Smart Relay: Ordering Information

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

Smart Relay TM

• Supports up to 48 I/Os pre-selected parameters of functional blocks,


(32 Digital Inputs & 16 Digital Outputs) viewing I/O status and programming on the device
• 250 lines of ladder programming • PC software for programming, online & offline
• 16 soft text messages, Time Switches, simulation, documentation & printing
Compare Counters, Timers, Counters & • Designed for use in automation for
12 Analog functions, 4 Hour Meters commercial & Industrial sectors
• DST Feature Available • Multi level password and run time
• Backlit LCD Screen for display & modification of parameter save facility

Ordering Information
Cat. No. Description Cat. No. Description
G7DDT11 110 - 240 VAC, Genie Nx Base Module G7DDT10E 110 - 240 VAC, Genie Nx Extension Module
G7DDT11B 110 - 240 VAC, Genie Nx Base Module, G8DDT10E 12 - 24 VDC, Genie Nx Extension Module
Without LCD Display
G9DDT10E 24V AC/DC, Genie Nx Extension Module
G8DDT11 12 - 24 VDC, Genie Nx Base Module
G9ADT10E 24V AC/DC, Genie Nx Base Module With 2 Analog I/P
G8DDT11B 12 - 24 VDC, Genie Nx Base Module, Without LCD Display (for 24V DC only), Extension Module
G9DDT11 24V AC/DC, Genie Nx Base Module GFDNN3M Memory Card
G9DDT11B 24V AC/DC, Genie Nx Base Module, Without display GFDNN2S RS 232 Serial Communication Cable
G9ADT11 24V AC/DC, Genie Nx Base Module With 2 Analog I/P GFDNN1 USB Cable
(for 24V DC only)
GNXNN2 Genie Nx Software supplied on CD-ROM compatible with
G9ADT11B 24V AC/DC, Genie Nx Base Module With 2 Analog I/P Windows 7, Windows 8, Windows 8.1 & Windows 10
(for 24V DC only), Without display

UL approval is not applicable for G9 Cat. Nos.


Note: 10 Series Cat. No. available on request.

104
Smart Relay TM

Cat. No. G7DDT11 G8DDT11


Parameters
Supply Voltage ( ) 110 - 240 VAC 12 - 24 VDC
Supply Variation -20% to +10% (of )
Frequency 50/60 Hz
Power Consumption 5W
Digital Input 8 6
Analog Input NA 2 (Can be used as Digital Inputs)
Digital Input Range (0 - 50 VAC) OFF, (80 - 265 VAC) ON (0 - 4 VDC) OFF, (8 - 26.4 VDC) ON
Analog Input Range NA 0 to 10 VDC
Relay Output 4 ‘NO’
Digital Contact Rating 8A @ 240 VAC / 5A @ 30 VDC (Resistive)
Output Electrical Life 105
7
Mechanical Life 10
AC - 15 Rated Voltage (Ue): 120/240 V, Rated Current (Ie): 3.0/1.5 A
Utilization Category
DC - 13 Rated Voltage (Ue): 24/125/250 V, Rated Current (Ie): 2.0/0.22/0.1 A
I/O Extensions (Max.) 3
Power Reserve (For Clock Only) 7 yrs. (at -10oC to 55oC)
Modbus Communication Yes (RTU) (Slave)
DST Settable
Lines for Ladder Programming 250
Timers 16 (ON Delay, Interval, Cyclic ON-OFF, OFF Delay)
Counters 16 (Up / Down, Retentive selectable)
Time Switches 16 (Weekly / Daily)
Function
Blocks Compare Counters 16
Analog Functions NA 12
Soft Text Messages 16 (Priority Driven)
Auxiliary Relays 64
Hour Meter 4
Operating Temperature -10O C To + 55O C
Storage Temperature -20O C To + 70O C
Humidity (Non Condensing) 35 to 85% (Rh)
Enclosure Flame Retardant UL 94-V0
Dimension (W x H x D) (in mm) 72 X 90 X 65
Weight (unpacked) Approx. 230 g
Mounting Base / DIN Rail
Degree of Protection IP 20 for Terminals, IP 40 for Enclosure

Certification RoHS Compliant


LISTED

EMI / EMC
Harmonic Current Emissions IEC 61000-3-2
ESD IEC 61000-4-2
Radiated Susceptibility IEC 61000-4-3
Electrical Fast Transients IEC 61000-4-4
Surges IEC 61000-4-5
Conducted Susceptibility IEC 61000-4-6
Voltage Dips & Interruptions (AC) IEC 61000-4-11
Voltage Dips & Interruptions (DC) IEC 61000-4-11
Conducted Emission CISPR 14-1
Radiated Emission CISPR 14-1

Environmental
Cold Heat IEC 60068-2-1
Dry Heat IEC 60068-2-2
Vibration IEC 60068-2-6
Repetitive Shock IEC 60068-2-27
Non-Repetitive Shock IEC 60068-2-27

