Ace5 Inverter: User Manual
Ace5 Inverter: User Manual
EQUIPMENTS CONSTRUCTION
Via Parma, 59 – 42028 – POVIGLIO (RE) – ITALY
Tel +39 0522 960050 (r.a.) – Fax +39 0522 960259
e-mail: [email protected] – web: www.zapispa.it
EN
User Manual
ACE5
INVERTER
Copyright © 1975-2011 Zapi S.p.A.
All rights reserved
The contents of this publication is a ZAPI S.p.A. property; all related authorizations are covered
by Copyright. Any partial or total reproduction is prohibited.
Under no circumstances will Zapi S.p.A. be held responsible to third parties for damage caused
by the improper use of the present publication and of the device/devices described in it.
Zapi spa reserves the right to make changes or improvements to its products at any time and
without notice.
The present publication reflects the characteristics of the product described at the moment of
distribution. The publication therefore does not reflect any changes in the characteristics of the
product as a result of updating.
NOTES LEGEND
APPROVAL SIGNS
PROJECT MANAGER
TECHNICAL ELECTRONIC
MANAGER VISA
4 The use of special devices to be connected to the inverter, has to discussed with
Zapi Technicians
The coil of the main contactor has to be connected between the pins PMC (A27)
and NMC (A26)
It can be driven in two ways:
- on/off control: the coil is driven with the full battery voltage.
- the coil is switched at high frequency (1 kHz) with a duty cycle around 60%;
this feature is useful to decrease the power dissipation of the contactor coil.
Each coil has a preferred way which has to be used to energize it.
The ACE5 supports both driving methods: a software parameter can switch
between on/off control and switching control.
3.2 Microswitches
- The microswitches must have a contact resistance lower than 0.1 ohm and a
leakage current lower than 100 µA.
- Under maximum load, the voltage drop between the key switch contacts
must be lower than 0.1 V.
- The microswitches send a voltage signal to the microprocessor when a
function request (for ex.: “forward” request) is made.
- Microswitches are used to send digital signals and thus are typically
connected to digital inputs.
The main analog input CPOT (A16 Ampseal connector version) can read signals
ranging from 0 to 10 V.
Potentiometer value should be in the 0.5 – 10 kohm range; generally, the load
The Procedure for automatic potentiometer signal acquisition is carried out using
the Console. This enables adjustment of the minimum and maximum useful
signal level (PROGRAM VACC function), in either direction. This function is
unique when it is necessary to compensate for asymmetry with the mechanical
elements associated with the potentiometer, especially relating to the minimum
level. The sequence of procedure is described in the programming console
manual.
The two graphs show the output voltage from a non-calibrated potentiometer with
respect to the mechanical “zero” of the control lever. MI and MA indicate the point
where the direction switches close. 0 represents the mechanical zero of the
rotation.
The left hand graph shows the relationship of the motor voltage without signal
acquisition being made. The right hand graph shows the same relationship after
signal acquisition of the potentiometer.
2) Electric motors very often have a thermal sensor, which can be digital (on/off
sensor, normally closed) or analog. These sensor are 2-wire components in
the majority of cases.
4 Note: The encoder resolution and the motor poles pair (the controller can
handle), is specified in the home page display of the handset showing following
headline:
AC5T2D ZP1.13
That means:
AC5T= AC-5 traction controller
(AC5P= AC-5 pump controller)
2 = motor’s poles pair number
D = 128 pulses/rev encoder
The encoder resolution is given by the last letter in the following list:
A = 32 pulses/rev
B = 64 pulses/rev
C = 80 pulses/rev
D = 128 pulses/rev
4 Notice that the purpose of the power fuse is not to protect the power section of
the inverter. In case of short circuit a damage in the inverter will occur too quickly
and the fuse will not blow. The purpose of the fuse is to protect the power cables
U Before doing any operation, ensure that the battery is disconnected. When
all the installation is completed, start the machine with the drive wheels
raised from the floor to ensure that any installation error do not
compromise safety.
After operation, even with the Key switch open, the internal capacitors may
remain charged for some time. For safe operation, we recommend that the
battery is disconnected, and a short circuit is made between Battery
Positive and Battery Negative power terminals of the inverter using a
Resistor between 10 ohm and 100 ohm.
