VHC-102 Hydraulic Control Specifications: Vertitron Midwest, Inc
VHC-102 Hydraulic Control Specifications: Vertitron Midwest, Inc
VHC-102 Hydraulic Control Specifications: Vertitron Midwest, Inc
VHC-102
Hydraulic Control
Specifications
Mailing Address
Vertitron Midwest, Inc.
19336 607th Avenue
Mankato, MN 56001
Telephone
Toll Free Tech Support: (888)-864-3683
Voice: (507) 245-3399
Fax: (507) 245-3799
1.1. The 4 X 20-character display allows the mechanic to see all of the following information at
the same time.
1.2. Time Clock – Displays the time and date. Is used to log date and time of errors.
3.1.1. The control system shall be provided with the following inspections operations per ANSI
A17.1 code.
3.2.1. The control system shall be provide with a “Test” operation that is activated by a switch
labeled “test” that is located on the control panel. With the TEST switch in the ON position
the elevator door opening sequence and all hall calls shall be disabled. Car calls shall remain
operational. The elevator doors can only be opened with constant pressure on the door open
button. This enables a technician to run the controller floor to floor using car calls without
having to worry about people entering the elevator. Fire Service operation shall override the
TEST mode immediately.
3.3.1. The Shunt Trip breaker shall send a signal to the controller when an over heat condition
occurs at the breaker. The elevator shall stop at the next available landing, open the doors
and shut down. An elevator that is stopped at a landing shall open the doors and shut down.
Once the elevator has been taken out of service the controller sends a signal to the shunt trip
breaker. The breaker then removes power from the control panel. The intention is to stop the
elevator and remove power before the sprinkler system is activated. The shunt trip feature
should override all other operations including Fire Service.
3.4.1. Provide automatic 2-way leveling device to maintain platform within 3/8' of landing
regardless of the load up to the rated capacity. The Leveling device shall function when
doors and gates are open or closed.
3.5.1. Fireman Operation shall meet the requirements of the ASME A17.1d-2000 code section
211.
3.6.1. Controller shall be provided with Hoistway and Car Door Bypass Switches. When either
or both of the switches are in the “BYPASS” position, all means of operation shall be made
inoperative except top-of-car and in-car inspection operation. A warning sign shall be
adjacent to the “BYPASS” switches stating, “Jumpers shall not be used to bypass hoistway-
door or car-door electric contacts.”
3.7.1. The momentary pressing on one or more car buttons shall send the car to the designated
landings in the order in which the landings are reached by the car, irrespective of the
sequence in which the buttons are pressed. During this operation, the car shall answer calls
from the landings which are in the prevailing direction of travel and each call shall be
cancelled when answered.
3.7.2. With the momentary pressing of a hall button above the car, the car shall start up and
answer any “up” calls as they are reached by the car irrespective of the sequence in which
the buttons are pressed. The car shall not stop at floors where “down” buttons only are
pressed. Similarly, the car shall start down to answer calls below the car and shall not stop
where “up” calls only are registered. When traveling “up,” the car shall reverse at the
highest call and proceed to answer calls below it, Similarly, when traveling “down,” the car
shall reverse at the lowest call and answer calls above it.
3.7.3. Should both an “up” or “down” call be registered at an intermediate landing, only the call
corresponding to the direction in which the car is traveling shall be canceled upon the
stopping of the car at that landing.
3.8.1. The Independent Service operation is activated with a key switch located in the elevator.
Once placed on independent service all current car and hall calls on a simplex system shall
be erased and the elevator will park with the doors open. If the elevator is in motion when
the key switch is activated stop the elevator at the next available landing and park with the
doors open. Car and hall Lantern outputs are not operational. The elevator will respond only
to car calls. Automatic doors shall close only constant pressure on the door close push
button until the doors are fully closed. If the elevator is on independent service and a fire
service signal is activated the light and buzzer shall immediately be activated. Doors that are
fully open will wait 15 – 60 seconds to close and transfer from independent service to
fireman operation.
