Board Lisa 20 Error
Board Lisa 20 Error
Board Lisa 20 Error
Error description
2 Fehlermeldungen
This manual and the product described herein are protected by copyright for Schneider Steuerungstechnik GmbH or their suppliers
with reservation of all rights. According to copyright, this manual must not be copied in whole or in part without prior written
approval of Schneider Steuerungstechnik GmbH, unless within the context of normal use of the product or in order to create
backups. This exception does not include copies made for and sold to any third parties or ceded to them in any other way.
However, the whole purchased material (including any backups) may be sold, ceded or lent to any third parties. According to legal
stipulations, creating a translation also falls within the definition of copying.
Schneider Steuerungstechnik GmbH does not accept any responsibility or liability for the contents of this manual.
They decline any legal warranty for the marketability or suitability for any special purpose.
Schneider Steuerungstechnik GmbH cannot be held responsible for errors in this manual or any direct or indirect damage related to
the delivery, performance or use of this manual. Schneider Steuerungstechnik GmbH reserves the right to review this manual from
time to time without notice and make changes to its contents.
The operation is not permitted in the USA and in countries with a similar judicial system.
As of: 07.12.2016
Error core : 0
Rückstellung Automatisch
Short text NO_ERR
Long text No error
Description
Reaction General
Rope
Hydraulic
Remedy
Error code : 1
Rückstellung Automatic
Short text Module do not exist!
Long text Critical module not\nalive!
Description A function was programmed to a non-existing Bus-module.
Reaction General The control switches into „out-of-order“ mode.
Rope
Hydraulic
Remedy - Install the missing module
- Re-programm the desired function on an existing module
Error code : 2
-- Reserved error code
Error code : 3
-- Reserved error code
Error code : 4
-- Reserved error code
Error code : 5
Reset 800 + Ok / Recall / Reset
Short text K5 not active!
Long text K5 not active!
Description The control contact of safety relay K5 reports a permanently deenergized relay despite the zone being approached or travelled through.
Reaction General The control switched into „out of operation 5“
Rope The control stops in the next possible landing.
Hydraulic The control stops in the next possible landing and descends into the lowest landing from there.
Remedy
- Check selection signals SM/SZ (First SZ and then SM must turn active when approaching the zone.)
- Check selection signals for voltage (When a signal is active one should be able to measure a 24V voltage between the signal and +24V.)
- Check the DIL switch „S1“ on the LiSA20-relay board (All switches must be positioned on “off”)
- Check the jumper „J3“ (refer to the wiring diagram)
- Visually check the safety relays K5/K6/K7 (deformed contact pins)
- Check the connection processor board -> relay board
Error core : 6
Reset 800 + Ok / Recall
Short text K5 permanently active!
Long text K5 always active!
Description The control contact of safety relay K5 reports a permanently energized relay despite having left the zone.
Reaction General The control switched into „out of operation 6“
Rope The control stops in the next possible landing.
Hydraulic The control stops in the next possible landing and descends into the lowest landing from there.
Remedy
- Check selection signals SM/SZ (First SZ and then SM must turn active when approaching the zone.) ( Pay attention to the LEDs over the relays)
- Check selection signals for voltage (When a signal is active one should be able to measure a 24V voltage between the signal and +24V.)
- Check the DIL switch „S1“ on the LiSA20-relay board (All switches must be positioned on “off”)
- Check the jumper „J3“ (refer to the wiring diagram)
- Visually check the safety relays K5/K6/K7 (deformed contact pins)
- Check the connection processor board -> relay board
Error code : 7
Reset Automatic
Short text SK1 interruption
Long text SK1 interruption in normal mode
Description The safety circuit 1 was interrupted during travel.
Reaction Due to the interruption of the safety circuit the lift is forced to stop and the control switches into „Out-of-operation7“ mode.
Causes - Main switch was switched off
- Control fuse (-F1) has triggered
- Speed governor or lift arrestor contact have triggered
- Other contact before the SK1 tap has triggered (refer to the wiring diagram)
Error code : 8
Reset Automatic
Short text SK1 interruption
Long text SK1 interruption in inspection mode
Description The safety circuit 1 was interrupted during travel
Reaction General Lift stops and no further inspection run can be carried out
Rope
Hydraulic
Causes - Main switch was switched off
- Control fuse (-F1) has triggered
- Speed governor or lift arrestor contact have triggered
- Other contact before the SK1 tap has triggered (refer to the wiring diagram)
Error code : 9
Reset Automatic
Short text SK2 interruption
Long text SK2 interruption
Description The safety circuit was interrupted during normal operation.
Reaction General Due to the interruption of the safety circuit the lift is forced to stop and the control switches into „Out-of-operation“ mode.
Rope
Hydraulic
Causes - Emergency stop was activated
- Revolving door contact has opened
- Other contact between SK1 tap and SK2 tap has triggered (refer to the wiring diagram)
Fehlercode : 10
Reset Rope automatic/Hydro 800+OK
Short text SK2 In","SK1 Off
Long text SK2 active, but SK1 not active
Description This is not a logical state since the safety circuit is fed in after the SK1 tap.
