Balanced Faults Notes
Balanced Faults Notes
By
Dr. E. Matlotse
Introduction
• Fault studies are a fundamental instance of
power system analysis.
• Problem entails determining of bus voltages and
line currents during different types of faults.
• Faults are segregated into 3-φ balanced faults
and unbalanced faults
• Various types of unbalanced faults are line-to-
ground fault, line-to-line fault and double line-to-
ground fault.
Introduction
• Information sourced from fault studies are
utilised for proper relay setting and
coordination.
• 3-φ balanced fault information is used to
select and set phase relays, while the line-to-
ground fault information is used for ground
relays.
• Also, fault studies are used to obtain the
rating of the protective switchgears.
Balanced Three-Phase Fault
• This fault is the simultaneous short circuit
across all the three phases.
• It occurs less often, but it is the most severe
type of fault.
• Since the network remains balanced during
this type of fault, the problem is solved on a
per-phase basis.
• Other 2 phases carry identical currents except
for the phase shift.
Balanced Three-Phase Fault
• A fault represent a structural network change
equivalent with that caused by the addition of
an impedance at the place of fault.
( j 0.4)( j 0.4)
Z3 j 0.1 pu
j1.6
Solution
The Y network is
Solution
Combining the parallel branches, Thevenin’s
impedance is
( j 0.4)( j 0.6)
Z 33 j 0.1 j 0.34 pu
j 0.4 j 0.6
The resulting circuit becomes,
Solution
Therefore, the fault current is
V3 ( F ) 1
I3 (F ) j 2.0 pu
Z 33 Z f j 0.34 j 0.16
Current divisions between the two generators
are
j 0.6
I G1 ( j 2.0) j1.2 pu
j 0.4 j 0.6
j 0.4
IG2 ( j 2.0) j 0.8 pu
j 0.4 j 0.6
Solution
Bus Voltage Changes
V1 ( F ) V3 ( F ) 0.76 0.32
I13 ( F ) j1.1 pu
z13 j 0.4
V2 ( F ) V3 ( F ) 0.68 0.32
I 23 ( F ) j 0.9 pu
z 23 j 0.4
Short-Circuit Capacity (SSC)
• SCC at a bus is a common measure of the
strength of a bus.
• SCC or the short-circuit MVA at bus k is
defined as the product of the magnitudes of
the rated bus voltage and the fault current.
• SCC is used to determine the dimension of a
busbar and the interrupting capacity of a
circuit breaker.
Short-Circuit Capacity (SSC)
based on the above definitions, the SCC at bus
k is given by
SCC 3VLK I K ( F ) x10 3 MVA (1)
where: line-to-line VLK is in kV
I K (F ) is in Amperes
The symmetrical 3-φ fault current in pu is
VK (0)
I K (F ) (2)
X KK
Short-Circuit Capacity (SSC)
where: VK (0) is the per unit prefault bus voltage
and X KK is the per unit reactance to the point
of fault. The base current3 is given by
S x10
IB B (3)
3VB
where: S B is the base MVA and VB is the line-
to-line base voltage in kV. The fault current in
amps is I (F ) I (F ) I
K K pu B
VK (0) S B x10 3
(4)
X KK 3VB
Short-Circuit Capacity (SSC)
Substituting for IK(F) in (4) into (1) yields
V (0) S BVL
SCC K (5)
X KK VB
If the base voltage is equal to the rated
voltage, i.e. VL = VB
V (0) S B
SCC K (6)
X KK
The prefault bus voltage is usually assumed to
be 1 per-unit and we therefore obtain from (6)
Short-Circuit Capacity (SSC)
the following approximate formula for the
short-circuit capacity
SB
SCC MVA (7)
X KK
Systematic Fault Analysis Using Bus
Impedance Matrix
Figure 1:
Systematic Fault Analysis Using Bus
Impedance Matrix
• Consider a typical bus of an n-bus power system
network as shown in figure 1.
• System is assumed to be operating under
balanced condition and, therefore, a per-phase
circuit model is used.
• Each machine is represented by a constant
voltage source behind a proper reactance.
• Transmission lines are represented by their
equivalent π model and all impedances are
expressed in per-unit on a common MVA base.
Systematic Fault Analysis Using Bus
Impedance Matrix
• A balanced 3-φ fault is to be applied at bus K
through impedance Zf.
• Prefault bus voltages are obtained from the
power flow solution and are represented by
the column vector
(1)
Systematic Fault Analysis Using Bus
Impedance Matrix
The bus load is represented by a constant
impedance evaluated at the prefault bus
voltage 2
Vi (0)
Z iL (2)
S L*
• Changes in the network voltage caused by the
fault with impedance Zf is equivalent to those
caused by the added voltage VK(0) with all
other sources short-circuited.
Systematic Fault Analysis Using Bus
Impedance Matrix
• Zeroing all voltage sources and representing
components and loads by their appropriate
impedances, we obtain the Thevenin’s circuit as
shown in figure 2.
Figure 2
Systematic Fault Analysis Using Bus
Impedance Matrix
The bus voltage changes caused by the fault in
this circuit are represented by the column vector
(3)
(8)
or
(12)
• Since we have only one single non-zero
element in the current vector, the Kth
equation in (12) becomes
V ( F ) V (0) Z I ( F ) (13)
K K KK K
Systematic Fault Analysis Using Bus
Impedance Matrix
• Also, from the Thevenin’s circuit shown in
fig.2, we have
VK ( F ) Z f I K ( F ) (14)
• For a solid fault, Z f 0 and VK ( F ) 0 .
Substituting for VK (F ) from (14) into (13) and
solving for the faulted current, we get
VK (0)
IK
Z Z
(15)
KK f
Systematic Fault Analysis Using Bus
Impedance Matrix
• Thus, for a fault at bus K, we need only the ZKK
element of the bus impedance matrix.
• This element is the Thevenin’s impedance as
viewed from the faulted bus.
• Also, writing the ith equation in (12) in terms
of its elements, we have
Vi ( F ) Vi (0) ZiK I K ( F ) (16)
Systematic Fault Analysis Using Bus
Impedance Matrix
• Substituting for IK(F), bus voltage during the
fault at bus i becomes
Z iK
Vi ( F ) Vi (0)
Z KK Z f
VK (0) (17)