Faac 415 Manual
Faac 415 Manual
Faac 415 Manual
4 1 5 L L S O pe r a t or A n d
4 2 5 D C o n t r o l P a ne l
THE 415 L LS OPERATOR AND I n s t a l l a ti o n M a n u a l
CONTENTS
Important Safety Information 2
Technical Data 4
Unpacking the Operator 5
The 415 L LS Operator General Characteristics 6
Installation Instructions 6
Prepare the Gate 6
Manual Release Mechanism 6
Attach the Electric Cables 7
Install the Operator 7
Attach the Rear Mounting Bracket 8
Attach the Front Mounting Bracket to the Gate Leaf 8
Attach the Operator to the Rear Mounting Bracket 9
Attach the Operator to the Front Mounting Bracket 9
Adjusting the Limit Switches 10
Install the 425 D Control Panel 10
Exploded View, 415 L LS Operator 12
415 L LS Operator Parts List 13
The 425 D Control Panel General Description 14
The 425 D Control Panel
Installation Instructions
6. It is extremely unsafe to compensate for a damaged • Do not install or operate the equipment
gate by increasing hydraulic pressure. with bare feet.
7. Devices such as reversing edges and photobeams • Do not allow small children or incapable
must be installed to provide better protection for persons to use the equipment.
personal property and pedestrians. Install reversing 3. If a gate system component malfunctions, turn off
devices that are appropriate to the gate design and the main power before making any attempt to repair
gate application. it.
8. Before applying electrical power, be sure that the 4. Do not attempt to impede the movement of the
voltage requirements of the equipment correspond gate. You may injure yourself as a result.
to your supply voltage. Refer to the label on your
operator system. 5. This equipment may reach high temperatures
during operation; therefore, use caution when
touching the external housing of the operator.
USE 6. Learn to use the manual release mechanism
according to the procedures found in this in-
stallation manual.
1. Use this equipment only in the capacity for which it
was designed. Any use other than that stated should 7. Before carrying out any cleaning or maintenance
be considered improper and therefore dangerous. operations, disconnect the equipment from the
electrical supply.
2. When using any electrical equipment, observe some
fundamental rules: 8. To guarantee the efficiency of this equipment, the
manufacturer recommends that qualified personnel
• Do not touch the equipment with damp or periodically check and maintain the equipment.
humid hands or feet.
TECHNICAL DATA
THE 415 COMPACT OPERATOR
Parameter Measure
Power (Watt) 70
As you unpack the box, insure that all the parts listed (1) Parts package:
below are included (See Figure 1). (2) Manual Release keys
(4) Snap rings
(1) Control panel enclosure with control panel and (1) Long pins for rear mounting (each requires 2 snap
transformer. ring)
(1) Short pins for front mounting (each requires 2
(1) 415 Operator. snap rings)
(1) Cable Cover
(1) 2 Conductor Electric Cable for Motor Connection (2) Cable Strain Reliefs
Number Description
1 415 Operator
2 Manual Release Location
3 Piston Rod
9 4 Front Mounting B racket
5 Rear Mounting Bracket
INSTALLATION INSTRUCTIONS
Installing the 415 Operator involves preparing the gate, Make sure that the gate structure is solidly built. Add
installing the operator(s), installing the control panel, reinforcing crosspieces if necessary to the gate leaves.
programming control panel, and connecting other Make sure that the gate moves smoothly on its hinges
operational controls. without excessive friction by swinging it opened and
closed by hand. If necessary, lubricate all the gate's
Note: The following installation instructions assume moving parts.
you are fully capable of installing an electromechanical
operator on a gate. This manual does not instruct you Positive stops are not needed with the 415 Operator due
in designing a gate, installing a gate (whether on to built in limit switches.
masonry, wood, or metal posts), or basic electrical
wiring. The installation tasks discussed in this manual
are tasks particular to the 415 Operator.
MANUAL RELEASE MECHANISM
To manual release the 415 Operator perform the
PREPARE THE GATE following steps as shown in Figure 2.
Before you install the 415 Operator, you need to prepare 1. Slide the key access cover toward the front of the
the gate itself for the operator. Be sure to do the operator.
following: 2. Insert the key and turn it counterclockwise 1/4 turn.
October, 2005
4 1 5 L L S O pe ra t o r A n d Page 7
4 2 5 D C o n t r o l P a ne l I n s t a l l a ti o n M a n u a l
3. Turn the manual release knob clockwise 1/2 turn. After attaching the electric cables to the 415 Operator,
4. To re-engage the operator, perform the procedure you will need to thread the cables thru the assembled
in reverse. cable/strain relief cover and tighten the strain relief as
shown in figure 5.