Reaction General The control switches into „Out-of-order“ mode
Rope The lift comes to a halt
Hydraulic The lift descends into the lowest landing
Causes - Jumper in the safety circuit
Fehlercode : 11
Reset 800+Ok / Reset / SK4 opens during inspection mode
Short text SK4 permanently active
Long text SK4 was bridged\nin inspection
Description The control expects the safety circuit to be interrupted when letting go of the direction button during inspection mode. If this does not happen (SK4 remains on), this
error is be recorded.
Reaction General The control switches into „Out-of-order“ mode
Rope
Hydraulic
Causes - Jumper in the safety circuit
Fehlercode : 12
Reset Automatic
Short text Car emergency stop!
Long text Emergency stop in car\nis pressed
Description The emergency stop in the car is monitored by the control. When the emergency call is activated, this error is reported.
Reaction General The control switches into „Out-of-order“ mode
Rope
Hydraulic
Causes - Emergency stop in car is activated
Error code : 13
Reset Automatic
Short text Inverter fault
Long text Inverter fault
Description The inverter reports an error to the control
Reaction General The control switches into „Out-of-order“ mode
Rope
Hydraulic -----------------------------------------------------------------------------
Causes - Check wiring of the fault message contact (refer to the wiring diagram)
- Check the error log of the inverter
Error code : 14
Reset Automatic
Short text Overtemperature 1
Long text Overtemperature 1
Description The PTC thermistor in the travel motor or respectively in the pump motor of the hydraulic reservoir indicated a violation of the maximum allowed temperature (60°C) in
one of these operating equipments to the control at input U1.
Reaction General The control switches into „Out-of-order“ mode
Rope At standstill: After cool down the installation will resume operation
When travelling: The control stops in the next possible landing. After cool down the installation will resume operation.
Hydraulic At standstill: After cool down the installation will resume operation
When travelling: The control stops in the next possible landing. After cool down the installation will resume operation. The landing must be reached
within 10 seconds. Otherwise an emergency stop will be conducted.
Causes - High number of travels
- High ambient temperature
- Defective engine / defective engine fan
Error code : 15
Reset Automatic
Short text Overtemperature 2
Long text Overtemperature 2
Description The PTC thermistor in the travel motor or respectively in the oil of the hydraulic reservoir indicated a violation of the maximum allowed temperature (110°C) in one of
these operating equipments to the control at input U1.
Reaction General The control switches into „Out-of-order“ mode
Rope --------------------------------------------------------------------------
Hydraulic At standstill: After cool down the installation will resume operation
When travelling: The control stops in the next possible landing. After cool down the installation will resume operation. The landing must be reached
within 10 seconds. Otherwise an emergency stop will be conducted.
Causes - High number of travels
- High ambient temperature
- Defective engine
Error code : 16
Reset 800 + Ok
Short text Contactor control drop
Long text Contactor control drop
Description The control cannot read in the input „SAK“ after the end of travel. (contactor not deenergised)
Reaction General The control switches into „Out-of-order“ mode
Rope The control stops in the next possible landing.
Hydraulic The control stops in the next possible lading. Therefrom, the lift descends into the lowest landing.
Causes - Main- or brake contactor defective
- Close auxiliary contact of the contactors
- Lock the preselection relay on the LiSA RB
Error code : 17
Reset 800 + Ok
Short text Contactor monitor on
Long text Contactor monitor\npermanently on
Description The control recognized the input „SAK“ after beginning of travel (contactor not energized)
Reaction General The control switches into „Out-of-order“ mode
Rope The control stops in the next possible landing.
Hydraulic The control stops in the next possible lading. Therefrom, the lift descends into the lowest landing.
Causes - Main- or brake contactor defective
- Close auxiliary contact of the contactors
- Lock the preselection relay on the LiSA RB
Error code : 18
-- Reserved error code
Error code : 19
Reset Automatic
Short text Resend UP and DOWN
Long text Resend UP and DOWN are\nactiv!
Description Both direction signals apply at the controller even though the resend function is switched off.
Reaction General The control switches into „Out-of-order“ mode
Rope
Hydraulic
Remedy - Let go of the direction switch
- Check wiring
- Check jumper position on the PB board (refer to the wiring diagram) ( Jumper RUE/RAUF/RAB )
Error code : 20
Reset Automatic for rope / 800+Ok for hydraulic
Short text Up final switch
Long text Final switch upper floor!
Description If the lift stands above the flush position in the highest landing and the SK1 is interrupted, this error will be recorded.
Reaction General The control switches into „Out-of-order“ mode
Rope The control switches into normal mode when SK1 is closed.
Hydraulic The lift descends into the lowest landing and remains there in „out-of-order“ mode until the error is reset.
Causes - Brake has been released manually – the lift coasts away upwards.