4 CAN stands for Controller Area Network. It is a communication protocol for real
time control applications. CAN operates at data rate of up to 1 Megabits per
second.
It was invented by the German company Bosch for the car industry. It permits
communication among the various electronic modules of a vehicle. The following
image shows the typical connection:
- The best cable for can connections is the twisted pair; if it is necessary to
increase the immunity of the system to disturbances, a good choice would be
to use a cable with a shield connected to the frame of the truck. Sometimes it
is sufficient a simple double wire cable or a not shielded duplex cable.
- In a system like an industrial truck, where power cables carry hundreds of
Amperes, there are voltage drops due to the impedance of the cables, and
this could cause errors on the data transmitted through the can wires. In the
following figures there is an overview of wrong and right layouts of the cables
routing.
U Wrong Layout:
R
Can Bus
Power cables
Module Module
1 2
Module
3
R
This is apparently a good layout, but can bring to errors in the canbus line.
The best solution depends on the type of nodes (modules) connected in the
network.
If the modules are very different in terms of power, then the preferable
connection is the daisy chain.
U Correct Layout:
R
Can Bus
Power cables
Module
Module
1
2
Module
3
R
The chain starts from the –BATT post of the controller that works with the highest
current, and the others are connected in a decreasing order of power.
Otherwise, if two controllers are similar in power (for example a traction and a
pump motor controller) and a third module works with less current, the best way
to deal this configuration is to create a common ground point (star configuration).
U Correct Layout:
R
Can Bus
Power cables
Module
Module
1
2
Module
3
R
In this case the power cables starting from the two similar controllers must be as
short as possible. Of course also the diameter of the cable concurs in the voltage
drops described before (higher diameter means lower impedance), so in this last
4 Can advantages
The complexity of today systems needs more and more data, signal and
information must flow from a node to another. CAN is the solution to different
problems that arise from this complexity
- simplified design (readily available, multi sourced components and tools)
- lower costs (less and smaller cables)
- improved reliability (fewer connections)
- analysis of problems improved (easy connection with a pc to read the data
flowing through the cable).
U A cable connected to the wrong pin can lead to short circuits and failure;
so, before turning on the truck for the first time, verify with a multimeter the
continuity between the starting point and the end of a signal wire.
For information about the mating connector pin assignment see the chapter
“description of the connectors”.
4.2.5 Connection of the encoder
1) ACE5 supports different types of encoder. To control an AC motor with Zapi
inverter, it is necessary to install an incremental encoder with 2 phases
shifted of 90°. The encoder power supply can be +5 or +12 V. It can have
different electronic output.
U VERY IMPORTANT
When ordering the controller, It is necessary to specify to Zapi the type of
encoder used: power supply, electronic output and n° of pulses for
revolution. In fact the logic unit must be set in the correct way by Zapi.
U ZAPI controllers are designed according to the prEN954-1 and EN13849 for
safety related parts of control system and to UNI EN1175-1 norm. The
safety of the machine is strongly related to installation; length, layout and
screening of electrical connections have to be carefully designed.
ZAPI is always available to cooperate with the customer in order to evaluate
installation and connection solutions. Furthermore, ZAPI is available to
develop new SW or HW solutions to improve the safety of the machine,
according to customer requirements.
Machine manufacturer holds the responsibility for the truck safety features
and related approval.
4.4 EMC
EMC stands for Electromagnetic Compatibility, and it represents the studies and
the tests on the electromagnetic energy generated or received by an electrical
device.
So the analysis works in two directions:
6) The study of the immunity can be divided in two main branches: protection
from electromagnetic fields and from electrostatic discharge.
The electromagnetic immunity concern the susceptibility of the controller
with regard to electromagnetic fields and their influence on the correct work
made by the electronic device.
There are well defined tests whom the machine has to be exposed to.
These tests are carried out at determined levels of electromagnetic fields, to
simulate external undesired disturbances and verify the electronic devices
response.
