Performance of Coanda-Effect Screens in A Cold Climate
Performance of Coanda-Effect Screens in A Cold Climate
net/publication/273024525
CITATIONS READS
2 1,911
3 authors, including:
Some of the authors of this publication are also working on these related projects:
All content following this page was uploaded by Hanne Nøvik on 01 August 2016.
Abstract
This study assesses the performance of a Coanda-effect intake screen for a small hydropower plant in winter operation. The
unique self-cleaning screen is making use of the Coanda-effect for withdrawal of water and consists of panels with 2 mm wide
horizontal wedge wires with 1 mm spacing; underneath the screen is a canal conveying water to the power plant intake. A broad
understanding of the winter performance of the Coanda-effect screen in a cold climate was obtained from experiments in a
frost laboratory and monitoring program consisting of hydrological measurements, an online web camera and field observations
of an intake structure in Norway. Different freezing processes were observed, and critical hydrological conditions for the ice
blockage of the Coanda-Effect screen were evaluated. The Coanda-effect screen performed well under all normal conditions
without snow or ice, and was entirely self-cleaning. Two main types of ice formation on the screen were observed; Type I where
frazil ice particles stick to the screen wedge wires, but with remaining openings underneath the ice, and Type II where solid ice
form between the wedge wires at very low temperatures. There were some periods during the winter of 2011/2012 in which
there was a reduced intake capacity or complete blockage from ice. All of the complete ice blockage events were related to
supercooled water just upstream from the screen, thus indicating frazil ice, in addition to a temperature on the intake screen and
in the air below 0o C. The screen reopened without any operational measures after all events of ice blockages, and the intake
performed well even during periods with solid ice cover over the screen, whereby water entered the intake through the screen
wedge wires underneath the ice cover. In spite of some periods with reduced intake capacity, the intake screen is considered to
have performed reasonably well in a cold climate.
Keywords: Intake Screen, Frazil Ice, Hydropower
Research Methodology
Figure 2: Model of the Coanda-effect screen in the frost
The freezing processes on the Coanda-effect screen are laboratory. Water enters through the screen in a 15-20mm
studied in a frost laboratory, by field visits, and a contin- long wet zone just downstream from the acceleration plate.
uously filming web camera at Dyrkorn hydropower plant.
The critical hydrological conditions for ice blockage and
reduced capacity of the Coanda-effect screen are evaluated produced slush mixture was comparable enough to passive
based on measurements from the winter of 2011/2012. We frazil slush.
have defined a reduced intake capacity for the Coanda- Before adding the snow slush mixture to the tank, the in-
effect intake screen to be a combination of a reduction in take model with a continuously running pump was set in
power production, with > 10%, and an increased mea- the frost laboratory maintained to a preselected Ta in the
sured water discharge in the river, with > 10%, during the range between −3 ◦ C to −14 ◦ C. The temperature on the
same period. In order to find causal links between hydro- screen, Ts , and the water temperature, Tw , were measured
logic conditions and the performance of the Coanda-effect with an ASYC II MX 54 thermometer, with an accuracy of
screen, measurements of temperatures of air, water tem- ±0.5 ◦ C, hence supercooled water was not detected. The
perature and screen temperatures were logged simultane- wet zone where water enters through the screen was ap-
ously with observations of the ice coverage of the intake proximately 15 mm high. While the pump was running, the
pond, recorded precipitation, water discharge in the river Tw was close to 0 ◦ C, whereas the Ts , was closer to the
and power production. Ta in the frost laboratory. For each test, 0.0045 m3 of the
slush mixture was added to the upper tank of the test rig
and stirred with a hand blender, and the suspended ice then
Laboratory Test approached the screen along with the water. The freezing
The freezing processes on the Coanda-effect screen was as- processes on the Coanda-effect screen were observed and
sessed in a model intake located in a frost laboratory at the formation of the ice accumulation on the screen was
NTNU. The physical model consisted of a 300-mm-wide described. The entire screen was inspected by visual obser-
and 400-mm-high full scale Coanda-effect screen with a vations and eventual ice particles between the screen wedge
1 mm wedge wire spacing supplied by Dulas Ltd, as well wires were assessed.