- deceleration distance is not set correctly
- temperature-dependent hydraulic system
- control does not decelerate correctly
- emergency-stop switch is not positioned correctly
Error code : 21
Reset 800+Ok / Resend
Short text Down final switch
Long text Final switch lower floor!
Description If the lift is standing more than 50mm underneath the flush position of the lowest landing and the SK1 is interrupted, this error will be recorded.
Reaction General The control switches into „Out-of-order“ mode
Rope The control switches into normal mode when SK1 is closed.
Hydraulic Die Steuerung wechselt wieder in den Normalmodus wenn SK1 geschlossen ist
Causes - deceleration distance is not set correctly
- temperature-dependent hydraulic system
- Car is overloaded
- control does not decelerate correctly
- emergency-stop switch is not positioned correctly
Error code : 22
-- Reserved error code
Error code : 23
Reset Automatic
Short text Inspection UP and DOWN
Long text Inspection UP and DOWN\nare activ!
Description The controller recognizes both inspection-direction-switches as active.
Reaction General The control switches into „Out-of-order“ mode
Rope
Hydraulic
Causes - Both switches are activated
- Input at the controller is defective
Error code : 24
-- Reserved error code
Error code : 25
Reset Automatic
Short text Inspection & Resend
Long text Inspection & Resend are\n activ!
Description The controller recognizes that both inspection control and resend control are active.
Reaction General The control switches into „Out-of-order“ mode
Rope
Hydraulic
Causes - Both switches are activated
- Input at the controller is defective
-
Error code : 26
-- Reserved error code
Error code : 27
Reset 800+Ok / Resend / Inspection
Short text Error Travel time
Long text Travel time!
Error code : 28
-- Reserved error code
Error code : 29
Reset Automatic
Short text Resend up input active
Long text No resend but resend UPup\n is active
Description The controller recognizes the „up“ input of resend as active despite the resend control being deactivated.
Causes - Direction button is being pushed even though the resend control is not switched on.
- Input at the controller is defective
Error code : 30
Reset Automatic
Short text Resend down input!
Long text No resend but resend \nDOWN is active!
Description The controller recognizes the „down“ input of resend as active despite the resend control being deactivated.
Causes - Direction button is being pushed even though the resend control is not switched on.
- Input at the controller is defective
Error Code : 31
Reset Automatic
Short text Inspection up input?
Long text No inspection but \ninspection UP is active
Description The controller recognizes the „up“-input of inspection as active despite the inspection control being deactivated.
Causes - Direction button is being pushed even though the inspection control is not switched on.
- Check input on the status page (RAB)
Error code : 32
Reset Automatic
Short text Inspection DOWN input?
Long text No inspection but \ninspection DOWN is act.
Description The controller recognizes the „down“-input of inspection as active despite the inspection control being deactivated.
Causes - Direction button is being pushed even though the inspection control is not switched on.
- Check input on the status page
Error code : 33
-- Reserved error code
Error code : 34
Reset Automatic
Short text D1 Open/Close Limit-Sw.
Long text Open/close limit switch
\ndoor 1 together
Description The controller recognizes both door 1 limit switches as active
Causes - Limit switch wiring not correct
- Input at controller is defective
Error code : 35
Reset Automatic
Short text D2 Open/Close Limit-Sw.
Long text Open/close limit switch\ndoor 2 together
Description The controller recognizes both door 2 limit switches as active
Causes - Limit switch wiring not correct
- Input at controller is defective
Error code : 36
Reset Automatic
Short text Software final switch
Long text sortware final up switch
Description The value determined by the absolute encoder does not coincide with the reference value for the highest landing which is determined by the controller (zero-point
+nlandings)
Reaction General The controller switches into „out-of-order“ mode.
Rope The controller initiates an emergency stop.
Hydraulic The controller initiates an emergency stop and descends into the lowest landing.
Causes - Reading error of the absolute encoder
- Defective connection
- Magnetic tape not installed correctly (Installation manual!)
- Defective travelling cable
- Defective CPU
Error code : 37
Reset Automatic
Short text Undershoot lowest floor
Long text Undershoot or refrence \nlevel not correct
Description The value determined by the absolute encoder does not coincide with the reference value for the highest landing which is determined by the controller (zero-point)
Reaction General The controller switches into „out-of-order“ mode.
Rope The controller initiates an emergency stop.
Hydraulic The controller initiates an emergency stop and descends into the lowest landing.
Causes - Reading error of the absolute encoder
- Defective connection
- Magnetic tape not installed correctly (Installation manual!)
- Defective travelling cable
- Defective CPU
Error code : 38
Reset 800 + Ok /Resend / By entering a cabin call
Short text Door 1 did not close
Long text Door 1 did not close \nafter 5 retry
Description The controller initiated 10 attempts for closing, during all of which the safety cicuit failed to successfully close given the predetermined control time for the closing of
doors.
Reaction General The controller switches into „out-of-order“ mode.
