FR-E800 Instruction Manual (Function)
FR-E800 Instruction Manual (Function)
INVERTER
FR-E800
FR-E800
Instruction Manual (Function)
Compact, high functionality inverters
FR-E820-0008(0.1K) to 0330(7.5K)
FR-E840-0016(0.4K) to 0170(7.5K)
FR-E860-0017(0.75K) to 0120(7.5K)
FR-E820-0008(0.1K) to 0330(7.5K)-E
FR-E840-0016(0.4K) to 0170(7.5K)-E
FR-E860-0017(0.75K) to 0120(7.5K)-E
HEAD OFFICE: TOKYO BUILDING 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
CONTENTS
Chapter 2 Basic Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
2.5.1 Setting the frequency on the operation panel (example: operating at 30 Hz) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
2.5.2 Setting the frequency with switches (multi-speed setting) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
2.5.3 Setting the frequency using an analog signal (voltage input) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
2.5.4 Setting the frequency using an analog signal (current input) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
2.7.1 Giving a start command by using external signals for JOG operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
2.7.2 Giving a start command from the operation panel for JOG operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Chapter 3 Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
1
3.2 Use of a function group number for the identification of parameters . . . . . . . . . . . . . . . . . . . . 73
5.4 Performing high-accuracy, fast-response control (gain adjustment for Real sensorless vector
control and PM sensorless vector control) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
6.2 Setting procedure of Real sensorless vector control (torque control) . . . . . . . . . . . . . . . . . . 116
2
Chapter 7 (E) Environment Setting Parameters . . . . . . . . . . . . 126
CONTENTS
7.4 Frequency change increment amount setting (standard model) . . . . . . . . . . . . . . . . . . . . . . 132
3
8.6 Shortest acceleration/deceleration (automatic acceleration/deceleration) . . . . . . . . . . . . . . . 171
9.3 Start command source and frequency command source during communication operation. . 185
4
Chapter 11 (M) Item and Output Signal for Monitoring . . . . . . . 226
11.1 Speed indication and its setting change to rotations per minute . . . . . . . . . . . . . . . . . . . . . . 226
CONTENTS
11.4 Adjustment of terminal FM and terminal AM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 241
12.5 Torque (magnetic flux) setting current (voltage) bias and gain . . . . . . . . . . . . . . . . . . . . . . . 278
12.8 Selecting the condition to activate the Second function selection (RT) signal. . . . . . . . . . . . 289
5
Chapter 13 (C) Motor Constant Parameters. . . . . . . . . . . . . . . . 294
13.3 Offline auto tuning for a PM motor (motor constant tuning) . . . . . . . . . . . . . . . . . . . . . . . . . . 308
14.7 Automatic restart after instantaneous power failure / flying start with an induction motor . . . 351
14.8 Automatic restart after instantaneous power failure / flying start with a PM motor. . . . . . . . . 356
6
15.4 Energy saving control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 380
CONTENTS
15.8 Regenerative brake selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 386
17.1 For customers replacing the conventional model with this inverter . . . . . . . . . . . . . . . . . . . . 402
17.2 Specification comparison between PM sensorless vector control and induction motor control. .
405
17.3 Parameters (functions) and instruction codes under different control methods. . . . . . . . . . . 406
7
8
CHAPTER 1
CHAPTER 1 Introduction
4
10
9
1 Introduction
The contents described in this chapter must be read before using this product.
Always read the instructions before use.
Abbreviations
Item Description
PU Operation panel
Inverter Mitsubishi Electric inverter FR-E800 series
Pr. Parameter number (Number assigned to function)
PU operation Operation using the PU (operation panel)
External operation Operation using the control circuit signals
Combined operation Combined operation using the PU (operation panel) and External operation
Mitsubishi Electric standard
SF-JR
efficiency motor
Mitsubishi Electric constant-
SF-HRCA
torque motor
Mitsubishi Electric premium
SF-PR
efficiency motor
Trademarks
• Ethernet is a registered trademark of Fuji Xerox Corporation in Japan.
• MODBUS is a registered trademark of SCHNEIDER ELECTRIC USA, INC.
• BACnet is a registered trademark of the American Society of Heating, Refrigerating and Air-Conditioning Engineers
(ASHRAE).
• EtherNet/IP is a registered trademark of ODVA (Open DeviceNet Vendor Association, INC).
• PROFINET is a trademark of PROFIBUS Nutzerorganisation e.V. (PNO).
• Other company and product names herein are the trademarks and registered trademarks of their respective owners.
10 1. Introduction
1.1 Inverter model 1
Check the rating plate on the side of the product. Some characters in the model name indicate the specification as follows.
2
FR-E8 0- 3
A B C D E
4
Rating plate
Inverter model MODEL :FR-E820-0008-1 5
Input rating INPUT :XXXXX
8
• A: The voltage class is shown.
Symbol Voltage class 9
2 200 V class
4 400 V class
6 575 V class 10
• B: The inverter rated capacity or the inverter rated current is shown.
Symbol Voltage class
0.1K to 7.5K Inverter ND rated capacity (kW)
0008 to 0330 Inverter ND rated current (A)
• C: The communication type and the functional safety specification are shown.
Symbol Communication / functional safety
None Standard model (RS-485 + SIL2/PLd)
E Ethernet model (Ethernet + SIL2/PLd)
• D: The output specification for monitoring and the rated frequency are shown for the standard model, and the
communication protocol group is shown for the Ethernet model.
Symbol Monitor output / rated frequency / communication protocol
-1 Pulse (terminal FM), 60 Hz
-4 Voltage (terminal AM), 50 Hz
-5 Voltage (terminal AM), 60 Hz
PA Protocol group A (CC-Link IE TSN, CC-Link IE Field Network Basic, MODBUS/TCP, EtherNet/IP, and BACnet/IP)
PB Protocol group B (CC-Link IE TSN, CC-Link IE Field Network Basic, MODBUS/TCP, PROFINET)
• E: Availability of circuit board coating / plated conductors is shown.
Symbol Circuit board coating*1 Plated conductor
None Without coating Without plated conductors
-60 With coating Without plated conductors
1. Introduction
1.1 Inverter model
11
How to read the SERIAL number
The SERIAL consists of two symbols, three characters indicating the production year
Rating plate example
and month, and six characters indicating the control number.
Symbol Year Month Control number The last digit of the production year is indicated as the Year, and the Month is
SERIAL indicated by 1 to 9, X (October), Y (November), or Z (December).
12 1. Introduction
1.1 Inverter model
1.2 Operation steps 1
Installation/mounting
Inverter
output 3
frequency Wiring of the power
supply and motor
(b)
(Hz) Time
Start command ON (S)
Control mode selection (c) 4
How Start command via the PU/Ethernet
How
o
connector of the inverter and plug-in
to
to give
e aa start
give
command?
command?
m
start
option (Communication)
Initial setting for the Ethernet model
(d) 5
Connect a switch, relay, etc.
6
Start command with to the control circuit
on the operation panel (PU) terminal block of the inverter
to give a start command. (External)
Initial setting for the standard model
give
How
How w to
to
give aa frequency
frequency
re How
How w to
to
7
command?
command?
m give
give aa frequency
frequency
re
command?
command?
m
Set from the operation Change frequency Perform frequency setting Perform frequency setting
8
panel with ON/OFF switches by a voltage output device by a current output device
connected to terminals (Connection across (Connection across
(multi-speed setting) terminals 2 and 5) terminals 4 and 5)
(PU) (External) (External) (External) 9
(e) (f) (g) (h)
Set from the operation Change of frequency Perform frequency setting Perform frequency setting 10
panel with ON/OFF switches by a voltage output device by a current output device
connected to terminals (Connection across (Connection across
(multi-speed setting) terminals 2 and 5) terminals 4 and 5)
(PU) (External) (External) (External)
(i) (j) (k) (l)
1. Introduction
1.2 Operation steps
13
Symbol Overview Refer to page
Instruction Manual
(a) Install the inverter.
(Connection)
Instruction Manual
(b) Perform wiring for the power supply and the motor.
(Connection)
Select the control method (V/F control, Advanced magnetic flux vector control, Real sensorless vector control,
(c) 84
and PM sensorless vector control).
Instruction Manual
(d) Give the start command via communication.
(Communication)
(e) Give both the start and frequency commands from the PU. (PU operation mode) 33
Give the start command from the PU and the frequency command via terminals RH, RM, and RL. (External/
(f) 34
PU combined operation mode 2)
Give the start command from the PU and the frequency command by voltage input via terminal 2. (External/
(g) 35
PU combined operation mode 2)
Give the start command from the PU and the frequency command by current input via terminal 4. (External/
(h) 36
PU combined operation mode 2)
Give the start command via terminal STF or STR and the frequency command from the PU. (External/PU
(i) 38
combined operation mode 1)
Give the start command via terminal STF or STR and the frequency command via terminals RH, RM, and RL.
(j) 39
(External operation mode)
Give the start command via terminal STF or STR and the frequency command by voltage input via terminal 2.
(k) 40
(External operation mode)
Give the start command via terminal STF or STR and the frequency command by current input via terminal 4.
(l) 42
(External operation mode)
14 1. Introduction
1.2 Operation steps
1.3 About the related manuals 1
10
1. Introduction
1.3 About the related manuals
15
MEMO
16 1. Introduction
1.3 About the related manuals
CHAPTER 2
CHAPTER 2 Basic Operation
4
10
17
2 Basic Operation
This chapter explains the basic operation of this product.
Always read the instructions before use.
18 2. Basic Operation
2.1 Operation panel
1
(e)
3
(f)
(g)
4
(i)
(j) (h)
(k)
5
10
2. Basic Operation
2.1 Operation panel
19
No. Appearance Name Description
Shows a numeric value (readout) of a monitor item such as the frequency or a parameter
Monitor (4-digit
(a) number.
LED)
(The monitor item can be changed according to the settings of Pr.52, Pr.774 to Pr.776.)
Hz: ON when the actual frequency is monitored. (Blinks when the set frequency is monitored.)
(b) Unit indication A: ON when the current is monitored.
(Both "Hz" and "A" are OFF to indicate a value other than the frequency or the current.
PU: ON when the inverter is in the PU operation mode.
Inverter operation EXT: ON when the inverter is in the External operation mode. (ON when the inverter in the initial
(c) mode LED setting is powered ON.)
indicator NET: ON when the inverter is in the Network operation mode.
PU and EXT: ON when the inverter is in the External/PU combined operation mode 1 or 2.
Operation panel MON: ON or blinks only when the first, second, or third monitor is displayed.
(d) mode LED PRM: ON when the operation panel is in the parameter setting mode. The indicator blinks when
indicator the inverter is in the easy setting mode.
ON or blinks during inverter running.
Operating status ON: During forward rotation operation.
(e) Blinks slowly (1.4-second cycle): During reverse rotation operation.
indicator
Blinks quickly (0.2-second cycle): Operation is disabled although the start command is given.*1
ON when the inverter is set to control the PM motor.
Controlled motor
(f) The indicator blinks during test operation. The indicator is OFF when the inverter controls the
type LED indicator
induction motor.
PLC function LED
(g) ON when the PLC function of the inverter is valid.
indicator
The setting dial of the Mitsubishi Electric inverters. Turn the setting dial to change the setting
of frequency or parameter, etc.
Press the setting dial to perform the following operations:
(h) Setting dial
• To display a set frequency on the LED display in the monitor mode. (The monitor item shown
on the display can be changed by using Pr.992.)
• To display the present setting during calibration.
Switches between the PU operation mode, the PUJOG operation mode, and the External
operation mode.
(i) PU/EXT key The easy setting of the inverter operation mode is enabled by pressing this key simultaneously
with the MODE key.
Also cancels the PU stop warning.
Switches the operation panel to a different mode.
The easy setting of the inverter operation mode is enabled by pressing this key simultaneously
(j) MODE key with the PU/EXT key.
Every key on the operation panel becomes inoperable by holding this key for 2 seconds. The
key inoperable function is invalid when Pr.161 = "0 (initial setting)". (Refer to page 130.)
Confirms each selection. Initial setting in the monitor mode
When this key is pressed during inverter operation, Output Output Output
(k) SET key the monitor item changes. frequency current voltage
(The monitor item on each screen can be changed
according to the settings of Pr.52, Pr.774 to Pr.776.)
Start command
(l) RUN key
The direction of motor rotation depends on the Pr.40 setting.
Stops the operation commands.
(m) STOP/RESET key
Used to reset the inverter when the protective function is activated.
*1 Situations such as when the MRS/X10 signal is input, during the automatic restart after instantaneous power failure, after auto tuning is complete,
when "SE" (incorrect parameter setting) alarm occurs.
20 2. Basic Operation
2.1 Operation panel
Ethernet model
(a) (b) (c) (d)
1
(e)
(f) 2
(g)
(i)
(j) (h)
3
(k)
4
(o) (l) (m) (n)
10
2. Basic Operation
2.1 Operation panel
21
No. Appearance Name Description
Shows a numeric value (readout) of a monitor item such as the frequency or a parameter
Monitor (4-digit
(a) number.
LED)
(The monitor item can be changed according to the settings of Pr.52, Pr.774 to Pr.776.)
Hz: ON when the actual frequency is monitored. (Blinks when the set frequency is monitored.)
(b) Unit indication A: ON when the current is monitored.
(Both "Hz" and "A" are OFF to indicate a value other than the frequency or the current.
PU: ON when the inverter is in the PU operation mode.
Inverter operation EXT: ON when the inverter is in the External operation mode. (ON when the inverter in the initial
(c) mode LED setting is powered ON.)
indicator NET: ON when the inverter is in the Network operation mode.
PU and EXT: ON when the inverter is in the External/PU combined operation mode 1 or 2.
Operation panel MON: ON or blinks only when the first, second, or third monitor is displayed.
(d) mode LED PRM: ON when the operation panel is in the parameter setting mode. The indicator blinks when
indicator the inverter is in the easy setting mode.
ON or blinks during inverter running.
Operating status ON: During forward rotation operation.
(e) Blinks slowly (1.4-second cycle): During reverse rotation operation.
indicator
Blinks quickly (0.2-second cycle): Operation is disabled although the start command is given.*1
ON when the inverter is set to control the PM motor.
Controlled motor
(f) The indicator blinks during test operation. The indicator is OFF when the inverter controls the
type LED indicator
induction motor.
PLC function LED
(g) ON when the PLC function of the inverter is valid.
indicator
Ethernet
Indicates the Ethernet communication status. For details, refer to the Instruction Manual
(h) communication
(Communication).
status
Switches between the PU operation mode, the PUJOG operation mode, and the External
operation mode.
(i) PU/EXT key The easy setting of the inverter operation mode is enabled by pressing this key simultaneously
with the MODE key.
Also cancels the PU stop warning.
Switches the operation panel to a different mode.
The easy setting of the inverter operation mode is enabled by pressing this key simultaneously
(j) MODE key with the PU/EXT key.
Every key on the operation panel becomes inoperable by holding this key for 2 seconds. The
key inoperable function is invalid when Pr.161 = "0 (initial setting)". (Refer to page 130.)
Confirms each selection. Initial setting in the monitor mode
When this key is pressed during inverter operation, Output Output Output
(k) SET key the monitor item changes. frequency current voltage
(The monitor item on each screen can be changed
according to the settings of Pr.52, Pr.774 to Pr.776.)
Start command
(l) RUN key
The direction of motor rotation depends on the Pr.40 setting.
Stops the operation commands.
(m) STOP/RESET key
Used to reset the inverter when the protective function is activated.
*1 Situations such as when the MRS/X10 signal is input, during the automatic restart after instantaneous power failure, after auto tuning is complete,
when "SE" (incorrect parameter setting) alarm occurs.
22 2. Basic Operation
2.1 Operation panel
2.1.2 Basic operation of the operation panel
1
Basic operation (standard model)
Operation mode switchover/Frequency setting
2
External operation mode*1(displayed at power-ON) PU operation mode*1 PU Jog operation mode*1
3
Blinking
4
Change the setting.
Frequency setting written and complete
5
Monitor
7
Parameter setting
PU operation mode
8
Blinking
Parameter clear All parameter clear Fault history clear Initial value change list
10
2. Basic Operation
2.1 Operation panel
23
Basic operation (Ethernet model)
Operation mode switchover/Frequency setting
Network operation mode*1 (at power-ON) PU operation mode*1 PU Jog operation mode*1
Blinking
PU operation mode
Blinking
Parameter clear All parameter clear Fault history clear Initial value change list
24 2. Basic Operation
2.1 Operation panel
The following table explains the indications in the parameter setting mode.
10
Q R S T U V W X Y Z - _
2. Basic Operation
2.1 Operation panel
25
Parameter setting screen
Blinking
Hold down
For a 4-digit
parameter
number
NOTE
• If a parameter write condition is not satisfied, a parameter write error appears on the LCD display. (For details of the errors,
refer to the Instruction Manual (Maintenance).)
Calibration error
• When Pr.77 Parameter write selection = "0 (initial setting)," the parameter setting change is only available while the inverter
is stopped and under the PU operation mode. To enable the parameter setting change while the inverter is running or under
the operation mode other than PU operation mode, change the Pr.77 setting. (Refer to page 135.)
26 2. Basic Operation
2.1 Operation panel
2.2 Monitoring the inverter 1
• Press the SET key on the operation panel in the monitor mode to switch the monitor item between output frequency, output 3
current, and output voltage.
4
Operating procedure
1. Press the MODE key during inverter operation to monitor the output frequency. The [Hz] LED turns ON. 5
2. Press the SET key to monitor the output current. This operation is valid during running or stopping under any
operation mode. The [A] LED turns ON.
6
3. Press the SET key to monitor the output voltage. Unit LEDs are both OFF.
NOTE
• Other monitor item, such as output power or set frequency, is also available. Use Pr.52 Operation panel main monitor 7
selection or Pr.774 Operation panel monitor selection 1 to Pr.776 Operation panel monitor selection 3 to change the
setting. (Refer to page 228.)
8
2.2.2 First priority monitor screen
The first priority monitor screen, which is displayed first when the operation panel becomes in the monitor mode, is selectable.
9
To set it, press the SET key for a while when the desired monitor item is displayed on a monitor screen.
The following show the procedure to set the monitor screen displaying the output current as the first priority monitor screen.
10
Operating procedure
1. Change the mode of the operation panel to the monitor mode, and switch the monitor screen to the one on which
the output current can be monitored.
2. Press the SET key for a while (1 second). The output current monitor screen is set as the first priority monitor screen.
3. When the operation panel is in the monitor mode next time, the output current monitored value is displayed first.
NOTE
• Use Pr.52 Operation panel main monitor selection or Pr.774 Operation panel monitor selection 1 to Pr.776 Operation
panel monitor selection 3 to change the monitor item. (Refer to page 228.)
press the setting dial ( ) while the inverter runs in the PU operation mode or in the External/PU combined operation mode
NOTE
• Use Pr.992 Operation panel setting dial push monitor selection to change the item to be displayed. (Refer to page 228.)
2. Basic Operation
2.2 Monitoring the inverter
27
2.3 Easy setting of the inverter operation mode
The operation mode suitable for start and speed command combinations can be set easily using Pr.79 Operation mode
selection.
The following shows the procedure to operate with the external start command (STF/STR) and the frequency command by
using the operation panel.
Operating procedure
1. Press the PU/EXT key and MODE key for 0.5 second at the same time.
Blinking
2. Turn the setting dial or press the UP/DOWN key until "79-3" (External/PU combined operation mode 1) appears.
(For other settings, refer to the following table.)
Blinking
3. Press the SET key to confirm the setting. External/PU combined operation mode 1 (Pr.79 = "3") is set.
Operation method
Operation panel indication Frequency Operation mode
Start command
command
Analog voltage
Blinking RUN key External/PU combined operation mode 2
input
NOTE
• When the user group function is used (Pr.160 = "1") or the password function is enabled (with Pr.296 and Pr.297), the easy
setting is disabled (Pr.79 is not displayed).
• "ER2" appears if a setting change is attempted during inverter operation. Turn OFF the start command (the RUN key or STF/
STR signal).
• If the MODE key is pressed before pressing the SET key, the easy setting mode is terminated and the operation panel returns
to the monitor mode. If the easy setting is terminated while Pr.79 = "0 (initial value)", check the inverter operation mode
because the inverter may switch its operation mode between the PU operation mode and the External operation mode.
• Reset by pressing the STOP/RESET key is enabled.
• The following is the frequency commands listed in descending order of priority when "3" is set in Pr.79: Multi-speed setting
function (RL/RM/RH/REX signal) > PID control (X14 signal) > terminal 4 analog input (AU signal) > digital input from the
operation panel.
28 2. Basic Operation
2.3 Easy setting of the inverter operation mode
2.4 Frequently-used parameters (simple mode 1
parameters)
2
Parameters that are frequently used for the FR-E800 series are grouped as simple mode parameters.
When Pr.160 User group read selection = "9999", only the simple mode parameters are displayed on the operation panel.
This section explains the simple mode parameters. 3
2.4.1 Simple mode parameter list
For simple variable-speed operation of the inverter, the initial values of the parameters may be used as they are. Set the 4
necessary parameters to meet the load and operational specifications. Parameter's setting, change and check can be made
on the operation panel.
5
• Pr.160 User group read selection can narrow down the displayed parameters to only the simple mode parameters. (In the
initial setting, all parameters are displayed.) Set Pr.160 User group read selection as required. (To change the parameter
setting, refer to page 25.) 6
9999
Pr.160 setting Description
Only simple mode parameters are displayed.
7
All parameters (simple mode parameters and extended parameters)
0 (initial value)
are displayed.
1 Only parameters registered in user groups are displayed. 8
10
2. Basic Operation
2.4 Frequently-used parameters (simple mode parameters)
29
Simple mode parameters (standard model)
Initial value*9 Refer
Pr.
Pr. Name Increment Range Application to
group Gr.1 Gr.2 page
6%*1
Set this parameter to obtain a higher starting
5%*2 torque under V/F control. Also set this when a
0 G000 Torque boost 0.1% 4%*3 0% to 30% loaded motor cannot be driven, the warning 374
"OL" occurs, and the inverter output is shut off
3%*4
with the fault indication "E.OC1".
2%*5
Maximum
1 H400 0.01 Hz 120 Hz 0 to 120 Hz Set the upper limit for the output frequency.
frequency
211
Minimum
2 H401 0.01 Hz 0 Hz 0 to 120 Hz Set the lower limit for the output frequency.
frequency
Set this parameter when the rated motor
3 G001 Base frequency 0.01 Hz 60 Hz 50 Hz 0 to 590 Hz frequency is 50 Hz. Check the rating plate of 376
the motor.
Multi-speed
4 D301 setting (high 0.01 Hz 60 Hz 50 Hz 0 to 590 Hz
speed)
34,
Multi-speed Pre-set the speeds that will be switched
39,
5 D302 setting (middle 0.01 Hz 30 Hz 0 to 590 Hz among by terminals.
195
speed)
Multi-speed
6 D303 0.01 Hz 10 Hz 0 to 590 Hz
setting (low speed)
5 s*6
7 F010 Acceleration time 0.1 s 0 to 3600 s Set the acceleration time.
10 s*7
158
5 s*6
8 F011 Deceleration time 0.1 s 0 to 3600 s Set the deceleration time.
10 s*7
H000 Electronic thermal Inverter rated Protects the motor from heat. Set the rated
9 0.01 A 0 to 500 A 198
C103 O/L relay current*8 motor current.
Operation mode Select the start and frequency command
79 D000 1 0 0 to 4, 6, 7 174
selection sources.
Terminal 2 Change the frequency at the maximum
41,
125 T022 frequency setting 0.01 Hz 60 Hz 50 Hz 0 to 590 Hz potentiometer setting (5 V in the initial
273
gain frequency setting).
Terminal 4
Change the frequency at the maximum 43,
126 T042 frequency setting 0.01 Hz 60 Hz 50 Hz 0 to 590 Hz
current input (20 mA in the initial setting). 273
gain frequency
This function restricts the parameters that are
User group read
160 E440 1 0 0, 1, 9999 read by the operation panel and parameter 143
selection
unit.
0, 8009, Select the PM sensorless vector control and
PM parameter
998 E430 1 0 8109, 9009, set the parameters that are required to drive a 90
initialization
9109 PM motor.
Changes parameter settings as a batch. The
target parameters include communication
Automatic 10, 12, 20, parameters for the Mitsubishi Electric human
999 E431 1 9999 141
parameter setting 21, 9999 machine interface (GOT) connection and the
parameters for the rated frequency settings of
50/60 Hz.
*1 Initial value for the FR-E820-0050(0.75K) or lower and FR-E840-0026(0.75K) or lower.
*2 Initial value for the FR-E860-0017(0.75K).
*3 Initial value for the FR-E820-0080(1.5K) to FR-E820-0175(3.7K) and FR-E840-0040(1.5K) to FR-E840-0095(3.7K).
*4 Initial value for the FR-E820-0240(5.5K), FR-E820-0330(7.5K), FR-E840-0120(5.5K), FR-E840-0170(7.5K), FR-E860-0027(1.5K), and FR-E860-
0040(2.2K).
*5 Initial value for the FR-E860-0061(3.7K) to FR-E860-0120(7.5K).
*6 Initial value for the FR-E820-0175(3.7K) or lower, FR-E840-0095(3.7K) or lower, and FR-E860-0061(3.7K) or lower.
*7 Initial value for the FR-E820-0240(5.5K) or higher, FR-E840-0120(5.5K) or higher, FR-E860-0090(5.5K) or higher.
*8 The initial value for the FR-E820-0050(0.75K) or lower, the FR-E840-0026(0.75K) or lower, and the FR-E860-0017(0.75K) is set to the 85% of
the inverter rated current.
*9 Gr.1 and Gr.2 are the parameter initial value groups. (Refer to page 82.)
30 2. Basic Operation
2.4 Frequently-used parameters (simple mode parameters)
Simple mode parameters (Ethernet model)
Pr.
Initial value*9 Refer 1
Pr. Name Increment Range Application to
group Gr.1 Gr.2 page
6%*1
5%*2
Set this parameter to obtain a higher starting 2
torque under V/F control. Also set this when a
0 G000 Torque boost 0.1% 4%*3 0% to 30% loaded motor cannot be driven, the warning 374
"OL" occurs, and the inverter output is shut off
3%*4
2%*5
with the fault indication "E.OC1". 3
1 H400 Maximum frequency 0.01 Hz 120 Hz 0 to 120 Hz Set the upper limit for the output frequency.
211
2 H401 Minimum frequency 0.01 Hz 0 Hz 0 to 120 Hz Set the lower limit for the output frequency.
Set this parameter when the rated motor 4
3 G001 Base frequency 0.01 Hz 60 Hz 50 Hz 0 to 590 Hz frequency is 50 Hz. Check the rating plate of 376
the motor.
Multi-speed setting
4 D301
(high speed)
0.01 Hz 60 Hz 50 Hz 0 to 590 Hz
34,
5
Multi-speed setting Pre-set the speeds that will be switched
5 D302 0.01 Hz 30 Hz 0 to 590 Hz 39,
(middle speed) among by terminals.
195
Multi-speed setting
6 D303
(low speed)
0.01 Hz 10 Hz 0 to 590 Hz 6
5 s*6
7 F010 Acceleration time 0.1 s 0 to 3600 s Set the acceleration time.
10 s*7
5 s*6
158
7
8 F011 Deceleration time 0.1 s 0 to 3600 s Set the deceleration time.
*7
10 s
H000 Electronic thermal Inverter rated Protects the motor from heat. Set the rated
9 0.01 A 0 to 500 A 198
C103 O/L relay current*8 motor current. 8
Operation mode Select the start and frequency command
79 D000 1 0 0 to 4, 6, 7 174
selection sources.
Terminal 2 Change the frequency at the maximum
125 T022 frequency setting 0.01 Hz 60 Hz 50 Hz 0 to 590 Hz potentiometer setting (5 V in the initial
41,
273
9
gain frequency setting).
Terminal 4
Change the frequency at the maximum 43,
126 T042 frequency setting 0.01 Hz 60 Hz 50 Hz 0 to 590 Hz
gain frequency
current input (20 mA in the initial setting). 273
10
This function restricts the parameters that are
User group read
160 E440 1 0 0, 1, 9999 read by the operation panel and parameter 90
selection
unit.
DO0 output
313 M410 1 9999
selection
Set this parameter to assign the functions to
DO1 output Refer to page *10
314 M411 1 9999 the devices RX9 to RXB for the CC-Link IE
selection 228.
TSN and CC-Link IE Field Network Basic.
DO2 output
315 M412 1 9999
selection
Disable an error reset command given via
Communication *10
349 N010 1 0 0, 1 communication in the External operation
reset selection
mode or the PU operation mode.
Set this parameter to make the start
command (forward/reverse rotation) inverted
Frequency
by adding a plus or minus sign to the value of *10
541 N100 command sign 1 0 0, 1
the frequency command sent through the CC-
selection
Link IE TSN or the CC-Link IE Field Network
Basic.
Set this parameter to extend the function of
CC-Link extended 0, 1, 12, 14, *10
544 N103 1 0 the remote registers for the CC-Link IE TSN or
setting 18, 24, 28
the CC-Link IE Field Network Basic.
0, 8009, Select the PM sensorless vector control and
PM parameter
998 E430 1 0 8109, 9009, set the parameters that are required to drive a 90
initialization
9109 PM motor.
2. Basic Operation
2.4 Frequently-used parameters (simple mode parameters)
31
Initial value*9 Refer
Pr.
Pr. Name Increment Range Application to
group Gr.1 Gr.2
page
Changes parameter settings as a batch. The
target parameters include communication
Automatic 10, 12, 20, parameters for the Mitsubishi Electric human
999 E431 1 9999 141
parameter setting 21, 9999 machine interface (GOT) connection and the
parameters for the rated frequency settings of
50/60 Hz.
*1 Initial value for the FR-E820-0050(0.75K) or lower and FR-E840-0026(0.75K) or lower.
*2 Initial value for the FR-E860-0017(0.75K).
*3 Initial value for the FR-E820-0080(1.5K) to FR-E820-0175(3.7K) and FR-E840-0040(1.5K) to FR-E840-0095(3.7K).
*4 Initial value for the FR-E820-0240(5.5K), FR-E820-0330(7.5K), FR-E840-0120(5.5K), FR-E840-0170(7.5K), FR-E860-0027(1.5K), and FR-E860-
0040(2.2K).
*5 Initial value for the FR-E860-0061(3.7K) to FR-E860-0120(7.5K).
*6 Initial value for the FR-E820-0175(3.7K) or lower, FR-E840-0095(3.7K) or lower, and FR-E860-0061(3.7K) or lower.
*7 Initial value for the FR-E820-0240(5.5K) or higher, FR-E840-0120(5.5K) or higher, FR-E860-0090(5.5K) or higher.
*8 The initial value for the FR-E820-0050(0.75K) or lower, the FR-E840-0026(0.75K) or lower, and the FR-E860-0017(0.75K) is set to the 85% of
the inverter rated current.
*9 Gr.1 and Gr.2 are the parameter initial value groups. (Refer to page 82.)
*10 For details, refer to the Instruction Manual (Communication).
32 2. Basic Operation
2.4 Frequently-used parameters (simple mode parameters)
2.5 Basic operation procedure (PU operation) 1
Select a method to give the frequency command from the list below, and refer to the specified page for its procedure.
Method to give the frequency command Refer to page
2
Setting the frequency on the operation panel in the frequency setting mode 33
Give commands by turning ON/OFF switches wired to inverter's terminals (multi-speed setting) 34
Setting the frequency by inputting voltage signals 35 3
Setting the frequency by inputting current signals 36
6
Operation panel
5. Deceleration → stop
Press the STOP/RESET key to stop. The frequency value on the monitor decreases according to the setting of Pr.8
Deceleration time, "0.00" (0.00 Hz) appears on the monitor, and the motor stops rotating.
NOTE
• To display the set frequency in the standard model, press the setting dial while the inverter runs in the PU operation mode or
in the External/PU combined operation mode 1 (Pr.79 = "3"). (Refer to page 228.)
• The frequency can be set without pressing the SET key when Pr.161 Frequency setting/key lock operation selection = "1
or 11". (Refer to page 130.)
2. Basic Operation
2.5 Basic operation procedure (PU operation)
33
Parameters referred to
Pr.7 Acceleration time, Pr.8 Deceleration timepage 158
Pr.79 Operation mode selectionpage 174
• Use the RUN key on the operation panel to give a start command.
• Turn ON the RH, RM, or RL signal to give a frequency command (multi-speed setting).
• Set Pr.79 Operation mode selection = "4" (External/PU combination operation mode 2).
[Connection diagram]
Speed 1
Speed 2
High speed RH Operation panel (Middle speed)
Middle speed RM Speed 3
(Low speed)
Low speed RL
SD Time
RH ON
ON
RM
Switch RL
ON
The following shows the procedure to operate at a low speed (10 Hz).
Operating procedure
1. Turning ON the power of the inverter
The operation panel is in the monitor mode.
5. Deceleration → stop
Press the STOP/RESET key to stop. The frequency value on the monitor decreases according to the setting of Pr.8
Deceleration time, "0.00" (0.00 Hz) appears on the monitor, and the motor stops rotating. Turn OFF the low-speed
switch (RL signal).
NOTE
• The initial value is 60 Hz for terminal RH in Group 1 (50 Hz in Group 2), 30 Hz for terminal RM, and 10 Hz for terminal RL. (To
change the settings, use Pr.4, Pr.5, and Pr.6, respectively.)
• In the initial setting, if two or more speed switches (signals) are simultaneously turned ON, priority is given to the switch (signal)
for the lower speed. For example, when both RH and RM signals turn ON, the RM signal (Pr.5) has the higher priority.
• Up to 15-speed switching operation can be performed.
• Up to two external input terminals are available for the Ethernet model. Use Pr.178 STF/DI0 terminal function selection and
Pr.179 STR/DI1 terminal function selection to assign the functions to terminals DI0 and DI1.
Parameters referred to
Pr.4 to Pr.6 (multi-speed setting)page 195
Pr.7 Acceleration time, Pr.8 Deceleration timepage 158
Pr.79 Operation mode selectionpage 174
Pr.178 STF/DI0 terminal function selectionpage 283
34 2. Basic Operation
2.5 Basic operation procedure (PU operation)
2.5.3 Setting the frequency using an analog signal
(voltage input) 1
• Use the RUN key on the operation panel to give a start command. 2
• Use the frequency setting potentiometer to give a frequency command (by connecting it to terminals 2 and 5 (voltage input)).
• Set Pr.79 Operation mode selection = "4" (External/PU combination operation mode 2).
3
[Connection diagram] (The inverter supplies 5 V power to the frequency setting potentiometer via terminal 10.)
Inverter 4
Operation panel
10
Frequency setting
potentiometer
2
5
5
Potentiometer
6
The following shows the procedure to operate at 60 Hz.
Operating procedure 7
1. Turning ON the power of the inverter
The operation panel is in the monitor mode.
3. Start
9
Press the RUN key. The RUN LED blinks as no frequency command is given.
5. Deceleration
Turn the frequency setting potentiometer counterclockwise slowly to full. The frequency value on the monitor
decreases according to the setting of Pr.8 Deceleration time, "0.00" (0.00 Hz) appears on the monitor, and the
motor stops rotating. The RUN LED blinks.
6. Stop
Press the STOP/RESET key. The RUN LED turns OFF.
NOTE
• To change the frequency (60 Hz) at the maximum voltage input (initial value: 5 V), adjust Pr.125 Terminal 2 frequency setting
gain frequency.
• To change the frequency (0 Hz) at the minimum voltage input (initial value: 0 V), adjust the calibration parameter C2
Terminal 2 frequency setting bias frequency.
• When terminal 10 is used, the maximum output frequency may fluctuate in a range of ±6 Hz due to fluctuations in the output
voltage (5 ±0.5 VDC). Use Pr.125 or C4 to adjust the output frequency at the maximum analog input as required. (Refer to
page 273.)
Parameters referred to
Pr.7 Acceleration time, Pr.8 Deceleration timepage 158
Pr.79 Operation mode selectionpage 174
Pr.125 Terminal 2 frequency setting gain frequencypage 273
C2 Terminal 2 frequency setting bias frequencypage 273
2. Basic Operation
2.5 Basic operation procedure (PU operation)
35
2.5.4 Setting the frequency using an analog signal
(current input)
• Use the RUN key on the operation panel to give a start command.
• Use the current regulator which outputs 4 to 20 mA to give a frequency command (by connecting it across terminals 4 and 5
(current input)).
• Turn ON the AU signal.
• Set Pr.79 Operation mode selection = "4" (External/PU combination operation mode 2).
[Connection diagram]
Inverter
Operation panel
AU signal RL(AU)
SD
Current signal 4(+)
source
5(ー)
(4 to 20mADC)
Operating procedure
1. Turning ON the power of the inverter
The operation panel is in the monitor mode.
3. Assignment of AU signal
Set Pr.180 RL terminal function selection = "4" to assign the AU signal to terminal RL.
5. Start
Press the RUN key. The RUN LED blinks as no frequency command is given.
7. Deceleration
Input a current of 4 mA or less. The frequency value on the monitor decreases according to the setting of Pr.8
Deceleration time, "0.00" (0.00 Hz) appears on the monitor, and the motor stops rotating. The RUN LED blinks.
8. Stop
Press the STOP/RESET key. The RUN LED turns OFF.
NOTE
• The AU signal can be assigned to another terminal. Set "4" in any parameter from Pr.178 to Pr.184 (Input terminal function
selection) to assign the function to an input terminal. (For the Ethernet model, assign the signal to terminal DI0 or DI1 using
Pr.178 or Pr.179.)
• To change the frequency (60 Hz) at the maximum current input (initial value: 20 mA), adjust Pr.126 Terminal 4 frequency
setting gain frequency.
• To change the frequency (0 Hz) at the minimum current input (initial value: 4 mA), adjust the calibration parameter C5
Terminal 4 frequency setting bias frequency.
36 2. Basic Operation
2.5 Basic operation procedure (PU operation)
Parameters referred to
Pr.7 Acceleration time, Pr.8 Deceleration timepage 158
Pr.79 Operation mode selectionpage 174 1
Pr.126 Terminal 4 frequency setting gain frequencypage 273
Pr.178 to Pr.184 (Input terminal function selection)page 283
C5 Terminal 4 frequency setting bias frequencypage 273
10
2. Basic Operation
2.5 Basic operation procedure (PU operation)
37
2.6 Basic operation procedure (External operation)
Select a method to give the frequency command from the list below, and refer to the specified page for its procedure.
Method to give the frequency command Refer to page
Setting the frequency on the operation panel in the frequency setting mode 38
Turning ON/OFF switches wired to inverter's terminals (multi-speed setting) 39
Setting the frequency by inputting voltage signals 40
Setting the frequency by inputting current signals 42
[Connection diagram]
Inverter
Operation panel
Forward rotation STF
start
Reverse rotation STR
start
Switch SD
Operating procedure
1. Changing the operation mode
Set "3" in Pr.79. The PU LED and EXT LED turn ON. (To change the setting, refer to page 25.)
4. Deceleration → stop
Turn OFF the start switch (STF/STR signal). The frequency value on the monitor decreases according to the setting
of Pr.8 Deceleration time, "0.00" (0.00 Hz) appears on the monitor, and the motor stops rotating.
38 2. Basic Operation
2.6 Basic operation procedure (External operation)
NOTE
• When both the forward rotation start switch (STF signal) and the reverse rotation start switch (STR signal) are turned ON, the 1
motor cannot be started. If both are turned ON while the inverter is running, the inverter decelerates to a stop.
• Pr.178 STF/DI0 terminal function selection must be set to "60" (or Pr.179 STR/DI1 terminal function selection must be
set to "61") (initial value).
• Setting Pr.79 Operation mode selection = "3" enables multi-speed operation.
2
• If the STOP/RESET key on the operation panel is pressed during the External operation, the inverter stops and the PU stop
warning is activated ("PS" appears on the LCD display of the operation panel.) To reset the PU stop warning, turn OFF the
start switch (STF or STR signal), and then press the PU/EXT key. (Refer to page 129.) 3
Parameters referred to
Pr.4 to Pr.6 (multi-speed setting)page 195, Pr.7 Acceleration time, Pr.8 Deceleration timepage 158
Pr.178 STF/DI0 terminal function selection, Pr.179 STR/DI1 terminal function selectionpage 283
4
Pr.79 Operation mode selectionpage 174
Speed 1 8
Output frequency (Hz)
High speed RH
(Low speed)
9
Middle speed RM Time
Low speed RL RH ON
10
SD RM
ON
Switch
ON
RL
The following shows the procedure to operate at a high speed (60 Hz).
Operating procedure
1. Turning ON the power of the inverter
The operation panel is in the monitor mode.
4. Deceleration → stop
Turn OFF the start switch (STF/STR signal). The frequency value on the monitor decreases according to the setting
of Pr.8 Deceleration time, "0.00" (0.00 Hz) appears on the monitor, and the motor stops rotating. The RUN LED
turns OFF. Turn OFF the high-speed switch (RH signal).
2. Basic Operation
2.6 Basic operation procedure (External operation)
39
NOTE
• When both the forward rotation start switch (STF signal) and the reverse rotation start switch (STR signal) are turned ON, the
motor cannot be started. If both are turned ON while the inverter is running, the inverter decelerates to a stop.
• The initial value is 60 Hz for terminal RH in Group 1 (50 Hz in Group 2), 30 Hz for terminal RM, and 10 Hz for terminal RL. (To
change the settings, use Pr.4, Pr.5, and Pr.6, respectively.)
• In the initial setting, if two or more speed switches (signals) are simultaneously turned ON, priority is given to the switch (signal)
for the lower speed. For example, when both RH and RM signals turn ON, the RM signal (Pr.5) has the higher priority.
• Up to 15-speed switching operation can be performed.
• Up to two external input terminals are available for the Ethernet model. Use Pr.178 STF/DI0 terminal function selection and
Pr.179 STR/DI1 terminal function selection to assign the functions to terminals DI0 and DI1.
Parameters referred to
Pr.4 to Pr.6 (multi-speed setting)page 195
Pr.7 Acceleration time, Pr.8 Deceleration timepage 158
Pr.178 STF/DI0 terminal function selection, Pr.179 STR/DI1 terminal function selectionpage 283
[Connection diagram]
(The inverter supplies 5 V power to the frequency setting potentiometer via terminal 10.)
Inverter
10
Frequency setting
2
potentiometer
5
Potentiometer
Operating procedure
1. Turning ON the power of the inverter
The operation panel is in the monitor mode.
2. Start
Turn ON the start switch (STF/STR signal). The RUN LED on the operation panel blinks as no frequency command
is given.
4. Deceleration
Turn the frequency setting potentiometer counterclockwise slowly to full. The frequency value on the monitor
decreases according to the setting of Pr.8 Deceleration time, "0.00" (0.00 Hz) appears on the monitor, and the
motor stops rotating. The RUN LED blinks.
5. Stop
Turn OFF the start switch (STF/STR signal). The RUN LED turns OFF.
40 2. Basic Operation
2.6 Basic operation procedure (External operation)
NOTE
• When both the forward rotation start switch (STF signal) and the reverse rotation start switch (STR signal) are turned ON, the 1
motor cannot be started. If both are turned ON while the inverter is running, the inverter decelerates to a stop.
• Pr.178 STF/DI0 terminal function selection must be set to "60" (or Pr.179 STR/DI1 terminal function selection must be
set to "61") (initial value).
• When terminal 10 is used, the maximum output frequency may fluctuate in a range of ±6 Hz due to fluctuations in the output
2
voltage (5 ±0.5 VDC). Use Pr.125 or C4 to adjust the output frequency at the maximum analog input as required. (Refer to
page 273.)
3
Parameters referred to
Pr.7 Acceleration time, Pr.8 Deceleration timepage 158
Pr.178 STF/DI0 terminal function selection, Pr.179 STR/DI1 terminal function selectionpage 283
4
2.6.4 Changing the frequency (initial value: 60 Hz) at the
maximum voltage input (initial value: 5 V) 5
4. Start
Turn ON the start switch (STF/STR signal), and turn the frequency setting potentiometer clockwise slowly to full.
(Refer to steps 2 and 3 in 2.6.3.)
The motor is operated at 50 Hz.
NOTE
• To change the frequency at the input of 0 V (minimum voltage), use the calibration parameter C2.
Initial value
60Hz
(50Hz)
Output frequency
(Hz)
Gain Pr.125
Bias
C2
0 100%
0 5V
Frequency setting signal
0 10V
C3 C4
2. Basic Operation
2.6 Basic operation procedure (External operation)
41
• Other adjustment methods for the frequency setting voltage gain are the following: adjustment by applying a voltage directly
across terminals 2 and 5, and adjustment using a specified point without applying a voltage across terminals 2 and 5. (Refer
to page 273.)
Parameters referred to
Pr.125 Terminal 2 frequency setting gain frequencypage 273
C2 Terminal 2 frequency setting bias frequencypage 273
C4 Terminal 2 frequency setting gainpage 273
[Connection diagram]
Inverter
Operating procedure
1. Turning ON the power of the inverter
The operation panel is in the monitor mode.
2. Assignment of AU signal
Set Pr.180 RL terminal function selection = "4" to assign the AU signal to terminal RL.
4. Start
Turn ON the start switch (STF/STR signal). The RUN LED blinks as no frequency command is given.
6. Deceleration
Input a current of 4 mA or less. The frequency value on the monitor decreases according to the setting of Pr.8
Deceleration time, "0.00" (0.00 Hz) appears on the monitor, and the motor stops rotating. The RUN LED blinks.
7. Stop
Turn OFF the start switch (STF/STR signal). The RUN LED turns OFF.
42 2. Basic Operation
2.6 Basic operation procedure (External operation)
NOTE
• When both the forward rotation start switch (STF signal) and the reverse rotation start switch (STR signal) are turned ON, the 1
motor cannot be started. If both are turned ON while the inverter is running, the inverter decelerates to a stop.
• The AU signal can be assigned to another terminal. Set "4" in any parameter from Pr.178 to Pr.184 (Input terminal function
selection) to assign the function to an input terminal. (For the Ethernet model, assign the signal to terminal DI0 or DI1 using
Pr.178 or Pr.179.)
2
Parameters referred to
Pr.7 Acceleration time, Pr.8 Deceleration timepage 158
3
Pr.178 to Pr.184 (Input terminal function selection)page 283
The following shows the procedure to change the frequency at 20 mA from 60 Hz (initial value) to 50 Hz using a frequency 6
setting potentiometer for 4 to 20 mA input. Set 50 Hz in Pr.126 so that the inverter outputs 50 Hz at 20 mA input.
Operating procedure 7
1. Selecting the parameter
Turn the setting dial or press the UP/DOWN key until "P.126" (Pr.126) appears.
Press the SET key to show the present set value (60.00 Hz). 8
2. Changing the maximum frequency
Turn the setting dial or press the UP/DOWN key to change the value to "50.00" (50.00 Hz).
Press the SET key to confirm the setting. "50.00" blinks. 9
3. Selecting the mode and the monitor item
Press the MODE key twice to select the monitor mode and to monitor a frequency.
10
4. Start
Turn ON the start switch (STF or STR) to apply a 20 mA current (refer to steps 3 and 4 in 2.6.5).
Operate at 50 Hz.
NOTE
• To change the frequency at the input of 4 mA (minimum current), use the calibration parameter C5.
Initial value
60Hz
Output frequency
(50Hz)
(Hz)
Gain Pr.126
Bias
C5
0 20 100%
0 4 Frequency setting signal 20mA
0 1 5V
0 2 10V
C6 C7
• Other adjustment methods for the frequency setting current gain are the following: adjustment by applying a current through
terminals 4 and 5, and adjustment using a specified point without applying a current through terminals 4 and 5. (Refer to page
273.)
2. Basic Operation
2.6 Basic operation procedure (External operation)
43
Parameters referred to
Pr.126 Terminal 4 frequency setting gain frequencypage 273
C5 Terminal 4 frequency setting bias frequencypage 273
C7 Terminal 4 frequency setting gainpage 273
44 2. Basic Operation
2.6 Basic operation procedure (External operation)
2.7 Basic operation procedure (JOG operation) 1
Inverter 6
Forward rotation start STF
Reverse rotation start STR
JOG signal RL(JOG) 7
SD
Switch
5. Deceleration → stop
Turn OFF the start switch (STF/STR signal). The frequency value on the monitor decreases according to the setting
of Pr.16 Jog acceleration/deceleration time, "0.00" (0.00 Hz) appears on the monitor, and the motor stops
rotating. The RUN LED turns OFF. Turn OFF the JOG switch (JOG signal).
NOTE
• To change the frequency, change the setting of Pr.15 Jog frequency (initial value: 5 Hz).
• To change the acceleration/deceleration time, change the setting of Pr.16 Jog acceleration/deceleration time (initial value:
0.5 seconds).
• The JOG signal can be assigned to another terminal. Set "5" in any parameter from Pr.178 to Pr.184 (Input terminal function
selection) to assign the function to an input terminal. (For the Ethernet model, assign the signal to terminal DI0 or DI1 using
Pr.178 or Pr.179.)
• The JOG2 signal enables the JOG operation via communication. (Refer to page 194.)
Parameters referred to
Pr.15 Jog frequency, Pr.16 Jog acceleration/deceleration timepage 194
Pr.79 Operation mode selectionpage 174
2. Basic Operation
2.7 Basic operation procedure (JOG operation)
45
Pr.178 to Pr.184 (Input terminal function selection)page 283
• JOG operation is performed while the RUN key on the operation panel is pressed.
Operation panel
Operating procedure
1. Turning ON the power of the inverter
The operation panel is in the monitor mode.
4. Deceleration → stop
Release the RUN key. The frequency value on the monitor decreases according to the setting of Pr.16 Jog
acceleration/deceleration time, "0.00" (0.00 Hz) appears on the monitor, and the motor stops rotating.
NOTE
• To change the frequency, change the setting of Pr.15 Jog frequency (initial value: 5 Hz).
• To change the acceleration/deceleration time, change the setting of Pr.16 Jog acceleration/deceleration time (initial value:
0.5 seconds).
Parameters referred to
Pr.15 Jog frequency, Pr.16 Jog acceleration/deceleration timepage 194
46 2. Basic Operation
2.7 Basic operation procedure (JOG operation)
2.8 I/O terminal function assignment 1
• Functions can be assigned to the external I/O terminals (physical terminals) or communication (virtual terminals) by setting
parameters. 2
FR-E800 FR-E800-E
8
Output Input Output Input
9
NOTE
• Two or more plug-in options cannot be installed at the same time.
10
Input terminal function assignment
• Signals can be input to the inverter by using physical terminals or via communication.
• Use the following parameters to assign functions to input terminals. Check the terminal available for each parameter.
External input terminal
Terminal Input via
Pr. (physical terminal)
name communication*1
FR-E800 FR-E800-E
178 STF/DI0 ○ (STF) ○ (DI0) ○
179 STR/DI1 ○ (STR) ○ (DI1) ○
180 RL ○ — ○
181 RM ○ — ○
182 RH ○ — ○
183 MRS ○ — ○
184 RES ○ — ○
185 NET X1 — — ○
186 NET X2 — — ○
187 NET X3 — — ○
188 NET X4 — — ○
189 NET X5 — — ○
NOTE
• For the available signals, refer to page 283.
2. Basic Operation
2.8 I/O terminal function assignment
47
Output terminal function assignment
• Signals can be output to the inverter by using physical terminals or via communication or assigned to the extension
terminals of the plug-in option (FR-A8AY or FR-A8AR).
• Use the following parameters to assign functions to input terminals. Check the terminal available for each parameter.
External output terminal Option output terminal (physical
Terminal Output via
Pr. (physical terminal) terminal)*2
name communication*1
FR-E800 FR-E800-E FR-A8AY FR-A8AR
190 RUN ○ — ○ — —
191 FU ○ — ○ — —
192 A,B,C ○ ○ ○ — —
193 NET Y1 — — ○ — —
194 NET Y2 — — ○ — —
195 NET Y3 — — ○ — —
196 NET Y4 — — ○ — —
313 DO0 — — ○ ○ —
314 DO1 — — ○ ○ —
315 DO2 — — ○ ○ —
316 DO3 — — — ○ —
317 DO4 — — — ○ —
318 DO5 — — — ○ —
319 DO6 — — — ○ —
320 RA1 — — — — ○
321 RA2 — — — — ○
322 RA3 — — — — ○
NOTE
• For the available signals, refer to page 250.
48 2. Basic Operation
2.8 I/O terminal function assignment
CHAPTER 3
CHAPTER 3 Parameters
4
10
49
3 Parameters
This chapter explains the function setting for use of this product.
Always read the instructions before use.
The following marks are used to indicate the controls. (Parameters without any mark are valid for all the controls.)
Mark Control method Applied motor
V/F V/F control
Magnetic flux Advanced magnetic flux vector control Three-phase induction motor
Sensorless Real sensorless vector control
PM PM sensorless vector control PM motor
NOTE
• Simple indicates simple mode parameters. Use Pr.160 User group read selection to indicate the simple mode parameters
only (initial setting is to indicate the extended mode parameters).
• The changing of the parameter settings may be restricted in some operating statuses. Use Pr.77 Parameter write selection
to change the setting of the restriction.
• Refer to page 406 for instruction codes for communication and availability of Parameter clear, all clear, and Parameter copy.
Notation
[E800]: Available for the standard model.
[E800-1]: Available for the FM type inverter (standard model).
[E800-4]: Available for the AM (50 Hz) type inverter (standard model).
[E800-5]: Available for the AM (60 Hz) type inverter (standard model).
[E800-E]: Available for the Ethernet model.
[E800-EPA]: Available for the Protocol group A (Ethernet model).
[E800-EPB]: Available for the Protocol group B (Ethernet model).
[200/400 V class]: Available for the 200/400 V class.
[575 V class]: Available for the 575 V class inverters.
