High Performance Transistor Inverter True Torque Control Drive Series
High Performance Transistor Inverter True Torque Control Drive Series
High Performance Transistor Inverter True Torque Control Drive Series
December, 1998
ICC #10160-001
Introduction
Thank you for purchasing the “Profibus-DP Communications Interface” for the
Toshiba TOSVERT-130 G3 High-Performance Transistor Inverter. Before using the
Profibus-DP interface, please be sure to thoroughly read the instructions and
precautions contained in this manual. In addition, please make sure that this
instruction manual is delivered to the end user of the inverter unit into which the
Profibus-DP interface kit is installed, and keep this instruction manual in a safe place
for future reference or inverter inspection.
1
Usage Precautions
Operating Environment
•= Please use the interface only when the ambient temperature of the inverter unit into
which the interface is installed is within the following specified temperature limits:
Operation: -10 ∼ +40°C (+14 ∼ +104°F)
Storage: -25 ∼ +65°C (-13 ∼ +149°F)
•= Avoid installation locations that may be subjected to large shocks or vibrations.
•= Avoid installation locations that may be subjected to rapid changes in temperature or
humidity.
Installation • Wiring
•= Do not touch charged parts such as the terminal block while the inverter’s CHARGE
lamp is lit. A charge will still be present in the inverter unit’s internal electrolytic
capacitors, and therefore touching these areas may result in an electrical shock.
Always turn all inverter input power supplies OFF, and wait at least 5 minutes after the
CHARGE lamp has gone out before connecting communication cables or motor wiring.
•= When installing the interface board into the inverter and making wiring connections,
make certain that no clippings or wiring leads that could cause device failure fall into
the inverter or onto electronic components.
•= Proper ground connections are vital for both safety and signal reliability reasons. For
proper grounding procedures, please refer to the section in this manual pertaining to
grounding (section 3).
•= Route the communication cables separate from the inverter input/output power wiring.
•= To avoid the possibility of electric shock due to leakage currents, always ground the
inverter unit’s E/GND terminal and the motor. To avoid misoperation, do not connect
the Profibus interface board's shield terminal to either of the above-mentioned grounds
or any other power ground.
Other Precautions
•= The inverter’s EEPROM has a life span of 10,000 write cycles. Do not write to the
same parameter register more than 10,000 times.
•= Do not touch or insert a rod or any other item into the inverter while power is applied,
as this may lead to electrical shock or inverter damage.
•= Commission the disposal of the interface board to a specialist.
•= Do not assign the same address to more than one inverter in the same network.
•= Individual slave addresses can be set from 0 ∼ 125. Addresses 126 and above are
invalid, and will cause the inverter to trip "OPTION PCB ERROR".
•= When the inverter’s control power supply is turned on, the inverter performs
initialization functions for approximately 2 seconds, during which communications
capabilities are disabled. Communications capabilities will also be disabled for
approximately 2 seconds after momentary control power supply outages or inverter
resets.
2
TABLE OF CONTENTS
7. G3 Parameter Settings...........................................................................17
3
11.2.7 GROUP:PROTECTION FUNCTION PARAMETERS...........................43
11.2.8 GROUP:PATTERN RUN CONTROL PARAMETERS..........................45
11.2.9 GROUP:FEEDBACK CONTROL PARAMETERS................................48
11.2.10 GROUP:COMMUNICATION SETTING PARAMETERS ......................49
11.2.11 GROUP:AM/FM TERMINAL ADJUSTMENT PARAMS........................50
11.2.12 GROUP:UTILITY PARAMETERS........................................................51
11.2.13 GROUP:MOTOR RATING PARAMETERS .........................................53
11.3 Inverter Fault Codes ...................................................................................55
4
1. Interface Board Diagram
5
2. Interface Board Installation / Removal
The Profibus Communications Option ROM enclosed with the Profibus kit is
compatible only with G3 inverters with V120 or later main software. An error will
occur if the option ROM is installed in an inverter with pre-V120 main software. The
main software version number is printed on the CPU package (IC1) on the control
board. Additionally, this version number can be read from inverter memory by
displaying the parameter CPU VERSION in GROUP:UTILITY PARAMETERS. If you
are unsure of the software version of your inverter, please contact Toshiba
International Corporation for more information.
The Profibus option ROM version number is printed on the label attached to the
ROM. The option ROM version number can also be read from the inverter’s memory
and displayed on the LCD panel after initialization by displaying the parameter ROM
VERSION in GROUP:UTILITY PARAMETERS. The option ROM version number
replaces the standard ROM version number after installation/initialization.
IMPORTANT NOTE: The option ROM included with the Profibus interface kit
is for installation into G3 230V/460V units only. Do not install the option ROM into
any other inverter unit (such as H3, E3, or G3 600V units). All inverter units other
than the G3 230V/460V series are shipped from the factory with full communications
capability, and installation of the option ROM may cause incorrect operation or
inverter damage.
Please note that due to internal mechanical clearances, not all Profibus connectors
can be used on all inverter units. Ensure that the Profibus connector that you plan on
using does not come into contact with any of the drive’s internal components, circuit
boards or brackets. Toshiba has determined that connectors such as the ERNI
103648 (non-terminated) and 103649 (terminated) will work for all installations. If you
have difficulty locating a connector which will work properly in your unit, please
contact Toshiba International Corporation for assistance.
Additionally, certain drive models require a modified panel support bracket to allow
installation of the Profibus interface. Specifically, all G3 460v 10HP through 50HP
and 230v 7.5HP through 25HP units require a modified panel support bracket. To
obtain this support bracket, contact your local distributor or Toshiba International
Corporation.
6
•= Setting the standard mode selection parameter will be referred to in this manual
as performing a TYPE X RESET, where X is the parameter setting value.
Record the standard ROM version number prior to option ROM installation. The
standard ROM version can be read from parameter ROM VERSION in
GROUP:UTILITY PARAMETERS.
Standard ROM version = .
2. CAUTION! Verify that all input power sources to the inverter have
been turned OFF and are locked and tagged out.
4. Remove the inverter’s cover (open the door on units with hinged doors).
Verify that the CHARGE LED has gone out before continuing the installation
process.
5. Loosen the 4 screws attaching the G3’s operation panel support bracket to the
control board support bracket, and then remove the operation panel and support
bracket as a unit (refer to Figure 1).
7
operation panel
support bracket
6. CAUTION! The option ROM PCB assembly and interface board are
static-sensitive devices. Standard electrostatic-sensitive component handling
precautions should be observed. Locate the option ROM connector, labeled
CN41, on the lower-left side of the control PCB. Line up the connector on the
back of the option ROM PCB with CN41. Install the option ROM by pressing
gently but firmly on the option ROM PCB until a slight “click” is felt. Verify that the
option ROM PCB is seated properly and firmly in CN41. If the option ROM
connector does not appear to be mating with CN41 properly, verify that the ROM
is oriented properly and that there are no obstructions in either connector.
7. Install the 4 nylon standoffs into the holes provided in the control board support
bracket (refer to Figure 2).
8
standoff mounting holes
8. Install the Profibus network cable through the access holes at the bottom of the
inverter and route the cable in order to make connections to the interface board
connector (CN1). Take care to not route the cable near any sharp edges or in
positions where it may be pinched.
9. Connect the Profibus cable to the interface board connector (CN1). If a ground
cable is going to be used, attach the ground cable to the plated hole near CN1 on
the lower-right portion of the Profibus board (refer to section 3).