Rope
Hydraulic
Causes - defective interlocking contact
- defective door contact
- control time for closing doors is set too restrictively
- door motor has too little contact pressure
Error code : 39
-- Reserved error code
Error code : 40
Reset 800 + Ok
Short text ACCU Error
Long text ACCU-Control Error
Description The lead-battery which is mounted to the controller is either defective or not connected (is only checked in standstill)
Reaction General The controller switches into „out-of-order“ mode.
Rope The lift stops in the current landing
Hydraulic The lift descends into the lowest landing
Causes - battery disconnected
- defective battery
Error code : 41
-- Reserved error code ( still error A3 Board as of 20.01.2016)
Error code : 42
Reset Automatic
Short text Phase Error
Long text Phase Error
Description The integrated phase sequence detects a phase failure or a wrong direction of rotation.
Reaction General The controller switches into „out-of-order“ mode.
Rope The lift stops in the current landing
Hydraulic The lift descends into the lowest landing
Causes - Phase failure in the mains
- Phases are not clamped correctly L1/L2/L3
- Defective fuse in the controller/allocation
Error code : 43
Reset 800 + Ok / Resend
Short text Brake 1 not opened!
Long text Brake 1 not opened!
Description 3 seconds upon termination of travel, the controller checks whether the brakes are opened. That is, in case of an error, the input brake1 (P.42 on the PB) is still applied.
Reaction General The controller switches into „out-of-order“ mode.
Rope
Hydraulic
Causes - activation of the brake does not function properly (refer to wiring diagram)
- brake shoe contact is not set up correctly
- wiring is not correct
- brake fuse (-F8)
- defective input
Error code : 44
Reset 800 + Ok / Resend
Short text Brake 1 not closed!
Long text Brake 1 not closed!
Description 3 seconds upon termination of travel, the controller checks whether the brakes are closed. That is, in case of an error, the input brake1 (P.42 on the PB) is not applied.
Reaction General The controller switches into „out-of-order“ mode.
Rope
Hydraulic
Causes - activation of the brake does not function properly (refer to wiring diagram)
- brake shoe contact is not set up correctly
- wiring is not correct
- defective input
Error code : 45
Reset 800 + Ok / Resend
Short text Brake 2 not opened!
Long text Brake 2 not opened!
Description 3 seconds upon termination of travel, the controller checks whether the brakes are opened. That is, in case of an error, the input brake1 (P.42 on the PB) still applies.
Reaction General The controller switches into „out-of-order“ mode.
Rope
Hydraulic
Causes - activation of the brake does not function properly (refer to wiring diagram)
- brake shoe contact is not set up correctly
- wiring is not correct
- brake fuse (-F8)
- defective input
Error code : 46
Reset 800 + Ok / Resend
Short text Brake 2 not closed!
Long text Brake 2 not closed!
Description 3 seconds upon termination of travel, the controller checks whether the brakes are closed. That is, in case of an error, the input brake1 (P.42 on the PB) is not applied.
Reaction General The controller switches into „out-of-order“ mode.
Rope
Hydraulic
Causes - activation of the brake does not function properly (refer to wiring diagram)
- brake shoe contact is not set up correctly
- wiring is not correct
- defective input
Error code : 47
Reset Automatic
Short text Machin Room TEMPERATURE!
Long text Machine Room over \nTemperature (MRT)!
Description The maximum allowed mashine room temperature has been exceeded. The controller reads input MRT (P.37 on the PB) as active.
Reaction General The controller switches into „out-of- order“ mode. Should this error occur during travel, the current ride will be completed nonetheless.
Rope The lift stops in „out-of-order“ mode at the current landing.
Hydraulic The lift descends into the lowest landing.
Causes - mashine room temperature too high
- Threshold at the thermostat not set correctly
- Wiring not correct
- Defective input
Error code : 48
Reset Automatic
Short text Maximum pressure!
Long text Maximum hydraulic \npressure!
Description The hydraulic system reports to the controller that the max. allowed operating pressure is exceeded. The controller reads the input MAX (P.36 on the PB) as active.
Reaction General The controller switches into „out-of-order“ mode. An emergency stop is conducted.
Rope ---------------------------------------------------------------------------------------------------------------------------
Hydraulic
Causes - maximum pressure exceeded
- wrong settings at the hydraulic manifold
- For Bucher-SIUA defective contact
- wiring not correct
- lift car is overloaded
- defective input
Error code : 49
Reset Automatic
Short text Minimum pressure!
Long text minimum hydraulic \npressure!
Description The hydraulic system reports to the controller that the min. allowed operating pressure is exceeded. The controller reads the input MAX (P.35 on the PB) as active.
Reaction General The controller switches into „out-of-order“ mode. An emergency stop is conducted.
Rope ---------------------------------------------------------------------------------------------------------------------------
Hydraulic
Causes - minimum pressure not achieved
- wrong settings at the hydraulic manifold
- wiring not correct
- defective input
Error code : 50
Reset Automatic
Short text Minimum Room TEMPERATURE!
Long text Machine Room \nMinimum Temperature!
