Diesel Generator Set Model DNAE 60 HZ: Description Features
Diesel Generator Set Model DNAE 60 HZ: Description Features
Diesel Generator Set Model DNAE 60 HZ: Description Features
Description Features
Cummins Power Generation commercial generator sets are Onan Heavy-Duty Engine - Rugged 4-cycle liquid cooled
fully integrated power generation systems, providing optimum industrial diesel engine delivers reliable power and fast
performance, reliability, and versatility for stationary standby or response to load changes.
prime power applications. Alternator - Several alternator sizes offer selectable motor
A primary feature is strong motor-starting capability and fast starting capability with low reactance 2/3 pitch windings, low
recovery from transient load changes. The torque-matched waveform distortion with non-linear loads and fault clearing
system includes a heavy-duty Onan 4-cycle liquid-cooled short-circuit capability.
diesel engine, an AC alternator with high motor-starting Control systems - The PowerCommand electronic control
capacity, and an electronic voltage regulator for precise is standard equipment and provides total genset system
regulation under steady-state or transient loads. The GenSet integration, including automatic remote starting/stopping and
accepts 100% of the nameplate standby rating in one step, in precise frequency and voltage regulation. Optional features
compliance with NFPA110 Level 1 requirements. include alarm and status message display, output metering,
The standard PowerCommand® digital electronic control is an auto-shutdown at fault detection, and NFPA 110 Level 1
integrated system that combines engine and alternator compliance.
controls for high reliability and optimum GenSet performance. Cooling Systems - Standard cooling package provides
o
Optional weather-protective enclosures and coolant heaters reliable running up to 40 C ambient temperature.
shield the generator set from extreme operating conditions. Integral Vibration Isolation - Robust skid base supports
Environmental concerns are addressed by low exhaust the engine, alternator, and radiator on isolators, minimizing
emission engines, sound-attenuated enclosures, exhaust transmitted vibration.
silencers, and dual-wall fuel tanks. A wide range of options,
accessories, and services are available, allowing configuration Enclosures - Optional weather-protective enclosures are
to your specific power generation needs. available.
Every production unit is factory tested at rated load and power Fuel Tanks - Dual wall sub-base fuel tanks and in-skid day
factor. This testing includes demonstrated capacity at rated tanks are also offered.
power, single-step rated load pickup, and reactive current Certifications - Generator sets are designed,
capability to inductive loads. Cummins Power Generation manufactured, tested, and certified to relevant UL, NFPA,
manufacturing facilities are committed to the highest possible ISO, IEC, and CSA standards.
quality in the design, manufacture, and support of our
Warranty and Service - Backed by a comprehensive
products. The GenSet is CSA certified.
warranty and world wide distributor network.
All Cummins Power Generation systems are backed by a
comprehensive warranty program and supported by a
worldwide network of 170 distributors and service branches to
assist you with warranty, service, parts, and planned
maintenance support
© 2005 Cummins Power Generation Specifications subject to change without notice S-1219g (3/05)
.
Generator Set
The general specifications provide representative configuration details. Consult the outline drawing for installation design.
Specifications – General
See outline drawing 0184-0285 for installation design specifications.
Unit Width, in (mm) 28.0 (711)
Unit Height, in (mm) 38.8 (986)
Unit Length, in (mm) 58.3 (1481)
Unit Dry Weight, lb (kg) 824 (374)
Unit Wet Weight, lb (kg) 853 (387)
Rated Speed, rpm 1800
Voltage Regulation, No Load to Full Load ±2.0%
Random Voltage Variation ±1.0%
Frequency Regulation 5%
Random Frequency Variation ±0.5%
Radio Frequency Interference Meets requirements of most industrial and commercial applications
Cooling Standby Prime
Fan Load, HP (kW) 0.3 (0.2) 0.3 (0.2)
Coolant Capacity with radiator, US Gal (L) 2.0 (7.6) 2.0 (7.6)
Coolant Flow Rate, Gal/min (L/min) 11.6 (43.9) 11.6 (43.9)
Heat Rejection To Coolant, Btu/min (MJ/min) 780.0 (0.8) 710.0 (0.8)
Heat Radiated To Room, Btu/min (MJ/min) 260.0 (0.3) 240.0 (0.3)
Maximum Coolant Friction Head, psi (kPa) 1.4 (9.7) 1.4 (9.7)
Maximum Coolant Static Head, ft (m) 12.0 (3.7) 12.0 (3.7)
Air
Combustion Air, scfm (m3/min) 50.0 (1.4) 50.0 (1.4)
Alternator Cooling Air, scfm (m3/min) 175.0 (5.0) 175.0 (5.0)
Radiator Cooling Air, scfm (m3/min) 2200.0 (62.3) 2200.0 (62.3)
Max. Static Restriction, in H2O (Pa) 0.25 (62.25) 0.25 (62.25)
Rating Definitions
Standby Rating based on: Applicable for supplying emergency power for the duration of normal power interruption. No
sustained overload capability is available for this rating. (Equivalent to Fuel Stop Power in accordance with ISO3046, AS2789,
DIN6271 and BS5514). Nominally rated.