Now the 415 operator is manual released. You can
move the gate freely.
1 2
LIMIT SWITCH CABLE Follow the instructions below to install your operator
whether in an inward or outward swinging
Sticker Labeled Color Description configuration.
COM Blue Common Wire Installing the operator consists of the following steps:
FCC Brown Closing Limit
∗ Attaching the rear mounting bracket
FCA Black Opening Limit ∗ Attaching the operator to the rear mounting bracket
∗ Attaching the front mounting bracket to the
OPERATOR MOTOR CABLE
operator
Sticker Labeled Color Description ∗ Attaching the front mounting bracket to the gate
leaf
M Blue Motor Directional ∗ Installing the 425 D control panel
M Brown Motor Directional ∗ Setting the operating controls
You need to determine whether to attach the rear You should be able to lengthen or shorten the cylinder
mounting bracket directly to the post (or wall) or to by pulling or pushing the cylinder. Lengthen or shorten
notch the post and install a recessed liner. Large pillars the operator to the required distance for your gate
require a recessed liner to house the rear mounting installation:
bracket and part of the operator so that the pillar will
not interfere with the swing of the gate when it is fully Inward swinging: Lengthen the piston rod until
opened. the appropriate limit led goes out on the
control panel.
To determine whether you need a recessed liner,
measure the distances B and D (shown in Fig. 9) on your Outward swinging: Shorten the piston rod until
gate. If your measure of B or D is greater than the the appropriate limit led goes out on the
dimensions shown for your operator in Figure 9, notch control panel.
the post and construct a recessed liner for the post
mounting bracket (see Figure 7). The recessed liner With the gate in the fully closed position, temporarily
should be constructed of 3/16 or 1/4 in. steel with a clamp the front mounting bracket (previously attached
minimum interior height of 8in. (252.4 cm) so as to to the operator) to the gate leaf and insure that the
allow you to meet the required dimensions shown in cylinder is level.
Figure 9. Make sure the recessed liner is securely
embedded in the post (or wall). Remove the operator from the front mounting bracket
for welding.
There are two parts to the rear mounting bracket. The
horizontal bracket attaches to the operator, and the
If the cylinder has not been extended beyond its limit
slotted vertical plate attaches to the gate post. Weld the
two parts together and bolt the assembly to the gate switch attached to front mounting bracket, then with
post of column. Note, though, that use of the vertical the operator detached from the front mounting bracket,
rear mounting plate is optional. permanently attach (weld) the front mounting bracket to
the gate leaf (see Figure 8).
Once you have positioned the rear mounting bracket,
attach the bracket to the post (or wall or recessed liner), Once the front mounting bracket is welded in place, you
making sure the dimensions on your gate system match
can reattach the operator to the bracket.
those shown in Figure 9.
ATTACH THE OPERATOR TO THE REAR
Outward swinging gate:
5 29/32 in.
(15 cm)
Mounting Dimensions
90-deg Swing 110-deg Swing
A 7 5/8 in. (195 mm) 6 5/8 in. (170 mm)
B 7 5/8 in. (195 mm) 6 5/8 in. (170 mm)
WARNING! A and B should differ by no more than 2 in. Larger differences may dangerously
alter the speed of operation and possibly make the limit switches inoperable.
C 50 3/4 in. (1290 mm)
D Maximum 5 in. (125 mm) 4 2/5 in. (110 mm)
E Less Than A Less Than A
Gate post
Axis of rotation
(or column)
for gate leaf
Centerline of gate leaf
D E
A
F
Figure 10. Important
mounting dimensions for C
outward-swinging 415
Steel elbow B
Mounting Dimensions
90-deg Swing 110-deg Swing
A 7 5/8in. (195 mm) 6 5/8 in. (170 mm)
B 7 5/8 in. (195 mm) 6 5/8 in. (170 mm)
WARNING! A and B should differ by no more than 2 in. Larger differences may dangerously alter
WARNING! Motor one (1) limit switch must be wired For the complete 425 D Control Panel Installation
to FCA1 and FCC1 on the 425 D Control Panel. Motor Instructions, see pages 14—25 of this manual.
two (2) limit switch must be wired to FCA2 and FCC2
on the 425 D Control Panel.
Figure 11.