Description The minimum allowed machine room temperature is underrun (5°C)
Reaction General The controller switches into „out-of- order“ mode. Should this error occur during travel, the current ride will be completed nonetheless.
Rope The lift stops in „out-of-order“ mode at the current landing.
Hydraulic The lift descends into the lowest landing.
Causes - Machine room temperature too low (<5°C)
- Threshold at the thermostat not set correctly
- Wiring not correct
- Defective input
Error code : 51
Reset 800+OK+ Reset via key switch at the emergency unlock board // ( 800010 the output “Reset emergency unlock SW” should be programmed)
Short text Em. unlock reset active
Long text Emergency unlock reset \nactive!
Description The controller recognized the reset-input of the emergency unlock as active even though the input „emergency unlock active“ is not active.
Thereupon the controller switches the output “Reset emergency unlock” in such manner that the emergency unlock monitoring is activated.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - Wiring not correct
Defective input
Remedy - See causes
- Check input on the status page
If the input should be defective it can be parameterized to another available I/O any time.
Error code : 52
Reset Deactivate reset key -> 800+OK -> activate reset key and deactive within 2 sec. // ( 800010 the output “Reset emergency unlock SW” should be programmed)
Short text Em.unlock res.per.activ
Long text Emergency unlock reset \npermanently active!
Description The controller recognizes the reset input of the emergency unlock monitoring as being permanently active.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - Reset keyis being activated permanently
- Wiring not correct
- Defective input
Error code : 53
Reset activate reset key and deactive within 2 sec. // ( 800010 the output “Reset emergency unlock SW” should be programmed)
Short text Em. unlock no SKx
Long text Emergency unlock active\nbut no SAFETY chain!\ntry again
Description The emergency unlock has been restored by the reset, the safety circuit however has not been closed.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - Safety circuit still open at another spot
- wiring not correct
Error code : 54
-- Rerserved error code
Error code : 55
Reset 800+OK -> activate reset key and deactive within 2 sec. // ( 800010 the output “Reset emergency unlock SW” should be programmed)
Short text SSNOT not in safety ch.
Long text SNOT board K4 error \nEmergency-unlock active\n->safety circuit!
Description After activation of the emergency unlock, the controller still recognizes the SK1, SK2, SK3 or the SK4 input.
In the safety circuit, the emergency unlock monitoring contact is positioned after the SK2 query; thus after activation of the emergency unlock all subsequent safety
circuit queries must be inactive.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - contact not linked correctly
- bridges in the safety circuit
- wiring not correct
- defective input
Error code : 56
-- Reserved error code
Error code : 57
-- Reserved error code
Error code : 58
-- Reserved error code
Error code : 59
Reset Reset the emergency unlock monitoring or switch on the inspection control (take measures to ensure the upper protective space)
Short text Emergency-unlock up
Long text Emergency-unlock up\nactive
Description The emergency unlock which serves to recognize if someone wishes to embark onto the lift car has released.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - upper shaft doors are opened
- wiring not correct
- defective input
Error code : 60
Reset Reset the emergency unlock monitoring
Short text Emergency-unlock down
Long text Emergency-unlock down\nactive
Description The emergency unlock which serves to recognize if someone wishes to enter the shaft has activated. It is not possible to conduct a resend- or inspection run.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - bottom shaft doors are opened
- wiring not correct
- defective input
Error code : 61
Reset 800 + Ok / By entering a cabin call
Short text retrys close Door 2
Long text Door 2 did not close \nafter retrys!
Description The controller initiated 10 attempts for closing, during all of which the safety circuit failed to successfully close given the predetermined control time for the closing of
doors.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - defective interlock contact
- defective door contacts
- control time for the closing of doors is set too restrictively (too short)
- door motor has to little contact pressure
Error code : 62
-- Reserved error code
Errorcode : 63
Reset 700 + Ok // Tools > Adjustment > Page 2 > Delete UCM erron
Short text UCM by speed!
Long text UCM was detected by \nspeed
Description The controller checks the lift speed in the zone. If the measures speed value should be higher than the one given in “Menu -> Parameter -> General settings -> UCM ->
v UCM check” the controller will initiate an emergency stop.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - UCM detected
- approaching speed too high
- reading error of the absolute encoder
- parameters are not set correctly
Error code : 64
Reset 700 + Ok // Tools > Adjustment > Page 2 > Delete UCM error
Short text UCM by speed!
Long text UCM was detected by \nposition
Description After leaving the zone the controller recognizes the shaft doors to be open (SK4 not closed) and thus detects a UCM situation,
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - UCM detected
- reading error of the absolute encoder
Error code : 65
Reset 700 + Ok // Tools > Adjustment > Page 2 > Delete UCM error
Short text Locked fault!
Long text Locked fault occurred!
Description This error serves for internal error analysis. // If this error should be displayed, please conduct a controller reset.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes
Remedy
Error code : 66
Reset Automatic
Short text Cabin light!
Long text cabin light error!
Description The controller recognizes a missing phase for the cabin light. At the connecting terminal L4 on the relay board a 230V supply cannot be decteted.