50 3. Parameters
3.1 Parameter list (by parameter number)
Pr.0 to Pr.99
Minimum Initial 1
Pr. Refer Customer
Function Pr. Name Setting range setting value*1
group to page setting
increments Gr.1 Gr.2
6%*2
2
5%*2
0 G000 Torque boost Simple 0% to 30% 0.1% 4%*2 374
3%*2
3
2%*2
1 H400 Maximum frequency Simple 0 to 120 Hz 0.01 Hz 120 Hz 211
2 H401 Minimum frequency Simple 0 to 120 Hz 0.01 Hz 0 Hz 211
4
3 G001 Base frequency Simple 0 to 590 Hz 0.01 Hz 60 Hz 50 Hz 376
Basic function
frequency
11 G101
DC injection brake operation
0 to 10 s, 9999 0.1 s 0.5 s 382
9
time
6%*4
DC injection brake operation
12 G110
voltage
0% to 30% 0.1% 4%*4 382
10
1%*4
169,
— 13 F102 Starting frequency 0 to 60 Hz 0.01 Hz 0.5 Hz
170
— 14 G003 Load pattern selection 0 to 3 1 0 378
15 D200 Jog frequency 0 to 590 Hz 0.01 Hz 5 Hz 194
JOG operation
Jog acceleration/
16 F002 0 to 3600 s 0.1 s 0.5 s 194
deceleration time
Acceleration/deceleration
21 F001 0, 1 1 0 158
time increments
3. Parameters
3.1 Parameter list (by parameter number)
51
Minimum Initial
Pr. value*1 Refer Customer
Function Pr. Name Setting range setting
group to page setting
increments Gr.1 Gr.2
Stall prevention operation 100,
Multi-speed setting Stall prevention
Acceleration/deceleration
— 29 F100 0 to 2 1 0 163
pattern selection
Regenerative function
— 30 E300 0 to 2 1 0 386
selection
31 H420 Frequency jump 1A 0 to 590 Hz, 9999 0.01 Hz 9999 212
Frequency jump
52 3. Parameters
3.1 Parameter list (by parameter number)
Minimum Initial
Pr. value*1 Refer Customer
Function Pr.
group
Name Setting range setting
increments Gr.1 Gr.2
to page setting 1
[E800][E800-EPB]
0, 5 to 12, 14, 17, 18,
20, 23 to 25, 32, 33,
38, 40 to 42, 44, 45, 50 2
to 57, 61, 62, 67, 91,
Operation panel main 97, 100
52 M100 1 0 228
monitor selection [E800-EPA]
0, 5 to 12, 14, 17, 18, 3
20, 23 to 25, 32, 33,
38, 40 to 42, 44, 45, 50
Monitoring
351,
7
Automatic restart
Reference value at
62 F511 0% to 400%, 9999 1% 9999 171
acceleration
10
Reference value at
63 F512 0% to 400%, 9999 1% 9999 171
deceleration
3. Parameters
3.1 Parameter list (by parameter number)
53
Minimum Initial
Pr. value*1 Refer Customer
Function Pr. Name Setting range setting
group to page setting
increments Gr.1 Gr.2
— 72 E600 PWM frequency selection 0 to 15 1 1 146
— 73 T000 Analog input selection 0, 1, 6, 10, 11, 16 1 1 266
— 74 T002 Input filter time constant 0 to 8 1 1 271
Reset selection/
— disconnected PU detection/ 0 to 3, 14 to 17 14
PU stop selection
— 75 1 128
E100 Reset selection
0
E101 Disconnected PU detection 0, 1
E102 PU stop selection 1
— 77 E400 Parameter write selection 0 to 2 1 0 135
Reverse rotation prevention
— 78 D020 0 to 2 1 0 193
selection
Operation mode 174,
— 79 D000 0 to 4, 6, 7 1 0
selection Simple 184
86,
80 C101 Motor capacity 0.1 to 30 kW, 9999 0.01 kW 9999 299,
308
86,
81 C102 Number of motor poles 2, 4, 6, 8, 10, 12, 9999 1 9999 299,
308
82 C125 Motor excitation current 0 to 500 A, 9999 0.01 A 9999 299
[200 V class]
200 V
86,
[400 V class]
83 C104 Rated motor voltage 0 to 1000 V 0.1 V 299,
400 V
308
[575 V class]
575 V
86,
Motor constant
84 C105 Rated motor frequency 10 to 400 Hz, 9999 0.01 Hz 9999 299,
308
Speed control gain
89 G932 (Advanced magnetic flux 0% to 200%, 9999 0.1% 9999 90
vector)
299,
90 C120 Motor constant (R1) 0 to 50 Ω, 9999 0.001Ω 9999 308,
358
91 C121 Motor constant (R2) 0 to 50 Ω, 9999 0.001Ω 9999 299
Motor constant (L1)/d-axis 299,
92 C122 0 to 6000 mH, 9999 0.1 mH 9999
inductance (Ld) 308
Motor constant (L2)/q-axis 299,
93 C123 0 to 6000 mH, 9999 0.1 mH 9999
inductance (Lq) 308
94 C124 Motor constant (X) 0% to 100%, 9999 0.1% 9999 299
95 C111 Online auto tuning selection 0, 1 1 0 315
299,
96 C110 Auto tuning setting/status 0, 1, 11 1 0 308,
358
54 3. Parameters
3.1 Parameter list (by parameter number)
Pr.100 to Pr.199
Minimum Initial 1
Pr. Refer Customer
Function Pr. Name Setting range setting value*1
group to page setting
increments Gr.1 Gr.2
117 N020
PU communication station
number
0 to 31 1 0 *6
2
48, 96, 192, 384, 576, *6
118 N021 PU communication speed 1 192
768, 1152
—
PU communication stop bit
0, 1, 10, 11 1 3
PU connector communication
N023
PU communication stop bit
length
0, 1 1 4
PU communication parity *6
120 N024 0 to 2 1 2
check
121 N025
PU communication retry
0 to 10, 9999 1 1 *6 5
count
PU communication check *6
122 N026 0, 0.1 to 999.8 s, 9999 0.1 s 0
time interval
123 N027
PU communication waiting
0 to 150 ms, 9999 1 ms 9999 *6 6
time setting
PU communication CR/LF *6
124 N028 0 to 2 1 1
selection
— 125 T022
Terminal 2 frequency setting
0 to 590 Hz 0.01 Hz 60 Hz 50 Hz 273
7
gain frequency Simple
Terminal 4 frequency setting
— 126 T042 0 to 590 Hz 0.01 Hz 60 Hz 50 Hz 273
gain frequency Simple
8
PID control automatic
127 A612 0 to 590 Hz, 9999 0.01 Hz 9999 329
switchover frequency
0, 20, 21, 40 to 43, 50,
128 A610 PID action selection
51, 60, 61, 1000, 1001,
1 0
329, 9
1010, 1011, 2000, 344
2001, 2010, 2011
329,
129 A613 PID proportional band 0.1% to 1000%, 9999 0.1% 100%
10
PID operation
344
329,
130 A614 PID integral time 0.1 to 3600 s, 9999 0.1 s 1s
344
329,
131 A601 PID upper limit 0% to 100%, 9999 0.1% 9999
344
329,
132 A602 PID lower limit 0% to 100%, 9999 0.1% 9999
344
329,
133 A611 PID action set point 0% to 100%, 9999 0.01% 9999
344
329,
134 A615 PID differential time 0.01 to 10 s, 9999 0.01 s 9999
344
— 145 E103 Parameter for manufacturer setting. Do not set.
Acceleration/deceleration
— 147 F022 0 to 590 Hz, 9999 0.01 Hz 9999 158
time switching frequency
Output current detection
Current detection
3. Parameters
3.1 Parameter list (by parameter number)
55
Minimum Initial
Pr. value*1 Refer Customer
Function Pr. Name Setting range setting
group to page setting
increments Gr.1 Gr.2
1 to 3, 5 to 12, 14, 17,
AM terminal function 18, 21, 24, 32, 33, 50,
— 158 M301 1 1 237
selection [E800-4][E800-5] 52 to 54, 61, 62, 67,
70, 91, 97
User group read
— 160 E440 0, 1, 9999 1 0 143
selection Simple
Frequency setting/key lock
— 161 E200 0, 1, 10, 11 1 0 130
operation selection
Automatic restart after 351,
Current detection Automatic restart
E000
— 168
E080
Parameter for manufacturer setting. Do not set.
E001
— 169
E081
170 M020 Watt-hour meter clear 0, 10, 9999 1 9999 228
User group Cumulative monitor
56 3. Parameters
3.1 Parameter list (by parameter number)
Minimum Initial
Pr. value*1 Refer Customer
Function Pr.
group
Name Setting range setting
increments Gr.1 Gr.2
to page setting 1
0 to 5, 7, 8, 10, 12, 14
to 16, 18, 24 to 27, 30,
STF/DI0 terminal function
178 T700
selection
37, 46, 47, 50, 51, 60, 1
62, 65 to 67, 72, 92,
60 283
2
9999
0 to 5, 7, 8, 10, 12, 14
179 T701
STR/DI1 terminal function
to 16, 18, 24 to 27, 30,
37, 46, 47, 50, 51, 61, 1 61 283 3
selection
Input terminal function assignment
10
3. Parameters
3.1 Parameter list (by parameter number)
57
Minimum Initial
Pr. value*1 Refer Customer
Function Pr. Name Setting range setting
group to page setting
increments Gr.1 Gr.2
0, 1, 3, 4, 7, 8, 11 to 16,
20, 25, 26, 34, 35, 39
RUN terminal function to 41, 44 to 48, 57, 64,
190 M400 70, 80, 81, 90 to 93, 1 0 250
selection
95, 96, 98, 99, 100,
101, 103, 104, 107,
108, 111 to 116, 120,
125, 126, 134, 135,
139 to 141, 144 to 148,
157, 164, 170, 180,
181, 190 to 193, 195,
FU terminal function 196, 198, 199, 206,
191 M404 1 4 250
selection 211 to 213, 242 [E800-
E], 306, 311 to 313,
342 [E800-E]
0, 1, 3, 4, 7, 8, 11 to 16,
20, 25, 26, 34, 35, 39,
Output terminal function assignment
Pr.200 to Pr.299
Minimum Initial
Pr. Refer Customer
Function Pr. Name Setting range setting value*1
group to page setting
increments Gr.1 Gr.2
Multi-speed setting
Soft-PWM operation
— 240 E601 0, 1 1 1 146
selection
58 3. Parameters
3.1 Parameter list (by parameter number)
Minimum Initial
Pr. value*1 Refer Customer
Function Pr.
group
Name Setting range setting
increments Gr.1 Gr.2
to page setting 1
Analog input display unit
— 241 M043 0, 1 1 0 273
switchover
— 244 H100
Cooling fan operation
selection
0, 1 1 1 203 2
245 G203 Rated slip 0% to 50%, 9999 0.01% 9999 393
Slip compensation
9
261 A730 Power failure stop selection 0 to 2 1 0 146
10
— 267 T001 Terminal 4 input selection 0 to 2 1 0 266
Monitor decimal digits
— 268 M022 0, 1, 9999 1 9999 228
selection
— 269 E023 Parameter for manufacturer setting. Do not set.
Stop-on-contact control
270 A200 0, 1, 11 1 0 324
selection
Stop-on-contact
factor
PWM carrier frequency at
276 A206 0 to 9, 9999 1 9999 324
stop-on contact
Stall prevention operation
277 H630 0, 1 1 0 324
current switchover
278 A100 Brake opening frequency 0 to 30 Hz 0.01 Hz 3 Hz 320
Brake sequence
3. Parameters
3.1 Parameter list (by parameter number)
59
Minimum Initial
Pr. value*1 Refer Customer
Function Pr. Name Setting range setting
group to page setting
increments Gr.1 Gr.2
— 289 M431 Inverter output terminal filter 5 to 50 ms, 9999 1 ms 9999 250
Monitor negative output 228,
— 290 M044 0, 1, 4, 5, 8, 9, 12, 13 1 0
selection 237
A110 Automatic acceleration/ 171,
— 292 0, 1, 7, 8, 11 1 0
F500 deceleration 320
Acceleration/deceleration
— 293 F513 0 to 2 1 0 171
separate selection
Frequency change increment
— 295 E201 0, 0.01, 0.1, 1, 10, 0.01 0 132
amount setting
0 to 6, 99, 100 to 106,
Password
Pr.300 to Pr.399
Minimum Initial
Pr. Refer Customer
Function Pr. Name Setting range setting value*1
group to page setting
increments Gr.1 Gr.2
0, 1, 3, 4, 7, 8, 11 to 16,
320*7 M420 RA1 output selection 1 0 250
20, 25, 26, 34, 35, 39
to 41, 44 to 48, 57, 64,
321*7 M421 RA2 output selection 70, 80, 81, 90, 91, 95, 1 1 250
96, 98, 99, 206, 211 to
213, 242 [E800-E],
322*7 M422 RA3 output selection
9999
1 4 250
Communication operation
338 D010 0, 1 1 0 185
command source
RS-485 communication
Communication speed
339 D011 0 to 2 1 0 185
command source
[E800]
Communication startup 0
340 D001 0, 1, 10 1 184
mode selection [E800-E]
10
Communication EEPROM *6
342 N001 0, 1 1 0
write selection
343 N080 Communication error count (0 to 999) 1 0 *6
Communication reset
— 349*8 N010
selection
0, 1 1 0 *6
— 374 H800 Overspeed detection level 0 to 590 Hz, 9999 0.01 Hz 9999 224
% setting reference *6
— 390 N054 1 to 590 Hz 0.01 Hz 60 Hz 50 Hz
frequency
60 3. Parameters
3.1 Parameter list (by parameter number)
Pr.400 to Pr.499
Minimum Initial 1
Pr. Refer Customer
Function Pr. Name Setting range setting value*1
group to page setting
increments Gr.1 Gr.2
414 A800
PLC function operation
selection
0 to 2, 11, 12 1 0 364 2
PLC
442 N620
Default gateway address 1
[E800-E]
*6
3
Default gateway address 2 *6
Ethernet
443 N621
[E800-E]
0 to 255 1 0
444 N622
Default gateway address 3
[E800-E]
*6
4
Default gateway address 4 *6
445 N623
[E800-E]
[200 V class / 400 V 5
class]
0, 3, 5, 6, 10, 13, 15,
16, 20, 23, 40, 43, 50,
450 C200 Second applied motor
53, 70, 73, 8090, 8093,
9090, 9093
1 9999 294 6
[575 V class]
0, 3, 5, 6, 10, 13, 15,
16, 8090, 8093, 9090,
9093 7
Second motor control
451 G300 10 to 12, 20, 40, 9999 1 9999 86
method selection
453 C201 Second motor capacity 0.1 to 30 kW, 9999 0.01 kW 9999
299,
308
8
Number of second motor 299,
454 C202 2, 4, 6, 8, 10, 12, 9999 1 9999
poles 308
Second motor constant
455 C225
Second motor excitation
current
0 to 500 A, 9999 0.01 A 9999 299 9
[200 V class]
200 V
456 C204 Rated second motor voltage 0 to 1000 V 0.1 V
[400 V class]
400 V
299,
308
10
[575 V class]
575 V
Rated second motor 299,
457 C205 10 to 400 Hz, 9999 0.01 Hz 9999
frequency 308
299,
458 C220 Second motor constant (R1) 0 to 50 Ω, 9999 0.001 Ω 9999 308,
358
459 C221 Second motor constant (R2) 0 to 50 Ω, 9999 0.001 Ω 9999 299
Second motor constant (L1) / 299,
460 C222 0 to 6000 mH, 9999 0.1 mH 9999
d-axis inductance (Ld) 308
Second motor constant (L2) / 299,
461 C223 0 to 6000 mH, 9999 0.1 mH 9999
q-axis inductance (Lq) 308
462 C224 Second motor constant (X) 0% to 100%, 9999 0.1% 9999 299
299,
Second motor auto tuning
463 C210 0, 1, 11 1 0 308,
setting/status
358
495 M500 Remote output selection 0, 1, 10, 11 1 0 263
Remote
output
3. Parameters
3.1 Parameter list (by parameter number)
61
Pr.500 to Pr.599
Minimum Initial
Pr. Refer Customer
Function Pr. Name Setting range setting value*1
group to page setting
increments Gr.1 Gr.2
Stop mode selection at *6
— 502 N013 0 to 2, 6 1 0
communication error
503 E710 Maintenance timer 0 (0 to 9998) 1 0 152
Maintenance
541 N100 0, 1 1 0 *6
selection [E800-E]
[E800]
Communication
62 3. Parameters
3.1 Parameter list (by parameter number)
Minimum Initial
Pr. value*1 Refer Customer
Function
Multiple rating Second motor constant
Pr.
group
Name Setting range setting
increments Gr.1 Gr.2
to page setting 1
2
Second motor speed control
569 G942 0% to 200%, 9999 0.1% 9999 90
gain
4
570 E301 Multiple rating setting 1, 2 1 2 134
575 A621
Output interruption detection
time
0 to 3600 s, 9999 0.1 s 1s 329 6
PID control
577 A623
Output interruption cancel
level
900% to 1100% 0.1% 1000% 329 7
592 A300 Traverse function selection 0 to 2 1 0 327
593 A301 Maximum amplitude amount 0% to 25% 0.1% 10% 327
Amplitude compensation 8
Traverse
Pr.600 to Pr.699
10
Minimum Initial
Pr. Refer Customer
Function Pr. Name Setting range setting value*1
group to page setting
increments Gr.1 Gr.2
PID set point/deviation input 329,
PID control
609 A624 2 to 5 1 2
selection 344
PID measured value input 329,
610 A625 2 to 5 1 3
selection 344
351,
— 611 F003 Acceleration time at a restart 0 to 3600 s, 9999 0.1 s 9999
356
Inverter output fault
— 631 H182 detection enable/disable 0, 1 1 0 205
selection
Brake opening current
Speed smoothing control Brake sequence
3. Parameters
3.1 Parameter list (by parameter number)
63
Minimum Initial
Pr. value*1 Refer Customer
Function Pr. Name Setting range setting
group to page setting
increments Gr.1 Gr.2
Regeneration avoidance
— 665 G125 0% to 200% 0.1% 100% 390
frequency gain
SF-PR slip amount
adjustment operation
— 673 G060 2, 4, 6, 9999 1 9999 381
selection [200 V class / 400 V
class]
SF-PR slip amount
— 674 G061 adjustment gain [200 V class / 0% to 500% 0.1% 100% 381
400 V class]
User parameter auto storage
— 675 A805 1, 9999 1 9999 364
function selection
— 699 T740 Input terminal filter 5 to 50 ms, 9999 1 ms 9999 283
Pr.700 to Pr.799
Minimum Initial
Pr. Refer Customer
Function Pr. Name Setting range setting value*1
group to page setting
increments Gr.1 Gr.2
702 C106 Maximum motor frequency 0 to 400 Hz, 9999 0.01 Hz 9999 308
Induced voltage constant 0 to 5000 mV (rad/s), 0.1 mV
706 C130 9999 308
(phi f) 9999 (rad/s)
707 C107 Motor inertia (integer) 10 to 999, 9999 1 9999 308
711 C131 Motor Ld decay ratio 0% to 100%, 9999 0.1% 9999 308
712 C132 Motor Lq decay ratio 0% to 100%, 9999 0.1% 9999 308
Motor constant
64 3. Parameters
3.1 Parameter list (by parameter number)
Minimum Initial
Pr. value*1 Refer Customer
Function Pr.
group
Name Setting range setting
increments Gr.1 Gr.2
to page setting 1
[E800][E800-EPB]
Operation panel monitor 1 to 3, 5 to 12, 14, 17,
774 M101 1 9999 228
selection 1 18, 20, 23 to 25, 32, 2
33, 38, 40 to 42, 44,
45, 50 to 57, 61, 62,
Monitoring
776 M103
Operation panel monitor 45, 50 to 57, 61, 62,
67, 83, 91, 97, 100, 1 9999 228 4
selection 3
9999
selection
Torque command source
804 D400 0, 1, 3 to 6 1 0 117
selection
805 D401
Torque command value
(RAM)
600% to 1400% 1% 1000% 117 10
Torque command value
806 D402 600% to 1400% 1% 1000% 117
(RAM, EEPROM)
807 H410 Speed limit selection 0, 1 1 0 120
Speed limit
809 H412 Reverse-side speed limit 0 to 400 Hz, 9999 0.01 Hz 9999 120
3. Parameters
3.1 Parameter list (by parameter number)
65
Minimum Initial
Pr. value*1 Refer Customer
Function Pr. Name Setting range setting
group to page setting
increments Gr.1 Gr.2
820 G211 Speed control P gain 1 0% to 1000% 1% 60% 107
821 G212 Speed control integral time 1 0 to 20 s 0.001 s 0.333 s 107
822 T003 Speed setting filter 1 0 to 5 s, 9999 0.001 s 9999 271
Torque control P gain 1
824 G213 (current loop proportional 0% to 500% 1% 100% 122
gain)
Torque control integral time 1
825 G214 0 to 500 ms 0.1 ms 5 ms 122
(current loop integral time)
Adjustment
100,
Terminal 4 function
858 T040 0, 4, 9999 1 0 214,
assignment
270
Torque current/Rated PM 299,
859 C126 0 to 500 A, 9999 0.01 A 9999
motor current 308
Second motor torque
299,
860 C226 current/Rated PM motor 0 to 500 A, 9999 0.01 A 9999
308
current
864 M470 Torque detection 0% to 400% 0.1% 150% 262
865 M446 Low speed detection 0 to 590 Hz 0.01 Hz 1.5 Hz 257
Indication
selection
Regeneration avoidance
882 G120 0 to 2 1 0 390
operation selection
Regeneration avoidance
[200 V class]
400 V
Regeneration avoidance [400 V class]
883 G121 300 to 1200 V 0.1 V 390
operation level 780 V
[575 V class]
944 V
Regeneration avoidance
885 G123 compensation frequency 0 to 45 Hz, 9999 0.01 Hz 6 Hz 390
limit value
Regeneration avoidance
886 G124 0% to 200% 0.1% 100% 390
voltage gain
888 E420 Free parameter 1 0 to 9999 1 9999 140
Free parameter
66 3. Parameters
3.1 Parameter list (by parameter number)
Minimum Initial
Pr. value*1 Refer Customer
Function Pr.
group
Name Setting range setting
increments Gr.1 Gr.2
to page setting 1
Cumulative power monitor 228,
891 M023 0 to 4, 9999 1 9999
digit shifted times 244
892 M200 Load factor
Energy saving monitor
30% to 150% 0.1% 100%
Inverter rated
244
2
893 M201 0.1 to 30 kW 0.01 kW 244
Energy saving monitoring
— 998 E430
PM parameter
initialization Simple
0, 8009, 8109, 9009,
9109,
1 0 92 8
Automatic parameter
— 999 E431 10, 12, 20, 21, 9999 1 9999 141
setting Simple
9
Pr.1000 to Pr.1099
Minimum Initial
Pr. Refer Customer
Function Pr.
group
Name Setting range setting
increments
value*1
to page setting 10
Gr.1 Gr.2
— 1000 E108 Parameter for manufacturer setting. Do not set.
Lq tuning target current
— 1002 C150 50% to 150%, 9999 0.1% 9999 308
adjustment coefficient
1006 E020 Clock (year) 2000 to 2099 1 2000 127
Clock
3. Parameters
3.1 Parameter list (by parameter number)
67
Minimum Initial
Pr. value*1 Refer Customer
Function Pr. Name Setting range setting
group to page setting
increments Gr.1 Gr.2
1020 A900 Trace operation selection 0 to 3 1 0 366
1, 2, 5, 10, 50, 100,
1022 A902 Sampling cycle 1 1 366
500, 1000
1023 A903 Number of analog channels 1 to 8 1 4 366
1024 A904 Sampling auto start 0, 1 1 0 366
1025 A905 Trigger mode selection 0 to 4 1 0 366
Number of sampling before
1026 A906 0% to 100% 1% 90% 366
trigger
Analog source selection
1027 A910 201 366
(1ch)
Analog source selection
1028 A911 202 366
(2ch)
Analog source selection
1029 A912 1 to 3, 5 to 12, 14, 17, 203 366
(3ch)
18, 20, 23, 24, 32, 33,
Analog source selection
1030 A913 40 to 42, 52 to 54, 61, 204 366
(4ch)
62, 67, 83 [E800-EPA], 1
Analog source selection 91, 97, 201 to 210,
1031 A914 205 366
(5ch)
212, 213, 230 to 232,
Analog source selection 235 to 238
1032 A915 206 366
Trace
(6ch)
Analog source selection
1033 A916 207 366
(7ch)
Analog source selection
1034 A917 208 366
(8ch)
1035 A918 Analog trigger channel 1 to 8 1 1 366
Analog trigger operation
1036 A919 0, 1 1 0 366
selection
1037 A920 Analog trigger level 600 to 1400 1 1000 366
1038 A930 Digital source selection (1ch) 0 366
1039 A931 Digital source selection (2ch) 0 366
1040 A932 Digital source selection (3ch) 0 366
1041 A933 Digital source selection (4ch) 0 366
0 to 255 1
1042 A934 Digital source selection (5ch) 0 366
1043 A935 Digital source selection (6ch) 0 366
1044 A936 Digital source selection (7ch) 0 366
1045 A937 Digital source selection (8ch) 0 366
1046 A938 Digital trigger channel 1 to 8 1 1 366
Digital trigger operation
1047 A939 0, 1 1 0 366
selection
Pr.1100 to Pr.1399
Minimum Initial
Pr. value*1 Refer Customer
Function Pr. Name Setting range setting
group to page setting
increments Gr.1 Gr.2
Deceleration time at
— 1103 F040 0 to 3600 s 0.1 s 5s 158
emergency stop
1106 M050 Torque monitor filter 0 to 5 s, 9999 0.01 s 9999 228
Monitoring
1107 M051 Running speed monitor filter 0 to 5 s, 9999 0.01 s 9999 228
Excitation current monitor
1108 M052 0 to 5 s, 9999 0.01 s 9999 228
filter
Station number in inverter-to- *6
— 1124 N681 0 to 5, 9999 1 9999
inverter link [E800-E]
Number of inverters in
— 1125 N682 inverter-to-inverter link 2 to 6 1 2 *6
system [E800-E]
PLC function
68 3. Parameters
3.1 Parameter list (by parameter number)
Minimum Initial
Pr. value*1 Refer Customer
Function Pr.
group
Name Setting range setting
increments Gr.1 Gr.2
to page setting 1
AM output offset calibration
— 1200 M390 2700 to 3300 1 3000 241
[E800-4][E800-5]
— 1399 N649
Inverter identification enable/
disable selection [E800-E]
0, 1 1 1
*6
2
Pr.1400 to Pr.1499
Minimum Initial 3
Pr. Refer Customer
Function Pr. Name Setting range setting value*1
group to page setting
increments Gr.1 Gr.2
— 1412 C135
Motor induced voltage
constant (phi f) exponent
0 to 2, 9999 1 9999 308 4
Second motor induced
— 1413 C235 voltage constant (phi f) 0 to 2, 9999 1 9999 308
exponent
Ethernet communication *6
5
1424 N650 1 to 239 1 1
network number
Ethernet communication *6
1425 N651 1 to 120 1 1
station number
Link speed and duplex mode
6
1426 N641 0 to 4 1 0 *6
selection
Ethernet function selection
[E800-EPA]
1427 N630 Ethernet function selection 1 502, 5000 to 5002,
5006 to 5008, 5010 to
1 5001 *6
7
5013, 44818, 45237, *6
1428 N631 Ethernet function selection 2 1 45237
45238, 47808, 61450,
9999
[E800-EPB] *6
8
1429 N632 Ethernet function selection 3 1 45238
502, 5000 to 5002,
5006 to 5008, 5010 to
Ethernet function selection 4 5013, 34962, 45237,
1430 N633
45238, 61450, 9999
1 9999 *6
9
Ethernet signal loss *6
1431 N643 0 to 3 1 3
detection function selection
1432 N644
Ethernet communication
check time interval
0 to 999.8 s, 9999 0.1 s 1.5 *6
10
3. Parameters
3.1 Parameter list (by parameter number)
69
Minimum Initial
Pr. value*1 Refer Customer
Function Pr. Name Setting range setting
group to page setting
increments Gr.1 Gr.2
1434 N600 Ethernet IP address 1 0 to 255 1 192 *6
70 3. Parameters
3.1 Parameter list (by parameter number)
Minimum Initial
Pr. value*1 Refer Customer
Function Pr.
group
Name Setting range setting
increments Gr.1 Gr.2
to page setting 1
Load characteristics
1480 H520 0, 1 (2 to 5, 81 to 85) 1 0 219
measurement mode
1481 H521
Load characteristics load
reference 1
0% to 400%, 8888,
9999
0.1% 9999 219 2
Load characteristics load 0% to 400%, 8888,
1482 H522 0.1% 9999 219
reference 2 9999
1483 H523
Load characteristics load
reference 3
0% to 400%, 8888,
9999
0.1% 9999 219 3
Load characteristics fault detection
1485 H525
Load characteristics load 0% to 400%, 8888,
0.1% 9999 219 4
reference 5 9999
Load characteristics
1486 H526 0 to 590 Hz 0.01 Hz 60 Hz 50 Hz 219
maximum frequency
1487 H527
Load characteristics
0 to 590 Hz 0.01 Hz 6 Hz 219
5
minimum frequency
Upper limit warning detection
1488 H531 0% to 400%, 9999 0.1% 20% 219
width
1489 H532
Lower limit warning
0% to 400%, 9999 0.1% 20% 219
6
detection width
Upper limit fault detection
1490 H533 0% to 400%, 9999 0.1% 9999 219
width
Lower limit fault detection 7
1491 H534 0% to 400%, 9999 0.1% 9999 219
width
Load status detection signal
1492 H535 delay time / load reference 0 to 60 s 0.1 s 1s 219
measurement waiting time 8
Alphabet (calibration parameters, etc.)
Pr.
Minimum Initial
Refer Customer
9
Function Pr. Name Setting range setting value*1
group to page setting
increments Gr.1 Gr.2
FM terminal calibration
C0 M310
[E800-1]
— — — 241
10
AM terminal calibration
C1 M320 — — — 241
[E800-4][E800-5]
Terminal 2 frequency setting
C2 T200 0 to 590 Hz 0.01 Hz 0 Hz 273
bias frequency
Terminal 2 frequency setting
C3 T201 0% to 300% 0.1% 0% 273
bias
Terminal 2 frequency setting
125 T202 0 to 590 Hz 0.01 Hz 60 Hz 50 Hz 273
gain frequency
Terminal 2 frequency setting
Calibration parameter
3. Parameters
3.1 Parameter list (by parameter number)
71
Minimum Initial
Pr. value*1 Refer Customer
Function Pr. Name Setting range setting
group to page setting
increments Gr.1 Gr.2
C42 A630 PID display bias coefficient 0 to 500, 9999 0.01 9999 342
Clear parameters PID display
C43 A631 PID display bias analog value 0% to 300% 0.1% 20% 342
C44 A632 PID display gain coefficient 0 to 500, 9999 0.01 9999 342
C45 A633 PID display gain analog value 0% to 300% 0.1% 100% 342
PR.CL Parameter clear (0), 1 1 0 398
ALLC All parameter clear (0), 1 1 0 398
72 3. Parameters
3.1 Parameter list (by parameter number)
3.2 Use of a function group number for the 1
identification of parameters
2
A parameter identification number shown on the PU can be switched from a parameter number to a function group number.
As parameters are grouped by function and displayed by the group, the related parameters can be set continually at a time.
0
The setting of parameter identification number remains the same as
the last setting. 4
The parameter number is used for the identification of parameters,
1
and displayed in numerical order.
2
The function group number is used for the identification of
parameters, and displayed in alphanumeric order.
5
Operating procedure
1. Turning ON the power of the inverter
6
The operation panel is in the monitor mode.
3. Selecting a parameter 8
Turn the setting dial or press the UP/DOWN key until "Pr.MD" (Group parameter setting) appears.
Press the SET key to confirm the selection. "0" (initial value) will appear.
9
4. Selecting the use of the function group number
Turn the setting dial or press the UP/DOWN key to change the value to "2" (function group number). Press the SET
key to confirm the Group parameter setting. "2" blinks after the setting is completed.
10
Selecting a parameter by function group number to change its setting
The following shows the procedure to change the setting of P.H400 (Pr.1) Maximum frequency.
Operating procedure
1. Turning ON the power of the inverter
The operation panel is in the monitor mode.
5. Selecting a parameter
Turn the setting dial or press the UP/DOWN key until "H400" (P.H400 Maximum frequency) appears. Press the
SET key to display the present set value. "120.0" (initial value) appears.
3. Parameters
3.2 Use of a function group number for the identification of parameters
73
6. Changing the setting value
Turn the setting dial or press the UP/DOWN key to change the value to "60.00". Press the SET key to confirm the
setting. "60.00" blinks after the setting is completed.
74 3. Parameters
3.2 Use of a function group number for the identification of parameters
3.3 Parameter list (by function group number)
1
E: Environment setting Pr. group Pr. Name
Refer
3. Parameters
3.3 Parameter list (by function group number)
75
Refer Refer
Pr. group Pr. Name Pr. group Pr. Name
to page to page
Automatic acceleration/ 171, 198,
F500 292 Second electronic thermal O/L
deceleration 320 H010 51 299,
relay
F510 61 Reference current 171 308
Reference value at Cooling fan operation
F511 62 171 H100 244 203
acceleration selection
Reference value at Earth (ground) fault detection
F512 63 171 H101 249 204
deceleration at start
Acceleration/deceleration Inverter output fault detection
F513 293 171 H182 631 205
separate selection enable/disable selection
Output phase loss protection
H200 251 207
selection
D: Parameters for the setting of H300 65 Retry selection 208
operation command and H301 67
Number of retries at fault
208
occurrence
frequency command H302 68 Retry waiting time 208
Parameters for setting the command source to the inverter, H303 69 Retry count display erase 208
and the motor driving frequency and torque. H400 1 Maximum frequency Simple 211
Refer H401 2 Minimum frequency Simple 211
Pr. group Pr. Name
to page High speed maximum
Operation mode H402 18 211
174, frequency
D000 79
selection Simple 184 Speed deviation excess 109,
H416 285
Communication startup mode detection frequency 320
D001 340 184
selection H420 31 Frequency jump 1A 212
Communication operation H421 32 Frequency jump 1B 212
D010 338 185
command source H422 33 Frequency jump 2A 212
Communication speed H423 34 Frequency jump 2B 212
D011 339 185
command source
H424 35 Frequency jump 3A 212
NET mode operation command
D012 550 185 H425 36 Frequency jump 3B 212
source selection
Stall prevention operation 100,
PU mode operation command H500 22
D013 551 185 level (Torque limit level) 214
source selection
Stall prevention operation
Reverse rotation prevention H501 156 214
D020 78 193 selection
selection
Second stall prevention
100, H600 48 214
D030 811 Set resolution switchover operation level
226
Stall prevention operation
D200 15 Jog frequency 194
H610 23 level compensation factor at 214
Multi-speed setting (high double speed
D301 4 195
speed) Simple Stall prevention operation
H611 66 214
Multi-speed setting (middle reduction starting frequency
D302 5 195
speed) Simple Stall prevention operation
H630 277 324
current switchover
Multi-speed setting (low
D303 6 195 Voltage reduction selection
speed) Simple
H631 154 during stall prevention 214
D304 to Multi-speed setting (speed 4 to operation
24 to 27 195
D307 speed 7)
H103 997 Fault initiation 206
D308 to 232 to Multi-speed setting (speed 8 to
195 H800 374 Overspeed detection level 224
D315 239 speed 15)
Load characteristics
Torque command source H520 1480 219
D400 804 117 measurement mode
selection
Load characteristics load
D401 805 Torque command value (RAM) 117 H521 1481 219
reference 1
Torque command value (RAM,
D402 806 117 Load characteristics load
EEPROM) H522 1482 219
reference 2
Load characteristics load
H523 1483 219
H: Protective function parameter reference 3
Load characteristics load
Parameters to protect the motor and the inverter. H524 1484 219
reference 4
Refer Load characteristics load
Pr. group Pr. Name H525 1485 219
to page reference 5
198, Load characteristics maximum
Electronic thermal O/L H526 1486 219
H000 9 299, frequency
relay Simple Load characteristics minimum
308 H527 1487 219
frequency
76 3. Parameters
3.3 Parameter list (by function group number)
Refer Refer
Pr. group Pr. Name Pr. group Pr. Name
to page to page
Upper limit warning detection Power saving rate reference
1
H531 1488 219 M203 895 244
width value
Lower limit warning detection M204 896 Power unit cost 244
H532 1489 219
width
Upper limit fault detection
M205 897
Power saving monitor average
time
244 2
H533 1490 219
width Power saving cumulative
M206 898 244
Lower limit fault detection monitor clear
H534 1491 219
width
Load status detection signal
M207 899
Operation time rate (estimated
value)
244 3
H535 1492 delay time / load reference 219 FM terminal function selection
measurement waiting time M300 54 237
[E800-1]
M301 158
AM terminal function selection
237 4
M: Item and output signal for [E800-4][E800-5]
FM terminal calibration [E800-
monitoring M310 C0
1]
241
M021 563
Energization time carrying-
228
M410 313*3 DO0 output selection 250
8
over times M411 314 *3 DO1 output selection 250
Monitor decimal digits
M022 268 228 M412 315*3 DO2 output selection 250
selection
M023 891
Cumulative power monitor 228,
M413 316*3 DO3 output selection 250
9
digit shifted times 244 M414 317*3 DO4 output selection 250
M030 171 Operation hour meter clear 228 M415 318*3 DO5 output selection 250
Operating time carrying-over
M031 564
times
228 M416 319 *3 DO6 output selection 250
10
Frequency monitoring
M420 320*3 RA1 output selection 250
M040 55*1 237
reference M421 321*3 RA2 output selection 250
M041 56*1 Current monitoring reference 237 M422 322*3 RA3 output selection 250
M042 866 Torque monitoring reference 228 100,
M430 157 OL signal output timer
Analog input display unit 214
M043 241 273
switchover M431 289 Inverter output terminal filter 250
Monitor negative output 228, Output current detection
M044 290 M433 166 260
selection 237 signal retention time
M050 1106 Torque monitor filter 228 M440 870 Speed detection hysteresis 257
M051 1107 Running speed monitor filter 228 M441 41 Up-to-frequency sensitivity 257
Excitation current monitor M442 42 Output frequency detection 257
M052 1108 228
filter Output frequency detection for
Operation panel main monitor M443 43 257
M100 52 228 reverse rotation
selection M446 865 Low speed detection 257
Operation panel monitor M451 193 NET Y1 output selection 250
M101 774 228
selection 1
M452 194 NET Y2 output selection 250
Operation panel monitor
M102 775 228 M453 195 NET Y3 output selection 250
selection 2
M454 196 NET Y4 output selection 250
Operation panel monitor
M103 776 228 M460 150 Output current detection level 260
selection 3
Operation panel setting dial Output current detection
M104 992 228 M461 151 260
push monitor selection signal delay time
M200 892 Load factor 244 M462 152 Zero current detection level 260
Energy saving monitor M463 153 Zero current detection time 260
M201 893 244
reference (motor capacity) Output current detection
M464 167 260
Control selection during operation selection
M202 894 commercial power-supply 244 M470 864 Torque detection 262
operation
3. Parameters
3.3 Parameter list (by function group number)
77
T: Multi-function input terminal Pr. group Pr. Name
Refer
to page
parameters T753 187 NET X3 input selection 283
Parameters for the setting of the input terminals via which T754 188 NET X4 input selection 283
commands are given to the inverter. T755 189 NET X5 input selection 283
Refer
Pr. group Pr. Name
to page C: Motor constant parameters
T000 73 Analog input selection 266 Parameters for the applied motor setting.
T001 267 Terminal 4 input selection 266
Refer
T002 74 Input filter time constant 271 Pr. group Pr. Name
to page
T003 822 Speed setting filter 1 271
294,
T004 826 Torque setting filter 1 271 C100 71 Applied motor 299,
T005 832 Speed setting filter 2 271 308
T006 836 Torque setting filter 2 271 86, 299,
C101 80 Motor capacity
T007 849 Analog input offset adjustment 271 308
Terminal 2 frequency setting 86, 299,
T022 125 273 C102 81 Number of motor poles
gain frequency Simple 308
198,
100,
Terminal 4 function C103 9 Rated motor current Simple 299,
T040 858 214,
assignment 308
270
86, 299,
Terminal 4 frequency setting C104 83 Rated motor voltage
T042 126 273 308
gain frequency Simple
86, 299,
Terminal 2 frequency setting C105 84 Rated motor frequency
T200 C2 273 308
bias frequency C106 702 Maximum motor frequency 308
Terminal 2 frequency setting C107 707 Motor inertia (integer) 308
T201 C3 273
bias
C108 724 Motor inertia (exponent) 308
Terminal 2 frequency setting
T202 125 273 299,
gain frequency
C110 96 Auto tuning setting/status 308,
Terminal 2 frequency setting 358
T203 C4 273
gain
C111 95 Online auto tuning selection 315
Terminal 4 frequency setting
T400 C5 273 299,
bias frequency
C120 90 Motor constant (R1) 308,
Terminal 4 frequency setting 358
T401 C6 273
bias
C121 91 Motor constant (R2) 299
Terminal 4 frequency setting
T402 126 273 Motor constant (L1)/d-axis 299,
gain frequency C122 92
inductance (Ld) 308
Terminal 4 frequency setting
T403 C7 273 Motor constant (L2)/q-axis 299,
gain C123 93
inductance (Lq) 308
Terminal 4 bias command
T410 C38 273 C124 94 Motor constant (X) 299
(torque/magnetic flux)
C125 82 Motor excitation current 299
Terminal 4 bias (torque/
T411 C39 273 Torque current/Rated PM 299,
magnetic flux) C126 859
motor current 308
Terminal 4 gain command
T412 C40 273 Induced voltage constant (phi
(torque/magnetic flux) C130 706 308
f)
Terminal 4 gain (torque/
T413 C41 278 C131 711 Motor Ld decay ratio 308
magnetic flux)
STF/DI0 terminal function C132 712 Motor Lq decay ratio 308
T700 178 283
selection C133 725 Motor protection current level 308
STR/DI1 terminal function Motor induced voltage
T701 179 283 C135 1412 308
selection constant (phi f) exponent
T702 180 RL terminal function selection 283 Lq tuning target current
C150 1002 308
adjustment coefficient
T703 181 RM terminal function selection 283 Starting resistance tuning
C182 717 308
compensation coefficient 1
T704 182 RH terminal function selection 283
Starting magnetic pole
MRS terminal function C185 721 308
T709 183 283 position detection pulse width
selection
Starting resistance tuning
RES terminal function C188 720 308
T711 184 283 compensation coefficient
selection
C200 450 Second applied motor 294
MRS/X10 terminal input
T720 17 287 299,
selection C201 453 Second motor capacity
308
T740 699 Input terminal filter 283
299,
T751 185 NET X1 input selection 283 C202 454 Number of second motor poles
308
T752 186 NET X2 input selection 283
78 3. Parameters
3.3 Parameter list (by function group number)
Refer Refer
Pr. group Pr. Name Pr. group Pr. Name
to page to page
198, Automatic acceleration/ 171,
1
A110 292
C203 51 Rated second motor current 299, deceleration 320
308 Stop-on-contact control
A200 270 324
C204 456 Rated second motor voltage
299,
308
selection
Stop-on contact excitation
2
299, A205 275 current low-speed scaling 324
C205 457 Rated second motor frequency
308 factor
C206 743
Second motor maximum
frequency
308 A206 276
PWM carrier frequency at stop-
on contact
324 3
C207 744 Second motor inertia (integer) 308 A300 592 Traverse function selection 327
Second motor inertia A301 593 Maximum amplitude amount 327
C208 745 308
(exponent)
A302 594
Amplitude compensation
327 4
299, amount during deceleration
Second motor auto tuning
C210 463 308, Amplitude compensation
setting/status A303 595 327
358 amount during acceleration
C211 574
Second motor online auto
315 A304 596 Amplitude acceleration time 327 5
tuning A305 597 Amplitude deceleration time 327
299, Parameter for manufacturer setting. Do not
C220 458 Second motor constant (R1) 308, A600 759
set.
358
329, 6
C221 459 Second motor constant (R2) 299 A601 131 PID upper limit
344
Second motor constant (L1) / 299,
C222 460 329,
d-axis inductance (Ld) 308 A602 132 PID lower limit
C223 461
Second motor constant (L2) / 299, A603 553 PID deviation limit
344
329
7
q-axis inductance (Lq) 308
A604 554 PID signal operation selection 329
C224 462 Second motor constant (X) 299
Integral stop selection at
Second motor excitation A607 1015 329
C225 455
current
299 limited frequency 8
329,
Second motor torque current/ 299, A610 128 PID action selection
C226 860 344
Rated PM motor current 308
329,
C230 738
Second motor induced voltage
constant (phi f)
308
A611 133 PID action set point
344 9
PID control automatic
C231 739 Second motor Ld decay ratio 308 A612 127 329
switchover frequency
C232 740 Second motor Lq decay ratio 308
329,
C233 746
Second motor protection
current level
308
A613 129 PID proportional band
344 10
329,
Second motor induced voltage A614 130 PID integral time
C235 1413 308 344
constant (phi f) exponent 329,
Second motor starting A615 134 PID differential time
344
C282 741 resistance tuning 308
Output interruption detection
compensation coefficient 1 A621 575 329
time
Second motor magnetic pole
C285 742 308 Output interruption detection
detection pulse width A622 576 329
level
Starting resistance tuning Output interruption cancel
C288 737 308
compensation coefficient 2 A623 577 329
level
PID set point/deviation input 329,
A: Application parameters A624 609
selection 344
Parameters for the setting of a specific application. PID measured value input 329,
A625 610
selection 344
Refer A630 C42 PID display bias coefficient 342
Pr. group Pr. Name
to page A631 C43 PID display bias analog value 342
A100 278 Brake opening frequency 320 A632 C44 PID display gain coefficient 342
A101 279 Brake opening current 320 A633 C45 PID display gain analog value 342
Brake opening current Automatic restart after 351,
A102 280 320
detection time A700 162 instantaneous power failure 356,
A103 281 Brake operation time at start 320 selection 358
A104 282 Brake operation frequency 320 Rotation direction detection
A701 299 351
A105 283 Brake operation time at stop 320 selection at restarting
Brake opening current 351,
A108 639 320 A702 57 Restart coasting time
selection 356
Brake operation frequency A703 58 Restart cushion time 351
A109 640 320
selection Stall prevention operation
A710 165 351
level for restart
3. Parameters
3.3 Parameter list (by function group number)
79
Refer Refer
Pr. group Pr. Name Pr. group Pr. Name
to page to page
299, Stop mode selection at *2
A711 298 Frequency search gain N013 502
358 communication error
299, Operation frequency during *2
A712 560 Second frequency search gain N014 779
358 communication error
A730 261 Power failure stop selection 146 PU communication station *2
N020 117
PLC function operation number
A800 414 364
selection N021 118 PU communication speed *2
A916 1033 Analog source selection (7ch) 366 N080 343 Communication error count *2
A917 1034 Analog source selection (8ch) 366 Frequency command sign
N100 541 *2
A918 1035 Analog trigger channel 366 selection [E800-E]
Analog trigger operation CC-Link extended setting
A919 1036 366 N103 544 *2
selection [E800-E]
A920 1037 Analog trigger level 366 N600 1434 Ethernet IP address 1 *2
A930 1038 Digital source selection (1ch) 366 N601 1435 Ethernet IP address 2 *2
A931 1039 Digital source selection (2ch) 366 *2
N602 1436 Ethernet IP address 3
A932 1040 Digital source selection (3ch) 366
N603 1437 Ethernet IP address 4 *2
A933 1041 Digital source selection (4ch) 366
N610 1438 Subnet mask 1 *2
A934 1042 Digital source selection (5ch) 366
A935 1043 Digital source selection (6ch) 366 N611 1439 Subnet mask 2 *2
A936 1044 Digital source selection (7ch) 366 N612 1440 Subnet mask 3 *2
A937 1045 Digital source selection (8ch) 366 *2
N613 1441 Subnet mask 4
A938 1046 Digital trigger channel 366
N620 442 Default gateway address 1 *2
Digital trigger operation
A939 1047 366 N621 443 Default gateway address 2 *2
selection
N622 444 Default gateway address 3 *2
80 3. Parameters
3.3 Parameter list (by function group number)
Refer Refer
Pr. group Pr. Name Pr. group Pr. Name
to page to page
Extended setting for Ethernet SF-PR slip amount adjustment
1
*2 G061 674 381
N648 1457 signal loss detection function gain [200 V class / 400 V class]
selection DC injection brake operation
G100 10 382
N649 1399
Inverter identification enable/
disable selection [E800-E]
*2 frequency
DC injection brake operation
2
G101 11 382
Ethernet communication *2 time
N650 1424
network number G103 850 Brake operation selection 382
N651 1425
Ethernet communication
station number
*2 G106 250 Stop selection 384 3
Special regenerative brake
*2 G107 70 386
N660 1442 Ethernet IP filter address 1 duty
N661 1443 Ethernet IP filter address 2 *2 DC injection brake operation
N662 1444 Ethernet IP filter address 3 *2
G110 12
voltage
382
4
Regeneration avoidance
N663 1445 Ethernet IP filter address 4 *2 G120 882 390
operation selection
Ethernet IP filter address 2 Regeneration avoidance
5
N664 1446 *2
range specification G121 883 390
operation level
Ethernet IP filter address 3 *2 Regeneration avoidance
N665 1447
range specification G123 885 compensation frequency limit 390
Ethernet IP filter address 4 value
N666 1448
range specification
*2
G124 886
Regeneration avoidance
390
6
Ethernet command source *2
voltage gain
N670 1449
selection IP address 1 Regeneration avoidance
G125 665 390
Ethernet command source frequency gain
N671 1450
selection IP address 2
*2
G200 800 Control method selection 86 7
Ethernet command source *2 G203 245 Rated slip 393
N672 1451
selection IP address 3 Slip compensation time
G204 246 393
N673 1452
Ethernet command source
selection IP address 4
*2 constant
Constant output range slip
8
Ethernet command source G205 247 393
compensation selection
N674 1453 selection IP address 3 range *2
Constant output range torque 100,
specification G210 803
Ethernet command source
characteristic selection 117
9
G211 820 Speed control P gain 1 107
N675 1454 selection IP address 4 range *2
G212 821 Speed control integral time 1 107
specification
Torque control P gain 1
N681 1124
Station number in inverter-to-
inverter link [E800-E]
*2 G213 824 (current loop proportional 122 10
gain)
Number of inverters in
*2 Torque control integral time 1
N682 1125 inverter-to-inverter link system G214 825 122
(current loop integral time)
[E800-E]
Second motor control method
G300 451 86
selection
(G) Control parameters G311 830 Speed control P gain 2 107
Parameters for motor control. G312 831 Speed control integral time 2 107
Torque control P gain 2
Refer
Pr. group Pr. Name G313 834 (current loop proportional 122
to page
gain)
G000 0 Torque boost Simple 374 Torque control integral time 2
G314 835 122
G001 3 Base frequency Simple 376 (current loop integral time)
G002 19 Base frequency voltage 376 G400 286 Droop gain 394
G003 14 Load pattern selection 378 G401 287 Droop filter time constant 394
G010 46 Second torque boost 374 G410 653 Speed smoothing control 395
G011 47 Second V/F (base frequency) 376 Speed smoothing cutoff
G411 654 395
frequency
Energy saving control
G030 60 380 Speed control gain (Advanced
selection G932 89 90
magnetic flux vector)
SF-PR slip amount adjustment
G060 673 operation selection [200 V 381 Second motor speed control
G942 569 90
class / 400 V class] gain
*1 For the Ethernet model, the setting is available only when the *3 Available when the PLC function is enabled. (Pr.313 to
FR-A8AY is installed. Pr.315 are always available for settings in the Ethernet
*2 For details, refer to the Instruction Manual (Communication). model.)
*4 For the standard model, the setting is available only when a
communication option is installed.
3. Parameters
3.3 Parameter list (by function group number)
81
3.4 Parameter initial value groups
• Initial values of parameters of the FR-E800 differ depending on the parameter initial value group. In this Instruction Manual,
Gr.1 indicates the parameter initial value group 1, and Gr.2 indicates the parameter initial value group 2.
• FR-E800 inverters are divided into two groups as shown in the following table.
Parameter initial value groups Model Specification
FR-E800-1 RS-485 communication, terminal FM
Group 1 (Gr.1) FR-E800-5 RS-485 communication, terminal AM
FR-E800-EPA Ethernet communication (Protocol group A)
FR-E800-4 RS-485 communication, terminal AM
Group 2 (Gr.2)
FR-E800-EPB Ethernet communication (Protocol group B)
• The initial values of the following parameters differ depending on the parameter initial value group.
Initial value Refer to
Pr. Name
Gr.1 Gr.2 page
3 Base frequency 60 Hz 50 Hz 376
4 Multi-speed setting (high speed) 60 Hz 50 Hz 195
19 Base frequency voltage 9999 8888 376
20 Acceleration/deceleration reference frequency 60 Hz 50 Hz 158
55 Frequency monitoring reference 60 Hz 50 Hz 228
66 Stall prevention operation reduction starting frequency 60 Hz 50 Hz 214
125 Terminal 2 frequency setting gain frequency 60 Hz 50 Hz 273
126 Terminal 4 frequency setting gain frequency 60 Hz 50 Hz 273
249 Earth (ground) fault detection at start 0 1 204
301 BCD input gain 60 Hz 50 Hz *1
*1 The parameter is available when the plug-in option (FR-A8AX) is installed. For details, refer to the FR-A8AX Instruction Manual.
*2 For details, refer to the Instruction Manual (Communication).
82 3. Parameters
3.4 Parameter initial value groups
CHAPTER 4
CHAPTER 4 Control Method
4
10
83
4 Control Method
V/F control (initial setting), Advanced magnetic flux vector control, Real sensorless vector control, and PM sensorless vector
control are available with this inverter.
V/F control
The inverter controls the output frequency (F) and the output voltage (V) so that the ratio of frequency to voltage (V/F) is kept
constant when the frequency is changed.
NOTE
• Advanced magnetic flux vector control requires the following conditions.
If these conditions are not satisfied, select V/F control. Otherwise, malfunctions such as insufficient torque, uneven rotation
may occur.
• For the motor capacity, the rated motor current should be equal to or less than the rated inverter current. (Note that the motor
rated current should be 0.4 kW or higher (0.1 kW or higher for the 200 V class).)
If a motor with substantially low rated current compared with the inverter rated current is used, speed and torque accuracies
may deteriorate due to torque ripples, etc. Set the rated motor current to about 40% or higher of the inverter rated current.
• The motor described in the following table is used.
Motor Condition
Mitsubishi Electric standard efficiency motor (SF-JR)
Mitsubishi Electric high-efficiency motor (SF-HR)
Offline auto tuning is not required.
Mitsubishi Electric constant-torque motor (SF-JRCA 4P / SF-HRCA)
Mitsubishi Electric high-performance energy-saving motor (SF-PR)
Other motors (other manufactures' motors) Offline auto tuning is required.
• Single-motor operation (one motor to one inverter) is performed.
• The wiring length from inverter to motor is 30 m or less. (When the wiring length exceeds 30 m, perform offline auto tuning with
the wiring in place.)
84 4. Control Method
NOTE
• Real sensorless vector control requires the following conditions. 1
If these conditions are not satisfied, select V/F control. Otherwise, malfunctions such as insufficient torque, uneven rotation
may occur.
• For the motor capacity, the rated motor current should be equal to or less than the rated inverter current. (Note that the motor
rated current should be 0.4 kW or higher (0.1 kW or higher for the 200 V class).)
2
If a motor with substantially low rated current compared with the inverter rated current is used, speed and torque accuracies
may deteriorate due to torque ripples, etc. Set the rated motor current to about 40% or higher of the inverter rated current.
• Offline auto tuning is performed. 3
Offline auto tuning is required under Real sensorless vector control even when the Mitsubishi Electric motor is used since the
wiring length affects the operation.
• Single-motor operation (one motor to one inverter) is performed.
• A surge voltage suppression filter (FR-ASF/FR-BMF) is not used. 4
NOTE
10
• The PM sensorless vector control requires the following conditions.
• For the motor capacity, the rated motor current should be equal to or less than the rated inverter current. (Note that the motor
rated current should be 0.4 kW or higher (0.1 kW or higher for the 200 V class).)
If a motor with substantially low rated current compared with the inverter rated current is used, speed and torque accuracies
may deteriorate due to torque ripples, etc. Set the rated motor current to about 40% or higher of the inverter rated current.
• Offline auto tuning is performed.
• Single-motor operation (one motor to one inverter) is performed.
• The overall wiring length with the motor must be 100 m or less. (For the wiring length, refer to the Instruction Manual
(Connection).)
• A surge voltage suppression filter (FR-ASF/FR-BMF) is not used.
4. Control Method
85
4.1 Changing the control method and mode
Set the control method and the control mode.
V/F control, Advanced magnetic flux vector control, Real sensorless vector control, and PM sensorless vector control are the
control methods available for selection.
The available control modes are speed control and torque control modes.
• Select a control method and a control mode by setting Pr.800 (Pr.451) Control method selection.
• The control mode can be switched using a mode switching signal (MC).
Setting the motor capacity and the number of motor poles (Pr.80, Pr.81)
• Motor specifications (the motor capacity and the number of motor poles) must be set to select Advanced magnetic flux
vector control, Real sensorless vector control, or PM sensorless vector control.
• Set the motor capacity (kW) in Pr.80 Motor capacity and set the number of motor poles in Pr.81 Number of motor poles.
86 4. Control Method
4.1 Changing the control method and mode
• To enable the control method and the control mode selected in Pr.800 (Pr.451), the condition to start operation must be
satisfied as shown in the following table. Otherwise the operation does not start due to the setting error (SE) alarm when
the start signal is input.
1
Condition to start operation
Pr.800
setting
Pr.451
setting
Control method Control mode
Pr.80 (Pr.453),
Pr.81 (Pr.454)
Pr.71 MC signal 2
(Pr.450)
setting
Real sensorless vector control /
10 Speed control —*1 —
11
PM sensorless vector control
Torque control —
3
Induction ON: Torque
Real sensorless vector control Speed control / torque
12 Other than 9999 motor control OFF:
control switchover
NOTE
• Since current is not detected and voltage is not output, monitors related to current and voltage such as output current and
output voltage, etc. and output signals do not function.
Parameters referred to
Pr.178 to Pr.189 (Input terminal function selection)page 283
Pr.190 to Pr.196 (Output terminal function selection)page 250
4. Control Method
4.1 Changing the control method and mode
87
×: Disabled (0 is displayed at any time.)
Δ: A cumulative total before the test operation is displayed.
—: Not available
Monitoring on the Output via Monitoring on the Output via
Monitor item Monitor item
operation panel FM/AM operation panel FM/AM
Output frequency ○ ○ User monitor 1 ○ —
Output current × × User monitor 2 ○ —
Output voltage × × User monitor 3 ○ —
Communication station
Fault indication ○ — ○ —
number (PU port)
Frequency setting value ○ ○ Station number (CC-Link) ○ —
Motor speed ○ ○ Energy saving effect ○ ○
Motor torque × × Cumulative energy saving Δ —
Converter output voltage ○ ○ PID set point ○ ○
Brake duty × × PID measured value ○ ○
Electronic thermal O/L relay
load factor ×*1 ×*1 PID deviation ○ —
*1 When the inverter operation is switched to the test operation, the indication is changed to 0. When PM sensorless vector control is selected again
after the test operation, the output current peak value and the electronic thermal relay load factor from the last operation are displayed.
*2 When the inverter operation is switched to the test operation, the accumulated thermal value is reduced because the output current is considered
as 0.
Parameters referred to
Operation panel main monitor selectionpage 228
Pr.158 AM terminal function selectionpage 250
Changing the control method with external terminals (RT signal, X18
signal)
• Control method (V/F control, Advanced magnetic flux vector control, Real sensorless vector control) can be switched using
external terminals.
The control method can be switched using either the Second function selection (RT) signal or the V/F switchover (X18)
signal.
• Set the second motor in Pr.450 Second applied motor and set the second motor's control method in Pr.451 Second
motor control method selection. Turning ON the RT signal or X18 signal enables the second function, enabling the
switchover of the control method.