as a circulating water supply system, see Figure 2. A pump
with capacity of 0.002 m3 /s circulated water from the lower Field Monitoring Program
tank of 0.04 m3 to the upper 0.008 m3 tank, and the water
flow through the wedge wires in a 15 − 20 mm long wet The Dyrkorn SHPP is located next to the Storfjord along the
zone just downstream from the acceleration plate. western coast of Norway, and utilizes a net head of 220 m,
Instead of making frazil ice directly from supercooled wa- with the intake structure situated at elevation 225 masl.
ter, a slush mixture of snow and water with ice particle sizes The installed Coanda-effect screen from Dulas Ltd is 1.2 m
in the range from 1 − 10 mm was prepared. The ice par- high, with wedge wires openings of 1 mm and a guaranteed
ticles in the snow-water slush mixture were not as adhe- capacity of 0.14 m3 /s/m. 15 modules with a width of 1 m
sive as active frazil ice discs. But as the ice particles in have been installed, providing a total theoretical capacity of
the slush mixture stuck to the Coanda-effect screen during 2.1 m3 /s, where as the design discharge at Dyrkorn SHPP
the experiments, it was assumed that the behavior of the is 1.5 m3 /s. The locations of all the temperature measure-
Results
ments and the web camera are shown in Figure 3. The tem-
peratures in the air, Ta , and water, Tw , were logged using a Two main types of ice formation on the Coanda-effect in-
Vemco Minilog-II-T (Vemco 2011). The sampling interval take screen were observed, and are described below. Criti-
was specified at 30 minutes, and the outdoor temperature, cal conditions for ice-blockage and reopening of the screen
Ta , was measured at the gate housing wall. The logger for was then assessed.
the air temperature inside the intake chamber, Tac , was lo-
cated underneath the Coanda-effect screen, attached to the Freezing Process of the Coanda-effect Screen
concrete wall.
The water temperature, Tw , in the river was measured and Field and laboratory observations indicate that there are
logged upstream from the screen with a high accuracy in or- two main types of ice clogging of the Coanda-effect intake
der to identify periods of supercooling. A temperature sen- screen. Type I clogging occurs when soft and wet ice slush
sor, SeaBird 39, with an accuracy of ±0.002 ◦ C (SeaBird- clog by adhesion to the intake screen, Figure 4a). The ice
Electronics 2011), was located on the upstream side of particles sticks to the top surface of the screen and do not
the weir, 200 mm below the highest regulated water level enter between the screen wedge wires; hence the screen is
(HRWL), and the sampling interval was set to 15 min. more or less open underneath the soft ice cover. Type II
The temperature on the screen wedge wires, Ts , was mea- clogging is when the screen is so cold that solid ice forms
sured with a thermistor sensor attached to the downstream between the wedged wires, Figure 4b). Type II clogging
side of the screen wires and logged with a Comark EV was not observed in field during the winter of 2011/2012.
N2012 data logger located inside the gate housing. The The ice clogging was of Type I for all of the experiments
accuracy of the sensor was ±0.5 ◦ C (Comark 2011), and in the frost laboratory with air temperature, Ta , in the range
foam insulation was placed between the thermistor and the of −2.9 ◦ C to −6.8 ◦ C and screen temperature, Ts , in the
air. The measurements of Ts were taken on the upper part range of −0.4 ◦ C to −2.4 ◦ C. The ice particles started to
of the screen, and were most likely influenced by the water, build up on the wedge wires, just downstream from the
while the temperature on the lower part of the screen is ex- 15 − 20 mm long wet zone. Some ice was pushed further
pected to be lower than in the wet zone. Unfortunately, the down on the screen as the accumulated ice grew higher, Fig-
sensor cable was torn off by ice the 22nd of December 2011 ure 4a). At the end of the experiment, the ice slush accumu-
during an ice blockage event. lated up to a thickness of between 40−50 mm, with less ice
A web camera, type AXIS 214 PTZ, was mounted on the further down on the screen. The capacity of the screen was
gate house for a continuous observation of the Coanda not noticeably reduced. By inspection of the rear side of the
screen and the intake pond. There was no continuously screen, only a few ice particles were observed between the
recording, but a manual screen shot of the intake pond was screen wedge wires. Most of the ice particles were laying
taken daily for an estimation of the intake pond ice cover- on the top surface of the screen. After the test, the accumu-
age. Because of a lack of light, no pictures were taken at lated ice was removed and water was poured over the screen
Figure 5: Active frazil ice clogging of Type I at the Coanda-effect screen in field. The spacing between the screen wedge
wires are 1 mm. a) The frazil ice particles stick to the top surface of the screen wires. b) There are no frazil ice particles
between the screen wires underneath the removed ice.