CAUTION! Extremely high voltages exist in the area near the Profibus
interface board and connector. Ensure that no stray wires come into contact with
any internal inverter components. Also ensure that the communications cable is
not routed in such a manner that it may come into contact with high-voltage
inverter components, or inverter components that may heat up during operation
and damage the cable insulation.
10. Install the interface board into the inverter by carefully aligning the 4 nylon
standoffs with the 4 mounting holes provided in the interface board. Ensure that
connector CN5A on the back side of the interface board is aligned with connector
CN5 on the front side of the control board.
11. Press the interface board firmly onto the standoffs and connector CN5 until the
standoff retaining tabs lock. Ensure that CN5 and CN5A are thoroughly
interlocked.
12. Carefully re-install the operation panel and support bracket and tighten the 4
screws that attach the operation panel support bracket to the control board
support bracket. Once installed, take a moment to verify that all interface board
and network components have sufficient clearance from other drive components.
9
13. If a ground cable is being used, connect the ground cable to the selected ground
point.
14. Reinstall the inverter’s cover (close and latch the door on units with hinged
doors).
DANGER! Do not operate the unit with the cover off / cabinet
door open.
15. Turn all power sources to the inverter unit ON, and verify that the inverter
functions properly. If the inverter unit does not appear to power up, or does not
function properly, immediately turn power OFF. Repeat steps 2 ∼ 4 to remove
all power from the inverter. Then, verify all connections. Contact Toshiba
International Corporation for assistance if the problem persists.
16. To perform final verification that the option ROM is installed properly, display the
value of the ROM VERSION parameter in GROUP:UTILITY PARAMETERS. This
number should match the option ROM version number that was recorded in step
1. If this parameter value does not match the option ROM version number
recorded in step 1, repeat steps 2 ∼ 4 to remove all power from the inverter,
then re-verify that the option ROM is installed properly. If the option ROM
appears to be installed properly, but the version numbers still do not match,
contact Toshiba International Corporation for further assistance.
10
2.3 Removal
Removal of the Profibus interface board from a TOSVERT-130 G3 inverter should
only be performed by a qualified technician familiar with the maintenance and
operation of the G3. In order to protect the interface board connector’s reliability, do
not repeatedly connect and disconnect the interface. Use the following procedure if it
becomes necessary to remove the Profibus interface board from the inverter.
1. CAUTION! Verify that all input power sources to the inverter have
been turned OFF and are locked and tagged out.
3. Remove the inverter’s cover (open the door on units with hinged doors).
Verify that the CHARGE LED has gone out before continuing the removal
process.
4. Loosen the 4 screws attaching the operation panel support bracket to the control
board support bracket and remove the operation panel and support bracket as a
unit (refer to Figure 3).
11
operation panel
support bracket
5. CAUTION! The option ROM PCB and Profibus interface board are
static-sensitive devices. Standard electrostatic-sensitive component handling
precautions should be observed. Release the 4 corners of the interface board
from the standoffs by pressing down on the standoff locking tabs with a small flat-
headed screwdriver. Be careful to not apply any abnormal stress to the interface
board while performing this, as this may damage the interface board or control
board connectors.
6. Remove the interface board from the inverter.
7. Disconnect the communications cable from the interface board connector (CN1),
and pull the cable out through the access holes at the bottom of the inverter.
8. Locate the option ROM in the option ROM connector, labeled CN41, on the
lower-left side of the control PCB. Gently work the option ROM PCB up and
down while pulling on it until the ROM releases from the control PCB option ROM
connector.
IMPORTANT NOTE: Do not remove the option ROM on inverter units that
were received from the factory with option ROMs pre-installed. Units that are
shipped from the factory with option ROMs pre-installed (H3 and 600V G3 units,
for example) require these ROMs for correct operation, and removal of the option
ROM may cause incorrect operation or inverter damage. If you are in doubt
about the requirement of an option ROM in your inverter unit, contact Toshiba
International Corporation for assistance.
9. Carefully re-install the operation panel and support bracket and tighten the 4
screws that attach the operation panel support bracket to the control board
support bracket.
12
10. Reinstall the inverter’s cover (close and latch the door on units with hinged
doors).
13
3. Grounding
Grounding is of particular importance for reliable, stable operation. Communication
system characteristics may vary from system to system, depending on the system
environment and grounding method used. The Profibus interface card is provided
with a plated SHIELD connection point by CN1, on the lower right-hand side of the
board. This SHIELD connection point is directly connected to the metallic housing of
the DB9 connector, which should then be connected to the shield of the Profibus
network cable through the Profibus connector. To ground the network cable shield,
therefore, connect a wire with lug terminal to this SHIELD point, and then connect the
other end of the wire to an appropriate ground. For specific details and requirements
regarding protective grounding and the Profibus network, refer to the Profibus
Standard (DIN 19245, part 1).
Please be sure to consider the following points for making proper ground
connections:
4. Equipment Specifications
Item Specification
Indoors, less than 1000m above sea level, do not
Operating Environment
expose to direct sunlight or corrosive / explosive gasses.
Operating Temperature -10 ∼ +40°C (+14 ∼ +104°F)
Storage Temperature -25°C ∼ +65°C (-13 ∼ +149°F)
Relative Humidity 20% ∼ 90% (without condensation)
Vibration 5.9m/s2 {0.6G} or less (10 ∼ 55Hz)
Grounding According to DIN 19245, part 1
Cooling Method Self-cooled
14
5. Maintenance And Inspection
Preventive maintenance and inspection is required to maintain the Profibus
communication interface in its optimal condition, and to ensure a long operational
lifetime. Depending on usage and operating conditions, perform a periodic
inspection once every three to six months. Before starting inspections, always turn
off all power supplies to the inverter unit, and wait at least five minutes after the
inverter’s “CHARGE” lamp has gone out.
Inspection Points
•= Check that the network connector screws are not loose. Tighten if necessary.
•= Check that there are no defects in any attached grounding wire terminal crimp
points. Visually check that the crimp points are not scarred by overheating.
•= Visually check the wiring and cables for damage.
•= Clean off any accumulated dust and dirt. Place special emphasis on cleaning the
ventilation ports of the inverter and all installed PCBs. Always keep these areas
clean, as adherence of dust and dirt can cause premature component failure.
•= If use of the inverter unit is discontinued for extended periods of time, turn the
power on at least once every two years and confirm that the unit still functions
properly.
•= Do not perform hi-pot tests on the inverter or Profibus interface board, as they
may damage the unit’s internal components.
Please pay close attention to all periodic inspection points and maintain a good
operating environment.
15
6. Storage And Warranty
6.1 Storage
Observe the following points when the Profibus interface board is not used
immediately after purchase or when it is not used for an extended period of time.
•= Avoid storing the interface board in places that are hot or humid, or that contain
large quantities of dust or metallic dust. Store the interface board in a well-
ventilated location.
•= When not using the Profibus interface board for an extended period of time, turn
the power on at least once every two years and confirm that it still functions
properly.
6.2 Warranty
The Profibus communications interface kit is covered under warranty for a period of
12 months from the date of installation, but not to exceed 18 months from the date of
shipment from the factory. For further warranty or service information, please contact
Toshiba International Corporation.
16
7. G3 Parameter Settings
Profibus interface board communications are enabled by setting parameter
COMMUNICATION SELECTION in GROUP:COMMUNICATION SETTING PARAMETERS
to 2 (Profibus, Modbus, DeviceNet). None of the Tosline-F10 communication
parameter settings apply when using the Profibus interface. For more information on
methods for changing parameter settings, refer to the TOSHIBA G3 Operation
Manual.
The following is a list of the parameter settings that are required during setup to
enable Profibus communications:
Note: Although the INVERTER ID NUMBER parameter can be set from 0 to 255,
the allowable Profibus slave addresses range only from 0 to 125. Therefore,
if this parameter is set to a value from 126 to 255, the Profibus interface card
will trip “OPTION PCB ERROR” upon initialization. To correct this error, set
the INVERTER ID NUMBER parameter to a value from 0 to 125.
If the drive into which a Profibus communications interface board is installed trips
“OPTION PCB ERROR” for any reason during initialization or operation (for example,
if it becomes loose from its mounting connections), it is incapable of being reset via
the Profibus network. When this trip condition occurs, therefore, the drive can only
be reset locally via the panel or control terminal block.
Of course, input data can always be monitored from the network regardless of the
settings of COMMAND MODE SELECTION and FREQUENCY MODE SELECTION. Also
note that if the COMMAND MODE SELECTION or FREQUENCY MODE SELECTION
parameters are changed while the drive is running, the change will not take effect
until the next time the drive is stopped.
17
8. Feature Summary
The Toshiba Profibus-DP interface provides a wide array of network data access and
drive control features. Combined with the flexible configuration and high-speed data
transfer capabilities of the Profibus network, this allows powerful networked control
and monitoring systems to be designed. Some of the main features provided in the
G3 Profibus-DP interface which allow for this control and configurability are briefly
described here:
Protocol
Profibus DP (Decentralized Periphery). The interface can also co-exist
simultaneously on networks using Profibus-FMS.
Network Watchdog
A network watchdog function is always operating within the interface – in the event of
a disconnection from the network or loss of the network master, the interface will
automatically stop the drive for safety (note that either the COMMAND MODE
SELECTION or FREQUENCY MODE SELECTION parameter must be set to 3 (network
control) in order for the drive to stop when a watchdog time-out occurs).
18
Indicators
1 green LED is provided to indicate when the interface has achieved the
DATA_EXCHANGE state with the network master. This serves as a convenient
indicator that the master and drive are configured properly and are exchanging data.
Isolation
The network interface portion of the Profibus-DP board is fully optically-isolated for
optimal noise-immunity characteristics.
Network Connector
The network interface is a standard DB9 connector with the following signals
provided:
In addition to the above signals, the metallic housing of the DB9 connector is
connected to the shield section of the interface board. The shield section contains a
plated connection point where a ground wire can be attached to connect the network
cable shield to ground. Refer to section 3 of this document for more information
related to grounding.
Input/Output Data
The interface’s cyclic data sizes are fixed at 8 bytes of output (control) data
configured as 4 words, and 16 bytes of input (status) data configured as 7 words and
2 bytes. For detailed explanations of the format and usage of this data, refer to
sections 9 and 10 of this document.
19
9. Exchanged Data Structures
Frequency
2
command high byte
Drive’s frequency command
Frequency
3
command low byte
Parameter number
4 Parameter action bits and upper 4 bits of the
/ action high byte
parameter register number. Refer to section 10
Parameter number for a detailed explanation of this data word
5
low byte
Parameter data to
6 During parameter register writes, this word
write high byte
contains the data to write. Refer to section 10
Parameter data to for a detailed explanation of this data word
7
write low byte
The data contained in the frequency command word must be the desired frequency
command multiplied by 100, and then converted to hexadecimal. In other words, if a
frequency command of 55.34Hz is desired, then 55.34 x 100 = 5534, which
converted to hexadecimal is 0x159E. The frequency command high byte (offset 2)
must therefore contain 0x15, and the frequency command low byte (offset 3) must
contain 0x9E.
In this way, the G3’s allowable frequency command range of 0.00Hz ∼ 400.00Hz
equates to network values of 0x0000 ∼ 0x9C40.
Regardless of the frequency command value sent via the Profibus network to the
drive, the actual operating frequency of the drive will still be limited locally by the
LOWER LIMIT FREQUENCY, UPPER LIMIT FREQUENCY, and MAXIMUM OUTPUT
FREQUENCY parameter settings.
20
Table 1 : Command Word Format
selection 1: forward
3 Acc/dec #1 / #2 selection 0: Acc / dec #1
1: Acc / dec #2
4 Reserved
5 Reserved Value is ignored
6 Reserved
7 Jog mode selection 0: Normal (acc/dec mode)
1: Jog mode
8 Feedback control 0: Feedback valid
1: Feedback invalid
9 Compulsory DC injection 0: No compulsory DC injection braking
braking mode 1: Compulsory DC injection below DC
INJECTION START FREQUENCY
A Fundamental parameter 0: V/F #1
High Byte
switching 1: V/F #2
B Gate block (coast stop) 0: Normal
command 1: Gate block
C Emergency off command 0: Does nothing
1: Emergency off
D Reset command (trip clear) 0: Does nothing
1: Reset when tripped
E Reserved
Value is ignored
F Reserved
21
9.2 Input (Status) Data Format
The input data structure from the G3 Profibus interface card to the network master is
comprised of 16 bytes structured as 7 words and 2 independent bytes:
Output frequency
2
high byte
Drive’s current operating frequency
Output frequency
3
low byte
IV input terminal
4 Continuously reports the value of the drive’s IV
value high byte
analog input terminal. 0 ∼ 100% terminal input
IV input terminal corresponds to data values of 0x0000 ∼ 0xFFFF
5
value low byte
RR input terminal
6 Continuously reports the value of the drive’s RR
value high byte
analog input terminal. 0 ∼ 100% terminal input
RR input terminal corresponds to data values of 0x0000 ∼ 0xFFFF
7
value low byte
Input terminal
8 Bit-level status word of drive’s digital input
monitor high byte
terminals (refer to Table 3 : Input Terminal
Input terminal Monitor Word Format)
9
monitor low byte
Parameter number
12 Parameter action bits and upper 4 bits of the
/ action high byte
parameter register number. Refer to section 10
Parameter number for a detailed explanation of this data word
13
low byte
22
In order to determine the drive’s actual output frequency, the data contained in the
output frequency word (offsets 2 and 3) must first be converted from hexadecimal to
decimal, and then divided by 100. For example, if the output frequency high byte is
0x12 and the output frequency low byte is 0x34, then 0x1234 converted to decimal is
4660. Dividing this number by 100, the actual operating frequency of 46.60Hz is
obtained.
In this way, network data values of 0x0000 ∼ 0x9C40 correspond to the G3’s actual
allowable output frequency range of 0.00Hz ∼ 400.00Hz.
23
Table 3 : Input Terminal Monitor Word Format
1: Terminal – CC shorted
4 S3 0: Terminal – CC open
1: Terminal – CC shorted
5 S4 0: Terminal – CC open
1: Terminal – CC shorted
6 S5 (option) 0: Terminal – CC open
1: Terminal – CC shorted
7 S6 (option) 0: Terminal – CC open
1: Terminal – CC shorted
8 Reserved
9 Reserved
A Reserved Always 0
B Reserved
High Byte
C Reserved
D S7 (option) 0: Terminal – CC open
1: Terminal – CC shorted
E RES 0: Terminal – CC open
1: Terminal – CC shorted
F ST 0: Terminal – CC open
1: Terminal – CC shorted
9.3 Diagnostics
When the drive trips, 1 byte of high-priority user diagnostics is supplied to the master.
The value of the diagnostics byte is the drive’s fault code. Refer to section 11.3 for a
list of drive fault codes.
24
10. Parameter Register Access
Bit #: 15 14 13 12 11 8 7 4 3 0
Reserved
Reserved
Req1
Req0
Bit #: 15 12 11 8 7 4 3 0
25
10.2 Parameter Number / Action Input Words
The response by the G3 interface card to parameter read and write requests is
placed in 2 input words of the input data structure. The structure of these 2 input
words is as follows:
Bit #: 15 14 13 12 11 8 7 4 3 0
Resp1
Resp0
0 0 Parameter number (12 bits)
Bit #: 15 12 11 8 7 4 3 0
26
10.3 Parameter Access Procedure
In order to read from a parameter or write to a parameter, 2 control bits are provided.
These bits, labeled Req1 and Req0 in the Parameter number / action word, can have
the following values:
Similarly, when the drive responds to a parameter read or write request, 2 status bits
are provided. These bits, labeled Resp1 and Resp0 in the Parameter number /
action response word, can have the following values:
Performing a parameter read or write action from the Profibus master involves the
following process:
1. Send a “no action” code (Req1=0 and Req0=0). Every parameter access must
begin from the idle state. Once this state is sent, the Profibus master must then
wait for the G3 Profibus interface card to respond with an idle state acknowledge
(Resp1=0 and Resp0=0).
2. If the action is to be a data write, set the parameter data in the parameter data
write word. If the action is to be a data read, the parameter data write word value
is irrelevant.
3. Set the parameter register number (12 bits) and action code (Req1 and Req0).
For a list of parameter register numbers, refer to section 11.
4. Once the G3 Profibus interface receives the read or write request, it will begin
processing it. Typically, the drive will require from 20ms to 40ms to complete
each parameter access request (read or write).
5. Once the drive has completed the request, it will place its response in the
parameter number / action response word and data / error code response word:
•= If the request was a read, and the read was performed successfully, this will
be indicated to the master by Resp1:Resp0 changing from 0:0 to 0:1. The
parameter number response (12 bits) will equal the accessed parameter
number, and the resulting data read will be placed in the data / error code
response word.
•= If the request was a write, and the write was performed successfully, this will
be indicated to the master by Resp1:Resp0 changing from 0:0 to 1:0. The
parameter number response (12 bits) will equal the accessed parameter
number, and the data written to the drive will be reflected in the data / error
code response word.
27
•= If an error occurred during the read or write request, this will be indicated to
the master by Resp1:Resp0 changing from 0:0 to 1:1. The parameter
number response (12 bits) will equal the parameter number that the master
was attempting to access, and an error code reflecting the failure cause will
be placed in the data / error code response word. For a list of possible error
codes, refer to section 10.4.
6. In order to perform another parameter read or write, the master must once again
send a “no action” code (Req1=0 and Req0=0), and the drive must once again
respond with an idle state acknowledge (Resp1=0 and Resp0=0) before the next
read or write action can take place. Until a “no action” code is sent to the drive,
the drive will ignore all data in the Parameter number / action word and
Parameter write data word. Also, as long as the master sends the “no action”
code, the drive will loop-back in the parameter number / action response word
and parameter data / error code response word whatever data is sent to it in the
corresponding output words.
28
11. Parameter Registers
How To Use This Section:
This section contains tables which describe all of the parameter registers accessible
from the Profibus network. The descriptions for the columns in the listed tables are
as follows:
Bit .....................This column only applies to read-only registers (section 11.1). If the
register is comprised of a collection of individual bit-oriented status
items (for example, register 0D), this column will indicate which bit(s)
in the word-sized register the corresponding parameter described in
the Function column uses (bit 0 = LSB, bit F = MSB). If the
parameter uses the whole register, "word" will appear in this column,
indicating the parameter consumes the entire register (this does not
mean, however, that all register bits are used: refer to the
explanation for Mask below). All read/write registers (section 11.2)
have word-size data. Other possible values in this column are "low
byte" (bits 0 ∼ 7) and "high byte" (bits 8 ∼ F).
Mask .................The data bits within a register that are not covered by the
hexadecimal mask (for example, bits 8 ∼ F if the mask is 00FF) will
always be returned as 0 during data reads and will be ignored during
data writes. For example, if a hexadecimal value of AB98 is sent to
a register whose mask is 00FF, the actual value written to the
register's corresponding parameter will be 0098. As this is not
considered an error, no exception response will be generated if this
type of extraneous data condition occurs.
Adjustment Range ... Indicates valid data settings in real terms (Hz, ON/OFF, etc.)
Multiplier ...........Indicates scaling factor used to convert Adjustment Range data into
integer values. The equation used for this conversion is:
29
Example Table Excerpt:
•= All register numbers indicated are in hexadecimal notation (for example, 29 hex =
41 decimal). Occasionally, hexadecimal notation in this document may also take
the form of a number beginning with “0x”.
•= Throughout this document, the abbreviations "LL", "UL", and "Fmax" will stand for
LOWER LIMIT FREQUENCY, UPPER LIMIT FREQUENCY, and MAXIMUM
OUTPUT FREQUENCY, respectively.
•= Reading from or writing to registers marked as "Reserved" will generate an
“invalid register” error (error code 0x0003)
•= Certain parameter registers cannot be written to while the inverter is running.
These registers will be indicated by the character (∗). If an attempt is made to
write to these registers while the inverter is running, a “cannot execute” error
(error code 0x0001) will be generated.
•= The parameter register data for all read/write registers with Bank information
listed as 0/1 will be retrieved from bank 0 (RAM) during reads and will be written
to both banks 0 and 1 (RAM and EEPROM) during writes.
•= All parameters in GROUP:COMMUNICATION SETTING PARAMETERS (section
11.2.10) are retrieved by the drive from non-volatile memory upon inverter
initialization only. When any of these registers are modified, therefore, the drive
must be reset for the changed values to take effect.
•= If the COMMAND MODE SELECTION or FREQUENCY MODE SELECTION
parameters are changed while the drive is running, the change will not take effect
until the next time the drive is stopped.
30
11.1 Read-
Read-Only Registers
Register Bit Function Bank Mask Adjustment Range Multiplier
01 ∼ 09 word Reserved
0A word RX terminal analog input 0 FFFF 0000 ~ 7FFF (-100% ~ 0%) 1
value 7FFF ~ FFFF (0% ~ 100%)
0B word Frequency command 0 FFFF 0000 ∼ 9C40 0.01
monitor (0.00 ∼ 400.00 Hz)
0C word Input voltage monitor(Note 1) 0 FFFF 0 ~ 255% 0.1
0D word Output terminal status 0 00FF Refer to Table 4 (page 32)
monitor
0E word Inverter Status 1 0 FFFF Refer to Table 5 (page 32)
0F word Inverter Status 2 0 00FF Refer to Table 6 (page 32)
10 word Present trip 0 00FF
11 high 4th Past trip (most recent) 0 7F00
byte
low 3rd past trip 007F Refer to section 11.3 for fault
byte codes
12 high 2nd past trip 0 7F00
byte
low 1st past trip (oldest) 007F
byte
13 word Pre-compensation output 0 FFFF 0000 ∼ 9C40 0.01
frequency (0.00 ∼ 400.00 Hz)
14 word Post-compensation output 0 FFFF 0000 ∼ 9C40 0.01
frequency (0.00 ∼ 400.00 Hz)
15 word Torque current monitor 0 FFFF (Note 2) 0.01
16 word Excitation current monitor 0 00FF 00 ∼ FF (0 ~ 255%) 1
17 word PID feedback value 0 FFFF (Note 2) 0.02
18 word Motor overload ratio 0 FFFF 0 ~ 65535 100/65535
19 word Inverter overload ratio 0 FFFF 0 ~ 65535 100/65535
1A word DBR overload ratio 0 FFFF 0 ~ 65535 100/65535
1B word Input power (%) 0 FFFF 0 ~ 6553.5 0.1
1C word Input power (kW) 0 FFFF (Note 3)
1D word Output power (%) 0 FFFF (Note 2) 0.1
1E word Output power (kW) 0 FFFF (Note 2, Note 3)
1F, 20 word Reserved
21 word Input / output power units 0 0008 0000: 0.01kW
0008: 0.1kW
22 word Command mode status 0 0003 0000: terminal
0001: panel
0002: option
0003: RS232C
23 word Frequency mode selection 0 000C 0000: terminal
status 0004: panel
0008: option
000C: RS232C
24 low Profibus interface card
byte software revision
high Profibus interface card
byte software version
25 word Output current (amps) FFFF 0.0 ~ 6553.5 A 0.1
(Note 1) These monitor voltage units are not affected by the setting of VOLTAGE UNITS SELECTION in
GROUP:UTILITY PARAMETERS; they are always in units of %.
(Note 2) These registers use signed data (data values larger than 7FFFH are negative). If the register data is
8000H or larger, the actual value can be obtained by: actual value = - [FFFFH - (register data) + 1].
31
(Note 3) If the input / output power units data is 0, the monitored data is in 0.01kW units, and the multiplier is
0.01. If the input / output power units data is 1, the monitored data is in 0.1kW units, and the multiplier
is 0.1. These values are automatically set according to the inverter’s capacity.
32
11.2 Read/Write Registers
33
11.2.2 GROUP:FUNDAMENTAL PARAMETERS #2
34
11.2.4 GROUP:TERMINAL SELECTION PARAMETERS
35
Register Function / Title Bank Mask Adjustment Range Multiplier
60 “OUT” CONTACTS HOLD 0/1 00FF 0001 ∼ 0064 (1 ∼ 100) 1
TIME
61 LOW SPEED SIGNAL 0/1 FFFF 0 ∼ Fmax 0.01
OUTPUT FREQ
62 ACC/DEC COMPLETE 0/1 FFFF 0 ∼ Fmax 0.01
DETECT BAND
63 SPEED REACH MAXIMUM 0/1 FFFF 0 ∼ Fmax 0.01
FREQUENCY
64 SPEED REACH MINIMUM 0/1 FFFF 0 ∼ Fmax 0.01
FREQUENCY
65 COMMERCIAL POWER/INV 0/1 00C0 0000: OFF (0)
SWITCHING OUTPUT 0040: Auto switch on trip (1)
0080: At COMMERCIAL POWER/INV
SWITCH FREQ (2)
00C0: Both (1) and (2) (3)
66 2, 3 COMMERCIAL 0/1 FFFF 0 ∼ Fmax 0.01
POWER/INV
SWITCH FREQ
67 “FP” OUTPUT TERMINAL 0/1 0003 0000: 48f (0)
PULSE FREQUENCY 0001: 96f (1)
0002: 360f (2)
68 RR INPUT SPECIAL 0/1 00E0 0000: Standard (0)
FUNCTION SELECT 0040: Fmax (1)
0080: TACC/TDEC mult. (2)
00C0: VB mult. Factor (3)
0020: CL mult. Factor (4)
36
Table 7: Input Terminal Selections
Setting Data Function Setting Data Function
Value (Hex) Value (Hex)
0 10C8 R (reverse run) 28 04AF Binary bit #6
1 011C SS1 (preset speed selection) 29 08AF Binary bit #7
2 021C SS2 (preset speed selection) 30 10AF Binary bit #8
3 041C SS3 (preset speed selection) 31 20AF Binary bit #9
4 081C SS4 (preset speed selection) 32 40AF Binary bit #10
5 20C8 F (forward run) 33 04CE No effect
6 201B RES (fault reset) 34 01C7 UP/DOWN frequency setting (UP)
7 C0C9 ST (gate ON/OFF) 35 02C7 UP/DOWN frequency setting
(DOWN)
8 0CC8 JOG selection 36 04C7 UP/DOWN frequency clear
9 081A Acc/dec #1/#2 selection 37 08C7 PUSH-type RUN key
10 101B Emergency off 38 10C7 PUSH-type STOP key
11 021B DC injection braking ON/OFF 39 02B9 No effect
12 041B Fundamental parameter 40 C0C8 Forward/reverse run selection
switching (V/F #2)
13 011B Feedback control ON/OFF 41 20C7 RUN
14 10CE Pattern run selection #1 42 30C9 Binary data write
15 20CE Pattern run selection #2 43 0198 [LOCAL/REMOTE] key
16 40CE Pattern run selection #3 44 0298 [MON] key
17 80CE Pattern run selection #4 45 0498 [PRG] key
18 02CE Pattern run continue signal 46 0898 [UP] (▲) key
19 01CE Pattern run step trigger signal 47 1098 [DOWN] (▼) key
20 0AC9 JOG forward run 48 2098 [READ/WRITE] key
21 06C9 JOG reverse run 49 4098 [RUN] key
22 10AE Binary bit #0 50 8098 [STOP/CLEAR] key
23 20AE Binary bit #1 51 08CE Commercial power / inverter
switching signal
24 40AE Binary bit #2 52 40C7 Reserved for option use
25 80AE Binary bit #3 53 10CB RR frequency switching input
26 01AF Binary bit #4 54 20CB IV frequency switching input
27 02AF Binary bit #5
Note: In order for binary bit #0 ∼ #10 (setting values 22 ∼ 32) and UP/DOWN frequency setting (setting values 34 &
35) inputs to be valid, parameter FREQUENCY PRIORITY SELECTION #1 or FREQUENCY PRIORITY
SELECTION #2 in GROUP:FREQUENCY SETTING PARAMETERS must be set to 5 (BIN (binary setting or
UP/DOWN setting)).
37
Table 8: Output Terminal Selections (RCH, LOW, FL, OUT relay contacts)
Setting Data Function Setting Data Function
Value (Hex) Value (Hex)
0 0000 Lower limit frequency 32 C5B7 Executing emergency off
1 0100 /Lower limit frequency 33 CDB7 /Executing emergency off
2 0200 Upper limit frequency 34 B5BB Executing retry
3 0300 /Upper limit frequency 35 BDBB /Executing retry
4 0400 Low speed signal 36 D5CF Pattern run switching output
5 0500 /Low speed signal 37 DDCF /Pattern run switching output
6 0600 Accel/decel complete 38 D5D8 PID deviation limit
7 0700 /Accel/decel complete 39 DDD8 /PID deviation limit
8 0800 Selected speed reach signal 40 C5BB Run/stop
9 0900 /Selected speed reach signal 41 CDBB /Run/stop
10 0A00 Fault 42 1400 Severe fault (armature short, load-
end short, open phase, output
error, earth fault)
11 0B00 /Fault 43 1500 /Severe fault (armature short, load-
end short, open phase, output
error, earth fault)
12 0C00 Fault other than earth fault or 44 1600 Non-severe fault (overload,
load-end overcurrent overcurrent, overvoltage)
13 0D00 /Fault other than earth fault or 45 1700 /Non-severe fault (overload,
load-end overcurrent overcurrent, overvoltage)
14 95B5 Overcurrent pre-alarm 46 E5D8 Commercial power / inverter
switching output #1
15 9DB5 /Overcurrent pre-alarm 47 EDD8 /Commercial power / inverter
switching output #1
16 85C5 Inverter overload pre-alarm 48 F5D8 Commercial power / inverter
switching output #2
17 8DC5 /Inverter overload pre-alarm 49 FDD8 /Commercial power / inverter
switching output #2
18 95C5 Motor overload pre-alarm 50 85C0 Fan ON/OFF
19 9DC5 /Motor overload pre-alarm 51 8DC0 /Fan ON/OFF
20 D5C5 Overheat pre-alarm 52 F5B6 Executing JOG
21 DDC5 /Overheat pre-alarm 53 FDB6 /Executing JOG
22 A5B4 Overvoltage pre-alarm 54 1800 Local/remote operation
23 ADB4 /Overvoltage pre-alarm 55 1900 /Local/remote operation
24 E5B4 Undervoltage alarm 56 A5D1 Cumulative timer alarm
25 EDB4 /Undervoltage alarm 57 ADD1 /Cumulative timer alarm
26 85B5 Undercurrent alarm 58 1A00 Communication error alarm
27 8DB5 /Undercurrent alarm 59 1B00 /Communication error alarm
28 85D1 Overtorque alarm 60 A5B6 F/R
29 8DD1 /Overtorque alarm 61 ADB6 /F/R
30 E5BB Braking resistor OL pre-alarm 62 1E00 Run preparation complete
31 EDBB /Braking resistor OL pre-alarm 63 1F00 /Run preparation complete
38
11.2.5 GROUP:SPECIAL CONTROL PARAMETERS
39
11.2.6 GROUP:FREQUENCY SETTING PARAMETERS
40
Register Function / Title Bank Mask Adjustment Range Multiplier
98 BINARY INPUT STD OR 0/1 0001 0000: Standard (0)
ADJUSTABLE 0001: Adjustable (1)
99 1 BINARY REF 0/1 00FF 0000 ∼ 0064 (0 ∼ 100) 1
SETTING POINT #1
9A BINARY REF POINT 0/1 FFFF -Fmax ∼ Fmax 0.02
#1 FREQUENCY
9B BINARY REF 0/1 00FF 0000 ∼ 0064 (0 ∼ 100) 1
SETTING POINT #2
9C BINARY REF POINT 0/1 FFFF -Fmax ∼ Fmax 0.02
#2 FREQUENCY
9D JOG RUN FREQUENCY 0/1 FFFF 0000 ∼ 07D0 (0.00 ∼ 20.00) 0.01
9E Other JOG STOP 0/1 00C0 0000: Decelerated stop (0)
than 0 METHOD 0040: Coast stop (1)
0080: DC injection stop (2)
9F PRESET SPEED 0/1 000F 0000 ∼ 000F (0 ∼ 15) 1
SELECTION
A0 ∼ FF Reserved
100 Other PRESET SPEED 0/1 0004 0000: Deactivated (0)
than 0 MODE 0004: Activated (1)
ACTIVATION
101 PRESET SPEED 1 FFFF LL ∼ UL 0.01
#1 FREQUENCY
102 PRESET SPEED 1 040C 0004: (0) 1
#1 OPERATING 0000: (1)
MODE
000C: (2)
0008: (3)
0404: (4)
0400: (5)
040C: (6)
0408: (7)
103 2 or PRESET SPEED 1 FFFF LL ∼ UL 0.01
higher #2 FREQUENCY
104 PRESET SPEED 1 040C Same as PRESET SPEED #1 1
#2 OPERATING OPERATING MODE
MODE
105 3 or PRESET SPEED 1 FFFF LL ∼ UL 0.01
higher #3 FREQUENCY
106 PRESET SPEED 1 040C Same as PRESET SPEED #1 1
#3 OPERATING OPERATING MODE
MODE
107 4 or PRESET SPEED 1 FFFF LL ∼ UL 0.01
higher #4 FREQUENCY
108 PRESET SPEED 1 040C Same as PRESET SPEED #1 1
#4 OPERATING OPERATING MODE
MODE
109 5 or PRESET SPEED 1 FFFF LL ∼ UL 0.01
higher #5 FREQUENCY
10A PRESET SPEED 1 040C Same as PRESET SPEED #1 1
#5 OPERATING OPERATING MODE
MODE
10B 6 or PRESET SPEED 1 FFFF LL ∼ UL 0.01
higher #6 FREQUENCY
10C PRESET SPEED 1 040C Same as PRESET SPEED #1 1
#6 OPERATING OPERATING MODE
MODE
10D 7 or PRESET SPEED 1 FFFF LL ∼ UL 0.01
higher #7 FREQUENCY
10E PRESET SPEED 1 040C Same as PRESET SPEED #1 1
#7 OPERATING OPERATING MODE
MODE
41
Register Function / Title Bank Mask Adjustment Range Multiplier
10F 8 or PRESET SPEED 1 FFFF LL ∼ UL 0.01
higher #8 FREQUENCY
110 PRESET SPEED 1 040C Same as PRESET SPEED #1 1
#8 OPERATING OPERATING MODE
MODE
111 9 or PRESET SPEED 1 FFFF LL ∼ UL 0.01
higher #9 FREQUENCY
112 PRESET SPEED 1 040C Same as PRESET SPEED #1 1
#9 OPERATING OPERATING MODE
MODE
113 10 or PRESET SPEED 1 FFFF LL ∼ UL 0.01
higher #10 FREQUENCY
114 PRESET SPEED 1 040C Same as PRESET SPEED #1 1
#10 OPERATING OPERATING MODE
MODE
115 11 or PRESET SPEED 1 FFFF LL ∼ UL 0.01
higher #11 FREQUENCY
116 PRESET SPEED 1 040C Same as PRESET SPEED #1 1
#11 OPERATING OPERATING MODE
MODE
117 12 or PRESET SPEED 1 FFFF LL ∼ UL 0.01
higher #12 FREQUENCY
118 PRESET SPEED 1 040C Same as PRESET SPEED #1 1
#12 OPERATING OPERATING MODE
MODE
119 13 or PRESET SPEED 1 FFFF LL ∼ UL 0.01
higher #13 FREQUENCY
11A PRESET SPEED 1 040C Same as PRESET SPEED #1 1
#13 OPERATING OPERATING MODE
MODE
11B 14 or PRESET SPEED 1 FFFF LL ∼ UL 0.01
higher #14 FREQUENCY
11C PRESET SPEED 1 040C Same as PRESET SPEED #1 1
#14 OPERATING OPERATING MODE
MODE
11D 15 PRESET SPEED 1 FFFF LL ∼ UL 0.01
#15 FREQUENCY
11E PRESET SPEED 1 040C Same as PRESET SPEED #1 1
#15 OPERATING OPERATING MODE
MODE
42
11.2.7 GROUP:PROTECTION FUNCTION PARAMETERS
43
Register Function / Title Bank Mask Adjustment Range Multiplier
135 UNDERVOLTAGE TRIP 0/1 0080 0000: Trip disabled (0)
SELECTION 0080: Trip (during run) (1)
136 UNDERVOLTAGE DETECT 0/1 FFFF 0000 ∼ 03E8 (0.00 ∼ 10.00) 0.01
TIME
137 LOW CURRENT DETECT 0/1 0008 0000: Trip disabled (0)
SELECTION 0008: Trip on detection (1)
138 LOW CURRENT DETECT 0/1 00FF 0000 ∼ 0064 (0 ∼ 100) 1
LEVEL
139 LOW CURRENT DETECTION 0/1 00FF 0000 ∼ 00FF (0 ∼ 255) 1
TIME
140 OUTPUT SHORT-CIRCUIT 0/1 0003 0000: Standard motor (0)
DETECTION SELECT 0001: High-speed motor (1)
0002: Positioning use (standard
motor) (2)
0003: Positioning use (high-speed
motor) (3)
141 OVERTORQUE TRIP 0/1 0040 0000: Trip disabled (0)
SELECTION 0040: Trip enabled (1)
142 OVERTORQUE TRIP LEVEL 0/1 00FF 0000 ∼ 00C8 (0 ∼ 200) 1
143 FAULT TRIP EEPROM 0/1 0002 0000: Data cleared when powered
SAVE ENABLE OFF (0)
0002: Data retained when powered
OFF (1)
144 COOLING FAN CONTROL 0/1 0004 0000: Automatic (temperature
SELECTION detection) (0)
0004: Always ON (1)
145 CUMULATIVE RUN TIMER 0/1 FFFF 0000 ∼ C34B (0.00 ∼ 999.90) 0.02
ALARM SETTING
44
11.2.8 GROUP:PATTERN RUN CONTROL PARAMETERS
45
Register Function / Title Bank Mask Adjustment Range Multiplier
169 PATTERN GROUP #4 1 00FF 0000: Skip (0) 1
SPEED #0
16A PATTERN GROUP #4 0001 ∼ 000F: Speeds 1 ∼ 15
SPEED #1
16B PATTERN GROUP #4
SPEED #2
16C PATTERN GROUP #4
SPEED #3
16D PATTERN GROUP #4
SPEED #4
16E PATTERN GROUP #4
SPEED #5
16F PATTERN GROUP #4
SPEED #6
170 PATTERN GROUP #4
SPEED #7
171 PATTERN GROUP #4 0/1 00FF 0001 ∼ 00FF: 1 ∼ 255 1
NUMBER OF CYCLES
172 SPEED #1 CONTINUE 1 00FF 0000: Count in seconds from time of
MODE activation (0)
0001: Count in minutes from time of
activation (1)
0002: Count in seconds from speed
reach (2)
0003: Count in minutes from speed
reach (3)
0004: Non-stop (continue until
STOP command) (4)
0005: Continue until next step
command (5)
173 <4 SPEED #1 DRIVE 1 FFFF 0000 ∼ 1F40 (0 ∼ 8000) 1
TIME
174 SPEED #2 CONTINUE 1 00FF Same as SPEED #1 CONTINUE
MODE MODE
175 <4 SPEED #2 DRIVE 1 FFFF 0000 ∼ 1F40 (0 ∼ 8000) 1
TIME
176 SPEED #3 CONTINUE 1 00FF Same as SPEED #1 CONTINUE
MODE MODE
177 <4 SPEED #3 DRIVE 1 FFFF 0000 ∼ 1F40 (0 ∼ 8000) 1
TIME
178 SPEED #4 CONTINUE 1 00FF Same as SPEED #1 CONTINUE
MODE MODE
179 <4 SPEED #4 DRIVE 1 FFFF 0000 ∼ 1F40 (0 ∼ 8000) 1
TIME
17A SPEED #5 CONTINUE 1 00FF Same as SPEED #1 CONTINUE
MODE MODE
17B <4 SPEED #5 DRIVE 1 FFFF 0000 ∼ 1F40 (0 ∼ 8000) 1
TIME
17C SPEED #6 CONTINUE 1 00FF Same as SPEED #1 CONTINUE
MODE MODE
17D <4 SPEED #6 DRIVE 1 FFFF 0000 ∼ 1F40 (0 ∼ 8000) 1
TIME
17E SPEED #7 CONTINUE 1 00FF Same as SPEED #1 CONTINUE
MODE MODE
17F <4 SPEED #7 DRIVE 1 FFFF 0000 ∼ 1F40 (0 ∼ 8000) 1
TIME
180 SPEED #8 CONTINUE 1 00FF Same as SPEED #1 CONTINUE
MODE MODE
181 <4 SPEED #8 DRIVE 1 FFFF 0000 ∼ 1F40 (0 ∼ 8000) 1
TIME
46
Register Function / Title Bank Mask Adjustment Range Multiplier
182 SPEED #9 CONTINUE 1 00FF Same as SPEED #1 CONTINUE
MODE MODE
183 <4 SPEED #9 DRIVE 1 FFFF 0000 ∼ 1F40 (0 ∼ 8000) 1
TIME
184 SPEED #10 CONTINUE 1 00FF Same as SPEED #1 CONTINUE
MODE MODE
185 <4 SPEED #10 1 FFFF 0000 ∼ 1F40 (0 ∼ 8000) 1
DRIVE TIME
186 SPEED #11 CONTINUE 1 00FF Same as SPEED #1 CONTINUE
MODE MODE
187 <4 SPEED #11 1 FFFF 0000 ∼ 1F40 (0 ∼ 8000) 1
DRIVE TIME
188 SPEED #12 CONTINUE 1 00FF Same as SPEED #1 CONTINUE
MODE MODE
189 <4 SPEED #12 1 FFFF 0000 ∼ 1F40 (0 ∼ 8000) 1
DRIVE TIME
18A SPEED #13 CONTINUE 1 00FF Same as SPEED #1 CONTINUE
MODE MODE
18B <4 SPEED #13 1 FFFF 0000 ∼ 1F40 (0 ∼ 8000) 1
DRIVE TIME
18C SPEED #14 CONTINUE 1 00FF Same as SPEED #1 CONTINUE
MODE MODE
18D <4 SPEED #14 1 FFFF 0000 ∼ 1F40 (0 ∼ 8000) 1
DRIVE TIME
18E SPEED #15 CONTINUE 1 00FF Same as SPEED #1 CONTINUE
MODE MODE
18F <4 SPEED #15 1 FFFF 0000 ∼ 1F40 (0 ∼ 8000) 1
DRIVE TIME
47
11.2.9 GROUP:FEEDBACK CONTROL PARAMET
PARAMETERS
ERS
48
11.2.10 GROUP:COMMUNICATION SETTING PARAMETERS
Note 1: Although the INVERTER ID NUMBER parameter can be set from 0 to 255, the allowable Profibus slave
addresses range only from 0 to 125. Therefore, if this parameter is set to a value from 126 to 255, the
Profibus interface card will trip “OPTION PCB ERROR” upon initialization.
49
Register Function / Title Bank Mask Adjustment Range Multiplier
211 TOSLINE-S20 COMM 1 0002 0000: Data cleared (0) 1
ERROR MODE 0002: Data retained (1)
212 TOSLINE-S20 COMM 1 0004 0000: No effect (0) 1
OPTION RESET 0004: Reset (1)
213 RS485/12-BIT BINARY 0/1 0020 0000: OFF (0)
BIAS,GAIN 0020: ON (1)
214 1 RS485/12-BIT 0/1 00FF 0000 ∼ 0064 (0 ∼ 100) 1
BINARY POINT #1
215 RS485/12-BIT 0/1 FFFF 0000 ∼ Fmax (0 ∼ Fmax) 0.01
BINARY PT. #1
FREQ
216 RS485/12-BIT 0/1 00FF 0000 ∼ 0064 (0 ∼ 100) 1
BINARY POINT #2
217 RS485/12-BIT 0/1 FFFF 0000 ∼ Fmax (0 ∼ Fmax) 0.01
BINARY PT. #2
FREQ
50
11.2.12 GROUP:UTILITY
GROUP:UTILITY PARAMETERS
51
Register Function / Title Bank Mask Adjustment Range Multiplier
22D ACC/DEC TIME UNITS 0/1 0004 0000: 0.1 sec. (0)
SELECTION 0004: 0.01 sec. (1)
22E CURRENT UNITS 0/1 0008 0000: % (0)
SELECTION 0008: A (1)
22F VOLTAGE UNITS 0/1 0010 0000: % (0)
SELECTION 0010: V (1)
230 BLIND FUNCTION 0/1 0001 0000: Blind (0)
SELECTION 0001: Selective unblinding (1)
231 1 FUNDAMENTAL 0/1 0040 0000: Blind (0)
PARAMS #2 BLIND 0040: Unblind (1)
232 PANEL CONTROL 0/1 0080 0000: Blind (0)
PARAMS BLIND 0080: Unblind (1)
233 TERMINAL 0/1 0001 0000: Blind (0)
SELECTION PARAMS 0001: Unblind (1)
BLIND
234 SPECIAL CONTROL 0/1 0002 0000: Blind (0)
PARAMS BLIND 0002: Unblind (1)
235 FREQUENCY SETTING 0/1 0004 0000: Blind (0)
PARAMS BLIND 0004: Unblind (1)
236 PROTECTION 0/1 0008 0000: Blind (0)
FUNCTION PARAMS 0008: Unblind (1)
BLIND
237 PATTERN RUN 0/1 0010 0000: Blind (0)
CONTROL PARAMS 0010: Unblind (1)
BLIND
238 FEEDBACK CONTROL 0/1 0020 0000: Blind (0)
PARAMS BLIND 0020: Unblind (1)
239 COMMUNICATION 0/1 0040 0000: Blind (0)
PARAMS BLIND 0040: Unblind (1)
23A INDUSTRIAL 0/1 0080 0000: Blind (0)
APPL:PUMP PARAMS 0080: Unblind (1)
BLIND
23B INDUSTRIAL 0/1 0001 0000: Blind (0)
APPL:FAN PARAMS 0001: Unblind (1)
BLIND
23C INDUSTRIAL APPL: 0/1 0002 0000: Blind (0)
CONVEYOR BLIND 0002: Unblind (1)
23D INDUSTRIAL APPL: 0/1 0004 0000: Blind (0)
HOIST BLIND 0004: Unblind (1)
23E INDUSTRIAL APPL: 0/1 0008 0000: Blind (0)
TEXTILES BLIND 0008: Unblind (1)
23F INDUST 0/1 0010 0000: Blind (0)
APPL:MACHINE 0010: Unblind (1)
TOOLS BLIND
240 AM/FM ADJUSTMENT 0/1 0001 0000: Blind (0)
PARAMS BLIND 0001: Unblind (1)
241 MOTOR PARAMETERS 0/1 0004 0000: Blind (0)
BLIND 0004: Unblind (1)
52
11.2.13 GROUP:MOTOR RATING PARAMETERS
53
Table 9: Inverter Typeform Codes
Note: Due to the continual capacity expansion of the Toshiba adjustable speed drive
family, newly-released drive models may have typeform data which is not
documented in this table. If you encounter this situation, please contact
Toshiba International Corporation for verification of your model’s typeform
data.
54
11.3 Inverter Fault Codes
55
LCD Display Message Data Explanation
(Hex)
CURRENT DETECT ERROR ××1A Output current detection circuit error
(PRESS CLEAR)
OPTION PCB ERROR ××1B Option PCB error
(PRESS CLEAR)
OPTION ROM ERROR ××1C Option ROM error
LOW CURRENT TRIP ××1D Low current
(PRESS CLEAR)
UNDERVOLTAGE TRIP ××1E Main circuit undervoltage
(PRESS CLEAR)
××1F Unused
OVERTORQUE TRIP ××20 Overtorque
(PRESS CLEAR)
EARTH FAULT (SOFT) ××21 Earth fault (software)
(PRESS CLEAR)
EARTH FAULT (HARD) ××22 Earth fault (hardware)
(PRESS CLEAR)
OPEN FUSE TRIP ××23 Open fuse
(PRESS CLEAR)
DBR OVERCURRENT TRIP ××24 Dynamic braking resistor overcurrent
(PRESS CLEAR)
DC OVERCURRENT (ACC) ××25 Overcurrent in DC section during acceleration
(PRESS CLEAR)
DC OVERCURRENT (DEC) ××26 Overcurrent in DC section during deceleration
(PRESS CLEAR)
DC OVERCURRENT (RUN) ××27 Overcurrent in DC section during constant-speed run
(PRESS CLEAR)
AUTO-TUNING ERROR ××28 Auto-tuning error
(PRESS CLEAR)
INV TYPEFORM ERROR ××29 Inverter typeform error
(PRESS READ/WRITE)
56
12. GSD File
The following is a copy of the G3 Profibus interface card’s GSD file, which is used for
network commissioning and administration. An electronic version of this file can be
downloaded via the internet from http://www.iccdesigns.com.
;============================================================
; GSD File for Toshiba 3-series adjustable speed drive ;
; ;
; Toshiba International Corporation ;
; 13131 W. Little York Rd. ;
; Houston, TX 77041 ;
; (713) 466-0277 ;
; ;
; INV3-PROFIBUS ;
; File name: ICC087B.GSD ;
;============================================================
; Rev. 1 11.30.98 DH Initial file entry ;
;============================================================
;
#Profibus_DP
; Unit Definition List:
GSD_Revision = 1
Vendor_Name = "TOSHIBA"
Model_Name = "G3/VFA5 Inverter Interface"
Revision = "Rev. 1"
Ident_Number = 0x087B
Protocol_Ident = 0
Station_Type = 0
FMS_supp = 0
Hardware_Release = "Rev. A"
Software_Release = "Ver. 1.0"
;
9.6_supp = 1
19.2_supp = 1
93.75_supp = 1
187.5_supp = 1
500_supp = 1
1.5M_supp = 1
3M_supp = 1
6M_supp = 1
12M_supp = 1
;
MaxTsdr_9.6 = 60
MaxTsdr_19.2 = 60
MaxTsdr_93.75 = 60
MaxTsdr_187.5 = 60
MaxTsdr_500 = 100
MaxTsdr_1.5M = 150
MaxTsdr_3M = 250
MaxTsdr_6M = 450
MaxTsdr_12M = 800
;
Redundancy = 0
Repeater_Ctrl_Sig = 2
;
; Slave Specification:
24V_Pins = 0
;
Implementation_Type = "SPC3"
Freeze_Mode_supp = 1
57
Sync_Mode_supp = 1
Auto_Baud_supp = 1
Set_Slave_Add_supp = 1
Min_Slave_Intervall = 1
;
Modular_Station = 0
Max_Module = 1
Max_Input_Len = 16
Max_Output_Len = 8
Max_Data_Len = 24
;
; Module Definition:
Max_Diag_Data_Len = 8
Slave_Family = 0
OrderNumber = "INV3-PROFIBUS"
Module = "Toshiba ASD:5w2b2w In, 2w2w Out" 0x54,0x11,0xD1,0x61,0xE1
EndModule
58
13. Notes
59
60
TOSHIBA INTERNATIONAL CORPORATION
INDUSTRIAL DIVISION
13131 W est Little York Rd., Houston, TX 77041
Tel: [800] 231-1412 Fax: [713] 466-8773 Telex: 762078
W orld W ide W eb http://www.tic.toshiba.com
Printed in U.S.A