Limit Switch Cover with Fastening Screw.
1
2
5
78
3
1 A
4
A
5
A C
B 3
67
B
A
NOTE: Locate activation switches at
least10 ft from the gate.
C
D
98
Parts List
415 L LS Operator
POS PART NO. DESCRIPTION QTY
17 490104 Cylinder 1
23 60202165 Bushing 2
26 709324 Gasket 1
The 425 D control panel requires the 100VA USING A JUNCTION BOX
transformer (included) 115vac primary and 24vac
secondary. The power supply should be protected by If an operator is more than 2 ft away from the control
a 15 amp dedicated circuit breaker (not provided). panel, you must use a junction box for connection. Use
a U. L. Listed cord grip where the operator cord enters
The installer is responsible for providing the main the junction box.
power breaker switch, and for making sure that the
entire gate system meets all applicable electrical Note: If you have a one-leaf gate design, the
codes. The installer should refer to the installation operator must be connected to Motor 1 (terminals
manual for a given operator for more information. APM1 and CHM1) in the CN2 Terminal Block
NOTE: An installation is U.L. compliant only To wire up motor 1, connect the blue wire to terminal
when you install the FAAC operators APM1(on the CN2 terminal strip), the brown wire to
according to the UL325 standards. CHM1..
INSTALLING THE 425 D CONTROL Note: If you want to delay the closing of one gate
PANEL leaf in a two-leaf gate design, be sure to connect
its operator to Motor 1.
Installing the control panel consists of the following
general steps: In order to wire motor 2 in a bi-parting system, connect
the blue wire to terminal APM2 (on the CN2 terminal
∗ Connecting the main power strip), the brown wire to CHM2.
∗ Connecting the activating device
∗ Connecting the operator(s)
October, 2005
4 1 5 L L S O pe ra t o r A n d Page 15
4 2 5 D C o n t r o l P a ne l I n s t a l l a ti o n M a n u a l
with UL 325.
ACTIVATING DEVICES AND RADIO RECEIVER: The The STOP should be illuminated except when the stop
THE 425 D CONTROL PANEL INSTALLATION INSTRUCTIONS
activating devices and radio receiver for your gate button is pressed. FSWOP and FSWCL should be
must have normally open (N.O.) contacts. Connect illuminated except when the reversing devices, for
such devices to terminals OPEN A and COM. opening and closing, respectively, are triggered. Use the
LEDs and the next table to determine if the accessory
NOTE: The FAAC radio receiver plugs into devices you have installed are operating properly.
the 5 prongs labeled CN5 (Quick connect
port). Electric Locks: An electric lock can be wired to the
425 D in terminals ELS and ELS (24Vdc pulsed
Page 18 shows how to connect a three or four wire provided) in the CN2 terminal block. If a reversing
receiver. stroke is needed to allow the electric lock to release,
this must be done in programming.
FAAC PLUG IN RADIO RECIEVER: If you are
installing the FAAC Receiver use the quick-fit See page 18 for the connections for a magnetic locking
connector CN5. device.
NOTE: If your using both a receiver and WARNING LIGHT: Connect a warning light to
decoder, hard wire the decoder and plug in terminals labeled lamp in the CN2 terminal block.
the receiver. The terminals provide an output voltage of 24 VDC,
maximum power 15 Watts. This output voltage will
OPEN/HOLD OPEN DEVICE: To open and hold open power most 24 VDC warning lights.
the gate, simply maintain a contact across terminals
OPEN A and COM. (“A” Mode only) NOTE: The behavior of the warning light is as
follows. During programming the light will flash
STOP BUTTON: The stop button you install must every 1/2 second during opening and every 1 1/2
have normally closed (N.C.) contacts. Multiple stop seconds during closing. If you are in automatic
buttons must be wired in series. Connect your stop mode (A), upon reaching the open position, the
device between terminals STOP and COM. output will remain on for 5 seconds to inform you
that the gate will close automatically. It will also
NOTE: The 425 D will not operate the motors flash for up to 10 seconds if the gate is open and a
without a closed circuit between STOP & COM. safety is triggered.
The LED Indicators: The nine light emitting The output can also be set as a courtesy light that stays
diodes (LEDs) on the control panel can be used to illuminated for 90 seconds. See the programming
check for the proper function of the devices section (G0 and G1) for further details
attached to the panel. The LED lights are on
whenever the contacts are closed across each of the SET OPERATING MODES
respective terminals.