Reaction General The controller switches into „out-of- order“ mode.
Rope The lift stops in the current landing
Hydraulic The lift descends into the lowest landing
Causes - phase failure
- fuse disconnected (F4)
- wiring not correct
- defective input
Error code : 67
Reset Automatic
Short text Car light switch off!
Long text Cabin-light switched \noff!
Description Notification that the cabin light switch has been switched off at the controller.
Reaction General The controller switches into „out-of- order“ mode.
Rope The lift stops in the current landing
Hydraulic The lift descends into the lowest landing
Causes - cabin light switch is being activated
Remedy
Error code : 68
Reset Automatic
Short text Small head room UP!
Long text small head room to move\nup in inspection!
Description Notification that the Inspection end switch which is simulated by the software was reached during upward travel.
Reaction General
Rope
Hydraulic
Causes - end switch has been reached
Error code : 69
Reset Resolve error and enter 800+OK afterwards
Short text Apron input door 1!
Long text Apron input not active in \nnormal mode at door 1!
Description Under normal operation, the controller expects to receive input about the hinged apron being retracted.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - hinged apron folded out
- wiring not correct
- defective input
Error code : 70
Reset 800+Ok and note the instructions for retracting the aprons
Short text Apron magnet Door 1!
Long text Apron input is bridged!
Description Should the installation be equipped with a holding magnet (HM) for aprons, then an input about the HM’s retraction will be expected when issuing the output for the
HM.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - hinged apron folded out even though the HM is supplied with current.
- wiring not correct
- defective input
Error code : 71
Reset 800+Ok and note the instructions for retracting the aprons
Short text Apron door 1 SK chain!
Long text Apron not activ in normal \nmode at door 1, because\nof SK chain!
Description If the controller recognizes the SK4 input to open during travel, the holding magnet for the hinged apron deactivates.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - SK4 has been opened during travel
Remedy
Error code : 72
Reset 800+Ok and note the instructions for retracting the aprons
Short text Apron input door 2!
Long text Apron input avtive in \nnormal mode at door 2!
Description Under normal operation, the controller expects to receive input about the hinged aprion being retracted.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - hinged apron folded out
- wiring not correct
defective input
Remedy - retract hinged apron
- in case of automatic folding, please note the operating procedures
If the input should be defective it can be parameterized to another available I/O any time.
Error code : 73
Reset 800+Ok and note the instructions for retracting the aprons
Short text Apron magnet Door 2!
Long text Apron magnet output \ndoor 2 active but no \neffect on input!
Description Should the installation be equipped with a holding magnet (HM) for aprons, then an input about the HM’s retraction will be expected when issuing the output for the
HM.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - hinged apron folded out even though the HM is supplied with current.
- wiring not correct
- defective input
Error code : 74
Reset 800+Ok and note the instructions for retracting the aprons
Short text Apron door 2 SK chain!
Long text Apron activ in normal \nmode at door 2, because\nof SK chain!
Description If the controller recognizes the SK4 input to open during travel, the holding magnet for the hinged apron deactivates.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - SK4 has been opened during travel
Remedy
Error code : 75
-- Reserved error code
Error code : 76
-- Reserved error code
Error code : 77
Reset Automatic
Short text Small Pit room DOWN!
Long text small Pit room to move\ndown in inspection!
Description Notification that the inspection limit switch which is simulated by the software has been reached during downward travel.
Reaction General
Rope
Hydraulic
Causes - SImulated limit switch has been reached
Error code : 78
Reset Automatic
Short text Apron distance!
Long text Because of apron dis-\ntance not possible to \nmove down more!
Description The min. distance from the shaft pit which is allowed to be reached with an out-folded apron has been reached during downward travel.
Reaction General The controller initiates an emergency stop
Rope
Hydraulic
Causes - limit has been reached
- parameters not set correctly
Error code : 79
Reset 800 + Ok / Resend / Reset
Short text Brake 3 not opened!
Long text Brake 3 not opened!
Description 3 sec. after the beginning of travel, the controller checks whether the brakes are released; that is in case of an error the input Brake3 (P.44 on the PB) is still applied.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - brake activation does not function properly (refer to wiring diagram)
- brake shoe contact is not set up correctly
- wiring not coorect
- fuse for brake (-F8)
- defective input
Error code : 80
Reset 800 + Ok / Resend / Reset
Short text Brake 3 not closed!
Long text Brake 3 not closed!
Description 3 sec. after the termination of travel, the controller checks whether the brakes are closed; that is in case of an error the input Brake3 (P.44 on the PB) is not applied.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - brake activation does not function properly (refer to wiring diagram)
- brake shoe contact is not set up correctly
- wiring not coorect
- defective input
Error code : 81
Reset 800 + Ok
Short text Sink lock not opened!
Long text Sink lock not opened!
Description 3 sec. upon beginning of travel, the controller checks whether the monitoring contact of the descent protection has opened; that is in case of an error the input “control
descent protection” still applies.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - activation of the descent protection does not function properly (see wiring diagram)
- wiring not correct
- defective input
Error code : 82
Reset 800 + Ok
Short text Sink lock not closed!