88 4. Control Method
4.1 Changing the control method and mode
• To input the RT signal, set "3" in any parameter from Pr.178 to Pr.189 (Input terminal function selection) to assign the
function.
To input the X18 signal, set "18" in any parameter from Pr.178 to Pr.189 (Input terminal function selection) to assign
1
the function.
NOTE
7
• The RT signal is a second function selection signal. The RT signal also enables other second functions. (Refer to page 289.)
• When V/F control is set using the V/F switchover (X18) signal, the second functions are selected at the same time.
• The control method could be changed by external terminals (RT signal, X18 signal) while the inverter is stopped. If a signal is 8
switched during the operation, the control method changes after the inverter stops.
—: No function
NOTE
• Switching between the speed control and the torque control is always enabled regardless of the motor status: in a stop, in
running, or in DC injection brake.
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.178 to Pr.189 (Input terminal function selection)page 283
Pr.450 Second applied motorpage 294
Pr.804 Torque command source selectionpage 117
Pr.807 Speed limit selectionpage 120
Pr.810 Torque limit input method selectionpage 100
Pr.858 Terminal 4 function assignmentpage 270
4. Control Method
4.1 Changing the control method and mode
89
4.2 Selecting the Advanced magnetic flux vector
control
Magnetic flux
• To use the Advanced magnetic flux vector control, select the control method using Pr.800, and the motor type and specification
using Pr.71, Pr.80, and Pr.81.
2. Change the control method to Advanced magnetic flux vector control (Pr.800 = "20").
Other manufacturer's
constant-torque motor
10 (13) Offline auto tuning is required.*2
5. Set the motor capacity and number of motor poles (Pr.80, Pr.81). (Refer to page 86.)
Operation does not start when the setting value is "9999" (initial value).
6. Set the rated motor voltage and frequency (Pr.83, Pr.84). (Refer to page 299.)
As required
• Perform the offline auto tuning (Pr.96). (Refer to page 299.)
90 4. Control Method
4.2 Selecting the Advanced magnetic flux vector control
• Select the online auto tuning (Pr.95). (Refer to page 315.)
NOTE 1
• To perform driving in a better accuracy, perform offline auto tuning, then set the online auto tuning, and select Real sensorless
vector control.
• Under this control, rotations are more likely to be uneven than under V/F control. (This control method is not suitable for
grinder, wrapping machine, etc., which require even rotation at a low speed.)
2
• When the inverter is operated with a surge voltage suppression filter (FR-ASF-H/FR-BMF-H) installed between the inverter
and the motor, the output torque may decrease.
3
Keeping the motor speed constant when the load fluctuates (speed
control gain) 4
Initial Setting
Pr. Name Description
value range
89
Speed control gain 0% to 200%
Makes adjustments to keep the motor speed constant during variable load
operation under Advanced magnetic flux vector control. The reference
5
(Advanced magnetic flux 9999
G932 value is 100%.
vector)
9999 The gain set by Pr.71. (The gain set in accordance with the motor.)
Speed 10
Driving two motors under Advanced magnetic flux vector control
• Turning ON the Second function selection (RT) signal enables the second motor operation.
• Set a second motor in Pr.450 Second applied motor. (In the initial setting, "9999" (no second applied motor) is selected.
Refer to page 294.)
Function RT signal-ON (second motor) RT signal-OFF (first motor)
Applied motor Pr.450 Pr.71
Motor capacity Pr.453 Pr.80
Number of motor poles Pr.454 Pr.81
Speed control gain (Advanced magnetic flux
Pr.569 Pr.89
vector)
Control method selection Pr.451 Pr.800
NOTE
• The RT signal is a Second function selection signal. The RT signal also enables other second functions. (Refer to page 289.)
To input the RT signal, set "3" in any parameter from Pr.178 to Pr.189 (Input terminal function selection) to assign the
function.
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.71, Pr.450 Applied motorpage 294
Pr.800, Pr.451 Control method selectionpage 86
4. Control Method
4.2 Selecting the Advanced magnetic flux vector control
91
4.3 Selecting the PM sensorless vector control
PM
NOTE
• Make sure to set Pr.998 before setting other parameters. If the Pr.998 setting is changed after setting other parameters, some
of those parameters are initialized too. (Refer to the "List of the target parameters for the motor parameter initialization".)
• To change back to the parameter settings required to drive an induction motor, perform Parameter clear or All parameter clear.
• If the setting of Pr.998 PM parameter initialization is changed from "8009 or 9009 (rotations per minute)" to "8109 or 9109
(frequency)", all the relevant parameters are initialized.
The purpose of Pr.998 is not to change the display units. Use Pr.53 Frequency / rotation speed unit switchover to change
the display units between rotations per minute and frequency. Using Pr.53 enables switching the unit between rotations per
minute and frequencies without initializing the setting of the motor parameters.
• The PM parameter initialization (Pr.998) changes parameter settings for the first motor. When a PM motor is used as the
second motor, parameters for the second motor must be set individually.
92 4. Control Method
4.3 Selecting the PM sensorless vector control
• Performing Parameter clear or All parameter clear resets these parameter settings to the settings required to drive an
induction motor.
1
Setting
PM motor
PM motor Setting increments
Induction motor (rotations per
Pr. Name minute)
(frequency)
2
*1
0 (initial value) 8009, 0, 8109,
8009, 9009 8109, 9109
Gr.1 Gr.2 9009 9109
55
switchover
Frequency monitoring reference 60 Hz 50 Hz Pr.84 Pr.84 1 r/min 0.01 Hz
6
56 Current monitoring reference Inverter rated current Pr.859 Pr.859 0.01 A 0.01 A
71 Applied motor 0 — — 1 1
72 PWM frequency selection — 2 2 1 1 7
80 Motor capacity 9999 — — 0.01 kW 0.01 kW
81 Number of motor poles 9999 — — 1 1
84
125
Rated motor frequency
Terminal 2 frequency setting gain
9999 — — 1 r/min 0.01 Hz
8
60 Hz 50 Hz Pr.84 Pr.84 1 r/min 0.01 Hz
(903) frequency
126 Terminal 4 frequency setting gain
60 Hz 50 Hz Pr.84 Pr.84 1 r/min 0.01 Hz
(905)
240
frequency
Soft-PWM operation selection 1 0 0 1 1
9
Maximum motor
Maximum motor
374 Overspeed detection level 9999 rotations per minute 1 r/min 0.01 Hz
frequency + 10 Hz*3
+ 10 Hz *3*4
10
390 % setting reference frequency 60 Hz 50 Hz Pr.84 Pr.84 1 r/min 0.01 Hz
505 Speed setting reference 60 Hz 50 Hz — — 1 r/min 0.01 Hz
Current average value monitor
557 Inverter rated current Pr.859 Pr.859 0.01 A 0.01 A
signal output reference current
800 Control method selection 40 10 10 1 1
820 Speed control P gain 1 60% 30% 30% 1% 1%
821 Speed control integral time 1 0.333 s 0.333 s 0.333 s 0.001 s 0.001 s
Torque control P gain 1 (current loop
824 100% 100% 100% 1% 1%
proportional gain)
Torque control integral time 1
825 5 ms 20 ms 20 ms 0.1 ms 0.1 ms
(current loop integral time)
870 Speed detection hysteresis 0 Hz 0.5 Hz*4 0.5 Hz 1 r/min 0.01 Hz
Regeneration avoidance
885 6 Hz Pr.84 × 10% Pr.84 × 10% 1 r/min 0.01 Hz
compensation frequency limit value
Energy saving monitor reference Motor capacity Motor capacity
893 Inverter rated current 0.01 kW 0.01 kW
(motor capacity) (Pr.80) (Pr.80)
—: Not changed
*1 Gr.1 and Gr.2 are the parameter initial value groups. (Refer to page 82.)
*2 120% for LD rating and 150% for ND rating (Refer to Pr.570 Multiple rating setting on page 134.)
*3 The Pr.702 Maximum motor frequency is used as the maximum motor frequency (rotations per minute). When Pr.702 = "9999" (initial value),
the Pr.84 Rated motor frequency is used as the maximum motor frequency (rotations per minute).
*4 The setting value is converted from frequency to rotations per minute. (It differs according to the number of motor poles.)
NOTE
• When the motor parameter initialization is performed with the setting in units of rotations per minute (Pr.998 = "8009 or 9009"),
the parameters not listed in the table and the monitor items are also set and displayed in rotations per minute.
4. Control Method
4.3 Selecting the PM sensorless vector control
93
Setting for the V/F control by selecting PM parameter initialization on the
operation panel ("PM")
• When the control method is changed from PM sensorless vector control to V/F control, all the parameter settings required to
drive an induction motor are automatically set. (Refer to page 92.)
The following shows the procedure to change the control method from PM sensorless vector control to V/F control by selecting
PM parameter initialization on the operation panel.
Operating procedure
1. Turning ON the power of the inverter
The operation panel is in the monitor mode.
4. PM parameter initialization
Turn the setting dial or press the UP/DOWN key until "PM" (PM parameter initialization) appears.
NOTE
• If PM parameter initialization is selected on the operation panel to set V/F control, the setting of Pr.998 PM parameter
initialization is also changed automatically.
• The changed parameter settings are the same as those when Pr.998 = "0".
94 4. Control Method
4.3 Selecting the PM sensorless vector control
CHAPTER 5
CHAPTER 5 Speed control
4
5.1 Setting procedure of Real sensorless vector control (speed control) .....................................................................98
5.2 Setting procedure of PM sensorless vector control (speed control) .......................................................................99
6
5.3 Setting the torque limit level..................................................................................................................................100
5.4 Performing high-accuracy, fast-response control (gain adjustment for Real sensorless vector control and PM sen-
sorless vector control)107
7
5.5 Avoiding motor overrunning..................................................................................................................................109
5.6 Troubleshooting in the speed control....................................................................................................................110
8
10
95
5 Speed control
Refer
Purpose Parameter to set
to page
P.H500, P.H700
to P.H704, Pr.22, Pr.801,
To limit the torque during speed P.H710, P.H720, Pr.803, Pr.810
Torque limit 100
control P.H721, P.H730, to Pr.817,
P.D030, P.T040, Pr.858, Pr.874
P.G210
P.G211, P.G212, Pr.820, Pr.821,
To adjust the speed control gain Speed control P gain, speed control integral time 107
P.G311, P.G312 Pr.830, Pr.831
To avoid motor overrunning Speed deviation excess P.H416, P.H417 Pr.285, Pr.853 109
This chapter explains the speed control under Real sensorless vector control and PM sensorless vector control. Speed control
performs control so that the speed command and the actual motor rotation speed match.
RL Multi-speed
RM selection
[Pr. 4 to 6,
RH 24 to 27,
REX 232 to 239]
Option
Operation panel
Acceleration/deceleration processing
Maximum/minimum setting
[Pr. 1] Running
[Pr. 13] [Pr. 10]
[Pr. 2] A
[Pr. 7] [Pr. 8] During stop
Real sensorless
[Pr. 850 = 1] Vector control
Zero speed control
DC injection brake operation
[Pr. 850 = 0]
96 5. Speed control
Speed
A
+ RT control
P gain 1
+
1
- [Pr. 820] +
Speed control
integral
time 1
[Pr. 821]
2
Speed
estimation
Speed
RT control +
P gain 2
[Pr. 830] Speed control
+ 3
integral
time 2
[Pr. 831]
4
Torque
Torque limit Motor
5
control
Torque limit
[Pr. 810 = 0]
[Pr. 22, 812 to 817]
7
Torque [Pr. 74] [Pr. 803]
setting [Pr. 826 = 9999]
filter RT [Pr. 836 ≠ 9999]
[Pr. 836]
[Pr. 74]
[Pr. 836 = 9999]
Communication option 8
10
5. Speed control
97
5.1 Setting procedure of Real sensorless vector
control (speed control)
Sensorless
Operating procedure
1. Perform wiring properly. (Refer to the Instruction Manual (Connection).)
3. Set the overheat protection of the motor (Pr.9). (Refer to page 198.)
4. Set the motor capacity and number of motor poles (Pr.80, Pr.81). (Refer to page 86.)
Operation does not start when the setting value is "9999" (initial value).
5. Set the rated motor voltage and the rated motor frequency (Pr.83, Pr.84). (Refer to page 299.)
NOTE
• During Real sensorless vector control, offline auto tuning must be performed properly before starting operations.
• The speed command setting range under Real sensorless vector control is 0 to 400 Hz.
• The carrier frequency is limited during Real sensorless vector control. (Refer to page 146.)
• Torque control is not available in a low-speed (about 10 Hz or lower) regenerative range, or with a low speed and light load
(about 5 Hz or lower and rated torque about 20% or lower).
• This product with the start command ON may also rotate the motor at a low speed when the speed limit value is set to zero.
Confirm that the motor running does not cause any safety problems.
• Switching between the forward rotation command (STF) and reverse rotation command (STR) must not be performed during
operations under torque control. An overcurrent trip (E.OC[]) or opposite rotation deceleration fault (E.11) will occur.
• In case of starting the motor while the motor is coasting under Real sensorless vector control, the frequency search must be
set for the automatic restart after instantaneous power failure function (Pr.57 ≠ "9999", Pr.162 = "10"). (Refer to page 351.)
• When Real sensorless vector control is applied, there may not be enough torque provided in the ultra low-speed range of about
2 Hz or lower.
Generally, the speed control range is as follows.
For power driving, 1:200 (2, 4 or 6 poles) (available at 0.3 Hz or higher when the rating is 60 Hz), 1:30 (8 or 10 poles) (available
at 2 Hz or higher when the rating is 60 Hz).
For regenerative driving, 1:12 (2 to 10 poles) (available at 5 Hz or higher when the rating is 60 Hz).
98 5. Speed control
5.1 Setting procedure of Real sensorless vector control (speed control)
5.2 Setting procedure of PM sensorless vector control 1
(speed control)
2
PM
This inverter is set for an induction motor in the initial setting. Follow the following procedure to change the setting for the PM
sensorless vector control. 3
Operating procedure
1. Set the applied motor (Pr.9, Pr.71, Pr.80, Pr.81, Pr.83, and Pr.84). (Refer to page 294, page 308.)
4
Set "8093" (IPM motor) or "9093" (SPM motor) in Pr.71 Applied motor. Set Pr.9 Rated motor current, Pr.80 Motor
capacity, Pr.81 Number of motor poles, Pr.83 Rated motor voltage, and Pr.84 Rated motor frequency
according to the motor specifications. (Operation does not start when the setting values of Pr.80 and Pr.81 are
5
"9999" (initial value).)
NOTE
• To change to the PM sensorless vector control, perform PM parameter initialization after offline auto tuning. If parameter
initialization is performed after setting other parameters, some of those parameters are initialized too. (Refer to page 92 for
the parameters that are initialized.)
• To use a motor capacity that is one rank lower than the inverter capacity, set Pr.80 Motor capacity before performing PM
parameter initialization.
• The carrier frequency is limited during PM sensorless vector control. (Refer to page 146.)
• The protective function may be activated due to insufficient torque in the low-speed range of 10% of the rated motor frequency
or lower. The toque limit is not activated.
• During PM sensorless vector control, the RUN signal is output about 100 ms after turning ON the start command (STF, STR).
The delay is due to the magnetic pole detection.
5. Speed control
5.2 Setting procedure of PM sensorless vector control (speed control)
99
5.3 Setting the torque limit level
Sensorless PM
Pr.810 setting
Torque limit input
method
Operation 10
Perform the torque limit operation using the parameter (Pr.22, Pr.812 to Pr.814) settings.
0 (initial value) Internal torque limit 1 If changing the torque limit parameters via communication is enabled, the torque limit input
can be performed via communication.
1 External torque limit Torque limit using analog voltage (current) to terminal 4 is valid.
• The setting value of Pr.805 or Pr.806 is used as the torque limit value.
2 (Internal torque limit 2) • The torque limit via communication is enabled. (Under PM sensorless vector control, the
operation is the same as the one when Pr.810 = "0".)
5. Speed control
5.3 Setting the torque limit level
101
• To set individually for each quadrant, use Pr.812 Torque limit level (regeneration), Pr.813 Torque limit level (3rd
quadrant), Pr.814 Torque limit level (4th quadrant). When "9999" is set, Pr.22 setting is regarded as torque limit level
in all the quadrants.
Torque limit
+
Reverse Forward
regeneration driving
Reverse quad4 quad1 Forward
rotation (Pr.814) (Pr.22) rotation
Speed
quad3 quad2
(Pr.813) (Pr.812)
Reverse Forward
driving regeneration
-
Rated speed
Torque limit level using analog input (terminal 4) (Pr.810 = "1", Pr.858)
• The torque is limited with the analog input of terminal 4. (External torque limit)
• Torque limit using analog input is valid with a limit value lower than the internal torque limit (Pr.22, Pr.812 to Pr.814). (If
the torque limit using analog input exceeds the internal torque limit, the internal torque limit is valid.)
• For inputting from terminal 4, set Pr.858 Terminal 4 function assignment = "4".
• Torque limit using analog input can be calibrated by the calibration parameters C38 to C41. (Refer to page 278.)
400
Torque(%)
150
Gain
C40
Bias
C38 Initial value
0 20 100%
0 4 20mA
C39 Torque setting signal C41
+
Reverse regeneration Forward driving
Pr.805(Pr.806)
RWwC quad4 quad1
Pr.805(Pr.806)
RWwC 2
Speed
Pr.805(Pr.806) quad3 quad2 Pr.805(Pr.806)
RWwC RWwC 3
Reverse driving Forward regeneration
Reverse
regeneration
Forward
driving
8
Pr.815 Pr.815
- quad4 quad1 +
Speed
9
Pr.815 quad3 quad2 Pr.815
Reverse Forward
driving regeneration
Reverse
rotation
Forward
rotation
10
Rated speed
NOTE
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
5. Speed control
5.3 Setting the torque limit level
103
• When the difference between the set speed and rotation speed is -2 Hz or less, the torque limit level during deceleration
Torque limit level during deceleration (Pr.817) activates.
Output
frequency
(Hz) -2 Hz < set speed - rotation speed < 2 Hz
Set
frequency
Pr.816
Pr.817
1s
NOTE
• The internal resolution of the torque limit is 0.024% (100/212), and fractions below this resolution are rounded off.
• When Real sensorless vector control is selected, fractions below a resolution equivalent to 0.1% are rounded off even if Pr.811
= "10" is set.
Pr.803=0
Torque
Pr.803=1
Torque
2
Low-speed Constant torque Low-speed Constant torque
range range Constant power range range range Constant power range
3
Constant power limit
Pr.803=2
Torque
5
Low-speed Constant torque
range range Constant power range
Pr.803=10
8
Torque
Low-speed Constant torque
range range Constant power range
9
Constant power limit
NOTE
• When the Pr.801 setting value is less than the torque limit setting value (Pr.22, Pr.812 to Pr.817, etc.), the Pr.801 setting is
used for limiting the torque current.
5. Speed control
5.3 Setting the torque limit level
105
• When a high load is applied and the torque limit is activated under speed control, the motor stalls. At this time, if the rotation
speed is lower than the value set in Pr.865 Low speed detection and the output torque exceeds the level set in Pr.874
OLT level setting, and this state continues for 3 seconds, Stall prevention stop (E.OLT) is activated and the inverter output
is shut off.
Torque
Pr.865
Time
Start signal
(STF)
3s
Fault signal
(ALM) E.OLT occurrence
NOTE
• Under V/F control or Advanced magnetic flux vector control, if the output frequency drops to 0.5 Hz due to the stall prevention
operation and this state continues for 3 seconds, a fault indication (E.OLT) appears, and the inverter output is shut off. This
operation is activated regardless of the Pr.874 setting.
• This fault does not occur under torque control.
Adjusting the signal output under torque limit operation and output
timing (OL signal, Pr.157)
• If the output torque exceeds the torque limit level and the torque limit is activated, the overload warning (OL signal) is turned
ON for 100 ms or longer. When the output torque drops to the torque limit level or lower, the output signal also turns OFF.
• Pr.157 OL signal output timer can be used to set whether to output the OL signal immediately, or whether to output it
after a certain time period has elapsed.
• For the OL signal, set "3" (positive logic) or "103" (negative logic) in one of Pr.190 to Pr.196 (Output terminal function
selection) to assign the function to the output terminal.
Pr.157 setting value Description
0 (initial value) Output immediately.
0.1 to 25 Output after the set time (s).
9999 Not output.
• The OL signal is also output during the regeneration avoidance operation ("OLV" display (overvoltage stall)).
Overload state
(OL operation)
OL output signal
NOTE
• Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.22 Stall prevention operation levelpage 214
Pr.178 to Pr.189 (Input terminal function selection)page 283
Pr.190 to Pr.196 (Output terminal function selection)page 250
Pr.865 Low speed detectionpage 257
3
Sensorless PM
Gain adjustment is useful for achieving optimum machine performance or improving unfavorable conditions, such as vibration
and acoustic noise during operation with high load inertia or gear backlash.
Pr. Name
Initial
value
Setting
range
Description 4
The proportional gain during speed control is set. (Setting this
820 parameter higher improves the trackability for speed command
Speed control P gain 1 60% 0% to 1000%
G211 changes. It also reduces the speed fluctuation caused by external
disturbance.)
5
The integral time during speed control is set. (Setting this
821
Speed control integral time 1 0.333 s 0 to 20 s parameter lower shortens the return time to the original speed
G212
830
when the speed fluctuates due to external disturbance.)
0% to 1000% Second function of Pr.820 (valid when RT signal is ON)
6
Speed control P gain 2 9999
G311 9999 The Pr.820 setting is applied to the operation.
831 0 to 20 s Second function of Pr.821 (enabled when the RT signal is ON)
G312
Speed control integral time 2 9999
9999 The Pr.821 setting is applied to the operation. 7
Speed control gain adjustment
• The speed control gain can be adjusted for the conditions such as abnormal machine vibration, acoustic noise, slow 8
response, and overshoot.
• Setting 60% (initial value) in Pr.820 Speed control P gain 1 is equivalent to 120 rad/s (speed response of a single motor).
(Equivalent to the half the rad/s value during Real sensorless vector control.) Setting this parameter higher speeds up the 9
response, but setting this too high causes vibration and acoustic noise.
• Setting Pr.821 Speed control integral time 1 lower shortens the return time to the original speed during speed fluctuation,
but setting it too low causes overshoot. 10
Proportional gain
200 (100)rad/s*1
120 (60)rad/s*1
Pr.820
60% 100% Setting
(initial value *2)
*1 The value in the parentheses is applicable under Real sensorless vector control.
*2 Performing PM parameter initialization changes the settings. (Refer to page 92.)
Load
fluctuation
Speed
Since increasing the proportional gain enhances the
response level and decreases the speed fluctuation.
5. Speed control
5.4 Performing high-accuracy, fast-response control (gain adjustment for Real sensorless vector control and PM sensorless vector control)
107
Adjustment procedure
1. Change the Pr.820 setting while checking the conditions.
2. If it cannot be adjusted well, change Pr.821 setting, and perform step 1 again.
NOTE
• Pr.830 Speed control P gain 2 and Pr.831 Speed control integral time 2 are valid when terminal RT is ON. In this case,
replace them for Pr.820 and Pr.821 in the description above.
Torque shortage or motor Set the speed control gain higher. (The same as No.1.) If this cannot be prevented
backlash occurs when starting or through gain adjustment, raise Pr.13 Starting frequency for a fault that occurs
4
passing a low-speed range under when starting, or shorten the acceleration time and avoid continuous operation in a
Real sensorless vector control. low-speed range.
Unusual vibration, noise and
5 overcurrent of the motor or
Set Pr.824 Torque control P gain 1 (current loop proportional gain) lower.
machine occurs.
Lower the setting by 10% and set a value that is approximately 80% to 90% of the
Overcurrent or overspeed (E.OS) setting immediately before the condition improves.
6 occurs when starting under Real
sensorless vector control.
PM
Set frequency
Frequency
Pr.285
8
(Hz)
Time
Fault output
Pr.853
9
OFF ON
(ALM)
Speed deviation
excessive fault activated
(E. OSD)
10
NOTE
• This function is enable at a frequency equal to or higher than 10% of the rated motor frequency.
5. Speed control
5.5 Avoiding motor overrunning
109
5.6 Troubleshooting in the speed control
Sensorless PM
Parameters referred to
Pr.72 PWM frequency selectionpage 146
Pr.80 Motor capacity, Pr.81 Number of motor polespage 86
Pr.125 Terminal 2 frequency setting gain frequency, Pr.126 Terminal 4 frequency setting gain frequencypage 273
Pr.822 Speed setting filter 1page 271
Pr.824 Torque control P gain 1 (current loop proportional gain)page 122
10
111
6 Torque control
Refer
Purpose Parameter to set
to page
Torque command source selection or P.D400 to P.D402, P.G210,
Torque command Pr.801, Pr.803 to Pr.806 117
torque command value setting P.H704
To prevent the motor from
Speed limit P.H410 to P.H412 Pr.807 to Pr.809 120
overspeeding
Torque control gain P.G213, P.G214, P.G313, Pr.824, Pr.825, Pr.834,
To raise precision of torque control 122
adjustment P.G314 Pr.835
Block diagram
Constant power range
Torque command torque characteristic selection
Terminal 4 bias [C38,C39] source selection [Pr.803]
Terminal 4 gain [C40,C41] [Pr.804]
Terminal 4
[Pr. 858 = 4]
Torque RT [Pr.826≠9999]
setting [Pr.826]
filter [Pr.74]
[Pr.826 = 9999]
RT [Pr.836≠9999]
[Pr.836]
[Pr.74]
[Pr.836 = 9999]
Parameter
[Pr.805,806]
CC-Link (FR-A8NC)
CC-Link IE TSN
CC-Link IE Field Network Basic
Estimated speed
RT Torque control
< Speed limit value +
P gain 1 Motor
[Pr.824] +
Torque control
integral time 1
[Pr.825]
RT Torque control
+
P gain 2
[Pr.834] +
Torque control
estimated speed integral time 2
Speed limit value Speed control [Pr.835]
+
A (proportional
Speed ‒ control)
limit value
Speed
estimation
AU
Terminal 2 bias [C2,C3]
Terminal 2 gain [Pr.125, C4]
adjustment
[Pr.849] 1
Terminal 2
Terminal 4 bias [C5,C6] Analog
AU Terminal 4 gain [Pr.126, C7] input
2
Terminal 4 selection
[Pr. 858 = 0] [Pr. 73]
RT [Pr.822 ≠ 9999]
Speed
setting [Pr.822]
3
filter [Pr.74]
[Pr.822 = 9999]
RL Multi-speed
Operation Mode
[Pr.79] Speed limit selection
4
RM selection [Pr.807=0]
[Pr.4 to 6,
RH 24 to 27, [Pr.807=1]
232 to 239]
5
REX
Option
Operation
panel
Parameter
[Pr.808, Pr.809]
6
7
Acceleration/deceleration
Maximum/minimum processing
setting
[Pr.1]
A
[Pr.2]
[Pr.7] [Pr.8]
8
10
6. Torque control
6.1 Torque control
113
Operation transition
Speed limit value is
increased up to preset value
according to the Pr.7
Acceleration time setting. Speed limit value Speed limit value is decreased
down to zero according to the Pr.8
Deceleration time setting.
Start signal
The output torque is
determined by the torque
Speed control is performed during speed command.
Output torque
limit. (Thus, torque according to the
commanded is not developed.)
• If the setting value of Pr.7 and Pr.8 is "0", turning OFF the start signal enables speed control, and the output torque is
controlled by the torque limit value.
Speed limit value
Item Description
External operation STF, STR signal
Start signal
PU operation RUN key of the operation panel
Torque command Select the method to give the torque command, and give the torque command.
Speed limit Select the method to give the speed limit command, and input the speed limit value.
Operation example
Torque control is enabled when the rotation speed (estimated value) does not exceed the speed limit value.
When the speed (estimated value) reaches or exceeds the speed limit value, speed limit is activated, torque control is stopped,
and speed control (proportional control) is performed.
The operation is as follows.
Speed
Pr.7 Speed limit value Pr.8
*
* *
Speed (estimated value)
Time
STF
(Forward
rotation
command)
Speed limit operation Torque control operation Speed limit operation Torque Speed limit operation
(Speed control) (Speed control) control
(Speed control)
operation
OL ON ON ON
(Speed limit) * When the speed limit activates, torque according to the commanded is not developed.
• At the STF signal ON, the speed limit value is raised in accordance with the setting of Pr.7.
10
6. Torque control
6.1 Torque control
115
6.2 Setting procedure of Real sensorless vector
control (torque control)
Sensorless
Operating procedure
1. Perform wiring properly. (Refer to the Instruction Manual (Connection).)
4. Set the motor capacity and the number of motor poles (Pr.80, Pr.81). (Refer to page 86.)
Operation does not start when the setting value is "9999" (initial value).
5. Set the rated motor voltage and frequency (Pr.83, Pr.84). (Refer to page 299.)
NOTE
• During Real sensorless vector control, offline auto tuning must be performed properly before starting operations.
• The carrier frequency is limited during Real sensorless vector control. (Refer to page 146.)
• Torque control is not available in a low-speed (about 10 Hz or lower) regenerative range, or with a low speed and light load
(about 5 Hz or lower and rated torque about 20% or lower).
• This product with the start command ON may also rotate the motor at a low speed when the speed limit value is set to zero.
Confirm that the motor running does not cause any safety problems.
• Switching between the forward rotation command (STF) and reverse rotation command (STR) must not be performed during
operations under torque control. An overcurrent trip (E.OC[]) or opposite rotation deceleration fault (E.11) will occur.
• If starting may occur while the motor is coasting under Real sensorless vector control, the frequency search must be set for
the automatic restart after instantaneous power failure function (Pr.57 ≠ "9999", Pr.162 = "10").
• When Real sensorless vector control is applied, there may not be enough torque provided in the ultra low-speed range of about
2 Hz or lower.
Generally, the speed control range is as follows.
For power driving, 1:200 (2, 4 or 6 poles) (available at 0.3 Hz or higher when the rating is 60 Hz), 1:30 (8 or 10 poles) (available
at 2 Hz or higher when the rating is 60 Hz).
For regenerative driving, 1:12 (2 to 10 poles) (available at 5 Hz or higher when the rating is 60 Hz).
Sensorless
For torque control selection, the torque command source can be selected.
2
Initial
Pr. Name Setting range Description
value
801 0% to 400% Set the torque current limit level. 3
Output limit level 9999
H704 9999 The torque limit setting value is used for limiting the torque current level.
0, 10 Constant motor output command
803
Constant output range
1 Constant torque command
The torque is constant unless the
In the torque command setting, 4
torque characteristic 0 select torque command for the
G210 output limit of the torque current is
selection 2 constant output area.
reached. (The torque current is
0
limited.)
Torque command given by analog input via terminal 4
5
Torque command (-400% to 400%) given by the parameter setting
1
(Pr.805 or Pr.806)
804
D400
Torque command
source selection
0 3 Torque command via communication*1 6
4 12/16-bit digital input (FR-A8AX)
5
Torque command via communication*1
+ Speed control
Speed limit input
Speed (proportional control)
estimated Speed limit value
- value
Speed estimator
Real sensorless vector control
NOTE
• When the torque command exceeding the torque limit value (Pr.22, Pr.810, Pr.812 to Pr.817) is given, the output torque is
within the torque limit value. (Refer to page 112.)
6. Torque control
6.3 Torque command
117
• Torque commands given by analog inputs can be calibrated by the calibration parameters C38 to C41. (Refer to page
278.)
Torque command
150%
0 100% Terminal 4
analog input
400%
Pr.805, Pr.806
600% settings
1000% 1400%
NOTE
• When the torque command is set by Pr.805 (RAM), powering OFF the inverter erases the changed parameter value.
Therefore, the parameter set value is the one saved by Pr.806 (EEPROM) when the power is turned back on.
• If giving torque command by parameter setting, set the speed limit value properly to prevent overspeeding. (Refer to page
120.)
*1 The torque command value can also be set using the operation panel.
*2 The torque command can also be given by setting a value in Pr.805 or Pr.806.
*3 The setting range if set by the operation panel is "673 to 1327 (-327% to 327%)"; and the setting increment is 1%.
NOTE
• For the details of the CC-Link communication, refer to the FR-A8NC Instruction Manual. For the details of the CC-Link IE TSN
or CC-Link IE Field Network, refer to the Instruction Manual (Communication).
• For details of the setting using the PLC function, refer to the PLC Function Programming Manual.
• To avoid overload or overcurrent of the inverter or motor, use Pr.801 Output limit level to limit the torque current in the 7
constant power range.
Pr.801 setting Description
0% to 400% Set the torque current limit level. 8
9999 The torque limit setting value (Pr.22, Pr.812 to Pr.817, etc.) is used for limiting the torque current.
Pr.803=0, 1, 10 9
Torque
Constant torque range Constant power range
Pr.803=1:
constant torque command 10
Pr.803=0, 10:
constant power command
Pr.803 = 2
Torque
Constant torque range Constant power range
Parameters referred to
Pr.858 Terminal 4 function assignmentpage 270
Calibration parameters C38 to C41 (terminal 4 bias, gain torque)page 278
6. Torque control
6.3 Torque command
119
6.4 Speed limit
Sensorless
When operating under torque control, motor overspeeding may occur if the load torque drops to a value less than the torque
command value, etc. Set the speed limit value to prevent overspeeding.
If the actual speed reaches or exceeds the speed limit value, the control method switches from torque control to speed control,
preventing overspeeding.
Initial value*1 Setting
Pr. Name Description
Gr.1 Gr.2 range
0 Uses the speed command during speed control as the speed limit.
807
Speed limit selection 0 Sets the speed limits for forward and reverse directions individually by
H410 1
using Pr.808 and Pr.809.
808
Speed limit 60 Hz 50 Hz 0 to 400 Hz Sets speed limit.
H411
Sets the speed limit when the load has reversed the motor rotation
809 0 to 400 Hz
Reverse-side speed limit 9999 opposite to the torque polarity.
H412
9999 Pr.808 setting value is effective.
*1 Gr.1 and Gr.2 are the parameter initial value groups. (Refer to page 82).
Using the speed command during speed control (Pr.807 = "0" (initial
value))
• Speed limit is set by the same method as speed setting during speed control (speed setting by the operation panel, multi-
speed setting, plug-in option, etc.).
• When the start signal turns ON, the limit level increases from 0 Hz to the set speed by taking the time set in Pr.7
Acceleration time. When the start signal turns OFF, the limit level at the time decreases to the operation start level of
Pr.10 DC injection brake operation frequency, by taking the time set in Pr.8 Deceleration time.
The speed setting
Speed
value is the speed
Forward rotation limit value.
Pr.7 Pr.8
Speed setting
value during
speed control
Time
Torque controllable
range
Reverse rotation
STF(STR) ON OFF
NOTE
• The second acceleration/deceleration time can be set.
• When speed limit command exceeds Pr.1 Maximum frequency setting, the speed limit value becomes Pr.1 setting. When
speed limit command falls below Pr.2 Minimum frequency setting, the speed limit value becomes Pr.2 setting. Also, the
speed limit command is smaller than Pr. 13 Starting frequency, the speed limit value becomes 0 Hz.
• To use analog inputs to perform speed limit, calibrate analog input terminals 2 and 4. (Refer to page 273.)
• To use analog inputs to perform speed limit, turn OFF the external signals (RH, RM, RL). If any of the external signals (RH,
RM, RL) is ON, speed limit by multi-speed are enabled.
6
-Speed limit value Reverse-side
7
speed limit value
Pr.809
Range where torque
Rotation speed control is available
Rotation speed Range where torque
Pr.7
control is available
Pr.8
Pr.809 8
Reverse-side
Speed limit value speed limit value
Time Time
9
Speed limit value
Pr.7 Pr.8
10
-Pr.809
Reverse-side
speed limit value
When the torque command value is positive When the torque command value is negative
NOTE
• During the speed limit operation, "SL" is displayed on the operation panel and the OL signal is output.
• For the OL signal, set "3" (positive logic) or "103" (negative logic) in one of Pr.190 to Pr.196 (Output terminal function
selection) to assign the function to the output terminal. Changing the terminal assignment using Pr.190 to Pr.196 may affect
the other functions. Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.1 Maximum frequency, Pr.2 Minimum frequencypage 211
Pr.4 to Pr.6, Pr.24 to Pr.27, Pr.232 to Pr.239 (multi-speed operation)page 195
Pr.7 Acceleration time, Pr.8 Deceleration timepage 158
Pr.13 Starting frequencypage 169
Pr.190 to Pr.196 (Output terminal function selection)page 250
6. Torque control
6.4 Speed limit
121
6.5 Torque control gain adjustment
Sensorless PM
Operation is normally stable enough in the initial setting, but some adjustments can be made if abnormal vibration, noise or
overcurrent occur for the motor or machinery.
Setting
Pr. Name Initial value Description
range
824 Torque control P gain 1 (current loop
100% 0% to 500% Set the current loop proportional gain.
G213 proportional gain)
825 Torque control integral time 1 (current
5 ms 0 to 500 ms Set current loop integral compensation time.
G214 loop integral time)
Set the current loop proportional gain when RT signal is
834 Torque control P gain 2 (current loop 0% to 500%
9999 ON.
G313 proportional gain)
9999 The Pr.824 setting is applied to the operation.
Set the current loop integral compensation time when
835 Torque control integral time 2 (current 0 to 500 ms
9999 RT signal is ON.
G314 loop integral time)
9999 The Pr.825 setting is applied to the operation.
NOTE
• The RT signal is a second function selection signal which also enables other second functions. (Refer to page 289.)
• To assign the RT signal, set "3" in any parameter from Pr.178 to Pr.189 (Input terminal function selection).
Adjustment procedure
Adjust if any of phenomena such as unusual vibration, noise, current or overcurrent is produced by the motor or machinery.
10
6. Torque control
6.5 Torque control gain adjustment
123
6.6 Troubleshooting in torque control
Sensorless
Parameters referred to
Pr.72 PWM frequency selectionpage 146
Pr.178 to Pr.189 (Input terminal function selection)page 283
Pr.800 Control method selectionpage 86
Pr.807 Speed limit selectionpage 120
C38 to C41 (torque setting voltage (current) bias/gain)page 278
7.1 Clock.....................................................................................................................................................................127
7.2 Reset selection / disconnected PU detection / PU stop selection ........................................................................128
6
7.3 Automatic frequency setting / key lock operation selection ..................................................................................130
7.4 Frequency change increment amount setting (standard model) ..........................................................................132
7.5 RUN key rotation direction selection.....................................................................................................................133
7
7.6 Multiple rating setting............................................................................................................................................134
7.7 Parameter write selection .....................................................................................................................................135
7.8 Password ..............................................................................................................................................................137
8
7.9 Free parameter .....................................................................................................................................................140
7.10 Setting multiple parameters by batch ...................................................................................................................141
7.11 Extended parameter display and user group function ..........................................................................................143
9
7.12 PWM carrier frequency and Soft-PWM control.....................................................................................................146
7.13 Inverter parts life display.......................................................................................................................................148
7.14 Maintenance timer alarm ......................................................................................................................................152
10
7.15 Current average value monitor signal...................................................................................................................153
125
7 (E) Environment Setting Parameters
Refer to
Purpose Parameter to set
page
To set the time Simple clock function P.E020 to P.E022 Pr.1006 to Pr.1008 127
To set a limit for the reset function.
Reset selection /
To shut off output if the operation panel
Disconnected PU detection
disconnects. P.E100 to P.E102 Pr.75 128
/ PU stop selection / Reset
To force deceleration to stop on the operation
limit
panel.
To set the frequency automatically. Operation panel operation
P.E200 Pr.161 130
To disable the operation panel. selection
To change the frequency change increments
Frequency change
which changes when using the setting dial of P.E201 Pr.295 132
increment amount setting
the operation panel
To determine which direction the motor 133
RUN key rotation direction
rotates when the RUN key on the operation P.E202 Pr.40
selection
panel is pressed.
To use the regeneration unit to increase the Regenerative brake
P.E300, P.G107 Pr.30, Pr.70 386
motor braking torque selection
To change the overload current rating
Multiple rating setting P.E301 Pr.570 134
specification
Parameter write disable
To prevent parameter rewriting P.E400 Pr.77 135
selection
To restrict parameters with a password Password P.E410, P.E411 Pr.296, Pr.297 137
To use parameters freely Free parameter P.E420, P.E421 Pr.888, Pr.889 140
To change parameter settings for a PM motor
PM parameter initialization P.E430 Pr.998 92
by batch
Automatic parameter
To set multiple parameters by batch P.E431 Pr.999 141
setting
Applicable parameter
Pr.160, Pr.172 to
To display the required parameters display and user group P.E440 to P.E443 143
Pr.174
function
PWM carrier frequency Pr.72, Pr.240,
To reduce the motor noise and EMI P.E600 to P.E602 146
changing Pr.260
Pr.255 to Pr.259,
P.E700 to P.E706,
Inverter parts life display Pr.506, Pr.507, 148
P.E708
Pr.509
To understand the maintenance time of Environmental impact
P.E709 Pr.198 148
inverter parts and peripheral devices diagnosis function
Maintenance output
P.E710, P.E711 Pr.503, Pr.504 152
function
Current average monitor P.E720 to P.E722 Pr.555 to Pr.557 153
NOTE
• The time data of the internal clock is saved in the inverter's EEPROM every 10 minutes. 8
• The clock does not run while the control circuit power is OFF. The clock needs to be set every time after turning ON the inverter
power.
9
Time synchronization via CC-Link IE TSN communication (Ethernet
model)
• The internal clocks of connected devices on the CC-Link IE TSN Network can be synchronized.
10
NOTE
• The clock of the inverter is adjusted every minute according to the received clock data. (The clock of the inverter is not
synchronized when the received clock data is out of range.)
• For information about sending clock data, refer to the Instruction Manual of the CC-Link IE TSN master module.
Operation after PU
Pr.75 setting Reset input PU stop function
disconnection is detected
0 Always enabled. Operation continues. Disabled
1 When the protective function is activated. Operation continues. Disabled
2 Always enabled. Inverter output shutoff Disabled
3 When the protective function is activated. Inverter output shutoff Disabled
14 (initial value) Always enabled. Operation continues. Enabled
15 When the protective function is activated. Operation continues. Enabled
16 Always enabled. Inverter output shutoff Enabled
17 When the protective function is activated. Inverter output shutoff Enabled
NOTE
• When the RES signal is input during operation, the motor coasts since the inverter being reset shuts off the output. Also, the
cumulative values of electronic thermal O/L relay and regenerative brake duty are cleared.
• When "reset input always enabled" is selected, the reset key on the PU is enabled only when the protective function is
activated.
NOTE
• When the PU has been disconnected before power-ON, the output is not shut off.
• To restart the inverter operation, confirm that the PU is connected before reset.
• When the inverter detects that the PU is disconnected during PU JOG operation while P.E101 or Pr.75 is set to continue the
inverter operation even when the PU is disconnected, the inverter decelerates the motor to stop.
• During RS-485 communication operation via the PU connector, the Reset selection function and the PU stop selection function
are enabled but the Disconnected PU detection function is disabled. (The communication is checked according to Pr.122 PU
communication check time interval.)
• PU disconnection detection function is unavailable for Ethernet models.
NOTE
3
• The inverter decelerates to stop (PU stop function) also when the start command is input using a device which has the
command source (set in Pr.551) and then the STOP/RESET key is pressed on a PU which does not have the command
source. 4
(Example) When the operation panel has the command source and the stop command is input using a USB (FR
Configurator2), the PU stop function is activated.
5
How to restart the inverter which has been stopped in the External
operation mode by using the STOP/RESET key on the PU ("PS" (PU stop)
warning reset method) 6
• PU stop release method for operation panel
1. After completion of deceleration stop, turn OFF the STF and STR signals. 7
2. Press the PU/EXT key three times (the PS warning is reset)
when Pr.79 Operation mode selection = "0" (initial value) or "6".
When Pr.79 = "2, 3, or 7", the PU stop warning can be cleared with one keystroke. 8
Speed
9
Time
Key
Operation
panel
Key
10
STF ON
(STR) OFF
NOTE
• Even when Pr.250 Stop selection ≠ "9999" is set and coasting stop is selected, using the PU stop function in the External
operation mode does not provide coasting stop but deceleration stop.
CAUTION
• Do not perform a reset while a start signal is being input. Doing so will cause a sudden start of the motor, which
is dangerous.
Parameters referred to
Pr.79 Operation mode selectionpage 174
Pr.250 Stop selectionpage 384
Pr.551 PU mode operation command source selectionpage 185
When the automatic frequency setting is disabled (Pr.161 = "0 (initial value) or 10")
Blinking
Alternating
Within Alternating
Blinking 5 seconds
NOTE
• If the operation panel does not have the operation command source (Pr.551 = "2, 3, or 9999" (with USB and/or PU
connection)), the frequency cannot be set using the operation panel.
• If the operation mode is changed to one in which the inverter does not operate according to the frequency set on the operation
panel after the frequency value is stored in the RAM but before it is stored in the EEPROM, the value is not stored in the
EEPROM.
• If the power is OFF or the inverter is reset after the frequency value is stored in the RAM but before it is stored in the EEPROM,
the value is not stored in the EEPROM.
• When setting the frequency by turning the setting dial, the frequency goes up to the set value of Pr.1 Maximum frequency.
Be aware of what frequency Pr.1 is set to, and adjust the setting of Pr.1 according to the application.
NOTE
• Even if setting dial and key operations are disabled, the monitor indicator and STOP/RESET key are enabled.
4
• The PU stop warning cannot be reset by using keys while the key lock function is enabled.
5
Parameters referred to
Pr.1 Maximum frequencypage 211
10
Basic operation
• When Pr.295 ≠ "0", the minimum increment when the set frequency is changed with the setting dial can be set.
For example, when Pr.295 = 1.00 Hz, one click (one dial gauge) of the setting dial changes the frequency in increments
of 1.00 Hz, such as 1.00 Hz → 2.00 Hz → 3.00 Hz.
When Pr.295="1.00"
1 click 1 click
NOTE
• When machine speed display is selected in Pr.53 Frequency / rotation speed unit switchover, the minimum increments of
change are determined by Pr.295 as well. Note that the setting value may differ as speed setting changes the set machine
speed and converts it to the speed display again.
• For Pr.295, the increments are not displayed.
• The Pr.295 setting is enabled only for the changes to the set frequency. It does not apply to the settings of other parameters
related to frequency.
• When 10 is set, the frequency setting changes in 10 Hz increments. Be cautious of excessive speed (when Automatic
frequency setting enabled).
Parameters referred to
Pr.53 Frequency / rotation speed unit switchoverpage 226
The rotation direction of the motor when the RUN key on the operation panel is pressed can be selected.
Setting
2
Pr. Name Initial value Description
range
40 0 Forward rotation
RUN key rotation direction selection 0
E202 1 Reverse rotation 3
10
*2 The rated current and motor capacity values differ depending on the inverter capacity. Refer to the inverter rated specifications in the Instruction
Manual (Connection).
*3 The initial value for the FR-E820-0050(0.75K) or lower, the FR-E840-0026(0.75K) or lower, and the FR-E860-0017(0.75K) is set to the 85% of
the inverter rated current.
Whether to enable the parameter write or not can be selected. Use this function to prevent parameter values from being
rewritten by misoperation. 2
Pr. Name Initial value Setting range Description
0 Parameter write is enabled only during stop.
77
Parameter write selection 0
1 Parameter writing is disabled. 3
E400 Parameter writing is enabled in any operation mode
2
regardless of the operation status.
• Pr.77 can be set at any time regardless of the operation mode or operation status. (Setting through communication is 4
unavailable.)
Parameter write enabled only during stop (Pr.77 = "0" (initial value))
• Parameters can be written only during a stop in the PU operation mode.
5
• The following parameters can always be written regardless of the operation mode or operation status.
22
24 to 27
Stall prevention operation level
(Multi-speed setting speed 4 to speed 7)
551*2
555 to 557
PU mode operation command source selection
(Current average value monitoring)
7
52 Operation panel main monitor selection 675 User parameter auto storage function selection
54 FM terminal function selection 774 to 776 (Operation panel monitor item selection)
55 Frequency monitoring reference 805 Torque command value (RAM) 8
56 Current monitoring reference 806 Torque command value (RAM, EEPROM)
72*1 PWM frequency selection 866 Torque monitoring reference
75
Reset selection/Disconnected PU detection/PU
stop selection
888, 889 (Free parameter) 9
77 Parameter write selection 891 to 899 (Energy saving monitoring)
79*2 Operation mode selection C0 (900) FM terminal calibration
129 PID proportional band C1 (901) AM terminal calibration 10
Operation panel setting dial push monitor
130 PID integral time 992
selection
133 PID action set point 997 Fault initiation
134 PID differential time 998*2 PM parameter initialization
158 AM terminal function selection 999*2 Automatic parameter setting
160 User group read selection 1006 Clock (year)
232 to 239 (Multi-speed setting speed 8 to speed 15) 1007 Clock (month, day)
240*1 Soft-PWM operation selection 1008 Clock (hour, minute)
241 Analog input display unit switchover 1020 Trace operation selection
268 Monitor decimal digits selection 1124 Station number in inverter-to-inverter link
Stop-on contact excitation current low-speed 1125 Number of inverters in inverter-to-inverter link
275*1 scaling factor system
290 Monitor negative output selection 1150 to 1199 (PLC function user parameters)
1399, 1424 to
295 Frequency change increment amount setting 1432, 1434 to (Ethernet communication)
1457
296, 297 (Password setting) 1480 to 1485 (Load characteristics fault)
306 Analog output signal selection
310 Analog meter voltage output selection
340*2 Communication startup mode selection
416, 417 (PLC)
442 to 445 (Ethernet communication)
496, 497 (Remote output)
498 PLC function flash memory clear
*1 Writing during operation is enabled in PU operation mode, but disabled in External operation mode.
*2 Writing during operation is disabled. To change the parameter setting value, stop the operation.
These parameters can be set when Pr.160 User group read selection = "0". However, when Pr.296 ≠ 9999 (password lock
5
is set), Pr.297 can always be set, regardless of the setting in Pr.160.
*1 Although "0 or 9999" can be input in Pr.297, the value is invalid. (The display cannot be changed.)
6
Parameter reading/writing restriction level (Pr.296)
• The access (reading/writing) restriction level to parameters in the PU operation mode or NET operation mode can be
selected with Pr.296. 7
NET operation mode operation command*4
PU operation mode operation
RS-485 communication / PLC
Pr.296 setting command*3 via communication option
function*7
Read*1 Write*2 Read Write*2 Read Write*2
8
9999 ○ ○ ○ ○ ○ ○
0, 100*6 × × × × × ×
1, 101 ○ × ○ × ○ × 9
2, 102 ○ × ○ ○ ○ ○
3, 103 ○ ○ ○ × ○ ×
4, 104
5, 105
×
×
×
×
×
○
×
○
○
○
×
○
10
6, 106 ○ ○ × × ○ ×
Only the parameters registered in the user group can be read/written. (For the parameters not registered in the user
99, 199
group, the restriction level when "4 or 104" is set applies.)*5
○: Enabled, ×: Disabled
*1 If the parameter reading is restricted by the setting of Pr.160 User group read selection, those parameters cannot be read even when "○" is
indicated.
*2 If the parameter writing is restricted by the setting of Pr.77 Parameter write selection, those parameters cannot be written even when "○" is
indicated.
*3 Access from the command source in the PU operation mode (the operation panel in the initial setting) is restricted. (For the PU operation mode
command source selection, refer to page 185.)
*4 Access from the command source in the Network operation mode (the RS-485 communication or a communication option in the initial setting) is
restricted. (For the NET operation mode command source selection, refer to page 185.)
*5 Read/write is enabled only for the simple mode parameters registered in the user group when Pr.160 = "9999". Pr.296 and Pr.297 are always
read/write enabled whether registered to a user group or not.
*6 If a communication option is installed, the Option fault (E.OPT) occurs, and the inverter output shuts off.
*7 The PLC function user parameters (Pr.1150 to Pr.1199) can be written and read by the PLC function regardless of the Pr.296 setting.
1. Set the parameter reading/writing restriction level to enable the password protection. (Set a value other than "9999"
in Pr.296.)
Allowable number of failed password
Pr.296 setting Pr.297 readout
attempts
0 to 6, or 99 Unlimited Always 0
100 to 106, 199*1 Limited to 5 times Number of failed password attempts (0 to 5)
2. Write a 4-digit number (1000 to 9998) to Pr.297 as a password (writing is disabled when Pr.296 = "9999"). After a
password is set, parameters are locked and access (reading/writing) to the parameters is limited at the level set in
Pr.296 until the valid password is input to unlock the locked parameters.
NOTE
• After a password is set, the Pr.297 readout is always any of "0 to 5".
• "LOCD" appears when a password-protected parameter is attempted to be read/written.
• Even if a password is set, the parameters which are written by the inverter, such as parameters related to the life check of
inverter parts, are overwritten as needed.
NOTE
• If the password is forgotten, it can be reset by performing All parameter clear, but the other parameters are also reset.
• All parameter clear cannot be performed during the inverter operation.
• When using FR Configurator2 in the PU operation mode, do not set "0, 4, 5, 99, 100, 104, 105, or 199" (parameter read is
disabled) in Pr.296. Doing so may cause abnormal operation.
• The means to reset the password varies according to how the reset command is sent (from the operation panel, through RS-
485 communication, or via a communication option).
○: Enabled, ×: Disabled
*1 Reading/writing is disabled if reading is restricted by the Pr.160 setting. (Reading is available in the Network operation mode regardless of the
Pr.160 setting.)
*2 All parameter clear cannot be performed during the operation.
*3 Inputting a password is possible but the locked-up password cannot be unlocked or reset even with the valid password.
*4 Parameter clear can be performed only via a communication option.
Parameters referred to
Pr.77 Parameter write selectionpage 135
10
NOTE
• Pr.888 and Pr.889 do not influence the operation of the inverter.
The setting of particular parameters is changed by batch, such as communication parameters for connection with the Mitsubishi
Electric human machine interface (GOT), the parameters for the rated frequency (50/60 Hz) setting, or the parameters for 2
acceleration/deceleration time increment.
Multiple parameters are changed automatically. Users do not have to consider each parameter number (automatic parameter
setting). 3
Setting
Pr. Name Initial value Description
range
12
Automatically sets the communication parameters for the GOT
connection with a PU connector ("Controller Type" in GOT: "AUTO"→"GOT"→Write "2".
9
FREQROL 800 (Automatic Negotiation))
50 Hz rated
20 Sets the related parameters of the rated "AUTO"→"F50"→Write "1".
frequency
60 Hz rated
frequency according to the power supply 10
21 frequency —
frequency
NOTE
• If the automatic setting is performed with Pr.999 or the automatic parameter setting mode, the settings including the changed
parameter settings (changed from the initial setting) will be automatically changed. Before performing the automatic setting,
confirm that changing the parameters will not cause any problem.
• "AUTO" is displayed on the operation panel also when the user group function is used (Pr.160 = "1"). However, if Pr.999 is
not registered in the group, the automatic setting cannot be performed (write error (Er1) occurs).
NOTE
• Always perform an inverter reset after the initial setting.
• For the details of connection with GOT, refer to the Instruction Manual of GOT.
*1 Gr.1 and Gr.2 are the parameter initial value groups. (Refer to page 82).
*2 Refer to the Instruction Manual (Communication).
NOTE
• When the plug-in option FR-A8AX is used, Pr.301 BCD input gain and Pr.303 BIN input gain are not set automatically.
NOTE
• When a plug-in option in installed on the inverter, the option parameters can also be read. 8
• Every parameter can be read regardless of the Pr.160 setting when reading parameters via communication.
Operating procedure
1. Power ON
Make sure the motor is stopped.
4. Selecting a parameter
Turn the setting dial or press the UP/DOWN key until "P.173" (Pr.173) appears.
5. Parameter read
Press the SET key. "9999" appears.
6. Parameter registration
Turn the setting dial or press the UP/DOWN key until "3" (Pr.3) appears. Press the SET key to register the
parameter.
"3" blinks.
To continue adding parameters, repeat steps 5 and 6.
Parameters referred to
Pr.77 Parameter write selectionpage 135
Pr.296 Password lock level, Pr.297 Password lock/unlockpage 137
10
*1 The carrier frequency is automatically changed to 2 kHz in the low-speed range (lower than 3 Hz) under Real sensorless vector control, or in the
low-speed range (lower than 10% of the rated motor frequency) under PM sensorless vector control.
NOTE
• The carrier frequency may be automatically lowered in the low-speed range (lower than about 10 Hz) for the ND rating, and
over the entire speed range for the LD rating.
Motor noise increases, but not to the point of failure.
Parameters referred to
Pr.156 Stall prevention operation selectionpage 214
3
Pr.570 Multiple rating settingpage 134
Pr.800 Control method selectionpage 86
10
• In the life diagnosis of the main circuit capacitor, the Life alarm (Y90) signal is not output unless measurement by turning OFF
the power supply is performed.
• Pr.255 Life alarm status display and the Life alarm (Y90) signal can be used to check whether or not the life alarm output
level is reached for the following parts: the control circuit capacitor, main circuit capacitor, cooling fan, inrush current limit
circuit, relay contacts of terminals A, B, and C, inverter module, or control circuit board.