7) The second type of immunity, ESD, concerns the prevention of the effects of
electric current due to excessive electric charge stored in an object. In fact,
when a charge is created on a material and it remains there, it becomes an
“electrostatic charge”. ESD happens when there is a rapid transfer from a
charged object to another. This rapid transfer has, in turn, two important
effects:
A) this rapid charge transfer can determine, by induction, disturbs on the
signal wiring and thus create malfunctions; this effect is particularly
critical in modern machines, where serial communications (canbus)
are spread everywhere on the truck and carry critical information.
B) in the worst case and when the amount of charge is very high, the
discharge process can determine failures in the electronic devices; the
type of failure can vary from an intermittently malfunction to a completely
failure of the electronic device.
There are different solutions for EMC issues, depending on level of emissions/
immunity required, the type of controller, materials and position of the wires and
electronic components.
5.1 Diagnosis
The microcontroller continually monitors the inverter and carries out a diagnostic
procedure on the main functions. The diagnosis is different in the four main
operational modes:
1) Diagnosis at start-up: watchdog circuit, current sensor, capacitor charging,
phase's voltages, contactor drives, can-bus interface. It also checks if the
switch sequence for operation is correct and if the output of accelerator unit
is correct.
2) Standby diagnosis: watchdog circuit, phase's voltages, contactor driver,
4 If interested in one of these solutions, please contact Zapi for further information
4 Special software versions may have additional parameters and setting. In this
case additional documentation will be provided.
When the "Key Switch" is closed, if no alarms or errors are present, the Console
Display will be showing the Standard Zapi Opening Display.
If the controller is not configured to your requirements, follow the sequence
detailed here following. Remember to re-cycle the Key Switch if you make any
changes to the controller’s configuration.
8.5.1 Traction
5) Select the Options required, See Chapter 8.6. In particular:
- Select and set the Battery voltage.
- Select the type of motor temperature sensor.
6) Confirm correct installation of all wires. Use the Console’s TESTER (Chapter
8.8) to assist.
7) Perform the accelerator signal acquisition procedure using the Console
“PROGRAM VACC”. Procedure is detailed on Chapter 9.4.
8) Set the "MAXIMUM CURRENT” Current, using the table on Chapter 8.7.
9) Set the Acceleration Delay requirements for the machine. Test the
parameters in both directions.
10) Set the FREQUENCY CREEP level starting from level 0.6 Hz. The machine
should just move when the accelerator microswitch is closed. Increase the
Level accordingly.
11) Set the Speed Reductions as required. Make adjustments to “CUTBACK
SPEED” parameter. Check the performance with the accelerator pedal totally
depressed. If the machine is a forklift, check the performance with and
without load.
12) RELEASE BRAKING. Operate the machine at full speed. Release the
accelerator pedal. Adjust the level to your requirements. If the machine is a
forklift, check the performance with and without load.
13) INVERSION BRAKING. Operate the machine at 25% full speed. Whilst
travelling INVERT the Direction Switch. Set a soft Level of Inversion Braking.
When satisfactory, operate the machine at Full Speed and repeat. If the
machine is a Forklift, repeat the tests and make adjustments with and without
load. The unloaded full speed condition should be the most representative
condition.
14) PEDAL BRAKING (If used). Operate the machine at full Speed. Release the
accelerator pedal and press the Pedal Brake. Set braking level to your
requirements.
15) Set “MAX SPEED FORW”.
16) Set “MAX SPEED BACK” (Reverse).
17) Make the choice for the truck behaviour on a slope (see chapter 8.4). If the
"Stop on ramp" option is ON, set the desired value of "auxiliary time"
parameter.
9) AUX FUNCTION
- ON/OFF: if this option is programmed ON the traction inverter applies
maximum braking and traction torque.
10) ENABLE FUNCTION
- PRESENT: A7 input is managed as accelerator enable input.
- ABSENT: A7 input is managed as exclusive hydro input.
11) CHECK PUMP HYDRO
- ON/OFF: : if ON, it turns on the diagnosis of the CAN communication to a
pump module. In this case, if the traction inverter doesn’t receive any
messages by the pump inverter from the CAN-BUS line, the "CAN BUS
KO" warning appears on the traction and the maximum speed is reduced
down to 10%. The traction also checks via CAN that there aren’t alarms
in the pump. If pump is in alarm, the maximum speed is reduced down to
10%.
