Busbar Contact Resistance Test Report

The site acceptance test report summarizes testing of a 22 kV MV panel. Busbar contact resistance tests were performed and measurements were taken for each feeder. Test results showed contact resistances between 253-633 micro-ohms across the three phases. The test equipment used was a Megger MOM 200A microhm meter calibrated until June 2021.

Uploaded by

Gajendran Sriram
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
50% found this document useful (4 votes)
6K views1 page

Busbar Contact Resistance Test Report

The site acceptance test report summarizes testing of a 22 kV MV panel. Busbar contact resistance tests were performed and measurements were taken for each feeder. Test results showed contact resistances between 253-633 micro-ohms across the three phases. The test equipment used was a Megger MOM 200A microhm meter calibrated until June 2021.

Uploaded by

Gajendran Sriram
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 1

SITE ACCEPTANCE

TEST REPORT FOR


22 kV MV PANEL

PROJECT WO # DC 3295236 EQUIPMENT 22 kV MV PANEL


CLIENT ADDC SUBSTATION RBW3 / PLOT C20
CONTRACTOR TIME ELECTRO DATE 31.01.2021
TESTING COMPANY ALPHA POWER LLC PAGE Page 1 of 1

BUSBAR CONTACT RESISTANCE TEST

1. SWITCHGEAR DATA:

RATED VOLTAGE 22 kV RATED CURRENT 630 A


MAKE TAVRIDA ELECTRIC EXPORT AS TYPE SP25

2. BUSBAR CONTACT RESISTANCE TEST:

CURRENT INJECTED: 100A DC

L1 L2 L3
Sr.No FEEDER REFERENCE
(μΩ) (μΩ) (μΩ)
1 J01-J02 437 433 407
2 J02-J03 633 626 611
3 J03-J04 441 443 419
4 J04-J01 279 279 253

3. REMARKS

4. TEST EQUIPMENT DETAILS:

Description Make Model Serial No. Calibration Due Date


Micro Ohm Meter Megger MOM 200A 1202852 06.06.2021

TESTED BY CONTRACTOR WITNESS &APPROVED BY


COMPANY ALPHA POWER LLC TIME ELECTRO ADDC
NAME GAJENDRAN K
SIGNATURE
DATE 31.01.2021