LISA 20

Error description
2 Fehlermeldungen

Th.Pauly 23.02.2016 Erste Ausgabe Version 1.00


Th.Pauly 30.05.2016 Korrektur Version 1.01
F.Giebel / V.Milanovic 07.12.2016 Übersetzung englisch Version 1.01

Errors that are reset automatically.


Errors that are reset both manually and automatically.
Errors which need to be reset manually by entering 800+OK.
Errors which need to be reset manually by entering 700+OK.
Errors which require a reset procedure.
Notifications which are reset automatically.

© 2015 Schneider Steuerungstechnik GmbH. All rights reserved.

This manual and the product described herein are protected by copyright for Schneider Steuerungstechnik GmbH or their suppliers
with reservation of all rights. According to copyright, this manual must not be copied in whole or in part without prior written
approval of Schneider Steuerungstechnik GmbH, unless within the context of normal use of the product or in order to create
backups. This exception does not include copies made for and sold to any third parties or ceded to them in any other way.
However, the whole purchased material (including any backups) may be sold, ceded or lent to any third parties. According to legal
stipulations, creating a translation also falls within the definition of copying.

Schneider Steuerungstechnik GmbH does not accept any responsibility or liability for the contents of this manual.

They decline any legal warranty for the marketability or suitability for any special purpose.

Schneider Steuerungstechnik GmbH cannot be held responsible for errors in this manual or any direct or indirect damage related to
the delivery, performance or use of this manual. Schneider Steuerungstechnik GmbH reserves the right to review this manual from
time to time without notice and make changes to its contents.

The operation is not permitted in the USA and in countries with a similar judicial system.

As of: 07.12.2016

LiSA 20 Error Description Rev 1.01


Fehlermeldungen 3

Error core : 0
Rückstellung Automatisch
Short text NO_ERR
Long text No error
Description
Reaction General
Rope
Hydraulic
Remedy

Error code : 1
Rückstellung Automatic
Short text Module do not exist!
Long text Critical module not\nalive!
Description A function was programmed to a non-existing Bus-module.
Reaction General The control switches into „out-of-order“ mode.
Rope
Hydraulic
Remedy - Install the missing module
- Re-programm the desired function on an existing module

Error code : 2
-- Reserved error code

Error code : 3
-- Reserved error code

Error code : 4
-- Reserved error code

Error code : 5
Reset 800 + Ok / Recall / Reset
Short text K5 not active!
Long text K5 not active!
Description The control contact of safety relay K5 reports a permanently deenergized relay despite the zone being approached or travelled through.
Reaction General The control switched into „out of operation 5“
Rope The control stops in the next possible landing.
Hydraulic The control stops in the next possible landing and descends into the lowest landing from there.
Remedy
- Check selection signals SM/SZ (First SZ and then SM must turn active when approaching the zone.)
- Check selection signals for voltage (When a signal is active one should be able to measure a 24V voltage between the signal and +24V.)
- Check the DIL switch „S1“ on the LiSA20-relay board (All switches must be positioned on “off”)
- Check the jumper „J3“ (refer to the wiring diagram)
- Visually check the safety relays K5/K6/K7 (deformed contact pins)
- Check the connection processor board -> relay board

Error core : 6
Reset 800 + Ok / Recall
Short text K5 permanently active!
Long text K5 always active!
Description The control contact of safety relay K5 reports a permanently energized relay despite having left the zone.
Reaction General The control switched into „out of operation 6“
Rope The control stops in the next possible landing.
Hydraulic The control stops in the next possible landing and descends into the lowest landing from there.
Remedy
- Check selection signals SM/SZ (First SZ and then SM must turn active when approaching the zone.) ( Pay attention to the LEDs over the relays)
- Check selection signals for voltage (When a signal is active one should be able to measure a 24V voltage between the signal and +24V.)
- Check the DIL switch „S1“ on the LiSA20-relay board (All switches must be positioned on “off”)
- Check the jumper „J3“ (refer to the wiring diagram)
- Visually check the safety relays K5/K6/K7 (deformed contact pins)
- Check the connection processor board -> relay board

Error code : 7
Reset Automatic
Short text SK1 interruption
Long text SK1 interruption in normal mode
Description The safety circuit 1 was interrupted during travel.
Reaction Due to the interruption of the safety circuit the lift is forced to stop and the control switches into „Out-of-operation7“ mode.
Causes - Main switch was switched off
- Control fuse (-F1) has triggered
- Speed governor or lift arrestor contact have triggered
- Other contact before the SK1 tap has triggered (refer to the wiring diagram)

Remedy - Measure voltage between SK1 and NA


- If no voltage can be detected, check the safety circuit contacts
- If some voltage can be detected but is not indicated properly by the control it might that the optocoupler on the relay board is defective. Replace
optocoupler or relay board.

LiSA 20 Error Description Rev 1.01


4 Fehlermeldungen

Error code : 8
Reset Automatic
Short text SK1 interruption
Long text SK1 interruption in inspection mode
Description The safety circuit 1 was interrupted during travel
Reaction General Lift stops and no further inspection run can be carried out
Rope
Hydraulic
Causes - Main switch was switched off
- Control fuse (-F1) has triggered
- Speed governor or lift arrestor contact have triggered
- Other contact before the SK1 tap has triggered (refer to the wiring diagram)

Remedy - Measure voltage between SK1 and NA


- If no voltage can be detected, check the safety circuit contacts
- If some voltage can be detected but is not indicated properly by the control it might that the optocoupler on the relay board is defective. Replace
optocoupler or relay board.

Error code : 9
Reset Automatic
Short text SK2 interruption
Long text SK2 interruption
Description The safety circuit was interrupted during normal operation.
Reaction General Due to the interruption of the safety circuit the lift is forced to stop and the control switches into „Out-of-operation“ mode.
Rope
Hydraulic
Causes - Emergency stop was activated
- Revolving door contact has opened
- Other contact between SK1 tap and SK2 tap has triggered (refer to the wiring diagram)

Remedy - Measure voltage between SK1 and NA


- If no voltage can be detected, check the safety circuit contacts
- If some voltage can be detected but is not indicated properly by the control it might that the optocoupler on the relay board is defective. Replace
optocoupler or relay board.

Fehlercode : 10
Reset Rope automatic/Hydro 800+OK
Short text SK2 In","SK1 Off
Long text SK2 active, but SK1 not active
Description This is not a logical state since the safety circuit is fed in after the SK1 tap.
Reaction General The control switches into „Out-of-order“ mode
Rope The lift comes to a halt
Hydraulic The lift descends into the lowest landing
Causes - Jumper in the safety circuit

Remedy - Remove jumper(s) in the safety circuit

Fehlercode : 11
Reset 800+Ok / Reset / SK4 opens during inspection mode
Short text SK4 permanently active
Long text SK4 was bridged\nin inspection
Description The control expects the safety circuit to be interrupted when letting go of the direction button during inspection mode. If this does not happen (SK4 remains on), this
error is be recorded.
Reaction General The control switches into „Out-of-order“ mode
Rope
Hydraulic
Causes - Jumper in the safety circuit

Remedy - Remove jumper(s) in the safety circuit

Fehlercode : 12
Reset Automatic
Short text Car emergency stop!
Long text Emergency stop in car\nis pressed
Description The emergency stop in the car is monitored by the control. When the emergency call is activated, this error is reported.
Reaction General The control switches into „Out-of-order“ mode
Rope
Hydraulic
Causes - Emergency stop in car is activated

Remedy - Reset the emergency stop

LiSA 20 Error Description Rev 1.01


Fehlermeldungen 5

Error code : 13
Reset Automatic
Short text Inverter fault
Long text Inverter fault
Description The inverter reports an error to the control
Reaction General The control switches into „Out-of-order“ mode
Rope
Hydraulic -----------------------------------------------------------------------------
Causes - Check wiring of the fault message contact (refer to the wiring diagram)
- Check the error log of the inverter

Remedy - Remove the error at the inverter

Error code : 14
Reset Automatic
Short text Overtemperature 1
Long text Overtemperature 1
Description The PTC thermistor in the travel motor or respectively in the pump motor of the hydraulic reservoir indicated a violation of the maximum allowed temperature (60°C) in
one of these operating equipments to the control at input U1.
Reaction General The control switches into „Out-of-order“ mode
Rope At standstill: After cool down the installation will resume operation
When travelling: The control stops in the next possible landing. After cool down the installation will resume operation.
Hydraulic At standstill: After cool down the installation will resume operation
When travelling: The control stops in the next possible landing. After cool down the installation will resume operation. The landing must be reached
within 10 seconds. Otherwise an emergency stop will be conducted.
Causes - High number of travels
- High ambient temperature
- Defective engine / defective engine fan

Beseitigung - See causes

Error code : 15
Reset Automatic
Short text Overtemperature 2
Long text Overtemperature 2
Description The PTC thermistor in the travel motor or respectively in the oil of the hydraulic reservoir indicated a violation of the maximum allowed temperature (110°C) in one of
these operating equipments to the control at input U1.
Reaction General The control switches into „Out-of-order“ mode
Rope --------------------------------------------------------------------------
Hydraulic At standstill: After cool down the installation will resume operation
When travelling: The control stops in the next possible landing. After cool down the installation will resume operation. The landing must be reached
within 10 seconds. Otherwise an emergency stop will be conducted.
Causes - High number of travels
- High ambient temperature
- Defective engine

