATION EXAMPLES
CHAPTER 8
P446/EN/TM/E 8-1
8 Application Examples MiCOMho P446
8-2 P446/EN/TM/E
MiCOMho P446 8 Application Examples
1 CHAPTER OVERVIEW
The Application chapter describes how the MiCOMho P446 can be applied, providing application
examples where appropriate.
This chapter consists of the following sections:
1 Chapter Overview
2 Introduction
2.1 Protection of Overhead Line, Cable, and Hybrid Circuits
P446/EN/TM/E 8-3
8 Application Examples MiCOMho P446
8-4 P446/EN/TM/E
MiCOMho P446 8 Application Examples
P446/EN/TM/E 8-5
8 Application Examples MiCOMho P446
8-6 P446/EN/TM/E
MiCOMho P446 8 Application Examples
P446/EN/TM/E 8-7
8 Application Examples MiCOMho P446
2 INTRODUCTION
8-8 P446/EN/TM/E
MiCOMho P446 8 Application Examples
Caution The kZN Angle is different than previous LFZP, SHNB, and LFZR IEDs: When
importing settings from these older products, subtract. angle Z1.
Short line applications: Mho phase fault and quadrilateral earth fault zones.
Open delta (vee-connected) VT applications: Mho for phase fault, with earth fault distance
disabled, and only directional earth fault element used for earth fault protection.
Series compensated lines: Recommend always using mho characteristics for both phase and
earth faults.
P446/EN/TM/E 8-9
8 Application Examples MiCOMho P446
Time
Delay
t
Load
Blinder
Line Angle b
Angle
Blinder Radius
P1725ENa
Figure 2 shows the basic settings needed to configure a forward-looking quadrilateral zone (blinder
not shown).
Zone Reach
Z
Tilt Angle
Time
Delay
t
Line
Angle
Resistive
Reach
R
P1726ENa
8-10 P446/EN/TM/E
MiCOMho P446 8 Application Examples
P446/EN/TM/E 8-11
8 Application Examples MiCOMho P446
Note: In the case of the mho, the line impedance is not subtracted. This ensures that whatever the
amount of dynamic expansion of the circle, the reverse looking zone always detects all solid and
resistive faults capable of detection by Zone 2 at the remote line end.
Note: Because the fault current for a earth fault may be limited by tower footing resistance, high soil
resistivity, and weak infeeding; any arcing resistance is often higher than for a corresponding phase
fault at the same location. It maybe necessary to set the RG ground resistive settings to be higher
than the RPh phase setting (i.e. boosted higher than the rule of thumb in the last subsection). A
setting of RG three times that of RPh is not uncommon.
Dynamic tilting
Medium/ Long lines
In the case of medium and long line applications where Quad distance ground characteristic is used,
the recommended setting is ‘Dynamic tilt’ enabled at starting tilt angle of -3° (as per default settings).
The -3° is set to compensate for possible CT/VT and line data errors.
For high resistive faults during power exporting, the under-reaching zone 1 is only allowed to tilt down
by the angle difference between the faulted phase and negative sequence current (Iph-I2) starting
from the –3° set angle. This ensures stability of zone 1 for high resistance faults beyond the Zone 1
reach even during heavy load conditions (high load angle between two voltage sources) and sufficient
sensitivity for high resistance internal faults. The tilt angle for all other zones (that are by nature over-
reaching zones) remain at -3 deg.
8-12 P446/EN/TM/E
MiCOMho P446 8 Application Examples
In the case of power importing, Zone 1 remains at –3° while all other zones are allowed to tilt up by the
(Iph-I2) angle difference, starting from –3°. This increases the Zone 2 and Zone 4 resistive reaches
and secures correct operation in POR and blocking type schemes.
Short lines
For very short lines, typically below 10 Miles (16 km), the ratio of resistive to reactance reach setting
(R/X) could easily exceed 10. For such applications the geometrical shape of the Quad characteristic
could be such that the top reactance line is close or even crosses the resistive axis as presented in
Figure 3.
Figure 3: Example of high resistive Zone 1 fault that falls outside Zone 1 characteristic when
starting tilt angle of -3° is set (over-tilting effect)
In the case of high resistance external faults on a short line, particularly under heavy power exporting
conditions, Zone 1 remains stable due to dynamic downwards tilting of the top line. However, the
detection of high resistance internal faults especially towards the end of the line needs consideration.
In such applications a user has a choice to either detect high resistance faults using highly sensitive
Aided DEF or Delta Directional schemes or to clear the fault with distance ground protection. If
distance is to operate, it is necessary to eliminate over-tilting for internal faults by reducing the initial -
3° tilting angle to zero so that the overall top line tilt is equal to (Iph-I2) angle only.
As shown in Figure 3, the internal resistive fault then falls in the Zone 1 operating characteristic.
However, for short lines the load angle is relatively low when compared to long transmission lines for
the same transfer capacity and therefore the top line dynamic tilting may be moderate. Therefore it
may be necessary to reduce the Zone 1 reach to guarantee Zone 1 stability. This is particularly
recommended if distance is operating in an aided scheme. To summarize, for very short lines with
large R/X setting ratios, it is recommended to set the initial tilt angle to zero and Zone 1 reach to 70-
75% of the line impedance.
Note: The above discussion assumes homogenous networks where the angle of the negative sequence
current derived at relaying point is very close to the total fault current angle. If the network is non-
homogenous, there is a difference in angle that causes inaccurate dynamic tilting. Therefore in such
networks either quad with fixed tilt angle or even Mho characteristic should be considered to avoid
Zone 1 over-reach.
P446/EN/TM/E 8-13
8 Application Examples MiCOMho P446
To secure stability, the tilt angle of Zone 1 at exporting end has to be set negative and above the
maximum angle difference between sources feeding the resistive faults. This data should be known
from load flow study, but if unavailable, the minimum recommended setting would be the angle
difference between voltage and current measured at local end during the heaviest load condition
coupled with reduced Zone 1 reach of 70-75% of the line impedance.
Note: Figure 3 shows that at sharp fixed tilt angle, the effective resistive coverage would be significantly
reduced, and therefore for the short lines the dynamic tilting (with variable tilt angle depending on
fault resistance and location) is preferred. For all other over-reaching zones set tilting angle to zero.
Importing end
Set Zone 1 tilt angle to zero and for all other zones the typical setting should be positive and between
+(5-10)°.
Note: The setting accuracy for over-reaching zones is not crucial because it does not pose a risk for IED
mal-operation. The purpose is only to boost Zone 2 and Zone 4 reach and improve distance aided
schemes.
A tilt angle on the top line of any quadrilateral set for phase faults;
A minimum current sensitivity setting.
By factory defaults, the Top Line of quadrilateral characteristics is not fixed as a horizontal reactance
line. To account for phase angle tolerances in the line CT, VT and IED, the line is tilted downwards, at
a “droop” of –3o. This tilt down helps to prevent Zone 1 overreach.
The fixed Tilt setting on the phase elements may also be used to compensate for overreach effects
when prefault heavy load export was flowing. In such cases, fault arc resistance is phase shifted on
the impedance polar plot, tilting down towards the resistive axis and not appearing to be fully resistive
in nature. For long lines with heavy power flow, the Zone 1 top line might be tilted downwards in the
range –5 to –15o, mimicking the phase shift of the resistance.
Note 1: A minus angle is used to set a downwards tilt gradient, and a positive angle to tilt upwards.
Note 2: mho characteristics have an inherent tendency to avoid unwanted overreaching, making them very
desirable for long line protection, and one of the reasons for their inclusion in the IED.
The current Sensitivity setting for each zone is used to set the minimum current that must be flowing
in each of the faulted phases before a trip can occur. It is recommended to leave these settings at
their default. The exception is where the IED is made more insensitive to match the lesser sensitivity
of older IEDs existing on the power system, or to grade with the pickup setting of any ground
overcurrent protection for tee-off circuits.
8-14 P446/EN/TM/E
MiCOMho P446 8 Application Examples
to be precise. When a fault occurs, the delta current is never close to the characteristic boundary, so
an approximate setting is good enough.
The 60° angle is associated with mainly inductive sources and works perfectly well for most
applications. However, in series compensated line applications where the capacitor is physically
located behind the line VT, the Delta directional characteristic angle needs adjusting. In such
applications the capacitor is included in the equivalent source impedance. Then the overall source
impedance seen by the IED becomes predominantly capacitive if the inductance of the normally
strong source is less than the capacitor value. In this case, the calculated operating angle during an
internal fault may not fall within the default 60° delta directional line operating boundary. This could
lead to an incorrect (reverse) directional decision. A zero degree shift is most suitable for such a fault.
However, the constraining factor is the case of external faults for which the source is always inductive
regardless of the degree of compensation and for which the 60° shift is most appropriate. To ensure
correct, reliable and fast operation for both fault locations in the case of predominantly capacitive
source, a Delta Char Angle setting of 30° is strongly recommended.
Note: When using the long line filter the instantaneous operating time is increased by about a quarter of a
power frequency cycle.
P446/EN/TM/E 8-15
8 Application Examples MiCOMho P446
and to ensure that line faults are detected, (Line Angle -15o).
In practice, an angle half way between the worst-case leading load angle, and the protected line
impedance angle, is often used.
The MiCOMho P446 has a facility to allow the load blinder to be bypassed any time the measured
voltage for the phase in question falls below an undervoltage V< setting. Under such circumstances,
the low voltage could not be explained by normal voltage excursion tolerances on-load. A fault is
definitely present on the phase in question, and it is acceptable to override the blinder action and allow
the distance zones to trip according to the entire zone shape. The benefit is that the resistive
coverage for faults near to the IED location can be higher.
The undervoltage setting must be lower than the lowest phase-neutral voltage under heavy load flow
and depressed system voltage conditions. The typical maximum V< setting is 70% Vn.
Note (1): The MiCOMho P446 allows separate time delays to be applied to both phase and earth fault zones,
for example where earth fault delays are set longer to time grade with external ground/earth
overcurrent protection.
8-16 P446/EN/TM/E
MiCOMho P446 8 Application Examples
Note (2): Any zone (“#”) which may reach through a power transformer reactance, and measure secondary
side faults within that impedance zone should have a small time delay applied. This is to avoid
tripping on the inrush current when energizing the transformer. As a general rule, if: Z# Reach setting
> 50% XT transformer reactance, set: tZ# 100 ms. Alternatively, the 2nd harmonic detector
that is available in the Programmable Scheme Logic may be used to block zones that may be at risk
of tripping on inrush current. Settings for the inrush detector are found in the SUPERVISION menu
column.
Zone 3
Zone 2
Zone 1
A Z B
Z
Zone 1
Zone 2
Zone 3
Typical application
Relay A Relay B
Z1 TZ1 TZ1 Z1
Trip A Trip B
1 1
ZP ZP
TZP TZP
Z2 Z2
TZ2 TZ2
Z3 Z3
TZ3 TZ3
Z4 Z4
TZ4 TZ4
P446/EN/TM/E 8-17
8 Application Examples MiCOMho P446
Z8
t
Z7
V1
Z1
I1
R8 R 7 R7
R8
Z 7
Z 8
MAX Load
½ Rx Ph. Resistive
+R
Zone 7
Zone 8
8-18 P446/EN/TM/E
MiCOMho P446 8 Application Examples
2. Inner Zone 7 should be set in excess of total impedance ZT , which include local
source impedance ZS , line impedance ZL and remote source impedance ZR . Only
positive sequence impedances should be considered. The security margin for this
condition should be at least 20%. The recommended margin between Z7 and Z8
settings is 10%:
Z8 = 1.1*Z7
It is recommended then to set Z7’ and Z8’ equal to Z7 and Z8:
Z7’ = -Z7, Z8’ = -Z8.
The angle Alpha should be set equal to the angle of the total impedance ZT :
ZT
ZR
ZL
ZT ZT
ZS
P446/EN/TM/E 8-19
8 Application Examples MiCOMho P446
Zone 7 Zone 8
ZR
ZL
ZT
2 1
2
ZT
ZS
The PSB Reset Delay is used to maintain the PSB status when I naturally is low during the
swing cycle (near the current maxima and minima in the swing envelope). A typical setting of
0.2s is used to seal-in the detection until I has chance to appear again.
The PSB Unblock Dly is used to time the duration for which the swing is present. The intention
is to allow the distinction between a stable and an unstable swing. If after the timeout period the
swing has still not stabilized, the block for selected zones can be released (unblocking), giving
the opportunity to split the system. If no unblocking is required at the location of this IED, set to
maximum (10 s).
PSB should be disabled in distribution systems, where power swings do not normally occur.
8-20 P446/EN/TM/E
MiCOMho P446 8 Application Examples
Curve 1
Area 2
F Area 1
Po A E G
Out-of-Step
D
Curve 2 Curve 3
C
B
q
o q0 q1 o q2 q3 o
0 90 180
The figure above represents power angle curves, with no AR being performed, as follows:
Curve 1 - Pre-fault system operation through parallel lines where transmitted power is Po
Curve 2 - Transmitted power significantly reduced during two-phase to earth fault
Curve 3 - New power curve when the parallel line is tripped (fault cleared)
It can be seen that at a fault instance, the operating point A moves to B, with a lower transfer level.
There is therefore a surplus of power P=AB at the sending end and the corresponding deficit at the
receiving end. The sending end machines start to speed up, and the receiving end machines to slow
down, so phase angle θ increases, and the operating point moves along curve 2 until the fault is
cleared, when the phase angle is θ1. The operating point now moves to point D on curve 3 which
represents one line in service. There is still a power surplus at the sending end, and deficit at the
receiving end, so the machines continue to drift apart and the operating point moves along curve 3. If,
at some point between E and G (point F) the machines are rotating at the same speed, the phase
angle will stop increasing. According to the Equal Area Criterion, this occurs when area 2 is equal to
area 1. The sending end will now start to slow down and receiving end to speed up. Therefore, the
phase angle starts to decrease and the operating point moves back towards E. As the operating point
passes E, the net sending end deficit again becomes a surplus and the receiving end surplus
becomes a deficit, so the sending end machines begin to speed up and the receiving end machines
begin to slow down. With no losses, the system operating point would continue to oscillate around
point E on curve 3, but in practice the oscillation is dumped, and the system eventually settles at
operating point E.
To resume, if area 1<area 2, the system will stay in synchronism. This swing is usually called a
recoverable power swing. If, on contrary, the system passes point G with a further increase in angle
difference between sending and receiving ends, the system drifts out of synchronism and becomes
P446/EN/TM/E 8-21
8 Application Examples MiCOMho P446
unstable. This will happen if the initial power transfer Po was set too high in Figure 9, so that the area
1 is greater than area 2. This power swing is not recoverable and is usually called out of step or out
of synchronism or pole slip condition. After this, only system separation and re-synchronizing of the
machines can restore normal system operation.
In Figure 9, the point G is shown at approximately 120° deg, but it is not true in all cases. If, for
example the pre-fault transmitted power (Po) was too high and if the fault clearance was slow, the
area 1 will be greater so for the system to recover the angle θ would be close to 90 deg. On contrarily,
if the pre-fault transmitted power Po was low and fault clearance fast, the area 1 will be small, so that
based on area comparison, the angle θ could go closer to 180 deg and the system will still remain
stable.
The actual angle difference at which system will become unstable could only be determined by a
particular system studies, but for the purpose of settings recommendation where ‘OST’ setting is
selected, the typical angle beyond which system will not recover is assumed to be 120 deg.
1. Disabled
2. Predictive OST
3. OST
4. Predictive OST or OST
Set Option 1 on all lines except the line where tripping due to unrecoverable power oscillations is
required or for the system where power oscillations are not severe - mainly in well interconnected
systems operating with 3 phase tripping.
Setting Option 2 (and 4) is the best setting option from the system point of view, perhaps not being
widely used in the past. Some utilities prefer an early system split to minimize the angle shift between
ends and maximize the chances for the remaining two halves to stabilize as quickly as possible.
Special care must be taken when this method is applied to ensure that the actual circuit breaker
opening does not occur when the internal voltages at two ends are in anti phase. This is due to the
fact that most breakers are not designed to interrupt at double nominal voltage and any attempt to
break at that point would lead to flash over and possible circuit breaker damage. The fact is that
setting Option 2 (and 4) will be mainly applied do detect and trip fast power oscillations. When this is
coupled with a typical 2 cycle circuit breaker operating time, the two voltages angles may rapidly move
in opposite directions at the time of opening the circuit breaker. Therefore, if this setting option is
chosen, the above facts must be taken into account so that the actual CB opening must occur well
before the angle difference between two ends approaches 180 degrees. On that basis, accurate
settings have to be determined based on exhaustive system studies.
Setting Option 3 is the most commonly used approach. Once the Out of Step conditions are
detected, the OST command will split the system at pre-determined points. The slight disadvantages
of this method in comparison to Option 2 (and 4) is that the power oscillation will escalate further, thus
causing more difficulties for the split parts to remain stable but the advantage is that the timing of the
circuit breaker operation (‘tripping angle’) is easily controlled and the decision to split the system will
be correct even if errors were made in the system data and setting parameters. This extra security is
achieved by measuring and confirming the change of polarity of the resistive part of positive sequence
impedance on Zone 5 exit (reset).
Setting Option 4 provides 2 stages of Out of Step detection and tripping. If the power system
oscillation is very fast, the combination of ∆R and Delta t setting (as discussed below) must be set in
such a way that ‘Predictive OST’ operates. If however the oscillation is slower, the condition for the
‘Predictive OST’ will not be met and the ‘OST’ will operate later upon Z5 reset, providing that the
change in polarity of the resistive component was detected. This is to distinguish between a slower
non-recoverable oscillation and recoverable swings.
8-22 P446/EN/TM/E
MiCOMho P446 8 Application Examples
+jX
Z6
Z5
Predictive Out of
ZR step trip
ZT
ZL
R
R6' R5' R5 R6
Out of step trip
ZS
Z5'
Z6'
Figure 10: Setting determination for the positive sequence resistive component R5
P446/EN/TM/E 8-23
8 Application Examples MiCOMho P446
+jX
Z6
LOAD
ZT
R
O 32
R6' R6
Z6'
β = 32 + 90 – α
Z load min = OA
R6MAX < Zload min x cos β
Where:
Zload min is the minimum load impedance radius calculated above which already has built in
sufficient margin
32 deg is the load angle that corresponds to the lower power factor of 0.85
‘α’ is the load blinder angle that matches ZT angle
The setting of negative resistance R5’ should equal the R5 to accommodate the ‘load import’
condition. Starting from the limit values R5MIN and R6MAX the actual R5 and R6 (including the
corresponding R5’ and R6’) reaches will be set in conjunction with the ‘Delta t’ setting below.
8-24 P446/EN/TM/E
MiCOMho P446 8 Application Examples
Note: R6MAX reach must be greater than the maximum resistive reach of any distance zone to ensure
correct initiation of the 25 ms and ‘Delta t’ timers. However, the R5MIN reach could be set below the
distance maximum resistive reach (inside the distance characteristic) if an extensive resistive
coverage is required, meaning that Out of Step protection does not pose a restriction to the quad
applications.
Setting of reactance lines Z5 and Z6 depends on how far from the IED location the power oscillations
are to be detected. Normally, there is only one point where the system is to be initially split and that
point will be determined by system studies. For that reason, the Out of Step protection must be
enabled at that location and disabled on all others. To detect the Out of step conditions, the Z5’-Z5
and Z6’-Z6 setting must be set to comfortably encompass the total system impedance ZT, as shown in
Figure 10. A typical setting could be:
Z5 = Z5’ = 1/2 x 2 ZT = ZT
The Z6 and Z6’ setting is not of great importance and could be set to Z6 = Z6’ = 1.1 x Z5
The aim of pushing the R5 setting to the right is to detect the fast oscillation as soon as possible to
gain sufficient time to operate the breaker before the two source voltages are in opposite direction.
The only restriction would be the limitation of the Delta t minimum time delay of 30 ms and the speed
of oscillation. Set Delta t so that the following condition is satisfied:
‘Delta t’ does not expire after positive sequence impedance has passed the R6-R5 region
For this setting, knowledge of the accurate rate of change of swing impedance when crossing the R6-
R5 region is essential and therefore must be based on system studies.
Assumption that the rate of change of the positive sequence impedance during crossing the R6-R5
region is average rate of change for the whole swing cycle is wrong and could easily lead to incorrect
‘Predictive OST’ operation.
Note: For the fault, the R6-R5 region will be passed faster than 25 ms, therefore even very fast oscillations
of 7 Hz will not be mistaken with the fault condition and Predictive OST will not operate.
OST setting:
For the OST setting option the precise setting of blinders and Delta t is not necessary. This is based
on the fact that:
The wider the ∆R region and the shorter the ∆t setting, any oscillation will be successfully detected.
The only condition is that the fault impedance must pass through the ∆R region faster than ∆t setting.
Therefore, for the OST setting assume that θ = 120° and set:
P446/EN/TM/E 8-25
8 Application Examples MiCOMho P446
The point is that Delta t always expires, therefore the above setting will secure the detection of a wide
range of oscillations, starting from very slow oscillations caused by recoverable swings up to the
fastest oscillation of 7Hz. It should be noted that any fault impedance will pass the R6-R5 region
faster than the minimum settable Delta t time of
30 ms.
8-26 P446/EN/TM/E
MiCOMho P446 8 Application Examples
+jX
Z6
Z5
∆R
ZL
MOV’s operation
R
R6' R5' R5 R6
Z5'
Z6'
P1977Ena
Note: If the OST setting is chosen, the timer when triggered, will eventually expire as the power
oscillations progress, therefore MOV operation will not have any impact on Out of Step operation.
P446/EN/TM/E 8-27
8 Application Examples MiCOMho P446
If Virtual I Pol is set to Disabled it prevents checking of the faulted phase and subsequent removal of
the faulted phase voltage. The DEF protection is then polarized by the residual voltage only.
8-28 P446/EN/TM/E
MiCOMho P446 8 Application Examples
Note: This setting has to be above the maximum steady state residual current unbalance.
For the reverse fault detectors, these must be set more sensitively, as they are used to invoke the
blocking and current reversal guard elements. It is suggested that all reverse detectors are set at 66
to 80% of the setting of the forward detector, typically:
Delta V Rev = Delta V Fwd x 0.66
Delta I Rev = Delta I Fwd x 0.66
This setting philosophy is in-accordance with the well-proven Alstom Grid LFDC IED.
Note: Deltas by their nature are present only for 2 cycles on fault inception. If any distance elements are
enabled, these will automatically allow the delta forward or reverse decisions to seal-in, until such
time as the fault is cleared from the system. Therefore as a minimum, some distance zone(s) must
be enabled in the DISTANCE SETUP column as fault detectors. It does not matter what time delay
is applied for the zone(s). This can either be the typical distance delay for that zone or set to
Disabled in the SCHEME LOGIC column, if no distance tripping is required. As a minimum, Zone 3
must be enabled, with a reverse reach such as to allow seal-in of Delta Rev, and a forward reach to
allow seal-in of Delta Fwd.
P446/EN/TM/E 8-29
8 Application Examples MiCOMho P446
A mho characteristic is generally advised in such starter applications, although quadrilaterals are
acceptable. As the mho starter is likely to have a large radius, applying the Load Blinder is strongly
advised.
Note: The POR scheme also uses the reverse looking Zone 4 of the IED as a reverse fault detector. This
is used in the current reversal logic and in the optional weak infeed echo feature.
8-30 P446/EN/TM/E
MiCOMho P446 8 Application Examples
Recommended Dly setting = Max. Signalling channel operating time + 1 power frequency
cycle.
This scheme is similar to that used in the LFZP Optimho, SHNB Micromho, LFZR, and MiCOM P44x
(note 3) distance IEDs. (Note 3: matches BOP Z2 mode in P441/442/444).
Send logic: Reverse Zone 4
Trip logic: Zone 2, plus Channel NOT Received, delayed by Tp
Note: Two variants of a Blocking scheme are provided, Blocking 1 and Blocking 2. Both schemes operate
identically, except that the reversal guard timer location in the logic changes. Blocking 2 may
sometimes allow faster unblocking when a fault evolves from external to internal, and hence a faster
trip.
Note: The Time Delay for a permissive scheme aided trip would normally be set to zero.
P446/EN/TM/E 8-31
8 Application Examples MiCOMho P446
Caution The IEEE C.37.112 standard for IDMT curves permits some freedom to
manufacturers at which Time Dial (TD) value the reference curve applies.
Rather than pick a mid-range value, for the MiCOMho P446 the reference curve
norm applies at a time dial of 1. The time dial is merely a multiplier on the
reference curve to achieve the desired tripping time. Take care when grading
with other suppliers' IEDs which may take TD = 5, or TD = 7 as a mid-range
value to define the IDMT curve. The equivalent MiCOMho P446 setting to match
those IEDs is achieved by dividing the imported setting by 5 or 7.
8-32 P446/EN/TM/E
MiCOMho P446 8 Application Examples
Although it is possible to set the RCA to exactly match the system fault angle, it is recommended the
above figures are followed, as these settings have been shown to provide satisfactory performance
and stability under a wide range of system conditions.
An alarm can be raised on reaching a thermal state corresponding to a percentage of the trip
threshold. A typical setting might be ‘Thermal Alarm’ = 70% of thermal capacity.
An alarm can be raised on reaching a thermal state corresponding to a percentage of the trip
threshold. A typical setting might be ‘Thermal Alarm’ = 70% of thermal capacity.
Note: The thermal time constants given in the above tables are typical only. Reference should always be
made to the plant manufacturer for accurate information.
P446/EN/TM/E 8-33
8 Application Examples MiCOMho P446
3.8 Earth Fault (Ground Overcurrent) and Sensitive Earth Fault (SEF) Protection
Caution The IEEE C.37.112 standard for IDMT curves permits some freedom to
manufacturers at which Time Dial (TD) value the reference curve applies.
Rather than pick a mid-range value, for the MiCOMho P446 the reference curve
norm applies at a time dial of 1. The time dial is merely a multiplier on the
reference curve to achieve the desired tripping time. Take care when grading
with other suppliers' IEDs which may take TD = 5,or TD = 7 as a mid-range value
to define the IDMT curve. The equivalent MiCOMho P446 setting to match those
IEDs is achieved by dividing the imported setting by 5 or 7.
3.8.1.2 General Setting Guidelines for Directional Earth Fault (Ground Overcurrent) Protection
When setting the IED characteristic angle (RCA) for the directional earth fault element, a positive
angle setting was specified. This was due to the fact that the quadrature polarizing voltage lagged the
nominal phase current by 90°; i.e. the position of the current under fault conditions was leading he
polarizing voltage and hence a positive RCA was required. With directional earth fault DEF, the
residual current under fault conditions lies at an angle lagging the polarizing voltage. Hence, negative
RCA settings are required for DEF applications. This is set in cell 'I>N’ in the relevant earth fault
menu.
The following angle settings are recommended for a residual voltage polarized IED:-
For negative sequence polarization, the RCA settings must be based on the angle of the upstream
negative phase sequence source impedance.
8-34 P446/EN/TM/E
MiCOMho P446 8 Application Examples
Cable gland
Cable box
Incorrect
No operation
SEF
Correct
Operation
SEF
P0112ENa
Figure 13 shows that if the cable sheath is terminated at the cable gland and earthed directly at that
point, a cable fault (from phase to sheath) will not result in any unbalance current in the core balance
CT. Hence, prior to earthing, the connection must be brought back through the CBCT and earthed on
the feeder side. This then ensures correct IED operation during earth fault conditions.
P446/EN/TM/E 8-35
8 Application Examples MiCOMho P446
When applying differential protection such as REF, some suitable means must be employed to give
the protection stability under external fault conditions, therefore ensuring that IED operation only
occurs for faults on the transformer winding / connections.
Two methods are commonly used; bias or high impedance. The biasing technique operates by
measuring the level of through current flowing and altering the IED sensitivity accordingly. The high
impedance technique ensures that the IED circuit is of sufficiently high impedance so the differential
voltage that may occur under external fault conditions is less than that required to drive setting current
through the IED.
The REF protection in the IED can be configured to operate as high impedance element. The
following sections describe the application of the IED for the high impedance element.
Note: The high impedance REF element of the IED shares the same CT input as the SEF protection.
Hence, only one of these elements may be selected.
3.8.3.1 Setting Guidelines for High Impedance Restricted Earth Fault (REF)
From the SEF/REF options cell, Hi Z REF must be selected to enable this protection. The only setting
cell then visible is REF>s, which may be programmed with the required differential current setting.
This would typically be set to give a primary operating current of either 30% of the minimum earth fault
level for a resistance earthed system or between 10 and 60% of rated current for a solidly earthed
system.
The primary operating current (op) is a function of the current transformer ratio, the IED operating
current (REF>s1), the number of current transformers in parallel with an IED element (n) and the
magnetizing current of each current transformer (e) at the stability voltage (Vs). This relationship can
be expressed in three ways:
To determine the maximum current transformer magnetizing current to achieve a specific primary
operating current with a particular IED operating current:
1 op
e < x - REF > s
n CT ratio
To determine the minimum IED current setting to achieve a specific primary operating current with a
given current transformer magnetizing current.
op
[REF > s] < - ne
CT ratio
8-36 P446/EN/TM/E
MiCOMho P446 8 Application Examples
Vs (rms) x 2 4
(rms) = 0.52
C
Where: Vs(rms)= rms value of the sinusoidal voltage applied across the
metrosil.
This is due to the fact that the current waveform through the metrosil is not sinusoidal but appreciably
distorted.
For satisfactory application of a non-linear resistor (metrosil), its characteristic should be such that it
complies with the following requirements:
At the IED voltage setting, the non-linear resistor (metrosil) current should be as low as
possible, but no greater than approximately 30 mA rms for 1 A current transformers and
approximately 100 mA rms for 5 A current transformers.
At the maximum secondary current, the non-linear resistor (metrosil) should limit the voltage to
1500 V rms or 2120 V peak for 0.25 second. At higher IED voltage settings, it is not always
possible to limit the fault voltage to 1500V rms, so higher fault voltages may have to be
tolerated.
The following tables show the typical Metrosil types required, depending on IED current rating, REF
voltage setting etc.
At the IED voltage setting, the Metrosil current should be less than 30 mA rms.
At the maximum secondary internal fault current the Metrosil unit should limit the voltage to
1500 V rms if possible.
P446/EN/TM/E 8-37
8 Application Examples MiCOMho P446
The Metrosil units normally recommended for use with 1 Amp CTs are as shown in the following table:
Nominal
Relay voltage setting Recommended Metrosil type
characteristic
C Single pole relay Triple pole relay
Up to 125 V rms 600A/S1/S256 600A/S3/1/S802
450 900 0.25 0.25
125 to 300 V rms 600A/S1/S1088 600A/S3/1/S1195
Table 4: Recommended Metrosil type for use with 1 Amp CTs
Note: Single pole Metrosil units are normally supplied without mounting brackets unless otherwise
specified by the customer.
At the IED voltage setting, the Metrosil current should be less than 100 mA rms (the actual
maximum currents passed by the units shown below their type description.
At the maximum secondary internal fault current the Metrosil unit should limit the voltage to
1500 V rms for 0.25 secs. At the higher IED settings, it is not possible to limit the fault voltage
to 1500 V rms so higher fault voltages have to be tolerated (indicated by *, **, ***).
The Metrosil units normally recommended for use with 5 Amp CTs and single pole relays are
shown in the following table:
Secondary
internal fault Recommended Metrosil type
current
Relay voltage setting
Amps rms Up to 200 V rms 250 V rms 275 V rms 300 V rms
600A/S1/S1213 600A/S1/S1214 600A/S1/S1214 600A/S1/S1223
50 A C = 540/640 C = 670/800 C = 670/800 C = 740/870*
35 mA rms 40 mA rms 50 mA rms 50 mA rms
600A/S2/P/S1217 600A/S2/P/S1215 600A/S2/P/S1215 600A/S2/P/S1196
100 A C = 470/540 C = 570/670 C = 570/670 C = 620/740*
70 mA rms 75 mA rms 100 mA rms 100 mA rms
600A/S3/P/S1219 600A/S3/P/S1220 600A/S3/P/S1221 600A/S3/P/S1222
150 A C = 430/500 C = 520/620 C = 570/670** C = 620/740***
100 mA rms 100 mA rms 100 mA rms 100 mA rm
Note: *2400 V peak **2200 V peak ***2600 V peak
Table 5: Recommended Metrosil type for use with 5Amp CTs
In some situations single disc assemblies may be acceptable, contact Alstom Grid for detailed
applications.
8-38 P446/EN/TM/E
MiCOMho P446 8 Application Examples
Notes: The Metrosil units recommended for use with 5 Amp CTs can also be applied for use with triple pole
relays and consist of three single pole units mounted on the same central stud but electrically
insulated from each other. To order these units please specify Triple pole Metrosil type, followed
by the single pole type reference.
Metrosil units for higher IED voltage settings and fault currents can be supplied if required.
To express the protection primary operating current for a particular IED operating current and with a
particular level of magnetizing current.
To achieve the required primary operating current with the current transformers that are used, a
current setting (REF>s) must be selected for the high impedance element, as detailed in expression
(ii) above. The setting of the stabilizing resistor (RST) must be calculated in the following manner,
where the setting is a function of the required stability voltage setting (Vs) and the IED current setting
(REF>s).
Vs F (RCT + 2RL)
Rst = =
REF>s REF > s
The stabilizing resistor that can be supplied is continuously adjustable up to its maximum declared
resistance.
Negative phase sequence overcurrent elements give greater sensitivity to resistive phase-to-
phase faults, where phase overcurrent elements may not operate.
In certain applications, residual current may not be detected by an earth fault IED due to the
system configuration. For example, an earth fault IED applied on the delta side of a Dy (delta-
wye) transformer is unable to detect earth faults on the star (wye) side. However, negative
sequence current will be present on both sides of the transformer for any fault condition,
irrespective of the transformer configuration. Therefore a negative phase sequence overcurrent
element may be employed to provide time-delayed back-up protection for any uncleared
asymmetrical faults downstream.
It may be required to simply alarm for the presence of negative phase sequence currents on the
system. Operators may then investigate the cause of the unbalance.
P446/EN/TM/E 8-39
8 Application Examples MiCOMho P446
the current pick-up setting must be set approximately 20% below the lowest calculated negative phase
sequence fault current contribution to a specific remote fault condition.
3.9.2 Time Delay for the NPS Overcurrent Element, ‘2> Time Delay’
As stated above, correct setting of the time delay for this function is vital. It should also be noted that
this element is applied primarily to provide back-up protection to other protective devices or to provide
an alarm. Hence, in practice, it would be associated with a long time delay.
It must be ensured that the time delay is set greater than the operating time of any other protective
device (at minimum fault level) on the system which may respond to unbalanced faults.
For the negative phase sequence directional elements to operate, the IED must detect a polarizing
voltage above a minimum threshold, 2> V2pol Set. This must be set in excess of any steady state
negative phase sequence voltage. This may be determined during the commissioning stage by
viewing the negative phase sequence measurements in the IED.
Use of the IDMT characteristic gives the option of a longer time delay if the overvoltage
condition is only slight but results in a fast trip for a severe overvoltage. As the voltage settings
for both of the stages are independent, the second stage could then be set lower than the first
to provide a time delayed alarm stage if required.
8-40 P446/EN/TM/E
MiCOMho P446 8 Application Examples
Alternatively, if preferred, both stages could be set to definite time and configured to provide the
required alarm and trip stages.
If only one stage of overvoltage protection is required, or if the element is required to provide an
alarm only, the remaining stage can be disabled in the IED menu.
This type of protection must be coordinated with any other overvoltage IEDs at other locations on the
system. This should be carried out in a similar manner to that used for grading current operated
devices. The measuring mode (ph-N or ph-ph) and operating mode (single phase or 3 phase) for both
stages are independently settable.
Figure 14: Calculated Ferranti voltage rise on 345 kV and 765 kV lines
The two stage compensated overvoltage element can be applied as alarming or trip elements. Both
stages’ time delays should be set not to pick-up for transient overvoltages in the system with a typical
time delays of 1-2 seconds upwards being adequate for most applications. In the example above for a
345 kV transmission line of 400 km line length, the alarm threshold (stage 1) can be set to 105% and
the trip threshold set to 110% for example.
P446/EN/TM/E 8-41
8 Application Examples MiCOMho P446
Note: This condition causes a rise in the neutral voltage with respect to earth which is commonly referred
to as neutral voltage displacement or NVD.
Figure 15 and Figure 16 show the residual voltages that are produced during earth fault conditions
occurring on a solid and impedance earthed power system respectively.
E S R F
ZS ZL
A-G
VA
VA
VC VB VC VB VC VB
VA VRES
VA VRES
VB VB VB
VC VC VC
P0117ENa
Figure 15 shows the residual voltage measured by a IED for an earth fault on a solidly earthed system
is solely dependent upon the ratio of source impedance behind the IED to line impedance in front of
the IED, up to the point of fault. For a remote fault, the Zs/Zl ratio will be small, resulting in a
correspondingly small residual voltage. Depending on the setting, such an IED would only operate for
faults up to a certain distance along the system. The value of residual voltage generated for an earth
fault condition is given by the following general formula.