Long text Sink lock not closed!
Description 3 sec. upon termination of travel, the controller checks whether the monitoring contact of the descent protection has closed; that is in case of an error the input “control
descent protection” is not applied.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - activation of the descent protection does not function properly (see wiring diagram)
- wiring not correct
- defective input
Error code : 83
Reset Automatic
Short text IO not assigned!
Long text IO not assigned!
Description It is being referred to an IO which no function is assigned to.
Reaction Assign the desired function to the IO
Error code : 84
Reset Automatic
Short text Module not alive!
Long text Module not alive!
Description A function was programmed on to a physically not existing module
Reaction - integrate the module into the installation
- program the function onto another module
Error code : 85
Reserved error code
Error code : 86
Reset 700 + Ok // Tools > Adjustment > Page 2 > Delete UCM error
Short text Valve-Test < 24 Hour!
Long text Valve test have not \ndone more than last 24 \nhour!
Description The controller checks the valves every 24 hours so that the UCM function is ensured. If the testing is not conducted, this error will be registered.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - Another kind of error prevents the lift from travelling „normally” thereby also rendering the valve test unfeasible.
- After having exchanged the board the time is no longer indicated correctly.
Error code : 87
Reset 700 + Ok // Tools > Adjustment > Page 2 > Delete UCM error
Short text UCM at hydraulic K2!
Long text UCM at hydraulic K2!
Description During an automatic valve test the „KD“ contactor is being activated. If the controller then detects a cabin movement into downward direction, it is to assume that there
is a leaky “down valve”.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - leaky valve
- wiring error
Error code : 88
Reset 700 + Ok // Tools > Adjustment > Page 2 > Delete UCM error
Short text UCM at hydraulic KD!
Long text UCM at hydraulic KD!
Description During an automatic valve test the „K2“ contactor is being activated. If the controller then detects a cabin movement into downward direction, it is to assume that there
is a leaky “A3 valve”.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - defective contactor
- defective auxiliary contact
- wiring error (K2 contact is bridged)
Error code : 89
Reserved error code
Error code : 90
Reset Automatic
Short text Conflict IO address
Long text Conflict IO address
Description Two functions were programmed onto the same IO adress.
Reaction - change parametrisation
- the I/O assignment can be checked as follows:
Menu -> Tools -> IO-Assignment -> select Adress e.g. F51.1
Error code : 91
Reset Contact the hotline
Short text LiSA Bus driver / SPI!
Long text LiSA bus driver or\nSPI communication error!
Description Communication between CPU and the bus driver is disturbed.
Reaction General The controller switches into „out-of- order“ mode.
Rope The controller stops in the next possible landing,
Hydraulic The controller stops in the next possible landing and the lift then descends into the lowest landing.
Remedy Change the processor board
Error code : 92
Reset 800 + Ok / Reset
Short text Maximum speed!
Long text Maximum speed!
Description The controller detects a travelled speed which is higher than the value set in „Menu -> Parameter -> General settings -> Travel -> Maximum speed“
Reaction General The controller switches into „out-of- order“ mode.
Rope The controller initiates an emergency stop.
Hydraulic The controller conducts an emergency halt and the lift then descends into the lowest landing.
Causes - maximum speed has been reached
- absolute encoder reading error
- paramters are not set correctly
Reset - check the parameters (the value should lie between the rated speed and the speed governors tripping speed )
- Entering the value „0“deactivates the monitoring.
Should this type of error occur more frequently and possibly together with an absolute encoder reading error, one should consider exchanging the
abosulte encoder. (consult the hotline)
Error code : 93
Reset 800+Ok / Reset
Short text Deceleration UP!
Long text Deceleration UP!
Description The controller is capable of measuring the deceleration of the cabin and thus serves as simulated deceleration monitoring. After having switched to the slower speed, the
real deceleration of the cabin is measured. Should this value not coincide with the one set under „Parameter > General settings > Deceleration > Page2 > Min.
deceleration ( mm/s2), this error will be indicated.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - above parameter is not set correctly (the value should be slightly smaller than at the inverter)
- control does not decelerate correctly
- hydraulics do not decelerate correctly
Error code : 94
Reset 800+Ok / Reset
Short text Deceleration DOWN!
Long text Deceleration DOWN!
Description The controller is capable of measuring the deceleration of the cabin and thus serves as simulated deceleration monitoring. After having switched to the slower speed, the
real deceleration of the cabin is measured. Should this value not coincide with the one set under „Parameter > General settings > Deceleration > Page2 > Min.
deceleration( mm/s2), this error will be indicated.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - above parameter is not set correctly (the value should be slightly smaller than at the inverter)
- control does not decelerate correctly
- hydraulics do not decelerate correctly
Error code : 95
Reset Automatic
Short text Step (-) in up movement
Long text Stop before level in up\nmovement
Description The lift stopped BEFORE the landing during upward travel (cabin positioned too low)
Reaction General The controller relevels if relevelling is activated.