Prime (Unlimited Running Time) Rating based on: Applicable for supplying power in lieu of commercially purchased
power. Prime power is the maximum power available at a variable load for an unlimited number of hours. A 10% overload
capability is available for limited time. (Equivalent to Prime Power in accordance with ISO8528 and Overload Power in
accordance with ISO3046, AS2789, DIN6271, and BS5514). This rating is not applicable to all generator set models.
Base Load (Continuous) Rating based on: Applicable for supplying power continuously to a constant load up to the full
output rating for unlimited hours. No sustained overload capability is available for this rating. Consult authorized distributor for
rating. (Equivalent to Continuous Power in accordance with ISO8528, ISO3046, AS2789, DIN6271, and BS5514). This rating
is not applicable to all generator set models.
© 2005 Cummins Power Generation Specifications subject to change without notice S-1219g (3/05)
.
Engine
Onan heavy-duty diesel engines provide stable power, low fuel consumption, quiet operation, and fast response to sudden
load changes.
Mechanical governing is standard. Electronic governing is available for applications requiring constant (isochronous)
frequency regulation such as Uninterruptible Power Supply (UPS) systems, non-linear loads, or sensitive electronic loads.
Optional coolant heaters are recommended for all emergency standby installations or for any application requiring fast load
acceptance after start-up.
Specifications – Engine
Base Engine Onan LPW4, naturally aspirated, diesel-fueled
3
Displacement in (L) 113.5 (1.9)
Overspeed Limit, rpm 2100 ±50
Regenerative Power, kW 3.60
Cylinder Block Configuration Cast iron, In-line 4 cylinder
Battery Capacity 160 amps minimum at ambient temperature of 32°F(0°C)
Battery Charging Alternator 45-amp belt driven engine mounted.
Starting Voltage 12-volt, negative ground
Lube Oil Filter Types Single spin-On, full flow.
o o
Standard Cooling System 104 F (40 C) ambient radiator cooling system
© 2005 Cummins Power Generation Specifications subject to change without notice S-1219g (3/05)
.
Alternator
Single-bearing alternators couple directly to the engine flywheel with flexible discs for drivetrain reliability and durability. No
gear reducers or speed changers are used. Two-thirds pitch windings eliminate third-order harmonic content of the AC
voltage waveform and provide the standardization desired for paralleling of generator sets. The standard excitation system is
a self (shunt) excited system with the voltage regulator powered directly from the generator set output. The standard
alternator is a single-phase 4-lead 105oC rise. Optional alternators include 3-phase and 3-phase with full single-phase output
capability.
© 2005 Cummins Power Generation Specifications subject to change without notice S-1219g (3/05)
.
Specifications – Alternator
o o o
Single Phase Table 105 C 105 C 105 C
Feature Code B274 B256 B268
Alternator Data
Sheet Number
Voltage Ranges 120/2402 120/2401 120/2402
Surge kW 16.8 16.8 16.8
Motor Starting kVA Shunt 27 27 36
(at 90% sustained
voltage)
Full Load Current - 110/2201 110/2202 120/2401 120/2402
Amps at Standby 49 73 45 67
Rating
Notes:
1. The broad range alternators can supply single phase output up to 2/3 set rated 3-phase kW at 1.0 power factor.
2. The extended stack (full single phase output) and 4 lead alternators can supply single phase output up to full set rated 3-phase
kW at 1.0 power factor.
© 2005 Cummins Power Generation Specifications subject to change without notice S-1219g (3/05)
.
Control System
PowerCommand (1301) Control
© 2005 Cummins Power Generation Specifications subject to change without notice S-1219g (3/05)
.
Exhaust System
[ ] Critical grade exhaust silencer
Enclosures
[ ] Weather protective enclosure
w/silencer
[ ] Quiet Site Level I enclosure
w/silencer
[ ] Quiet Site Level II enclosure
w/silencer
© 2005 Cummins Power Generation Specifications subject to change without notice S-1219g (3/05)
.
Warranty
All components and subsystems are covered by an express limited one-year warranty. Other optional and extended factory
warranties and local distributor maintenance agreements are available. Contact your distributor/dealer for more information.
Certifications
PTS - The Prototype Test Support (PTS) program verifies the performance integrity of the generator set
design. Products bearing the PTS symbol have been subjected to demanding tests in accordance to
NFPA 110 Level 1 to verify the design integrity and performance under both normal and abnormal
operating conditions including short circuit, endurance, temperature rise, torsional vibration, and
transient response, including full load pickup.
Important: Backfeed to a utility system can cause electrocution and/or property damage. Do not connect generator sets to any
building electrical system except through an approved device or after building main switch is open.
© 2005 Cummins Power Generation Specifications subject to change without notice S-1219g (3/05)