8-42 P446/EN/TM/E
MiCOMho P446 8 Application Examples
E S R F
ZS ZL
N
ZE A-G
VA - G
S VA - G
G,F R G,F
G,F
VC - G VC - G
VC - G
VB - G VB - G VB - G
VC - G VC - G VC - G
Z S0 + 3ZE
VRES = x3E
2ZS1 + Z S0 + 2ZL1 + Z L0 + 3ZE
P0118ENa
Figure 16 shows that a resistance earthed system will always generate a relatively large degree of
residual voltage, as the zero sequence source impedance now includes the earthing impedance. It
follows then, that the residual voltage generated by an earth fault on an insulated system will be the
highest possible value (3 x phase-neutral voltage), as the zero sequence source impedance is infinite.
The detection of a residual overvoltage condition is an alternative means of earth fault detection,
which does not require any measurement of zero sequence current. This may be particularly
advantageous at a tee terminal where the infeed is from a delta winding of a transformer (and the
delta acts as a zero sequence current trap).
Note: Where residual overvoltage protection is applied, such a voltage will be generated for a fault
occurring anywhere on that section of the system and hence the NVD protection must coordinate
with other earth/earth fault protection.
P446/EN/TM/E 8-43
8 Application Examples MiCOMho P446
Note: IDMT characteristics are selectable on the first stage of NVD in order that elements located at
various points on the system may be time graded with one another.
Note: All CB Fail resetting involves the operation of the undercurrent elements. Where element reset or
CB open resetting is used the undercurrent time setting should still be used if this proves to be the
worst case.
Note: Where auxiliary tripping IEDs are used, an additional 10-15 ms must be added to allow for trip IED
operation.
8-44 P446/EN/TM/E
MiCOMho P446 8 Application Examples
It is possible to apply a negative phase sequence overcurrent IED to detect the above condition.
However, on a lightly loaded line, the negative sequence current resulting from a series fault condition
may be very close to, or less than, the full load steady state unbalance arising from CT errors, load
unbalance etc. A negative sequence element therefore would not operate at low load levels.
Note: A minimum value of 8% negative phase sequence current is required for successful IED operation.
Since sensitive settings have been employed, it can be expected that the element will operate for any
unbalance condition occurring on the system (for example, during a single pole auto-reclose cycle).
Hence, a long time delay is necessary to ensure coordination with other protective devices. A 60
second time delay setting may be typical.
The example following information was recorded by the IED during commissioning;
full load = 500 A
2 = 50 A
therefore the quiescent 2/1 ratio is given by;
2/1 = 50/500 = 0.1
To allow for tolerances and load variations a setting of 20% of this value may be typical: Therefore set
2/1 = 0.2
In a double circuit (parallel line) application, using a 40% setting will ensure that the broken conductor
protection will operate only for the circuit that is affected. Setting 0.4 results in no pick-up for the
parallel healthy circuit.
Set 2/1 Time Delay = 60 s to allow adequate time for short circuit fault clearance by time delayed
protections.
P446/EN/TM/E 8-45
8 Application Examples MiCOMho P446
Generally, North American multiplexer networks are based on 56 kbit/sec (and multiples thereof)
channels, whereas multiplexer networks in the rest of the world are based on
64 kbit/sec (and multiples thereof) channels.
This setting is not applicable if IEEE C37.94 mode selected.
Note: An alarm indicating the signalling has failed, refers only to the incoming signals. The remote IED will
monitor the other direction of the communications link for quality of transmission. If indication of the
quality of the signal transmitted from the local IED for reception at the remote IED is required, then
one of the InterMiCOM command channels can be used to reflect this back.
8-46 P446/EN/TM/E
MiCOMho P446 8 Application Examples
For indirect connections, the settings applied become more application and communication media
dependent. As for the direct connections, consider only the fastest baud rate but this will usually
increase the cost of the necessary modem/multiplexer. In addition, devices operating at these high
baud rates may suffer from data jams during periods of interference and in the event of
communication interruptions, may require longer re-synchronization periods. Both of these factors will
reduce the effective communication speed thereby leading to a recommended baud rate setting of 9.6
kbit/s. As the baud rate decreases, the communications will become more robust with fewer
interruptions, but the overall signalling times will increase.
Since it is likely that slower baud rates will be selected, the choice of signalling mode becomes
significant. However, once the signalling mode has been chosen it is necessary to consider what
should happen during periods of noise when message structure and content can be lost. If Blocking
Mode is selected, only a small amount of the total message is actually used to provide the signal,
which means that in a noisy environment there is still a good likelihood of receiving a valid message.
In this case, it is recommended that the IM# Fallback Mode is set to Default with a reasonably long
IM# FrameSyncTim. A typical default selection of Default = 1 (blocking received substitute) would
generally apply as the failsafe assignment for blocking schemes.
If Direct Intertrip mode is selected, the whole message structure must be valid and checked to
provide the signal, which means that in a very noisy environment the chances of receiving a valid
message are quite small. In this case, it is recommended that the IM# Fallback Mode is set to
Default with a minimum IM# FrameSyncTim setting i.e. whenever a non-valid message is received,
InterMiCOM will use the set default value. A typical default selection of Default = 0 (intertrip NOT
received substitute) would generally apply as the failsafe assignment for intertripping schemes.
If Permissive mode is selected, the chances of receiving a valid message is between that of the
Blocking and Direct Intertrip modes. In this case, it is possible that the IM# Fallback Mode is set to
Latched. Table 7 shows the recommended IM# FrameSyncTim settings for the different signalling
modes and baud rates:
Minimum recommended Minimum setting Maximum setting
Baud rate
“IM# FrameSyncTim” Setting (ms) (ms)
Direct intertrip mode Blocking mode
600 100 250 100 1500
1200 50 130 50 1500
2400 30 70 30 1500
4800 20 40 20 1500
9600 10 20 10 1500
19200 10 10 10 1500
Table 7: Recommended IM# FrameSyncTim settings
Note: No recommended setting is given for the Permissive mode since it is anticipated that Latched
operation will be selected. However, if Default mode is selected, the IM# FrameSyncTim setting
should be set greater than the minimum settings listed above. If the IM# FrameSyncTim setting is
set lower than the minimum setting listed above, there is a danger that the IED will monitor a correct
change in message as a corrupted message.
3.17.2 InterMiCOM64
P446/EN/TM/E 8-47
8 Application Examples MiCOMho P446
security for Intertripping (Direct transfer tripping), the InterMiCOM64 Direct command is issued only
when 2 valid consecutive messages are received. The recommended setting is:
The setting files provide independent setting for each of the first 8 commands. Due to the fast data
rate, there is minimal speed difference between the two mode options. Both give a typical operating
time as shown in the following table. The operating time is the PSL trigger at the send IED to the PSL
state change at the receive IED.
Channel mode
Application Typical delay (ms) Maximum (ms) Comments
setting
Assuming no repeaters (no
Permissive Direct Fibre 3 to 7 9
source of digital “noise”)
For channel bit error rate up
Multiplexed Link 5 to 8 + MUX 12 + MUX
to 1 x 10-3
Assuming no repeaters (no
Direct Intertrip Direct Fibre 4 to 8 10
source of digital “noise”)
For channel bit error rate up
Multiplexed link 6 to 8 + MUX 13 + MUX
to 1 x 10-3
Table 8: Typical operating times in ms
8-48 P446/EN/TM/E
MiCOMho P446 8 Application Examples
4.1.1 Objective
To protect the 100 km double circuit line between Green Valley and Blue River substations using a
MiCOMho P446 in distance POR Permissive Overreach mode and to set the IED at Green Valley
substation, shown in Figure 17. It is assumed that mho characteristics will be used.
100km
80km 60km
21 21
System data
Green Valley - Blue River transmission line
System voltage 230kv
System grounding solid
CT ratio 1200/5
VT ratio 230000/115
Line length 100km
Line impedance
Z1 = 0.089 + J0.476 OHM/km
Z2 = 0.426 + J1.576 OHM/km
Fault levelts
Green Valley substation busbars maximum 5000MVA, minimum 2000MVA
Blue River substation busbars maximum 3000MVA, minimum 1000MVA
P1019ENa
Circuit continous rating = 400MVA
Worst-case power factor of load = 0.85 P1019ENb
P446/EN/TM/E 8-49
8 Application Examples MiCOMho P446
8-50 P446/EN/TM/E
MiCOMho P446 8 Application Examples
P446/EN/TM/E 8-51
8 Application Examples MiCOMho P446
With such a heavy load flow, the system voltage may be depressed, typically with phase voltages
down to 90% of Vn nominal.
Allowing for a tolerance in the measuring circuit inputs (line CT error, VT error, IED tolerance, and
safety margin), this results in a load impedance which might be 3 times the expected “rating”.
To avoid the load, the blinder impedance needs to be set:
Z (Rated phase-ground voltage Vn) / (IFLC x 3)
= (115/√3) / (IFLC x 3)
Set the V< Blinder voltage threshold at the recommended 70% of Vn = 66.4 x 0.7 = 45 V.
Note: Dual-end infeed effects will make a fault resistance appear higher, because each IED cannot
measure the current contribution from the remote line end. The apparent fault resistance increase
factor could be 2 to 8 times the calculated resistance. Therefore it is recommended that the zone
resistive reaches are set to say, 4 times the primary arc resistance calculation.
In the example, the minimum phase fault level is 1000 MVA. This is equivalent to an effective short-
circuit fault feeding impedance of:
Z = kV 2/MVA = 2302/1000 = 53 (primary)
The lowest phase fault current level is equivalent to:
Ifault = (MVA x 1000)/(3 x kV)
= (1000 x 1000)/(3 x 230)
= 2.5 kA
And this fault current in the van Warrington formula would give an arc resistance of:
Ra = 4
8-52 P446/EN/TM/E
MiCOMho P446 8 Application Examples
As this impedance is relatively small compared to the value “Z” calculated above, there is no need to
perform an iterative equation to work out the actual expected Ifault, which would in reality be lower due
to the added Ra arc resistance in the fault loop. It is sufficient to increase the calculated Ra by the
recommended factor of four, and a little extra to account for the fault current being lower than that
calculated. So in this case use a minimum setting of 5 x Ra, which is 20 primary.
It is obvious that the setting could easily be set above 20 on the primary system (perhaps following
the rule of thumb formula in section 3.1.7). Typically, all zone resistive reaches would be set greater
than this 20 primary figure, and ideally less than the load impedance (see “load avoidance” section).
P446/EN/TM/E 8-53
8 Application Examples MiCOMho P446
A Ia Ib B
Z at Z bt
Ic
Z ct
C
V
Va = I a Z at +I b Z bt Impedance seen by relay A = a
Ia
P1018ENa
I b = Ia + Ic P1018ENb
Figure 19 (i) shows the case where a short tee is connected close to another terminal. In this
case, Zone 1 elements set to 80% of the shortest relative feeder length do not overlap. This
leaves a section not covered by any Zone 1 element. Any fault in this section would result in
Zone 2 time delayed tripping.
Figure 19 (ii) shows an example where terminal 'C' has no infeed. Faults close to this terminal
will not operate the IED at 'C' and hence the fault will be cleared by the Zone 2 time-delayed
elements of the IEDs at 'A' and 'B'.
Figure 19 (iii) shows a further difficulty for a PUR scheme. In this example current is outfed
from terminal 'C' for an internal fault. The IED at 'C' will therefore see the fault as reverse and
not operate until the breaker at 'B' has opened; i.e. sequential tripping will occur.
8-54 P446/EN/TM/E
MiCOMho P446 8 Application Examples
(i) A B
Z1A Z1C
= area where no zone 1 overlap exists
(ii) A B
Z1A Z1B
C
No infeed
(iii) A B
P1134ENa
Relay at C sees reverse fault until B opens P1166ENa
P446/EN/TM/E 8-55
8 Application Examples MiCOMho P446
4.3 VT Connections
This type of VT arrangement cannot pass zero-sequence (residual) voltage to the IED, or provide any
phase to neutral voltage quantities. Therefore any protection that is dependent on phase to neutral
voltage measurements should be disabled.
The ground directional comparison elements, ground distance elements, neutral voltage displacement
(residual overvoltage) and CT supervision all use phase-to-neutral voltage signals for their operation
and should be disabled. The DEF elements should be selected for negative sequence polarization to
avoid the use of phase-to-neutral voltages. Under and overvoltage protection can be set as phase-to-
phase measuring elements, whereas all other protection elements should remain operational.
The accuracy of the single phase voltage measurements can be impaired when using vee connected
VTs. The IED attempts to derive the phase to neutral voltages from the phase to phase voltage
vectors. If the impedance of the voltage inputs were perfectly matched the phase to neutral voltage
measurements would be correct, provided the phase to phase voltage vectors were balanced.
However, in practice there are small differences in the impedance of the voltage inputs, which can
cause small errors in the phase to neutral voltage measurements. This may give rise to an apparent
residual voltage. This problem also extends to single phase power measurements that are also
dependent on their respective single phase voltages.
The phase to neutral voltage measurement accuracy can be improved by connecting three well-
matched, load resistors between the following phase voltage inputs and neutral point therefore
creating a virtual neutral point. The connections are shown below for each product:
Product Phase Voltage Inputs Neutral Point
P446 C19, C20, C21 C22
The load resistor values must be chosen so that their power consumption is within the limits of the VT. It is
recommended that 10k 1% (6 W) resistors are used for the 110 V (Vn) rated IED, assuming the VT can
supply this burden.
8-56 P446/EN/TM/E
MiCOMho P446 8 Application Examples
This scheme provides supervision of the trip coil with the breaker open or closed, however, preclosing
supervision is not provided. This scheme is also incompatible with latched trip contacts, as a latched
contact will short out the opto for greater than the recommended DDO timer setting of 400 ms. If
breaker status monitoring is required a further 1 or 2 opto inputs must be used.
Note: A 52a CB auxiliary contact follows the CB position and a 52b contact is in the opposite state.
When the breaker is closed, supervision current passes through the opto input, blocking diode and trip
coil. When the breaker is open current still flows through the opto input and into the trip coil using the
52b auxiliary contact. Hence, no supervision of the trip path is provided while the breaker is open.
Any fault in the trip path will only be detected on CB closing, after a 400 ms delay.
Resistor R1 is an optional resistor that can be fitted to prevent mal-operation of the circuit breaker if
the opto input is inadvertently shorted, by limiting the current to <60 mA. The resistor should not be
fitted for auxiliary voltage ranges of 30/34 volts or less, as satisfactory operation can no longer be
guaranteed. Table 10 shows the appropriate resistor value and voltage setting (OPTO CONFIG
menu) for this scheme.
This TCS scheme will function correctly even without resistor R1, since the opto input automatically
limits the supervision current to less that 10 mA. However, if the opto is accidentally shorted the circuit
breaker may trip.
Auxiliary voltage (Vx) Resistor R1 (ohms) Opto voltage setting with R1 fitted
48/54 1.2 k 24/27
110/250 2.5 k 48/54
220/250 5.0 k 110/125
Table 10: Resistor values and voltage settings for TCS scheme 1
Note: When R1 is not fitted the opto voltage setting must be set equal to supply voltage of the supervision
circuit.
P446/EN/TM/E 8-57
8 Application Examples MiCOMho P446
or during normal tripping operation when the opto input is shorted by a self-reset trip contact. When
the timer is operated the NC (normally closed) output relay opens and the LED and user alarms are
reset.
The 50 ms delay on pick-up timer prevents false LED and user alarm indications during the IED power
up time, following an auxiliary supply interruption.
0 0
Opto Input Drop-Off Straight NC Output Relay
400 0
Latching LED
50
& Pick-up
0
User Alarm
P2229ENa
Much like scheme 1, this scheme provides supervision of the trip coil with the breaker open or closed
and also does not provide preclosing supervision. However, using two opto inputs allows the IED to
correctly monitor the circuit breaker status since they are connected in series with the CB auxiliary
contacts. This is achieved by assigning Opto A to the 52a contact and Opto B to the 52b contact.
Provided the Circuit Breaker Status is set to 52a and 52b (CB CONTROL column) the IED correctly
monitors the status of the breaker. This scheme is also fully compatible with latched contacts as the
supervision current will be maintained through the 52b contact when the trip contact is closed.
When the breaker is closed, supervision current passes through opto input A and the trip coil. When
the breaker is open current flows through opto input B and the trip coil. As with scheme 1, no
supervision of the trip path is provided while the breaker is open. Any fault in the trip path will only be
detected on CB closing, after a 400 ms delay.
As with scheme 1, optional resistors R1 and R2 can be added to prevent tripping of the CB if either
opto is shorted. The resistor values of R1 and R2 are equal and can be set the same as R1 in
scheme 1.
8-58 P446/EN/TM/E
MiCOMho P446 8 Application Examples
0 0
Opto Input Drop-Off Straight NC Output Relay
400 0
Latching LED
50
& Pick-up
0
User Alarm
P2229ENa
Trip
Circuit Breaker
R3
Trip
Trip
Coil
52a
R2
P54x
Opto R1 52b
P2231ENc
Scheme 3 is designed to provide supervision of the trip coil with the breaker open or closed, but unlike
schemes 1 and 2, it also provides preclosing supervision. Since only one opto input is used, this
scheme is not compatible with latched trip contacts. If CB status monitoring is required a further 1 or 2
opto inputs must be used.
When the breaker is closed, supervision current passes through the opto input, resistor R2 and the trip
coil. When the breaker is open current flows through the opto input, resistors R1 and R2 (in parallel),
resistor R3 and the trip coil. Unlike schemes 1 and 2, supervision current is maintained through the
trip path with the breaker in either state, therefore giving full preclosing supervision.
As with schemes 1 and 2, resistors R1 and R2 are used to prevent false tripping, if the opto-input is
accidentally shorted. However, unlike the other two schemes, this scheme is dependent upon the
position and value of these resistors. Removing them would result in incomplete trip circuit monitoring.
Table 11 shows the resistor values and voltage settings required for satisfactory operation.
Auxiliary voltage (Vx) Resistor R1 & R2 (ohms) Resistor R3 (ohms) Opto voltage setting
48/54 1.2 k 0.6 k 24/27
110/250 2.5 k 1.2 k 48/54
220/250 5.0 k 2.5 k 110/125
Table 11: Resistor values and Voltage settings for TCS scheme 3
P446/EN/TM/E 8-59
8 Application Examples MiCOMho P446
Note: Scheme 3 is not compatible with auxiliary supply voltages of 30/34 volts and below.
4.5.1 InterMiCOM64 Mapping for Three Ended Application – BLOCKING or PUR Example
The following figure shows a suggested InterMiCOM64 mapping:
8-60 P446/EN/TM/E
MiCOMho P446 8 Application Examples
P446/EN/TM/E 8-61
8 Application Examples MiCOMho P446
When InterMiCOM64 is being used as the transmission medium for the aided channel signal(s), all that
is required is to create one-to-one mapping between the Aided scheme logic, and the InterMiCOM64
(IM64) signals to be used. The PSL editor is used to perform the simple mapping required.
To configure the signal SEND logic:
Route the required Aided send DDB signal to the IM64 Output to be used.
To configure the signal RECEIVE logic:
Route the required IM64 Input signal to the Aided scheme Rx DDB input.
BLOCKING schemes are recommended to take a logical OR of the incoming IM64 signals,
before being mapped to Aided scheme Rx. This is to ensure that if the fault is declared as
external at any line end, Zone 2 accelerated tripping at the local end is blocked.
PERMISSIVE UNDERREACH schemes are recommended to take a logical OR of the incoming
IM64 signals, before being mapped to Aided scheme Rx. Thus, if the fault is declared as
internal at any remote line end, Zone 2 accelerated tripping at the local end is allowed. As
Zone 1 is an underreaching element, it can only key the channel for an internal fault, so there is
no need for AND logic.
PERMISSIVE OVERREACH schemes are recommended to take a logical AND of the incoming
IM64 signals, before being mapped to Aided scheme Rx. This is to ensure that the fault must
be seen as forward from both remote ends before Zone 2 accelerated tripping at the local end is
allowed. As Zone 2 keys the channel, confirmation of a forward decision at all three line ends
must be confirmed before aided scheme tripping is permitted.
In all three terminal schemes, the send logic is a one-to-many mapping. The Aided send is mapped to
the IM64 signals which transmit to both remote ends. The connection to Ch1 (channel 1), and Ch2
(channel 2) ensures communication to the two remote ends. In case of channel failure between any
two IEDs, the Aided 1 COS/LGS signal will become high in the IED that is not receiving and activate
the FallBackMode. Therefore to preserve the stability in 3-ended blocking scheme, the corresponding
IM_X DefaultValue in the setting file must be set high. In any PUR and POR schemes such a
precaution is not necessary since the aided signal can not be sent through broken communications.
Notes: Two Aided schemes are available, Aided 1 and Aided 2. This allows for example an independent
Distance aided scheme, and a DEF aided scheme to be configured. Whether Aided 1 is used
alone, or Aided 2 is used too will depend on the utility preference. Further detail is available in the
MiCOM Technical Manual.
The InterMiCOM64 bits are duplex in nature, in other words InterMiCOM64 bit 1 between the IED at
line end A and B is completely independent from the same bit travelling from end B to A.
8-62 P446/EN/TM/E
MiCOMho P446 8 Application Examples
Likewise, where Aided scheme 2 is applied, it is more logical to assign IM64 bit 2, providing that it is
not already used in the PSL for some other function.
The use of an opto input allows a check that correct DC battery voltages are present for local
teleprotection purposes, or perhaps that a selector switch has not taken the scheme out of
service.
The use of a Control Input allows switching in or out of the teleprotection using menu
commands on the IED concerned. This provides convenient in-out switching of the entire
teleprotection scheme by visiting/addressing just one line end IED.
The exact logic condition to declare the local “signalling healthy” condition will be chosen such as to
reflect the utility’s practices. In the example shown, this logical condition is then mapped to IM64
Output 2 (bit 2), for transmitting to the two remote line ends.
To declare that the signalling scheme is healthy, bit 2 (the assigned health-check bit) must be received
from both remote ends. This can be combined with a general check on InterMiCOM64 messaging,
DDB #314. The AND gate shows that signalling is only healthy if:
A logical AND combination is used, with the gate output inverted to feed into the aided scheme logic.
This scheme failure output then feeds the standard Channel out of Service (COS) logic.
The fourth dotted box shows how the same scheme failure alarm (COS) can then be simply mapped
to any LED indication, or output contact for alarming.
Note: If a simpler scheme is preferred, it is not necessary to assign a health-check bit. In such instances,
the IM64 Scheme Fail alarm alone can be used to drive COS. However, if a test mode selection
were to disable the aided scheme at one end, the other line ends would have no indication of the
depleted operation.
For this reason, the use of the health-check bit is recommended.
P446/EN/TM/E 8-63
8 Application Examples MiCOMho P446
The assignment of IM64 bits is completely independent, per channel. For example if all 8
possible bits per channel are assigned to discrete functions, this allows a total of 16 end-end
signals.
The receive logic should employ AND (“both”) or OR (“any”) logic gate functions to combine the
dual redundant signals, as appropriate to the desired operation.
4.5.9.4 InterMiCOM64 Application Example - Directional Earth Fault (DEF) POR Permissive Overreach
8-64 P446/EN/TM/E
MiCOMho P446 8 Application Examples
Note: When adding any multiplexer delays, the maximum response time of the multiplexed link should be
assumed. This should include any addition for rerouting in self-healing networks.
P446/EN/TM/E 8-65
8 Application Examples MiCOMho P446
8-66 P446/EN/TM/E
MiCOMho P446 8 Application Examples
Also it is essential that the protection fully resets during the dead time, so that correct time
discrimination will be maintained after reclosure onto a fault. For high speed auto-reclose
instantaneous reset of protection is required.
For highly interconnected systems synchronism is unlikely to be lost by the tripping out of a single line.
Here the best policy may be to adopt longer dead times, to allow time for power swings on the system
resulting from the fault to settle.
P446/EN/TM/E 8-67
8 Application Examples MiCOMho P446
If the reclosure of the lead circuit breaker is successful, the follower circuit breaker can be allowed to
reclose. Delaying the reclosure of the follower circuit breaker will allow any transients to decay before
the switching and if the transient decay figure is known, can be used to determine a minimum follower
time value. The larger of the two values can then be used as the minimum follower time.
Note: The follower circuit breaker should only be reclosed if the system is healthy. In a dual circuit breaker
scheme where the system is healthy, the follower circuit breaker acts more like a bus coupler. In
this case there is no need for fast switching and a time delay in excess of 1s is often appropriate.
The MiCOMho P446 default follower time is chosen as 5 s and this can comfortably be applied to
most applications.
Note: For single pole high-speed auto-reclose, the capacitive current induced from the healthy phases can
increase the time taken to de-ionize fault arcs.
In practice a few additional cycles would be added to allow for tolerances, so Dead Time 1 could be
chosen as 300 ms, and 1Pole Dead Time could be chosen as 600 ms. The overall system dead
8-68 P446/EN/TM/E
MiCOMho P446 8 Application Examples
time is found by adding (d) to the chosen settings, and then subtracting (a). (This gives 335 ms and
635 ms respectively here).
Fault incidence/Past experience - Small reclaim times may be required where there is a high
incidence of recurrent lightning strikes to prevent unnecessary lockout for transient faults
Spring charging time - For high speed auto-reclose the reclaim time may be set longer than the
spring charging time. A minimum reclaim time of >5s may be needed to allow the CB time to
recover after a trip and close before it can perform another trip-close-trip cycle. This time will
depend on the duty (rating) of the CB. For delayed auto-reclose there is no need as the dead
time can be extended by an extra CB healthy check AR Inhibit Time window time if there is
insufficient energy in the CB
Switchgear Maintenance - Excessive operation resulting from short reclaim times can mean
shorter maintenance intervals
The Reclaim Time setting is generally set greater than the tZ2 distance zone delay
P446/EN/TM/E 8-69
8 Application Examples MiCOMho P446
Note: The settings are CB1 Broken ^, and CB2 Broken ^.
For circuit breakers operating on higher voltage systems, practical evidence suggests that the value of
“Broken ^” = 2 may be inappropriate. In such applications “Broken ^” may be set lower, typically 1.4
or 1.5. An alarm in this instance may indicate the need for gas/vacuum interrupter HV pressure
testing, for example. The setting range for “Broken ^” is variable between 1.0 and 2.0 in 0.1 steps. It
is imperative that any maintenance program must be fully compliant with the switchgear
manufacturer’s instructions.
Note: The settings use No. CB1 Ops Maint and No. CB2 Ops Maint.
8-70 P446/EN/TM/E
MiCOMho P446 8 Application Examples
6.1 Introduction
This application example is for two shot, single and three phase, auto-reclosing at one end of an EHV
(500 kV) overhead transmission line switched by two circuit breakers in a one and a half switch
configuration.
The circuit breakers are capable of either single phase or three phase tripping. Circuit breaker 1 (CB1)
is designated as Leader and recloses before Circuit breaker 2 (CB2). CB2 becomes the designated
Follower, and recloses after a Follower Time delay after CB1 has successfully reclosed.
The Leader, CB1 is arranged for single/three phase tripping and reclosing. The Follower, CB2 is
arranged to trip three phase for all faults.
For a single phase fault, CB1 trips single phase and CB2 trips three phase. When the fault has been
cleared, CB1 recloses single phase without any system voltage checks after the selected Single
Phase AR dead time. After the follower time delay, CB2 recloses three phase subject to a
synchronism check between the line and Bus 2.
For a two phase or three phase fault, both circuit breakers trip three phase. When the fault has been
cleared, CB1 recloses three phase after the selected Three Phase AR dead time, with either live
bus/dead line or live bus/live line check synchronism between the line and Bus 1. When CB1 has
successfully reclosed, after the follower time delay, CB2 recloses three phase, subject to a
synchronism check between the line and Bus 2.
For live line/live bus three phase reclosing of either circuit breaker, acceptable conditions are typically:
It is assumed that reclosing at the remote line end is either single phase with no system voltage
checks, or three phase with live bus/live line synchronism check.
3 phase input (3P + N, magnitude 110 V Ph-Ph, 63.5 V Ph-N) from a line VT, connected to the
Line VT (main VT) input;
1 phase input (A-B, magnitude 110 V) from a Bus1 VT connected to the Bus1 VT
(CB1 CS VT), input;
P446/EN/TM/E 8-71
8 Application Examples MiCOMho P446
1 phase input (A-B, magnitude 110 V) from a Bus2 VT connected to the Bus2 VT
(CB2 CS VT), input.
Under healthy system conditions each bus VT (check sync VT) input leads the A-phase to Neutral
Line VT input (main VT) by 30 degrees and has voltage magnitude of 110 V (assumes settings in
secondary values).
Main VT Primary (0A 01): set nominal system primary ph-ph voltage (500 kV);
Main VT Sec’y (0A 02): set 110 V;
CB1 CS VT Prim’y (0A 03): set nominal system primary ph-ph voltage (500 kV);
CB1 CS VT Sec’y (0A 04): set 110 V;
CB2 CS VT Prim’y (0A 05): set nominal system primary ph-ph voltage (500 kV);
CB2 CS VT Sec’y (0A 06): set 110 V;
CS Input (0A 0F): set A-N;
CB1 CS VT PhShft (0A 21): set -30 degrees (this creates a “compensated” Bus1 phase angle
normally in phase with the selected CS Input);
CB1 CS VT Mag (0A 22): set 0.58 (this creates a “compensated” Bus1 voltage magnitude
normally equal to that of the selected CS Input);
CB2 CS VT PhShft (0A 23): set -30 degrees (this creates a “compensated” Bus2 phase angle
normally in phase with the selected CS Input);
CB2 CS VT Mag (0A 24): set 0.58 (creates a “compensated” Bus2 voltage magnitude normally
equal to that of the selected CS Input);
8-72 P446/EN/TM/E
MiCOMho P446 8 Application Examples
Note: VT secondary voltage settings in this section of the menu are always set in terms of phase to phase
values, even when the actual inputs are taken from phase to neutral VT terminals.
Live Line (48 85): set 32 V (typical setting 50% of nominal applied voltage of selected CS Input
(set to A-N in this example))
Dead Line (48 86): set 13 V (typical setting 20% of nominal applied voltage of selected CS
Input (set to A-N in this example))
Live Bus 1 (48 87): set 32 V (typical setting 50% of “compensated” nominal applied voltage)
Dead Bus 1 (48 88): set 13 V (typical setting 20% of “compensated” nominal applied voltage)
Live Bus 2 (48 89): set 32 V (typical setting 50% of “compensated” nominal applied voltage)
Dead Bus 2 (48 8 A): set 13 V (typical setting 20% of “compensated” nominal applied voltage)
CS UV (48 8B): set 54 V (typical setting 85% of nominal applied voltage of selected
CS Input (set to A-N in this example))
CS OV (48 8C): set 76 V (typical setting 120% of nominal applied voltage of selected CS Input
(set to A-N in this example))
Sys Checks CB1 (48 8D): set Enabled
CB1 CS Volt. Blk (48 8E): set V< V> and Vdiff
CB1 CS1 Status (48 8F): set Enabled
CB1 CS1 Angle (48 90): set 20 degree
CB1 CS1 Vdiff (48 91): set 6.5 V (typical setting 10% of nominal applied voltage of selected CS
Input (set to A-N in this example))
CB1 CS1 SlipCtrl (48 92): set Enabled
CB1 CS1 SlipFreq (48 93): set 0.05 Hz
CB1 CS2 Status (48 94): set Disabled
Sys Checks CB2 (48 9B): set Enabled
CB2 CS Volt. Blk (48 9C): set V< V> and Vdiff
CB2 CS1 Status (48 9D): set Enabled
CB2 CS1 Angle (48 9E): set 20 degrees
P446/EN/TM/E 8-73
8 Application Examples MiCOMho P446
CB2 CS1 Vdiff (48 9F): set 6.5 V (typical setting 10% of nominal applied voltage of selected CS
Input (set to A-N in this example))
CB2 CS1 SlipCtrl (48 A0): set Enable
CB2 CS1 SlipFreq (48 A1): set 0.05 Hz
CB2 CS2 Status (48 94): set Disabled
8-74 P446/EN/TM/E
MiCOMho P446 8 Application Examples
To test the application example, as well as applying appropriate current and voltage connections, the
settings, and the PSL, it is necessary to use some secondary test equipment capable of mimicking the
circuit breaker status.
P446/EN/TM/E 8-75
8 Application Examples MiCOMho P446
For any specific application, the Application Engineer must analyze the particular power systems to
determine the appropriate settings and PSL mappings.
8-76 P446/EN/TM/E
MiCOMho P446 8 Application Examples
Note: It is not necessary to repeat the calculation for earth faults, as the phase reach calculation (3) is
the worst-case for CT dimensioning.
P446/EN/TM/E 8-77
8 Application Examples MiCOMho P446
8-78 P446/EN/TM/E
MiCOMho P446 8 Application Examples
7.6.9 Calculation of Line Impedance Till Zone1 Reach Point (80 kms)
Zzone1 = 0.8 * ZL = 7.12 + j 38.08 ohms
= 38.73 ohms with an angle of 79.4 deg
P446/EN/TM/E 8-79
8 Application Examples MiCOMho P446
7.6.16 Vk to be considered
Using the above sections, the different Vk requirements are to be calculated for all the functions that
will be enabled, or that will be brought into operation. Then the highest Vk shall be considered for the
CT design.
8-80 P446/EN/TM/E
MiCOMho P446 8 Application Examples
P446/EN/TM/E 8-81
8 Application Examples MiCOMho P446
Alternatively, Miniature Circuit Breakers (MCBs) may be used to protect the auxiliary supply circuits.
8-82 P446/EN/TM/E
MICOMho P446 9 SCADA Communications
SCADA COMMUNICATIONS
CHAPTER 9
P446/EN/TM/E 9-1
9 SCADA Communications MICOMho P446
9-2 P446/EN/TM/E
MICOMho P446 9 SCADA Communications
1 CHAPTER OVERVIEW
The MiCOM Px40 series supports substation SCADA communications based on two communications
technologies; serial and Ethernet. Serial communications has been around for a long time, and there
are many substations still wired up this way. Ethernet is a more modern medium and all modern
substation communications is based on this technology. Alstom Grid's MiCOM Px40 products support
both of these communication technologies.
This chapter consists of the following sections:
1 Chapter Overview
2 Communication Interfaces
3 Serial Communication
3.1 EIA(RS)232 Bus
3.2 EIA(RS)485 Bus
3.3 K-Bus
3.4 Optical Fibre
8 IEC 60870-5-103
8.1 Physical Connection and Link Layer
8.2 Initialization
8.3 Time Synchronization
8.4 Spontaneous Events
8.5 General Interrogation (GI)
8.6 Cyclic Measurements
8.7 Commands
P446/EN/TM/E 9-3
9 SCADA Communications MICOMho P446
9 DNP 3.0
9.1 Physical Connection and Link Layer
9.2 Object 1 Binary Inputs
9.3 DNP 3.0 Object 10 Binary Outputs
9.4 Object 20 Binary Counters
9.5 Object 30 Analogue Input
9.6 Object 40 Analogue Output
9.7 Configuration
10 IEC 61850
10.1 Benefits of IEC 61850
10.2 IEC 61850 Interoperability
10.3 The IEC 61850 Data Model
10.4 IEC 61850 in MiCOM IEDs
10.5 The IEC 61850 Data Model of MiCOM IEDs
10.6 The IEC 61850 Communication Services of MiCOM IEDs
10.7 IEC 61850 Peer-to-peer (GSSE) communications
10.8 Mapping GOOSE Messages to Virtual Inputs
10.8.1 IEC 61850 GOOSE Configuration
10.9 Ethernet Functionality
10.9.1 Ethernet Disconnection
10.9.2 Loss of Power
9-4 P446/EN/TM/E
MICOMho P446 9 SCADA Communications
2 COMMUNICATION INTERFACES
The MiCOM Px40 IEDs have a number of standard and optional communication interfaces. The
standard and optional hardware and protocols are summarised below:
Physical
Port Availability Use Data Protocols
layer
Front Standard RS232 Local settings Courier
Rear Port 1 RS232 / RS485 / SCADA Courier, MODBUS, IEC60870-5-103, DNP3.0
Standard
(RP1 copper) K-Bus Remote settings (order option)
Rear Port 1 SCADA Courier, MODBUS, IEC60870-5-103, DNP3.0
Optional Fibre
(RP1 fibre) Remote settings (order option)
Rear Port 2 RS232 / RS485 / SCADA
Optional Courier
(RP2) K-Bus Remote settings
IEC 61850 or DNP3 IEC 61850, Courier (tunnelled) or DNP3.0
Ethernet Optional Ethernet
Remote settings (order option)
Notes:
1. Optional communications boards are always fitted into slot A and only slot A.
2. When optional fibre board is used for serial SCADA communication over optical fibre, the fibre port
assumes designation RP1. The RP1 copper ports on power supply board are then disabled.
3. It is only possible to fit one optional communications board, therefore RP2 and Ethernet
communications are mutually exclusive.
P446/EN/TM/E 9-5
9 SCADA Communications MICOMho P446
3 SERIAL COMMUNICATION
Serial communication is possible over metallic or optical fibre cables.
The physical layer standards that are used for metallic serial communications for SCADA purposes
are:
9-6 P446/EN/TM/E
MICOMho P446 9 SCADA Communications
It may be necessary to bias the signal wires to prevent jabber. Jabber occurs when the signal level
has an indeterminate state because the bus is not being actively driven. This can occur when all the
slaves are in receive mode and the master is slow to turn from receive mode to transmit mode. This
may be because the master is waiting in receive mode, in a high impedance state, until it has
something to transmit. Jabber causes the receiving device(s) to miss the first bits of the first character
in the packet, which results in the slave rejecting the message and consequently not responding.
