Client: Nlcil Subject: Quality Assurance Plan For Side Drain (Rev-00)
Client: Nlcil Subject: Quality Assurance Plan For Side Drain (Rev-00)
CLIENT: NLCIL
SUBJECT: QUALITY ASSURANCE PLAN FOR SIDE DRAIN (REV- 00)
Records to Agency
Sl. No Item Category Type / Method of check Extent of Reference Acceptance Format of record be Remarks
check document norms
furnished CONTRACTOR CLIENT
A B C D E F G H I J K
1 Survey
Co-ordinates / Levels of
a) Bench Mark recoding of Critical Visual checks 100% Approved Drg. As per approved Drg. Joint Record Yes P W Site Verification/Review
all effected working area
Checking of Calibration
Verifiaction of Calibartion
c) report for both machine Critical 100% Approved Drg. As per approved Drg. Calibration report Yes External Agency W Site Verification/Review
certifiacte
& prizom
2 Surface dressing
Specifications/ Specifications/
a) Checking for layout Major Dimensional check 100% Joint Records Yes P RW Site Verification/Review
Methodology Methodology
Disposal/proper stacking
Specifications/ Specifications/
d) of breaking materials in Minor Visual Checks 60% -- No P RW Site Verification/Review
Methodology Methodology
demarked area.
Checking of vibrating by
Site Verification/Review
neddle / plate Vibrator, if Specifications/
b) Critical Visual Check 80% As per IS 2505/2506 -- No P RW & minimum 14 days
reqd. as per site situation Methodology
Curing reqd.
basis
Checking vibrating
needle/plate vibrator Specifications/
b) Critical Visual Check 100% As per IS 2505/2506 -- No P RW Site Verification/Review
before & during the Methodology
pouring of concrete
8 Brick Work
c) Check for final level Critical Visual Checks 100% Drawings Drawings - Yes P RW Site Verification/Review
Legends: P PERFORM
R RANDOM
W WITNESS
RW RANDOM WITNESS
RM RANDOM MONITORING
MPDD MODIFIED PROCTOR DRY DENSITY
SPDD STANDARD PROCTOR DRY DENSITY