105
Smart Relay TM

• Nx-Comm RS 485 Module

Ordering Information
Cat. No. Description
G7XDTR4 110 - 240 VAC, RS 485 Communication Module
G8XDTR4 12 - 24 VDC, RS 485 Communication Module

106
Smart Relay TM

Cat. No. G7XDTR4 G8XDTR4


Parameters
Supply Voltage ( ) 110 - 240 VAC 12 - 24 VDC
Input TTL Level
Output RS 485 Protocol (Two wires, D +, D -)
Number of Nodes 32 Standard unit loads
Isolation voltage 2000 Vrms
Baud Rate 300, 600, 1200, 2400, 4800, 9600
Operating Temperature -10°C to + 55°C
Storage Temperature -20°C to + 70°C
Modbus Communication Yes (RTU) (Slave)
LED Indications Red LED's for Tx & Rx. Green LED for Power indication.

Certification RoHS Compliant


LISTED

Weight (unpacked) 80 g 84 g

MOUNTING DIMENSION (mm)


1.5

100.0 C/C

90.0
68.0
45.0
100.0 C/C

90.0
45.0

49.4
Ø 4.2 60.0
Ø 4.2 65.0 36.0
72.0
G7XDTR4, G8XDTR4
G7DDT11, G7DDT11B, G8DDT11, G8DDT11B, G7DDT10E, G8DDT10E

CONNECTION DIAGRAM
FUSE
L
FUSE 1 UP TO 3 EXTENSION
INPUTS
MODULES N
AC
EXT ADDITIONAL SUPPLY
SUPPLY INPUTS INPUTS
INPUT
L N 1 2 3 4 5 6 7 8 C1 C2 L N 1 2 3 4 5 6 7 8 C1 C2
110 - 240 V AC INPUT
8 X AC
110 - 240 V AC INPUT 110 - 240 V AC INPUT
8 X AC 8 X AC

X
DEL ALT

X
PROGRAM
1 2 3 4 5 6 7 8 RUN
DEL ALT
PROGRAM PARAMETERS
Z4
IP UTILITIES
RUN OP
A

PARAMETERS Z1
Z2
Z3 1 2 3 4
B

UTILITIES SEL C

ESC OK

Extension Module

MEMORY SERIAL OUTPUT OUTPUT


CARD INTERFACE SERIAL
CABLE 4 x RELAY / 8A 4 x RELAY / 8A D1 D2 INTERFACE

GFDNN3M GFDNN2S
CABLE Q1 Q2 Q3 Q4

TWO WIRE HALF


Q1 Q2 Q3 Q4 OP1 OP2 OP3 OP4 DUPLEX RS 485 BUS
ADDITIONAL OUTPUTS
OUTPUTS
OUTPUTS

TERMINAL TORQUE & CAPACITY

0.54 N.m (6 Lb.in)


Ø 3.5
1 x 2.5 mm2 Solid Wire/Stranded
AWG 1 x 24 to 12

107
Smart Relay TM

FEATURES
Programming:
Programming can be carried out independently using the keys on the Genie-NX base module with
the help of ladder diagram or on a PC, using "G-Soft NX." software.

LCD Backlighting:
Backlight of the LCD display is present for a minimum 15 seconds whenever the device is powered
ON or a key is pressed on the base module. The backlight can also be configured to be permanently
ON or permanently OFF by configuring the "Device Utilities" option in the device menu or by using
the G-Soft NX application software.

Memory Card:
Genie-NX has a Program Transfer feature, which allows programs to be transferred or copied into
another Genie-NX with the help of memory card. This feature enables quick copy of the programs
without the use of a laptop or a PC.

I/O Extensions:
User can connect a maximum of 3 Extension Modules to the Genie-NX base module & each
Extension Module has 8 inputs and 4 outputs, so we can expand up to 48 I/O extensions if
necessary via the Genie-NX. Expansions are made in daisy chain fashion.

Communication Module:
A module for communication on the Modbus network is available, which is called "NX-Comm "to
facilitate communication of the logic relay over a 2 wire half duplex RS 485 link. Modules are
powered by 110- 240 VAC or 12- 24 VDC power supplies. The base module can be connected to
this communication interface by means of the cable and the communication takes place via the
NX-Comm. on the RS 485 link.

APPLICATIONS
• HVAC Controls
• Machine Controls involving Motor, Pump and Valve
• Operational Monitoring systems like Access control,
Vehicle Control Monitoring, Baggage handling etc.
• Materials handling Equipments, Conveyor systems and Elevators
• Exhaust and Filtering Systems
• Water-treatment plants
• Printing and Packaging Machines
• Ancillary equipments in Textile and Plastic Industry
• Interior and Exterior Lighting Control
• Door, Gate, Shutter, Sun blinds and Awning control
• Irrigation Control Systems
• Automation of Compressors and Pumps for Air Conditioning requirements

108

You might also like