• For accurate life measurement of the main circuit capacitor, wait three hours or longer after turning OFF. The temperature left
in the main circuit capacitor affects measurement.
3. Switch the power OFF. The inverter applies DC voltage to the motor to measure the capacitor capacity while the
inverter is OFF.
4. After confirming that the LED of the operation panel is OFF, power ON again.
NOTE
• When the main circuit capacitor life is measured under the following conditions, "forced end" (Pr.259 = "8"), or "measurement
error" (Pr.259 = "9") may occur, or the status may remain in "measurement start" (Pr.259 = "1"). To perform measurement,
first eliminate the following conditions. Under the following conditions, even if "measurement complete" (Pr.259 = "3") is
reached, measurement cannot be performed correctly.
- FR-HC2 or FR-XC is connected.
- DC power supply is connected to the terminals P/+ and N/-.
- The power supply is switched ON during measurement.
- The motor is not connected to the inverter.
- The motor is running (coasting).
- The motor capacity is smaller than the inverter capacity by two ranks or more.
- The inverter output is shut off or a fault occurred while the power was OFF.
- The inverter output is shut off with the MRS signal.
- The start command is given while measuring.
- The applied motor setting is incorrect.
• Operation environment: Surrounding air temperature (annual average of 40°C (free from corrosive gas, flammable gas, oil
mist, dust and dirt)).
Output current: 80% of the inverter rating
• Since repeated inrush currents at power ON will shorten the life of the converter circuit, frequent starts and stops of the
magnetic contactor must be avoided.
WARNING
• When measuring the main circuit capacitor capacity (Pr.259 = "1"), the DC voltage is applied to the motor for about 1
second at power OFF. Never touch the motor terminal, etc. right after powering OFF to prevent an electric shock.
NOTE
• When the inverter is mounted with two or more cooling fans, "FN" is displayed even only one of the fans is detected.
• Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
First power ON
9998
(999800h) Set "0" in Pr.503
Maintenance
timer Pr.504
(Pr. 503)
Time
• The cumulative energization time of the inverter is stored in the EEPROM every hour and displayed in Pr.503 in 100 h
increments. The number indication on Pr.503 stopped at 9998 (999,800 hours).
• When the value in Pr.503 reaches the time (100 h increments) set in Pr.504, the Maintenance timer (Y95) signal is output,
and also "MT" is displayed on the operation panel.
• For the terminal used for the Y95 signal output, assign the function by setting "95" (positive logic) or "195" (negative logic)
in any parameter from Pr.190 to Pr.196 (Output terminal function selection).
NOTE
• The cumulative energization time is counted every hour. Energization time of less than 1 h is not counted.
• Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.190 to Pr.196 (Output terminal function selection)page 250
The output current average value during constant-speed operation and the maintenance timer value are output to the Current
average monitor (Y93) signal as a pulse. The output pulse width can be used in a device such as the I/O unit of a programmable 2
controller as a guideline for the maintenance time for mechanical wear, belt stretching, or deterioration of devices with age.
The pulse is repeatedly output during constant-speed operation in cycles of 20 seconds to the Current average monitor (Y93)
signal. 3
Programmable controller
Output Input
4
unit unit
Inverter
maintenance
time
5
parts have
reached their life 6
555
Pr. Name Initial value Setting range Description
Set the time for calculating the average current during start
7
Current average time 1s 0.1 to 1 s
E720 pulse output (1 second).
556 Set the time for not obtaining (masking) transitional state
Data output mask time 0s 0 to 20 s
E721 data. 8
Current average value
557 Inverter rated Set the reference (100%) for outputting the output current
monitor signal output 0 to 500 A
E722 current average value signal.
reference current
Operation example 9
• The pulse output of the Current average monitor (Y93) signal is indicated below.
• For the terminal used for the Y93 signal output, assign the function by setting "93" (positive logic) or "193" (negative logic)
in any parameter of Pr.190, Pr.191, Pr.193 to Pr.196 (Output terminal function selection). (This cannot be assigned by
10
setting in Pr.192 ABC terminal function selection.)
Time
1 cycle (20 s) Next cycle
Y93 signal
Data output mask time End pulse
When the speed has changed to constant output as low pulse
from acceleration/deceleration, Y93 signal is shape for 1 to 16.5 s
not output for Pr. 556 time.
Maintenance timer pulse
Start pulse The maintenance timer value (Pr. 503) is output
Output as Hi pulse shape for 1 s (fixed) as Hi output pulse shape for 2 to 9 s (16000h to
The output currents are averaged during the time 72000h).
period set in Pr.555. Pr. 503 100h
Signal output time= 5s
40000h
Output current average value pulse
The averaged current value is output as low pulse shape for
0.5 to 9 s (10 to 180%) during start pulse output.
output current average value (A)
Signal output time= 5s
Pr. 557 (A)
The output time range is 0.5 to 9 seconds. When the output current average value is less than 10% of the setting value in
Pr.557, the output time is 0.5 second, and when it is more than 180%, the output time is 9 seconds.
For example, when Pr.557 = 10 A and the output current average value is 15 A:
15 A/10 A × 5 s = 7.5 s, thus the Current average monitor signal maintains LOW output for 7.5 seconds.
Signal output time
(s)
9
0.5
10 180 (%)
Output current average value
Pr.503 × 100
×5s (Maintenance timer value 100%/5 s)
40000h
The output time range is 2 to 9 seconds. When Pr.503 is less than 16000 hours, the output time is 2 seconds. When it is more
than 72000 hours, the output time is 9 seconds.
Signal output time
(s)
9
2
16000 72000 (h)
Maintenance timer value
• Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
8
Parameters referred to
Pr.57 Restart coasting timepage 351, page 356
Pr.190 to Pr.196 (Output terminal function selection)page 250
9
Pr.503 Maintenance timerpage 152
10
10
157
8 (F) Settings for Acceleration/Deceleration
45
Second deceleration time 9999
0 to 3600 s Set the deceleration time used while the RT signal is ON. 8
F021 9999 The acceleration time applies to the deceleration time.
Set the frequency where the acceleration/deceleration time
147 Acceleration/deceleration time 0 to 590 Hz
9999 switches to the time set in Pr.44 and/or Pr.45.
F022 switching frequency
9999 Function disabled. 9
Set the acceleration time in a low-speed range (less than 1/
0 to 3600 s
791 Acceleration time in low-speed 10 of the rated motor frequency).
9999
F070 range
9999
The acceleration time set in Pr.7 is applied. (While the RT
signal is ON, the second function is enabled.)
10
Set the deceleration time in a low-speed range (less than 1/
0 to 3600 s
792 Deceleration time in low-speed 10 of the rated motor frequency).
9999
F071 range The deceleration time set in Pr.8 is applied. (While the RT
9999
signal is ON, the second function is enabled.)
1103 Deceleration time at Set the motor deceleration time at a deceleration by turning
5s 0 to 3600 s
F040 emergency stop ON the X92 signal.
*1 Gr.1 and Gr.2 are the parameter initial value groups. (Refer to page 82.)
*2 Initial value for the FR-E820-0175(3.7K) or lower, FR-E840-0095(3.7K) or lower, and FR-E860-0061(3.7K) or lower.
*3 Initial value for the FR-E820-0240(5.5K), FR-E820-0330(7.5K), FR-E840-0120(5.5K), FR-E840-0170(7.5K), FR-E860-0090(5.5K), and FR-E860-
0120(7.5K).
RT-ON
Acceleration and
deceleration time
in low-speed range
(Pr.791, Pr.792) Output frequency 10% of the rated motor frequency
Acceleration time setting = Pr.20 setting × (Acceleration time to change the frequency from stop status to maximum
frequency) / (Maximum frequency - Pr.13 setting)
• For example, the following calculation is performed to find the setting value for Pr.7 when increasing the output frequency
to the maximum frequency of 50 Hz in 10 seconds with Pr.20 = 60 Hz (initial value) and Pr.13 = 0.5 Hz.
Pr.20
(60Hz/50Hz) Set
frequency
frequency (Hz)
Output
Time
Deceleration time setting = Pr.20 setting × (Deceleration time to change the frequency from maximum frequency to stop
status) / (Maximum frequency - Pr.10 setting)
• For example, the following calculation is used to find the setting value for Pr.8 when decreasing the output frequency from
the maximum frequency of 50 Hz in 10 seconds with Pr.20 = 120 Hz and Pr.10 = 3 Hz.
NOTE
• If the acceleration/deceleration time is set, the actual motor acceleration/deceleration time cannot be made shorter than the
shortest acceleration/deceleration time determined by the mechanical system J (moment of inertia) and motor torque.
• If the Pr.20 setting is changed, the Pr.125 and Pr.126 (frequency setting signal gain frequency) settings do not change.
Set Pr.125 and Pr.126 to adjust the gains.
• Under PM sensorless vector control, if the protective function (E.OLT) is activated due to insufficient torque in the low-speed
range, set longer acceleration/deceleration times only in the low-speed range in Pr.791 Acceleration time in low-speed range
and Pr.792 Deceleration time in low-speed range.
Output frequency
(Hz)
Set
frequency
Pr. 147
setting
Time
Pr.7 Pr.44 Pr.44 Pr.8 Pr.7 Pr.44 Pr.44 Pr.8
(Pr.45) (Pr.45)
RT signal ON
NOTE
• The reference frequency during acceleration/deceleration depends on the Pr.29 Acceleration/deceleration pattern
selection setting. (Refer to page 163.)
• The RT signal can be assigned to an input terminal by setting Pr.178 to Pr.189 (Input terminal function selection). Changing
the terminal assignment may affect other functions. Set parameters after confirming the function of each terminal.
• The RT signal is the Second function selection signal which also enables other second functions. (Refer to page 289.)
Low-speed range
(rated motor frequency/10)
Time
Acceleration time Deceleration time
in low-speed range in low-speed range
Slope set by Pr. 791 Slope set by Pr.792
Acceleration time Deceleration time
Slope set by Pr.7 Slope set by Pr.8
NOTE
• Set Pr.791 (Pr.792) to a value larger than the Pr.7 (Pr.8) setting. If set as Pr.791 < Pr.7, the operation is performed as Pr.791
= Pr.7. If set as Pr.792 < Pr.8, the operation is performed as Pr.792 = Pr.8.
Time
Start signal ON OFF ON
X92 OFF ON OFF
NOTE
• The X92 signals can be assigned to an input terminal by setting Pr.178 to Pr.189 (Input terminal function selection).
Changing the terminal assignment may affect other functions. Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.3 Base frequencypage 376
Pr.10 DC injection brake operation frequencypage 382
Pr.29 Acceleration/deceleration pattern selectionpage 163
Pr.125, Pr.126 (frequency setting gain frequency)page 273
Pr.178 to Pr.189 (Input terminal function selection)page 283
29 Acceleration/deceleration pattern
0 Linear acceleration/deceleration 3
0 1 S-pattern acceleration/deceleration A
F100 selection
2 S-pattern acceleration/deceleration B
[Linear acceleration
/ deceleration]
6
(Hz)
Time
7
S-pattern acceleration/deceleration A (Pr.29 = "1")
• Use this when acceleration/deceleration is required for a short time until a high-speed area equal to or higher than the base 8
frequency, such as for the main shaft of the machine.
• The acceleration/deceleration pattern has the Pr.3 Base frequency (Pr.84 Rated motor frequency under PM motor
control) (fb) as the point of inflection in an S-pattern curve, and the acceleration/deceleration time can be set to be suitable 9
for the motor torque reduction in the constant-power operation range at the base frequency (fb) or more.
Setting value "1"
[S-pattern acceleration 10
Output frequency
/deceleration A]
fb
(Hz)
Time
• Acceleration/deceleration time calculation method when the set frequency is equal to or higher than the base frequency
NOTE
• For the acceleration/deceleration time setting of the S-pattern acceleration/deceleration A, set the time to Pr.3 (Pr.84 under
PM sensorless vector control) instead of Pr.20 Acceleration/deceleration reference frequency.
f1
Output frequency
f2
(Hz)
Time
NOTE
• When the RT signal turns ON during acceleration or deceleration with the S-pattern acceleration/deceleration B enabled, a
pattern of acceleration or deceleration changes to linear at the moment.
• When acceleration/deceleration time (such as Pr.7 and Pr.8) is set to "0 s" under Real sensorless vector control, linear
acceleration and deceleration are performed for the S-pattern acceleration/deceleration (Pr.29 ="1 or 2").
• Set linear acceleration/deceleration (Pr.29 = "0" (initial setting)) when torque control is performed under Real sensorless vector
control. When acceleration/deceleration patterns other than the linear acceleration/deceleration are selected, the protective
function of the inverter may be activated.
Parameters referred to
Pr.3 Base frequencypage 376
Pr.7 Acceleration time, Pr.8 Deceleration time, Pr.20 Acceleration/deceleration reference frequencypage 158
Even if the operation panel is located away from the enclosure, contact signals can be used to perform continuous variable-
speed operation, without using analog signals. 2
Description
Initial Setting
Pr. Name RH, RM, RL signal Frequency setting Deceleration to the
value range
function storage main speed or lower 3
0 Multi-speed setting —
1 Remote setting Enabled
2 Remote setting Disabled
Disabled Not available 4
(Turning OFF the STF/STR
3 Remote setting
signal clears the remotely-
59 Remote function
F101 selection
0
11 Remote setting
set frequency.)
Enabled
5
12 Remote setting Disabled
Disabled Available
13 Remote setting
(Turning OFF the STF/STR
signal clears the remotely-
6
set frequency.)
STF/STR Forward/Reverse
The inverter accelerates the motor in the forward or reverse direction up to
the main speed or to the frequency stored by the remote setting function.
8
RH Acceleration The set frequency increases according to the Pr.44 setting.
RM Deceleration The set frequency decreases according to the Pr.45 setting.
RL Clear The set frequency is cleared and the main speed is applied. 9
The setting of the main speed is used as a base. The main speed is
Terminal 2 (analog signal) Main speed
increased by the RH signal and decreased by the RM signal.
Connection
diagram for remote setting Time
RH (Acceleration) ON
RM (Deceleration) ON
RL (Clear) ON
STF (Forward) ON
Main speed
• The main speed used in the remote setting corresponds with each of the following operation modes.
Operation mode Main speed
PU operation mode / NET operation mode Digital setting
External operation mode / PU/External combined operation mode 2 (Pr.79 = "4") Analog input
PU/External combined operation mode 1 (Pr.79 = "3") Analog input via terminal 4 (AU signal ON)
Acceleration (RH) ON
Deceleration (RM) ON
Set frequency
Time
Pr.44 Pr.45
Output frequency
Time
Pr.7 Pr.8
NOTE
• If the time setting of the output frequency is longer than the time setting of the set frequency, the motor accelerates/decelerates
according to the time setting of the output frequency.
Forward rotation(STF) ON
ON
Acceleration(RH)
ON
Deceleration(RM)
• Regardless of whether the remote setting is enabled or disabled, the acceleration/deceleration time set for the output
frequency can be changed to the second acceleration/deceleration time by turning ON the RT signal.
• The acceleration/deceleration time setting of the set frequency is fixed at the Pr.44/Pr.45 setting.
• Storage conditions
The remotely-set frequency is stored at the point when the start signal (STF or STR) turns OFF. The remotely-set
frequency is stored every minute after turning OFF (ON) the RH and RM signals together. Every minute, the frequency is
overwritten in the EEPROM if the latest frequency is different from the previous one when comparing the two. This cannot
be written using the RL signal.
5
Acceleration(RH) ON
Deceleration(RM) ON
Forward rotation(STF) ON
• Even if the start signal (STF or STR) is OFF, turning ON the RH or RM signal varies the preset frequency.
• The RH, RM, or RL signal can be assigned to an input terminal by setting Pr.178 to Pr.189 (Input terminal function 6
selection). Changing the terminal assignment may affect other functions. Set parameters after confirming the function of each
terminal.
• The inverter can be used in the Network operation mode.
• The remote setting function is invalid during JOG operation and PID control operation.
7
• The multi-speed operation function is invalid when remote setting function is selected.
Within 1 minute
Acceleration (RH) ON
Deceleration (RM) OFF
ON
Clear (RL)
Forward rotation ON ON
(STF)
Power supply ON ON
Output frequency
(Hz)
one minute
Operation is performed at the set
frequency 0Hz.
Time
Acceleration (RH) ON
Deceleration (RM) OFF
ON
Clear (RL)
CAUTION
• When using the remote setting function, set the maximum frequency again according to the machine.
Parameters referred to
Pr.1 Maximum frequency, Pr.18 High speed maximum frequencypage 211
Pr.7 Acceleration time, Pr.8 Deceleration time, Pr.44 Second acceleration/deceleration time, Pr.45 Second deceleration timepage 158
Pr.178 to Pr.189 (Input terminal function selection)page 283
13
Pr. Name Initial value Setting range Description
Set the starting frequency at which the start signal is turned
3
Starting frequency 0.5 Hz 0 to 60 Hz
F102 ON.
571 0 to 10 s Set the holding time of the frequency set in Pr.13.
Holding time at a start 9999
F103 9999 The holding function at start is disabled. 4
Starting frequency setting (Pr.13)
• The frequency at start can be set in the range of 0 to 60 Hz.
• Set the starting frequency at which the start signal is turned ON.
5
Output
frequency
(Hz)
60
6
Setting range
Pr.13 7
0
Time
STF ON
8
NOTE
• The inverter does not start if the frequency setting signal has a value lower than that of Pr.13.
For example, while Pr.13 = 5 Hz, the inverter output starts when the frequency setting signal reaches 5 Hz. 9
Pr.13
0
Time
Pr. 571 setting time
STF ON
NOTE
• When Pr.13 = 0 Hz, the starting frequency is held at 0.01 Hz.
• When the start signal was turned OFF during start-time hold, deceleration is started at that point.
• At switching between forward rotation and reverse rotation, the starting frequency is valid but the start-time hold function is
disabled.
CAUTION
• Note that when Pr.13 is set to a value equal to or lower than the setting of Pr.2 Minimum frequency, simply turning ON
the start signal runs the motor at the frequency set in Pr.2 even if the command frequency is not given.
Parameters referred to
Pr.2 Minimum frequencypage 211
Set frequency
Output
frequency
Pr.13
0
Time
Output from 0.01Hz
STF ON
NOTE
• Under induction motor control (under V/F control, Advanced magnetic flux vector control, and Real sensorless vector control),
the output starts at the frequency set in Pr.13. Under PM sensorless vector control, the output always starts at 0.01 Hz.
• The inverter does not start if the frequency setting signal has a value lower than that of Pr.13. For example, while Pr.13 = 20
Hz, the inverter output starts when the frequency setting signal reaches 20 Hz.
CAUTION
• Note that when Pr.13 is set to a value equal to or lower than Pr.2 Minimum frequency, simply turning ON the start signal
runs the motor at the frequency set in Pr.2 even if the command frequency is not given.
Parameters referred to
Pr.2 Minimum frequencypage 211
Pr.7 Acceleration timepage 158
NOTE
• When Real sensorless vector control is selected with the shortest acceleration/deceleration, Pr.61 to Pr.63 are invalid.
• Even if Pr.61 to Pr.63 are set once, changing the setting to other than the shortest acceleration/deceleration (Pr.292 ≠ "1 or
11") automatically resets to the initial setting (9999). Set Pr.61 to Pr.63 after setting Pr.292.
Parameters referred to
Pr.7 Acceleration time, Pr.8 Deceleration timepage 158
Pr.22 Stall prevention operation levelpage 214
Pr.22 Torque limit levelpage 100
10
173
9 (D) Operation Command and Frequency
Command
Refer to
Purpose Parameter to set
page
To select the operation mode Operation mode selection P.D000 Pr.79 174
To start up the inverter in Network operation Communication startup
P.D000, P.D001 Pr.79, Pr.340 184
mode at power-ON mode selection
Operation and speed
command sources during
To select the command source during Pr.338, Pr.339, Pr.550,
communication operation, P.D010 to P.D013 185
communication operation Pr.551
command source
selection
To prevent the motor from rotating Reverse rotation
P.D020 Pr.78 193
reversely prevention selection
To change the setting resolution of the
Set resolution switchover P.D030 Pr.811 226
torque limit
To perform JOG (inching) operation JOG operation P.D200, P.F002 Pr.15, Pr.16 194
Pr.28, Pr.4 to Pr.6,
To control the frequency with combinations
Multi-speed operation P.D300 to P.D315 Pr.24 to Pr.27, Pr.232 195
of terminals
to Pr.239
To select the torque command method Torque command source P.D120, P.D121, Pr.432, Pr.433, Pr.804
117
during torque control selection P.D400 to P.D402 to Pr.806
The following table lists valid and invalid commands in each operation mode.
NET operation
mode 4
External operation 6
mode
Fixed at External operation
Sent using external signals
mode.
(input via terminal 2 or 4, using
2
However, the inverter
operation mode can also be
the JOG signal, using the
Sent using external signals (via
terminal STF or STR). NET operation
178 7
multi-speed setting function,
changed to the Network mode
etc.).
operation mode.
8
Sent from the operation panel
or sent using external signals
External/PU combined (input using the multi-speed Sent using external signals (via
3 179
operation mode 1 setting function or via terminal terminal STF or STR).
External/PU
combined 9
4).*1 operation mode
Sent using external signals
(input via terminal 2 or 4, using
4
External/PU combined
operation mode 2
the JOG signal, using the
Input using the RUN key on the
operation panel
179 10
multi-speed setting function,
etc.).
PU operation
Operation mode switchover during operation. mode
6 Switching from among the PU, External, and NET operation modes can be performed during 180
operation.
External operation
mode
*1 The following is the frequency commands listed in descending order of priority when "3" is set in Pr.79: Multi-speed setting function (RL/RM/RH/
REX signal) > PID control (X14 signal) > terminal 4 analog input (AU signal) > digital input from the operation panel.
connector 9
connector 9
External 10
External 10
Network Network
External Communication operation External Communication operation
terminal option mode terminal option mode
Programmable Programmable
Network controller Network controller
operation operation
PU connector mode Personal computer Ethernet mode Personal computer
connector
PU operation RUN MON
Hz
mode A
PU EXT
Personal computer
NOTE
• There is a choice of two settings, "3" and "4", for the External/PU combined operation mode. The startup method differs
according to the setting value.
• In the initial setting, the PU stop selection (function to stop the inverter operation by pressing the STOP/RESET key on the
operation panel) is enabled even in the operation mode other than the PU operation mode. (Refer to Pr.75 on page 128.)
4
When "10 or 12" is set in Pr. 340
Network operation
Press on the PU to light
PU operation 5
10
Frequency setting
10
2
4
potentiometer
5
Potentiometer
9
PU/External combined operation mode 1 (Pr.79 = "3")
• Select the PU/External combined operation mode 1 when giving a frequency command from the operation panel and giving 10
a start command with the external start switches.
• Set "3" in Pr.79. The mode cannot be changed to other operation modes.
• When the frequency commands are given using the multi-speed setting signals (external signals), they have a higher
priority than the frequency commands given from the PU. When the AU signal is ON, inputting the command signals via
terminal 4 is enabled.
Inverter
Operation panel
Forward rotation STF
start
Reverse rotation STR
start
Switch SD
*1 Depends on the Pr.77 Parameter write selection setting and other parameter write conditions. (Refer to page 135.)
OFF→ON Enabled
During stop During stop
External
During
ON→OFF
OFF→ON
External*2
Running→Output stop
Disabled
Disabled
3
running ON→OFF Output stop→Running Disabled
*1 The mode is switched to the External operation mode regardless of the ON/OFF state of the start signal (STF/STR). Thus, the motor runs under
the External operation mode when the X12 (MRS) signal turns OFF while the STF or STR signal is ON. 4
*2 When a fault occurs, the inverter can be reset by pressing the STOP/RESET key on the operation panel.
NOTE
• The operation mode cannot be switched to the PU operation mode with the start signal (STF/STR) ON state even if the X12 5
(MRS) signal turns ON.
• If the MRS signal is ON and Pr.79 is written to a value other than "7" when the MRS signal is used as the PU interlock signal,
the MRS signal will act as a regular MRS function (output stop). Also, when Pr.79 = "7", the MRS signal becomes the PU
interlock signal. 6
• The logic of the signal follows the Pr.17 MRS/X10 terminal input selection setting also when the MRS signal is used as the
PU operation interlock signal. When Pr.17 = "2 to 5", ON and OFF in the table above are reversed.
• Changing the terminal assignment using Pr.178 to Pr.184 (Input terminal function selection) may affect the other functions. 7
Set parameters after confirming the function of each terminal.
NOTE
• The operation mode is determined by the setting of Pr.340 Communication startup mode selection and the ON/OFF state
of the X65 and X66 signals. (For the details, refer to page 182.)
• The priority of Pr.79 and Pr.340 and signals is Pr.79 > X12 > X66 > X65 > X16 > Pr.340.
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
3. Set "65" in any parameter from Pr.178 to Pr.184 to assign the PU/NET operation switchover (X65) signal to a
terminal.
4. When the X65 signal is ON, the PU operation mode is selected. When the X65 signal is OFF, the NET operation
mode is selected.
X12 (MRS) Switching between the External operation mode The signal is OFF during operation in the External
ON and PU operation mode is enabled.*2 operation mode.
7
X12 (MRS) The operation mode is forcibly switched to the
External operation mode
OFF External operation mode.
*1 When the X66 signal is ON, the NET operation mode is selected.
*2 When the X16 signal is OFF, the PU operation mode is selected. Also, when "0" is set for Pr.550 NET mode operation command source
selection and the communication option is not connected (communication option is the command source), the PU operation mode is selected.
When the X16 signal is ON, the External operation mode is selected.
• To switch between the Network operation mode and the External operation mode
1. Set Pr.79 = "0 (initial value), 2, 6, or 7". (When Pr.79 = "7" and the X12 (MRS) signal is ON, the operation mode can
be switched.)
2. Set Pr.340 Communication startup mode selection = "0" (initial value) or "1".
3. Set "66" in one of Pr.178 to Pr.184 to assign the NET-External operation switching signal (X66) to a terminal.
4. When the X66 signal is ON, the NET operation mode is selected. When the X66 signal is OFF, the External
operation mode is selected.
0 (initial 3, 4 External/PU combined operation mode Fixed at External/PU combined operation mode.
value), 1 External operation The operation mode can be changed during
6 NET operation mode*1
mode*2 operation.
X12 (MRS) External operation The signal is OFF during operation in the External
NET operation mode*1
ON mode*2 operation mode.
7
X12 (MRS) The operation mode is forcibly switched to the
External operation mode
OFF External operation mode.
*1 When Pr.550 NET mode operation command source selection = "0" (communication option control source) and no communication option is
connected, the External operation mode is selected.
*2 When the X16 signal is OFF, the PU operation mode is selected. Also, when the X65 signal is assigned, the operation mode follows the ON/OFF
state of the X65 signal.
2
Parameters referred to
Pr.15 Jog frequencypage 194
Pr.4 to Pr.6, Pr.24 to Pr.27, Pr.232 to Pr.239 multi-speed operationpage 195
Pr.75 Reset selection/disconnected PU detection/PU stop selectionpage 128
Pr.161 Frequency setting/key lock operation selectionpage 130
3
Pr.178 to Pr.189 (Input terminal function selection)page 283
Pr.190 to Pr.196 (Output terminal function selection)page 250
Pr.340 Communication startup mode selectionpage 184
Pr.550 NET mode operation command source selectionpage 185
4
10
Parameters referred to
Pr.57 Restart coasting timepage 351, page 356
Pr.79 Operation mode selectionpage 174
Pr. Name
Initial Setting
Description
3
value range
Communication 0 Start command source is communication.
338
operation command 0
D010
source 1 Start command source is external.
4
0 Frequency command source is communication.
1 Frequency command source is external.
339 Communication speed
0
D011 command source
2
Frequency command source is external. (When there is no external
input, the frequency command given via communication is valid, and 5
the frequency command given via terminal 2 is invalid.)
The communication option is the command source in the NET
0
2*1
operation mode.
The PU connector is the command source in the NET operation mode.
6
NET mode operation The Ethernet connector is the command source in the NET operation
550 5*2
command source 9999 mode.
D012
selection
The communication option is recognized automatically. 7
Normally, the PU connector or Ethernet connector is the command
9999
source. When the communication option is installed, the
communication option is the command source.
2*1 The PU connector is the command source in the PU operation mode. 8
3 The USB connector is the command source in the PU operation mode.
PU mode operation
551 4 The operation panel is the command source in the PU operation mode.
command source 9999
D013
selection
9999
The USB is recognized automatically.
Normally, the operation panel is the command source. When the USB 9
is connected, the USB connector is the command source.
NOTE
• In the initial setting, "9999" (communication option automatic recognition) is set for Pr.550. Thus, if the communication option
is installed, parameters cannot be written or the start and frequency commands cannot be sent by communications through
the PU connector or the Ethernet connector. (Monitoring or parameter reading can be performed.)
• Standard model
Command source
Pr.550 Pr.551 PU connector
Operation USB Communication Remarks
setting setting Operation RS-485
panel connector option
option*1 communication
2 × × PU PU*2 NET*3
3 × PU × × NET*3
0 4 PU × × × NET*3
9999 (initial
value) PU*4 PU*4 PU*4 × NET*3
PU Switching to NET
2 × × PU*2 ×
operation mode disabled
3 × PU × NET ×
2
4 PU × × NET ×
9999 (initial
value) PU*4 PU*4 PU*4 NET ×
2 × × PU PU*2 NET*3
× With communication
NET*3 option
3 × PU ×
NET Without communication
×
option
9999 × With communication
(initial NET*3 option
value) 4 PU × ×
NET Without communication
×
option
With communication
× NET*3 option
9999 (initial
value) PU*4 PU*4 PU*4
Without communication
NET ×
option
• Ethernet model
Command source
Pr.550 Pr.551
Ethernet Communication Remarks
setting setting Operation panel USB connector
connector option
3 × PU × NET*3
0 4 PU × × NET*3
9999 (initial
value) PU*4 PU*4 × NET*3
3 × PU NET ×
4 PU × NET ×
5
9999 (initial
value) PU*4 PU*4 NET ×
PU: Enabled in PU operation mode, NET: Enabled in Network operation mode, ×: Not available
*1 When the enclosure surface operation panel (FR-PA07) is used.
*2 The MODBUS RTU protocol cannot be used in the PU operation mode.
10
Combined Combined
NET
operation
1
Command NET
Condition Item PU External operation operation (when the
interface operation
operation operation mode 1 mode 2 PU/Ethernet
(via option)
(Pr.79 = "3") (Pr.79 = "4") connector
is used) 2
Operation command
○ × × ○ × ×
(start, stop)
Frequency setting
Pr.551 = "3, 9999" Monitor
○
○
×
○
○
○
×
○
×
○
×
○
3
Parameter write ○*5 ×*6 ○ ○ ×*6 ×*6
Parameter read ○ ○ ○ ○ ○ ○
USB Inverter reset ○ ○ ○ ○ ○ ○ 4
connector Operation command
× × × × × ×
(start, stop)
Frequency setting × × × × × ×
Other than the Monitor ○ ○ ○ ○ ○ ○
5
above
Parameter write ×*6 ×*6 ×*6 ×*6 ×*6 ×*6
Parameter read ○ ○ ○ ○ ○ ○
Inverter reset ○ ○ ○ ○ ○ ○ 6
Operation command
(start, stop)
× × × × — ○*4
RT*1
Second function selection/ Stop-on-contact
NET EXT
Pr.270 = "1" (stop-on-contact) 5
selection 1
AU*1 Terminal 4 input selection — Combined — Combined
JOG*1 Jog operation selection — EXT
OH*1 External thermal relay input EXT
6
REX*1 15-speed selection NET EXT NET EXT Pr.59 ="0" (multi-speed)
*1 Inverter run enable EXT
X10
X12 *1 PU operation external interlock EXT
7
X14*1 PID control valid NET EXT NET EXT
*1 Brake opening completion NET EXT
BRI
X16*1 PU/External operation switchover EXT
8
X18*1 V/F switchover NET EXT
Output stop Combined EXT Pr.79 ≠ "7"
MRS*1 Pr.79 = "7". 9
PU operation interlock EXT
When X12 signal is not assigned.
STP
Start self-holding selection — EXT
(STOP)*1
10
MC*1 Control mode switchover NET EXT
TL*1 Torque limit selection NET EXT
*1 NET EXT
JOG2
X37*1 Traverse function selection NET EXT
TRG*1 Trace trigger input Combined EXT
TRC*1 Trace sampling start/end Combined EXT
Pr.414 = "1": Valid when there is
SQ*1 Sequence start EXT or NET EXT external or network input.
Pr.414 = "2": External.
X51*1 Fault clear Combined EXT
STF*1 Forward rotation command NET EXT
*1 Reverse rotation command NET EXT
STR
*1 Inverter reset EXT
RES
X65*1 PU/NET operation switchover EXT
*1 External/NET operation switchover EXT
X66
*1 Command source switchover EXT
X67
*1 PID P control switchover NET EXT NET EXT
X72
*1 Emergency stop Combined EXT
X92
*1 Use Pr.178 to Pr.189 (Input terminal function selection) to assign the function to an input terminal. (Refer to page 283.)
NOTE
• The ON/OFF state of the X67 signal is applied only during a stop. When the terminals are switched during operation, the ON/
OFF state is reflected after a stop.
• When the X67 is OFF, a reset via communication is disabled.
• Changing the terminal assignment using Pr.178 to Pr.184 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.59 Remote function selectionpage 165
Pr.79 Operation mode selectionpage 174
This function can prevent reverse rotation fault resulting from the incorrect input of the start signal.
Pr. Name Initial value Setting range Description
2
0 Both forward and reverse rotations allowed
78 Reverse rotation
0 1 Reverse rotation disabled
D020 prevention selection
2 Forward rotation disabled 3
• Set this parameter to limit the motor rotation to only one direction.
• This parameter is valid for all of the RUN key of the operation panel, the start signals (STF, STR signals) via external
terminals, and the forward and reverse rotation commands through communication. 4
10
JOG/JOG2 signal ON
NOTE
• The reference frequency during acceleration/deceleration depends on the Pr.29 Acceleration/deceleration pattern
selection setting. (Refer to page 163.)
• The Pr.15 setting should be equal to or higher than the Pr.13 Starting frequency setting.
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
• During JOG operation, the second acceleration/deceleration function using the RT signal is disabled. (Other second functions
are enabled (refer to page 289).)
• When Pr.79 Operation mode selection = "4", JOG operation is started by one push of the RUN key on the operation panel
and stopped by the STOP/RESET key.
• This function is invalid when Pr.79 = "3".
Parameters referred to
Pr.13 Starting frequencypage 169
Pr.20 Acceleration/deceleration reference frequency, Pr.21 Acceleration/deceleration time incrementspage 158
Pr.29 Acceleration/deceleration pattern selectionpage 163
Pr.79 Operation mode selectionpage 174
Pr.178 to Pr.189 (Input terminal function selection)page 283
Use these parameters to change among pre-set operation speeds with the terminals. The speeds are pre-set with parameters.
Any speed can be selected by simply turning ON/OFF the contact signals (RH, RM, RL, and REX signals). 2
Initial value*1
Pr. Name Setting range Description
Gr.1 Gr.2
4
Multi-speed setting (high speed) 60 Hz 50 Hz 0 to 590 Hz Sets the frequency when RH is ON.
3
D301
5 Multi-speed setting (middle
30 Hz 0 to 590 Hz Sets the frequency when RM is ON.
D302 speed)
6 4
Multi-speed setting (low speed) 10 Hz 0 to 590 Hz Sets the frequency when RL is ON.
D303
24
Multi-speed setting (speed 4)
D304
25
5
Multi-speed setting (speed 5)
D305
26
Multi-speed setting (speed 6)
D306
27
6
Multi-speed setting (speed 7)
D307
232
Multi-speed setting (speed 8)
D308 7
233 Frequency from 4th speed to 15th speed can
Multi-speed setting (speed 9)
D309 be set according to the combination of the RH,
9999 0 to 590 Hz, 9999
234 RM, RL and REX signals.
D310
Multi-speed setting (speed 10)
9999: Not selected 8
235
Multi-speed setting (speed 11)
D311
236
D312
Multi-speed setting (speed 12)
9
237
Multi-speed setting (speed 13)
D313
238
D314
Multi-speed setting (speed 14)
10
239
Multi-speed setting (speed 15)
D315
*1 Gr.1 and Gr.2 are the parameter initial value groups. (Refer to page 82).
Inverter Speed 1
Output frequency (Hz)
(High speed)
NOTE
• In the initial setting, if two or more speed switches (signals) are simultaneously turned ON, priority is given to the switch (signal)
for the lower speed. For example, when both RH and RM signals turn ON, the RM signal (Pr.5) has the higher priority.
• The RH, RM and RL signals are assigned to the terminals RH, RM and RL, respectively, in the initial status. To assign each
signal to a different terminal, set "0" (RL signal), "1" (RM signal), or "2" (RH signal) in any of Pr.178 to Pr.189 (Input terminal
function selection).
Output frequency
Speed 10
Speed 5 Speed 11
Speed 6 Speed 12
Forward Speed 9
Speed 13
rotation Inverter Speed 4 Speed 8
STF Speed 14
(Hz)
Multi-speed selection
Speed 7 Speed 15
REX
RH Time
ON ON ON ON ON ON ON
RM RH
RL ON ON ON ON ON ON ON
RM
SD ON ON ON ON ON ON
RL
ON ON ON ON ON ON ON ON
REX
∗1
*1 When the RH, RM and RL signals are OFF and the REX signal is ON while "9999" is set to Pr.232 Multi-speed setting (speed 8), the inverter
operates at the frequency set in Pr.6.
NOTE
• The priority of the frequency commands given by the external signals are as follows: JOG operation > multi-speed operation
> terminal 4 analog input > terminal 2 analog input. (For details on frequency commands given by analog input, refer to page
273.)
• The input compensation of multi-speed setting is enabled when the inverter is in the External operation mode or PU/External
combined operation mode (Pr.79 = "3 or 4").
• Multi-speed parameters can also be set during PU operation or External operation.
• The Pr.24 to Pr.27 and Pr.232 to Pr.239 settings have no priority among them.
• When Pr.59 Remote function selection ≠ "0", the multi-speed setting is invalid since the RH, RM, and RL signals are for
remote setting.
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.15 Jog frequencypage 194
Pr.59 Remote function selectionpage 165
Pr.79 Operation mode selectionpage 174
Pr.178 to Pr.189 (Input terminal function selection)page 283
10
197
10 (H) Protective Function Parameters
Purpose Parameter to set Refer to page
To protect the motor from overheating Electronic thermal O/L relay P.H000, P.H010 Pr.9, Pr.51 198
Cooling fan operation
To extend the life of the cooling fan P.H100 Pr.244 203
selection
Earth (ground) fault detection
To detect an earth (ground) fault at start P.H101 Pr.249 204
at start
Inverter output fault
To detect a fault on the output side of
detection enable/disable P.H182 Pr.631 205
the inverter
selection
To initiate an inverter protective
Fault initiation P.H103 Pr.997 206
function
To disable the I/O phase loss protective
I/O phase loss P.H200, P.H201 Pr.251, Pr.872 207
function
To restart using the retry function when
Retry operation P.H300 to P.H303 Pr.65, Pr.67 to Pr.69 208
the protective function is activated
To set the upper and lower limits of the Maximum/minimum
P.H400 to P.H402 Pr.1, Pr.2, Pr.18 211
output frequency frequency
To prevent the motor from
Speed limit P.H410 to P.H412 Pr.807 to Pr.809 120
overspeeding under torque control
To avoid overdriving the motor during
Overdriving prevention P.H416, P.H417 Pr.285, Pr.853 109
speed control
To operate avoiding resonance points Frequency jump P.H420 to P.H425 Pr.31 to Pr.36 212
P.H500, P.H501,
Pr.22, Pr.23, Pr.48,
To limit the output current so that the P.H600, P.H610,
Pr.66, Pr.154,
inverter protective function does not Stall prevention P.H611, P.H630, 214
Pr.156, Pr.157,
activate P.H631, P.M430,
Pr.277, Pr.858
P.T040
P.H500, P.H700 to
Pr.22, Pr.801,
P.H704, P.H710,
Pr.803, Pr.810,
To limit the torque during speed control Torque limit P.H720, P.H721, 100
Pr.812 to Pr.817,
P.H730, P.T040,
Pr.858, Pr.874
P.G210
Load characteristics fault P.H520 to P.H527,
To monitor for load faults Pr.1480 to Pr.1492 219
detection P.H531 to P.H535
To shut off output if the operation panel
Overspeed detection level P.H800 Pr.374 224
disconnects
70 30Hz or more*3
30Hz
this region
or more*3 20Hz
4
Operation region
20Hz 10Hz Region on the right of
60 characteristic curve
10Hz
6Hz Non-operation region
6Hz
0.5Hz Region on the left of
50 0.5Hz characteristic curve
Characteristic when
electronic thermal relay 5
Second display in this region
NOTE
• The internal accumulated heat value of the electronic thermal relay function is reset to the initial value by the inverter's power
10
reset or reset signal input. Avoid unnecessary reset and power-OFF.
• Install an external thermal relay (OCR) between the inverter and motors to operate several motors, a multi-pole motor or a
dedicated motor with one inverter. When setting an external thermal relay, note that the current indicated on the motor rating
plate is affected by the line-to-line leakage current. The cooling effect of the motor drops during low-speed operation. Use a
motor with built-in thermal protector. (For details of the line-to-line leakage current, refer to the Instruction Manual
(Connection).)
• When the difference between the inverter and motor capacities is large and the set value is small, the protective characteristics
of the electronic thermal relay function will be deteriorated. Use an external thermal relay in such cases.
• A dedicated motor cannot be protected by an electronic thermal O/L relay. Use an external thermal relay.
• The transistor protection thermal O/L relay is activated early when the Pr.72 PWM frequency selection setting is increased.
2000r/min
Thermal relay
(133.33Hz) or lower
this region
60
3000r/min
50 (200Hz)
240
2000r/min
Thermal relay operation time [s]
Second display in this region
(133.33Hz) or lower
180
3000r/min
(200Hz)
120
Range for the
transistor
protection
60
0
80 100 120 140 160 200 220 240 260 280 300
Current [%] ∗∗
Protective function activated area: the area right of the characteristic curve
Normal operation area: the area left of the characteristic curve
NOTE
• The internal accumulated heat value of the electronic thermal relay function is reset to the initial value by the inverter's power
reset or reset signal input. Avoid unnecessary reset and power-OFF.
• The transistor protection thermal O/L relay is activated early when the Pr.72 PWM frequency selection setting is increased.
MC
U
V M
W
RT
SD
• These settings are used when rotating two motors with different rated current separately by a single inverter. (When
rotating two motors together, use an external thermal relay.)
• Set the rated motor current for the second motor in Pr.51 Second electronic thermal O/L relay.
NOTE
• The RT signal is the Second function selection signal. The RT signal also enables other second functions. (Refer to page 289.) 7
• For the RT signal, set "3" in any parameter from Pr.178 to Pr.189 (Input terminal function selection) to assign the function.
Electronic thermal O/L relay pre-alarm (TH) and warning signal (THP 8
signal)
• If the accumulated electronic thermal value reaches 85% of the Pr.9 or Pr.51 setting, electronic thermal O/L relay function 9
pre-alarm (TH) is displayed and the electronic thermal O/L relay pre-alarm (THP) signal is output. If the value reaches
100% of the Pr.9 setting, the motor thermal protection (E.THM/E.THT) is activated to shut off the inverter output. The
inverter output is not shut off with the TH display. 10
• For the terminal used for the THP signal output, set "8" (positive logic) or "108" (negative logic) in any parameter from
Pr.190 to Pr.196 (Output terminal function selection).
Electronic thermal 100%
relay function 85%
operation level
NOTE
• Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
NOTE
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.71 Applied motorpage 294
Pr.72 PWM frequency selectionpage 146
Pr.178 to Pr.189 (Input terminal function selection)page 283
Pr.190 to Pr.196 (Output terminal function selection)page 250
NOTE
• The cooling fan is installed on the FR-E820-0080(1.5K) or higher, the FR-E840-0040(1.5K) or higher, and FR-E860-
0027(1.5K) of higher.
• Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.190 to Pr.196 (Output terminal function selection)page 250
NOTE
• Because the detection is performed at start, output is delayed for approx. 20 ms every start.
• Use Pr.249 to enable/disable ground fault detection at operation start.
10
NOTE
• If a protective function is already operating, no fault can be activated by Pr.997.
• The retry function is disabled when a protective function has been initiated by the fault initiation function.
• If a fault occurs after a protective function has been activated, the protective function indication does not change. The fault is
not saved in the fault history either.
The output phase loss protection function, which stops the inverter output if one of the three phases (U, V, W) on the inverter's
output side (load side) is lost, can be disabled. 2
The input phase loss protective function on the inverter input side (R/L1, S/L2, T/L3) can be disabled.
NOTE
• When several motors are connected, output phase loss cannot be detected even if the wiring to one motor loses phase. 7
• In the case of R/L1, S/L2 phase loss, the input phase loss protection does not operate, and the inverter output is shut off.
• If an input phase loss continues for a long time, the lives of converter section and capacitor of the inverter become shorter.
• If the load is light or during a stop, lost phase cannot be detected because detection is performed based on the fluctuation of
bus voltage. Large unbalanced phase-to-phase voltage of the three-phase power supply may also cause input phase loss
8
protection (E.ILF).
• Phase loss cannot be detected during regeneration load operation.
9
Parameters referred to
Pr.261 Power failure stop selectionpage 362
10
Initial
Pr. Name Setting range Description
value
65
Retry selection 0 0 to 5 Faults which trigger the retry operation can be selected.
H300
0 The retry function disabled.
Set the number of retries at a fault occurrence.
1 to 10
67 Number of retries at fault A fault output is not provided during the retry operation.
0
H301 occurrence Set the number of retries at a fault occurrence. (The setting value minus
101 to 110 100 is the number of retries.)
A fault output is provided during the retry operation.
68 Set the time delay from when an inverter fault occurs until the retry
Retry waiting time 1s 0.1 to 600 s
H302 operation starts.
69 Retry count display Setting "0" clears the retry success counter ("retry success" means that
0 0
H303 erase the inverter successfully restarts).
• When retries fail consecutively more than the number of times set in Pr.67, a retry count excess (E.RET) occurs, resulting
in an inverter retries. (Refer to the Retry failure example.)
• Use Pr.68 to set the waiting time from a protective function activation to a retry in the range of 0.1 to 600 s.
• During retry operation, the During retry (Y64) signal is ON. For the Y64 signal, set "64" (positive logic) or "164" (negative
logic) in any parameter from Pr.190 to Pr.196 (Output terminal function selection) to assign the function.
Y64 ON
(ALM)
Y64 ON ON ON
4
Retry success example Retry failure example
NOTE
• Use the retry function only when the operation can be resumed after resetting a protective function activation. Making a retry
against the protective function, which is activated by an unknown condition, will lead the inverter and motor to be faulty. Identify
and remove the cause of the protective function activation before restarting the operation.
• If the retry function operates during PU operations, the operating conditions (forward/reverse rotation) are stored; and
operations resume after retry reset.
• Only the fault details for the first fault that occurred during retry are stored in the fault history.
• The reset by the retry function does not clear the accumulated data of the electronic thermal O/L relay, regenerative brake
duty, etc. (This is different from power supply reset or reset by RES signal.)
• When the parameter storage device fault (E.PE) is occurring and reading of the retry-function-related parameters is not
possible, retry cannot operated.
• Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.57 Restart coasting timepage 351, page 356
1
Pr. Name Initial value Setting range Description
3
Maximum frequency 120 Hz 0 to 120 Hz Set the upper limit of the output frequency.
H400
2
Minimum frequency 0 Hz 0 to 120 Hz Set the lower limit of the output frequency.
H401
18 High speed maximum
4
120 Hz 0 to 590 Hz Set when operating at 120 Hz or higher.
H402 frequency
Output frequency
Clamped at the
maximum frequency 7
(Hz)
Pr.1
Pr.18
8
Pr.2 Frequency setting
9
0 5, 10V
Clamped at the (4mA) (20mA)
minimum frequency
NOTE
• To operate with a frequency higher than 60 Hz using frequency-setting analog signals, change the Pr.125 (Pr.126) (frequency
setting gain) setting. Simply changing the Pr.1 and Pr.18 settings does not enable the operation at a frequency higher than
60 Hz.
• Under Real sensorless vector control and PM sensorless vector control, the upper and lower limits are for the commanded
frequency. The final output frequency that is decided by each control may exceed the lower or upper limits.
• When Pr.15 Jog frequency is equal to or less than Pr.2, the Pr.15 setting takes precedence.
• If a jump frequency that exceeds the setting of Pr.1 (Pr.18) is set, the maximum frequency setting is the set frequency. If the
jump frequency is less than the setting of Pr.2, the jump frequency is the set frequency. (The set frequency can be equal to or
less than the frequency lower limit.) When stall prevention is activated to decrease the output frequency, the output frequency
may drop to Pr.2 or below.
CAUTION
• Note that when Pr.2 is set to any value equal to or higher than Pr.13 Starting frequency, simply turning ON the start
signal runs the motor at the frequency set in Pr.2 even if the command frequency is not given.
Parameters referred to
Pr.13 Starting frequencypage 169, page 170
Pr.15 Jog frequencypage 194
Pr.125 Terminal 2 frequency setting gain frequency, Pr.126 Terminal 4 frequency setting gain frequencypage 273
Frequency jump
Pr.36
frequency jump (Hz)
Set frequency after
Pr.35
Pr.33
Pr.34
Pr.32
Pr.31
Example 1) To fix the frequency to 30 Hz in the range of 30 Hz to 35 Hz, set 35 Hz in Pr.34 and 30 Hz in Pr.33.
Pr.34: 35 Hz
Pr.33: 30 Hz
Example 2) To jump the frequency to 35 Hz in the range of 30 Hz to 35 Hz, set 35 Hz in Pr.33 and 30 Hz in Pr.34.
Pr.33: 35 Hz
Pr.34: 30 Hz
Pr.32 Pr.32
3
Maximum frequency (Pr.1) Minimum frequency (Pr.2)
Pr.31 Pr.31
4
Set frequency Set frequency
Maximum frequency and frequency jump Minimum frequency and frequency jump
5
Parameters referred to
Pr.1 Maximum frequency, Pr.2 Minimum frequency, Pr.18 High speed maximum frequencypage 211
10
This function monitors the output current and automatically changes the output frequency to prevent the inverter from shutting
off due to overcurrent, overvoltage, etc. It can also limit the stall prevention and fast-response current limit operation during
acceleration/deceleration and power/regenerative driving.
This function is disabled under Real sensorless vector control and PM sensorless vector control.
• Stall prevention:
If the output current exceeds the stall prevention operation level, the output frequency of the inverter is automatically
changed to reduce the output current. Also, the second stall prevention function can limit the output frequency range in
which the stall prevention function is enabled.
• Fast-response current limit:
If the current exceeds the limit value, the output of the inverter is shut off to prevent an overcurrent.
Initial value*1
Pr. Name Setting range Description
Gr.1 Gr.2
0 Stall prevention operation disabled.
22 Stall prevention
150% Set the current limit at which the stall prevention operation
H500 operation level 0.1% to 400%*2 starts.
156 Stall prevention Enable/disable the stall prevention operation and the fast-
0 0 to 31, 100, 101
H501 operation selection response current limit operation.
0 Second stall prevention operation disabled.
48 Second stall prevention The stall prevention operation level can be changed using
H600 operation level
9999 0.1% to 400%*2 the RT signal.
9999 Same as Pr.22.
Stall prevention The stall operation level when running at high speeds above
0% to 200%
23 operation level the rated frequency can be reduced.
9999
H610 compensation factor at
9999 Stall prevention operation disabled at double speed.
double speed
Stall prevention
66 Set the frequency at which the stall operation level reduction
operation reduction 60 Hz 50 Hz 0 to 590 Hz
H611 starts.
starting frequency
Voltage reduction 1 Does not suppress the overvoltage protective function
154
selection during stall 1
H631 11 Suppresses the overvoltage protective function
prevention operation
Set the OL signal output start time when stall prevention is
157 0 to 25 s
OL signal output timer 0s activated.
M430
9999 No OL signal output.
277 0 Stall prevention is activated when the output current
H630 Stall prevention exceeds the stall prevention operation level.
operation current 0 1 Stall prevention is activated when the output torque (current
switchover equivalent to the torque) exceeds the stall prevention
operation level.
*1 Gr.1 and Gr.2 are the parameter initial value groups. (Refer to page 82).
*2 The upper limit of stall prevention operation is limited internally to the following.
150% (LD rating), 200% (ND rating)
Output frequency
this parameter in the initial setting. 2
• Stall prevention operation stops acceleration (makes
n De
io deceleration) during acceleration, makes deceleration
at ce
er
3
l le
ce Constant ra during constant speed, and stops deceleration during
Ac speed tio
n
deceleration.
Time
OL • When the stall prevention operation is performed, the
Stall prevention operation example Overload warning (OL) signal is output. 4
NOTE
• A continuous overloaded condition may activate a protective function such as motor overload trip (electronic thermal O/L relay
function) (E.THM).
5
• When Pr.156 has been set to activate the fast response current limit (initial value), the Pr.22 setting should not be higher than
170%. Such setting prevents torque generation.
• When Real sensorless vector control is selected using Pr.800 Control method selection, Pr.22 serves as the torque limit 6
level.
10
NOTE
• When the load is heavy or the acceleration/deceleration time is short, stall prevention operates and acceleration/deceleration
may not be performed according to the time set. Set the Pr.156 and stall prevention operation level to the optimum values.
• For lift applications, make settings to disable the fast-response current limit. Otherwise, the torque may be insufficient, causing
the load to drop.
NOTE 7
• If the stall prevention operation has lowered the output frequency to 1 Hz and kept the level for 3 seconds, the stall prevention
stop (E.OLT) is activated to shut off the inverter output.
• Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
8
120
Stall prevention operation
72
level (%)
36
level (%)
• When operating at the rated motor frequency or higher, acceleration may not be made because the motor current does
not increase. Also, when operating in the high-frequency range, the current flowing to the locked motor becomes less than
the rated output current of the inverter. Even if the motor is stopped, the protective function does not operate (OL). In a
case like this, the stall prevention level can be reduced in the high-frequency range to improve the motor's operating
characteristics. This is useful when operating up to the high speed range, such as when using a centrifuge. Normally, set
Pr.66 Stall prevention operation reduction starting frequency to 60 Hz, and Pr.23 Stall prevention operation level
compensation factor at double speed to 100%.
• Calculation formula for stall prevention operation level
Stall prevention operation level (%) Pr.22 - A Pr.23 - 100
in the high-frequency range = A + B × [ Pr.22 - B ] × [ 100
]
• When Pr.23 = "9999" (initial value), the stall prevention operation level is constant at the Pr.22 level up to 590 Hz.
NOTE
• The torque limit cannot work properly when two or more motors are driven by one inverter.
• In the constant power range (Pr.3 Base frequency), the torque limit is activated at the torque less than the stall prevention
operation level, since the magnetic flux decreases.
• When the torque limit is activated during regenerative driving, the output frequency is increased up to the maximum frequency.
• The toque limit is not activated at the frequency of 5 Hz or less during deceleration.
• When using the torque limit under V/F control, note the following points:
- Use the inverter whose capacity is the same as that of the motor.
- The stall prevention operation level (torque limit level) is based on the rating torque of the motor whose capacity is the same
as that of the inverter.
- When a large value is set in Pr.0 Torque boost, the torque limit may be activated in the low-speed range.
- If more accurate torque limit is required, select Advanced magnetic flux vector control.
NOTE
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
• The RT signal is the Second function selection signal which also enables other second functions. (Refer to page 289).
CAUTION
• Do not set the stall prevention operation current too low.
Doing so will reduce the generated torque.
• Be sure to perform the test operation.
Stall prevention operation during acceleration may extend the acceleration time.
Stall prevention operation during constant-speed operation may cause sudden speed changes.
Stall prevention operation during deceleration may extend the deceleration time.
Parameters referred to
Pr.22 Torque limit levelpage 100
Pr.178 to Pr.184 (Input terminal function selection)page 283
Pr.190 to Pr.196 (Output terminal function selection)page 250
This function is used to monitor whether the load is operating in normal condition by storing the speed/torque relationship in
the inverter to detect mechanical faults or for maintenance. When the load operating condition deviates from the normal range, 2
the protective function is activated or the warning is output to protect the inverter or the motor.
Initial value*1
Pr. Name
Gr.1 Gr.2
Setting
range
Description 3
Load characteristics measurement mode does not start.
0
(Measurement of load characteristics complete without fault.)
1480
H520
Load characteristics
measurement mode
0
1
2, 3, 4, 5,
Load characteristics measurement mode is started.
4
The load characteristics measurement status is displayed.
81, 82, 83,
(Read-only)
84, 85
1481
H521
Load characteristics load
reference 1
9999 5
1482 Load characteristics load
9999
H522 reference 2
1483 Load characteristics load
9999
Used to set the reference value of normal load characteristics.
