Conductor Design:
- Number, diameter and type of Core n, mm 1 5.97 R CC
- Number, equiv. round wire diameter and type of wire in layer 1 n, mm 6 3.51 T Al
- Number, equiv. round wire diameter and type of wire in layer 2 n, mm 10 3.49 T Al
- Diameter tolerance of Core mm ± 0.06
- Lay ratio of aluminium D 10 - 16
- Lay ratio of outer layer D 10 - 14
- Overall diameter mm 15.65
Mechanical Properties:
▪ Aluminium
2
- Nominal Cross-sectional area mm 153.7
- Nominal Mass per unit length kg/km 425.6
- Minimum tensile strength, aluminium wire MPa 58.6
- Conductivity % IACS 63
▪ Composite Core
2
- Nominal Cross-sectional area mm 28
- Nominal Mass per unit length kg/km 54
- Rated Tensile Strength kN 60.4
-6
- Coefficient of linear expansion /°C 1.61 x 10
- Modulus of elasticity MPa 117000
▪ Total of Conductor
2
- Nominal Cross-sectional area mm 181.7
- Nominal Mass per unit length kg/km 479.6
- Rated Tensile Strength kN 64
Electrical Properties:
- DC resistance at 20 °C (maximum) Ohm/km 0.1861
- Current Carrying Capacity at maximum continuous operating temperature *
A 754
(Calculated)
- Maximum continuous operating temperature °C 175
CC: Composite Core (Carbon-Glass Fiber); Al: Aluminium 1350-O; R: Round; T: Trapezoidal; D: Diameter after stranding