3.9.1. Nudging, Fireman Service, and EMT shall share the buzzer output. This is possible
because nudging is disabled during Fireman Operation.
3.10.1. The car direction lanterns and gong shall be activated when the elevator is stopping at a
floor and the car has a future direction demand or the elevator is answering a hall call. This
sequence should start after the doors have started to open. This allows the passenger
standing outside the elevator to see the direction lantern sequence. The up lantern output
shall be activated once if the future direction is up and the down lantern twice if the future
direction is down. The gong sequence will match the lanterns (once for up and twice for
down). The gong output is a pulse. The UP lantern should stay lit until the doors have fully
closed.
3.11.1. A sensor located in the oil reservoir shall activate low oil operation. The controller will
activate the low oil output and the elevator shall return to the lowest landing and be placed
out of service. The door open button shall remain operational. Calls and position indicator
signals shall be inoperative.
3.12.1. A sensor located in the oil pressure line activates the negative pressure input. The control
system disables the down high speed and down leveling outputs. Leveling in the up
direction (anti-creep) is still operational. If pressure is lost in the system and the elevator is
not at the lowest landing it is assumed that the elevator is physically stuck. The door
operation should be disabled and the elevator should be taken out of service. An elevator
that is at the lowest landing when the negative pressure input is activated is assumed to be
on the buffer springs. In this condition the elevator shall be taken out of service with the
door open button still operational.
3.13. Nudging
3.13.1. Blocking the elevator proximity device or photo eye for more than 30 seconds
(programmable timer) while there are registered calls in the system the controller shall
activate the nudging operation. The nudging output combined with the door close output
will cause the doors to close in slow speed. If the safety edge input is activated while the
doors are closing in nudging operation the doors shall stop. Closing will continue after the
safety edge signal is removed. The nudging buzzer output will be active until the doors are
fully closed.
3.13.2. The door open button shall reopen the doors and cancel nudging operation. The doors
will then re-close in normal operation after the reopen timer has expired.
3.14.1. If the controller does not see a USL (Up Speed Limit) or HSU (High Speed Up
slowdown) input while trying to move in the up direction the Pump Run Timer shall expire
causing the elevator to be place in the “Pump Run Timer” operation. The controller shall
cancel all calls and descend to the lowest landing and be taken out of service. The door open
button shall remain operational. Cycling the power to the control panel will reset the
controller to normal operation.
3.15.1. If any of the down valve outputs are activated for more than 30 seconds without the
controller inputs DSL (Down Speed Limit) or HSD (High Speed Down) being activated it is
assumed that the elevator has stalled while moving in the down direction. The controller
shall cancel all calls and be taken out of service. Cycling the power to the control panel will
reset the controller to normal operation
3.16. Homing
3.16.1. Homing is an optional feature that can be turned on or off by accessing the parameter
programming. If the homing feature is disabled the elevator will park at the last floor served
when no calls are registered in the system. Enabling the homing feature will allow the
customer to choose the homing floor along with the amount of time (1-45 minutes) before
the elevator returns to the home floor. The homing timer will start when the elevator doors
have closed and there are no calls in the system. The elevator shall proceed to the
programmed home floor and park with the doors closed. Any call registered while the car is
traveling to the home landing shall cause the controller to cancel the homing function and
respond to that call. If the elevator was traveling away from the landing for which the call is
registered, it shall stop at the next available landing and reverse its direction.
4.1.1. The operation of each elevator from within the car shall be such that the momentary
pressing of one or more buttons shall send the car to the designated landings. Stops shall be
made in the order in which the landings are reached by the car, irrespective of the sequence
in which the buttons are pressed. During this operation, the car shall also answer calls from
the landings, but only one car shall respond to any one call, and it shall be the car nearest the
call and set for the direction of the hall button pressed. The control shall be arranged so that,
normally, one car shall be parked at the main lower terminal and the other free car, parked at
the landing it last served to be available to answer subsequent hall calls. Should both cars
happen to finish their calls at the main lower terminal, the car which arrived there first shall
become a free car to answer subsequent hall calls.