Symptoms of this are; poor response times (due to retries), increasing message error counts, erratic
communications, and in the worst case, complete failure to communicate.
Biasing Requirements
Biasing requires that the signal lines be weakly pulled to a defined voltage level of about 1 V. There
should only be one bias point on the bus, which is best situated at the master connection point. The
DC source used for the bias must be clean to prevent noise being injected. Figure 2 shows a typical
biasing arrangement.
Note: Some devices may be able to provide the bus bias, in which case external components would not
be required.
It is possible to use the product’s field voltage output (48 V DC) to bias the bus using values of 2.2 kΩ
0.5 W bias resistors instead of the 180 Ω resistors shown in the above diagram. If using the field
voltage, please heed the following warnings.
As the field voltage is much higher than that required, Alstom Grid cannot
assume responsibility for any damage that may occur to a device connected
to the network as a result of incorrect application of this voltage
Ensure the field voltage is not used for other purposes, such as powering
logic inputs, because noise may be passed to the communication network.
P446/EN/TM/E 9-7
9 SCADA Communications MICOMho P446
3.3 K-Bus
K-Bus is a robust signalling method based on RS485 voltage levels. K-Bus incorporates message
framing, based on a 64 kbps synchronous HDLC protocol with FM0 modulation to increase speed and
security.
The rear interface is used to provide a permanent connection for K-Bus, which allows multi-drop
connection.
A K-Bus spur consists of up to 32 IEDs connected together in a multi-drop arrangement using twisted
pair wiring. The spur can be up to 1000 m in length. The K-Bus twisted pair connection is non-
polarized.
Two-core screened twisted pair cable should be used. The final cable specification is dependent on
the application, although a multi-strand 0.5 mm2 per core is normally adequate. The total cable length
must not exceed 1000 m. It is important to avoid circulating currents, which can cause noise and
interference, especially when the cable runs between buildings. For this reason, the screen should be
continuous and connected to ground at one end only, normally at the master connection point.
The K-Bus signal is a differential signal and there is no signal ground connection. If a signal ground
connection is present in the bus cable then it must be ignored. At no stage should this be connected
to the cable's screen or to the product’s chassis. This is for both safety and noise reasons.
It is not possible to use a standard EIA(RS)232 to EIA(RS)485 converter to convert IEC 60870-5
FT1.2 frames to K-Bus. A protocol converter, namely the KITZ101, KITZ102 or KITZ201, must be
used for this purpose. Please consult Alstom Grid for information regarding the specification and
supply of KITZ devices. The following figure demonstrates a typical K-Bus connection.
9-8 P446/EN/TM/E
MICOMho P446 9 SCADA Communications
P0109ENf
Further information about K-Bus is available in the publication R6509: K-Bus Interface Guide, which is
available on request.
P446/EN/TM/E 9-9
9 SCADA Communications MICOMho P446
9-10 P446/EN/TM/E
MICOMho P446 9 SCADA Communications
P4406ENa
The RSTP solution is based on open standards. It is therefore compatible with other Manufacturers’
IEDs that use the RSTP protocol. The RSTP recovery time is typically 300 ms but it increases with
network size, therefore cannot achieve the desired bumpless redundancy.
P446/EN/TM/E 9-11
9 SCADA Communications MICOMho P446
The devices shown in Figure 4 are repeaters with a standard 802.3 Ethernet switch plus the Self-
Healing Manager (SHM). Figure 5 shows the internal architecture of such a device.
9-12 P446/EN/TM/E
MICOMho P446 9 SCADA Communications
The SHM functions manage the ring. If the fibre optic connection between two devices is broken, the
network continues to run correctly.
Normally the Ethernet packets travel on the primary fibre in the same direction, and only a checking
frame (4 octets) is sent every 5 μs on the secondary fibre in the opposite direction.
If the link goes down, both SHMs immediately start the network self-healing. At one side of the break,
received messages are no longer sent to the primary fibre but are sent to the secondary fibre. On the
other side of the break, messages received on the secondary fibre are sent to the primary fibre and
the new topological loop is closed in less than 1 ms.
As well as providing bumpless redundancy for unintentional network failure, this system can also be
used to extend the number of devices, or the size of a sub-station network, without having to disable
the network.
First, the loop is opened intentionally and it immediately self heals. Then the new equipment is
connected and it immediately self heals again, closing the loop.
To increase the reliability some additional mechanisms are used:
The quality of transmission is monitored. Each frame (Ethernet packet or checking frame) is
controlled by the SHM. Even if the link is not broken, but a larger than normal error rate is
detected, the redundancy mechanism is initiated.
Even if there is no traffic in the primary link, the secondary link is still supervised by sending out
checking frames every 5 μs.
P446/EN/TM/E 9-13
9 SCADA Communications MICOMho P446
Each frame carries a sequence number which is incremented and inserted into both frames.
Specific frames are used to synchronize the discard mechanism.
9-14 P446/EN/TM/E
MICOMho P446 9 SCADA Communications
The H36x is a repeater with a standard 802.3 Ethernet switch, plus the DHM. Figure 9 shows the
internal architecture of such a device.
Embedded Flash
Managed Switch Memory
Port MII
Failsafe
Dual Homing Address
Output
Relays Manager (DHM) Switch
Link A Link A
Rx Tx
Tx Rx
Link B Link B
P4415ENc
Key: PHY = Physical port
P446/EN/TM/E 9-15
9 SCADA Communications MICOMho P446
5.2 Forwarding
The MiCOM ALSTOM Ethernet switch products support store and forward mode. The switch forwards
messages with known addresses to the appropriate port. The messages with unknown addresses,
the broadcast messages and the multicast messages are forwarded out to all ports except the source
port. MiCOM ALSTOM switches do not forward error packets, 802.3x pause frames, or local packets.
9-16 P446/EN/TM/E
MICOMho P446 9 SCADA Communications
database that provides a logical collection of managed object definitions. The MIB defines the data
type of each managed object and describes the object.
The SNMP-related branches of the MIB tree are located in the internet branch, which contains two
main types of branches:
Public branches (mgmt=2), which are defined by the Internet Engineering Task Force (IETF).
Private branches (private=4), which are assigned by the Internet Assigned Numbers Authority
(IANA). These are defined by the companies and organizations to which these branches are
assigned.
The following figure shows the structure of the SNMP MIB tree. There are no limits on the width and
depth of the MIB tree.
iso = 1
org = 3
dod = 6
internet = 1
mgmt = 2 private = 4
mib-2 = 1 enterprises = 1
sysDescr = 1
P4516ENa
The top four levels of the hierarchy are fixed. These are:
Management (mgmt) is the main public branch. It defines network management parameters common
to devices from all vendors. Underneath the Management branch is MIB-II (mib-2), and beneath this
are branches for common management functions such as system management, printers, host
resources, and interfaces.
The private branch of the MIB tree contains branches for large organizations, organized under the
enterprises branch. This is not applicable to Alstom Grid.
P446/EN/TM/E 9-17
9 SCADA Communications MICOMho P446
sysDescr
sysUpTime
sysName.
Various SNMP client software tools can be used. Alstom Grid recommends using an SNMP MIB
browser, which can perform the basic SNMP operations such as GET, GETNEXT and RESPONSE.
Note: There are two IP addresses visible when communicating with the Redundant Ethernet Card via the
fibre optic ports: One for the IED itself and one for the on-board Ethernet switch. To access the
network using SNMP, use the IP address of the on-board Ethernet Switch and not that of the IED
REB. See the configuration chapter for further information.
9-18 P446/EN/TM/E
MICOMho P446 9 SCADA Communications
P446/EN/TM/E 9-19
9 SCADA Communications MICOMho P446
The relationship of these protocols to the lower level physical layer protocols is shown in Figure 12.
9-20 P446/EN/TM/E
MICOMho P446 9 SCADA Communications
7 COURIER
This section should provide sufficient detail to enable understanding of the Courier protocol at a level
required by most users. For situations where the level of information contained in this manual is
insufficient, further publications (R6511 and R6512) containing in-depth details about the protocol and
its use, are available on request.
Courier is an Alstom Grid proprietary communication protocol. Courier uses a standard set of
commands to access a database of settings and data in the IED. This allows a master to
communicate with a number of slave devices. The application-specific elements are contained in the
database rather than in the commands used to interrogate it, meaning that the master station does not
need to be preconfigured. Courier also provides a sequence of event (SOE) and disturbance record
extraction mechanism.
The front serial RS232 port (for connection to Settings application software on, for example, a
laptop
Rear Port 1 (RP1) - for permanent SCADA connection via RS485 or K-Bus
Optional fibre port (RP1 in slot A) - for permanent SCADA connection via optical fibre
Optional Rear Port 2 (RP2) - for permanent SCADA connection via RS485, K-Bus, or RS232
For either of the rear ports, both the IED address and baud rate can be selected using the front panel
menu or by a suitable application such as MiCOM S1 Studio.
With the exception of the Disturbance Recorder settings, changes made to the control and support
settings are implemented immediately and stored in non-volatile memory. Changes made to the
Protection settings and the Disturbance Recorder settings are stored in ‘scratchpad’ memory and are
not immediately implemented. These need to be committed by writing to the Save Changes cell in the
CONFIGURATION column.
P446/EN/TM/E 9-21
9 SCADA Communications MICOMho P446
Method 1
This uses a combination of three commands to perform a settings change:
First, enter Setting mode: This checks that the cell is settable and returns the limits.
1. Preload Setting: This places a new value into the cell. This value is echoed to ensure that
setting corruption has not taken place. The validity of the setting is not checked by this action.
2. Execute Setting: This confirms the setting change. If the change is valid, a positive response
is returned. If the setting change fails, an error response is returned.
3. Abort Setting: This command can be used to abandon the setting change.
This is the most secure method. It is ideally suited to on-line editors because the setting limits are
extracted before the setting change is made. However, this method can be slow if many settings are
being changed because three commands are required for each change.
Method 2
The Set Value command can be used to change a setting directly. The response to this command is
either a positive confirm or an error code to indicate the nature of a failure. This command can be
used to implement a setting more rapidly than the previous method, however the limits are not
extracted. This method is therefore most suitable for off-line setting editors such as MiCOM S1
Studio, or for issuing preconfigured control commands.
9-22 P446/EN/TM/E
MICOMho P446 9 SCADA Communications
Event Types
The IED generates events under certain circumstances such as:
Cell reference
Time stamp
Cell text
Cell value
The Menu Database contains tables of possible events, and shows how the contents of the above
fields are interpreted. Fault and Maintenance records return a Courier Type 3 event, which contains
the above fields plus two additional fields:
These events contain additional information, which is extracted from the IED using the RECORDER
EXTRACTION column B4. Row 01 of the RECORDER EXTRACTION column contains a Select
Record setting that allows the fault or maintenance record to be selected. This setting should be set
to the event number value returned in the record. The extended data can be extracted from the IED by
uploading the text and data from the column.
P446/EN/TM/E 9-23
9 SCADA Communications MICOMho P446
Domain cell (B204): Used to select either PSL settings (upload or download) or PSL
configuration data (upload only)
Sub-Domain cell (B208): Used to select the Protection Setting Group to be uploaded or
downloaded.
Version cell (B20C): Used on a download to check the compatibility of the file to be
downloaded.
Transfer Mode cell (B21C): Used to set up the transfer process.
Data Transfer cell (B120): Used to perform upload or download.
The programmable scheme-logic settings can be uploaded and downloaded to and from the IED using
this mechanism. MiCOM S1 Studio must be used to edit the settings. MiCOM MiCOM S1 Studio also
performs checks on the validity of the settings before they are transferred to the IED.
7.9 Configuration
To configure the IED for Courier, please see the Configuration chapter
9-24 P446/EN/TM/E
MICOMho P446 9 SCADA Communications
8 IEC 60870-5-103
The specification IEC 60870-5-103 (Telecontrol Equipment and Systems Part 5 Section 103:
Transmission Protocols), defines the use of standards IEC 60870-5-1 to IEC 60870-5-5, which were
designed for communication with protection equipment
This section describes how the IEC 60870-5-103 standard is applied to the Px40 platform. It is not a
description of the standard itself. The level at which this section is written assumes that the reader is
already familiar with the IEC 60870-5-103 standard.
This section should provide sufficient detail to enable understanding of the standard at a level required
by most users. For situations where the level of information contained in this manual is insufficient, a
further publication (R6510) is available on request.
The IEC 60870-5-103 interface is a master/slave interface with the device as the slave device. The
device conforms to compatibility level 2,as defined in the IEC60870-5-103.standard.
The following IEC 60870-5-103 facilities are supported by this interface:
Initialization (reset)
Time synchronization
Event record extraction
General interrogation
Cyclic measurements
General commands
Disturbance record extraction
Private codes
If the optional fibre optic port is fitted, a menu item appears in which the active port can be selected.
However the selection is only effective following the next power up.
For either of the two connection modes, both the IED address and baud rate can be selected using the
front panel menu or by a suitable application such as MiCOM S1 Studio.
8.2 Initialization
Whenever the device has been powered up, or if the communication parameters have been changed
a reset command is required to initialize the communications. The device will respond to either of the
two reset commands; Reset CU or Reset FCB (Communication Unit or Frame Count Bit). The
difference between the two commands is that the Reset CU command will clear any unsent messages
in the transmit buffer, whereas the Reset FCB command does not delete any messages.
The device will respond to the reset command with an identification message ASDU 5. The Cause of
Transmission (COT) of this response will be either Reset CU or Reset FCB depending on the nature of
the reset command. The content of ASDU 5 is described in the IEC 60870-5-103 section of the Menu
Database, available from Alstom Grid separately if required.
In addition to the above identification message, it will also produce a power up event.
P446/EN/TM/E 9-25
9 SCADA Communications MICOMho P446
Function type
Information Number
The IEC 60870-5-103 profile in the Menu Database contains a complete listing of all events produced
by the device.
8.7 Commands
A list of the supported commands is contained in the Menu Database. The device will respond to
other commands with an ASDU 1, with a cause of transmission (COT) indicating ‘negative
acknowledgement’.
9-26 P446/EN/TM/E
MICOMho P446 9 SCADA Communications
8.11 Configuration
To configure the IED for IEC 60870-1-5-103, please see the Configuration chapter.
P446/EN/TM/E 9-27
9 SCADA Communications MICOMho P446
9 DNP 3.0
This section describes how the DNP 3.0 standard is applied to the Px40 platform. It is not a
description of the standard itself. The level at which this section is written assumes that the reader is
already familiar with the DNP 3.0 standard.
The descriptions given here are intended to accompany the device profile document that is included in
the Menu Database document. The DNP 3.0 protocol is not described here, please refer to the
documentation available from the user group. The device profile document specifies the full details of
the DNP 3.0 implementation. This is the standard format DNP 3.0 document that specifies which
objects; variations and qualifiers are supported. The device profile document also specifies what data
is available from the device using DNP 3.0. The IED operates as a DNP 3.0 slave and supports
subset level 2, as described in the DNP 3.0 standard, plus some of the features from level 3.
The DNP 3.0 protocol is defined and administered by the DNP Users Group. For further information
on DNP 3.0 and the protocol specifications, please see www.dnp.org.
The IED address and baud rate can be selected using the front panel menu or by a suitable
application such as MiCOM S1 Studio.
When using a serial interface, the data format is: 1 start bit, 8 data bits, 1 stop bit and optional
configurable parity bit.
If the Control Input DDB signal is already SET and a new DNP SET command is sent to the
Control Input, the Control Input DDB signal goes momentarily to RESET and then back to SET.
9-28 P446/EN/TM/E
MICOMho P446 9 SCADA Communications
If the Control Input DDB signal is already RESET and a new DNP RESET command is sent to
the Control Input, the Control Input DDB signal goes momentarily to SET and then back to
RESET.
Control Input
(Latched)
Aliased Control
Input
(Latched)
Control Input
(Pulsed)
Aliased Control
Input
(Pulsed)
'Behaviour of Control Inputs
Existing with Pulsed/Latched Setting
Aliased Control Inputs with Pulsed/Latched Setting
Note: The pulse width is equal to the duration of one protection
iteration (1/16 cycle)
P4218ENe
Many of the IED’s functions are configurable so some of the object 10 commands described in the
following sections may not be available. A read from object 10 reports the point as off-line and an
operate command to object 12 generates an error response.
Examples of object 10 points that maybe reported as off-line are:
P446/EN/TM/E 9-29
9 SCADA Communications MICOMho P446
running counters of object 20 accept the read, freeze and clear functions. The freeze function takes
the current value of the object 20 running counter and stores it in the corresponding object 21 frozen
counter. The freeze and clear function resets the object 20 running counter to zero after freezing its
value.
Binary counter and frozen counter change event values are available for reporting from object 22 and
object 23 respectively. Counter change events (object 22) only report the most recent change, so the
maximum number of events supported is the same as the total number of counters. Frozen counter
change events (object 23) are generated whenever a freeze operation is performed and a change has
occurred since the previous freeze command. The frozen counter event queues store the points for
up to two freeze operations.
9.7 Configuration
To configure the IED for DNP 3.0, please see the Configuration chapter
9-30 P446/EN/TM/E
MICOMho P446 9 SCADA Communications
10 IEC 61850
This section describes how the IEC 61850 standard is applied to the Px40 platform. It is not a
description of the standard itself. The level at which this section is written assumes that the reader is
already familiar with the IEC 61850 standard.
IEC 61850 is the international standard for Ethernet-based communication in substations. It enables
integration of all protection, control, measurement and monitoring functions within a substation, and
additionally provides the means for interlocking and inter-tripping. It combines the convenience of
Ethernet with the security that is so essential in substations today.
Standardized models for IEDs and other equipment within the substation
Standardized communication services (the methods used to access and exchange data)
Standardized formats for configuration files
Peer-to-peer communication
The standard adheres to the requirements laid out by the ISO OSI model and thus provides complete
vendor interoperability and flexibility on the transmission types and protocols used. This includes
mapping of data onto Ethernet, which is becoming more and more widely used in substations, in
favour of RS485. Using Ethernet in the substation offers many advantages, most significantly
including:
Ethernet allows high-speed data rates (currently 100 Mbps, rather than 10’s of kbps or less
used by most serial protocols)
Ethernet provides the possibility to have multiple clients
Ethernet is an open standard in every-day use
There is a wide range of Ethernet-compatible products that may be used to supplement the LAN
installation (hubs, bridges, switches)
P446/EN/TM/E 9-31
9 SCADA Communications MICOMho P446
An IEC 61850 client (or master), for example a PACiS computer (MiCOM C264)
An HMI
9-32 P446/EN/TM/E
MICOMho P446 9 SCADA Communications
An MMS browser, with which the full data model can be retrieved from the IED, without any prior
knowledge of the IED
The IEC 61850 compatible interface standard provides capability for the following:
Note: Setting changes are not supported in the current IEC 61850 implementation. Currently these setting
changes are carried out using Alstom Grid's MiCOM S1 Studio Settings & Records application.
Note: Multicast messages cannot be routed across networks without specialized equipment.
Each new message is re-transmitted at configurable intervals, to counter for possible corruption due to
interference, and collisions, thus ensuring delivery. In practice, the parameters controlling the
message transmission cannot be calculated. Time must be allocated to the testing of GSSE schemes
before or during commissioning, in just the same way a hardwired scheme must be tested.
P446/EN/TM/E 9-33
9 SCADA Communications MICOMho P446
BOOLEAN
BSTR2
INT16
INT32
INT8
UINT16
UINT32
UINT8
9-34 P446/EN/TM/E
MiCOMho P446 10 Cyber Security
CYBER SECURITY
CHAPTER 10
P446/EN/TM/E 10-1
10 Cyber Security MiCOMho P446
10-2 P446/EN/TM/E
MiCOMho P446 10 Cyber Security
1 OVERVIEW
In the past, substation networks were traditionally isolated and the protocols and data formats used to
transfer information between devices were more often than not proprietary.
For these reasons, the substation environment was very secure against cyber attacks. The terms used
for this inherent type of security are:
Security by isolation (if the substation network is not connected to the outside world, it can’t be
accessed from the outside world).
Security by obscurity (if the formats and protocols are proprietary, it is very difficult to interpret
them.
The increasing sophistication of protection schemes coupled with the advancement of technology and
the desire for vendor interoperability has resulted in standardization of networks and data interchange
within substations. Today, devices within substations use standardized protocols for communication.
Furthermore, substations can be interconnected with open networks, such as the internet or
corporate-wide networks, which use standardized protocols for communication. This introduces a
major security risk making the grid vulnerable to cyber-attacks, which could in turn lead to major
electrical outages.
Clearly, there is now a need to secure communication and equipment within substation environments.
This chapter describes the security measures that have been put in place for Alstom Grid's range of
Intelligent Electronic Devices (IEDs).
The chapter contains the following sections:
1 Overview
2 The need for Cyber Security
3 Standards
3.1 NERC Compliance
3.1.1 CIP 002
3.1.2 CIP 003
3.1.3 CIP 004
3.1.4 CIP 005
3.1.5 CIP 006
3.1.6 CIP 007
3.1.7 CIP 008
3.1.8 CIP 009
3.2 IEEE 1686-2007
P446/EN/TM/E 10-3
10 Cyber Security MiCOMho P446
10-4 P446/EN/TM/E
MiCOMho P446 10 Cyber Security
The threats to cyber security may be unintentional (e.g. natural disasters, human error), or intentional
(e.g. cyber attacks by hackers).
Good cyber security can be achieved with a range of measures, such as closing down vulnerability
loopholes, implementing adequate security processes and procedures and providing technology to
help achieve this.
Examples of vulnerabilities are:
To help tackle these issues, standards organizations have produced various standards, by which
compliance significantly reduces the threats associated with lack of cyber security.
P446/EN/TM/E 10-5
10 Cyber Security MiCOMho P446
3 STANDARDS
There are several standards, which apply to substation cyber security (see Table 1).
Country
NERC CIP (North American Electric Reliability Framework for the protection of the grid critical Cyber
USA
Corporation) Assets
BDEW (German Association of Energy and Water Requirements for Secure Control and
Germany
Industries) Telecommunication Systems
ICS oriented then Relevant for EPU completing existing
ANSI ISA 99 USA standard and identifying new topics such as patch
management
International Standard for substation IED cyber security
IEEE 1686 International
capabilities
IEC 62351 International Power system data and Comm. protocol
Framework for the protection of the grid critical Cyber
ISO/IEC 27002 International
Assets
NIST SP800-53 (National Institute of Standards and Complete framework for SCADA SP800-82and ICS
USA
Technology) cyber security
CPNI Guidelines (Centre for the Protection of National Clear and valuable good practices for Process Control
UK
Infrastructure) and SCADA security
Table 1: Standards applicable to cyber security
The standards currently applicable to Alstom Grid IEDs are NERC and IEEE1686.
10-6 P446/EN/TM/E
MiCOMho P446 10 Cyber Security
The following sections provide further details about each of these standards, describing the associated
responsibilities of the utility company and where the IED manufacturer can help the utilities with the
necessary compliance to these standards.
P446/EN/TM/E 10-7
10 Cyber Security MiCOMho P446
Test procedures
Ports and services
Security patch management
Antivirus
Account management
Monitoring
An annual vulnerability assessment should be performed
10-8 P446/EN/TM/E
MiCOMho P446 10 Cyber Security
Passwords are 8 characters long and can contain upper-case, lower-case, numeric and special
characters.
Passwords are never displayed or transmitted to a user.
IED functions and features are assigned to different password levels. The assignment is fixed.
Record of an audit trail listing events in the order in which they occur, held in a circular buffer.
Records contain all defined fields from the standard and record all defined function event types
where the function is supported.
No password defeat mechanism exists. Instead a secure recovery password scheme is
implemented.
Unused ports (physical and logical) may be disabled.
P446/EN/TM/E 10-9
10 Cyber Security MiCOMho P446
Four-level Access
Password strengthening
Disabling of unused application and physical ports
Inactivity timer
Storage of security events (logs) in the IED
NERC-compliant default display
External to the IEDs, the following cyber security measures have been implemented:
Antivirus
Security patch management
10-10 P446/EN/TM/E
MiCOMho P446 10 Cyber Security
P446/EN/TM/E 10-11
10 Cyber Security MiCOMho P446
NERC COMPLIANT
P/WORD WAS SAVED
The IED does not enforce NERC compliance. It is the responsibility of the user to ensure that
compliance is adhered to as and when necessary. In the case that the password entered is not NERC-
compliant, the user is required to actively confirm this, in which case the non-compliance is logged.
If the entered password is not NERC compliant, the following text is displayed:
NERC COMPLIANCE
NOT MET CONFIRM?
On confirmation, the non-compliant password is stored and the following acknowledgement message
is displayed for 2 seconds.
10-12 P446/EN/TM/E
MiCOMho P446 10 Cyber Security
NON-NERC P/WORD
SAVED OK
If the action is cancelled, the password is rejected and the following message displayed for 2 seconds.
NON-NERC P/WORD
NOT SAVE
If the password is entered through a communications port using Courier or Modbus protocols the IED
will store the password, irrespective of whether it is or isn’t NERC-compliant, and then uses
appropriate response codes to inform the client that the password was NERC-compliant or not. The
client then can choose if he/she wishes to enter a new password that is NERC-compliant or leave the
entered one in place.
BLANK PASSWORD
ENTERED CONFIRM
P446/EN/TM/E 10-13
10 Cyber Security MiCOMho P446
NOT ACCEPTED
ENTRY IS BLOCKED
Appropriate responses achieve the same result if the password is written through a communications
port.
The attempts count, attempts timer and blocking timer can be configured, as shown in Table 4.
Cell
Setting Units Default Setting Available Setting
col row
Attempts Limit 25 02 3 0 to 3 step 1
Attempts Timer 25 03 Minutes 2 1 to 3 step 1
Blocking Timer 25 04 Minutes 5 1 to 30 step 1
Table 4: Password blocking configuration
On power up
Whenever settings are set back to default
On expiry of validity timer (see below)
When the recovery password is entered
As soon as the security code is displayed on the LCD display, a validity timer is started. This validity
timer is set to 72 hours and is not configurable. This provides enough time for the contact centre to
manually generate and send a recovery password. The Service Level Agreement (SLA) for recovery
password generation is one working day, so 72 hours is sufficient time, even allowing for closure of
the contact centre over weekends and bank holidays.
To prevent accidental reading of the IED security code the cell will initially display a warning message:
PRESS ENTER TO
READ SEC. CODE
The security code will be displayed on confirmation, whereupon the validity timer will be started. Note
that the security code can only be read from the front panel.
10-14 P446/EN/TM/E
MiCOMho P446 10 Cyber Security
passwords appropriate for the function for which they are intended, ensuring NERC compliance, if
required.
On this action, the following message is displayed:
PASSWORDS HAVE
BEEN SET TO
DEFAULT
The recovery password can be applied through any interface, local or remote. It will achieve the same
result irrespective of which interface it is applied through.
REAR PORT 1 TO BE
DISABLED.CONFIRM
Front port
Rear port 1
Rear port 2 (not implemented on all models)
Ethernet port (not implemented on all models)
Note: It is not possible to disable a port from which the disabling port command originates.
Note: The port disabling setting cells are not provided in the settings file
Caution Disabling the Ethernet port will disable all Ethernet based communications.
P446/EN/TM/E 10-15
10 Cyber Security MiCOMho P446
If it is not desirable to disable the Ethernet port, it is possible to disable selected protocols on the
Ethernet card and leave others functioning.
Three protocols can be disabled:
IEC61850
DNP3 Over Ethernet
Courier Tunnelling
Note: If any of these protocols are enabled or disabled, the Ethernet card will reboot.
DO YOU WANT TO
LOG OUT?
You will only be asked this question if your password level is higher than the fallback level.
If you confirm, the following message is displayed for 2 seconds:
LOGGED OUT
Access Level <x>
LOGOUT CANCELLED
Access Level <x>
4.8 Events
The implementation of NERC-compliant cyber security necessitates the generation of a range of Event
records, which log security issues such as the entry of a non-NERC-compliant password, or the
selection of a non-NERC-compliant default display. Table 5 lists all Security events.
Event Value Display
USER LOGGED IN
PASSWORD LEVEL UNLOCKED
ON <int> LEVEL <n>
USER LOGGED OUT
PASSWORD LEVEL RESET
ON <int> LEVEL <n>
P/WORD SET BLANK
PASSWORD SET BLANK
BY <int> LEVEL <p>
10-16 P446/EN/TM/E
MiCOMho P446 10 Cyber Security
P446/EN/TM/E 10-17
10 Cyber Security MiCOMho P446
Where:
int is the interface definition (UI, FP, RP1, RP2, TNL, TCP)
prt is the port ID (FP, RP1, RP2, TNL, DNP3, IEC, ETHR)
grp is the group number (1, 2, 3, 4)
crv is the Curve group number (1, 2, 3, 4)
n is the new access level (0, 1, 2, 3)
p is the password level (1, 2, 3)
nov is the number of events (1 – nnn)
Each event is identified with a unique number that is incremented for each new event so that it is
possible to detect missing events as there will be a ‘gap’ in the sequence of unique identifiers. The
unique identifier forms part of the event record that is read or uploaded from the IED.
Note: It is no longer possible to clear Event, Fault, Maintenance, and Disturbance Records
10-18 P446/EN/TM/E
MiCOMho P446 10 Cyber Security
A summary of the relevant columns is shown in Table 6. A complete listing of the settings criteria is
described in the Settings and Records chapter.
Cell Interface In Setting
Parameter Default Setting Available Setting
col row Applicability file?
Password 00 02 ASCII 33 to 122 All Yes
0 = Read Some,
1 = Read All,
Yes, Not
Access Level 00 D0 2 = Read All + Write All
Settable
Some,
3 = Read All + Write All
Password Level 1 00 D2 ASCII 33 to 122 All Yes
Password Level 2 00 D3 ASCII 33 to 122 All Yes
Password Level 3 00 D4 ASCII 33 to 122 All Yes
Yes, Not
Security Feature 00 DF 1 All
Settable
SECURITY CONFIG 25 00 All Yes
ACCESS ONLY FOR
Use Banner 25 01 ASCII 32 to 163 All Yes
AUTHORISED USERS
Attempts Limit 25 02 3 0 to 3 step 1 All Yes
Attempts Timer 25 03 2 1 to 3 step 1 All Yes
Blocking Timer 25 04 5 1 to 30 step 1 All Yes
0 = Disabled or
Front Port 25 05 Enabled All No
1 = Enabled
0 = Disabled or
Rear Port 1 25 06 Enabled All No
1 = Enabled
0 = Disabled or
Rear Port 2 25 07 Enabled All No
1 = Enabled
0 = Disabled or
Ethernet Port* 25 08 Enabled All No
1 = Enabled
0 = Disabled or
Courier Tunnel*† 25 09 Enabled All No
1 = Enabled
0 = Disabled or
IEC61850*† 25 0A Enabled All No
1 = Enabled
0 = Disabled or
DNP3 OE*† 25 0B Enabled All No
1 = Enabled
Yes, Not
Attempts Remain 25 11 All
Settable
Yes, Not
Blk Time Remain 25 12 All
Settable
0 = Password Level 0,
1 = Password Level 1, Yes, Not
Fallbck PW Level 25 20 0 All
2 = Password Level 2, Settable
3 = Password Level 3
Security Code 25 FF UI Only No
Evt Unique Id (Normal
01 FE All No
Extraction)
Evt Iface Source ±
01 FA All No
(Bits 0 – 7 of Event State)
P446/EN/TM/E 10-19
10 Cyber Security MiCOMho P446
Where:
* - These cells will not be present in a non-Ethernet product
†- These cells will be invisible if the Ethernet port is disabled.
± - These cells invisible if event is not a Security event
Ω – This cell is invisible in current phase as it does not contain any data. It is reserved for future
use.
10-20 P446/EN/TM/E
MiCOMho P446 11 PSL Editor
PSL EDITOR
CHAPTER 11
P446/EN/TM/E 11-1
11 PSL Editor MiCOMho P446
11-2 P446/EN/TM/E
MiCOMho P446 11 PSL Editor
1 CHAPTER OVERVIEW
The purpose of the Programmable Scheme Logic (PSL) is to allow you to configure an individual
scheme to suit your own particular application. This is achieved through the use of programmable
logic gates and delay timers. This chapter describes the PSL Editor, which allows you to do this. It
consists of the following sections:
1 CHAPTER OVERVIEW
2 INTRODUCTION TO THE PSL EDITOR
2.1 Warnings
P446/EN/TM/E 11-3
11 PSL Editor MiCOMho P446
Relay outputs
Light emitting diodes
IEC 61850 GOOSE outputs
Trigger signals
Internal signals include “inputs” to the PSL (i.e. signals generated within the product that can be used
to affect the operation of the scheme logic) and “outputs” from the PSL (i.e. signals that can be driven
from the PSL to activate specific functions in the product). Examples of internal inputs and outputs
include:
IN>1 Trip: an input that is asserted if the Stage 1 Earth fault protection trip operates
Thermal Trip: an input that is asserted if the thermal trip operates
Reset Relays/LED : an output that can be asserted to reset the output relays and LEDs
The PSL consists of software logic gates and timers which combine and condition the DDB signals.
The logic gates can be programmed to perform a range of different logic functions and can accept any
number of inputs. The timers are used either to create a programmable delay or to condition the logic
outputs.
The PSL logic is event driven. Only the part of the PSL logic that is affected by the particular input
change that has occurred is processed. This reduces the amount of processing time that is used by
the PSL.
The system gives you flexibility to create your own scheme logic design. This also means that the
PSL can be configured into a very complex system, so you need a suitable PC support package to
allow you to design your PSL scheme. This PC support package is provided in the form of the S1
Studio suite of tools, which includes the PSL Editor.
With the Px40 PSL Module you can:
11-4 P446/EN/TM/E
MiCOMho P446 11 PSL Editor
From the S1 Studio main menu, select: Tools > PSL editor (Px40)
By creating a model system in S1 studio with the correct model number and opening the default
PSL and open it.
For more information on the PSL editor, see the online help built into the PSL Editor.
2.1 Warnings
Checks are made before a scheme is downloaded to the IED. Various warning messages may be
displayed as a result of these checks.
In most cases, the model number of the unit will match that of the model number stored in the PSL
software on the PC. The Editor first reads in the model number of the connected unit, then compares
it with its stored model number using a "wildcard" comparison. If a model mismatch occurs, a warning
is generated before sending starts. Both the stored model number and the number read from the IED
are displayed with the warning.
It is up to the user to decide whether the settings to be downloaded are compatible, and to be aware
that incompatible settings could lead to undesirable behavior of the unit.
If there are any obvious potential problems, a list is generated. The types of potential problems that
the program attempts to detect are:
One or more gates, LED signals, contact signals, or timers have their outputs linked directly
back to their inputs. An erroneous link of this sort could lock up the IED, or cause other
problems to arise.
A programmable gate has its ITT (Inputs To Trigger) value set to greater than the number of
actual inputs. This will mean the gate can never activate. There is no check for the case where
the ITT value is lower than the number of inputs. A 0-value does not generate a warning.
Too many gates. There is a theoretical upper limit of 256 gates in a scheme, but the practical
limit is determined by the complexity of the logic. In practice the scheme would have to be very
complex, and this error is unlikely to occur.
Too many links. There is no fixed upper limit to the number of links in a scheme. However, as
with the maximum number of gates, the practical limit is determined by the complexity of the
logic. In practice the scheme would have to be very complex, and this error is unlikely to occur.
P446/EN/TM/E 11-5
11 PSL Editor MiCOMho P446
The logic symbol toolbar provides icons to place each type of logic element into the scheme diagram.
Not all elements are available in all devices. Icons will only be displayed for those elements available
in the selected device.
Symbol Function Explanation
Link Create a link between two logic symbols
11-6 P446/EN/TM/E
MiCOMho P446 11 PSL Editor
LED Signal Create an LED input signal that repeats the status of tri-color LED
P446/EN/TM/E 11-7
11 PSL Editor MiCOMho P446
1. Use the logic toolbar to select logic signals. This is enabled by default but to hide or show it,
select View > Logic Toolbar.
2. Zoom in or out of a logic diagram using the toolbar icon or select View > Zoom Percent.
3. Right-click any logic signal and a context-sensitive menu appears.
Certain logic elements show the Properties… option. If you select this, a Component Properties
window appears. The contents of this window and the signals listed will vary according to the logic
symbol selected. The following sections describe each of the available logic symbols. The actual
DDB numbers are dependent on the model and are provided in the DDB table in the PSL Schemes
chapter.
3. Check the box to invert the link. Or uncheck for a non-inverted link
An inverted link is shown with a small circle on the input to a gate. A link must be connected to the
input of a gate to be inverted.
Links can only be started from the output of a signal, gate, or conditioner, and must end at an input to
any element.
Signals can only be an input or an output. To follow the convention for gates and conditioners, input
signals are connected from the left and output signals to the right. The Editor automatically enforces
this convention.
A link is refused for the following reasons:
There has been an attempt to connect to a signal that is already driven. The reason for the
refusal may not be obvious because the signal symbol may appear elsewhere in the diagram.
In this case you can right-click the link and select Highlight to find the other signal. Click
anywhere on the diagram to disable the highlight.
An attempt has been made to repeat a link between two symbols. The reason for the refusal
may not be obvious because the existing link may be represented elsewhere in the diagram.