SUBMENU "ADJUSTMENTS"
1) SET POT BRK MIN
It records the minimum value of braking pedal potentiometer when the
braking pedal switch is closed; the procedure is similar to the "Program Vacc"
function (see chapter 9.4). This procedure must be carried out only if the
"Pedal braking" option is programmed as "Analog".
2) SET POT BRK MAX
It records the maximum value of braking pedal potentiometer when the
braking pedal is fully pressed; the procedure is similar to the "Program Vacc"
function (see chapter 9.4). This procedure must be carried out only if the
"Pedal braking" option is programmed as "Analog".
3) SET BATTERY TYPE
It selects the nominal battery voltage.
4) ADJUST BATTERY
Fine adjustment of the battery voltage measured by the controller.
5) THROTTLE 0 ZONE
It establishes a deadband in the accelerator input curve (see also curve
below).
6) THROTTLE X POINT
This parameter changes the characteristic of the accelerator input curve.
7) THROTTLE Y POINT
This parameter changes the characteristic of the accelerator input curve.
8.6.2 Pump
Using the CONFIG menu of the programming console, the user can configure the
following functions.
SUBMENU "ADJUSTMENTS"
1) SET BATTERY TYPE
It selects the nominal battery voltage.
2) ADJUST BATTERY
Fine adjustment of the battery voltage measured by the controller.
3) THROTTLE 0 ZONE
VACC MIN and VACC MAX are values programmable by the "Program
Vacc" function.
6) ADJUSTMENT #04
This parameter determines the motor temperature level at which the “Motor
temperature” alarm is signalled. The range is from 70 °C to 160 °C with 10 °C
steps. This parameter must be adjusted only if the “Set temperature” (menu
“Set option”) parameter is programmed “Analog”.
7) ADJUSTMENT #03
This parameter isn’t used.
8) ADJUSTMENT #02
It adjusts the lower level of the battery discharge table.
9) ADJUSTMENT #01
It adjusts the upper level of the battery discharge table.
AC5T2BF ZP1.00
1) Opening Zapi Menu. 80V 1000A 00000
CONFIG MENU
3) The Display will show: SET MODEL. SET MODEL
CONFIG MENU
5) SET OPTIONS appears on the display. SET OPTIONS
' % '
6) Press ENTER to go into the SET MODEL Menu. ' ' '
HOUR COUNTER
7) The display will shows the first OPTION. RUNNING
BATTERY CHECK
9) Desired OPTION appears. OFF
BATTERY CHECK
11) New OPTION appears. ON
14) Press ENTER to accept the changes, or press ' % ' ' ' '
OUT if you do not accept the changes. ' ' ' ' % '
CONFIG MENU
15) SET OPTIONS Menu appears. SET OPTIONS
16) Press OUT again. Display now show the ' ' '
Opening Zapi Menu. ' % '
AC5T2BF ZP1.00
1) Opening Zapi Menu. 80V 1000A 00000
CONFIG MENU
3) The display will show: SET MODEL. SET MODEL
CONFIG MENU
5) ADJUSTMENTS appears on the display. ADJUSTMENTS
BATTERY TYPE
7) The display will shows SET BATTERY TYPE. 48V
TROTTLE 0 ZONE
9) The desired parameter appears. 3%
TROTTLE 0 ZONE
7%
' % '
12) Press ENTER to confirm. ' ' '
13) Repeat the same from 5 to 12 points for the
other adjustments.
AC5T2BF ZP1.00
1) Opening Zapi Menu. 80V 1000A 00000
CONFIG MENU
3) The Display will show: SET MODEL. SET MODEL
CONFIG MENU
5) ADJUSTMENTS appears on the display. ADJUSTMENTS
12) Press ENTER to accept the changes, or press ' % ' ' ' '
OUT if you do not accept the changes. ' ' ' ' % '
13) Press OUT. Display now shows the Opening ' ' '
Zapi Menu. ' % '
AC5T2BF ZP1.00
1) Opening Zapi Menu. 80V 1000A 00000
CONFIG MENU
3) The Display will show: SET MODEL. SET MODEL
CONFIG MENU
5) ADJUSTMENTS appears on the display. ADJUSTMENTS
ADJUSTMENT BATTERY
9) ADJUST BATTERY appears. 82.1V
ADJUSTMENT BATTERY
11) Battery value appears on the display. 84.5V
14) Press ENTER to accept the changes, or press ' % ' ' ' '
OUT if you do not accept the changes. ' ' ' ' % '
CONFIG MENU
15) ADJUSTMENTS Menu appears. ADJUSTMENTS
16) Press OUT. Display now show the Opening ' ' '
Zapi Menu. ' % '
1) ACCELERATION DELAY
It determines the acceleration ramp. The parameter value (in seconds) sets
the time needed to speed up the motor from 0 to 100Hz.