4.1.2. An idle free car shall answer any hall call either above or below the floor where it is
standing, except hall calls at or below the main lower terminal floor. These calls shall be
answered by the car parked at the main lower terminal. When the free car is clearing calls,
the other car shall automatically start to answer hall calls under any of the following
conditions:
4.1.2.1. Registration of an “up” hall call below the “up” traveling free car.
4.1.2.2. Registration of an “up” or “down” hall call above the “down” traveling free car.
4.1.2.3. The free car is delayed beyond a predetermined time interval.
4.2.1. The hall direction lanterns and gong shall be activated when the elevator is stopping at a
floor and the car has a future direction demand or the elevator is answering a hall call. This
sequence shall start when the elevator initiates a slowdown to stop at a floor and there is a
future direction demand or the elevator is answering a hall call. The up lantern output shall
be activated once if the future direction is up and the down lantern twice if the future
direction is down. The gong sequence will match the lanterns (once for up and twice for
down). The gong output is a pulse. The DOWN lantern should flash twice and stay lit after
the second flash until the doors have fully closed.
4.3.1. An automatic emergency lowering feature shall be incorporated into the control system.
In the event of the loss of normal power the elevator shall return to the lowest landing and
open the doors. The door open push button shall remain active. Upon the resumption of
normal power the elevator shall return to normal operation.
4.4.1. The control system shall be provided with the following “Emergency Power” operation.
4.4.2. A Pre- Emergency Power test signal shall be provided. Upon activation of the Pre-signal
the elevator shall stop at the next available landing and open the doors. After 15 seconds the
doors shall close and the car will be taken out of service. The door open button shall remain
operational.
4.4.3. An Emergency Power On signal shall be provided to indicate that the elevator is currently
operating on “Emergency Power”.
4.4.4. Upon activation of the “Emergency Power On” signal all elevators that are in automatic
operation and located above the designated emergency power lobby shall immediately
return to the designated emergency power lobby and open the doors. After 15 seconds the
doors shall close and the car will be taken out of service. The door open button shall remain
operational.
4.4.5. An elevator currently at or below the designated lobby when the “Emergency Power On”
signal is activated shall remain at that location and open the doors. After 15 seconds the
doors shall close and the car will be taken out of service. The door open button shall remain
operational.
4.4.6. A selector switch shall be provided to send a signal to allow an elevator to run while on
emergency power.
4.4.7. An elevator that is selected to run when the Emergency Power is activated shall continue
to run without delay.
4.4.8. A 30 second delay shall be provided on the “Emergency Power Car Enable” signal to
allow a previously selected car to reach the next available landing before returning to the
designated lobby.
4.5.1. Load Weighing Phase I - When the Load Weighing Phase I input is activated the
controller shall prevent the car from moving keep automatic-closing doors open, and
activate the load weighing output (used to drive an indicator and/or buzzer.
4.5.2. Load Weighing Phase II – When the Load Weighing Phase II input is continually
monitored. When this input is activated the car shall stop only at landings where a car call
has been registered. The hall calls registered at those landings at which the elevator did not
stop shall remain in the system.
4.5.3. Deactivating either of the load weighing inputs will immediately remove the elevator
from the load weighing operation.
4.6. Viscosity
4.6.1. A temperature sensor (provided by VMI) must be wired to the temperature sensor input
located on the main relay board before the Hot Oil or Viscosity features can be activated. To
verify that the sensor is installed and working properly access the Monitor / Volts & Temp
screen from the Main Menu section on the controller diagnostic display and verify that
current oil temperature value is displayed.
4.6.2. The VISCOSITY feature parameter must be set to YES in the feature set-up menu to
activate Viscosity feature.
VISCOSITY = ON
OFF
Once the Viscosity operation is enabled the Viscosity temperature must be set.
(The current oil temperature is displayed at the bottom of the VISCOSITY setup screen)
4.6.3. Once the VIS ON TEMP is reached the elevator will return to the lowest floor and the
motor will run with the valves de-energized until the oil reaches temperature 3 degrees
warmer than the VIS ON TEMP setting. The Viscosity feature has a maximum run time of 5
minutes. Any demand on the elevator will disable the viscosity operation.
4.7.1. A temperature sensor (provided by VMI) must be wired to the temperature sensor input
located on the main relay board before the HOT OIL SHUTDOWN feature can be activated.
To verify that the sensor is installed and working properly access the Monitor / Volts &
Temp screen from the Main Menu section on the controller diagnostic display and verify
that current oil temperature value is displayed.
4.7.2. The Hot Oil feature parameter must be set to ON in the feature set-up menu to activate
HOT OIL SHUTDOWN feature.
Once the HOT OIL SHUTDOWN is enabled the HOT ON TEMP must be set.
(The current oil temperature is displayed at the bottom of the HOT OIL SHUTDOWN
setup screen)
4.7.3. Once the HOT ON TEMP is reached and there are no car calls in the system the elevator
shall return to the lowest floor and park with the doors closed. The Door Open button shall
remain active. Call demands shall be ignored until the oil temperature has been reduced by 5
degrees.
4.7.4. If the temperature sensor is “OPEN” or “SHORTED” the HOT OIL SHUTDOWN
feature is disabled.
4.8.1. The Out of Service output shall be activated any time the elevator is not in automatic
operation with the ability to answer both car and hall calls. This output can be wired to an
indicator in a lobby panel.
4.9.1. Telescopic Resynch operation is a sequence that takes less than 5 min to complete. The
intention is to bring the elevator to the lowest landing and then proceed to bypass the
terminal limits and run in leveling speed for a predetermined amount of time to allow the
elevator to land on the buffer springs. By doing this the telescopic cylinders will be allowed
to resynch. All door function will be disabled during this operation. The controller can be
filed programmed to initiate the resynch operation based on an internal trip counter. The
counter monitors the number of starter outputs. .
4.10.1. Activating the car to lobby input shall cause the elevator to cancel all current calls and
return to the lobby floor (programmable) and park with the doors open. If the car to lobby
input is removed the elevator will return to normal operation after it has reached the lobby
floor.
4.11.1. The intention of the Car Capture feature is to secure the elevator at the “car capture”
programmed floor with the doors closed. Once the Car Capture Security input is removed
the elevator doors shall open and the elevator shall return to automatic operation.
4.11.3. An elevator that is traveling away from the designated floor shall stop at the next
available landing and reverse direction and return nonstop to the designated floor.
4.11.4. Doors that have started opening shall reverse direction and close. The door open button
shall be disabled. Door safety protection devices (photo eye, safety edge, and proximity
device) shall remain operational.
4.11.5. An elevator that is at the “car capture” floor with the doors open shall close the doors and
remain at the landing with the doors closed while the “car capture” input is active. The
doors will only open when the “car capture” input is removed.
4.12.1. VMI will provide a dedicated output that can be used to bypass a security key switch or
card reader device when the elevator is placed on Fireman operation. Custom security
features will be available with the operation and cost based on a written specification.
5.1.1. Parameters
# Stops
Fire Lobby
Alternate Lobby
Machine Room Location
Home Floor
Starter Type
Fire Code
Down Lantern output (1 or 2 pulse)
Inspection Speed
Car Lanterns / Hall Lanterns / Car and Hall Lanterns
5.1.2. Timers
Main Lobby
Alt Lobby
MR at Lobby (Yes or No)
Hoist Detector (Top or Bottom)
Fire Code
Fire Edition (1998 or 2000)