11-8 P446/EN/TM/E
MiCOMho P446 11 PSL Editor
Each opto-input can be selected and used for programming in PSL. Activation of the opto-input will
drive an associated DDB signal.
IED logic functions provide logic output signals that can be used for programming in PSL. Depending
on the IED functionality, operation of an active IED function will drive an associated DDB signal in
PSL.
Logic functions provide logic input signals that can be used for programming in PSL. Depending on
the output relay functionality, activation of the output signal will drive an associated DDB signal in PSL
and cause an associated response to the output relay function.
The Programmable Scheme Logic interfaces with the GOOSE Scheme Logic by means of 32 Virtual
inputs. The Virtual Inputs can be used in much the same way as the opto-input signals.
The logic that drives each of the Virtual Inputs is contained within the GOOSE Scheme Logic file. It is
possible to map any number of bit-pairs, from any subscribed device, using logic gates onto a Virtual
Input (see S1 documentation for further details).
The Programmable Scheme Logic interfaces with the GOOSE Scheme Logic by means of 32 Virtual
outputs.
It is possible to map virtual outputs to bit-pairs for transmitting to any subscribed devices (see S1
documentation for further details).
There are 32 control inputs which can be activated via the menu, the hotkeys or via courier
communications. Depending on the programmed setting that is, latched or pulsed, an associated
DDB signal will be activated in PSL when a control input is operated.
P446/EN/TM/E 11-9
11 PSL Editor MiCOMho P446
There are 16 InterMiCOM inputs that can be used for teleprotection and remote commands.
“InterMiCOM In” is a received signal from remote end that can be mapped to a selected output relay or
logic input.
IED End B
There are 16 InterMiCOM outputs that can be used for teleprotection and remote commands.
“InterMiCOM Out” is a send command to a remote end that can be mapped to any logic output or
opto-input. This will be transmitted to the remote end as a corresponding “InterMiCOM In” command.
IED End A
At end A, InterMiCOM Output 1 is mapped to the command indication “Clear Statistics” (issued at end
A).
Each function key can be selected and used for programming in PSL. Activation of the function key
will drive an associated DDB signal. The DDB signal will remain active according to the programmed
setting (toggled or normal). Toggled mode means the DDB signal will remain in the new state until the
function key is pressed again. In Normal mode, the DDB will only be active for the duration of the key
press.
The fault recording facility can be activated, by driving the fault recorder trigger DDB signal.
All programmable LEDs will drive associated DDB signals when the LED is activated.
11-10 P446/EN/TM/E
MiCOMho P446 11 PSL Editor
All output relay contacts will drive associated DDB signal when the output contact is activated.
752
753
752
753
752
753
1. Select the LED name from the list (only shown when inserting a new symbol).
2. Configure the LED output to be Red, Yellow or Green.
3. Configure a Green LED by driving the Green DDB input.
4. Configure a RED LED by driving the RED DDB input.
5. Configure a Yellow LED by driving the RED and GREEN DDB inputs simultaneously
6. Configure the LED output to be latching or non-latching
P446/EN/TM/E 11-11
11 PSL Editor MiCOMho P446
1. Select the contact name from the Contact Name list (only shown when inserting a new
symbol).
2. Choose the conditioner type required in the Mode tick list.
3. Set the Pick-up Time (in milliseconds), if required.
4. Set the Drop-off Time (in milliseconds), if required.
1. Choose the operation mode from the Timer Mode tick list.
11-12 P446/EN/TM/E
MiCOMho P446 11 PSL Editor
An AND gate requires that all inputs are TRUE for the output to be TRUE.
An OR gate requires that one or more input is TRUE for the output to be TRUE.
A Programmable gate requires that the number of inputs that are TRUE is equal to or greater
than its ‘Inputs to Trigger’ setting for the output to be TRUE.
P446/EN/TM/E 11-13
11 PSL Editor MiCOMho P446
Select if the output of the gate should be inverted using the Invert Output check box. An inverted
output is indicated with a "bubble" on the gate output.
11-14 P446/EN/TM/E
MiCOMho P446 12 PSL Schemes
PSL SCHEMES
CHAPTER 12
P446/EN/TM/E 12-1
12 PSL Schemes MiCOMho P446
12-2 P446/EN/TM/E
MiCOMho P446 12 PSL Schemes
1 OVERVIEW
This chapter describes the PSL scheme and mappings specific to the devices in question. It contains
the following sections:
1 Overview
2 Description of logic nodes
3 Mappings
3.1 Logic Input Mappings
3.2 Standard Output Relay Mappings
3.3 Programmable LED Output Mappings
3.4 Fault Recorder Start Mappings
3.5 PSL DATA Column
4 Viewing and printing psl diagrams
P446/EN/TM/E 12-3
12 PSL Schemes MiCOMho P446
Note: The DDB numbers are displayed as part of the associated symbol in the PSL editor.
12-4 P446/EN/TM/E
MiCOMho P446 12 PSL Schemes
3 MAPPINGS
P446/EN/TM/E 12-5
12 PSL Schemes MiCOMho P446
Relay type
Default
Relay Conditioner Function (High-break or
Menu Text
Standard)
Output R12 Dwell 100 ms CB2 Fail1 Trip Standard
Output R13 Straight-through Cntl CB2 Close Standard
Output R14 Straight-through Cntl CB2 Trip Standard
Output R15 Dwell 100 ms CB1 Fail2 Trip Standard
Output R16 Dwell 100 ms CB2 Fail2 Trip Standard
Output R17 Dwell 100 ms CB2 Trip A Standard
Output R18 Dwell 100 ms CB2 Trip B Standard
Output R19 Dwell 100 ms CB2 Trip C Standard
Output R20 Straight-through Dist Inst Trip Standard
Output R21 Straight-through Dist Delay Trip Standard
Output R22 Straight-through Aided DEF Trip Standard
Output R23 Straight-through Signalling Fail Standard
Output R24 Straight-through Aided 1 Send Standard
Output R25 Straight-through Not Used Standard
Output R26 Straight-through Not Used Standard
Output R27 Straight-through VTS Standard
Output R28 Straight-through PSB Standard
Output R29 Straight-through AR CB1 Lockout Standard
Output R30 Straight-through AR CB2 Lockout Standard
Output R31 Straight-through AR in progress Standard
Output R32 Straight-through Success Close Standard
Table 2: Output relay mappings – P446 model B
Relay type
Default
Relay Conditioner Function (High-break or
Menu Text
Standard)
Output R1 Straight-through Trip Zone 1 Standard
Output R2 Straight-through Any Start Standard
Output R3 Dwell 100 ms Any Trip Standard
Output R4 Dwell 500 ms General Alarm Standard
Output R5 Straight-through IM64 1 Standard
Output R6 Dwell 100 ms CB1 Fail1 Trip Standard
Output R7 Straight-through Cntl CB1 Close Standard
Output R8 Straight-through Cntl CB2 Close Standard
Output R9 Dwell 100 ms CB1 Trip A High-break
Output R10 Dwell 100 ms CB1 Trip B High-break
Output R11 Dwell 100 ms CB1 Trip C High-break
Output R12 Dwell 100 ms CB2 Trip A High-break
Output R13 Dwell 100 ms CB2 Trip B High-break
Output R14 Dwell 100 ms CB2 Trip C High-break
Output R15 Dwell 100 ms CB1 Trip A High-break
Output R16 Dwell 100 ms CB1 Trip B High-break
Output R17 Dwell 100 ms CB1 Trip C High-break
Output R18 Dwell 100 ms CB2 Trip A High-break
12-6 P446/EN/TM/E
MiCOMho P446 12 PSL Schemes
Relay type
Default
Relay Conditioner Function (High-break or
Menu Text
Standard)
Output R19 Dwell 100 ms CB2 Trip B High-break
Output R20 Dwell 100 ms CB2 Trip C High-break
Table 3: Output relay mappings – P446 model C
Relay type
Default
Relay Conditioner Function (High-break or
Menu Text
Standard)
Output R1 Straight-through Trip Zone 1 Standard
Output R2 Straight-through Any Start Standard
Output R3 Dwell 100 ms Any Trip Standard
Output R4 Dwell 500 ms General Alarm Standard
Output R5 Straight-through IM64 1 Standard
Output R6 Dwell 100 ms CB1 Fail1 Trip Standard
Output R7 Straight-through Cntl CB1 Close Standard
Output R8 Straight-through Cntl CB1 Trip Standard
Output R9 Dwell 100 ms CB1 Trip A Standard
Output R10 Dwell 100 ms CB1 Trip B Standard
Output R11 Dwell 100 ms CB1 Trip C Standard
Output R12 Straight-through AR in Prog Standard
Output R13 Straight-through Cntl CB2 Close Standard
Output R14 Straight-through Cntl CB2 Trip Standard
Output R15 Dwell 100 ms CB2 Fail1 Trip Standard
Output R16 Straight-through Aid 1 Send Standard
Output R17 Dwell 100 ms CB1 Trip A High-break
Output R18 Dwell 100 ms CB1 Trip B High-break
Output R19 Dwell 100 ms CB1 Trip C High-break
Output R20 Dwell 100 ms CB1 Trip 3ph High-break
Output R21 Dwell 100 ms CB2 Trip A High-break
Output R22 Dwell 100 ms CB2 Trip B High-break
Output R23 Dwell 100 ms CB2 Trip C High-break
Output R24 Dwell 100 ms CB2 Trip 3ph High-break
Table 4: Output relay mappings – P446 model D
Note: A fault record can be generated by connecting one or several contacts to the Fault Record Trigger
in PSL. It is recommended that the triggering contact is self reset and not latching. If a latching
contact is used, the fault record is not generated until the contact has fully reset.
P446/EN/TM/E 12-7
12 PSL Schemes MiCOMho P446
Default
Latched Function Red LED Function Yellow LED Function Green LED
Menu Text
FnKey 2 Non-latching CB1 Open B ph CB1 Closed B ph
FnKey 3 Non-latching CB1 Open C ph CB1 Closed C ph
FnKey 4 Non-latching CB1 AR Lockout
FnKey 5 Non-latching CB1 AR In Prog CB1 AR Successful
FnKey 6 Non-latching CB2 Open A ph CB2 Closed A ph
FnKey 7 Non-latching CB2 Open B ph CB2 Closed B ph
FnKey 8 Non-latching CB2 Open C ph CB2 Closed C ph
FnKey 9 Non-latching CB2 AR Lockout
FnKey 10 Non-latching CB2 AR In Prog CB2 AR Successful
Table 5: LED output mappings – all P446 models
Note: The above cells are repeated for each setting group.
12-8 P446/EN/TM/E
MiCOMho P446 12 PSL Schemes
To download the default PSL diagrams for the device and to print them:
1. Close S1 Studio.
2. Select Programs > Alstom Grid > S1 Studio > Data Model Manager.
3. Click Add then Next.
4. Click Internet then Next.
5. Select your language then click Next.
6. From the tree view, select the model and software version.
7. Click Install. When complete click OK.
8. Close the Data Model Manager and start S1 Studio.
9. Select Tools > PSL Editor (Px40).
10. In the PSL Editor select File > New > Default Scheme.
11. In the dialogue select the IED type
12. Use the advance button to select the software and then select the required model number.
13. Highlight the required PSL diagram and select File > Print.
Caution Read the notes in the default PSL diagrams, as these provide critical
information
P446/EN/TM/E 12-9
12 PSL Schemes MiCOMho P446
12-10 P446/EN/TM/E
MiCOMho P446 13 Installation
INSTALLATION
CHAPTER 13
P446/EN/TM/E 13-1
13 Installation MiCOMho P446
13-2 P446/EN/TM/E
MiCOMho P446 13 Installation
1 CHAPTER OVERVIEW
This chapter describes the installation of the unit and consists of the following sections:
1 Chapter Overview
2 Handling the goods
3 Pre-installation Requirements
4 Mounting the Unit
5 Cables and Connectors
5.1 Terminal blocks
5.2 Wire Sizes
5.3 Power Supply Terminals
5.4 EIA(RS)485 rear port (RP1)
5.5 IRIG-B port
5.6 GPS Fibre-optic port
5.7 Ethernet Fibre-optic ports
5.8 Current Differential / IM64 ports
5.9 Ethernet RJ-45 metallic port
5.10 EIA(RS)232 front port
5.11 Download/monitor port
5.12 Earth connection
6 Case Dimensions
P446/EN/TM/E 13-3
13 Installation MiCOMho P446
Caution Before lifting or moving the equipment you should be familiar with the Safety
Information chapter of this manual.
Unpacking
When unpacking and installing the unit, take care not to damage any of the parts and make sure that
additional components are not accidentally left in the packing or lost. Do not discard any CDROMs or
technical documentation. These should accompany the unit to its destination substation.
Note: With the lower access cover open, the red tab of the battery isolation strip protrudes from the
positive battery terminal. Do not remove this strip because it prevents battery drain during
transportation and storage; it will be removed as part of the commissioning process.
The site should be well lit to aid inspection, clean, dry and reasonably free from dust and excessive
vibration. This particularly applies to installations, which are being carried out at the same time as
construction work.
Storage
If the unit is not installed immediately, store it in a place free from dust and moisture in its original
packaging. Keep any de-humidifier bags included in the packing. The de-humidifier crystals lose their
efficiency if the bag is exposed to ambient conditions. Restore the crystals by gently heating the bag
for about an hour before replacing it in the carton.
On subsequent unpacking, make sure that any dust on the carton does not fall inside. Avoid storing in
locations of high humidity. In locations of high humidity the packaging may become impregnated with
moisture and the de-humidifier crystals will lose their efficiency.
The unit can be stored between –25º to +70ºC (-13ºF to +158ºF).
13-4 P446/EN/TM/E
MiCOMho P446 13 Installation
3 PRE-INSTALLATION REQUIREMENTS
If your IED is equipped with a redundant Ethernet board (REB), you may be required to partially
dismantle it in order to set the IP address. You will only have to do this if the last octet of the IP
address you need is different from that of the delivered configuration.
The IP address of the REB is configured in both software and hardware. The first three octets are
configured with software, but the last octet is configured in hardware.
Caution This hardware configuration should ideally take place before the unit is
installed.
1. Make sure you are familiar with the safety section of this technical manual.
2. Switch off the IED. Disconnect the power and all connections.
3. Before the front cover is removed take precautions to prevent electrostatic discharge damage,
according to the ANSI/ESD-20.20 -2007 standard.
4. Wear a 1 MΩ earth strap and connect it to the earthing point (M4 earthing stud), located in the
bottom left hand corner on the back of the IED.
5. Lift the upper and lower flaps. Remove the six screws securing the front panel and pull the
front panel outwards.
P446/EN/TM/E 13-5
13 Installation MiCOMho P446
F6
F6
Trip
Alarm F7
F7
Out of Service F8
F8
Healthy
F9
F9
OK
F10
F10
C
P4393ENd
6. Press the levers either side of the connector to disconnect the ribbon cable from the front
panel.
P4396ENa
7. You now have access to the address switches on the dual Ethernet board, which is situated in
slot A on the right hand side of the unit looking from the front.
13-6 P446/EN/TM/E
MiCOMho P446 13 Installation
8. Set the last octet of the board IP address by setting the DIP switches.
9. Once you have set the IP address, reassemble the relay, following the above instructions in
the reverse order.
Caution Take care not to damage the pins of the ribbon cable connector on the front
panel when reinserting the ribbon cable.
P446/EN/TM/E 13-7
13 Installation MiCOMho P446
Panel mounting
Panel-mounted variants can be flush mounted into panels using M4 SEMS Taptite self-tapping screws
with captive 3 mm thick washers (also known as a SEMS unit). These fastenings are available in
packs of five (our part number ZA0005 104).
Caution Risk of damage to the front cover molding. Do not use conventional self-
tapping screws, including those supplied for mounting MiDOS products
because they have slightly larger heads.
Alternatively tapped holes can be used if the panel has a minimum thickness of 2.5 mm.
For applications where the product needs to be semi-projection or projection mounted, a range of
collars are available.
13-8 P446/EN/TM/E
MiCOMho P446 13 Installation
If several products are mounted in a single cut-out in the panel, mechanically group them horizontally
or vertically into rigid assemblies before mounting in the panel.
Note: Fastening MiCOM ALSTOM products with pop rivets is not advised because it does not allow easy
removal if repair is necessary.
If the product is mounted on a BS EN60529 IP52 compliant panel, fit a metallic sealing strip between
adjoining products (part no GN2044 001) and fit a sealing ring around the complete assembly,
according to the following table.
Width Single tier Double tier
10TE GJ9018 002 GJ9018 018
15TE GJ9018 003 GJ9018 019
20TE GJ9018 004 GJ9018 020
25TE GJ9018 005 GJ9018 021
30TE GJ9018 006 GJ9018 022
35TE GJ9018 007 GJ9018 023
40TE GJ9018 008 GJ9018 024
45TE GJ9018 009 GJ9018 025
50TE GJ9018 010 GJ9018 026
55TE GJ9018 011 GJ9018 027
60TE GJ9018 012 GJ9018 028
65TE GJ9018 013 GJ9018 029
70TE GJ9018 014 GJ9018 030
75TE GJ9018 015 GJ9018 031
80TE GJ9018 016 GJ9018 032
Table 1: IP52 sealing rings
Rack mounting
Panel-mounted variants can also be rack mounted using single-tier rack frames (our part number
FX0021 101), as shown in Figure 2. These frames are designed with dimensions in accordance with
IEC 60297 and are supplied pre-assembled ready to use. On a standard 483 mm (19 inch) rack this
enables combinations of case widths up to a total equivalent of size 80TE to be mounted side by side.
The two horizontal rails of the rack frame have holes drilled at approximately 26 mm intervals. Attach
the products by their mounting flanges using M4 Taptite self-tapping screws with captive 3 mm thick
washers (also known as a SEMS unit). These fastenings are available in packs of five (our part
number ZA0005 104).
Caution Risk of damage to the front cover molding. Do not use conventional self-
tapping screws, including those supplied for mounting MiDOS products
because they have slightly larger heads.
Once the tier is complete, the frames are fastened into the racks using mounting angles at each end of
the tier.
P446/EN/TM/E 13-9
13 Installation MiCOMho P446
P4535ENb
Products can be mechanically grouped into single tier (4U) or multi-tier arrangements using the rack
frame. This enables schemes using products from the MiCOM ALSTOM and MiDOS product ranges
to be pre-wired together before mounting.
Use blanking plates if there are empty spaces. The spaces may be for future installation of products
or because the total size is less than 80TE on any tier. Blanking plates can also be used to mount
ancillary components. Table 2 shows the sizes that can be ordered.
For further details on mounting MiDOS products, see publication R7012, MiDOS Parts Catalogue and
Assembly Instructions.
Case size summation Blanking plate part number
5TE GJ2028 101
10TE GJ2028 102
15TE GJ2028 103
20TE GJ2028 104
25TE GJ2028 105
30TE GJ2028 106
35TE GJ2028 107
40TE GJ2028 108
Table 2: Blanking plates
13-10 P446/EN/TM/E
MiCOMho P446 13 Installation
Caution Before carrying out any work on the equipment you should be familiar with the
Safety Section and the ratings on the equipment’s rating label.
HD Terminal Block MD Terminal Block Midos Terminal Block RTD/CLIO Terminal Block
P4522ENa .
Figure 3: Terminal block types
MiCOM ALSTOM products are supplied with sufficient M4 screws for making connections to the rear
mounted terminal blocks using ring terminals, with a recommended maximum of two ring terminals per
terminal.
If required, M4 90° crimp ring terminals can be supplied in three different sizes depending on wire
size. Each type is available in bags of 100.
Part number Wire size Insulation color
2
ZB9124 901 0.25 - 1.65 mm (22 – 16 AWG) Red
ZB9124 900 1.04 - 2.63 mm2 (16 – 14 AWG) Blue
P446/EN/TM/E 13-11
13 Installation MiCOMho P446
Caution For safety reasons always fit an insulating sleeve over the ring terminal.
Due to the limitations of the ring terminal, the maximum wire size that can be used for any of the
medium or heavy duty terminals is 6.0 mm2 using ring terminals that are not pre-insulated. If using
only pre-insulated ring terminals, the maximum wire size that can be used is reduced to 2.63 mm2 per
ring terminal. If you need a larger wire size, use two wires in parallel, each terminated in a separate
ring terminal at the product.
With the exception of the EIA(RS)485 port, the wire used for all connections to the medium and heavy
duty terminal blocks, should have a minimum voltage rating of 300 V RMS.
Each opto-input has a selectable preset ½ cycle filter. This makes the input immune to noise induced
on the wiring. Although this is secure it can be slow, particularly for intertripping. If you switch off the
½ cycle filter, either use double pole switching on the input, or screened twisted cable on the input
circuit.
Caution Current transformer circuits must never be fused. Other circuits should be
appropriately fused to protect the wire used.
13-12 P446/EN/TM/E
MiCOMho P446 13 Installation
Power: Terminals 1 + 2 of
PSU terminal block.
1 T1 = -ve
2
T2 = +ve
16
17
18
P4538ENa
Protect the auxiliary power supply wiring with a 16 A high rupture capacity (HRC) type NIT or TIA fuse.
P446/EN/TM/E 13-13
13 Installation MiCOMho P446
Note: For models equipped with redundant Ethernet connections the product must be partially dismantled
to set the fourth octet of the second IP address. This ideally, should be done before installation.
13-14 P446/EN/TM/E
MiCOMho P446 13 Installation
Note: To prevent any possibility of electrolytic action between brass or copper ground conductors and the
rear panel of the product, precautions should be taken to isolate them from one another. This could
be achieved in several ways, including placing a nickel-plated or insulating washer between the
conductor and the product case, or using tinned ring terminals.
P446/EN/TM/E 13-15
13 Installation MiCOMho P446
6 CASE DIMENSIONS
13-16 P446/EN/TM/E
MiCOMho P446 13 Installation
P1616ENi
P446/EN/TM/E 13-17
13 Installation MiCOMho P446
13-18 P446/EN/TM/E
MiCOMho P446 14 Commissioning Instructions
COMMISSIONING INSTRUCTIONS
CHAPTER 14
P446/EN/TM/E 14-1
14 Commissioning Instructions MiCOMho P446
14-2 P446/EN/TM/E
MiCOMho P446 14 Commissioning Instructions
1 OVERVIEW
The Commissioning Instructions chapter describes in detail the commissioning process for the
product.
It consists of the following sections:
1 Overview
2 General Guidelines
3 Commissioning Test Menu
3.1 Opto I/P Status
3.2 Relay O/P Status
3.3 Test Port Status
3.4 LED Status
3.5 Monitor Bits 1 to 8
3.6 Test Mode
3.7 Test Pattern
3.8 Contact Test
3.9 Test LEDs
3.10 Test Autoreclose
3.11 Static Test Mode
3.12 Loopback Mode
3.13 IM64 Test Pattern
3.14 IM64 Test Mode
3.15 Using a Monitor/Download Port Test Box
4 Commissioning Equipment
4.1 Minimum Equipment Required
4.2 Optional equipment
5 Product Checks
5.1 With the IED De-energized
5.1.1 Visual Inspection
5.1.2 Current Transformer Shorting Contacts
5.1.3 Insulation
5.1.4 External Wiring
5.1.5 Test Watchdog Contacts (IED not Energized)
5.1.6 Auxiliary Supply
5.2 With the IED Energized
5.2.1 Test Watchdog Contacts (IED Energized)
5.2.2 LCD
5.2.3 Date and Time
5.2.4 LEDs
5.2.5 Testing the Alarm and Out-of-Service LEDs
5.2.6 Testing the trip LED
5.2.7 Test user-programmable LEDs
5.2.8 Test Field voltage supply
5.2.9 Test Input Opto-Isolators
5.2.10 Test Output Relays
5.2.11 Communication Port RP1
5.2.11.1 Courier
P446/EN/TM/E 14-3
14 Commissioning Instructions MiCOMho P446
8 Setting Checks
8.1 Apply Application-Specific Settings
8.1.1 Transferring settings from a settings file
8.1.2 Entering the settings using the IED's front panel HMI panel
8.1.3 Protection communications loopback
8.1.4 Reset statistics
8.2 Distance Protection
8.2.1 Distance Protection Single-ended Testing
8.2.1.1 Connection and preliminaries
8.2.1.2 Zone 1 reach check
8.2.1.3 Zone 2 reach check
8.2.1.4 Zone 3 reach check
8.2.1.5 Zone 4 reach check (if enabled)
8.2.1.6 Zone P reach check (if enabled)
8.2.1.7 Resistive reach (quadrilateral characteristics only)
8.2.1.8 Load blinder
8.2.2 Distance Protection Operation and Contact Assignment
8.2.2.1 Phase A
8.2.2.2 Phase B
8.2.2.3 Phase C
8.2.2.4 Time delay settings tZ1 Ph, and tZ2 - tZ4
8.2.3 Distance Protection Scheme Testing
8.2.3.1 Scheme Trip Test for Zone 1 Extension Only
8.2.3.2 Scheme trip tests for permissive schemes (PUR/POR only)
8.2.3.3 Scheme trip tests for blocking scheme only
8.2.3.4 Signal send test for permissive schemes (PUR/POR only)
8.2.3.5 Signal send test for blocking scheme only
8.2.4 Scheme Timer Settings
8.3 Delta Directional Comparison
8.3.1 Delta Protection Single-ended Testing
8.3.1.1 Connection and preliminaries
8.3.1.2 Single-ended Injection Test
8.3.1.3 Forward fault preparation
14-4 P446/EN/TM/E
MiCOMho P446 14 Commissioning Instructions
11 On-load Checks
11.1 Confirm Voltage Connections
11.2 Confirm Current Connections
11.3 On load directional test
11.4 Signalling channel check (if not already completed)
12 Final Checks
P446/EN/TM/E 14-5
14 Commissioning Instructions MiCOMho P446
2 GENERAL GUIDELINES
Px40 IEDs are self-checking and raise an alarm in the unlikely event of a failure. This is why the
commissioning tests are less extensive than those for non-numeric electronic devices or electro-
mechanical relays.
To commission the IEDs, you do not need to test every IED function. You need only verify that the
hardware is functioning correctly and that the application-specific software settings have been applied.
You can check the settings by extracting them with appropriate setting software or by using the front
panel interface (HMI panel).
The customer is usually responsible for determining the settings to be applied and for testing any
scheme logic.
The menu language is user-selectable, so the Commissioning Engineer can change it for
commissioning purposes if required.
Note: Restore the language setting to the customer’s preferred language on completion.
Warning: Before carrying out any work on the equipment you should be familiar with
the contents of the Safety Section or Safety Guide SFTY/4LM as well as the
ratings on the equipment’s rating label.
Warning: Do not disassemble the IED in any way during commissioning, other than to
test the CT shorting links.
14-6 P446/EN/TM/E
MiCOMho P446 14 Commissioning Instructions
Note: When the Test Mode cell is set to Contacts Blocked, this cell continues to indicate which contacts
would operate if the IED was in-service. It does not show the actual status of the output relays.
P446/EN/TM/E 14-7
14 Commissioning Instructions MiCOMho P446
The pins of the monitor/download port used for monitor bits are as follows:
Monitor Bit 1 2 3 4 5 6 7 8
Monitor/Download Port Pin 11 12 15 13 20 21 23 24
Warning: When the cell is in Test mode, the scheme logic still drives the output relays,
which could trip the circuit breakers. To avoid this, set the Test Mode cell to
Contacts Blocked.
Notes: Test mode and Contacts Blocked mode can also be selected by energizing an opto-input mapped
to the Test Mode signal, and the Contact Block signal respectively.
Note: When the Test Mode cell is set to Contacts Blocked the Relay O/P Status cell does not show the
current status of the output relays so can not be used to confirm operation of the output relays.
Therefore it is necessary to monitor the state of each contact in turn.
14-8 P446/EN/TM/E
MiCOMho P446 14 Commissioning Instructions
Note: The default settings for the programmable scheme logic has the AR Trip Test signals mapped to
the Trip Input signals. If the programmable scheme logic has been changed, it is essential that
these signals retain this mapping for the‘Test Auto-Reclose facility to work.
The IED relies on voltage memory and delta step changes in a real power system, therefore certain
functions are disabled or bypassed to allow injection testing. Selecting the Static Mode test option
bypasses the delta phase selectors, and power swing detection.
For the tests, the delta directional line is replaced by a conventional distance directional line. Extra
filtering of distance comparators is used so the filtering slows to use a fixed one cycle window.
Memory polarizing is replaced by cross-polarizing from unfaulted phases.
Note: Trip times may be up to ½ cycle longer when tested in the static mode, due to the nature of the test
voltage and current, and the slower filtering. This is normal, and perfectly acceptable.
P446/EN/TM/E 14-9
14 Commissioning Instructions MiCOMho P446
Note: If the cell is set to Internal, only the IED software is checked. If the cell is set to External, both the
software and hardware are checked.
When the device is switched into Loopback Mode, it automatically uses generic addresses 0-0. It
responds as if it is connected to a remote device. The sent and received IM64 signals continue to be
routed to and from the signals defined in the programmable logic.
Note: Loopback mode can also be selected by energizing an opto-input mapped to the Loopback signal.
14-10 P446/EN/TM/E
MiCOMho P446 14 Commissioning Instructions
4 COMMISSIONING EQUIPMENT
P446/EN/TM/E 14-11
14 Commissioning Instructions MiCOMho P446
5 PRODUCT CHECKS
These product checks are designed to ensure that the device has not been physically damaged prior
to commissioning, is functioning correctly and that all input quantity measurements are within the
stated tolerances.
If the application-specific settings have been applied to the IED prior to commissioning, make a copy
of the settings. This allows you to restore them at a later date if necessary. This can be done by:
If the customer has changed the password that prevents unauthorized changes to some of the
settings, either the revised password should be provided, or the original password restored before
testing.
Note: If the password has been lost, a recovery password can be obtained from Alstom Grid.
DANGER: The following group of tests should be carried out without the auxiliary
supply being applied to the IED and, if applicable, with the trip circuit
isolated.
The current and voltage transformer connections must be isolated from the IED for these checks. If a
P991 test block is provided, the required isolation can be achieved by inserting test plug type P992.
This open-circuits all wiring routed through the test block.
Before inserting the test plug, check the scheme diagram to ensure that this will not cause damage or
a safety hazard (the test block may, for example, be associated with protection current transformer
circuits). The sockets in the test plug, which correspond to the current transformer secondary
windings, must be linked before the test plug is inserted into the test block.
DANGER: Never open-circuit the secondary circuit of a current transformer since the
high voltage produced may be lethal and could damage insulation.
If a test block is not provided, the voltage transformer supply to the IED should be isolated using the
panel links or connecting blocks. The line current transformers should be short-circuited and
disconnected from the IED terminals. Where means of isolating the auxiliary supply and trip circuit (for
example isolation links, fuses and MCB) are provided, these should be used. If this is not possible,
the wiring to these circuits must be disconnected and the exposed ends suitably terminated to prevent
them from being a safety hazard.
14-12 P446/EN/TM/E
MiCOMho P446 14 Commissioning Instructions
Warning: The rating information given under the top access cover on the front of the
IED should be checked. Check that the IED being tested is correct for the
line or circuit. Ensure that the circuit reference and system details are
entered onto the setting record sheet. Check the CT secondary current
rating and record the CT tap which is in use.
Carefully examine the IED to see that no physical damage has occurred since installation.
Ensure that the case earthing connections (bottom left-hand corner at the rear of the IED case) are
used to connect the IED to a local earth bar using an adequate conductor.
A B C DE FG H J K L M N
1
1
1
1
1 2 3 19
2
2
3
3
3
4 5 6 20
4
4
5
5
5
IRIG-B
6
6
6
6
6
7 8 9 21
7
7
8
8
9
9
9
10 11 12 22
10
10
10
10
10
10
10
10
11
11
11
11
11
11
11
11
12
12
12
12
12
12
12
12
13 14 15 23
13
13
13
13
13
13
13
13
TX
RX
14
14
14
14
14
14
14
14
15
15
15
15
15
15
15
15
16 17 18 24
16
16
16
16
16
16
16
16
17
17
17
17
17
17
17
17
18
18
18
18
18
18
18
18
P3003ENb
The heavy-duty terminal blocks are fastened to the rear panel using four crosshead screws. These
are located two at the top and two at the bottom.
Note: Use a magnetic bladed screwdriver to minimize the risk of the screws being left in the terminal block
or lost.
Pull the terminal block away from the rear of the case and check with a continuity tester that all the
shorting switches being used are closed.
5.1.3 Insulation
Insulation resistance tests are only necessary during commissioning if explicitly requested.
Isolate all wiring from the earth and test the insulation with an electronic or brushless insulation tester
at a DC voltage not exceeding 500 V. Terminals of the same circuits should be temporarily connected
together.
The main groups of IED terminals are:
P446/EN/TM/E 14-13
14 Commissioning Instructions MiCOMho P446
Warning: Check that the external wiring is correct to the relevant IED diagram and
scheme diagram. Ensure as far as practical that phasing/phase rotation
appears to be as expected. The IED diagram number appears on the rating
label under the top access cover on the front of the device.
If a P991 test block is provided, the connections should be checked against the scheme diagram. We
recommend that you make the supply connections to the live side of the test block (coloured orange)
and use the odd numbered terminals (1, 3, 5, 7 …).
The auxiliary supply normally uses terminals 13 (supply positive) and 15 (supply negative). Terminals
14 and 16 connected are connected to the IED’s positive and negative auxiliary supply terminals
respectively. However, you should check the wiring against the schematic diagram to ensure
compliance with the customer’s normal practice.
14-14 P446/EN/TM/E
MiCOMho P446 14 Commissioning Instructions
Note: The IED can withstand an ac ripple of up to 12% of the upper rated voltage on the dc auxiliary
supply.
Warning: Do not energize the relay or interface unit using the battery charger with the
battery disconnected as this can irreparably damage the relay’s power supply
circuitry.
Energise the relay only if the auxiliary supply is within the specified operating ranges. If a test block is
provided, it may be necessary to link across the front of the test plug to connect the auxiliary supply to
the relay.
Warning: The current and voltage transformer connections must remain isolated from
the IED for these checks. The trip circuit should also remain isolated to
prevent accidental operation of the associated circuit breaker.
The following group of tests verifies that the IED hardware and software is functioning correctly and
should be carried out with the auxiliary supply applied to the IED.
5.2.2 LCD
The Liquid Crystal Display (LCD) is designed to operate in a wide range of substation ambient
temperatures and therefore has a contrast setting. This is factory preset but to adjust it use
CONFIGURATION > LCD Contrast.
Warning: Before applying a contrast setting, make sure it does not make the display
too light or dark so the menu text becomes unreadable. The display visibility
can be restored by downloading a MiCOM S1 Studio setting file, with the LCD
contrast set in the range of 7 to 11.
P446/EN/TM/E 14-15
14 Commissioning Instructions MiCOMho P446
2. Press on the battery lightly, to prevent it from falling out of the battery compartment, then pull
the red tab to remove the isolation strip.
Now it is necessary to set the date and time to the correct values. The method of setting depends on
whether accuracy is maintained by the IRIG-B port at the rear or by the IED's internal clock.
1. In the DATE AND TIME column, set the IRIG-B Sync cell to Enabled.
2. Ensure the IED is receiving the IRIG-B signal by checking that cell IRIG-B Status reads
Active.
3. Once the IRIG-B signal is active, adjust the time offset of the universal co coordinated time
(satellite clock time) on the satellite clock equipment so that local time is displayed.
4. Check that the time, date and month are correct in the Date/Time cell. The IRIG-B signal
does not contain the current year so it needs to be set manually in this cell.
5. If the auxiliary supply fails, the time and date are maintained by the auxiliary battery.
Therefore, when the auxiliary supply is restored, you should not have to set the time and date
again. To test this, remove the IRIG-B signal, and then remove the auxiliary supply. Leave
the device de-energized for approximately 30 seconds. On re energization, the time should be
correct.
6. Reconnect the IRIG-B signal.
1. Set the date and time to the correct local time and date using Date/Time cell or using the
serial protocol.
2. If the auxiliary supply fails, the time and date are maintained by the auxiliary battery.
Therefore, when the auxiliary supply is restored, you should not have to set the time and date
again. To test this, remove the auxiliary supply. Leave the device de-energized for
approximately 30 seconds. On re energization, the time should be correct.
5.2.4 LEDs
On power-up, all LEDs first flash yellow. Following this, the green "Healthy" LED switches ON,
indicating that the device is healthy.
The IED's non-volatile memory stores the states of the alarm, trip and user-programmable LEDs (if
configured to latch). If the auxiliary supply is disconnected, then at some later time reconnected, the
LEDS return to their previous states. If any LEDs were ON previously, they switch ON when the
auxiliary supply is applied.
If any of these LEDs are ON, reset them before proceeding with further testing. If the LED switches
OFF, this means it has reset successfully so it is operational and no testing is needed.
Note: In most cases, alarms related to the communications channels do not reset at this stage.
14-16 P446/EN/TM/E
MiCOMho P446 14 Commissioning Instructions
2. Check that the out of service LED is ON continuously and the alarm LED flashes.
It is not necessary to return the Test Mode cell to Disabled at this stage because the test mode is
required for later tests.
1. Measure the field voltage across terminals M7 and M9 of the power supply terminal block.
2. Check the polarity is correct.
3. Check the field voltage is in the range 40 V to 60 V when no load is connected
4. Repeat for terminals M8 and M10.
The status of each opto-isolated input can be viewed using either the Opto I/P Status cell in the
SYSTEM DATA column, or the Opto I/P Status cell in the COMMISSION TESTS column.
A '1' indicates an energized input and a '0' indicates a de-energized input. When each opto-input is
energized, one of the characters on the bottom line of the display changes to indicate the new state of
the input.
Caution: The high break output contacts, fitted to some models, are polarity sensitive.
External wiring should be verified against polarity requirements described in
the external connection diagram to ensure correct operation.
P446/EN/TM/E 14-17
14 Commissioning Instructions MiCOMho P446
This test checks that all the output relays are functioning correctly.
1. Ensure that the IED is still in test mode by checking that COMMISSION TESTS > Test Mode
is set to Blocked.
2. Energize the output relays one at a time. To select output relay 1 for testing, set the Test
Pattern cell to 1.
3. Connect a continuity tester across the terminals corresponding to output relay 1 as shown in
the external connection diagram.
4. To operate the output relay set the Contact Test cell to Apply Test.
5. Check the operation with a continuity tester.
6. Measure the resistance of the contacts in the closed state.
7. Reset the output relay by setting the Contact Test cell to Remove Test.
8. Repeat the test for the remaining output relays.
9. Return the IED to service by setting COMMISSION TESTS > Test Mode to Disabled.
Warning: Keep the time between application and removal of the contact test as short
as possible to avoid excessive heating. Ensure the associated output relay
does not exceed the thermal ratings of anything connected to the output
relays during the contact test procedure.
Copper connection
The copper rear communication port RP1 is presented on pins 16, 17 and 18 of the power supply
terminal block. Screened twisted pair cable is used. Pin 16 is the earth connection for the screen and
pins 17 and 18 are for the communication signal. The optional fibre connection is presented on a
separate board, housed in the communications slot.
For K-Bus applications, pins 17 and 18 are not polarity sensitive and it does not matter which way
round the wires are connected. EIA(RS)485 is polarity sensitive, so you must ensure the wires are
connected the correct way round (pin 17 is positive, pin 18 is negative).
If K-Bus is being used, a Kitz protocol converter (KITZ101, KITZ102 OR KITZ201) will have been
installed to convert the K-Bus signals into RS232. Likewise, if RS485 is being used, an RS485-RS232
converter will have been installed. In the case where a protocol converter is being used, a laptop PC
running appropriate software (such as MiCOM S1 Studio or PAS&T) can be connected to the
incoming side of the protocol converter, as shown in Figure 2.
14-18 P446/EN/TM/E
MiCOMho P446 14 Commissioning Instructions
K-Bus
KITZ RS232
IED IED IED Protocol
Converter
RS485
RS485-RS232 RS232
IED IED IED
Converter
K-Bus can only be used with the Courier protocol, whereas RS485 and RS232 can be used for a
variety of serial protocols as required by the device in question, so communication using the chosen
data protocol also needs to be checked, as described in the following sections.
Fibre Connection
Some models have an optional fibre optic communications port fitted (on a separate communications
board). The communications port to be used is selected by setting the Physical Link cell in the
COMMUNICATIONS column, the values being 'Copper' or 'K-Bus' for the RS485/K-bus port and 'Fibre
Optic’ for the fibre optic port.
5.2.11.1 Courier
K-Bus
1. Set COMMUNICATIONS > Physical Link to K-Bus
2. Ensure that the communications baud rate and parity settings in the application software are
set the same as those on the protocol converter.
3. In COMMUNICATIONS > Remote Address set the IED's Courier address to a value between
1 and 254.
4. Check that communications can be established with this IED using the portable PC/Master
Station.
Copper
1. Set COMMUNICATIONS > Physical Link to copper.
2. Ensure that the communications baud rate and parity settings in the application software are
set the same as those of the IED.
3. In COMMUNICATIONS > Remote Address set the IED's Courier address to a value between
1 and 254.
4. Check that communications can be established with this IED using the portable PC/Master
Station
Fibre
1. Set COMMUNICATIONS > Physical Link to fibre-optic.
2. Ensure that the address and baud rate settings in the application software are set the same as
those of the IED.
3. Check that communications with the IED can be established using the Master Station.
P446/EN/TM/E 14-19
14 Commissioning Instructions MiCOMho P446
Copper
1. Set COMMUNICATIONS > Physical Link to copper.
2. IEC60870-5-103/VDEW communication systems are designed to have a local Master Station
and this should be used to verify that the rear fibre optic or EIA(RS)485 port, as appropriate, is
working. Ensure that the IED address and baud rate settings in the application software are
set the same as those in the IED.
3. Check that communications with the IED can be established using the Master Station.
Fibre
1. Set COMMUNICATIONS > Physical Link to fibre-optic.
2. Ensure that the address and baud rate settings in the application software are set the same as
those of the IED.
3. Check that communications with the IED can be established using the Master Station.
Copper
1. Set COMMUNICATIONS > Physical Link to copper.
2. Ensure that the IED address, baud rate and parity settings in the application software are set
the same as those in the IED.
3. Check that communications with this IED can be established using the Master Station.
Fibre
1. Set COMMUNICATIONS > Physical Link to fibre-optic.
2. Ensure that the address and baud rate settings in the application software are set the same as
those of the IED.
3. Check that communications with the IED can be established using the Master Station.
1. Connect a portable PC running the appropriate IEC 61850 Client Software or MMS browser to
the IED's Ethernet port (RJ45 or ST fibre optic connection). Alternatively, you can use a
simple Ethernet 'ping' to the configured IP address.
2. Configure the IP parameters (IP Address, Subnet Mask, Gateway) and SNTP time
synchronization parameters (SNTP Server 1, SNTP Server 2) Configuration of the IP
parameters can be imported from an SCL file or made manually by using the IED Configurator
tool, which is installed as part of MiCOM S1 Studio. In either case, these parameters are sent
to the IED using the IED Configurator via a serial connection to the IED’s front port - they
cannot be configured via the IED’s HMI on the front panel.
Note: If the assigned IP address is duplicated elsewhere on the same network, the remote
communications operates in an indeterminate way. However, the device checks for a conflict on
every IP configuration change and at power up. An alarm is raised if an IP conflict is detected. The
device can be configured to accept data from networks other than the local network using the
‘Gateway’ setting.
14-20 P446/EN/TM/E
MiCOMho P446 14 Commissioning Instructions
1. Connect a portable PC running the appropriate software (for example MiCOM S1 Studio) to
the rear EIA(RS)232 port (SK5)
2. Ensure that the communications baud rate and parity settings in the application software are
set the same as those in the IED.
3. In COMMUNICATIONS > RP2 Address set the IED's Courier address to a value between 1
and 254.
4. Set COMMUNICATIONS > RP2 Port Config to EIA(RS)232.
5. Check that communications can be established with this IED using the portable PC.
1. Apply current equal to the line current transformer secondary winding rating to each current
transformer input in turn. See the external connection diagram for the terminal numbers.
P446/EN/TM/E 14-21
14 Commissioning Instructions MiCOMho P446
2. Check its magnitude using a multi-meter or test set readout. The corresponding reading can
then be checked in the MEASUREMENTS 1 column.
3. Record the displayed value. The measured current values are either in primary or secondary
Amperes. If MEASURE’T SETUP > Local Values is set to Primary, the value displayed
should be equal to the applied current multiplied by the corresponding current transformer
ratio (set in the CT AND VT RATIOS column). See Table 4. If Local Values is set to
Secondary, the value displayed should be equal to the applied current.
Note: If a PC is connected to the IED rear communications port to display the measured current, the
process is similar. However, the MEASURE’T SETUP > Remote Values setting determines
whether the displayed values are in primary or secondary Amperes.
The measurement accuracy of the IED is ±1%. However, an additional allowance must be made for
the accuracy of the test equipment being used.
Corresponding CT ratio
Cell in MEASUREMENTS 1
(in ‘CT and VT RATIOS‘ column)
IA magnitude
IB magnitude Phase CT Primary / Phase CT Secondary
IC magnitude
IM magnitude Mcomp CT Primary / Mcomp CT Secondary
ISEF magnitude SEF amp CT Primary / SEF amp CT Secondary
Table 4: CT Ratios settings
Note: If a PC connected to the IED using the rear communications port is being used to display the
measured current, the process is similar. However, setting MEASURE’T SETUP > Remote Values
determines whether the displayed values are in primary or secondary Amperes.
Corresponding CT ratio
Cell in MEASUREMENTS 1
(in ‘CT and VT RATIOS‘ column)
VAN magnitude
VBN magnitude Main VT Primary / Main VT Secondary
VCN magnitude
Check Sync Voltage Magnitude C/S VT Primary / C/S VT Secondary
CB2 Check Sync Volt Magnitude (for dual circuit
CB2 C/S VT Primary / CB2 C/S VT Secondary
breaker variants)
Table 5: Voltage ratio settings
14-22 P446/EN/TM/E
MiCOMho P446 14 Commissioning Instructions
Note: Two channels may have different implementations. The sections describing commissioning the
interfaces and the loopback tests should be used as is relevant to each channel.
Warning: NEVER look directly into the transmit port or the end of an optical fibre, as
this could severely damage your eyes
P446/EN/TM/E 14-23
14 Commissioning Instructions MiCOMho P446
Notes: The propagation delay measurement is not valid in this mode of operation. The IED responds as if it
is connected to a remote IED. It indicates a loopback alarm which can only be cleared by setting
COMMISSION TESTS > Loopback Mode to Disabled.
In loopback mode the signals sent and received through the protection communications interface
continue to be routed to and from the signals defined in the programmable logic.
A test pattern can also be sent to the remote end to test the whole InterMiCOM communication path.
To do this, set COMMISSION TESTS >IM64 Test Mode to Enable and connect two ends. Take
special care because the test pattern is executed using PSL at the remote end.
14-24 P446/EN/TM/E
MiCOMho P446 14 Commissioning Instructions
Note: If INTERMICOM COMMS > Loopback Mode is set to Internal, only the internal software of the
device is checked. This is useful for testing functionality if no communications connections are
made. Use the External setting during commissioning because it checks both the software and
hardware used by InterMiCOM . When the IED is switched into either Internal or External Loopback
Mode it automatically uses generic addresses and inhibits the InterMiCOM messages to the PSL by
setting all eight InterMiCOM message command states to zero.
Set INTERMICOM COMMS > Loopback Mode to External and form a communications loopback by
connecting the transmit signal (pin 2) to the receive signal (pin 3).
Note: The DCD signal must be held high (by connecting pin 1 to pin 4) if the connected equipment does
not support DCD. A communications converter is probably used and the loopback is not at the
InterMiCOM connector. Make the loopback as far into the communications channel as possible so
that as much wiring, and as many ancillary communication components as possible are included in
the test.
The loopback mode is shown on the front panel by an Alarm LED and the message IM Loopback on
the LCD.
P446/EN/TM/E 14-25
14 Commissioning Instructions MiCOMho P446
Check that all connections are correct and the software is working correctly. Check that
INTERMICOM COMMS > Loopback Status shows OK.
1. Enter any test pattern in the Test Pattern cell in the by scrolling through and changing
selected bits between 1 and 0. The entered pattern is transmitted through the loopback.
2. Check that the IM Output Status cell matches the applied Test Pattern.
3. Check that all 8 bits in the IM Input Status cell are zero.
Data CD Status
FrameSync Status
Message Status
Channel Status
1. Simulate a failure of the communications link by breaking a connection and checking that
some of these cells show Fail.
2. Restore the communications loopback and ensure that the four diagnostic cells display OK
Note: Some or all of these cells show Fail depending on the communications configuration and the way
the link has failed.
14-26 P446/EN/TM/E
MiCOMho P446 14 Commissioning Instructions
8 SETTING CHECKS
The setting checks ensure that all of the application-specific settings have been correctly applied, both
the IED’s function and the programmable scheme logic settings.
Note: If applicable, the trip circuit remains isolated during these checks to prevent accidental operation of
the associated circuit breaker.
Transferring settings to the IED from a pre-prepared setting file using MiCOM S1 Studio
Enter the settings manually using the IED’s front panel HMI
1. Connect a laptop/PC (that is running MiCOM S1 Studio) to the IED's front serial port, or any
rear Courier communications port (with a KITZ protocol converter if necessary).
2. Power on the IED
3. Right-click on the appropriate device name in the Studio Explorer pane and select Send
4. In the Send to dialog select the setting files and click Send
5. Close the Send to dialog by clicking Close
Notes: If the device name does not already exist in the Studio Explorer system, first perform a
QuickConnect to the IED. Then manually add the settings file to the device name in the Studio
Explorer system. Refer to the MiCOM S1 Studio help for details of how to do this.
If application-specific Programmable Logic Scheme (PSL) is used, this must be transferred to the
IED from MiCOM S1 Studio. It is not possible to change the PSL using the IED’s front panel HMI.
8.1.2 Entering the settings using the IED's front panel HMI panel
Note: It is not possible to change the PSL using the IED’s front panel HMI.
1. Starting at the default display, press the down cursor key to show the first column heading.
2. Use the horizontal cursor keys to select the required column heading.
3. Use the vertical cursor keys to view the setting data in the column.
4. To return to the column header, either press and hold the up cursor key, or press the Cancel
key once. It is only possible to move across columns at the column heading level.
5. To return to the default display, press the up cursor key or the Cancel key from any of the
column headings. If you use the auto-repeat function of the up cursor key, you cannot go
straight to the default display from one of the column cells because the auto-repeat stops at
the column heading.
P446/EN/TM/E 14-27
14 Commissioning Instructions MiCOMho P446
6. To change the value of a setting, go to the relevant cell in the menu, then press the Enter key
to change the cell value. A flashing cursor on the LCD shows that the value can be changed.
You may be prompted for a password first.
7. To change the setting value, press the up and down cursor keys. If the setting to be changed
is a binary value or a text string, select the required bit or character to be changed using the
left and right cursor keys.
8. Press the Enter key to confirm the new setting value or the Clear key to discard it. The new
setting is automatically discarded if it is not confirmed within 15 seconds.
9. For protection group settings and disturbance recorder settings, the changes must be
confirmed before they are used. When all required changes have been entered, return to the
column heading level and press the down cursor key. Before returning to the default display,
the following prompt appears.
Update settings
ENTER or CLEAR
10. Press the Enter key to accept the new settings or press the Clear key to discard the new
settings.
Notes: If the menu time-out occurs before the setting changes have been confirmed, the setting values are
also discarded.
Control and support settings are updated immediately after they are entered, without the Update
settings prompt
Warning: If the installation needs application-specific PSL, the relevant .psl files, must
be transferred to the IED for each setting group that will be used.
If you do not do this, the factory default PSL is still resident. This may have
severe operational and safety consequences.
Note: If, as a result of applying the application settings, the communication mode (Comms Mode cell) has
been changed, a comms changed alarm is raised on the user interface. This alarm can only be
cleared by power cycling the relay. If the alarm appears, remove and then re-apply the auxiliary
supply to the relay.
14-28 P446/EN/TM/E
MiCOMho P446 14 Commissioning Instructions
1. If testing the distance elements using using test sets that do not provide a dynamic model to
generate true fault delta conditions, set COMMISSIONING TESTS > Static Test Mode to
Enabled. When set, this disables phase selector control and forces the device to use a
conventional (non-delta) directional line.
2. For lower specification test equipment that cannot apply a full three phase set of healthy
simulated pre-fault voltages, the VT supervision may need to be disabled to avoid spurious
pickup. Set CONFIGURATION > Supervision to Disabled.
3. Connect the test equipment to the device using the test block(s), taking care not to open-
circuit any CT secondary windings. If using MMLG type test blocks, the live side of the test
plug must be provided with shorting links before it is inserted into the test block.
4. When the test is complete, make sure COMMISSIONING TESTS > Static Test Mode is set
back to Disabled.
1. Apply a dynamic A-phase-to-neutral fault, slightly in excess of the expected reach. The
duration of the injection should be in excess of the tZ1 timer setting, but less than tZ2. These
settings are in the DISTANCE column. No trip should occur, and the red Trip LED should
remain OFF.
2. Reduce the impedance and reapply the simulated fault.
3. Repeat this procedure until a trip occurs. When this happens, the display shows
Alarms/Faults present and the Alarm and Trip LEDs switch ON.
4. To view the alarm message, keep pressing the read key until the yellow alarm LED changes
from flashing to being steadily on.
5. At the prompt Press clear to reset alarms, press the C key. This clears the fault record from
the display.
6. Record the impedance at which the device trips. The measured impedance should be within
+/- 10% of the expected reach.
7. Read and reset the alarms
P446/EN/TM/E 14-29
14 Commissioning Instructions MiCOMho P446
Modern injection test sets usually calculate the expected fault loop impedance from the device
settings. For those that do not, the appropriate loop impedance is given by the vector sum:
1. Apply a dynamic B-C fault, slightly in excess of the expected reach. The duration of the
injection should be in excess of the tZ2 timer setting, but less than tZ3. These settings are in
the DISTANCE column. No trip should occur, and the red Trip LED should remain OFF.
2. Repeat the test described above to find the zone reach.
3. Record the impedance at which the device trips. The measured impedance should be within
+/- 10% of the expected reach.
4. Read and reset the alarms.
Modern injection test sets usually calculate the expected fault loop impedance from the device
settings. For those that do not, check the reach for phase-phase and confirm the operation of the
appropriate contacts. The appropriate loop impedance is now given by:
2 x Z2 Ω
1. Apply a dynamic C-A fault, slightly in excess of the expected reach. The duration of the
injection should be in excess of the tZ3 timer setting (typically tZ3 + 100 ms).
2. Repeat the test described above to find the zone reach.
3. Record the impedance at which the device trips. The measured impedance should be within
+/- 10% of the expected reach.
4. Read and reset the alarms.
5. Check that the correct reverse offset (Z3’) has been applied. The setting is in the Z3’ Ph Rev
Reach and Z3’ Gnd Rev Reach cells.
1. Apply a dynamic B-N fault, slightly in excess of the expected reach. The duration of the
injection should be in excess of the tZ4 timer setting (typically tZ4 + 100 ms).
2. Repeat the test described above to find the zone reach.
3. Record the impedance at which the device trips. The measured impedance should be within
+/- 10% of the expected reach.
4. Read and reset the alarms.
14-30 P446/EN/TM/E
MiCOMho P446 14 Commissioning Instructions
1. Apply a dynamic C-N fault, slightly in excess of the expected reach. The duration of the
injection should be in excess of the tZP timer setting (typically tZP + 100 ms).
2. Repeat the test described above to find the zone reach.
3. Record the impedance at which the relay trips. The measured impedance should be within
+/-10% of the expected reach.
4. Read and reset the alarms.
R1Ph, R2Ph, R3Ph, R3Ph reverse, R4Ph and RP Ph for phase fault zones.
R1Gnd, R2Gnd, R3Gnd, R3Gnd reverse, R4Gnd and RP Gnd for ground fault zones.
Note: Zone 3 has an independent setting for the forward resistance reach (right-hand resistive reach line),
and the reverse resistance reach (left-hand resistive reach line).
8.2.2.1 Phase A
4. For two breaker applications, stop the timer when CB1 and CB2 trip contacts have both
closed.
5. Monitor by connecting the contacts in series to stop the timer if necessary.
6. Record the phase A trip time.
7. Switch OFF the AC supply and reset the alarms.
8.2.2.2 Phase B
P446/EN/TM/E 14-31
14 Commissioning Instructions MiCOMho P446
2. Repeat the test, this time ensuring that the breaker trip contacts relative to B phase operation
close correctly.
3. Record the phase B trip time.
4. Switch OFF the AC supply and reset the alarms.
8.2.2.3 Phase C
The average of the recorded operating times for the three phases should typically be less than 20 ms
for 50 Hz, and less than 16.7 ms for 60 Hz when set for instantaneous operation.
Note• Where a non-zero tZ1 Gnd time delay is set in the DISTANCE menu column, the expected operating
time is typically within +/- 5% of the tZ1 setting plus the “instantaneous” delay quoted above.
Note: The P446 allows separate time delay settings for phase (“Ph”) and ground (“Gnd”) fault elements.
BOTH must be checked to ensure that they have been set correctly.
14-32 P446/EN/TM/E
MiCOMho P446 14 Commissioning Instructions
Zone 1 fault: A dynamic forward A-B fault at half the Zone 1 reach is simulated.
End of line fault: A dynamic forward A-B fault at the remote end of the line is simulated. The
fault impedance simulated should match the Line Impedance setting in the LINE
PARAMETERS menu column.
Zone 4 fault: A dynamic reverse A-B fault at half the Zone 4 reach is simulated.
IED RESPONSE
Fault type Forward fault in Forward fault at end of line
Reverse fault in zone 4
simulated zone 1 (within Z1X/Z2)
Signal receive opto ON OFF ON OFF ON OFF
Zone 1 extension Trip Trip No Trip Trip No Trip No Trip
Trip, Trip, No Trip, No Trip, No Trip, Signal No Trip, Signal
Blocking scheme
No Signal Send No Signal Send Signal Send No Signal Send Send Send
1. Energize the Reset Z1X (Reset Zone 1 Extension) opto-input. This is done by applying a
continuous dc voltage onto the required opto-input, either from the test set, station battery, or
IED field voltage. The commissioning engineer decides on the best method.
2. Inject an end of line fault. The duration of injection should be set to 100 ms. No trip should
occur.
3. De-energize the Reset Z1X opto-input
4. Repeat the test injection and record the operating time. This should typically be less than
20 ms for 50 Hz, and less than 16.7 ms for 60 Hz when set for instantaneous operation.
5. Switch OFF the ac supply and reset the alarms.
Note: Where a non-zero tZ1 Ph or tZ1 Gnd time delay is set in the DISTANCE column, the expected
operating time is typically within +/- 5% of the tZ1 setting plus the “instantaneous” delay quoted
above.
1. Energize the Signal Receive opto-input. This is done by applying a continuous dc voltage
onto the required opto-input from the test set, station battery, or IED field voltage (it is up to
commissioning engineer to decide on the best method).
2. Inject an end of line fault, and record the operating time. The measured operating time should
typically be less than 20 ms for 50 Hz, and less than 16.7ms for 60 Hz when set for
instantaneous operation.
3. Switch OFF the ac supply and reset the alarms.
P446/EN/TM/E 14-33
14 Commissioning Instructions MiCOMho P446
Note: Where a non-zero Aided Distance Dly time delay is set in the DISTANCE menu column, the
expected operating time is typically within +/- 5% of the tZ1 setting plus the “instantaneous” delay
quoted above.
De-energize the Signal Receive opto-input (remove the temporary energization link, to turn it OFF).
1. Energize the Signal Receive opto-input. This is done by applying a continuous DC voltage
onto the required opto-input, either from the test set, station battery, or IED field voltage. The
commissioning engineer decides on the best method.
2. Inject an end of line fault. The duration of injection should be set to 100 ms. No trip should
occur.
3. De-energize the channel received opto-input.
4. Repeat the test injection, and record the operating time.
5. Switch OFF the ac supply and reset the alarms.
Note For blocking schemes, a non-zero Aided Distance Dly time delay is set, so the expected operating
time is typically within +/- 5% of the delay setting plus the “instantaneous” operating delay. The trip
time should thus be less than 20 ms for 50 Hz, and less than 16.7 ms for 60 Hz, plus 1.05 x Delay
setting.
1. Reconnect the test set so that the timer is no longer stopped by the Trip contact, but is now
stopped by the Signal Send contact (the contact that would normally be connected to the
pilot/signalling channel).
2. Inject a Zone 1 fault, and record the signal send contact operating time. The measured
operating time should typically be less than 20 ms for 50 Hz, and less than 16.7 ms for 60 Hz
applications.
3. Switch OFF the ac supply and reset the alarms.
1. Reconnect the test set so that the timer is no longer stopped by the Trip contact, but is now
stopped by the Signal Send contact. This is the contact that would normally be connected to
the pilot/signalling channel.
2. Inject a Zone 4 fault, and record the signal send contact operating time. The measured
operating time should typically be less than 20 ms for 50 Hz, and less than 16.7 ms for 60 Hz
applications.
3. Switch OFF the ac supply and reset the alarms.
14-34 P446/EN/TM/E
MiCOMho P446 14 Commissioning Instructions
1. When the tests are completed, restore all settings that were disabled for
testing purposes.
2. Set the Static Test Mode to Disabled.
3. Remove any wires or leads temporarily fitted to energize the channel receive
opto-input.
1. In the CONFIGUARATION column, disable all protection elements other than the one being
tested.
2. Make a note of which elements need to be re-enabled after testing
P446/EN/TM/E 14-35
14 Commissioning Instructions MiCOMho P446
IED RESPONSE
Direction of fault
Forward fault Reverse fault
test injection
Permissive scheme Trip, No Trip, No Trip, No Trip,
(POR/POTT) Signal Send Signal Send No Signal Send No Signal Send
Table 8: Delta protection scheme response
3. Simulate a healthy three-phase set of balanced voltages, each of magnitude Vn. No load
current should be simulated. The duration of injection should be set to 1 second. Step 1
therefore mimics a healthy unloaded line before the onset of a fault.
4. Simulate a forward fault on the A-phase. The A-phase voltage must be simulated to drop by 3
times the Dir. V Fwd setting,
Va = Vn – 3(Dir. V Fwd)
The fault current on the A-phase should be set to 3 times the Dir. I Fwd setting, lagging Va by
a phase angle equal to the line angle,
Phase A
1. Prepare a dynamic A-phase-to-neutral fault, as detailed above.
2. Set a timer to start when the fault injection is applied, and to stop when the trip occurs.
3. To verify the correct output contact mapping use the trip contacts that would be expected to
trip the circuit breaker(s), as shown in the following table.
Tripping type Single breaker Two circuit breakers
Three Pole Tripping Any Trip Any Trip (CB1) and Any Trip (CB2)
Single Pole Tripping Trip A Trip A (CB1) and Trip A (CB2)
4. For two breaker applications, stop the timer when CB1 and CB2 trip contacts have both
closed.
5. Monitor by connecting the contacts in series to stop the timer if necessary.
6. Record the phase A trip time
7. Switch OFF the ac supply and reset the alarms
14-36 P446/EN/TM/E
MiCOMho P446 14 Commissioning Instructions
Phase B
1. Reconfigure to test a B phase fault.
2. Repeat the test, this time ensuring that the breaker trip contacts relative to B phase operation
close correctly.
3. Record the phase B trip time.
4. Switch OFF the ac supply and reset the alarms.
Phase C
1. Reconfigure to test a C phase fault.
2. Repeat the test, this time ensuring that the breaker trip contacts relative to C phase operation
close correctly.
3. Record the phase C trip time.
4. Switch OFF the ac supply and reset the alarms.
The average of the recorded operating times for the three phases should typically be less than 20 ms
for 50 Hz, and less than 16.7 ms for 60 Hz when set for instantaneous operation.
Note; For Blocking schemes, where a non-zero Delta Dly time delay is set, the expected operating time is
typically within +/- 5% of the delay setting plus the “instantaneous” delay quoted above.
1. Simulate a healthy three-phase set of balanced voltages, each of magnitude Vn. No load
current should be simulated. The duration of injection should be set to 1 second. Step 1
therefore mimics a healthy unloaded line, prior to the onset of a fault.
2. Simulate a reverse fault on the A-phase. The A-phase voltage must be simulated to drop by 3
times the Dir. V Rev setting,
Va = Vn – 3(Dir. V Rev)
The fault current on the A-phase should be set to 3 times the DI Rev setting, and in antiphase
to the forward injections,
1. Prepare the dynamic A phase reverse fault, as detailed above. Ensure that the test set is
simulating Steps 1 and 2 as one continuous transition.
P446/EN/TM/E 14-37
14 Commissioning Instructions MiCOMho P446
2. Set a timer to start when the fault injection is applied, and to stop when the Delta scheme
Signal Send contact closes.
3. Apply the test, and record the signal send contact response time. The recorded operating
time should typically be less than 20 ms for 50 Hz, and less than 16.7 ms for 60 Hz
applications.
4. Switch OFF the ac supply and reset the alarms.
1. When the tests are completed, restore all settings that were disabled for
testing purposes.
2. Remove any wires or leads temporarily fitted to energize the channel receive
opto-input.
+jX
Z6
Z5
State 4
State 3
State 2
State 1
R
R6' R5' R5 R6
∆R
Z5'
Z6'
Depending on the Out of Step (OST) settings, use one of the following setting options.
OST setting
Predictive OST setting
Predictive and OST setting
14-38 P446/EN/TM/E
MiCOMho P446 14 Commissioning Instructions
OST setting
1. Clear all alarms.
2. Set the OST timer to zero.
3. To test OST, a 4-state test sequence is required. Based on healthy voltages (VA = VB = VC =
57.8 V) calculate the currents to generate the impedances as below.
State 1 State 2 State 3 State 4
4. Now apply the 4-state sequence, check that all 3-phases have tripped and that an OST alarm
is displayed on the local LCD.
Note: The angle in the table above is the angle between voltages and their respective currents. In state 4
the currents are displaced 180° from their respective voltages.
4. Now apply the 3-state sequence, check that all 3-phases have tripped and that an OST alarm
is displayed on the local LCD.
P446/EN/TM/E 14-39
14 Commissioning Instructions MiCOMho P446
Note: The device must be tested in isolation, with the communications channel to the remote line terminal
disconnected.
1. Determine which output relays have been selected to operate when a DEF trip occurs, by
viewing the programmable scheme logic. If the trip outputs are phase segregated (a different
output relay allocated for each phase), the output relay assigned for tripping on ‘A’ phase
faults should be used.
2. Connect the output relay so that its operation trips the test set and stops the timer.
3. Connect the current output of the test set to the ‘A’ phase current transformer input
4. Connect, all three phase voltages Va, Vb, and Vc.
5. Depending on the test equipment used, make sure the timer is set to start when the current is
applied to the relay.
1. Ensure that the timer is reset and prepare the following test shot.
2. Simulate a forward fault on the A-phase. The A-phase voltage must be simulated to drop by 4
times the DEF Vpol setting,
Va = Vn - 4( DEF Vpol)
Set the fault current on the A-phase should to 2 times the DEF Threshold setting, and in the forward
direction. For a forward fault, the current Ia should lag the voltage Va by the DEF Char Angle setting,
14-40 P446/EN/TM/E
MiCOMho P446 14 Commissioning Instructions
IED RESPONSE
Direction of fault
Forward fault Reverse fault
test injection
Signal Receive Opto ON OFF ON OFF
No Trip, Trip, No Trip, No Trip,
Blocking Scheme
No Signal Send No Signal Send Signal Send Signal Send
Permissive Scheme Trip, No Trip, No Trip, No Trip,
(POR/POTT) Signal Send Signal Send No Signal Send No Signal Send
Table 9: DEF scheme response
The aided earth fault (DEF) scheme trip time for POR schemes (permissive overreach) POR schemes
should be less than 40 ms.
For blocking schemes, where a non-zero DEF Dly time delay is set, the expected operating time is
typically within +/- 5% of the delay setting plus the “instantaneous” (40 ms) delay quoted above.
There is no need to repeat the test for phases B and C, as these trip assignments have already been
proven by the distance/delta trip tests.
P446/EN/TM/E 14-41
14 Commissioning Instructions MiCOMho P446
1. When the tests are completed, restore all settings that were disabled for
testing purposes.
2. Remove any wires or leads temporarily fitted to energize the channel receive
opto-input.
Note: If the default PSL is used, output relay 3 can be used as I1> is mapped to Trip inputs 3 Ph (DDB
529), which in turn is mapped internally to Any Trip (DDB 522), which is mapped to output relay 3.
2. Connect the output relay so that its operation trips the test set and stops the timer.
3. Connect the current output of the test set to the A-phase current transformer input.
If the I>1 Directional cell in the GROUP 1 OVERCURRENT column is set to ‘Directional Fwd’,
the current should flow out of terminal C2. If set to ‘Directional Rev’, it should flow into terminal
2.
If the I>1 Directional cell in the GROUP 1 OVERCURRENT column has been set to
‘Directional Fwd’ or ‘Directional Rev’, the rated voltage should be applied to terminals 20 and
21.
4. Ensure that the timer starts when the current is applied to the relay.
Note: If the timer does not stop when the current is applied and stage 1 has been set for directional
operation, the connections may be incorrect for the direction of operation set. Try again with the
current connections reversed.
14-42 P446/EN/TM/E
MiCOMho P446 14 Commissioning Instructions
Notes: with the exception of the definite time characteristic, the operating times given in Table 10 are for a
Time Multiplier Setting (TMS) or Time Dial Setting (TDS) of 1. For other values of TMS or TDS, the
values need to be modified accordingly.
For definite time and inverse characteristics there is an additional delay of up to 0.02 second and
0.08 second respectively. You may need to add this the IED's acceptable range of operating times.
Caution: When the tests are completed, restore all settings that were disabled for testing
purposes.
one from the voltage transformer input from the line side of the circuit breaker (Main VT)
one from the VT on the bus side of the circuit breaker (CS VT).
P446/EN/TM/E 14-43
14 Commissioning Instructions MiCOMho P446
For a dual circuit breaker installation (breaker-and-a-half switch or mesh/ring bus), three VT inputs are
required:
one from the common point of the two circuit breakers, identified as the line (Main VT)
one from the bus side of CB1 (CB1 CS VT)
one from the bus side of CB2 (CB2 CS VT).
In most cases the line VT input is three phase, whereas the bus VTs are single phase.
The bus VT inputs are normally single phase so the system voltage checks are made on single
phases and the VT may be connected to either a phase-to-phase or phase to neutral voltage.
For these reasons, the IED has to be programmed with the appropriate connection. The CS Input
setting in the CT AND VT RATIOS column can be set to A-N, B-N, C-N, A-B, B-C or C-A according to
the application.
The single-phase bus VT inputs each have associated phase shift and voltage magnitude
compensation settings to compensate for healthy voltage angle and magnitude differences between
the check sync VT input and the selected main VT reference phase. These are:
CB1 CS VT PhShft, CB1 CS VT Mag, CB2 CS VT PhShft and CB2 CS VT Mag for dual CB
models
Any voltage measurements or comparisons using bus VT inputs are made using the compensated
values.
Each circuit breaker controlled can have two stages of check synchronism enabled according to the
settings:
Sys Checks CB1, CB1 CS1 Status, CB1 CS2 Status, Sys Checks CB2, CB2 CS1 Status,
CB1 CS2 Status for dual circuit breaker models.
When the system voltage check conditions are satisfied, the relevant DDB signals are asserted high
as follows:
14-44 P446/EN/TM/E
MiCOMho P446 14 Commissioning Instructions
The CB Healthy DDB should either not be mapped, or if it is mapped it must be asserted high.
The CB status inputs (52A, etc.) should either not be mapped, or if they are mapped they
should be activated to mimic the circuit breaker operation.
If configured for single pole tripping, either the VTs Connected setting in the CT/VT RATIO
column should be set to No, or appropriate voltage signals need to be applied to prevent the
pole dead logic from converting to 3-pole tripping.
1. To test the first three-phase auto-reclose cycle, set COMMISSION TESTS > Test Auto-
reclose to Trip 3 Pole. The IED performs a trip/reclose cycle.
2. Repeat this operation to test the subsequent three-phase auto-reclose cycles.
3. Check all output relays (used for such as circuit breaker tripping and closing, or blocking other
devices) operate at the correct times during the trip/close cycle.
Check the auto-reclose cycles for single phase trip conditions one at a time by sequentially setting
COMMISSION TESTS > Test Auto-reclose to Trip Pole A, Trip Pole B and Trip Pole C.
P446/EN/TM/E 14-45
14 Commissioning Instructions MiCOMho P446
Note 1: End-to-end communication requires a working telecommunication channel between line ends (which
may be a multiplexed link or may be a direct connection). If the telecommunication channel is not
available, it is not possible to establish end-to end communication. Unless otherwise directed by
local operational practice, follow the instructions in this section so the scheme is ready for full
operation when the telecommunications channels become available.
Note 2: The trip circuit should remain isolated during these checks to prevent accidental operation of the
associated circuit breaker.
1. Check the alarm records to ensure that no communications failure alarms have occurred while
the loopback test was in progress. If it was necessary to ‘fail’ the communications while
testing the non-current differential elements, observe the communications behaviour for a few
minutes before removing the loopbacks.
2. After you are satisfied with the communications behaviour in loopback, set COMMISSION
TESTS > Test Mode and Loopback Mode to Disabled.
Note: Most of the required optical signal power levels have already been measured and recorded. If all
signalling uses P59x interface units, no further measurements are required. If, however, direct fibre
or C37.94 communications are used, further measurements are needed.
1. Remove the loopback test fibres and at both ends of each channel used, reconnect the fibre
optic cables for communications between IEDs.
2. For each channel fitted, remove the fibre connecting to the optical receiver (RX).
3. Using an optical power meter measure the strength of the signal received from the remote
IED. The measurements should be within -25.4dBm and -16.8dBm for 850 nm fibre
connections and between -37dBm and -7dBm for 1300nm fibre connections
4. Record the received power level(s).
5. Reconnect the fibre(s) to the IED receiver(s).
Warning: NEVER look directly into the transmit port or the end of an optical fibre, as
this could severely damage your eyes
14-46 P446/EN/TM/E
MiCOMho P446 14 Commissioning Instructions
P446/EN/TM/E 14-47
14 Commissioning Instructions MiCOMho P446
1. Put the IED in test mode by setting COMMISSION TESTS > Test Mode to Blocked.
2. Record which contact is assigned as the Signal Send 1 output
3. Select this output contact as the one to test and advise the engineer at the remote end that the
contact is about to be tested.
1. At the local end, set the COMMISSION TESTS > Contact Test to Apply Test.
2. Reset the output relay by setting COMMISSION TESTS > Contact Test to Remove Test.
Note: Ensure that thermal ratings of anything connected to the output relays during the contact test
procedure are not exceeded by being operated for too long. We therefore advise that the time
between application and removal of the contact test is kept short.
3. Check with the engineer at the remote end that the Aided Channel 1 signal did change state
as expected. The Test Port Status cell should have responded as in the table below:
DDB No. 507 493
Monitor Bit 8 7 6 5 4 3 2 1
Contact Test OFF X X X X X X X 0
Contact Test Applied (ON) X X X X X X X 1
Test OFF X X X X X X X 0
14-48 P446/EN/TM/E
MiCOMho P446 14 Commissioning Instructions
4. Return the IED to service by setting COMMISSION TESTS > Test Mode to Disabled.
P446/EN/TM/E 14-49
14 Commissioning Instructions MiCOMho P446
11 ON-LOAD CHECKS
The objectives of the on-load checks are to:
Confirm the external wiring to the current and voltage inputs is correct
Measure the magnitude of capacitive current
Directionality check for distance elements
These checks can only be carried out if there are no restrictions preventing the energization of the
plant, and the other devices in the group have already been commissioned.
Remove all test leads and temporary shorting leads, and replace any external wiring that has been
removed to allow testing.
Warning: If any external wiring has been disconnected for the commissioning process,
replace it in accordance with the relevant external connection or scheme
diagram.
If the Local Values cell is set to ‘Secondary’, the values displayed should be equal to the applied
secondary voltage. The values should be within 1% of the applied secondary voltages. However, an
additional allowance must be made for the accuracy of the test equipment being used.
If the Local Values cell is set to ‘Primary’, the values displayed should be equal to the applied
secondary voltage multiplied the corresponding voltage transformer ratio set in the CT & VT RATIOS
column. The values should be within 1% of the expected values, plus an additional allowance for the
accuracy of the test equipment being used.
14-50 P446/EN/TM/E
MiCOMho P446 14 Commissioning Instructions
2. Check that the current transformer polarities are correct by measuring the phase angle
between the current and voltage, either against a phase meter already installed on site and
known to be correct or by determining the direction of power flow by contacting the system
control centre.
3. Ensure the current flowing in the neutral circuit of the current transformers is negligible.
4. Compare the values of the secondary phase currents and phase angle with the measured
values, which can be found in the MEASUREMENTS 1 column.
If the Local Values cell is set to ‘Secondary’, the values displayed should be equal to the applied
secondary voltage. The values should be within 1% of the applied secondary voltages. However, an
additional allowance must be made for the accuracy of the test equipment being used.
If the Local Values cell is set to ‘Primary’, the values displayed should be equal to the applied
secondary voltage multiplied the corresponding voltage transformer ratio set in the CT & VT RATIOS
column. The values should be within 1% of the expected values, plus an additional allowance for the
accuracy of the test equipment being used.
For load current flowing in the Forward direction (power export to the remote line end), the A
Phase Watts cell in the MEASUREMENTS 2 column should show positive power signing.
For load current flowing in the Reverse direction (power import from the remote line end), the A
Phase Watts cell in the MEASUREMENTS 2 column should show negative power signing.
Note: This check applies only for Measurement Modes 0 (default), and 2. This should be checked in the
MEASURE’T. SETUP column (Measurement Mode = 0 or 2). If measurement modes 1 or 3 are
used, the expected power flow signing would be opposite to that shown above.
In the event of any uncertainty, check the phase angle of the phase currents with respect to their
phase voltage.
P446/EN/TM/E 14-51
14 Commissioning Instructions MiCOMho P446
12 FINAL CHECKS
The tests are now complete.
In either case, compare the settings with the original application-specific setting records
Finally, ensure that all protection elements required have been set to Enabled in the
CONFIGURATION column
5. If the IED is in a new installation or the circuit breaker has just been maintained, the circuit
breaker maintenance and current counters should be zero. These counters can be reset
using the Reset All Values cell. If the required access level is not active, the device requests
a password so the setting change can be made.
6. If the menu language has been changed to allow accurate testing it should be restored to the
customer’s preferred language.
7. If a P991/MMLG test block is installed, remove the P992/MMLB test plug and replace the
cover so that the protection is put into service.
8. Ensure that all alarms and LEDs and communications statistics have been reset.
9. If applicable, replace the secondary front cover of the unit.
14-52 P446/EN/TM/E
MiCOMho P446 15 Maintenance & Troubleshooting
MAINTENANCE &
TROUBLESHOOTING
CHAPTER 15
P446/EN/TM/E 15-1
15 Maintenance & Troubleshooting MiCOMho P446
15-2 P446/EN/TM/E
MiCOMho P446 15 Maintenance & Troubleshooting
1 CHAPTER OVERVIEW
The Maintenance and Troubleshooting chapter provides details of how to maintain and troubleshoot
products based on the Px40 platform. It is important to heed the warning signs in this chapter, as not
do so may result injury or defective equipment.
Caution Before carrying out any work on the equipment you should be familiar with the
contents of the Safety Section or the Safety Guide SFTY/4LM and the ratings
on the equipment’s rating label.
The troubleshooting part of the chapter allows an error condition on the IED to be identified so that
appropriate corrective action can be taken.
If the IED develops a fault, it is usually possible to identify which module needs replacing. It is not
possible to perform an on-site repair to a faulty module.
If you return a faulty unit or module to the manufacturer or one of their approved service centres, you
should include a completed copy of the Repair or Modification Return Authorization (RMA) form.
This chapter consists of the following sections:
1 Chapter Overview
2 Maintenance
2.1 Maintenance Checks
2.1.1 Alarms
2.1.2 Opto-isolators
2.1.3 Output relays
2.1.4 Measurement accuracy
2.2 Replacing the unit
2.3 Repairing the unit
2.4 Removing the front panel
2.5 Replacing PCBs
2.5.1 Replacing the main processor board
2.5.2 Replacement of communications boards
2.5.3 Replacement of the input module
2.5.4 Replacement of the power supply board
2.5.5 Replacement of the I/O boards
2.6 Recalibration
2.7 Changing the battery
2.7.1 Post Modification Tests
2.7.2 Battery Disposal
2.8 Cleaning
3 Troubleshooting
3.1 Problem Identification
3.2 Power-up Errors
3.3 Error Message or Code on Power-up
3.4 Out of Service LED on at power-up
3.5 Error Code during Operation
3.6 Mal-operation during Testing
3.6.1 Failure of Output Contacts
3.6.2 Failure of Opto-inputs
P446/EN/TM/E 15-3
15 Maintenance & Troubleshooting MiCOMho P446
15-4 P446/EN/TM/E
MiCOMho P446 15 Maintenance & Troubleshooting
2 MAINTENANCE
Although some functionality checks can be performed from a remote location, these are predominantly
restricted to checking that the unit is measuring the applied currents and voltages accurately, and
checking the circuit breaker maintenance counters. For this reason, maintenance checks should also
be performed locally at the substation.
Caution Before carrying out any work on the equipment you should be
familiar with the contents of the Safety Section or the Safety Guide
SFTY/4LM and the ratings on the equipment’s rating label.
2.1.1 Alarms
First check the alarm status LED to see if any alarm conditions exist. If so, press the Read key
repeatedly to step through the alarms.
After dealing with any problems, clear the alarms. This will clear the relevant LEDs.
2.1.2 Opto-isolators
Check the opto-inputs by repeating the commissioning test detailed in the Commissioning chapter.
P446/EN/TM/E 15-5
15 Maintenance & Troubleshooting MiCOMho P446
Caution Replacing PCBs requires the correct on-site environment (clean and dry) as
well as suitably trained personnel.
Caution If the repair is not performed by an approved service centre, the warranty will
be invalidated.
Caution Before carrying out any work on the equipment, you should be familiar with
the contents of the Safety Information section of this guide or the Safety Guide
SFTY/4LM, as well as the ratings on the equipment’s rating label. This should
ensure that no damage is caused by incorrect handling of the electronic
components. .
Warning Before working at the rear of the unit, isolate all voltage and current supplying
it.
Note: The MiCOM ALSTOM products have integral current transformer shorting switches which will close,
for safety reasons, when the heavy duty and/or MiDOS terminal block is removed
1. Carefully disconnect the cables not connected to the terminal blocks (e.g. IRIG-B, fibre optic
cables, earth), as appropriate, from the rear of the unit.
2. Remove the terminal block screws using a magnetic bladed screwdriver to minimize the risk of
losing the screws or leaving them in the terminal block.
15-6 P446/EN/TM/E
MiCOMho P446 15 Maintenance & Troubleshooting
Note: There are four types of terminal block: RTD/CLIO input, heavy duty, medium duty, and MiDOS. The
terminal blocks are fastened to the rear panel using slotted screws on the RTD/CLIO input blocks
and crosshead screws on the heavy and medium duty blocks. See Figure 1.
3. Without exerting excessive force or damaging the scheme wiring, pull the terminal blocks
away from their internal connectors.
4. Remove the terminal block screws that fasten the unit to the panel and rack. These are the
screws with the larger diameter heads that are accessible when the access covers are fitted
and open.
If the top and bottom access covers have been removed, some more
screws with smaller diameter heads are made accessible. Do NOT remove
these screws, as they secure the front panel to the unit.
5. Withdraw the unit from the panel and rack. Take care, as the unit will be heavy due to the
internal transformers.
6. To reinstall the unit, follow the above instructions in reverse, ensuring that each terminal block
is relocated in the correct position and the chassis ground, IRIG-B and fibre optic connections
are replaced. The terminal blocks are labelled alphabetically with ‘A’ on the left hand side
when viewed from the rear.
Once the unit has been reinstalled, it should be re-commissioned as set out in the Commissioning
chapter.
HD Terminal Block MD Terminal Block Midos Terminal Block RTD/CLIO Terminal Block
P4522ENa
P446/EN/TM/E 15-7
15 Maintenance & Troubleshooting MiCOMho P446
Replacement of printed circuit boards and other internal components must be undertaken by Alstom
Grid-approved Service Centres. Failure to obtain the authorization of Alstom Grid after-sales
engineers prior to commencing work may invalidate the product warranty.
We recommend that you entrust any repairs to Alstom Grid Automation Support teams, which are
available world-wide.
Warning Before removing the front panel to replace a PCB, you must first remove the
auxiliary power supply and wait 5 seconds for the internal capacitors to
discharge. You should also isolate voltage and current transformer
connections and trip circuit.
Caution Before removing the front panel, you should be familiar with the contents of
the Safety Information section of this guide or the Safety Guide SFTY/4LM, as
well as the ratings on the equipment’s rating label.
1. Open the top and bottom access covers. You must open the hinged access covers by more
than 90° before they can be removed.
2. If fitted, remove the transparent secondary front cover.
3. Apply outward pressure to the middle of the access covers to bow them and disengage the
hinge lug, so the access cover can be removed. The screws that fasten the front panel to the
case are now accessible.
4. Undo and remove the screws. The 40TE case has four crosshead screws fastening the front
panel to the case, one in each corner, in recessed holes. The 60TE/80TE cases have an
additional two screws, one midway along each of the top and bottom edges of the front plate.
Do not remove the screws with the larger diameter heads which are accessible
when the access covers are fitted and open. These screws hold the relay in its
mounting (panel or cubicle).
5. When the screws have been removed, pull the complete front panel forward to separate it
from the metal case. The front panel is connected to the rest of the circuitry by a 64-way
ribbon cable.
The internal circuitry is now exposed and is not protected against electrostatic
discharge and dust ingress. Therefore ESD precautions and clean working
conditions must be maintained at all times.
6. The ribbon cable is fastened to the front panel using an IDC connector; a socket on the cable
and a plug with locking latches on the front panel. Gently push the two locking latches
outwards which eject the connector socket slightly. Remove the socket from the plug to
disconnect the front panel.
15-8 P446/EN/TM/E
MiCOMho P446 15 Maintenance & Troubleshooting
4. Remove the PCB in accordance with the board-specific instructions detailed later in this
section.
Note: To ensure compatibility, always replace a faulty PCB with one of an identical part number.
Note: After replacing the main processor board, all the settings required for the application need to be re-
entered. This may be done either manually or by downloading a settings file.
P446/EN/TM/E 15-9
15 Maintenance & Troubleshooting MiCOMho P446
P2020ENA
15-10 P446/EN/TM/E
MiCOMho P446 15 Maintenance & Troubleshooting
Note: If individual boards within the input module are replaced, recalibration will be necessary. We
therefore recommend replacement of the complete module to avoid on-site recalibration.
Caution Before removing the front panel, you should be familiar with the contents of
the Safety Information section of this guide or the Safety Guide SFTY/4LM, as
well as the ratings on the equipment’s rating label.
The power supply board is fastened to an output relay board with push fit nylon pillars. This doubled-
up board is secured on the extreme left hand side, looking from the front of the unit.
P446/EN/TM/E 15-11
15 Maintenance & Troubleshooting MiCOMho P446
2.6 Recalibration
Recalibration is not needed when a PCB is replaced, unless it is one of the boards in the input
module. If any of the boards in the input module is replaced, the unit must be recalibrated.
Although recalibration is needed when a board inside the input module is replaced, it is not needed if
the input module is replaced in its entirety.
Although it is possible to carry out recalibration on site, this requires special test equipment and
software. We therefore recommend that the work be carried out by the manufacturer, or entrusted to
an approved service centre.
15-12 P446/EN/TM/E
MiCOMho P446 15 Maintenance & Troubleshooting
Only use a type ½AA Lithium battery with a nominal voltage of 3.6 V and safety
approvals such as UL (Underwriters Laboratory), CSA (Canadian Standards
Association) or VDE (Vereinigung Deutscher Elektrizitätswerke).
5. Ensure that the battery is held securely in its socket and that the battery terminals make good
contact with the socket terminals.
6. Close the bottom access cover.
Note: Events, disturbance and maintenance records will be lost if the battery is replaced whilst the IED is
de-energized.
2.8 Cleaning
Warning Before cleaning the IED, ensure that all AC and DC supplies and current and
transformer connections are isolated, to prevent any chance of an electric
shock while cleaning.
Only clean the equipment with a lint-free cloth dampened with clean water. Do not use detergents,
solvents or abrasive cleaners as they may damage the product's surfaces and leave a conductive
residue.
P446/EN/TM/E 15-13
15 Maintenance & Troubleshooting MiCOMho P446
3 TROUBLESHOOTING
15-14 P446/EN/TM/E
MiCOMho P446 15 Maintenance & Troubleshooting
P446/EN/TM/E 15-15
15 Maintenance & Troubleshooting MiCOMho P446
15-16 P446/EN/TM/E
MiCOMho P446 15 Maintenance & Troubleshooting
1. Select the nominal battery voltage for all opto-inputs by selecting one of the five standard
ratings in the Global Nominal V cell.
2. Select 'Custom' to set each opto-input individually to a nominal voltage.
3. Using a voltmeter, check that the voltage on its input terminals is greater than the minimum
pick-up level (See the Technical Specifications chapter for opto pick-up levels).
If the signal is correctly applied, this indicates failure of an opto-input, which may be situated on
standalone opto-input board, or on an opto-input board that is part of the input module. Separate opto-
input boards can simply be replaced. If, however, the faulty opto-input board is part of the input
module, the complete input module should be replaced. This is because the analogue input module
cannot be individually replaced without dismantling the module and recalibration of the IED.
1. Compare the displayed measured values with the actual magnitudes at the terminals.
2. Check the correct terminals are used (in particular the dual-rated CT inputs)
3. Check the CT and VT ratios set on the relay are correct.
4. Check the phase displacement to confirm the inputs are correctly connected
P446/EN/TM/E 15-17
15 Maintenance & Troubleshooting MiCOMho P446
Incompatible IED
This occurs if the IEDs trying to communicate with each other are of incompatible types.
Comms changed
This indicates that the Comms Mode setting has been changed without a subsequent power off and
on.
The IED address is not valid (this address is always 1 for the front port)
Password in not valid
Communication set-up (COM port, Baud rate, or Framing) is not correct
Transaction values are not suitable for the IED or the type of connection
The connection cable is not wired correctly or broken. See MiCOM S1 Studio connection
configurations
The option switches on any KITZ101/102 in use may be incorrectly set
15-18 P446/EN/TM/E
MiCOMho P446 15 Maintenance & Troubleshooting
Sometimes a gate type does not appear as expected. For example, a single-input AND gate in the
original scheme appears as an OR gate when uploaded. Programmable gates with an inputs-to-
trigger value of 1 also appear as OR gates.
P446/EN/TM/E 15-19
15 Maintenance & Troubleshooting MiCOMho P446
If required, an acceptance of the quote must be delivered before going to the next stage.
15-20 P446/EN/TM/E
MiCOMho P446 16 Technical Specifications
TECHNICAL SPECIFICATIONS
CHAPTER 16
P446/EN/TM/E 16-1
16 Technical Specifications MiCOMho P446
16-2 P446/EN/TM/E
MiCOMho P446 16 Technical Specifications
1 CHAPTER OVERVIEW
The Technical Specifications chapter consists of the following sections:
1 Chapter Overview
2 Interfaces
2.1 Front Serial Port
2.2 Download/Monitor port
2.3 Rear Serial Port
2.4 Optional Second Rear Serial Port SK4
2.5 Optional Second Rear Serial Port SK5
2.6 Optional Rear Serial Fiber Port
2.7 Optional IRIG-B (Demodulated)
2.8 Optional IRIG-B (Modulated)
2.9 Rear Ethernet port (copper)
2.10 Rear Ethernet port (fiber including redundancy option)
2.11 InterMiCOM fibre Interface
3 Protection Functions
3.1 Distance Protection
3.2 InterMiCOM64 Fibre optic Teleprotection
3.3 Out of Step
3.4 Slow Power Swing Blocking
3.5 Three Phase Overcurrent Protection
3.6 Earth Fault Protection
3.7 Negative Sequence Overcurrent
3.8 Undervoltage
3.9 Overvoltage
3.10 Neutral Displacement / Residual Overvoltage
3.11 Circuit Breaker Fail and Undercurrent
3.12 Broken Conductor Logic
3.13 Thermal Overload
3.14 Voltage Transformer Supervision (VTS)
3.15 Current Transformer Supervision
3.16 CB State Monitoring and Condition Monitoring
3.17 Programmable Scheme Logic
3.18 Auto-reclose and Check Synchronism
5 Standards Compliance
5.1 EMC Compliance: 2004/108/EC
5.2 Product Safety: 2006/95/EC:
5.3 R&TTE Compliance
P446/EN/TM/E 16-3
16 Technical Specifications MiCOMho P446
6 Mechanical Specifications
6.1 Physical Parameters
6.2 Enclosure Protection: IEC 60529:1992
6.3 Mechanical Robustness
7 Terminals
7.1 AC Current and Voltage Measuring Inputs
7.2 General Input/Output Terminals
7.3 Case Protective Ground Connection
8 Ratings
8.1 AC Measuring Inputs
8.2 AC Current
8.3 AC Voltage
8.4 Auxiliary voltage (Vx)
8.5 Field Output Voltage
8.6 Nominal burden
8.7 Power-up
8.8 Power Supply Interruption
8.9 Output Contacts
8.10 High Break Contacts (Optional)
8.11 Watchdog Contacts
8.12 Fiber defect contacts (watchdog relay – redundant Ethernet version)
8.13 Opto-isolated digital inputs
9 Environmental Conditions
9.1 Ambient Temperature Range
9.2 Ambient Humidity Range
9.3 Corrosive Environments (for relays with harsh environment coating of PCBs)
10 Type Tests
10.1 Insulation
10.2 Creepage Distances and Clearances
10.3 High Voltage (Dielectric) Withstand
10.4 Impulse Voltage Withstand Test
16-4 P446/EN/TM/E
MiCOMho P446 16 Technical Specifications
P446/EN/TM/E 16-5
16 Technical Specifications MiCOMho P446
2 INTERFACES
16-6 P446/EN/TM/E
MiCOMho P446 16 Technical Specifications
P446/EN/TM/E 16-7
16 Technical Specifications MiCOMho P446
16-8 P446/EN/TM/E
MiCOMho P446 16 Technical Specifications
Optical budget
850 nm 1300 nm 1300 nm 1550 nm
Multi mode Multi mode Single mode Single mode
Min. transmit output level (average power) -19.8 dBm -6 dBm -6 dBm -6 dBm
Receiver sensitivity
-25.4 dBm -49 dBm -49 dBm -49 dBm
(average power)
Optical budget 5.6 dB 43.0 dB 43.0 dB 43.0 dB
Less safety margin (3 dB) 2.6 dB 40.0 dB 40.0 dB 40.0 dB
Typical cable loss 2.6 dB/km 0.8 dB/km 0.4 dB/km 0.3 dB/km
Max. transmission distance 1 km 50.0 km 100.0 km 130 km
P446/EN/TM/E 16-9
16 Technical Specifications MiCOMho P446
3 PROTECTION FUNCTIONS
Accuracy
Stability angle +/- 2° or 4%, whichever is greater
Current and voltage starters +/- 2%
Operating time with default settings, back-to-back
propagation delay included
50 Hz, 1 p.u. ≤ relay current < 2 p.u. <45 ms
60 Hz, 1 p.u. ≤ relay current < 2 p.u. <40 ms
50 Hz, relay current ≥ 2 p.u. <35 ms
60 Hz, relay current ≥ 2 p.u. <30 ms
Repeatability +/- 2.5%
40
Operating time versus reach percentage, for faults Performance:
Subcycle up
close to line angle. 30 to 75% Reach
50 Hz, SIR = 5 20
10
All quoted operating times include closure of the
trip output contact
0 50% 70% 80% 90%
Operating time for resistive faults > 20% inside the 50 Hz, up to SIR = 30 < 30 ms
characteristic 60 Hz, up to SIR = 30 < 25 ms
Accuracy
+/- 5% for on-angle fault (on the set line angle)
+/- 10% for off-angle fault
Characteristic shape, up to SIR = 30
Example: For a 70 degree set line angle, injection testing
at 40 degrees would be referred to as “off-angle”.
Zone time delay deviations +/- 20 ms or 2%, whichever is greater
16-10 P446/EN/TM/E
MiCOMho P446 16 Technical Specifications
P446/EN/TM/E 16-11
16 Technical Specifications MiCOMho P446
Earth Fault
DT reset +/- 2% or 50 ms, whichever is greater
Repeatability +/- 5%
Wattmetric SEF
Pick-up P = 0 W ISEF > +/-5% or 5 mA
Pick-up P > 0 W P > +/-5%
Drop-off P = 0 W 0.95 x ISEF> +/- 5% or 5 mA
Drop-off P > 0 W 0.9 x P> +/- 5% or 5 mA
Boundary accuracy +/-5% with hysteresis < 1°
Repeatability +/- 1%
Polarizing Quantities
Pick-up VN> and V2> level detectors +/- 10%
Resetting ratio VN> and V2> level detectors 0.9
Pick-up I2> level detector +/- 10%
Resetting ratio I2> level detectors 0.9
16-12 P446/EN/TM/E
MiCOMho P446 16 Technical Specifications
Accuracy
Directional boundary accuracy +/- 2% with hysteresis < 1°
Repeatability +/- 1%
3.8 Undervoltage
Accuracy
DT Pick-up Setting +/- 5%
IDMT Pick-up 0.98 x Setting +/- 2%
Drop-off 1.02 x Setting +/-2%
DT operation +/- 40 ms or 2%, whichever is greater
Reset < 35 ms
IDMT shape +/- 40 ms or 2%, whichever is greater
Repeatability +/- 1%
3.9 Overvoltage
Accuracy
DT Pick-up Setting +/- 1%
IDMT Pick-up 1.02 x Setting +/- 2%
Drop-off 0.98 x Setting +/-2%
DT operation +/- 40 ms or 2%, whichever is greater
Reset < 75 ms
IDMT shape +/- 40 ms or 2%, whichever is greater
Repeatability +/- 1%
P446/EN/TM/E 16-13
16 Technical Specifications MiCOMho P446
16-14 P446/EN/TM/E
MiCOMho P446 16 Technical Specifications
P446/EN/TM/E 16-15
16 Technical Specifications MiCOMho P446
4.1 General
General Measurement Accuracy
General measurement accuracy Typically +/- 1%, but +/- 0.5% between 0.2 - 2 In/Vn
Current 0.05 to 3 In +/- 1.0% of reading
Voltage 0.05 to 2 Vn +/- 1.0% of reading
0.2 to 2 Vn and 0.05 to 3 In +/- 5.0% of reading at unity power
Power (W)
factor
Reactive power (Vars) 0.2 to 2 Vn to 3 In +/- 5.0% of reading at zero power factor
Apparent power (VA) 0.2 to 2 Vn 0.05 to 3 In +/- 5.0% of reading
Energy (Wh) 0.2 to 2 Vn 0.2 to 3 In +/- 5.0% of reading at zero power factor
Phase 0° to 360° +/- 0.5%
Frequency 45 to 65 Hz +/- 0.025 Hz
16-16 P446/EN/TM/E
MiCOMho P446 16 Technical Specifications
Accuracy
Reset time < 30 ms
Undercurrent Accuracy
Pick-up +/- 10% or 25 mA, whichever is greater
Operating time < 20 ms
Reset time < 25 ms
P446/EN/TM/E 16-17
16 Technical Specifications MiCOMho P446
5 STANDARDS COMPLIANCE
16-18 P446/EN/TM/E
MiCOMho P446 16 Technical Specifications
6 MECHANICAL SPECIFICATIONS
Vibration and Drop Release Tests Vibration tests in 3 orientations, vibratory movement 7 Hz,
amplitude 5.3 mm, acceleration 1.05g
P446/EN/TM/E 16-19
16 Technical Specifications MiCOMho P446
7 TERMINALS
16-20 P446/EN/TM/E
MiCOMho P446 16 Technical Specifications
8 RATINGS
8.2 AC Current
AC Current
Nominal current (In) 1A and 5A dual rated*
Nominal burden per phase < 0.2 VA at In
Continuous: 4*In
10 s: 30 x In
AC current thermal withstand
1 s: 100 x In
Linear to 64 x In (non-offset ac current)
Note: 1A and 5A inputs use different transformer tap connections, check correct terminals are wired.
8.3 AC Voltage
AC Voltage
Nominal voltage 100 to 120 V phase-phase
Nominal burden per phase < 0.02 VA at Vn
Thermal withstand Continuous: 2*Vn, 10 s: 2.6*Vn
P446/EN/TM/E 16-21
16 Technical Specifications MiCOMho P446
8.7 Power-up
Power-up
Time to power up < 11 s
Mounting: Front panel, Type: ½ AA, 3.6 V Lithium Thionyl Chloride
Battery Backup
Battery
Type: ½ AA, 3.6 V Lithium Thionyl Chloride Battery (SAFT advanced:
Battery Type
LS14250)
Battery Life >10 years (based on 90% energization time)
16-22 P446/EN/TM/E
MiCOMho P446 16 Technical Specifications
P446/EN/TM/E 16-23
16 Technical Specifications MiCOMho P446
Note: Typical for repetitive shots with 2 minutes idle for thermal dissipation
16-24 P446/EN/TM/E
MiCOMho P446 16 Technical Specifications
Note: Opto-inputs operated with filtering removed are more susceptible to EM interference and
precautions should be taken to minimize pickup on the external wiring.
P446/EN/TM/E 16-25
16 Technical Specifications MiCOMho P446
9 ENVIRONMENTAL CONDITIONS
9.3 Corrosive Environments (for relays with harsh environment coating of PCBs)
Corrosive Environments
Compliance IEC 60068-2-60: 1995, Part 2, Test Ke, Method (class) 3
Industrial corrosive environment/poor environmental 21 days at 75% relative humidity and +30oC
control, mixed gas flow test exposure to elevated concentrations of H2S,
(100 ppb) NO2, (200 ppb) Cl2 (20 ppb).
Tested as per
IEC 60068-2-52 Salt mist (7 days)
IEC 60068-2-43 H2S (21 days), 15 ppm
IEC 60068-2-42 SO2 (21 days), 25 ppm
16-26 P446/EN/TM/E
MiCOMho P446 16 Technical Specifications
10 TYPE TESTS
10.1 Insulation
Insulation
Compliance IEC 60255-27: 2005
Insulation resistance > 100 M at 500 V dc (Using only electronic/brushless insulation tester)
Exceptions: EIA(RS)232 ports and EIA(RS485) ports and normally-open output contacts
P446/EN/TM/E 16-27
16 Technical Specifications MiCOMho P446
16-28 P446/EN/TM/E
MiCOMho P446 16 Technical Specifications
P446/EN/TM/E 16-29
16 Technical Specifications MiCOMho P446
16-30 P446/EN/TM/E
MiCOMho P446 17 Symbols and Glossary
CHAPTER 17
P446/EN/TM/E 17-1
17 Symbols and Glossary MiCOMho P446
17-2 P446/EN/TM/E
MiCOMho P446 17 Symbols and Glossary
1 CHAPTER OVERVIEW
This chapter consists of the following sections:
1 Chapter Overview
2 Acronyms and Abbreviations
3 Company Proprietary Terms
4 ANSI and IEC61850 Terms
5 Units for Digital Communications
6 American vs British English Terminology
7 Logic Symbols and terms
8 Logic Timers
9 Logic Gates
P446/EN/TM/E 17-3
17 Symbols and Glossary MiCOMho P446
17-4 P446/EN/TM/E
MiCOMho P446 17 Symbols and Glossary
Term Description
CS Check Synchronism.
CSV Comma Separated Values (a file format for database information)
CT Current Transformer
CTRL. Control
CTS Current Transformer Supervision: To detect CT input failure.
CTx Channel Transmit: Typically used to indicate a teleprotection signal send.
CU Communication Unit
CVT Capacitor-coupled Voltage Transformer - equivalent to terminology CCVT.
DAU Data Acquisition Unit
DC Data Concentrator
DC / dc Direct Current
DCC An Omicron compatible format
Digital Data Bus within the programmable scheme logic: A logic point that has a zero or 1
DDB
status. DDB signals are mapped in logic to customize the relay’s operation.
DDR Dynamic Disturbance Recorder
DEF Directional earth fault protection: A directionalized ground fault aided scheme.
DG Distributed Generation
DHCP Dynamic Host Configuration Protocol
DHP Dual Homing Protocol
Diff Differential protection.
DIN Deutsches Institut für Normung (German standards body)
Dist Distance protection.
DITA Darwinian Information Typing Architecture
Dead-Line Dead-Bus: In system synchronism check, indication that both the line and bus
DLDB
are de-energized.
Dead-Line Live-Bus: In system synchronism check, indication that the line is de-energized
DLLB
whilst the bus is energized.
DLR Dynamic Line Rating
DLY / Dly Time Delay
DMT Definite Minimum Time
DNP Distributed Network Protocol
DPWS Device Profile for Web Services
DST Daylight Saving Time
Definite Time: in the context of protection elements:
DT An element which always responds with the same constant time delay on operation.
Abbreviation of “Dead Time” in the context of auto-reclose:
DTD Document Type Definition
DTOC Definite Time Overcurrent
DTS Date and Time Stamp
EF or E/F Earth Fault (Directly equivalent to Ground Fault)
EIA Electronic Industries Alliance
ELR Environmental Lapse Rate
ER Engineering Recommendation
FCB Frame Count Bit
FFT Fast Fourier Transform
FIR Finite Impulse Response
P446/EN/TM/E 17-5
17 Symbols and Glossary MiCOMho P446
Term Description
FLC Full load current: The nominal rated current for the circuit.
FLT / Flt Fault - typically used to indicate faulted phase selection.
Fn or FN Function
FPGA Field Programmable Gate Array
FPS Frames Per Second
FTP File Transfer Protocol
FWD, Fwd or Fwd. Indicates an element responding to a flow in the “Forward” direction
GIF Graphic Interchange Format – a file format for a computer graphic
GND / Gnd Ground: used in distance settings to identify settings that relate to ground (earth) faults.
GOOSE Generic Object Oriented Substation Event
GPS Global Positioning System
GRP / Grp Group. Typically an alternative setting group.
GSE General Substation Event
GSSE Generic Substation Status Event
GUI Graphical User Interface
HMI Human Machine Interface
HSR High-availability Seamless Ring
HTML Hypertext Markup Language
I Current
I/O Input/Output
I/P Input
ICAO International Civil Aviation Organization
ID Identifier or Identification. Often a label used to track a software version installed.
Inverse Definite Minimum Time. A characteristic whose trip time depends on the measured
IDMT
input (e.g. current) according to an inverse-time curve.
IEC International Electro-technical Commission
IED Intelligent Electronic Device
IEEE Institute of Electrical and Electronics Engineers
IIR Infinite Impulse Response
Inh An Inhibit signal
Inst An element with Instantaneous operation: i.e. having no deliberate time delay.
IP Internet Protocol
IRIG InterRange Instrumentation Group
ISA International Standard Atmosphere
ISA Instrumentation Systems and Automation Society
ISO International Standards Organization
JPEF Joint Photographic Experts Group – a file format for a computer graphic
L Live
LAN Local Area Network
LCD Liquid Crystal Display: The front-panel text display on the relay.
LD Level Detector: An element responding to a current or voltage below its set threshold.
LDOV Level Detector for Overvoltage
LDUV Level Detector for Undervoltage
LED Light Emitting Diode: Red or green indicator on the front-panel.
17-6 P446/EN/TM/E
MiCOMho P446 17 Symbols and Glossary
Term Description
Live-Line Dead-Bus : In system synchronism check, indication that the line is energized
LLDB
whilst the bus is de-energized.
Ln Natural logarithm
LN Logical Node
LoL A Loss of Load scheme, providing a fast distance trip without needing a signaling channel.
LPDU Link Protocol Data Unit
LPHD Logical Physical Device
MC MultiCast
MCB Miniature Circuit Breaker
MCL MiCOM Configuration Language
MICS Model Implementation Conformance Statement
MMF Magneto-Motive Force
MMS Manufacturing Message Specification
MRP Media Redundancy Protocol
MU Merging Unit
MV Measured Value
N Neutral
N/A Not Applicable
N/C A Normally Closed or “break” contact: Often called a “form B” contact.
N/O A Normally Open or “make” contact: Often called a “form A” contact.
NERC North American Reliability Corporation
NIST National Institute of Standards and Technology
NPS Negative Phase Sequence
NVD Neutral voltage displacement: Equivalent to residual overvoltage protection.
NXT Abbreviation of “Next”: In connection with hotkey menu navigation.
O/C Overcurrent
O/P Output
Opto An Optically coupled logic input. Alternative terminology: binary input.
OSI Open Systems Interconnection
PCB Printed Circuit Board
PCT Protective Conductor Terminal (Ground)
PDC Phasor Data Concentrator
Ph Phase - used in distance settings to identify settings that relate to phase-phase faults.
PICS Protocol Implementation Conformance Statement
PMU Phasor Measurement Unit
PNG Portable Network Graphics – a file format for a computer graphic
Pol Polarize - typically the polarizing voltage used in making directional decisions.
POR Permissive Over Reach
POST Power On Self Test
POTT Permissive Over Reach Transfer Tripping
PRP Parallel Redundancy Protocol
PSB Power Swing Blocking, to detect power swing/out of step functions (ANSI 78).
Programmable Scheme Logic: The part of the relay’s logic configuration that can be
PSL
modified by the user, using the graphical editor within S1 Studio software.
PT Power Transformer
P446/EN/TM/E 17-7
17 Symbols and Glossary MiCOMho P446
Term Description
PTP Precision Time Protocol
PUR A Permissive UnderReaching transfer trip scheme (alternative terminology: PUTT).
Q Quantity defined as per unit value
R Resistance
RBAC Role Based Access Control
RCA Relay Characteristic Angle - The center of the directional characteristic.
REB Redundant Ethernet Board
REF Restricted Earth Fault
Rev. Indicates an element responding to a flow in the “reverse” direction
Root mean square. The equivalent a.c. current: Taking into account the fundamental, plus
RMS / rms
the equivalent heating effect of any harmonics.
RP Rear Port: The communication ports on the rear of the IED
RS232 A common serial communications standard defined by the EIA
RS485 A common serial communications standard defined by the EIA (multi-drop)
RST or Rst Reset generally used in the context of reset functions in circuit breaker control.
RSTP Rapid Spanning Tree Protocol
RTU Remote Terminal Unit
Rx Receive: Typically used to indicate a communication transmit line/pin.
SBS Straight Binary Second
SC Synch-Check or system Synchronism Check.
SCADA Supervisory Control and Data Acquisition
SCL Substation Configuration Language
SCU Substation Control Unit
SEF Sensitive Earth Fault
SHP Self Healing Protocol
SIR Source Impedance Ratio
SMV Sampled Measured Values
SNTP Simple Network Time Protocol
SOA Service Oriented Architecture
SOAP Simple Object Access Protocol
SOC Second of Century
SOTF Switch on to Fault protection. Modified protection on manual closure of the circuit breaker.
SP Single pole.
SPAR Single pole auto-reclose.
SPC Single Point Controllable
SPDT Single Pole Dead Time. The dead time used in single pole auto-reclose cycles.
SPS Single Point Status
SQRT Square Root
STP Spanning Tree Protocol
SV Sampled Values
SVM Sampled Value Model
TAF Turbine Abnormal Frequency
TCP Transmission Control Protocol
TCS Trip Circuit Supervision
TD Time Dial. The time dial multiplier setting: Applied to inverse-time curves (ANSI/IEEE).
17-8 P446/EN/TM/E
MiCOMho P446 17 Symbols and Glossary
Term Description
TE Unit for case measurements: One inch = 5TE units
THD Total Harmonic Distortion
TICS Technical Issues Conformance Statement
TIFF Tagged Image File Format – a file format for a computer graphic
TLS Transport Layer Security protocol
TMS Time Multiplier Setting: Applied to inverse-time curves (IEC)
TOC Trip On Close (“line check”) protection. Offers SOTF and TOR functionality.
TOR Trip On Reclose protection. Modified protection on autoreclosure of the circuit breaker.
TP Two-Part
TUC Timed UnderCurrent
TVE Total Vector Error
Tx Transmit
UDP User Datagram Protocol
UPCT User Programmable Curve Tool
USB Universal Serial bus
UTC Universal Time Coordinated
V Voltage
VA Phase A voltage: Sometimes L1, or red phase
VB Phase B voltage: Sometimes L2, or yellow phase
VC Phase C voltage: Sometimes L3, or blue phase
VDR Voltage Dependant Resistor
VT Voltage Transformer
VTS Voltage Transformer Supervision: To detect VT input failure.
WAN Wide Area Network
XML Extensible Markup Language
XSD XML Schema Definition
Z S / ZL Source to Line Impedance Ratio
Table 1: Acronyms and abbreviations
P446/EN/TM/E 17-9
17 Symbols and Glossary MiCOMho P446
17-10 P446/EN/TM/E
MiCOMho P446 17 Symbols and Glossary
P446/EN/TM/E 17-11
17 Symbols and Glossary MiCOMho P446
17-12 P446/EN/TM/E
MiCOMho P446 17 Symbols and Glossary
P446/EN/TM/E 17-13
17 Symbols and Glossary MiCOMho P446
17-14 P446/EN/TM/E
MiCOMho P446 17 Symbols and Glossary
τ “Tau”: Used to indicate a time constant, often associated with thermal characteristics.
Φ Flux rad
< Less than: Used to indicate an “under” threshold, such as undercurrent (current dropout).
> Greater than: Used to indicate an “over” threshold, such as overcurrent (current overload)
1 Logical “OR”: Used in logic diagrams to show an OR-gate function.
C Capacitance A
F>1 First stage of overfrequency protection: Could be labeled 81-O in ANSI terminology. Hz
I’f Maximum internal secondary fault current (may also be expressed as a multiple of In) A
I>1 First stage of phase overcurrent protection: Could be labeled 51-1 in ANSI terminology. A
I>2 Second stage of phase overcurrent protection: Could be labeled 51-2 in ANSI terminology. A
I>3 Third stage of phase overcurrent protection: Could be labeled 51-3 in ANSI terminology. A
I>4 Fourth stage of phase overcurrent protection: Could be labeled 51-4 in ANSI terminology. A
Earth fault current setting
I0 A
Zero sequence current: Equals one third of the measured neutral/residual current.
I1 Positive sequence current. A
P446/EN/TM/E 17-15
17 Symbols and Glossary MiCOMho P446
IB Phase B current: Might be phase L2, yellow phase.. or other, in customer terminology. A
IC Phase C current: Might be phase L3, blue phase.. or other, in customer terminology. A
Idiff Current setting of biased differential element A
If max
Maximum secondary contribution from a feeder to an internal fault A
int
If Z1 Maximum secondary phase fault current at Zone 1 reach point A
Ife Maximum secondary through fault earth current A
Ifn Maximum prospective secondary earth fault current or 31 x I> setting (whichever is lowest) A
Ifp Maximum prospective secondary phase fault current or 31 x I> setting (whichever is lowest) A
Im Mutual current A
IM64 InterMiCOM64.
IN Neutral current, or residual current: This results from an internal summation of the three measured phase currents. A
IN>1 First stage of ground overcurrent protection: Could be labeled 51N-1 in ANSI terminology. A
IN>2 Second stage of ground overcurrent protection: Could be labeled 51N-2 in ANSI terminology. A
Iref Reference current of P63x calculated from the reference power and nominal voltage A
IRm2 Second knee-point bias current threshold setting of P63x biased differential element A
K Dimensioning factor
km Distance in kilometers
17-16 P446/EN/TM/E
MiCOMho P446 17 Symbols and Glossary
L Inductance A
m1 Lower bias slope setting of P63x biased differential element None
mi Distance in miles.
PN> Wattmetric earth fault protection: Calculated using residual voltage and current quantities.
R Resistance Ω
R Gnd. A distance zone resistive reach setting: Used for ground (earth) faults.
t A time delay.
t’ Duration of first current flow during auto-reclose cycle s
V<1 First stage of undervoltage protection: Could be labeled 27-1 in ANSI terminology. V
V<2 Second stage of undervoltage protection: Could be labeled 27-2 in ANSI terminology. V
P446/EN/TM/E 17-17
17 Symbols and Glossary MiCOMho P446
V>2 Second stage of overvoltage protection: Could be labeled 59-2 in ANSI terminology. V
V0 Zero sequence voltage: Equals one third of the measured neutral/residual voltage. V
V1 Positive sequence voltage. V
VA Phase A voltage: Might be phase L1, red phase.. or other, in customer terminology. V
VB Phase B voltage: Might be phase L2, yellow phase.. or other, in customer terminology. V
VC Phase C voltage: Might be phase L3, blue phase.. or other, in customer terminology. V
Vf Theoretical maximum voltage produced if CT saturation did not occur V
Vn Nominal voltage V
Vn The rated nominal voltage of the relay: To match the line VT input. V
Vx An auxiliary supply voltage: Typically the substation battery voltage used to power the relay. V
X Reactance None
X/R Primary system reactance/resistance ratio None
Y Admittance p.u.
Z Impedance p.u.
Z0 Zero sequence impedance.
Z1X Reach-stepped Zone 1X, for zone extension schemes used with auto-reclosure.
Ψr Remanent flux Wb
17-18 P446/EN/TM/E
MiCOMho P446 17 Symbols and Glossary
P446/EN/TM/E 17-19
17 Symbols and Glossary MiCOMho P446
8 LOGIC TIMERS
Logic
Explanation Time chart
symbols
INPUT
t
t OUTPUT
Delay on pick-up timer, t
0 INPUT
t
OUTPUT
INPUT
OUTPUT
0 t
Delay on drop-off timer, t INPUT
t
OUTPUT
t
INPUT
t1 t2
t1 OUTPUT
Delay on pick-up/drop-off timer
t2 INPUT
t1 t2
OUTPUT
INPUT
t
OUTPUT
Pulse timer
t
INPUT
t
OUTPUT
INPUT
Pulse pick-up falling edge t
t OUTPUT
INPUT
Pulse pick-up raising edge t
t OUTPUT
17-20 P446/EN/TM/E
MiCOMho P446 17 Symbols and Glossary
Logic
Explanation Time chart
symbols
INPUT
Latching Latch
OUTPUT
INPUT
Dwell t
OUTPUT
Dwell timer
Timer
INPUT
t
OUTPUT
P446/EN/TM/E 17-21
17 Symbols and Glossary MiCOMho P446
9 LOGIC GATES
17-22 P446/EN/TM/E
MiCOMho P446 18 Wiring Diagrams
WIRING DIAGRAMS
CHAPTER 18
P446/EN/TM/E 18-1
18 Wiring Diagrams MiCOMho P446
The following diagrams are for indication only. Please refer to the wiring diagrams supplied with the IED.
18-2 P446/EN/TM/E
MiCOMho P446 18 Wiring Diagrams
P1727ENb
P446/EN/TM/E 18-3
18 Wiring Diagrams MiCOMho P446
10P44600_1
18-4 P446/EN/TM/E
MiCOMho P446 18 Wiring Diagrams
10P44601_1
P446/EN/TM/E 18-5
18 Wiring Diagrams MiCOMho P446
10P44601_2
18-6 P446/EN/TM/E
MiCOMho P446 18 Wiring Diagrams
10P44602_1
Figure 5: P446 Model C external connection diagram - 24 inputs, 8 standard outputs & 12 high-
break outputs
P446/EN/TM/E 18-7
18 Wiring Diagrams MiCOMho P446
10P44602_2
IN
Figure 6: P446 Model C external connection diagram - 24 inputs, 8 standard outputs & 12 high-
break outputs
18-8 P446/EN/TM/E
MiCOMho P446 18 Wiring Diagrams
10P44603_1
Figure 7: P446 Model D external connection diagram - 24 inputs, 16 standard outputs & 8 high-
break outputs
P446/EN/TM/E 18-9
18 Wiring Diagrams MiCOMho P446
10P44603_2
Figure 8: P446 Model D external connection diagram - 24 inputs, 16 standard outputs & 8 high-
break outputs
18-10 P446/EN/TM/E
Appendix A Commissioning Record
COMMISSIONING RECORD
APPENDIX A
Appendix A-1
Appendix A Commissioning Record
Appendix A-2
Appendix A Commissioning Record
1 TEST RECORD
1.4 Tests
The following tests are to be carried out with the product de-energized
Test Result
Was the IED damaged on visual inspection? Yes No
Is the rating information correct for installation? Yes No
Appendix A-3
Appendix A Commissioning Record
Test Result
Is the case earth installed? Yes No
Are the current transformer shorting contacts closed? Yes No Not checked
Is the insulation resistance >100 M at 500 V DC? Yes No Not tested
Wiring checked against diagram? Yes No
Test block connections checked? Yes No N/A
Watchdog terminals 11 and 12 contacts closed? Yes No
Watchdog terminals 13 and 14 contacts open? Yes No
Measured auxiliary supply V AC DC
The following tests are to be carried out with the product energized
General Tests Result
Watchdog terminals 11 and 12 contact open? Yes No
Watchdog terminals 13 and 14 contact closed? Yes No
LCD contrast setting used
Clock set to local time? Yes No
Time maintained when auxiliary supply removed? Yes No
Alarm (yellow) LED working? Yes No
Out of service (yellow) LED working? Yes No
All 18 programmable LEDs working? Yes No
Field supply voltage measured between terminals 8 and 9 V DC
All opto-inputs working? Yes No
All output relays working? Yes No
Communications Result
Courier
DNP3.0
SCADA Communication standard
IEC61850
IEC60870-5-103
Communications established? Yes No
Protocol converter tested? Yes No N/A
Appendix A-4
Appendix A Commissioning Record
Appendix A-5
Appendix A Commissioning Record
Appendix A-6
Appendix B P59x Commissioning
Instructions
P59X COMMISSIONING
INSTRUCTIONS
APPENDIX B
Appendix B-1
Appendix B P59x Commissioning
Instructions
1 OVERVIEW
This Appendix provides instructions on how to commission the P59x devices (P591, P592, P593)
It consists of the following sections:
1 Overview
2 Commissioning the P59x unit
2.1 P59x visual Inspection
2.2 P59x Insulation Tests
2.3 P59x External Wiring
2.4 P59x Auxiliary Supply
2.5 P59x LEDs
2.6 Optical Received Signal Level
2.7 Loopback
2.8 Optical Transmitter Signal Level
2.9 Optical Signal Optical Received from P59x
Appendix B-3
Appendix B P59x Commissioning
Instructions
1. Isolate all wiring from the earth and test the insulation with an electronic or brushless
insulation tester at a dc voltage not exceeding 500 V.
2. The auxiliary DC supply terminals should be temporarily connected together.
On completion of the insulation resistance tests, ensure all external wiring is correctly reconnected to
the P59x.
Note: The V.35 circuits and the X.21 circuits of the P592 and P593 respectively are isolated from all other
circuits but are electrically connected to the outer case. The circuits must therefore not be insulation
or impulse tested to the case.
Warning: Ensure that the DC supplies are wired with the correct polarity.
Warning: Do not energize the unit using the battery charger with the battery
disconnected as this can irreparably damage the unit’s power supply
circuitry.
P592 only
The four red LED’s can be tested by appropriate setting of the DIL switches on the unit’s front plate.
Set the data rate switch according to the communication channel bandwidth available. Set all other
switches to 0. To illuminate the ‘DSR OFF’ and ‘CTS OFF’ LED’s, disconnect the V.35 connector from
the rear of the P592 and set the ‘DSR’ and ‘CTS’ switches to ‘0’. The ‘OPTO LOOPBACK’ and ‘V.35
LOOPBACK’ LEDs can be illuminated by setting their corresponding switches to ‘1’.
Once operation of the LED’s has been established set all DIL switches, except for the ‘OPTO
LOOPBACK’ switch, to ‘0’ and reconnect the V.35 connector.
P593 only
Set the ‘X.21 LOOPBACK’ switch to ‘ON’. The green ‘CLOCK’ and red ‘X.21 LOOPBACK’ LED’s
should illuminate. Reset the ‘X.21 LOOPBACK’ switch to the ‘OFF’ position.
Set the ‘OPTO LOOPBACK’ switch to ‘ON’. The red ‘OPTO LOOPBACK’ LED should illuminate. Do
not reset the “OPTO LOOPBACK’ switch as it is required in this position for the next test.
2.7 Loopback
P591
It is necessary to loop the transmitted electrical G.703 signal presented on terminals 3 and 4 of the
P591 to the received signal presented on terminals 7 and 8.
If test links have been designed into the scheme to facilitate this they should be used. Alternatively,
remove any external wiring from terminals 3, 4, 7 and 8 at the rear of each P591 unit. Loopback the
G.703 signals on each unit by connecting a wire link between terminals 3 and 7, and a second wire
between terminals 4 and 8.
P592
With the ‘OPTO LOOPBACK’ switch in the ‘1’ position, the receive and transmit optical ports are
connected together. This allows the optical fibre communications between the IED and the P592 to be
tested, but not the internal circuitry of the P592 itself.
P593
With the ‘OPTO LOOPBACK’ switch in the ‘1’ position, the receive and transmit optical ports are
connected together. This allows the optical fibre communications between the IED and the P592 to be
tested, but not the internal circuitry of the P592 itself.
Appendix B-5
Appendix B P59x Commissioning
Instructions
Set the ‘OPTO LOOPBACK’ switch to ‘OFF’ and ‘X.21 LOOPBACK’ switch to ‘ON’ respectively. With
the ‘X.21 LOOPBACK’ switch in this position the ‘Receive Data’ and ‘Transmit Data’ lines of the X.21
communication interface are connected together. This allows the optical fibre communications
between the IED and the P593, and the internal circuitry of the P593 itself to be tested.
DDB SIGNALS
APPENDIX C
Appendix C-1
Appendix C DDB Signals
Appendix C-2
Appendix C DDB Signals
Appendix C-3
Appendix C DDB Signals
Appendix C-4
Appendix C DDB Signals
Appendix C-5
Appendix C DDB Signals
Appendix C-6
Appendix C DDB Signals
Appendix C-7
Appendix C DDB Signals
Virtual output 1 - allows user to control a binary signal which can be mapped via
256 Virtual Output 1 PSL
SCADA protocol output to other devices
Virtual output 2 - allows user to control a binary signal which can be mapped via
257 Virtual Output 2 PSL
SCADA protocol output to other devices
Virtual output 3 - allows user to control a binary signal which can be mapped via
258 Virtual Output 3 PSL
SCADA protocol output to other devices
Virtual output 4 - allows user to control a binary signal which can be mapped via
259 Virtual Output 4 PSL
SCADA protocol output to other devices
Virtual output 5 - allows user to control a binary signal which can be mapped via
260 Virtual Output 5 PSL
SCADA protocol output to other devices
Virtual output 6 - allows user to control a binary signal which can be mapped via
261 Virtual Output 6 PSL
SCADA protocol output to other devices
Virtual output 7 - allows user to control a binary signal which can be mapped via
262 Virtual Output 7 PSL
SCADA protocol output to other devices
Virtual output 8 - allows user to control a binary signal which can be mapped via
263 Virtual Output 8 PSL
SCADA protocol output to other devices
Virtual output 9 - allows user to control a binary signal which can be mapped via
264 Virtual Output 9 PSL
SCADA protocol output to other devices
Virtual output 10 - allows user to control a binary signal which can be mapped
265 Virtual Output10 PSL
via SCADA protocol output to other devices
Virtual output 11 - allows user to control a binary signal which can be mapped
266 Virtual Output11 PSL
via SCADA protocol output to other devices
Virtual output 12 - allows user to control a binary signal which can be mapped
267 Virtual Output12 PSL
via SCADA protocol output to other devices
Virtual output 13 - allows user to control a binary signal which can be mapped
268 Virtual Output13 PSL
via SCADA protocol output to other devices
Virtual output 14 - allows user to control a binary signal which can be mapped
269 Virtual Output14 PSL
via SCADA protocol output to other devices
Virtual output 15 - allows user to control a binary signal which can be mapped
270 Virtual Output15 PSL
via SCADA protocol output to other devices
Virtual output 16 - allows user to control a binary signal which can be mapped
271 Virtual Output16 PSL
via SCADA protocol output to other devices
Virtual output 17 - allows user to control a binary signal which can be mapped
272 Virtual Output17 PSL
via SCADA protocol output to other devices
Virtual output 18 - allows user to control a binary signal which can be mapped
273 Virtual Output18 PSL
via SCADA protocol output to other devices
Virtual output 19 - allows user to control a binary signal which can be mapped
274 Virtual Output19 PSL
via SCADA protocol output to other devices
Virtual output 20 - allows user to control a binary signal which can be mapped
275 Virtual Output20 PSL
via SCADA protocol output to other devices
Virtual output 21 - allows user to control a binary signal which can be mapped
276 Virtual Output21 PSL
via SCADA protocol output to other devices
Virtual output 22 - allows user to control a binary signal which can be mapped
277 Virtual Output22 PSL
via SCADA protocol output to other devices
Appendix C-8
Appendix C DDB Signals
Virtual output 24 - allows user to control a binary signal which can be mapped
279 Virtual Output24 PSL
via SCADA protocol output to other devices
Virtual output 25 - allows user to control a binary signal which can be mapped
280 Virtual Output25 PSL
via SCADA protocol output to other devices
Virtual output 26 - allows user to control a binary signal which can be mapped
281 Virtual Output26 PSL
via SCADA protocol output to other devices
Virtual output 27 - allows user to control a binary signal which can be mapped
282 Virtual Output27 PSL
via SCADA protocol output to other devices
Virtual output 28 - allows user to control a binary signal which can be mapped
283 Virtual Output28 PSL
via SCADA protocol output to other devices
Virtual output 29 - allows user to control a binary signal which can be mapped
284 Virtual Output29 PSL
via SCADA protocol output to other devices
Virtual output 30 - allows user to control a binary signal which can be mapped
285 Virtual Output30 PSL
via SCADA protocol output to other devices
Virtual output 31 - allows user to control a binary signal which can be mapped
286 Virtual Output31 PSL
via SCADA protocol output to other devices
Virtual output 32 - allows user to control a binary signal which can be mapped
287 Virtual Output32 PSL
via SCADA protocol output to other devices
Setting group selection opto inputs have detected an invalid (disabled) settings
288 SG-opto Invalid Group Selection
group
289 Prot'n Disabled Commissioning Test Protection disabled - typically out of service due to test mode
Static test mode option bypasses the delta phase selectors, power swing
290 Static Test Mode Commissioning Test detection and reverts to conventional directional line and cross polarization to
allow testing with test sets that can not simulate a real fault
This alarm indicates that DDB CB1 I^ Lockout (1107) or DDB CB1 Ops Lock
300 CB1 Mon LO Alarm CB Monitoring
(1109) or DDB CB1 Time lockout (1111)
Appendix C-9
Appendix C DDB Signals
CB1 Status Alarm - set when CB1 status is determined by inputs from BOTH
52A and 52B type auxiliary contacts (setting "CB1 Status Input = 52A&52B-
301 CB1 Status Alm CB Status
xPole), and both inputs are in the same state (both = 0 or both = 1) for time
period => 5sec, indicating a problem with the auxiliary switch mechanism).
CB1 Failed to Trip - alarm set if CB1 does not trip within set Trip Pulse Time
302 CB1 Trip Fail CB Control
when CB1 trip command is issued.
CB1 Failed to Close - alarm set if CB1 fails to close within set Close Pulse Time
303 CB1 Close Fail CB Control
when CB1 close command is issued
ManCB1 Unhealthy - alarm set if CB1 remains "unhealthy" for CB Control set
304 ManCB1 Unhealthy CB Control time "CB Healthy Time" when operator controlled CB1 close sequence is
initiated. (Please see description for CB Control setting "CB Healthy Time").
NoCS CB1ManClose - alarm set if selected system check conditions for manual
closing CB1 remain unsatisfied for CB Control set time "Check Sync Time" when
305 NoCS CB1ManClose CB Control
operator controlled CB1 close sequence is initiated. (Please see description for
CB Control setting "Check Sync Time").
306 CB1 AR Lockout Autoreclose CB1 AR Lockout - alarm set when CB1 autoreclose is locked out.
AR CB1 Unhealthy - alarm set if CB1 remains "unhealthy" for Autoreclose set
307 AR CB1 Unhealthy Autoreclose time "CB Healthy Time" when CB1 close sequence is initiated by autoreclose
function. (Please see description for Autoreclose setting "CB Healthy Time").
AR CB1 No C/S - alarm set if selected system check conditions for autoreclosing
CB1 remain unsatisfied for Autoreclose set time "Check Sync Time" when CB1
308 AR CB1 No C/S Autoreclose
close sequence is initiated by autoreclose function. (Please see description for
Autoreclose setting "Check Sync Time").
It will appear in case of at least one of the following: CH1 (or CH2) loss of signal,
315 IEEE C37.94 Fail C Diff
CH1 (or CH2) PATH_YELLOW or CH1 (or CH2) BAD_RX_N
316 Reserved C Diff Unused
Aided channel scheme 1 - channel out of service indication, indicating channel
317 Aid 1 Chan Fail PSL
failure
This alarm indicates that DDB CB2 I ^ Lockout Alarm (1114) or DDB CB Ops
322 CB2 Mon LO Alarm CB Monitoring
Lock (1116) or DDB CB Time lockout (1118)
CB2 Status Alarm - set when CB2 status is determined by inputs from BOTH
52A and 52B type auxiliary contacts (setting "CB2 Status Input = 52A&52B-
323 CB2 Status Alm CB Status
xPole), and both inputs are in the same state (both = 0 or both = 1) for time
period => 5sec, indicating a problem with the auxiliary switch mechanism).
CB2 Failed to Trip - alarm set if CB2 does not trip within set Trip Pulse Time
324 CB2 Trip Fail CB2 Control
when CB2 trip command is issued.
Appendix C-10
Appendix C DDB Signals
ManCB2 Unhealthy - alarm set if CB2 remains "unhealthy" for CB Control set
326 ManCB2 Unhealthy CB2 Control time "CB Healthy Time" when operator controlled CB2 close sequence is
initiated. (Please see description for CB Control setting "CB Healthy Time").
NoCS CB2ManClose - alarm set if selected system check conditions for manual
closing CB2 remain unsatisfied for CB Control set time "Check Sync Time" when
327 NoCS CB2ManClose CB2 Control
operator controlled CB2 close sequence is initiated. (Please see description for
CB Control setting "
328 CB2 AR Lockout Autoreclose CB2 AR Lockout - alarm set when CB2 autoreclose is locked out.
AR CB2 Unhealthy - alarm set if CB2 remains "unhealthy" for Autoreclose set
329 AR CB2 Unhealthy Autoreclose time "CB Healthy Time" when CB2 close sequence is initiated by autoreclose
function. (Please see description for Autoreclose setting "CB Healthy Time").
AR CB2 No C/S - alarm set if selected system check conditions for autoreclosing
CB2 remain unsatisfied for Autoreclose set time "Check Sync Time" when CB2
330 AR CB2 No C/S Autoreclose
close sequence is initiated by autoreclose function. (Please see description for
Autoreclose setting
331 Invalid AR Mode Autoreclose AR Mode selected via optos is not supported
332 Reserved C Diff Unused
333 InValid Mesg Fmt C Diff Invalid Message Format
Indicates a failure with the Co-Processor, this will affect the protections that run
334 Main Prot. Fail Co-processor interface on this board, eg. current differential, phase comparision, distance and DEF
Protections.
Front panel miniature battery failure - either battery removed from slot, or low
352 Battery Fail Self monitoring
voltage
353 Field Volts Fail Self monitoring 48V field voltage failure
354 Rear Comm 2 Fail Self monitoring Comm2 hardware failure - second rear communications board
355 GOOSE IED Absent Ethernet Interface The IED is not subscribed to a publishing IED in the current scheme
356 NIC Not Fitted Ethernet Interface Ethernet board not fitted
357 NIC No Response Ethernet Interface Ethernet board not responding
Appendix C-11
Appendix C DDB Signals
367 IM Data CD Fail InterMiCOM EIA(RS)232 InterMiCOM Data Channel Detect Fail i.e. modem failure
EIA(RS)232 InterMiCOM Channel Failure alarm. No messages were received
368 IM Channel Fail InterMiCOM
during the alarm time setting
This is an alarm that is ON if any setting fail during the setting changing process.
369 Backup Setting Self monitoring
If this happens, the relay will use the last known good setting
370 Reserved Self monitoring Bad DNP Settings
371 Backup Usr Curve Self monitoring Backup Curve
372 Reserved Platform Alarm 21
373 Reserved Platform Alarm 22
374 Reserved Platform Alarm 23
375 Reserved Platform Alarm 24
376 Reserved Platform Alarm 25
377 Reserved Platform Alarm 26
378 Reserved Platform Alarm 27
379 Reserved Platform Alarm 28
380 Reserved Platform Alarm 29
381 Reserved Platform Alarm 30
382 Reserved Platform Alarm 31
383 Reserved Platform Alarm 32
384 Block Zone 1 Gnd PSL Zone 1 ground basic scheme blocking
385 Block Zone 1 Phs PSL Zone 1 phase basic scheme blocking
386 Block Zone 2 Gnd PSL Zone 2 ground basic scheme blocking
387 Block Zone 2 Phs PSL Zone 2 phase basic scheme blocking
388 Block Zone 3 Gnd PSL Zone 3 ground basic scheme blocking
389 Block Zone 3 Phs PSL Zone 3 phase basic scheme blocking
390 Block Zone P Gnd PSL Zone P ground basic scheme blocking
391 Block Zone P Phs PSL Zone P phase basic scheme blocking
392 Block Zone 4 Gnd PSL Zone 4 ground basic scheme blocking
393 Block Zone 4 Phs PSL Zone 4 phase basic scheme blocking
394 Aid1 InhibitDist PSL Block distance aided scheme 1 tripping
395 Aid1 Inhibit DEF PSL Block DEF aided scheme 1 tripping
396 Aid1 Inhib Delta PSL Block Delta directional aided scheme 1 tripping
397 Aid2 InhibitDist PSL Block distance aided scheme 2 tripping
398 Aid2 Inhibit DEF PSL Block DEF aided scheme 2 tripping
Appendix C-12
Appendix C DDB Signals
Appendix C-13
Appendix C DDB Signals
DDB mapped in PSL from opto or comms input. External signal to force CB1
448 Block CB1 AR PSL
autoreclose to lockout.
449 Unused PSL Unused
450 Unused PSL Unused
Pole discrepancy (from external detector) - input used to force a 3 pole trip on
451 Pole Discrep.CB1 PSL
CB1.
452 Loopback Mode PSL To enable loopback mode via opto input
453 Unused Unused
454 Stub Bus Enabled To enable stub bus protection, requires setting to enable feature.
455 to 457 Unused Unused
458 Inhibit WI PSL Inhibit weak infeed aided scheme logic
459 Test Mode PSL Commissioning tests - automatically places relay in test mode
For IEC-870-5-103 protocol only, used for "Command Blocking" (relay ignores
460 103 CommandBlock PSL
SCADA commands)
For IEC-870-5-103 protocol only, used for "Monitor Blocking" (relay is quiet -
461 103 MonitorBlock PSL
issues no messages via SCADA port)
462 Unused Unused
463 Inhibit I>1 PSL Inhibit stage 1 overcurrent protection
464 Inhibit I>2 PSL Inhibit stage 2 overcurrent protection
465 Inhibit I>3 PSL Inhibit stage 3 overcurrent protection
466 Inhibit I>4 PSL Inhibit stage 4 overcurrent protection
467 Inhibit IN>1 PSL Inhibit stage 1 earth fault protection
468 Inhibit IN>2 PSL Inhibit stage 2 earth fault protection
469 Inhibit IN>3 PSL Inhibit stage 3 earth fault protection
470 Inhibit IN>4 PSL Inhibit stage 4 earth fault protection
471 Inhibit V<1 PSL Inhibit stage 1 undervoltage protection
472 Inhibit V<2 PSL Inhibit stage 2 undervoltage protection
473 Inhibit V>1 PSL Inhibit stage 1 overvoltage protection
474 Inhibit V>2 PSL Inhibit stage 2 overvoltage protection
475 Inhibit VN>1 PSL Inhibit stage 1 residual overvoltage protection
476 Inhibit VN>2 PSL Inhibit stage 2 residual overvoltage protection
477 Unused PSL Unused
478 Inhibit Thermal PSL Inhibit thermal overload protection
Inhibit circuit breaker state monitoring (no alarm for defective/stuck auxiliary
479 InhibitCB Status PSL
contact)
Appendix C-14
Appendix C DDB Signals
This signal is to reset the Z1X reach back to Z1 reach in Z1 extension scheme.
489 AR Reset Z1 EXT Zone 1 Extension Scheme
DDB to be mapped in PSL from either internal or external AR
Reset zone Z1X back to Z1 reach using logic input (i.e. case when external AR
490 Reset Zone 1 Ext PSL
and Z1 extension scheme are used)
491 Inhibit LoL PSL Inhibit Loss of Load scheme function
Aided 1 channel out of service signal (COS) or Loss of Guard Signal (LGS) in
492 Aided 1 COS/LGS PSL distance unblocking schemes. This signal is normally driven from an opto input
on conventional channels or from InterMiCOM
Aided channel 1 - external signal received, for input to distance fixed scheme
493 Aided1 Scheme Rx PSL
logic
494 Aided 1 Receive Aided Scheme Logic Aided channel 1 - internal signal received generated in the signal receive logic
495 Unused Unused
496 Aid1 Block Send PSL Prevent sending by customized logic - aided scheme 1
497 Aid1 Custom Send PSL Programmable send logic for special customized scheme (aided channel 1)
498 Aided 1 Send Aided Scheme Logic Aided channel 1 send - internal send signal generated in signal send logic
When using a custom programmable aided scheme 1, the user is able to include
499 Aid1 Custom T In PSL a current reversal guard timer. Energizing this DDB will additionally start this
timer, from PSL
When using customized aided scheme 1, this signal is used to indicate any
additional condition that should be treated as permission for an aided trip (for
500 Aid1 CustomT Out Aided Scheme Logic
example a permissive signal received could be connected, or a blocking signal
could be inverted and then connected)
Aided scheme 1 trip enable - this is a permissive signal used to accelerate zone
501 Aid1 Trip Enable Aided Scheme Logic 2, or a blocking signal which has been inverted. It is a signal output, part-way
through the internal fixed logic of aided schemes
Aided 2 channel out of service signal (COS) or Loss of Guard Signal (LGS) in
506 Aided 2 COS/LGS PSL distance unblocking schemes. This signal is normally driven from an opto input
on conventional channels or from InterMiCOM
Aided channel 2 - external signal received, for input to distance fixed scheme
507 Aided2 Scheme Rx PSL
logic
508 Aided 2 Receive Aided Scheme Logic Aided channel 2 - internal signal received generated in the signal receive logic
509 RP1 Read Only RP1 Read Only Enables RP1 Read Only
510 RP2 Read Only RP2 Read Only Enables RP2 Read Only
511 NIC Read Only NIC Read Only Enables NIC Read Only
512 Aid2 Block Send PSL Prevent sending by customized logic - aided scheme 2
513 Aid2 Custom Send PSL Programmable send logic for special customized scheme (aided channel 2)
514 Aided 2 Send Aided Scheme Logic Aided channel 2 send - internal send signal generated in signal send logic
When using a custom programmable aided scheme 2, the user is able to include
515 Aid2 Custom T In PSL a current reversal guard timer. Energizing this DDB will additionally start this
timer, from PSL
Appendix C-15
Appendix C DDB Signals
When using customized aided scheme 2, this signal is used to indicate any
additional condition that should be treated as permission for an aided trip (for
516 Aid2 CustomT Out Aided Scheme Logic
example a permissive signal received could be connected, or a blocking signal
could be inverted and then connected)
Aided scheme 2 trip enable - this is a permissive signal used to accelerate zone
517 Aid2 Trip Enable Aided Scheme Logic 2, or a blocking signal which has been inverted. It is a signal output, part-way
through the internal fixed logic of aided schemes
Trip signal for CB1 phase A - used as a command to drive CB1 trip A output
523 CB1 Trip OutputA Trip Conversion Logic
contact(s). Takes the output from the internal trip conversion logic
Trip signal for CB1 phase B - used as a command to drive CB1 trip B output
524 CB1 Trip OutputB Trip Conversion Logic
contact(s). Takes the output from the internal trip conversion logic
Trip signal for CB1 phase C - used as a command to drive CB1 trip C output
525 CB1 Trip OutputC Trip Conversion Logic
contact(s). Takes the output from the internal trip conversion logic
Trip signal for CB1 3ph - used as a command to drive CB1 trip 3ph output
526 CB1 Trip 3ph Trip Conversion Logic
contact(s). Takes the output from the internal trip conversion logic
B phase trip - input to trip conversion logic. Essential to ensure correct single or
531 Trip Inputs B PSL
three pole trip command results (e.g. converts a 2 pole trip to 3 phase)
C phase trip - input to trip conversion logic. Essential to ensure correct single or
532 Trip Inputs C PSL
three pole trip command results (e.g. converts a 2 pole trip to 3 phase)
External DDB input to host protection trip conversion logic to force 3 Pole
533 Force 3PTrip CB1 PSL
tripping of CB1 for all faults
CB1 Ext Trip3ph - allows external protection to initiate breaker fail, circuit
534 CB1 Ext Trip3ph PSL breaker condition monitoring statistics, and internal auto-reclose (if enabled) of
CB1
CB1 Ext Trip A - allows external protection to initiate breaker fail, circuit breaker
535 CB1 Ext Trip A PSL condition monitoring statistics, and internal auto-reclose (if enabled) (A Ph) of
CB1
CB1 Ext Trip B - allows external protection to initiate breaker fail, circuit breaker
536 CB1 Ext Trip B PSL condition monitoring statistics, and internal auto-reclose (if enabled) (B Ph) of
CB1
CB1 Ext Trip C - allows external protection to initiate breaker fail, circuit breaker
537 CB1 Ext Trip C PSL condition monitoring statistics, and internal auto-reclose (if enabled) (C Ph) of
CB1
CB2 Ext Trip3ph - allows external protection to initiate breaker fail, circuit
538 CB2 Ext Trip3ph PSL breaker condition monitoring statistics, and internal auto-reclose (if enabled) of
CB2
Appendix C-16
Appendix C DDB Signals
Setting group selector X1 (low bit)-selects SG2 if only DDB 542 signal is active.
542 SG Select x1 SG1 is active if both DDB 542 & DDB 543=0
SG4 is active if both DDB 542 & DDB 543=1
Setting group selector 1X (high bit)-selects SG3 if only DDB 543 is active.SG1 is
543 SG Select 1x active if both DDB 542 & DDB 543=0SG4 is active if both DDB 542 & DDB
543=1
To reset all statistics values cumulated on the relay. If mapped, the input for this
544 Clear Statistics PSL signal could come from a command of the remote end (DDB 1020 - clear stats
cmd -) via IM64
Appendix C-17
Appendix C DDB Signals
Appendix C-18
Appendix C DDB Signals
Appendix C-19
Appendix C DDB Signals
Appendix C-20
Appendix C DDB Signals
Appendix C-21
Appendix C DDB Signals
Phase B undervoltage level detector used in the pole dead logic. Detectors
830 VB< start Poledead
have a settable threshold: default undervoltage pickup 38.1 V-drop off 43.8 V
Phase C undervoltage level detector used in the pole dead logic. Detectors
831 VC< start Poledead
have a settable threshold: default undervoltage pickup 38.1 V-drop off 43.8 V
Control trip - operator trip instruction to circuit breaker 2, via menu, or SCADA.
840 Control TripCB2 CB Control
(Does not operate for protection element trips)
Control close in progress CB1 - the relay has been given an instruction to close
842 CB1 Close inProg CB Control the circuit breaker, but the manual close timer delay has not yet finished timing
out
843 Unused Autoreclose Unused
844 CB1 AR 3p InProg Autoreclose CB1 Auto Reclose AR 3 pole in Progress
845 CB1 AR 1p InProg Autoreclose CB1 Auto Reclose AR 1 pole in Progress
846 Seq Counter = 0 Autoreclose Sequence Counter = 0
Appendix C-22
Appendix C DDB Signals
This is a signal issued by the autoreclose logic to the general CB1 Control logic
854 Auto Close CB1 Autoreclose when the conditions to autoreclose CB1 are satisfied (dead time complete, CB
healthy etc).
Indicates contacts blocked mode enabled. Can be mapped in PSL and sent via
863 Contacts Blocked SW
InterMiCOM/IM64 to block contacts at the remote end.
A phase undercurrent level detector pickup (detects low current). It is used for
864 IA< Start Undercurrent
breaker failure and for fault record reset.
B phase undercurrent level detector pickup (detects low current). It is used for
865 IB< Start Undercurrent
breaker failure and for fault record reset.
C phase undercurrent level detector pickup (detects low current). It is used for
866 IC< Start Undercurrent
breaker failure and for fault record reset.
Appendix C-23
Appendix C DDB Signals
Output from CB1 system check logic: indicates system checks for CB1 are
880 SChksInactiveCB1 Check sync disabled (setting "System Checks CB1" = Disabled or global setting "System
Checks" = Disabled)
DDB input must be high to enable CB1check sync stage1 logic to operate.
881 CB1 CS1 Enabled PSL
Defaults to high if not mapped in PSL; if mapped in PSL must be driven high.
DDB input must be high to enable CB1check sync stage 2 logic to operate.
882 CB1 CS2 Enabled PSL
Defaults to high if not mapped in PSL; if mapped in PSL must be driven high.
Output from CB1 Check Sync logic, when enabled: indicates set conditions for
883 CB1 CS1 OK Check sync
CB1 sync check stage 1 are satisfied.
Output from CB1 Check Sync logic, when enabled: indicates set conditions for
884 CB1 CS2 OK Check sync
CB1 sync check stage 2 are satisfied.
885 Unused PSL Unused
886 Live Bus 1 Voltage Monitoring Indicates Bus 1 input is live, i.e. voltage >= setting "Live Bus 1"
887 Dead Bus 1 Voltage Monitoring Indicates Bus 1 input is dead, i.e. voltage < setting "Dead Bus 1"
888 Live Line Voltage Monitoring Indicates Line input is live, i.e. voltage >= setting "Live Line"
889 Dead Line Voltage Monitoring Indicates Line input is dead, i.e. voltage < setting "Dead Line"
890 All Poles Dead Poledead logic Pole dead logic detects 3 phase breaker open
891 Any Pole Dead Poledead logic Pole dead logic detects at least one breaker pole open
892 Pole Dead A Poledead logic Phase A Pole Dead
893 Pole Dead B Poledead logic Phase B Pole Dead
894 Pole Dead C Poledead logic Phase C Pole Dead
895 VTS Acc Ind Fixed Logic Any Trip
896 VTS Volt Dep Fixed Logic Any Voltage Dependent Function
897 Unused PSL Unused
Input to the circuit breaker control logic to indicate manual check synchronization
898 Ctl Check Sync PSL
conditions are satisfied
899 Unused PSL Unused
900 CB1 Ext CS OK PSL External check-sync is OK for CB1
901 CB2 Ext CS OK PSL External check-sync is OK for CB2
902 Unused PSL Unused
903 CB1 Open 3 ph CB Status Circuit breaker 1 is open, all three phases
904 CB1 Open A ph CB Status Circuit breaker 1 A phase is open
905 CB1 Open B ph CB Status Circuit breaker 1 B phase is open
906 CB1 Open C ph CB Status Circuit breaker 1 C phase is open
907 CB1 Closed 3 ph CB Status Circuit breaker 1 is closed, all three phases
908 CB1 Closed A ph CB Status Circuit breaker 1 A phase is closed
909 CB1 Closed B ph CB Status Circuit breaker 1 B phase is closed
910 CB1 Closed C ph CB Status Circuit breaker 1 C phase is closed
911 CB2 Open 3 ph CB Status Circuit breaker 2 is open, all three phases
912 CB2 Open A ph CB Status Circuit breaker 2 A phase is open
913 CB2 Open B ph CB Status Circuit breaker 2 A phase is open
914 CB2 Open C ph CB Status Circuit breaker 2 A phase is open
915 CB2 Closed 3 ph CB Status Circuit breaker 2 is closed, all three phases
Appendix C-24
Appendix C DDB Signals
Faulted phase B - must be assigned, as this sets the start flag used in records,
953 Faulted Phase B PSL
and on the LCD display
Faulted phase C - must be assigned, as this sets the start flag used in records,
954 Faulted Phase C PSL
and on the LCD display
Faulted phase N (fault involves ground) - must be assigned, as this sets the start
955 Faulted Phase N PSL
flag used in records, and on the LCD display
Started phase A - must be assigned, as this sets the start flag used in records,
956 Started Phase A PSL
and on the LCD display
Started phase B - must be assigned, as this sets the start flag used in records,
957 Started Phase B PSL
and on the LCD display
Started phase C - must be assigned, as this sets the start flag used in records,
958 Started Phase C PSL
and on the LCD display
Started phase N (fault involves ground) - must be assigned, as this sets the start
959 Started Phase N PSL
flag used in records, and on the LCD display
Appendix C-25
Appendix C DDB Signals
2nd harmonic current ratio exceeds threshold on phase A (may be used to block
1016 Ih(2) Loc Blk A Inrush Detector any instantaneous distance elements that reach through the reactance of a
power transformer)
2nd harmonic current ratio exceeds threshold on phase B (may be used to block
1017 Ih(2) Loc Blk B Inrush Detector any instantaneous distance elements that reach through the reactance of a
power transformer)
2nd harmonic current ratio exceeds threshold on phase C (may be used to block
1018 Ih(2) Loc Blk C Inrush Detector any instantaneous distance elements that reach through the reactance of a
power transformer)
Appendix C-26
Appendix C DDB Signals
Appendix C-27
Appendix C DDB Signals
Assignment of signal to drive output function key LED 1 red. This LED is
1076 FnKey LED1 ConR LED_CON_R9
associated with function key 1
Assignment of signal to drive output function key LED 1 green. This LED is
1077 FnKey LED1 ConG LED_CON_G9 associated with function key 1. To drive function key LED, yellow DDB 1040
and DDB 1041 must be active at the same time
Assignment of signal to drive output function key LED 2 red. This LED is
1078 FnKey LED2 ConR LED_CON_R10
associated with function key 2
Assignment of signal to drive output function key LED 2 green. This LED is
1079 FnKey LED2 ConG LED_CON_G10 associated with function key 2. To drive function key LED, yellow DDB 1042
and DDB 1043 must be active at the same time
Assignment of signal to drive output function key LED 3 red. This LED is
1080 FnKey LED3 ConR LED_CON_R11
associated with function key 3
Assignment of signal to drive output function key LED 3 green. This LED is
1081 FnKey LED3 ConG LED_CON_G11 associated with function key 3. To drive function key LED, yellow DDB 1044
and DDB 1045 must be active at the same time
Assignment of signal to drive output function key LED 4 red. This LED is
1082 FnKey LED4 ConR LED_CON_R12
associated with function key 4
Assignment of signal to drive output function key LED 4 green. This LED is
1083 FnKey LED4 ConG LED_CON_G12 associated with function key 4. To drive function key LED, yellow DDB 1046
and DDB 1047 must be active at the same time
Assignment of signal to drive output function key LED 5 red. This LED is
1084 FnKey LED5 ConR LED_CON_R13
associated with function key 5
Assignment of signal to drive output function key LED 5 green. This LED is
1085 FnKey LED5 ConG LED_CON_G13 associated with function key 5. To drive function key LED, yellow DDB 1048
and DDB 1049 must be active at the same time
Assignment of signal to drive output function key LED 6 red. This LED is
1086 FnKey LED6 ConR LED_CON_R14
associated with function key 6
Assignment of signal to drive output function key LED 6 green. This LED is
1087 FnKey LED6 ConG LED_CON_G14 associated with function key 6. To drive function key LED, yellow DDB 1050
and DDB 1051 must be active at the same time
Assignment of signal to drive output function key LED 7 red. This LED is
1088 FnKey LED7 ConR LED_CON_R15
associated with function key 7
Assignment of signal to drive output function key LED 7 green. This LED is
1089 FnKey LED7 ConG LED_CON_G15 associated with function key 7. To drive function key LED, yellow DDB 1052
and DDB 1053 must be active at the same time
Appendix C-28
Appendix C DDB Signals
Assignment of signal to drive output function key LED 8 green. This LED is
1091 FnKey LED8 ConG LED_CON_G16 associated with function key 8. To drive function key LED, yellow DDB 1054
and DDB 1055 must be active at the same time
Assignment of signal to drive output function key LED 9 red. This LED is
1092 FnKey LED9 ConR LED_CON_R17
associated with function key 9
Assignment of signal to drive output function key LED 9 green. This LED is
1093 FnKey LED9 ConG LED_CON_G17 associated with function key 9. To drive function key LED, yellow DDB 1056
and DDB 1057 must be active at the same time
Assignment of signal to drive output function key LED 10 red. This LED is
1094 FnKey LED10 ConR LED_CON_R18
associated with function key 10
Assignment of signal to drive output function key LED 10 green. This LED is
1095 FnKey LED10 ConG LED_CON_G18 associated with function key 10. To drive function key LED, yellow DDB 1058
and DDB 1059 must be active at the same time
Broken current maintenance alarm - circuit breaker cumulative duty alarm set-
1106 CB1 I^ Maint CB Monitoring
point CB1
Broken current lockout alarm - circuit breaker cumulative duty has been
1107 CB1 I^ Lockout CB Monitoring
exceeded CB1
Appendix C-29
Appendix C DDB Signals
Appendix C-30
Appendix C DDB Signals
Appendix C-31
Appendix C DDB Signals
Appendix C-32
Appendix C DDB Signals
Appendix C-33
Appendix C DDB Signals
Appendix C-34
Appendix C DDB Signals
Appendix C-35
Appendix C DDB Signals
This applies only if distance primary FUN is selected (in IEC870-5-103) This is
1379 Teleprot Rx an output signal available in the PSL, which could be mapped to a signal receive
of one of the two teleprotection channels
This is an output signal available in the PSL, which can be mapped in IEC870-5-
1380 Group Warning
103 to a minor defect which does not shut down the main protection
This is an output signal available in the PSL, which can be mapped in IEC870-5-
1381 Group Alarm
103 to a major problem normally linked to the watchdog
This is an output signal available in the PSL, which can be mapped to enable
1382 AR On Pulse
AR via pulse
This is an output signal available in the PSL, which can be mapped to disable
1383 AR Off Pulse
AR via pulse
If setting "Leader Select By:" = Opto, then preferred leader CB is CB1 if input
1408 CB2 Lead PSL
DDB "CB2 LEAD" is low, or CB2 if DDB "CB2 LEAD" is high.
If setting "Foll AR Mode" = Opto, then if input DDB "FARSP" is high, the follower
1409 Foll AR Mode 1P PSL CB is enabled for single phase autoreclose, if "FARSP" is low, the follower CB is
NOT enabled for single phase autoreclose.
Appendix C-36
Appendix C DDB Signals
DDB mapped in PSL from opto or comms input. This input DDB is used when
1418 Ext Rst CB2Shots PSL
required to reset the CB2 cumulative "Shots" counters.
DDB mapped in PSL. Reset Manual CB2 Close Timer Delay (stop & reset
1419 Rst CB2 CloseDly PSL
Manual Close Delay time for closing CB2).
DDB mapped in PSL from opto or comms input. External signal to inhibit
1420 Inhibit AR PSL
autoreclose.
DDB mapped in PSL from opto or comms input. External signal to force CB2
1421 Block CB2 AR PSL
autoreclose to lockout.
DDB mapped in PSL from opto or comms input. Reset Lockout Opto Input to
1422 Rst CB2 Lockout PSL
reset CB2 Lockout state
DDB mapped in PSL from opto input (Bus2 VT secondary MCB tripped or VT fail
1423 MCB/VTS CB2 CS PSL
detected by external VTS scheme), or signal from host relay VTS scheme
DDB mapped in PSL from opto input (external signal to inhibit Live Bus 2
1424 Inhibit LB2 PSL
function)
DDB mapped in PSL from opto input (external signal to inhibit Dead Bus 2
1425 Inhibit DB2 PSL
function)
DDB input must be high to enable CB2 check sync stage 1 logic to operate.
1426 CB2 CS1 Enabled PSL
Defaults to high if not mapped in PSL; if mapped in PSL must be driven high.
DDB input must be high to enable CB2 check sync satge 2 logic to operate.
1427 CB2 CS2 Enabled PSL
Defaults to high if not mapped in PSL; if mapped in PSL must be driven high.
1428 CB2 In Service CB2 In Service (can be initiated for autoreclose)
1429 CB2 NoAR Autoreclose CB2 not available for autoreclose
1430 Unused Unused
1431 Leader CB2 Autoreclose CB2 set as leader
1432 Follower CB1 Autoreclose CB1 set as follower
1433 Follower CB2 Autoreclose CB2 set as follower
1434 CB2 AR Init Autoreclose CB2 AR cycle initiation
1435 CB2 ARIP Autoreclose CB2 AR cycle in progress
1436 to 1440 Unused Autoreclose Unused
1441 CB2 Failed AR CB2 autoreclose failed due to persistent fault
Output DDB indicates conditions to enable CB2 lead single phase autoreclose
1442 DTOK CB2L 1P
dead time to run are satisfied
Output DDB indicates conditions to enable CB2 lead three phase autoreclose
1443 DTOK CB2L 3P
dead time to run are satisfied
1444 CB2 3P DTime Indicates CB2 three phase autoreclose dead time running
1445 En CB2 Follower Indicates conditions are satisfied to enable CB2 follower sequence
1446 1P Follower Time Indicates a single pole autoreclose follower time is running (either CB)
1447 3P Follower Time Indicates a three pole autoreclose follower time is running (either CB)
This is a signal issued by the autoreclose logic to the general CB2 Control logic
1448 Auto Close CB2 when the conditions to autoreclose CB2 are satisfied (dead time complete, CB
healthy etc).
1449 Set CB2 Close Indicates a CB2 Auto Close signal has been issued
Appendix C-37
Appendix C DDB Signals
This signal is set when CB2 has successfully completed a single phase
1451 CB2 Succ 1P AR
autoreclose cycle.
This signal is set when CB2 has successfully completed a three phase
1452 CB2 Succ 3P AR
autoreclose cycle.
Control close in progress CB2 - the relay has been given an instruction to close
1453 CB2 Close inProg the circuit breaker, but the manual close timer delay has not yet finished timing
out
1454 CB2 Fast SCOK OK to reclose CB2 with sync check without waiting for dead time to complete
1455 CB2L SCOK System conditions OK to reclose CB2 as leader when dead time complete
1456 CB2F SCOK System conditions OK to reclose CB2 when follower time complete
1457 Unused Unused
1458 CB2 Man SCOK System conditions OK to manually close CB2
1459 CB2 Fail Pr Trip signal to force CB2 AR lockout if CB2 fails to trip when protection operates
1460 Unused Unused
1461 Live Bus 2 Indicates Bus 2 input is live, i.e. voltage >= setting "Live Bus 2"
1462 Dead Bus 2 Indicates Bus 2 input is dead, i.e. voltage < setting "Dead Bus 2"
Output from CB2 Check Sync logic, when enabled: indicates set conditions for
1463 CB2 CS2 OK
CB2 sync check stage 2 are satisfied.
Line-Bus 1 slip freq > setting [48 98] (frequency difference (slip) between line
1464 CB1 CS2 SlipF> voltage and bus 1 voltage is greater than maximum slip permitted for CB1
synchronism check stage 2)
Line-Bus 1 slip freq < setting [48 98] (frequency difference (slip) between line
1465 CB1 CS2 SlipF< voltage and bus 1 voltage is within the permitted range for CB1 synchronism
check stage 2)
Line-Bus 2 slip freq > setting [48 A1] (frequency difference (slip) between line
1466 CB2 CS1 SlipF> voltage and bus 2 voltage is greater than maximum slip permitted for CB2
synchronism check stage 1)
Line-Bus 2 slip freq < setting [48 A1] (frequency difference (slip) between line
1467 CB2 CS1 SlipF< voltage and bus 2 voltage is within the permitted range for CB2 synchronism
check stage 1)
Line-Bus 2 slip freq > setting [48 A6] (frequency difference (slip) between line
1468 CB2 CS2 SlipF> voltage and bus 2 voltage is greater than maximum slip permitted for CB2
synchronism check stage 2)
Line-Bus 2 slip freq < setting [48 A6] (frequency difference (slip) between line
1469 CB2 CS2 SlipF< voltage and bus 2 voltage is within the permitted range for CB2 synchronism
check stage 2)
Voltage magnitude difference between Line V and Bus2 V is greater than setting
1470 CB2 CS1 VL>VB
[48 9F] (line V > Bus V)
Voltage magnitude difference between Line V and Bus2 V is greater than setting
1471 CB2 CS2 VL>VB
[48 A4] (line V > Bus V)
Voltage magnitude difference between Line V and Bus2 V is greater than setting
1472 CB2 CS1 VL<VB
[48 9F] (line V < Bus V)
Voltage magnitude difference between Line V and Bus2 V is greater than setting
1473 CB2 CS2 VL<VB
[48 A4] (line V < Bus V)
Frequency difference between Line V and Bus2 V is greater than setting [48 A1]
1474 CB2 CS1 FL>FB
(line freq > Bus freq)
Frequency difference between Line V and Bus2 V is greater than setting [48 A6]
1475 CB2 CS2 FL>FB
(line freq > Bus freq)
Appendix C-38
Appendix C DDB Signals
Frequency difference between Line V and Bus2 V is greater than setting [48 A6]
1477 CB2 CS2 FL<FB
(line freq < Bus freq)
Line/Bus2 phase angle in range: setting [48 9E] to +180deg (anticlockwise from
1478 CB2 CS1 AngHigh+
Vbus)
Line/Bus2 phase angle in range: setting [48 9E] to -180deg (clockwise from
1479 CB2 CS1 AngHigh-
Vbus)
Line/Bus2 phase angle in range: setting [48 A3] to +180deg (anticlockwise from
1480 CB2 CS2 AngHigh+
Vbus)
Line/Bus2 phase angle in range: setting [48 A3] to -180deg (clockwise from
1481 CB2 CS2 AngHigh-
Vbus)
Line freq > (Bus2 freq + 0.001Hz) (Line voltage vector rotating anticlockwise
1482 CB2 CS AngRotACW
relative to VBus2)
Bus2 freq > (Line freq + 0.001Hz) (Line voltage vector rotating clockwise relative
1483 CB2 CS AngRotCW
to VBus2)
Output from CB2 system check logic: indicates system checks for CB2 are
1484 SChksInactiveCB2 disabled (setting "System Checks CB2" = Disabled or global setting "System
Checks" = Disabled)
Frequency difference between Line V and Bus1 V is greater than setting [48 98]
1494 CB1 CS2 FL<FB
(line freq < Bus freq)
Line/Bus1 phase angle in range: setting [48 95] to +180deg (anticlockwise from
1495 CB1 CS2 AngHigh+
Vbus)
Line/Bus1 phase angle in range: setting [48 95] to -180deg (clockwise from
1496 CB1 CS2 AngHigh-
Vbus)
If setting "Lead AR Mode" = Opto, then if input DDB "AR Mode 1P" is high, the
1497 AR Mode 1P PSL leader CB is enabled for single phase autoreclose, if "AR Mode 1P" is low, the
leader CB is NOT enabled for single phase autoreclose.
If setting "Lead AR Mode" = Opto, then if input DDB "AR Mode 3P" is high, the
1498 AR Mode 3P PSL leader CB is enabled for three phase autoreclose, if "AR Mode 3P" is low, the
leader CB is NOT enabled for three phase autoreclose.
DDB mapped in PSL from opto or comms input. Input operation will initiate APh
1504 Init APh AR Test PSL
test trip & autoreclose cycle
Appendix C-39
Appendix C DDB Signals
DDB mapped in PSL from opto or comms input. Input operation will initiate CPh
1506 Init CPh AR Test PSL
test trip & autoreclose cycle
DDB mapped in PSL from opto or comms input. Input operation will initiate 3Ph
1507 Init 3P AR Test PSL
test trip & autoreclose cycle
DDB mapped in PSL from opto or comms input: indicates external protection
1508 Ext Fault APh PSL
operated for fault involving A phase
DDB mapped in PSL from opto or comms input: indicates external protection
1509 Ext Fault BPh PSL
operated for fault involving C phase
DDB mapped in PSL from opto or comms input: indicates external protection
1510 Ext Fault CPh PSL
operated for fault involving C phase
DDB mapped in PSL from opto or comms input: if setting "AR Skip Shot 1" =
Enable and this input is high when a protection operation initiates an autoreclose
1511 AR Skip Shot1 PSL cycle, then the sequence counter advances directly to SC:COUNT = 2 so the
autoreclose cycle skips (omits) Shot 1 and instead starts at Dead Time 2 for the
first reclose attempt.
DDB mapped in PSL from opto or comms input. This input DDB is used when
1518 Ext Rst CB1Shots PSL
required to reset the CB1 cumulative "Shots" counters.
1519 Unused PSL Unused
1520 Unused PSL Unused
DDB mapped in PSL from opto input (Bus1 VT secondary MCB tripped or VT fail
1521 MCB/VTS CB1 CS PSL
detected by external VTS scheme), or signal from host relay VTS scheme
1522 Inhibit LL PSL DDB mapped in PSL from opto input (external signal to inhibit Live Line function)
DDB mapped in PSL from opto input (external signal to inhibit Dead Line
1523 Inhibit DL PSL
function)
DDB mapped in PSL from opto input (external signal to inhibit Live Bus 1
1524 Inhibit LB1 PSL
function)
DDB mapped in PSL from opto input (external signal to inhibit Dead Bus 1
1525 Inhibit DB1 PSL
function)
1526 CB1 In Service CB1 In Service (can be initiated for autoreclose)
1527 Unused Unused
1528 CB1 NoAR Autoreclose CB1 not available for autoreclose
1529 Unused Unused
1530 Leader CB1 Autoreclose CB1 set as leader
1531 to 1534 Unused Unused
1535 CB1 Trip AR MemA CB1 A Ph trip & AR initiation memory
1536 CB1 Trip AR MemB CB1 B Ph trip & AR initiation memory
1537 CB1 Trip AR MemC CB1 C Ph trip & AR initiation memory
1538 Unused Unused
1539 Unused Unused
1540 Unused Unused
1541 AR Start Autoreclose Any AR initiation signal present
1542 ARIP Autoreclose Any AR cycle in progress
1543 CB1 AR Init Autoreclose CB1 AR cycle initiation
1544 CB1 ARIP Autoreclose CB1 AR cycle in progress
Appendix C-40
Appendix C DDB Signals
If a single phase fault evolves to a multi-phase fault during the single phase
1547 Evolve 3Ph dead time, this DDB indicates the fault has evolved and that SPAR will be
stopped and 3PAR started.
Output DDB indicates conditions to enable CB1 lead three phase autoreclose
1553 DTOK CB1L 3P
dead time to run are satisfied
1554 1P DTime Indicates single phase autoreclose dead time running
1555 OK Time 3P OK to start 3PAR dead time
1556 3P DTime1 3Phase dead time 1 running
1557 3P DTime2 3Phase dead time 2 running
1558 3P DTime3 3Phase dead time 3 running
1559 3P DTime4 3Phase dead time 4 running
1560 CB1 3P DTime Indicates CB1 three phase autoreclose dead time running
1561 1PF TComp Either CB SP follower time complete
1562 3PF TComp Either CB 3P follower time complete
1563 Unused Unused
1564 Unused Unused
1565 Set CB1 Close Indicates a CB1 Auto Close signal has been issued
Output DDB can be applied to inhibit CB1 reclose by adjacent scheme until local
1566 CB1 Control
autoreclose scheme confirms it is OK to close CB1
1567 1P Reclaim Time Single Phase AR reclaim time running
1568 1P Reclaim TComp Single Phase AR reclaim time complete
1569 3P Reclaim Time Three Phase AR reclaim time running
1570 3P Reclaim TComp Three Phase AR reclaim time complete
This signal is set when CB1 has successfully completed a single phase
1571 CB1 Succ 1P AR
autoreclose cycle.
1572 CB1 Fast SCOK OK to reclose CB1 with sync check without waiting for dead time to complete
1573 CB1L SCOK System conditions OK to reclose CB1 when dead time complete
1574 CB1 Man SCOK System conditions OK to manually close CB1
1575 CB1 Fail Pr Trip signal to force CB1 AR lockout if CB1 fails to trip when protection operates
1576 Unused Unused
Output from CB2 Check Sync logic, when enabled: indicates set conditions for
1577 CB2 CS1 OK
CB2 sync check stage 1 are satisfied.
Line-Bus 1 slip freq > setting [48 93] (frequency difference (slip) between line
1578 CB1 CS1 SlipF> voltage and bus 1 voltage is greater than maximum slip permitted for CB1
synchronism check type 1)
Line-Bus 1 slip freq < setting [48 93] (frequency difference (slip) between line
1579 CB1 CS1 SlipF< voltage and bus 1 voltage is greater than maximum slip permitted for CB1
synchronism check type 1)
Appendix C-41
Appendix C DDB Signals
Voltage magnitude difference between Line V and Bus1 V is greater than setting
1587 CB1 CS2 VL>VB
[48 96] (line V > Bus V)
Voltage magnitude difference between Line V and Bus1 V is greater than setting
1588 CB1 CS1 VL<VB
[48 91] (line V < Bus V)
Voltage magnitude difference between Line V and Bus1 V is greater than setting
1589 CB1 CS2 VL<VB
[48 96] (line V < Bus V)
Frequency difference between Line V and Bus1 V is greater than setting [48 93]
1590 CB1 CS1 FL>FB
(line freq > Bus freq)
Frequency difference between Line V and Bus1 V is greater than setting [48 93]
1591 CB1 CS1 FL<FB
(line freq < Bus freq)
Line/Bus1 phase angle in range: setting [48 90] to +180deg (anticlockwise from
1592 CB1 CS1 AngHigh+
Vbus)
Line/Bus1 phase angle in range: setting [48 90] to -180deg (anticlockwise from
1593 CB1 CS1 AngHigh-
Vbus)
Line freq > (Bus1 freq + 0.001Hz) (Line voltage vector rotating anticlockwise
1594 CB1 CS AngRotACW
relative to VBus1)
Bus1 freq > (Line freq + 0.001Hz) (Line voltage vector rotating clockwise relative
1595 CB1 CS AngRotCW
to VBus1)
1596 Unused Unused
1597 Rst CB2 Data Reset CB2 Maintenance values
1598 CB2 Pre-Lockout CB2 Condition Monitoring Pre-Lockout condition
Composite Lockout Alarm - circuit breaker locked out due to auto-recloser, or
1599 CB2 LO Alarm
condition monitioring
Trip signal for CB2 3ph - used as a command to drive CB2 trip 3ph output
1600 CB2 Trip 3ph Trip Conversion Logic
contact(s). Takes the output from the internal trip conversion logic
Trip signal for CB2 phase A - used as a command to drive CB2 trip A output
1601 CB2 Trip OutputA Trip Conversion Logic
contact(s). Takes the output from the internal trip conversion logic
Trip signal for CB2 phase B - used as a command to drive CB2 trip B output
1602 CB2 Trip OutputB Trip Conversion Logic
contact(s). Takes the output from the internal trip conversion logic
Trip signal for CB2 phase C - used as a command to drive CB2 trip C output
1603 CB2 Trip OutputC Trip Conversion Logic
contact(s). Takes the output from the internal trip conversion logic
External DDB input to host protection trip conversion logic to force 3 Pole
1604 Force 3PTrip CB2 PSL
tripping of CB2 for all faults
External input via DDB to enable CB2, if "in service", to be initiated for
1605 AR Enable CB2 autoreclosing by an AR initiation signal from protection. DDB input defaults to
high if not mapped in PSL, so CB2 AR initiation is permitted.
Pole discrepancy (from external detector) - input used to force a 3 pole trip on
1606 Pole Discrep.CB2 PSL
CB2.
Appendix C-42
Appendix C DDB Signals
Appendix C-43
Appendix C DDB Signals
Appendix C-44
Appendix C DDB Signals
GOOSE virtual input 1 - provides the Quality attributes of any data object in an
1728 Quality VIP 1 GOOSE Input Command
incoming GOOSE message
GOOSE virtual input 2 - provides the Quality attributes of any data object in an
1729 Quality VIP 2 GOOSE Input Command
incoming GOOSE message
GOOSE virtual input 3 - provides the Quality attributes of any data object in an
1730 Quality VIP 3 GOOSE Input Command
incoming GOOSE message
GOOSE virtual input 4 - provides the Quality attributes of any data object in an
1731 Quality VIP 4 GOOSE Input Command
incoming GOOSE message
GOOSE virtual input 5 - provides the Quality attributes of any data object in an
1732 Quality VIP 5 GOOSE Input Command
incoming GOOSE message
GOOSE virtual input 6 - provides the Quality attributes of any data object in an
1733 Quality VIP 6 GOOSE Input Command
incoming GOOSE message
GOOSE virtual input 7 - provides the Quality attributes of any data object in an
1734 Quality VIP 7 GOOSE Input Command
incoming GOOSE message
GOOSE virtual input 8 - provides the Quality attributes of any data object in an
1735 Quality VIP 8 GOOSE Input Command
incoming GOOSE message
GOOSE virtual input 9 - provides the Quality attributes of any data object in an
1736 Quality VIP 9 GOOSE Input Command
incoming GOOSE message
GOOSE virtual input 10 - provides the Quality attributes of any data object in an
1737 Quality VIP 10 GOOSE Input Command
incoming GOOSE message
GOOSE virtual input 11 - provides the Quality attributes of any data object in an
1738 Quality VIP 11 GOOSE Input Command
incoming GOOSE message
GOOSE virtual input 12 - provides the Quality attributes of any data object in an
1739 Quality VIP 12 GOOSE Input Command
incoming GOOSE message
GOOSE virtual input 13 - provides the Quality attributes of any data object in an
1740 Quality VIP 13 GOOSE Input Command
incoming GOOSE message
GOOSE virtual input 14 - provides the Quality attributes of any data object in an
1741 Quality VIP 14 GOOSE Input Command
incoming GOOSE message
GOOSE virtual input 15 - provides the Quality attributes of any data object in an
1742 Quality VIP 15 GOOSE Input Command
incoming GOOSE message
GOOSE virtual input 16 - provides the Quality attributes of any data object in an
1743 Quality VIP 16 GOOSE Input Command
incoming GOOSE message
GOOSE virtual input 17 - provides the Quality attributes of any data object in an
1744 Quality VIP 17 GOOSE Input Command
incoming GOOSE message
GOOSE virtual input 18 - provides the Quality attributes of any data object in an
1745 Quality VIP 18 GOOSE Input Command
incoming GOOSE message
GOOSE virtual input 19 - provides the Quality attributes of any data object in an
1746 Quality VIP 19 GOOSE Input Command
incoming GOOSE message
GOOSE virtual input 20 - provides the Quality attributes of any data object in an
1747 Quality VIP 20 GOOSE Input Command
incoming GOOSE message
GOOSE virtual input 21 - provides the Quality attributes of any data object in an
1748 Quality VIP 21 GOOSE Input Command
incoming GOOSE message
GOOSE virtual input 22 - provides the Quality attributes of any data object in an
1749 Quality VIP 22 GOOSE Input Command
incoming GOOSE message
Appendix C-45
Appendix C DDB Signals
GOOSE virtual input 24 - provides the Quality attributes of any data object in an
1751 Quality VIP 24 GOOSE Input Command
incoming GOOSE message
GOOSE virtual input 25 - provides the Quality attributes of any data object in an
1752 Quality VIP 25 GOOSE Input Command
incoming GOOSE message
GOOSE virtual input 26 - provides the Quality attributes of any data object in an
1753 Quality VIP 26 GOOSE Input Command
incoming GOOSE message
GOOSE virtual input 27 - provides the Quality attributes of any data object in an
1754 Quality VIP 27 GOOSE Input Command
incoming GOOSE message
GOOSE virtual input 28 - provides the Quality attributes of any data object in an
1755 Quality VIP 28 GOOSE Input Command
incoming GOOSE message
GOOSE virtual input 29 - provides the Quality attributes of any data object in an
1756 Quality VIP 29 GOOSE Input Command
incoming GOOSE message
GOOSE virtual input 30 - provides the Quality attributes of any data object in an
1757 Quality VIP 30 GOOSE Input Command
incoming GOOSE message
GOOSE virtual input 31 - provides the Quality attributes of any data object in an
1758 Quality VIP 31 GOOSE Input Command
incoming GOOSE message
GOOSE virtual input 32 - provides the Quality attributes of any data object in an
1759 Quality VIP 32 GOOSE Input Command
incoming GOOSE message
GOOSE virtual input 10- indicates if the GOOSE publisher responsible for
1769 PubPres VIP 10 GOOSE Input Command
publishing the data that derives a virtual input is present.
GOOSE virtual input 11- indicates if the GOOSE publisher responsible for
1770 PubPres VIP 11 GOOSE Input Command
publishing the data that derives a virtual input is present.
GOOSE virtual input 12- indicates if the GOOSE publisher responsible for
1771 PubPres VIP 12 GOOSE Input Command
publishing the data that derives a virtual input is present.
GOOSE virtual input 13- indicates if the GOOSE publisher responsible for
1772 PubPres VIP 13 GOOSE Input Command
publishing the data that derives a virtual input is present.
GOOSE virtual input 14- indicates if the GOOSE publisher responsible for
1773 PubPres VIP 14 GOOSE Input Command
publishing the data that derives a virtual input is present.
GOOSE virtual input 15- indicates if the GOOSE publisher responsible for
1774 PubPres VIP 15 GOOSE Input Command
publishing the data that derives a virtual input is present.
Appendix C-46
Appendix C DDB Signals
GOOSE virtual input 17- indicates if the GOOSE publisher responsible for
1776 PubPres VIP 17 GOOSE Input Command
publishing the data that derives a virtual input is present.
GOOSE virtual input 18- indicates if the GOOSE publisher responsible for
1777 PubPres VIP 18 GOOSE Input Command
publishing the data that derives a virtual input is present.
GOOSE virtual input 19- indicates if the GOOSE publisher responsible for
1778 PubPres VIP 19 GOOSE Input Command
publishing the data that derives a virtual input is present.
GOOSE virtual input 20- indicates if the GOOSE publisher responsible for
1779 PubPres VIP 20 GOOSE Input Command
publishing the data that derives a virtual input is present.
GOOSE virtual input 21- indicates if the GOOSE publisher responsible for
1780 PubPres VIP 21 GOOSE Input Command
publishing the data that derives a virtual input is present.
GOOSE virtual input 22- indicates if the GOOSE publisher responsible for
1781 PubPres VIP 22 GOOSE Input Command
publishing the data that derives a virtual input is present.
GOOSE virtual input 23- indicates if the GOOSE publisher responsible for
1782 PubPres VIP 23 GOOSE Input Command
publishing the data that derives a virtual input is present.
GOOSE virtual input 24- indicates if the GOOSE publisher responsible for
1783 PubPres VIP 24 GOOSE Input Command
publishing the data that derives a virtual input is present.
GOOSE virtual input 25- indicates if the GOOSE publisher responsible for
1784 PubPres VIP 25 GOOSE Input Command
publishing the data that derives a virtual input is present.
GOOSE virtual input 26- indicates if the GOOSE publisher responsible for
1785 PubPres VIP 26 GOOSE Input Command
publishing the data that derives a virtual input is present.
GOOSE virtual input 27- indicates if the GOOSE publisher responsible for
1786 PubPres VIP 27 GOOSE Input Command
publishing the data that derives a virtual input is present.
GOOSE virtual input 28- indicates if the GOOSE publisher responsible for
1787 PubPres VIP 28 GOOSE Input Command
publishing the data that derives a virtual input is present.
GOOSE virtual input 29- indicates if the GOOSE publisher responsible for
1788 PubPres VIP 29 GOOSE Input Command
publishing the data that derives a virtual input is present.
GOOSE virtual input 30- indicates if the GOOSE publisher responsible for
1789 PubPres VIP 30 GOOSE Input Command
publishing the data that derives a virtual input is present.
GOOSE virtual input 31- indicates if the GOOSE publisher responsible for
1790 PubPres VIP 31 GOOSE Input Command
publishing the data that derives a virtual input is present.
GOOSE virtual input 32- indicates if the GOOSE publisher responsible for
1791 PubPres VIP 32 GOOSE Input Command
publishing the data that derives a virtual input is present.
1792 to 2015 Unused Unused
2016 Timer in 17 PSL Input to Auxiliary Timer 17
2017 Timer in 18 PSL Input to Auxiliary Timer 18
2018 Timer in 19 PSL Input to Auxiliary Timer 19
2019 Timer in 20 PSL Input to Auxiliary Timer 20
2020 Timer in 21 PSL Input to Auxiliary Timer 21
2021 Timer in 22 PSL Input to Auxiliary Timer 22
2022 Timer in 23 PSL Input to Auxiliary Timer 23
2023 Timer in 24 PSL Input to Auxiliary Timer 24
2024 Timer in 25 PSL Input to Auxiliary Timer 25
2025 Timer in 26 PSL Input to Auxiliary Timer 26
2026 Timer in 27 PSL Input to Auxiliary Timer 27
2027 Timer in 28 PSL Input to Auxiliary Timer 28
Appendix C-47
Appendix C DDB Signals
Appendix C-48
PXXX
Product Description
Alstom Grid
www.alstom.com
GRID