Instruction Manual (Input Conversion)

1) The document describes procedures for changing the input type of a DC1010/1020/1030/1040 device from thermocouple to RTD or linear input by moving a jumper. No calibration is required for the input conversion. 2) Wiring distinctions are provided for thermocouple, RTD, and linear inputs. Hardware settings like resistors and jumpers are also described for configuring the linear input type. 3) Steps are outlined for unlocking parameters, showing the ANL1 and ANH1 calibration parameters, and then calibrating the input by inputting minimum and maximum signals and adjusting the ANL1 and ANH1 values accordingly.

Uploaded by

voicedont die
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
85 views9 pages

Instruction Manual (Input Conversion)

1) The document describes procedures for changing the input type of a DC1010/1020/1030/1040 device from thermocouple to RTD or linear input by moving a jumper. No calibration is required for the input conversion. 2) Wiring distinctions are provided for thermocouple, RTD, and linear inputs. Hardware settings like resistors and jumpers are also described for configuring the linear input type. 3) Steps are outlined for unlocking parameters, showing the ANL1 and ANH1 calibration parameters, and then calibrating the input by inputting minimum and maximum signals and adjusting the ANL1 and ANH1 values accordingly.

Uploaded by

voicedont die
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 9

Instruction Manual

(Input Conversion)

DC1010/1020
1030/1040

Rev 4
Contents

1. Input Change (TC & Linear  RTD) ......................................................................................3


2. Wiring Distinction between TC& Linear .....................................................................................4
3. Linear Input H/W Setting .........................................................................................................5
4. To view the ANL1, ANH1 parameters. .......................................................................................7
4-1. Unlock the protection.....................................................................................................7
4-2. Show the parameters.....................................................................................................7
4-3. Calibration ....................................................................................................................8
4-4. Procedure of Calibration .................................................................................................9
1. Input Change (TC & Linear  RTD)
To change the input type from TC to RTD or RTD to TC,Move a jumper.
For Linear type, it’s same as that of TC.

1) DC1010

TC

RTD

2) DC1020/DC1030/1040

TC

RTD

* No Calibration or Adjustment Required


While Input Conversion between TC & RTD.
2. Wiring Distinction between TC& Linear
1) DC1010
Input Wiring

Linear TC
7 7 Set Input Code in Level 3
for TC or Linear Input after Profer Wiring
8 8

9 9

10 10

2) DC1030
Input Wiring

Linear TC
11 11
Set Input Code in Level 3
for TC or Linear Input after Profer Wiring
12 12

13 13

14 14

3) DC1020/1040
Input Wiring

Linear TC
17 17
Set Input Code in Level 3
for TC or Linear Input after Profer Wiring
18 18

19 19

20 20
3. Linear Input H/W Setting
For jumper, please see ‘1. Input Changes’ section.
1) DC1010

R1
R4 R2
S1 S4 R5 R3
S2
S3
S5

7 8 9 10

Input Code S1 to S5
Input Type R1 to R5
AN 4 AN 5 Jumper Status
0~20 mA
mA R3 = 100  R5 = 2.4  S3 & S5 Short
4~20 mA
0~1 V R1 = 2 K S1 & S4 Short
V 0~5 V 1~5 V R2 = 10 K R4 = 100  S2 & S4 Short
0~10 V 2~10 V R3 = 22 K S3 & S4 Short
mV 0~100mV 20~100mV - - S3 & S4 Short

2) DC1030

R1
R4 R2
S1 S4 R5 R3
S2
S3
S5

11 12 13 14

Input Code S1 to S5
Input Type R1 to R5
AN 4 AN 5 Jumper Status
0~20 mA
mA R3 = 100  R5 = 2.4  S3 & S5 Short
4~20 mA
0~1 V R1 = 2 K S1 & S4 Short
V 0~5 V 1~5 V R2 = 10 K R4 = 100  S2 & S4 Short
0~10 V 2~10 V R3 = 22 K S3 & S4 Short
mV 0~100mV 20~100mV - - S3 & S4 Short
3) DC1020/1040
R1
R4 R2
S1 S4 R5 R3
S2
S3 S5