0% to 400% 8888: The present load status is written as reference status. 6
H523 reference 3
9999: The load reference is invalid.
1484 Load characteristics load
9999
H524 reference 4
1485 Load characteristics load
9999
7
H525 reference 5
1486 Load characteristics Used to set the upper frequency limit of the load characteristics
60 Hz 50 Hz 0 to 590 Hz
H526 maximum frequency fault detection range.
1487 Load characteristics
6 Hz 0 to 590 Hz
Used to set the lower frequency limit of the load characteristics 8
H527 minimum frequency fault detection range.
Used to set the detection range of when the upper limit load fault
1488 Upper limit warning detection 0% to 400%
20% warning is output.
H531 width
9999 Function disabled 9
Used to set the detection range of when the lower limit load fault
1489 Lower limit warning detection 0% to 400%
20% warning is output.
H532 width
9999 Function disabled
Used to set the detection range of when output is shut-off when
10
1490 Upper limit fault detection 0% to 400%
9999 the upper limit load fault occurs.
H533 width
9999 Function disabled
Used to set the detection range of when output is shut-off when
1491 Lower limit fault detection 0% to 400%
9999 the lower limit load fault occurs.
H534 width
9999 Function disabled
Used to set the waiting time after the load fault is detected until
Load status detection signal warning output or output shutoff.
1492
delay time / load reference 1s 0 to 60 s In the load characteristics measurement mode, set the waiting
H535
measurement waiting time time after the load measurement frequency is reached until the
load reference is set.
*1 Gr.1 and Gr.2 are the parameter initial value groups. (Refer to page 82).
f1 f2 f3 f4 f5 Output frequency
(Pr.1487) (Pr.1486)
• Setting Pr.1480 Load characteristics measurement mode = "1" enables automatic measurement of the load
characteristics reference. (Load characteristics measurement mode)
• Use Pr.1486 and Pr.1487 to set the frequency band for the measurement, and set Pr.1480 = "1". After setting, when the
inverter is started, the measurement starts. (When the value set in Pr.1486 is equal to or smaller than the value set in
Pr.1487, the measurement does not start.)
• The automatically measured load characteristics reference is written in Pr.1481 to Pr.1485.
• After the measurement is started, read Pr.1480 to display the status of the measurement. If "8" appears in the tens place,
the measurement has not properly completed.
Read value of Pr.1480
Status
Tens place Ones place
— 1 During measurement from the starting point to Point 1
— 2 During measurement from Point 1 to Point 2
— 3 During measurement from Point 2 to Point 3
— 4 During measurement from Point 3 to Point 4
— 5 During measurement from Point 4 to Point 5
— 0 Normal completion
Termination of measurement by an activation of a protective function, Inverter reset, turning ON of MRS
8 1 to 5 signal, turning OFF of the start command, or timeout. (The value in the ones place represents the above-
mentioned measurement point.)
• While measuring automatically, the During load characteristics measurement (Y213) signal is output. For the Y213 signal,
assign the function by setting "213" (positive logic) or "313" (negative logic) in any of in any parameter from Pr.190 to
Pr.196 (Output terminal function selection).
Frequency(Hz)
Load reference 5 recorded 2
f5(Pr.1486) Pr.41
Load reference 4 recorded
f4
Load reference 3 recorded
Pr.41 3
f3 Pr.41
Load reference 2 recorded
f2
Load reference
Pr.41 Operation at the
set frequency 4
1 recorded
f1(Pr.1487) Pr.41
STF=ON
Pr.1480=1 Time
5
Measurement start
Pr.1492 Pr.1492 Pr.1492 Pr.1492 Pr.1492
10
Setting the load characteristics reference manually (Pr.1481 to Pr.1485)
• Set Pr.1480 Load characteristics measurement mode = "0" (initial value).
• Set Pr.1486 and Pr.1487 to specify the frequency band for the measurement, and calculate the frequency as the load
characteristics reference (f2 to f4) using the following table.
• Start the inverter operation, and set Pr.1481 = "8888" during operation at the frequency of the load characteristics
reference 1 (f1). The load status at that point is set in Pr.1481 (only when the set frequency is within ±2 Hz of the frequency
of the measurement point, and the SU signal is ON).
• Set load references in Pr.1482 to Pr.1485 in the same way as Pr.1481.
Reference Frequency Load reference
Load characteristics reference 1 f1: load characteristics minimum frequency (Pr.1487) Pr.1481
Load characteristics reference 2 f2 = (f5 - f1)/4 + f1 Pr.1482
Load characteristics reference 3 f3 = (f5 - f1)/2 + f1 Pr.1483
Load characteristics reference 4 f4 = (f5 - f1) × 3/4 + f1 Pr.1484
Load characteristics reference 5 f5: load characteristics maximum frequency (Pr.1486) Pr.1485
NOTE
• When inputting values directly in Pr.1481 to Pr.1485 under V/F control, input the load meter monitored values at the frequency
of each load characteristics reference.
• When inputting values directly in Pr.1481 to Pr.1485 under Advanced magnetic flux vector control, Real sensorless vector
control, or PM sensorless vector control, input the load meter monitored values at the frequency of each load characteristics
reference.
Load(%)
120
100
80
60
40
26
20
0
0 10 20 30 40 50 60 70 Frequency(Hz)
NOTE
• When the load reference is not set for five points, the load characteristics value is determined by linear interpolation of the set
load reference values only. If there is only one load reference setting, the set load reference is used as the load reference all
through the range.
Pr.1492
Lower limit warning detection width (Pr.1491) 3
Pr.1492
LUP ON 4
LDN ON ON
E.LDN Output shutoff
LDF warning indication ON ON ON 5
NOTE
• Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
6
Parameters referred to
Pr.41 Up-to-frequency sensitivitypage 257
7
Pr.190 to Pr.196 (Output terminal function selection)page 250
10
Motor speed
Pr.374
Coast to stop
Time
ON
ALM
E.OS
11.1 Speed indication and its setting change to rotations per minute ..........................................................................226
11.2 Monitor item selection on operation panel or via communication .........................................................................228
6
11.3 Monitor display selection for terminals FM and AM ..............................................................................................237
11.4 Adjustment of terminal FM and terminal AM.........................................................................................................241
11.5 Energy saving monitoring .....................................................................................................................................244
7
11.6 Output terminal function selection ........................................................................................................................250
11.7 Output frequency detection...................................................................................................................................257
11.8 Output current detection function..........................................................................................................................260
8
11.9 Output torque detection function...........................................................................................................................262
11.10 Remote output function.........................................................................................................................................263
9
10
225
11 (M) Item and Output Signal for Monitoring
Purpose Parameter to set Refer to page
To display the motor speed (the
number of rotations per minute). Speed indication and its
P.M000, P.M001,
To switch the unit of measure to set setting change to rotations Pr.37, Pr.53, Pr.505 226
P.M003
the operation speed from frequency per minute
to motor speed.
Pr.52, Pr.170,
P.M020 to P.M023, Pr.171, Pr.268,
Operation panel monitor item
P.M030, P.M031, Pr.290, Pr.563,
To change the item monitored on the selection
P.M044, P.M050 to Pr.564, Pr.774 to 228
operation panel clearing the cumulative value
P.M052, P.M100 to Pr.776, Pr.891,
during monitoring
P.M104 Pr.992, Pr.1106 to
Pr.1108
P.M040 to P.M042, Pr.54, Pr.55, Pr.56,
To change the monitor item whose Terminal FM/AM function
P.M044, P.M300, Pr.158, Pr.290, 237
data is output via terminal FM or AM selection
P.M301 Pr.866
To adjust the output via terminal FM P.M310, P.M320, Pr.867, C0, C1,
Terminal FM/AM calibration 241
or AM P.M321, P.M390 Pr.1200
P.M023, P.M100,
Pr.52, Pr.54, Pr.158,
To check the effects of energy saving Energy saving monitoring P.M200 to P.M207, 244
Pr.891 to Pr.899
P.M300, P.M301
P.M400, P.M404,
P.M405, P.M410 to Pr.190 to Pr.196,
To assign functions to the output Output terminal function
P.M416, P.M420 to Pr.289, Pr.313 to 250
terminals assignment
P.M422, P.M431, Pr.322
P.M451 to P.M454
Up-to-frequency sensitivity
P.M440 to P.M443, Pr.41 to Pr.43,
To detect the output frequency Output frequency detection 257
P.M446 Pr.865 to Pr.870
Low speed detection
Output current detection P.M433, P.M460 to Pr.150 to Pr.153,
To detect the output current 260
Zero current detection P.M464 Pr.166, Pr.167
To detect the output torque Output torque detection P.M470 Pr.864 262
To use the remote output function Remote output P.M500 to P.M502 Pr.495 to Pr.497 263
Initial value*1
Pr. Name Setting range Description
Gr.1 Gr.2
0 Monitoring and setting of frequency
37
Speed display 1800 Set a number for the speed of machine operated at
M000 0.01 to 9998*2 the speed (frequency) set in Pr.505.
Frequency / rotation 0 Frequency displayed
53
speed unit 0 1 Rotation speed displayed
M003
switchover 4 Machine speed displayed
505 Speed setting
M001 reference
60 Hz 50 Hz 1 to 590 Hz*2 Set the reference speed (frequency) for Pr.37.
*1 Gr.1 and Gr.2 are the parameter initial value groups. (Refer to page 82).
*2 The setting ranges of Pr.1 (Pr.18), Pr.37, and Pr.505 are limited so that the following formula is satisfied.
Pr.1 (Pr.18) × Pr.37 / Pr.505< 8388.607
The setting range of Pr.1 (Pr.18) is not limited when the machine speed display is not selected. To display the machine speed, set values which
satisfy the formula.
4
0.001 (machine
speed*1)
0.001 (machine
speed*1)
1 (machine speed*1)
0.001 (machine
speed*1)
0.01 Hz 15
*1 Motor speed r/min conversion formula: frequency × 120 / number of motor poles (Pr.81 or Pr.454)
Machine speed conversion formula: Pr.37 × frequency / Pr.505
The item set in Pr.505 is consistently a frequency (Hz). 16
When Pr.81 (Pr.454) = "9999", the number of motor poles is regarded as 4.
NOTE
• The inverter's output frequency is displayed as synchronous speed under V/F control. The displayed value is "actual motor 17
speed" + "motor slip". When Advanced magnetic flux vector control, Real sensorless vector control, or PM sensorless vector
control is selected, the actual motor speed (estimated value by motor slip calculation) is used.
• To change the main monitor of the operation panel (operation panel main display), refer to Pr.52.
• Since the panel display of the operation panel is in 4 digits, the monitor value of more than "9999" is displayed as "----". Display 18
the frequency on the operation panel when a value equal to or more than 10000 r/min needs to be monitored or set.
• The displayed machine speed is the value converted from the frequency. Therefore, the setting value and read value may
fluctuate due to rounding during the conversion.
19
CAUTION 20
• Make sure to set the running speed and the number of motor poles.
Otherwise, the motor might run at extremely high speed, damaging the machine.
Parameters referred to
Pr.1 Maximum frequencypage 211
Pr.52 Operation panel main monitor selectionpage 228
Pr.81 Number of motor polespage 86
Pr.800 Control method selectionpage 86
b15 b0
X15 X14 X13 X12 X11 X10 X9 X8 X7 X6 X5 X4 X3 X2 X1 X0
*12 The details of bits for the option input terminal status 2 are as follows. (1: ON state, 0: OFF state of a terminal on the FR-A8AX. "—" denotes an
indefinite (null) value.) Every bit is 0 (OFF) when the option is not installed.
b15 b0
- - - - - - - - - - - - - - - DY
*13 The details of bits for the option output terminal status are as follows. (1: ON state, 0: OFF state of a terminal on the FR-A8AY/A8AR. "—" denotes
an indefinite (null) value.) Every bit is 0 (OFF) when the option is not installed.
b15 b0
- - - - - - RA3 RA2 RA1 Y6 Y5 Y4 Y3 Y2 Y1 Y0
*14 The increment varies depending on the Pr.53 setting. (Refer to page 226).
*15 The monitored values are retained even if an inverter fault occurs. Resetting clears the retained values.
For example, when Pr.52 = "20" (cumulative energization time), the monitor is displayed on the operation panel as shown
below.
• Power-on monitor (first monitor) • Second monitor • Third monitor • Fault monitor
With fault
Output frequency monitor Output current monitor Cumulative energization time monitor
• Pr.774 sets the output frequency monitor, Pr.775 sets the output current monitor, and Pr.776 sets the monitor description
to be displayed at the output voltage monitor position. When Pr.774 to Pr.776 = "9999" (initial value), the Pr.52 setting
value is used.
NOTE
• On the operation panel, the Hz LED is lit while displaying the output frequency, the Hz LED blinks when displaying the set
frequency.
• When the operation panel is used, the displayed units are Hz and A only, and the others are not displayed.
NOTE
• During an error, the output frequency at error occurrence appears.
• During output shutoff by the MRS signal, the values displayed are the same as during a stop.
• During offline auto tuning, the tuning state monitor takes priority.
Operation panel setting dial push display (Pr.992) (only for the standard
model)
• Use Pr.992 to select the monitor that appears when the setting dial on the operation panel is pushed.
• When Pr.992 = "0 (initial value)", keep pressing the setting dial when in PU operation mode or External/PU combined
operation mode 1 (Pr.79 Operation mode selection = "3") to show the presently set frequency.
• When Pr.992 = "100", the set frequency is displayed during stop, and output frequency is displayed during running.
Pr.992 setting Status Monitor displayed by the setting dial push
0 During running/stop Set frequency
During stop Set frequency*1
100
During running Output frequency
*1 Displays the frequency that is output when the start command is ON. The value considers the maximum/minimum frequency and frequency
jumps. It is different from the frequency setting displayed when Pr.992 = "5".
17
O-2 O-5 O-8 O-11
O-3 O-6 O-9 O-12 Segments corresponding
to output terminals
• The decimal point of the last digit on the LED is lit for the input option terminal monitor.
X1 X2 X4 X5 X7 X8
X0 X3 X6 X9
X10 X13 DY
X11 X14
X12 X15
Decimal point LED of the last digit LED is always ON
• The decimal point of the second last digit on the LED is lit for the output option terminal monitor.
FR-A8AY
Y1 Y2 Y4 Y5
Y0 Y3 Y6
RA1
RA2
RA3 FR-A8AR
Decimal point LED of the second last digit LED is always ON
*1 Power is measured in the range of 0 to 99999.99 kWh, and displayed in 4 digits. After the watt-hour meter (cumulative power counter) reaches
"99.99" (999.99 kWh), the meter displays values in 0.1 increments such as "100.0" (1000.0 kWh). Use Pr.891 to shift the decimal point position
when the monitored value becomes equal to or higher than 10000 kWh.
• The decimal point position on the watt-hour meter can be shifted to left. The number of digits to be shifted is equal to the
setting of Pr.891 Cumulative power monitor digit shifted times. For example, when Pr.891 = "2", the cumulative power
value 1278.56 kWh is displayed as 12.78 (in 100 kWh increments) on the operation panel, or displayed as 12 on a display
used for monitoring via communication.
• When Pr.891 = "0 to 4", the meter stops at the maximum number. When Pr.891 = "9999", the meter returns to 0 and the
counting starts again.
• The cumulative power can be monitored as 32-bit data via communication by setting Pr.52 = "77 to 80". The maximum
monitored value is 42949672 kWh in 1 kWh increments or 42949672.94 kWh in 0.01 kWh increments. Pr.891 setting is
invalid while 32-bit cumulative power is monitored. (For details on communication for 32-bit cumulative power monitor, refer
to the Instruction Manual (Communication) or the Instruction Manual of the communication option.)
• Writing "0" in Pr.170 clears the cumulative power monitor.
NOTE
• When Pr.170 is read just after "0" has been written in Pr.170, the setting "9999" or "10" is displayed.
NOTE
• The cumulative energization time does not increase if the power is turned OFF after less than an hour.
12
Hiding the decimal places for the monitors (Pr.268)
• The numerical figures after a decimal point displayed on the operation panel may fluctuate during analog input, etc. The
decimal places can be hidden by selecting the decimal digits with Pr.268. 13
Pr.268 setting Description
9999 (initial value) No function
For the first or second decimal places (0.1 increments or 0.01 increments) of the monitor, numbers 14
0 in the first decimal place and smaller are rounded to display an integral value (1 increments). The
monitor value equal to or smaller than 0.99 is displayed as 0.
When monitoring with the second decimal place (0.01 increments), the 0.01 decimal place is
1 dropped and the monitor displays the first decimal place (0.1 increments). When monitoring with the 15
first decimal place, the display will not change.
NOTE
• The number of readout digits of the cumulative energization time (Pr.52 = "20"), actual operation time (Pr.52 = "23"),
16
cumulative energy (Pr.52 = "25"), and cumulative energy saving (Pr.52 = "51") does not change.
17
Enabling display of negative numbers during monitoring (Pr.290)
• Negative values can be used for indication via terminal AM (analog voltage output), on communication options, and via
terminal AM0 (of the FR-A8AY). To check which items can be monitored with indication of negative numbers, refer to 18
Monitor description list (on page 229).
Negative numbers
Negative numbers Negative numbers indication (via
Pr.290 setting
indication (via terminal AM)
indication (via
communication option)*1
terminal AM0) (with the FR-A8AY) 19
0 (initial value) — — —
1 Enabled — —
4 — Enabled — 20
5 Enabled Enabled —
8 — — Enabled
9 Enabled — Enabled
12 — Enabled Enabled
13 Enabled Enabled Enabled
NOTE
• When indication with negative numbers is enabled for the output via terminal AM/AM0 (analog voltage output), the output is
within the range of -10 to +10 VDC. Connect the meter with which output level is matched.
• The operation panel displays only unsigned numbers.
Pr. Name
Initial value*1
Setting range Description
13
Gr.1 Gr.2
1 to 3, 5 to 12, 14, 17,
54 18, 21, 24, 32, 33, 50,
M300*2
FM terminal function selection
52, 53, 61, 62, 67, 70,
Select the item monitored via terminal FM.
14
1 (output 97
frequency) 1 to 3, 5 to 12, 14, 17,
158 18, 21, 24, 32, 33, 50,
M301*3
AM terminal function selection
52 to 54, 61, 62, 67, 70,
Select the item monitored via terminal AM.
15
91, 97
55 Set the full-scale value when the output
Frequency monitoring reference 60 Hz 50 Hz 0 to 590 Hz frequency monitor value is output via terminal
M040*4 FM or AM. 16
56 Set the full-scale value when the output
Inverter rated
Current monitoring reference 0 to 500 A current monitor value is output via terminal FM
M041*4 current
or AM.
866
Torque monitoring reference 150% 0% to 400%
Set the full-scale value when the torque 17
M042 monitor value is output via terminal FM or AM.
Set the availability of negative values for
290 Monitor negative output indication via terminal AM, via communication,
M044 selection
0 0, 1, 4, 5, 8, 9, 12, 13
and via terminal AM0 (of the FR-A8AY). (Refer 18
to page 235.)
*1 Gr.1 and Gr.2 are the parameter initial value groups. (Refer to page 82).
*2
*3
The setting is available only for the FR-E800-1.
The setting is available only for the FR-E800-4 and FR-E800-5. 19
*4 For the Ethernet model, the setting is available only when the plug-in option (FR-A8AY) is installed.
Pr.54 (FM),
Increment and Terminal FM/AM Negative
Monitor item Pr.158 (AM) Remarks
unit full-scale value output
setting
Output frequency 0.01 Hz 1 Pr.55 ○
Output current*1 0.01 A 2 Pr.56
200 V class: 400 V,
Output voltage 0.1 V 3 400 V class: 800 V,
575 V class: 1000 V
Frequency setting value 0.01 Hz 5 Pr.55
Pr.55 or the value
converted with the
Refer to page 226 for the
Motor speed 1 (r/min) 6 Pr.37 or Pr.81 ○
monitoring of the operation speed.
(Pr.454) value from
Pr.55.
Motor torque 0.1% 7 Pr.866 ○
Converter output 200 V class: 400 V,
0.1 V 8 400 V class: 800 V,
voltage*1 575 V class: 1000 V
12
1Hz 60Hz Output frequency 590Hz
(initial value)
13
Setting range of Pr.55
• Enter the full-scale value of the meter corresponding to a voltage of 10 VDC output via terminal AM. Enter the current value
(for example, 60 Hz or 120 Hz) at full scale of the meter (10 VDC voltmeter) installed between terminal AM and terminal 14
5. Output voltage is proportional to the frequency. (The maximum output voltage is 10 VDC.)
Output voltage
15
10VDC
16
60Hz
60Hz *1 590Hz
17
(initial value)
*2
Setting range of Pr.55
-10VDC
Inverter
24V
2.2K 3.3K FM
20K SD
Indicator
1mA full-scale (Digital indicator)
analog meter
1mA 1440 pulses/s(+) (-)
FM FM
(+) (-) T1
Calibration
resistor *1 8VDC
SD SD
T2
Pulse width T1: Adjust using calibration parameter C0
Pulse cycle T2: Set with Pr.55 (frequency monitor)
Set with Pr.56 (current monitor)
*1 Not required when calibrating with operation panel.
Use a calibration resistor when the indicator (frequency meter) needs to be calibrated by a neighboring device because the indicator is located
far from the inverter.
However, the frequency meter needle may not deflect to full-scale if the calibration resistor is connected. In this case, use the resistor and
operation panel together.
*2 In the initial setting, 1 mA full-scale and 1440 pulses/s terminal FM are used at 60 Hz.
By using the operation panel, you can adjust (calibrate) terminal FM and terminal AM to full-scale deflection.
12
Pr. Name Initial value Setting range Description
C0
FM terminal calibration — — Calibrates the scale of the meter connected to terminal FM.
M310*1
C1
13
Calibrates the scale of the analog meter connected to terminal
AM terminal calibration — —
M320*2 AM.
867
M321*2
AM output filter 0.01 s 0 to 5 s Set a filter for output via terminal AM.
14
1200
AM output offset calibration 3000 2700 to 3300 Calibrates the scale of the meter when the analog output is 0.
M390*2
*1
*2
The setting is available only for the FR-E800-1.
The setting is available only for the FR-E800-4 and FR-E800-5.
15
Terminal FM calibration (C0) (FM type only)
• The output via terminal FM is set to the pulse output. By setting C0, the meter connected to the inverter can be calibrated 16
by parameter setting without use of a calibration resistor.
• The pulse train output via terminal FM can be used for digital display on a digital counter. The output is 1440 pulses/s at
full scale. (Refer to page 237 for the full-scale value of each monitor item.) 17
Indicator
1mA full-scale (Digital indicator)
1mA
analog meter
1440 pulses/s(+) (-) 18
FM FM
(+) (-) T1
Calibration
SD
resistor *1 8VDC
SD
19
T2
Pulse width T1: Adjust using calibration parameter C0
Pulse cycle T2: Set with Pr.55 (frequency monitor)
Set with Pr.56 (current monitor)
20
*1 Not required when calibrating with operation panel.
Use a calibration resistor when the indicator (frequency meter) needs to be calibrated by a neighboring device because the indicator is located
far from the inverter.
However, the frequency meter needle may not deflect to full-scale if the calibration resistor is connected. In this case, perform calibration using
the operation panel.
*2 In the initial setting, 1 mA full-scale and 1440 pulses/s terminal FM are used at 60 Hz.
1. Connect an indicator (frequency meter) across terminals FM and SD on the inverter. (Note the polarity. Terminal FM
is positive.)
2. When a calibration resistor has already been connected, adjust the resistance to "0" or remove the resistor.
3. Set a monitor item in Pr.54 FM terminal function selection. (Refer to page 237.)
When the output frequency or inverter output current is selected on the monitor, set the output frequency or current
value at which the output signal will be 1440 pulses/s, using Pr.55 Frequency monitoring reference or Pr.56
Current monitoring reference beforehand. Normally, at 1440 pulses/s the meter deflects to full-scale.
4. If the meter needle does not point to maximum even at maximum output, calibrate it with C0.
5. Selecting a parameter
Turn the setting dial until "C0" (C0 FM terminal calibration) appears. Press the SET key to enable the parameter
setting.
The monitored value of the item (initially the output frequency) selected by Pr.54 FM terminal function selection
will appear.
7. Scale adjustment
Turn the setting dial to move the meter needle to a desired position.
8. Setting completed
Press the SET key to confirm the setting. The monitor indicator blinks.
• Turn the setting dial to read another parameter.
• Press the SET key to return to the "C---" display.
• Press the SET key twice to show the next parameter.
NOTE
• Calibration can also be made for External operation. Set the frequency in the External operation mode, and make calibration
in the above procedure.
• Calibration can be performed during operation.
Inverter 12
AM
10VDC
13
5
NOTE 17
• When outputting an item such as the output current, which cannot reach a 100% value easily by operation, set Pr.158 to "21"
(reference voltage output) and calibrate. A voltage of 10 VDC is output via terminal AM.
• When Pr.306 Analog output signal selection = "21", the output via terminal AM cannot be calibrated. For the details of
Pr.306, refer to the Instruction Manual of the FR-A8AY.
18
• Use Pr.290 Monitor negative output selection to enable negative signals output via terminal AM. The output voltage range
is -10 to +10 VDC. Calibrate the maximum positive value output via terminal AM.
19
Calibration when 0 V is output via terminal AM (Pr.1200)
• When 0 is output via terminal AM, use Pr.1200 AM output offset calibration to calibrate the meter. If the meter needle
does not point to 0 while 0 is output via terminal AM, set a value in Pr.1200 so that the needle points to 0.
20
• Set a larger value in Pr.1200 when the needle points a minus output voltage while the 0 is output via terminal AM. Set a
smaller value in Pr.1200 when the needle points a plus output voltage while the 0 is output via terminal AM.
Parameters referred to
Pr.54 FM terminal function selectionpage 228
Pr.55 Frequency monitoring referencepage 228
Pr.56 Current monitoring referencepage 228
Pr.158 AM terminal function selectionpage 228
Pr.290 Monitor negative output selectionpage 228
NOTE
• The operation panel have a 4-digit display. This means, for example, that a monitored value up to "99.99" is displayed in 0.01
increments and a monitor value of 1000 or more is displayed in 0.1 increments as "100.0". The maximum monitored value
displayed is "9999".
• The maximum monitored value via communication is 65535 when Pr.898 Power saving cumulative monitor clear = "9999".
The maximum monitored value on monitoring in 0.01 increments is "655.35", and that on monitoring in 0.1 increments is
"6553.5".
• On [2 Power saving rate] monitoring, the rate of the saved power considering the consumed power (estimate) during the
power supply operation as 100% is displayed when Pr.895 Power saving rate reference value is set to "0". When Pr.895
is set to "1", the rate of the saved power with respect to the setting of Pr.893 Energy saving monitor reference (motor
capacity) that is referenced as 100% is displayed.
2. Change the setting of Pr.898 to "0" when you want to start measuring the energy saving. The cumulative value is
cleared and the cumulative energy saving meter restarts.
3. Change the setting of Pr.898 to "1" when you want to stop measuring the energy saving. The meter stops and the
cumulative value is fixed.
NOTE
• The cumulative value of energy saving is refreshed every hour. This means that the last cumulative value is displayed at a
restart of the inverter and the cumulative meter restarts if the time elapsed between turning OFF and re-turning ON of the
inverter is shorter than an hour. (In some cases, the cumulative energy value may decrease.)
80
Valve control
70 (pump)
60
50
40 Inlet damper control
(fan)
30
20
10
0
0 10 20 30 40 50 60 70 80 90100110
Ratio of speed to rating [%]
• The estimated input power (kW) for the commercial power supply operation is calculated from the motor capacity set in
Pr.893, the setting of Pr.892 Load factor, and the rate of power consumption using the following formula.
NOTE
• If the output frequency rises to the setting of Pr.3 Base frequency or higher, it stays at a constant value because the rotations
per minute cannot rise higher than the power supply frequency during commercial power supply operation.
2. Calculate the operation days per year (days/year) using the following formula: Average operation days per month ×
12 (months).
3. Calculate the annual operation time (h/year) from values determined in Step 1 and Step 2, using the following
formula.
Annual operation time (h/year) = average time (h/day) × number of operation days (days/year)
4. Calculate the operation time rate using the following formula, and set it in Pr.899.
Annual operation time (h/year)
Operation time rate (%) = × 100(%)
24 (h/day) × 365 (days/year)
• When the power cost per hour is set in Pr.896 Power unit cost, the annual energy cost savings can be monitored.
15
The annual energy cost savings is determined by calculation using the following formula.
Annual power cost saving = annual power saving amount (kWh/year) × Pr.896
NOTE 16
• During regenerative driving, substitute the output power during the commercial power supply operation for the saved power
(therefore, input power = 0).
17
Parameters referred to
Pr.3 Base frequencypage 376
Pr.52 Operation panel main monitor selectionpage 228
Pr.54 FM terminal function selectionpage 237 18
Pr.158 AM terminal function selectionpage 237
19
20
Initial
Pr. Name Signal name Setting range
value
190 RUN terminal 0, 1, 3, 4, 7, 8, 11 to 16, 20, 25, 26, 34, 35, 39 to
0 RUN (Inverter running)
M400 function selection 41, 44 to 48, 57, 64, 70, 80, 81, 90 to 93, 95, 96,
For open 98, 99, 100, 101, 103, 104, 107, 108, 111 to 116,
collector output 120, 125, 126, 134, 135, 139 to 141, 144 to 148,
191 NET Y2 output FU (Output frequency 157, 164, 170, 180, 181, 190 to 193, 195, 196,
terminal 4
M404 selection detection) 198, 199, 206, 211 to 213, 242, 306, 311 to 313,
342, 9999*1
0, 1, 3, 4, 7, 8, 11 to 16, 20, 25, 26, 34, 35, 39 to
41, 44 to 48, 57, 64, 70, 80 to 82, 90, 91, 95, 96,
98, 99, 100, 101, 103, 104, 107, 108, 111 to 116,
192 A,B,C terminal For relay output 120, 125, 126, 134, 135, 139 to 141, 144 to 148,
99 ALM (Fault)
M405 function selection terminal 157, 164, 170, 180 to 182, 190, 191, 195, 196,
198, 199, 206, 211 to 213, 242, 306, 311 to 313,
342, 9999*1
193 NET Y1 output 0, 1, 3, 4, 7, 8, 11 to 16, 20, 25, 26, 34, 35, 39 to
M451 selection 41, 44 to 48, 57, 64, 70, 80, 81, 90 to 93, 95, 98,
194 NET Y2 output Virtual output 99, 100, 101, 103, 104, 107, 108, 111 to 116,
M452 selection terminal for 120, 125, 126, 134, 135, 139 to 141, 144 to 148,
9999 No function 157, 164, 170, 180, 181, 190 to 193, 195, 198,
195 NET Y3 output communication
operation 199, 206, 211 to 213, 242, 306, 311 to 313, 342,
M453 selection
196 NET Y4 output 9999*1
M454 selection
313 DO0 output
9999 No function
M410*2 selection
314 DO1 output
9999 No function
M411*2 selection
315 DO2 output 0, 1, 3, 4, 7, 8, 11 to 16, 20, 25, 26, 34, 35, 39,
9999 No function 40, 41, 44 to 48, 57, 64, 70, 80, 81, 90 to 93, 95,
M412*2 selection
96, 98, 99, 100, 101, 103, 104, 107, 108, 111 to
316 DO3 output
9999 No function 116, 120, 125, 126, 134, 135, 139, 140, 141, 144
M413*2 selection to 148, 157, 164, 170, 180, 181, 190 to 193, 195,
317 DO4 output 196, 198, 199, 206, 211 to 213, 242, 306, 311 to
9999 No function
M414*2 selection For terminal on 313, 342, 9999*1
318 DO5 output the option
9999 No function
M415*2 selection
319 DO6 output
9999 No function
M416*2 selection
320
RA1 output selection 0 RUN (Inverter running)
M420*2
0, 1, 3, 4, 7, 8, 11 to 16, 20, 25, 26, 34, 35, 39,
321
*2 RA2 output selection 1 SU (Up to frequency) 40, 41, 44 to 48, 57, 64, 70, 80, 81, 90, 91, 95,
M421
96, 98, 99, 206, 211 to 213, 242, 9999*1
322 FU (Output frequency
RA3 output selection 4
M422*2 detection)
Initial
Pr. Name Setting range Description
value
289 Inverter output terminal 5 to 50 ms Set the time delay for the output terminal response.
9999
M431 filter 9999 No filtering of the output terminal.
*1 The setting range differs depending on the model. For the details, refer to Output signal list.
*2 The setting is available when the PLC function is enabled. (Pr.313 to Pr.315 are always available for settings in the Ethernet model.)
Setting
Positive Negative
Signal
Function Operation
Related
Refer to page
20
name parameter
logic logic
Output during operation when the inverter
0 100 RUN Inverter running output frequency reaches Pr.13 Starting — 254
frequency or higher.
Output when the output frequency reaches
1 101 SU Up to frequency *1 the set frequency.
Pr.41 257
98 198 LF Alarm
Output when an Alarm fault (fan fault or a
communication error) occurs.
Pr.121, Pr.244 203 15
Output when the inverter's protective
function is activated to stop the power output
99 199 ALM Fault — 255
(when the Fault occurs). The signal output
stops when the inverter reset starts. 16
Cooling fan operation Output when the cooling fan operation is
206 306 Y206 Pr.244 203
command commanded.
NOTE
• One function can be assigned to more than one terminal.
• The function works during the terminal conducts when the parameter setting is any of "0 to 99, 200 to 299", and the function
works during the terminal does not conduct when the setting is "100 to 199, 300 to 399".
• Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
• Do not assign the signal to terminals A, B, and C which frequently changes its state between ON and OFF. Otherwise, the life
of the relay contact may be shortened.
Time
RUN ON OFF
Pr.289 = 9999
ON OFF
RUN
Pr.289 ≠ 9999
Pr.289 Pr.289
Inverter operation ready signals (RY signal) and inverter running signals
(RUN, RUN2, RUN3 signals)
• When the inverter is ready for operation, the Inverter operation ready (RY) signal turns ON (and stays ON during
operation).
• When the inverter output frequency reaches the setting of Pr.13 Starting frequency or higher, the inverter running signals
(RUN, RUN2 signals) turn ON. The signals are OFF while the inverter is stopped or during the DC injection brake operation.
• The Inverter running and start command ON (RUN3) signal is ON while the inverter is running or while the start command
signal is ON (When the start command signal is ON, the RUN3 signal is ON even while the inverter's protective function
is activated or while the MRS signal is ON.) The RUN3 signal is ON even during the DC injection brake operation, and the
signal is OFF when the inverter stops.
Power ON OFF
supply
ON OFF
STF
ON
RH
Output frequency
DC injection brake
operation point
DC injection
brake
Pr. 13 operation
Reset Time
processing
ON OFF
RY
RUN ON OFF
(RUN2)
ON OFF
RUN3
• The ON/OFF state of each signal according to the inverter operating status is shown in the matrix below.
Automatic restart after
Inverter output
Start signal During DC instantaneous power failure
Start signal Start signal shutoff*2
Output ON injection During coasting Inverter
OFF (inverter ON (inverter
signal (inverter brake running
stopped) stopped) Start Start Start Start
running) operation after
signal ON signal OFF signal ON signal OFF
restart
RY*3 ON ON ON ON OFF ON*1 ON
RUN OFF OFF ON OFF OFF OFF ON
RUN2 OFF OFF ON OFF OFF OFF ON
RUN3 OFF ON ON ON ON OFF ON OFF ON
Operation under Real sensorless vector control and PM sensorless vector control
• When the inverter is ready for operation, the Inverter operation ready (RY) signal turns ON (and stays ON during
operation).
• When the inverter output frequency reaches the setting of Pr.13 Starting frequency or higher, the Inverter running (RUN)
turns ON. The signal is OFF during an inverter stop, during the DC injection brake operation, during tuning at start-up, or
during zero speed control.
• The Inverter running 2 (RUN2) signal is ON while the inverter is running or while the start command signal is ON. (When
the inverter's protective function is activated or the MRS signal is ON, the RUN2 signal turns OFF.)
Power
supply ON OFF
12
STF ON OFF
RH ON 13
MRS ON
14
Output frequency
ON OFF
16
RY
ON OFF
RUN
RUN2
ON OFF
17
ON OFF
RUN3
• The ON/OFF state of each signal according to the inverter operating status is shown in the matrix below.
18
During DC Automatic restart after
Start signal Start signal Start Inverter output
injection brake instantaneous power failure
Output OFF ON*1 (zero signal ON shutoff*3
operation During coasting Inverter
signal (inverter
stopped)
speed
control)
(inverter
running)
(zero speed Start Start Start Start running 19
control) signal ON signal OFF signal ON signal OFF after restart
RY*4 ON ON ON ON OFF ON*2 ON
RUN OFF OFF ON OFF OFF OFF ON 20
RUN2 OFF ON ON OFF OFF OFF ON
RUN3 OFF ON ON ON ON OFF ON OFF ON
*1 When the start signal is ON and the frequency command is 0 Hz, such state is designated as "during zero speed control".
*2 The signal is OFF during power failure or undervoltage.
*3 This means the state during a fault occurrence or while the MRS signal is ON, etc.
*4 The signal is OFF while power is not supplied to the main circuit.
• To use the RY, RUN, RUN2, or RUN3 signal, set the corresponding number selected from the following table in any
parameter from Pr.190 to Pr.196 (Output terminal function selection) to assign the function to an output terminal.
Pr.190 to Pr.196 settings
Output signal
Positive logic Negative logic
RY 11 111
RUN 0 100
RUN2 44 144
RUN3 45 145
NOTE
• The RUN signal (positive logic) is initially assigned to the terminal RUN (standard models only).
Time
ALM ON OFF
RES ON OFF
Reset processing
(about 1s)
Reset ON
NOTE
• For details of the inverter faults, refer to the Instruction Manual (Maintenance).
Parameters referred to
Pr.13 Starting frequencypage 169, page 170
If the inverter output frequency which reaches a specific value is detected, the relative signal is output.
12
*1
Initial value Setting
Pr. Name Description
Gr.1 Gr.2 range
41
M441
Up-to-frequency
sensitivity
10% 0% to 100% Set the level where the SU signal turns ON. 13
42 Output frequency
6 Hz 0 to 590 Hz Set the frequency at which the FU (or FB) signal turns ON.
M442 detection
43
Output frequency
detection for reverse 9999
0 to 590 Hz
Set the frequency at which the FU (or FB) signal turns ON only
while the motor rotates in reverse direction.
14
M443
rotation 9999 The frequency same as the Pr.42 setting is set.
865
M446
Low speed detection 1.5 Hz 0 to 590 Hz Set the frequency at which the LS signal turns ON.
15
870 Speed detection
0 Hz 0 to 15 Hz Set the hysteresis width for the detected frequency.
M400 hysteresis
*1 Gr.1 and Gr.2 are the parameter initial value groups. (Refer to page 82).
16
Setting the notification zone of the output frequency reaching the set
point (SU signal, Pr.41)
• The Up to frequency (SU) signal is output when the output frequency reaches the set frequency. 17
• Set the value in the range of 1% to 100% in Pr.41 to determine tolerance for the set frequency (considered as 100% point).
• It may be useful to use this signal to start operating related equipment after checking that the set frequency has been
reached. 18
• To use the SU signal, set "1" (positive logic) or "101" (negative logic) in one of Pr.190 to Pr.196 (Output terminal function
selection) to assign function to an output terminal.
Set frequency Adjustment 19
Output frequency
range Pr.41
20
(Hz)
Time
OFF ON OFF
SU
Forward
rotation
Output frequency
Pr.42
Pr.43 Time
(Hz)
Output Reverse
signal rotation
FU/FB OFF ON OFF ON OFF
• To use each signal, set the corresponding number selected from the following table in any parameter from Pr.190 to
Pr.196 (Output terminal function selection) to assign the function to an output terminal.
Pr.190 to Pr.196 settings
Output signal Related Parameter
Positive logic Negative logic
FU 4 104
42, 43
FB 41 141
Pr.865
(Hz)
Time
LS ON OFF ON
Output frequency
(Hz)
Pr.870
SU output level
Pr.870
Output
frequency Pr.41
(Hz) Set frequency
Pr.42 Pr.870
Pr.870 SU output level
Pr.870
Time
ON SU signal ON ON
FB
ON ON ON
Example of the speed detection (FB) signal Example of the up to frequency (SU) signal
Reference frequency
Control method or function
FU FB, SU, LS 12
V/F control Output frequency Output frequency
Advanced magnetic flux vector Output frequency before the slip Output frequency before the slip
control compensation compensation
Parameters referred to
Pr.190 to Pr.196 (Output terminal function selection)page 250
Pr.874 OLT level settingpage 100
16
17
18
19
20
Initial
Pr. Name Setting range Description
value
150 Output current detection Set the level to detect the output current. Consider the value of
150% 0% to 400%
M460 level the rated inverter current as 100%.
Set the timing to detect the output current. Enter the delay time
151 Output current detection between the time when the output current reaches the set
0s 0 to 10 s
M461 signal delay time current or higher and the time when the Output current
detection (Y12) signal is output.
152 Set the level to detect the zero current. Consider the value of
Zero current detection level 5% 0% to 400%
M462 the inverter rated current as 100%.
Set the time from the time when the output current drops to the
153
Zero current detection time 0.5 s 0 to 10 s Pr.152 setting or lower to the time when the Zero current
M463
detection (Y13) signal is output.
0 to 10 s Set the retention time period during which the Y12 signal is ON.
166 Output current detection
0.1 s The Y12 signal is retained ON. The signal turns OFF at the next
M433 signal retention time 9999
start-up of the inverter.
167 Output current detection Select the inverter operation at the time when the Y12 signal
0 0, 1, 10, 11
M464 operation selection and the Y13 signal turn ON.
Pr.150
Output current
Pr.151
Time
Pr.166
Output current
detection signal OFF ON OFF
(Y12)
Zero current
detection time
OFF
Pr.153
ON OFF
Pr.153
ON
15
(Y13)
Detection time Detection time
19
CAUTION
• The setting of the zero current detection level should not be too low, and the setting of the zero current detection time
should not be too long. Doing so may cause the signal for the zero current detection not to be output when the output
20
current is very low and the motor torque is not generated.
• A safety backup such as an emergency brake must be provided to prevent machines or equipment in hazardous
conditions even if the Zero current detection is used.
Parameters referred to
Online auto tuningpage 315
Offline auto tuningpage 299, page 308
Pr.190 to Pr.196 (Output terminal function selection)page 250
Pr.864
Time
TU ON OFF
NOTE
• Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.190 to Pr.196 (Output terminal function selection)page 250
The signal can be turned ON or OFF via the output terminal on the inverter as if the terminal is the remote output terminal for
a programmable controller. 12
Setting
Pr. Name Initial value Description
range
Remote output data is cleared when
13
0
the inverter power is turned OFF. Remote output data is cleared
Remote output data is retained even during an inverter reset.
1
495
M500
Remote output selection 0
after the inverter power is turned OFF. 14
Remote output data is cleared when
10
the inverter power is turned OFF. Remote output data is retained
Remote output data is retained even during an inverter reset.
11
after the inverter power is turned OFF. 15
Set a decimal number to enter a binary number in every bit
496
Remote output data 1 0 0 to 4095 corresponding to each of the output terminals of the inverter or
M501
communication.
497
Set a decimal number to enter a binary number in every bit 16
Remote output data 2 0 0 to 4095 corresponding to each of the output terminals of the option FR-A8AY or
M502
FR-A8AR, or communication.
b11 b0
RUN
ABC
FU
*1
*1
*1
*1
*1
*1
*1
*1
*1
Pr.497
b11 b0
RA3 ∗3
RA2 ∗3
RA1 ∗3
Y6 ∗2
Y5 ∗2
Y4 ∗2
Y3 ∗2
Y2 ∗2
Y1 ∗2
Y0 ∗2
∗1
∗1
*1 Any value
*2 Y0 to Y6 are available by installing the output-extending option (FR-A8AY) or via communication.
*3 RA1 to RA3 are available by installing the relay output option (FR-A8AR) or via communication.
Reset ON Reset ON
NOTE
• The output terminal to which the REM signal is not assigned by using Pr.190 to Pr.192 does not turn ON or OFF when "1 or
0" is set in bit corresponding to each of the terminals by using Pr.496 and Pr.497. (ON/OFF command affects only the terminal
to which the REM signal is assigned.)
• If the power supply is turned OFF during an inverter reset, the remote output data is not stored even when Pr.495 = "1 or 11".
Parameters referred to
Pr.190 to Pr.196 (Output terminal function selection)page 250
10
265
12 (T) Multi-Function Input Terminal Parameters
Refer to
Purpose Parameter to set
page
To inverse the rotation direction with the
voltage/current analog input selection Analog input selection P.T000, P.T001 Pr.73, Pr.267 266
(terminals 2 and 4)
To assign functions to analog input
Terminal 4 function assignment P.T040 Pr.858 270
terminals
Pr.74, Pr.822, Pr.826,
To eliminate noise on analog inputs Analog input filter P.T002 to P.T007 Pr.832, Pr.836, 271
Pr.849
P.T200 to P.T203,
To adjust analog input frequency/voltage Frequency setting voltage Pr.125, Pr.126,
P.T400 to P.T403, 273
(current) (calibration) (current) bias and gain Pr.241, C2 to C7
P.M043
To adjust analog input torque/voltage Torque setting voltage (current) P.T410 to P.T413,
Pr.241, C38 to C41 278
(current) (calibration) bias and gain P.M043
Input terminal function P.T700 to P.T711, Pr.178 to Pr.189,
To assign functions to input terminals 283
selection P.T740 Pr.699
Output stop signal (MRS) /
To change the input specification (NO/NC
Inverter run enable signal (X10) P.T720 Pr.17 287
contact) of input signals
input selection
To assign start and forward/reverse Start signal (STF/STR) operation
P.G106 Pr.250 291
commands to different signals selection
Voltage/current Voltage/current
12
input switch input switch
Standard model Ethernet model
Switch 2 2 Switch 2 2
V I V I 13
Switch 4 4 Switch 4 4
14
15
Switch 4
I Current input (initial status)
Terminal 4
For current input, the input resistance is 245±5 Ω and the
maximum permissible current is 30 mA.
17
V Voltage input
• Change the setting of the voltage/current input selection switch to change the rated specification of terminal 2 or 4.
• Set Pr.73 (Pr.267) and the voltage/current input selection switch according to the analog signal input. The incorrect 18
settings shown in the following table cause a failure. The inverter does not operate properly with other incorrect settings.
Setting causing a failure
Switch setting Terminal input
Operation 19
Causes an analog signal output circuit failure in an external device (due to increased loads on the
I (current input) Voltage input
signal output circuit of the external device).
• When the Terminal 4 input selection (AU) signal is turned ON, terminal 4 is used to set the main speed. In this case,
terminal 2 is not used to set the main speed.
• Set Pr.267 and the voltage/current input selection switch according to the following table.
Pr.267 setting Terminal 4 input Switch 4 Reversible operation
0 (initial value) 4 to 20 mA I
Determined by Pr.73
1 0 to 5 V V
setting
2 0 to 10 V V
Forward Inverter
Inverter Inverter rotation STF
Forward STF Forward STF Terminal 4 AU Voltage/current
Voltage/current
rotation SD
Voltage/current rotation SD input switch input selection input switch
input switch SD
0 to 5 VDC 2 0 to 5 VDC 2
10 2 0 to 10 VDC 10
Frequency V I Frequency V I
2 V I Voltage 2 4
setting Frequency input setting
5 setting 5 4 4
4 equipment 5
NOTE
• The wiring length of terminal 10, 2, and 5 should be 30 m at maximum.
Inverter
Forward STF
rotation AU Voltage/current
input switch
SD
4 to 20mADC
2
4 V I
Frequency Current
input
setting equipment 5 4
18
Set frequency (Hz)
Reverse Forward
rotation rotation
Pr.125
Reversible
19
Not reversible
NOTE
• Note that the reverse rotation operation is performed when analog input stops (only the start signal is input) while the reversible
operation is set.
• When the reversible operation is enabled, the reversible operation by terminal 4 is performed in the initial setting (reverse
operation is performed when 0 to 4 mA is input, and forward operation when 4 to 20 mA).
Parameters referred to
Pr.125 Terminal 2 frequency setting gain frequency, Pr.126 Terminal 4 frequency setting gain frequencypage 273
Pr.858 Terminal 4 function assignmentpage 270
Parameters referred to
Advanced magnetic flux vector controlpage 90
Real sensorless vector controlpage 86
Pr.804 Torque command source selectionpage 117
Pr.810 Torque limit input method selectionpage 100
822 0 to 5 s
Set the primary delay filter time constant to the external 14
Speed setting filter 1 9999 speed command (analog input command).
T003
9999 As set in Pr.74.
826
Torque setting filter 1 9999
0 to 5 s
Set the primary delay filter time constant to the external
torque command (analog input command). 15
T004
9999 As set in Pr.74.
832 Second function of Pr.822 (enabled when the RT signal is
Speed setting filter 2 9999 0 to 5 s, 9999
T005
836
ON)
Second function of Pr.826 (enabled when the RT signal is
16
Torque setting filter 2 9999 0 to 5 s, 9999
T006 ON)
Set offset for the analog speed input (terminal 2). The motor
849 Analog input offset
T007 adjustment
100% 0% to 200% is prevented from rotating due to noise in the analog input
or other factors when a zero speed command is given.
17
Block diagram
Pr.822 = 9999
Pr.74 18
Speed command
RT-OFF
Pr.826 ≠ 9999
Pr.832 = 9999
Pr.832
Pr.832 ≠ 9999
Pr.836 = 9999
Pr.836
Pr.836 ≠ 9999
Frequency
command Slope determined
according to Pr.125
and C2 to C4
Slope does not
change.
NOTE
• The analog input filter is invalid (no filter) during PID control operation.
Parameters referred to
Pr.73 Analog input selectionpage 266
Pr.125, C2 to C4 (bias and gain of the terminal 2 frequency setting)page 273
The magnitude (slope) of the output frequency can be set as desired in relation to the frequency setting signal (0 to 5 VDC, 0
to 10 VDC, or 4 to 20 mA). Use Pr.73 Analog input selection (Pr.267 Terminal 4 input selection) and the voltage/current 12
input selection switch to switch among input of 0 to 5 VDC, 0 to 10 V, and 0 to 20 mA. (Refer to page 266.)
Initial value*1
Pr. Name
Gr.1 Gr.2
Setting
range
Description 13
C2 Terminal 2 frequency setting
0 Hz 0 to 590 Hz Set the bias frequency for the terminal 2 input.
T200 bias frequency
C3
T201
Terminal 2 frequency setting
bias
0%
0% to
300%
Set the converted % of the bias voltage (current) for the terminal
2 input.
14
125
Terminal 2 frequency setting
T202 60 Hz 50 Hz 0 to 590 Hz Set the gain (maximum) frequency for the terminal 2 input.
gain frequency
T022
C4 Terminal 2 frequency setting 0% to Set the converted % of the gain voltage (current) for the terminal
15
100%
T203 gain 300% 2 input.
C5 Terminal 4 frequency setting
0 Hz 0 to 590 Hz Set the bias frequency for the terminal 4 input.
T400 bias frequency 16
C6 Terminal 4 frequency setting 0% to Set the converted % of the bias current (voltage) for the terminal
20%
T401 bias 300% 4 input.
126
T402
Terminal 4 frequency setting
gain frequency
60 Hz 50 Hz 0 to 590 Hz Set the gain (maximum) frequency for the terminal 4 input. 17
T042
C7 Terminal 4 frequency setting 0% to Set the converted % of the gain current (voltage) for the terminal
100%
T403 gain 300% 4 input.
241 Analog input display unit
0
0 % display
Select the unit for analog input display.
18
M043 switchover 1 V/mA display
*1 Gr.1 and Gr.2 are the parameter initial value groups. (Refer to page 82).
Changing the frequency for the maximum analog input (Pr.125, Pr.126)
• Use Pr.125 (Pr.126) to change the frequency setting (gain) for the maximum analog input voltage (current).
(The C2 to C7 settings need not be changed.)
Output frequency
Output frequency
(50Hz) (50Hz)
(Hz)
(Hz)
0 100% 0 20 100%
0 5V 0 4 Frequency setting signal 20mA
Frequency setting signal 0 1 5V
0 10V
0 20mA 0 2 10V
C3 C4 C6 C7
• There are three methods to adjust the bias/gain frequency setting voltage (current).
Adjustment by applying voltage (current) between terminals 2 and 5 (4 and 5) to set the voltage (current) at the bias/gain
frequency. page 275
Adjustment by selecting the voltage (current) at the bias/gain frequency without applying voltage (current) between
terminals 2 and 5 (4 and 5). page 276
Adjustment by changing the frequency without adjusting the voltage (current). page 277
NOTE
• Always calibrate the input after changing the voltage/current input signal with Pr.73 (Pr.267) and the voltage/current input
selection switch.
5. Selecting a parameter
Turn the setting dial or press the UP/DOWN key until "C4" (C4 Terminal 2 frequency setting gain) appears for 16
terminal 2, or "C7" (C7 Terminal 4 frequency setting gain) for terminal 4.
8. Setting completed 19
Press the SET key to confirm the setting. The analog voltage (current) value (%) blinks when it is applied.
• Turn the setting dial or press the UP/DOWN key to read another parameter.
• Press the SET key to return to the "C---" display. 20
• Press the SET key twice to show the next parameter.
5. Selecting a parameter
Turn the setting dial or press the UP/DOWN key until "C4" (C4 Terminal 2 frequency setting gain) appears for
terminal 2, or "C7" (C7 Terminal 4 frequency setting gain) for terminal 4.
8. Setting completed
Press the SET key to confirm the setting. The analog voltage (current) value (%) blinks when it is applied.
• Turn the setting dial or press the UP/DOWN key to read another parameter.
• Press the SET key to return to the "C---" display.
• Press the SET key twice to show the next parameter.
NOTE
• The present frequency setting bias/gain setting can be checked by pressing the setting dial or pressing the UP/DOWN key one
time after step 6. The setting cannot be checked after step 7.
NOTE
• If the frequency meter (display meter) connected to terminal FM or terminal AM of the standard model does not indicate exactly 17
60 Hz, set the calibration parameter C0 or C1. (Refer to page 241.)
• If the voltage (current) values at the gain and bias frequencies are too close to each other, an error "Er3" may be indicated.
• Changing C4 or C7 (gain adjustment) will not change the Pr.20. 18
• To set the value to 120 Hz or higher, the Pr.18 High speed maximum frequency needs to be 120 Hz or higher. (Refer to
page 211.)
• Use the calibration parameter C2 or C5 to set the bias frequency. (Refer to page 273.)
19
CAUTION 20
• Be cautious when setting any value other than "0" as the bias frequency at 0 V (0 mA). Even if a speed command is not
given, simply turning ON the start signal will start the motor at the preset frequency.
Parameters referred to
Pr.1 Maximum frequency, Pr.18 High speed maximum frequencypage 211
Pr.20 Acceleration/deceleration reference frequencypage 158
Pr.73 Analog input selection, Pr.267 Terminal 4 input selectionpage 266
Pr.79 Operation mode selectionpage 174
Pr.858 Terminal 4 function assignmentpage 270
The magnitude (slope) of the torque can be set as desired in relation to the torque setting signal (0 to 5 VDC, 0 to 10 VDC, or
4 to 20 mA).
Use Pr.267 Terminal 4 input selection to switch among input 0 to 5 VDC, 0 to 10 V, and 4 to 20 mA. (Refer to page 266.)
Initial
Pr. Name Setting range Description
value
C38 Terminal 4 bias command (torque/ Set the bias torque (magnetic flux) for the terminal 4
0% 0% to 400%
T410 magnetic flux) input.
C39 Terminal 4 bias (torque/magnetic Set the converted % of the bias current (voltage) for the
20% 0% to 300%
T411 flux) terminal 4 input.
C40 Terminal 4 gain command (torque/ Set the gain (maximum) torque (magnetic flux) for the
150% 0% to 400%
T412 magnetic flux) terminal 4 input.
C41 Terminal 4 gain (torque/magnetic Set the converted % of the gain current (voltage) for the
100% 0% to 300%
T413 flux) terminal 4 input.
241 Analog input display unit 0 % display Select the unit for analog input
0
M043 switchover 1 V/mA display display.
11
400
Torque(%)
150 Gain 12
C40
Bias
C38
Initial value
13
0 20 100%
0 4 20mA
C39
Torque setting signal
C41 14
Calibration example of terminal 4
• There are three methods to adjust the bias/gain for torque setting current (voltage).
15
Adjustment by applying current (voltage) between terminals 4 and 5 to set the current (voltage) at the bias/gain torque.
page 279
Adjustment by selecting the current (voltage) at the bias/gain torque without applying current (voltage) between terminals
16
4 and 5. page 281
Adjustment by changing the torque without adjusting the current (voltage). page 282
NOTE 17
• Always calibrate the input after changing the voltage/current input signal with Pr.267 and the voltage/current input selection
switch.
18
Display unit changing for analog input (Pr.241)
• The analog input display unit (%/V/mA) can be changed for analog input bias/gain calibration.
