Style 28 Coupling: Applied Vic-Ring System
Style 28 Coupling: Applied Vic-Ring System
07
Style 28 Coupling
PRODUCT DESCRIPTION
The Victaulic Style 28 Coupling is a heavy duty coupling for use with Vic-Ring
Adapters to join pipes of non-standard dimensions or where internal wear or
corrosion is of concern and roll or cut grooving are not acceptable.
MATERIAL SPECIFICATIONS Housings: Six segments per coupling (20" size has 4 segments)
• Material:
Ductile Iron conforming to ASTM A536 Grade 65-45-12
• Finish:
Orange enamel
Gaskets:
• Grade "L" Silicone
Temperature range –30°F to +350°F/–34° C to +177°C. Recommended for dry heat,
air without hydrocarbons to +350°F/+177°C and certain chemical services.
Bolts/Nuts: Six sets per coupling (20” size uses four sets)
• Material:
Heat treated, zinc plated, carbon steel, track-head, conforming to the
physical properties of ASTM A183, minimum tensile 110,000 PSI.
• Bolt Torque:
Not required, housings to be tightened until bolt pads meet "metal to metal"
Note: Type ‘C’ and Type ‘B’ Vic-Rings may also be used,
contact Victaulic for details.
www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2008 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.
REV_A 16.07_
APPLIED VIC-RING SYSTEM 16.07
Style 28 Coupling
PRODUCT DESCRIPTION
Pipe Ends
Install couplings in accordance with Victaulic’s published installation instructions for large diameter multiple segment couplings
contained in the I-100 Field Installation Handbook.
Length STYLE 28
TYPE 'D' VIC-RING
ABRASIVE SERVICE Standard Vic-Ring on Beveled Pipe
'A' Dim
Face Stamped
"FRONT"
Back Weld: 1.4T x 45°
1/2" x 45° or as specified by
Chamfer piping designer.
1/2" Groove
1/4" REF
Weld
Standard Vic-Ring on Square Cut Pipe Special Vic-Ring with 1/4" Chamfer
'T' for Chromium Carbide Overlay
Face Stamped
IMPORTANT: Vic-Ring adapters must be "FRONT"
installed with the face marked "FRONT"
oriented toward the pipe end. The pipe end
and weld must not protrude beyond the
face of the Vic-Ring adapter. 1/2" REF
Option for Non-Abrasive Services
All welding shall be completed by qualified welders and shall conform to local codes and regulations that apply where the
product in installed.
www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2008 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.
16.07_ REV_A
APPLIED VIC-RING SYSTEM 16.07
Style 28 Coupling
PRODUCT DESCRIPTION
DIMENSIONS Z Z
Y X
1 2 3 4 5 6 7
Size Wall 'T' Nom Nom Weight Ea.
(NPS) In. / mm Size Length X Y Z Bolt Size No. Lbs./Kg
18 0.500" / 12.70 20 3-1⁄4" / 82.6 25.4" / 645 28.7" / 729 4.2" / 107 1-1⁄8" x 4" 4 109.0 / 49
20 0.500" / 12.70 20 3-1⁄4" / 82.6 25.4" / 645 28.7" / 729 4.2" / 107 1-1⁄8" x 4" 4 109.0 / 49
22 0.500" / 12.70 24 3-1⁄2" / 88.9 31.0" / 787 33.5" / 851 4.9" / 125 1-1⁄8" x 4" 6 150.0 / 68
24 0.500" / 12.70 24 3-1⁄2" / 88.9 31.0" / 787 33.5" / 851 4.9" / 125 1-1⁄8" x 4" 6 150.0 / 68
26 0.500" / 12.70 27 4-1⁄2" / 114.3 35.3" / 897 39.4" / 1000 5.6" / 142 1-1⁄2" x 4-1⁄2" 6 280.0 / 127
27 0.500" / 12.70 27 4-1⁄2" / 114.3 35.3" / 897 39.4" / 1000 5.6" / 142 1-1⁄2" x 4-1⁄2" 6 280.0 / 127
28 0.500" / 12.70 30 4-1⁄2" / 114.3 38.4" / 975 42.8" / 1087 6.2" / 158 1-1⁄2" x 4-1⁄2" 6 330.0 / 150
30 0.500" / 12.70 30 4-1⁄2" / 114.3 38.4" / 975 42.8" / 1087 6.2" / 158 1-1⁄2" x 4-1⁄2" 6 330.0 / 150
Notes:
Column 1: “Size (NPS)” is the nominal NPS steel pipe size.
NOTE: Special Vic-Rings are offered to permit the four sizes of Style 28 couplings listed
in Column 3 to be used to join eight different sizes of pipe listed in Column 1. Contact
Victaulic for specific details.
Couplings are compatible with multiple pipe sizes as shown below:
20" coupling - 18 & 20" pipe
24" coupling- 22 & 24" pipe
27"coupling- 26 & 27" pipe
30" coupling- 28 & 30" pipe
Column 2: “Wall ‘T’” is the standard minimum wall thickness for use with Victaulic Vic-Ring® Adapters.
Lighter wall thicknesses may by used, possibly at lower working pressures. Contact Victaulic
for details.
Column 3: “Nom Size” is the nominal size for Victaulic Style 28 Couplings and Victaulic Vic-Ring™
Adapters. Note this nominal diameter may be larger than the nominal pipe size as shown in
the chart.
Column 4: “Nom Length” is nominal length of the Vic-Ring™ and is provided for identifying clearance
requirements.
Column 5: Overall dimensions of Style 28 couplings.
Column 6: Coupling bolt size and number required.
Column 7: Coupling weight each, Lbs / Kg.
Important: The joint performance data which is published in this document only applies to
genuine Vic-Ring™ adapters designed and supplied by Victaulic Company.
Victaulic Company cannot warrant the performance of joints using adapter rings
supplied by others.
www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2008 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.
REV_A 16.07_
APPLIED VIC-RING SYSTEM 16.07
Style 28 Coupling
PRODUCT DESCRIPTION
1 2 3 4 5 6 7 8 9
Notes:
Column 1: “Size (NPS)” is the nominal NPS steel pipe size. Nominal Size Style 28 coupling.
Column 2: Nominal pipe outside diameter. Couplings may be used to join pipe with nominal diameters smaller than the coupling size as indicated
in this column.
Column 3: Nominal pipe wall thickness.
Column 4: Coupling Style.
Column 5, 6: Vic-Ring™ Type and outside diameter. Contact Victaulic for specific details.
Column 7: Maximum working pressure, including surge pressure, to which a joint may be subjected. This figure provides a nominal safety factor of three.
These pressure ratings are based on suitable steel pipe of the required wall thickness with appropriate Vic-Ring™ adapters.
Column 8: Standard nominal pipe end gap (separation), and the joint deflection from centerline based on couplings and Vic-Rings of nominal
dimensions. A joint deflected to the maximum angle will not provide any linear movement. This data does not apply to Vic-Ring™ adapters
manufactured for “reduced pipe end gaps” for use with FlushSeal gaskets, or to reduce the effects of turbulence at the joints. This data does
not take into account the effects of manufacturing and installation tolerances. If this data is to be used for system design purposes, customers
should contact Victaulic for assistance.
Column 9: Maximum End Load, published in pounds, is the total of all loads on the coupling joint from all sources, external and internal, including internal
pressure thrust.
Important: The joint performance data contained in the above chart applies to Vic-Ring™ adapters supplied by Victaulic Company. Victaulic
Company cannot warrant the performance of joints using adapter rings supplied by others.
INSTALLATION Reference should always be made to the I-100 Victaulic Field Installation Handbook for the product
you are installing. Handbooks are included with each shipment of Victaulic products for complete
installation and assembly data, and are available in PDF format on our website at www.victaulic.com.
WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details.
NOTE This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be
installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the
right to change product specifications, designs and standard equipment without notice and without
incurring obligations.