water flow momentum and the shear forces and uplifting is when the screen is so cold that solid ice forms between
forces from hydraulic pressure on the ice particles. the wedged wires. Based on laboratory experiments, as
Based on the data received in field, the reopening of the long as Ta > −7 ◦ C and Ts > −2.5 ◦ C, the ice forma-
Coanda-effect screen, which is confirmed by the startup of tion will take place mainly above the wedge wires, a Type I
the SHPP, took place without any intervention for all the ice blockage. According to Andersson and Daly (1992), the
complete ice blockage events, and for most of the complete initialization of ice accumulation is at the upstream side of
ice blockage cases, 1 − 10 h after the last measurement of a screen bar, and the ice will extend upstream, increase in
supercooled water, Table 1. For some of the ice blockage width until the ice creates a bridge between two successive
events, supercooled water was measured up to 10 hours af- bars. Their finding correspond well with Type I ice clog-
ter the screen was reopened. It can therefore be deduced ging. The Coanda-effect screen was completely self clean-
that once the frazil ice production stops, after an event of ing and the screen reopened without any manual interven-
ice clogging of Type I, the screen reopens without any in- tion after all observed ice blockage events in field. Frazil ice
tervention since the spacing between the wedge wires are in combination with air and screen temperature below 0 ◦ C
free from ice. The intake may also start performing again is critical for ice to affect the intake screen flow capacity. If
if an ice cover protects the screen from more approaching frazil ice reaches screen wedge wires with a Ts < 0 ◦ C, the
suspended ice and the clogging ice particles are removed intake may become blocked, even though no ice particles
by erosion or melting underneath an ice cover. The ice may enter between the screen wires. As long as the frazil ice
also be washed away by an increased water discharge in the formation in the river stops or suspended ice is prevented
river exceeding the screen capacity. from reaching the screen, the Coanda-effect intake screen
will reopen and start performing in a cold climate.
In order to improve the performance of a Coanda-effect in-
Conclusions take screen in a cold climate, it is recommended to pro-
vide for an early stage solid ice cover over the screen,
This study reveals that the Coanda-effect intake screen per- by placing a fabric or something similar above the boul-
formed well in a cold climate, even during periods with a der bars, may be extended upstream from the weir. A
solid ice cover over the screen, water entered the intake solid ice cover may reduce the amount of frazil ice reach-
through the screen wedge wires underneath the ice, as re- ing the screen and hence a Type I clogging. An ice cover
ported by ENTEC (1998). But ice formation may temporar- will also protect the screen from condensation and a Type
ily reduce the intake flow capacity of the screen or lead to II ice blocking. It is also a theoretical possibility of in-
complete ice blockage. Two main types of ice clogging of stalling a heating system to the screen wires. Previous
the Coanda-effect intake screen has been observed. Type studies on intake screen heating systems suggest a required
I clogging occurs when soft and wet ice slush clog by ad- heat of 2 − 8 kW/m2 in order to retard the frazil ice ad-
hesion to the top surface of the screen and no ice particles hesion (Logan 1974). Heat is not sufficient to stop larger
enter between the screen wedge wires. Type II clogging