2) RELEASE BRAKING
It controls the deceleration ramp when the travel request is released. The
parameter value (in seconds) sets the time needed to slow down the motor
from 100 to 0Hz.
3) INVERS. BRAKING
It controls the deceleration ramp when the direction switch is inverted during
travel. The parameter value (in seconds) sets the time needed to slow down
the motor from 100 to 0Hz.
4) PEDAL BRAKING
It determines the deceleration ramp when the travel request is released and
the brake pedal switch is closed. The parameter value (in seconds) sets the
time needed to slow down the motor from 100 to 0Hz.
5) SPEED LIMIT BRK.
Deceleration ramp when the pedal position is changed but not completely
released. The parameter value (in seconds) sets the time needed to slow
down the motor from 100 to 0Hz.
6) BRAKE CUTBACK
It determines the deceleration ramp when the speed reduction input becomes
active and the motor slow down. The parameter value (in seconds) sets the
time needed to slow down the motor from 100 to 0Hz.
7) MAX SPEED FORW
It determines the maximum speed in forward direction.
8) MAX SPEED BACK
It determines the maximum speed in backward direction.
9) CUTBACK SPEED
Speed reduction (percentage of the max speed) when the cutback switch is
active.
10) CURVE CUTBACK
Determines the speed reduction (percentage of the max speed) during a
steering movement and only if an electric steering control, like a Zapi EPS, is
present in the truck.
11) FREQUENCY CREEP
Minimum speed (in Hz) when the forward or reverse switch is closed, but the
accelerator is at its minimum position.
12) MAXIMUM CURRENT
This parameter changes the maximum current of the inverter. It is a
percentage of the current defined by factory settings.
13) BACKING SPEED
It determines the speed while the inching function is active.
14) BACKING TIME
It determines the time duration of the inching function.
15) AUXILIARY TIME
During the time, defined by this option, the truck is hold on the ramp if the
The following table shows the different values at which the parameters can be
set.
PROGRAMMED LEVEL
PARAMETER UNIT
0 1 2 3 4 5 6 7 8 9
ACCELERATION DELAY (*) Sec. 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0
RELEASE BRAKING (**) Sec. 5.5 5.0 4.5 4.0 3.5 3.0 2.5 2.0 1.5 1.0
INVERS. BRAKING (**) Sec. 5.5 5.0 4.5 4.0 3.5 3.0 2.5 2.0 1.5 1.0
PEDAL BRAKING (**) Sec. 5.5 5.0 4.5 4.0 3.5 3.0 2.5 2.0 1.5 1.0
SPEED LIMIT BRK. (**) Sec. 8.9 8.3 7.7 7.1 6.6 6.0 5.5 4.9 4.4 3.8
BRAKE CUTBACK (**) Sec. 5.5 5.0 4.5 4.0 3.5 3.0 2.5 2.0 1.5 1.0
MAX SPEED FORW Hz 65 80 95 110 125 140 155 170 185 200
MAX SPEED BACK Hz 65 80 95 110 125 140 155 170 185 200
CUTBACK SPEED %Max Sp 10 20 30 40 50 60 70 80 90 100
CURVE CUTBACK %Max Sp 0 10 21 33 44 55 66 78 89 100
FREQUENCY CREEP Hz 0.3 0.6 0.9 1.2 1.5 1.8 2.1 2.4 2.7 3.0
MAXIMUM CURRENT %IMAX 47 53 58 64 70 76 82 88 94 100
BACKING SPEED Hz 0 2 4 6 8 10 12 14 16 18
BACKING TIME Sec. 0. 2 0.5 1.0 1.4 1.8 2.3 2.7 3.1 3.6 4.0
AUXILIARY TIME Sec. 0 1 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5
(*) The acceleration time shown is the time from 0 Hz to 100 Hz. This is the
ideal ramp calculated by the software; the real ramp could change as a
function of motor control parameter setting and, obviously, as a function
of the load.