17 18 19 20

Input Code S1 to S5
Input Type R1 to R5
AN 4 AN 5 Jumper Status
0~20 mA
mA R3 = 100  R5 = 2.4  S3 & S5 Short
4~20 mA
0~1 V R1 = 2 K S1 & S4 Short
V 0~5 V 1~5 V R2 = 10 K R4 = 100  S2 & S4 Short
0~10 V 2~10 V R3 = 22 K S3 & S4 Short
mV 0~100mV 20~100mV - - S3 & S4 Short

Input Code
Input Type
AN 1 AN 2 AN 3 AN 4 AN 5
mV -10~10mV 0~10mV 0~20mV 0~50mV 10~50mV
4. Calibration Procedure
Check if it shows the ANL1 and ANH1 on CONFIGURATION2. (Go to step 4-3.)
If the parameters are not shown, go to below steps.
4-1. Unlock the protection
Go to ‘LCK’ parameter on CONFIGURATION 1.
(1-1) Press the SET key for 5 seconds. It will show P1 on CONFIGURATION 1.

5seconds

5seconds

Step (1-4)
(1-2) Press the SET key until it will show LCK parameter.
(1-3) Input ‘1111’ to LCK parameter by using up/down and shift key.
(1-4) Press the SET and shift key for 5 seconds at ‘step (1-3)’. It shows ‘SET1’ of Step (2-1).
4-2. Show the parameters
Modify parameter of ‘CONFIGURATION 3’
SET2.4
SET2.3
SET2.2
SET2.1

Step (2-3)
(2-1) Press the SET key just one time until it will shows ‘SET2’.
(2-2) Change the first value of left side to 1. (SET2.2 = 1)
In case of RSP(Input2), SET2.4=1.(It shows ANL2, ANH2.)
(2-3) Press the SET and shift key for 5 seconds and return to OPERATION.
4-3. How to Calibrate
(3-1) Preparation of sources
- DC Current source : DC 0~20mA or 4~20mA
- DC voltage source : DC 0~1V, 0~5V, 0~10V, 1~5V, 2~10V
(3-2) Press the SET and shift key for 5 seconds, it will show ‘INP1’ of Configuration2.
Set INP1 to ‘AN5’ in case of DC 4~20mA.(Refer to INPUT CODE of ‘Linear input H/W setting’)

(3-3) Press the SET key just one time to show ANL1 parameter.
(3-4) Connect input source with INP1 terminals according to wiring diagram.
(3-5) Adjust the calibration values for Lower side(ANL1) and Upper side(ANH1).

In case of RSP(Input2), execute the calibration for each ANL2, ANH2.


(3-6) Refer to procedures as followings.
4-4. Procedure of Calibration
(Range of PV : 0~3000, Input : 4~20mA)
Set ‘INP1 = AN5’ Set INP1(Level 3), 4~20mA : AN5
(Refer to ‘3. Linear Input H/W
‘SET 2.2 = 1’ Setting’)
In case of Linear input model,
(To activate the steps of ANL1 & The default is ‘SET2.2 = 1’
ANH1 )

Set ‘DP=0000’ DP : Decimal Point


Set Decimal point place

Define LSPL & USPL in Level 3 Assuming LSPL = 0, USPL = 3000

Input ‘Lower Limit signal’ In case of 4~20mA, input 4mA

Go to ‘ANL1’ step in Level 3

PV
Adjust SP, until ‘PV=LSPL’
Press ‘ ’ key, adjust ‘ANL1’
SP (In case of this, PV=0)

Input ‘Upper Limit signal’ In case of 4~20mA, input 20mA

Go to ‘ANH1’ step in Level 3

Adjust SP, until ‘PV=USPL’


PV
(In case of this, PV=3000)
Press ‘ ’ key, adjust ‘ANH1’
SP

No Check LSPL, USPL if right value


Check, ‘OK’ ?
(Input Lower/Upper Limit signal, Check)
Yes
END