DL6 Stop Device Stop Signal • A (automatic): The gate opens on command
STOP Normal Given and automatically closes after a pause phase. A
second command while opening is ignored; a
second command during the pause phase
DL2,DL3 interrupts the pause time; a second command
Limit Switches Limit Switches
DL4,DL5 during closing reopens the gate. A maintained
Normal Triggered
Limits open command will hold the gate open.
October, 2005
4 1 5 L L S O pe ra t o r A n d Page 17
4 2 5 D C o n t r o l P a ne l I n s t a l l a ti o n M a n u a l
LEAF DELAY: You may choose to delay one leaf on OBSTACLE RECOGNITION
closing for overlapping gate leaves. Be sure the
operator on the leaf for delayed closing is connected In the event that two obstacles are sensed in succession,
to Motor 1. the motor(s) will stop. At this point the control panel will
require an activation signal which will cause the motor(s)
The opening leaf-delay time of 1.5 seconds cannot be to run open and then close at slow speed to “reprogram”
adjusted. the location of the open and closed limit switches.
The closing leaf-delay time is adjustable from 1.5 to
10 seconds.
(a) To the U. L. Listed gate operator (b) U.L. Listed Control Panel Enclosure
Ground
Conduit to U.L. Listed con-
trol panel enclosure ac-
To the U.L. Listed cording to N.E.C.
control panel
-
+ Lock
-24V +24V
24 vdc
OPEN COM
C Relay
NO N.C.
A
ELS
N.O.
COM
ELS
Partial Activation Device
(Open Motor 1
only on a dual gate) Limit Sw itch Jumpers
OPEN COM
Reversing Photocells
3 & 4 Wire Radio Receivers
(DC Radios Only)
Additional
Reversing Devices 1
TX If 4 Wire Receiver
2
+24V -24V OPEN COM
C
+24V -24V FSW COM
1 NO
CL
2 -
3 RX +
4
5
WARNING! Turn off the main power before you 1.5 seconds
make any electrical connections or set any
switches inside the control panel box. 3 seconds
Left Right
Courtesy Light (Light stays lit solid for
90 seconds)
Low
Minimum force, maximum
sensitivity LIMIT SWITCHES (WITH/WITHOUT)
The following table shows the descriptions of the display Fuse Protects
during a normal operating procedure
F1 = 10Amp Main Power
250V
Value Shows Descriptions
F2 = 1.6Amp Accessories/Charging
—— —— Gate Closed and at Rest 250V Circuit
F3 = .800mAmp Flashing Light
Gate is Opening (Open in “E” Mode) 250V
NOTE: The operators will run at slow speed during the motor
run time programming phase.
MAINTENANCE
THE 415 OPERATOR THE 425 D CONTROL PANEL
Keep the Control Panel free from spider webs, insects,
The FAAC 415 Operator requires no maintenance.
etc. Otherwise the Control Panel requires no
Periodically inspect the operator, however, to ensure
continued proper operation. maintenance.
• Outward swinging gates with automatic • An automatic gate operator should not be
operators should not open into a public area. installed on a gate if people can reach or
extend their arms or legs through the gate.
Such gates should be guarded or screened to
prevent such access.
October, 2005
Page 22 4 1 5 L L S O pe r a t o r A n d
4 2 5 D C o n t ro l P a ne l I n s t a l l a ti o n M a n u a l
TROUBLESHOOTING
WARNING! Before you do any work on the control panel,
be sure to turn off the main power. And disconnect the batteries
NOTE: Any control panel specific information in the following applies to the 425 D control panel only.
PROBLEM: THE GATE DOES NOT RESPOND TO PROBLEM: THE GATE DOES NOT FULLY OPEN
AN ACTIVATING SIGNAL. (OR CLOSE).
SOLUTION: SOLUTION:
You should have at least one operator wired to The control panel might need to be reprogrammed. If the gate
terminals APM1 and CHM1. has warn or damaged hinges or hardware the panel might
need to be reprogrammed for this type of problem.
Verify that all the correct leds are illuminated. If they are
not illuminated, be sure that you have closed circuits in Check to see that there are no obstructions in the path
the stop and reversing inputs. of the gate or that the hinges are not binding.
Verify that your activating device works properly. OP
should illuminate on the display when you signal the PROBLEM: THEOPERATOR DOESN'T WORK
gate to open. If OP does not illuminate when you signal SMOOTHLY AND THE GATE JERKS AS IT OPENS
the gate, then the problem may be in your activating AND CLOSES.
device. Short across terminals OPEN A and COM. If the
short causes the gate to open, then the problem is in
the activating device. Repair or replace the device.