(**) The braking feature is based upon deceleration ramps. The value shown
in the table is the time to decrease the speed from 100 Hz to 0 Hz. This
is the ideal ramps calculated by the software; the real ramp could
change as a function of motor control parameter setting and, obviously,
as a function of the load.
1) ACCELER. DELAY
It determines the acceleration ramp. The parameter value (in seconds) sets
the time needed to speed up the motor from 0 to 100Hz.
2) DECELER. DELAY
It controls the deceleration ramp when the pump request is released. The
parameter value (in seconds) sets the time needed to slow down the motor
from 100 to 0Hz.
The following table shows the different values at which the parameters can be
set.
PROGRAMMED LEVEL
PARAMETER UNIT
0 1 2 3 4 5 6 7 8 9
ACCELER. DELAY (*) Sec. 0.5 0.7 1.0 1.4 1.9 2.5 3.2 4.0 4.8 5.5
DECELER. DELAY (**) Sec. 0.5 0.7 1.0 1.4 1.9 2.5 3.2 4.0 4.8 5.5
MAX SPEED UP Hz 65 80 95 110 125 140 155 170 185 200
MIN SPEED UP Hz 0 13.5 15.0 16.5 18.0 19.5 21.0 22.5 24.0 25.5
CUTBACK SPEED %Max Sp 10 20 30 40 50 60 70 80 90 100
SPEED FINE (ALL) (***) Hz - - - - - - - - - -
MAXIMUM CURRENT %IMAX 47 53 58 64 70 76 82 88 94 100
AUXILIARY TIME Sec. 0 0.2 0.4 0.8 1.0 1.5 2.0 3.0 4.0 5.0
(*) The acceleration time shown is the time from 0 Hz to 100 Hz (maximum
selectable speed). This is the ideal ramp calculated by the software; the
real ramp could change as a function of motor control parameter setting
and, obviously, as a function of the load.
(**) The deceleration time shown in the table is the time from 100 Hz to 0
Hz. This is the ideal ramp calculated by the software; the real ramp
could change as a function of motor control parameter setting and,
obviously, as a function of the load.
Flow Chart showing how to make Programme changes using Digital Console.
AC5T2BF ZP1.00
1) Opening Zapi Display. 80V 1000A 00000
' % '
2) Press ENTER to go into the General Menu. ' ' '
MAIN MENU
3) The Display will show: PARAMETER CHANGE
ACCEL. DELAY
5) The Display will show the first parameter. LEVEL = 4
RELEASE BRAKING
9) The Display will show the New Level. LEVEL = 6
10) When you are satisfied with the results of the ' ' '
changes you have made, press OUT. ' % '
MAIN MENU
13) The Display will show: PARAMETER CHANGE
AC5T2BF ZP1.00
1) Opening Zapi Display. 80V 1000A 00000
' % '
2) Press ENTER to go into the General menu. ' ' '
MAIN MENU
3) The Display will show: PARAMETER CHANGE
MAIN MENU
5) The Display shows: TESTER
' % '
6) Press ENTER to go into the TESTER function. ' ' '
FREQUENCY
10) The Display shows: Hz
11) Press OUT again and return to Opening Zapi ' ' '
Display. ' % '
MAIN MENU
TESTER
Remember it is not possible to make any changes using TESTER. All you can do
is measure as if you were using a pre-connected multimeter.
Flow Chart showing how to use the SAVE function of the Digital Console.
AC5T2BF ZP1.00
1) Opening Zapi Display. 80V 1000A 00000
' % '
2) Press ENTER to go into the General menu. ' ' '
MAIN MENU
3) The Display will show: PARAMETER CHANGE
MAIN MENU
5) The Display will show: SAVE PARAM.
' % '
6) Press ENTER to go into the SAVE function. ' ' '
SELECT: MOD. 01
FREE
' % '
9) Press ENTER to commence SAVE routine. ' ' '
10) You can see the items that are being stored READING …
whilst the SAVE routine is happening. ACCEL. DELAY (ECC.)
MAIN MENU
11) When finished, the Console shows: SAVE PARAM
Flow Chart showing how to use the RESTORE function of the Digital Console.
AC5T2BF ZP1.00
1) Opening Zapi Display. 80V 1000A 00000
' % '
2) Press ENTER to go into the General menu. ' ' '
MAIN MENU
3) The Display will show: PARAMETER CHANGE
MAIN MENU
5) The Display will show: RESTORE PARAM.
SELECT : MOD. 01
AC5 ZAPI V1
10) The Display will ask “ARE YOU SURE?”. ARE YOU SURE?
YES=ENTER NO=OUT
MAIN MENU
13) When finished the Console displays: RESTORE PARAM.
14) Press OUT to return to the Opening Zapi ' ' '
Display. ' % '
Flow Chart showing how to use the ALARMS function via the Digital Console.
AC5T2BF ZP1.00
1) Opening Zapi Display. 80V 1000A 00000
' % '
2) Press ENTER to go into the General menu. ' ' '
MAIN MENU
3) The Display will show: PARAMETER CHANGE
MAIN MENU
5) The Display will show: ALARMS
' % '
6) Press ENTER to go into the ALARMS function. ' ' '
CODE
7) The Display will show the most recent Alarm. 00005 #02 20°C
CLEAR LOGBOOK?
11) The Display will ask “CLEAR LOGBOOK?”. YES=ENTER NO=OUT
13) Press OUT to return to the Opening Zapi ' ' '
Display. ' % '
Flow Chart showing how to use the PROGRAM VACC function of the Digital
Console.
AC5T2BF ZP1.00
1) Opening Zapi Display. 80V 1000A 00000
' % '
2) Press ENTER to go into the General Menu. ' ' '
MAIN MENU
3) The Display will show: PARAMETER CHANGE
MAIN MENU
5) The Display will show: PROGRAM VACC
11) Select the Reverse Direction and repeat part MIN VACC MAX
10. 0.6 ↑ 4.4
' % '
14) Press ENTER for yes, or OUT for NO. ' % '
MAIN MENU
15) When finished, the Console shows: PROGRAM VACC
16) Press OUT again to return to the Opening Zapi ' ' '
Menu. ' % '
4 Notice that special software versions may have additional alarm codes. Please
ask Zapi for further information
3) LOGIC FAILURE #1
This alarm signals that an undervoltage / overvoltage protection operation
has occurred. This alarms stops the controller operation and opens the MC.
Two possible reasons:
A) A real undervoltage / overvoltage situation happened. The alarm should
disappear by simply switching off and on again the key. The cause of the
undervoltage/overvoltage event has to be found on the application. For
example: a very strong regenerative braking has increased too much the
4 The gain acquisition test can be carried out only by Zapi personnel or other
trained technicians!
4 The gain acquisition test can be carried out only by Zapi personnel or other
trained technicians!
C29509 SW 200 80 V
Single Pole Contactor
C29532 SW 200 48 V
Single Pole Contactor
Check the Foot pedal or Tiller microswitch. Using a suitable test meter, confirm
that there is no electrical resistance between the contacts by measuring the volt
drop between the terminals. Switches should operate with a firm click sound.
Microswitches should be checked every 3 months.
Check the Battery cables, cables to the inverter, and cables to the motor. Ensure
the insulation is sound and the connections are tight.
Cables should be checked every 3 months.
Check the mechanical operation of the pedal or tiller. Are the return springs ok.
Do the potentiometers wind up to their full or programmed level.
Check every 3 months.
Checks should be carried out by qualified personnel and any replacement parts
used should be original. Beware of NON ORIGINAL PARTS.
The installation of this electronic controller should be made according to the
diagrams included in this Manual. Any variations or special requirements should
be made after consulting a Zapi Agent. The supplier is not responsible for any
problem that arises from wiring methods that differ from information included in
this Manual.
During periodic checks, if a technician finds any situation that could cause
damage or compromise safety, the matter should be bought to the attention of a
Zapi Agent immediately. The Agent will then take the decision regarding
operational safety of the machine.