Remedy - See causes

Error code : 16
Reset 800 + Ok
Short text Contactor control drop
Long text Contactor control drop
Description The control cannot read in the input „SAK“ after the end of travel. (contactor not deenergised)
Reaction General The control switches into „Out-of-order“ mode
Rope The control stops in the next possible landing.
Hydraulic The control stops in the next possible lading. Therefrom, the lift descends into the lowest landing.
Causes - Main- or brake contactor defective
- Close auxiliary contact of the contactors
- Lock the preselection relay on the LiSA RB

Remedy - Replace defective contactor/relay

Error code : 17
Reset 800 + Ok
Short text Contactor monitor on
Long text Contactor monitor\npermanently on
Description The control recognized the input „SAK“ after beginning of travel (contactor not energized)
Reaction General The control switches into „Out-of-order“ mode
Rope The control stops in the next possible landing.
Hydraulic The control stops in the next possible lading. Therefrom, the lift descends into the lowest landing.
Causes - Main- or brake contactor defective
- Close auxiliary contact of the contactors
- Lock the preselection relay on the LiSA RB

Remedy - Replace defective contactor/relay

Error code : 18
-- Reserved error code

LiSA 20 Error Description Rev 1.01


6 Fehlermeldungen

Error code : 19
Reset Automatic
Short text Resend UP and DOWN
Long text Resend UP and DOWN are\nactiv!
Description Both direction signals apply at the controller even though the resend function is switched off.
Reaction General The control switches into „Out-of-order“ mode
Rope
Hydraulic
Remedy - Let go of the direction switch
- Check wiring
- Check jumper position on the PB board (refer to the wiring diagram) ( Jumper RUE/RAUF/RAB )

Error code : 20
Reset Automatic for rope / 800+Ok for hydraulic
Short text Up final switch
Long text Final switch upper floor!
Description If the lift stands above the flush position in the highest landing and the SK1 is interrupted, this error will be recorded.
Reaction General The control switches into „Out-of-order“ mode
Rope The control switches into normal mode when SK1 is closed.
Hydraulic The lift descends into the lowest landing and remains there in „out-of-order“ mode until the error is reset.
Causes - Brake has been released manually – the lift coasts away upwards.
- deceleration distance is not set correctly
- temperature-dependent hydraulic system
- control does not decelerate correctly
- emergency-stop switch is not positioned correctly

Remedy - Set the deceleration distances correctly


- Check parameters of the controller

Error code : 21
Reset 800+Ok / Resend
Short text Down final switch
Long text Final switch lower floor!
Description If the lift is standing more than 50mm underneath the flush position of the lowest landing and the SK1 is interrupted, this error will be recorded.
Reaction General The control switches into „Out-of-order“ mode
Rope The control switches into normal mode when SK1 is closed.
Hydraulic Die Steuerung wechselt wieder in den Normalmodus wenn SK1 geschlossen ist
Causes - deceleration distance is not set correctly
- temperature-dependent hydraulic system
- Car is overloaded
- control does not decelerate correctly
- emergency-stop switch is not positioned correctly

Remedy - Set the deceleration distances correctly


- Check parameters of the controller
-

Error code : 22
-- Reserved error code

Error code : 23
Reset Automatic
Short text Inspection UP and DOWN
Long text Inspection UP and DOWN\nare activ!
Description The controller recognizes both inspection-direction-switches as active.
Reaction General The control switches into „Out-of-order“ mode
Rope
Hydraulic
Causes - Both switches are activated
- Input at the controller is defective

Remedy - Check position of switched


- Check inputs on the status page (IU/ID)

Error code : 24
-- Reserved error code

Error code : 25
Reset Automatic
Short text Inspection & Resend
Long text Inspection & Resend are\n activ!
Description The controller recognizes that both inspection control and resend control are active.
Reaction General The control switches into „Out-of-order“ mode
Rope
Hydraulic
Causes - Both switches are activated
- Input at the controller is defective
-

Remedy - Check position of switched


- Check inputs on the status page ( RUE / IEI )
- From SW Version 2.008X this error is no longer reported. In this case, the inspection control is set to “dominate” the resend control.

LiSA 20 Error Description Rev 1.01


Fehlermeldungen 7

Error code : 26
-- Reserved error code

Error code : 27
Reset 800+Ok / Resend / Inspection
Short text Error Travel time
Long text Travel time!

Description Travel time is exceeded.


During travel between two adjacent landings, the time limit determined in the parameter “Travel time” is exceeded.
Reaction General The controller initiates an emergency-stop and switches into “out-of-order” mode.
Rope The lift comes to a halt.
Hydraulic The lift descends into the lowest landing.
Causes Hydraulic - Valves are not energized / valves are clogged
- rectifier is defective
- Electric valve activation is defective (Behringer/AZRV)
-
Causes - Frequency control is defective
Rope controlled - Outputs of the PB are defective (not in the case of DCP)
- brake does not release

Remedy See causes

Error code : 28
-- Reserved error code

Error code : 29
Reset Automatic
Short text Resend up input active
Long text No resend but resend UPup\n is active
Description The controller recognizes the „up“ input of resend as active despite the resend control being deactivated.
Causes - Direction button is being pushed even though the resend control is not switched on.
- Input at the controller is defective

Remedy - Release direction button


- Check input on the status page (RAU)

Error code : 30
Reset Automatic
Short text Resend down input!
Long text No resend but resend \nDOWN is active!
Description The controller recognizes the „down“ input of resend as active despite the resend control being deactivated.
Causes - Direction button is being pushed even though the resend control is not switched on.
- Input at the controller is defective

Remedy - Release direction button


- Check input on the status page (RAB)

Error Code : 31
Reset Automatic
Short text Inspection up input?
Long text No inspection but \ninspection UP is active
Description The controller recognizes the „up“-input of inspection as active despite the inspection control being deactivated.
Causes - Direction button is being pushed even though the inspection control is not switched on.
- Check input on the status page (RAB)

Remedy - Release direction button


- Check input on the status page (IU)

Error code : 32
Reset Automatic
Short text Inspection DOWN input?
Long text No inspection but \ninspection DOWN is act.
Description The controller recognizes the „down“-input of inspection as active despite the inspection control being deactivated.
Causes - Direction button is being pushed even though the inspection control is not switched on.
- Check input on the status page

Remedy - Release direction button


- Check input on the status page (ID)

Error code : 33
-- Reserved error code

Error code : 34
Reset Automatic
Short text D1 Open/Close Limit-Sw.
Long text Open/close limit switch
\ndoor 1 together
Description The controller recognizes both door 1 limit switches as active
Causes - Limit switch wiring not correct
- Input at controller is defective

Remedy - Check wiring


- Check NNC (normally closed contact) setting in parameters
- Check input on the status page (OL/CL)

LiSA 20 Error Description Rev 1.01


8 Fehlermeldungen

Error code : 35
Reset Automatic
Short text D2 Open/Close Limit-Sw.
Long text Open/close limit switch\ndoor 2 together
Description The controller recognizes both door 2 limit switches as active
Causes - Limit switch wiring not correct
- Input at controller is defective

Remedy - Check wiring


- Check NNC (normally closed contact) setting in parameters
- Check input on the status page (OL/CL)

Error code : 36
Reset Automatic
Short text Software final switch
Long text sortware final up switch
Description The value determined by the absolute encoder does not coincide with the reference value for the highest landing which is determined by the controller (zero-point
+nlandings)
Reaction General The controller switches into „out-of-order“ mode.
Rope The controller initiates an emergency stop.
Hydraulic The controller initiates an emergency stop and descends into the lowest landing.
Causes - Reading error of the absolute encoder
- Defective connection
- Magnetic tape not installed correctly (Installation manual!)
- Defective travelling cable
- Defective CPU

Remedy - See causes


- Check landing heights (Menu -> Setup)

Error code : 37
Reset Automatic
Short text Undershoot lowest floor
Long text Undershoot or refrence \nlevel not correct
Description The value determined by the absolute encoder does not coincide with the reference value for the highest landing which is determined by the controller (zero-point)
Reaction General The controller switches into „out-of-order“ mode.
Rope The controller initiates an emergency stop.
Hydraulic The controller initiates an emergency stop and descends into the lowest landing.
Causes - Reading error of the absolute encoder
- Defective connection
- Magnetic tape not installed correctly (Installation manual!)
- Defective travelling cable
- Defective CPU

Remedy - See causes


- Check zero point (Menu -> Setup)

Error code : 38
Reset 800 + Ok /Resend / By entering a cabin call
Short text Door 1 did not close
Long text Door 1 did not close \nafter 5 retry
Description The controller initiated 10 attempts for closing, during all of which the safety cicuit failed to successfully close given the predetermined control time for the closing of
doors.
Reaction General The controller switches into „out-of-order“ mode.
Rope
Hydraulic
Causes - defective interlocking contact
- defective door contact
- control time for closing doors is set too restrictively
- door motor has too little contact pressure

Remedy - See causes

Error code : 39
-- Reserved error code

Error code : 40
Reset 800 + Ok
Short text ACCU Error
Long text ACCU-Control Error
Description The lead-battery which is mounted to the controller is either defective or not connected (is only checked in standstill)
Reaction General The controller switches into „out-of-order“ mode.
Rope The lift stops in the current landing
Hydraulic The lift descends into the lowest landing
Causes - battery disconnected
- defective battery

Remedy - See causes


If the battery should be defective, one deactivate the monitoring via the menu “Tools -> Adjustment -> Surveillance -> Battery control j/n”
We highly URGE you to note that the battery needs to be replaced both at your installation and in the maintenance book.