Rope
Hydraulic
Causes - braking deceleration is not set correctly
- load-dependent hydraulic system
- unprecise control (open loop)
- disruption during DCP transmission
Reset - set braking deceleration (reduce) (readjust only if this error occures at each landing equally)
- readjust landing hight
- readjust control
Error code : 96
Reset Automatic
Short text Glide in up movement!
Long text Cabin glide in up \nmovement!
Description The lift has passed by the landing during upward travel (SoZone)
Reaction General The controller relevels if relevelling is activated.
Rope
Hydraulic
Causes - braking deceleration is not set correctly
- load-dependent hydraulic system
- unprecise control (open loop)
- disruption during DCP transmission
Reset - set braking deceleration (increase) (readjust only if this error occures at each landing equally)
- readjust landing hight
- readjust control
Error code : 97
Reset Automatic
Short text Glide in down movement!
Long text Cabin glide in DOWN\nmovement!
Description The lift has passed by the landing during downward travel (SuZone)
Reaction General The controller relevels if relevelling is activated.
Rope
Hydraulic
Causes - braking deceleration is not set correctly
- load-dependent hydraulic system
- unprecise control (open loop)
- disruption during DCP transmission
Reset - set braking deceleration (increase) (readjust only if this error occurs at each landing equally)
- readjust landing hight
- readjust control
Error code : 98
Reset Automatic
Short text Step (+) in DOWN move!
Long text Cabin stoped in DOWN\nmovement!
Description The lift stopped BEFORE the landing during downward travel (cabin positioned too high)
Reaction General The controller relevels if relevelling is activated.
Rope
Hydraulic
Causes - braking deceleration is not set correctly
- load-dependent hydraulic system
- unprecise control (open loop)
- disruption during DCP transmission
-
Reset - set braking deceleration (reduce) (readjust only if this error occurs at each landing equally)
- readjust landing hight
- readjust control
Error code : 99
Reset Contact hotline
Short text Decel. small/ABE-Error!
Long text Deceleration is small \nor ABE pos. is wrong. \nUpper / lower floor!
Description The controller reads an invalid value from the absolute encoder (the allowed range is: (zero point – 900mm as lowest bound) +nlandingdistances+900mm as highest
bound)
Reaction General
Rope
Hydraulic
Causes - reading error of the absolute encoder
Reset Since the inspection limit switch is of highest importance to ensure the technicians safety, it is impossible to conduct an inspection run until the proper functioning of the
inspection limit switch is confirmed. Resetting this error via reset or by entering 800 is not possible.
The lift may be moved by using the resend function or in the case of hydraulic installations by means of the software resend. As soon as the error is rectified it will be
necessary to move the lift into the upper-most landing (e.g. via resend function). Here, an incoming –H is considered as a verification for the proper functioning of the
inspection limit switch.
Afterwards, the installation can resume normal operation and it is also possible to travel under inspection again.
Hydraulic
Remedy - Disconnect the landing bus. If the error is then still being indicated, it is rooted in the control cabinet.
- Remove the EBus jack on the PB board. If the error is then still being indicated, contact the hotline.
- If the error disappears after disconnection of the landing bus, the error is to be found in the shaft.
Rope
Hydraulic
Remedy - Disconnect the landing bus. If the error is then still being indicated, it is rooted in the control cabinet.
- Remove the EBus jack on the PB board. If the error is then still being indicated, contact the hotline.
- If the error disappears after disconnection of the landing bus, the error is to be found in the shaft.
Rope
Hydraulic
Remedy - Disconnect the car bus. If the error is then still being indicated, it is rooted in the control cabinet.
- Remove the FBus jack on the PB board. If the error is then still being indicated, contact the hotline.
- If the error disappears after disconnection of the car bus, the error is to be found on the car/travelling cable.
- If the installation is equipped with 2 door sides and a selective door controlling it is furthermore necessary to check the car bus in the shaft.
Remedy - Disconnect the car bus. If the error is then still being indicated, it is rooted in the control cabinet.
- Remove the FBus jack on the PB board. If the error is then still being indicated, contact the hotline.
- If the error disappears after disconnection of the car bus, the error is to be found on the car/travelling cable.
- If the installation is equipped with 2 door sides and a selective door controlling it is furthermore necessary to check the car bus in the shaft.
Remedy - Enter a phone number under „ Menu -> Parameter -> Emergency“
Hydraulic
Remedy - If the input should be defective it can be parameterized to another available I/O any time
Remedy - Menu –> Tools -> Page 2 -> Reset service intervall
Remedy - Programm I/O „Menu > Parameter > General settings > Deceleration control“
Remedy - Set nominal speed: „Menu > Parameter > General settings > Travel > Nominal speed“
Reaction General The controller switches into „out-of-oder“ mode and conducts an emergency stop
Rope
Hydraulic
Causes - Defective contactor/relay
- Burnt contact
- Wiring not correct
- Defective input