• Depending on the terminal input specification setting of Pr.73 (Pr.267), the units of the displayed values of C39 and C41 19
change as shown below:
Analog command (via terminal 4)
(depending on the Pr.267 setting)
Pr.241 = "0" (initial value) Pr.241 = "1" 20
0 to 5 V input 0% to 100% (0.1%) 0 to 5 V (0.01 V)
0 to 10 V input 0% to 100% (0.1%) 0 to 10 V (0.01 V)
0 to 20 mA input 0% to 100% (0.1%) 0 to 20 mA (0.01 mA)
5. Selecting a parameter
Turn the setting dial or press the UP/DOWN key until "C41" (C41 Terminal 4 gain (torque/magnetic flux)) appears.
8. Setting completed
Press the SET key to confirm the setting. The analog current (voltage) value (%) blinks when it is applied.
• Turn the setting dial or press the UP/DOWN key to read another parameter.
• Press the SET key to return to the "C---" display.
• Press the SET key twice to show the next parameter.
5. Selecting a parameter
15
Turn the setting dial or press the UP/DOWN key until "C41" (C41 Terminal 4 gain (torque/magnetic flux)) appears.
NOTE 20
• The present torque setting bias/gain setting can be checked by pressing the setting dial or pressing the UP/DOWN key one
time after step 6. The setting cannot be checked after step 7.
4. Start
Turn ON the start switch (STF or STR) to apply a voltage across terminals 4 and 5.
Operation is performed with 130% torque.
NOTE
• If the current (voltage) values at the gain and bias torques are too close to each other, an error ("Er3") may be indicated.
• Use the calibration parameter C38 to set the bias torque. (Refer to page 278.)
CAUTION
• When setting a value other than "0" as the bias torque, note that simply turning ON the start signal will supply torque to
the motor even if a torque command is not given.
Parameters referred to
Pr.20 Acceleration/deceleration reference frequencypage 158
Pr.267 Terminal 4 input selectionpage 266
Pr.79 Operation mode selectionpage 174
Pr.858 Terminal 4 function assignmentpage 270
Use the following parameters to select or change the input terminal functions.
Initial
12
Pr. Name Initial signal Setting range
value
178 STF/DI0 terminal 0 to 5, 7, 8, 10, 12, 14 to 16, 18, 24 to 27, 30, 37,
60 STF (Forward rotation command)
T700 function selection 46, 47, 50, 51, 60, 62, 65 to 67, 72, 92, 9999 13
179 STR/DI1 terminal 0 to 5, 7, 8, 10, 12, 14 to 16, 18, 24 to 27, 30, 37,
61 STR (Reverse rotation command)
T701 function selection 46, 47, 50, 51, 61, 62, 65 to 67, 72, 92, 9999
180 RL terminal function
T702 selection
0 RL (Low-speed operation command)
14
181 RM terminal function
1 RM (Middle-speed operation command)
T703 selection
182 RH terminal function 0 to 5, 7, 8, 10, 12, 14 to 16, 18, 24 to 27, 30, 37,
T704 selection
2 RH (High-speed operation command)
46, 47, 50, 51, 62, 65 to 67, 72, 92, 9999*3 15
183 MRS terminal
24 MRS (Output stop)
T709 function selection
62*1 RES (Inverter reset)
184
T711
RES terminal
function selection 9999 *2 No function
16
185 NET X1 input
9999 No function
T751 selection
186 NET X2 input
9999 No function 17
T752 selection
187 NET X3 input 0 to 4, 8, 14, 15, 18, 24, 26, 27, 30, 37, 46, 47,
9999 No function
T753 selection 50, 51, 72, 92, 9999
188 NET X4 input
9999 No function
18
T754 selection
189 NET X5 input
9999 No function
T755 selection
Initial
19
Pr. Name Setting range Description
value
699 5 to 50 ms Set the time delay for the input terminal response.
T740
Input terminal filter 9999
9999 No filter for the input terminal 20
*1 The initial value is for standard models.
*2 The initial value is for Ethernet models.
*3 The setting range differs depending on the model. For more information, refer to the parameters available for each signal.
26
(STOP)
MC ○ ○ ○ ○ ○ ○ ○
20
27 TL ○ ○ ○ ○ ○ ○ ○
30 JOG ○ ○ ○ ○ ○ ○ ○
37 X37 ○ ○ ○ ○ ○ ○ ○
46 TRG ○ ○ ○ ○ ○ ○ ○
47 TRC ○ ○ ○ ○ ○ ○ ○
50 SQ ○ ○ ○ ○ ○ ○ ○
51 X51 ○ ○ ○ ○ ○ ○ ○
60 STF ○ — — — ○ — —
61 STR — ○ — — — ○ —
62 RES ○ ○ ○ — ○ ○ —
65 X65 ○ ○ ○ — ○ ○ —
66 X66 ○ ○ ○ — ○ ○ —
67 X67 ○ ○ ○ — ○ ○ —
72 X72 ○ ○ ○ ○ ○ ○ ○
92 X92 ○ ○ ○ ○ ○ ○ ○
9999 No function ○ ○ ○ ○ ○ ○ ○
Time
ON OFF
STF
Pr.699 9999
Pr.699 Pr.699
NOTE
• The Pr.699 setting is invalid (no filter) for the following signals.
— Input signals which are already in the ON state when the power is turned ON
— Input signals used for the PLC function
— Output stop (MRS) signal
The inverter output can be shut off with the MRS signal. The logic of the MRS signal can also be selected.
Description
12
Initial
Pr. Name Setting range
value MRS signal input X10 signal input*1
0 Normally open input
1 Normally open input Normally closed input (NC 13
contact input specification)
2 Normally open input
Normally closed input (NC
3 Normally closed input (NC
17
T720
MRS/X10 terminal input
selection
0 contact input specification)
contact input specification) 14
4 External terminal: Normally Normally open input
closed input (NC contact input
specification) Normally closed input (NC
5
Communication: Normally open contact input specification) 15
input
*1 Refer to page 386 for the details of the X10 signal.
MRS signal ON 19
STF (STR)
signal ON
• When the Output stop (MRS) signal is turned ON while operating the inverter, the inverter output is instantaneously shut 20
off.
• To input the MRS signal, set "24" in any parameter from Pr.178 to Pr.189 (Input terminal function selection) to assign
the function.
• The response time of the MRS signal is within 2 ms.
• The MRS signal is used in the following cases.
Application Description
To stop the motor using a mechanical brake (e.g.
The inverter output is shut off when the mechanical brake operates.
electromagnetic brake)
To provide interlock to disable the motor operation by the With the MRS signal ON, the motor cannot be driven by the inverter even if
inverter the start signal is input to the inverter.
When the start signal is turned OFF, the inverter decelerates the motor to
To coast the motor to a stop a stop in the preset deceleration time, but when the MRS signal is turned
ON, the motor coasts to a stop.
NOTE
• When using an external terminal to input the MRS signal, the MRS signal shuts off the output in any of the operation modes.
• The MRS signal is valid regardless of whether it is input through the external terminal or via network, but when the MRS signal
is used as the Inverter run enable (X10) signal, input the signal through the external terminal.
• When the terminal assignment is changed using Pr.178 to Pr.189 (Input terminal function selection), wiring may be
mistaken due to different terminal name and signal contents, or may affect other functions. Set parameters after confirming
the function of each terminal.
Parameters referred to
Pr.79 Operation mode selectionpage 174
Pr.178 to Pr.189 (Input terminal function selection)page 283
16
Start STF/STR Acceleration
Second function selection RT time is applied
High speed RH
Time 17
Middle speed RM RT
SD
RH
RM
18
• When the RT signal is ON, second functions are selected. The following table shows the functions which can be changed
to the second function. 19
First function parameter Second function parameter
Function Refer to page
number number
Torque boost
Base frequency
Pr.0
Pr.3
Pr.46
Pr.47
374
376
20
Acceleration time Pr.7 Pr.44 158
Deceleration time Pr.8 Pr.44, Pr.45 158
Electronic thermal
Pr.9 Pr.51 198
O/L relay
Stall prevention Pr.22 Pr.48 214
Applied motor *1 Pr.71 Pr.450 294
Pr.80 to Pr.84, Pr.90 to
Pr.94, Pr.298, Pr.702,
Pr.453 to Pr.462, Pr.560,
Pr.706, Pr.707, Pr.711,
Motor constant*1 Pr.712, Pr.717, Pr.721,
Pr.738 to Pr.746, Pr.860, 299, 308
Pr.1413
Pr.724, Pr.725, Pr.859,
Pr.1412
Speed control gain (Advanced
Pr.89 Pr.569 90
magnetic flux vector)*1
Offline auto tuning*1 Pr.96 Pr.463 299, 308
*1 Pr.95 Pr.574 315
Online auto tuning
*1 Pr.800 Pr.451 86
Motor control method
Speed control gain Pr.820, Pr.821 Pr.830, Pr.831 107
Analog input filter Pr.822, Pr.826 Pr.832, Pr.836 271
Torque control gain Pr.824, Pr.825 Pr.834, Pr.835 122
*1 The function can be changed by switching the RT signal ON/OFF while the inverter is stopped. If a signal is switched during operation, the
operation method changes after the inverter stops. (Pr.450 ≠ 9999)
Parameters referred to
Pr.178 to Pr.189 (Input terminal function selection)page 283
8888
STF signal: Start signal
STR signal: Forward/reverse
when the start signal is turned OFF. 16
rotation signal
20
Forward
rotation start STF Start signal STF
Reverse Forward
rotation rotation
rotation rotation
Output frequency
Output frequency
Time Time
ON ON
STF STF
ON ON
STR STR
2-wire type connection example (Pr.250 = "9999") 2-wire type connection example (Pr.250 = "8888")
NOTE
• By setting Pr.250 = "0 to 100, 1000 to 1100", the motor will coast to a stop when the start command is turned OFF. (Refer to
page 384.)
• The STF and STR signals are assigned to Pr.178 STF/DI0 terminal function selection and Pr.179 STR/DI1 terminal
function selection in the initial status. The STF signal can be assigned to only Pr.178 STF/DI0 terminal function selection,
and the STR signal can be assigned to only Pr.179 STR/DI1 terminal function selection.
Reverse Forward
Reverse Forward
rotation rotation
rotation rotation
Output frequency
Output frequency
Time Time
ON ON ON
STF STF
ON
STR STR ON
NOTE
• When the JOG operation is enabled by turning ON the JOG signal, the STP (STOP) signal will be disabled.
• Even when the output is stopped by turning ON the MRS signal, the self-holding function is not canceled.
Parameters referred to
Pr.4 to Pr.6 (multi-speed setting)page 195
Pr.178 to Pr.189 (Input terminal function selection)page 283
10
293
13 (C) Motor Constant Parameters
Purpose Parameter to set Refer to page
To select the motor to be used Applied motor P.C100, P.C200 Pr.71, Pr.450 294
P.C100 to P.C105,
P.C107, P.C108, Pr.9, Pr.51, Pr.71,
P.C110, P.C120 to Pr.80 to Pr.84, Pr.90 to
P.C126, P.C182, Pr.94, Pr.96, Pr.453 to
To maximize the performance of the
Offline auto tuning PC188, P.C200 to Pr.463, Pr.707, Pr.717, 299
induction motor
P.C205, P.C207, Pr.720, Pr.724, Pr.737,
P.C208, P.C210, Pr.741, Pr.744, Pr.745,
P.C220 to P.C226, Pr.859, Pr.860
P.C282, P.C288
P.C100 to P.C108, Pr.9, Pr.51, Pr.71,
P.C110, P.C120, Pr.80, Pr.81, Pr.83,
P.C122, P.C123, Pr.84, Pr.90, Pr.92,
P.C126, P.C130 to Pr.93, Pr.96, Pr.450,
P.C133, P.C135, Pr.453, Pr.454, Pr.456
P.C150, P.C182, to Pr.458, Pr.460,
To maximize the performance of the PM motor offline auto
P.C185, P.C200 to Pr.461, Pr.463, Pr.702, 308
PM motor tuning
P.C208, P.C210, Pr.706, Pr.707, Pr.711,
P.C220, P.C222, Pr.712, Pr.717, Pr.721,
P.C223, P.C226, Pr.724, Pr.725, Pr.738
P.C230 to P.C233, to Pr.746, Pr.859,
P.C235, P.C282, Pr.860, Pr.1002,
P.C285 Pr.1412, Pr.1413
To perform high accuracy operation
without being affected by temperature Online auto tuning P.C111, P.C211 Pr.95, Pr.574 315
and high-torque/ultra-low speed
NOTE
• Regardless of the Pr.71 (Pr.450) setting, offline auto tuning can be performed according to Pr.96 (Pr.463) Auto tuning
setting/status. (Refer to page 299 for offline auto tuning.)
NOTE
• Regardless of the Pr.71 (Pr.450) setting, offline auto tuning can be performed according to Pr.96 (Pr.463) Auto tuning
setting/status. (Refer to page 299 for offline auto tuning.)
Automatic change of torque boost for the SF-PR motor (200/400 V class)
• When the SF-PR motor is selected (Pr.71 = "70 or 73"), the Pr.0 Torque boost setting is automatically changed to enable
output of the 6 Hz 150% torque under V/F control by setting Pr.81 Number of motor poles according to the number of
the SF-PR motor poles.
NOTE
• When selecting the automatic change of torque boost for the SF-PR motor, set Pr.14 Load pattern selection = "0 (initial
value)".
• When the Pr.0 setting is changed from its initial value, the automatic change is not performed.
NOTE
• When the Pr.0 and Pr.12 settings are changed from their initial values, the automatic change is not performed.
• When the SF-PR motor is selected (Pr.71 = "70 or 73"), the output current may become large due to a small load by setting
Pr.81 Number of motor poles according to the number of the SF-PR motor poles.
• When the SF-PR motor is used, the output current tends to increase compared with the case where the SF-JR or SF-HR motor
is used. Depending on the load conditions, the output current may increase even though the torque boost value has been
automatically changed. When the protective function such as the electronic thermal O/L relay (E.THT, E.THM) or stall
prevention (OL, E.OLT) is activated, adjust the Pr.0 Torque boost according to the load.
CAUTION
• Make sure to set this parameter correctly according to the motor used. Incorrect setting may cause the motor and the
inverter to overheat and burn.
Parameters referred to
Pr.0 Torque boostpage 374
Pr.12 DC injection brake operation voltagepage 382
Pr.14 Load pattern selectionpage 378
Pr.96 Auto tuning setting/statuspage 299
Pr.178 to Pr.189 (Input terminal function selection)page 283
Pr. Name
Initial
value
Setting range Description 14
0, 3, 5, 6, 10, 13, 15, 16, 20,
71 23, 40, 43, 50, 53, 70, 73, By selecting a motor, the thermal characteristic and motor
Applied motor 0
C100 constant of each motor are set.
8090, 8093, 9090, 9093*1 15
80 0.1 to 30 kW Set the applied motor capacity.
Motor capacity 9999
C101 9999 V/F control
81 Number of motor 2, 4, 6, 8, 10, 12 Set the number of motor poles.
C102 poles
9999
9999 V/F control 16
Inverter
9 Electronic thermal rated 0 to 500 A Set the rated motor current.
C103 O/L relay
current*2
83 200/400/
17
Rated motor voltage 0 to 1000 V Set the rated motor voltage (V).
C104 575 V*3
84 Rated motor 10 to 400 Hz Set the rated motor frequency (Hz).
C105 frequency
9999
9999 The setting value of Pr.3 Base frequency is used. 18
707 Motor inertia
9999 10 to 999, 9999 Set the motor inertia.
C107 (integer)
9999: The constant value of Mitsubishi Electric motor (SF-PR,
724 Motor inertia
C108 (exponent)
9999 0 to 7, 9999 SF-JR, SF-HR, SF-JRCA, SF-HRCA and so on) is used.
19
0 No offline auto tuning
96 Auto tuning setting/ 1 Offline auto tuning is performed without the motor rotating.
0
C110 status
11
Offline auto tuning is performed without the motor rotating
(under V/F control). (Refer to page 358.) 20
90
C120
Motor constant (R1) 9999 0 to 50 Ω, 9999*4
91
C121
Motor constant (R2) 9999 0 to 50 Ω, 9999*4
Pr.71 setting
Motor constant Motor constant
Motor Motor constant parameter
parameter mH, %, parameter internal
Ω, mΩ, and A unit setting
and A unit setting data setting
Mitsubishi Electric standard SF-JR 0 (initial value) 3 —
efficiency motor SF-JR 4P 1.5 kW or lower 20 23 —
Mitsubishi Electric high- SF-HR 40 43 —
efficiency motor Others 0 (initial value) 3 —
SF-JRCA 4P 10 13 —
Mitsubishi Electric constant-
SF-HRCA 50 53 —
torque motor
Others (SF-JRC, etc.) 10 13 —
Mitsubishi Electric high-
performance energy-saving SF-PR 70 73 —
motor
Other manufacturer's 5 (wye connection motor)
— 0 (initial value) 3
standard motor 6 (delta connection motor)
Other manufacturer's 15 (wye connection motor)
— 10 13
constant-torque motor 16 (delta connection motor)
NOTE
• When Pr.11 DC injection brake operation time = "0" or Pr.12 DC injection brake operation voltage = "0", offline auto
tuning is performed at the initial setting of Pr.11 or Pr.12.
• If "wye connection" or "delta connection" is incorrectly selected in Pr.71, Advanced magnetic flux vector control and Real
sensorless vector control are not performed properly.
• For tuning accuracy improvement, set the following parameters when the motor constants are known in advance.
Mitsubishi Electric motor
First motor Second
Name (SF-PR, SF-JR, SF-HR, SF- Other motors
Pr. motor Pr.
JRCA, SF-HRCA)
707 744 Motor inertia (integer) Motor inertia*3 Jm = Pr.707 × 10^(-Pr.724)
9999 (initial value)
724 745 Motor inertia (exponent) (kg·m2)
*3 The setting is valid only when a value other than "9999" is set in both Pr.707 (Pr.744) and Pr.724 (Pr.745).
Performing tuning
• Before performing tuning, check the monitor display of the operation panel if the inverter is in the state ready for tuning. The
motor starts by turning ON the start command while tuning is unavailable.
• In the PU operation mode, press the RUN key on the operation panel.
In the External operation, turn ON the start command (STF signal or STR signal). Tuning starts.
(1) Setting 17
NOTE
• The motor constants measured once during offline auto tuning are stored as parameters and their data are held until offline
auto tuning is performed again. However, the tuning data is cleared when performing All parameter clear.
• Changing Pr.71 (Pr.450) after tuning completion will change the motor constant. For example, if "3" is set in Pr.71 after tuning
is performed with Pr.71 = "0", the tuning data becomes invalid. To use the tuned data, set "0" again in Pr.71.
• If offline auto tuning has ended in error (see the following table), motor constants are not set. Perform an inverter reset and
restart tuning.
NOTE
• An instantaneous power failure occurring during tuning will result in a tuning error. After power is restored, the inverter starts
normal operation. Therefore, when the STF (STR) signal is ON, the motor starts forward (reverse) rotation.
• Any fault occurring during tuning is handled as in the normal operation. However, if the retry function is set, no retry is
performed.
• The set frequency monitor displayed during the offline auto tuning is 0 Hz.
CAUTION
• Note that the motor may start running suddenly.
• For performing offline auto tuning with the motor rotating in vertical lift applications, etc., caution is required to avoid falling
due to insufficient torque.
Changing the motor constants (when setting the Pr.92 and Pr.93 motor
constants in units of mH)
• Set Pr.71 as follows.
Motor Pr.71 setting
SF-JR 0 (initial value)
Mitsubishi Electric standard efficiency motor
SF-JR 4P 1.5 kW or lower 20
Mitsubishi Electric high-efficiency motor
SF-HR 40
SF-JRCA 4P 10
Mitsubishi Electric constant-torque motor
SF-HRCA 50
Mitsubishi Electric high-performance energy-
SF-PR 70
saving motor
R1 I1 I2
R1: Primary resistance
12
R2: Secondary resistance
I1: Primary leakage inductance
I2: Secondary leakage inductance
V M R2/S M: Excitation inductance 13
S: Slip
298 560
current
Frequency search gain 0 to 32767, 9999 1
18
Starting resistance tuning
717 741 0% to 200% 0.1%
compensation coefficient 1
720 737
Starting resistance tuning
compensation coefficient 2
0% to 200% 0.1% 19
NOTE
• If "9999" is set in the motor constant parameters, tuning data will be invalid and the constant values for Mitsubishi Electric
20
motors (SF-PR, SF-JR, SF-HR, SF-JRCA, SF-HRCA and so on) are used.
NOTE
• As the motor constants measured in the offline auto tuning have been converted into internal data (****), refer to the following
setting example when making setting. (The value displayed has been converted into a value for internal use. Therefore, simple
addition of a value to the displayed value does not bring the desired effect.)
Setting example: To slightly increase the Pr.90 value (5%)
When "2516" is displayed for Pr.90, set 2642 (2516 × 1.05 = 2641.8) in Pr.90.
• If "9999" is set in the motor constant parameters, tuning data will be invalid and the constant values for Mitsubishi Electric
motors (SF-PR, SF-JR, SF-HR, SF-JRCA, SF-HRCA and so on) are used.
Changing the motor constants (when setting the Pr.92, Pr.93, and Pr.94
motor constants in units of Ω)
• Set Pr.71 as follows.
Pr.71 setting
Applied motor
Wye connection motor Delta connection motor
Standard motor 5 6
Constant-torque motor 15 16
NOTE
• If "wye connection" or "delta connection" is incorrectly selected in Pr.71, Advanced magnetic flux vector control and Real
sensorless vector control are not performed properly.
• If "9999" is set in the motor constant parameters, tuning data will be invalid and the constant values for Mitsubishi Electric
motors (SF-PR, SF-JR, SF-HR, SF-JRCA, SF-HRCA and so on) are used.
Initial
Pr. Name Setting range Description
value
0, 3, 5, 6, 10, 13, 15, 16,
71 20, 23, 40, 43, 50, 53, 70, By selecting a motor, the thermal characteristic and motor
Applied motor 0 73, 8090, 8093, 9090,
C100 constant of each motor are set.
9093*1
80 0.1 to 30 kW Set the applied motor capacity.
Motor capacity 9999
C101 9999 V/F control
81 2, 4, 6, 8, 10, 12 Set the number of motor poles.
Number of motor poles 9999
C102 9999 V/F control
Inverter
9 Electronic thermal O/L rated 0 to 500 A Set the rated motor current.
C103 relay
current*2
83 200/400/
Rated motor voltage 0 to 1000 V Set the rated motor voltage (V).
C104 575 V*3
84 10 to 400 Hz Set the rated motor frequency (Hz).
Rated motor frequency 9999
C105 9999 Inverter internal data is used.
702 0 to 400 Hz Set the permissible speed (frequency) of the motor.
Maximum motor frequency 9999
C106 9999 The Pr.84 setting is used.
707
Motor inertia (integer) 9999 10 to 999, 9999
C107 Set the motor inertia.
724 9999: Inverter internal data is used.
Motor inertia (exponent) 9999 0 to 7, 9999
C108
0 No offline auto tuning
96 1 Offline auto tuning is performed without the motor rotating.
Auto tuning setting/status 0
C110 Offline auto tuning is performed without the motor rotating
11
(under V/F control).
90
C120
Motor constant (R1) 9999 0 to 50 Ω, 9999*4
Settings
• To perform tuning, set the following parameters about the motor.
First motor Pr. Second motor Pr. Name Setting
80 453 Motor capacity Motor capacity (kW)
81 454 Number of motor poles Number of motor poles (2 to 12)
9 51 Electronic thermal O/L relay Rated motor current (A)
84 457 Rated motor frequency Rated motor frequency (Hz)
83 456 Rated motor voltage Rated motor voltage (V)
8090, 8093 (IPM motor),
71 450 Applied motor
9090, 9093 (SPM motor)*1
96 463 Auto tuning setting/status 1
*1 Set Pr.71 Applied motor according to the motor to be used. According to the Pr.71 setting, the range of the motor constant parameter setting
values and units can be changed. (For other setting values of Pr.71, refer to page 294.)
Pr.71 setting
Motor
Motor constant parameter Ω, mH, and A unit setting Motor constant parameter internal data setting
IPM motor 8090 8093
SPM motor 9090 9093
*1 The setting is valid only when a value other than "9999" is set in both Pr.707 (Pr.744) and Pr.724 (Pr.745).
13
Performing tuning
• Before performing tuning, check the monitor display of the operation panel if the inverter is in the state ready for tuning. The 14
motor starts by turning ON the start command while tuning is unavailable.
15
• In the PU operation mode, press the RUN key on the operation panel.
In the External operation, turn ON the start command (STF signal or STR signal). Tuning starts.
16
NOTE
• Satisfy the required inverter start conditions to start offline auto tuning. For example, stop the input of the MRS signal.
• To force tuning to end, use the MRS or RES signal or the STOP/RESET key on the operation panel. (Turning OFF the start
signal (STF signal or STR signal) also ends tuning.) 17
• During offline auto tuning, only the following I/O signals are valid (initial value).
Input terminals <effective signals>: MRS, RES, STF, STR, S1, and S2
Output terminals: RUN, FM, AM, ABC, and SO 18
• When the rotation speed and the output frequency are selected for terminals FM and AM, the progress status of offline auto
tuning is output in 15 steps from FM and AM (in the standard model).
• Do not perform ON/OFF switching of the Second function selection (RT) signal during offline auto tuning. Auto tuning will not
be performed properly. 19
• A motor with 14 or more poles cannot be tuned.
• Since the Inverter running (RUN) signal turns ON when tuning is started, pay close attention especially when a sequence which
releases a mechanical brake by the RUN signal has been designed.
• When executing offline auto tuning, input the operation command after switching ON the main circuit power (R/L1, S/L2, T/L3)
20
of the inverter.
• While Pr.79 Operation mode selection = "7", turn ON the PU operation external interlock (X12) signal for tuning in the PU
operation mode.
(1) Setting
Blinking
(3) Normal completion
• When offline auto tuning ends, press the STOP/RESET key on the operation panel during PU operation. In the External
operation, turn OFF the start signal (STF signal or STR signal). This operation resets the offline auto tuning, and the
monitor display of the operation panel returns to normal. (Without this operation, next operation cannot be started.)
• If offline auto tuning has ended in error (see the following table), motor constants are not set.
Perform an inverter reset and perform tuning again.
Error display Error cause Countermeasures
8 Forced end Set "1" in Pr.96 (Pr.463) and retry.
9 Inverter protective function operation Make the setting again.
Check for the power supply voltage fluctuation.
92 The converter output voltage fell to 75% of the rated voltage.
Check the Pr.83 Rated motor voltage setting.
Calculation error.
93 Check the motor wiring and make the setting again.
The motor is not connected.
• When tuning is ended forcibly by pressing the STOP/RESET key or turning OFF the start signal (STF or STR) during
tuning, offline tuning does not end properly. (The motor constants have not been set.)
Perform an inverter reset and perform tuning again.
NOTE
• An instantaneous power failure occurring during tuning will result in a tuning error.
After power is restored, the inverter starts normal operation. Therefore, when the STF (STR) signal is ON, the motor starts
forward (reverse) rotation.
• Any fault occurring during tuning is handled as in the normal operation. However, if the retry function is set, no retry is
performed even when a protective function that performs a retry is activated.
• The set frequency monitor displayed during the offline auto tuning is 0 Hz.
CAUTION
• Note that the motor may start running suddenly.
NOTE
• If "9999" is set in the motor constant parameters, tuning data will be invalid and the inverter internal constant is used.
16
• To change a motor induced voltage constant of PM motors, the setting in Pr.706 Induced voltage constant (phi f) or Pr.738
Second motor induced voltage constant (phi f) must be changed. If the constant after the change exceeds the setting range
of Pr.706 or Pr.738 (0 to 5000 mV (rad/s)), set Pr.1412 Motor induced voltage constant (phi f) exponent or Pr.1413 17
Second motor induced voltage constant (phi f) exponent. Set a value in the exponent n in the formula, Pr.706 (Pr.738) ×
10n [mV (rad/s)], to set the induced voltage constant (phi f).
• When Pr.71 (Pr.450) = "8093 or 9093", or Pr.1412 (Pr.1413) = "9999", the motor induced voltage constant is as set in Pr.706
(Pr.738). (No exponent setting)
18
Parameters referred to
Pr.9 Electronic thermal O/L relaypage 198
Pr.71 Applied motorpage 294
Pr.178 to Pr.189 (Input terminal function selection)page 283
If online auto tuning is selected under Advanced magnetic flux vector control or Real sensorless vector control, favorable torque
12
accuracy is retained by adjusting temperature even when the resistance value varies due to increase in the motor temperature.
Pr. Name Initial value
0
Setting range Description
No online auto tuning
13
95
Online auto tuning selection 0
C111 1 Online auto tuning is performed at startup.
574 Select online auto tuning for the second motor.
C211
Second motor online auto tuning 0 0, 1
(The settings are the same as those in Pr.95.) 14
9999 100%
717 Starting resistance tuning
9999 R1 compensation coefficient for start-time
C182 compensation coefficient 1 0% to 200%
tuning
Operating procedure
19
1. Perform offline auto tuning. (Refer to page 299.)
2. Check that Pr.96 Auto tuning setting/status = "3" (offline auto tuning completion) and values other than "9999" 20
are set in Pr.717 (Pr.741) and Pr.720 (Pr.737).
3. Set Pr.95 Online auto tuning selection = "1" (online auto tuning at start).
Online auto tuning is enabled at the next start.
4. Check that the following parameters are set before starting operation.
Pr. Description
9 Rated motor current or electronic thermal O/L relay
71 Applied motor
80 Motor capacity (with the rated motor current equal to or less than the inverter rated current)*1
81 Number of motor poles
*1 If a motor with substantially low rated current compared with the inverter rated current is used, speed and torque accuracies may deteriorate due
to torque ripples, etc. Set the rated motor current to about 40% or higher of the inverter rated current.
5. In the PU operation mode, press the RUN key on the operation panel.
In the External operation, turn ON the start command (STF signal or STR signal).
Time
Start signal
Tuning status Completed
Tune
Y39 signal
NOTE
• Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
*1 If a motor with substantially low rated current compared with the inverter rated current is used, speed and torque accuracies may deteriorate due
to torque ripples, etc. Set the rated motor current to about 40% or higher of the inverter rated current.
NOTE
• The RT signal is the Second function selection signal. The RT signal also enables other second functions. (Refer to page 283.)
To use the RT signal, set "3" in any parameter from Pr.178 to Pr.189 (Input terminal function selection) to assign the
function to an input terminal.
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.9 Electronic thermal O/L relaypage 198
12
13
14
15
16
17
18
19
20
10
319
14 (A) Application Parameters
Refer to
Purpose Parameter to set
page
To stop the motor with a mechanical P.A100 to P.A105,
Pr.278 to Pr.283, Pr.292,
brake (operation timing of mechanical Brake sequence function P.F500, P.A108, 320
Pr.639, Pr.640
brake) P.A109
To stop the motor with a mechanical
P.A200, P.A205,
brake (vibration control at stop-on- Stop-on-contact control Pr.270, Pr.275, Pr.276 324
P.A206
contact)
To strengthen or weaken the frequency
Traverse operation P.A300 to P.A305 Pr.592 to Pr.597 327
at a constant cycle
P.A601 to P.A604,
Pr.127 to Pr.134, Pr.553,
P.A607, P.A610 to
To perform process control, such as for PID control Pr.554, Pr.575 to Pr.577, 329
P.A615, P.A621 to
the pump flow volume and air volume Pr.609, Pr.610, Pr.1015
P.A625
PID display adjustment P.A630 to P.A633 C42 to C45 342
P.A601, P.A602,
P.A610, P.A611,
To control the dance roll for winding/ Pr.44, Pr.45, Pr.128 to
Dancer control P.A613 to P.A615, 344
unwinding Pr.134, Pr.609, Pr.610
P.A624, P.A625,
P.F020 to P.F021
Automatic restart after
instantaneous power failure P.A700 to P.A703, Pr.57, Pr.58, Pr.162,
351
/ flying start function for P.A710, P.F003 Pr.165, Pr.299, Pr.611
induction motors
Frequency search accuracy P.A700, P.A711,
To restart without stopping the motor at Pr.96, Pr.162, Pr.298,
improvement (V/F control, P.A712, P.C110, 358
instantaneous power failure Pr.463, Pr.560
offline auto tuning) P.C210
Automatic restart after
instantaneous power failure P.A700, P.A702,
Pr.57, Pr.162, Pr.611 356
/ flying start function for PM P.F003
motors
Power failure time
To decelerate the motor to a stop at
deceleration-to-stop P.A730 Pr.261 362
power failure
function
P.A800, P.A801, Pr.414, Pr.415, Pr.498,
To operate with sequence program PLC function P.A804, P.A805, Pr.675, Pr.1150 to 364
P.A810 to P.A859 Pr.1199
P.A900, P.A902 to
To store the operating status of the P.A906, P.A910 to Pr.1020, Pr.1022 to
Trace function 366
inverter in the RAM in the inverter P.A920, P.A930 to Pr.1047
P.A939
This function outputs operation timing signals of the mechanical brake from the inverter, such as for lift applications.
This function is useful in preventing load slippage at a start due to poor mechanical brake timing and overcurrent alarm in stop
status and enable secure operation.
Initial Setting
Pr. Name Description
value range
278 Set the frequency value calculated by adding approx. 1.0 Hz to the
Brake opening frequency 3 Hz 0 to 30 Hz
A100 rated slip frequency. This can be set only when Pr.278 ≤ Pr.282.
Set between 50% and 90% because load slippage is more likely to
279 occur when a start setting is too low.
Brake opening current 130% 0% to 400%
A101 The inverter rated current is regarded as 100%, or the rated motor
torque is regarded as 100%. (According to Pr.639 setting)
280 Brake opening current
0.3 s 0 to 2 s Generally set between 0.1 and 0.3 s.
A102 detection time
282
Turn OFF the Brake opening request (BOF) signal and set the
frequency for operating the electromagnetic brake. Generally, set the 12
Brake operation frequency 6 Hz 0 to 30 Hz
A104 value calculated by adding 3 to 4 Hz to the Pr.278 setting value. This
can be set only when Pr.282 ≥ Pr.278.
283
When Pr.292 = "7", set the value calculated by adding 0.1 s to the
mechanical delay time until the brake closes. When Pr.292 = "8", set 13
Brake operation time at stop 0.3 s 0 to 5 s
A105 the value calculated by adding to approx. 0.2 to 0.3 s to the
mechanical delay time until the brake closes.
0 Normal operation
Operation with the shortest acceleration/deceleration time. (Refer to
14
292 Automatic acceleration/ 1, 11
0 page 171.)
F500 deceleration
7 Brake sequence mode 1
8 Brake sequence mode 2 15
639 Brake opening current 0 Brake opening by output current
0
A108 selection 1 Brake opening by motor torque
0 Brake closing operation by frequency command
640
A109
Brake operation frequency
selection
0
1
Brake closing operation by the actual motor rotation speed (estimated 16
value)
Connection diagram
MC
17
Sink logic
Mechanical
Pr.184 = 15 brake
Pr.190 = 20 18
MCCB
R/L1 U
Power
supply
S/L2
T/L3 W
V Motor
19
Start signal STF 24VDC
Multi-speed signal RH *3 MC
20
*2
RUN(BOF) Brake opening request
Brake opening completion signal RL(BRI)*1 signal (BOF)
(BRI) SD SE
NOTE
• The automatic restart after instantaneous power failure function does not operate when brake sequence is selected.
• To use this function, set the acceleration/deceleration time to 1 second or higher.
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) or Pr.190 to Pr.196 (Output
terminal function selection) may affect the other functions. Set parameters after confirming the function of each terminal.
NOTE
• Under torque control, the brake sequence function is disabled.
Target frequency
Pr.13 setting
Pr.280 or 0.5Hz,
Pr.282 Pr.281 whichever is lower
Pr.278
Pr.13
Time
ON Pr.283
STF
Output current or motor torque Pr.279
(select by Pr.639)
Brake opening request ON
(BOF signal)
Brake opening completion ON
(BRI signal)
Electromagnetic brake Closed Opened Closed
operation
NOTE
• Even if the brake sequence operation has been selected, inputting the JOG signal (JOG operation) during an inverter stop
16
changes the operation method to normal operation and give a priority to the JOG operation. Note that the JOG signal input by
the brake sequence function is invalid during operation.
17
Protective function
• If one of the following faults occurs while the brake sequence function is enabled, the inverter enters a fault status, shuts
off output, and turns OFF the brake opening request signal (BOF).
18
Fault
Description
indication
When 2 seconds or more have elapsed after the start command (forward or reverse rotation) is input, but the BOF signal
19
E.MB4
does not turn ON.
E.MB5 When 2 seconds or more have elapsed after the BOF signal turned ON, but the BRI signal does not turn ON.
E.MB6
E.MB7
When the inverter had turned ON the brake opening request signal (BOF), but the BRI signal turned OFF.
When 2 seconds or more have elapsed after the BOF signal turned OFF at a stop, but the BRI signal does not turn OFF.
20
NOTE
• During deceleration, inverter output is shut OFF when the frequency reaches Pr.13 Starting frequency or 0.5 Hz, whichever
is lower. For Pr.278 Brake opening frequency, set a frequency equal to or higher than the Pr.13 setting or 0.5 Hz.
• Setting Pr.278 too high activates the stall prevention and may cause E.MB4.
• E.MB4 occurs when the time period calculated by adding Pr.280 to the acceleration time from Pr.13 to Pr.278 reaches or
exceeds 2 seconds.
Output frequency (Hz)
Less than 2s
Output
frequency
Pr.278 (Hz)
Pr.13
Pr.280
Time
ON
Brake opening request
(BOF signal)
Parameters referred to
Pr.13 Starting frequencypage 169
Pr.178 to Pr.189 (Input terminal function selection)page 283
Pr.190 to Pr.196 (Output terminal function selection)page 250
To ensure accurate positioning at the upper limit, etc. of a lift, stop-on-contact control causes the mechanical brake to close
while the motor creates a holding torque to keep the load in contact with a mechanical stopper, etc.
This function suppresses vibration that is likely to occur when the load is stopped upon contact in lift applications, thereby
ensuring reliable and highly accurate positioning stop.
<Without stop-on-contact control> <With stop-on-contact control>
Lift Lift
Setting
Pr. Name Initial value Description
range
6 Multi-speed setting (low
10 Hz 0 to 590 Hz Set the output frequency for stop-on-contact control.
D303 speed)
22
Stall prevention operation level 150% 0% to 400%
H500 Set the stall prevention operation level for stop-on-contact control.
48 Second stall prevention 0% to 400%, The smaller value set in either Pr.22 or Pr.48 has priority.
9999
H600 operation level 9999
0 Normal operation
270 Stop-on-contact control
0 1 Stop-on-contact control
A200 selection
11 Stop-on-contact control (E.OLT is invalid)
Stop-on contact excitation Set the force (holding torque) for stop-on-contact control.
275 0% to 300%
current low-speed scaling 9999 Normally, set the scaling factor between 130% to 180%.
A205
factor 9999 Not compensated.
Set a PWM carrier frequency for stop-on-contact control.
For Real sensorless vector control, the carrier frequency is always
276 PWM carrier frequency at stop- 0 to 9 2 kHz when the setting value is "0 to 5" and always 6 kHz when
9999
A206 on contact the setting value is "6 to 9". (Valid at the output frequency of 3 Hz
or less.)
9999 As set in Pr.72 PWM frequency selection.
Stop-on contact
Output frequency
NOTE 14
• By increasing the Pr.275 setting, the low-speed (stop-on-contact) torque increases, but overcurrent fault (E.OC[]) may occur
or the machine may oscillate in stop-on-contact status.
• The stop-on-contact function is different from the servo-lock function, and if used to stop or hold a load for an extended period, 15
this function can cause the motor to overheat. After a stop, immediately switch to a mechanical brake to hold the load.
• Under the following operating conditions, the stop-on-contact function is invalid:
PU operation (Pr.79), JOG operation (JOG signal), PU + External operation (Pr.79), PID control function operation (Pr.128),
Remote setting function operation (Pr.59), Automatic acceleration/deceleration operation (Pr.292), Start time tuning 16
*1 By 0 to 5 V (0 to 10 V), 4 to 20 mA input
NOTE
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.4 to Pr.6, Pr.24 to Pr.27 (multi-speed setting)page 195
Pr.15 Jog frequencypage 194
Pr.22 Stall prevention operation level, Pr.48 Second stall prevention operation level levelpage 214
Pr.22 Torque limit levelpage 100
Pr.59 Remote function selectionpage 165
Pr.72 PWM frequency selectionpage 146
Pr.79 Operation mode selectionpage 174
Pr.95 Online auto tuning selectionpage 315
Pr.128 PID action selectionpage 329
Pr.178 to Pr.189 (Input terminal function selection)page 283
Pr.292 Automatic acceleration/decelerationpage 171
The traverse operation, which oscillates the frequency at a constant cycle, is available.
Pr. Name Initial value Setting range Description
12
0 Traverse function invalid
Traverse function valid only in External operation
592
A300
Traverse function
selection
0
1
mode 13
Traverse function valid regardless of the operation
2
mode
593 Maximum amplitude
A301 amount
10% 0% to 25% Level of amplitude during traverse operation
14
Amplitude
594 Compensation amount during amplitude inversion
compensation amount 10% 0% to 50%
A302 (from acceleration to deceleration)
during deceleration
595
Amplitude
Compensation amount during amplitude inversion
15
compensation amount 10% 0% to 50%
A303 (from deceleration to acceleration)
during acceleration
596 Amplitude acceleration Time period of acceleration during traverse
A304 time
5s 0.1 to 3600 s
operation 16
597 Amplitude deceleration Time period of deceleration during traverse
5s 0.1 to 3600 s
A305 time operation
• Setting Pr.592 Traverse function selection = "1 or 2" enables the traverse function. 17
• Assigning the Traverse function selection (X37) signal to the input terminal enables the traverse function only when the
X37 signal is ON. (When the X37 signal is not assigned, the traverse function is always available.) To input the X37 signal,
set "37" in any parameter from Pr.178 to Pr.189 (Input terminal function selection) to assign the function to a terminal.
18
Output frequency(Hz) Traverse operation
f0: set frequency
f2 f1: amplitude amount from the set frequency
f1 Pr.7 (f0 × Pr.593/100)
f2: compensation amount at transition from
19
f0
acceleration to deceleration
f1 (f1 × Pr.594/100)
f3
20
f3: compensation amount at transition from
Pr.8
deceleration to acceleration
(f1 × Pr.595/100)
Pr.7 t2 t1 t1: time from acceleration during traverse
(Pr.597) (Pr.596) operation (Time from (f0 − f1) to (f0 + f1))
Time(s) (Pr.596)
STF(STR) t2: time from deceleration during traverse
ON
signal operation (Time from (f0 + f1) to (f0 − f1))
X37 signal ON (Pr.597)
• The motor accelerates to the set frequency f0 according to the normal Pr.7 Acceleration time at turn ON of the start
command (STF or STR).
• When the output frequency reaches f0 and the X37 signal turns ON, the inverter begins traverse operation and accelerates
to f0 + f1. The acceleration time at this time is according to the Pr.596 setting. (If the X37 signal turns ON before the output
frequency reaches f0, traverse operation begins after the output frequency reaches f0.)
• After the inverter accelerates the motor to f0 + f1, this is compensated with f2 (f1 × Pr.594), and the motor decelerates to
f0 - f1. The deceleration time at this time is according to the Pr.597 setting.
• After the inverter decelerates the motor to f0 - f1, this is compensated with f3 (f1 × Pr.595), and the motor accelerates again
to f0 + f1.
• When the X37 signal turns OFF during traverse operation, the inverter accelerates/decelerates the motor to f0 according
to the normal acceleration/deceleration time (Pr.7, Pr.8). If the start command (STF or STR) is turned OFF during traverse
operation, the inverter decelerates the motor to a stop according to the normal deceleration time (Pr.8).
Parameters referred to
Pr.29 Acceleration/deceleration pattern selectionpage 163
Pr.178 to Pr.189 (Input terminal function selection)page 283
Pr.190 to Pr.196 (Output terminal function selection)page 250
Process control such as flow rate, air volume or pressure are possible on the inverter.
A feedback system can be configured and PID control can be performed with the set point and feed back values set by analog 12
input signals (terminals 2 and 4) or using parameter values given via communication or by the PLC function.
Measured value
P action
Time
I action
Time
PI action
Time
PD action
PD action is a combination of proportional action (P) and differential action (D), and applies a manipulated amount according
to the speed of the deviation to improve excessive characteristics.
[Example of action when the measured value changes proportionately]
Set point
Deviation
Measured value
P action
Time
D action
Time
PD
action
Time
PID action 11
PID action is a combination of PI and PD action, which enables control that incorporates the respective strengths of these
actions.
Set point 12
Deviation
Measured value
P action
Time 13
I action
14
Time
D action
Time
y = at2 + bt + c
15
PID action
Time
(Note) PID action is the result of all P, I and D actions being added together.
16
Reverse action
When deviation X = (set point - measured value) is a plus value, the manipulated amount (output frequency) is increased, and
when the deviation is a minus value, the manipulated amount is decreased. 17
Deviation Set point
[Heating]
Set
+ X>0
Cold Increase 18
point X<0 Hot Decrease
- Measured value
Feedback signal
(measured value)
19
Forward action
When deviation X = (set point - measured value) is a minus value, the manipulated amount (output frequency) is increased,
and when the deviation is a plus value, the manipulated amount is decreased.
20
Measured value
[Cooling]
+ X>0 Set point
Set Too cold Decrease
point - X<0 Hot Increase
Feedback signal
(measured value) Deviation
0 24V
Power *1
supply
AC1φ
200/220V 50/60Hz
*1 Prepare a power supply matched to the power supply specifications of the detector.
*2 The applied output terminals differ by the settings of Pr.190 to Pr.196 (Output terminal function selection).
*3 The applied input terminals differ by the settings of Pr.178 to Pr.189 (Input terminal function selection) Assigning the PID control valid (X14)
signal to an input terminal enables PID control to be performed only when the X14 signal is turned ON.
*4 The AU signal need not be input.
Selection of deviation value, measured value and set point input method,
and PID action method (Pr.128, Pr.609, Pr.610)
• Using Pr.128, select the input method for the PID set point, measured value detected by the meter, and externally
calculated deviation. Also, select forward or reverse action.
2010
Reverse action (without
frequency reflected)
17
— — According to Pr.609
Forward action (without
2011
frequency reflected)
*1
*2
When Pr.133 ≠ "9999", the Pr.133 setting is valid.
CC-Link, CC-Link IE TSN, CC-Link IE Field Network Basic, and BACnet/IP is available. For the details of each communication, refer to the FR-
18
A8NC Instruction Manual or the Instruction Manual (Communication).
• The set point/deviation input method can also be flexibly selected by Pr.609 PID set point/deviation input selection and 19
the measured value input method can be selected by Pr.610 PID measured value input selection. Selection by Pr.609
and Pr.610 is valid when Pr.128 = "1000 to 2011".
Pr.609 to Pr.610 settings Input method 20
2 Terminal 2*3
3 Terminal 4*3
4 Communication*4
5 PLC function
*3 When the same input method has been selected for the set point and measured value at Pr.609 and Pr.610, set point input is invalid. (Inverter
runs at set point 0%)
*4 CC-Link, CC-Link IE TSN, CC-Link IE Field Network Basic, and BACnet/IP is available. For details on communication, refer to the Instruction
Manual of each option.
NOTE
• When terminals 2 and 4 are selected for deviation input, perform bias calibration using C3 and C6 to prevent a minus voltage
from being entered as the deviation input signal. Input of a minus voltage might damage devices and the inverter.
NOTE
• Always calibrate the input after changing the voltage/current input specification with Pr.73 and Pr.267, and the voltage/current
input selection switch.
*1 CC-Link, CC-Link IE TSN, and CC-Link IE Field Network Basic are available.
*2 Input value is "0" when the PLC function is disabled. PID control is disabled when bit 0 of SD1255 is "0".
*3 When Pr.133 ≠ "9999", the Pr.133 setting is used for the set point.
*4 When communication is not specified for the command source in the Network operation mode or when the speed command source is other than
communication, the set point cannot be input via communication. Instead, it can be input via an external terminal (PID control is enabled).
*5 CC-Link, CC-Link IE TSN, and CC-Link IE Field Network Basic are available.
*9 CC-Link, CC-Link IE TSN, and CC-Link IE Field Network Basic are available. 15
*10 Input value is "0" when the PLC function is disabled. PID control is disabled when bit 0 of SD1255 is "0".
*11 The deviation is input via the external terminal set in Pr.609.
Input/output signals 16
• Assigning the PID control valid signal (X14) to the input terminal by Pr.178 to Pr.189 (Input terminal function selection)
enables PID control to be performed only when the X14 signal is turned ON. When the X14 signal is OFF, regular inverter
running is performed without PID action. (When the X14 signal is not assigned, PID control is enabled only by setting 17
Pr.128 ≠ "0".)
• Input signal
Signal Function
Pr.178 to Pr.189
Description
18
setting
When this signal is assigned to the input terminal, PID control is enabled
X14 PID control valid 14
when this signal is ON.
Only the proportional term is valid when this signal is turned ON. (Integral and 19
X72 PID P control switchover 72
differential values are reset.)
• Output signal
Pr.190 to Pr.196
20
setting
Signal Function Description
Positive Negative
logic logic
FUP PID upper limit 15 115 Output when the measured value signal exceeds Pr.131 PID upper limit.
FDN PID lower limit 14 114 Output when the measured value signal falls below Pr.132 PID lower limit.
"Hi" is output when the output display of the operation panel is forward
PID forward/reverse
RL 16 116 rotation (the RUN LED is ON) and "Low" is output when the display is reverse
rotation output
rotation (the RUN LED blinks) and stop (the RUN LED is OFF).
Turns ON during PID control.
When the PID calculation result is reflected to the output frequency (Pr.128 <
During PID control "2000"), the PID signal turns OFF at turn OFF of the start signal.
PID 47 147
activated When the PID calculation result is not reflected to the output frequency
(Pr.128 ≥ "2000"), the PID signal turns ON during PID calculation regardless
of the start signal status.
Y48 48 148 Output when the absolute deviation value exceeds the limit value set in
PID deviation limit
Pr.553 PID deviation limit.
Set Pr.575 Output interruption detection time ≠ "9999". This signal turns
SLEEP PID output interruption 70 170
ON when the PID output suspension function is activated.
NOTE
• Changing the terminal functions with Pr.178 to Pr.189 and Pr.190 to Pr.196 may affect other functions. Set parameters after
confirming the function of each terminal.
Output frequency
Without PID
control PID control
Pr.127
Time
STF
PID
Operation selection and sleep function stop selection when a value error
is detected (FUP signal, FDN signal, Y48 signal, Pr.554)
• Using Pr.554 PID signal operation selection, set the action when the measured value input exceeds the upper limit
(Pr.131 PID upper limit) or lower limit (Pr.132 PID lower limit), or when the deviation input exceeds the permissible value
(Pr.553 PID deviation limit).
• Choose whether to output the signals (FUP, FDN, Y48) only or to activate the protective function to output the inverter
shutoff.
• The stop action when the inverter output is shut off by the sleep function can be selected.
Inverter operation
Pr.554 setting
At FUP/FDN signal output*1 At Y48 signal output*1 At sleep operation start
0 (initial value) Signal output only
Signal output only
1 Signal output + output shutoff (E.PID)
Coasts to stop
2 Signal output only
Signal output + output shutoff (E.PID)
3 Signal output + output shutoff (E.PID)
10 Signal output only
Signal output only
11 Signal output + output shutoff (E.PID)
Deceleration stop
12 Signal output only
Signal output + output shutoff (E.PID)
13 Signal output + output shutoff (E.PID)
*1 When each of Pr.131, Pr.132 and Pr.553 settings corresponding to each of the FUP, FDN and Y48 signals is "9999" (no function), signal output
and protective function are not available.
13
Output frequency
Pr.576 14
Less than Pr.575
Pr.575 or more SLEEP period
Time
RUN OFF
15
PID
SLEEP ON
16
When Pr.554="10 to 17", reverse operation (Pr.128="10")
Deviation
17
Pr.577 - 1000% Cancel
level
18
Output frequency
19
Deceleration stop ∗1
Pr.576
20
Less than Pr.575
Pr.575 or more SLEEP period
Time
RUN OFF
PID
SLEEP ON
*1 When the PID output shutoff release level is reached during a deceleration stop, output shutoff is released, operation is re-accelerated and PID
control is continued. During deceleration, Pr.576 Output interruption detection level is invalid.
Adjustment procedure
1. Enable PID control
When Pr.128 ≠ "0", PID control is enabled.
Set the set point, measured value and deviation input methods at Pr.128, Pr.609 and Pr.610.
3. Terminal setting
Set the I/O terminals for PID control. (Pr.178 to Pr.189 (Input terminal function selection), Pr.190 to Pr.196
(Output terminal function selection))
5. Operation
14
Make calibration. Make the following calibration∗1 when the target setting input (0 to 5 V)
and detector output (4 to 20mA) must be calibrated.
Operation When performing operation, first set the proportional band (Pr. 129) to a slightly larger value, the integral time 16
(Pr. 130) to a slightly longer time, and the differential time (Pr. 134) to "9999" (no function), and while looking
Set the proportional band (Pr. 129) at the system operation, decrease the proportional band (Pr. 129) and increase the integral time (Pr. 130).
to a slightly larger value, the integral
time (Pr. 130) to a slightly longer For slow response system where a deadband exists, differential control (Pr. 134) should be turned ON and
time, and the differential time (Pr.
134) to "9999" (no function), and turn
increased slowly.
17
ON the start signal.
Parameter adjustment
To stabilize the measured value, change
Parameter optimization
While the measured value is stable
19
the proportional band (Pr. 129) to a larger throughout the operation status, the
value, the integral time (Pr. 130) to a proportional band (Pr. 129) may be
slightly longer time, and the differential decreased, the integral time (Pr. 130)
time (Pr. 134) to a slightly shorter time. decreased, and the differential time (Pr. 134)
may be increased. 20
Adjustment end
1. 1. Apply the input (for example, 0 V) of set point setting 0% across terminals 2 and 5.
2. Using C2, enter the frequency (for example, 0 Hz) to be output by the inverter when the deviation is 0%.
4. Apply the input (for example, 5 V) of set point setting 100% across terminals 2 and 5.
5. Using Pr.125, enter the frequency (for example, 60 Hz) to be output by the inverter when the deviation is 100%.
1. Apply the input (for example, 4 mA) of measured value 0% across terminals 4 and 5.
3. Apply the input (for example, 20 mA) of measured value 100% across terminals 4 and 5.
NOTE
• Set the frequencies set at C5 and Pr.126 to each of the same values set at C2 and Pr.125.
• The display unit for analog input can be changed from "%" to "V" or "mA". (Refer to page 273.)
• The following figure shows the results of having performed the calibration above.
0 0 0
0 5 (V) 0 4 20 (mA) 0 100 Deviation (%)
*1 The upper limit of the manipulated amount is the Pr.125 setting value.
NOTE
• Even if the X14 signal is ON, PID control is stopped and multi-speed or JOG operation is performed when the multi-speed
operation (RH, RM, RL, or REX) signal or JOG signal (JOG operation) is input.
• PID control is invalid under the following settings.
Pr.79 Operation mode selection = "6" (Switchover mode)
• To use terminal 4 input in PID control, set "0" (initial value) to Pr.858 Terminal 4 function assignment. When a value other
than "0", PID control is invalid.
• Changing the terminal functions with Pr.178 to Pr.189 and Pr.190 to Pr.196 may affect other functions. Set parameters after
confirming the function of each terminal.
• When PID control is selected, the minimum frequency becomes the frequency of C2 and the maximum frequency becomes
the frequency of Pr.125.
(The Pr.1 Maximum frequency and Pr.2 Minimum frequency settings also are valid.)
• During PID operation, the remote operation function is invalid.
• When control is switched to PID control during normal operation, the frequency during that operation is not carried over, and
the value resulting from PID calculation referenced to 0 Hz becomes the command frequency.
Frequency
command
Frequency command
during normal operation
PID action ON
Normal operation PID operation Normal operation
Parameters referred to
Pr.59 Remote function selectionpage 165
12
13
14
15
16
17
18
19
20
Setting
Pr. Name Initial value Description
range
Set the coefficient of the bias side (minimum) of measured value
C42 0 to 500
PID display bias coefficient 9999 input.
A630
9999 Displayed in %.
C43 Set the converted % of the bias side (minimum) current/voltage
PID display bias analog value 20% 0% to 300%
A631 of measured value input.
Set the coefficient of the gain side (maximum) of measured value
C44 0 to 500
PID display gain coefficient 9999 input.
A632
9999 Displayed in %.
C45 Set the converted % of the gain side (maximum) current/voltage
PID display gain analog value 100% 0% to 300%
A633 of measured value input.
Gain
Bias C44
C42
0 20 100%
0 4 20mA
Frequency setting signal
0 1 5V
0 2 10V
C43 C45
NOTE
• Always calibrate the input after changing the voltage/current input specification with Pr.73 and Pr.267, and the voltage/current
input selection switch.