Error code : 41
-- Reserved error code ( still error A3 Board as of 20.01.2016)

LiSA 20 Error Description Rev 1.01


Fehlermeldungen 9

Error code : 42
Reset Automatic
Short text Phase Error
Long text Phase Error
Description The integrated phase sequence detects a phase failure or a wrong direction of rotation.
Reaction General The controller switches into „out-of-order“ mode.
Rope The lift stops in the current landing
Hydraulic The lift descends into the lowest landing
Causes - Phase failure in the mains
- Phases are not clamped correctly L1/L2/L3
- Defective fuse in the controller/allocation

Remedy - See causes


If the phase sequence monitoring should not be needed, one can deactivate the monitoring via the menu “Tools -> Adjustment -> Surveillance -> Phase
control j/n”
We highly URGE you to note this circumstance both at your installation and in the maintenance book.

Error code : 43
Reset 800 + Ok / Resend
Short text Brake 1 not opened!
Long text Brake 1 not opened!
Description 3 seconds upon termination of travel, the controller checks whether the brakes are opened. That is, in case of an error, the input brake1 (P.42 on the PB) is still applied.
Reaction General The controller switches into „out-of-order“ mode.
Rope
Hydraulic
Causes - activation of the brake does not function properly (refer to wiring diagram)
- brake shoe contact is not set up correctly
- wiring is not correct
- brake fuse (-F8)
- defective input

Remedy - See causes


- Check input on the status oage (BR1)
If the input should be defective it can be parameterized to another available I/O any time.

Error code : 44
Reset 800 + Ok / Resend
Short text Brake 1 not closed!
Long text Brake 1 not closed!
Description 3 seconds upon termination of travel, the controller checks whether the brakes are closed. That is, in case of an error, the input brake1 (P.42 on the PB) is not applied.
Reaction General The controller switches into „out-of-order“ mode.
Rope
Hydraulic
Causes - activation of the brake does not function properly (refer to wiring diagram)
- brake shoe contact is not set up correctly
- wiring is not correct
- defective input

Remedy - See causes


- Check input on the status page (BR1)
If the input should be defective it can be parameterized to another available I/O any time.

Error code : 45
Reset 800 + Ok / Resend
Short text Brake 2 not opened!
Long text Brake 2 not opened!
Description 3 seconds upon termination of travel, the controller checks whether the brakes are opened. That is, in case of an error, the input brake1 (P.42 on the PB) still applies.
Reaction General The controller switches into „out-of-order“ mode.
Rope
Hydraulic
Causes - activation of the brake does not function properly (refer to wiring diagram)
- brake shoe contact is not set up correctly
- wiring is not correct
- brake fuse (-F8)
- defective input

Remedy - See causes


- Check input on the status oage (BR2)
If the input should be defective it can be parameterized to another available I/O any time.

Error code : 46
Reset 800 + Ok / Resend
Short text Brake 2 not closed!
Long text Brake 2 not closed!
Description 3 seconds upon termination of travel, the controller checks whether the brakes are closed. That is, in case of an error, the input brake1 (P.42 on the PB) is not applied.
Reaction General The controller switches into „out-of-order“ mode.
Rope
Hydraulic
Causes - activation of the brake does not function properly (refer to wiring diagram)
- brake shoe contact is not set up correctly
- wiring is not correct
- defective input

Remedy - See causes


- Check input on the status page (BR2)
If the input should be defective it can be parameterized to another available I/O any time.

LiSA 20 Error Description Rev 1.01


10 Fehlermeldungen

Error code : 47
Reset Automatic
Short text Machin Room TEMPERATURE!
Long text Machine Room over \nTemperature (MRT)!
Description The maximum allowed mashine room temperature has been exceeded. The controller reads input MRT (P.37 on the PB) as active.
Reaction General The controller switches into „out-of- order“ mode. Should this error occur during travel, the current ride will be completed nonetheless.
Rope The lift stops in „out-of-order“ mode at the current landing.
Hydraulic The lift descends into the lowest landing.
Causes - mashine room temperature too high
- Threshold at the thermostat not set correctly
- Wiring not correct
- Defective input

Remedy - See causes


- Check input on the status page (MRT)
If the input should be defective it can be parameterized to another available I/O any time.

Error code : 48
Reset Automatic
Short text Maximum pressure!
Long text Maximum hydraulic \npressure!
Description The hydraulic system reports to the controller that the max. allowed operating pressure is exceeded. The controller reads the input MAX (P.36 on the PB) as active.
Reaction General The controller switches into „out-of-order“ mode. An emergency stop is conducted.
Rope ---------------------------------------------------------------------------------------------------------------------------
Hydraulic
Causes - maximum pressure exceeded
- wrong settings at the hydraulic manifold
- For Bucher-SIUA defective contact
- wiring not correct
- lift car is overloaded
- defective input

Remedy - See causes


- Note the error description of the hydraulic manufacturer
- Check input on the status page (MAX)
If the input should be defective it can be parameterized to another available I/O any time.

Error code : 49
Reset Automatic
Short text Minimum pressure!
Long text minimum hydraulic \npressure!
Description The hydraulic system reports to the controller that the min. allowed operating pressure is exceeded. The controller reads the input MAX (P.35 on the PB) as active.
Reaction General The controller switches into „out-of-order“ mode. An emergency stop is conducted.
Rope ---------------------------------------------------------------------------------------------------------------------------
Hydraulic
Causes - minimum pressure not achieved
- wrong settings at the hydraulic manifold
- wiring not correct
- defective input

Remedy - See causes


- Note the error description of the hydraulic manufacturer
- Check input on the status page (MIN)
If the input should be defective it can be parameterized to another available I/O any time.

Error code : 50
Reset Automatic
Short text Minimum Room TEMPERATURE!
Long text Machine Room \nMinimum Temperature!
Description The minimum allowed machine room temperature is underrun (5°C)
Reaction General The controller switches into „out-of- order“ mode. Should this error occur during travel, the current ride will be completed nonetheless.
Rope The lift stops in „out-of-order“ mode at the current landing.
Hydraulic The lift descends into the lowest landing.
Causes - Machine room temperature too low (<5°C)
- Threshold at the thermostat not set correctly
- Wiring not correct
- Defective input

Remedy - See causes


- Check input on the status page
If the input should be defective it can be parameterized to another available I/O any time.

Error code : 51
Reset 800+OK+ Reset via key switch at the emergency unlock board // ( 800010 the output “Reset emergency unlock SW” should be programmed)
Short text Em. unlock reset active
Long text Emergency unlock reset \nactive!
Description The controller recognized the reset-input of the emergency unlock as active even though the input „emergency unlock active“ is not active.
Thereupon the controller switches the output “Reset emergency unlock” in such manner that the emergency unlock monitoring is activated.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - Wiring not correct
Defective input
Remedy - See causes
- Check input on the status page
If the input should be defective it can be parameterized to another available I/O any time.

LiSA 20 Error Description Rev 1.01


Fehlermeldungen 11

Error code : 52
Reset Deactivate reset key -> 800+OK -> activate reset key and deactive within 2 sec. // ( 800010 the output “Reset emergency unlock SW” should be programmed)
Short text Em.unlock res.per.activ
Long text Emergency unlock reset \npermanently active!
Description The controller recognizes the reset input of the emergency unlock monitoring as being permanently active.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - Reset keyis being activated permanently
- Wiring not correct
- Defective input

Remedy - See causes


- Check input on the status page
If the input should be defective it can be parameterized to another available I/O any time.

Error code : 53
Reset activate reset key and deactive within 2 sec. // ( 800010 the output “Reset emergency unlock SW” should be programmed)
Short text Em. unlock no SKx
Long text Emergency unlock active\nbut no SAFETY chain!\ntry again
Description The emergency unlock has been restored by the reset, the safety circuit however has not been closed.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - Safety circuit still open at another spot
- wiring not correct

Remedy Close safety circuits completely

Error code : 54
-- Rerserved error code

Error code : 55
Reset 800+OK -> activate reset key and deactive within 2 sec. // ( 800010 the output “Reset emergency unlock SW” should be programmed)
Short text SSNOT not in safety ch.
Long text SNOT board K4 error \nEmergency-unlock active\n->safety circuit!
Description After activation of the emergency unlock, the controller still recognizes the SK1, SK2, SK3 or the SK4 input.
In the safety circuit, the emergency unlock monitoring contact is positioned after the SK2 query; thus after activation of the emergency unlock all subsequent safety
circuit queries must be inactive.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - contact not linked correctly
- bridges in the safety circuit
- wiring not correct
- defective input

Remedy - See causes


- Check input on the status page (SK 2/3/4)

Error code : 56
-- Reserved error code

Error code : 57
-- Reserved error code

Error code : 58
-- Reserved error code

Error code : 59
Reset Reset the emergency unlock monitoring or switch on the inspection control (take measures to ensure the upper protective space)
Short text Emergency-unlock up
Long text Emergency-unlock up\nactive
Description The emergency unlock which serves to recognize if someone wishes to embark onto the lift car has released.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - upper shaft doors are opened
- wiring not correct
- defective input

Remedy - See causes


If the input should be defective it can be parameterized to another available I/O any time.

LiSA 20 Error Description Rev 1.01


12 Fehlermeldungen

Error code : 60
Reset Reset the emergency unlock monitoring
Short text Emergency-unlock down
Long text Emergency-unlock down\nactive
Description The emergency unlock which serves to recognize if someone wishes to enter the shaft has activated. It is not possible to conduct a resend- or inspection run.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - bottom shaft doors are opened
- wiring not correct
- defective input

Remedy - See causes


If the input should be defective it can be parameterized to another available I/O any time.

Error code : 61
Reset 800 + Ok / By entering a cabin call
Short text retrys close Door 2
Long text Door 2 did not close \nafter retrys!
Description The controller initiated 10 attempts for closing, during all of which the safety circuit failed to successfully close given the predetermined control time for the closing of
doors.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - defective interlock contact
- defective door contacts
- control time for the closing of doors is set too restrictively (too short)
- door motor has to little contact pressure

Remedy - See causes

Error code : 62
-- Reserved error code

Errorcode : 63
Reset 700 + Ok // Tools > Adjustment > Page 2 > Delete UCM erron
Short text UCM by speed!
Long text UCM was detected by \nspeed
Description The controller checks the lift speed in the zone. If the measures speed value should be higher than the one given in “Menu -> Parameter -> General settings -> UCM ->
v UCM check” the controller will initiate an emergency stop.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - UCM detected
- approaching speed too high
- reading error of the absolute encoder
- parameters are not set correctly

Remedy - See causes


- Entering the value „0“ disables the speed monitoring

Error code : 64
Reset 700 + Ok // Tools > Adjustment > Page 2 > Delete UCM error
Short text UCM by speed!
Long text UCM was detected by \nposition
Description After leaving the zone the controller recognizes the shaft doors to be open (SK4 not closed) and thus detects a UCM situation,
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - UCM detected
- reading error of the absolute encoder

Remedy - See causes

Error code : 65
Reset 700 + Ok // Tools > Adjustment > Page 2 > Delete UCM error
Short text Locked fault!
Long text Locked fault occurred!
Description This error serves for internal error analysis. // If this error should be displayed, please conduct a controller reset.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes
Remedy

LiSA 20 Error Description Rev 1.01


Fehlermeldungen 13

Error code : 66
Reset Automatic
Short text Cabin light!
Long text cabin light error!
Description The controller recognizes a missing phase for the cabin light. At the connecting terminal L4 on the relay board a 230V supply cannot be decteted.
Reaction General The controller switches into „out-of- order“ mode.
Rope The lift stops in the current landing
Hydraulic The lift descends into the lowest landing
Causes - phase failure
- fuse disconnected (F4)
- wiring not correct
- defective input

Remedy - See causes


If the light monitoring should not be necessary one disable the monitoring via the menu „ Tools -> Adjustment -> Surveillance -> Cabin light monitor j/n“
We urge you to please make a note about this at the installation and in the maintenance book.

Error code : 67
Reset Automatic
Short text Car light switch off!
Long text Cabin-light switched \noff!
Description Notification that the cabin light switch has been switched off at the controller.
Reaction General The controller switches into „out-of- order“ mode.
Rope The lift stops in the current landing
Hydraulic The lift descends into the lowest landing
Causes - cabin light switch is being activated

Remedy

Error code : 68
Reset Automatic
Short text Small head room UP!
Long text small head room to move\nup in inspection!
Description Notification that the Inspection end switch which is simulated by the software was reached during upward travel.
Reaction General
Rope
Hydraulic
Causes - end switch has been reached

Remedy - leave the end switches by travelling downwards


- check parameters

Error code : 69
Reset Resolve error and enter 800+OK afterwards
Short text Apron input door 1!
Long text Apron input not active in \nnormal mode at door 1!
Description Under normal operation, the controller expects to receive input about the hinged apron being retracted.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - hinged apron folded out
- wiring not correct
- defective input

Remedy - retract hinged apron


- in case of automatic folding, please note the operating procedures
If the input should be defective it can be parameterized to another available I/O any time.

Error code : 70
Reset 800+Ok and note the instructions for retracting the aprons
Short text Apron magnet Door 1!
Long text Apron input is bridged!
Description Should the installation be equipped with a holding magnet (HM) for aprons, then an input about the HM’s retraction will be expected when issuing the output for the
HM.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - hinged apron folded out even though the HM is supplied with current.
- wiring not correct
- defective input

Remedy - retract hinged apron


- in case of automatic folding, please note the operating procedures
If the input should be defective it can be parameterized to another available I/O any time.

Error code : 71
Reset 800+Ok and note the instructions for retracting the aprons
Short text Apron door 1 SK chain!
Long text Apron not activ in normal \nmode at door 1, because\nof SK chain!
Description If the controller recognizes the SK4 input to open during travel, the holding magnet for the hinged apron deactivates.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - SK4 has been opened during travel

Remedy

LiSA 20 Error Description Rev 1.01


14 Fehlermeldungen

Error code : 72
Reset 800+Ok and note the instructions for retracting the aprons
Short text Apron input door 2!
Long text Apron input avtive in \nnormal mode at door 2!
Description Under normal operation, the controller expects to receive input about the hinged aprion being retracted.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - hinged apron folded out
- wiring not correct
defective input
Remedy - retract hinged apron
- in case of automatic folding, please note the operating procedures
If the input should be defective it can be parameterized to another available I/O any time.

Error code : 73
Reset 800+Ok and note the instructions for retracting the aprons
Short text Apron magnet Door 2!
Long text Apron magnet output \ndoor 2 active but no \neffect on input!
Description Should the installation be equipped with a holding magnet (HM) for aprons, then an input about the HM’s retraction will be expected when issuing the output for the
HM.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - hinged apron folded out even though the HM is supplied with current.
- wiring not correct
- defective input

Remedy - retract hinged apron


- in case of automatic folding, please note the operating procedures
If the input should be defective it can be parameterized to another available I/O any time.

Error code : 74
Reset 800+Ok and note the instructions for retracting the aprons
Short text Apron door 2 SK chain!
Long text Apron activ in normal \nmode at door 2, because\nof SK chain!
Description If the controller recognizes the SK4 input to open during travel, the holding magnet for the hinged apron deactivates.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - SK4 has been opened during travel

Remedy

Error code : 75
-- Reserved error code

Error code : 76
-- Reserved error code

Error code : 77
Reset Automatic
Short text Small Pit room DOWN!
Long text small Pit room to move\ndown in inspection!
Description Notification that the inspection limit switch which is simulated by the software has been reached during downward travel.
Reaction General
Rope
Hydraulic
Causes - SImulated limit switch has been reached

Remedy - Leave the limit switch by travelling up


- check parameters

Error code : 78
Reset Automatic
Short text Apron distance!
Long text Because of apron dis-\ntance not possible to \nmove down more!
Description The min. distance from the shaft pit which is allowed to be reached with an out-folded apron has been reached during downward travel.
Reaction General The controller initiates an emergency stop
Rope
Hydraulic
Causes - limit has been reached
- parameters not set correctly

Remedy - retract the hinged apron, retract the telescopic apron


- check parameters Menu -> Parameter -> Input/Output -> In car -> Autom. hinged Apron -> Dist.limit to drive

LiSA 20 Error Description Rev 1.01


Fehlermeldungen 15

Error code : 79
Reset 800 + Ok / Resend / Reset
Short text Brake 3 not opened!
Long text Brake 3 not opened!
Description 3 sec. after the beginning of travel, the controller checks whether the brakes are released; that is in case of an error the input Brake3 (P.44 on the PB) is still applied.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - brake activation does not function properly (refer to wiring diagram)
- brake shoe contact is not set up correctly
- wiring not coorect
- fuse for brake (-F8)
- defective input

Remedy - see causes


- check input on the status page (BR3)
If the input should be defective it can be parameterized to another available I/O any time.

Error code : 80
Reset 800 + Ok / Resend / Reset
Short text Brake 3 not closed!
Long text Brake 3 not closed!
Description 3 sec. after the termination of travel, the controller checks whether the brakes are closed; that is in case of an error the input Brake3 (P.44 on the PB) is not applied.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - brake activation does not function properly (refer to wiring diagram)
- brake shoe contact is not set up correctly
- wiring not coorect
- defective input

Remedy - see causes


- check input on the status page (BR3)
If the input should be defective it can be parameterized to another available I/O any time.

Error code : 81
Reset 800 + Ok
Short text Sink lock not opened!
Long text Sink lock not opened!
Description 3 sec. upon beginning of travel, the controller checks whether the monitoring contact of the descent protection has opened; that is in case of an error the input “control
descent protection” still applies.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - activation of the descent protection does not function properly (see wiring diagram)
- wiring not correct
- defective input

Remedy - see causes


- check input on the status page
If the input should be defective it can be parameterized to another available I/O any time.

Error code : 82
Reset 800 + Ok
Short text Sink lock not closed!
Long text Sink lock not closed!
Description 3 sec. upon termination of travel, the controller checks whether the monitoring contact of the descent protection has closed; that is in case of an error the input “control
descent protection” is not applied.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - activation of the descent protection does not function properly (see wiring diagram)
- wiring not correct
- defective input

Remedy - see causes


- check input on the status page
If the input should be defective it can be parameterized to another available I/O any time.

Error code : 83
Reset Automatic
Short text IO not assigned!
Long text IO not assigned!
Description It is being referred to an IO which no function is assigned to.
Reaction Assign the desired function to the IO

Error code : 84
Reset Automatic
Short text Module not alive!
Long text Module not alive!
Description A function was programmed on to a physically not existing module
Reaction - integrate the module into the installation
- program the function onto another module

Error code : 85
Reserved error code

LiSA 20 Error Description Rev 1.01


16 Fehlermeldungen

Error code : 86
Reset 700 + Ok // Tools > Adjustment > Page 2 > Delete UCM error
Short text Valve-Test < 24 Hour!
Long text Valve test have not \ndone more than last 24 \nhour!
Description The controller checks the valves every 24 hours so that the UCM function is ensured. If the testing is not conducted, this error will be registered.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - Another kind of error prevents the lift from travelling „normally” thereby also rendering the valve test unfeasible.
- After having exchanged the board the time is no longer indicated correctly.

Remedy - see causes

Error code : 87
Reset 700 + Ok // Tools > Adjustment > Page 2 > Delete UCM error
Short text UCM at hydraulic K2!
Long text UCM at hydraulic K2!
Description During an automatic valve test the „KD“ contactor is being activated. If the controller then detects a cabin movement into downward direction, it is to assume that there
is a leaky “down valve”.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - leaky valve
- wiring error

Reset - see causes


- compare to wiring diagram

Error code : 88
Reset 700 + Ok // Tools > Adjustment > Page 2 > Delete UCM error
Short text UCM at hydraulic KD!
Long text UCM at hydraulic KD!
Description During an automatic valve test the „K2“ contactor is being activated. If the controller then detects a cabin movement into downward direction, it is to assume that there
is a leaky “A3 valve”.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - defective contactor
- defective auxiliary contact
- wiring error (K2 contact is bridged)

Reset - see causes


- compare to wiring diagram

Error code : 89
Reserved error code

Error code : 90
Reset Automatic
Short text Conflict IO address
Long text Conflict IO address
Description Two functions were programmed onto the same IO adress.
Reaction - change parametrisation
- the I/O assignment can be checked as follows:
Menu -> Tools -> IO-Assignment -> select Adress e.g. F51.1

Error code : 91
Reset Contact the hotline
Short text LiSA Bus driver / SPI!
Long text LiSA bus driver or\nSPI communication error!
Description Communication between CPU and the bus driver is disturbed.
Reaction General The controller switches into „out-of- order“ mode.
Rope The controller stops in the next possible landing,
Hydraulic The controller stops in the next possible landing and the lift then descends into the lowest landing.
Remedy Change the processor board

Error code : 92
Reset 800 + Ok / Reset
Short text Maximum speed!
Long text Maximum speed!
Description The controller detects a travelled speed which is higher than the value set in „Menu -> Parameter -> General settings -> Travel -> Maximum speed“
Reaction General The controller switches into „out-of- order“ mode.
Rope The controller initiates an emergency stop.
Hydraulic The controller conducts an emergency halt and the lift then descends into the lowest landing.
Causes - maximum speed has been reached
- absolute encoder reading error
- paramters are not set correctly

Reset - check the parameters (the value should lie between the rated speed and the speed governors tripping speed )
- Entering the value „0“deactivates the monitoring.
Should this type of error occur more frequently and possibly together with an absolute encoder reading error, one should consider exchanging the
abosulte encoder. (consult the hotline)

LiSA 20 Error Description Rev 1.01


Fehlermeldungen 17

Error code : 93
Reset 800+Ok / Reset
Short text Deceleration UP!
Long text Deceleration UP!
Description The controller is capable of measuring the deceleration of the cabin and thus serves as simulated deceleration monitoring. After having switched to the slower speed, the
real deceleration of the cabin is measured. Should this value not coincide with the one set under „Parameter > General settings > Deceleration > Page2 > Min.
deceleration ( mm/s2), this error will be indicated.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - above parameter is not set correctly (the value should be slightly smaller than at the inverter)
- control does not decelerate correctly
- hydraulics do not decelerate correctly

Remedy - see causes


- Entering the value „0“ deatives themonitoring.

Error code : 94
Reset 800+Ok / Reset
Short text Deceleration DOWN!
Long text Deceleration DOWN!
Description The controller is capable of measuring the deceleration of the cabin and thus serves as simulated deceleration monitoring. After having switched to the slower speed, the
real deceleration of the cabin is measured. Should this value not coincide with the one set under „Parameter > General settings > Deceleration > Page2 > Min.
deceleration( mm/s2), this error will be indicated.
Reaction General The controller switches into „out-of- order“ mode.
Rope
Hydraulic
Causes - above parameter is not set correctly (the value should be slightly smaller than at the inverter)
- control does not decelerate correctly
- hydraulics do not decelerate correctly

Reset - see causes


- Entering the value „0“ deatives themonitoring.

Error code : 95
Reset Automatic
Short text Step (-) in up movement
Long text Stop before level in up\nmovement
Description The lift stopped BEFORE the landing during upward travel (cabin positioned too low)
Reaction General The controller relevels if relevelling is activated.
Rope
Hydraulic
Causes - braking deceleration is not set correctly
- load-dependent hydraulic system
- unprecise control (open loop)
- disruption during DCP transmission

Reset - set braking deceleration (reduce) (readjust only if this error occures at each landing equally)
- readjust landing hight
- readjust control

Error code : 96
Reset Automatic
Short text Glide in up movement!
Long text Cabin glide in up \nmovement!
Description The lift has passed by the landing during upward travel (SoZone)
Reaction General The controller relevels if relevelling is activated.
Rope
Hydraulic
Causes - braking deceleration is not set correctly
- load-dependent hydraulic system
- unprecise control (open loop)
- disruption during DCP transmission

Reset - set braking deceleration (increase) (readjust only if this error occures at each landing equally)
- readjust landing hight
- readjust control

Error code : 97
Reset Automatic
Short text Glide in down movement!
Long text Cabin glide in DOWN\nmovement!
Description The lift has passed by the landing during downward travel (SuZone)
Reaction General The controller relevels if relevelling is activated.
Rope
Hydraulic
Causes - braking deceleration is not set correctly
- load-dependent hydraulic system
- unprecise control (open loop)
- disruption during DCP transmission

Reset - set braking deceleration (increase) (readjust only if this error occurs at each landing equally)
- readjust landing hight
- readjust control

LiSA 20 Error Description Rev 1.01


18 Fehlermeldungen

Error code : 98
Reset Automatic
Short text Step (+) in DOWN move!
Long text Cabin stoped in DOWN\nmovement!
Description The lift stopped BEFORE the landing during downward travel (cabin positioned too high)
Reaction General The controller relevels if relevelling is activated.
Rope
Hydraulic
Causes - braking deceleration is not set correctly
- load-dependent hydraulic system
- unprecise control (open loop)
- disruption during DCP transmission
-

Reset - set braking deceleration (reduce) (readjust only if this error occurs at each landing equally)
- readjust landing hight
- readjust control

Error code : 99
Reset Contact hotline
Short text Decel. small/ABE-Error!
Long text Deceleration is small \nor ABE pos. is wrong. \nUpper / lower floor!
Description The controller reads an invalid value from the absolute encoder (the allowed range is: (zero point – 900mm as lowest bound) +nlandingdistances+900mm as highest
bound)
Reaction General
Rope
Hydraulic
Causes - reading error of the absolute encoder

Error code : 100


Reset Automatic
Short text DCP ERROR!
Long text Error DCP communication!
Description The controller recognizes a malfunctioning during the communication with the frequency inverter
Reaction General The controller switches into „out-of-oder“ mode. Should the error occur during travel, it is first checked whether the inverter would initiate the
deceleration with proper timing. If this is not the case, an emergency stop is conducted.
Rope
Hydraulic
Causes - jack not connected properly
- isolation of the cable jammed inbetween
- wiring not correct (for longer distances it is curcial to use a shielded and twisted cable)
- shield not placed/cable not led properly
-

Reset - See causes

Error code : 101


Reset 800+ Ok
Short text Valve 1 not opend!
Long text Valve 1 not opend!
Description In the case of electronically monitored valves, an opening of the down valve1 has not been detected
Reaction General The controller switches into „out-of-oder“ mode.
Rope
Hydraulic
Causes - Defective Valve
- Valve is not set correctly
- Wiring error
- Defective input

Reset - see causes


- check input on the status page
- If the input should be defective it can be parameterized to another available I/O any time. ( I: Check valve 1)

Error code : 102


Reset 800+ Ok
Short text Valve 1 not closed!
Long text Valve 1 not closed!
Description In the case of electronically monitored valves, it has not been recognized that upon termination of travel the down valve1 has closed.
Reaction General The controller switches into „out-of-oder“ mode.
Rope
Hydraulic
Causes - Defective Valve
- Valve is not set correctly
- Wiring error
- Defective input

Reset - see causes


- check input on the status page
- If the input should be defective it can be parameterized to another available I/O any time. ( I: Check valve 1)

LiSA 20 Error Description Rev 1.01


Fehlermeldungen 19

Error code : 103


Reset 800+ Ok
Short text Valve 2 not opend!
Long text Valve 2 not opend!
Description In the case of electronically monitored valves, it has not been recognized that upon beginning of travel the down valve2 has opened.
Reaction General The controller switches into „out-of-oder“ mode.
Rope
Hydraulic
Causes - Defective Valve
- Valve is not set correctly
- Wiring error
- Defective input

Reset - see causes


- check input on the status page
- If the input should be defective it can be parameterized to another available I/O any time. ( I: Check valve 2)

Error code : 104


Reset 800+ Ok
Short text Valve 2 not closed!
Long text Valve 2 not closed!
Description In the case of electronically monitored valves, it has not been recognized that upon termination of travel the down valve2 has closed.
Reaction General The controller switches into „out-of-oder“ mode.
Rope
Hydraulic
Causes - Defective Valve
- Valve is not set correctly
- Wiring error
- Defective input

Reset - see causes


- check input on the status page
- If the input should be defective it can be parameterized to another available I/O any time. ( I: Check valve 2)

Error code : 105


Reserved error code

Error code : 106


Reset Automatic
Short text No Group packet!
Long text Group packet was not \nreceived
Description After having issued a group telegram, the controller expects to receive a response from the remaining parts of the group. Should this not happen, this error will be
recorded.
Reaction - Wiring not correct
- Cable guiding (it is curcial to use shielded and twisted cables)
- Defective group board

Error code : 107


Reset Automatic
Short text Inspection end limit!
Long text Inspection: end limit \nswitch is active!
Description The inspection limit switch was surpassed during upward travel
Reaction General The controller switches into „out-of-oder“ mode and conducts an emergency stop.
Rope
Hydraulic
Causes - Limit switch surpassed
- Defective input

Remedy - See causes


- Leave limit switch in downward direction
- Check input on the status page
- If the input should be defective it can be parameterized to another available I/O any time

Error code : 108


Reset Ensure proper functioning of the limit switch by means of a resend travel initiated via activation of the limit switch.
Short text Inspection end limit!
Long text Inspection: end limit \nswitch is active!
Description If there is no –H applying on the programmed input when approaching the highest landing, the controller will immediately switch into „out-of-order“ mode. The error
message „Error inspection limit switch“ will be indicated in the TFT.
Reaction General The controller switches into „out-of-oder“ mode
Rope The lift stops in the upper-most landing.
Hydraulic The lift descends into the lowest landing. Revelling remains active.
Causes - Limit switch not wired
- Wiring not correct
- Defective input

Remedy - See causes


- Check input on the status page
- If the input should be defective it can be parameterized to another available I/O any time

Reset Since the inspection limit switch is of highest importance to ensure the technicians safety, it is impossible to conduct an inspection run until the proper functioning of the
inspection limit switch is confirmed. Resetting this error via reset or by entering 800 is not possible.
The lift may be moved by using the resend function or in the case of hydraulic installations by means of the software resend. As soon as the error is rectified it will be
necessary to move the lift into the upper-most landing (e.g. via resend function). Here, an incoming –H is considered as a verification for the proper functioning of the
inspection limit switch.
Afterwards, the installation can resume normal operation and it is also possible to travel under inspection again.

LiSA 20 Error Description Rev 1.01


20 Fehlermeldungen

Error code : 109


Reserved error code

Error code : 110


Reset Automatic
Short text Short circuit EBus +H
Long text Short circuit EBus to +H
Description The controller detects a short circuit between the landing bus and 24V (+H).

Reaction General The controller switches into „out-of-oder“ mode


Rope

Hydraulic

Causes - Short circuit between landing bus and 24 V

Remedy - Disconnect the landing bus. If the error is then still being indicated, it is rooted in the control cabinet.
- Remove the EBus jack on the PB board. If the error is then still being indicated, contact the hotline.
- If the error disappears after disconnection of the landing bus, the error is to be found in the shaft.

Error code : 111


Reset Automatic
Short text Short circuit EBus -H
Long text Short circuit EBus to -H
Description The controller detects a short circuit between the landing bus and GND (-H).

Reaction General The controller switches into „out-of-oder“ mode

Rope

Hydraulic

Causes - Short circuit between landing bus and GND

Remedy - Disconnect the landing bus. If the error is then still being indicated, it is rooted in the control cabinet.
- Remove the EBus jack on the PB board. If the error is then still being indicated, contact the hotline.
- If the error disappears after disconnection of the landing bus, the error is to be found in the shaft.

Error code : 112


Reset Automatic
Short text Short circuit FBus +H
Long text Short circuit FBus to +H
Description The controller detects a short circuit between the car bus and 24V (+H).

Reaction General The controller switches into „out-of-oder“ mode

Rope

Hydraulic

Causes - Short circuit between landing bus and 24V

Remedy - Disconnect the car bus. If the error is then still being indicated, it is rooted in the control cabinet.
- Remove the FBus jack on the PB board. If the error is then still being indicated, contact the hotline.
- If the error disappears after disconnection of the car bus, the error is to be found on the car/travelling cable.
- If the installation is equipped with 2 door sides and a selective door controlling it is furthermore necessary to check the car bus in the shaft.

Error code : 113


Reset Automatic
Short text Short circuit FBus -H
Long text Short circuit FBus to -H
Description The controller detects a short circuit between the car bus and GND (-H).

Reaction General The controller switches into „out-of-oder“ mode


Rope
Hydraulic
Causes - Short circuit between car bus and GND

Remedy - Disconnect the car bus. If the error is then still being indicated, it is rooted in the control cabinet.
- Remove the FBus jack on the PB board. If the error is then still being indicated, contact the hotline.
- If the error disappears after disconnection of the car bus, the error is to be found on the car/travelling cable.
- If the installation is equipped with 2 door sides and a selective door controlling it is furthermore necessary to check the car bus in the shaft.

Error code : 114


Reset 700 + Ok // Tools > Adjustment > Page 2 > Delete UCM error
Short text RUN/READY on stop mode
Long text NGVA3-Fault: RUN/READY\non in stop mode
Description The electronic valve block sends the „run and ready“ signal during standtill.
Reaction General The controller switches into „out-of-oder“ mode
Rope
Hydraulic
Causes - Defective NGV (during standstill only the „ready“ signal is allowed to apply)
- Wiring error
- Defective input

Remedy - See causes


- Check input on the status page
- If the input should be defective it can be parameterized to another available I/O any time

LiSA 20 Error Description Rev 1.01


Fehlermeldungen 21

Error code : 115


Reset 700 + Ok // Tools > Adjustment > Page 2 > Delete UCM error
Short text RUN/READY beide ein in Fahrt
Long text NGVA3-Fehler RUN/READY beide ein in Fahrt
Description The electronic valve block sends the „run and ready“ signal while travelling.
Reaction General The controller switches into „out-of-oder“ mode
Rope
Hydraulic
Causes - Defective NGV (during standstill only the „run“ signal is allowed to apply)
- Wiring error
- Defective input

Remedy - See causes


- Check input on the status page
- If the input should be defective it can be parameterized to another available I/O any time

Error code : 116


Reset 700 + Ok // Tools > Adjustment > Page 2 > Delete UCM error
Short text RUN/READY off stop mode
Long text NGVA3-Fault: RUN/READY\noff in stop mode
Description The electronic valve block send neither the „run“ nor the „ready“ signal during standtill.
Reaction General The controller switches into „out-of-oder“ mode
Rope
Hydraulic
Causes - Defective NGV (during standstill the „ready“ must apply)
- Wiring error
- Defective input

Remedy - See causes


- Check input on the status page
- If the input should be defective it can be parameterized to another available I/O any time

Error code : 117


Reset 700 + Ok // Tools > Adjustment > Page 2 > Delete UCM error
Short text RUN/READY both off runn.
Long text NGVA3-Fault: RUN/READY\noff between lift running
Description The electronic valve block send neither the „run“ nor the „ready“ signal while travelling
Reaction General The controller switches into „out-of-oder“ mode
Rope
Hydraulic
Causes - Defective NGV (while travelling the „run“ must apply)
- Wiring error
- Defective input

Remedy - See causes


- Check input on the status page
- If the input should be defective it can be parameterized to another available I/O any time

Error code : 118


Reset 800+ Ok / Resend
Short text SM SZ Sequence!
Long text SM SZ sequence wrong
Description The zone switch switching sequence is wrong. When approaching the zone the Sz signal must arrive first, followed by the SM signal.
Reaction General The controller switches into „out-of-oder“ mode
Rope
Hydraulic
Causes - Zone magnets not set correctly
- Landing hight not set correctly (cabin does also not stop in flush position)
- Defective input (SZ)

Remedy - See causes


- Check input on the status page

Error code : 119


Reset Automatic after entry of the telephone number
Short text Dial number not set
Long text Emergency center dial number not set
Description If the controller is set to serve as an emergency call system, it requires the entry of an emergency call telephone number.

Reaction General The controller switches into „out-of-oder“ mode


Rope
Hydraulic
Causes - No telephone number provided

Remedy - Enter a phone number under „ Menu -> Parameter -> Emergency“

LiSA 20 Error Description Rev 1.01


22 Fehlermeldungen

Error code : 120


Reset Automatic
Short text Modem communication!
Long text Error communication to serial modem
Description If there is a modem which is indicated as active at the controller (emergency or remote diagnostics) but cannot be detected, this error will be issued consequently.

Reaction General The controller switches into „out-of-oder“ mode


Rope
Hydraulic
Causes - Modem switched off
- Cable unplugged
- Defective cable
- Modem operation activated even though there is no modem available at the installation

Remedy - See causes

Error code : 121


Reset 800+Ok / Resend / Reset
Short text Error opening door 1
Long text Error opening door 1
Description The controller failed to identify open car doors after 5 attempts to open the doors (SK3/4 does not open)

Reaction General The controller switches into „out-of-oder“ mode


Rope

Hydraulic

Causes - Defective door drive


- Wiring error (APO -> door drive)
- Defective bus module output

Remedy - See causes


- If the input should be defective it can be parameterized to another available I/O any time

Error code : 122


Reset 800+ Ok
Short text cabin movement!
Long text No valid cabin movement!
Description The controller is permanently monitoring whether the car is moving. If no car movement is detected, this error will be issued prior to reaching the travel control time.
(refer to description: Parameter > Special > Fault setup > Cabin movement“)
Reaction General The controller switches into „out-of-oder“ mode
Rope The controller performs an emergency stop
Hydraulic The controller performs an emergency stop and the lift then descends into the lowest landing
Causes - Parameters not set correctly
- Lift does not move inspite of active drive commands

Remedy - See causes


- Entering the value „0“ disabled the monitoring

Error code : 123 ( only with Bucher IValve System )


Reset 700 + Ok // Tools > Adjustment > Page 2 > Delete UCM error
Short text Ivalve A Keine OV
Long text Ivalve A : Keine OV während des Zeitfensters A (Fahrt) erkannt
Description The controller expects a „GND“ signals from the SMA contact during the time span „A“ at the input „control Ivalve“
Reaction General The controller switches into „out-of-oder“ mode
Rope
Hydraulic
Causes - Defective IValve electronic card
- Wiring not correct
- Defective input
- When starting (soft starter is activating), the run is aborted prior to the opening of the valves (short tapping during inspection run)
- When relevelling (relevelling is started and aborted again due to teetering of the car)

Remedy - See causes


- If the input should be defective it can be parameterized to another available I/O any time
- Read the system description Ivalve/SMA
- Set the parameter “IValve deceleration” to 3000 ms

Error code : 124 ( only with Bucher IValve System )


Reset 700 + Ok // Tools > Adjustment > Page 2 > Delete UCM error
Short text Ivalve B: Keine 24V
Long text Ivalve B: Keine 24V während des Zeitfensters B (Stillstand) erkannt
Description During standstill, the controller expects the SMA contact (24V) to close within the time span „B“ of the „Control Ivalve“ input
Reaction General The controller switches into „out-of-oder“ mode
Rope
Hydraulic
Causes - Defective IValve electronic card
- Wiring not correct
- Defective input

Remedy - See causes


- If the input should be defective it can be parameterized to another available I/O any time
- Read the system description Ivalve/SMA

LiSA 20 Error Description Rev 1.01


Fehlermeldungen 23

Error code : 125


Reset 800+ Ok
Short text SZ permanently on!
Long text SZ permanently on!
Description The zone switch SZ is permanently perceived as active by the controller. It needs to be switched off outside of the zone.
Reaction General The controller switches into „out-of-oder“ mode
Rope
Hydraulic
Causes - Zone magnets are not set correctly, so that the magnet switch can no longer be switched off (pay attention to the polarity)
- Defective magnet switch
- Wiring nor correct
- End in travelling cable (compare to wiring diagram)
- Defective input

Remedy - See causes

Error code : 126


Reset 800+ Ok
Short text SZ permanently off!
Long text SZ permanently off!
Description The controller is never able to recognize the zone switch SZ. Wihtin the zone however it needs to be detected.
Reaction General The controller switches into „out-of-oder“ mode
Rope
Hydraulic
Causes - Zone magnets are not set correctly, so that the magnet switch can no longer be switched on (pay attention to the polarity)
- Defective magnet switch
- Wiring nor correct
- Switch not connected
- Defective input

Remedy - See causes

Error code : 127


Reset 800+ Ok
Short text SZ not active in zone!
Long text SZ not active in zone!
Description The controller expects an activated „SZ“ signal in the zone.
Reaction General The controller switches into „out-of-oder“ mode
Rope
Hydraulic
Causes - Zone magnets not set correctly
- Landing hights in the controller do not correspond with reality

Remedy - See causes

Error code : 128


Reset 800+ Ok
Short text SZ toggle not detected!
Long text SZ toggle not detected!
Description The controller expects a change in the „SZ“ signal during travel. Outside of the zone, the signal needs to be inactive and active within the zone.
Reaction General The controller switches into „out-of-oder“ mode
Rope
Hydraulic
Causes - Zone magnets are not set correctly so that the magnet switch cannot be switched on or off (pay attention to the polarity)
- Defective magnet switch
- Wiring not correct
- Switch not connected
- Defective input

Remedy - See causes

Error code : 129


Reset Automatic
Short text Turn off command
Long text Abnormmally request to\nturn off movement cmd
Description If for some reason the controller is forced to conduct an emergency stop this notifictaion will be recorded. Please consult the entries before and after this error in the
error log since they might contain hints concerning the reason for the emergency stop.

Causes - See error log

Error code : 130


Reset Automatic
Short text Emergency Center Err!
Long text Error: emergency center\n not reachable!
Description This error is reported if the controller serves as emergency devise and the control room cannot be contacted during a routine call.
Reaction General The controller switches into „out-of-oder“ mode
Rope
Hydraulic
Causes - Telephone line is disrupted
- No perception in case of a GSM-based emergency call device
- Telephone system is misaligned (number for an outside line is dialed)

Remedy - See causes

LiSA 20 Error Description Rev 1.01


24 Fehlermeldungen

Error code : 131


Reset 800+ Ok / Resend
Short text Movement on start!
Long text Error: movement on\nstart!
Description The controller monitors whether the car starts moving within 3 sec. Of activation of the travelling signals. If no car movement is detected, this error is issued before travel
control time is reached. (compare to: Parameter > Special > Fault Setup > Start cabin movement“)
Reaction General The controller switches into „out-of-oder“ mode
Rope
Hydraulic
Causes - Parameter not set correctly
- Lift does not move even though a travelling command was given

Remedy - See causes


- Entering value „0“ disables the monitoring

Error code : 132


Reset Automatic
Short text Alarm always on!
Long text Alarm always on!
Description If the controller detects the alarm button to be „activated“ for more than 10 minutes, this notification will be reported.
Reaction General The controller switches into „out-of-oder“ mode
Rope
Hydraulic
Causes - Alarm button activated
- Chort circuit on „AL“ or „EC“
- Travelling cable
- Wiring error
- Defective input

Remedy - See causes

Error code : 133


Reset Automatic
Short text ABE not exist!
Long text ABE(WACHENDORF)\nnot exist!
Description If an absolute encoder by Co. Wachendorf is being employed and the controller is not receiving any data from it, this notification will be reported.
Reaction General The controller switches into „out-of-oder“ mode
Rope
Hydraulic
Causes - Defective ABE
- ABE not connected
- Wiring not correct
- Defective travelling cable
- Defective input

Remedy - See causes


- It is absolutely curcial to use shielded cables which are twisted in pairs for connecting the ABE.

Error code : 134


Reset Automatic
Short text ABE not exist!
Long text ABE(ELGO) not exist!
Description If an absolute encoder by Co. Elgo is being employed (LiSA standard) and the controller is not receiving any data from it, this notification will be reported.
Reaction General The controller switches into „out-of-oder“ mode
Rope
Hydraulic
Causes - Defective ABE
- ABE not connected
- Wiring not correct
- Defective travelling cable
- Defective input

Remedy - See causes


- It is absolutely curcial to use shielded cables which are twisted in pairs for connecting the ABE.

Error code : 135


Reserved error code

Error code : 136


Reserved error code

Error code : 137


Reserved error code

Error code : 138


Reserved error code

LiSA 20 Error Description Rev 1.01


Fehlermeldungen 25

Error code : 139


Reset Automatic
Short text Resend en. in 2 input
Long text Resend enable in two point
Description The „RUE“ input (P.45) on the PB as well as one additionally programmed input for resend ( Parameter > Input/Output > General Inputs > I:Resend ) are simultaneously
active.
Reaction General The controller switches into „out-of-oder“ mode
Rope
Hydraulic
Causes - Both inputs are active
- Wiring error
- Parameter not correct
- Defective input

Remedy - See causes


- Check input on the status page
- If the input should be defective it can be parameterized to another available I/O any time

Error code : 140


Reset 800+ Ok
Short text Input emergency call!
Long text Error: input emergency\ncall
Description When an emergency call is activated,
Wird ein Notrufsystem genutzt, so kann am Eingang „ Parameter > Ein/Ausgänge > Eingänge Allgemein > Seite 5 > I:Fehler GSM/Notrufsys. ) der Störmeldekontakt des NS
angeschlossen werden. Ist der Eingang aktiviert, wird dieser Fehler hinterlegt
Reaction General The controller switches into „out-of-oder“ mode
Rope The lift terminates its run and then stops.
Hydraulic The lift terminates its run and descends into the lowest landing.
Causes - Emergency call system is reporting an error
- No power supply coverage when GSM
- Wiring not correct
- Defective input

Remedy - See causes


- Check input on the status page
- If the input should be defective it can be parameterized to another available I/O any time

Error Code : 141


Reset 800+ Ok
Short text Reset apron active!
Long text Input reset apron\npermanently on!
Description The controller recognizes that the „reset“ input for the hinged apron is permanently acitve. If the apron is to be reset, there should only be a „reset impulse“.
Reaction General The controller switches into „out-of-oder“ mode
Rope
Hydraulic
Causes - Reset switch hanging/switched permanently
- Wiring error
- Defective input

Remedy - If the input should be defective it can be parameterized to another available I/O any time

Error code : 142


Reset Automatic
Short text ABE magnet band!
Long text Error ABE magnet band!
Description The ABE reading head communicates a defective magnetic tape to the controller.
Reaction General The controller switches into „out-of-oder“ mode and conducts an emergency stop.
Rope
Hydraulic
Causes - Defective magnetic tape
- Magentic tape not installed correctly (compare ABE (absolute encoder) installation manual)
- ABE reading error
- Wiring not correct (for longer distances it is curcial to use a shielded cable which is twisted in pairs)
- Shield not applied/ cable not led properly

Remedy - See causes

Error code : 143


Reset Automatic
Short text No inverter-READY!
Long text Inverter ready input\nnot active!
Description Only for installations with a „standby“ function: The controller expects to receive a „ready“ signal, which is to be issued as soons as the inverter accepts drive commands.
Should such a signal not be received, this notification will be recorded.
Reaction General The controller switches into „out-of-oder“ mode
Rope
Hydraulic
Causes - Inverter not ready
- Wiring not correct
- Defective input

Remedy - See causes


- If the input should be defective it can be parameterized to another available I/O any time

LiSA 20 Error Description Rev 1.01


26 Fehlermeldungen

Error code : 144 ( Only for Bucher IValve System )


Reset 700+ Ok
Short text Ivalve B2: no 0V->6sec!
Long text Ivalve B2: 0V not detec-\nted after 6sec!
Description The controller expects to receive a „GND“ signal from the SMA within 6s.
Reaction General The controller switches into „out-of-oder“ mode
Rope ---------------------------------------------------------------------------
Hydraulic The lift descends into the lowest landing
Causes - Defective IValve electronic card
- Wiring not correct
- Defective input

Remedy - See causes


- If the input should be defective it can be parameterized to another available I/O any time
- Read system description for Ivalve / SMA

Error code : 145 ( Only with Bucher IValve System )


Reset Automatic
Short text IValve IO Error!
Long text IValve IO Bus Modul nicht erkannt!
Description Sind die Eingänge zur Überwachung des Ivalve auf einem Bus Modul programmiert, so ist sicherzustellen, dass die Steuerung diese Modul immer „sieht“, also das Modul
aktiv ist. Sollte das Modul ausfallen, erkennt die Steuerung dies und setzt die Anlage still.
Reaction General The controller switches into „out-of-oder“ mode
Rope
Hydraulic
Causes - Defective Bus module
- Bus module is not properly mounted to the bus cable (loose contact)

Remedy - Exchange the Bus module


- Press Bus module again to restore proper fit

Error code : 146


Reserved error

Error code : 147


Reset Menu > Tools > Seite 2 > Reset Wartungsintervall ( Nur für Benutzer mit „Priority Level“ )
Short text Maintenance interval
Long text Maintenance interval\nreached!
Description The value set under Menu -> Parameter -> Special -> Maintenance intervall has been reached. The maintenance interval can be effected from number of travels,
operating hours and direction changes.
Reaction General The controller switches into „out-of-oder“ mode
Rope
Hydraulic
Causes - Maintenance interval has been reached

Remedy - Menu –> Tools -> Page 2 -> Reset service intervall

Error code : 148


Reset Automatic
Short text Module 48 error!
Long text Module 48 error!
Description Das Fahrkorbmodul mit der Adresse 48 wird zum einlesen der Inspektionsteuerung genutzt. Damit die uneingeschränkte Funktion der Inspektionssteuerung immer
gewährleistet ist, wird dieses Modul permanent überwacht.
Reaction General The controller switches into „out-of-oder“ mode
Rope
Hydraulic
Causes - Defective module
- Module not plugged
- No communication between controller and car (bus disturbed)

Remedy - Change module (pay attention to jumpers)


- Plug module (possibly corroded contacts)
- If none of the modules can be recognized (status page) check the wiring of the car bus.

Error code : 149


Reset 800 +Ok
Short text ext.Sicherheitssch.inakt.
Long text external Sicherheitsschaltung inaktive
Description If an external safety circuit is being used, the controller offers a possibility to monitor it. The controller expects a status change at the monitoring input in order to ensure
the proper functioning of the safety circuit. Should the controller detect a permanently inactive signal one can expect an error case.
Reaction General The controller switches into „out-of-oder“ mode and conducts an emergency stop.
Rope
Hydraulic
Causes - Monitoring function has activated
- Defective safety relay
- Wiring not correct
- Defective input (Menu > Paramater > Input/Output > General inputs > Page 5 -> I:Test ext. Safetyrelays)

Remedy - See causes


- If the input should be defective it can be parameterized to another available I/O any time

LiSA 20 Error Description Rev 1.01


Fehlermeldungen 27

Error code : 150


Reset 800 +Ok
Short text ext.Sicherheitssch.akt.
Long text external Sicherheitsschaltung aktive
Description If an external safety circuit is being used, the controller offers a possibility to monitor it. The controller expects a status change at the monitoring input in order to ensure
the proper functioning of the safety circuit. Should the controller detect a permanently active signal one can expect an error case.
Reaction General The controller switches into „out-of-oder“ mode and conducts an emergency stop.
Rope
Hydraulic
Causes - Monitoring function has activated
- Defective safety relay
- Wiring not correct
- Defective input (Menu > Paramater > Input/Output > General inputs > I:Test ext. safetyrelays)

Remedy - See causes


- If the input should be defective it can be parameterized to another available I/O any time

Error code : 151


Reset Automatic
Short text mode_change_1
Long text GO_TO_INSPECTION_BETWEEN_MOVEMENT
Description Inspection was activated during travel
Causes See description

Error code : 152


Reset Automatic
Short text mode_change_2
Long text GO_TO_RESEND_BETWEEN_MOVEMENT
Description Resend control was activatived during travel
Causes See description

Error code : 153


Reset Automatic
Short text mode_change_3
Long text GO_TO_INSTALATION_BETWEEN_MOVEMENT
Description Installation run was activated during travel
Causes See description

Error code : 154


Reset 800 +Ok / automatic when SK4 is being closed
Short text CAM_TIME_OUT
Long text ADDITIONAL_RETIRING_CAM_TIME_OUT
Description When the locking magnet is activated by the controller, the safety circuit should close (SK4). If this is not the case, this error notification will be recorded.
The controller deactivates the interlock and a retry is conducted after 50 sec.
Reaction General The controller switches into „out-of-oder“ mode and conducts an emergency stop.
Rope
Hydraulic
Causes - Defective locking magnet
- Wiring not correct
- Defective output (Relay)
- Locking contact not set correctly

Remedy - See causes

Error code : 155


Reset
Short text HARDFAULT_HANDLER
Long text HARDFAULT_HANDLER
Description There is a problem in the CPU.
Remedy Contact hotline

Error code : 156 (only for activated deceleration monitoring control)


Reset Automatic after entry of the I/Os
Short text no. IOs defi. for decal. Contr.
Long text No inputs defined for deceleration control
Description The installation is equipped with a deceleration monitoring control (VZK), where the controller represents part of the monitoring unit. Hence, several I/Os need tob e
defined. This notification will be issued should they not be programmed,
Reaction General The controller switches into „out-of-oder“ mode
Rope
Hydraulic
Causes - Deceleration control active but no I/Os were programmed

Remedy - Programm I/O „Menu > Parameter > General settings > Deceleration control“

LiSA 20 Error Description Rev 1.01


28 Fehlermeldungen

Error code : 157 (only for activated deceleration monitoring control)


Reset Automatic after entry of the speed value
Short text Nominal speed is not set
Long text Nominal speed is not set
Description If the installation is equipped with a deceleration monitoring control (VZK) where the controller represents part of the monitoring unit, it is absolutely necessary to set a
nominal speed.
Reaction General The controller switches into „out-of-oder“ mode
Rope
Hydraulic
Causes - Deceleration control active but no nominal speed is set

Remedy - Set nominal speed: „Menu > Parameter > General settings > Travel > Nominal speed“

Error code : 158 (only for activated deceleration monitoring control)


Reset 800+Ok / Reset
Short text Safety circuit decel. Contr.
Long text Safety circuit for deceleration control tripped
Description When the installation is equipped with a deceleration monitoring control (VZK) where the controller represents a part of the monitoring unit, an external safety circuit
will be used for this. It will be permanently monitored by the controller to ensure proper functioning. This error message will be issued, should the controller detect an
error.
Reaction General The controller switches into „out-of-oder“ mode and conducts an emergency stop
Rope
Hydraulic
Causes - Error in the safety circuit
- Wiring not correct
- Defective input

Remedy - See causes


- If the input should be defective it can be parameterized to another available I/O any time

Error code : 159 (only for activated deceleration monitoring control)


Reset 800+Ok / Reset
Short text Contact. Drop decel. control
Long text Contactor monitoring for deceleration control
Description When the installation is equipped with a deceleration monitoring control (VZK) where the controller represents a part of the monitoring unit, the contactors and relays
which are used for this purpose are monitored as to whether they pull in and release.

Reaction General The controller switches into „out-of-oder“ mode and conducts an emergency stop
Rope
Hydraulic
Causes - Defective contactor/relay
- Burnt contact
- Wiring not correct
- Defective input

Remedy - See causes


- If the input should be defective it can be parameterized to another available I/O any time

Error code : 160


Reset Automatic
Short text Modul inspection in pit!
Long text Modul inspection in pit is not alive
Description The bus module responsible for the inspection control in the pit is not recognized by the controller.
Reaction General The controller switches into „out-of-oder“ mode
Rope
Hydraulic
Causes - Bus module not connected
- Defective bus module
- I/Os parameterized onto a non-existing module

Remedy - Connect module


- Check parameters

Error code : 161


Reset Automatic
Short text Pit emergency stop!
Long text Emergency stop in PIT\nis pressed
Description The emergency stop at the car is monitored by the controller. This notification is recorded after activation of the emergency stop.
Reaction General The controller switches into „out-of-oder“ mode
Rope
Hydraulic
Causes - Emergency stop activated in the pit
- Defective input
- Wiring not correct

Remedy - Reset emergency stop


- See causes

LiSA 20 Error Description Rev 1.01