SOLUTION:
Make sure the Manual Release Mechanism has fully
PROBLEM: THEGATE DOESN'T OPEN (OR CLOSE) engaged the worm screw operation of the operator.
THOUGH THE MOTORS ARE RUNNING.
Make sure that a flexible gate leaf is not the problem. If
the gate leaf flexes, then stiffen the gate or use a slower
SOLUTION:
operator.
Make sure that the motor is running in the right
direction, and make sure the Manual Release
mechanism has fully engaged the system.
SOLUTION:
Make sure you have selected the desired operating
mode.
NOTES
October, 2005
4 1 5 L L S O pe ra t o r A n d Page 24
4 2 5 D C o n t r o l P a ne l I n s t a l l a ti o n M a n u a l
LIMITED WARRANTY
To the original purchaser only: FAAC International, been operated under conditions more severe than, or
Inc., warrants, for twenty-four (24) months from the otherwise exceeding, those set forth in the
date of invoice, the gate operator systems and other specifications for such product(s). Neither FAAC S.p.A.
related systems and equipment manufactured by FAAC or FAAC International, Inc., shall be liable for any loss or
S.p.A. and distributed by FAAC International, Inc., to be damage whatsoever resulting, directly or indirectly,
free from defects in material and workmanship under from the use or loss of use of the product(s). Without
normal use and service for which it was intended limiting the foregoing, this exclusion from liability
provided it has been properly installed and operated. embraces a purchaser's expenses for downtime or for
FAAC International, Inc.'s obligations under this making up downtime, damages for which the purchaser
warranty shall be limited to the repair or exchange of may be liable to other persons, damages to property,
any part of parts manufactured by FAAC S.p.A. and and injury to or death of any persons. Neither FAAC
distributed by FAAC International, Inc. Defective S.p.A. or FAAC International, Inc., assumes nor
products must be returned to FAAC International, Inc., authorizes any person to assume for them any other
freight prepaid by purchaser, within the warranty liability in connection with the sale or use of the
period. Items returned will be repaired or replaced, at products of FAAC S.p.A. or FAAC International, Inc. The
FAAC International, Inc.'s option, upon an examination warranty hereinabove set forth shall not be deemed to
of the product by FAAC International, Inc., which cover maintenance parts, including, but not limited to,
discloses, to the satisfaction of FAAC International, Inc., hydraulic oil, filters, or the like. No agreement to replace
that the item is defective. FAAC International, Inc. will or repair shall constitute an admission by FAAC S.p.A. or
return the warranted item freight prepaid. The products FAAC International, Inc., of any legal responsibility to
manufactured by FAAC S.p.A. and distributed by FAAC effect such replacement, to make such repair, or
International, Inc., are not warranted to meet the otherwise. This limited warranty extends only to
specific requirements, if any, of safety codes of any wholesale customers who buy directly through FAAC
particular state, municipality, or other jurisdiction, and International, Inc.'s normal distribution channels. FAAC
neither FAAC S.p.A. or FAAC International, Inc., assume International, Inc., does not warrant its products to end
any risk or liability whatsoever resulting from the use consumers. Consumers must inquire from their selling
thereof, whether used singly or in combination with dealer as to the nature and extent of that dealer's
other machines or apparatus. warranty, if any.
Any products and parts not manufactured by FAAC This warranty is expressly in lieu of all other
S.p.A. and distributed by FAAC International, Inc., will warranties expressed or implied including the war-
carry only the warranty, if any, of the manufacturer. This ranties of merchantability and fitness for use. This
warranty shall not apply to any products or parts thereof warranty shall not apply to products or any part
which have been repaired or altered, without FAAC thereof which have been subject to accident, negli-
International, Inc.'s written consent, outside of FAAC gence, alteration, abuse, or misuse or if damage was
International, Inc.'s workshop, or altered in any way so due to improper installation or use of improper
as, in the judgment of FAAC International, Inc., to affect power source, or if damage was caused by fire, flood,
adversely the stability or reliability of the product(s) or lightning, electrical power surge, explosion, wind
has been subject to misuse, negligence, or accident, or storm, hail, aircraft or vehicles, vandalism, riot or
has not been operated in accordance with FAAC civil commotion, or acts of God.
International, Inc.'s or FAAC S.p.A.'s instructions or has