15
500
16
Set point 400
Deviation +40
Measured value 360
17
100
18
0
20% 100%
* ( ) indicates the deviation value (0%) (25%) (35%) (100%)
which the inverter can recognize
Deviation -10%
• The display of the following parameters is changed according to the C42 and C44 settings. 19
Pr. Name
131 PID upper limit
132
133
PID lower limit
PID action set point
20
553 PID deviation limit
577 Output interruption cancel level
Ratio
12
PID deviation
Acceleration/
Limit deceleration
Pr.128 = 42, 43 +
Dancer roll +
PID control
1
X14 + 13
setting point Kp(1+ +Td S)
- Ti S Pr.128 = 40, 41
Pr.133
16
Dancer roll position detection
*1 The main speed can be selected in all operation modes, External (analog voltage input, multi-speed), PU (digital frequency setting) and
Communication.
17
Outline of dancer control
• Dancer control is performed by setting "40 to 43" in Pr.128 PID action selection. The main speed command is the speed
command for each operation mode (External, PU, and communication). PID control is performed by the dancer roll position 18
detection signal, and the control result is added to the main speed command. For the main speed acceleration/deceleration
time, set the acceleration time to Pr.44 Second acceleration/deceleration time and the deceleration time to Pr.45
Second deceleration time. 19
Output frequency PID adding value
20
Output frequency
Main speed
Time
STF ON
NOTE
• Normally, set Pr.7 Acceleration time and Pr.8 Deceleration time to 0 s. When the Pr.7 and Pr.8 settings are large, dancer
control response becomes slow during acceleration/deceleration.
• If an automatic restart after instantaneous power failure is activated during dancer control, E.OC[] or E.OV[] is likely to occur.
In such case, disable the automatic restart after instantaneous power failure function (Pr.57 = "9999").
*1 The main speed command differs according to each operation mode (External, PU, communication).
*2 The applied output terminals differ by the settings of Pr.190 to Pr.196 (Output terminal function selection).
*3 The applied input terminals differ by the settings of Pr.178 to Pr.189 (Input terminal function selection).
*4 The AU signal need not be input.
• To enable dancer control, set "40 to 43" in Pr.128 PID action selection.
• Dancer control is enabled only when the PID control valid (X14) signal turns ON when "14" is set in one of Pr.178 to Pr.182
(Input terminal function selection) and X14 signal is assigned. When the X14 signal is not assigned, dancer control is
enabled only by the Pr.128 setting.
• Input the main speed command (External, PU, Communication). Dancer control is also supported by the main speed
command in all operation modes.
• Input the set point between the terminals 2 and 5 (the setting can be selected using Pr.133 or Pr.609) and input the
measured value signal (dancer roll position detection signal) between the inverter terminals 4 and 5 (the setting can be
selected using Pr.610).
• The action of Pr.129 PID proportional band, Pr.130 PID integral time, Pr.131 PID upper limit, Pr.132 PID lower limit
and Pr.134 PID differential time is the same as PID control action. In the relationship between the control amount (%)
and frequency in PID control, 0% is equivalent to the frequencies set in C2 and 100% is equivalent to the frequencies set
in Pr.125.
NOTE
• When Pr.128 is set to "0" or the X14 signal is OFF, regular inverter running not dancer control is performed.
• Dancer control is enabled by turning ON/OFF the bits of terminals assigned the X14 signal by RS-485 communication or over
the network.
• When dancer control is selected, set the PID output suspension function (Pr.575 Output interruption detection time =
"9999").
*1 When the same input method has been selected for the set point and measured value at Pr.609 and Pr.610, set point input is invalid. (Inverter
runs at set point 0%) 15
*2 CC-Link, CC-Link IE TSN, CC-Link IE Field Network Basic, and BACnet/IP is available. For the details of each communication, refer to the FR-
A8NC Instruction Manual or the Instruction Manual (Communication).
NOTE
• After changing the Pr.73 or Pr.267 settings, check the voltage/current input selection switch. Incorrect setting may cause a
16
fault, failure or malfunction. (Refer to page 266 for the setting.)
• When terminals 2 and 4 are selected for deviation input, perform bias calibration using C3 and C6 to prevent a minus voltage
from being entered as the deviation input signal. Input of a minus voltage might damage devices and the inverter. 17
• The following shows the relationship between the input values of the analog input terminals, and the set point and
measured value. 18
Input Relationship with analog input
Input terminal Calibration parameter
specification*3 Set point Result
0 to 5 V
0 V = 0% 0 V = 0% 19
5 V = 100% 5 V = 100%
0 V = 0% 0 V = 0%
Terminal 2 0 to 10 V Pr.125, C2 to C4
10 V = 100% 10 V = 100%
0 mA = 0% 0 mA = 0% 20
0 to 20 mA
20 mA = 100% 20 mA = 100%
0 to 1 V = 0% 0 to 1 V = 0%
0 to 5 V
5 V = 100% 5 V = 100%
0 to 2 V = 0% 0 to 2 V = 0%
Terminal 4 0 to 10 V Pr.126, C5 to C7
10 V = 100% 10 V = 100%
0 to 4 mA = 0% 0 to 4 mA = 0%
0 to 20 mA
20 mA = 100% 20 mA = 100%
*3 Can be changed by Pr.73 and Pr.267 and the voltage/current input switch. (Refer to page 266.)
Gain
Bias Pr.125
C2
Input/output signals
• The following signals can be used by assigning functions to Pr.178 to Pr.189 (Input terminal function selection) and
Pr.190 to Pr.196 (Output terminal function selection).
• Input signal
Pr.178 to Pr.189
Signal Function Description
setting
When this signal is assigned to the input terminal, PID control is enabled when this
X14 PID control valid 14
signal is ON.
PID forward/reverse PID control is switched between forward and reverse action without changing
X64 64
action switchover parameters by turning ON this signal.
PID P control Only proportional term is valid when this signal is turned ON. (Integral and
X72 72
switchover differential values are reset.)
• Output signal
Pr.190 to Pr.196
setting
Signal Function Description
Positive Negative
logic logic
FUP PID upper limit 15 115 Output when the measured value signal exceeds Pr.131 PID upper limit.
FDN Lower limit output 14 114 Output when the measured value signal falls below Pr.132 PID lower limit.
"Hi" is output when the output display of the operation panel is forward rotation (the
PID forward/reverse
RL 16 116 RUN LED is ON) and "Low" is output when the display is reverse rotation (the RUN
rotation output
LED blinks) and stop (the RUN LED is OFF).
During PID control
PID 47 147 Turns ON during PID control.
activated
NOTE
• Changing the terminal functions with Pr.178 to Pr.189 and Pr.190 to Pr.196 may affect other functions. Set parameters after
confirming the function of each terminal.
NOTE
• Refer to page 338 for details on other PID control monitors.
15
20mA 5V(10V) Upper limit
position
16
4mA 0V
0% 100% Lower limit Potentiometer, etc.
17
Feedback value position
1. Switch the voltage/current input selection switch (switch 4) to "V", set "2" in Pr.267, and set terminal 4 input to
18
voltage input.
2. Input 0 V across terminals 4 and 5, and calibrate C6. (The % display that is indicated at analog calibration is not 19
related to the % of the feedback value.)
3. Input 7 V across terminals 4 and 5, and calibrate C7. (The % display that is indicated at analog calibration is not
related to the % of the feedback value.) 20
4. Set Pr.133 to "50%".
NOTE
• After changing the Pr.267 setting, check the voltage/current selection switch. Incorrect setting may cause a fault, failure or
malfunction. (Refer to page 266 for the setting.)
• If the Multi-speed operation (RH, RM, RL, or REX) signal, or JOG signal is input during regular PID control, PID control is
interrupted. However, at dancer control, these signals are treated as main speed commands, so PID control is continued.
• During dancer control, Pr.44 and Pr.45 (Second acceleration/deceleration time) is the parameter for setting the acceleration/
deceleration time for the main speed command. This function does not work as a second function.
• When the switchover mode is set by setting "6" to Pr.79, dancer control (PID control) is invalid.
• The acceleration/deceleration action of the main speed command is the same as that when the frequency is increased or
decrease by analog input. The SU signal sometimes stays ON even if operation is turned ON/OFF by the start signal. The set
frequency monitor is the value "main speed command + PID control" which is constantly changing.
• With the main speed setting frequency setting, acceleration/deceleration is performed for the acceleration/deceleration time
set in Pr.44 and Pr.45, and with the output frequency setting, acceleration/deceleration is performed for the acceleration/
deceleration time set in Pr.7 and Pr.8. For this reason, with the output frequency, when the time set in Pr.7 and Pr.8 is longer
than the time set in Pr.44 and Pr.45, acceleration/deceleration is performed for the acceleration/deceleration time set in Pr.7
and Pr.8.
• The limit of the integral term is the smaller of 100% and the value after conversion of the straight line after interpolation of Pr.1
Maximum frequency by C2 and Pr.125 to the PID manipulated amount.
However, note that the lower limit frequency limits the output frequency, but does not restrict the action of the integral item.
Parameters referred to
Pr.57 Restart coasting timepage 351
Pr.59 Remote function selectionpage 165
Pr. Name
Initial
value
Setting
range
Description 14
0 Frequency search only performed at the first start
Automatic restart after
162 1 Reduced voltage start only at the first start (no frequency search)
A700
instantaneous power
failure selection
0
10 Frequency search at every start 15
11 Reduced voltage start at every start (no frequency search)
0 Rotation direction detection disabled
1 Rotation direction detection enabled
299
Rotation direction
detection selection at 0 When Pr.78 Reverse rotation prevention selection = "0", with rotation
16
A701 direction detection
restarting 9999
When Pr.78 Reverse rotation prevention selection = "1 or 2", without
rotation direction detection
0 Coasting time differs according to the inverter capacity.*1
17
57 Set the time delay for the inverter to perform a restart after restoring power
Restart coasting time 9999 0.1 to 30 s
A702 due to an instantaneous power failure.
9999 No restart 18
58
Restart cushion time 1s 0 to 60 s Set the voltage cushion time for restart.
A703
165 Stall prevention operation Set the stall prevention level at restart operation on the assumption that the
A710 level for restart
150% 0% to 400%
inverter rated current is 100%. 19
Set the acceleration time to reach Pr.20 Acceleration/deceleration
0 to 3600 s
611 Acceleration time at a reference frequency at restart.
9999
F003 restart Standard acceleration time (for example, Pr.7) is applied as the acceleration
9999
time at restart. 20
*1 The coasting time when Pr.57 = "0" is as shown below. (When Pr.162 and Pr.570 are set to the initial value.)
0.5 s for the FR-E860-0027(1.5K) or lower.
1 s for the FR-E820-0080(1.5K) or lower, FR-E840-0040(1.5K) or lower, and FR-E860-0040(2.2K) to FR-E860-0120(7.5K)
2 s for the FR-E820-0110(2.2K) to FR-E820-0330(7.5K) and FR-E840-0060(2.2K) to FR-E840-0170(7.5K)
• To operate the inverter with the automatic restart after instantaneous power failure function enabled, check the following
points.
• Set Pr.57 Restart coasting time = "0".
V/F control, Advanced magnetic flux vector control Real sensorless vector control
Instantaneous (power failure) time Instantaneous (power failure) time
Power supply
Power supply
(R/L1, S/L2,
(R/L1, S/L2,
T/L3)
T/L3)
Motor speed N Motor speed N
(r/min)
(r/min)
Inverter output * Inverter output
frequency f(Hz) frequency f(Hz)
output voltage *
Inverter output
voltage E(V) E(V)
Speed
Restart cushion Coasting + detection Acceleration time
Speed time (Pr.57) time
Coasting time (Pr.58 setting) at a restart
+ detection (Pr.611 setting)
time (Pr.57) time
* The output shut off timing differs
* The output shut off timing differs Acceleration time according to the load condition.
according to the load condition. at a restart
(Pr.611 setting)
NOTE
• The rotation speed detection time (frequency search) changes according to the rotation speed of the motor (maximum 1
second).
• When the inverter capacity is two ranks or greater than the motor capacity, the overcurrent protective function (E.OC[]) is
sometimes activated and prevents the inverter from restarting.
• If two or more motors are connected to one inverter, this function operates abnormally. (The inverter does not restart
successfully.)
• Because a DC injection brake is applied instantaneously at speed detection during a restart, the speed might drop if the
moment of inertia (J) of the load is small.
• If reverse operation is detected when "1" (reverse rotation disabled) is set to Pr.78, operation decelerates by reverse rotation
and then changes to forward rotation when the start command is forward rotation. The inverter does not restart when the start
command is reverse rotation.
15
Coasting time
Pr.57 setting Restart cushion time
(Pr.58 setting)
* The output shut off timing differs according to the load condition. 16
NOTE
• This restart method uses the output frequency that was active before the instantaneous power failure stored in memory. If the
instantaneous power failure time is 0.2 second or more, the output frequency can no longer be stored and held in memory, so 17
the restart is performed from Pr.13 Starting frequency (initial value: 0.5 Hz).
• During Real sensorless vector control, the operation is the same as one when Pr.162 = "0 or 10".
18
Restart at every start (Pr.162 = "10 or 11")
• When "10 or 11" is set in Pr.162, a restart operation is performed at each start and automatic restart after instantaneous
power failure (after the time period set in Pr.57 elapsed). When "0 (initial value) or 1" is set in Pr.162, a restart operation 19
is performed at the first start after a power-ON, and from the second power-ON onwards, a start from the starting frequency
is performed.
20
Automatic restart operation of the MRS (X10) signal
• The restart operation after restoration from output shutoff by the MRS (X10) signal is as shown in the following table
according to the Pr.30 setting.
Pr.30 setting Operation after restoration from output shutoff by the MRS (X10) signal
2 Restart operation (starting from the coasting speed)
Other than the above Starting from Pr.13 Starting frequency.
NOTE
• When output is shut off using safety stop function (terminals S1 and S2), the inverter restarts in the same way as when output
is shut off by the MRS (X10) signal.
• Operation is selectable as shown in the table above when Pr.162 Automatic restart after instantaneous power failure
selection = "0 or 1". When Pr.162 Automatic restart after instantaneous power failure selection = "10 or 11" (automatic
restart operation at each start), a restart operation is performed regardless of the setting of Pr.30 Regenerative function
selection.
• Set "24" in any parameter from Pr.178 to Pr.189 (Input terminal function selection) to assign the output stop (MRS) signal
to the input terminal, and "10" to assign the Inverter operation enable (X10) signal.
Voltage Inverter
Coasting time (s)
class ND LD
FR-E820-0080(1.5K) or lower FR-E820-0050(0.75K) or lower 1
200 V
FR-E820-0110(2.2K) or higher FR-E820-0080(1.5K) or higher 2
FR-E840-0040(1.5K) or lower FR-E840-0026(0.75K) or lower 1
400 V
FR-E840-0060(2.2K) or higher FR-E840-0040(1.5K) or higher 2
FR-E860-0027(1.5K) or lower FR-E860-0017(0.75K) 0.5
575 V
FR-E860-0040(2.2K) or higher FR-E860-0027(1.5K) or higher 1
• Inverter operation is sometimes hindered by the size of the moment of inertia (J) of the load, output frequency, or the
residual magnetic flux in the motor. Adjust this coasting time within the range 0.1 to 30 seconds to match the load
specification.
NOTE
• Pr.58 is invalid under Real sensorless vector control.
NOTE
• Pr.165 is invalid under Real sensorless vector control.
• Changing the Pr.21 setting does not affect the Pr.611 setting increment.
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
• The SU and FU signals are not output during the restart. These signals are output after the restart cushion time passes.
• Restart operation is also performed after the inverter reset is released or after the retry by the retry function occurs.
CAUTION
• When the automatic restart after instantaneous power failure function is selected, the motor suddenly starts
(after reset time passes) when an instantaneous power failure occurs. Stay away from the motor and machinery.
When the automatic restart after instantaneous power failure function has been selected, apply the CAUTION
sticker(s), which are found in the Inverter Safety Guideline enclosed with the inverter, to easily visible places.
Parameters referred to
Pr.7 Acceleration time, Pr.21 Acceleration/deceleration time incrementspage 158
Pr.13 Starting frequencypage 169, page 170
Pr.65, Pr.67 to Pr.69 Retry functionpage 208
12
13
14
15
16
17
18
19
20
Power supply
(R/L1,S/L2,T/L3)
Motor
speed N (r/min)
Inverter output *
frequency f (Hz)
Inverter output
voltage E (V)
Speed
Coasting + detection
time (Pr.57) time
Acceleration time
at a restart
* The output shut off timing differs (Pr.611 setting)
according to the load condition
NOTE
• Because a DC injection brake is applied instantaneously at speed detection during a restart, the speed might drop if the
moment of inertia (J) of the load is small.
• Restart operation with reduced voltage is not available for PM sensorless vector control.
• A protective function may be activated for some motor models or at certain running speeds, disabling restarting.
16
CAUTION
• A PM motor is a motor with interior permanent magnets. High voltage is generated at motor terminals while the motor is
running.
17
Do not touch motor terminals and other parts until the motor stops to prevent an electric shock.
• When the automatic restart after instantaneous power failure function is selected, the motor suddenly starts (after reset
time passes) when an instantaneous power failure occurs.
18
Stay away from the motor and machinery.
When the automatic restart after instantaneous power failure function has been selected, apply the CAUTION sticker(s),
which are found in the Inverter Safety Guideline enclosed with the inverter, to easily visible places.
19
Parameters referred to
Pr.13 Starting frequencypage 169, page 170
Pr.65, Pr.67 to Pr.69 Retry functionpage 208
Pr.78 Reverse rotation prevention selectionpage 193
20
Pr.882 Regeneration avoidance operation selectionpage 390
Under V/F control, the accuracy of the "frequency search", which is used to detect the motor speed for the automatic restart
after instantaneous power failure and flying start, can be improved.
Initial
Pr. Name Setting range Description
value
0 Frequency search only performed at the first start
Automatic restart after 1 Reduced voltage start only at the first start (no frequency search)
162
instantaneous power 0
A700 10 Frequency search at every start
failure selection
11 Reduced voltage start at every start (no frequency search)
The offline auto tuning automatically sets the gain required for the
0 to 32767
298 frequency search.
Frequency search gain 9999
A711 The constant value of Mitsubishi Electric motor (SF-PR, SF-JR, SF-
9999
HR, SF-JRCA, SF-HRCA and so on) is used.
The offline auto tuning automatically sets the gain required for the
0 to 32767
560 Second frequency frequency search of the second motor.
9999
A712 search gain The constant value of Mitsubishi Electric motor (SF-PR, SF-JR, SF-
9999
HR, SF-JRCA, SF-HRCA and so on) is used for the second motor.
0 No offline auto tuning
Offline auto tuning is performed under Advanced magnetic flux vector
96 Auto tuning setting/ 1 control, Real sensorless vector control, or PM sensorless vector
0
C110 status control. (Refer to page 299 and page 308.)
Offline auto tuning is performed without the motor rotating (under V/
11
F control).
Tuning data (The value measured by offline auto tuning is
90 automatically set.)
Motor constant (R1) 9999 0 to 50 Ω, 9999
C120 9999: The constant value of Mitsubishi Electric motor (SF-PR, SF-JR,
SF-HR, SF-JRCA, SF-HRCA and so on) is used.
0 No auto tuning for the second motor.
Offline auto tuning is performed for the second motor. (Refer to page
463 Second motor auto 1
0 299 and page 308.)
C210 tuning setting/status
Offline auto tuning is performed without the second motor rotating
11
(under V/F control).
458 Second motor
9999 0 to 50 Ω, 9999 Tuning data of the second motor (same as Pr.90)
C220 constant (R1)
Performing tuning 17
• Before performing tuning, check the monitor display of the operation panel if the inverter is in the state ready for tuning. The 18
motor starts by turning ON the start command while tuning is unavailable.
• In the PU operation mode, press the RUN key on the operation panel. 19
In the External operation, turn ON the start command (STF signal or STR signal). Tuning starts. (At this time, excitation
noise occurs.)
NOTE 20
• It takes about 10 seconds for tuning to complete. (The time depends on the inverter capacity and motor type.)
• Satisfy the required inverter start conditions to start offline auto tuning. For example, stop the input of the MRS signal.
• To force tuning to end, use the MRS or RES signal or the STOP/RESET key on the operation panel.
(Turning OFF the start signal (STF signal or STR signal) also ends tuning.)
• During offline auto tuning, only the following I/O signals are valid (initial value).
Input terminals <effective signals>: MRS, RES, STF, STR, S1, and S2
Output terminals: RUN, FM, AM, ABC, and SO
• When the rotation speed and the output frequency are selected for terminals FM and AM, the progress status of offline auto
tuning is output in 15 steps from FM and AM.
• Do not perform ON/OFF switching of the Second function selection (RT) signal during offline auto tuning. Auto tuning will not
be performed properly.
• Since the RUN signal turns ON when tuning is started, pay close attention especially when a sequence which releases a
mechanical brake by the RUN signal has been designed.
• When executing offline auto tuning, input the operation command after switching ON the main circuit power (R/L1, S/L2, T/L3)
of the inverter.
• While Pr.79 Operation mode selection = "7", turn the PU operation external interlock (X12) signal ON to tune in the PU
operation mode.
Setting
Tuning in progress
Blinking
Normal end
• When offline auto tuning ends, press the STOP/RESET key on the operation panel during PU operation. For External
operation, turn OFF the start signal (STF signal or STR signal). This operation resets the offline auto tuning, and the
monitor display of the operation panel returns to normal. (Without this operation, next operation cannot be started.)
• At tuning completion, the tuning results are set in the following parameters:
Parameter Name
90 Motor constant (R1)
298 Frequency search gain
96 Auto tuning setting/status
NOTE
• The motor constants measured once during offline auto tuning are stored as parameters and their data are held until offline
auto tuning is performed again. However, the tuning data is cleared when performing All parameter clear.
• If offline auto tuning has ended in error, motor constants are not set.
Perform an inverter reset and restart tuning.
Error display Error cause Countermeasures
8 Forced end Set "11" in Pr.96 and retry.
9 Inverter protective function operation Make the setting again.
Set the acceleration/deceleration time longer.
91 The current limit (stall prevention) function is activated.
Set Pr.156 Stall prevention operation selection = "1".
92 The converter output voltage fell to 75% of the rated voltage. Check for the power supply voltage fluctuation.
Calculation error.
93 Check the motor wiring and make the setting again.
The motor is not connected.
• When tuning is ended forcibly by pressing the STOP/RESET key or turning OFF the start signal (STF or STR) during
tuning, offline tuning does not end properly. (The motor constants have not been set.)
Perform an inverter reset and restart tuning.
• If the rated power supply of the motor is 200/220 V (400/440 V) 60 Hz, set the rated motor current multiplied by 1.1 in Pr.9
Electronic thermal O/L relay after tuning is complete.
• For a motor with a thermal protector or other thermal detection, set "0" (motor overheat protection by inverter invalid) in
Pr.9 to protect the motor from overheating.
NOTE
• An instantaneous power failure occurring during tuning will result in a tuning error. After power is restored, the inverter starts
normal operation. Therefore, when the STF (STR) signal is ON, the motor starts forward (reverse) rotation.
• Any fault occurring during tuning is handled as in the normal operation. However, if the retry function is set, no retry is
performed.
• The set frequency monitor displayed during the offline auto tuning is 0 Hz.
14
Parameters referred to
Pr.9 Electronic thermal O/L relaypage 198
Pr.65, Pr.67 to Pr.69 Retry functionpage 208
Pr.71 Applied motor, Pr.450 Second applied motorpage 294
Pr.79 Operation mode selectionpage 174 15
Pr.156 Stall prevention operation selectionpage 214
Pr.178 to Pr.189 (Input terminal function selection)page 283
16
17
18
19
20
Pr.261=1
Power
supply
During deceleration at
Output frequency
Time
STF
Y46
NOTE
• If the automatic restart after instantaneous power failure is selected (Pr.57 Restart coasting time ≠ "9999") while the power
failure time deceleration stop function is set enabled (Pr.261 = "1"), the power failure time deceleration stop function is
disabled.
• When the power failure time deceleration stop function is enabled (Pr.261 = "1"), the inverter does not start even if the power
is turned ON or inverter reset is performed with the start signal (STF/STR) ON. Turn OFF the start signal once and then ON
again to make a start.
Power supply ON
Not started as inverter Output
is stopped due to power frequency
failure
Time
STF OFF ON
Y46 ON
NOTE
• The power failure time deceleration stop function is disabled during a stop or when the breaker is tripped.
19
• When the load is high during PM sensorless vector control, an undervoltage sometimes causes the coasting stop.
• Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal. 20
CAUTION
• Even if the power failure time deceleration-to-stop function is set, some loads might cause the inverter to trip and the
motor to coast.
The motor coasts if sufficient regenerative power is not obtained from the motor.
Parameters referred to
Pr.57 Restart coasting timepage 351, page 356
Pr.190 to Pr.196 (Output terminal function selection)page 250
Initial Setting
Pr. Name Description
value range
0 PLC function disabled
The conditions to enable the SQ signal
414 PLC function operation 1, 11
0 depends on the Pr.338 setting.
A800 selection PLC function enabled
The SQ signal is enabled by input from an
2, 12
external input terminal.
The inverter start command is enabled regardless of the operating status of
0
415 Inverter operation lock the sequence program.
0
A801 mode setting The inverter start command is enabled only while the sequence program is
1
running.
0: Clears the flash memory fault display (no operation after
writing while the flash memory is in normal operation).
9696: Clears the flash memory (no operation after writing Write
while the flash memory is at a fault).
498 PLC function flash 0, 9696 (0 to Other than 0 and 9696: Outside the setting range
0
A804 memory clear 9999) 0: Normal display
1: The flash memory is not cleared because the PLC
function is enabled. Read
9696: During flash memory clearing operation or flash
memory fault
User parameter auto 1 Auto storage function enabled
675
storage function 9999
A805 9999 Auto storage function disabled
selection
Desired values can be set.
1150 to
Because devices D206 to D255 used by the PLC function can be mutually
1199 User parameters 1 to
0 0 to 65535 accessed, the values set to Pr.1150 to Pr.1199 can be used by the
A810 to User parameters 50
sequence program. The result of performing calculation by a sequence
A859
program can also be monitored by Pr.1150 to Pr.1199.
NOTE
• The auto storage function may fail if the EEPROM is accessed by other functions at the same time at power OFF. To ensure 16
the auto storage, provide a power source for the control circuit separately from that of the main circuit.
0
0, 1, 2 EEPROM
EEPROM 19
Inverter (via communication), 11, 12 RAM
FR Configurator2 0, 1, 2 RAM
1 RAM
11, 12
0, 1, 2
RAM
(Differs according to the option type.)
20
0 EEPROM
11, 12 RAM
Communication option
0, 1, 2 RAM
1 RAM
11, 12 RAM
0, 1, 2 EEPROM
0 EEPROM
11, 12 RAM
Operation panel
0, 1, 2 EEPROM
1 RAM
11, 12 RAM
NOTE
• For the details of the PLC function, refer to the PLC Function Programming Manual and the Instruction Manual of FR
Configurator2.
Sampling data
0% 90% 100%
Sampling data
0% 90% 100%
Tracing procedure
1. Prior setting for tracing
Set Pr.1022 Sampling cycle and Pr.1023 Number of analog channels according to the necessary sampling time.
Use Pr.1027 to Pr.1034 to set analog sources, and Pr.1038 to Pr.1045 to set digital sources.
Set a trigger type in Pr.1025.
3. Waveform check
By using FR Configurator2, trace data stored in the internal RAM can be displayed on a computer screen. For
details, refer to the Instruction Manual of FR Configurator2.
*4 ND rated
9 Regenerative brake duty 202 *U-phase output current ○
current
Electronic thermal O/L relay load *4 ND rated
10 203 *V-phase output current ○
factor current
*4 ND rated
11 Output current peak value 204 *W-phase output current ○
current
Converter output voltage peak *4 400/800/
12 205 Converter output voltage
value 1000 V
*4 ND rated
14 Output power 206 *Output current (all three phases)
current
*4 ND rated
17 Load meter 207 *Excitation current (A)
current
*4 ND rated
18 Motor excitation current 208 *Torque current (A)
current
20 Cumulative energization time 65535 209 Terminal 2 100%
23 Actual operation time 65535 210 Terminal 4 100%
24 Motor load factor *4 212 *Excitation current (%) ○ 100%
32 Torque command *4 213 *Torque current (%) ○ 100%
33 Torque current command *4 230 *Output frequency (signed) ○ Pr.84
40 PLC function user monitor 1 ○ *4 231 *Motor speed (with sign) ○ *5
*1 In Pr.1037, set the number obtained by adding 1,000 to the trigger level.
NOTE
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
Sampling retry
• If any error is found in the trace data, the sampling stops and then restarts (sampling retry).
• If another error is found within a minute from when an error is found, the sampling stops (sampling retry count excess).
• The sampling retry status can be checked by monitoring the trace status.
1000s place
Indicates internal RAM state.
1s place
Indicates trace operation.
13
100s place 10s place
Indicates sampling retry state. Indicates trigger state.
Monitor value
Trace status 14
Fourth digit Third digit Second digit First digit
Sampling retry not
0 or no display*1 No trace data in internal RAM
performed
Trigger not detected Tracing stopped
1 Trace data in internal RAM Sampling retry performed Trigger detected Trace operation
15
2 — Sampling retry count excess — —
*1 The value(s) "0" to the left of the leftmost non-zero value is(are) not shown in the monitor display. For example, if no trace data is in internal RAM,
sampling retry is not performed, no trigger is detected, and trace operation is performed, "1" appears. (not "0001") 16
• During trace operation, the Trace status (Y40) signal can be output.
To use the Y40 signal, set "40" (positive logic) or "140" (negative logic) in one of Pr.190 to Pr.196 (Output terminal 17
function selection) to assign function to an output terminal.
NOTE
• Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other
18
functions. Set parameters after confirming the function of each terminal.
19
Parameters referred to
Pr.52 Operation panel main monitor selectionpage 228
Pr.178 to Pr.189 (Input terminal function selection)page 266
Pr.190 to Pr.196 (Output terminal function selection)page 250
20
10
373
15 (G) Control Parameters
Refer to
Purpose Parameter to set
page
To set the starting torque manually Manual torque boost P.G000, P.G010 Pr.0, Pr.46 374
Base frequency, base frequency P.G001, P.G002,
To set the motor constant Pr.3, Pr.19, Pr.47 376
voltage P.G011
To select the V/F pattern matching the
Load pattern selection P.G003 Pr.14 378
application
To perform energy saving operation Energy saving operation P.G030 Pr.60 380
To compensate the motor slip amount when
SF-PR slip amount adjustment
replacing an SF-JR motor with an SF-PR P.G060, P.G061 Pr.673, Pr.674 381
mode
motor
DC injection brake, zero speed P.G100, P.G101, Pr.10 to Pr.12,
To adjust the motor braking torque 382
control P.G103, P.G110 Pr.850
To coast the motor to a stop Selection of motor stop method P.G106 Pr.250 384
To use the regeneration unit to increase the P.E300, P.G107,
Regenerative brake selection Pr.17, Pr.30, Pr.70 386
motor braking torque P.T720
To avoid overvoltage fault due to Pr.882, Pr.883,
P.G120, P.G121,
regenerative driving by automatic Regeneration avoidance function Pr.885, Pr.886, 390
P.G123 to P.G125
adjustment of output frequency Pr.665
To select the control method Control method selection P.G200, P.G300 Pr.800, Pr.451 86
To secure the low-speed torque by
Slip compensation P.G203 to P.G205 Pr.245 to Pr.247 393
compensating the slip of the motor
Constant output range torque
To select the torque characteristic P.G210 Pr.803 100, 117
characteristic selection
P.G211, P.G212, Pr.820, Pr.821,
To adjust the speed control gain Speed control gain 107
P.G311, P.G312 Pr.830, Pr.831
P.G213, P.G214, Pr.824, P.825,
To adjust the torque control gain Torque control gain 122
P.G313, P.G314 Pr.834, P.835
To perform frequency control appropriate for
Droop control P.G400, P.G401 Pr.286, Pr.287 394
load torque
To suppress the machine resonance Speed smoothing control P.G410, P.G411 Pr.653, Pr.654 395
To adjust the speed gain for Advanced
Speed control gain P.G932, P.G942 Pr.89, Pr.569 90
magnetic flux vector control
Voltage drop in the low-frequency range can be compensated, improving reduction of the motor torque in the low-speed range.
• Motor torque in the low-frequency range can be adjusted according to the load, increasing the motor torque at the start up.
• By using the RT signal, it is possible to switch between 2 types of torque boost.
46 0% to 30% Set the torque boost value at when the RT signal is ON.
Second torque boost 9999
G010 9999 Without the second torque boost
Output
16
voltage
Pr.0
Pr.46
Setting
range
17
0 Output Base
frequency frequency
(Hz)
18
Setting multiple torque boosts (RT signal, Pr.46)
• When changing the torque boost depending on the application or when using single inverter switching between multiple
motors, use the second torque boost. 19
• Pr.46 Second torque boost is enabled when the RT signal is ON. To input the RT signal, set "3" in any parameter from
Pr.178 to Pr.189 (Input terminal function selection) to assign the function.
NOTE
20
• The RT signal is the Second function selection signal which also enables other second functions. (Refer to page 289.)
• Set a larger value when the distance between the inverter and the motor is long or when there is not enough motor torque in
the low-speed range. It may cause overcurrent trip when it is set too large.
• Setting for Pr.0 and Pr.46 becomes enabled only when the V/F control is selected.
• When the initial value is set in Pr.0, the Pr.0 setting is automatically changed by changing the Pr.71 Applied motor or Pr.81
Number of motor poles setting. (Refer to page 294.)
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.3 Base frequency, Pr.19 Base frequency voltagepage 376
Pr.71 Applied motorpage 294
Pr.178 to Pr.189 (Input terminal function selection)page 283
Use this function to adjust the inverter outputs (voltage, frequency) to match with the motor rating.
Initial value*1
Pr. Name Setting range Description
Gr.1 Gr.2
3
Base frequency 60 Hz 50 Hz 0 to 590 Hz Set the frequency at the rated motor torque. (50/60 Hz)
G001
0 to 1000 V Set the base voltage.
19
Base frequency voltage 9999 8888 8888 95% of the power supply voltage
G002
9999 Same as the power supply voltage
47 0 to 590 Hz Set the base frequency when the RT signal is ON.
Second V/F (base frequency) 9999
G011 9999 Second V/F disabled
*1 Gr.1 and Gr.2 are the parameter initial value groups. (Refer to page 82).
Pr.19
Output frequency
(Hz)
Pr.3
Pr.47
NOTE
• The RT signal is the Second function selection signal which also enables other second functions. (Refer to page 289.)
13
Parameters referred to
Pr.14 Load pattern selectionpage 378
Pr.29 Acceleration/deceleration pattern selectionpage 163
Pr.83 Rated motor voltage, Pr.84 Rated motor frequencypage 378
Pr.178 to Pr.189 (Input terminal function selection)page 283 14
15
16
17
18
19
20
Optimal output characteristics (V/F characteristics) for application or load characteristics can be selected.
Setting
Pr. Name Initial value Description
range
0 For constant-torque load
14 1 For variable-torque load
Load pattern selection 0
G003 2 For constant-torque lift (boost at reverse rotation: 0%)
3 For constant-torque lift (boost at forward rotation: 0%)
Pr.14 = 0
100%
Output voltage
Select for constant-torque load (setting value "0") even for fan and pump in the following cases.
• When accelerating a blower with large moment of inertia (J) in a short period of time.
• When it is a constant-torque load such as rotary pump or gear pump.
• When the load torque increases in low speed such as screw pump.
Pr.14 = 1
100%
Output voltage
voltage
Output
Output
rotation rotation
Reverse Forward
Pr.0 rotation Pr.0 rotation 14
Base frequency Base frequency
Output frequency (Hz) Output frequency (Hz)
NOTE 15
• When torque is continuously regenerated as vertical lift load, it is effective to set the rated voltage in Pr.19 Base frequency
voltage to prevent trip due to current at regeneration.
16
Parameters referred to
Pr.0 Torque boostpage 374
Pr.178 to Pr.189 (Input terminal function selection)page 283
17
18
19
20
The inverter will automatically perform energy saving operation without setting detailed parameters.
This control method is suitable for applications such as fans and pumps.
NOTE
• In the Optimum excitation control mode, an energy saving effect is not expected when the motor capacity is extremely small
compared with the inverter capacity or when multiple motors are connected to a single inverter.
• When the Optimum excitation control mode is selected, the deceleration time may become longer than the setting value. Also,
it may cause overvoltage more often compared to constant-torque load characteristics, so set the deceleration time longer.
• When the motor becomes unstable during the acceleration, set the acceleration time longer.
• Output current may increase slightly with the energy saving operation mode or the Optimum excitation control mode since the
output voltage is controlled.
V/F
• As compared to our conventional SF-JR motor, the slip amount is small for the high-performance energy-saving SF-PR
12
motor. When replacing the SF-JR to the SF-PR, the slip amount is reduced and the rotations per minute increases.
Therefore, when the SF-PR is used with the same frequency setting as that of the SF-JR, power consumption may
increase as compared to the SF-JR.
13
• By setting the slip amount adjustment mode, the frequency command can be adjusted to keep the rotations per minute of
the SF-PR equivalent to those of the SF-JR for power consumption reduction.
14
Pr. Name Initial value Setting range Description
673 SF-PR slip amount adjustment 2, 4, 6 Set the number of SF-PR motor poles.
9999
G060*1 operation selection 9999 The slip amount adjustment is disabled. 15
674 SF-PR slip amount adjustment
100% 0% to 500% Setting is available for fine adjustment of the slip amount.
G061*1 gain
*1 The setting is available only for the 200/400 V class.
• By setting the number of SF-PR motor poles in Pr.673 SF-PR slip amount adjustment operation selection, the SF-PR 16
slip amount adjustment mode is activated.
• The SF-PR slip amount adjustment mode is available only under V/F control.
• Use Pr.674 SF-PR slip amount adjustment gain to fine-tune the rotations per minute. To reduce the rotations per minute 17
(to increase the compensation frequency), set a larger value in Pr.674. To increase the rotations per minute (to reduce the
compensation frequency), set a smaller value in Pr.674. (Lower rotations per minute reduce the power consumption, and
higher rotations per minute increase the power consumption.) 18
NOTE
• The slip amount adjustment is not available in the following conditions.
During acceleration/deceleration, during DC injection brake operation, during PID control, during stall prevention operation,
19
during regeneration avoidance operation, during traverse operation, and while the slip compensation is valid (Pr.245).
• The slip amount adjustment is not available when the applicable motor capacity of the inverter is not compatible with the SF-
PR. (For the details of the applicable motor capacity, refer to the Instruction Manual (Connection).) 20
Pr. 10 Operation
frequency
Time
DC injection Pr.12
brake Operation
voltage voltage
Time
3.7 kW or lower
Motor capacity
4%
Pr.12 setting
16
5.5 kW or higher 3%
• Even if the setting value of Pr.12 is made larger, braking torque will be limited so the output current will be within the rated
current of the inverter.
17
NOTE
• When restarting the operation after a brake operation under Real sensorless vector control, set Pr.850 = "1" (zero speed
control). Setting "0" (DC injection brake) may cause a delay of about 2 seconds from the time the start up command is input
until it actually is output.
CAUTION
• Install a mechanical brake to make an emergency stop or to stay stopped for a long time.
Parameters referred to
Pr.13 Starting frequencypage 169, page 170
Pr.71 Applied motorpage 294
Pr.80 Motor capacitypage 299
Pr.178 to Pr.189 (Input terminal function selection)page 283
Initial Description
Pr. Name Setting range
value Start signal (STF/STR)*1 Stop operation
The motor coasts to a stop after a
STF signal: Forward rotation start
0 to 100 s lapse of the setting time when the
STR signal: Reverse rotation start
start signal is turned OFF.
The motor coasts to a stop after a
STF signal: Start signal lapse of the (Pr.250 - 1000)
250 1000 to 1100 s
Stop selection 9999 STR signal: Forward/reverse rotation signal seconds when the start signal is
G106
turned OFF.
STF signal: Forward rotation start
9999
STR signal: Reverse rotation start The motor is decelerated to a stop
STF signal: Start signal when the start signal is turned OFF.
8888
STR signal: Forward/reverse rotation signal
*1 For the start signal selection, refer to page 291.
Deceleration starts
Output frequency
DC brake
Time
Start
ON OFF
signal
RUN
signal ON OFF
Time
15
16
17
18
19
20
Initial
Pr. Name Setting range Description
value
No regenerative function
Brake resistor (MRS, MYS type)
Brake unit (FR-BU2)
0
Multifunction regeneration converter (FR-XC)
Power regeneration common converter (FR-CV)
30 Regenerative function High power factor converter (FR-HC2)
0
E300 selection
Brake resistor (MYS type) used at 100% torque, 6%ED
1
High-duty brake resistor (FR-ABR)
When the automatic restart operation after instantaneous
2 power failure function is enabled while a brake resistor and a
regeneration unit is used
70
Special regenerative brake duty 0% 0% to 100% Set the %ED of the built-in brake transistor operation.
G107
0 X10: Normally open input
X10: Normally closed input
MRS: Normally open input
1 (NC contact input
specification)
2 X10: Normally open input
MRS: Normally closed input
17 MRS/X10 terminal input X10: Normally closed input (NC contact input
0 3 (NC contact input
T720 selection specification)
specification)
4 X10: Normally open input External terminal: Normally
closed input (NC contact input
X10: Normally closed input specification)
5 (NC contact input
Communication: Normally
specification)
open input
When using the brake resistor (MRS, MYS type), brake unit (FR-BU2),
multifunction regeneration converter (FR-XC), power regeneration
common converter (FR-CV), and high power factor converter (FR-HC2)
• Set Pr.30 = "0" (initial setting). The Pr.70 setting is invalid. At this time, the regenerative brake duty is as follows.
Inverter Regenerative brake duty
FR-E820-0008(0.1K), FR-E820-0015(0.2K) 0%
FR-E820-0030(0.4K) to FR-E820-0175(3.7K) 3%
FR-E820-0240(5.5K), FR-E820-0330(7.5K)
2%
FR-E840-0016(0.4K) to FR-E840-0170(7.5K)
• When connecting the converter unit (FR-XC, FR-HC2, or FR-CV), assign the Inverter run enable (X10) signal to a contact
input terminal. To ensure coordinated protection of the converter unit, use the Inverter operation enable (X10) signal to
shut off the inverter output. Input the Inverter operation enable (RYB/RDY/RDYB) signal of the converter unit. The X10
signal can be input only via an external input terminal. For the terminal used for the X10 signal input, set "10" (X10) in any
parameter from Pr.178 to Pr.184 to assign the function.
When using the brake resistor (MYS type) used at 100% torque, 6%ED
(FR-E820-0175(3.7K) only)
• Set Pr.30 = "1".
• Set Pr.70 = "6%".
Time
• Relationship between Pr.17 and the Inverter run enable signal of each option unit
Corresponding signals of the option unit
Pr.17 setting Operation according to the X10 signal status
FR-HC2 FR-CV FR-XC
RDY (negative logic)
0/2/4 (initial values) RDYB RYB X10-ON: Inverter output shutoff (NO contact)
(initial setting)
1, 3, 5 RDY (positive logic) RDYA RYA X10-OFF: Inverter output shutoff (NC contact)
Regenerative brake duty warning output and the warning signal (RBP
signal)
• When the regenerative brake duty reaches 85% of the Pr.70 setting, "RB" is indicated on the operation panel and the
Regenerative brake prealarm signal (RBP) signal is output. When it reaches 100% of the Pr.70 setting, it will become
regenerative overvoltage (E.OV[]).
• The inverter output is not shut off with the warning signal.
• For the terminal to be used for the RBP signal output, set "7" (positive logic) or "107" (negative logic) to one of Pr.190 to
Pr.196 (Output terminal function selection), and assign the function.
Regenerative Time
brake pre-alarm OFF ON ON
(RBP)
NOTE
• When Pr.30 = "0" (initial value), "RB" is not indicated.
• Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
Connection of a brake resistor other than the FR-ABR, MRS type, and
MYS type
A brake resistor can be used with the FR-E820-0030(0.4K) to FR-E820-0330(7.5K), FR-E840-0016(0.4K) to FR-E840-
0170(7.5K), and FR-E860-0017(0.75K) to FR-E860-0120(7.5K).
CAUTION
• If the resistor selection is incorrect, overcurrent may damage the inverter built-in brake transistor. Besides, the resistor
may be burned due to overheat.
• If the selection of the thermal relay is incorrect, the resistor may be burned due to overheat.
Parameters referred to
Pr.57 Restart coasting timepage 351, page 356
Pr.178 to Pr.189 (Input terminal function selection)page 283
Pr.190 to Pr.196 (Output terminal function selection)page 250
Setting
Pr. Name Initial value Description
range
0 The regeneration avoidance function is disabled.
Regeneration
882 1 The regeneration avoidance function is always enabled.
avoidance operation 0
G120 The regeneration avoidance function is enabled only during
selection 2
constant-speed operation.
200 V Set the bus voltage level to operate the regeneration avoidance
400 VDC
class operation. When the bus voltage level is set low, it will be harder
Regeneration 400 V to generate overvoltage error, but actual deceleration time will
883 780 VDC 300 to 1200 V be longer.
avoidance operation class
G121
level Set the setting value higher than the (power supply voltage ×
575 V
944 VDC
class √2 ) value.
Regeneration Set the limit value for frequency to rise when the regeneration
0 to 45 Hz
885 avoidance avoidance function is activated.
6 Hz
G123 compensation
9999 The frequency limit is disabled.
frequency limit value
886 Regeneration Adjust the response during the regeneration avoidance
100% 0% to 200%
G124 avoidance voltage gain operation. Increasing the setting improves the response to
Regeneration change in the bus voltage. However, the output frequency may
665 become unstable. If setting a smaller value in Pr.886 does not
avoidance frequency 100% 0% to 200%
G125
gain suppress the vibration, set a smaller value in Pr.665.
Pr. 883
(VDC)
Pr. 883
(VDC)
Bus voltage
Pr. 883
(VDC)
Time
frequency(Hz)
Time
frequency(Hz)
Output
Time
Output
frequency(Hz)
Output
During regeneration
avoidance function operation During regeneration
avoidance function operation Time
Time
During regeneration Time
avoidance function operation
• The DC bus voltage of the inverter will be approximately √2 times of the normal input voltage.
The bus voltage is approx. 311 VDC at an input voltage of 220 VAC (622 VDC at 440 VAC and 813 VDC at 575 VAC). 12
However, it may vary depending on the input power supply waveform.
• Make sure that the setting value of Pr.883 will not get under DC bus voltage level. The frequency will rise with operation of the
regeneration avoidance function even during operation other than the regenerative operation.
• The stall prevention (overvoltage) (OLV) will be activated only during deceleration, stopping the lowering of output frequency.
13
On the other hand, the regeneration avoidance function will be activated constantly (Pr.882 = "1") or only at constant speed
(Pr.882 = "2"), and raise the frequency depending on the amount of regeneration.
• When the motor becomes unstable due to the stall prevention (overcurrent) (OLC) during the regeneration avoidance 14
operation, increase the deceleration time or set a lower value in Pr.883.
Pr.885
Pr.885/2
Time
NOTE
• During the regeneration avoidance operation, the stall prevention (overvoltage) "OLV" is displayed and the Overload warning
(OL) signal is output. Set the operation pattern at an OL signal output using Pr.156 Stall prevention operation selection.
Use Pr.157 OL signal output timer to set the OL signal output timing.
• The stall prevention is enabled even during regeneration avoidance operation.
• The regeneration avoidance function cannot decrease the actual deceleration time for the motor to stop. Since the actual
deceleration time is determined by the regenerative power consumption performance, consider using a regeneration unit (FR-
BU2, BU, FR-BU, FR-XC, FR-CV, FR-HC2) or brake resistor (FR-ABR, etc.) to decrease the deceleration time.
• When using a regeneration unit (FR-BU2, BU, FR-BU, FR-XC, FR-CV, FR-HC2) or brake resistor (FR-ABR, etc.) to consume
the regenerative power at constant speed, set Pr.882 = "0 (initial value)" (the regeneration avoidance function is disabled).
When consuming the regenerative power at the time of deceleration with the regeneration unit, etc., set Pr.882 = "2" (enables
regeneration avoidance function only at the constant speed).
V/F
Under V/F control, the slip of the motor is estimated from the inverter output current to maintain the rotation of the motor
12
constant.
Droop control
• Droop control is enabled under Advanced magnetic flux vector control, Real sensorless vector control, and PM sensorless
vector control.
• In the droop control, the speed command changes depending on the amount of the current for torque.
Frequency
Droop compensation
frequency
Rated frequency
Droop
gain
Current for torque after filtering Pr.84 Rated motor frequency × Pr.286 Droop gain
Droop compensation frequency = ×K×
Rated torque current 100
When the output frequency is equal to or lower than the rated frequency set in Pr.84: K = 1
Rated frequency (Pr.84)
When the output frequency is higher than the rated frequency set in Pr.84: K = Output frequency
NOTE
• Set the droop gain equivalent to the rated slip of the motor.
Synchronized speed at the time of base frequency - rated rotation speed
Rated slip = × 100[%]
Synchronized speed at the time of base frequency
• Droop control is disabled in the following conditions:
During DC injection brake operation, during PID control, during stall prevention operation, during traverse operation
Parameters referred to
Pr.1 Maximum frequencypage 211
Pr.178 to Pr.189 Input terminal function selection page 283
12
V/F Magnetic flux
The output current (torque) of the inverter sometimes becomes unstable due to vibration caused by mechanical resonance.
Such vibration can be suppressed by reducing fluctuation of the output current (torque) by changing the output frequency.
+ Output frequency
16
Speed Frequency output
V/F control
command Voltage output
-
Speed smoothing control
Cutoff frequency
Pr.654
17
Proportional gain
Current for torque
Pr.653
18
Setting method
• When vibration caused by mechanical resonance occurs, set 100% in Pr.653 Speed smoothing control, perform
operation at the frequency with the largest vibration, and check if the vibration is suppressed after few seconds. 19
• If the setting is not effective, gradually increase the value set in Pr.653 and repeat the operation to check the effect to
determine the most effective value (Pr.653).
• If the vibration increases by increasing the value in Pr.653, decrease the value in Pr.653 from 100% to check the effect. 20
• When the vibrational frequency at which mechanical resonance occurs (during fluctuation of torque, speed, or converter
output voltage) is measured using an instrument such as a tester, set 1/2 to 1 times of the vibrational frequency in Pr.654
Speed smoothing cutoff frequency. (Setting the resonance frequency range mitigates vibration more effectively.)
Cutoff frequency
Current for
torque
Torque fluctuation
detection range
NOTE
• Depending on the equipment, the vibration may not be suppressed sufficiently or the setting is not effective.
10
397
16 Checking and Clearing of Settings
16.1 Parameter clear / All parameter clear
• Set "1" to Pr.CL Parameter clear or ALLC All parameter clear to initialize the parameter. (The parameter cannot be cleared
when Pr.77 Parameter write selection = "1".)
• Pr.CL does not clear calibration parameters or the terminal function selection parameters.
• Refer to the parameter list on page 50 for parameters cleared with this operation.
Operating procedure
1. Turning ON the power of the inverter
The operation panel is in the monitor mode.
5. Parameter clear
Turn the setting dial or press the UP/DOWN key to change the value to "1". Press the SET key to confirm the setting.
"1" and "Pr.CL" ("ALLC") are displayed alternately after parameters are cleared.
• Turn the setting dial or press the UP/DOWN key to read another parameter.
• Press the SET key to show the setting again.
• Press the SET key twice to show the next parameter.
Description
Setting
Pr.CL Parameter clear ALLC All parameter clear
0 Initial display (Parameters are not cleared.)
The settings of all the parameters, including calibration
The settings of parameters except for calibration parameters
1 parameters and terminal function selection parameters, are
and terminal function selection parameters are initialized.
initialized.
NOTE
• "1" and "Er4" are displayed alternately when the operation mode is other than the PU operation mode.
1) Press the PU/EXT key.
The PU LED turns ON, and "1" appears on the monitor. (When Pr.79 ="0" (initial value))
2) Press the SET key to clear the parameter.
• Stop the inverter first. Writing error occurs if parameter clear is attempted while the inverter is running.
• To clear the parameter, the inverter must be in the PU operation mode even if "2" is set to Pr.77.
• For availability of the Parameter clear or All parameter clear operation for each parameter, refer to the parameter list on page
406.
NOTE
• Calibration parameters (C0 to C7, C38 to C45) are not displayed even when these are changed from the initial settings.
18
• Only the simple mode parameters are displayed when the simple mode is set (Pr.160 ="9999").
• Only user groups are displayed when user groups are set (Pr.160 = "1").
• Pr.160 is displayed independently of whether the setting value is changed or not. 19
20
• Set Er.CL Fault history clear = "1" to clear the fault history.
Operating procedure
1. Turning ON the power of the inverter
The operation panel is in the monitor mode.
17.1 For customers replacing the conventional model with this inverter ......................................................................402
17.2 Specification comparison between PM sensorless vector control and induction motor control............................405
6
17.3 Parameters (functions) and instruction codes under different control methods....................................................406
10
401
17 Appendix
APPENDIX provides the reference information for use of this product.
Refer to APPENDIX as required.
Shape of
Spring clamp type
Standard control circuit terminal model: screw
type
11
terminal block
Safety stop function model: Spring clamp type
Standard model: 7 Standard control circuit terminal model: 7
Contact input
Analog input
Ethernet model: 2
2
Safety stop function model: 6
2
12
Control circuit
Relay output 1 1
terminal
Open collector Standard model: 2
2
output Ethernet model: 0 13
Pulse output 1 (FM type only) 1 (FR-E700)
Analog output 1 (AM type only) 1 (FR-E700-NA/EC/CHT)
Safety input/
output
S1, S2, SIC, SO, SOC S1, S2, PC (safety stop function model only)
14
2 ports (Ethernet model)
1 port (FR-E700-NE only)
CC-Link IE TSN, CC-Link IE Field Network Basic,
Ethernet CC-Link IE Field Network Basic and MODBUS/
EtherNet/IP, PROFINET, MODBUS/TCP, and
Communication
BACnet/IP
TCP
15
1 port (standard model) 1 port
RS-485
Mitsubishi inverter protocol, MODBUS RTU Mitsubishi inverter protocol, MODBUS RTU
Mini B connector: USB bus power available
USB
(Maximum SCCR: 500 mA)
Mini B connector: USB bus power unavailable 16
200/400 V class: -20°C to +60°C (Derate the rated
current when using the inverter in a temperature of
50°C or higher.)
Surrounding air temperature
575 V class: -10°C to +60°C (Derate the rated
-10°C to +50°C 17
current when using the inverter in a temperature of
50°C or higher.)
Storage temperature -40°C to +70°C -20°C to +65°C
Plug-in option Dedicated plug-in options (not interchangeable) 18
Compatible (Use the installation interchange attachment for replacement of the FR-E720-175(3.7K)
Installation size
and FR-E740-016(0.4K) to 040(1.5K).)
Panel through attachment Not compatible
The rotation speed is displayed when Pr.53 = "1".
19
The machine speed is displayed when Pr.53 = "4". The machine speed is displayed when Pr.37 ≠
Machine speed display
Use Pr.37 and Pr.505 to set the reference for "0".
Installation precautions
• Removal procedure of the front cover is different. (Refer to the Instruction Manual (Connection).)
• Plug-in options of the FR-E700 series are not compatible.
Wiring instructions
• When the FR-E700 standard control circuit terminal model is replaced, the terminal block type is changed from the screw
type to the spring clamp type. Use of blade terminals is recommended.
• To use the PU connector, note that wiring methods are different. (Refer to the Instruction Manual (Connection).)
17. Appendix
17.1 For customers replacing the conventional model with this inverter
403
17.1.2 Replacement of the FR-E500 series
Installation precautions
• Installation size is compatible. (Use the installation interchange attachment for replacement of the FR-E520-3.7K and
E540-0.4K to 1.5K.)
• Operation panel (PA02) cannot be used.
20
17. Appendix
17.2 Specification comparison between PM sensorless vector control and induction motor control
405
17.3 Parameters (functions) and instruction codes
under different control methods
*1 Instruction codes are used to read and write parameters in accordance with communication (such as the Mitsubishi inverter protocol). (For details
of communication, refer to the Instruction Manual (Communication).)
*2 Function availability under each control method is shown as follows:
○: Available
×: Not available
Δ: Available with some restrictions
*3 For Parameter copy, Parameter clear, and All parameter clear, ○ indicates the function is available, and × indicates the function is not available.
*4 Communication parameters that are not cleared by parameter clear or all parameter clear (H5A5A or H55AA) via communication. (For details of
communication, refer to the Instruction Manual (Communication).)
*5 When a communication option is installed, parameter clear (lock release) during password lock (Pr.297 Password lock/unlock ≠ ”9999”) can be
performed only from the communication option.
Notation
Mark Description Mark Description
Available for the FM type inverter (standard model). Available for the 200 V class inverters.
Available for the AM (50 Hz) type inverter (standard model). Available for the 400 V class inverters.
Available for the AM (60 Hz) type inverter (standard model). Available when the FR-A8AX is installed.
Available for the Ethernet model. Available when the FR-A8AY is installed.
Available when the FR-A8AR is installed.
Available for the Protocol group A (Ethernet model).
Available when the FR-A8NC is installed.
Instruction
Control method*2 Parameter
code*1
Sensorless PM
All clear*3
Extended
Pr. Name
Magnetic flux
Clear*3
Write
V/F
Read
Torque
Speed
Speed
0 Torque boost 00 80 0 ○ × × × × ○ ○
1 Maximum frequency 01 81 0 ○ ○ ○ ○ ○ ○ ○
2 Minimum frequency 02 82 0 ○ ○ ○ ○ ○ ○ ○
3 Base frequency 03 83 0 ○ × × × × ○ ○
4 Multi-speed setting (high speed) 04 84 0 ○ ○ ○ ○ ○ ○ ○
5 Multi-speed setting (middle speed) 05 85 0 ○ ○ ○ ○ ○ ○ ○
6 Multi-speed setting (low speed) 06 86 0 ○ ○ ○ ○ ○ ○ ○
7 Acceleration time 07 87 0 ○ ○ ○ ○ ○ ○ ○
8 Deceleration time 08 88 0 ○ ○ ○ ○ ○ ○ ○
9 Electronic thermal O/L relay 09 89 0 ○ ○ ○ ○ ○ ○ ○
10 DC injection brake operation frequency 0A 8A 0 ○ ○ ○ ○ ○ ○ ○
11 DC injection brake operation time 0B 8B 0 ○ ○ ○ ○ ○ ○ ○
12 DC injection brake operation voltage 0C 8C 0 ○ ○ × × × ○ ○
13 Starting frequency 0D 8D 0 ○ ○ ○ ○ ○ ○ ○
14 Load pattern selection 0E 8E 0 ○ × × × × ○ ○
15 Jog frequency 0F 8F 0 ○ ○ ○ ○ ○ ○ ○
16 Jog acceleration/deceleration time 10 90 0 ○ ○ ○ ○ ○ ○ ○
17 MRS/X10 terminal input selection 11 91 0 ○ ○ ○ ○ ○ ○ ○
18 High speed maximum frequency 12 92 0 ○ ○ ○ ○ ○ ○ ○
19 Base frequency voltage 13 93 0 ○ × × × × ○ ○
20 Acceleration/deceleration reference frequency 14 94 0 ○ ○ ○ ○ ○ ○ ○
21 Acceleration/deceleration time increments 15 95 0 ○ ○ ○ ○ ○ ○ ○
22 Stall prevention operation level (Torque limit level) 16 96 0 ○ ○ ○ × ○ ○ ○
Stall prevention operation level compensation
23 17 97 0 ○ ○ × × × ○ ○
factor at double speed
24 Multi-speed setting (speed 4) 18 98 0 ○ ○ ○ ○ ○ ○ ○
25 Multi-speed setting (speed 5) 19 99 0 ○ ○ ○ ○ ○ ○ ○
26 Multi-speed setting (speed 6) 1A 9A 0 ○ ○ ○ ○ ○ ○ ○
27 Multi-speed setting (speed 7) 1B 9B 0 ○ ○ ○ ○ ○ ○ ○
All clear*3
Extended
Pr. Name
Magnetic flux
Clear*3
Write
V/F
Read
Torque
Speed
Speed
12
29 Acceleration/deceleration pattern selection 1D 9D 0 ○ ○ ○ ○ ○ ○ ○
30 Regenerative function selection 1E 9E 0 ○ ○ ○ ○ ○ ○ ○
31 Frequency jump 1A 1F 9F 0 ○ ○ ○ ○ ○ ○ ○ 13
32 Frequency jump 1B 20 A0 0 ○ ○ ○ ○ ○ ○ ○
33 Frequency jump 2A 21 A1 0 ○ ○ ○ ○ ○ ○ ○
34 Frequency jump 2B 22 A2 0 ○ ○ ○ ○ ○ ○ ○
35 Frequency jump 3A 23 A3 0 ○ ○ ○ ○ ○ ○ ○ 14
36 Frequency jump 3B 24 A4 0 ○ ○ ○ ○ ○ ○ ○
37 Speed display 25 A5 0 ○ ○ ○ ○ ○ ○ ○
40 RUN key rotation direction selection 28 A8 0 ○ ○ ○ ○ ○ ○ ○ 15
41 Up-to-frequency sensitivity 29 A9 0 ○ ○ ○ × ○ ○ ○
42 Output frequency detection 2A AA 0 ○ ○ ○ Δ ○ ○ ○
43 Output frequency detection for reverse rotation 2B AB 0 ○ ○ ○ Δ ○ ○ ○
44 Second acceleration/deceleration time 2C AC 0 ○ ○ ○ ○ ○ ○ ○ 16
45 Second deceleration time 2D AD 0 ○ ○ ○ ○ ○ ○ ○
46 Second torque boost 2E AE 0 ○ × × × × ○ ○
47
48
Second V/F (base frequency)
Second stall prevention operation level
2F
30
AF
B0
0
0
○
○
×
○
×
×
×
×
×
×
○
○
○
○
17
51 Second electronic thermal O/L relay 33 B3 0 ○ ○ ○ ○ ○ ○ ○
52 Operation panel main monitor selection 34 B4 0 ○ ○ ○ ○ ○ ○ ○
53 Frequency / rotation speed unit switchover 35 B5 0 ○ ○ ○ ○ ○ ○ ○ 18
54 FM terminal function selection 36 B6 0 ○ ○ ○ ○ ○ ○ ○
55 Frequency monitoring reference 37 B7 0 ○ ○ ○ ○ ○ ○ ○
56 Current monitoring reference 38 B8 0 ○ ○ ○ ○ ○ ○ ○ 19
57 Restart coasting time 39 B9 0 ○ ○ ○ ○ ○ ○ ○
58 Restart cushion time 3A BA 0 ○ ○ × × × ○ ○
59 Remote function selection 3B BB 0 ○ ○ ○ ○ ○ ○ ○
60 Energy saving control selection 3C BC 0 ○ ○ × × × ○ ○ 20
61 Reference current 3D BD 0 ○ ○ ○ × × ○ ○
62 Reference value at acceleration 3E BE 0 ○ ○ ○ × × ○ ○
63 Reference value at deceleration 3F BF 0 ○ ○ ○ × × ○ ○
65 Retry selection 41 C1 0 ○ ○ ○ ○ ○ ○ ○
Stall prevention operation reduction starting
66 42 C2 0 ○ ○ × × × ○ ○
frequency
67 Number of retries at fault occurrence 43 C3 0 ○ ○ ○ ○ ○ ○ ○
68 Retry waiting time 44 C4 0 ○ ○ ○ ○ ○ ○ ○
69 Retry count display erase 45 C5 0 ○ ○ ○ ○ ○ ○ ○
70 Special regenerative brake duty 46 C6 0 ○ ○ ○ ○ ○ ○ ○
71 Applied motor 47 C7 0 ○ ○ ○ ○ ○ ○ ○
72 PWM frequency selection 48 C8 0 ○ ○ ○ ○ ○ ○ ○
73 Analog input selection 49 C9 0 ○ ○ ○ ○ ○ × ○
74 Input filter time constant 4A CA 0 ○ ○ ○ ○ ○ ○ ○
Reset selection/disconnected PU detection/PU
75 4B CB 0 ○ ○ ○ ○ ○ × ×
stop selection
77 Parameter write selection 4D CD 0 ○ ○ ○ ○ ○ ○ ○
78 Reverse rotation prevention selection 4E CE 0 ○ ○ ○ ○ ○ ○ ○
79 Operation mode selection 4F CF 0 ○ ○ ○ ○ ○ ○ ○
80 Motor capacity 50 D0 0 × ○ ○ ○ ○ ○ ○
81 Number of motor poles 51 D1 0 ○ ○ ○ ○ ○ ○ ○
82 Motor excitation current 52 D2 0 ○ ○ ○ ○ × × ○
83 Rated motor voltage 53 D3 0 × ○ ○ ○ ○ ○ ○
84 Rated motor frequency 54 D4 0 × ○ ○ ○ ○ ○ ○
Speed control gain (Advanced magnetic flux
89 59 D9 0 × ○ × × × × ○
vector)
17. Appendix
17.3 Parameters (functions) and instruction codes under different control methods
407
Instruction
Control method*2 Parameter
code*1
Sensorless PM
All clear*3
Extended
Pr. Name
Magnetic flux
Clear*3
Write
V/F
Read
Torque
Speed
Speed
90 Motor constant (R1) 5A DA 0 × ○ ○ ○ ○ × ○
91 Motor constant (R2) 5B DB 0 × ○ ○ ○ × × ○
92 Motor constant (L1)/d-axis inductance (Ld) 5C DC 0 × ○ ○ ○ ○ × ○
93 Motor constant (L2)/q-axis inductance (Lq) 5D DD 0 × ○ ○ ○ ○ × ○
94 Motor constant (X) 5E DE 0 × ○ ○ ○ × × ○
95 Online auto tuning selection 5F DF 0 × ○ ○ ○ × ○ ○
96 Auto tuning setting/status 60 E0 0 × ○ ○ ○ ○ × ○
*4
117 PU communication station number 11 91 1 ○ ○ ○ ○ ○ ○ ○*4
118 PU communication speed 12 92 1 ○ ○ ○ ○ ○ ○*4 ○*4
119 PU communication stop bit length / data length 13 93 1 ○ ○ ○ ○ ○ ○*4 ○*4
120 PU communication parity check 14 94 1 ○ ○ ○ ○ ○ ○*4 ○*4
*4
121 PU communication retry count 15 95 1 ○ ○ ○ ○ ○ ○ ○*4
122 PU communication check time interval 16 96 1 ○ ○ ○ ○ ○ ○*4 ○*4
*4
123 PU communication waiting time setting 17 97 1 ○ ○ ○ ○ ○ ○ ○*4
124 PU communication CR/LF selection 18 98 1 ○ ○ ○ ○ ○ ○*4 ○*4
125 Terminal 2 frequency setting gain frequency 19 99 1 ○ ○ ○ ○ ○ × ○
126 Terminal 4 frequency setting gain frequency 1A 9A 1 ○ ○ ○ ○ ○ × ○
127 PID control automatic switchover frequency 1B 9B 1 ○ ○ ○ × ○ ○ ○
128 PID action selection 1C 9C 1 ○ ○ ○ × ○ ○ ○
129 PID proportional band 1D 9D 1 ○ ○ ○ × ○ ○ ○
130 PID integral time 1E 9E 1 ○ ○ ○ × ○ ○ ○
131 PID upper limit 1F 9F 1 ○ ○ ○ × ○ ○ ○
132 PID lower limit 20 A0 1 ○ ○ ○ × ○ ○ ○
133 PID action set point 21 A1 1 ○ ○ ○ × ○ ○ ○
134 PID differential time 22 A2 1 ○ ○ ○ × ○ ○ ○
145 Parameter for manufacturer setting. Do not set.
Acceleration/deceleration time switching
147 2F AF 1 ○ ○ ○ ○ ○ ○ ○
frequency
150 Output current detection level 32 B2 1 ○ ○ ○ ○ ○ ○ ○
151 Output current detection signal delay time 33 B3 1 ○ ○ ○ ○ ○ ○ ○
152 Zero current detection level 34 B4 1 ○ ○ ○ ○ ○ ○ ○
153 Zero current detection time 35 B5 1 ○ ○ ○ ○ ○ ○ ○
Voltage reduction selection during stall prevention
154 36 B6 1 ○ ○ × × × ○ ○
operation
156 Stall prevention operation selection 38 B8 1 ○ ○ ○ × ○ ○ ○
157 OL signal output timer 39 B9 1 ○ ○ ○ ○ ○ ○ ○
158 AM terminal function selection 3A BA 1 ○ ○ ○ ○ ○ ○ ○
160 User group read selection 00 80 2 ○ ○ ○ ○ ○ ○ ○
161 Frequency setting/key lock operation selection 01 81 2 ○ ○ ○ ○ ○ × ○
Automatic restart after instantaneous power failure
162 02 82 2 ○ ○ ○ ○ ○ ○ ○
selection
165 Stall prevention operation level for restart 05 85 2 ○ ○ × × × ○ ○
166 Output current detection signal retention time 06 86 2 ○ ○ ○ ○ ○ ○ ○
167 Output current detection operation selection 07 87 2 ○ ○ ○ ○ ○ ○ ○
168
Parameter for manufacturer setting. Do not set.
169
170 Watt-hour meter clear 0A 8A 2 ○ ○ ○ ○ ○ × ○
171 Operation hour meter clear 0B 8B 2 ○ ○ ○ ○ ○ × ×
172 User group registered display/batch clear 0C 8C 2 ○ ○ ○ ○ ○ × ×
173 User group registration 0D 8D 2 ○ ○ ○ ○ ○ × ×
174 User group clear 0E 8E 2 ○ ○ ○ ○ ○ × ×
178 STF/DI0 terminal function selection 12 92 2 ○ ○ ○ ○ ○ × ○
179 STR/DI1 terminal function selection 13 93 2 ○ ○ ○ ○ ○ × ○
All clear*3
Extended
Pr. Name
Magnetic flux
Clear*3
Write
V/F
Read
Torque
Speed
Speed
12
180 RL terminal function selection 14 94 2 ○ ○ ○ ○ ○ × ○
181 RM terminal function selection 15 95 2 ○ ○ ○ ○ ○ × ○
182 RH terminal function selection 16 96 2 ○ ○ ○ ○ ○ × ○ 13
183 MRS terminal function selection 17 97 2 ○ ○ ○ ○ ○ × ○
184 RES terminal function selection 18 98 2 ○ ○ ○ ○ ○ × ○
185 NET X1 input selection 19 99 2 ○ ○ ○ ○ ○ × ○
186 NET X2 input selection 1A 9A 2 ○ ○ ○ ○ ○ × ○ 14
187 NET X3 input selection 1B 9B 2 ○ ○ ○ ○ ○ × ○
188 NET X4 input selection 1C 9C 2 ○ ○ ○ ○ ○ × ○
189 NET X5 input selection 1D 9D 2 ○ ○ ○ ○ ○ × ○ 15
190 RUN terminal function selection 1E 9E 2 ○ ○ ○ ○ ○ × ○
191 FU terminal function selection 1F 9F 2 ○ ○ ○ ○ ○ × ○
192 ABC terminal function selection 20 A0 2 ○ ○ ○ ○ ○ × ○
193 NET Y1 output selection 21 A1 2 ○ ○ ○ ○ ○ × ○ 16
194 NET Y2 output selection 22 A2 2 ○ ○ ○ ○ ○ × ○
195 NET Y3 output selection 23 A3 2 ○ ○ ○ ○ ○ × ○
196
198
NET Y4 output selection
Display corrosion level
24
26
A4
A6
2
2
○
○
○
○
○
○
○
○
○
○
×
×
○
×
17
232 Multi-speed setting (speed 8) 28 A8 2 ○ ○ ○ ○ ○ ○ ○
233 Multi-speed setting (speed 9) 29 A9 2 ○ ○ ○ ○ ○ ○ ○
234 Multi-speed setting (speed 10) 2A AA 2 ○ ○ ○ ○ ○ ○ ○ 18
235 Multi-speed setting (speed 11) 2B AB 2 ○ ○ ○ ○ ○ ○ ○
236 Multi-speed setting (speed 12) 2C AC 2 ○ ○ ○ ○ ○ ○ ○
237
238
Multi-speed setting (speed 13)
Multi-speed setting (speed 14)
2D
2E
AD
AE
2
2
○
○
○
○
○
○
○
○
○
○
○
○
○
○
19
239 Multi-speed setting (speed 15) 2F AF 2 ○ ○ ○ ○ ○ ○ ○
240 Soft-PWM operation selection 30 B0 2 ○ ○ ○ ○ ○ ○ ○
241 Analog input display unit switchover 31 B1 2 ○ ○ ○ ○ ○ ○ ○ 20
244 Cooling fan operation selection 34 B4 2 ○ ○ ○ ○ ○ ○ ○
245 Rated slip 35 B5 2 ○ × × × × ○ ○
246 Slip compensation time constant 36 B6 2 ○ × × × × ○ ○
Constant output range slip compensation
247 37 B7 2 ○ × × × × ○ ○
selection
249 Earth (ground) fault detection at start 39 B9 2 ○ ○ ○ ○ ○ ○ ○
250 Stop selection 3A BA 2 ○ ○ ○ ○ ○ ○ ○
251 Output phase loss protection selection 3B BB 2 ○ ○ ○ ○ ○ ○ ○
255 Life alarm status display 3F BF 2 ○ ○ ○ ○ ○ × ×
256 Inrush current limit circuit life display 40 C0 2 ○ ○ ○ ○ ○ × ×
257 Control circuit capacitor life display 41 C1 2 ○ ○ ○ ○ ○ × ×
258 Main circuit capacitor life display 42 C2 2 ○ ○ ○ ○ ○ × ×
259 Main circuit capacitor life measuring 43 C3 2 ○ ○ ○ ○ ○ ○ ○
260 PWM frequency automatic switchover 44 C4 2 ○ ○ ○ ○ ○ ○ ○
261 Power failure stop selection 45 C5 2 ○ ○ ○ ○ ○ ○ ○
267 Terminal 4 input selection 4B CB 2 ○ ○ ○ ○ ○ × ○
268 Monitor decimal digits selection 4C CC 2 ○ ○ ○ ○ ○ ○ ○
269 Parameter for manufacturer setting. Do not set.
270 Stop-on-contact control selection 4E CE 2 ○ ○ ○ × × ○ ○
Stop-on contact excitation current low-speed
275 53 D3 2 × ○ ○ × × ○ ○
scaling factor
276 PWM carrier frequency at stop-on contact 54 D4 2 × ○ ○ × × ○ ○
277 Stall prevention operation current switchover 55 D5 2 ○ ○ × × × ○ ○
278 Brake opening frequency 56 D6 2 × ○ ○ × × ○ ○
279 Brake opening current 57 D7 2 × ○ ○ × × ○ ○
280 Brake opening current detection time 58 D8 2 × ○ ○ × × ○ ○
17. Appendix
17.3 Parameters (functions) and instruction codes under different control methods
409
Instruction
Control method*2 Parameter
code*1
Sensorless PM
All clear*3
Extended
Pr. Name
Magnetic flux
Clear*3
Write
V/F
Read
Torque
Speed
Speed
281 Brake operation time at start 59 D9 2 × ○ ○ × × ○ ○
282 Brake operation frequency 5A DA 2 × ○ ○ × × ○ ○
283 Brake operation time at stop 5B DB 2 × Δ × × × ○ ○
285 Speed deviation excess detection frequency 5D DD 2 × × × × Δ ○ ○
286 Droop gain 5E DE 2 × ○ ○ × ○ ○ ○
287 Droop filter time constant 5F DF 2 × × ○ × ○ ○ ○
289 Inverter output terminal filter 61 E1 2 ○ ○ ○ ○ ○ × ○
290 Monitor negative output selection 62 E2 2 ○ ○ ○ ○ ○ ○ ○
292 Automatic acceleration/deceleration 64 E4 2 Δ Δ Δ × × ○ ○
293 Acceleration/deceleration separate selection 65 E5 2 ○ ○ ○ × × ○ ○
295 Frequency change increment amount setting 67 E7 2 ○ ○ ○ ○ ○ ○ ○
296 Password lock level 68 E8 2 ○ ○ ○ ○ ○ × ○
297 Password lock/unlock 69 E9 2 ○ ○ ○ ○ ○ *5 ○
○
298 Frequency search gain 6A EA 2 ○ ○ ○ ○ × × ○
299 Rotation direction detection selection at restarting 6B EB 2 ○ ○ ○ × × ○ ○
300 BCD input bias 00 80 3 ○ ○ ○ ○ ○ ○ ○
301 BCD input gain 01 81 3 ○ ○ ○ ○ ○ ○ ○
302 BIN input bias 02 82 3 ○ ○ ○ ○ ○ ○ ○
303 BIN input gain 03 83 3 ○ ○ ○ ○ ○ ○ ○
Digital input and analog input compensation
304 04 84 3 ○ ○ ○ ○ ○ ○ ○
enable/disable selection
305 Read timing operation selection 05 85 3 ○ ○ ○ ○ ○ ○ ○
306 Analog output signal selection 06 86 3 ○ ○ ○ ○ ○ ○ ○
307 Setting for zero analog output 07 87 3 ○ ○ ○ ○ ○ ○ ○
308 Setting for maximum analog output 08 88 3 ○ ○ ○ ○ ○ ○ ○
Analog output signal voltage/current
309 09 89 3 ○ ○ ○ ○ ○ ○ ○
switchover
310 Analog meter voltage output selection 0A 8A 3 ○ ○ ○ ○ ○ ○ ○
311 Setting for zero analog meter voltage output 0B 8B 3 ○ ○ ○ ○ ○ ○ ○
Setting for maximum analog meter voltage
312 0C 8C 3 ○ ○ ○ ○ ○ ○ ○
output
313 DO0 output selection 0D 8D 3 ○ ○ ○ ○ ○ × ○
314 DO1 output selection 0E 8E 3 ○ ○ ○ ○ ○ × ○
315 DO2 output selection 0F 8F 3 ○ ○ ○ ○ ○ × ○
316 DO3 output selection 10 90 3 ○ ○ ○ ○ ○ × ○
317 DO4 output selection 11 91 3 ○ ○ ○ ○ ○ × ○
318 DO5 output selection 12 92 3 ○ ○ ○ ○ ○ × ○
319 DO6 output selection 13 93 3 ○ ○ ○ ○ ○ × ○
320 RA1 output selection 14 94 3 ○ ○ ○ ○ ○ × ○
321 RA2 output selection 15 95 3 ○ ○ ○ ○ ○ × ○
322 RA3 output selection 16 96 3 ○ ○ ○ ○ ○ × ○
323 AM0 0V adjustment 17 97 3 ○ ○ ○ ○ ○ × ○
324 AM1 0mA adjustment 18 98 3 ○ ○ ○ ○ ○ × ○
329 Digital input unit selection 1D 9D 3 ○ ○ ○ ○ ○ × ○
338 Communication operation command source 26 A6 3 ○ ○ ○ ○ ○ ○*4 ○*4
339 Communication speed command source 27 A7 3 ○ ○ ○ ○ ○ ○*4 ○*4
340 Communication startup mode selection 28 A8 3 ○ ○ ○ ○ ○ ○*4 ○*4
342 Communication EEPROM write selection 2A AA 3 ○ ○ ○ ○ ○ ○ ○
343 Communication error count 2B AB 3 ○ ○ ○ ○ ○ × ×
349 Communication reset selection 31 B1 3 ○ ○ ○ ○ ○ ○*4 ○*4
374 Overspeed detection level 4A CA 3 × × ○ ○ ○ ○ ○
All clear*3
Extended
Pr. Name
Magnetic flux
Clear*3
Write
V/F
Read
Torque
Speed
Speed
12
390 % setting reference frequency 5A DA 3 ○ ○ ○ ○ ○ ○ ○
414 PLC function operation selection 0E 8E 4 ○ ○ ○ ○ ○ × ×
415 Inverter operation lock mode setting 0F 8F 4 ○ ○ ○ ○ ○ ○ ○ 13
416 Pre-scale function selection 10 90 4 ○ ○ ○ ○ ○ ○ ○
417 Pre-scale setting value 11 91 4 ○ ○ ○ ○ ○ ○ ○
418
442
Extension output terminal filter
Default gateway address 1
12
2A
92
AA
4
4
○
○
○
○
○
○
○
○
○
○
×
○ *4
○
○*4
14
443 Default gateway address 2 2B AB 4 ○ ○ ○ ○ ○ ○*4 ○*4
444 2C AC 4 ○ ○ ○ ○ ○ ○*4 ○*4
445
Default gateway address 3
Default gateway address 4 2D AD 4 ○ ○ ○ ○ ○ ○*4 ○*4
15
447 Digital torque command bias 2F AF 4 × × × ○ × ○ ○
448 Digital torque command gain 30 B0 4 × × × ○ × ○ ○
450 Second applied motor 32 B2 4 ○ ○ ○ ○ ○ ○ ○ 16
451 Second motor control method selection 33 B3 4 ○ ○ ○ ○ ○ ○ ○
453 Second motor capacity 35 B5 4 × ○ ○ ○ ○ ○ ○
454 Number of second motor poles 36 B6 4 ○ ○ ○ ○ ○ ○ ○ 17
455 Second motor excitation current 37 B7 4 ○ ○ ○ ○ × × ○
456 Rated second motor voltage 38 B8 4 × ○ ○ ○ ○ ○ ○
457 Rated second motor frequency 39 B9 4 × ○ ○ ○ ○ ○ ○
458 Second motor constant (R1) 3A BA 4 × ○ ○ ○ ○ × ○ 18
459 Second motor constant (R2) 3B BB 4 × ○ ○ ○ × × ○
Second motor constant (L1) / d-axis inductance
460 3C BC 4 × ○ ○ ○ ○ × ○
(Ld)
Second motor constant (L2) / q-axis inductance
19
461 3D BD 4 × ○ ○ ○ ○ × ○
(Lq)
462 Second motor constant (X) 3E BE 4 × ○ ○ ○ × × ○
463 Second motor auto tuning setting/status 3F BF 4 × ○ ○ ○ ○ × ○ 20
495 Remote output selection 5F DF 4 ○ ○ ○ ○ ○ ○ ○
496 Remote output data 1 60 E0 4 ○ ○ ○ ○ ○ × ×
497 Remote output data 2 61 E1 4 ○ ○ ○ ○ ○ × ×
498 PLC function flash memory clear 62 E2 4 ○ ○ ○ ○ ○ ○ ○
500 Communication error execution waiting time 00 80 5 ○ ○ ○ ○ ○ ○ ○
Communication error occurrence count
501 01 81 5 ○ ○ ○ ○ ○ ○ ○
display
502 Stop mode selection at communication error 02 82 5 ○ ○ ○ ○ ○ ○ ○
503 Maintenance timer 03 83 5 ○ ○ ○ ○ ○ × ×
504 Maintenance timer warning output set time 04 84 5 ○ ○ ○ ○ ○ × ○
505 Speed setting reference 05 85 5 ○ ○ ○ ○ ○ ○ ○
Display estimated main circuit capacitor residual
506 06 86 5 ○ ○ ○ ○ ○ × ×
life
507 Display ABC relay contact life 07 87 5 ○ ○ ○ ○ ○ × ×
509 Display power cycle life 09 89 5 ○ ○ ○ ○ ○ × ×
541 Frequency command sign selection 29 A9 5 ○ ○ ○ × ○ ○*4 ○*4
542 Communication station number (CC-Link) 2A AA 5 ○ ○ ○ ○ ○ ○*4 ○*4
543 Baud rate selection (CC-Link) 2B AB 5 ○ ○ ○ ○ ○ ○*4 ○*4
544 CC-Link extended setting 2C AC 5 ○ ○ ○ ○ ○ ○*4 ○*4
547 USB communication station number 2F AF 5 ○ ○ ○ ○ ○ ○*4 ○*4
548 USB communication check time interval 30 B0 5 ○ ○ ○ ○ ○ ○*4 ○*4
549 Protocol selection 31 B1 5 ○ ○ ○ ○ ○ ○*4 ○*4
550 NET mode operation command source selection 32 B2 5 ○ ○ ○ ○ ○ ○*4 ○*4
*4
551 PU mode operation command source selection 33 B3 5 ○ ○ ○ ○ ○ ○ ○*4
553 PID deviation limit 35 B5 5 ○ ○ ○ × ○ ○ ○
17. Appendix
17.3 Parameters (functions) and instruction codes under different control methods
411
Instruction
Control method*2 Parameter
code*1
Sensorless PM
All clear*3
Extended
Pr. Name
Magnetic flux
Clear*3
Write
V/F
Read
Torque
Speed
Speed
554 PID signal operation selection 36 B6 5 ○ ○ ○ × ○ ○ ○
555 Current average time 37 B7 5 ○ ○ ○ ○ ○ ○ ○
556 Data output mask time 38 B8 5 ○ ○ ○ ○ ○ ○ ○
Current average value monitor signal output
557 39 B9 5 ○ ○ ○ ○ ○ ○ ○
reference current
560 Second frequency search gain 3C BC 5 ○ ○ ○ ○ × × ○
563 Energization time carrying-over times 3F BF 5 ○ ○ ○ ○ ○ × ×
564 Operating time carrying-over times 40 C0 5 ○ ○ ○ ○ ○ × ×
569 Second motor speed control gain 45 C5 5 × ○ × × × × ○
570 Multiple rating setting 46 C6 5 ○ ○ ○ ○ ○ × ×
571 Holding time at a start 47 C7 5 ○ ○ ○ ○ × ○ ○
574 Second motor online auto tuning 4A CA 5 × ○ ○ ○ × ○ ○
575 Output interruption detection time 4B CB 5 ○ ○ ○ × ○ ○ ○
576 Output interruption detection level 4C CC 5 ○ ○ ○ × ○ ○ ○
577 Output interruption cancel level 4D CD 5 ○ ○ ○ × ○ ○ ○
592 Traverse function selection 5C DC 5 ○ ○ ○ × ○ ○ ○
593 Maximum amplitude amount 5D DD 5 ○ ○ ○ × ○ ○ ○
Amplitude compensation amount during
594 5E DE 5 ○ ○ ○ × ○ ○ ○
deceleration
Amplitude compensation amount during
595 5F DF 5 ○ ○ ○ × ○ ○ ○
acceleration
596 Amplitude acceleration time 60 E0 5 ○ ○ ○ × ○ ○ ○
597 Amplitude deceleration time 61 E1 5 ○ ○ ○ × ○ ○ ○
609 PID set point/deviation input selection 09 89 6 ○ ○ ○ × ○ ○ ○
610 PID measured value input selection 0A 8A 6 ○ ○ ○ × ○ ○ ○
611 Acceleration time at a restart 0B 8B 6 ○ ○ ○ × ○ ○ ○
Inverter output fault detection enable/disable
631 1F 9F 6 ○ ○ ○ ○ ○ × ×
selection
639 Brake opening current selection 27 A7 6 × ○ ○ × × ○ ○
640 Brake operation frequency selection 28 A8 6 × × ○ × × ○ ○
653 Speed smoothing control 35 B5 6 ○ ○ × × × ○ ○
654 Speed smoothing cutoff frequency 36 B6 6 ○ ○ × × × ○ ○
665 Regeneration avoidance frequency gain 41 C1 6 ○ ○ ○ × ○ ○ ○
SF-PR slip amount adjustment operation
673 49 C9 6 ○ × × × × ○ ○
selection
674 SF-PR slip amount adjustment gain 4A CA 6 ○ × × × × ○ ○
675 User parameter auto storage function selection 4B CB 6 ○ ○ ○ ○ ○ ○ ○
699 Input terminal filter 63 E3 6 ○ ○ ○ ○ ○ × ○
702 Maximum motor frequency 02 82 7 × × × × ○ ○ ○
706 Induced voltage constant (phi f) 06 86 7 × × × × ○ × ○
707 Motor inertia (integer) 07 87 7 × × ○ × ○ ○ ○
711 Motor Ld decay ratio 0B 8B 7 × × × × ○ × ○
712 Motor Lq decay ratio 0C 8C 7 × × × × ○ × ○
Starting resistance tuning compensation
717 11 91 7 × ○ ○ ○ ○ × ○
coefficient 1
Starting resistance tuning compensation
720 14 94 7 × ○ ○ ○ × × ○
coefficient
Starting magnetic pole position detection pulse
721 15 95 7 × × × × ○ × ○
width
724 Motor inertia (exponent) 18 98 7 × × ○ × ○ ○ ○
725 Motor protection current level 19 99 7 × × × × ○ ○ ○
*4
728 Device instance number (Upper 3 digits) 1C 9C 7 ○ ○ ○ ○ ○ ○ ○*4
*4
729 Device instance number (Lower 4 digits) 1D 9D 7 ○ ○ ○ ○ ○ ○ ○*4
Starting resistance tuning compensation
737 25 A5 7 × ○ ○ ○ × × ○
coefficient 2
All clear*3
Extended
Pr. Name
Magnetic flux
Clear*3
Write
V/F
Read
Torque
Speed
Speed
12
738 Second motor induced voltage constant (phi f) 26 A6 7 × × × × ○ × ○
739 Second motor Ld decay ratio 27 A7 7 × × × × ○ × ○
740 Second motor Lq decay ratio 28 A8 7 × × × × ○ × ○ 13
Second motor starting resistance tuning
741 29 A9 7 × ○ ○ ○ ○ × ○
compensation coefficient 1
742 Second motor magnetic pole detection pulse width 2A AA 7 × × × × ○ × ○
743 Second motor maximum frequency 2B AB 7 × × × × ○ ○ ○ 14
744 Second motor inertia (integer) 2C AC 7 × × ○ × ○ ○ ○
745 Second motor inertia (exponent) 2D AD 7 × × ○ × ○ ○ ○
746
759
Second motor protection current level
Parameter for manufacturer setting. Do not set.
2E AE 7 × × × × ○ ○ ○
15
774 Operation panel monitor selection 1 4A CA 7 ○ ○ ○ ○ ○ ○ ○
775 Operation panel monitor selection 2 4B CB 7 ○ ○ ○ ○ ○ ○ ○
776 Operation panel monitor selection 3 4C CC 7 ○ ○ ○ ○ ○ ○ ○ 16
779 Operation frequency during communication error 4F CF 7 ○ ○ ○ ○ ○ ○ ○
791 Acceleration time in low-speed range 5B DB 7 × × × × ○ ○ ○
792
800
Deceleration time in low-speed range
Control method selection
5C
00
DC
80
7
8
×
○
×
○
×
○
×
○
○
○
○
○
○
○
17
801 Output limit level 01 81 8 × × ○ ○ × ○ ○
Constant output range torque characteristic
803 03 83 8 × × ○ ○ × ○ ○
selection 18
804 Torque command source selection 04 84 8 × × × ○ × ○ ○
805 Torque command value (RAM) 05 85 8 × × × ○ × ○ ○
806 Torque command value (RAM, EEPROM) 06 86 8 × × × ○ × ○ ○
807 Speed limit selection 07 87 8 × × × ○ × ○ ○ 19
808 Speed limit 08 88 8 × × × ○ × ○ ○
809 Reverse-side speed limit 09 89 8 × × × ○ × ○ ○
810 Torque limit input method selection 0A 8A 8 × × ○ × ○ ○ ○ 20
811 Set resolution switchover 0B 8B 8 × × ○ × ○ ○ ○
812 Torque limit level (regeneration) 0C 8C 8 × × ○ × ○ ○ ○
813 Torque limit level (3rd quadrant) 0D 8D 8 × × ○ × ○ ○ ○
814 Torque limit level (4th quadrant) 0E 8E 8 × × ○ × ○ ○ ○
815 Torque limit level 2 0F 8F 8 × × ○ × ○ ○ ○
816 Torque limit level during acceleration 10 90 8 × × ○ × ○ ○ ○
817 Torque limit level during deceleration 11 91 8 × × ○ × ○ ○ ○
820 Speed control P gain 1 14 94 8 × × ○ × ○ ○ ○
821 Speed control integral time 1 15 95 8 × × ○ × ○ ○ ○
822 Speed setting filter 1 16 96 8 × × ○ ○ ○ ○ ○
Torque control P gain 1 (current loop proportional
824 18 98 8 × × ○ ○ ○ ○ ○
gain)
Torque control integral time 1 (current loop integral
825 19 99 8 × × ○ ○ ○ ○ ○
time)
826 Torque setting filter 1 1A 9A 8 × × ○ ○ ○ ○ ○
830 Speed control P gain 2 1E 9E 8 × × ○ × ○ ○ ○
831 Speed control integral time 2 1F 9F 8 × × ○ × ○ ○ ○
832 Speed setting filter 2 20 A0 8 × × ○ ○ ○ ○ ○
Torque control P gain 2 (current loop proportional
834 22 A2 8 × × ○ ○ ○ ○ ○
gain)
Torque control integral time 2 (current loop integral
835 23 A3 8 × × ○ ○ ○ ○ ○
time)
836 Torque setting filter 2 24 A4 8 × × ○ ○ ○ ○ ○
849 Analog input offset adjustment 31 B1 8 ○ ○ ○ ○ ○ ○ ○
850 Brake operation selection 32 B2 8 × × ○ ○ × ○ ○
853 Speed deviation time 35 B5 8 × × × × Δ ○ ○
858 Terminal 4 function assignment 3A BA 8 ○ ○ ○ ○ ○ × ○
17. Appendix
17.3 Parameters (functions) and instruction codes under different control methods
413
Instruction
Control method*2 Parameter
code*1
Sensorless PM
All clear*3
Extended
Pr. Name
Magnetic flux
Clear*3
Write
V/F
Read
Torque
Speed
Speed
859 Torque current/Rated PM motor current 3B BB 8 × ○ ○ ○ ○ × ○
Second motor torque current/Rated PM motor
860 3C BC 8 × ○ ○ ○ ○ × ○
current
864 Torque detection 40 C0 8 × × ○ ○ ○ ○ ○
865 Low speed detection 41 C1 8 ○ ○ ○ ○ ○ ○ ○
866 Torque monitoring reference 42 C2 8 × ○ ○ ○ ○ ○ ○
867 AM output filter 43 C3 8 ○ ○ ○ ○ ○ ○ ○
870 Speed detection hysteresis 46 C6 8 ○ ○ ○ ○ ○ ○ ○
872 Input phase loss protection selection 48 C8 8 ○ ○ ○ ○ ○ ○ ○
874 OLT level setting 4A CA 8 × × ○ × ○ ○ ○
882 Regeneration avoidance operation selection 52 D2 8 ○ ○ ○ × ○ ○ ○
883 Regeneration avoidance operation level 53 D3 8 ○ ○ ○ × ○ ○ ○
Regeneration avoidance compensation frequency
885 55 D5 8 ○ ○ ○ × ○ ○ ○
limit value
886 Regeneration avoidance voltage gain 56 D6 8 ○ ○ ○ × ○ ○ ○
888 Free parameter 1 58 D8 8 ○ ○ ○ ○ ○ × ×
889 Free parameter 2 59 D9 8 ○ ○ ○ ○ ○ × ×
891 Cumulative power monitor digit shifted times 5B DB 8 ○ ○ ○ ○ ○ ○ ○
892 Load factor 5C DC 8 ○ ○ ○ ○ ○ ○ ○
893 Energy saving monitor reference (motor capacity) 5D DD 8 ○ ○ ○ ○ ○ ○ ○
Control selection during commercial power-supply
894 5E DE 8 ○ ○ ○ ○ ○ ○ ○
operation
895 Power saving rate reference value 5F DF 8 ○ ○ ○ ○ ○ ○ ○
896 Power unit cost 60 E0 8 ○ ○ ○ ○ ○ ○ ○
897 Power saving monitor average time 61 E1 8 ○ ○ ○ ○ ○ ○ ○
898 Power saving cumulative monitor clear 62 E2 8 ○ ○ ○ ○ ○ × ○
899 Operation time rate (estimated value) 63 E3 8 ○ ○ ○ ○ ○ ○ ○
C0 FM terminal calibration 5C DC 1 ○ ○ ○ ○ ○ × ○
C1 AM terminal calibration 5D DD 1 ○ ○ ○ ○ ○ × ○
C2 Terminal 2 frequency setting bias frequency 5E DE 1 ○ ○ ○ ○ ○ × ○
C3 Terminal 2 frequency setting bias 5E DE 1 ○ ○ ○ ○ ○ × ○
125 Terminal 2 frequency setting gain frequency 5F DF 1 ○ ○ ○ ○ ○ × ○
C4 Terminal 2 frequency setting gain 5F DF 1 ○ ○ ○ ○ ○ × ○
C5 Terminal 4 frequency setting bias frequency 60 E0 1 ○ ○ ○ ○ ○ × ○
C6 Terminal 4 frequency setting bias 60 E0 1 ○ ○ ○ ○ ○ × ○
126 Terminal 4 frequency setting gain frequency 61 E1 1 ○ ○ ○ ○ ○ × ○
C7 Terminal 4 frequency setting gain 61 E1 1 ○ ○ ○ ○ ○ × ○
C38 Terminal 4 bias command (torque/magnetic flux) 20 A0 9 × × ○ ○ ○ × ○
C39 Terminal 4 bias (torque/magnetic flux) 20 A0 9 × × ○ ○ ○ × ○
C40 Terminal 4 gain command (torque/magnetic flux) 21 A1 9 × × ○ ○ ○ × ○
C41 Terminal 4 gain (torque/magnetic flux) 21 A1 9 × × ○ ○ ○ × ○
C42 PID display bias coefficient 22 A2 9 ○ ○ ○ × ○ × ○
C43 PID display bias analog value 22 A2 9 ○ ○ ○ × ○ × ○
C44 PID display gain coefficient 23 A3 9 ○ ○ ○ × ○ × ○
C45 PID display gain analog value 23 A3 9 ○ ○ ○ × ○ × ○
990 Parameter for manufacturer setting. Do not set.
991 Parameter for manufacturer setting. Do not set.
Operation panel setting dial push monitor
992 5C DC 9 ○ ○ ○ ○ ○ ○ ○
selection
997 Fault initiation 61 E1 9 ○ ○ ○ ○ ○ ○ ○
998 PM parameter initialization 62 E2 9 ○ ○ ○ ○ ○ ○ ○
999 Automatic parameter setting 63 E3 9 ○ ○ ○ ○ ○ × ○
1000 Parameter for manufacturer setting. Do not set.
1002 Lq tuning target current adjustment coefficient 02 82 A × × × × ○ ○ ○
All clear*3
Extended
Pr. Name
Magnetic flux
Clear*3
Write
V/F
Read
Torque
Speed
Speed
12
1006 Clock (year) 06 86 A ○ ○ ○ ○ ○ × ×
1007 Clock (month, day) 07 87 A ○ ○ ○ ○ ○ × ×
1008 Clock (hour, minute) 08 88 A ○ ○ ○ ○ ○ × × 13
1015 Integral stop selection at limited frequency 0F 8F A ○ ○ ○ × ○ ○ ○
1020 Trace operation selection 14 94 A ○ ○ ○ ○ ○ ○ ○
1022 Sampling cycle 16 96 A ○ ○ ○ ○ ○ ○ ○
1023 Number of analog channels 17 97 A ○ ○ ○ ○ ○ ○ ○ 14
1024 Sampling auto start 18 98 A ○ ○ ○ ○ ○ ○ ○
1025 Trigger mode selection 19 99 A ○ ○ ○ ○ ○ ○ ○
1026 Number of sampling before trigger 1A 9A A ○ ○ ○ ○ ○ ○ ○ 15
1027 Analog source selection (1ch) 1B 9B A ○ ○ ○ ○ ○ ○ ○
1028 Analog source selection (2ch) 1C 9C A ○ ○ ○ ○ ○ ○ ○
1029 Analog source selection (3ch) 1D 9D A ○ ○ ○ ○ ○ ○ ○
1030 Analog source selection (4ch) 1E 9E A ○ ○ ○ ○ ○ ○ ○ 16
1031 Analog source selection (5ch) 1F 9F A ○ ○ ○ ○ ○ ○ ○
1032 Analog source selection (6ch) 20 A0 A ○ ○ ○ ○ ○ ○ ○
1033
1034
Analog source selection (7ch)
Analog source selection (8ch)
21
22
A1
A2
A
A
○
○
○
○
○
○
○
○
○
○
○
○
○
○
17
1035 Analog trigger channel 23 A3 A ○ ○ ○ ○ ○ ○ ○
1036 Analog trigger operation selection 24 A4 A ○ ○ ○ ○ ○ ○ ○
1037 Analog trigger level 25 A5 A ○ ○ ○ ○ ○ ○ ○ 18
1038 Digital source selection (1ch) 26 A6 A ○ ○ ○ ○ ○ ○ ○
1039 Digital source selection (2ch) 27 A7 A ○ ○ ○ ○ ○ ○ ○
1040
1041
Digital source selection (3ch)
Digital source selection (4ch)
28
29
A8
A9
A
A
○
○
○
○
○
○
○
○
○
○
○
○
○
○
19
1042 Digital source selection (5ch) 2A AA A ○ ○ ○ ○ ○ ○ ○
1043 Digital source selection (6ch) 2B AB A ○ ○ ○ ○ ○ ○ ○
1044 Digital source selection (7ch) 2C AC A ○ ○ ○ ○ ○ ○ ○ 20
1045 Digital source selection (8ch) 2D AD A ○ ○ ○ ○ ○ ○ ○
1046 Digital trigger channel 2E AE A ○ ○ ○ ○ ○ ○ ○
1047 Digital trigger operation selection 2F AF A ○ ○ ○ ○ ○ ○ ○
1103 Deceleration time at emergency stop 03 83 B ○ ○ ○ ○ ○ ○ ○
1106 Torque monitor filter 06 86 B ○ ○ ○ ○ ○ ○ ○
1107 Running speed monitor filter 07 87 B ○ ○ ○ ○ ○ ○ ○
1108 Excitation current monitor filter 08 88 B ○ ○ ○ ○ ○ ○ ○
*4
1124 Station number in inverter-to-inverter link 18 98 B ○ ○ ○ ○ ○ ○ ○*4
Number of inverters in inverter-to-inverter link
1125 19 99 B ○ ○ ○ ○ ○ ○*4 ○*4
system
1150 PLC function user parameters 1 32 B2 B ○ ○ ○ ○ ○ ○ ○
1151 PLC function user parameters 2 33 B3 B ○ ○ ○ ○ ○ ○ ○
1152 PLC function user parameters 3 34 B4 B ○ ○ ○ ○ ○ ○ ○
1153 PLC function user parameters 4 35 B5 B ○ ○ ○ ○ ○ ○ ○
1154 PLC function user parameters 5 36 B6 B ○ ○ ○ ○ ○ ○ ○
1155 PLC function user parameters 6 37 B7 B ○ ○ ○ ○ ○ ○ ○
1156 PLC function user parameters 7 38 B8 B ○ ○ ○ ○ ○ ○ ○
1157 PLC function user parameters 8 39 B9 B ○ ○ ○ ○ ○ ○ ○
1158 PLC function user parameters 9 3A BA B ○ ○ ○ ○ ○ ○ ○
1159 PLC function user parameters 10 3B BB B ○ ○ ○ ○ ○ ○ ○
1160 PLC function user parameters 11 3C BC B ○ ○ ○ ○ ○ ○ ○
1161 PLC function user parameters 12 3D BD B ○ ○ ○ ○ ○ ○ ○
1162 PLC function user parameters 13 3E BE B ○ ○ ○ ○ ○ ○ ○
1163 PLC function user parameters 14 3F BF B ○ ○ ○ ○ ○ ○ ○
1164 PLC function user parameters 15 40 C0 B ○ ○ ○ ○ ○ ○ ○
1165 PLC function user parameters 16 41 C1 B ○ ○ ○ ○ ○ ○ ○
17. Appendix
17.3 Parameters (functions) and instruction codes under different control methods
415
Instruction
Control method*2 Parameter
code*1
Sensorless PM
All clear*3
Extended
Pr. Name
Magnetic flux
Clear*3
Write
V/F
Read
Torque
Speed
Speed
1166 PLC function user parameters 17 42 C2 B ○ ○ ○ ○ ○ ○ ○
1167 PLC function user parameters 18 43 C3 B ○ ○ ○ ○ ○ ○ ○
1168 PLC function user parameters 19 44 C4 B ○ ○ ○ ○ ○ ○ ○
1169 PLC function user parameters 20 45 C5 B ○ ○ ○ ○ ○ ○ ○
1170 PLC function user parameters 21 46 C6 B ○ ○ ○ ○ ○ ○ ○
1171 PLC function user parameters 22 47 C7 B ○ ○ ○ ○ ○ ○ ○
1172 PLC function user parameters 23 48 C8 B ○ ○ ○ ○ ○ ○ ○
1173 PLC function user parameters 24 49 C9 B ○ ○ ○ ○ ○ ○ ○
1174 PLC function user parameters 25 4A CA B ○ ○ ○ ○ ○ ○ ○
1175 PLC function user parameters 26 4B CB B ○ ○ ○ ○ ○ ○ ○
1176 PLC function user parameters 27 4C CC B ○ ○ ○ ○ ○ ○ ○
1177 PLC function user parameters 28 4D CD B ○ ○ ○ ○ ○ ○ ○
1178 PLC function user parameters 29 4E CE B ○ ○ ○ ○ ○ ○ ○
1179 PLC function user parameters 30 4F CF B ○ ○ ○ ○ ○ ○ ○
1180 PLC function user parameters 31 50 D0 B ○ ○ ○ ○ ○ ○ ○
1181 PLC function user parameters 32 51 D1 B ○ ○ ○ ○ ○ ○ ○
1182 PLC function user parameters 33 52 D2 B ○ ○ ○ ○ ○ ○ ○
1183 PLC function user parameters 34 53 D3 B ○ ○ ○ ○ ○ ○ ○
1184 PLC function user parameters 35 54 D4 B ○ ○ ○ ○ ○ ○ ○
1185 PLC function user parameters 36 55 D5 B ○ ○ ○ ○ ○ ○ ○
1186 PLC function user parameters 37 56 D6 B ○ ○ ○ ○ ○ ○ ○
1187 PLC function user parameters 38 57 D7 B ○ ○ ○ ○ ○ ○ ○
1188 PLC function user parameters 39 58 D8 B ○ ○ ○ ○ ○ ○ ○
1189 PLC function user parameters 40 59 D9 B ○ ○ ○ ○ ○ ○ ○
1190 PLC function user parameters 41 5A DA B ○ ○ ○ ○ ○ ○ ○
1191 PLC function user parameters 42 5B DB B ○ ○ ○ ○ ○ ○ ○
1192 PLC function user parameters 43 5C DC B ○ ○ ○ ○ ○ ○ ○
1193 PLC function user parameters 44 5D DD B ○ ○ ○ ○ ○ ○ ○
1194 PLC function user parameters 45 5E DE B ○ ○ ○ ○ ○ ○ ○
1195 PLC function user parameters 46 5F DF B ○ ○ ○ ○ ○ ○ ○
1196 PLC function user parameters 47 60 E0 B ○ ○ ○ ○ ○ ○ ○
1197 PLC function user parameters 48 61 E1 B ○ ○ ○ ○ ○ ○ ○
1198 PLC function user parameters 49 62 E2 B ○ ○ ○ ○ ○ ○ ○
1199 PLC function user parameters 50 63 E3 B ○ ○ ○ ○ ○ ○ ○
1200 AM output offset calibration 00 80 C ○ ○ ○ ○ ○ × ○
Inverter identification enable/disable
1399 63 E3 D ○ ○ ○ ○ ○ ○*4 ○*4
selection
1412 Motor induced voltage constant (phi f) exponent 0C 8C E × × × × ○ × ○
Second motor induced voltage constant (phi f)
1413 0D 8D E × × × × ○ × ○
exponent
1424 Ethernet communication network number 18 98 E ○ ○ ○ ○ ○ ○*4 ○*4
*4
1425 Ethernet communication station number 19 99 E ○ ○ ○ ○ ○ ○ ○*4
1426 Link speed and duplex mode selection 1A 9A E ○ ○ ○ ○ ○ ○*4 ○*4
*4
1427 Ethernet function selection 1 1B 9B E ○ ○ ○ ○ ○ ○ ○*4
1428 Ethernet function selection 2 1C 9C E ○ ○ ○ ○ ○ ○*4 ○*4
1429 Ethernet function selection 3 1D 9D E ○ ○ ○ ○ ○ ○*4 ○*4
1430 Ethernet function selection 4 1E 9E E ○ ○ ○ ○ ○ ○*4 ○*4
Ethernet signal loss detection function
1431 1F 9F E ○ ○ ○ ○ ○ ○*4 ○*4
selection
1432 Ethernet communication check time interval 20 A0 E ○ ○ ○ ○ ○ ○*4 ○*4
1434 Ethernet IP address 1 22 A2 E ○ ○ ○ ○ ○ ○*4 ○*4
1435 Ethernet IP address 2 23 A3 E ○ ○ ○ ○ ○ ○*4 ○*4
All clear*3
Extended
Pr. Name
Magnetic flux
Clear*3
Write
V/F
Read
Torque
Speed
Speed
12
1436 Ethernet IP address 3 24 A4 E ○ ○ ○ ○ ○ ○*4 ○*4
1437 Ethernet IP address 4 25 A5 E ○ ○ ○ ○ ○ ○*4 ○*4
1438 Subnet mask 1 26 A6 E ○ ○ ○ ○ ○ ○*4 ○*4
13
1439 Subnet mask 2 27 A7 E ○ ○ ○ ○ ○ ○*4 ○*4
1440 Subnet mask 3 28 A8 E ○ ○ ○ ○ ○ ○*4 ○*4
1441 Subnet mask 4 29 A9 E ○ ○ ○ ○ ○ ○*4 ○*4 14
1442 Ethernet IP filter address 1 2A AA E ○ ○ ○ ○ ○ *4 *4
○ ○
1443 Ethernet IP filter address 2 2B AB E ○ ○ ○ ○ ○ ○*4 ○*4
1444 Ethernet IP filter address 3 2C AC E ○ ○ ○ ○ ○ ○ *4
○*4 15
1445 Ethernet IP filter address 4 2D AD E ○ ○ ○ ○ ○ ○*4 ○*4
Ethernet IP filter address 2 range
○*4 ○*4
1446
specification
2E AE E ○ ○ ○ ○ ○
16
Ethernet IP filter address 3 range *4 *4
1447 2F AF E ○ ○ ○ ○ ○ ○ ○
specification
Ethernet IP filter address 4 range
1448
specification
30 B0 E ○ ○ ○ ○ ○ ○*4 ○*4 17
Ethernet command source selection IP address
1449 31 B1 E ○ ○ ○ ○ ○ ○*4 ○*4
1
1450
Ethernet command source selection IP address
2
32 B2 E ○ ○ ○ ○ ○ ○*4 ○*4 18
Ethernet command source selection IP address
1451 33 B3 E ○ ○ ○ ○ ○ ○*4 ○*4
3
1452
Ethernet command source selection IP address
34 B4 E ○ ○ ○ ○ ○ ○*4 ○*4
19
4
Ethernet command source selection IP address 3
1453 35 B5 E ○ ○ ○ ○ ○ ○*4 ○*4
range specification
Ethernet command source selection IP address 4 20
1454 36 B6 E ○ ○ ○ ○ ○ ○*4 ○*4
range specification
1455 Keepalive time 37 B7 E ○ ○ ○ ○ ○ ○*4 ○*4
*4
1456 Network diagnosis selection 38 B8 E ○ ○ ○ ○ ○ ○ ○*4
Extended setting for Ethernet signal loss detection
1457 39 B9 E ○ ○ ○ ○ ○ ○*4 ○*4
function selection
1480 Load characteristics measurement mode 50 D0 E ○ ○ ○ ○ ○ ○ ○
1481 Load characteristics load reference 1 51 D1 E ○ ○ ○ ○ ○ ○ ○
1482 Load characteristics load reference 2 52 D2 E ○ ○ ○ ○ ○ ○ ○
1483 Load characteristics load reference 3 53 D3 E ○ ○ ○ ○ ○ ○ ○
1484 Load characteristics load reference 4 54 D4 E ○ ○ ○ ○ ○ ○ ○
1485 Load characteristics load reference 5 55 D5 E ○ ○ ○ ○ ○ ○ ○
1486 Load characteristics maximum frequency 56 D6 E ○ ○ ○ ○ ○ ○ ○
1487 Load characteristics minimum frequency 57 D7 E ○ ○ ○ ○ ○ ○ ○
1488 Upper limit warning detection width 58 D8 E ○ ○ ○ ○ ○ ○ ○
1489 Lower limit warning detection width 59 D9 E ○ ○ ○ ○ ○ ○ ○
1490 Upper limit fault detection width 5A DA E ○ ○ ○ ○ ○ ○ ○
1491 Lower limit fault detection width 5B DB E ○ ○ ○ ○ ○ ○ ○
Load status detection signal delay time / load
1492 5C DC E ○ ○ ○ ○ ○ ○ ○
reference measurement waiting time
17. Appendix
17.3 Parameters (functions) and instruction codes under different control methods
417
Revisions
*The manual number is given on the bottom left of the back cover.
*
Print date Manual number Revision
Dec. 2019 IB(NA)-0600868ENG-A First edition
418 IB-0600868ENG-A
INVERTER
INVERTER
FR-E800
FR-E800
Instruction Manual (Function)
Compact, high functionality inverters
FR-E820-0008(0.1K) to 0330(7.5K)
FR-E840-0016(0.4K) to 0170(7.5K)
FR-E860-0017(0.75K) to 0120(7.5K)
FR-E820-0008(0.1K) to 0330(7.5K)-E
FR-E840-0016(0.4K) to 0170(7.5K)-E
FR-E860-0017(0.75K) to 0120(7.5K)-E
HEAD OFFICE: TOKYO BUILDING 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN