MiCOM P139 TechnicalManual1
MiCOM P139 TechnicalManual1
MiCOM P139 TechnicalManual1
P139/EN M/Ana
Technical Manual
Volume 1 of 2
MiCOM P139
P139/EN M/Ea8
(AFSV.12.10172 D)
Version P139 -307 -411/412/413 -614
Technical Manual
Volume 1 of 2
! Warning
When electrical equipment is in operation dangerous voltage will be present in certain parts of the equipment.
Failure to observe warning notices, incorrect use or improper use may endanger personnel and equipment
and cause personal injury or physical damage.
Before working in the terminal strip area, the device must be isolated. Where stranded conductors are used,
insulated crimped wire end ferrules must be employed.
The signals 'M a i n : B l o c k e d / f a u l t y ' and 'S F M O N : W a r n i n g ( L E D ) ' (permanently assigned to the LEDs
labeled 'OUT OF SERVICE' and 'ALARM') can be assigned to output relays to indicate the health of the
device. Schneider Electric strongly recommends that these output relays are hardwired into the
substation's automation system, for alarm purposes.
Any modifications to this device must be in accordance with the manual. If any other modification is made
without the express permission of Schneider Electric, it will invalidate the warranty, and may render the
product unsafe.
Proper and safe operation of this device depends on appropriate shipping and handling, proper storage,
installation and commissioning, and on careful operation, maintenance and servicing.
For this reason only qualified personnel may work on or operate this device.
The User should be familiar with the warnings in the Safety Guide (SFTY/4LM/G11 or later version), with the
warnings in Chapters 5, 9, 10 and 11 and with the content of Chapter 13, before working on the equipment. If
the warnings are disregarded, it will invalidate the warranty, and may render the product unsafe.
A protective conductor (ground/earth) of at least 1.5 mm2 must be connected to the DHMI protective
conductor terminal to link the DHMI and the main relay case; these must be located within the same
substation.
To avoid the risk of electric shock the DHMI communication cable must not be in contact with hazardous live
parts.
The DHMI communication cable must not be routed or placed alongside high-voltage cables or connections.
Currents can be induced in the cable which may result in electromagnetic interference.
Qualified Personnel
are individuals who
are familiar with the installation, commissioning and operation of the device and of the system to which it is being connected;
are able to perform switching operations in accordance with safety engineering standards and are authorized to energize and de-
energize equipment and to isolate, ground and label it;
are trained in the care and use of safety apparatus in accordance with safety engineering standards;
are trained in emergency procedures (first aid).
Note
The operating manual for this device gives instructions for its installation, commissioning and operation. However, the manual cannot
cover all conceivable circumstances or include detailed information on all topics. In the event of questions or specific problems, do
not take any action without proper authorization. Contact the appropriate Schneider Electric technical sales office and request the
necessary information.
Any agreements, commitments, and legal relationships and any obligations on the part of Schneider Electric, including settlement of
warranties, result solely from the applicable purchase contract, which is not affected by the contents of the operating manual.
3
Changes after going to press
3 Operation 3-1
3.1 Modular Structure 3-1
3.2 Operator-Machine Communication 3-3
3.3 Configuration of the Bay Panel and of the Measured (LOC)* 3-4
Value Panels; Selection of the Control Point
3.4 Serial Interfaces 3-12
3.4.1 PC interface (PC) 3-12
3.4.2 Communication Interface 1 (COMM1) 3-14
3.4.3 Communication Interface 2 (COMM2) 3-23
3.4.4 Communication interface 3 (COMM3) 3-26
3.4.5 Communication Interface IEC 61850 (IEC, 3-31
GOOSE,
GSSE)
3.5 IRIG-B Clock Synchronization (IRIGB) 3-39
3.6 Configuration and Operating Mode of the Binary (INP) 3-40
Inputs
3.7 Measured Data Input (MEASI) 3-42
3.7.1 Direct Current Input on the Analog (I/O) Module Y 3-44
3.7.2 Connecting a Resistance Thermometer 3-49
to the "PT 100 Analog Input" on the Analog (I/O)
Module Y
3.7.3 Connecting Temperature Sensors to the 3-50
Temperature P/C Board (the RTD Module)
3.8 Configuration, Operating Mode, and Blocking of (OUTP) 3-54
the Output Relays
3.9 Measured Data Output (MEASO) 3-57
3.9.1 BCD Measured Data Output 3-60
3.9.2 Analog Measured Data Output 3-65
3.9.3 Output of ‘External’ Measured Data 3-71
3.10 Configuration and Operating Mode of the LED (LED) 3-72
Indicators
________________________
* : Function Group(s), Short Form
4 Design 4-1
4.1 Designs 4-1
4.2 Dimensional Drawings 4-3
4.2.1 Surface-Mounted Case 4-3
4.2.2 Flush Mounted Case 4-4
4.2.3 Device views for Connection of Detachable HMI 4-6
4.3 Modules 4-7
7 Settings 7-1
7.1 Parameter 7-1
7.1.1 Device Identification 7-2
7.1.2 Configuration Parameters 7-6
7.1.3 Function Parameters 7-67
7.1.3.1 Global 7-67
7.1.3.2 General Functions 7-75
7.1.3.3 Parameter Subsets 7-95
7.1.3.4 Control 7-121
7.2 Protection of Increased-Safety Machines 7-130
7.2.1 General 7-130
7.2.2 Restrictive Safety-Oriented Configuration 7-131
9 Commissioning 9-1
9.1 Safety Instructions 9-1
9.2 Commissioning Tests 9-3
10 Troubleshooting 10-1
11 Maintenance 11-1
12 Storage 12-1
Appendix AN-1
Contents AN-2
A Glossary A-1
B List of Signals B-1
C List of Bay Types C-1
D Overview of Changes D-1
The P139 time-overcurrent protection and control device is a one-box solution for
protection and control.
The protection functions available in the device provide selective short-circuit protection,
ground fault protection, and overload protection in medium- and high-voltage systems.
The systems can be operated as impedance-grounded, resonant-grounded, grounded-
neutral or isolated-neutral systems. The multitude of protection functions incorporated
into the device enable the user to cover a wide range of applications in the protection of
cable and line sections, transformers and motors. The relevant protection parameters
can be stored in four independent parameter subsets in order to adapt the protection
device to different operating and power system management conditions.
The control functions are designed for the control of up to six electrically operated
switchgear units equipped with plant status signaling and located in the bay of a
medium-voltage substation (or a high-voltage station with basic topology). The P139
has almost 300 predefined Bay Types stored for selection and it is also possible to load
user-defined bay templates.
The number of external auxiliary devices required is largely minimized by the integration
of binary signal inputs operating from any auxiliary voltage, and versatile relay output
contacts, by the direct connection option for current and voltage transformers, and by the
comprehensive interlocking capabilities. This simplifies the handling of switch bay
protection and control technology from planning to commission.
During operation, the user-friendly interface makes it easy to set the device parameters
and allows safe operation of the substation by preventing non-permissible switching
operations.
The P139 is equipped with a large number of protection and control functions.
These can be individually configured and cancelled.
These features give the user the means to adapt the device to the protection and control
capacity required in a specific application.
The powerful programmable logic provided by the protection device also makes it
possible to accommodate special applications.
50/51 P,Q,N DTOC Definite-time overcurrent protection, four stages, phase selective
(includes negative-sequence overcurrent protection)
51 P,Q,N (IDMT1, IDMT2) Inverse-time overcurrent protection, one stage, phase selective
(includes negative-sequence overcurrent protection)
67 P,N SCDD Short-circuit direction determination
50 SOTF Switch on to fault protection
85 PSIG Protective signaling
79 ARC Auto-reclosing control (three-pole)
25 ASC Automatic synchronism check ( )
67W/YN GFDSS Ground fault direction determination using steady-state values or
admittance evaluation
TGFD Transient ground fault direction determination ( )
37/48/49/
MP Motor protection
49LR/50S/66
49 THERM Thermal overload protection
46 I2> Unbalance protection
27/59/47 V<> Time-Voltage Protection
81 f<> Frequency protection
32 P<> Power directional protection
50BF CBF Circuit breaker failure protection
CBM Circuit breaker supervision
MCMON Measuring-circuit monitoring
LIMIT Limit value monitoring
LOGIC Programmable logic
General Functions
Functions listed in the tables above are self-contained function groups (except for
ILOCK) and can be individually configured or de-configured according to the specific
application requirements. Unused or cancelled function groups are hidden to the user,
thus simplifying the menu.
This concept provides a large choice of functions and makes wide-ranging application of
the protection device possible, with just one model version. On the other hand simple
and clear parameter settings can be made.
In this way the protection and control functions (except for ILOCK) can be included in or
excluded from the configuration; they are arranged on the branch "General Functions" of
the menu tree.
Control functions
Switchgear contact positions are acquired by the through up to 20 binary signal inputs,
that can signal and process a maximum of 10 two-pole contact positions. A maximum of
12 output relays are available to control a maximum of 10 two-pole switchgear units.
Up to 40 operation signals can be acquired though binary signal inputs and they are
processed according to their primary significance (e.g. CB readiness). Each binary
signal input for signals from switchgear and single-pole operations can have the
debouncing and chatter suppression from eight groups assigned, for which the
debouncing and chatter time can be individually set.
A binary signal input is configurable to acquire a binary counter value. The binary
integrated total is stored should the supply voltage fail. Counting continues from the
stored total as the starting value when the device restarts.
The sends control signals only after it has checked the readiness and validity to carry
out such commands, and it then monitors the operating time of the switchgear units. If
the protection device detects that a switchgear unit has failed, it will signal this
information (e.g. by configuration to a LED indicator).
Before a switching command is issued the interlocking logic on the checks if this new
switchgear status corresponds with the bay and station topology. The interlocking logic
is stored in form of bay interlocking, with and without station interlocking, for each Bay
Panel in the default setting. The interlocking conditions can be adapted to the actual bay
and station topology. Interlocking display and operation correspond to the
programmable logic.
When a is included in a station control system the local interlocking can easily be
integrated with the overall system interlocking.
When the device is not included in a station control system then bay interlocking is
applied without station interlocking.
If the bay and station topology are found to be valid the switching command is issued.
If a non-permissible status would result from the switching action then the issuing of
such a switching command is refused and an alarm is issued.
If not all binary outputs are required by the bay type then these vacant binary outputs
can be freely utilized for other purposes.
Besides issuing switching commands binary outputs may also be triggered by persistent
commands.
Global functions
In addition to the listed features, and extensive self-monitoring, the is equipped with the
following global functions:
C o n tro/Mo
l n ito rin g o f u p InterMiCOM Se lf-
Co mmu n ica tio ns COMM1 COMM2 IEC IRIGB R e co rd in g a n d Overload
to 3, o r o p tio n a lly u p to6, Mo n ito rin g
d a ta
sw itch g e a r u n its
a cq u isitio n
Ground Fault
D EV IL OC K to SC AD A / su b sta tio n co n tro l/ R TU / mo d e m ...
via R S4 8 5 o r Fib re Op tics
u sin g IEC 6 0 8 7 0-5 -1 0 1, -1 0 3, Mo d b u s, D N P3,
C o u rie r LIMIT Metering
85 D istu rb a n ce
re sp. via R J4 5 o r Fib re Op tics u sin g IEC 6 1 8 5 0 LOGIC
PSIG
V ref
27 /59 /47 81 32
COUNT SIG_1 CMD _ 1 MEASI MEASO
V<> f<> P<> P139 Feeder Management
a lw a ys w ith VT fu rth e r
a va ila b le in p u ts o p tio n s and Bay Control Unit
Design
The P139 is modular in design. The plug-in modules are housed in a robust aluminum
case and electrically interconnected via one analog p/c board and one digital p/c board.
4 current-measuring inputs
4 or 5 voltage-measuring inputs
8 or 14 output relays, freely-configurable
6 binary signal inputs (opto-coupler) and 6 output relays to control 3 switchgear units
or
12 binary signal inputs (opto-coupler) and 12 output relays to control 6 switchgear
units
4, 8 or 28 additional binary signal inputs with user-definable function assignment
With the maximum number of binary signal inputs and output relays fitted, 10 switchgear
units can be monitored and 6 of these can be electrically controlled.
The nominal currents and nominal voltages of the standard measuring inputs can be set.
As an option, currents and voltages from non-conventional instrument transformers can
be connected to the NCIT module.
The nominal voltage range of the binary signal inputs (opto-coupler) is 24 to 250 V DC.
As an option binary signal input modules with a higher operate threshold are available.
The auxiliary voltage input for the power supply is also designed for an extended range.
The nominal voltage ranges are 48 to 250 V DC and 100 to 230 V AC. As an option
there is a variant available for the lower nominal voltage range 24 V to 36 V DC.
All output relays can be utilized for signaling and command purposes.
The optional (up to 10) inputs for resistance thermometers on the temperature p/c board
are lead-compensated and balanced.
Two selectable measured variables (cyclically updated measured operating data and
stored measured fault data) can be output as a burden-independent direct current via
the two optional 0 to 20 mA outputs. The characteristics are defined by 3 adjustable
interpolation points allowing a minimum output current (4 mA, for example) for slave-side
open-circuit monitoring, knee-point definition for fine scaling, and a limitation to lower
nominal currents (10 mA, for example). Where sufficient output relays are available, a
selectable measured variable can be output in BCD-coded form by contacts.
Using the first of the two communication interfaces (COMM1), the numerical protection
device can be wired either to the substation control system or to a telecontrol system.
The first communication interface is optionally available with a switcheable protocol
(per IEC 60870-5-103, IEC 870-5-101, DNP 3.0, Modbus or Courier) or as an IEC 61850
interface.
External clock synchronization can be accomplished by using the optional IRIG-B input.
A direct link to other MiCOM protection devices can be set up by applying the optional
InterMiCOM interface (COMM3).
2 Technical Data
2.1 Conformity
Notice
Applicable to P139, version -307-411/412/413-614.
Declaration of conformity
(Per Article 10 of EC Directive 72/73/EC.)
The product designated ‘P139 Time-Overcurrent Protection and Control Unit’ has been
designed and manufactured in conformance with the European standards EN 60255-6
and EN 61010-1 and with the ‘EMC Directive’ and the ‘Low Voltage Directive’ issued by
the Council of the European Community.
Installation Position
Vertical ± 30°.
Degree of Protection
Per DIN VDE 0470 and EN 60529 or IEC 529.
IP 52; IP 20 for rear connection space with flush-mounted case.
Weight
40 TE case: Approx. 7 kg
84 TE case: Approx. 11 kg
Terminals
PC interface (X6): EIA RS232 (DIN 41652) connector, type D-Sub, 9-pin
2.3 Tests
Type tests
All tests per EN 60255-6 or IEC 255-6.
Electromagnetic
compatibility (EMC)
Interference Suppression
Per EN 55022 or IEC CISPR 22, Class A.
Insulation
Voltage Test
Per EN 61010-1 and IEC 255-5
2 kV AC, 60 s
Only direct voltage (2.8 kV DC) must be used for the voltage test on the power supply
inputs. The PC interface and the NCIT current and voltage measuring inputs must not be
subjected to the voltage test.
Mechanical robustness
1(**)
Vibration Test
Per EN 60255-21-1 or IEC 255-21-1, test severity class 1
Frequency range in operation: 10 to 60 Hz, 0.035 mm and 60 to 150 Hz, 0.5 g
Frequency range during transport: 10 to 150 Hz, 1 g
Seismic Test
Per EN 60255-21-3 or IEC 60255-21-3, test procedure A, class 1
Frequency range:
5 to 8 Hz, 3.5 mm / 1.5 mm, 8 to 35 Hz, 10 / 5 m/s2, 3 x 1 cycle.
Mechanical robustness
2 (**)
Vibration Test
Per EN 60255-21-1 or IEC 255-21-1, test severity class 2
Frequency range in operation: 10 to 60 Hz, 0.075 mm and 60 to 150 Hz, 1.0 g
Frequency range during transport: 10 to 150 Hz, 2 g
Seismic Test
Per EN 60255-21-3 or IEC 60255-21-3, test procedure A, class 2
Frequency range:
5 to 8 Hz, 7.5 mm / 3.5 mm, 8 to 35 Hz, 20 / 10 m/s2, 3 x 1 cycle.
(**)
Mechanical robustness 2:
Applicable to the following case variants:
Flush mounted case, flush-mounting method 2 (with angle brackets and frame)
Surface-mounted case
Voltage Test
Per IEC 255-5
2.2 kV AC, 1 s
Only direct voltage (2.8 kV DC) must be used for the voltage test on the power supply
inputs.
The PC interface must not be subjected to the voltage test.
Environment
Temperatures
Recommended temperature range: -5°C to +55°C [+23°F to +131°F].
Limit temperature range: -25°C to +70°C [-13°F to +158°F].
Solar Radiation
Direct solar radiation on the front of the device must be avoided.
Measuring inputs
Current Measuring Inputs (conventional)
Nominal current Inom: 1 and 5 A AC (adjustable)
Nominal consumption per phase: < 0.1 VA at Inom
Load rating:
continuous 4 Inom
for 10 s: 30 Inom
for 1 s: 100 Inom
Nominal surge current: 250 Inom
or
Current Measuring Inputs (NCIT)
Per IEC 60044-8
NCIT voltage 22.5 mA at 50 A
or
Voltage Measuring Inputs (NCIT)
Per IEC 60044-7
NCIT voltage 3.25 V / √3 at Vnom,prim / √3
Frequency
Nominal frequency fnom: 50 Hz and 60 Hz (adjustable)
Operating range: 0.95 to 1.05 fnom
Frequency protection: 40 to 70 Hz
Special variants:
VA > switching threshold: VA • 5 mA ± 30 %.
Notes
The standard variant of binary signal inputs (opto couplers) is recommended in most
applications, as these inputs operate with any voltage from 19 V. Special versions with
higher pick-up/drop-off thresholds are provided for applications where a higher switching
threshold is expressly required.
The maximum voltage permitted for all binary signal inputs is 300V DC.
IRIG-B interface
Minimum / maximum input voltage level (peak-peak): 100 mVpp / 20 Vpp.
Input impedance: 33 kΩ at 1 kHz.
Electrical isolation: 2 kV
Resistance thermometer
Resistance thermometer:
Only PT 100 permitted for analog (I/O) module, mapping curve per IEC 75.1
PT 100, Ni 100 or Ni 120 permitted for temperature p/c board (the RTD module)
Value range: -40.0°C to +215.0°C (-40°F to +419°F)
3-wire configuration: max. 20 Ω per conductor
Open and short-circuited input permitted
Open-circuit monitoring: Θ > +215°C and ° < -40°C (Θ > +419°F and ° < -40°F)
Direct Current Output
Output current: 0 to 20 mA
Maximum permissible load: 500 Ω
Maximum output voltage: 15 V
Output relays
Binary I/O module X (6xI, 6xO):
for switchgear control
Rated voltage: 250 V DC, 250 V AC
Continuous current: 8A
Short-duration current: 30 A for 0.5 s
Making capacity: 1000 W (VA) at L/R = 40 ms
Breaking capacity: 0.2 A at 220 V DC and L/R = 40 ms,
4 A at 230 V AC and cosϕ = 0.4
2.6 Interfaces
PC interface
Transmission rate: 300 to 115,200 baud (adjustable)
Communication interface
The communication module can be provided with up to three communication channels,
depending on the module variant. Channel 1 and 3 may either be equipped to connect
wire leads or optical fibers and channel 2 is only available to connect wire leads.
Communication interface 2 can only be operated with the interface protocol based on
IEC 60870-5-103.
Transmission rate: 300 or 57600 baud (adjustable).
Wire Leads
Per RS 485 or RS 422, 2 kV isolation
Distance to be bridged
Point-to-point connection: max. 1200 m
Multipoint connection: max. 100 m
IEC Communication
interface
Wire Leads
IEC 61850-compliant, Ethernet-based communications:
Transmission rate: 10 or 100 Mbit/s
RJ45, 1.5 kV isolation
Maximum distance: 100 m
IRIG-B interface
B122 format
Amplitude modulated signal
Carrier frequency: 1 kHz
BCD- coded variable data (daily)
2.8 Settings
Time-Voltage Protection
Operate time including output relay (measured variable from nominal value to 1.2-fold
operate value or measured variable from nominal value to 0.8-fold operate value):
≤ 40 ms, approx. 30 ms
Reset time (measured variable from 1.2-fold operate value to nominal value or measured
variable from 0.8-fold operate value to nominal value):
≤ 45 ms, approx. 30 ms
Resetting ratio for V<>: 1 to 10 % (adjustable)
2.9 Deviations
Definitions
Reference Conditions
Sinusoidal signals at nominal frequency fnom, total harmonic distortion ≤ 2 %, ambient
temperature 20°C (68°F), and nominal auxiliary voltage VA,nom.
Deviation
Deviation relative to the setting under reference conditions.
Measuring-circuit
monitoring
Operate values Ineg, Vneg
Deviation: ± 3 %
Definite-time and inverse-
time overcurrent protection
Phase and Residual Current Stages
Deviation: ± 5 %
Short-Circuit Direction
Determination
Deviation: ± 10°
Unbalance protection
Deviation: ± 5 %
Time-Voltage Protection
Operate Values
V<>, Vpos<>: ± 1 % (in the range 0.6 to 1.4 Vnom)
VNG>, Vneg>: ± 1 % % (in the range > 0.3 Vnom)
Frequency protection
Operate values f<>
± 30 mHz (fnom = 50 Hz)
± 40 mHz (fnom = 60 Hz)
Power directional
protection
Operate Values P<>, Q<>
Deviation: ± 5 %
Sector angle:
Deviation: 1°
Resistance thermometer
Deviation: ± 2° or ± 1 %
Definitions
Reference Conditions
Sinusoidal signals at nominal frequency fnom, total harmonic distortion ≤ 2 %, ambient
temperature 20°C (68°F), and nominal auxiliary voltage VA,nom.
Deviation
Deviation relative to the setting under reference conditions.
Definite-time stages
Deviation: ± 1% + 20 ms to 40 ms
Inverse-time stages
Deviation when I ≥ 2 Iref:
± 5 % + 10 to 25 ms
for "extremely inverse" IEC characteristics and for thermal overload characteristics:
± 7.5 % + 10 to 20 ms
Definitions
Reference Conditions
Sinusoidal signals at nominal frequency fnom, total harmonic distortion ≤ 2 %, ambient
temperature 20°C (68°F), and nominal auxiliary voltage VA,nom.
Deviation
Deviation relative to the setting under reference conditions.
Operating Data
Measurement
Measuring Input Currents
Deviation: ± 1 %
Load angle
Deviation: ± 1°
Frequency
Deviation: ± 10 mHz
Temperature
Deviation: ± 2°BSc
Fault data
Short-Circuit Current and Voltage
Deviation: ± 3 %
Internal clock
With free running internal clock:
Deviation: < 1 min/month
Time resolution
20 sampled values per period
Residual current
Dynamic range: 16 Inom or 2 Inom
Amplitude resolution:
at Inom = 1 A: 0.98 mArms or 0.12 mArms
at Inom = 5 A: 4.9 mArms or 0.61 mArms
Phase-to-ground voltages
and Neutral-point
displacement voltage
Dynamic range: 150 V
Amplitude resolution: 9.2 mVrms
Overload memory
Number: The 8 most recent overload events
Scope for signals: All signals relevant for an overload event from a total of
1024 different (see Address List: "Overload Memory")
Depth for signals 200 entries per overload event
Fault memory
Number: The 8 most recent faults
Signals
Time resolution: 1 ms
Fault values
Time resolution: 20 sampled values per period
Residual current
Dynamic range: 16 Inom / 2 Inom (adjustable)
Amplitude resolution: 0.98 mA r.m.s / 0.12 mA r.m.s for Inom = 1 A
4.9 mA r.m.s / 0.61 mA r.m.s for Inom = 5 A
Voltages
Dynamic range: 150 V AC
Amplitude resolution: 9.2 mV r.m.s.
The following equation is used to calculate the specifications of a current transformer for
the offset maximum primary current:
( )
Vsat = (R nom + R i ) ⋅ n ⋅ I nom ≥ R op + R i ⋅ k ⋅ I'1, max
with:
Vsat: saturation voltage (IEC knee point)
I'1,max: non-offset maximum primary current, converted to the secondary side
Inom: rated secondary current
n: rated overcurrent factor
k: over-dimensioning factor
Rnom: rated burden
Rop actual connected operating burden
Ri internal burden
The specifications of a current transformer can then be calculated for the minimum
required saturation voltage Vsat as follows:
( )
Vsat ≥ R op + R i ⋅ k ⋅ I'1,max
With
Theoretically, the specifications of the current transformer could be calculated for lack of
saturation by inserting instead of the required over-dimensioning factor k its maximum
value:
k max ≈ 1 + ωT1
with:
ω: system angular frequency
T1: system time constant
If the P139 is to be used for definite-time overcurrent protection, then the over-
dimensioning factor k that is to be selected is primarily a function of the ratio of the
maximum short-circuit current to the set operate value and, secondly, of the system time
constant T1. The required over-dimensioning factor can be read from the empirically
determined curves in Figure 2-1. When inverse-time maximum current protection is
used, the over-dimensioning factor can be taken from Figure 2-2.
10
T1= 10 ms
T1= 25 ms
T1= 50 ms
T1= 250 ms
0.01
1 10 100
I' /I
1,max operate
2-1 Required over-dimensioning factor for definite-time overcurrent protection with fnom = 50 Hz
2-2 Required over-dimensioning factor for inverse-time maximum current protection with fnom = 50 Hz
When the P139 is equipped with a CT/VT-Board with NCIT, non-conventional instrument
transformers per IEC 60044-8 (electronic current transformers) and IEC 60044-7
(electronic voltage transformers) can be connected to the P139 instead of conventional
CTs or VTs.
This feature will enable the user to utilize the advantages that the non-conventional
instrument transformer technology offers and because of the diversity of available
sensors their numbers in the bay may be reduced. Up to five devices can be connected
to one NCIT. (Designing with 200 kΩ terminal resistors is required.)
In addition transformer saturation is avoided and thermal loading of cables and
protection inputs is low because signals are low level/low burden.
*
A A
D D
*option
NCIT_1_EN
2-3 Connecting NCITs to the P139 equipped with a CT/VT-Board with NCIT
The NCIT inputs I1 to I3 on the MiCOM P30 series are designed as follows:
Rated range of the primary phase currents from 50 to 4000 A, adjustable in steps of
50 A (M A I N : I n o m p r i m . N C I T )
Dynamic range of measuring input designed for 25 kA
Optimization of the dynamic range through an internal amplification factor which is
defined by the set rated range
Dynamic range 25 Inom / 100 Inom (setting depends on model) similar to standard
processing of measured values
Residual current measurement IN with the NCIT inputs on the MiCOM P30 range:
Generating the residual current by analog summation in order to obtain the highest
sensitivity for the measurand with its own amplification factor
No individual core balance transformer necessary for the measurement of the
sensitive earth fault (residual current)
Rated range of the primary residual currents from 10 to 800 A, adjustable in steps of
10 A (M A I N : I N , n o m p r i m . N C I T )
X3
4 + +
IA (100 x Inom)
5 + -
IA' (25 x Inom)
1 + +
IB (100 x Inom)
2 + -
IB' (25 x Inom)
7 + +
IC (100 x Inom)
+ -
8
IC' (25 x Inom)
IN (16 x Inom)
IN' (2 x Inom)
NCIT_2_EN
2-4 NCIT inputs on the MiCOM P30 range (dynamic range dependent on model)
V X1
4 +
O
L 5 - V1
B
T +
B 1
A1 -
2 V2
G
E 7 +
8 - V3
X2
V 4
+
O -
LB 5
+
TB 1
Vref
A2 2
-
G +
7
E -
8
NCIT_3_EN
3 Operation
The P139, a numeric device, is part of the MiCOM P 30 family of devices. The device
types included in this family are built from identical uniform hardware modules.
Figure 3-1 shows the basic hardware structure of the P139.
The external analog and binary quantities – electrically isolated – are converted to the
internal processing levels by the peripheral modules T, Y, and X. Commands and
signals generated by the device internally are connected to external plant via contacts
through the binary I/O modules X. The external auxiliary voltage is applied to the power
supply module V, which supplies the auxiliary voltages that are required internally.
Analog data is transferred from the transformer module T via the analog bus module B to
the processor module P. The processor module contains all the elements necessary for
the conversion of measured analog variables, including multiplexers and analog/digital
converters. The analog data conditioned by the analog I/O module Y is transferred to
the processor module P via the digital bus module. Binary signals are fed to the
processor module by the binary I/O modules X via the digital bus module. The
processor handles the processing of digitized measured variables and of binary signals,
generates the protective trip as well as control commands and signals, and transfers
them to the binary I/O modules X via the digital bus module. The processor module also
handles overall device communication. As an option, communication module A can be
mounted on the processor module to provide serial communication with substation
control systems.
The control and display elements of the integrated local control panel and the integrated
PC interface are housed on control module L.
The following interfaces are available for the exchange of information between the user
and the device:
All settings and signals as well as all measurements and control functions are arranged
within the branches of the menu tree following a scheme that is uniform throughout the
device family. The main branches are:
‘Parameters’ branch
All settings are contained in this branch. This branch carries all settings, including the
device identification data, the configuration parameters for adapting the device interfaces
to the system, and the function parameters for adapting the device functions to the
process. All values in this group are stored in non-volatile memory, which means that
the values will be preserved even if the power supply fails.
‘Operation’ branch
This branch includes all information relevant for operation such as measured operating
data and binary signal states. This information is updated periodically and consequently
is not stored. In addition, various controls are grouped here, for example those for
resetting counters, memories and displays.
‘Events’ branch
The third branch is reserved for the recording of events. All information in this group is
therefore stored. In particular, the start/end signals during a fault, the measured fault
data, and the sampled fault waveforms are stored here and can be read out when
required.
Settings and signals are displayed either in plain text or as addresses, in accordance
with the user’s choice. The appendix documents the settings and signals of the P139 in
the form of an ‘address list’. This address list is complete and thus contains all settings,
signals and measured variables used with the P139.
As a rule the local control panel shows the 'Bay Panel' displaying the current switching
states of the switchgear. The configuration of the local control panel also permits the
installation of Measured Value 'Panels’ on the LCD display. Different Panels are
automatically displayed for specific system operating conditions. Priority increases from
normal operation to operation under overload conditions and finally to operation following
a short circuit in the system. Thus the P139 provides the measured data relevant for the
prevailing conditions.
3.3 Configuration of the Bay Panel and of the Measured Value Panels;
Selection of the Control Point (Function Group LOC)
The layout of a bay with its switchgear units is displayed on the Bay Panel. A Bay Panel
usually consists of one Bay Panel image as a standard but after applying the bay editor
from the PC Access Software MiCOM S1 and having loaded a customized Bay Panel it
can be sub-divided into up to eight pages. The graphic LCD also permits the display of
Event and configurable Signal Panels. In addition the P139 offers Measured Value
Panels, which display the measured values relevant at a given time.
During normal power system operation; the Bay Panel or – if activated – the Operation
Panel is displayed. If the Operation Panel is activated as an event occurs, the display
switches to the appropriate Event Panel – provided that measured values have been
selected for the Event Panels. In the event of overload or ground fault events, the
display will automatically switch to the Operation Panel at the end of the event. In the
event of a fault, the Fault Panel remains active until the LED indicators or the fault
memories are reset.
Bay Panel
The P139 offers a selection from pre-defined bay types. Should the required bay type
be missing from the standard selection then the user can contact the manufacturer of the
P139 to request the definition of a customized bay type to download into the P139.
By applying the bay editor from the PC Access Software MiCOM S1 the user can also
define new bay types. The number of this additional bay type will then be displayed at
MAIN: Customized bay type.
The Bay Panel displays the up-to-date switching status of the selected bay as a single
line (phase) diagram. The activation of the Bay Panel display is described in the
Chapter entitled "Local Control Panel". The user can switch between two character sets
to represent the switchgear units on the Bay Panel display. The character sets are also
described in Chapter "Local Control Panel". Each external device represented in the
Bay Panel is identified by an external device designation as selected by the user. The
user can also select the designations for busbars and busbar sections. The display of
external device designations can be deactivated. The display of the control point (local
or remote control) and interlocking can also be deactivated.
The switchgear unit to be controlled needs to be selected first. The selection is valid for
the set time L O C : R e t u r n t i m e s e l e c t .
The measured values that will be displayed on the Bay Panel can first be selected
separately for the numerical and the bar chart display by an "m out of n" parameter.
Measured values to be displayed in bar chart form must also be selected for display as
numerical measured values. However, not all measured values that can be displayed in
numerical form can also be displayed in bar chart form. In such cases, a dummy or
placeholder must be included in the selection list for the bar chart display at the same
point at which a measured value that cannot be displayed in bar chart form appears in
the selection list for numerical measured values.
For the bar chart display, the orientation of the bar and the scaling can be selected (the
latter separately for the current and voltage data). Display of the scaling can be
deactivated.
Signal Panel
The Signal Panel is displayed when it is selected and when at least one signal has been
configured. From all physical and logical binary states that the device has available up
to 28 signals can be selected for display on the Signal Panel by an "m out of n"
parameter. This occurs without influencing the Event Panel, which is additionally
available. When more signals are selected for display than the LC display can
accommodate, then the display will switch to the next set of signals at intervals defined
by the setting at L O C : P a n e l H o l d - T i m e or when the appropriate key on the local
control panel is pressed. If automatic switching to the Signal Panel is configured at
L O C : A u t . a c t i v . S i g n . P a n e l then the Signal Panel is automatically selected
when there is a change of state for a signal configured in the panel.
Signal
m out of n
Signal
Signal LOC: Autom. LOC: Autom.
return time
return time
Signal
LOC: Hold-time LOC: Hold-time
Selected signals for Panels for panels
LOC: Aut.activ.
LOC: Indicat.Sign. Sign.Panel
Panel
LOC: Stat.ind.
Sign.Panel
no signal.
flash. panel LOC: Sign.caus.
Sign.Panel
flash. lines
Selection
C
LOC: Chg.Sig.
Panel stat.
Sig. Panel
LOC:Chg.Sig.
Panel flash.
Operation Panel
The Operation Panel is displayed when it is selected and when at least one measured
value has been configured. The user can select which of the measured operating values
will be displayed on the Operation Panel by means of an ‘m out of n’ parameter. If more
measured values are selected for display than the LC display can accommodate, then
the display will switch to the next set of values at intervals defined by the setting at
L O C : H o l d - T i m e f o r P a n e l s or when the appropriate key on the local control panel
is pressed.
LOC: Fct.
Operation Panel
[ 053 007 ]
FT_RC: Record.
in progress
[ 035 000 ]
S1 1 ≥1 C
R1
OL_RC: Record.
in progress ≥1
[ 035 003 ] Operation Panel
GF_RC: Record.
in progress
[ 035 005 ]
MAIN: General
reset USER
[ 003 002 ]
1: execute ≥1
MAIN: General
reset EXT
[ 005 255 ]
FT_RC: Reset
record. USER
[ 003 006 ]
1: execute
FT_RC: Reset
record. EXT
[ 005 243 ]
MAIN: Reset LED
306 020
50Z01CXA_EN
Fault panel
The Fault Panel is displayed in place of another data panel when there is a fault,
provided that at least one measured value has been configured. The Fault Panel
remains on display until the LED indicators or the fault memories are cleared.
The user can select the measured fault values that will be displayed on the Fault Panel
by setting an 'm out of n' parameter. If more measured values are selected for display
than the LC display can accommodate, then the display will switch to the next set of
values at intervals defined by the setting at L O C : H o l d - T i m e fo r P a n e l s or when
the appropriate key on the local control panel is pressed.
Selected meas.values
LOC: Hold-time
for Panels
[ 031 075 ]
R
MAIN: General
reset USER
[ 003 002 ]
1: execute ≥1 Fault Panel
MAIN: General
reset EXT
[ 005 255 ]
FT_RC: Reset
record. USER
[ 003 006 ]
1: execute
FT_RC: Reset
record. EXT
[ 005 243 ]
MAIN: Reset LED
306 020
50Z01EJA_EN
The user can select the measured values that will be displayed on the Ground Fault
Panel by setting a 'm out of n' parameter. If more measured values are selected for
display than the LC display can accommodate, then the display will switch to the next set
of values at intervals defined by the setting at L O C : H o l d - T i m e fo r P a n e l s or when
the appropriate key on the local control panel is pressed.
Selected
measured values
LOC: Hold-time
for Panels
[ 031 075 ]
R
MAIN: General
reset USER
[ 003 002 ]
1: execute ≥1 Ground Fault Panel
MAIN: General
reset EXT
[ 005 255 ]
GF_RC: Reset
record. USER
[ 100 000 ]
1: execute
GF_RC: Reset
record. EXT
[ 005 242 ]
MAIN: Reset
LED
306 020
50Z0139 B_EN
Overload Panel
The Overload Panel is automatically displayed in place of another data panel when there
is an overload, provided that at least one measured value has been configured. The
Overload Panel remains on display until the overload ends, unless a fault occurs. In this
case the display switches to the Fault Panel.
The user can select the measured values that will be displayed on the Overload Panel
by setting a 'm out of n' parameter. If more measured values are selected for display
than the LC display can accommodate, then the display will switch to the next set of
values at intervals defined by the setting at L O C : H o l d - T i m e fo r P a n e l s or when
the appropriate key on the local control panel is pressed.
LOC: Fct.
Overload Panel
[ 053 005 ]
50Z0140 A_EN
If only remote control is enabled then there will be a local access blocking. If only local
control is enabled then there will be a remote access blocking.
LOC: Rem.acc.
block.active
Local LOC: Loc.acc.
Remote block.active
Remote & Local LOC:Remote&
local control
MAIN: Inp.asg
L/R key sw.
Signal
Signal
Signal
Signal
Without function
Selected signal
If the communication module A with two communication channels is installed, settings for
two communication interfaces will be available. The setting of communication interface 1
(COMM1) may be assigned to the physical communication channels 1 or 2 (see section
"Main Functions"). If the COMM1 settings have been assigned to communication
channel 2, then the settings of communication interface 2 (COMM2) will automatically be
active for communication channel 1. Communications channel 2 can only be used to
transmit data to and from the P139 if its PC interface has been de-activated. As soon as
the PC interface is used to transmit data, communications channel 2 becomes "dead".
If tests are run on the P139, the user is advised to activate the test mode. In this way the
PC or the control system will recognize all incoming test signals accordingly (see section
"Main Functions").
Communication between the device and a PC is through the PC interface. In order for
data transfer between the P139 and the PC to function, several settings must be made in
the P139.
There are several different interface protocols available at the communication interface 1.
The following user-selected interface protocols are available for use with the P139:
In order for data transfer to function properly, several settings must be made in the P139.
COMM1: IEC
870-5-103
[ 003 219 ]
COMM1: General
enable USER
[ 003 170 ]
1: yes
COMM1: Command
blocking
[ 003 174 ]
COMM1: Sig./
meas.block.USER
[ 003 076 ]
0
1
0: No COMM1: Sig./
1: Yes meas.val.block.
[ 037 075 ]
COMM1: Sig./meas.
block EXT
[ 037 074 ]
MAIN: Prot. ext.
disabled
[ 038 046 ]
12Z62FFA_EN
3-11 Communication interface 1, settings for the IEC 60870-5-103 interface protocol
3-12 Communication interface 1, settings for the IEC 870-5-101 interface protocol
Checking spontaneous
signals
For interface protocols based on IEC 60870-5-103, IEC 870-5-101, or ILS_C it is
possible to select a signal for test purposes. The transmission of this signal to the control
station as ‘sig. start‘ or ‘sig. end‘ can then be triggered via setting parameters.
In order for data transfer to function properly, several settings must be made in the P139.
Checking spontaneous
signals
It is possible to select a signal for test purposes. The transmission of this signal to the
control station as ‘sig. start‘ or ‘sig. end‘ can then be triggered via setting parameters.
Spontan.
signal start
Spontan.
signal end
Application
Communication interface 3 is designed to establish a digital communication link between
two MiCOM devices over which up to 8 binary protection signals may be transmitted.
Whereas communication interfaces 1 and 2 are designed as information interfaces to
connect to data acquisition subsystems and for remote access, communication
interface 3 is designed as a protection signaling interface that will transmit real time
signals (InterMiCOM protection signaling interface). Its main application is to transmit
signals from protective signaling (function group PSIG). In addition, any other internal or
external binary signals may also be transmitted.
Physical medium
COMM3 is provided as an asynchronous, full-duplex communication interface.
To transmit data the following physical media are available:
Digital network:
Asynchronous data interface of primary multiplexing equipment
Telegram configuration
The communication baud rate is settable (C O M M 3 : B a u d r a t e ) to adapt to the
transmission channel requirements. Sending and receiving addresses
(C O M M 3 : S o u r c e a d d r e s s and C O M M 3 : R e c e i v i n g a d d r e s s can be set
to different values, thus avoiding that the device communicates with itself.
Binary signals 1 to 4:
Operating mode settable to 'Blocking' or 'Direct intertrip'
Binary signals 5 to 8:
Operating mode settable to 'Permissive' or 'Direct intertrip'
Speed
fast
Blocking
Permissive
slow
low
high high
Direct
Security Intertrip Dependability
47Z1030A_EN
3-20 Comparison of speed, security and dependability offered by the three operating modes.
Communication monitoring
Timer stage C O M M 3 : T i m e - o u t c o m m . f a u l t is used for monitoring the
transmission channel (this timer is re-triggered with each complete and correct received
telegram). The wide setting range allows adaptation to the actual channel transmission
times and above all this is needed for time-critical schemes such as the blocking
scheme. After the timer has elapsed, signals C O M M 3 : C o m m u n i c a t i o n s f a u l t
and
S F M O N : C o m m u n i c . f a u l t C O M M 3 are issued and the received signals are
automatically set to their user-defined default values
(C O M M 3 : D e f a u l t v a l u e r e c . x , with x = 1 to 8). As the main application for this
protective signaling the fault signal may be mapped to the corresponding input signal in
function group PSIG with the C O M M 3 : S i g . a s g . c o m m . f a u l t setting.
Message
received
Blocking signals
accepted
Permissive signals
accepted
(Re-)Trigger
COMM3: Time-out
comm.fault
[120 033]
COMM3:
1 Communications
fault
[120 043]
COMM3: Time-out
link fail
[120 035]
47Z1031 B_EN
Supervision of
communication
link quality
After a syntax check of each received message, InterMiCOM updates the ratio of
incorrectly received messages, based on a total of the last 1000 received messages.
The result is provided as an updating measurand C O M M 3 : N o . t e l . e r r o r s p . u .
and the overall maximum ratio can be read from
COMM3: No.t.err.,max,stored.
If the set threshold C O M M 3 : L i m i t t e l e g r . e r r o r s is exceeded the
corresponding signals C O M M 3 : L i m . e x c e e d . , t e l . e r r .
and S F M O N : L i m . e x c e e d . , t e l . e r r . will be issued. All corrupted telegrams are
counted (C O M M 3 : N o . t e l e g r a m e r r o r s ) . This counter as well as the stored
maximum ratio of corrupted messages can be reset via
C O M M 3 : Rset.No.tlg.err.USER (as well as via the binary signal C O M M 3 : Reset
No.tlg.err.EXT).
Commissioning tools
The actual values of send and receive signals can be read from the device as physical
state signals (C O M M 3 : S t a t e s e n d x and C O M M 3 : S t a t e r e c e i v e x , with
x = 1 to 8). In addition, InterMiCOM provides 2 test facilities for commissioning of the
protection interface.
For a loop-back test, the send output is directly linked back to the receive input.
After setting the bit pattern wanted (as an equivalent decimal number at
C O M M 3 : L o o p b a c k s e n d ) the test can be triggered via
C O M M 3 : L o o p b a c k t e s t . This bit pattern is sent for the duration of the hold time
set at C O M M 3 : H o l d t i m e f o r t e s t . For this test only, the source address is set
to '0'; this value is not used for regular end-to-end communication. The test result can
be checked as long as the hold-time is running by reading the measured operating data
C O M M 3 : L o o p b a c k r e s u l t and C O M M 3 : L o o p b a c k r e c e i v e . As soon
as the hold-time has expired, the loopback test is terminated and InterMiCOM reverts to
the normal sending mode (e.g. sending the actual values of the configured send signals,
using the set source address).
Thus, in case of problems with the InterMiCOM protection signaling interface, the
loopback test can be used to verify or to exclude a defective device. The transmission
channel including the receiving device can be checked manually by setting individual
binary signals
(C O M M 3 : S e n d s i g n a l f o r t e s t ) to user-defined test values
(C O M M 3 : L o g . s t a t e f o r t e s t ). After triggering the test by
C O M M 3 : S e n d s i g n a l , t e s t , the preset binary signal is sent with the preset value
for the set hold time C O M M 3 : H o l d t i m e f o r t e s t . The 7 remaining binary
signals are not affected by this test procedure and remain to be sent with their actual
values. During the hold time, a received signal can be checked at the receiving device,
e.g. by reading the physical state signal. After the hold time has expired, the test mode
is reset automatically and the actual values of all 8 signals are transmitted again.
The IEC 61850 communication protocol is implemented by these function groups and
the Ethernet module.
Note:
Function group IEC is only available as an alternative to function group COMM1
(hardware ordering option!).
3.4.5.1 Communication Interface IEC 61850 (Function Group IEC)
As a further option the P139 now includes an interface protocol according to the Ethernet
based communication standard IEC 61850.
IEC 61850
IEC 61850 was created jointly by users and manufacturers as an international standard.
The main target of IEC 61850 is interoperability of devices. This includes the capability
of two or more intelligent electronic devices (IED), manufactured by the same company
or different companies, to exchange data for combined operation.
Now this new communication standard IEC 61850 has created an open and common
basis for communication from the process control level down to the network control level,
for the exchange of signals, data, measured values and commands.
For a standardized description of all information and services available in a field device a
data model, which lists all visible functions, is created. Such a data model, specifically
created for each device, is used as a basis for an exchange of data between the devices
and all process control installations interested in such information. In order to facilitate
engineering at the process control level a standardized description file of the device,
based on XML, is created with the help of the data model. This file can be imported and
processed further by the relevant configuration program used by the process control
device. This makes possible an automated creation of process variables, substations
and signal images.
The following documentation with the description of the IEC 61850 data model, used
with the P139, is available:
IDC file based on XML in the SCL (Substation Configuration Description Language)
with a description of data, properties and services, available from the device, that are
to be imported into the system configurator.
PICS_MICS_ADL file with the following contents:
PICS (Protocol Implementation Conformance Statement) with an overview of
available services.
MICS (Model Implementation Conformance Statement) with an overview of
available object types.
ADL (Address Assignment List) with an overview of the assignment of parameter
addresses (signals, measuring values, commands, etc.) used by the device with
the device data model as per IEC 61850.
Ethernet Module
The optional Ethernet module provides an RJ45 connection and a fiber optic interface
where an Ethernet network can be connected. The selection which of the two interfaces
is to be used to connect to the Ethernet network is made by setting the parameter
I E C : E t h e r n e t m e d i a . For the optical interface on the Ethernet communications
module the user may either select the ordering option ST connector or SC connector
with 100 Mbit/s and 1300 nm. The RJ45 connector supports 10 Mbit/s and 100 Mbit/s.
The optional Ethernet module additionally provides an RS485 interface for remote
access with the operating program MiCOM S1 (function group COMM2).
Notes: The P139 may only be equipped with the optional Ethernet module as an
alternative to the standard optional communication module. Therefore the
Ethernet based communication protocol IEC 61850 is only available as an
alternative to function group COMM1.
The parameter settings for function groups IEC, GOOSE and GSSE in the device are not
automatically activated. An activation occurs either when the command I E C : E n a b l e
c o n f i g u r a t i o n is executed or automatically when the device is switched online with
MAIN: Device on-line.
Client Log-on
Communication in Ethernet no longer occurs in a restrictive master slave system, as is
common with other protocols. Instead server or client functionalities, as defined in the
'Abstract Communication Service Interface' (ACSI, IEC 61870-7-2), are assigned to the
devices. A 'server' is always that device which provides information to other devices.
A client may log-on to this server so as to receive information, for instance 'reports'.
In a network a server can supply any number of clients with spontaneous or cyclic
information.
In its function as server the P139 can supply up to 16 clients with information.
Clock Synchronization
With IEC 61850 clock synchronization occurs via the SNTP protocol, defined as
standard for Ethernet. Here the P139 functions as a SNTP client.
For clock synchronization one can select between the operating modes Broadcast from
SNTP Server or Request from Server. With the first operating mode synchronization
occurs by a broadcast message sent from the SNTP server to all devices in the network,
and in the second operating mode the P139 requests the device specific time signal
during a settable cycle.
Two SNTP servers may be set. In this case, clock synchronization is preferably
performed by the first server. The second server is used only when messages are no
longer received from the first server.
When looking at the source priority for clock synchronization, which is set at the MAIN
function then, by selecting "COMM1", synchronization per IEC 61850 is automatically
active but only if this communication protocol is applied.
Control and Monitoring of
Switchgear Units
Control of switchgear units (external devices) by the P139 can be carried out from all
clients that have previously logged-on to the device. Only one control command is
executed at a time, i.e. further control requests issued by other clients during the
execution of such a command are rejected. To control external devices the following
operating modes can be set at
IEC: DEV control model:
Control service mode
Direct enh. security (Direct control with enhanced security)
SBO enh. security (SBO [Select before operate] with enhanced security)
When set to the operating mode Select before operate the switchgear unit is selected by
the client before the control command is issued. Because of this selection the
switchgear unit is reserved for the client. Control requests issued by other clients are
rejected. If, after a selection no control command is issued by the client, the P139 resets
this selection after 2 minutes have elapsed.
The switchgear units’ contact positions signaled to the clients are made with the Report
Control Blocks of the switchgear units.
Fault Transmission
Transmission of fault files is supported per "File Transfer".
Transmission of "Goose
Messages"
The so-called "Goose Message" is a particular form of data transmission. Whereas
normal server-client-services are transmitted at the MMS and TCP/IP level, the "Goose
Message" is transmitted directly at the Ethernet level with a high transmission priority.
Furthermore these "Goose Messages" can be received by all participants in the
respective sub-network, independent of their server or client function. In IEC 61850
"Goose Messages" are applied for the accelerated transmission of information between
two or more devices. Application fields are, for example, a reverse interlocking, a
transfer trip or a decentralized substation interlock. In future the "Goose Message" will
therefore replace a wired or serial protective interface.
According to IEC 61850 there are two types of "Goose Messages", GSSE and
IEC-GOOSE. The GSSE is used to transmit binary information with a simple
configuration by 'bit pairs', and it is compatible with UCA2. However IEC-GOOSE
enables transmission of all data formats available in the data model, such as binary
information, integer values or even analog measured values. But this will require more
extensive configuration with the help of the data model from the field unit situated on the
opposite side. With IEC-GOOSE the P139 at this time supports sending and receiving of
binary information or two-pole external device states.
Communication with the
Operating Program
MiCOM S1 via the Ethernet
Interface
Direct access by the operating program MiCOM S1 via the Ethernet interface on the
device may occur through the "tunneling principle". Transmission is carried out by an
Ethernet Standard Protocol, but this is only supported by the associated operating
program MiCOM S1 (specific manufacturer solution). Such transmission is
accomplished over the same hardware for the network, which is used for server-client
communication and "Goose Messages".
Available are all the familiar functions offered by the operating program MiCOM S1 such
as reading/writing of setting parameters or retrieving stored data.
The various settings, measured values and signals for function group IEC are described
in chapters 7 and 8.
The parameter settings for function groups IEC, GOOSE and GSSE in the device are not
automatically activated. An activation occurs either when the command I E C : E n a b l e
c o n f i g u r a t i o n is executed or automatically when the device is switched online with
M A I N : D e v i c e o n - l i n e . In addition function group IEC must be configured and
enabled.
Sending GOOSE
With GOOSE up to 32 logic binary state signals and up to 3 two-pole states from the
maximum of 3 possible external devices associated to the P139 can be sent. Selection of
binary state signals is made by setting G O O S E : O u t p u t n f c t . a s s i g . (n = 1 to 32).
The up to 3 two-pole states of the external devices are a fixed part of GOOSE for which
there is no necessity to set parameters. The assignment of data object indexes to logic
state signals is made in the range from 1 to 32 according to the assignment to GOOSE
outputs. The two-pole state signals from external devices 1 to 3 receive a permanent
assignment of data object indexes in ascending order from 33 to 35.
GOOSE is automatically sent with each new state change of a configured binary state
signal or an external device. There are numerous send repetitions in fixed ascending
time periods (10 ms, 20 ms, 50 ms, 100 ms, 500 ms, 1000 ms, 2000 ms). If after
2 seconds there is no further state change apparent, GOOSE is then sent cyclically at
2-second intervals.
In order to have unambiguous identification of GOOSE sent, characteristics such as the
Goose ID number, MAC address, application ID and VLAN identifier must be entered
through parameter settings. Further characteristics are the 'Dataset Configuration
Revision' with the fixed value "100" as well as the 'Dataset Reference', which is made up
of the IED name (setting in function group IEC) and the fixed string
"System/LLNO$GooseST".
VLAN Identifier: 0
VLAN Priority: 4
Application ID : 12288
49Z6101B _EN
Receiving GOOSE
With GOOSE up to 16 logic binary state signals and the two-pole contact position signals
from up to 16 external devices can be received. Configuration of the logic state signals
received (G O O S E : I n p u t n f c t . a s s i g . (n = 1 to 16)) is made on the basis of the
selection table of the binary inputs (opto coupler inputs). Contact position signals
received from external devices are listed in the selection table for interlocking equations
of the function group ILOCK, which are available to design a decentralized substation
interlock.
For each state or contact position signal to be received from an external device the
"Goose Message" must be selected that includes the information wanted by setting the
Goose ID, the Application ID and the 'Dataset Reference'. With the further setting of the
data object index and the data attribute index through parameters, the required
information from the chosen GOOSE will be selected. The device will not evaluate the
identification features VLAN identifier and ‘Dataset Configuration Revision’ that are also
included in the GOOSE received.
Each GOOSE includes time information on the duration of validity of its information.
This corresponds to the double time period to the next GOOSE repetition. If the duration
of validity has elapsed without having received this GOOSE again (i.e. because of a
communications fault), the received signals will automatically be set to their respective
default values G O O S E : I n p u t n d e f a u l t or G O O S E : E x t . D e v n d e f a u l t
(n = 1 to 16).
The various settings, measured values and signals for function group GOOSE are
described in chapters 7 and 8.
The parameter settings for function groups IEC, GOOSE and GSSE in the device are not
automatically activated. An activation occurs either when the command I E C : E n a b l e
c o n f i g u r a t i o n is executed or automatically when the device is switched online with
M A I N : D e v i c e o n - l i n e . In addition the function group IEC must be configured and
enabled.
Sending GSSE
With GSSE up to 32 logic binary state signals can be sent. Selection of binary state
signals is made by setting
G S S E : O u t p u t n f c t . a s s i g . (n = 1 to 32). Each selected state signal is to be
assigned to a bit pair in GSSE (G S S E : O u t p u t n b i t p a i r (n = 1 to 32)), which will
transmit this state signal.
GSSE is automatically sent with each state change of a selected state signal. There will
be multiple send repetitions at ascending time periods. The first send repetition occurs
at the given cycle time set with the parameter G S S E : M i n . c y c l e . The cycles for
the following send repetitions result from a conditional equation with the increment set
with the parameter G S S E : I n c r e m e n t . Should no further state changes occur up to
the time when the maximum cycle time has elapsed (G S S E : M a x . c y c l e ) , then
GSSE will be sent cyclically at intervals as set for the max. cycle time.
In order to have unambiguous identification of a GSSE sent, the IED name is used which
was set in function group IEC.
Receiving GSSE
With GSSE up to 32 logic binary state signals can be received. Configuration of the
logic binary state signals received
(G S S E : I n p u t n f c t . a s s i g . (n = 1 to 32))
is made on the basis of the selection table of the binary inputs (opto coupler inputs).
For each state signal to be received, the GSSE message, which will include the required
information, must be selected by setting the IED name (G S S E : I E D n a m e ) .
Selection of information wanted from the selected GSSE will occur by setting the bit pair
(G S S E : B i t p a i r ) .
Each GSSE includes time information on the duration of validity of its information.
This corresponds to the double time period to the next GSSE repetition. If the duration
of validity has elapsed without having received this GSSE again (i.e. because of a
communications fault), the signals received will automatically be set to their respective
default value ( G S S E : I n p u t n d e f a u l t (n = 1 to 32)).
The various settings, measured values and signals for function group GOOSE are
described in chapters 7 and 8.
If, for example, a GPS receiver with IRIG-B connection is available, the internal clock of
the P139 can be synchronized to run on GPS time using the optional IRIG-B interface.
It should be noted that the IRIG-B signal holds information on the day only (day of the
current year). Using this information and the year set at the P139, the P139 calculates
the current date (DD.MM.YY).
Synchronization readiness
If the IRIG-B interface is enabled and receiving a signal, the P139 checks the received
signal for plausibility. Implausible signals are rejected by the P139. If the P139 does not
receive a correct signal in the long run, synchronization will not be ready any longer.
3.6 Configuration and Operating Mode of the Binary Inputs (Function Group INP)
The P139 has opto coupler inputs for processing binary signals from the substation.
The functions that will be activated in the P139 by triggering these binary signal inputs
are defined by the configuration of the binary signal inputs. In order to ensure that
during normal operation the P139 will recognize an input signal, it must persist for at
least 20 ms. With the occurrence of a general starting this time period may have to be
increased to 40 ms under unfavorable conditions.
In this manual, we assume that the required functions (marked 'EXT' in the address
description) have been assigned to binary signal inputs by configuration.
Filter function
An additional filter function may be enabled in order to suppress transient interference
peaks at the logic signal inputs (operating modes Active 'high', filt. or Active 'low', filt.).
With this function enabled a status change at the binary logic input is only signaled when
the input signal remains at a steady signal level during a set number of sampling steps
(sampling step size = period / 20). The number of sampling steps is set at parameter
INP: Filter.
INP: Fct.assignm.
Uxx
[ XXX XXX ]
Function 1 EXT
Function 2 EXT
Function 3 EXT
Function n EXT
2
3
0: active "Low"
1: active "High"
2: active "Low", filt.
3: active "High",filt.
-Uxxx
&
Input signal
&
INP: Control
& U xxx
[ ZZZ ZZZ ]
&
12Z6213 A_EN
There is a second optional analog module available for the P139. In addition to the
analog (I/O) module Y with analog inputs and outputs there is now a second analog
module obtainable, the temperature p/c board (also called the RTD module).
When the P139 is equipped with the analog (I/O) module Y it has two analog inputs
available for measured data input. Direct current is fed to the P139 through the 20 mA
analog input (input channel 1). The other input is designed for connection of a PT 100
resistance thermometer.
The temperature p/c board (the RTD module) mounted in the P139 has 9 analog inputs
available to connect temperature sensors T1 to T9. These analog inputs are designed
for connection of PT 100, Ni 100 or Ni 120 resistance thermometers.
The input current IDC present at the analog (I/O) module Y is displayed as a measured
operating value. The current that is conditioned for monitoring purposes (IDC,lin) is also
displayed as a measured operating value. In addition, it is monitored by the Limit Value
Monitoring function to detect whether it exceeds or falls below set thresholds (see "Limit
Value Monitoring").
The measured temperatures are also displayed as measured operating values and
monitored by the Limit Value Monitoring function to determine whether they exceed or
fall below set thresholds (see "Limit Value Monitoring").
All measured variables are also forwarded to the Thermal Overload Protection function.
With this protection it is possible to set whether the PT 100 resistance thermometer, the
20 mA analog input or – if configured – one of the temperature sensors T1 to T9 is to be
used for the thermal replica (see "Thermal Overload Protection").
When setting the characteristic the user must remember that only a rising/rising or
falling/falling curve sense is allowed (no peak or vee-shapes). If the setting differs, the
signal S F M O N : I n v a l i d s c a l i n g I D C will be generated.
IDClin / IDC,nom
1.2
1.1
1
IDClin20
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
IDClin1 0
0 0.1 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.6 IDC/ IDC,nom
IDC1 IDC20
D5Z52KDA
19Z5266A_EN
IDClin / IDC,nom
0.8
Interpolation points
IDC,lin20 0.7
0.6
IDC,lin4 0.5
0.4
IDC,lin3 0.3
IDC,lin2 0.2
IDC,lin1 0.1
0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2
3-27 Example of a characteristic with five interpolation points (characteristic with zero suppression setting of 0.1 IDC,nom is shown as a broken
line)
Zero suppression
Zero suppression is defined by setting M E A S I : E n a b l e I D C p . u . If the direct
current does not exceed the set threshold, the per-unit input current IDC p.u. and the
current IDC,lin will be displayed as having a value of ‘0’.
The input current is monitored in order to protect the 20 mA analog input against
overloading. If it exceeds the set threshold of 24.8 mA, the signal
M E A S I : O v e r l o a d 2 0 m A i n p u t is issued.
Backup sensors
The open circuit signal on the 20 mA analog input from the function group MEASI is
forwarded to the Thermal Overload Protection function. Here it is possible to set
whether the resistance thermometer connected to the PT 100 input or – if configured –
one of the temperature sensors T1 to T9, connected to the temperature p/c board (the
RTD module), is to be used as a backup sensor (see "Thermal Overload Protection").
Beyond the linearization described above, the user has the option of scaling the
linearized values. Thereby negative values, for example, can be displayed as well and
are available for further processing by protection functions.
3.7.2 Connecting a Resistance Thermometer to the "PT 100 Analog Input" on the
Analog (I/O) Module Y
This analog input on the analog (I/O) module Y is designed to connect a PT 100
resistance thermometer. The mapping curve R = f(T) of PT 100 resistance
thermometers is defined in standard IEC 751. If the PT 100 resistance thermometer is
connected using the 3-wire method, then no further calibration is required.
Open-circuit monitoring
If there is an open measuring circuit due to a broken wire, the signal M E A S I : O p e n
c i r c . P T 1 0 0 is issued.
MEASI: Enabled
SFMON: PT100
open circuit
MEASI: Temperature
T
MEASI: Temperature
p.u. T
MEASI: Temperature
Tmax
19Z5262A_EN
3-30 Temperature measurement using a PT 100 resistance thermometer connected to the analog (I/O) module
Backup sensors
The open circuit signal on the PT 100 analog input from the function group MEASI is
forwarded to the functions Thermal Overload Protection and Limit Value Monitoring.
In the Thermal Overload Protection it is possible to set whether the 20 mA input or – if
configured – one of the temperature sensors T1 to T9, connected to the temperature p/c
board (the RTD module), is to be used as a backup (see "Thermal Overload Protection").
In the Limit Value Monitoring function the limit values assigned to the faulty PT 100 are
blocked.
3.7.3 Connecting Temperature Sensors to the Temperature P/C Board (the RTD
Module)
The temperature p/c board (the RTD module) mounted in the P139 has 9 analog inputs
available to connect temperature sensors T1 to T9. These analog inputs are designed
for connection of PT 100, Ni 100 or Ni 120 resistance thermometers.
If the PT 100 resistance thermometer is connected using the 3-wire method, then no
further calibration is required.
All nine temperature sensors must be of the same type, which is set under
MEASI: Type of TempSensors
Open-circuit monitoring
If one of the measuring circuits is open due to a broken wire, the signal
M E A S I : O p e n c i r c . P T 1 0 0 T x (x = 1 to 9) is issued.
MEASI: Enabled
SFMON: PT100 T1
open circuit
MEASI: Temperature
T1
MEASI: Temperature
p.u. T1
MEASI: Temperature
T1max
19Z5263A_EN
3-31 Temperature measurement with temperature sensor T1 connected to the temperature p/c board. The same applies to sensors T2 to T9.
Backup sensors
The open circuit signals from temperature sensors, issued by function group MEASI, are
forwarded to the Thermal Overload Protection function. Should the main temperature
sensor (that has been set in the Thermal Overload Protection) fail, it is possible to select
in whether the 20 mA input or – if configured – one of the temperature sensors T1 to T9,
connected to the temperature p/c board (the RTD module), is to be used as a backup
sensor (see "Thermal Overload Protection").
In addition to this, the open circuit signals from the temperature sensors, issued by the
function group MEASI, are forwarded to the Limit Value Monitoring function.
The selection of such backup sensors for the Limit Value Monitoring function is made in
the function group M E A S I .
For this purpose the temperature sensors connected to the temperature p/c board (RTD
board) are divided into three groups:
If the backup temperature sensor from group 2 also fails it will be replaced by the
corresponding sensor from group 3, under the assumption that
M E A S I : B a c k u p T e m p S e n s o r P S x is set to Group 1 –2/3.
Main sensor Backup sensor from group 2 Backup sensor from group 3
With setting: With setting:
Group 1 -2 Group 1 -2/3
or
Group 1 -2/3
T1 T4 T7
T2 T5 T8
T3 T6 T9
Should temperature sensor T1 fail, with the setting Group 1 –2/3, it will replaced by T4.
Should temperature sensor T4 also fail it will replaced by T7.
For further details refer to section with the description of the "Limit Value Monitoring".
Application example
A motor protection application is shown in the figure below with temperature sensors T1
to T9 connected to the temperature p/c board (RTD module) and a "PT 100" resistance
thermometer connected to the analog (I/O) module Y.
RTD
RTD
RTD
RTD
RTD
RTD
RTD
RTD
Stator
RTD
RTD
Rotor
Bearing Bearing
19B5236A_EN
3-32 Temperature measurements on a motor to be used with the Limit Value Monitoring function (LIMIT) and the Thermal Overload protection
(THERM)
The P139 has output relays for the output of binary signals. The binary signal
assignment is freely-configured by the user.
OUTP: Outp.rel.
block USER
[ 021 014 ]
0
OUTP: Outp.
1 ≥1 relays blocked
[ 021 015 ]
0: No
OUTP: Block 1: Yes
outp.rel. EXT
[ 040 014 ] ≥1
MAIN: Prot.
ext. disabled
[ 038 046 ]
SFMON: Hardware
fault
304 950
1 ≥1
2
3
4 -K xxx
≥1
5
6
≥1
1: ES updating
2: ES manual reset
≥1
3: ES reset (fault)
4: ES reset (syst.dist)
5: NE updating & ≥1 OUTP: State K xxx
[ zzz zzz ]
6: NE manual reset &
&
& ≥1
Signal 1
Signal 2
Signal 3 m out of n
Signal n
≥1 & ≥1
Selected signals
&
FT_RC: Record.
in progress OUTP: Latching
[ 035 000 ] 1 reset
& [ 040 088 ]
FT_RC: System
disturb. runn
[ 035 004 ]
MAIN: General
reset USER
[ 003 002 ]
1: execute
MAIN: General
reset EXT
[ 005 255 ]
OUTP: Reset
latch. USER
[ 021 009 ]
0
1 1
100 ms
0: don’t execute
1: execute
OUTP: Reset
latch. EXT
[ 040 015 ]
50Z0141 A_EN
3-33 Configuration, setting the operating mode, and blocking the output relays
Measurands made available by the P139 can be provided in BCD (binary coded
decimal) form through output relays or in analog form as direct current output. Output as
direct current can only occur if the device is equipped with analog module Y. BCD
output is always possible, whether the device is equipped with analog module Y or not.
The measured data output function is reset from the integral local control panel or
through an appropriately configured binary signal input.
There is a general reset.
LED indicators reset
MEASO: Reset
output USER
[ 037 116 ]
0
1
0: don’t execute
1: execute
MAIN: General
reset USER MEASO: Reset
[ 003 002 ] meas.val.outp.
1: execute 304 601
MAIN: Reset
indicat. USER
[ 021 010 ]
1: execute
MAIN: General
reset EXT
[ 005 255 ]
MAIN: Reset
indicat. EXT
[ 065 001 ]
47Z13H6A_EN
Scaling
Scaling is used to map the physical measuring range to the device inherent setting
range.
Scaling of analog output is also suited for directional-signed output of some fault
measurands, in particular fault location in percent.
The user can select a measurand for output in BCD form by assigning output relays.
The selected measurand is available in BCD-coded form for the duration of the set hold
time M E A S O : H o l d T i m e O u t p u t B C D . If the selected variable was not measured,
then there is no output of a measurand value.
Output of measured event
values
If the measured event value is updated during the hold time, the measurand output
memory is cleared and the hold time is re-started. This leads to an immediate availability
at the output of the updated value.
Output of measured
operating values
The selected measured operating value is available for the duration of the set hold time.
After the hold time has elapsed, the current value is saved and the hold time is re-
started. If the hold time has been set to 'blocked', the measured operating value that has
been output will be stored until the measured data output function is reset.
The BCD display range should be set so that the value 399 is never exceeded. If this
should occur or if the measurand is outside the acceptable measuring range, then the
value for "Overflow" (all relays triggered) is transmitted.
Measurands Range
Measurands of the Mx,RL1 ... Mx,RL2
variable Mx
Associated scaled 0 ... 1
measurands
Scaling is made with reference to the complete range of values for the selected
measurand (variable Mx). The complete range of values is defined by their end values
Mx,RL1 and Mx,RL2. (Mx,RL1 and Mx,RL2 are listed in the operating program S&R-103
- PC Access Software MiCOM S1 - under "minimum" and "maximum".)
Designation of the set "Scaled min. val. BCD" ... "Scaled max. val. BCD"
values in the data model
Measurands Range
Fault measurand: -320.00% ... +320.00%
FT_DA:Fault locat.
percent
Associated scaled 0 ... 1
measurands
/Parameter/Config. parameters/
Address Description Current value
056 020 MEASO: Function group MEASO With
031 074 MEASO: General enable USER Yes
053 002 MEASO: Fct. assignm. BCD FT_DA: Fault locat. percent
010 010 MEASO: Hold time output BCD 1.00 s
037 140 MEASO: Scaled min. val. BCD 0.500
037 141 MEASO: Scaled max. val. BCD 0.813
037 142 MEASO: BCD-Out min. value 0
037 143 MEASO: BCD-Out max. value 200
The following figure displays the values output as a function of the fault location.
The BCD value and the signal M E A S O : V a l i d B C D v a l u e = 'Yes' are only issued in
the value range 0% to 200%.
200
BCD value
0
-320% 0% 200% 320% [004.027] FT_DA:
Fault locat. percent
47Z1040A_EN
Note:
Except from radial, single circuit lines the fault location value gives a reasonable value
only for faults up to the line end. For any fault on a subsequent line the fault location is
more or less incorrect due to unknown fault current infeed in the remote substation.
It is recommended to limit the calculation of a fault location to a practical and sensible
range on the line by setting F T _ D A: O u tp u t fa u l t l o c a t. = 'Only aft.tr.t1/t1,ze'.
MEASO: 1-digit
bit
MEASO: 1-digit
bit
Setting blocked
MEASO: 1-digit
bit
measured
MEASO: Fct.
assignm. BCD value
Measured value 1
Measured value 2
Measured value 3
Measured value n
Scaling of the
Selected meas. val. BCD output
++
MEASO: Output
value x
19Z5264A_EN
3-39 BCD measured data output. Overflow behavior is displayed in BCD example (see previous figure)
The user can select two of the measurands available in the P139 for output in the form of
load-independent direct current. Three interpolation points per channel can be defined
for specific adjustments such as adjustment to the scaling of a measuring instrument.
The direct current that is output is displayed as a measured operating value.
The selected measurand is output as direct current for the duration of the set hold time
M E A S O : H o l d T i m e O u t p u t A - x . If the selected variable was not measured, then
there is no output of a measurand value.
Output of measured event
values
If the measured event value is updated during the hold time, the measurand output
memory is cleared and the hold time is re-started. This leads to an immediate availability
at the output of the updated value.
Output of measured
operating values
The selected measured operating value is available for the duration of the set hold time.
After the hold time has elapsed, the current value is saved and the hold time is re-
started. If the hold time has been set to blocked, the measured operating value that has
been output will be stored until the measured data output function is reset.
Configuration of output
relays assigned to the
output channels
The user must keep in mind that direct current output only occurs when the output relays
assigned to the output channels are configured for M E A S O : V a l u e A - x O u t p u t ,
since the output channels would otherwise remain short-circuited (see terminal
connection diagrams).
Measurand range to be
output
The measurand range to be output is (Mx,min ... Mx,knee ... Mx,max),
with:
Mx,min: minimum value to be output
Mx,knee: Knee-point value for the measurand range to be output
Mx,max: maximum value to be output
Measurands Range
Measurands of the Mx,RL1 ... Mx,RL2
variable Mx
Associated scaled 0 ... 1
measurands
Measurands Range
Measurands of the 0 V ... 150 V
variable Mx
Associated scaled 0 ... 1
measurands
/Parameter/Config. parameters/
Address Description Current value
056 020 MEASO: Function group MEASO With
031 074 MEASO: General enable USER Yes
053 000 MEASO: Fct. assignm. A-1 MAIN:
Voltage A-B p.u.
010 114 MEASO: Hold time output A-1 1.00 s
037 104 MEASO: Scaled min. val. A-1 0.013 (corresponds with
0.02 Vnom)
037 105 MEASO: Scaled knee val. A-1 0.067 (corresponds with
0.10 Vnom)
037 106 MEASO: Scaled max. val. A-1 0.667 (corresponds with
1.00 Vnom)
037 107 MEASO: AnOut min. val. A-1 4 mA
037 108 MEASO: AnOut knee point A-1 16 mA
037 109 MEASO: AnOut max. val. A-1 18 mA
A check of the set characteristic and its acceptance by the device, if the setting was
properly entered, will only occur after the device, with the setting M AIN : D e vi c e
o n - l i n e is again switched on-line.
Ia / mA
20
Max.
output value18
Knee point
16
output value
14
12
10
6
Min.
output value 4
2
0
0 0.02 0.1 1 1.2 1.3 1.4 1.5 Vnom
0,013 0,067 0,667 1,0Mx,scal
D5Z52KFA
19Z5265A_EN
3-40 Example of a characteristic curve for analog measured data output . In this example the range starting value is = 0; also possible is
directional-signed output (see corresponding example in section BCD Measured Data Output).
Measured data from external devices, which must be scaled to 0 ... 100%, can be written
to the following parameters of the P139 via the communications interface.
The P139 has 17 LED indicators for the indication of binary signals. Four of the LED
indicators are permanently assigned to fixed functions. The other LED indicators are
freely configurable. These freely configurable LEDs will emit either red or green or
amber light (amber is made up of red and green light and may not be configured
independently).
H 1 (green) “HEALTHY” Not configurable. H 1 indicates the operational readiness of the device
(supply voltage is present).
H 17 (red) “EDIT MODE” Not configurable. H 17 indicates the input (edit) mode. Only when the
device is in this mode, can parameter settings be changed by pressing
the “Up“ and “Down“ keys. (See Chapter 6, section 'Display and
Keypad')
H 4 (red) “TRIP COMMAND” With the P139 this LED indicator is customarily configured with function
M A I N : G e n . t r i p s i g n a l - but the configuration may be modified.
The factory setting for LED indicator H 4 is shown in the terminal
connection drawings at the end of Chapter 5 and it is included in the
supporting documents.
H 4 (green) ---- Function assignment to this green LED indicator is freely configurable.
H 5 to H 16 ---- For each of these LED indicators both colors (red & green) may be
configured freely and independently.
The following figures illustrate the layout of LED indicators situated on the local control
panel with case 40T/84T devices.
TRIP
ALARM
OUT OF SERVICE
C
HEALTHY G
EDIT MODE
G
O I L/R
For each of the freely configurable LED indicators, the operating mode can be selected
separately. This setting will determine whether the LED indicator will operate either in
energize-on-signal (ES) or normally-energized (NE) mode, whether it will be flashing and
whether it will be in latching mode. Latching is disabled either manually via setting
parameters or by an appropriately configured binary signal input (see "Main Functions of
the P139"), at the onset of a new fault or of a new system disturbance, depending on the
selected operating mode.
Therefore the operating modes turn out to be the 23=8 possible combinations of the
following components:
• flashing / continuous,
• energize-on-signal (ES) / normally-energized (NE),
• updating / latching with manual reset,
• energize-on-signal (ES) with reset after new fault (flashing / continuous) and
• energize-on-signal (ES) with reset after new system disturbance (flashing /
continuous),
LED: Operating
mode H xx
[ xxx xxx ]
1
2
3
4
5
6
7
8
9
10
11
-Hxx
12 (red)
1: ES updating ! G !
2: ES manual reset
3: ES reset (fault)
4: ES reset (syst.dist) ≥1
5: NE updating
6: NE manual reset
7: ES updating bl
2: ES manual reset
8: ES manual reset bl
3: ES reset (fault) LED: State H xx
& red
9: ES reset (fault) bl [ zzz zzz ]
10: ES rst (syst.dst) bl &
11: NE updating bl &
12: NE manual reset bl
& S1 1
R1
LED: Fct.assig.
Hxx red
[ yyy yyy ]
Signal 1
Signal 2
Signal 3 m out of n LED: State H xx
Signal n & green
[ zzz zzz ]
&
&
Selected signals
& S1 1
R1
LED: Fct.assig.
Hxx green
[ yyy yyy ]
Signal 1
Signal 2 -Hxx
Signal 3 m out of n (green)
Signal n
&
FT_RC: Record.
in progress
[ 035 000 ] &
FT_RC: System
disturb. runn
[ 035 004 ]
MAIN: General
reset EXT
[ 005 255 ]
MAIN: General
reset USER
[ 003 002 ]
1: execute
MAIN: Reset
LED
306 020
12Z6200 A_EN
In the acquisition of signals for control purposes, the functions real time acquisition (time
tagging), debouncing and chatter suppression are included as standard. Each of these
signals can be assigned to one of eight groups and for each of these groups the
debouncing time and chatter suppression can be set. Matching of these two parameters
achieves the suppression of multiple spurious pickups.
3-43 Group assignment and setting of debouncing and chatter suppression, illustrated for group 1
Debouncing
The first pulse edge of a signal starts a timer stage running for the duration of the set
debouncing time. Each pulse edge during the debouncing time re-triggers the timer
stage.
If the signal is stable until the set debouncing time elapses, a telegram containing the
time tag of the first pulse edge is generated. As an alternative the time tag may be
generated after debouncing by setting parameter M A I N : T i m e t a g to the value
'After debounce time'.
After the set debouncing time has elapsed, the state of the signal is checked. If it is the
same as prior to the occurrence of the first pulse edge, no telegram is generated.
Time-tagged entries of the first pulse edge are only generated after debounce time has
elapsed. If these entries are saved without delay (setting of M A I N : T i m e t a g to the
value '1stEdge,OpMem unsort') they are not necessarily saved in chronological order in
the operating data memory. If above parameter has been set to the value
'1stEdge,OpMem sorted' then all entries are always saved in chronological order in the
operating data memory.
3-44 Signal flow with debouncing when time tagging occurs with the 1st pulse edge
(e.g. parameter M A I N : T i m e t a g set to the value '1stEdge,OpMem unsort' or '1stEdge,OpMem sorted'.)
Example: Set debouncing time: 50 ms
s: start
e: end
Chatter suppression
Sending of the first telegram starts a timer stage running for the duration of the set
monitoring time. While the timer stage is elapsing, telegrams are generated for the
admissible signal changes. The number of admissible signal changes can be set.
After the first "inadmissible" signal change, no further telegrams are generated and the
timer stage is re-triggered. While the timer stage is elapsing, it is re-triggered by each
new signal change. Once the timer stage has elapsed, each signal change triggers a
telegram.
The P139 is designed to control up to six switchgear units. The bay type defines the
layout of a bay with its switchgear units.
The P139 offers a selection from pre-defined bay types. Should the required bay type
be missing from the standard selection then the user can contact the manufacturer of the
P139 to request the definition of a customized bay type to download into the P139. By
applying the bay editor from the PC Access Software MiCOM S1 the user can define
new bay types. The number of this additional bay type will then be displayed at
MAIN: Customized bay type.
Once the user has selected a bay type, the P139 can automatically configure the binary
inputs and output relays with function assignments for the control of switchgear units.
The assignment of inputs and outputs for an automatic configuration is shown in the
List of Bay Types in the Appendix.
The secondary phase currents of the system transformers are fed to the P139. There is
the option of connecting up to five voltage transformers. The measured variables are –
electrically isolated – converted to normalized electronics levels. Air-gap transformers
are used in the phase current path to suppress low frequency (DC decays and offsets)
signal components. The analog quantities are digitized and are thus available for further
processing.
Settings that do not refer to nominal quantities are converted by the P139 to nominal
quantities. The user must therefore set the secondary nominal currents and voltages of
the system transformers.
The connection direction of the measuring circuits on the P139 must also be set.
Figure 3-47 shows the standard connection. By this setting the phase of the digitized
currents is rotated by 180°.
If the P139 is to operate with the GFDSS function (ground fault direction determination
using steady-state values), current transformer T4 needs to be connected to a current
transformer in Holmgreen connection (dashed lines in Figure 3-47 ) or to a core balance
current transformer.
When the P139 is equipped with the NCIT module (non conventional instrument
transformer) the conventional CTs are exchanged by NCITs as shown in the following
figure ("Connecting the P139 measuring circuits"), and described in Chapter 2
"Connecting NCITs to the NCIT Module".
When the P139 is equipped with the temperature p/c board (RTD module for PT 100,
Ni 100 or Ni 120, terminal connection diagram in Annex D) further resistance
thermometers, in addition to the PT 100 resistance thermometer connected to the analog
module (I/O), can be connected to the RTD module as described in Chapter 3 section
"Measured Data Input”, ‘Connecting resistance thermometers to the RTD module’.
A
B
C
MAIN: Vref,nom
V.T. sec.
[ 031 052 ]
1U
2U Vref
X X. Y IA
IB
IB
X X. Y
IC IC
X X. Y
1: Standard
IN (Y = 1)
2: Opposite
(Y = -1)
IN
X X . Y
1: Standard
(Y = 1)
2: Opposite
(Y = -1)
MAIN: VNG,nom
V.T. sec.
[ 010 028 ]
n e
n VN-G
MAIN: Vnom
V.T. sec.
[ 010 009 ]
U
VA-G
e V
VB-G
W
VC-G
N
19Z6402 A_EN
3-47 Connecting the P139 measuring circuits (when the P139 is equipped with the NCIT module or the RTD module; see references in previous
text)
The P139 has an operating data measurement function for the display of currents and
voltages measured as well as quantities derived from these measured values. For the
display of measured values, set lower thresholds need to be exceeded, to avoid
fluctuating small values from noise. If these lower thresholds are not exceeded, the
value "not measured" is displayed. The following measured variables are displayed:
The measured data are updated at 1 s intervals. Updating is interrupted when a general
starting signal is issued or if the self-monitoring function detects a hardware fault.
According to the following formulas the P139 will determine the negative-sequence
current and positive-sequence current, taking into account the set phase sequence:
I pos =
1
( 2
⋅ I + a ⋅ I B + a ⋅ IC
3 A
) I pos =
1
( 2
⋅ I + a ⋅ I B + a ⋅ IC
3 A
)
a = e j120°
a 2 = e j240°
MAIN: Hardware c
fault
306 540
IA c1
IB c2
IC c3
c4
c5
c6
1 MAIN: Current A
p.u.
[ 005 041 ]
2 MAIN: Current B
p.u.
[ 006 041 ]
3 MAIN: Current C
p.u.
[ 007 041 ]
+
+ 4 MAIN: Current
+ (IP) p.u.
[ 005 011 ]
5 MAIN: Current
COMP IP,max p.u.
[ 005 051 ]
6 MAIN: Current
IP,min p.u.
[ 005 056 ]
Imax
MAIN: Inom C.T.
Imin prim.
[ 010 001 ]
MAIN: Current A
prim.
[ 005 040 ]
MAIN: Current B
prim.
[ 006 040 ]
MAIN: Current C
prim.
[ 007 040 ]
MAIN: Current
(IP) prim.
[ 005 010 ]
MAIN: Curr.
IP,max prim.
[ 005 050 ]
MAIN: Curr.
IP,min prim.
[ 005 055 ]
19Z6403A_EN
MAIN: IA p.u.,
demand
[ 006 235 ]
MAIN: IB p.u.,
demand
[ 006 236 ]
MAIN: IC p.u.,
demand
[ 006 237 ]
MAIN: IA p.u.,
MAIN: Current A demand stor.
p.u. [ 006 232 ]
[ 005 041 ] R
MAIN: IA prim,
demand
[ 006 226 ]
MAIN: IB prim,
demand
[ 006 227 ]
MAIN: IC prim,
demand.
[ 006 228 ]
MAIN: IP,max
prim.,demand
[ 005 036 ]
MAIN: Reset
IP,max,st.USER MAIN: IA prim,
[ 003 033 ]
demand stor.
[ 006 223 ]
0
MAIN: IB prim,
1 demand stor.
[ 006 224 ]
MAIN: General 0: don`t execute
reset USER 1: execute MAIN: IC prim,
[ 003 002 ] demand stor.
1: execute [ 006 225 ]
MAIN: General
reset EXT MAIN: IP,max
[ 005 255 ] prim,demand.st.
MAIN: Reset [ 005 034 ]
IP,max,st. EXT
[ 005 211 ]
19Z6404 A_EN
3-49 Measured operating data - phase current, part 2: demand values (delayed and stored phase currents and maximum phase current)
The stored phase currents are implemented as for the stored maximum phase current.
MAIN: Current
IP,max p.u.
[ 005 051 ]
MAIN: IP,max
p.u.,demand
[ 005 037 ]
MAIN: Current
IP,max p.u.
[ 005 051 ]
MAIN: IP,max
p.u.,demand.st
[ 005 035 ]
MAIN: Current
IP,max p.u.
[ 005 051 ]
MAIN: IP,max
p.u.,demand.st
[ 005 035 ]
MAIN: Reset
IP,max,st.USER
[ 003 033 ]
MAIN: Reset
IP,max,st. EXT
[ 005 211 ] 50Z0115A_EN
3-51 Operation of delayed and stored maximum phase current display - display of demand values
3-52 Determining the minimum and maximum phase-to-ground and phase-to-phase voltages
MAIN: General
starting C
306 539
MAIN: Hardware
fault MAIN: Meas. value
306 540 rel. V
[ 011 032 ]
VA-G C1
VB-G C2
VC-G C3
VPG,max C4
VPG,min C5
Σ(VPG)/3 C6
VA-B C7
VB-C C8
VC-A C9
VPP,max C10
VPP,min C11
Vneg C12
Vpos C13
12Z6204A_EN
MAIN: Angle
& C ΣVPG/IN p.u.
[ 005 072 ]
MAIN: Angle
ΣVPG vs. IN
[ 005 009 ]
+
+
+
MAIN: General
starting
306 539
MAIN: Hardware
Fault
306 018
12Z6203 A_EN
3-56 Measured operating data - power, active power factor, and angle
Phase relation IN
The P139 checks if the phase relations of calculated residual current and measured
residual current are coherent. If the phase displacement between the two currents is
≤ 45°, then the indication ‘Equal phase’ is displayed.
Frequency
The P139 determines the frequency from the voltage VA-B. This voltage needs to exceed
a minimum threshold of 0.65 Vnom in order for frequency to be determined.
MAIN: General C
starting
306 539
MAIN: Hardware
fault
306 018 >0.65*Vnom
MAIN: Frequency f
VA-G + C p.u.
[ 004 070 ]
VB-G -
f MAIN: Frequency f
[ 004 040 ]
12Z6209 A_EN
There are two procedures available to determine active and reactive energy.
If procedure 1 is selected, active and reactive energy are determined every 2 s
(approximately). If procedure 2 is selected, active and reactive energy are determined
every 100 ms (approximately). In this way higher accuracy is achieved. Whenever the
maximum value of 655.35 MWh or 655.35 MVAr h is exceeded, a counter is incremented
and the determination of the energy output is restarted. The value that exceeded the
range is transferred to the new cycle.
MAIN: No.ov/fl.
Overflow reac.en.inp
[ 009 093 ]
Transfer
12Z6133A_EN
3-59 Determining the active and reactive energy output and input
1
Determination of the active and reactive energy
Constant load and slow load variations (no
every 2 s (approximately) significant load variations within 1 second).
Reduced system loading
Phase angles below 70° (cos ϕ > 0.3 ).
5%
2%
3-60 Error of measurement in the determination of energy output resulting from the phase angle error of the P139
For phase angles ϕ with |cosϕ| < 0.3, or when the error of measurement resulting from
the maximum phase-angle error is not acceptable, external counters should be used to
determine the energy output.
Canceling a device
function
The following conditions must be met before a device function can be cancelled or
removed:
No functions of the device function being cancelled can be selected in a list setting.
If the above conditions are met, proceed through the 'Configuration' branch of the menu
tree to access the setting relevant for the device function to be cancelled.
If, for example, the "LIMIT" function group is to be cancelled, the setting of
L I M I T : F u n c t i o n g r o u p L I M I T is set to 'Without'. To re-include the "LIMIT"
function in the device configuration, the same setting is accessed and its value is
changed to 'With'.
The device function to which a setting, a signal, or a measured value belongs is defined
by the function group designation (example: "LIMIT"). In the following description of the
device functions, it is presumed that the corresponding device function is included in the
configuration.
Enabling or disabling a
device function
Besides cancelling device functions from the configuration, it is also possible to disable
protection via a function parameter or binary signal inputs. Protection can only be
disabled or enabled through binary signal inputs if the M A I N : D i s a b l e
P r o t e c t . E X T and M A I N : E n a b l e p r o t e c t . E X T functions are both
configured. When neither or only one of the two functions is configured, the condition is
interpreted as "Protection externally enabled". If the triggering signals of the binary
signal inputs are implausible – i.e. both are at logic level = "1" – then the last plausible
state remains stored in memory.
Note: If the protection is disabled via a binary signal input that is configured for
M A I N : D i s a b l e P r o t e c t . E X T , the signal
M A I N : B l o c k e d / F a u l t y is not issued.
Enabling of the residual current systems of the DTOC/IDMT protection depends on the
setting at M A I N : S y s t . I N e n a b l e d U S E R . If this enabling function has been
activated, the residual current systems of the DTOC/IDMT protection can be disabled or
enabled with parameters or through appropriately configured binary signal inputs.
Parameters and configured binary signal inputs have equal status. If only the
M A I N : System IN en a b l e E X T function is assigned to a binary signal input, then the
residual current systems of the DTOC/IDMT protection will be enabled by a positive
edge of the input signal and disabled by a negative edge. If only the M A I N : S y s t e m
I N d i s a b l e E X T function has been assigned to a binary signal input, then a signal at
this input will have no effect.
3-62 Disabling or enabling the residual current systems of the DTOC/IDMT protection
For several of the protection functions, it is possible for the duration of the set hold time
to switch over to other settings - the "dynamic parameters" – via an appropriately
configured binary signal input. If the hold time is set to 0 s, switching is effective as long
as the binary signal input is being triggered.
t1 = 0 s &
The inrush stabilization function detects high inrush current flows that occur when
transformers or machines are switched on, and, if detected, it will then block the
following functions:
The inrush stabilization function identifies an inrush current by evaluating the ratio of the
second harmonic current components to the fundamental. If this ratio exceeds the set
threshold, then the inrush stabilization function operates. Another settable current
trigger blocks inrush stabilization if the current exceeds this trigger. The setting of the
operating mode determines whether inrush stabilization will operate phase-selectively or
across all phases.
0
1
2
0: Without
&
1: Not phase-
selective
2: Phase-
selective
MAIN: Inrush
stabil. trigg
306 014
0.1 Inom
MAIN: Rush
I(2fn)/I(fn) PSx
[ * ]
fnom
I(2*fn)/I(fn)
2*fnom
fnom
2*fnom I(2*fn)/I(fn)
fnom
2*fnom I(2*fn)/I(fn)
12Z6206 A_EN
By including function blocks in the bay interlock conditions, switching operations can be
prevented independent of the switching status at the time, for example, by an external
signal "CB drive not ready" or by the trip command from an external protection device.
Two multiple blocking conditions can be defined via 'm out of n' parameters. The items
available for selection are found in the Address List. The functions defined by selection
may be blocked via an appropriately configured binary signal input.
3.11.10 Blocked/Faulty
3.11.11 Coupling between Control and Protection for the CB Closed Signal
Bay type selection defines the external device (DEV01 or DEV02 or ...) that represents
the circuit breaker. Coupling between control and protection for the "Closed" position
signal is made by the setting M A I N : S i g . a s g . C B c l o s e d . As a result, the CB
status signal needs to be assigned to one binary signal input only if this coupling is
implemented.
3-68 Coupling between control and protection for the CB closed signal
The circuit breaker can be closed by the auto-reclosing control function (ARC), by the
automatic synchronism check (ASC), by parameters or via an appropriately configured
binary signal input. The close command by parameters or a binary signal input is only
executed if there is no trip command present and no trip has been issued by a protection
device operating in parallel. Moreover, the close command is not executed if there is a
"CB closed" position signal present. The duration of the close command can be set.
If the ARC function issues a close request while the ASC function is enabled, then the
close command requires a close enable by the ASC function.
0
1
0: don’t execute
MAIN: Man. close
1: execute command
[ 037 068 ]
MAIN: Man. close
cmd. EXT &
[ 041 022 ]
MAIN: Man.cl.cmd.
enabl.EXT
[ 041 023 ]
ARC: (Re)close
request &
[ 037 077 ]
ASC: Close enable
[ 037 083 ]
ASC: Enabled
[ 018 024 ]
&
ASC: Manual
close request
305 000
&
0
1 + MAIN: No. close
commands
MAIN: General 0: don’t execute [ 009 055 ]
reset USER R
[ 003 002 ] 1: execute
1: execute
MAIN: General
reset EXT
[ 005 255 ]
MAIN: Reset c.
cl/tr.c EXT
[ 005 210 ]
12Z6207A_EN
The multiple signals 1 and 2 are formed by the programmable logic function using OR
operators. The programmable logic output to be interpreted as multiple signaling is
defined by the configuration of the binary signal input assignment with the corresponding
multiple signaling. Both an updated and a stored signal are generated. The stored
signal is reset by the following actions:
General reset
Latching reset
LED indicators reset
A command received through the communication interface.
If the multiple signaling is still present at the time of a reset, the stored signal will follow
the updated signal.
MAIN: Inp.asg.
mult.sig. 1
[ 221 051 ]
Signal 1
Signal 2
Signal 3
Signal n
MAIN: Mult.
Selected signal sig. 1 active
[ 221 017 ]
MAIN: Mult.
sig. 1 stored
S1 1 [ 221 054 ]
MAIN: Inp.asg.
mult.sig. 2
[ 221 052 ] R1
COMM1: Reset
mult. sig. 1 MAIN: Mult.
[ --- --- ] sig. 2 stored
S1 1 [ 221 055 ]
COMM1: Reset
mult. sig. 2 R1
[ --- --- ]
MAIN: General
reset USER
[ 003 002 ]
1: execute
MAIN: General
reset EXT
[ 005 255 ]
OUTP: Reset
latching
402 102
12Z62FMA_EN
If a ground fault has been detected by either the GFDSS function (ground fault direction
determination by steady-state values) or the TGFD function (transient ground fault
direction determination), the P139 analyzes the phase-to-ground voltages and identifies
the phase on which the ground fault has occurred.
During a ground fault, the P139 determines the lowest phase-to-ground voltage and
checks if the two other phase-to-ground voltages exceed the threshold of 0.2 Vnom.
In addition, the two higher phase-to-ground voltages must exceed the lowest phase-to-
ground voltage by a factor of 1.5. If these conditions are met, a ground fault signal is
issued for the phase with the lowest phase-to-ground voltage.
Ground fault signals generated either by ground fault direction determination using
steady-state values (GFDSS) or transient ground fault direction determination (TGFD)
are grouped together to form multiple signaling.
3-72 Erdschluss-Sammelmeldungen
Phase-selective starting
signals
Common phase-selective starting signals are formed from the internal phase-selective
starting signals of definite-time overcurrent protection and of inverse-time overcurrent
protection.
An adjustable timer stage is started by the phase-selective starting signals, the residual
current starting signal and the negative-sequence starting signal. While this timer stage
is running, the starting signals are blocked. The starting signals are also blocked directly
by the motor protection if the startup of a motor has been detected. Blocking is
suspended if a trip signal is present.
The operate delays for the residual current and negative-sequence current stages of the
DTOC and IDMT protection functions can be blocked for a single-pole or multi-pole
starting (depending on the setting).
MAIN: Suppr.
start.sig.PSx
[ * ]
0 t
MAIN: Starting N
int.
306 516
MAIN: Bl.tim.st. MAIN: Starting
IN,neg PSx Ineg
[ * ] 306 517
0
MAIN: Block tim.
& st. IN,neg
1 306 400
&
2
0: Without
1: For single-ph. start
2: For multi-ph. start.
3-73 Phase-selective starting signals. (IDMT represents IDMT1 and IDMT2; the addresses apply to IDMT1.)
General starting
The general starting signal is formed from the starting signals of the DTOC and IDMT
protection functions. A setting governs whether the residual current stages and the
negative-sequence current stage will be involved in forming the general starting signal.
If the operate signal from one of the residual current stages and the negative-sequence
current stage does not cause a general starting (due to the setting) then the associated
operate delays will be blocked. As a result, a trip command cannot be issued by residual
current and negative-sequence current stages.
MAIN: Block
start. signal
306 512 * Parameter MAIN: Gen.
start. Mode PSx
MAIN: tGS
PSx
set 1 017 027 017 005
set 2 001 219 001 225
set 3 001 220 001 226
set 4 001 221 001 227
12Z6201A_EN
3-74 General starting. (IDMT represents IDMT1 and IDMT2; the addresses apply to IDMT1.)
DTOC: tIN>>>>
elapsed
[ 035 040 ]
12Z5122A
3-75 Multiple signaling by the DTOC and IDMT protection functions (IDMT represents IDMT1 and IDMT2; the addresses apply to IDMT1.)
Trip command
The P139 provides two trip commands. The functions required to issue a trip can be
selected by setting a 'm out of n' parameter independently for each of the two trip
commands. The minimum trip command closure time may be set. The trip signals are
present only as long as the conditions for the signal are met.
1 ≥1
MAIN: General 0: don't execute
reset USER
[ 003 002 ] 1: execute
1: execute
MAIN: General
reset EXT
[ 005 255 ]
MAIN: Reset.c.cl/
tr.cEXT
[ 005 210 ]
12Z6190 A_EN
The binary signal input configured for “tripping” is set to a logic value of '1' or the
selected trip command from the P139 is present.
At the binary signal input configured as “CB trip” a logic value of '1' is present.
The CB trip signal from an external device can also be signaled. For this task, two
binary signal inputs need to be configured as “CB trip enable ext.“ and as “CB trip ext.“.
Before a switching unit within the bay is closed or opened by the control functions of the
P139, the P139 first checks whether the switch command may be executed. A switch
command will be executed if the optional control enable has been issued and the
interlock conditions are met. The interlock conditions are defined in the interlocking logic
for each switching unit within the bay that is subject to control actions and for each
control direction (Open/Close). Different conditions are defined for the bay interlock
equations to operate with or without station interlock. The check of bay or station
interlock equations can be cancelled for all electrically controllable switchgear units
within a bay. If the station interlock is active, it may be cancelled selectively for each
switching unit and each control direction (see section ‘Control and Monitoring of
Switchgear Units').
If “Local” has been selected as the control point, the bay and station interlocks may be
cancelled through an appropriately configured binary signal input.
3-80 General enable for switch commands issued by the control functions; activating or canceling the interlocks
For bays with direct motor drive control of load disconnecting switches, isolating links or
grounding switches, a monitoring function is provided to protect motors from
overheating.
The number of switching operations within a set monitoring period is counted. If the
number of switching operations within the monitoring period exceeds the set limit, the
signal M A I N : M o n . m o t . d r i v e s t r . is issued. For the duration of the set cooling
time, no control commands to motor-driven switchgear units will be executed. Once the
set cooling time has elapsed, the control commands are enabled again.
n = 1
MAIN: Mon.time
mot.drives
[ 221 026 ]
MAIN: Cool.time
mot.drives t
[ 221 028 ]
19Z6417A_EN
If a link to the control station cannot be established or if the link is interrupted, the signal
"Communication error" will be issued. This signal will also be issued if communication
module A is not fitted.
The data stored in the operating data memory, the monitoring signal memory and the
event memories are date- and time-tagged. For correct tagging, the date and time need
to be set in the P139.
3-84 Date/time setting and clock synchronization with minute pulses presented at a binary signal input
Synchronization source
The P139 provides numerous options to synchronize the internal clock:
o Telegram with the time of day via the communication interface COMM1/IEC (full
time)
o Telegram with the time of day via the communication interface COMM2/PC (full time)
o IRIG-B Signal (IRIGB; time of day only)
o Minute pulse presented at a binary signal input (MAIN), see figure 3-84 and previous
paragraph
With older device versions these interfaces had equal ranking i.e. clock synchronization
was carried out regardless of which sub-function initiated triggering. No conflicts have to
be taken into account as long as synchronization sources (communication master,
IRIG-B and minute pulse source) operate at the same time of day. Should the
synchronization sources operate with a different time basis unwanted step changes in
the internal clock may occur. On the other hand a redundant time of day synchronization
is often used so as to sustain time synchronization via IRIG-B interface even if and while
the SCADA communication is out of service.
With the current device versions a primary and a backup source for time of day
synchronization may now be set, where both provide the four options listed in the above.
MAIN: Prim.Source TimeSync
MAIN: BackupSourceTimeSync
With this feature synchronization occurs continuously from the primary source as long as
time synchronization telegrams are received within a time-out period set at
M A I N : T i m e s y n c . t i m e - o u t . The backup source is required if after the set time-
out there is no synchronization through the primary source.
When selecting the time telegram via IEC as the primary source the device will expect
time synchronization telegrams from server SNTP2 after server SNTP 1 has become
defective, before it will switch over to the backup source.
Time synchronization occurs solely from the primary source when the time-out stage is
blocked.
Stored data such as event logs, measured fault data etc, can be cleared in several ways.
The following types of resetting actions are possible:
Automatic resetting of the event signals provided by LED indicators (given that the
LED operating mode has been set accordingly) and of the display of measured event
data on the local control panel LCD whenever a new event occurs. In this case only
the displays on the local control panel LCD are cleared but not the internal memories
such as the fault memory.
Resetting of LED indicators and measured event data displayed on the local control
panel LCD by pressing the "CLEAR" key C located on the local control panel.
By selecting the required function at L O C : F c t . r e s e t k e y further memories
may be assigned which will then also be cleared when the "CLEAR" key is pressed.
Selective resetting of a particular memory type (e.g. only the fault memory) via setting
parameters. (For this example: Navigate to menu point
F T _ R C : R e s e t r e c o r d . U S E R and set to 'Execute', see also the exact step-
by-step description in Chapter 6 "Local Control", section 'Reset'.)
Selective resetting of a particular memory type (e.g. only the fault memory) through
appropriately configured binary signal inputs. (For this example: Assign parameter
F T _ R C : R e s e t r e c o r d . E X T to the relevant binary signal input e.g.
I N P : F c t . a s s i g n m . U 3 0 1 .)
Group resetting by setting parameters, by navigating to menu point
M A I N : G r o u p r e s e t x U S E R and setting it to 'Execute'. For this the relevant
memories (i.e. those to be reset) must be assigned to parameter
MAIN: Fct.assign. reset x.
Group resetting through appropriately configured binary signal inputs. (That is assign
parameter M A I N : G r o u p r e s e t . x E X T to the relevant binary signal input, e.g.
I N P : F c t . a s s i g n m . U 3 0 1 after memories to be reset have been assigned to
parameter M A I N : F c t . a s s i g n . r e s e t x .)
General resetting by setting parameters (menu point
M A I N : G e n e r a l r e s e t U S E R ). All memories, counters, events etc. are reset
without any special configuration options.
Should several resetting actions have been configured for one particular memory then
they all have equal priority.
In the event of a cold restart, namely simultaneous failure of both internal battery and
substation auxiliary supply, all stored signals and values will be lost.
Further resetting possibilities are basically not distinct resetting actions but make access
especially easy to one of the resetting actions described above i.e. by configuring them
to a function key.
MAIN: General
reset USER
[ 003 002 ]
1 1: execute
0: don't execute
1: execute
MAIN: Reset
indicat. USER
[ 021 010 ]
0
1
0: don't execute
1: execute
≥1 MAIN: Reset LED
306 020
MAIN: Reset
indicat. EXT
[ 065 001 ]
12Z6115 A_EN
3-85 General reset, LED reset and measured event data reset from the local control panel
m out of n
MAIN: Group
reset 1 USER
[ * ]
0
1 ≥1 &
0: don't execute
1: execute
MAIN: Group
reset 1 EXT
[ * ]
MAIN: Fct.assign.
reset 1
[ * ]
m out of n
12Z61RMB_EN
3-86 "CLEAR" key on the local control panel and, as an example, group resetting of the operating data recording (e.g. as an example for the
reset signal OP_RC: Reset record. EXT); further examples for resetting signals generated in this way are:
- [004 140] TGFD: Reset signal EXT
- [005 210] MAIN: Reset c. cl/tr.c EXT
- [005 211] MAIN: Reset IP,max,st. EXT
- [005 212] MAIN: Reset meas.v.en. EXT
- [005 240] MT_RC: Reset record. EXT
- [005 241] OL_RC: Reset record. EXT
- [005 242] GF_RC: Reset record. EXT
- [005 243] FT_RC: Reset record. EXT
- [005 244] ARC: Reset counters EXT
- [005 245] GFDSS: Reset counters EXT
- [005 246] TGFD: Reset counters EXT
- [005 247] CBM: Reset meas.val. EXT
- [005 255] MAIN: General reset EXT
- [006 054] COMM3: Reset No.tlg.err.EXT
- [006 074] ASC: Reset counters EXT
- [006 075] f<>: Reset meas.val. EXT
- [006 076] MEASI: Reset Tmax EXT
- [036 087] MEASI: Reset output EXT
- [038 061] THERM: Reset replica EXT
- [040 015] OUTP: Reset latch. EXT
- [040 138] MAIN: Reset latch.trip EXT
- [041 082] MP: Reset replica EXT
- [217 004] COUNT: Reset EXT
Depending on the design version of the communications module A there are up to two
communications channels available (see Chapter "Technical Data"). These physical
communications channels may be assigned to communications interfaces COMM1 and
COMM2.
If tests are run on the P139, the user is advised to activate the test mode so that all
incoming signals via the serial interfaces will be identified accordingly.
With the P139, four independent parameter subsets may be pre-set. The user may
switch between parameter subsets during operation without interrupting the protection
function.
If, after the supply voltage is turned on, no logic level of ' 1 ' is present at any of the
binary signal inputs selected for the parameter subset selection, then the parameter
subset selected via the function parameter will become active once the stored time has
elapsed. The previous parameter subset remains active while the stored hold timer
stage is running.
Parameter subset selection may also occur during a starting condition. When subset
selection is handled via binary signal inputs, a maximum inherent delay of approximately
100 ms must be taken into account.
Settings for which only one address is given in the following sections are equally
effective for all four parameter subsets.
Comprehensive monitoring routines in the P139 ensure that internal faults are detected
and do not lead to malfunctions. The selection of function assignments to the alarm
signal includes, among others, self-monitoring signals from the communication monitor,
measuring-circuit monitoring (V, Vref, I), open-circuit monitoring (20 mA input,
temperature sensors) and the logic outputs 30 to 32 and 30(t) to 32(t).
Cyclic tests
After start-up has been successfully completed, cyclic self-monitoring tests will be run
during operation. In the event of a positive test result, a specified monitoring signal will
be issued and stored in a non-volatile(NV) memory – the monitoring signal memory –
along with the assigned date and time (see section ‘Monitoring Signal Recording’).
The self-monitoring function monitors the built-in battery for any drop below the minimum
acceptable voltage level. If the associated monitoring signal is displayed, then the
battery should be replaced within a month, since otherwise there is the danger of data
loss if the supply voltage should fail. Chapter 11 gives further instructions on battery
replacement.
Signal
The monitoring signals are also signaled via the output relay configured
S F M O N : W a r n i n g . The output relay operates as long as an internal fault is
detected.
Device response
The response of the P139 is dependent on the type of monitoring signal. The following
responses are possible:
Signaling Only
If there is no malfunction associated with the monitoring signal, then only a signal is
issued, and there are no further consequences. This situation exists, for example,
when internal data acquisition memories overflow.
Selective Blocking
If a fault is diagnosed solely in an area that does not affect the protective functions,
then only the affected area is blocked. This would apply, for example, to the
detection of a fault on the communication module or in the area of the PC interface.
Warm Restart
If the self-monitoring function detects a fault that might be eliminated by a system
restart – such as a fault in the hardware –, then a procedure called a warm restart is
automatically initiated. During this procedure, as with any start-up, the computer
system is reset to a defined state. A warm restart is characterized by the fact that no
stored data and, in particular, no setting parameters are affected by the procedure.
A warm restart can also be triggered manually by control action. During a warm
restart sequence the protective functions and the communication through serial
interfaces will be blocked. If the same fault is detected after a warm restart has been
triggered by the self-monitoring system, then the protective functions remain blocked
but communication through the serial interfaces will usually be possible again.
Cold Restart
If a corrupted parameter subset is diagnosed during the checksum test, which is part
of the self-monitoring procedure, then a cold restart is carried out. This is necessary
because the protection device cannot identify which parameter in the subset is
corrupted. A cold restart causes all internal memories to be reset to a defined state.
This means that all the protection device settings are also erased after a cold restart.
The settings that then apply are shown underlined in the column "Range of Values" in
the Address List. In order to establish a safe initial state, the default values have
been selected so that the protective functions are blocked. Both the monitoring signal
that triggered the cold restart and the value indicating parameter loss are entered in
the monitoring signal memory.
The default for this timer stage is ‘blocked’ e.g. blocking of the protection device with two
identical faults occurs independent of the time evolved since the first fault monitoring
signal was issued.
The behavior caused by sporadic faults could lead to an unwanted blocking of the device
if the monitoring signal memory has not been reset in the interim, for example, because
the substation is difficult to reach in wintertime or reading-out and clearing of the
monitoring signal memory via the communication interfaces was not enabled. To defuse
this problem it is suggested to set the function parameter to a specific time duration
period so that blocking will only occur if the same fault occurs again within this time
period. Otherwise, the device will continue to operate normally after a warm restart.
OP_RC: Operat.
data record.
[ 003 024 ]
Operating data
MAIN: Oper.- memory
relev. signal
306 024
MAIN: General
Reset USER + OP_RC: No. oper.
[ 003 002 ] data sig.
[ 100 002 ]
1: execute R
MAIN: General
Reset EXT
[ 005 255 ]
OP_RC: Reset
record EXT
[ 005 213 ]
OP_RC: Reset
record USER
[ 100 001 ]
0: don't execute
1: execute
12Z61CMB_EN
3-91 Operating data recording and counter for signals relevant to system operation
The monitoring signals generated by the self-monitoring function are recorded in the
monitoring signal memory. A listing of all possible entries in this monitoring signal
memory is given in the address list (see Appendix). The memory buffer allows for a
maximum of 30 entries. If more than 29 monitoring signals occur without interim memory
clearance, the SFMON: O v e r f l o w M T _ R C signal is entered as the last entry.
Monitoring signals prompted by a hardware fault in the unit are always entered in the
monitoring signal memory. Monitoring signals prompted by a peripheral fault can be
entered into the monitoring signal memory, if desired. The user can select this option by
setting an 'm out of n' parameter (see 'Self-Monitoring').
If at least one entry is stored in the monitoring signal memory, this fact is signaled by the
red LED indicator H 3 on the local control panel. Each new entry causes the LED to
flash (on/off/on....).
The monitoring signal memory can only be cleared manually by a control action. Entries
in the monitoring signal memory are not cleared automatically, even if the corresponding
test in a new test cycle now shows the device to be healthy. The contents of the
monitoring signal memory can be read from the local control panel or through the PC or
communication interface. The time and date information assigned to the individual
entries can be read out through the PC or communication interface or from the local
control panel.
SFMON: Hardware
fault
304 950
Select monit.
signal
MT_RC: Reset
record. USER
[ 003 008 ]
CT30 SFMON: Overflow
≥1 MT_RC
[ 090 012 ]
0
MT_RC: No. monit.
1 ≥1 signals
[ 004 019 ]
0: don't execute
1: execute
MT_RC: Reset
record. EXT
[ 005 240 ]
12Z6155A_EN
Overload duration
In the event of an overload, the P139 determines the overload duration. The overload
duration is defined as the time between the start and end of the OL_ R C : R e c o r d . i n
p r o g r e s s signal.
MAIN: General
reset USER
[ 003 002 ]
1: execute
MAIN: General
reset EXT
[ 005 255 ]
OL_RC: Reset
record. EXT
[ 005 241 ]
OL_RC: Reset
record. USER
[ 100 003 ]
1: execute
50Z0137A_EN
Acquiring measured
overload data from the
motor protection
During a motor startup the measured values for the startup time, the maximum startup
current and heating during startup are determined and stored at the end of the startup
period.
OL_DA: Start-up
current
MP IP
r.m.s./Iref
OL_DA: Heat.
dur. start-up
19Z5280A_EN
Acquiring measured
overload data from the
thermal overload protection
Measured overload values are derived from the thermal overload protection’s measured
operating data. They are stored at the end of an overload event.
OL_RC: Record.
in progress C
[ 035 003 ]
MAIN: General
reset USER
[ 003 002 ]
1: execute ≥1
MAIN: General
reset EXT
[ 005 255 ]
OL_RC: Reset
record. EXT
[ 005 241 ]
OL_RC: Reset
record. USER
[ 100 003 ]
1: execute
12Z6238A_EN
OL_RC: Record. in
progress
[ 035 003 ]
THERM: Starting
k*Iref> +
[ 041 108 ]
MP: Starting R OL_RC: No.
k*Iref> overload
[ 041 057 ] [ 004 101 ]
MAIN: General
Reset USER
[ 003 002 ]
1: execute
MAIN: General
Reset EXT
[ 005 255 ]
OL_RC: Reset
record EXT
[ 005 241 ]
OL_RC: Reset
record USER
[ 100 003 ]
1: execute
12Z62C3B_EN
Time tagging
The date of each overload event is stored. The overload start or end signals are likewise
time-tagged by the internal clock. The date and time assigned to an overload event
when the event begins can be read out from the overload memory on the local control
panel or through the PC and communication interfaces. The time information (relative to
the onset of the overload) can be retrieved from the overload memory or through the PC
or one of the communication interfaces.
Overload logging
Protection signals during an overload event are logged in chronological order with
reference to the specific event. A total of eight overload events, each involving a
maximum of 200 start or end signals, can be stored in the non-volatile overload
memories. After eight overload events have been logged, the oldest overload log will be
overwritten, unless memories have been cleared in the interim. If more than 199 start or
end signals have occurred during a single overload event, then O L _ R C : O v e r l .
m e m . o v e r f l o w will be entered as the last signal.
In addition to the signals, the measured overload data will also be entered in the
overload memory.
The overload logs can be read from the local control panel or through the PC or
communication interfaces.
OL_RC: Record. C
in progress
[ 035 003 ]
OL_RC: Overload
n
Measured value 1 recording n
1 ≥1
MAIN: General
reset USER 0: don't execute
[ 003 002 ] 1: execute
1: execute
MAIN: General
reset EXT
[ 005 255 ]
OL_RC: Reset
record. EXT
[ 005 241 ]
12Z6117 A_EN
During a ground fault the P139 determines the following measured ground fault data:
Resetting measured
ground fault data
After pressing the reset key ‘C’ on the local control panel, the measured ground fault
data value is displayed as 'Not measured'. However, the values are not erased and can
continue to be read out through the PC and communication interfaces.
MAIN: General
reset USER
[ 003 002 ]
1: execute
MAIN: General
reset EXT
[ 005 255 ]
GF_RC: Reset
record. EXT
[ 005 242 ]
GF_RC: Reset
record. USER
[ 100 000 ]
1: execute
50Z01DWA_EN
S1 1 & C
R1
GFDSS: Grd.
fault pow./adm.
[ 009 037 ]
MAIN: General
reset USER
[ 003 002 ]
1: execute
MAIN: General
reset EXT
[ 005 255 ]
MAIN: Reset
LED
306 020
50Z0144A_EN
3-99 Measurement and storing the ground fault duration from steady state value evaluation
Residual current
The residual current flowing at the time when the time period set at G F D S S : t V N G >
has elapsed, is stored. Also stored is the active and reactive component of the residual
current determined at the time when the directional decision is issued. All measured
values are issued as per-unit quantities referred to the device’s nominal current Inom.
Neutral-point displacement
voltage
The neutral-point displacement voltage present at the time when the time period set at
G F D S S : t V N G > has elapsed, is stored.
GFDSS: Grd. C
fault pow./adm.
[ 009 037 ]
GF_DA: Current
IN IN p.u.
[ 009 021 ]
R
GFDSS: Direct.
forward/LS C
[ 009 035 ]
GFDSS: Direct.
backward/BS
[ 009 036 ]
GFDSS: Current GF_DA: Curr.
IN,act p.u. IN,act p.u.
[ 004 045 ] [ 009 022 ]
& R
GF_DA: Voltage
GFDSS: VNG VNG p.u.
304 150 [ 009 020 ]
R
MAIN: General
reset USER
[ 003 002 ]
1: execute
MAIN: General
reset EXT
[ 005 255 ]
MAIN: Reset
LED
306 020
50Z0145A_EN
3-100 Residual current and neutral-point displacement voltage from steady state value evaluation
S1 1 & C
R1
MAIN: General
reset USER
[ 003 002 ]
1: execute
MAIN: General
reset EXT
[ 005 255 ]
MAIN: Reset
LED
306 020
50Z0148A_EN
3-101 Measurement and storing the ground fault duration from steady state power evaluation
Residual current
The filtered and un-filtered residual current flowing at the time when the time period set
at G F D S S : O p e r a t e d e l a y I N has elapsed, is stored.
GF_DA: Current IN
IN p.u.
[ 009 021 ]
R
GF_DA: Curr. IN
GFDSS: 2IN filt. p.u.
filtered [ 009 025 ]
304 159
R
MAIN: General
reset USER
[ 003 002 ]
1: ausführen
MAIN: General
reset EXT
[ 005 255 ]
MAIN: Reset
LED
306 020
50Z0151A_EN
S1 1 & C
R1
GFDSS: Admittance R
ready
[ 038 167 ] R
GFDSS: Grd.
fault pow./adm.
[ 009 037 ]
MAIN: General
reset USER
[ 003 002 ]
1: execute
MAIN: General
reset EXT
[ 005 255 ]
MAIN: Reset
LED
306 020
50Z0152A_EN
3-103 Measurement and storing the ground fault duration from admittance evaluation
Admittance, conductance
and susceptance
Conductance and susceptance are stored at the time when the directional decision is
issued. The admittance value is measured at the time when the timer period set at
G F D S S : O p e r a t e d e l a y Y ( N ) > has elapsed.
Residual current
The residual current flowing at the time when the time period set at G F D S S : t V N G >
has elapsed, is stored. This measured value is issued as a per-unit quantity referred to
the device’s nominal current Inom.
Neutral-point displacement
voltage
The neutral-point displacement voltage present at the time when the time period set at
G F D S S : t V N G > has elapsed, is stored.
IN GF_DA: Current IN
p.u.
[ 009 021 ]
R
GFDSS: Oper.delay C
Y(N)> elapsed
304 175
GFDSS: Direct.
forward/LS C
[ 009 035 ]
GFDSS: Direct.
backward/BS
[ 009 036 ]
GFDSS: Conduct. GF_DA: Conduct.
G(N) p.u. G(N) p.u.
[ 004 192 ] [ 009 066 ]
& R
MAIN: General
Reset USER
[ 003 002 ]
1: execute
MAIN: General
Reset EXT
[ 005 255 ]
MAIN: Reset
LED
306 020
50Z0153A_EN
MAIN: General
reset USER + GF_RC: No. ground
[ 003 002 ] faults
1: execute [ 004 100 ]
≥1 R
MAIN: General
reset EXT
[ 005 255 ]
GF_RC: Reset
record. USER
[ 100 000 ]
1: execute
GF_RC: Reset
record. EXT
[ 005 242 ]
50Z01B8A_EN
Time tagging
The date of each ground fault event is stored. A ground fault’s individual start or end
signals are likewise time-tagged. The date and time assigned to a ground fault event
when the event begins can be read out from the ground fault memory on the local control
panel or through the PC and communication interfaces. The time information (relative to
the onset of the ground fault) that is assigned to the signals can be retrieved from the
ground fault memory or through the PC or communication interfaces.
In addition to the signals, the measured ground fault data will also be entered in the
ground fault memory.
The ground fault logs can be read from the local control panel or through the PC or
communication interfaces.
GF_RC: Record. C
in progress
[ 035 005 ]
n GF_RC: Ground
flt.record. n
Measured value 1
1 033 010
Measured value 2
2 033 011
Measured value 3
3 033 012
Measured value n
MAIN: Time tag 4 033 013
306 021
5 033 014
& 6 033 015
FT_RC: Record. in
progress
[ 035 000 ] 7 033 016
R 8 033 017
GF_RC: Reset
record. USER
[ 100 000 ]
1 ≥1
0: don't execute
MAIN: General 1: execute
reset USER
[ 003 002 ]
1: execute
MAIN: General
reset EXT
[ 005 255 ]
GF_RC: Reset
record. EXT
[ 005 242 ]
12Z6141 A_EN
When there is a primary system fault, the P139 collects the following measured fault
data:
Running time
Fault duration
Short-circuit current
Short-circuit voltage
Short-Circuit Impedance
Fault reactance (short-circuit reactance) in percent of line reactance and in Ω
Fault angle
Fault distance
Ground fault (short-circuit) current
Ground fault angle
Relative fault location
Fault location in km
≥1
MAIN: General ≥1
reset USER
[ 003 002 ]
1: execute ≥1
MAIN: General
reset EXT
[ 005 255 ]
50Z01A9A_EN
End of fault
Acquisition at the end of the fault.
Trigg., trip, GS end
Acquisition at the time
when an appropriately configured binary signal input is triggered during a general
starting state,
when a general trip signal is issued,
when a general starting state ends.
Depending on the setting a fault location output will occur during a general starting state
or during a general starting state with a simultaneous general trip signal.
3-108 Enabling of measured fault data acquisition and fault location output
Acquisition of
Fault data
The P139 selects a measuring loop based on the phase-selective starting decision.
The fault impedance (short-circuit impedance) and the fault direction are determined
from the voltage and current values collected from these measuring loops. With single-
phase starting signals with ground the current values, corrected by the ground factor, are
used for the selected measured variables. For three-phase starting signals with or
without ground the minimum voltage value and the associated phase-to-phase current
are selected from the phase-to-phase voltages as measured variables.
The fault must be present for at least 60 ms so that fault measured variables (short-
circuit data) may be determined.
To determine short-circuit data the selected measured variables Imeas and Vmeas are
applied when the fault was identified by the fault data acquisition function. One phase
current is selected as the fault current corresponding to the measuring loop selected.
For multi-pole starting it will be the fault current of the leading phase in the cycle.
The primary fault reactance is calculated from the per-unit fault reactance using the
nominal data for the set primary current and voltage transformers.
The ground fault data are only determined if a phase-to-ground loop has been selected
for the measurement by the fault data acquisition function. The geometric sum of the
three phase currents is displayed as the ground fault current. The ground fault angle is
the phase displacement between ground fault current and the selected measuring
voltage.
Only the short-circuit current is determined should an m.c.b. trip signal be present or the
transformer module fitted not include voltage transformers and the maximum phase
current is displayed.
Fault current and voltage are displayed as per-unit quantities referred to Inom and Vnom.
If the measured or calculated values are outside of the acceptable measuring range,
‘overflow’ is displayed.
FT_DA: Output
meas. values C 1,2
305 075
60 ms 0
MAIN: General C 1
starting ≥1
306 539
FT_DA: Fault
4 1 impedance, sec
[ 004 023 ]
R
MAIN: Sel. meas. 2 ... 3
loop A-G C 1
306 546 1
1 FT_DA: Fault
reactance,sec.
MAIN: Sel. meas. 4 [ 004 028 ]
loop B-G C 2 R
306 547
V < 2V
MAIN: Vmeas C
306 544
MAIN: General
reset USER
[ 003 002 ]
1: execute ≥1
MAIN: General
reset EXT
[ 005 255 ]
MAIN: Reset LED
306 020
50Z0155 B_EN
FT_DA: Line
length
[ 010 005 ]
FT_DA: Line
reactance
[ 010 012 ]
FT_DA: Output C
fault locat.
305 076
FT_DA: Fault
FT_DA: Fault location
reactance,sec.. [ 004 022 ]
[ 004 028 ] R
50Z01B4A_EN
Load impedance
Load angle
Residual current
The same measuring loop used to determine fault impedance is used to determine load
impedance and load angle. The load current and the voltage must exceed the
thresholds 0.1 Inom and 0.1 Vnom , respectively, in order for the load data to be
determined. If the thresholds are not reached or if the general starting signal was
shorter than 60 ms, the display ‘Not measured’ will appear.
MAIN: General 1
starting
306 539
60 ms 0
S1 1
R1
C 1
MAIN: Sel. meas. & S
loop A-G R
306 546
306 544 R
FT_DA: IA-kG
307 126 &
1
FT_DA: IB-kG
307 127 2
FT_DA: IC-kG
≥ 0.1 Vnom
307 128 3
4
UA-G C
UB-G
5
FT_DA: Load
UC-G imped.post-flt.
6 [ 004 037 ]
R
FT_DA: Resid.curr.
IC post-flt
[ 004 039 ]
R
IN
MAIN: General
reset USER
[ 003 002 ]
1: execute ≥1
MAIN: General
reset EXT
[ 005 255 ]
50Z0156B_EN
In addition, the user can set a logical "OR" combination of logic signals ('m out of n'
parameter) whose appearance will trigger fault recording.
Fault counting
Faults are counted and identified by sequential numbers.
FT_RC: I>
[ 017 065 ]
FT_RC: I>
IA triggered
[ 040 063 ]
IB
IC
FT_RC: Fct.
assig. trigger
[ 003 085 ]
Signal 1
Signal 2
m out of n
Signal 3
Signal n
Selected signals
FT_RC: Record.
FT_RC: Trigger trig active
USER [ 002 002 ]
[ 003 041 ]
12Z6221 A_EN
Time tagging
The date that is assigned to each fault by the internal clock is stored. A fault’s individual
start or end signals are likewise time-tagged. The date and time assigned to a fault
when the fault begins can be read out from the fault memory on the local control panel or
through the PC and communication interfaces. The time information (relative to the
onset of the fault) that is assigned to the signals can be retrieved from the fault memory
or through the PC or communication interfaces.
Fault recordings
Protection signals, including the signals during the settable pre-fault and post-fault
windows, are logged in chronological order with reference to the specific fault. A total of
eight faults, each involving a maximum of 200 start or end signals, can be stored in the
non-volatile fault memories. After eight faults have been recorded, the oldest fault
recording will be overwritten, unless memories have been cleared in the interim. If more
than 199 start or end signals have occurred during a single fault, then
F T _ R C : F a u l t m e m . o v e r f l o w will be entered as the last signal. If the time and
date are changed during the pre-fault time, the signal F T _ R C : F a u l t y t i m e t a g is
generated.
In addition to the fault signals, the RMS measured fault data will also be entered in the
fault memory.
The fault recordings can be read from the local control panel or through the PC or
communication interfaces.
FT_RC: Record. C
in progress
[ 035 000 ]
FT_RC: Fault mem.
Signal 1 + CT200 overflow
1 [ 035 001 ]
Signal 2 1 R
Signal 3 1
Signal n 1
FT_RC: Fault
recording n
1 [ * ]
FT_RC: Pre-fault
time
[ 003 078 ]
FT_RC: Post-
fault time
[ 003 079 ]
n FT_RC: Fault
recording n
Fault memory n
1 003 000
2 033 001
3 033 002
MAIN: General
reset USER &
[ 003 002 ]
1: execute R
MAIN: General
reset EXT
[ 005 255 ]
FT_RC: Reset
record. EXT
[ 005 243 ]
FT_RC: Reset
record. USER
[ 003 006 ]
0
1 1: execute
0: don’t execute
1: execute
12Z6161 B_EN
Phase currents
Phase-to-ground voltages
Residual current measured by the P139 at the T 4 transformer
Neutral-point displacement voltage measured by the P139 at the T 90 transformer
Reference voltage Vref (when a synchrocheck VT is fitted).
The signals are recorded before, during and after a fault. The window length for
oscillography recording before and after the fault can be set. A maximum time period of
16.4 s is available for recording. This period can be divided among a maximum of eight
faults. The maximum recording time per fault can be set. If a fault, including the set pre-
fault and post-fault times, lasts longer than the set maximum recording time, then
recording will terminate when the set maximum recording time is reached.
The pre-fault time is exactly adhered to if it is shorter than the set maximum recording
time. Otherwise the pre-fault time is set to the maximum recording time minus a
sampling increment, and the post-fault time is set to zero.
If the maximum recording time of 16.4 s is exceeded, the analog values for the oldest
fault are overwritten, but not the binary values. If more than eight faults have occurred
since the last reset, then all data for the oldest fault are overwritten.
The analog oscillography data of the fault record can only be read out through the PC or
communication interfaces.
When the supply voltage is interrupted or after a warm restart, the values of all faults
remain stored.
FR_RC: Record.
in progress C
[ 035 000 ]
FR_RC: Max.
recording time
[ 003 075 ]
FR_RC: Pre-fault
time
[ 003 078 ]
FR_RC: Post-
fault time
[ 003 079 ]
IA Analog channel 1
R
IB Analog channel 2
R
IC Analog channel 3
R
VC-G
Analog channel 6
R
IN Analog channel 7
R
VN-G
Analog channel 8
R
FR_RC: Reset
record. USER
[ 003 006 ]
1: execute ≥1
MAIN: General
reset USER
[ 003 002 ]
1: execute
MAIN: General
reset EXT
[ 005 255 ]
FR_RC: Reset
record. EXT
[ 005 243 ]
12Z6220A_EN
Enabling or disabling
DTOC protection
DTOC protection can be disabled or enabled via parameter settings. Moreover, enabling
can be carried out separately for each parameter subset.
When the inrush stabilization function (see: ‘Main Functions of the P139’) is triggered,
the 1st stage of the DTOC function is blocked.
The trip signals from all phase current stages are blocked by the auto-reclosing control
function (ARC) when this function is able to issue a trip command.
The trip signals from the DTOC function (stages I> and I>> only) can be blocked by the
short-circuit direction determination function. Depending on the setting of the short-
circuit direction determination function, the trip signal of stages I> or I>> will be enabled.
Negative-sequence current
stages
The P139 calculates the negative-sequence current from the three phase current values
according to this formula. The result depends on the M A I N : P h a s e s e q u e n c e
setting.
The timer stages can be blocked by appropriately configured binary signal inputs.
In addition these timer stages can also be automatically blocked by single-pole or multi-
pole starting (depending on the setting).
The trip signals from the negative-sequence current stages are only enabled if the
operating mode for the general starting has been set to 'With starting IN, Ineg'.
When the inrush stabilization function (see section ‘Main Functions of the P139’) is
triggered, the 1st stage of the negative-sequence current function is blocked.
When the short-circuit direction determination function (SCDD) is active, trip signals from
the DTOC negative-sequence current stages have no directional dependence.
The trip signals from all negative-sequence current stages are blocked by the auto-
reclosing control function (ARC) when this function is able to issue a trip command.
MAIN: Inrush
stabil.306trigg
014 &
MAIN: Rush
restr.selec.
306 401
fct.
DTOC: Enabled
[ 040 120 ] &
MAIN: Protection
active 306 001
MAIN: Dynam.
param. active
[ 040 090 ]
DTOC: Block.
tIneg> EXT DTOC: tIneg>
[ 036 141 ] C PSx
[ * ]
MAIN: Block
tim.st. IN,neg
306 400 DTOC: Ineg>
& c PSx
[ * ] t 0
DTOC: tIneg>
MAIN: Phase DTOC: Ineg> elapsed
sequence & c dynamic PSx [ 036 148 ]
[ 010 049 ] [ * ]
DTOC: Starting
IA Ineg>
IB & [ 036 145 ]
Ineg
IC
& DTOC: Trip signal
tIneg>
ARC: Blocking [ 036 151 ]
trip
[ 042 000 ]
DTOC: Ineg>>
& c PSx
[ * ] t 0 DTOC: tIneg>>
elapsed
DTOC: Ineg>> [ 036 149 ]
& c dynamic PSx
[ * ]
DTOC: Starting
Ineg>>
[ 036 146 ]
DTOC: Starting
Ineg>>>
[ 036 147 ]
DTOC: Trip signal
MAIN: Gen. start. & tIneg>>>
Mode PSx [ 036 153 ]
[ * ]
1: With start.
IN, Ineg
MAIN: Gen.
start. Mode PSx
[ * ] * Parameter MAIN: Gen.
1: With start. start. Mode PSx
IN, Ineg set 1 017 027
set 2 001 219
set 3 001 220
set 4 001 221 19Z5282B_EN
Enabling or disabling
DTOC residual current
stages
DTOC residual current stages can be disabled or enabled via setting parameters or
through binary signal inputs.
The timer stages can be blocked by appropriately configured binary signal inputs.
In addition these timer stages can also be automatically blocked by single-pole or multi-
pole starting (depending on the setting).
The trip signals from the residual current stages are only enabled if the operating mode
for the general starting has been set to 'With starting IN, Ineg'.
The trip signals from all residual current stages are blocked by the auto-reclosing control
function (ARC) when this function is able to issue a trip command.
The trip signals from the DTOC function (stages IN> and IN>> only) can be blocked by
the short-circuit direction determination function (SCDD). Depending on the setting of
the short-circuit direction determination function, the trip signal of stages IN> or IN>> will
be enabled.
IN>,>>,>>> PSx
IN>,>>,>>> PSx
12Z5104A
DTOC: Starting N
DTOC: Enabled 305 461
[ 040 120 ] &
DTOC: System IN
enabled
[ 040 133 ]
DTOC: Blocking DTOC: tIN>
tIN> EXT C
[ 041 063 ] PSx
[ * ]
DTOC: IN>
& c PSx
MAIN: Block [ * ] t
tim.st. IN,neg 0
306 400 DTOC: tIN>
DTOC: IN> dynamic elapsed
& c PSx [ 040 013 ]
[ * ]
DTOC: IN>>
& c PSx
[ * ] t 0 DTOC: tIN>>
elapsed
DTOC: IN>> [ 040 121 ]
& c dynamic PSx
[ * ]
DTOC: Starting
IN>>
MAIN: Dynam. [ 040 041 ]
param. active
[ 040 090 ]
DTOC: Blocking DTOC: tIN>>>
tIN>>> EXT C PSx
[ 041 065 ] [ * ]
DTOC: IN>>>
& c PSx
[ * ] t 0 DTOC: tIN>>>
DTOC: IN>>> elapsed
c dynamic PSx [ 039 079 ]
&
[ * ]
DTOC: Starting
IN>>>
[ 039 078 ]
DTOC: Starting
IN>>>>
[ 035 031 ]
* Parameter DTOC: IN> DTOC: IN> DTOC: tIN> DTOC: IN>> DTOC: IN>> DTOC: tIN>>
PSx dynamic PSx PSx PSx dynamic PSx PSx
set 1 017 003 017 081 017 008 017 009 017 086 017 010
set 2 073 015 073 035 073 027 073 016 073 036 073 028
set 3 074 015 074 035 074 027 074 016 074 036 074 028
set 4 075 015 075 035 075 027 075 016 075 036 075 028
* Parameter DTOC: IN>>> DTOC: IN>>> DTOC: tIN>>> DTOC: IN>>>> DTOC: IN>>>> DTOC: tIN>>>>
PSx dynamic PSx PSx PSx dynamic PSx PSx
set 1 017 018 017 087 017 019 072 018 072 036 072 030
set 2 073 017 073 037 073 029 073 018 072 105 073 030
set 3 074 017 074 037 074 029 074 018 072 202 074 030
set 4 075 017 075 037 075 029 075 018 072 219 075 030
12Z6280A_EN
SCDD: Block.
direct. tIN>>
304 464
As the IN> starting in the residual current stage commences, the hold time is reset.
At the same time, the starting time is accumulated when IN> starting commences.
As IN> starting ends, the timer stage D T O C : P u l s . p r o l . I N > , i n t P S x is started
and the charging of the accumulation buffer is thereby lengthened by the set value of
the timer stage.
The accumulation result is compared to the settable limit value at
DTOC: tIN>, interm. PSx.
If the limit value is reached and a general starting is present, then a trip results,
provided that it is permitted by the relevant MAIN settings:
MAIN: Block tim.st. IN,neg
(Address 017 015)
MAIN: Gen. starting mode
(Address 017 027)
MAIN: Fct.assig.trip cmd.1
(Address 021 001)
MAIN: Fct.assig.trip cmd.2
(Address 021 002)
If the limit value is reached while the timer stage
D T O C : P u l s . p r o l . I N > , i n t P S x is running, then a trip will occur when the next
general starting phase commences.
With each release of the trigger stage IN>, the set hold-time
D T O C : H o l d - t . t I N > , i n t m P S x is restarted. When the hold time has elapsed
or after the hold-time logic has issued a trip
(D T O C : T r i p s i g . t I N > , i n t m .), accumulation is stopped and the accumulation
buffer is cleared.
3-126 Signal flow for values below the accumulation limit value
DTOC: Pulse
prolong. runn.
DTOC: t2 N
Startings not
illustrated
have occured
here.
Settings
DTOC: Puls.prol. DTOC: tIN,interm. DTOC: Hold-t.
IN>,intPSx PSx tIN>,intmPSx
Setting Setting Setting
19Z5243A_EN
Note:
This description is also valid for IDMT2 (if there is no indication to the contrary).
The addresses given apply to IDMT1. The addresses for function group IDMT2 are
given in chapters 7 and 8.
For example, the address for I D M T 1 : G e n e r a l e n a b l e U S E R is 017 096
(given in the following picture), but the address for I D M T 2 : G e n e r a l e n a b l e
U S E R is 017 052.
The inverse-time overcurrent protection function (IDMT) operates with three separate
measuring systems for:
3-128 Disabling or enabling IDMT protection. (IDMT represents IDMT1 and IDMT2; the addresses apply to IDMT1.)
Time-dependent
characteristics
The measuring systems for phase currents, residual current and negative-sequence
current operate independently of each other and can be set separately. The user can
select from a large number of characteristics (see table below). The measured variable
is the maximum phase current, the negative-sequence current, or the residual current,
depending on the measuring system. The tripping characteristics available for selection
are shown in figures 3-129 to 3-132.
1000 1000
100 100
k=10
10 10 k=10
t/s k=1
t/s
1 1 k=1
k=0.1
0.1 k=0.05 0.1
k=0.1
k=0.05
0.01 0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/Iref I/Iref
S8Z50K1A S8Z50K2A
1000 1000
100 100
k=10
10 10
k=1
t/s t/s
k=10
1 1
k=0.1
k=1 k=0.05
0.1 0.1
k=0.1
0.01 k=0.05 0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/Iref I/Iref
S8Z50K3A S8Z50K4A
1000 1000
100 100
10 k=10 10
k=10
t/s t/s
1 k=1 1
k=1
I/Iref I/Iref
S8Z50K5C S8Z50K6C
1000
100
10
t/s
k=10
1
k=1
0.1
k=0.1
0.01 k=0.05
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/Iref
S8Z50K7C
Characteristic No. 7
1000 1000
100 100
10 10
t/s t/s
k=10
1 1
k=10
k=1
0.1 0.1
k=1
k=0.1 k=0.1
0.01 k=0.05 0.01 k=0.05
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/Iref I/Iref
S8Z50K8C S8Z50K9C
1000
100
k=10
10
t/s k=1
1
k=0.1
0.1 k=0.05
0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/Iref
S8Z50KAC
Characteristic No. 10
1000 1000
100 100
k=10
k=10
10 10
t/s k=1 t/s
k=1
1 1
k=0.1
k=0.1
k=0.05
0.1 0.1 k=0.05
0.01 0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/Iref I/Iref
S8Z50KBA S8Z50KCA
When the inrush stabilization function (see section ‘Main Functions of the P139’) is
triggered, the phase current stage is blocked.
The trip signal from the IDMT protection may also be blocked by the short-circuit
direction determination or the auto-reclosing control function. Depending on the setting
of the short-circuit direction determination the trip signal will be enabled. The trip signal
from the phase current stage is blocked by the auto-reclosing control function (ARC)
when this function is able to issue a trip command.
IDMT: Enabled
[ 040 100 ] &
MAIN: Protection
active
306 001 IDMT: Iref,P
C PSx
& [ * ]
IDMT: Starting A
IDMT: Iref,P 304 359
C
IDMT: Starting C
304 361
1.05 * Iref
IDMT: Starting
Iref,P>
IA & [ 040 080 ]
IB &
IC &
IDMT: Setting
Characteristic P IDMT: Characteristic
PSx PSx
[ * ]
0: Definite Time
IDMT: Min. trip
time P PSx 1: IEC Standard Inverse
[ * ] 2: IEC Very Inverse
IDMT: Factor kt,P 3: IEC Extr. Inverse
PSx 4: IEC Long Time Inv.
Setting [ * ]
5: IEEE Moderately Inv .
IDMT: Release P PSx
IDMT: Hold time P 6: IEEE Very Inverse
PSx
1: Without delay [ * ] 7: IEEE Extremely Inv.
2: Delayed as per 8: ANSI Normally Inv.
char. IDMT: Release P
PSx 9: ANSI Short Time Inv.
[ * ] 10: ANSI Long Time Inv.
11: RI-Type Inverse
IDMT: Block.
tIref,P> EXT C 12: RXIDG-Type Inverse
[ 040 101 ]
C
IDMT: Memory P
clear
[ 040 110 ]
IDMT: tIref,P>
elapsed
[ 040 082 ]
Parameter IDMT: Factor IDMT: Min. trip IDMT: Hold time IDMT: Release P
kt,P PSx time P PSx P PSx PSx
set 1 072 053 072 077 072 071 072 059
set 2 073 053 073 077 073 071 073 059
set 3 074 053 074 077 074 071 074 059
set 4 075 053 075 077 075 071 075 059
10Z5008B_EN
3-133 Phase current element. (IDMT represents IDMT1 and IDMT2; the addresses apply to IDMT1.) (Trip signal: see following figures)
IDMT1: tIref,P>
elapsed IDMT1: Trip signal
[ 040 082 ] tIref,P>
ARC: Blocking [ 040 084 ]
trip
[ 042 000 ]
SCDD: Block.
direct. tkIref>
304 465
IDMT1: ARC
Starting Iref,P>
304 367
IDMT1: Starting
Iref,P>
[ 040 080 ]
12Z5111 B_EN
2 1
21 23
12Z5112A
Negative-sequence
current stage
According to the following formulas the P139 will determine the negative-sequence
current and positive-sequence current, taking into account the set phase sequence
(alternative terminology: Rotary field):
I neg =
1
3
(
⋅ IA + a 2 ⋅ IB + a ⋅ IC ) I net =
1
3
(
⋅ IA + a ⋅ IB + a 2 ⋅ IC )
a = e j120°
a 2 = e j240°
The negative-sequence current is monitored by the P139 to detect when it exceeds the
set thresholds. Alternatively, two different thresholds can be active. The "dynamic"
threshold is active for the set hold time for the "dynamic parameters" (see section
‘Activation of Dynamic Parameters’) and the "normal" threshold is active when no hold
time is running. The IDMT protection will trigger when the 1.05-fold of the set reference
current value is exceeded by the negative-sequence current. Depending on the
characteristic selected and the residual current magnitude the P139 will determine the
tripping time. Moreover the tripping time will under no circumstances fall below a
settable minimum time threshold irrespective of the negative-sequence current flow
magnitude.
When the inrush stabilization function (see section: ‘Main Functions of the P139’) is
triggered, the negative-sequence current stage is blocked.
When the short-circuit direction determination function (SCDD) is enabled, a trip signal
from the IDMT negative-sequence current stage is always non-directional.
The trip signal from the negative-sequence current stage is blocked by the auto-
reclosing control function (ARC) when this function is able to issue a trip command.
IDMT: Enabled
[ 040 100 ] &
MAIN: Protection
active
306 001 IDMT: Iref,neg
C PSx
& [ * ]
IDMT: Iref,neg
& C dynamic
[ *
PSx
]
MAIN: Dynam.
param. active
[ 040 090 ]
1.05 * Iref
Ineg/Iref,neg
MAIN: Phase C
sequence
[ 010 049 ]
IDMT: Starting
IA & Iref,neg>
Ineg [ 040 107 ]
IB
IC
Parameter IDMT: Min.trip IDMT: Hold time IDMT: Release MAIN: Gen.
time neg PSx neg PSx neg. PSx start. mode PSx
set 1 072 078 072 072 072 060 017 027
set 2 073 078 073 072 073 060 001 219
set 3 074 078 074 072 074 060 001 220
set 4 075 078 075 072 075 060 001 221
12Z6211A_EN
3-136 Negative-sequence current stage. (IDMT represents IDMT1 and IDMT2; the addresses apply to IDMT1.)
(Note: Previous terminology of MAIN : Phase sequence was MAIN: Rotary field)
3-137 Selecting the measured variable. (IDMT represents IDMT1 and IDMT2; the addresses apply to IDMT1.)
The trip signal from the IDMT1 protection may also be blocked by the short-circuit
direction determination or the auto-reclosing control function. Depending on the setting
of the short-circuit direction determination the trip signal will be enabled. The trip signals
of the residual current stages IDMT1 and IDMT2 are blocked by the auto-reclosing
control function (ARC) when this function is able to issue a trip command.
IDMT: Enabled
[ 040 100 ] &
MAIN: System IN
enabled
[ 040 133 ]
IDMT: Iref,N
MAIN: Dynam. & C PSx
param. active [ * ]
[ 040 090 ]
IDMT: Iref,N
& C dynamic
[ *
PSx
]
C
1.05 * Iref
IDMT: tIref,N>
elapsed
[ 040 083 ]
Parameter IDMT: Factor IDMT: Min. trip IDMT: Hold time IDMT: Release N
kt,N PSx time N PSx N PSx PSx
set 1 072 055 072 079 072 073 072 061
set 2 073 055 073 079 073 073 073 061
set 3 074 055 074 079 074 073 074 061
set 4 075 055 075 079 075 073 075 061
12Z6210A_EN
3-138 Residual current stage. (IDMT represents IDMT1 and IDMT2; the addresses apply to IDMT1.) (Trip signal: see following figures)
IDMT1: tIref,N>
elapsed IDMT1: Trip signal
[ 040 083 ] tIref,N>
[ 040 085 ]
ARC: Blocking
trip
[ 042 000 ]
SCDD: Block.
direct. tkINref>
304 466
12Z5113 B_EN
2 2
22 24
12Z5114A
Holding time
Depending on the current flow the P139 will determine the tripping time and a timer
stage is started. The setting of the hold time defines the time period during which the
IDMT protection starting time is stored after the starting has dropped out. Should
starting recur during the hold time period then the time of the renewed starting will be
added to the time period stored. When the starting times sum reach the tripping time
value determined by the P139 then the corresponding signal will be issued. Should
starting not recur during the hold time period then, depending on the setting, the memory
storing the accumulated starting times value will either be cleared without delay or
according to the characteristic set. In figure 3-141 the effect of hold time is shown by the
example of a phase current stage.
3-141 Effect of hold time shown with a phase current stage as an example
Example A: Hold time determined is not reached.
Example B: Hold time determined is reached.
The P139 provides short circuit direction determination (SCDD). With this feature it is
possible to apply the P139 for directional definite-time overcurrent protection and
directional inverse-time overcurrent protection. Two separate measuring systems are
available for this purpose for:
As an example for a single-pole fault in phase A to ground the phase A current value (I),
the phase B to phase C voltage value (V) and the characteristic angle = +45° are
selected as measured variables (see figure 3-143).
The vector of the selected phase-to-phase voltage is the reference quantity. Beginning
with the reference quantity the characteristic angle αP will determine the measuring
relation. Depending on the type of fault the P139 will present various characteristic
angles. The measuring relation is defined as the angle bisector for the directional zone
"Forward". Forward directional is apparent if the vector of the selected phase current
lies in the range ≤ ± 90° of the measuring relation.
Backward directional is apparent if the vector of the selected phase current lies in the
range > ± 90° of the measuring relation.
3-143 Example for the forming of a directional phase current stage decision with a single-pole fault in phase A to ground (A-G) and with an
inductive system and a phase sequence A-B-C (or clockwise rotary field direction)
Enabling for
phase current stages
Direction determination for phase current stages is only enabled if the following
conditions are met simultaneously:
Voltage memory can be applied when 3-pole faults have occurred. (See description at
the end of this section.)
After being enabled and depending on the direction determination decision one of the
following signals will be issued:
2: A – C – B
SCDD: Determin.
P enabled
304 456
MAIN: Starting
A int.
306 513
MAIN: Starting
B int. Starting Selected meas. var. Characteristic angle αP
306 514
IA at Setting at Setting
Rotary field Rotary field
IB
A – B – C A – C – B
IC
A IA UB-C +45° +135°
UA-G + B IB UC-A +45° +135°
UB-G - C IC UA-B +45° +135°
UC-G + A-B IA UB-C +60° +150°
SCDD: Fault P
forward
[ 036 018 ]
Direction determination
SCDD: Fault P
backward
[ 036 019 ]
19Z5029B_EN
A blocking signal for the first DTOC phase current stage is formed when one of the
following conditions is met:
The direction for tI> is set to 'Forward directional' and the short-circuit direction
determination detects a fault in backward direction.
The direction for tI> is set to 'Backward directional' and the short-circuit direction
determination detects a fault in forward direction.
A blocking signal for the second DTOC phase current stage is formed when one of the
following conditions is met:
The direction for tI>> is set to 'Forward directional' and the short-circuit direction
determination detects a fault in backward direction.
The direction for tI>> is set to 'Backward directional' and the short-circuit direction
determination detects a fault in forward direction.
A blocking signal for the IDMT phase current stage is formed when one of the following
conditions is met:
The direction for tIref,P> is set to 'Forward directional' and the short-circuit direction
determination detects a fault in backward direction.
The direction for tIref,P> is set to 'Backward directional' and the short-circuit direction
determination detects a fault in forward direction.
In case the direction determination function is not enabled (e.g. with a M.c.b. trip) it is
possible to select whether stages set to 'Forward directional' may be operated with
biased tripping by enabling S C D D : T r i p b i a s P S x .
SCDD: Block.
direct. tkIref>
19Z5030 B_EN
3-146 Forming the blocking signals for the phase current stages
The reference quantity is the neutral-point displacement vector. Beginning with the
reference quantity the characteristic angle will determine the measuring relation. The
measuring relation is defined as the angle bisector for the directional zone "Forward".
Forward directional is apparent if the vector of the residual current lies in the range
≤ ± 90° of the measuring relation.
Backward directional is apparent if the vector of the residual current lies in the range
> ± 90° of the measuring relation.
In the following example the system neutral is grounded with a relatively low resistance.
Here the residual current apparent with a single-pole fault in phase A to ground (A-G)
and a forward directional fault will take up the approximate position as shown in figure
3-147. With the characteristic angle αN = -45° a forward directional decision will be
issued.
3-147 Example for forming a directional decision in the residual current stage
SCDD: Evaluation
VNG PSx
[ * ]
VN-G 2
1
VA-G
VB-G 1 ... 2 SCDD: VNG
310 026
VC-G
1: Calculated
2: Measured
Enabling for
residual current stages
Direction determination for residual current stages is only enabled if the following
conditions are met simultaneously:
SCDD: Enabled
[ 040 098 ]
MCMON: Meas.
circ. V faulty
[ 038 023 ]
MAIN: Starting
N int.
306 516
DTOC: Starting
IN>>
[ 040 041 ]
SCDD: VNG>
DTOC: Starting PSx
IN>>> [ * ]
[ 039 078 ]
SCDD: VN-G
310 026
SCDD: Determin.
N enabled
304 455
IN SCDD: Resid.
curr.stage bl.
304 454
19Z6451 A_EN
After being enabled and depending on the direction determination decision one of the
following signals will be issued:
IN
Direction
determination
SCDD: VN-G
310 026
SCDD: Ground
fault forward
[ 040 037 ]
SCDD: Ground
fault backw.
[ 040 038 ]
A blocking signal for the first DTOC residual current stage is formed when one of the
following conditions is met:
The direction for tIN> is set to 'Forward directional' and the short-circuit direction
determination detects a fault in backward direction.
The direction for tIN> is set to 'Backward directional' and the short-circuit direction
determination detects a fault in forward direction.
A blocking signal for the second DTOC residual current stage is formed when one of the
following conditions is met:
The direction for tIN>> is set to 'Forward directional' and the short-circuit direction
determination detects a fault in backward direction.
The direction for tIN>> is set to 'Backward directional' and the short-circuit direction
determination detects a fault in forward direction.
A blocking signal for the IDMT residual current stage is formed when one of the following
conditions is met:
The direction for tIref,N> is set to 'Forward directional' and the short-circuit direction
determination detects a fault in backward direction.
The direction for tIref,N> is set to 'Backward directional' and the short-circuit direction
determination detects a fault in forward direction.
In case the direction determination function is not enabled (e.g. with a M.c.b. trip) it is
possible to select whether stages set to 'Forward directional' may be operated with
biased tripping by enabling S C D D : T r i p b i a s P S x . In case of a phase current
starting bias tripping in the residual current stage may be suppressed by enabling
SCDD: Block. Bias G PSx.
SCDD: Block.
direct. tkINref>
19Z5033 B_EN
3-150 Forming the blocking signals for the residual current stages
Signaling logic
Fault directional signals generated by the directional determination function of the phase
and residual current stages are grouped together to a combined function.
3-151 Fault signals from phase or residual current stages forward or backward directional
Short-circuit direction
determination using
voltage memory
The short-circuit direction determination (SCDD) function group is subdivided into two
subsets.
For direction determination in a residual current system the measured residual current IN
and the vector addition of the phase-ground voltages are applied.
In this case voltage memory is not used.
For direction determination in a phase system the SCDD function uses the fault-
dependent short-circuit current and – in general – the phase-to-phase, un-faulted
voltages (not involved in the short-circuit) assigned to the type of fault. This ensures that
with single-pole and two-pole faults there is always sufficient voltage available for
direction determination.
This procedure can also be applied to three-pole faults with a phase-to-phase voltage
> 200 mV.
Should a three-pole fault occur close to the point of measurement, there could be such a
large 3-phase voltage drop, that direction determination on above basis is no longer
possible. For such fault occurrences there is a voltage memory available from which the
SCDD function can obtain the necessary voltage information for direction determination.
With a three-pole fault in the phase-current stage the measurement loop voltage
(VABmeas) is compared to the selected operate value (Vop.Val.) of the voltage memory
set by the user at S C D D : O p e r . v a l . V m e m o r y P S x . If VABmeas < Vop.Val. then
the SCDD function will not use VABmeas but will revert to the voltage memory, if it has
been enabled. The following signal is issued:
If the voltage memory has not been enabled (i.e. |Delta f| > 2.5 Hz) the SCDD function
will check if VABmeas is sufficient for direction determination.
Should the result with a disabled voltage memory be VABmeas > 200 mV the direction
will be determined on the basis of VABmeas. The following signal is issued:
If V12meas < 200 mV, a forward fault is detected if the voltage memory is disabled and if
the pre-orientation is active (set under S C D D : T r i p b i a s ), otherwise the directional
decision is blocked. The following signal is issued:
To ensure rapid clearing with manual closing, the manual close signal must be applied
not only to the circuit breaker but at the same time also to the P139. With the manual
close command a settable timer stage will be triggered, as long as there is no close
request present from the ARC and no HSR cycle from an external auto reclose control is
operating. By setting a parameter it is possible to choose which starting decisions from
the overcurrent protection will generate a trip signal while the timer stage is running.
An internal blocking signal is generated together with the trigger signal for the timer
stage. This internal blocking signal will prevent that ARC is activated during an existing
fault when a manual close signal is issued.
Protective signaling
Protective signaling is used together with the short-circuit direction determination in
power systems with single-side infeed and a subsequent parallel line configuration (line
section). Selective instantaneous clearing of the line section affected by the fault is
initiated by this function, while the DTOC or IDMT tripping times are bypassed.
Disabling or enabling
protective signaling
Disabling or enabling may be carried out with a parameter or binary signal inputs.
It must be activated.
There is no external block.
There is no transmission fault.
Setting up a
communications link
When setting up a communications link the make contact or the break contact
(dependent on the selected transmission relay operating mode 'Transm. rel. make con.'
or 'Transm. rel. break con.') is to be connected by pilot wires to the input labeled
"PSIG: R e c e i v e E X T " at the remote station (see Chapter 5 "Installation and
Connection" and figure 3-154). With both operating modes and in the idle state there is
a receive signal (DC loop closed) present at the local and at the remote station.
S8Z 5031B_EN
3-154 Protective signaling over pilot wires, operating mode selected 'Transm. rel. break con.'
Operation of
protective signaling
When a general starting condition is issued the DC loop is opened without delay (Send).
Closing again of the DC loop with the general starting condition present after the set
tripping time has elapsed occurs according to the operating mode selected at
PS I G : D i r e c . d e p e n d e n c e P S x and dependent on the directional decisions:
No No No No
No No No Yes
No Yes No No
No Yes No Yes
Yes No No Yes
When protective signaling is not ready the DC loop is open when the operating mode is
set to 'Transm. rel. make con.' and it is closed when the operating mode is set to
'Transm. rel. break con.'
PSIG: Tripping
PSIG: Ready C time PSx
[ 037 027 ] [ * ]
SCDD: Fault P
forward
[ 036 018 ]
SCDD: Fault P
backward
[ 036 019 ]
SCDD: Ground
fault forward
[ 040 037 ]
SCDD: Ground
fault backw.
[ 040 038 ]
PSIG: Release t.
send PSx
[ * ]
PSIG: Send
(signal)
[ 036 035 ]
PSIG: Send
(transm.relay)
[ 037 024 ]
PSIG: Test
telecom. USER
[ 015 009 ] PSIG: DC loop
op. mode PSx
[ * ]
0
1 1
0: don't execute 2
1: execute 1: Transm.rel.break con
2: Transm.rel.make con.
PSIG: Test
telecom. chann.
[ 034 016 ]
PSIG: Test
telecom. EXT
[ 036 038 ]
19Z6423 A_EN
In order to test the DC loop the communications link may be broken by setting the
parameter at P S I G : T e s t t e l e c o m . U S E R to 'execute'.
Under certain conditions the automatic reclosure control function (ARC) will cause a line
section to be cleared and then, when the dead time has elapsed, automatic reclosure of
the line section will occur.
Figure 3-157 shows an example for the usual sequence of a failed high-speed reclosure
(HSR) followed by a subsequent successful time-delay reclosure (TDR).
ARC blocking
Under certain conditions the ARC will be blocked and the signal A R C : B l o c k e d will
be issued, provided that one of the following conditions is met:
When all blocking conditions have been removed, the blocking time is started. When the
blocking time has elapsed, ARC blocking is canceled.
Tripping times
When protection functions operating with auto-reclosure control are started, the tripping
times (HSR or TDR) are started together with the operative time. If the tripping time has
elapsed during an active ARC cycle while the operative time is still running, a trip signal
is issued. The HSR or TDR trip time having caused the trip signal also determines which
dead time (HSR or TDR) is to be triggered. Once the dead time commences, all tripping
times already triggered and the operative time will be terminated.
The beginning of the following starts or input signals trigger the tripping times provided
that the starting conditions are met and the respective tripping times are not blocked.
If short-circuit direction determination (SCDD) is enabled, then some of the starting
signals are directional:
General starting
DTOC Starting I> (directional)
DTOC Starting I>> (directional)
DTOC Starting I>>>
DTOC Starting IN> (directional)
DTOC Starting IN>> (directional)
DTOC Starting IN>>>
IDMT Starting Iref,P> (directional)
IDMT Starting Iref,N> (directional)
IDMT starting Iref,neg>
Start by programmable logic
Ground fault direction determination by steady-state values (GFDSS) has operated
and detected one of the following faults:
GFDSS starting fault 'forward/LS'
GFDSS starting Y(N)>
GFDSS starting fault 'forward/LS' or GFDSS starting Y(N)>
If - in the operating mode HSR/TDR permitted - only one of the starting conditions listed
above applies, then the first trip signal is always generated by the HSR trip time stage,
regardless of the duration of the HSR or TDR tripping time setting. HSR precedes TDR.
If more than one starting is present then the trip signal will be issued after the HSR
tripping time that has elapsed first. As an exception, a TDR will be triggered first after
having elapsed first, if the associated HSR tripping time is set to Blocked.
If the trip signal has been generated by a TDR tripping time stage, then no HSR will be
initiated within the same ARC cycle.
The ARC trip signal must be included in the ‘m out of n’ selection of the trip commands.
ARC: HSRtrip.t.
Iref,P PSx
[ * ]
ARC: HSRtrip.t.
Iref,N PSx
[ * ]
IDMT: ARC
Starting Iref,N>
304 368
ARC: HSRtr.t.
Iref,neg
PSx
[ * ]
IDMT: Starting
Iref,neg>
[ 040 107 ]
ARC: Block/
reset HSR
303 104
ARC: TDRtrip.t.
Iref,P PSx
[ * ]
ARC: TDRtrip.t.
Iref,N PSx
[ * ]
ARC: TDRtr.t.
Iref,neg
PSx
[ * ]
AWE: Block/
reset TDR
303 105
Parameter ARC: HSRtrip.t. ARC: HSRtrip.t. ARC: HSRtr.t. ARC: TDRtrip.t. ARC: TDRtrip.t. ARC: TDRtr.t.
Iref,P PSx Iref,N PSx Iref,negPSx Iref,P PSx Iref,N PSx Iref,negPSx
set 1 015 094 015 096 015 034 015 095 015 097 015 035
set 2 024 106 024 107 024 108 024 118 024 119 024 120
set 3 024 156 024 157 024 158 024 168 024 169 024 170
set 4 025 106 025 107 025 108 025 118 025 119 025 120
12Z6230 A_EN
3-164 Tripping time, part 3 (In this figure IDMT represents IDMT1)
Except by the setting value Blocked the TDR tripping time stages are blocked or reset by
one of the following conditions:
ARC cycle
An ARC cycle begins, provided that the starting condition is met, with the presence of a
relevant starting option (DTOC/IDMT starting, starting via programmable logic, GFDSS,
or start of a test HSR), as long as the signal A R C : R e a d y is present at this time.
As the ARC cycle proceeds, the signal A R C : R e a d y is no longer taken into account.
An ARC cycle is running if the ARC is not blocked and one of the following conditions is
met:
Example of programmable
logic in the ARC
This example (see figure ) illustrates the possible interconnection and the binary signal
output for starting the tripping time stage via a binary signal input.
By using the programmable logic a binary signal input with serial operate delay and an
AND element is implemented. The function AR C : Bl o c k i n g tr i p "NOT" has been
assigned to the second input on this AND element. The output from the AND element
must be included in the configuration of the ‘m out of n’ selection for the general trip
command. The tripping time can be started by the output signal
ARC: Start by logic.
For this example the following list parameters need to be set from the local control panel
(see the section on ‘Setting a List Parameter’ in the chapter entitled ‘Local Control’).
List Parameter
LOGIC: Fct.assignm. OR e.g. LOGIC: Input 4 EXT
output 1 (address 034 003)
(address 030 000)
LOGIC: Fct.assignm. OR LOGIC: Output 1 (t)
output 2 (address 042 033)
AND NOT ARC: Blocking trip
(address 042 000)
In general, any equation within the programmable logic function can be used to start the
ARC tripping time.
One of the options offered by the programmable logic is the triggering of the ARC by an
external protection device.
While the ASC function is enabled, reclosure requires a close enable by the ASC
function, which implements a check of the synchronism conditions.
3-170 ARC sequence control. (In this figure IDMT represents IDMT1.)
If the starting conditions are met then any ARC-relevant protection startings will trigger
an ARC cycle. The startings set off the associated tripping time stages and the
operative time. If an HSR tripping time is running during the operative time then the
signal A R C : T r i p s i g n a l is issued and this signal can lead to a trip command if the
function assignment for the trip commands is configured appropriately. With the release
of the starting, the operative time is terminated and the HSR dead time begins. If there
is no starting during the dead time, a reclosure command is issued once the dead time
has elapsed. The reclaim time is started simultaneously. If during the reclaim time there
is no starting with trip command, the signal ARC: R e c l o s u r e s u c c e s s f u l is issued
and the ARC cycle is terminated once the reclaim time has elapsed.
If the HSR does not succeed and another starting occurs then a TDR is started if at least
one TDR is permitted. If TDR after HSR is not permitted then the current reclaim time
will be the last reclaim time of the ARC cycle. If the last reclaim time has elapsed and
another starting occurs then the tripping time stages are no longer started. Instead the
signal AR C : Bl o c k i n g tr i p is set to a logic value of ‘0’ and a trip by other protection
functions is enabled. If a trip signal occurs during the last reclaim time then it will be
regarded as a final trip. The ARC cycle is completed after the last reclaim time has
elapsed.
If the operative time has elapsed before the starting drops out, the last reclaim time will
be started directly and the blocking of protection trip signals is cancelled.
During the dead time, the P139 keeps checking whether any ARC-relevant startings
occur. If this is the case, the last reclaim time is started and the blocking of protection
trip signals is cancelled.
While the ASC function is enabled, the procedures described in the following section
"Joint Operation of the ARC and ASC Functions" are also applicable.
3-171 HSR signal sequence (example shown is with ASC disabled – see also next section "Joint Operation of the ARC and ASC Functions")
Figure shows the joint operation of the ARC and ASC functions, illustrated for a high-
speed reclosure (HSR).
If the starting conditions are met then any ARC-relevant protection startings will trigger
an ARC cycle. The startings set off the associated tripping time stages and the
operative time. If a HSR tripping time is running during the operative time then the signal
A R C : T r i p s i g n a l is issued, and this signal can lead to a trip command if the
function assignment for the trip commands is configured appropriately. With the release
of the starting, the operative time is terminated and the HSR dead time begins. After the
dead time has elapsed, a close request is sent to the ASC. The ASC checks to
determine whether reclosure is possible. If a positive decision is reached during the
ASC operative time, then there is a close enable, and the close command is issued.
If the ASC is disabled or deactivated, or if its decisions are to be ignored, then a close
command is issued immediately.
Moreover, the reclaim time is started. If during the reclaim time there is no starting with
trip command, the signal ARC: R e c l o s u r e s u c c e s s f u l is issued and the ARC
cycle is terminated once the reclaim time has elapsed.
If the ASC function decides against a reclosure then the reclaim time is started and the
ARC cycle is completed after the reclaim time has elapsed.
Test HSR
A test HSR can only be triggered when the ARC is ready to operate and if the operating
mode has been set to Test HSR only permit. In this operating mode, the blocking of the
trip signals from the DTOC, IDMT and other protection functions is cancelled so that any
system fault can be properly cleared.
Once a test HSR has been triggered, a trip signal of defined duration is issued.
The subsequent sequence corresponds to a successful HSR (open and reclose
command when the HSR dead time has elapsed). Once the close command pulse time
has elapsed, further triggering during the reclaim time does not result in a further HSR.
A test HSR can be triggered either via setting parameter or via a binary signal input and
adds an increment to the A R C : N u m b e r H S R counter.
Each ‘Test HSR’ request that does not result in a test HSR generates the signal
ARC: Reject test HSR.
Multiple reclosures using TDRs are possible if the operating mode is set accordingly. A
TDR may occur after a HSR if reclosure has occurred as the result of the HSR or if the
operating mode set for the ARC allows only TDRs. This is only possible if the setting for
A R C : N o . o f p e r m i t . T D R P S x (number of permitted TDRs) is not zero.
If the starting conditions are met then any ARC-relevant protection startings will trigger
the associated tripping times. The operative time is started simultaneously. If a TDR
tripping time is running during the operative time then the signal A R C : T r i p s i g n a l
is issued and this signal can lead to a trip command if the function assignment for the trip
commands is configured appropriately. With the release of the starting, the operative
time is terminated and the TDR dead time begins. If there is no starting during the dead
time, a reclosure command is issued once the dead time has elapsed. The reclaim time
is started simultaneously. If no further TDR is permitted during the current ARC cycle
then this will be the last reclaim time. If the last reclaim time has elapsed and another
starting occurs then the tripping time stages are no longer started. Instead the signal
A R C : B l o c k i n g t r i p is set to a logic value of ‘0’ and a final trip by other protection
functions is enabled. If a trip signal occurs during the last reclaim time then it will be
regarded as a final trip. The ARC cycle is completed after the last reclaim time has
elapsed. If during the last reclaim time there is no starting with trip command, the signal
A R C : R e c l o s u r e s u c c e s s f u l will be issued.
If there is a new starting during the reclaim time and at least one TDR is still permitted
then the reclaim time is terminated and another trip is issued when the tripping time has
elapsed. Once the dead time has elapsed, a further reclosure command is issued.
If the operative time has elapsed before the starting drops out, the last reclaim time will
be started directly and the blocking of protection trip signals is cancelled.
During the dead time, the P139 keeps checking whether any ARC-relevant startings
occur. If this is the case, the last reclaim time is started and the blocking of protection
trip signals is cancelled.
While the ASC function is enabled, the procedures described in the previous section
"Joint Operation of the ARC and ASC Functions" are also applicable.
3-174 Signal sequence of a failed HSR followed by a failed TDR and then by a final successful TDR (example shown is with ASC disabled)
1 ≥1
MAIN: General 0: don't execute
reset USER
[ 003 002 ] 1: execute
1: execute
MAIN: General
reset EXT
[ 005 255 ]
ARC: Reset
counters EXT
[ 005 244 ]
12Z6147 A_EN
The maximum number of CB operations within an ARC cycle (or within a specific time
period) may be set with parameter M A I N : C B 1 m a x o p e r . c a p . Associated with
this parameter is the counter at M A I N : C B 1 a c t . o p e r . c a p . to which the
maximum number of CB operations permitted is assigned as soon as the positive edge
of an event is present that has been selected by a '1 out of n' parameter at
MAIN: CB1 ready fct.assign.
The automatic synchronism check (ASC) function allows the device to verify that before
a close or reclose command is issued synchronism exists between system sections that
are to be synchronized (paralleled) or whether one of the system sections is de-
energized. In order to check for synchronism, two voltages – generally the voltages on
the line and busbar sides – are compared for differences in frequency, angle, and
voltage. Connecting the reference voltage transformer will determine which of the
system sections will provide the reference voltage (e.g. the line side or the busbar side).
The measurement loop must be set to correspond to the reference voltage connection
(A S C : M e a s u r e m e n t l o o p P S x ) so that the correct measuring voltage is
selected for the comparison. In the connection example shown in the section entitled
'Conditioning the Measured Variables' (chapter 3 / MAIN), the busbar voltage VA-B is the
reference voltage.
No
Yes
ASC: Enable
PSx
ASC: Enabled
No
Yes
Address
Address
ASC: Enabled
ASC: Enable EXT
ASC: Enable USER
don't execute
execute
don't execute
execute
The user can also specify separately for high-speed reclosures (HSR) and time-delay
reclosures (TDR) whether reclosure will be carried out with or without a check.
Close request
The ASC function can be triggered by ARC, via setting parameters, from an
appropriately configured binary signal input (A S C : C l o s e r e q u e s t E X T ), or via a
close request from the control function. Close requests via a setting parameter, the
binary signal input or the control function are only accepted if no ARC cycle is running.
The ASC operative time is started with the close request. If the close enable is issued
before the ASC operative time has elapsing, the close command is issued. Otherwise
an A S C : C l o s e r e j e c t i o n signal is generated for 100 ms.
Voltage-checked
Sync.-checked
Voltage/synchronism-checked
Voltage-checked
The synchronism-checked close enable can be bypassed using the voltage-checked
close enable without affecting the former. For this purpose the three phase-to-ground
voltages and the reference voltage Vref are monitored to determine whether they exceed
or fall below the set threshold values (A S C : V > v o l t . c h e c k and
A S C : V < v o l t . c h e c k ). Depending on the operating mode selected for the voltage
check, all three phase-to-ground voltages need to exceed or fall below the set value in
order to meet the condition for voltage-checked closing. If the conditions corresponding
to the set operating mode for the voltage-checked synchronism check are met, then the
close enable is issued after the set minimum time has elapsed
(A S C : t m i n v o l t . c h e c k ). The following operating modes for voltage checking can
be selected separately for each parameter subset:
ASC: Enabled
ASC: Active
VA G
VB G
VC G
V V
ASC: Op.mode ASC: V> volt. ASC: V< volt. ASC: tmin volt.
volt.chk.PSx check PSx check PSx check PSX
set
set
set
set
19Z5233A_EN
Synchronism-checked
Before a close enable is issued, the ASC checks the voltages for synchronism.
Synchronism is recognized if the following conditions are met simultaneously:
The three phase voltage and the reference voltage must exceed the set threshold
value (A S C : V > s y n c . c h e c k ) . When with a three-phase voltage the setting of
M A I N : N e u t r a l - p o i n t t r e a t . is 'Low-imped. grounding' both the phase-to-ground
and the phase-to-phase voltages are checked. If the setting is "Isol./res.w.start.(or
w/o st.)PG" only the phase-to-phase voltages are checked.
The difference in magnitude between measuring voltage and reference voltage must
not exceed the set threshold value (A S C : D e l t a V m a x ).
The frequency difference between measuring voltage and reference voltage must not
exceed the set threshold value (A S C : D e l t a f m a x ).
The angle difference between measuring voltage and reference voltage must not
exceed the set threshold value (A S C : D e l t a p h i m a x ). In these comparisons
the set offset angle A S C : P h i o f f s e t is taken into account.
If these conditions are met for at least the set time A S C : t m i n s y n c . c h e c k , then a
close enable is issued. The ASC operating time for determination of differences in
voltage, angle, and frequency is approximately 100 ms.
The voltage magnitude difference, angle difference, and frequency difference are stored
as measured synchronism data at the time the close request is issued. In the event of
another close request, they are automatically overwritten by the new data.
Voltage/synchronism-
checked
If this setting has been selected, then the close enable is issued if the conditions for
voltage- or synchronism-checked closing are met.
The ASC cycle and the operating time are started by the test close request.
The network synchronism is checked during the whole operating time and
A S C : C l o s e e n a b l e is set accordingly. If at the end of the operate time no network
synchronism is registered, a 100 ms signal A S C : C l o s e r e j e c t i o n is issued.
2
ASC: >
Operative time PSx
set
set
set
set
19Z5230A_EN
3-185 Integrating the ASC function into the control and monitoring of switchgear units
Outside of the ASC cycle the measured values have the status of "not measured".
ASC: Transm.cycle,
meas.v.
101 212
ASC: Cycle
running
038 019
ASC: Voltage
Vref
004 087
ASC: Angle
difference
004 089
ASC: Frequ.
difference
004 090
19Z5231A_EN
ASC counters
The following ASC signals are counted:
The counters can be reset individually (at the address at which they are displayed) or as
a group.
ASC: Reset
counters USER
[ 003 089 ]
0: don’t execute
1: execute
47Z1377A_EN
By using the ARC function it is possible to intervene in the functional sequence of ground
fault direction determination using steady-state values.
GFDSS: Enable
PSx
[ * ]
0
1
0: no
1: yes
GFDSS: General
enable USER
[ 016 060 ]
GFDSS: Enabled
& [ 042 096 ]
0
1
0: no
1: yes
&
MAIN: Protection
active
306 001
GFDSS: Operating
mode
[ 016 090 ]
1
2
3
1: Steady-state power
2: Steady-state current
3: Steady-state admitt.
GFDSS: GF (pow.)
& ready
[ 038 026 ]
GFDSS: GF (curr.) GFDSS: GF (pow.)
eval. EXT not ready
[ 038 020 ] [ 038 027 ]
GFDSS: GF (curr.)
& ready
[ 038 028 ]
GFDSS: GF (curr.)
not ready
[ 038 029 ]
GFDSS: GF (curr.)
evaluat.
[ 039 071 ]
GFDSS: Admit-
& tance ready
[ 038 167 ]
3-188 Enable/disable the ground fault direction determination using steady-state values
EWATT: Eval-
uation VNG PSx
[ * ]
VN-G 2
1
VA-G
VB-G 1 ... 2 GFDSS: VN-G
304 150
VC-G
1: Calculated
2: Measured
The ground fault direction determination using steady-state values requires the neutral-
point displacement voltage and the residual current values to be able to determine a
ground fault direction. The frequency provided by the setting f/fnom is filtered from these
values by using a Fourier analysis. Three periods are used for evaluation if the time
stage G F D S S : t V N G > has been set to a time period equal to or greater than 60 ms.
This will result in the suppression of typical ripple-control frequencies in addition to all
integer-frequency harmonics. If the time stage was set to a time period less than 60 ms
only one period will be used for filtering.
The measurement is enabled when the time period set at G F D S S : t V N G > and
which was triggered by VNG> has elapsed. Dependent on the operating mode selected
(e.g. 'cos phi circuit' or 'sin phi circuit') the sign of the active power
(G F D S S : O p . m o d e G F p o w . / a d m 'cos phi circuit') or of the reactive power
(G F D S S : O p . m o d e G F p o w . / a d m 'sin phi circuit') is used to determine the
direction. Connection of the measuring circuits is taken into account by the setting at
G F D S S : M e a s u r i n g d i r e c t i o n . When the connection 'Standard' has been made
a ground fault on the line side will issue the decision 'LS' and a ground fault on the
busbar side will issue the decision 'BS'.
MAIN: General
starting
306 539 t 0
GFDSS: Grd.
fault pow./adm.
[ 009 037 ]
GFDSS: VNG>
triggered
304 151
GFDSS: f/fnom
C (P meas.) PSx
[ * ]
2 2
1: cos phi circuit 1: Standard
2: sin phi circuit 2: Opposite
C C
GFDSS: Direction
LS
Q 304 153
GFDSS: Direction
BS
304 154
GFDSS: P
304 155
GFDSS: Q
304 156
Parameter GFDSS: VNG> GFDSS: f/fnom GFDSS: tVNG> GFDSS: Op.m.GF GFDSS: Meas.
PSx (P meas.) PSx PSx pow./adm PSx direction PSx
set 1 016 062 016 091 016 061 016 063 016 070
set 2 000 233 001 044 000 230 000 236 001 002
set 3 000 234 001 045 000 231 000 237 001 003
set 4 000 235 001 046 000 232 000 238 001 004
12Z6240 A_EN
The directional decision is not enabled until the active component of the residual current
exceeds the set threshold and the phase displacement between residual current and
neutral-point displacement voltage is smaller than the set sector angle. The sector angle
makes it possible to extend the "dead zone" to take into account the expected phase-
angle errors of the measured variables. These settings make it possible to achieve the
characteristic shown in Figure 3-191.
The trip signal 'forward directional' issued by the ground fault direction determination
using steady-state values (GFDSS) is blocked by the auto-reclosing control function
(ARC) when this function is able to issue a trip command.
3-191 Characteristic of the ground fault direction determination using steady-state values, operating mode 'cos phi circuit'
The trip signal 'forward directional' issued by the ground fault direction determination
using steady-state values (GFDSS) is blocked by the auto-reclosing control function
(ARC) when this function is able to issue a trip command.
3-192 Characteristic of the ground fault direction determination using steady-state values, operating mode 'sin phi circuit'
GFDSS: GF
(pow.) ready
[ 038 026 ]
GFDSS: Op.m.GF
pow./adm PSx GFDSS: IN,act>/
[ * ] C reac> LS PSx
1, 3, 4 [ * ]
1: cos phi circuit
2, 3, 4
2: sin phi circuit
GFDSS: P
304 155
IN,act 1, 3
GFDSS: VNG GFDSS: IN,act>/
C reac> BS PSx
filtered [ * ]
304 152
GFDSS: Q
304 156
IN,react 2, 4
GFDSS: Curr.
4 IN,reac p.u.
[ 004 046 ]
3
GFDSS: Current
1 ... 2 IN,act p.u.
[ 004 045 ]
GFDSS: Direction
LS
304 153
GFDSS: Direction
BS
304 154
ARC: Blocking
trip
[ 042 000 ]
GFDSS: Starting
forward/LS
[ 009 040 ]
GFDSS: Trip
signal forw./LS
[ 009 031 ]
GFDSS: Sector
C angle LS PSx GFDSS: Direct.
[ * ] forward/LS
[ 009 035 ]
C GFDSS: Sector
angle BS PSx
[ * ] GFDSS: Direct.
backward/BS
[ 009 036 ]
< Sector angle BS
GFDSS: GF (curr.)
not ready
[ 038 029 ]
GFDSS: Starting
backw. /BS
[ 009 041 ]
Parameter GFDSS: Op.m.GF GFDSS: Sector GFDSS: Sector GFDSS: IN,act>/ GFDSS: IN,act>/
pow./adm PSx angle LS PSx angle BS PSx reac> LS PSx reac> BS PSx
set 1 016 063 016 065 016 068 016 064 016 067
set 2 000 236 000 242 000 248 000 239 000 251
set 3 000 237 000 243 000 249 000 240 000 252
set 4 000 238 000 244 000 250 000 241 000 253
3-193 Output of the direction decisions with the operating mode 'steady-state power'
The frequency provided by the setting f/fnom is filtered from the residual current value by
using a Fourier analysis. Three periods are used for evaluation. If the residual current
value exceeds the set threshold a ground fault signal is issued after the settable operate
delay time period has elapsed.
GFDSS:
Admittance ready
[ 038 167 ]
GFDSS: GF (pow.)
ready
[ 038 026 ]
t 0 0 t
IN
GFDSS: IN>
triggered
304 158
GFDSS: IN
filtered
304 159
GFDSS: Curr. IN
filt. p.u.
[ 004 047 ]
1
0: don't execute
MAIN: General 1: execute
Reset USER
[ 003 002 ]
1: execute
MAIN: General
Reset EXT
[ 005 255 ]
GFDSS: Reset
Counters EXT
[ 005 245 ]
12Z61BRB_EN
To determine a ground fault direction the steady-state admittance evaluation requires the
neutral-point displacement voltage and the residual current values. The frequency
provided by the setting f/fnom is filtered from these values by using a Fourier analysis.
The measurement is enabled when the time period set at G F D S S : t V N G > and
which was triggered by VNG> has elapsed. Dependent on the operating mode selected
(e.g. 'cos phi circuit' or 'sin phi circuit') the sign of the active power
(G F D S S : O p . m o d e G F p o w . / a d m 'cos phi circuit') or of the reactive power
(G F D S S : O p . m o d e G F p o w . / a d m 'sin phi circuit') is used to determine the
direction. Connection of the measuring circuits is taken into account by the setting at
G F D S S : M e a s u r i n g d i r e c t i o n . When the connection 'Standard' has been made
a ground fault on the line side will issue the decision 'LS' and a ground fault on the
busbar side will issue the decision 'BS'. Phase-angle errors of the system transformers
can be compensated with the setting at G F D S S : C o r r e c t i o n a n g l e .
GFDSS: Admittance
ready
[ 038 167 ] t 80 ms
GFDSS: Grd.
fault pow./adm.
[ 009 037 ]
GFDSS: VNG>
triggered
304 151
GFDSS: f/fnom
C (P meas.) PSx
[ * ]
2 2
1: cos phi circuit 1: Standard
2: sin phi circuit 2: Opposite
GFDSS: Correction
C angle PSx
[ * ]
C C
GFDSS: Direction
LS
Q 304 153
GFDSS: Direction
BS
304 154
GFDSS: P
304 155
GFDSS: Q
304 156
Parameter GFDSS: VNG> GFDSS: f/fnom GFDSS: tVNG> GFDSS: Op.m.GF GFDSS: Correction GFDSS: Meas.
PSx (P meas.) PSx PSx pow./adm PSx angle PSx direction PSx
set 1 016 062 016 091 016 061 016 063 016 110 016 070
set 2 000 233 001 044 000 230 000 236 001 026 001 002
set 3 000 234 001 045 000 231 000 237 001 027 001 003
set 4 000 235 001 046 000 232 000 238 001 028 001 004
12Z6245 B_EN
The trip signal in forward direction issued by the ground fault direction determination
using steady-state values (GFDSS) is blocked by the auto-reclosing control function
(ARC) when this function is able to issue a trip command.
3-197 Characteristic of the ground fault direction determination using steady-state admittance, operating mode 'cos phi circuit'
The trip signal in forward direction issued by the ground fault direction determination
using steady-state values (GFDSS) is blocked by the auto-reclosing control function
(ARC) when this function is able to issue a trip command.
3-198 Characteristic of the ground fault direction determination using steady-state admittance, operating mode 'sin phi circuit'
GFDSS: Admittance
ready
[ 038 167 ]
C GFDSS: G(N)> /
B(N)> LS PSx
GFDSS: Direction [ * ]
LS
304 153
GFDSS: Op.m.GF
pow./adm PSx
[ * ]
1, 3, 4, 5 GFDSS: G(N)> /
1: cos phi circuit C B(N)> BS PSx
[ * ]
2, 3, 4, 5
2: sin phi circuit
GFDSS: Starting
GFDSS: P backw. /BS
304 155 [ 009 041 ]
G(N) 1, 3
GFDSS: VNG
filtered
304 152
GFDSS: Q
304 156
B(N) 2, 4
Y(N) 5
GFDSS: Admitt.
Y(N) p.u.
[ 004 191 ]
5 GFDSS: Conduct.
G(N) p.u.
4 [ 004 192 ]
GFDSS: Suscept.
3 B(N) p.u.
[ 004 193 ]
1 ... 2
ARC: Blocking GFDSS: Trip
trip signal forw./LS
[ 042 000 ] [ 009 031 ]
t 0 0 t GFDSS: Direct.
forward/LS
[ 009 035 ]
t 0 0 t GFDSS: Direct.
backward/BS
[ 009 036 ]
GFDSS: GF (curr.)
not ready
[ 038 029 ]
3-199 Output of the direction decisions with the operating mode 'steady-state admittance'
Non-directional ground
fault determination
The admittance value from the ground return is used for evaluation. If the admittance
value exceeds the set threshold a ground fault signal is issued after the settable operate
delay time period has elapsed.
The trip signal from the non-directional ground fault determination is blocked by the auto-
reclosing control function (ARC) when this function is able to issue a trip command.
GFDSS: Oper.delay
Y(N)> elapsed
304 175
t 0 0 t GFDSS: Trip
IN Y(N)>
[ 009 075 ]
GFDSS: GF
(curr.) ready
[ 038 028 ]
GFDSS: GF (pow.)
ready
[ 038 026 ] GFDSS: Trip
signal Y(N)>
ARC: Blocking [ 009 072 ]
trip
[ 042 000 ] GFDSS: Starting
Y(N)>
[ 009 074 ]
The number of ground faults and directional decisions are counted. The counters may
be reset individually or together with other counters (see section 'Resetting Actions').
GFDSS: No. GF
GFDSS: Oper.delay + admitt. Y(N)
Y(N)> elapsed [ 009 060 ]
304 175
R
GFDSS: Grd. fault GFDSS: No. GF
pow./adm. + power/admitt.
[ 009 037 ] [ 009 002 ]
R
GFDSS: Direct. GFDSS: No. GF
forward/LS + forward/LS
[ 009 035 ] [ 009 000 ]
R
GFDSS: Direct. GFDSS: No. GF
backward/BS + backward/BS
[ 009 036 ] [ 009 001 ]
R
GFDSS: Reset
counters USER
[ 003 004 ]
1 ≥1
MAIN: General 0: don’t execute
reset USER 1: execute
[ 003 002 ]
1: execute
MAIN: General
reset EXT
[ 005 255 ]
GFDSS: Reset
counters EXT
[ 005 245 ]
12Z6191 B_EN
By applying the transient ground fault measuring procedure the ground fault direction is
determined by evaluating the neutral-point displacement voltage and the residual
current.
Enable/disable the
transient ground fault
detection function.
The transient ground fault detection function (TGFD) can be disabled or enabled via
setting parameters. Moreover, enabling can be carried out separately for each
parameter subset.
MAIN: Protection
active
306 001
TGFD: Enable
PSx
[ * ]
0
1
0: No
1: Yes
TGFD: General
enable USER
[ 016 040 ]
0 TGFD: Enabled
[ 037 100 ]
1
0: No
1: Yes
MAIN: Nominal
frequ. fnom
[ 010 030 ]
50: 50 Hz SFMON: Fcts.not
perm.f.60Hz
60: 60 Hz [ 093 098 ]
TGFD: Ready
[ 037 080 ]
TGFD: Blocking
EXT[ 004 034 ]
TGFD: Direct.
determined
[ 004 030 ]
SFMON: TGFD mon.
triggered
[ 093 094 ]
TGFD: Not ready
[ 037 081 ]
SFMON: Module N
RAM faulty
[ 093 091 ]
SFMON: Time-out
module N
[ 093 092 ]
SFMON: Invalid SW
vers. N
[ 093 093 ]
SFMON: DAC faulty
module N Parameter TGFD: Enable
[ 093 095 ] PSx
SFMON: +15V set 1 001 054
faulty mod. N
[ 093 096 ] set 2 001 055
SFMON: -15V set 3 001 056
faulty mod. N set 4 001 057
[ 093 097 ]
12Z6282 A_EN
3-202 Enabling, disabling and readiness of the transient ground fault detection function
TGFD: Evaluation
VNG PSx
[ * ]
VN-G 2
1
VA-G
VB-G 1 ... 2 TGFD: VN-G
VC-G 304 200
1: Sum (VA-B-C-G)
2: Measured
The higher frequency content is filtered from the measured values for residual current
and neutral-point displacement voltage. Settable triggers monitor the amplitudes of the
residual current and neutral-point displacement voltage harmonics as well as the neutral-
point displacement voltage fundamental. To determine the ground fault direction the
P139 will evaluate trigger decisions by the harmonics monitoring function, separately for
the positive and negative half-wave.
Furthermore the starting of a current trigger will start a timer stage that, after it has
elapsed, will enable the TGFD function to detect further transient ground faults.
The time period after which a new transient ground fault may be detected is given by the
setting of the operate delay +40 ms.
TGFD: Hardware
fault
304 207
IN TGFD: IN,p>
triggered
304 201
TGFD: VNG>
PSx TGFD: Operate
[ * ] delay PSx
[ * ]
TGFD: Ground
fault
TGFD: VN-G [ 004 033 ]
304 200
C TGFD: VNG>
(f0) triggered
304 202
TGFD: VNG>
triggered
304 203
S1 1
R1
S1 1
R1
S1 1
R1
TGFD: Measurem.
direc. PSx
[ * ]
TGFD: Direction
1 LS
304 204
1 TGFD: Direction
2 BS
304 205
2
1: Standard
2: Opposite
Directional decisions are issued for the duration of the set buffer time. If buffer time is
set to 0 s directional decisions are issued for as long as the neutral-point displacement
voltage fundamental exceeds the trigger threshold set at T G F D : V N G > .
TGFD: Hardware
fault
304 207
TGFD: Buffer
time PSx
[ * ]
TGFD: Forward /
TGFD: Direction LS
1 [ 004 031 ]
LS R
304 204
TGFD: Backward /
TGFD: Direction 1 BS
BS [ 004 032 ]
304 205 R
TGFD: VNG>
(f0) triggered
304 202
S1 1
R1 Parameter TGFD: Buffer
time PSx
S1 1 set 1 016 043
set 2 001 070
R1 set 3 001 071
set 4 001 072
12Z62EVA_EN
Resetting a directional
decision
While the buffer time is elapsing the directional decisions can be reset from the
integrated local control panel, a setting parameter or through an appropriately configured
binary signal input. Should the buffer time be set to ∞ ("infinity") the directional decision
must be reset so that a new transient ground fault can again be detected.
TGFD: Reset
signals USER
[ 003 009 ]
0
1 ≥1 100 ms TGFD: Signals
reset
0: don't execute [ 004 141 ]
1: execute
TGFD: Reset
signals EXT
[ 004 140 ]
TGFD: VNG>(f0)
triggered &
304 202
TGFD: Ready
[ 037 080 ]
MT_RC: Reset
record USER
[ 003 008 ]
1: execute
MT_RC: Reset
record EXT
[ 005 240 ]
12Z61EXC_EN
TGFD: Ground
fault + TGFD: No. GF
[ 004 033 ] [ 004 015 ]
R
0
1 ≥1
MAIN: General 0: don't execute
reset USER 1: execute
[ 003 002 ]
1: execute
MAIN: General
reset EXT
[ 005 255 ]
TGFD: Reset
counters EXT
[ 005 246 ]
12Z61EYA_EN
The P139 features a motor protection function (MP function). This motor protection
function is specifically designed to protect directly switched high-voltage asynchronous
motors with thermally critical rotors. Protection functions specially adapted for this
application are available:
The definite-time overcurrent protection stages required for global motor protection
operation as well as the necessary unbalance protection are described in sections
‘DTOC Protection’ and ‘Unbalance Protection (I2>)’, respectively.
Starting conditions
The overcurrent stage Iref,P> is used as a starting stage for overload protection. For this
the maximum value of the three phase currents is evaluated. The settable reference
current Iref is used as the reference quantity for the operate value and the tripping time.
When the threshold kP·Iref is exceeded then the current stage operates.
The output signal from the current stage Iref,P> is used as the starting signal.
Machine stopped:
If the measured maximum RMS phase current value has dropped below the threshold
of 0.1·Iref the function will decide on 'machine stopped' (signaled by
M P : M a c h i n e s t o p p e d ). No-load currents for asynchronous motors lie
significantly above the current threshold value of 0.1 Iref.
Machine running:
If the measured maximum RMS phase current value exceeds the threshold of 0.1 Iref
the function will decide on 'machine running' (signaled by
M P : M a c h i n e r u n n i n g ).
Overload range:
For a machine the overload range starts with current values exceeding the maximum
permissible continuous thermal current of the machine. The overload memory will be
incremented if the measured maximum RMS phase current value exceeds the
threshold value of Iref,P>.
Startup:
The onset of startup in a directly switched asynchronous motor is detected when the
measured maximum RMS phase current value exceeds the threshold value set at
M P : I S t U p > P S x for a minimum time duration period set at M P : t I S t U p > .
The end of a startup process is detected when, after the onset of startup has been
identified, the measured maximum RMS phase current value falls below the threshold
value of 0.6·IStUp> .
Overload memory
The thermal overload protection function featured by the P139 is specifically suited for
protection of high-voltage asynchronous motors with thermally critical rotors, a very
common motor type. For this there is a specific overload memory available that presents
a replica of the protected object’s relative over-temperature based on the coolant
temperature and with a values range from 0 to 100 %. The following values stored in the
overload memory have particular significance within the range of this model:
0%:
The value 0% represents the cold state of a protected object, e.g. it has cooled down
to ambient temperature.
20%:
The value 20% represents the minimum value stored by the overload memory when
the protected object is at operating temperature or after initial startup. A running
machine is always considered as being at operating temperature.
40%:
The value 40% temporarily represents the minimum value stored by the overload
memory after two consecutive startups of the machine.
60%:
The value 60% temporarily represents the minimum value stored by the overload
memory after three consecutive startups of the machine.
100%:
The instant when the overload memory reaches the value of 100% (trip threshold) an
overload protection trip will be issued. The hysteresis for a defined release of the trip
signal is 1%.
The overload memory mapping process that results in a replica of the actual thermal
conditions existing in the protected object includes the following operations:
Mapping of heating:
Basically the overload memory is continuously incremented when the maximum
RMS phase current value measured will have exceeded the threshold value of kP Iref
(overload range). The rate of this increase of the storing value depends on the
magnitude of the maximum RMS phase current value and, to a certain extent, on the
selected tripping characteristic (M P : C h a r a c t e r i s t i c P P S x ).
Mapping of cooling:
When the measured maximum RMS phase current value has fallen below the current
threshold of IkIref,P> and when the mapping of heat transfer, if applicable, has been
completed, then cooling of the protected object is simulated by a continuous
decreasing of the value stored in the overload memory. If the machine is running,
decreasing of the stored value will be governed by the cooling time constant
M P : T a u m a c h . r u n n i n g P S x and will continue until the minimum loading
state of 20 % is reached. If the machine is stopped, decreasing of the stored value
will be governed by the constant M P : T a u m a c h . s t o p p e d P S x and will
continue until the minimum loading state of 0 % is reached. Decreasing of the stored
value is an exponential function of time. The cooling time duration from an initial
value m0 to an interim value of m(t) can be determined as follows:
m − 0.2
Machine running: t = τ rotating machine ⋅ In 0
m(t ) − 0.2
m0
Machine stopped: t = τ machine stopped ⋅ In
m(t )
Startup frequency
monitoring
The P139 features a startup counter in 'count down' circuit configuration for startup
frequency monitoring. Depending on the setting of M P : P e r m . N o . s t . - u p s P S x ,
the permissible number of consecutive startups is either 'three from cold or two from
warm' or 'two from cold or one from warm'. The counter reading at any given time
indicates the number of consecutive startups that are still permitted. The startup counter
is controlled as follows (see Figure 3-211):
The permissible number of consecutive startups is limited to 'two from cold or one
from warm' (M P : P e r m . N o . s t . - u p s P S x ) ) .
For the permissible startup time tStUp (M P : S t . - u p t i m e t S t U p P S x ), a higher
value is set than for the maximum permissible blocking time tE from operating
temperature (M P : B l o c k i n g t i m e t E P S x ). These two setting values are only
relevant for this particular application; if both settings are identical, they have no
effect on the protective function and the heavy starting logic is not active.
When this logic function has been activated, then the two timer stages tE and tStUp are
triggered at the time when the onset of a startup is detected, corrected by the
discrimination time tStUp >. Once the set time tE has elapsed, the logic function checks to
see whether the machine is actually running. The presence of an external signal - from
an overspeed monitor, for example - serves as the criterion for a running machine.
When a running machine is detected once the set time tE has elapsed, then the stored
value in the overload memory is automatically frozen and tracking is only restarted after
the set startup time tStUp has elapsed. When a locked rotor state is detected after the set
time tE has elapsed, the overload memory is automatically set to a value of 100%, which
leads to an immediate trip decision.
Tripping time
characteristics
The P139 user can choose between the following two tripping time characteristics:
Logarithmic: t = (1 − m 0 ) ⋅ t 6 I ref ⋅ 36 ⋅ In
(I I ref )2
(I I ref )2 − 1
where m0 in each case signifies the pre-charging of the overload memory at time t = 0.
With reference to the basic physical model (two-body model), the logarithmic
characteristic in the overload range also takes into account heat transfer to the coolant,
but this heat transfer becomes less significant as the overcurrent increases. At I = 6·Iref,
for example, the tripping time increase is only about 1.4% and is thus below the specified
accuracy of the protection device. For a low overcurrent range, selection of the
logarithmic characteristic provides significantly higher tripping times than selection of the
reciprocally squared characteristic (see Figure 3-212), since the latter characteristic
neglects any heat transfer to the cooling medium in the overload range. The possibility
of choosing between two different tripping time characteristics takes into account the fact
that the user or the application may require a more restrictive or a less restrictive type of
protection. For currents in excess of 10 Iref, the tripping times are limited in the direction
of lower values.
The equation for determining the setting value t6Iref can be derived from the above
equations for tripping time t. For this the startup current Istartup and the maximum
permissible blocking time from cold tblock,cold for the asynchronous motor must be known.
Setting the overload protection function on the basis of the 'cold' tripping time where
m0 = 0 % ('cold curve') is permitted since the conditions for a machine at operating
temperature are automatically taken into account. The conditional equations for the
setting value t6Iref are therefore the following:
10000
A
1000
B
C
100
D
E
t in s 10
F
0,1
1 2 3 4 5 6 7 8 9 10 11
I / Iref
A = logarithmic characteristic D = reciprocally squared
(at t6Iref=100s) characteristic (at t6Iref=10s)
3-213 Tripping characteristic of motor protection (at I/Iref = 2.5 we have m=0.2, at I/Iref > 2.5 we have m=0)
Plausibility conditions
A number of plausibility conditions need to be observed in order to ensure that the
protected object is given optimum protection and that unintended tripping is prevented.
When the permissible number of consecutive startups is set for the sequence 'three
from cold or two from warm' and if this set permissible number of consecutive
startups is also intended to be used up during operation, then the heating during
startup in the overload memory (O L _ D A : H e a t . d u r . s t a r t - u p , M P ) must not
exceed 60%. When the calculation is based on a constant startup current
(O L _ D A : S t a r t - u p c u r r e n t ) over the entire startup period, then this will result
in the plausibility condition tstartup = 0.6·tblock,cold. However, since the startup current
decreases during the course of the startup time
(O L _ D A : T i m e t a k e n f . s t a r t u p ), thereby causing the rate of value storing
into the memory to decrease as well, it can therefore be assumed that there is a
corresponding extra margin available.
The setting value for the overload protection function is determined on the basis of
the stated maximum permissible blocking time from the cold state tblock,cold. However,
when a machine at operating temperature is connected, a protective trip during the tE
period must be guaranteed. Therefore, it is always necessary to check and ensure
that the plausibility condition tblock,cold = 1.25·tE is met.
Initialization or plausibility
check of the thermal
replica
Under the following conditions, the P139 will not be able to track the thermal replica of
the protected object, and re-initialization of the thermal replica will be triggered:
1000
100
t in s 10
0.1
1 2 3 4 5 6 7 8 9 10
I / Iref
MP protection: set reciprocally squared characteristic, t6Iref = 1 s
THERM protection: set time constant 1 = 300 s, trip limit value = 100 %
S8Z50F3A
3-214 Tripping characteristic of motor protection with operating mode 'With THERM' ('cold’ characteristic)
MP: Therm.repl.
buffer MP
[ 004 018 ]
MP: Therm. repl.
MP p.u.
[ 005 071 ]
MP: Trip signal
[ 040 046 ]
MP: St-ups still
permitt
[ 004 012 ]
MP: St-ups st.
perm.p.u.
[ 005 086 ]
MP: Reclosure
blocked
[ 040 049 ]
MP: Trip by
failed st-up
[ 041 081 ]
12Z6232 A_EN
Startup counter
The motor startups are counted. The counter can be reset either individually or with
others as a group.
The low load protection function makes it possible to monitor the load torque of a motor
drive for a minimum level. If the operating state recognition function detects a running
machine and the measured maximum RMS phase current falls below the set operate
value for a set time, then an appropriate signal is issued. The signal needs to be
configured to a separate output relay, as it cannot be linked directly to either the general
starting signal or the trip command.
Motors that are operated in hazardous areas must not reach a temperature level in the
case of overload or blocking that would be critical for the existing air-gas mixture.
The P139 is suitable for this type of application, which requires increased-safety
protection (type 'Ex e'.), but the device must be installed outside the hazardous area.
Additionally the number of hours run may be defaulted to any desired initial value
ranging from 0 to 65000 hours. This value is defined at
M P : I n i t . v a l . H o u r s _ R u n . The default is initialized by setting
M P : I n i t i a l i z e H o u r s _ R u n to 'Execute'.
Using this function, thermal overload protection can be implemented. The Thermal
Overload Protection function can be operated together with the Motor Protection
function.
Disabling or enabling
thermal overload protection
Thermal overload protection may be disabled or enabled by setting parameters.
Moreover, enabling can be carried out separately for each parameter set.
THERM: Enabled
USER
[ 022 050 ]
0
THERM: Enabled
1 & [ 040 068 ]
0: No
1: Yes
THERM: Enable
PSx
[ * ]
1
0: No
1: Yes PSS: PS x Parameter THERM: Enable
x Enabled PSx
PSS: PS x Enabled 1 036 090 Set 1 072 175
[ * ] 2 036 091 Set 2 073 175
3 036 092 Set 3 074 175
4 036 093 Set 4 075 175
19Z6112 B_EN
Readiness of thermal
overload protection
Thermal overload protection will issue T H E R M : N o t r e a d y if one of the following
conditions applies:
THERM: Therm.
repl.block EXT
[ 041 074 ]
THERM: Setting
error,block.
[ 039 110 ]
19Z6113 B_EN
3-220 Signal T H E R M : n o t r e a d y
Operating modes
Two operating modes can be selected for thermal overload protection.
Relative replica
Absolute replica
Either operating mode can be enabled or disabled individually. Only one of the
operating modes may be enabled for thermal overload protection. However, if both
operating modes are enabled at the same time, the thermal overload protection is
blocked and an error message is generated by the :
THERM: Setting error,block.
M E A S I : T 1 o p e n c i r c . to
MEASI: PT100 T9 open circ.
The thermal model uses these signals as a criterion to determine a fault in the coolant
temperature measurement. A fault at both measured value inputs selected will lead to
the issuance of the signal T H E R M : C T A e r r o r .
All relevant parameters for coolant temperature (ambient) acquisition are hidden if none
of the two analog modules Y available have been fitted. The tripping time is calculated
by including the setting for T H E R M : D e f a u l t C T A P S x .
Thermal overload
protection operation
without coolant
temperature (ambient)
acquisition
In order to guarantee thermal overload protection, without considering an offset due to a
variable coolant temperature, it is recommended to set the parameter
T H E R M : D e f a u l t C T A P S x to the max coolant temperature permitted.
THERM: Select
meas.inputPSx
[ * ]
0
1
2
n
0: None
1: PT100
2: 20mA input
n = 3 ... 11: Tx
&
MEASI: Open circ. &
PT 100
[ 040 190 ]
MEASI: Overload &
20mA input >1
[ 040 191 ] &
MEASI: Open circ.
20mA input
[ 040 192 ]
MEASI: Open circ.
Tx
[ * ]
THERM: Sel.
backup th. PSx
[ * ]
THERM: With CTA
305 201
0
&
1
2
n
0: None
1: PT100
2: 20mA input
n = 3 ... 11: Ty
THERM: CTA error
& [ 039 111 ]
& SFMON: CTA error
[ 098 034 ]
&
THERM: Funct.
f.CTA fail.PSx
[ * ]
1
2
& THERM: Block.
3 by CTA error
305 200
MEASI: Tx Ty
Open circ.
T1 040 193 040 193
T2 040 194 040 194
T3 040 195 040 195
T4 040 208 040 208
T5 040 209 040 209
T6 040 218 040 218 Parameter THERM: Select THERM: Sel. THERM: Funct.
meas.inputPSx backup th. PSx f.CTA fail.PSx
T7 040 219 040 219 Set 1 072 177 072 080 076 177
T8 040 252 040 252 Set 2 073 177 073 080 077 177
Set 3 074 177 074 200 078 177
T9 040 253 040 253 Set 4 075 177 075 200 079 177
19Z6110 B_EN
Relative replica
The rated operating current of the protected object and its overload tolerance for
maximum coolant (ambient) temperature are the basis of the relative thermal replica.
In the "Relative replica" operating mode, the following settings have to be made for
thermal overload protection:
Absolute replica
The thermal limit current of the protected object is the reference current of the absolute
thermal replica. For this limit current, an overtemperature results at the maximum
coolant temperature.
In the "Absolute replica" operating mode, the following parameters have to be set for
thermal overload protection:
Note: The maximum permissible coolant temperature Θa,max is derived from the
difference between the parameters T H E R M : M a x . p e r m . o b j . t m p . P S x
and T H E R M : O / T f . I r e f p e r s . P S x
Tripping characteristics
The maximum RMS phase current I is used to track a first-order thermal replica as
specified in IEC 255-8. Other than the operating mode dependent settings the following
parameters will govern the tripping time:
2
⎛ I ⎞
⎜⎜ ⎟⎟ − ∆ϑ0
t = τ ⋅ In ⎝ I ref ⎠
2
⎛ I ⎞ ⎛ Θ − Θ a , max ⎞
⎜⎜ ⎟⎟ − ∆ϑ trip ⋅ ⎜1 − a ⎟
⎜ ⎟
⎝ I ref ⎠ ⎝ Θ max − Θ a ,max ⎠
The tripping threshold ∆ϑtrip is set to a fixed value of 100 % ( = 1 ) if the operating mode
is "Absolute replica".
θtrip / %
10000
200
1000
110
τ/min
50
100
200
110
10 1000
50
t/min 200
1
110
50 30
0.1
0.01 1
0 1 2 3 4 5 6 7 8 9 10 11
0.00
I/Iref
D5Z50BE
3-222 Tripping characteristics of thermal overload protection (tripping characteristics apply to ∆ϑ0 = 0 % and identical settings for the maximum
permissible coolant temperature and coolant temperature)
Warning
Depending on the selected operating mode, a warning signal can be set at one of the
following parameters:
Additionally, a pre-trip time limit can be set; when the time left until tripping falls below
this pre-trip limit, a warning will be issued.
Trip
The trip threshold is set according to the selected operating mode with the following
parameters:
If a trip command is issued, the trip signal is maintained until the status of the thermal
replica has decreased by the value T H E R M : T r i p H y s t e r e s i s P S x , at least for
a fixed time of 5s.
Cooling
If the current falls below the default threshold of 0.1 Iref, the thermal replica is applied with
the set time constant T H E R M : T i m . c o n s t . 2 , < I b l P S x . This element in the
thermal model takes account of the cooling characteristics of stopped motors.
Note: These two time constants should be set to the same value for transformers
and power lines.
The motor protection will effect the thermal overload protection and not vice versa if both
protection functions are applied simultaneously.
IA COMP THERM: I
IB 305 202
IC
IP,max AR_MV
MAIN: Protection
active & C
306 001
THERM: Enabled
[ 040 068 ]
THERM: Starting
k*Iref>
THERM: Therm.repl. [ 041 108 ]
block EXT
[ 041 074 ]
THERM: Block. by &
CTA error
305 200 C
MP: Block.
replica THERM THERM: Tim.
304 700 C const.1,>Ibl
[ *
PSx
]
THERM: Iref THERM: Tim.
PSx <0.1 Iref C const.2,<Ibl PSx
[ * ] [ * ]
THERM: Start. THERM: O/T
fact.OL_RC PSx C f.Iref pers. PSx
[ * ] [ * ]
THERM: Warning
k*Iref C[temp. PSx
* ]
THERM: Max.perm.
THERM: Absolute C obj.tmp.PSx
[ * ]
replica THERM: Max.perm.
[ 022 065 ]
C cool.tmpPSx
[ * ] THERM: Within
0 THERM: Rel. O/T pre-trip time
C warning PSx [ 041 109 ]
1
[ * ]
SFMON: Setting
THERM: Rel. O/T error THERM
0: No C[trip PSx [ 098 035 ]
* ]
1: Yes THERM:Setting
THERM: Default error,block.
C CTA
[ *
PSx
] [ 039 110 ]
THERM: Relative THERM: Hysteresis THERM: Warning
replica trip PSx [ 039 025 ]
[ 022 064 ] [ * ]
THERM: Warning THERM: Trip
pre-trip PSx signal
0 [ 039 020 ]
[ * ]
1 THERM: Reclosure
blocked
0: No [ 039 024 ]
1: Yes THERM:Buffer
empty
[ 039 112 ]
THERM: Status
C THERM replica
[ 004 016 ]
R THERM: Object
I/Iref temperature
[ 004 137 ]
THERM: Coolant
temperature
[ 004 149 ]
THERM: With C THERM: Pre-trip
CTA time left
305 201
[ 004 139 ]
Coolant THERM: Temp. offset
temperature replica
THERM: Reset [ 004 109 ]
replica THERM: Coolant
[ 039 061 ] temp. p.u.
[ 004 178 ]
THERM: Object
temp. p.u.
[ 004 179 ]
THERM: Therm.
replica p.u.
[ 004 017 ]
Parameter THERM: Iref THERM: Start. THERM: Tim. THERM: Tim. THERM: O/T THERM: Warning THERM: Max.perm.
PSx fact.OL_RC PSx const.1,>Ibl PSx const.2,<Ibl PSx f.Iref pers. PSx temp. PSx obj.tmp.PSx
Set 1 072 179 072 180 072 187 072 188 072 167 072 153 072 182
Set 2 073 179 073 180 073 187 073 188 073 167 073 153 073 182
Set 3 074 179 074 180 074 187 074 188 074 167 074 153 074 182
Set 4 075 179 075 180 075 187 075 188 075 167 075 153 075 182
Parameter THERM: Max.perm. THERM: Rel. O/T THERM: Rel. O/T THERM: Default THERM: Hyst- THERM: Warning
cool.tmpPSx warning PSx trip PSx CTA PSx eresis trip PSx pre-trip PSx
Set 1 072 185 072 184 072 181 072 186 072 183 072 191
Set 2 073 185 073 184 073 181 073 186 073 183 073 191
Set 3 074 185 074 184 074 181 074 186 074 183 074 191
Set 4 075 185 075 184 075 181 075 186 075 183 075 191
19Z6111 B_EN
Reset
The thermal replica may be reset either via a setting parameter or via an appropriately
configured binary signal input. Resetting is possible even when thermal overload
protection is disabled. Thermal overload protection can be blocked via an appropriately
configured binary signal input.
THERM: Reset
replica USER
[ 022 061 ]
0
THERM: Reset
1 replica
[ 039 061 ]
0: don't
execute
1: execute
THERM: Enabled
[ 040 068 ]
THERM: Reset
replica EXT
[ 038 061 ]
Q9Z5020 B_EN
Enable/disable the
unbalance protection
function
The unbalance protection function can be disabled or enabled using setting parameters.
Moreover, enabling can be carried out separately for each parameter subset.
Functional description
The presence or absence of unbalance is assessed on the basis of the negative-
sequence system current. The negative-sequence current is monitored to determine
whether it exceeds the set thresholds. After the set operate delay periods have elapsed,
a signal is issued. The following stages are available for the negative-sequence current:
The unbalance protection signals can be configured to separate output relays. These
signals cannot be linked to the general starting signal but can be configured to the trip
command.
I2>: Blocking
tIneg> EXT
[ 041 076 ]
I2>: Blocking
tIneg>> EXT
[ 041 077 ]
I2>: Enabled
[ 040 073 ] &
MAIN: Protection
active
306 001
t 0 I2>: tIneg>
>0.1 Inom |Ineg|/Inom elapsed
[ 035 033 ]
I2>: Starting
Ineg>
IA [ 035 024 ]
IB
I2>: Ineg>> I2>: tIneg>>
IC PS1 PS1
[ * ] [ * ]
I2>: tIneg>>
MAIN: Rotary field elapsed
[ 010 049 ] [ 035 034 ]
I2>: Starting
Ineg>>
[ 035 025 ]
Ineg
19Z5083B_EN
The time-voltage protection function evaluates the fundamental wave of the phase
voltages and of the neutral-point displacement voltage as well as the positive-sequence
voltage and negative-sequence voltage obtained from the fundamental waves of the
three phase-to-ground voltages.
Disabling or enabling
V<> protection
V<> protection can be disabled or enabled via a parameter setting. Moreover, enabling
can be carried out separately for each parameter subset.
If the decisions of undervoltage monitoring are to be included in the trip commands, then
it is recommended that transient signals be used. Otherwise the trip command would
always be present when the system voltage was disconnected, and thus it would not be
possible to close the circuit breaker again.
Minimum current
monitoring
Furthermore there is an enabling threshold available with the V<> element which is
based on minimum current monitoring for undervoltage stage V<. The following two
settings may be used to activate the operating mode for minimum current monitoring and
to set the enabling threshold:
V gegen =
1
(
⋅ V A −G + a ⋅ V B−G + a 2 ⋅ V C −G )
Negative-sequence voltage: 3
a = e j120°
a 2 = e j240°
MAIN: Phase
sequence
[ 010 049 ]
D5Z50AYB_EN
If the decisions of undervoltage monitoring are to be included in the trip commands, then
it is recommended that transient signals be used. Otherwise the trip command would
always be present when the system voltage was disconnected, and thus it would not be
possible to close the circuit breaker again.
The P139 monitors the voltage to determine whether it exceeds or falls below set
frequencies. The frequency is determined from the difference in time between the zero
crossings of the voltage (voltage zeroes). The over-/underfrequency protection function
has four stages. The operation of over-/underfrequency protection will be explained
below using the first stage as an example.
Disabling or enabling
over-/underfrequency
protection
The frequency protection can be disabled or enabled using setting parameters.
Moreover, enabling can be carried out separately for each parameter subset.
Frequency monitoring
Frequency monitoring combined with differential frequency gradient monitoring (df/dt)
Frequency monitoring combined with mean frequency gradient monitoring (∆f/∆t)
Frequency monitoring
Depending on the setting, the P139 monitors the frequency to determine whether it
exceeds or falls below set thresholds. If an operate threshold in excess of the set
nominal frequency is set, the P139 checks to determine whether the frequency exceeds
the operate threshold. If an operate threshold below the set nominal frequency is set,
the P139 checks to determine whether the frequency falls below the operate threshold.
If it exceeds or falls below the set threshold, a set timer stage is started. The timer stage
can be blocked by way of an appropriately configured binary signal input.
Frequency monitoring
combined with differential
frequency gradient
monitoring (df/dt)
In this operating mode of the over-/ underfrequency protection function, the frequency is
also checked to determine whether the set frequency gradient is reached (in addition to
being monitored for exceeding or falling below the set threshold). Monitoring for
overfrequency is combined with monitoring for a frequency increase; monitoring for
underfrequency is combined with monitoring for a frequency decrease. If both operate
conditions are satisfied, a set timer stage is started. The timer stage can be blocked by
way of an appropriately configured binary signal input.
Frequency monitoring
combined with mean
frequency gradient
monitoring (∆f/∆t)
The frequency gradient can differ for system disturbances in individual substations and
may vary over time due to power swings. Therefore it makes sense to take the mean
value of the frequency gradient into account for load-shedding systems.
Monitoring the mean value of the frequency gradient is started with the starting of
frequency monitoring. If the frequency decreases by the set value ∆f within the set
time ∆t, then the ∆t/∆f monitoring function operates instantaneously and generates a trip
signal. If a frequency change does not lead to an operate decision of the monitoring
function, then the ∆t/∆f monitoring function will be blocked until the underfrequency
monitoring function drops out. The trip signal can be blocked by way of an appropriately
configured binary signal input.
fmin/fmax measurement
For the acquisition of the minimum frequency during an underfrequency condition and for
the acquisition of the maximum frequency during an overfrequency condition, the two
following measured event values are available:
Both measured event values are reset automatically at the onset of a new overfrequency
or underfrequency situation. A manual reset is also possible:
The power directional protection function determines the active and reactive power from
the fundamental currents and voltages. The sign of the active or the reactive power,
respectively, is evaluated for direction determination
Disabling or enabling
P<> protection
The power directional protection can be disabled or enabled via setting parameters.
Moreover, enabling can be carried out separately for each parameter subset.
Power determination
The P139 determines the active and reactive power from the three phase currents and
the phase-to-ground voltages. If the measuring-circuit monitoring function detects
malfunctioning in the voltage measuring circuit, power determination will be blocked.
Power monitoring
The P139 checks the determined power values to detect whether they exceed or fall
below set thresholds. The triggers are followed by timer stages that can be blocked via
appropriately configured binary signal inputs.
If the decisions of power monitoring are to be included in the trip commands when
values have fallen below set thresholds, then it is recommended that transient signals be
used. Otherwise the trip command would always be present when the system voltage
was disconnected, and thus it would not be possible to close the circuit breaker again.
When the active power exceeds the set thresholds, a starting results. The starting signal
is followed by the set operate and resetting delays.
P<>: Operate
delay P> PSx
P<>: Release
P<>: Blocking delay P> PSx
tP> EXT
035 082
P<>: Diseng.
ratio P> PSx
P<>: Starting
P>
035 086
P<>: Operate
delay P>>PSx
P<>: Release
delay P>>PSx
P<>: Blocking
tP>> EXT
035 083
P<>: Diseng.
ratio P>>PSx
P<>: Starting
P>>
035 089
19Z5271A_EN
3-244 The direction-dependent trip signal of the active power protection function when set thresholds are exceeded
When the reactive power exceeds the set thresholds, a starting results. The starting
signal is followed by the set operate and resetting delays.
P<>: Operate
delay Q> PSx
P<>: Release
P<>: Blocking delay Q> PSx
tQ> EXT
035 084
P<>: Diseng.
ratio Q> PSx
P<>: Starting
Q>
035 092
P<>: Operate
delay Q>>PSx
P<>: Release
delay Q>>PSx
P<>: Blocking
tQ>> EXT
035 085
P<>: Diseng.
ratio Q>>PSx
P<>: Starting
Q>>
035 095
3-246 The direction-dependent trip signal of the reactive power protection function when set thresholds are exceeded
When the active power falls below the set thresholds, a starting results. The starting
signal is followed by the set operate and resetting delays.
P<>: P<
PSx P<>: Operate delay
[ * ] P<PSx
[ * ]
P<>: Diseng. P<>: Release
ratio P< PSx delay P<PSx
[ * ] C [ * ]
Setting blocked
P<>: Starting P<
[ 035 054 ]
P<>: P<<
PSx P<>: Operate delay
[ * ]
P<<PSx
[ * ]
P<>: Diseng. P<>: Release
ratio P<< PSx delay P<<PSx
[ * ] C [ * ]
Setting blocked
P<>: Starting
P<<
[ 035 060 ]
&
P<>: tP<<
elapsed trans.
[ 035 062 ]
P<>: tP</tP<<
elaps.trans
[ 035 178 ]
P<>: P<< P<>: Diseng. P<>: Operate P<>: Release P<>: tTransient
Parameter PSx ratio P<< PSx delay P<<PSx delay P<<PSx pulse PSx
set 1 017 234 017 238 017 242 017 246 018 246
set 2 017 235 017 239 017 243 017 247 018 247
set 3 017 236 017 240 017 244 017 248 018 248
set 4 017 237 017 241 017 245 017 249 018 249
19Z5272 B_EN
3-247 Active power monitoring when values fall below set thresholds
P<>: Starting
P<
[ 035 054 ]
P<>: Direction
P< PSx
[ * ]
1
2
3
1: Forward directional
2: Backward directional
3: Non-directional
&
P<>: P-
402 634
&
P<>: Starting
P<<
[ 035 060 ]
P<>: Direction
P<< PSx
[ * ]
1
2
3
1: Forward directional
2: Backward directional
3: Non-directional
&
&
19Z5273 B_EN
3-248 The direction-dependent trip signal of the active power protection function when values fall below set thresholds
1
P<>: Starting
P<
035 054
P<>: Operate
delay P< PSx
*
P<>: Release
delay P< PSx
* 2
P<>: Signal
P< delayed
035 055
P<>: tP<
elapsed trans.
035 056 3
P<>: Fault
P<
035 057
P<>: Operate
1 delay P< PSx *
P<>: Release
2 delay P< PSx *
P<>: tTransient
3 pulse PSx *
19Z5278A_EN
3-249 Performance of the transient signal and the fault signal issued by the active power monitoring
When the reactive power falls below the set thresholds, a starting results. The starting
signal is followed by the set operate and resetting delays.
P<>: Q<
PSx P<>: Operate
[ * ] delay Q< PSx
[ * ]
P<>: Diseng. P<>: Release
ratio Q< PSx delay Q< PSx
[ * ] C [ * ]
Setting blocked
P<>: Starting Q<
[ 035 066 ]
P<>: Q<<
PSx P<>: Operate
[ * ] delay Q<< PSx
[ * ]
P<>: Diseng. P<>: Release
ratio Q<< PSx delay Q<< PSx
[ * ] C [ * ]
Setting blocked
P<>: Starting
Q<<
[ 035 010 ]
P<>: tQ<<
elapsed trans.
[ 035 016 ]
P<>: tQ</tQ<<
elaps.trans
[ 035 179 ]
P<>: Q<< P<>: Diseng. P<>: Operate P<>: Release P<>: tTransient
Parameter PSx ratio Q<< PSx delay Q<< PSx delay Q<< PSx pulse PSx
set 1 018 085 018 095 018 213 018 236 018 246
set 2 018 086 018 096 018 214 018 237 018 247
set 3 018 087 018 097 018 215 018 238 018 248
set 4 018 088 018 098 018 216 018 239 018 249
19Z5276 B_EN
3-250 Reactive power monitoring when values fall below set thresholds
P<>: Starting
Q<
[ 035 066 ]
P<>: Direction
Q< PSx
[ * ]
2
3
1: Forward directional
2: Backward directional
3: Non-directional
&
P<>: Q-
402 636
&
P<>: Starting
Q<<
[ 035 010 ]
P<>: Direction
Q<< PSx
[ * ]
1
2
3
1: Forward directional
2: Backward directional
3: Non-directional
&
&
&
19Z5277 B_EN
3-251 The direction-dependent trip signal of the reactive power protection function when values fall below set thresholds
1
P<>: Starting
Q<
035 066
P<>: Operate
delay Q< PSx
*
P<>: Release
delay Q< PSx
* 2
P<>: Signal
Q< delayed
035 067
P<>: tQ<
elapsed trans.
035 068 3
P<>: Fault
Q<
035 069
P<>: Operate
1 delay Q< PSx *
P<>: Release
2 delay Q< PSx *
P<>: tTransient
3 pulse PSx *
19Z5279A_EN
3-252 Performance of the transient signal and the fault signal issued by the reactive power monitoring
P<>: Direction P
& forw.
[ 035 181 ]
P<>: Starting P>
[ 035 086 ]
P<>: P-
402 634
19Z5274B_EN
P<>: Q+
402 635
P<>: Direction Q
forw.
P<>: Q-
402 636
& [ 035 193 ]
19Z 5275B_EN
The P139 features the CB failure protection function. After a trip command has been
issued the CBF function monitors that the circuit breaker has actually been triggered.
Enable/disable circuit
breaker failure protection
The activation of the function is enabled at C B F : G e n e r a l e n a b l e U S E R . If this
parameter has been activated the CBF function may be enabled or disabled by
parameters or through appropriately configured binary signal inputs. Parameters and
configured binary signal inputs have equal status. If only the function C B F : E n a b l e
E X T is assigned to a binary signal input, then circuit breaker protection will be enabled
by a positive edge of the input signal and disabled by a negative edge. If only the
function C B F : D i s a b l e E X T is assigned to a binary signal input, then a signal at
this input will have no effect.
CBF: General
enable USER
[ 022 080 ]
0
CBF: Enabled
1 & [ 040 055 ]
0: No
1: Yes
INP: Fct.
assignm. U xxx
[ xxx xxx ]
U x1
U x2
U x3
U xx
0
1
0: don't execute
1: execute
0
1
0: don't execute
1: execute
47Z1138 B_EN
Readiness of circuit
breaker protection
Circuit breaker failure protection will not be available under the following conditions:
&
CBF: Blocking EXT
[ 038 058 ]
≥1
CBF: t1 3p
[ 022 165 ]
Blocked &
CBF: t2
[ 022 166 ]
Blocked
CBF: Delay/
starting trig.
[ 022 155 ]
Blocked
CBF: Delay/fault
beh. CB
[ 022 171 ]
Blocked
CBF: Delay/CB
sync.superv
[ 022 172 ]
Blocked
19Z6130 B_EN
Detecting a CB tripping
A break in current flow is the preferred criterion to detect a successful CB tripping.
Protection functions that have tripping criteria not directly dependent on current flow may
additionally be provided with status signals from CB auxiliary contacts for evaluation.
As long as the current flow remains higher than the set threshold value of C B F : I < ,
then the appropriate phase-selective messages C B F : C u r r e n t f l o w A ,
C B F : C u r r e n t f l o w B , C B F : C u r r e n t f l o w C and the multiple signal
C B F : C u r r e n t f l o w P h x will be issued continuously.
CBF: I<
[ 022 160 ]
47Z1139 D_EN
If only one of the two possible CB status signals has been configured, then this
configured signal will always be considered plausible by the P139.
As an alternative the status signals from the external device may be used by the P139.
Assigning necessary for this is made with the parameters
M A I N : S i g . a s g . C B o p e n or M A I N : S i g . a s g . C B c l o s e d . Status signals
from external devices are processed similar to CB status signals
M A I N : C B o p e n 3 p E X T and M A I N : C B c l o s e d s i g . E X T .
INP: Fct.
assignm. U xxx
[ xxx yyy ]
U x01
U x02
U x03
U xxx
19Z6131C_EN
Startup criteria
The startup of the circuit breaker failure protection function will occur when the CB is
recognized as closed during a start criterion. The following criteria are evaluated as a
startup criterion:
Note:
The startup criterion drops off if the configured general trip signal or the external
starting criterion drops off. This occurs independently of the current flow and CB
state signal criteria.
These trip signals will be issued as long as the startup criteria are met. Should a loss of
gas pressure occur in the explosion chambers of installed type SF-6 circuit breakers
then all surrounding circuit breakers must be immediately tripped without waiting for a
reaction from the damaged switch. In case of an external CB fault the elapse of timer
stage t2 may be interrupted by a signal to the binary signal input appropriately
configured at C B F : C B f a u l t y E X T .
CBF: Fct.
assignm. CBAux.
[ 022 159 ]
Signal 1
Signal 2 m out of n
Signal 3
Selected signals
CBF: CB pos.
implausible
[ 038 210 ]
CBF: I<
[ 022 160 ] &
≥1
&
IA & & S 1 1
IB
R 1
IC
MAIN: CB open 3p
EXT ≥1
[ 031 028 ]
MAIN: CB closed
sig. EXT
[ 036 051 ]
>1
0
1 & ≥1
0: No
MAIN: Trip cmd. 1: Yes
blocked
[ 021 013 ] &
MAIN: Gen. trip &
signal 1
[ 036 005 ]
MAIN: Manual trip
signal
[ 034 017 ]
INP: Fct.
assignm. U xxx
[ xxx yyy ]
U x01
U x02
U x03
U xxx & ≥1
19Z6132D_EN
CBF: Trip
t 0 ≥1 signal t2
[ 038 219 ]
&
CBF: CB faulty
EXT
[ 038 234 ]
19Z6433 A_EN
Trip commands
While trip signals issued by the CB failure protection have no timer stages available the
user can set minimum time delay periods for trip commands.
By appropriate setting it can be selected that trip commands, issued by the CB failure
protection, will operate in latching mode. The respective trip command, set to latch
mode, will remain active until reset by operating parameters or through an appropriately
configured binary signal input.
CBF: Min.dur.
trip cmd.t1
[ 022 167 ]
MAIN: Trip cmd. CBF: Trip command
blocked t1
[ 021 013 ] & t 0 ≥1 [ 038 220 ]
CBF: Trip signal t1 ≥1
[ 038 215 ]
CBF: Latching
trip cmd.t1
[ 022 169 ]
0 & S 1 1
1 R 1
CBF: Min.dur.
0: No trip cmd.t2
1: Yes [ 022 168 ]
CBF: Trip command
& t 0 ≥1 t2
[ 038 224 ]
CBF: Trip signal t2
[ 038 219 ]
≥1
CBF: Latching
trip cmd.t2
[ 022 170 ]
0 & S 1 1
1 R 1
0: No
1: Yes
MAIN: Latch. trip c.
reset
[ 040 139 ]
19Z6134 B_EN
Starting trigger
The signal C B F : S t a r t i n g will be issued when the signal
C B F : S t a r t i n g t r i g . E X T is presented to an appropriately configured binary signal
input and a general starting is present. The signal C B F : T r i p s i g n a l will be issued
after timer stage C B F : D e l a y / s t a r t i n g t r i g . has elapsed.
CBF: Delay/
starting trig.
[ 022 155 ]
19Z6135 B_EN
Fault behind CB protection recognizes such faults through the current criterion if the
circuit breaker does not provide the information that it is closed after the time delay set at
C B F : D e l a y / f a u l t b e h . C B has elapsed.
CBF: CB pos.
implausible
[ 038 210 ] CBF: Delay/
fault beh. CB
CBF: I< [ 022 171 ]
[ 022 160 ]
t 0 CBF: Fault behind CB
& [ 038 225 ]
IA &
IB
IC
MAIN: CB open 3p
EXT
[ 031 028 ]
MAIN: CB closed
sig. EXT
[ 036 051 ]
19Z6136D_EN
CB synchronization
supervision
CB synchronization supervision recognizes states where not all circuit breaker contacts
are open or closed. This function uses both current flow monitoring and evaluation of
CB status signals to detect CB synchronization. In order to bridge CB operate times the
time delay C B F : D e l a y / C B s y n c h . s u p e r v can be used. When this time period
has elapsed the signal C B F : T r i p S i g C B s y n c h . s u p e r is issued. Poles that are
recognized as being open will still be signaled.
CBF: CB pos.
implausible
[ 038 210 ]
MAIN: CB open 3p
EXT ≥1
[ 031 028 ] CBF: Delay/CB
MAIN: CB closed sync.superv
sig. EXT [ 022 172 ]
[ 036 051 ] CBF: TripSig
CBF: I> & t 0 CBsync.super
[ 022 160 ] [ 038 226 ]
IA ≥1
IB
IC
<3
CBF: CBsync.superv
& A open
[ 038 227 ]
CBF: CBsync.superv
& B open
[ 038 228 ]
CBF: CBsync.superv
& C open
[ 038 229 ]
19Z6137 D_EN
The P139 features a circuit breaker monitoring function. This function supports state-
controlled maintenance of circuit breakers.
Enable/disable circuit
breaker monitoring
Circuit breaker monitoring may be disabled or enabled using setting parameters.
1 2 3 4 5 6 7
CBM: Enabled
USER
[ 022 010 ]
1 CBM: Enabled
[ 044 130 ]
0: No
1: Yes
48Z5404B_EN
Variants
The wear condition of a circuit breaker may be determined using a variety of methods:
CB wear characteristic
Manufacturers of circuit breakers usually provide wear characteristics displaying the
maximum number of permissible CB operations in relation to the disconnection current.
Figure 3-266 displays the wear characteristics for a circuit breaker with a nominal current
of 2000 A and a maximum cutoff current of 63 kA. The mean disconnection current is
48 kA.
100000
10000
Number of permissible CB operations
1000
100
10
0,1 1 10 100
Disconnection current in kA 19Z6123A_EN
The knee points in figure 3-266 are necessary to set the wear characteristic for the circuit
breaker:
The nominal current C B M : I n o m , C B for the circuit breaker and the permitted
number of CB operations at nominal current C B M : P e r m . C B o p . I n o m , C B
The medium disconnection current C B M : M e d . C u r r . I t r i p , C B for the circuit
breaker and the permitted number of CB operations at medium disconnection current
CBM: Perm. CB op. Imed,CB
The maximum cutoff current C B M : M a x . c u r r . I t r i p , C B for the circuit breaker
and the permitted number of CB operations at maximum cutoff current
CBM: Perm. CB op. Imax,CB
Not all types of circuit breakers provide a value for the medium disconnection current.
In such a case the parameters for this knee point are to be set to 'blocked'. A knee point
is not considered in the characteristic when at least one of the parameters for the knee
point is set to 'blocked'.
For proper performance of circuit breaker monitoring it should be observed that the knee
points must be applied in a logically correct sequence (continuously descending).
When setting currents and numbers of CB operations are not plausible according to the
characteristic the P139 will issue an error message and block circuit breaker monitoring.
With:
Operating modes
Setting the parameter C B M : O p e r a t i n g m o d e will select the condition under
which the function will be triggered:
Measured values and counters are re-determined with each triggering and compared
with set threshold values.
The cycle is started by a trigger criterion. Definition for the end of a cycle: The remaining
time of a power cycle duration has elapsed after the last detected current zero crossing.
The signal C B M : C u r r . F l o w e n d e d X (X = A, B or C) is then issued.
The maximum cycle time duration is defined with 220 milliseconds. The start of the cycle
time is corrected by the settable correction times. A fault on a CB pole is considered to
be apparent if further current zero crossings are detected after the maximum cycle time
has elapsed. Measured values from the respective CB tripping are canceled and the
signal C B M : t m a x > X (X = A, B or C) is issued.
Signal 1
Signal 2 m out of n
Signal n
>1 CBM: Internal
Selected signal trip cmd
310 025
MAIN: Gen. trip
command 1
[ 036 071 ]
19Z6124 C_EN
The external devices state signal "open" may be linked to the control function state signal
"open" by setting the parameter C B M : S i g . a s g . t r i p c m d . so that the function in
the P139 will be triggered by CB auxiliary contacts.
Pole-selective counter
values and measured
values
The P139 separately evaluates each phase current and generates an individual wear
presentation for each CB pole.
The following measured values are presented pole-selectively, and per-unit values refer
to CB nominal current:
The disconnection current is derived from the RMS current value detected before a last
zero crossing.
The integral of the current-time area is calculated between the trip time and current
disappearance. Current reset is recognized when there are no further current zero
crossings detected. An example for calculation of the current-time integral is displayed
in figure 3-269.
20,00
15,00
10,00
5,00
0,00
-5,00
-10,00
-15,00
19Z6126A_EN
3-269 Calculation of the current-time integral when CBM is triggered by a general trip command 1
Note: Only such measured values and counter values in the P139 may be set to
new values that do not have their default values set to 'blocked'.
The stored value will remain unchanged if the default value is set to "blocked".
Executing the set command results in initializing all default values in the P139
to 'blocked'.
MAIN: Protection
active & C
306 001
CBM: Enabled
[ 044 130 ] CBM: Operating
mode
[ 022 007 ]
0 &
1 &
2 & C
1: With trip cmd. only
2: With CB sig.EXT only C CBM: Inom,CB
[ 022 012 ]
3: CB sig. EXT or trip
MAIN: Inom C.T.
CBM: Blocked prim.
[ 044 199 ] [ 010 001 ]
CBM: Internal CBM: Perm. CB op.
trip cmd Inom,CB
310 025 [ 022 013 ]
MAIN: Internal CB
trip CBM: Med. curr.
310 030 Itrip,CB
fnom [ 022 014 ]
Ix CBM: Perm. CB op.
Imed,CB[ 022 015 ]
CBM: Itrip A
S [ * ]
CBM: Itrip**2 A
S [ * ]
CBM: I*t A
S [ * ]
CBM: No. of CB
oper. A
S [ * ]
Phase x / CBM: Set No. CB CBM: Set remain. CBM: Set Itrip CBM: Set CBM: Set I*t CBM: No. of CB CBM: Remain.
Current Ix oper. A CB op. A A Itrip**2 A A oper. A No. CB op. A
A / IA 022 131 022 134 022 137 022 140 022 143 008 011 008 014
B / IB 022 132 022 135 022 138 022 141 022 144 008 012 008 015
C / IC 022 133 022 136 022 139 022 142 022 145 008 013 008 016
Phase x / CBM: Itrip A CBM: I*t A CBM: Itrip,prim CBM: Itrip**2 CBM: Itrip A CBM: Itrip**2 CBM: I*t A
Current Ix A A A
A / IA 009 047 009 061 009 212 009 051 009 071 009 077 009 087
B / IB 009 048 009 062 009 213 009 052 009 073 009 078 009 088
C / IC 009 049 009 063 009 214 009 053 009 076 009 079 009 089
19Z6120 B_EN
CBM: Remain.
No. CB op. B
[ 008 015 ]
CBM: Remain.
No. CB op. C
[ 008 016 ]
19Z6121 B_EN
At the same time each switching operation will increment the P139 counter for the
number of CB operations The number of CB operations performed is displayed.
A threshold value can be set with the parameter C B M : N o . C B o p e r a t i o n s > .
An alarm is issued should the number of CB operations performed exceed this threshold.
CBM: No. CB
C operations >
[ 022 019 ]
19Z6122 B_EN
Monitoring disconnection
currents
In addition to the evaluation of the CB wear state and monitoring of the number of CB
operations performed, the P139 features the means to accumulate and display the
disconnection current values and the squares of these values. Threshold values can be
set with the parameters C B M : Σ I t r i p > , C B M : Σ I t r i p * * 2 > and C B M : Σ I * t .
An alarm is issued should the accumulated current values exceed any of these
thresholds.
Blocking circuit breaker
monitoring
When protection injection testing is carried out the circuit breaker monitoring function
should be blocked, so that such testing does not corrupt monitoring results. CBM
protection is blocked if one of the following conditions is met:
1 2 3 4 5 6 7
&
CBM: Blocking
EXT
[ 044 128 ]
CBM: Blocking
USER
[ 022 150 ]
0
1
0: No
1: Yes
48Z5346C_EN
Monitoring of the reference voltage has been added to the measuring-circuit monitoring
function.
The P139 monitors the phase currents and voltages for balance during healthy system
operation. If either unbalance or the lack of measuring voltage is detected, action is
taken to prevent the unit from malfunctioning.
Current monitoring
Current monitoring is only enabled if the following conditions are met simultaneously:
I P, max − I P, min
≥ I diff
I P,max
where IP,max is the highest of the three phase currents and IP,min is the lowest; Idiff> is the
set operate value M C M O N : I d i f f > . In order to suppress short-term transients, the
measuring stage Idiff> is followed by a set operate-delayed timer stage
MCMON: Operate delay
If connection is to two current transformers only (phase ANC connection only) evaluation
of current IB can be disabled by an appropriate selection for the operating mode.
Voltage monitoring
Voltage monitoring is only enabled if the following conditions are met simultaneously:
In addition to these conditions, either a minimum current having the default threshold
setting of I > 0.05 ⋅ I nom or the closed position of the circuit breaker contacts can be used
as enabling criteria. If at least one of the phase-to-phase voltages falls below the set
trigger value M C M O N : V m i n < for the period of the operate-delayed timer stage
M C M O N : O p e r a t e d e l a y , then the M C M O N : U n d e r v o l t a g e signal is issued.
Phase-sequence
monitoring
Phase-sequence monitoring is only enabled if the following conditions are met
simultaneously:
MCMON: Operate
delay
[ 017 023 ]
MAIN: General
starting
[ 040 000 ]
MCMON: Enabled >0.05 Inom
[ 040 094 ] C
IA
IB
IC
1
2 &
3 &
1: Vmin<
2: Vmin< with I enable
MAIN: CB closed 3: Vmin< w.CB cont.enab
sig. EXT
[ 036 051 ]
MCMON: Vmin<
& C
[ 017 022 ] t 0 MCMON: Undervoltage
& [ 038 038 ]
VA-G +
VB-G SFMON: Undervoltage
- [ 098 009 ]
+
VC-G -
-
+
>0.65 Unom
C
MCMON: Meas.
& voltage o.k.
[ 038 048 ]
0
1
0: No
1: Yes
>0.4 Vnom
C
&
& C
60°< (VA-B)<180°
60°< (VB-C)<180° MCMON: Phase sequ.
V faulty
60°< (VC-A)<180° [ 038 049 ]
t 0 SFMON: Phase sequ.
V faulty
[ 098 001 ]
19Z5088 B_EN
Fuse Failure monitoring must be able to discriminate between a short circuit in the three-
phase network being monitored and a reference voltage missing because of a short
circuit or an open circuit in the secondary circuits of the reference voltage.
A short circuit or an open circuit in the secondary circuits of the reference voltage is
present when the following conditions are met:
If any of the measured values exceeds or falls below the corresponding upper or lower
limit values, then a signal is issued after the associated time period has elapsed.
VC-G
t 0
VPP,max LIMIT: tVPP>>
elapsed
VPP,min [ 040 229 ]
t 0
LIMIT: tVPP<
elapsed
[ 040 230 ]
t 0
LIMIT: tVPP<<
elapsed
[ 040 231 ]
t 0
LIMIT: tVPG>
elapsed
[ 040 224 ]
t 0
VPG,max LIMIT: tVPG>>
elapsed
VPG,min [ 040 225 ]
t 0
LIMIT: tVPG<
elapsed
[ 040 226 ]
t 0
LIMIT: tVPG<<
elapsed
[ 040 227 ]
47Z0154 B_EN
3-279 Limit Value Monitoring of maximum and minimum phase-to-phase voltage and maximum and minimum phase-to-ground voltage
LIMIT: General
enable USER
014 010
LIMIT:
Enabled
040 074
0: no
MAIN: Device 1: yes
on-line LIMIT: Vref> LIMIT: tVref>
003 030
042 144 042 148
1: yes (= on)
LIMIT: tVref>
elapsed
042 152
LIMIT: tVref>>
Vref elapsed
042 153
LIMIT: tVref<
elapsed
042 154
LIMIT: tVref<<
abgelaufen
042 155
19Z5215A_EN
LIMIT Starting
MAIN: Protection
active
MEASI: Temperature LIMIT
elapsed
LIMIT Starting
LIMIT LIMIT
LIMIT
elapsed
LIMIT Starting
LIMIT LIMIT
LIMIT
elapsed
LIMIT Starting
LIMIT LIMIT
LIMIT
elapsed
19Z5212A_EN
LIMIT: Starting
T1>
040 200
LIMIT Enabled LIMIT: T1> LIMIT: tT1>
LIMIT: Starting
T1>>
040 201
LIMIT: T1>> LIMIT: tT1>>
LIMIT: tT1>>
elapsed
040 203
LIMIT: Starting
T1<
040 204
LIMIT: T1< LIMIT: tT1<
040 206
LIMIT: Starting
T1<<
040 205
LIMIT: T1<< LIMIT: tT1<<
040 207
19Z5213A_EN
3-284 Monitoring the measured temperature value T1 as an example for measured temperature values T1 to T9
Backup sensors
When an open circuit has occurred the 2-out-of-3 logic available with the Limit Value
Monitoring function will revert to backup sensors.
The selection of such backup sensors for the Limit Value Monitoring function is made in
the function group M E A S I .
For this purpose the temperature sensors connected to the temperature p/c board (RTD
module) are divided into three groups:
If the backup temperature sensor from group 2 also fails it will be replaced by the
corresponding sensor from group 3, under the assumption that
M E A S I : B a c k u p T e m p S e n s o r P S x is set to Group 1 –2/3.
Main sensor Backup sensor from group 2 Backup sensor from group 3
With setting: With setting:
Group 1 -2 Group 1 -2/3
or
Group 1 -2/3
T1 T4 T7
T2 T5 T8
T3 T6 T9
Should temperature sensor T1 fail, with the setting Group 1 –2/3, it will replaced by T4.
Should temperature sensor T4 also fail it will replaced by T7.
2-out-of-3 monitoring
Limit values resulting from temperature values measured by main sensors (from
group 1) or their corresponding backup sensors are processed by the '2-out-of-3' Limit
Value Monitoring function, L I M I T : 2 o u t o f 3 w i t h T 1 , 2 , 3 . This is displayed in the
following figure.
19Z5210A_EN
3-285 Using backup sensors ("BackupTempSensor") with the '2-out-of-3' Limit Value Monitoring function
All functions associated with temperature sensors operate in a parallel mode. In this
way the '2-out-of-3' Limit Value Monitoring function, L I M I T : 2 o u t o f 3 w i t h T 4 , 5 , 6
may use temperature sensors from group 2 even though these backup sensors are
configured to group 1.
19Z5211A_EN
3-286 Limit Value Monitoring function '2-out-of-3' for temperature sensors T4 to T6 and T7 to T9. If M E A S I : B a c k u p T e m p S e n s o r P S x
is set to 'Without' this scheme will also apply to temperature sensors T1 to T4.
Application example
A motor protection application is shown in the figure below with temperature sensors T1
to T9 connected to the temperature p/c board (RTD module) and a "PT 100" resistance
thermometer connected to the analog (I/O) module Y.
On the stator there are three temperature sensors as the main sensors (group 1: T1,
T2, T3) and three backup sensors (group 2: T4, T5, T6) used by the '2-out-of-3' Limit
Value Monitoring function
One temperature sensor on each of the bearings is used for individual Limit Value
signaling
One main and one backup sensor inside the coolant are used by the thermal replica
in the Thermal Overload protection
RTD
RTD
RTD
RTD
RTD
RTD
RTD
RTD
Stator
RTD
RTD
Rotor
Bearing Bearing
19B5236A_EN
3-287 Temperature measurements on a motor to be used with the Limit Value Monitoring function (L I M I T ) and the Thermal Overload protection
(THERM)
Programmable (or user-configurable) logic enables the user to link binary signals within
a framework of Boolean equations.
Binary signals in the P139 may be linked by logical 'OR' or 'AND' operations with the
option of additional NOT operations by setting L O G I C : F c t . A s s i g n m . O u t p . n ,
where n = 1 to 32. The Boolean equations need to be defined without the use of
brackets. The following rule applies to the operators: ‘NOT’ before ‘AND’ before ‘OR’.
Logical operations can be controlled through the binary signal inputs in different ways.
The binary input signals L O G I C : I n p u t n E X T (n = 1 to 16) have an updating
function, whereas the input signals L O G I C : S e t n E X T (n = 1 to 8) are latched.
The logic can only be controlled from the binary signal inputs configured for
L O G I C : S e t n E X T if the corresponding reset input L O G I C : R e s e t n E X T )
has been configured for a binary signal input. If only one or neither of the two functions
is configured, then this is interpreted as ‘Logic externally set’. If the input signals of the
two binary signal inputs are implausible (such as when they both have a logic value of
‘1’), then the last plausible state remains stored in memory.
When using the programmable logic, the user must carry out a functional type test to
conform with the requirements of the relevant protection/control application. In
particular, it is necessary to verify that the requirements for the implementation of logic
linking (by setting) as well as the time performance during device startup, during
operation and when there is a fault (device blocking) are fulfilled.
3-288 Control of logic operations via setting parameters or stored input signals
3-289 Setting options for programmable logic (shown here for output 1)
The output signal of an equation can be fed into a further, higher ordinal number
equation as an input signal thus leading to a set of interlinked Boolean equations. The
equations are processed according to the sequence of their ordinal numbers. It should
be noted that in the case of overlapping equations, the result is provided by the equation
with the highest ordinal number.
The output signal of each equation is fed to a separate timer stage with two timer
elements and a choice of operating modes. This offers the possibility of assigning a
freely configurable time characteristic to the output signal of each Boolean equation. In
the Minimum Dwell operating mode, the setting of timer stage t2 has no effect. Figures
3-290 to 3-294 show the time characteristics for the various timer stage operating
modes.
Note: If the device is switched to offline the equations are not processed and all
outputs are set to the '0' logic level.
The P139 is designed to control up to 6 switchgear units. The Bay Panel type defines
the layout of a bay with its switchgear units.
When a Bay Panel type is selected, the binary inputs for switchgear status signals and
the output relays for control commands are configured automatically if M A I N : A u t o -
a s s i g n m e n t I / O is set to 'Yes'. If set to 'No', the user will need to carry out this
configuration. The list of Bay Panel types in the Appendix shows which binary inputs
and output relays have been assigned signals or commands for control of switchgear
units in the case of automatic configuration.
Setting options for the P139 and the different possibilities to integrate a switchgear unit
into the functional sequence of the P139 (processing of status signals only or controlling
and signaling) will be explained below, using one switchgear unit as an example.
Function group DEV01 will be used throughout in this example. If a signal is identified in
the function diagrams by function group "COMM1:" with a blank address [--- ---], it will
indicate that it is a signal to or from the communication interface and that it has not been
assigned an address. Signals listed in the function diagrams as ‘signal 1’ to ‘signal n’
are specified in the configuration tables of the Address List.
The status signals ‘Open’ and ‘Closed’ are assigned to binary signal inputs. The signals
conditioned by debouncing and chatter suppression (see: ‘Main Functions of the P139’)
are used for further processing. If no logic value of '1' is present at any of the two binary
signal inputs, the running time monitoring function is started. For the duration of the set
time period for running time monitoring or until the contacts on the switchgear unit are
back to a defined position - either ‘Open’ or ‘Closed’ - the signal ‘Intermediate position’ is
issued.
The signal ‘Faulty position’ is issued if the contacts on the switchgear unit have not
reached either their ’Open’ or ‘Closed’ position after the set time period for running time
monitoring and the delay time set in M A I N : D e l a y M a n . O p . S u p e r v . have
elapsed. If D E V 0 1 : S t a t . i n d . i n t e r m . p o s . is set to 'Yes', a delay time of 5 s is
started. Once this time period has elapsed and there is no status signal for the position,
the state actually present at the binary inputs will be signaled.
Switch truck
For switchgear units mounted on switch trucks with switch truck plugs, it is possible to
configure a single-pole status signal from the switch truck plug. If such a configuration
has been assigned, the status signal for the position of the associated switchgear unit is
set to ‘Open’ while the input has a logic value of '1'.
Dependent on the respective position of control the P139 will issue the following logic
state signals:
Enabling switching
commands
Before a switching command is executed, the P139 checks the interlocking conditions
defined in the interlocking logic to determine whether a switching command is permitted
or not. Bay interlock conditions for operation with or without the station interlock function
can be defined. The assignment of an output relay from the interlocking logic to a
switching command determines the interlocking conditions that define, for example, the
conditions for the 'Open' command for operation without the station interlock function.
3-298 Assignment of the equations of the interlocking logic to the switching commands; enabling of switching commands by the bay interlock
function
If there is to be a check on the bay interlock and the station interlock function, the bay
interlock will be checked first. If bay interlocking issues a switching enable, a switching
request will be sent to the substation control level. At substation control level, there will
then be a check - taking into account the station interlock functions – as to whether
switching is permitted or not. If the substation control level also issues an enabling
command, the switching operation is carried out provided that the enable from the bay
interlock is still present. Optionally, the ‘Open’ or ‘Close’ switching operation can be
carried out without checking the station interlock function conditions. In this case, the
bay interlock conditions defined for operation without station interlock functions will be
considered.
Linking protection
commands to switching
commands
For circuit breakers, the ‘Open’ command can be linked to the protection trip signals.
The 'Close' command can also be linked to the close command of the protection
functions. The Bay Panel type defines which of the switchgear units are circuit breakers.
The trip (open) or close commands of the protection functions are executed directly
without a check of the interlocking conditions.
Issue of switching
commands
Dependent on the operating mode (set at D E V x x : O p e r . M o d e c m d . ) set for
commands, switching commands are issued for the set timer durations or according to
time control.
When the automatic synchronism check (ASC) is active and the parameter
A S C : S y s t e m i n t e g r a t . P S x is set to 'Autom. synchr. control' a 'Close' request
will automatically issue a 'Close' command for the circuit breaker after a ‘close enable'
was issued by the ASC.
If the contacts on the switchgear unit have not reached either their ‘Open’ or ‘Closed’
position after the set time period for running time monitoring has elapsed the signal
'Faulty position' is issued. If D E V 0 1 : S t a t . i n d . i n t e r m . p o s . is set to 'Yes', a
delay time of 5 s is started. Once this time period has elapsed and there is no status
signal for the position, the state actually present at the binary inputs will be signaled.
Switch truck
For switchgear units mounted on switch trucks with switch truck plugs, it is possible to
configure a single-pole status signal from the switch truck plug. If such a configuration
has been assigned, the status signal for the position of the associated switchgear unit is
set to ‘Open’ while the input has a logic value of '1'.
DEV01: Close
command
210 029 1
3
DEV01: Switch.
device open
210 036
DEV01: Switch.
device closed
210 037
4
1 10 ms
19Z5201A_EN
3-303 Sequence for time control of switching commands without external termination control
DEV01: Close
command
210 029
1
3
DEV01: Switch.
device open
210 036
DEV01: Switch.
device closed
210 037
DEV01:Inp.asg.
end Close
210 016
1 10 ms
3 DEV01: Latching time 210 005
19Z5202A_EN
3-304 Sequence for time control of switching commands with external termination control
If a Bay Panel type with direct motor control is selected, a binary input for the status
signal of the motor relay and one output relay each to trigger the motor relay and the
shunt windings will have to be configured. In the example illustrated in Figure 3-305, the
single-pole command C M D _ 1 : C o m m a n d C 0 1 2 is defined for control of the motor
relay, the single-pole command C M D _ 1 : C o m m a n d C 0 1 1 is defined for control of
the shunt windings and the single-pole signal S I G _ 1 : S i g n a l S 0 1 2 (debounced
and conditioned by chatter suppression) is defined for the status signal to the motor
relay.
After triggering the motor relay, a set monitoring time period is started during which the
status signal must be issued by the motor relay. If the status signal is not received
during this time period the 'Close' command issued to the output relays, configured to
control the motor relay and the shunt windings, is terminated. In addition a signal is
transferred to the substation control level.
If the status signal from the motor relay is issued during the monitoring time period, the
running time monitoring of the motor relay is started simultaneously with this status
signal. Monitoring of the switching command is then the same as with
electromechanically operated switchgear units.
CMD_1: Command
C011
200 051
DEV01: Close
command
210 029
1 2
CMD_1: Command
C012
200 056 2
3
DEV01: Switch.
device open
210 036
DEV01: Switch.
device closed
210 037
4
1 10 ms
19Z5203A_EN
3-306 Sequence of time monitoring for direct motor control without external termination
DEV01: Close
command
210 029
1 2
CMD_1: Command
C012
200 056 2
3
DEV01: Switch.
device open
210 036
DEV01: Switch.
device closed
210 037
DEV01: Inp.
asg.end Close
210 016
1 10 ms
19Z5204A_EN
3-307 Sequence of time monitoring for direct motor control with external termination
Switching commands issued to switching units within the bay that are subject to control
actions are only enabled after interlock conditions have been checked. The definition of
interlock conditions is carried out in the interlocking logic by Boolean equations.
By selecting a Bay Panel type the bay interlock conditions to set switching units within
the bay to the “Closed” or “Open” position are defined automatically. Different conditions
are defined for the bay interlock equations to operate with or without station interlock
(see Appendix, ‘List of Bay Types’). Such interlock conditions that are automatically
defined by selecting a Bay Panel type may be adapted at any time by the user according
to system requirements. The following signals acquired by the P139 may be linked
logically for the bay interlock:
There are max 32 equations each with 32 equation elements available to define interlock
conditions. The Boolean equations need to be defined without the use of brackets. The
following rule applies to the operators: ‘NOT’ before ‘AND’ before ‘OR’. The output
signal of an equation can be fed into a higher ordinal number equation as an input thus
leading to a set of interlinked Boolean equations.
Commands may be transmitted to the P139 via the communications interface. When the
P139 receives such a command, and the remote control mode is enabled, an
appropriately configured output relay will be triggered and a signal is issued.
The operating mode may be selected individually for each single-pole command. The
following settings are possible:
Long command
Short command
Persistent command
If the operating mode long or short command has been selected the output relay will be
triggered for the time period set at M A I N : C m d . d u r . l o n g c m d . or
MAIN: Cmd. dur. short cmd.
The setting possibilities and the functional sequence is displayed in the example for
Command C001. This will apply accordingly to all other single-pole commands.
3-309 Functional sequence for single-pole commands in the example for Command C001
Binary, single-pole signals issued by the system may be transmitted by the P139 via its
appropriately configured binary signal inputs to the control station.
Such single-pole input signals are conditioned by debouncing and chatter suppression
(see: ‘Main Functions of the P139’). This conditioned signal is then presented as
SIG_1: Logic signal Sxxx.
Without function
Start/end signal
Transient signal
If setting "Without function" has been selected then no message is transmitted when the
signal state at the binary signal input changes. If setting "Start/end signal" has been
selected then a message is transmitted every time the signal state at the binary signal
input changes. A requirement for transmission of the "Start signal" message is that the
logic "1" signal is present for the set minimum time period. If setting "Transient signal"
has been selected then a message is transmitted every time the signal state at the
binary signal input changes form logic "0" to logic "1".
The following figure displays setting modes and the functional sequence with the
example for logic signal S001. This will apply accordingly to all other single-pole
signals.
3-310 Functional sequence for single-pole signals with the example for logic signal S001
The P139 features a binary counter that can count the positive pulse edges of a binary
signal present at an appropriately configured binary signal input. Such a binary signal
can be provided with debouncing.
Enable/disable the
counting function
The counting function (COUNT) can be disabled or enabled via setting parameters.
Debouncing
The first positive pulse edge of the binary input signal to be counted will trigger a timer
stage which will continue to run for the set debouncing time period. Each positive pulse
edge during the debouncing time re-triggers the timer stage. The binary input signal will
be counted if it is stable during the set debouncing time period.
After the set debouncing time has elapsed, the state of the signal is checked. If it is the
same as prior to the occurrence of the first pulse edge, it will not be counted.
Counting function
A debounced binary signal is counted by a 16 bit counter. The counter may be set to a
specific count value (preload function) by setting a parameter or via the serial interfaces.
The counter value can be shown on the LC-display and read out via the PC interface or
the communications interface.
COUNT: General
enable USER
[ 217 000 ]
0
1 COUNT: Enabled
[ 217 001 ]
0: No
1: Yes
MAIN: Device
online COUNT: Count 1
[ 003 030 ] [ 217 100 ]
1: Yes (= on)
COUNT: Set +
counter 1 EXT Entprellung
[ 217 130 ] R
COUNT: Transmit
counts USER
[ 217 008 ]
0
COUNT: Transmit
1 counts
[ 217 010 ]
0: don't execute
1: execute
COUNT: Transmit C
counts EXT
[ 217 009 ]
COUNT: Cycle
C t.count transm COMM1: Count 1
[ 217 007 ]
[ --- --- ]
COUNT: Reset
USER
[ 217 003 ]
= 0 min
0
1 COUNT: Reset
[ 217 005 ]
0: don't execute
1: execute
COUNT: Reset
EXT
[ 217 004 ]
MAIN: General
Reset USER
[ 003 002 ]
1: execute
MAIN: General
Reset EXT
[ 005 255 ]
19Z64ANA_EN
4 Design
The P139 is available in different types of cases and with different combinations of
modules.
The P139 – like all other device types in the MiCOM Px30 system – is equipped with the
standard local control panel (LOC). The local control panel is covered with a tough film
so that the specified degree of IP protection will be maintained. In addition to the
essential control and display elements, a parallel display consisting of a total of 17 LED
indicators is also incorporated. The meaning of the various LED indications is shown in
plain text on a label strip.
The PC interface (9-pin D-Sub female connector) is located under the hinged cover at
the bottom of the local control panel.
4.1 Designs
Electrical connections are made via plug-in threaded terminal blocks. The threaded
terminal blocks in the surface-mounted case are accessible from the front of the device
after unscrewing the crosshead screws on the sides (see Figure 4-1, c) and removing
the local control panel. The local control panel can then be secured by inserting the tabs
in the slots in the left side wall (see Figure 4-1, d). The flush-mounted case is
connected at the back of the case.
The secondary circuit of live system current transformers must not be opened! If the
secondary circuit of a live CT is opened, there is the danger that the resulting voltages
will endanger personnel and damage the insulation.
The threaded terminal block for system current transformer connection is not a shorting
block! Therefore always short-circuit the system current transformers before loosening
the threaded terminals.
4-1 Surface-mounted case, removal of local control panel (example for a 40 T device)
Aus-Kommando
Warnung
Block./ Stör ung
Betr ieb
Änderungsmod .
147,5
177,5
184,5
213,4 257,1
242,6
260,2
Aus-Kommando
War nung
Block./ Sö
t r ung
Betr ieb
Änder ungsmod
.
147,5
177,5
184,5
434,8 257,1
464,0
481,6
Aus- Kommando
War nung
Block./ Stör ung
Betr ieb
Änder ungsmod .
177,5
213,4 227,9
253,6
203,0
155,4
159,0
168,0
5,0
5,0
181,3
4-4 Dimensional drawing for 40 T flush-mounted case with instrument panel cut-out, flush-mount method 1 (without the angle brackets and
frame) (dimensions in mm)
Aus- Kommando
Warnung
Block./ Störung
Betr ieb
Änderungsmod .
101,6
177,5
213,4 227,9
253,6
242,6
260,2
6,4
101,6
186,5
224,5
242,6
4-5 Flush-mounted case 40T with instrument panel cut-out, flush-mount method 2 (with angle brackets and frame)
Note: The device has increased mechanical robustness if flush-mount method 2 (with angle brackets and frame, shown in this
drawing) is used for the flush-mounted case.
Aus-Kommando
Warnung
Block./ Stör ung
Betr ieb
Änder ungsmod .
177,5
434,8 227,9
253,6
284,9
259,0
25,9
159,0
168,0
5,0
5,0
410,0
4-6 Dimensional drawing for 84 T flush-mounted case with panel opening flush-mount method 1 (without the angle brackets and frame)
(dimensions in mm)
Aus-Kommando
War nung
Bo
l ck./ Stör ung
Betr e
ib
Änderungsmod .
101,6
177,5
434,8 227,9
253,6
464,0
481,6
6,4
101,6
186,5
445,9
464,0
4-7 Flush-mounted case 84T with panel opening, flush-mount method 2 (with angle brackets and frame)
Note: The device has increased mechanical robustness if flush-mount method 2 (with angle brackets and frame, shown in this
drawing) is used for the flush-mounted case.
Aus-Kommando
War nung
Block./ Stör ung
Betr e
ib
ACHTUNG:
Aus- Kommando
War nung
Block./ Stör ung
Betr e
ib
ACHTUNG:
Aus- Kommando
War nung
107,3
213,4 20,7
46,3
197,5
192,5
148,0
168,0
3,0
181,3
4-8 Device and panel opening views for connection of detachable HMI
Note: Connection of protective grounding conductor: See section 5.5
4.3 Modules
The P139 is constructed from standard hardware modules. The following table gives an
overview of the modules relevant for the P139.
(*: modules that are not shown in the location diagrams, {: optional, z: standard
equipment,
: depending on order).
A 9651 427 A ff Ethernet module (for 100 Mbit/s Ethernet, glass fiber, 4T { {
SC connector and RJ45 wire)
A 9651 471 A ff Ethernet module (for 100 Mbit/s Ethernet, glass fiber, 4T { {
ST connector and RJ45 wire)
A 9650 827 B ff InterMiCOM Module COMM3 (RS 485) 4T { {
L 9650 319 D ff * Local Control Module (for device version 40T without DHMI)
L 9650 257 D ff * Local Control Module (for device version 84T without DHMI)
L 9651 470 B ff * Local control module (for device version with DHMI)
L 9650 563 F ff * Front plate (for device version 40T with DHMI)
L 9651 920 A ff * Front plate (for device version 84T with DHMI)
Location
The location of the individual modules and the position of the threaded terminal blocks in
the P139 are shown in the location figures and terminal connection diagrams at the end
of Chapter 5.
Only qualified personnel, familiar with the "Warning" page at the beginning of this
manual, may work on or operate this device.
The instructions given in the "Protective and Operational Grounding" section should be
noted. In particular, check that the protective ground connection is secured with a tooth
lock washer, as per the diagram "Installing the protective grounding conductor terminal".
If a cable screen is added to this connection or removed from it, then the protective
grounding should be checked again.
The SC connector and RJ45 wire of the Ethernet module cannot be connected at the
same time. (The selection for IEC : Eth e r n e t M e d i a should be noted.)
All P139 overcurrent and control devices are packaged separately into dedicated cartons
and shipped with outer packaging. Use special care when opening cartons and
unpacking devices, and do not use force. In addition, make sure to remove supporting
documents and the type identification label supplied with each individual device from the
inside carton. The design revision level of each module included in the device when
shipped can be determined from the list of components (assembly list). This list of
components should be filed carefully.
If the P139 needs to be shipped, both inner and outer packaging must be used. If the
original packaging is no longer available, make sure that packaging conforms to
DIN ISO 2248 specifications for a drop height ≤ 0.8 m.
The nominal data and design type of the P139 can be determined by checking the type
identification label (see Figure 5-1). One type identification label is located under the
upper hinged cover on the front panel and a second label can be found on the inside of
the device. Another copy of the type identification label is fixed to the outside of the
P139 packaging.
The P139 design version can be determined from the order number. A breakdown of the
order number is given in Chapter 14 of this manual.
The P139 has been designed to conform to DIN 57 435 part 303. Therefore it is
important when choosing the installation location to make certain that it provides the
operating conditions as specified in above DIN norm sections 3.2 to 3.4. Several of
these important operating conditions are listed below.
Environmental Conditions
Ambient temperature: -5 °C to +55 °C [+23 °F to +131 °F]
Relative humidity: The relative humidity must not result in the formation of
either condensed water or ice in the P139.
Ambient air: The ambient air must not be significantly polluted by dust,
smoke, gases or vapors, or salt.
Solar Radiation: Direct solar radiation on the front of the device must be
avoided to ensure that the LC-Display remains readable.
Mechanical conditions
Vibration stress: 10 to 60 Hz, 0.035 mm and 60 to 150 Hz, 0.5 g
Earth quake resistance: 5 ... 8 Hz, 3.5 mm / 1.5 mm, 8 ... 35 Hz, 5 m/s2,
3 x 1 cycle
Electromagnetic conditions
Substation secondary system design must follow the best of modern practices,
especially with respect to grounding and EMC.
5.4 Installation
The dimensions and mounting dimensions for surface-mounted cases are given in
Chapter 4. When the P139 is surface-mounted on a panel, the wiring to the P139 is
normally run along the front side of the mounting plane. If the wiring is to be at the back,
an opening can be provided above or below the surface-mounted case. Figure 5-2
shows such an opening below the surface-mounted case.
5-2 Opening (cutout) for running the connecting leads to an 40 TE surface-mounted case
Flush-mounted cases are designed for control panels. The dimensions and mounting
dimensions are given in Chapter 4. When the P139 is mounted on a cabinet door,
special sealing measures are necessary to provide the degree of protection required for
the cabinet (IP 51).
For flush-mount method 1 (without angle brackets and frame), the procedure is as
follows:
Before the P139 can be installed into a control panel, the local control panel (or the front
element of the case for devices with detachable display) must be taken down. The local
control panel is removed as described below:
Remove both top and bottom hinged flaps from the device. (Lift/lower both hinged
flaps 180°up/down. Hold them in the middle and bend them slightly. The side
mountings of both hinged flaps can then be disengaged.)
Remove the M3 screws (see Figure ).
Then remove the local control panel.
The local control panel (or front element) is connected to processor module P by a plug-
in connecting cable. Make sure the connector position is correct. Do not bend the
connecting cable!
Then remove the lower M4 screws and only loosen the upper M4 screws (see
Figure 5-3). Now insert the P139 into the panel opening from the rear so that the upper
M4 screws fit into the corresponding holes. Then tighten all the M4 screws. After this,
replace the local control panel.
Note: If the control panel thickness ≥ 2 mm, the longer M3 and M4 bolts must be
used. Longer screws are enclosed within the device packing.
Completely removethe
lower screws before
installation.
12Y6181 A_EN
5-3 Installation of a case into a control panel. Flush-mount method 1 (without the angle brackets and frame ).
Example for a device with a 40 TE case.
The P139 has increased mechanical robustness if either the surface-mounted case or for the flush-mounted case flush-mount method 2 (with
angle brackets and frame, see figure 5-5)) is used.
For flush-mount method 2 (using the angle brackets and frame), the procedure is as
follows:
Remove the screws as shown in Figure 5-4, c and mount the enclosed angle
brackets using these same screws.
Then push the device into the control panel cutout from the front.
Secure the device to the control panel by using the enclosed M6 screws (see
Figure 5-5).
Assemble the cover frame and snap-fasten onto the fixing screws.
Angle brackets
M6
B6
6.4
M6 x 15
Height: 204 mm
Frame for the
80 mm
W idt h: 2 nted cas
e
s h-m ou
40T E flu
12Y6183 B_EN
5-5 Installation of a case into a control panel, flush-mount method 2 (with angle brackets and frame)
Example for a device in a 40 TE case.
The device has an increased mechanical robustness, if flush-mount method 2 (with angle brackets and frame, shown on this page) is used for
the flush-mounted cases.
A rack mounting kit can be used to combine a flush-mounted 40 TE case with a second
sub-rack to form a 19" mounting rack (see Figure 5-6). The second sub-rack can be
another device, for example, or an empty sub-rack with a blank front panel. Fit the
19" mounting rack to a cabinet as shown in Figure 5-7.
In addition, a protective ground connection at the terminal contact on the power supply
module (identified by the letters "PE" on the terminal connection diagram) is also
required for proper operation of the device. The cross-section of this ground conductor
must also conform to applicable national standards. A minimum cross section of
1.5 mm2 is required.
The grounding connection at both locations must be low-inductance, i.e. it must be kept
as short as possible.
19Y5220A_EN
The protective conductor (earth) must always be connected to the protective grounding conductor terminal in order to guarantee the
safety given by this set-up.
5.6 Connection
The P139 overcurrent and control device must be connected in accordance with the
terminal connection diagram as indicated on the type identification label. The terminal
connection diagram is included in the supporting documents supplied with the device.
The relevant terminal connection diagrams that apply to the P139 are to be found in
Chapter 5.
In general copper conductors with a cross section of 2.5 mm² are sufficient to connect a
system current transformer to a current input on the P139. To reduce CT knee-point
voltage requirements, it may be necessary to install shorter copper conductors with a
greater cross section between the system current transformers and the current inputs on
the P139. Copper conductors having a cross section of 1.5 mm2 are adequate to
connect binary signal inputs, the output relays and the power supply input.
All connections run into the system must always have a defined potential. Connections
that are pre-wired but not used should preferably be grounded when binary inputs and
output relays are isolated. When binary inputs and output relays are connected to
common potential, the pre-wired but unused connections should be connected to the
common potential of the grouped connections.
Power supply
Before connecting the auxiliary voltage VA for the P139 power supply, it must be ensured
that the nominal value of the auxiliary device voltage corresponds with the nominal value
of the auxiliary system voltage.
Current-measuring inputs
When connecting the system transformers, it must be ensured that the secondary
nominal currents of the system and the device correspond.
The secondary circuit of live system current transformers must not be opened! If the
secondary circuit of a live CT is opened, there is the danger that the resulting voltages
will endanger personnel and damage the insulation.
The threaded terminal block for system current transformer connection is not a shorting
block! Therefore always short-circuit the system current transformers before loosening
the threaded terminals.
The P139 is generally fitted with four current-measuring inputs. Three-pole or two-pole
connection is possible to suit the individual power system and substation.
The steady-state ground fault direction determination requires either the three
phase-to-ground voltages or, alternatively, the neutral-point displacement voltage from
the open delta winding of a voltage transformer assembly as the measured voltage.
The phase voltages are drawn from the same transformers like the measured variables
for the time voltage protection. An additional voltage transformer (T 90) is available in
the P139 to connect an open delta winding. When setting the protection function, the
selected voltage needs to be taken into account.
Figure 5-10 shows the standard connection for ground fault direction determination by
steady-state values where the voltage measuring circuit is connected to an open delta
winding. With this connection configuration, ‘forward/LS’ is displayed if a ground fault
occurs on the line side. A reversed connection is possible for the system current or
voltage transformer if the appropriate setting is configured (see Chapter 7).
Connection to Connection to
Holmgreen group Core balance CT
A
B BS
C
19Z5290A_EN
5-10 Connecting the steady-state ground fault direction determination function to Holmgreen-configuration and core balance transformers
Connecting protective
signaling
Either a transmission device or pilot wires are required for signal transmission,
depending on the operating mode selected. Twisted pair cores should be used as pilot
wires. Two or four cores are required. If only two cores are available, there must be an
all-or-nothing relay in each station for coupling received and transmitted signals. The
coils of the all-or-nothing relays must be designed for half the loop voltage. Figure 5-11
shows connection with two cores and Figure 5-12 connection with four cores.
The protective signaling transmitting relay can be set to either Transm. rel. break con. or
Transm. rel. make con. In the first case the break contact of the transmitting relay must
be wired, and in the second case the make contact must be wired. The figures show the
connection for the setting Transm. rel. break con.
Connecting a resistance
thermometer
A resistance thermometer can be connected if the device is fitted with analog module Y.
This analog I/O module input is designed to connect a PT 100 resistance thermometer.
The PT 100 should be connected using the 3-wire method (see Figure 5-13). No supply
conductor compensation is required in this case.
The polarity for connected binary signal inputs is to be found in the terminal connection
diagrams (see supporting documents supplied with the device or end of this chapter).
This is to be understood as a recommendation only. Connection to binary inputs can be
made as desired.
Connection of switchgear
units having direct motor
control
In the case of bay types having direct motor control, one binary input is configured for
the status signal and one output relay is configured for triggering and resetting the motor
relay. Configuration of appropriate output relays to trigger the armature and shunt
windings of motors on load disconnect switches, isolating links or grounding switches is
in accordance with the ‘List of Bay Types’ (see Appendix). A connection example for a
direct motor control is shown in Figure 5-14.
PC interface
The PC interface is provided so that personnel can operate the device from a personal
computer (PC).
Communication interface
The selection and assembly of a properly cut fiber-optic connecting cable requires
special knowledge and expertise and is therefore not covered in this operating manual.
The fiber-optic interface may only be connected or disconnected when the supply
voltage for the device is shut off.
An RS485 data transmission link between a master and several slave devices can be
established by using the optional communication interface. The communication master
could be, for instance, a central control station. Devices linked to the communication
master, e.g. P139, are set-up as slave devices.
The RS 485 interface available on the P139 was designed so that data transfer in a full
duplex transmission mode is possible using a 4-wire data link between devices. Data
transfer between devices using the RS 485 interface is set up only for a half duplex
transmission mode. To connect the RS485 communication interface the following must
be observed:
Only twisted pair shielded cables must be used, that are common in
telecommunication installations.
At least one symmetrical twisted pair of wires is necessary.
Conductor insulation and shielding must only be removed from the core in the
immediate vicinity of the terminal strips and connected according to national
standards.
All shielding must be connected to an effective protective ground surface at both
ends.
Unused conductors must all be grounded at one end.
P139
P139
P139
P139
01 02 03 04 05 06 07 08 09 10
P A N T X X X V X
CH1 alt. -/4J 6I 6I 24I 4I
CH2 -/4V/5V 6O 6O 8O 6O
Y
alt . alt . alt.
9T
A alt. T Y
ETH A 3J 4I
CH2 CH3 6V
01 02 03 04 05 06 07 08 09 10
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21
P A N T X X X X V
CH1 alt. -/4J 6I 6I 24I 4I
CH2 -/4V/5V 6O 6O 6O 8O
Y
alt. 9T alt. alt.
A alt . T Y
ETH A 3J 4I
CH2 CH3 6V
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21
Transformer Type T NCIT Type T Power Supply Type V Binary Type X Binary Type X
module -/4J -/4V/5V module 3J/6V Module 4I / 8O module 6I 6O module 24I
Ring Pin Voltage measuring X044 Low- level Ring Pin Ring Pin
X041 X041 inputs X_1 X_1 Output Relays X_1 X_1 Output relays Ring Pin Signal inputs
X054 inputs
Option: 4 VA-G,1 +
U 1 1 1 1 X_1 X_1 V in
13 1 VAG
U51 2 2
5 - K_01 2 2 1 1
T5 # U_01
14 2 VBG 6 3 3 3 3 2 2
U_02
15 3 VCG T6 1 VB-G,1 +
U 4 4 4 4 K_1 3 3
16 4 T7 2 - U52 5 5 5 5 4 4
U_03
# U_04
17 5 VNG 3 6 6 K_02 6 6 K_2 5 5
T90 U_05
18 6 7 VC-G,1 + U 7 7 7 7 6 6
8 - U53 8 8 8 8 7 7
U_06
# U_07
Option: 9 9 9 K_03 9 9 8 8
11 7 K_3 9 9
U_08
Vref
12 8 T15 X045 X_2 X_2
X055 10 1 10 1
4 VA-G,2 +
U 11 2 K_04 11 2 K_4 X_2
V in
Current measuring 5 -
U54 12 3 K_05 12 3 10 1
# U_9
inputs 6 Vref / 13 4 K_06 13 4 11 2
X042 Option: 1 VB-G,2 +
U 14 5 K_07 14 5 12 3
U_10
U55 U_11
1 1 IA T1 2 - 15 6 15 6 K_5 13 4
# U_12
2 2 3 16 7 K_08 16 7 14 5
U_13
3 3 IB T2 7 VC-G,2 +
U 17 8 17 8 K_6 15 6
U56 U_14
4 4 8 - 18 9 16 7
# U_15
5 5 IC T3 9 Signal Inputs 17 8
6 6 18 9 18 9
U_16
UE
7 7 IN T4 X046 U_01 X_3 Signal inputs
8 8 X056 X_3 19 1 Vin
4 IA + U 19 1 U_1 X_3
U57 V in
5 - 20 2 20 2 Vin 19 1
# UE U_18
6 21 3 U_02 21 3 20 2
1 IB + U 22 4 22 4 U_2 21 3
U_18
U58 UE Vin U_19
2 - U_03 22 4
# U_20
3 23 5 UE 23 5 Vin U_3 23 5
U U_21
7 IC + 24 6 U_04 24 6 24 6
8 -
U59 25 7 U_4 25 7
U_22
# Vin
9
U_23
Power Supply 26 8
U_5 U_24
25 7 + UH 26 8 Vin 27 9
26 8 - U100 27 9
27 9 PE U_6
1
RJ45 M5[DCD]
2
D2[R] X_3
3
D1[T] 19 1 1)
COMM2 4
E U27 20 2 K_04
wire link 5
E2[G] 21 3
22 4 1)
X10 7 +UB
1
X//Y 23 5 K_05
24 6
2 D2[ R]
3
RS 232 25 7
U20 26 8 K_06
4
27 9
5 D1[ T]
RS 485
Control is also possible through the PC interface. This requires a suitable PC and a
specific operating program.
TRIP
ALARM
OUT OF SERVICE
C
HEALTHY G
EDIT MODE
O I L/R
6-1 View of the local control panel and layout of the LED indicators on case 40T and case 84T devices
Display levels
All data relevant for operation and all device settings are displayed on two levels. Data
such as the switching status or the measured operating values is displayed at the panel
level and provides an up-to-date overview of the status of the bay. The menu tree level
below the panel level allows the user to select all data points (settings, signals,
measured variables, etc.) and to change them, if appropriate. To access a selected
event recording from either the panel level or from any other point in the menu tree,
press the "READ" key . G
Bay Panel Signal Panel Measured Value Panel (s) Event Panel
(state-dependent)
P432 Page H 17:58:34 Signals 17:58:44 Fault 17:58:44 Record View
Signals 17:58:44 Ground fault 17:58:44
P432 Page B 17:58:34 Signals 17:58:44 Overload 17:58:44
Oper/Rec/OP_RC
G
P432 Page A 17:58:34 Signals 17:58:44 Meas. values 17:58:44 Events 17:58:54 Operat. data record.
BB1 MAIN: Voltage A-B prim.
20.04.98
BB2 M.c.b. trip V EXT 20.7 kV 05:21:32.331 ARC
Q Q PBB : Voltage B-C prim.
Enabled
1 2 PS 1 active 20.6 kV Start
PBB : Voltage C-A prim.
Q
PS 2 active 20.8 kV
0 23:58:17.501 MAIN
G
MAIN: Current IA prim. CB closed sig. EXT
Q Bay interlock. act. 416 A End
8 MAIN: Current IB prim. 21.04.98
Locked Subst. interl. act. 415 A
Remote 05:21:32.331 DEV01
Current IC prim.
1088 A ↑ 417 A Switch.device closed
Curr. IP,max prim. ↓ Start
↑↓ ↑↓
Gerätetyp
Control and Display Panels
Display panels
The following display panels are available with the P139:
Bay Panel
Signal Panel
Measured Value Panels, which are called up according to system conditions
Event Panel
The Bay Panel displays the up-to-date switching status of the selected bay as a one line
diagram. If user-defined bay types are applied, resulting information may be sub-divided
into up to eight pages. A maximum of 28 physical and logic binary status may be
configured to one Signal Panel and, depending on the operating mode, acknowledged.
Selected measured values are displayed on the Measured Value Panels. Only the
Measured Value Panels relevant for the particular design version of the given device and
its associated range of functions are actually available.
The Event Panel displays the most recent events, each with a time tag, such as the
opening of a switchgear unit.
ENTER Key
G
Panel Level:
By pressing the ENTER key at the Panel level, the user can go to the first menu tree
level.
Menu Tree Level:
To enter the input mode, press the ENTER key. Press the ENTER key a second time
to accept the changes as entered and leave the input mode. The LED indicator
labeled EDIT MODE signals that the input mode is active.
CLEAR Key C G
Press the CLEAR key to reset the LED indicators and clear all measured event data.
The records in the recording memories are not affected by this action.
Panel Level:
Bay Panel:
If the CLEAR key is pressed while selecting a switchgear unit on the Bay Panel then
the selection of the switchgear unit is canceled. The LED indicators are not reset in
this procedure.
Signal Panel:
A selected flashing signal may be acknowledged individually by pressing the CLEAR
key. This acknowledgement will switch the flashing signal to a static status but will
not cause the LED indicators to reset or clear measured event data.
Menu Tree Level:
Input mode:
When the CLEAR key is pressed all changes entered are rejected and the input
mode is exited.
G
READ Key
Press the READ key to access a selected event recording from either the Panel level
or from any other point in the menu tree.
Page Key
Panel Level:
Pressing the page key shows the next panel.
Menu Tree Level:
When the page key is pressed the Menu Tree Level is exited and the Bay Panel is
accessed.
Selection Key
Bay Panel:
The Selection key is effective only in the Bay Panel and only if local control is
activated.
If local control has been selected, pressing the selection key selects the switchgear
unit to be controlled. The selected external device will be marked by an asterisk (*) –
as long as no external device names are displayed. Otherwise the external device
name will flash and will be displayed in the status line.
Signal Panel:
The Selection key is used to select a flashing signal (not yet acknowledged) and will
also automatically switch to pages that might be available. When the last flashing
signal has been reached pressing the Selection key again will start with the first
flashing signal.
OPEN Key O
The OPEN key is effective in the Bay Panel only.
Pressing the OPEN key controls the selected switchgear unit – taking into account
the interlock equation – to assume the ‘open’ status.
CLOSE Key I
The CLOSE key is effective in the Bay Panel only.
Pressing the CLOSE key controls the selected switchgear unit – taking into account
the interlock equation – to assume the ‘closed’ status.
The following presentation of the individual control steps shows which displays can be
changed in each case by pressing keys. A small black square to the right of the enter
key indicates that the LED indicator labeled EDIT MODE is illuminated. An underscored
external device name in the Bay Panel indicates a selected switchgear unit. The
examples used here are not necessarily valid for the device type described in this
manual; they merely serve to illustrate the control principles involved.
After start-up of the device, the display is at the Panel Level. The Bay Panel is
displayed.
device. SS1
SS2
Note: Q1 Q2
X YYY
Parameters
Level to the Menu Tree Level.
SS1
SS2
Alternatively first press the ‘up’ key and hold it G
down while pressing the CLEAR key. + C
G
Q1 Q2
Note: Q0
It is important to press the ‘up’ key first and Q9
release it last in order to avoid unintentional
resetting of stored data.
Q8
Locked
Remote
1088 A
Curr. IP,max prim.
After the set return time has elapsed (setting in menu tree: "Par/Conf/LOC"), the display
will switch automatically to the Bay Panel.
If none of the control keys is pressed, the display illumination will switch off once the set
‘return time illumination’ (setting in menu tree: "Par/Conf/LOC") has elapsed. Pressing
any of the control keys will turn the display illumination on again. In this case the control
action that is normally triggered by that key will not be executed. Reactivation of the
display illumination is also possible by using a binary input.
If continuous display illumination is required, the function ‘return time illumination’ is set
to ‘blocked’.
At Panel Level, the user can move from one Panel type to another by pressing the Page
key (in one direction only) or the ‘left’/’right’ keys (in both directions).
Information displayed on
the Bay Panel
Figure 6-3 shows an example of a Bay Panel. The top line shows the device type on the
left and the current time of day on the right. Together with a customized Bay Type with
more than one Bay Panel page the top line will include a page marker in the center. The
page markers run from "Page A" (first page) to "Page H" (eighth page).
The Bay Panel shown below in one-line diagram representation is a function of the set
BayType. The symbols shown in the following table are used to represent the
switchgear units and other external devices as well as the status of switchgear units.
The user can switch between character sets 1, 2, and 3. Character set 3 is identical to
character set 1 in as-delivered condition but can be replaced by a user-defined character
set – by using a special ancillary tool. The symbols of character set 2 are used in the
following description.
The fourth line from the bottom shows (in abbreviated form) whether a bay interlock is
active. The third line from the bottom indicates whether remote or local control is
permitted. In the example shown here, remote control is activated. The two lines at the
bottom contain measured value data. The arrows to the right of the measured value
data indicate that additional measured values can be called up by pressing the ‘up’ or
’down’ keys.
X YYY 10:33:22
SS1
SS2
Q1 Q2
Q0
Q9
Q8
Locked
Remote
1088 A
Curr. IP,max prim.
On
‘In-motion’, ’Faulty’
On
‘In-motion’, ’Faulty’
Disconnector Off
On
‘In-motion’, ’Faulty’
On
‘In-motion’, ’Faulty’
Fuse Off
On
displayed. Remote
1088 A
Curr. IP,max prim.
G
1 By pressing the ‘up’ or ‘down’ key the next or
X YYY 10:33:25
Q9
Q8
Locked
Remote
1000 A
Curr. IA prim.
Controlling switchgear
units
Switchgear units can be controlled from the local control panel, provided that the unit has
been set for 'local control'. If the local/remote key is set to switch between remote and
local control (R↔L), then the switch from 'remote' to 'local' operation requires a
password. When more than one Bay Panel page is used only joint 'local/remote'
switching is available.
The following example is based on the (R↔L) setting for the local/remote key and the
factory-set L/R password. If the password has been changed by the user (see the
section 'Changing the Password') the following description will apply accordingly.
SS1
SS2
Q1 Q2
Q0
Q9
Q8
Locked
Remote
1088 A
Curr. IP,max prim.
L/R
1 Press the 'local/remote' key (L/R) to switch XX YYY 10:33:25
the device to local operation. The Bay Panel is
no longer displayed. The device type appears ********
in the first line and eight asterisks (*) appear in
the fourth line as a prompt to enter the
password.
‘Down’ G
XX YYY 10:33:29
G
‘Right’ G
XX YYY 10:33:31
G
‘Up’ G
XX YYY 10:33:33
The display will change as shown in the
G
Q8
Locked
Local
1088 A
Curr. IP,max prim.
C
2b This control step can be canceled at any X YYY 10:33:22
Q0
Q9
Q8
Locked
Remote
1088 A
Curr. IP,max prim.
Q0
Q9
Q8
Locked
Local
1088 A
Curr. IP,max prim.
Q9
Q8
Locked
Local
1088 A
Curr. IP,max prim.
Q1 Q2
Q0
Q9
Q8
Locked
Local
1088 A
Curr. IP,max prim.
Q8
Locked
Local
1088 A
Curr. IP,max prim.
Q0
Q9
Q8
Locked
Remote
1088 A
Curr. IP,max prim.
The Signal Panel is used to display the up to 28 different physical and logical binary
states that the device has available. The top line in the display shows the panel
designation 'Signals' and the current time of day. The following empty line separates the
heading from actual signals. This gives display capacity of up to seven signals to one
Signal Panel. Additional pages are created when more than seven signals have been
configured. As with all other panels, switching between pages is carried out
automatically, after the parameter panel hold-time (LOC: H o l d - t i m e f o r P a n e l s )
has elapsed, or manually by pressing the ‘Up’/‘Down’ keys.
Each signal consists of two lines. The first line shows a status marker (square)
and the associated function group. The second line shows the full text for this signal.
Automatic activation
When automatic activation of the Signal Panel is set (L O C : A u t . a c t i v . S i g n . P a n e l )
each status change of signals, configured to a panel, is automatically switched from the
Bay Panel page or the Operation Panel/Event Panel (depending on the actual selection)
to the Signal Panel. Depending on the range of functions available in the device, the
displays of Overload Panels, Ground Fault Panels or Fault Panels have a higher priority
and will be shown when an event has occurred. Using the Page key will make the
display jump to the other panels at any time.
Each status change of signals, configured to a panel of the Bay Panel page can be set to
call for user attention either by having the status marker or both signal lines flash when a
new event has occurred. The switching control will then automatically switch to the
page, which includes the first signal that has experienced a status change. After
pressing the Selection key this flashing signal is selected on the current page (signal
preceded by a flashing cursor “>“). The next flashing signal can be called up by pressing
the Selection key again. At this point it may occur that the display will automatically
jump to the next page. When the last flashing signal has been reached pressing the
Selection key again will start with the first flashing signal.
Acknowledging flashing
signals
Acknowledging a flashing signal that has been selected will occur by pressing the
CLEAR key C . This will not reset illuminated LED indicators but will only acknowledge
the display. The flashing will stop when the CLEAR key is pressed and a static status
display will appear. Then the display will automatically jump to the next flashing signal.
This will enable the user to acknowledge any flashing signals by multiple pressing of the
CLEAR key. As long as the Selection key is pressed and no resetting has occurred
the current page will be continuously displayed (no automatic switching to the next
page). The selection will remain active until the time set in L O C : R e t u r n t i m e
s e l e c t has elapsed. When the time has elapsed the display will jump to the next page.
During an active selection the user may at any time jump to the next or the previous
page by pressing the 'up’ or 'down' keys (similar to the Measured Value Panel and the
Event Panel).
As long as at least one status change signal in the Signal Panel has not been
acknowledged, L O C : C h g . S i g . P a n e l s t a t . will show the status change of the
Signal Panel as a static signal. This signal is made available in the selection tables for
the function groups LED, OUTP, LOGIC, PC, COMM1 and COMM2.
Description Display
The Measured Value Panels are called up according to system conditions. If, for
example, the device detects an overload or a ground fault, then the corresponding
Measured Value Panel will be displayed as long as the overload or ground fault situation
exists. If the device detects a fault, then the Fault Panel is displayed and remains active
until the measured fault values are reset, by pressing the CLEAR key C , for example.
0 The uppermost line of the display shows the Meas. values 16:57:33
The Event Panel shows the signals relevant for operation, each with the complete time
tag (date and time of day). A maximum of three signals are displayed. The Event Panel
is based on entries in the operating data memory (menu tree: "Oper/Rec/OP_RC").
08:10:59.688 MAIN
Blocked/Faulty
End
Folders and
Function Groups
All data points are organized in different folders based on practical control requirements.
At the root of the menu tree is the unit type; the tree branches into the three main folders
‘Settings’, ‘Measurements & Tests’ and ‘Fault & Event Records’, which form the first
folder level. Up to two further folder levels follow so that the entire folder structure
consists of three main branches and a maximum of three folder levels.
At the end of each branch of folders are the various function groups in which the
individual data points (settings) are combined.
PX yyy
Unit
type
Oper/
Folder Cyclic measurements
plane 2
Oper/Cycl/
Folder Meas. operating data
plane 3
Oper/Cycl/Data/
Function MAIN
groups
Oper/Cycl/Data/MAIN
Data Date
points 01.01.99 dd.mm.yy
The display on the local control panel can be switched between address mode and plain
text mode. In the address mode the display shows settings, signals, and measured
values in numerically coded form, that is, as addresses. In plain text mode the settings,
signals, and measured values are displayed in the form of plain text descriptions. In
either case, control is guided by the menu tree. The active branch of the menu tree as
well as the display panel headers are displayed in plain text in both modes. Bay Panel
displays are also always in plain text. In the following examples, the display is shown in
plain text mode only.
Although it is possible to select any data point in the menu tree and read the associated value
by pressing the keys, it is not possible to switch directly to the input mode. This safeguard
prevents unintended changes in the settings.
This setup is designed to prevent accidental output and applies even when the global
change-enabling function has been activated. The following example is based on the factory-
set password. If the password has been changed by the user (see section 'Changing the
Password'), the following description will apply accordingly.
No
*
‘Right’ G
Oper/CtrlTest/LOC
Param. change enabl.
G
No
*
‘up’ G
Oper/CtrlTest/LOC
Param. change enabl.
G
No
*
‘down’. G
Oper/CtrlTest/LOC
The display will change as shown in the Param. change enabl.
G
G
Yes
G
The LED Oper/CtrlTest/LOC
Param. change enabl.
indicator will go out. The unit is enabled for Yes
further setting changes.
The same procedure applies to any setting change unless the global change-enabling
function has been activated. This method is recommended for a single setting change
only. If several settings are to be changed, then the global change-enabling function is
preferable. In the following examples, the global change-enabling function has been
activated.
Automatic return
The automatic return function prevents the change-enabling function from remaining
activated after a change of settings has been completed. Once the set return time (menu
tree ‘Par/Conf/LOC’) has elapsed, the change-enabling function is automatically
deactivated, and the display switches to a Measured Value Panel corresponding to the
current system condition. The return time is restarted when any of the control keys is
pressed.
Forced return
The return described above can be forced from the local control panel by either pressing
the Page key or by first pressing the ‘Up’ key and then holding it down and also pressing
the CLEAR key.
Note: It is important to press the ‘up’ key first and release it last in order to avoid
unintentional deletion of stored data.
Even when the change-enabling function is activated, not all settings can be changed.
With some settings it is additionally required that the device is switched to "offline" (Menu
tree: Par/Func/Glob/MAIN: Device on-line). Such settings include the configuration
settings, by means of which the device interfaces can be adapted to the system. The
following entries in the "Change" column of the address list (see appendix) indicate
whether values can be changed or not:
"on": The value can be changed when the device is switched to "on-line".
"off": The value can only be changed when the device is switched to "offline".
"-": The value can be read out but cannot be changed.
The device is delivered with the factory-setting to "offline".
If all the conditions for a value change are satisfied (see above), the desired setting can
be entered.
G
50000 s
50000 s
50010 s
meantime the device will continue to operate
with the old value.
Using list settings, the user is able to select several elements from a list in order to
perform tasks such as defining a trip command or defining the measurements that will be
displayed on Measured Value Panels. The maximum possible number ’m’ that can be
selected out of the total number ’n’ of the set is given in the address list in the ’Remarks’
column. As a rule, the selected elements are linked by an ‘OR’ operator. Other
operators (NOT, OR, AND, NOT OR and NOT AND) are available in the LOGIC function
group for linking the selected list items. In this way binary signals and binary input
signals can be processed in a Boolean equation tailored to meet user requirements. For
the DNP 3.0 communication protocol, the user defines the class of a setting instead of
assigning operators. The definition of a trip command shall be used here as an
illustration.
#01 DIST
and fourth lines, respectively. The symbol Trip zone 1
‘#01’ in the display indicates the first item of the
selection. If 'MAIN: Without function’ appears
as the first item, then this means that no
function assignment has yet been made.
OR #02 DIST
Trip zone 2
#02 DIST
mode. Trip zone 4
OR #02 DIST
only the ‘OR’ operator can be selected. There Trip zone 4
is no limitation on the selection of classes.
G
The LED indicator Par/Func/Glob/MAIN
Fct.assign.trip cmd.
will go out. The assignment has been made. OR #02 DIST
The unit will now operate with the new settings. Trip zone 4
G
C
8 If you wish to reject the new setting while Par/Func/Glob/MAIN
Fct.assign.trip cmd.
you are still entering it (LED indicator labeled OR #02 DIST
EDIT MODE is on), press the CLEAR key. The Trip zone 2
LED indicator labeled EDIT MODE will go out.
Memories can be read out after going to the corresponding entry point. This does not
necessitate activating the change-enabling function or even switching the device to
"offline". Inadvertent clearing of a memory at the entry point is not possible.
G
Enabled USER
No
Enabled USER
No
point.
G
Checksum error param
(Yes) or is no Reset: No
longer detected (No) by the self- Number: 5
monitoring function.
Reset: The fault was no longer detected by
the self-monitoring function and
has been reset (Yes).
Number: The signal occurred x times.
point.
G
Event
this example it is the 22nd fault since the last 22
reset.
Running time
signals in chronological order. The time shown 0.17 s
in the second line is the time, measured from
the onset of the fault, at which the value was
measured or the binary signal started or G
Fault recording 1
ended. 0 ms FT_RC
G
Record. in progress
Once the end of the fault has been reached Start
(after the ‘right’ key has been pressed
repeatedly), pressing the ‘right’ key again will
have no effect.
G
Fault recording 1
241 ms FT_RC
G
Record. in progress
End
Record. in progress
Start
01.01.99 10:00:33
6.5.7 Reset
All information memories – including the event memories and the monitoring signal
memory – as well as the LED indicators can be reset manually. In addition, the LED
indicators are automatically cleared and initialized at the onset of a new fault – provided
that the appropriate operating mode has been selected – so that they always indicate the
latest fault.
The LED indicators can also be reset manually by pressing the CLEAR key, which is
always possible in the standard control mode. This action also triggers an LED indicator
test and an LCD display test. The event memories are not affected by this action, so that
inadvertent deletion of the records associated with the reset signal pattern is reliably
prevented.
Because of the ring structure of the event memories, the data for eight consecutive
events are updated automatically so that manual resetting should not be necessary, in
principle. If the event memories need to be cleared completely, however, as would be
the case after injection testing, this can be done after selecting the appropriate setting.
The resetting procedure will now be illustrated using the fault memory as an example. In
this example the global change-enabling function has already been activated.
Oper/CtrlTest/FT_RC
setting to ‘Execute’.
G
Reset recording
10
Execute
Oper/CtrlTest/FT_RC
labeled EDIT MODE will go out. The value in Reset recording
line 3 is reset to ‘0’. 0
Some actions initiated from the local control panel (e.g. a manual trip command for
testing purposes) can only be carried out after entering a password, and only if the
global change-enabling function has been activated (see the section entitled 'Enabling
Parameter Changes'), so as to prevent any unwanted operations.
This setup is designed to prevent accidental output and applies even when the global
change-enabling function has been activated. The password consists of a pre-defined
sequential key combination entered within a specific time interval. If the password has
been changed by the user (see section 'Changing the Password'), the following
description will apply accordingly.
Don't execute
*
‘Right’ G
Oper/CtrlTest/MAIN
Man. trip cmd. USER
G
Don't execute
*
‘up’ G
Oper/CtrlTest/MAIN
Man. trip cmd. USER
G
Don't execute
*
‘down’. G
Oper/CtrlTest/MAIN
The display will change as shown in the Man. trip cmd USER
G
Execute
G
The LED Oper/CtrlTest/MAIN
Man. trip cmd. USER
indicator labeled EDIT MODE will go out. The Don't execute
unit will execute the command.
C
5 As long as the LED indicator labeled EDIT Oper/CtrlTest/MAIN
Man. trip cmd. USER
MODE is on, the control action can be Don't execute
terminated by pressing the CLEAR key. The
LED indicator labeled EDIT MODE will go out.
The password consists of a combination of keys that must be entered sequentially within
a specific time interval. The ‘left’, ’right’, ‘up’ and ‘down’ keys may be used to define the
password and represent the numbers 1, 2, 3 and 4, respectively:
3
G
1 2
G
The password can be changed by the user at any time. The procedure for this change is
described below. The starting point is the factory-set password.
G
Eight asterisks (*) Par/Conf/LOC
Password
appear in the fourth line of the display. ********
********
G
change as shown in the column on the right. ********
*
G
Par/Conf/LOC
Password
G
********
*
G
Par/Conf/LOC
Password
G
********
*
G
Par/Conf/LOC
Password
G
********
*
*
followed by the DOWN key.
G
Par/Conf/LOC
G
Password
**
G
**
*
G
Par/Conf/LOC
Password
G
**
**
G
If the Par/Conf/LOC
Password
password has been re-entered correctly, the ********
LED indicator labeled EDIT MODE goes out
and the display appears as shown on the right.
The new password is now valid.
Operation from the local control panel without password protection is also possible. To
select this option, immediately press the ENTER key a second time in steps 4 and 6
without entering anything else. This will configure the local control panel without
password protection, and no control actions involving changes will be possible until the
global change-enabling function has been activated (see section ‘Enabling Parameter
Changes’).
If the configured password has been forgotten, it can be called up on the LCD display as
described below. The procedure involves turning the device off and then on again.
G
TEST
directional keys (‘left’, ‘right’, ‘up’ and ‘down’) at
the same time and hold them down.
Password
startup, the password is displayed.
G
1234
G
********
display will change as shown in the column on *
the right.
G
Par/Conf/LOC
Password L/R
G
********
*
G
Par/Conf/LOC
Password L/R
G
********
*
G
Par/Conf/LOC
Password L/R
G
********
*
*
followed by the DOWN key.
G
Par/Conf/LOC
G
Password L/R
**
G
**
*
G
Par/Conf/LOC
G
Password L/R
**
**
G
If the new Par/Conf/LOC
Password L/R
Password L/R has been re-entered correctly, ********
the red LED indicator labeled EDIT MODE will
be extinguished and the display appears as
shown on the right. The new Password L/R is
now valid.
7 Settings
7.1 Parameter
The P139 must be adjusted to the system and to the protected equipment by appropriate
settings. This chapter gives instructions for determining the settings, which are located
in the folder titled ‘Parameters’ in the menu tree. The sequence in which the settings are
listed and described in this chapter corresponds to their sequence in the menu tree.
The 'Address List' in the Appendix lists all parameters, along with setting ranges and step
sizes or selection tables.
The units are supplied with a factory-set configuration of settings that in most cases
correspond to the default settings given in the Address List. If the factory settings differ
from the default settings, then this is indicated below at the appropriate points.
The default settings given in the Address List are activated after a cold restart.
The P139 is blocked in that case. All settings must be re-entered after a cold restart.
Note:
In the following tables (except for function group DVICE) an indication for the localization
of the corresponding function description is shown in the right hand side column.
"Figure: 3-xxx" refers to a logic diagram which displays the address, "Figure*: 3-xxx" to a
figure subtitle or accompanying text, "Page: 3-xxx" to a page.
The device identification settings are used to record the ordering information and the
design version of the P139. They have no effect on the device functions. These settings
should only be changed if the design version of the P139 is modified.
Identification of the change level of the texts of the data model. This display
cannot be altered.
DVICE: Text vers.data model 002 121
Using the ‘text replacement tool’ provided by the operating program, the
user can change the parameter descriptors (plain text designations) and
load them into the device. These customized data models contain an
identifier defined by the user while preparing the data model. This identifier
is displayed at this point in the menu tree. Standard data models have the
identifier ‘0’ (factory-set default).
DVICE: F number 002 124
The F number is the serial number of the device. This display cannot be
altered.
DVICE: AFS Order No. 001 000
Order numbers for the device. The user cannot alter this number.
Index letter specifying the version of the module fitted in the respective slot.
DVICE: Variant of module A 086 047
MAC address for the network hardware of the Ethernet module. This
address is introduced during manufacture and can only be read.
DVICE: Variant of module L 086 048
Set your numerically coded user data here for your records.
DVICE: Location 001 201
When set to 'Yes' it is apparent that the device is fitted with the local control
panel (HMI).
The password to be used for changing settings from the local control panel
can be defined here. Further information on changing the password is
given in Chapter 6.
LOC: Password L/R 221 040
The password used to change the setting from 'Remote' to 'Local' control
can be defined here. (Switching from 'Local' to 'Remote'control occurs
without checking the password.)
LOC: Displ. ext.dev.desig 221 032 Fig. 3-2
This setting defines whether the control site – 'Local' or 'Remote' – shall be
displayed on the bay panel.
LOC: Displ. interl. stat. 221 071 Fig. 3-2
Note:
Character set 3 is identical to character set 1 in the factory default setting,
but can be replaced by an user-defined character set, by applying an
accessory tool to the operating program.
Selection of specified counters or event logs that are reset by pressing the
RESET key on the local control panel.
LOC: Fct. read key 080 110
Selection of the event log that will be displayed when the READ key is
pressed.
LOC: Fct. menu jmp list 1 030 238
Note:
Measured values to be displayed in bar chart form must also be selected for
display as numerical measured values. However, not all measured values
that can be displayed in numerical form can also be displayed in bar chart
form! In such cases, a dummy or placeholder must be included in the
selection list for the bar chart display at the same point at which a measured
value that cannot be displayed in bar chart form appears in the selection list
for numerical measured values.
Example:
Deactivation of the bar chart display or definition of the orientation of the bar
chart to display measured values on the Bay Panel.
LOC: Scal. bar display I 221 044 Fig. 3-2
Setting for the time period during which a panel is displayed, before the unit
switches to the next panel. This setting is only relevant if more values are
selected than can be shown on the LC-Display.
LOC: Autom. return time 003 014 Fig. 3-4
If the user does not press a key on the local control panel during this set
time period, the change-enabling function is deactivated.
LOC: Return time select. 221 030 Fig. 3-2
If the user does not press a key on the local control panel during this set
time period, then the selection of a switchgear unit is cancelled.
LOC: Return time illumin. 003 023
If the user does not press a key on the local control panel during this set
time period, then the backlighting of the LCD display is switched off, and
any switchgear selection that might have been made is cancelled.
Set the same parity that is set at the interface of the PC connected to the
P139.
PC: Spontan. sig. enable 003 187 Fig. 3-9
Enable for the cyclic transmission of measured values via the PC interface.
PC: Cycl. data ILS tel. 003 185 Fig. 3-9
The active power value is transmitted via the PC interface if it differs by the
set delta quantity from the last measured value transmitted.
PC: Delta f 003 057 Fig. 3-9
All measured values are transmitted again via the PC interface after this
time period has elapsed – provided that transmission has not been triggered
by the other delta conditions.
PC: Time-out 003 188 Fig. 3-9
Setting for the time to elapse after the last telegram exchange via the PC
interface before activating the second communication channel of
communication module B.
Enabling additional settings that are relevant for the protocol based on
IEC 870-5-101.
COMM1: Addit. ILS enable 003 217 Fig. 3-10
Enabling additional settings that are relevant for the ILS protocol.
COMM1: MODBUS enable 003 220 Fig. 3-10
Select the communication protocol that shall be used for the communication
interface.
COMM1: -103 prot. variant 003 178 Fig. 3-11
In the DNP 3.0 protocol, a 16-bit address is used to identify devices. The
address that can be set here is the higher-order octet, whereas the address
set at C OMM1 : Oc te t co mm. addr ess is the lower-order octet of the
DNP address.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Test monitor on 003 166 Fig: 3-11,
3-12, 3-13,
3-14, 3-15,
3-16
Setting specifying whether data shall be recorded for service activities.
Setting for the length of the common higher-order address for identification
of telegram structures.
Note:
This setting is hidden unless the IEC 870-5-101 protocol is enabled.
"ASDU": Application Service Data Unit
COMM1: Addr.length inf.obj. 003 196 Fig. 3-12
Setting for the transmission direction. Normally this value will be set to '1' at
the control center and to '0' at the substation.
Note: This setting is hidden unless the IEC 870-5-101 protocol is
enabled.
COMM1: Time-out interval 003 228 Fig. 3-12
Setting the maximum time that will elapse until the status signal for the
acknowledgment command is issued.
Note: This setting is hidden unless the IEC 870-5-101 protocol is
enabled.
COMM1: Reg.asg. selec. cmds 003 210 Fig. 3-14
Number of bits that must pass between the receipt of the 'request' and the
start of sending the 'response'.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Phys. Char. Timeout 003 242 Fig. 3-15
Number of bits that may be missing from the telegram before receipt is
terminated.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Link Confirm. Mode 003 243 Fig. 3-15
Setting the time period within which the master must acknowledge at the
link layer.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Link Max. Retries 003 245 Fig. 3-15
Number of repetitions that are carried out on the link layer if errors have
occurred during transmission (such as failure to acknowledge).
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Appl.Confirm.Timeout 003 246 Fig. 3-15
Setting the time period within which the master must acknowledge at the
application layer.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
Time interval within which the slave cyclically requests time synchronization
from the master.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Ind./cl. bin. inputs 003 232 Fig. 3-15
Selection of data points and data classes for object 1 – binary inputs.
Assignment of indexes is made in the order of selection, beginning with 0.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Ind./cl. bin.outputs 003 233 Fig. 3-15
Selection of data points and data classes for object 10 – binary outputs.
Assignment of indexes is made in the order of selection, beginning with 0.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Ind./cl. bin. count. 003 234 Fig. 3-15
Selection of data points and data classes for object 20 – binary counters.
Assignment of indices is made in the order of selection, beginning with 0.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Ind./cl. analog inp. 003 235 Fig. 3-15
Selection of data points and data classes for object 30 – analog inputs.
Assignment of indices is made in the order of selection, beginning with 0.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Ind./cl. analog outp 003 236 Fig. 3-15
Selection of data points and data classes for object 40 – analog outputs.
Assignment of indexes is made in the order of selection, beginning with 0.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Delta meas.v. (DNP3) 003 250 Fig. 3-15
Cycle time at the conclusion of which the selected measured values are
again transmitted.
Note: This setting is hidden unless the Courier protocol is enabled.
Set the same parity that is set at the interface of the control system
connected to the P139.
COMM2: Dead time monitoring 103 176 Fig. 3-18
The time between two polling calls from the communication master must be
less than the time set here.
COMM2: Positive ackn. fault 103 203
The communication address and the ASDU address are used to identify the
device in communication via the interface. An identical setting must be
selected for both addresses.
"ASDU": Application Service Data Unit
COMM2: Name of manufacturer 103 161 Fig. 3-18
The communication address and the ASDU address are used to identify the
device in communication via the interface. An identical setting must be
selected for both addresses.
"ASDU": Application Service Data Unit
COMM2: Spontan. sig. enable 103 177 Fig. 3-18
All measured values are transmitted again via the communication interface
after this time period has elapsed – provided that transmission has not been
triggered by the other delta conditions.
Adjustment of the baud rate for telegram transmission via the teleprotection
interface (InterMiCOM interface) so as to meet the requirements of the
transmission carrier.
COMM3: Source address 120 031 Page: 3-26
This timer triggers the alarm signals CO MM 3 : Com mu nic a ti ons fau l t
and SFM ON : Co mm un ic .fa ul t CO MM 3 and sets the received signals
to their user-defined default values. Time-out occurs when the set time has
elapsed since the most recent 100% valid telegram was received.
COMM3: Sig.asg. comm.fault 120 034 Page: 3-28
Using this setting, the alarm signal can be configured (assigned) to the
corresponding PSIG input signal.
COMM3: Time-out link fail. 120 035 Fig. 3-21
Name of the device (IED has server function). This device name serves as
device identification in the IEC 61850 system, it is included in the Logical
Device Name in the IEC data model and must therefore be unambiguous.
All devices logged-on to the network should have non-recurring IED names.
IEC: TCP keep-alive timer 104 062
The subnet mask defines which part of the IP address is addressed by the
sub-network and which part by the device that is logged-on to the network.
Note:
In the S&R 103 operating program, the complete IP address is displayed at
IEC : Sub net m ask . The device’s front panel display only displays the IP
address distributed to these four data model addresses.
Device (IED) poll cycle time for time synchronization when operating mode
is set to Request from Server.
IEC: SNTP server 1 IP 104 202
Time difference between UTC and local time at the devices' substation
(IED).
IEC: Diff. dayl.sav. time 104 207
These three parameters define the date (e.g. at what day of the year) for
switching from standard time over to daylight saving time. Available for
I E C : D a y l . s a v . t i m e s t a r t are the values 'first', 'second', 'third',
'fourth', and 'last'. For I E C : D a y l . s a v . t i m e s t . d the seven weekdays
are available so that for example a setting like "on the last Sunday in March"
may be used.
IEC: Dayl.sav.t.st.0:00 + 104 223
This defines the time difference and the time of day (on the specific
changeover day) when the clock is to be switched to daylight saving time.
The time is given in the number of minutes after midnight, e.g. when the
clock changeover to 3:00 AM always occurs at 2:00 AM, then the value to
be entered at I E C : D a y l . s a v . t . s t . 0 : 0 0 + is 120 [minutes] and at
I E C : D i f f . d a y l . s a v . t i m e it is 60 [minutes].
IEC: Dayl.sav.time end 104 225
This parameter defines the date and time of day for the clock changeover
from daylight saving time to standard time. The setting is similar to that for
the clock changeover to daylight saving time.
IEC: Update Measurements 104 229
Setting to calculate the filter value for all IP Report Control Blocks (RCB).
Should a change occur in one of the IP measured values, which is greater
than the filter value, the RCB is again sent to all clients. The filter value for
each measured value is calculated according to this formula:
step size measured value • s e t ti n g I EC : D e a d b a n d I P
IEC: Dead band IN 104 231
Setting to calculate the filter value for all IN Report Control Blocks (RCB).
Should a change occur in one of the IN measured values, which is greater
than the filter value, the RCB is again sent to all clients. The filter value for
each measured value is calculated according to this formula:
step size measured value • s e t ti n g I EC : D e a d b a n d IN
IEC: Dead band VPP 104 232
Setting to calculate the filter value for all VPP Report Control Blocks (RCB).
Should a change occur in one of the VPP measured values, which is
greater than the filter value, the RCB is again sent to all clients. The filter
value for each measured value is calculated according to this formula:
step size measured value • s e t ti n g I EC : D e a d b a n d VP P
IEC: Dead band VPG 104 233
Setting to calculate the filter value for all VPG Report Control Blocks (RCB).
Should a change occur in one of the VPG measured values, which is
greater than the filter value, the RCB is again sent to all clients. The filter
value for each measured value is calculated according to this formula:
step size measured value • s e tti ng IEC : Dead band VPG
Setting to calculate the filter value for all f Report Control Blocks (RCB).
Should a change occur in one of the f measured values, which is greater
than the filter value, the RCB is again sent to all clients. The filter value for
each measured value is calculated according to this formula:
step size measured value • s e t ti n g I EC : D e a d b a n d f
IEC: Dead band P 104 235
Setting to calculate the filter value for all P Report Control Blocks (RCB).
Should a change occur in one of the P measured values, which is greater
than the filter value, the RCB is again sent to all clients. The filter value for
each measured value is calculated according to this formula:
step size measured value • s e t ti n g I EC : D e a d b a n d P
IEC: Dead band phi 104 236
Setting to calculate the filter value for all φ Report Control Blocks (RCB).
Should a change occur in one of the φ measured values, which is greater
than the filter value, the RCB is again sent to all clients. The filter value for
each measured value is calculated according to this formula:
step size measured value • s e t ti ng I EC : D ea d ba nd p hi
IEC: Dead band Z 104 237
Setting to calculate the filter value for all Z Report Control Blocks (RCB).
Should a change occur in one of the Z measured values, which is greater
than the filter value, the RCB is again sent to all clients. The filter value for
each measured value is calculated according to this formula:
step size measured value • s e t ti n g I EC : D e a d b a n d Z
IEC: Dead band min/max 104 238
Setting to calculate the filter value for all min/max Report Control Blocks
(RCB). Should a change occur in one of the min/max measured values,
which is greater than the filter value, the RCB is again sent to all clients.
The filter value for each measured value is calculated according to this
formula:
step size measured value • s e t ti ng I EC : D ea d ba nd min / ma x
IEC: Dead band ASC 104 239
Setting to calculate the filter value for all ASC Report Control Blocks (RCB).
Should a change occur in one of the ASC measured values, which is
greater than the filter value, the RCB is again sent to all clients. The filter
value for each measured value is calculated according to this formula:
step size measured value • s e t ti n g I EC : D e a d b a n d ASC
IEC: Dead band temp. 104 240
Setting to calculate the filter value for all temperature Report Control Blocks
(RCB). Should a change occur in one of the temperature measured values,
which is greater than the filter value, the RCB is again sent to all clients.
The filter value for each measured value is calculated according to this
formula:
step size measured value • s e t ti n g I EC : D e a d b a n d tem p .
IEC: Dead band 20mA 104 241
Setting to calculate the filter value for all 20mA Report Control Blocks
(RCB). Should a change occur in one of the 20mA measured values, which
is greater than the filter value, the RCB is again sent to all clients. The filter
value for each measured value is calculated according to this formula:
step size measured value • s e t ti ng I EC : D ea d ba nd 2 0m A
Cycle time to send energy value by Report Control Block (RCB). No RCB
transmission with setting to blocked!
IEC: DEV control model 221 081
Generic Object Oriented GOOSE: Function group GOOSE 056 068 Page: 3-35
Substation Event
Cancelling function group GOOSE or including it in the configuration.
If the function group is cancelled from the configuration, then all associated
settings and signals are hidden. The parameters of this function group are
only active if function group IEC has been configured and is activated, and if
the parameters of this function group have been activated through the
parameter I E C : E n a b l e c o n f i g u r a t i o n or by switching the device
off-line/on-line.
GOOSE: General enable USER 106 001 Page: 3-35
Goose ID being sent by this device (IED). GOOSE includes a Dataset with
32 binary and configurable virtual outputs and 10 two-pole states to the
maximum of 10 monitored external devices
GOOSE: VLAN Identifier 106 006 Fig. 3-22
VLAN identifier of GOOSE being sent by this device (IED). The VLAN
identifier makes it possible to have switches in the network filter messages,
if the switches support such a function. Because so-called multicast MAC
addresses are applied, switches are unable to filter messages in the
network if they do not include a VLAN identifier.
GOOSE: VLAN Priority 106 007 Fig. 3-22
Goose ID for GOOSE, which is to be received by this device (IED) for the
virtual binary GOOSE input.
Default for the virtual binary GOOSE input. The state of a virtual two-pole
GOOSE input will revert to default as soon as the continuously monitored
communication link to a GOOSE sending device (IED situated on the
opposite side) is in fault or has disappeared altogether.
Goose ID for GOOSE, which is to be received by this device (IED) for the
virtual two-pole GOOSE input, representing the state of an external device.
Virtual GOOSE inputs can be linked with interlocking equations of assigned
external devices.
GOOSE: Ext.Dev01 DataSetRef 108 002
Default for the virtual two-pole GOOSE input, representing the state of an
external device. The state of a virtual two-pole GOOSE input will revert to
default as soon as the continuously monitored communication link to a
GOOSE sending device (IED situated on the opposite side) is in fault or has
disappeared altogether.
IEC Generic Substation GSSE: Function group GSSE 056 060 Page: 3-38
Status Events
Cancelling function group GSSC or including it in the configuration.
If the function group is cancelled from the configuration, then all associated
settings and signals are hidden. The parameters of this function group are
only active if function group IEC has been configured and is activated, and if
the parameters of this function group have been activated through the
parameter I E C : E n a b l e c o n f i g u r a t i o n or by switching the device
off-line/on-line.
GSSE: General enable USER 104 049 Page: 3-38
Minimum value for the GSSE repetition cycle time in ms. The repetition
cycle time for a GSSE message is calculated, according to a standard, with
this formula:
Repetition cycle time = Min. cycle + (1 + (increment/1000))N-1 [ms]
The repetitions counter N will be restarted at count 1 after each state
change of a GSSE bit pair.
GSSE: Max. cycle 104 053
Maximum value for the GSSE repetition cycle time in s. For the formula to
calculate the repetition cycle time see Min. cycle. Should the calculated
value for the repetition cycle time be equal to or greater than the set max.
value then the GSSE message will be sent repeatedly at the set max. value
time.
GSSE: Increment 104 054
Increment for the GSSE repetition cycle. For the formula to calculate the
repetition cycle time see Min. cycle.
GSSE: Operating mode 104 055
Setting with which GSSE bit pair the configured binary signal of the virtual
GSSE outputs is to be transmitted. A GSSE is always transmitted
consisting of a fixed number of 96 bit pairs, of which a maximum of 32 are
used by this device (IED) during a send operation.
Setting which GSSE bit pair is assigned to which virtual GSSE input. A
GSSE is always received consisting of a fixed number of 96 bit pairs, of
which a maximum of 32 are processed by this device (IED).
IED name for the virtual GSSE input used to identify a GSSE received.
Default for the virtual binary GSSE input. The state of a virtual two-pole
GSSE input will revert to default as soon as the continuously monitored
communication link to a GSSE sending device (IED situated on the opposite
side) is in fault or has disappeared altogether.
Binary input
The P139 has optical coupler inputs for processing binary signals from the system. The
number and connection schemes for the available binary inputs are shown in the
terminal connection diagrams. The Address List in the Appendix gives information about
the configuration options for all binary inputs.
The P139 identifies the installed modules during startup. If a given binary I/O module is
not installed or has fewer binary signal inputs than the maximum number possible at this
slot, then the configuration addresses for the missing binary signal inputs are
automatically hidden in the menu tree.
When configuring binary inputs, one should keep in mind that the same function can be
assigned to several signal inputs. Thus one function can be activated from several
control points having different signal voltages.
The configuration in slots A and B and the configuration for the binary inputs U C01 to
U C08 will be changed with the selection of a new bay type. (Whether automatic
configuration occurs, is defined in the setting M A I N : A u t o - a s s i g n m e n t I / O .)
Depending on the connection type chosen for the P139 – pin type or ring type cable
socket terminals – the symbolic slots A, B and C refer to the following slots:
Symbolic slot Pin type cable socket Ring type cable socket
terminals terminals
a 06 12
BSb 07 14
BSc 08 16
The configuration of binary inputs for each bay type – in the case of auto-assignment – is
given in the List of Bay Types in the Appendix.
Note: Before selecting a new bay type, make sure that the binary inputs at slots A
and B as well as the binary inputs U C01 to U C08 are configured for
functions from the DEVxx function groups only. Otherwise there will be an
error message, and the new bay type will not be activated.
Note: Before selecting a new bay type, make sure that all binary inputs specified in
the List of Bay types for the selected bay type are actually available in the
device. Otherwise there will be an error message, and the new bay type will
not be activated.
In order to ensure that the device will recognize the input signals, the triggering signals
must persist for at least 30 ms.
The operating mode for each binary signal input can be defined. The user can specify
whether the presence (active ‘high’ mode) or absence (active ‘low’ mode) of a voltage
shall be interpreted as the logic ‘1’ signal.
Input filter which is activated when either the mode "active ‘high’, filtered" or
active ‘low’, filtered" has been selected. In order to suppress transient
interference peaks at the logic signal inputs it is suggested to set this
parameter to 6 [steps]. For further information see Chapter 3.
INP: Fct. assignm. U 301 152 217 Fig: 3-24,
3-255, 3-258,
3-259
INP: Fct. assignm. U 302 152 220
Setting the minimum current that must flow in order for the P139 to display a
measured value > 0 (zero suppression).
MEASI: IDC< open circuit 037 191 Fig. 3-28
If the input current falls below the set threshold, the P139 will issue an ‘open
circuit’ signal.
MEASI: IDC 1 037 150 Fig. 3-28
Setting for the input current that will correspond to a linearized value that
has been set accordingly.
Setting for the linearized current that will correspond to an input current that
has been set accordingly.
MEASI: Scaled val. IDC,lin1 037 192 Fig. 3-29
Binary outputs
The P139 has output relays for the output of binary signals. The number and connection
schemes for the available output relays are shown in the terminal connection diagrams.
The Address List in the Appendix gives information about the configuration options for all
binary outputs.
The P139 identifies the installed modules during startup. If a given binary I/O module is
not installed or has fewer output relays than the maximum number possible at that slot,
then the configuration addresses for the missing output relays are automatically hidden
in the menu tree.
The contact data for the all-or-nothing relays permits them to be used either as
command relays or as signal relays. It is important to note that the contact rating of the
binary I/O modules (X) varies (see Chapter 'Technical Data'). One signal can also be
assigned simultaneously to several output relays for the purpose of contact
multiplication.
Selecting a new bay type can change the configuration for slots A and B! (Whether
automatic configuration occurs, is defined in the setting M A I N : A u t o - a s s i g n m e n t
I / O .) Depending on the connection type chosen for the P139 – pin type or ring type
cable socket terminals – the symbolic slots A and B correspond to the following slots:
Symbolic slot Pin type cable socket Ring type cable socket
terminals terminals
a 06 12
BSb 07 14
The configuration of output relays for each bay type – in the case of auto-assignment – is
given in the List of Bay Types in the Appendix.
Note: Before selecting a new bay type, make sure that the output relays at slots A
and B are configured for functions from the DEVxx function groups only.
Otherwise there will be an error message, and the new bay type will not be
activated.
Note: Before selecting a new bay type, make sure that the output relays of slots A
and B are configured for functions from the DEVxx function groups only.
Otherwise there will be an error message, and the new bay type will not be
activated.
An operating mode can be defined for each output relay. Depending on the selected
operating mode, the output relay will operate in either an energize-on-signal (ES) mode
or a normally-energized (NE) mode and in either a latching or non-latching mode. For
output relays operating in latching mode, the operating mode setting also determines
when latching will be cancelled.
Setting the time period for transmission of the selected measured value in
BCD form.
MEASO: Scaled min. val. BCD 037 140 Fig. 3-39
MEASO: Scaled max. val. BCD 037 141 Fig. 3-39
MEASO: BCD-Out min. value 037 142 Fig. 3-39
MEASO: BCD-Out max. value 037 143 Fig. 3-39
Setting the time period for output of the selected measured value.
Measurands Range
Measurands of the
variable Mx Mx,RL1 ... Mx,RL2
Associated scaled measurands 0 ... 1
with:
Mx,min. ... Mx,max. : measured values to be issued
MEASO: Output value 1 037 120 Fig. 3-41
LED indicators
The P139 has a total of 23 LED indicators (for the case 40T and case 84T devices) for
parallel display of binary signals. The case 24T device variant is fitted 10 LED
indicators. LED indicator H 1 is not configurable. It is labeled "HEALTHY" and signals
the operational readiness of the protection unit (supply voltage present). LED indicators
H 2 and H 3 are not configurable either. H 2 is labeled "OUT OF SERVICE" and signals
a blocking or malfunction; H 3 is labeled "ALARM" and signals a warning alarm.
LED indicator H 17 indicates that the user is in the "EDIT MODE".
Section 6.1 describes the layout of the LED indicators and the factory setting for LED
indicator H 4. At this point it is specifically emphasized that for the case 40T and case
84T devices there is no permanent association between the freely configurable function
keys and the LED indicators H 18 to H 23 situated directly next to these function keys.
An operating mode can be defined for each LED indicator. Depending on the set
operating mode, the LED indicator will operate in either energize-on-signal (ES) mode
('open-circuit principle') or normally-energized (NE) mode ('closed-circuit principle') and
in either latching or non-latching mode. For LED indicators operating in latching mode,
the operating mode setting also determines when latching will be cancelled.
With the multi-color LED indicators (H 4 – H 16, H 18 – H 23 on the case 40T and case
84T devices) the colors red and green can be independently assigned with functions.
The third color amber results as a mixture of red and green, i.e. when both functions
assigned to the LED indicator are simultaneously present.
If a user-specific (customized) bay type has been loaded, its bay type No.
will be displayed. If no customized bay type has been loaded, the number '0'
will be displayed.
MAIN: Prim.Source TimeSync 103 210 Fig.*: 3-84
Selection of the primary source for date and time synchronization. Available
are COMM1, COMM2/PC, IRIG-B or a binary input for minute signal pulses.
MAIN: BackupSourceTimeSync 103 211 Fig.*: 3-84
Selection of the backup source for date and time synchronization. Available
are COMM1, COMM2/PC, IRIG-B or a binary input for minute signal pulses.
The backup source is used when there is no synchronization generated by
the primary source after M AIN : Ti me s ync . ti me -ou t has elapsed.
MAIN: Time sync. time-out 103 212 Fig.*: 3-84
Fault recording FT_RC: Rec. analog chann. 1 035 160 Fig.*: 3-126
The user specifies the channel on which each physical variable is recorded.
The figure shown illustrates an overview of the assignment.
Cancelling a protection
or control function
The user can adapt the device to the requirements of a particular high-voltage system by
including the relevant protection or control functions in the device configuration and
cancelling all others (removing them from the device configuration).
The following conditions must be met before cancelling a protection or control function:
None of the signals of the protection or control function may be linked to other signals
by way of an ‘m out of n’ parameter.
protection
Cancelling function group DTOC or including it in the configuration.
If the function group is cancelled from the configuration, then all associated
settings and signals are hidden.
protection 1
Cancelling function group IDMT1 or including it in the configuration.
If the function group is cancelled from the configuration, then all associated
settings and signals are hidden, with the exception of this setting.
protection 2
Cancelling function group IDMT2 or including it in the configuration.
If the function group is cancelled from the configuration, then all associated
settings and signals are hidden, with the exception of this setting.
determination
Cancelling function group SCDD or including it in the configuration.
If any function group is cancelled from the configuration, then all associated
settings and signals are hidden.
determination using
steady-state values
Cancelling function group GFDSS or including it in the configuration.
If the function group is cancelled from the configuration, then all associated
settings and signals are hidden.
direction determination
Cancelling function group TGFD or including it in the configuration.
If any function group is cancelled from the configuration, then all associated
settings and signals are hidden.
protection
Cancelling function group f<> or including it in the configuration.
If the function group is cancelled from the configuration, then all associated
settings and signals are hidden.
protection
Cancelling function group CBF or including it in the configuration.
If the function group is cancelled from the configuration, then all associated
settings and signals are hidden, with the exception of this setting.
Note:
If the IEC 870-5-101 communication protocol has been set, then the 'low
address' of the information object will be defined by this setting. If the ILS-C
protocol has been set, then this setting will correspond to DN2.
DEV01: Inform. No., signal 210 035
Note:
If the IEC 870-5-101 communication protocol has been set, then the 'high
address' of the information object will be defined by this setting. If the ILS-C
protocol has been set, then this setting will correspond to DN3.
DEV01: Funct. type, command 210 032
Note:
If the IEC 870-5-101 communication protocol has been set, then the 'low
address' of the information object will be defined by this setting. If the ILS-C
protocol has been set, then this setting will correspond to DN2.
Note:
If the IEC 870-5-101 communication protocol has been set, then the 'high
address' of the information object will be defined by this setting. If the ILS-C
protocol has been set, then this setting will correspond to DN3.
7.1.3.1 Global
Communication interface 1 COMM1: Command block. USER 003 172 Fig. 3-10
Communication interface 2 COMM2: Command block. USER 103 172 Fig. 3-18
Switching the device off-line or on-line. Parameters marked 'No (=off)' in the
Address List can only be changed when protection is disabled.
MAIN: Test mode USER 003 012 Fig. 3-88
When the test mode user is activated, signals or measured data for PC and
communication interfaces are labeled 'test mode'.
MAIN: Nominal frequ. fnom 010 030 Fig. 3-240
For bay control function signals detected via binary signal inputs and
conditioned with debouncing it is now possible to select whether the time
tag for the signal is to be issued after debouncing or when the first pulse
edge is detected. Furthermore it is defined whether entries in the operating
data memory are made in chronological order or not.
MAIN: Inom C.T. prim. 010 001 Fig: 3-48,
3-111, 3-270
Setting for the primary nominal current of the main current transformers for
measurement of phase currents.
MAIN: IN,nom C.T. prim. 010 018 Fig. 3-50
Setting for the primary nominal current of the main current transformer for
measurement of residual current.
MAIN: Vnom V.T. prim. 010 002 Fig: 3-53,
3-111
Setting for the primary nominal voltage of the system transformer for
measurement of phase-to-ground and phase-to-phase voltages.
MAIN: VNG,nom V.T. prim. 010 027 Fig. 3-54
Setting for the primary nominal voltage of the system transformer for
measurement of neutral-point displacement voltage.
MAIN: Vref,nom V.T. prim. 010 100 Fig. 3-55
Setting for the primary nominal voltage of the system transformer for
measurement of reference voltage for automatic synchronism check.
MAIN: Inom prim. NCIT 010 037
Setting the primary nominal current of the NCIT for measurement of residual
current.
MAIN: Vnom prim. NCIT 010 038
Setting the primary nominal voltage of the NCIT for measurement of phase-
to-ground and phase-to-phase voltages.
MAIN: Ph. err. VAG,1 NCIT 010 180
Setting the phase error of the system transformer for each phase-to-ground
voltage in voltage measuring channel 1 of the NCIT.
MAIN: Ph. err. VAG,2 NCIT 010 192
Setting the phase error of the system transformer for each phase-to-ground
voltage (or for the reference voltage Vref, with ASC activated) in voltage
measuring channel 2 of the NCIT.
MAIN: Channel select. NCIT 010 187
Setting for the secondary nominal current of the system transformer for
measurement of phase currents. This also corresponds to the nominal
device current.
MAIN: IN,nom device 010 026 Fig. 3-47
Setting for the secondary nominal current of the system transformer for
measurement of residual current. This also corresponds to the nominal
device current.
MAIN: Vnom V.T. sec. 010 009 Fig. 3-47
Setting for the secondary nominal voltage of the system transformer for
measurement of phase-to-ground and phase-to-phase voltages.
MAIN: VNG,nom V.T. sec. 010 028 Fig. 3-47
Setting for the secondary nominal voltage of the system transformer for
measurement of neutral-point displacement voltage.
MAIN: Vref,nom V.T. sec. 031 052 Fig. 3-47
Setting for the secondary nominal voltage of the system transformer for
measurement of reference voltage for automatic synchronism check.
MAIN: Conn. meas. circ. IP 010 004 Fig. 3-47
This parameter allows inverting the sign for the following measured
operating values:
MAIN: Active power P prim. (004 050)
MAIN: Reac. power Q prim. (004 052)
MAIN: Active power P p.u. (004 051)
MAIN: Reac. power Q p.u. (004 053)
MAIN: Meas. value rel. IP 011 030 Fig. 3-48
Setting the minimum current that must be exceeded so that the measured
operating value of the residual current is displayed.
Setting the minimum voltage that must be exceeded so that the measured
operating value of the neutral-point displacement voltage is displayed.
MAIN: Meas. val. rel. Vref 011 034 Fig. 3-55
Setting the minimum voltage that must be exceeded so that the measured
operating value of the reference voltage for the automatic synchronism
check is displayed.
MAIN: Op. mode energy cnt. 010 138
Setting for the time after which the delayed maximum current display shall
reach 95% of the maximum current IP,max.
MAIN: Fct.assign. reset 1 005 248 Fig. 3-86
Definition of the binary signal used by the P139 to evaluate the 'CB open'
position signal.
MAIN: Sig. asg. CB closed 021 020 Fig. 3-68
Definition of the binary signal used by the P139 to evaluate the 'CB closed'
position signal.
MAIN: Debounce time gr. 1 221 200 Fig. 3-43
MAIN: Debounce time gr. 2 221 203
Setting the number of signal changes allowed during the chatter monitoring
time before chatter suppression operates.
MAIN: Cmd. dur.long cmd. 221 230 Fig: 3-301,
3-309
Setting the command duration for a long command.
MAIN: Cmd. dur. short cmd. 221 231 Fig: 3-301,
3-309
Setting the command duration for a short command.
MAIN: Electrical control 221 061 Fig. 3-297
This setting determines whether the binary inputs, that are configured to
control switchgear, will be active with remote control or local control
After the delay time period, to be set in this window, has elapsed (with the
signal "Sw. dev. interm. pos." already present and the status signal
continuously absent), the actual switchgear status signal, as obtained from
the respective binary inputs, will be issued. (See also "Processing status
signals from manually operated switchgear")
MAIN: W. ext. cmd. termin. 221 063 Page: 3-416
Definition of the binary signal used to switch from remote control to local
control.
MAIN: Auto-assignment I/O 221 065 Fig. 3-46
When a bay type is selected the binary inputs and outputs, required to
control switchgear, are automatically configured with function assignments.
MAIN: Inp.assign. tripping 221 010 Fig. 3-79
Selection of the protection function trip command that will be used to form
the CB trip signal.
MAIN: Inp. asg. CB trip 221 013 Fig. 3-79
Definition of the binary signal used by the P139 to signal the 'CB open'
position signal.
MAIN: Inp.asg.CB tr.en.ext 221 050 Fig. 3-79
Definition of the binary signal used to carry the CB trip signal of an external
device.
MAIN: Inp.asg. mult.sig. 1 221 051 Fig. 3-70
Parameter subset selection PSS: Control via USER 003 100 Fig. 3-89
The setting of this timer stage is relevant only if parameter subset selection
is carried out via binary signal inputs. Any voltage-free pause that may
occur during selection is bridged. If, after this time period has elapsed, no
binary signal input has yet been set, then the parameter subset selected
from the local control panel shall apply.
Fault data acquisition FT_DA: Line length 010 005 Fig. 3-112
This setting defines the distance in km that the fault locator interprets as
100 % when calculating the line distance to a fault.
FT_DA: Line reactance 010 012 Fig. 3-112
This setting defines the reactance X that the fault locator interprets as
100 % when calculating the line distance to a fault.
FT_DA: Angle kG 012 036 Fig. 3-109
Z0 − Z L
kG =
3⋅ Z L
Z 0 : zero-sequence impedance
Z L : positive-sequence impedance
X0 − XL X
angle kG = arc tan − arc tan L
R0 − RL RL
R0 : resistance component of zero-sequence impedance
RL : resistance component of positive-sequence impedance
X 0 : reactance component of zero-sequence impedance
X L : reactance component of positive-sequence impedance
If the calculated value cannot be set exactly, then a next smaller value
should be set.
Z0 − ZL
kG =
3 ⋅ ZL
Z 0 : zero-sequence impedance
Z L : positive-sequence impedance
(X 0 − X L )2 + (R0 − RL )2
kG =
3 ⋅ RL + X L
2 2
If the calculated value cannot be set exactly, then a next smaller value
should be set.
FT_DA: Start data acquisit. 010 011 Fig. 3-108
This setting determines at what point during a fault the acquisition of fault
data should take place.
FT_DA: Output fault locat. 010 032 Fig. 3-108
Setting for the conditions under which a fault location output occurs.
Fault recording FT_RC: Fct. assig. trigger 003 085 Fig. 3-114
This setting defines the signals that will trigger fault recording and fault data
acquisition.
FT_RC: I> 017 065 Fig. 3-114
This setting defines the threshold value of the phase currents that will
trigger fault recording and fault data acquisition.
FT_RC: Pre-fault time 003 078 Fig. 3-116
Setting for the time during which data will be recorded before a fault occurs
(pre-fault recording time).
FT_RC: Post-fault time 003 079 Fig. 3-116
Setting for the time during which data will be recorded after the end of a
fault (post-fault recording time).
FT_RC: Max. recording time 003 075 Fig. 3-116
Setting for the maximum recording time per fault. This includes pre-fault
and post-fault recording times.
Main function MAIN: Syst.IN enabled USER 018 008 Fig. 3-62
Definite-time overcurrent DTOC: General enable USER 022 075 Fig. 3-117
protection
Enable/disable the definite-time overcurrent protection function.
Inverse-time overcurrent IDMT1: General enable USER 017 096 Fig. 3-128
protection
IDMT2: General enable USER 017 052
Short-circuit direction SCDD: General enable USER 017 070 Fig. 3-142
determination
Enable/disable the short-circuit direction determination.
Switch on to fault protection SOTF: General enable USER 011 068 Fig. 3-152
The setting of the operating mode defines whether, while the timer is
running, a general starting will lead to a trip command ("trip with starting") or
if the measuring range of the impedance zone 1 is extended by the set zone
extension factor D IST : kze H SR PSx ("trip with extension").
SOTF: Manual close timer 011 060 Fig. 3-152
Setting for the timer stage that will be started by a manual close.
Protective signaling PSIG: General enable USER 015 004 Fig. 3-153
Auto-reclosing control ARC: General enable USER 015 060 Fig. 3-159
Automatic synchronism check ASC: General enable USER 018 000 Fig. 3-177
Ground fault direction GFDSS: General enable USER 016 060 Fig. 3-185
determination using
steady-state values
Enable/disable the ground fault direction determination by steady-state
values.
GFDSS: Operating mode 016 090 Fig. 3-185
Transient ground fault TGFD: General enable USER 016 040 Fig. 3-202
direction determination
Enable/disable the transient ground fault direction determination.
Motor protection MP: General enable USER 017 059 Fig. 3-209
Thermal overload protection THERM: General enable USER 022 050 Fig. 3-219
Unbalance protection I2>: General enable USER 018 090 Fig. 3-225
Time-voltage protection V<>: General enable USER 023 030 Fig. 3-227
Setting the evaluation time. The operate conditions must be met for the
duration of the set evaluation time so that a signal is issued.
f<>: Undervolt. block. V< 018 200 Fig. 3-238
Setting for the threshold of undervoltage blocking. If the voltage falls below
this threshold, the over-/underfrequency protection function will be blocked.
Power directional protection P<>: General enable USER 014 220 Fig. 3-241
Circuit breaker failure CBF: General enable USER 022 080 Fig. 3-255
protection
Enable/disable the circuit breaker failure protection function.
CBF: Start with man. trip 022 154 Fig. 3-259
Setting that a manual trip signal will also be used as a start criterion.
CBF: Fct.assignm. CBAux. 022 159 Fig. 3-259
The 1st timer stage trip command, set to latch mode, will remain active until
reset by operating parameters or through an appropriately configured binary
signal input.
CBF: Latching trip cmd.t2 022 170 Fig. 3-261
The 2nd timer stage trip command, set to latch mode, will remain active until
reset by operating parameters or through an appropriately configured binary
signal input.
CBF: Delay/starting trig. 022 155 Fig. 3-262
If during this delay time period the circuit breaker does not provide a signal
from its auxiliary contacts that it is closed, then faults behind the CB are
recognized through the current criterion (see section "Fault behind CB
protection").
CBF: Delay/CB sync.superv 022 172 Fig. 3-264
Setting the delay time period to bridge circuit breaker operate times during
CB synchronization supervision.
Circuit Breaker Monitoring CBM: General enable USER 022 010 Fig. 3-265
Using the setting for external devices the trip command issued by the
control function may be linked to the trip command 1 issued by the
protection by assigning the trip command issued by the control function by
this parameter.
CBM: Operating mode 022 007 Fig. 3-270
Setting the warning stage with the sum of the current-time integrals of the
CB disconnection current values
Measuring-circuit monitoring MCMON: General enable USER 014 001 Fig. 3-275
Setting the operate value for the voltage trigger Vmin< of measuring circuit
monitoring.
MCMON: Operate delay 017 023 Fig. 3-275
Setting for the time delay for "Fuse Failure" monitoring of the reference
voltage Vref.
Limit value monitoring LIMIT: General enable USER 014 010 Fig. 3-278
Setting for the operate value of the first overcurrent stage for limit value
monitoring.
LIMIT: I>> 014 020 Fig. 3-278
Setting for the operate value of the second overcurrent stage for limit value
monitoring.
LIMIT: tI> 014 031 Fig. 3-278
Setting for the operate delay of the first overcurrent stage for limit value
monitoring.
LIMIT: tI>> 014 032 Fig. 3-278
Setting for the operate delay of the second overcurrent stage for limit value
monitoring.
LIMIT: I< 014 021 Fig. 3-278
Setting for the operate value of the first undercurrent stage for limit value
monitoring.
Setting for the operate value of the second undercurrent stage for limit value
monitoring.
LIMIT: tI< 014 033 Fig. 3-278
Setting for the operate delay of the first undercurrent stage for limit value
monitoring.
LIMIT: tI<< 014 034 Fig. 3-278
Setting for the operate delay of the second undercurrent stage for limit value
monitoring.
LIMIT: VPG> 014 023 Fig. 3-279
Setting for the operate value of overvoltage stage VPG> for limit value
monitoring.
LIMIT: VPG>> 014 024 Fig. 3-279
Setting for the operate value of overvoltage stage VPG>> for limit value
monitoring.
LIMIT: tVPG> 014 035 Fig. 3-279
Setting for the operate delay of overvoltage stage VPG> for limit value
monitoring.
LIMIT: tVPG>> 014 036 Fig. 3-279
Setting for the operate delay of overvoltage stage VPG>> for limit value
monitoring.
LIMIT: VPG< 014 025 Fig. 3-279
Setting for the operate value of undervoltage stage VPG< for limit value
monitoring.
LIMIT: VPG<< 014 026 Fig. 3-279
Setting for the operate value of undervoltage stage VPG<< for limit value
monitoring.
LIMIT: tVPG< 014 037 Fig. 3-279
Setting for the operate delay of undervoltage stage VPG< for limit value
monitoring.
LIMIT: tVPG<< 014 038 Fig. 3-279
Setting for the operate delay of undervoltage stage VPG<< for limit value
monitoring.
LIMIT: VPP> 014 027 Fig. 3-279
Setting for the operate value of overvoltage stage VPP> for limit value
monitoring.
LIMIT: VPP>> 014 028 Fig. 3-279
Setting for the operate value of overvoltage stage VPP>> for limit value
monitoring.
LIMIT: tVPP> 014 039 Fig. 3-279
Setting for the operate delay of overvoltage stage VPP> for limit value
monitoring.
LIMIT: tVPP>> 014 040 Fig. 3-279
Setting for the operate delay of overvoltage stage VPP>> for limit value
monitoring.
Setting for the operate value of undervoltage stage VPP< for limit value
monitoring.
LIMIT: VPP<< 014 030 Fig. 3-279
Setting for the operate value of undervoltage stage VPP<< for limit value
monitoring.
LIMIT: tVPP< 014 041 Fig. 3-279
Setting for the operate delay of undervoltage stage VPP< for limit value
monitoring.
LIMIT: tVPP<< 014 042 Fig. 3-279
Setting for the operate delay of undervoltage stage VPP<< for limit value
monitoring.
LIMIT: VNG> 014 043 Fig. 3-280
Setting for the operate value of overvoltage stage VNG> for limit value
monitoring.
LIMIT: VNG>> 014 044 Fig. 3-280
Setting for the operate value of overvoltage stage VNG>> for limit value
monitoring.
LIMIT: tVNG> 014 045 Fig. 3-280
Setting for the operate delay of overvoltage stage VNG> for limit value
monitoring.
LIMIT: tVNG>> 014 046 Fig. 3-280
Setting for the operate delay of overvoltage stage VNG>> for limit value
monitoring.
LIMIT: Vref> 042 144 Fig. 3-282
Setting the operate value of overvoltage stage Vref> for limit value
monitoring. (Relevant only with circuit board 5V, i.e. ordering option Vnom
= 50 to 130 V {5 poles} for ASC).
LIMIT: Vref>> 042 145 Fig. 3-282
Setting the operate value of overvoltage stage Vref>> for limit value
monitoring. (Relevant only with circuit board 5V).
LIMIT: tVref> 042 148 Fig. 3-282
Setting the operate delay of overvoltage stage Vref> for limit value
monitoring. (Relevant only with circuit board 5V).
LIMIT: tVref>> 042 149 Fig. 3-282
Setting the operate delay of overvoltage stage Vref>> for limit value
monitoring. (Relevant only with circuit board 5V).
LIMIT: Vref< 042 146 Fig. 3-282
Setting the operate value of undervoltage stage Vref< for limit value
monitoring. (Relevant only with circuit board 5V).
LIMIT: Vref<< 042 147 Fig. 3-282
Setting the operate value of undervoltage stage Vref<< for limit value
monitoring. (Relevant only with circuit board 5V).
LIMIT: tVref< 042 150 Fig. 3-282
Setting the operate delay of undervoltage stage Vref< for limit value
monitoring. (Relevant only with circuit board 5V).
LIMIT: tVref<< 042 151 Fig. 3-282
Setting the operate delay of undervoltage stage Vref<< for limit value
monitoring. (Relevant only with circuit board 5V).
Setting for the operate value IDC,lin> for monitoring the linearized direct
current.
LIMIT: IDC,lin>> 014 111 Fig. 3-281
Setting for the operate value IDC,lin>> for monitoring the linearized direct
current.
LIMIT: tIDC,lin> 014 112 Fig. 3-281
Setting for the operate value IDC,lin< for monitoring the linearized direct
current.
LIMIT: IDC,lin<< 014 115 Fig. 3-281
Setting for the operate value IDC,lin<< for monitoring the linearized direct
current.
LIMIT: tIDC,lin< 014 116 Fig. 3-281
These settings define the static input conditions for the logic function.
LOGIC: Fct.assignm. outp. 1 030 000 Fig: 3-169,
3-289
LOGIC: Fct.assignm. outp. 2 030 004 Fig. 3-169
LOGIC: Fct.assignm. outp. 3 030 008
These settings define the operating modes for the output timer stages.
These settings assign the function of a binary input signal to the output of
the logic equation.
These settings assign the function of a binary input signal to the output of
the logic equation.
Group assignment for the debouncing time and the chatter suppression.
SIG_1: Min. sig. dur. S001 226 002 Fig. 3-310
SIG_1: Min. sig. dur. S002 226 010
The logic '1' signal must be available for this minimum time setting so that a
telegram can be sent in the "Start/end signal" mode.
Binary counts COUNT: General enable USER 217 000 Fig. 3-288
Setting the scaling factor to transmit the counter value via IEC 61850.
According to the standard the resulting value is calculated as:
Value transmitted = actual value * pulsQty
(see IEC 61850: Value = actVal * pulsQty).
COUNT: Cycle t.count transm 217 007 Fig. 3-288
Setting the cycle time for the periodic transmission of the counts.
Measured data input MEASI: BackupTempSensor PSx 004 243 004 244 004 245 004 246 Fig. 3-285
Main function MAIN: Neutr.pt. treat. PSx 010 048 001 076 001 077 001 078
Setting the hold time of the "dynamic parameters". After switching to the
"dynamic" thresholds, the latter will remain active in place of the "normal"
thresholds during this period.
MAIN: Bl.tim.st.IN,neg PSx 017 015 001 214 001 215 001 216 Fig. 3-73
This setting defines whether a blocking of the residual current stages should
take place for single-pole or multi-pole phase current startings.
MAIN: Gen. start. mode PSx 017 027 001 219 001 220 001 221 Fig: 3-74,
3-121, 3-124,
3-136, 3-138
This setting defines whether the triggering of the residual current stages IN>,
Iref,N>, IN>> or IN>>> as well as the negative-sequence current stage Iref,neg>
should result in the formation of the general starting signal. If the setting is
'W/o start. IN, Ineg' then the associated time delays tIN>, tIref,N>, tIN>>, tIN>>>,
tIref,neg> are automatically excluded from the formation of the trip command.
MAIN: Op. rush restr. PSx 017 097 001 088 001 089 001 090 Fig. 3-64
MAIN: I>lift rush restrPSx 017 095 001 085 001 086 001 087 Fig. 3-64
Definite-time overcurrent DTOC: Enabled PSx 072 098 073 098 074 098 075 098 Fig. 3-117
protection
This setting defines the parameter subset in which definite-time overcurrent
protection is enabled.
DTOC: I> PSx 017 000 073 007 074 007 075 007 Fig. 3-118
Setting the operate value of the first overcurrent stage (phase current
stage).
Caution! The range of setting values includes operate values that are not
permitted as continuous current values (see Chapter 'Technical Data').
DTOC: I> dynamic PSx 017 080 073 032 074 032 075 032 Fig. 3-118
Setting the operate value of the first overcurrent stage in dynamic mode
(phase current stage). This operate value is effective only while the timer
stage M AIN: H ol d- time d yn . par am . is elapsing.
Caution! The range of setting values includes operate values that are not
permitted as continuous current values (see Chapter 'Technical Data').
DTOC: I>> PSx 017 001 073 008 074 008 075 008 Fig. 3-118
Setting the operate value of the second overcurrent stage (phase current
stage).
Caution! The range of setting values includes operate values that are not
permitted as continuous current values (see Chapter 'Technical Data').
DTOC: I>> dynamic PSx 017 084 073 033 074 033 075 033 Fig. 3-118
Setting for the operate value of the second overcurrent stage in dynamic
mode (phase current stage). This operate value is effective only while the
timer stage M AIN : Ho ld -ti me d yn . p ara m . is elapsing.
Caution! The range of setting values includes operate values that are not
permitted as continuous current values (see Chapter 'Technical Data').
DTOC: I>>> PSx 017 002 073 009 074 009 075 009 Fig. 3-118
Setting the operate value of the third overcurrent stage (phase current
stage).
Caution! The range of setting values includes operate values that are not
permitted as continuous current values (see Chapter 'Technical Data').
DTOC: I>>> dynamic PSx 017 085 073 034 074 034 075 034 Fig. 3-118
Setting the operate value of the third overcurrent stage in dynamic mode
(phase current stage). This operate value is effective only while the timer
stage M AIN: H ol d- time d yn . par am . is elapsing.
Caution! The range of setting values includes operate values that are not
permitted as continuous current values (see Chapter 'Technical Data').
DTOC: tI> PSx 017 004 073 019 074 019 075 019 Fig. 3-118
Setting for the operate delay of overcurrent stage Ineg> (Ineg = negative-
sequence current).
DTOC: tIneg>> PSx 072 024 073 024 074 024 075 024 Fig. 3-120
DTOC: IN> PSx 017 003 073 015 074 015 075 015 Fig. 3-123
Setting the operate value of the first overcurrent stage (residual current
stage).
Caution! The range of setting values includes operate values that are not
permitted as continuous current values (see Chapter 'Technical Data').
DTOC: IN> dynamic PSx 017 081 073 035 074 035 075 035 Fig. 3-123
Setting the operate value of the dynamic first overcurrent stage (residual
current stage). This operate value is effective only while the timer stage
M A IN : H o ld - t i me d y n . p ar a m . is elapsing.
Caution! The range of setting values includes operate values that are not
permitted as continuous current values (see Chapter 'Technical Data').
DTOC: IN>> PSx 017 009 073 016 074 016 075 016 Fig. 3-123
Setting the operate value of the second overcurrent stage (residual current
stage).
Caution! The range of setting values includes operate values that are not
permitted as continuous current values (see Chapter 'Technical Data').
DTOC: IN>> dynamic PSx 017 086 073 036 074 036 075 036 Fig. 3-123
Setting the operate value of the second overcurrent stage in dynamic mode
(residual current stage). This operate value is effective only while the timer
stage M AIN: H ol d- time d yn . par am . is elapsing.
Caution! The range of setting values includes operate values that are not
permitted as continuous current values (see Chapter 'Technical Data').
DTOC: IN>>> PSx 017 018 073 017 074 017 075 017 Fig. 3-123
Setting the operate value of the third overcurrent stage (residual current
stage).
Caution! The range of setting values includes operate values that are not
permitted as continuous current values (see Chapter 'Technical Data').
DTOC: IN>>> dynamic PSx 017 087 073 037 074 037 075 037 Fig. 3-123
Setting the operate value of the dynamic third overcurrent stage (residual
current stage). This operate value is effective only while the timer stage
M A IN : H o ld - t i me d y n . p ar a m . is elapsing.
Caution! The range of setting values includes operate values that are not
permitted as continuous current values (see Chapter 'Technical Data').
DTOC: IN>>>> PSx 072 018 073 018 074 018 075 018 Fig. 3-123
Setting the operate value of the fourth overcurrent stage (residual current
stage).
Caution! The range of setting values includes operate values that are not
permitted as continuous current values (see Chapter 'Technical Data').
DTOC: IN>>>> dyn. PSx 072 036 072 105 072 202 072 219 Fig. 3-123
Setting the operate value of the dynamic fourth overcurrent stage (residual
current stage). This operate value is effective only while the timer stage
M A IN : H o ld - t i me d y n . p ar a m . is elapsing.
Caution! The range of setting values includes operate values that are not
permitted as continuous current values (see Chapter 'Technical Data').
DTOC: tIN> PSx 017 008 073 027 074 027 075 027 Fig. 3-123
Setting the operate delay of the first overcurrent stage (residual current
stage).
DTOC: tIN>> PSx 017 010 073 028 074 028 075 028 Fig. 3-123
Setting the operate delay of the second overcurrent stage (residual current
stage).
DTOC: tIN>>> PSx 017 019 073 029 074 029 075 029 Fig. 3-123
Setting the operate delay of the third overcurrent stage (residual current
stage).
DTOC: tIN>>>> PSx 072 030 073 030 074 030 075 030 Fig. 3-123
Setting the operate delay of the fourth overcurrent stage (residual current
stage).
DTOC: Puls.prol.IN>,intPSx 017 055 073 042 074 042 075 042 Fig. 3-125
Setting the pulse prolongation time of the hold-time logic for intermittent
ground faults.
DTOC: tIN,interm. PSx 017 056 073 038 074 038 075 038 Fig. 3-125
Setting the tripping time of the hold-time logic for intermittent ground faults.
DTOC: Hold-t. tIN>,intmPSx 017 057 073 039 074 039 075 039 Fig. 3-125
Inverse-time overcurrent IDMT1: Enabled PSx 072 070 073 070 074 070 075 070 Fig. 3-128
protection IDMT2: Enabled PSx 076 042 076 043 076 044 076 045
Setting the reference current in dynamic mode (phase current system). This
operate value is effective only while the timer stage M AIN : Ho ld -ti me
d yn . pa ram. is elapsing.
IDMT1: Characteristic P PSx 072 056 073 056 074 056 075 056 Fig. 3-133
IDMT2: Characteristic P PSx 071 004 071 005 071 006 071 007
Setting for the factor kt,P of the starting characteristic (phase current
system).
IDMT1: Min. trip time P PSx 072 077 073 077 074 077 075 077 Fig. 3-133
IDMT2: Min. trip time P PSx 071 044 071 045 071 046 071 047
Setting for the minimum trip time (phase current system). As a rule, this
value should be set as for the first DTOC stage (I>).
IDMT1: Hold time P PSx 072 071 073 071 074 071 075 071 Fig. 3-133
IDMT2: Hold time P PSx 071 028 071 029 071 030 071 031
Setting the holding time for intermittent short circuits (phase current
system).
IDMT1: Release P PSx 072 059 073 059 074 059 075 059 Fig. 3-133
IDMT2: Release P PSx 071 016 071 017 071 018 071 019
IDMT1: Iref,neg PSx 072 051 073 051 074 051 075 051 Fig. 3-133
IDMT2: Iref,neg PSx 076 250 076 251 076 252 076 253
Setting for the factor kt,N of the starting characteristic (residual current
system).
IDMT1: Min. trip time N PSx 072 079 073 079 074 079 075 079 Fig. 3-138
IDMT2: Min. trip time N PSx 071 052 071 053 071 054 071 055
Setting the minimum trip time (residual current system). As a rule, this
value should be set as for the first DTOC stage (IN>).
IDMT1: Hold time N PSx 072 073 073 073 074 073 075 073 Fig. 3-138
IDMT2: Hold time N PSx 071 036 071 037 071 038 071 039
Setting the holding time for intermittent short circuits (residual current
system).
IDMT1: Release N PSx 072 061 073 061 074 061 075 061 Fig. 3-138
IDMT2: Release N PSx 071 024 071 025 071 026 071 027
Short-circuit direction SCDD: Enabled PSx 076 235 077 235 078 235 079 235 Fig. 3-142
determination This setting defines the parameter subset in which short-circuit direction
determination is enabled.
SCDD: Trip bias PSx 017 074 077 236 078 236 079 236 Fig. 3-146
This setting for the measuring direction determines whether a tI> trip signal
in the DTOC phase current stage will be issued for forward, backward or
non-directional fault decisions. If the ARC is enabled and has been set
accordingly then a starting will trigger the associated ARC tripping time.
SCDD: Direction tI>> PSx 017 072 077 238 078 238 079 238 Fig. 3-146
This setting for the measuring direction determines whether a tI>> trip signal
in the DTOC phase current stage will be issued for forward, backward or
non-directional fault decisions. If the ARC is enabled and has been set
accordingly then a starting will trigger the associated ARC tripping time.
SCDD: Direct. tIref,P> PSx 017 066 077 239 078 239 079 239 Fig. 3-146
This setting for the measuring direction determines whether a tIref,P> trip
signal in the IDMT1 phase current stage will be issued for forward,
backward or non-directional fault decisions. If the ARC is enabled and has
been set accordingly then a starting will trigger the associated ARC tripping
time.
SCDD: Direction tIN> PSx 017 073 077 240 078 240 079 240 Fig. 3-150
This setting for the measuring direction determines whether a tIN> trip
signal in the DTOC residual current stage will be issued for forward,
backward or non-directional fault decisions. If the ARC is enabled and has
been set accordingly then a starting will trigger the associated ARC tripping
time.
SCDD: Direction tIN>> PSx 017 075 077 241 078 241 079 241 Fig. 3-150
This setting for the measuring direction determines whether a tIN>> trip
signal in the DTOC residual current stage will be issued for forward,
backward or non-directional fault decisions. If the ARC is enabled and has
been set accordingly then a starting will trigger the associated ARC tripping
time.
SCDD: Direct. tIref,N> PSx 017 067 077 242 078 242 079 242 Fig. 3-150
This setting for the measuring direction determines whether a tIref,N> trip
signal in the IDMT1 residual current stage will be issued for forward,
backward or non-directional fault decisions. If the ARC is enabled and has
been set accordingly then a starting will trigger the associated ARC tripping
time.
SCDD: Charact. angle G PSx 017 076 077 243 078 243 079 243 Fig. 3-149
Setting the operate value VNG>. This setting value is an enabling criterion
of the base point release of short-circuit direction determination.
In choosing this setting, the set nominal voltage M AIN : VNG ,nom V.T .
sec . should be taken into account.
SCDD: Evaluation VNG PSx 071 056 071 057 071 058 071 059 Fig: 3-148a
This setting defines whether the trip bias of the residual current stage
should be blocked in the event of a phase current starting.
SCDD: Oper.val.Vmemory PSx 010 109 010 116 010 117 010 118
In the event of a three-phase fault in the phase current stage, the measured
voltage VABmeas is compared with the selected operate value, Vop.Val., of
the voltage memory. If VABmeas < Vop.Val. then the SCDD function will
not use VABmeas but will revert to the voltage memory, if it has been
enabled.
Protective signaling PSIG: Enabled PSx 015 014 015 015 015 016 015 017 Fig. 3-153
PSIG: Direc.dependence PSx 015 001 015 115 015 116 015 117 Fig. 3-155
Without
Phase curr. system
Residual curr. system
Phase/resid.c.system
Auto-reclosing control ARC: Enabled PSx 015 046 015 047 015 048 015 049 Fig. 3-159
This setting defines whether the CB closed position will be scanned or not.
If the setting is 'With', a binary signal input must be configured accordingly.
ARC: Operating mode PSx 015 051 024 025 024 085 025 045 Fig: 3-158,
3-168
The operating mode setting defines which of the following reclosure types is
permitted.
TDR only permitted
HSR/TDR permitted
Test HSR only permit
ARC: Operative time PSx 015 066 024 035 024 095 025 055 Fig: 3-170,
3-172
Setting for the operative time 1.
ARC: HSR trip.time GS PSx 015 038 024 100 024 150 025 100 Fig. 3-166
Setting the HSR tripping time and start via a general starting condition.
ARC: HSR trip.time I> PSx 015 072 024 040 025 000 025 060 Fig: 3-162,
3-172
Setting the HSR tripping time and start via a phase current starting in the
first DTOC overcurrent stage.
ARC: HSR trip.time I>>PSx 015 074 024 101 024 151 025 101 Fig. 3-162.7
Setting the HSR tripping time and start via a phase current starting in the
second DTOC overcurrent stage.
ARC: HSRtrip.time I>>>PSx 014 096 024 102 024 152 025 102 Fig: 3-162,
Setting the HSR tripping time and start via a phase current starting in the
third DTOC overcurrent stage.
ARC: HSR trip.time IN>PSx 015 076 024 103 024 153 025 103 Fig: 3-162,
Setting the HSR tripping time and start via a residual current starting in the
first DTOC overcurrent stage.
ARC: HSRtrip.time IN>>PSx 015 031 024 104 024 154 025 104 Fig: 3-162,
Setting the HSR tripping time and start via a residual current starting in the
second DTOC overcurrent stage.
ARC: HSRtrip.t. IN>>> PSx 014 098 024 105 024 155 025 105 Fig: 3-162,
Setting the HSR tripping time and start via a residual current starting in the
third DTOC overcurrent stage.
ARC: HSRtrip.t.Iref,P PSx 015 094 024 106 024 156 025 106 Fig. 3-164
Setting the HSR tripping time and start via a starting in the IDMT1 phase
current system.
ARC: HSRtrip.t.Iref,N PSx 015 096 024 107 024 157 025 107 Fig. 3-164
Setting the HSR tripping time and start via a starting in the IDMT1 residual
current system.
ARC: HSRtr.t.Iref,neg PSx 015 034 024 108 024 158 025 108 Fig. 3-164
Setting the HSR tripping time and start via a starting in the IDMT1 negative-
sequence current system.
ARC: HSR trip t.GFDSS PSx 015 078 024 109 024 159 025 109 Fig. 3-165
Setting the HSR tripping time and start via ‘ground fault direction
determination using steady-state values’.
ARC: HSRtrip.t. LOGIC PSx 015 098 024 110 024 160 025 110 Fig. 3-167
Setting the HSR tripping time and start via programmable logic.
ARC: HSR block.f. I>>>PSx 015 080 024 111 024 161 025 111 Fig. 3-168
Setting for the number of time-delayed reclosures permitted. With the ‘0’
setting, only one HSR is carried out.
ARC: TDR trip.time GS PSx 015 039 024 112 024 162 025 112 Fig. 3-166
Setting the TDR tripping time and start via a general starting condition.
ARC: TDR trip.time I> PSx 015 073 024 041 025 001 025 061 Fig. 3-163
Setting the TDR tripping time and start via a phase current starting in the
first DTOC overcurrent stage.
ARC: TDR trip.time I>>PSx 015 075 024 113 024 163 025 113 Fig. 3-163
Setting the TDR tripping time and start via a phase current starting in the
second DTOC overcurrent stage.
ARC: TDRtrip.time I>>>PSx 014 097 024 114 024 164 025 114 Fig. 3-163
Setting the TDR tripping time and start via a phase current starting in the
third DTOC overcurrent stage.
ARC: TDR trip.time IN>PSx 015 077 024 115 024 165 025 115 Fig. 3-163
Setting the TDR tripping time and start via a residual current starting in the
first DTOC overcurrent stage.
ARC: TDRtrip.time IN>>PSx 015 032 024 116 024 166 025 116 Fig. 3-163
Setting the TDR tripping time and start via a residual current starting in the
second DTOC overcurrent stage.
ARC: TDRtrip.t. IN>>> PSx 014 099 024 117 024 167 025 117 Fig. 3-163
Setting the TDR tripping time and start via a residual current starting in the
third DTOC overcurrent stage.
ARC: TDRtrip.t.Iref,P PSx 015 095 024 118 024 168 025 118 Fig. 3-164
Setting the TDR tripping time and start via a starting in the IDMT1 phase
current system.
ARC: TDRtrip.t.Iref,N PSx 015 097 024 119 024 169 025 119 Fig. 3-164
Setting the TDR tripping time and start via a starting in the IDMT1 residual
current system.
ARC: TDRtr.t.Iref,neg PSx 015 035 024 120 024 170 025 120 Fig. 3-164
Setting the TDR tripping time and start via a starting in the IDMT1 negative-
sequence current system.
ARC: TDR trip t.GFDSS PSx 015 079 024 121 024 171 025 121 Fig. 3-165
Setting the TDR tripping time and start via ‘ground fault direction
determination using steady-state values’.
ARC: TDRtrip.t. LOGIC PSx 015 099 024 122 024 172 025 122 Fig. 3-167
Setting the TDR tripping time and start via programmable logic.
ARC: TDR dead time PSx 015 057 024 031 024 091 025 051 Fig. 3-170
Setting for the time that will elapse before the ARC will be ready again after
blocking by a binary signal input.
Automatic synchronism check ASC: Enabled PSx 018 020 018 021 018 022 018 023 Fig. 3-177
This setting defines the function group DEVxx that will control the circuit
breaker.
ASC: System integrat. PSx 037 135 037 136 037 137 037 138 Fig. 3-185
This setting defines whether ASC will operate in 'Autom. synchron. check' or
'Autom. synchr. control' mode.
ASC: Active for HSR PSx 018 001 077 030 078 030 079 030 Fig. 3-178
This setting defines whether reclosing after a three-pole HSR will occur only
after being enabled by ASC.
ASC: Active for TDR PSx 018 002 077 031 078 031 079 031 Fig. 3-178
This setting defines whether reclosing after a three-pole TDR will occur only
after being enabled by ASC.
ASC: Clos.rej.w.block PSx 018 003 077 032 078 032 079 032 Fig. 3-178
Criteria for a close enable are defined by setting for the operating mode.
ASC: Op.mode volt.chk.PSx 018 029 018 030 018 031 018 032 Fig. 3-181
This setting defines the logic linking of trigger decisions for a voltage
controlled close enable.
ASC: V> volt.check PSx 026 017 077 043 078 043 079 043 Fig. 3-181
Setting the voltage threshold that the phase-to-ground voltages and the
reference voltage must exceed so that they are recognized as "Voltage
showing".
Setting the voltage threshold that the phase-to-ground voltages and the
reference voltage must fall below so that they are recognized as "Voltage
showing".
Setting for the operate delay value to define the minimum time period during
which voltage conditions must be met so that the close enable of the ASC is
effected.
ASC: Measurement loop PSx 031 060 077 044 078 044 079 044 Fig. 3-176
Setting for the operate delay value to define the minimum time period during
which synchronism conditions must be met so that the close enable of the
ASC is effected.
Ground fault direction GFDSS: Enabled PSx 001 050 001 051 001 052 001 053 Fig. 3-188
determination using This setting defines the parameter subset in which the GFDSS function is
steady-state values enabled.
GFDSS: Op.m.GF pow./adm PSx 016 063 000 236 000 237 000 238 Fig: 3-190,
3-196
Setting the operating mode of the ground fault direction determination by
steady-state values. The following settings are possible: The following
settings are possible:
"Cos ϕ circuit" for resonant-grounded systems.
"Sin ϕ circuit" for isolated neutral-point systems.
GFDSS: Evaluation VNG PSx 016 083 001 011 001 012 001 013 Fig. 3-189
Setting of the sector angle for measurement in the line side direction.
GFDSS: Sector angle BS PSx 016 068 000 248 000 249 000 250 Fig. 3-193
Setting the sector angle for measurement in the direction of the busbar side.
Setting the operate value of the admittance for the non-directional ground
fault determination (in the operating mode "admittance evaluation").
GFDSS: Phi offset PSx 016 110 001 026 001 027 001 028 Fig. 3-196
Setting the operate delay value of the admittance for the non-directional
ground fault determination (in the operating mode "admittance evaluation").
GFDSS: Rel. delay Y(N)> PSx 016 115 001 041 001 042 001 043 Fig. 3-200
Setting the release delay value of the admittance for the non-directional
ground fault determination (in the operating mode "admittance evaluation").
TGFD: Enabled PSx 001 054 001 055 001 056 001 057 Fig. 3-202
This setting defines the parameter subset in which the TGFD function is
enabled.
TGFD: Evaluation VNG PSx 016 048 001 058 001 059 001 060 Fig. 3-203
TGFD: Measurem. direc. PSx 016 045 001 073 001 074 001 075 Fig. 3-204
Setting the signal buffer time for transient ground fault direction
determination.
Motor protection MP: Enabled PSx 024 148 024 147 024 197 025 147 Fig. 3-209
For the determination of the reference current, the nominal motor current
needs to be calculated first from the motor data.
Pnom
I nom,motor =
3 ⋅ Vnom ⋅ η ⋅ cos ϕ
The reference current is the nominal motor current as projected onto the
transformer secondary side and is thus calculated as follows:
I ref I T
= nom,motor nom
I nom,( relay ) I nom,( relay )
Example:
MP: Factor kP PSx 017 040 024 132 024 182 025 132 Fig. 3-210
Example:
Motor Data:
Setting the operate delay for the operational status determination 'machine
starting up'. Usually, the default setting can be retained.
MP: Characteristic P PSx 017 029 024 135 024 185 025 135 Fig. 3-215
MP: t6Iref PSx 017 041 024 136 024 186 025 136 Fig. 3-215
This Setting the overload tripping time t6Iref is determined from the cold
machine data, using Iref = Inom,motor.
I ref = Inom,motor
Based on the setting value thus determined, the tripping time for a warm
machine is now defined as follows.
For the reciprocally squared characteristic we set:
t = (1 − 0.2) ⋅ t 6I ref ⋅
36
2
⎛ Istartup ⎞
⎜ ⎟
⎜I ⎟
⎝ nom,motor ⎠
16 s at Vnom
MP: Tau after st.-up PSx 018 042 024 137 024 187 025 137 Fig. 3-215
Setting the heat dispersion time constant after startup. Usually, the default
setting can be retained.
MP: Tau mach.running PSx 017 088 024 138 024 188 025 138 Fig. 3-215
MP: Tau mach.stopped PSx 017 089 024 139 024 189 025 139 Fig. 3-215
This setting defines whether motor protection will be operated together with
thermal overload protection (THERM).
MP: St.-up time tStUpPSx 017 043 024 143 024 193 025 143 Fig. 3-215
MP: Blocking time tE PSx 017 044 024 144 024 194 025 144 Fig. 3-215
Setting the operate value of the minimum current stage of the underload
protection function of motor protection.
MP: tI< PSx 017 050 024 146 024 196 025 146 Fig. 3-218
Setting the operate delay of the minimum current stage of the underload
protection function of motor protection.
Thermal overload protection THERM: Enabled PSx 072 175 073 175 074 175 075 175 Fig. 3-219
Setting for the thermal time constants of the protected object with current
flow (Ibl: base line current).
THERM: Tim.const.2,<Ibl PSx 072 188 073 188 074 188 075 188 Fig. 3-223
Setting for the thermal time constants of the protected object without current
flow (Ibl: base line current).
Note:
This setting option is only relevant when machines are running. In all other
cases, time constant 2 must be set equal to time constant 1.
THERM: Max.perm.obj.tmp.PSx 072 182 073 182 074 182 075 182 Fig. 3-223
Selecting the backup temperature sensor for the parameter subset PSx.
THERM: Warning temp. PSx 072 153 073 153 074 153 075 153 Fig. 3-223
Setting for the operate value of the warning stage (for the 'Absolute replica'
operating mode).
THERM: Default CTA PSx 072 186 073 186 074 186 075 186 Fig. 3-223
Setting the coolant temperature to be used for calculation of the trip time if
coolant temperature is not measured.
THERM: Rel. O/T warning PSx 072 184 073 184 074 184 075 184 Fig. 3-223
THERM: Warning pre-trip PSx 072 191 073 191 074 191 075 191 Fig. 3-223
A warning will be given in advance of the trip. The time difference between
the warning time and the trip time is set here.
THERM: Funct.f.CTA fail.PSx 076 177 077 177 078 177 079177 Fig. 3-221
This setting specifies how the thermal overload protection function should
continue to operate in the event of faulty coolant temperature acquisition.
The user may select between Default temp. value, Last meas.temperat. and
Blocked.
Unbalance protection I2>: Enabled PSx 018 220 018 221 018 222 018 223 Fig. 3-225
Time-voltage protection V<>: Enabled PSx 076 246 077 246 078 246 079 246 Fig. 3-227
This setting defines the threshold value of the minimum current monitoring
for undervoltage stage V<.
V<>: Op. mode V< mon. PSx 001 162 001 163 001 164 001 165 Page: 3-332
Setting for the operate delay of overvoltage stage V> when all three trigger
stages are activated.
V<>: tV>> PSx 076 006 077 006 078 006 079 006 Fig. 3-229
Setting for the operate delay of undervoltage stage V< when all three trigger
stages are activated.
V<>: tV<< PSx 076 010 077 010 078 010 079 010 Fig. 3-230
V<>: Vneg> PSx 076 023 077 023 078 023 079 023 Fig. 3-233
Setting for the time limit of the signals generated by the undervoltage
stages.
V<>: Hyst. V<> meas. PSx 076 048 077 048 078 048 079 048 Fig. 3-229
Setting for the hysteresis of the trigger stages for monitoring measured
voltages.
V<>: Hyst. V<> deduc. PSx 076 049 077 049 078 049 079 049 Fig. 3-232
Setting for the hysteresis of the trigger stages for monitoring derived
voltages such as Vneg and VNG.
Over-/underfrequency f<>: Enabled PSx 018 196 018 197 018 198 018 199 Fig. 3-236
protection
This setting defines the parameter subset in which over-/underfrequency
protection is enabled.
f<>: Oper. mode f1 PSx 018 120 018 121 018 122 018 123 Fig. 3-240
f<>: Oper. mode f2 PSx 018 144 018 145 018 146 018 147
f<>: Oper. mode f3 PSx 018 168 018 169 018 170 018 171
f<>: Oper. mode f4 PSx 018 192 018 193 018 194 018 195
f<>: f3 PSx 018 148 018 149 018 150 018 151
f<>: f4 PSx 018 172 018 173 018 174 018 175
f<>: tf3 PSx 018 152 018 153 018 154 018 155
f<>: tf4 PSx 018 176 018 177 018 178 018 179
f<>: df3/dt PSx 018 156 018 157 018 158 018 159
f<>: df4/dt PSx 018 180 018 181 018 182 018 183
f<>: Delta f3 PSx 018 160 018 161 018 162 018 163
f<>: Delta f4 PSx 018 184 018 185 018 186 018 187
f<>: Delta t3 PSx 018 164 018 165 018 166 018 167
f<>: Delta t4 PSx 018 188 018 189 018 190 018 191
Power directional protection P<>: Enabled PSx 014 252 014 253 014 254 014 255 Fig. 3-241
This setting of the measuring direction determines whether a P> trip signal
will be issued for 'forward', 'backward' or 'non-directional' fault decisions.
P<>: Diseng. ratio P> PSx 017 124 017 125 017 126 017 127 Fig. 3-243
Setting the disengaging ratio of the operate value P> for the active power.
P<>: P>> PSx 017 140 017 141 017 142 017 143 Fig. 3-243
This setting of the measuring direction determines whether a P>> trip signal
will be issued for 'forward', 'backward' or 'non-directional' fault decisions.
P<>: Diseng. ratio P>>PSx 017 144 017 145 017 146 017 147 Fig. 3-243
Setting the disengaging ratio of the operate value P>> for the active power.
P<>: Q> PSx 017 160 017 161 017 162 017 163 Fig. 3-245
This setting of the measuring direction determines whether a Q> trip signal
will be issued for 'forward', 'backward' or 'non-directional' fault decisions.
P<>: Diseng. ratio Q> PSx 017 164 017 165 017 166 017 167 Fig. 3-245
Setting the disengaging ratio of the operate value Q> of the reactive power.
P<>: Q>> PSx 017 180 017 181 017 182 017 183 Fig. 3-245
P<>: Direction Q>> PSx 017 196 017 197 017 198 017 199 Fig. 3-245
This setting of the measuring direction determines whether a Q>> trip signal
will be issued for 'forward', 'backward' or 'non-directional' fault decisions.
P<>: Diseng. ratio Q>>PSx 017 184 017 185 017 186 017 187 Fig. 3-245
Setting the disengaging ratio of the operate value Q>> of the reactive
power.
P<>: P< PSx 017 030 017 031 017 032 017 033 Fig. 3-247
This setting of the measuring direction determines whether a P< trip signal
will be issued for 'forward', 'backward' or 'non-directional' fault decisions.
P<>: Diseng. ratio P< PSx 017 034 017 035 017 036 017 037 Fig. 3-247
Setting the disengaging ratio of the operate value P< for the active power.
P<>: P<< PSx 017 234 017 235 017 236 017 237 Fig. 3-247
This setting of the measuring direction determines whether a P< trip signal
will be issued for 'forward', 'backward' or 'non-directional' fault decisions.
P<>: Diseng.ratio P<< PSx 017 238 017 239 017 240 017 241 Fig. 3-247
Setting the disengaging ratio of the operate value P<< for the active power.
P<>: Q< PSx 018 035 018 036 018 037 018 038 Fig. 3-250
This setting of the measuring direction determines whether a Q< trip signal
will be issued for 'forward', 'backward' or 'non-directional' fault decisions.
P<>: Diseng. ratio Q< PSx 018 044 018 045 018 046 018 047 Fig. 3-250
Setting the disengaging ratio of the operate value Q< of the reactive power.
P<>: Q<< PSx 018 085 018 086 018 087 018 088 Fig. 3-250
P<>: Operate delay Q<<PSx 018 213 018 214 018 215 018 216 Fig. 3-250
This setting of the measuring direction determines whether a Q<< trip signal
will be issued for 'forward', 'backward' or 'non-directional' fault decisions.
P<>: Diseng.ratio Q<< PSx 018 095 018 096 018 097 018 098 Fig. 3-250
Setting the disengaging ratio of the operate value Q<< of the reactive
power.
P<>: tTransient pulse PSx 018 246 018 247 018 248 018 249 Fig: 3-247,
3-249, 3-250,
3-252
Setting the time limit of the signals generated by the stages P<, P<<, Q<
and Q<< after the respective operate delay has elapsed.
7.1.3.4 Control
Selecting the bay interlocking function from the local control panel.
MAIN: SI active USER 221 002 Fig. 3-80
Selecting the station interlocking function from the local control panel.
MAIN: Inp.asg. fct.block.1 221 014 Fig. 3-65
MAIN: Inp.asg. fct.block.2 221 022 Fig. 3-65
Setting the permissible motor drive operations within the time interval
defined at M A I N : M o n . t i m e m o t . d r i v e s .
MAIN: CB1 max. oper. cap. 221 084 Page: 3-256;
422
MAIN: CB2 max. oper. cap. 221 088 Page: 3-256;
422
Setting the maximum number of CB operations for an ARC cycle (or for a
limited time period).
MAIN: Mon.time mot.drives 221 026 Fig. 3-82
Assigning the external device to one of eight groups for debouncing and
chatter suppression.
DEV01: Interm. pos. suppr. 210 012 Fig: 3-296,
3-302
DEV02: Interm. pos. suppr. 210 062
This setting determines whether the actual status will be signaled with a 5 s
delay after the 'Faulty position' signal is issued.
DEV01: Oper. mode cmd. 210 024
Select the operating mode of the command from long command, short
command or time control.
This setting specifies whether the circuit breaker will be opened by “general
trip command 1” of the protection function.
Note: This setting is only visible (active) for external devices that are
defined as ‘circuit breakers’. This definition is included in the bay type
definitions.
DEV01: With gen. trip cmd.2 210 022 Fig. 3-300
This setting specifies whether the circuit breaker will be opened by “general
trip command 2” of the protection function.
Note: This setting is only visible (active) for external devices that are
defined as ‘circuit breakers’. This definition is included in the bay type
definitions.
This setting specifies whether the circuit breaker will be closed by the "close
command" of the protection function.
Note: This setting is only visible (active) for external devices that are
defined as ‘circuit breakers’. This definition is included in the bay type
definitions.
DEV01: Inp.asg.el.ctrl.open 210 019 Fig. 3-297
This setting defines the binary signal that will be used as the control signal
to move the switchgear unit to the open position.
Note: Only signals that are defined in the DEVxx function groups can
be selected.
DEV01: Inp.asg.el.ctr.close 210 020 Fig. 3-297
This setting defines the binary signal that will be used as the control signal
to move the switchgear unit to the 'Closed' position.
Note: Only signals that are defined in the DEVxx function groups can
be selected.
This setting defines the binary signal that will be used to terminate the
'Open' command.
DEV01: Inp. asg. end Close 210 016 Fig. 3-304
DEV02: Inp. asg. end Close 210 066
This setting defines the binary signal that will be used to terminate the
'Close' command.
DEV01: Open w/o stat.interl 210 025 Fig. 3-299
DEV02: Open w/o stat.interl 210 075
This setting defines which output will issue the 'Open' enable to the
interlocking logic when there is 'bay interlock with substation interlock'.
Note:
The interlock conditions for bay interlock with station interlock are included
in the bay type definitions (see List of Bay Types in the Appendix).
If the interlock condition is to be modified, this is possible by modifying the
corresponding Boolean equation in the interlocking logic or by defining a
new interlocking logic equation. Only in the latter case is it necessary to
change the function assignment.
DEV01: Fct.assig.BIwSI clos 210 040 Fig. 3-298
DEV02: Fct.assig.BIwSI clos 210 090
This setting defines which output will issue the 'Close' enable to the
interlocking logic when there is 'bay interlock with substation interlock'.
Note:
The interlock conditions for bay interlock with station interlock are included
in the bay type definitions (see List of Bay Types in the Appendix).
If the interlock condition is to be modified, this is possible by modifying the
corresponding Boolean equation in the interlocking logic or by defining a
new interlocking logic equation. Only in the latter case is it necessary to
change the function assignment.
This setting defines which output will issue the 'Open' enable to the
interlocking logic when there is 'bay interlock without substation interlock'.
Note:
The interlock conditions for bay interlock without station interlock are
included in the bay type definitions (see List of Bay Types in the Appendix).
If the interlock condition is to be modified, this is possible by modifying the
corresponding Boolean equation in the interlocking logic or by defining a
new interlocking logic equation. Only in the latter case is it necessary to
change the function assignment.
DEV01: Fct.asg.BI w/o SI cl 210 042 Fig. 3-298
This setting defines which output will issue the 'Close' enable to the
interlocking logic when there is 'bay interlock without substation interlock'.
Note:
The interlock conditions for bay interlock without station interlock are
included in the bay type definitions (see List of Bay Types in the Appendix).
If the interlock condition is to be modified, this is possible by modifying the
corresponding Boolean equation in the interlocking logic or by defining a
new interlocking logic equation. Only in the latter case is it necessary to
change the function assignment.
7.2.1 General
The P139 was subjected to risk analysis based on the DIN V 19 250 standard of May
1994 (on basic safety considerations for measuring and protection relays) as well as
DIN V 19 251 of February 1995 (on measuring and protection relays, specifications and
measures for their fail-safe functioning) and owing to a lack of more specific standards
also based on DIN V VDE 0801 (on computers in safety systems).
Based on this risk analysis involving the examination of extensive measures for
prevention and management of malfunction, the P139 has been classified in
specifications class 3. According to NAMUR NE 31 (NAMUR: German committee on
standards for measuring and control engineering), specifications class 3 corresponds to
risk area 1. For this risk area, a protection device of single-channel design with alarm
signal and/or normally-energized arrangement (‘closed-circuit principle’) will normally
suffice. In special cases, a requirement for a higher specifications class can be met by a
customized ‘1 out of 2’ or ‘2 out of 3’ circuit.
By connection and configuration of the output relay M AIN : Blocke d /fau l ty , the
increased-safety machine can be switched off immediately or, alternatively, an alarm
signal can be given for delayed switch-off based on an assessment of the operational
conditions by trained staff.
For the P139 to operate in a restrictive safety-oriented mode under all operational
conditions, the output relays must be operated in a normally-energized arrangement
('closed-circuit principle'). In this arrangement, the relevant output relay is energized
during normal operation and drops out in the event of an activation of the associated
function or in the event of a malfunction.
1
siehe Kapitel ”Bedienung” dieser Betriebsanleitung.
P139/EN M/Aa8 // AFSV.12.10170 D /// P139-307-411/412/413-614 7-131
7 Settings
(continued)
During device startup and during P139 operation, cyclic self-monitoring tests are run. In
the event of a positive test result, a specified monitoring signal will be issued and stored
in a non-volatile (NV) memory – the monitoring signal memory (see Chapter
'Troubleshooting'). A listing of all possible entries in this monitoring signal memory is
given in the address list (see Appendix). Monitoring signals prompted by a serious
hardware or software fault in the unit are always entered in the monitoring signal
memory. The entry of monitoring signals of lesser significance into the monitoring signal
memory is optional. The user can select this option by setting a 'm out of n' parameter.
The blocking of the protection device is governed by similar principles, that is, signals
prompted by a serious hardware or software fault in the unit always lead to a blocking of
the unit. The assignment of signals of lesser significance to the signal
M AIN : Blocke d /fau l ty by an ‘m out of n’ parameter (M AIN : F c t . a s s i g n m .
F a u l t ) is optional.
For safety-oriented operation, the ‘Warning’ can be configured onto an output relay as in
the following example.
8.1 Operation
The P139 generates a large number of signals, processes binary input signals, and
acquires measured data during fault-free operation of the protected object as well as
fault-related data. A number of counters are available for statistical purposes.
This information can be read out from the integrated local control panel.
All this information can be found in the ‘Operation’ and ‘Events’ folders in the menu tree.
Note:
Communication interface 3 COMM3: No. tel. errors p.u. 120 040 Page:3-30
While the hold time is running, the loop back test results can be checked by
reading out these values.
Measured data input MEASI: Current IDC 004 134 Fig. 3-28
Measured data output MEASO: Current A-1 005 100 Fig. 3-41
MEASO: Current A-2 005 099
Date display.
Note:
The time can be set here for standard time or daylight saving time.
Display of the updated value for the residual current as a primary quantity.
MAIN: Volt. VPG,max prim. 008 042 Fig. 3-53
Display of the updated value for phase-to-ground voltage B-G referred to Vnom.
MAIN: Voltage C-G p.u. 007 043 Fig. 3-53
Display of the updated value for phase-to-ground voltage C-G referred to Vnom.
MAIN: Volt. Σ(VPG)/©3 p.u. 005 013 Fig. 3-53
Display of the updated value for phase-to-phase voltage A-B referred to Vnom.
MAIN: Voltage B-C p.u. 006 045 Fig. 3-53
Display of the updated value for phase-to-phase voltage B-C referred to Vnom.
MAIN: Voltage C-A p.u. 007 045 Fig. 3-53
Display of the updated value for phase-to-phase voltage C-A referred to Vnom.
MAIN: Voltage Vpos p.u. 009 018 Fig. 3-53
Ground fault direction GFDSS: Current IN,act p.u. 004 045 Fig. 3-193
determination using Display of the updated value for the active component of residual current
steady-state values referred to IN,nom.
GFDSS: Curr. IN,reac p.u. 004 046 Fig. 3-193
Display of the updated value for the reactive component of residual current
referred to IN,nom.
GFDSS: Curr. IN filt. p.u. 004 047 Fig. 3-194
Display of the updated value for the harmonic content of residual current
referred to IN,nom. This display is only active when the steady-state current
evaluation mode of the ground fault direction determination function
(GFDSS) is enabled.
GFDSS: Admitt. Y(N) p.u. 004 191 Fig. 3-199
Thermal overload protection THERM: Status THERM replica 004 016 Fig. 3-223
If, on the other hand, the coolant temperature and the maximum permissible
coolant temperature have been set to the same value, then the coolant
temperature is not taken into account and the characteristic is a function of
the current only. The additional reserve amounts to zero in this case.
Substation Event
GOOSE: Output 2 state 106 012
Status Events
GSSE: Output 2 state 104 103
"High": Energized.
This display appears regardless of the setting for the binary signal input
mode.
This display appears regardless of the operating mode set for the output
relay.
Communication interface 1 COMM1: Command block. EXT 003 173 Fig. 3-10
COMM1: Sig./meas. block EXT 037 074 Fig: 3-11,
3-12,3-13
COMM1: Command blocking 003 174 Fig. 3-10
COMM1: Buffer overrun 221 100
Display when an Ethernet module has not initiated properly, i.e. if the MAC
address is missing or there is a non-plausible parameter setting!
IEC: Control reservation 221 082
Substation Event
GOOSE: Ext.Dev02 position 109 005
Binary open state of the virtual two-pole GOOSE input, representing the
state of an external device.
GOOSE: Ext.Dev01 closed 109 002
Binary closed state of the virtual two-pole GOOSE input, representing the
state of an external device.
Events
Display if the continuously monitored communication link to a GSSE
sending device (IED situated on the opposite side) is in fault or has
disappeared altogether. To each GSSE the GSSE sending device will
attach a validity stamp, up to which a repetition of GSSE will be carried out
independent of a change of state. Thus the device monitors the time period
at which the next state signal must be received.
Measured data input MEASI: Reset Tmax EXT 006 076 Fig.*: 3-86
MEASI: Enabled 035 008 Fig. 3-25
MEASI: RTD HW Failure 006 102
Binary outputs OUTP: Block outp.rel. EXT 040 014 Fig. 3-33
OUTP: Reset latch. EXT 040 015 Fig. 3-33
OUTP: Outp. relays blocked 021 015 Fig. 3-33
OUTP: Latching reset 040 088 Fig. 3-33
MEASO: Enabled 037 102 Fig. 3-35
MEASO: Outp. enabled EXT 036 085 Fig. 3-36
MEASO: Reset output EXT 036 087 Fig. 3-37
MEASO: Output reset 037 117 Fig. 3-37
MEASO: Valid BCD value 037 050 Fig: 3-38,
3-39
Measured data output MEASO: 1-digit bit 0 (BCD) 037 051 Fig. 3-39
MEASO: 1-digit bit 1 (BCD) 037 052 Fig. 3-39
MEASO: 1-digit bit 2 (BCD) 037 053 Fig. 3-39
MEASO: 1-digit bit 3 (BCD) 037 054 Fig. 3-39
MEASO: 10-digit bit 0 (BCD) 037 055 Fig. 3-39
MEASO: 10-digit bit 1 (BCD) 037 056 Fig. 3-39
MEASO: 10-digit bit 2 (BCD) 037 057 Fig. 3-39
MEASO: 10-digit bit 3 (BCD) 037 058 Fig. 3-39
MEASO: 100-digit bit 0 (BCD) 037 059 Fig. 3-39
MEASO: 100-digit bit 1 (BCD) 037 060 Fig. 3-39
MEASO: Value A-1 valid 069 014 Fig. 3-41
MEASO: Value A-1 output 037 118 Fig. 3-41
MEASO: Value A-2 valid 069 015
Parameter subset selection PSS: Control via user EXT 036 101 Fig. 3-89
PSS: Activate PS 1 EXT 065 002 Fig. 3-89
PSS: Activate PS 2 EXT 065 003 Fig. 3-89
PSS: Activate PS 3 EXT 065 004 Fig. 3-89
PSS: Activate PS 4 EXT 065 005 Fig. 3-89
PSS: Control via user 036 102 Fig. 3-89
PSS: Ext.sel.param.subset 003 061 Fig. 3-89
PSS: PS 1 activated ext. 036 094 Fig. 3-89
PSS: PS 2 activated ext. 036 095 Fig. 3-89
PSS: PS 3 activated ext. 036 096 Fig. 3-89
PSS: PS 4 activated ext. 036 097 Fig. 3-89
PSS: Actual param. subset 003 062 Fig. 3-89
PSS: PS 1 active 036 090 Fig. 3-89
PSS: PS 2 active 036 091 Fig. 3-89
PSS: PS 3 active 036 092 Fig. 3-89
PSS: PS 4 active 036 093 Fig. 3-89
Operating data recording OP_RC: Reset record. EXT 005 213 Fig. 3-86
Monitoring signal recording MT_RC: Reset record. EXT 005 240 Fig.*: 3-86
Overload recording OL_RC: Reset record. EXT 005 241 Fig.*: 3-86
OL_RC: Record. in progress 035 003 Fig. 3-96
OL_RC: Overl. mem. overflow 035 007 Fig. 3-97
Ground fault recording GF_RC: Reset record. EXT 005 242 Fig.*: 3-86
GF_RC: Record. in progress 035 005 Fig. 3-105
GF_RC: GF memory overflow 035 006 Fig. 3-106
Fault data acquisition FT_DA: Trigger EXT 036 088 Fig. 3-108
Definite-time overcurrent DTOC: Blocking tI> EXT 041 060 Fig. 3-118
protection
DTOC: Blocking tI>> EXT 041 061 Fig. 3-118
DTOC: Blocking tI>>> EXT 041 062 Fig. 3-118
DTOC: Block. tIneg> EXT 036 141 Fig. 3-120
DTOC: Block. tIneg>> EXT 036 142 Fig. 3-120
DTOC: Block. tIneg>>> EXT 036 143 Fig. 3-120
DTOC: Blocking tIN> EXT 041 063 Fig. 3-123
DTOC: Blocking tIN>> EXT 041 064 Fig. 3-123
DTOC: Blocking tIN>>> EXT 041 065 Fig. 3-123
DTOC: Blocking tIN>>>> EXT 041 101 Fig. 3-123
DTOC: Enabled 040 120 Fig. 3-117
DTOC: Starting I> 040 036 Fig. 3-118
DTOC: Starting I>> 040 029 Fig. 3-118
DTOC: Starting I>>> 039 075 Fig. 3-118
DTOC: Starting Ineg> 036 145 Fig: 3-73,
3-74,3-120
DTOC: Starting Ineg>> 036 146 Fig: 3-73,
3-74,3-120
DTOC: Starting Ineg>>> 036 147 Fig: 3-73,
3-74,3-120
DTOC: Starting IN> 040 077 Fig. 3-123
DTOC: Starting IN>> 040 041 Fig. 3-123
DTOC: Starting IN>>> 039 078 Fig. 3-123
DTOC: Starting IN>>>> 035 031 Fig. 3-123
DTOC: tI> elapsed 040 010 Fig. 3-118
DTOC: tI>> elapsed 040 033 Fig. 3-118
DTOC: tI>>> elapsed 040 012 Fig. 3-118
DTOC: Trip signal tI> 041 020 Fig. 3-119
DTOC: Trip signal tI>> 040 011 Fig. 3-119
DTOC: Trip signal tI>>> 040 076 Fig. 3-119
DTOC: tIneg> elapsed 036 148 Fig: 3-75,
3-94,3-120
DTOC: tIneg>> elapsed 036 149 Fig: 3-75,
3-94,3-120
DTOC: tIneg>>> elapsed 036 150 Fig: 3-75,
3-94,3-120
DTOC: Trip signal tIneg> 036 151 Fig: 3-75,
3-94,3-120,
3-121
DTOC: Trip signal tIneg>> 036 152 Fig: 3-94,
3-120,3-121
DTOC: Trip signal tIneg>>> 036 153 Fig: 3-94,
3-120,3-121
DTOC: tIN> elapsed 040 013 Fig. 3-123
DTOC: tIN>> elapsed 040 121 Fig. 3-123
DTOC: tIN>>> elapsed 039 079 Fig. 3-123
DTOC: tIN>>>> elapsed 035 040 Fig. 3-123
DTOC: Trip signal tIN> 041 021 Fig. 3-124
DTOC: Trip signal tIN>> 040 028 Fig. 3-124
DTOC: Trip signal tIN>>> 040 079 Fig. 3-124
DTOC: Trip sign. tIN>>>> 035 046 Fig. 3-124
DTOC: H.-time tIN>,i. runn 040 086 Fig. 3-125
DTOC: tIN>,interm. elapsed 040 099 Fig. 3-125
DTOC: Trip sig. tIN>,intm. 039 073 Fig. 3-125
Inverse-time overcurrent IDMT1: Block. tIref,P> EXT 040 101 Fig. 3-133
protection
IDMT1: Block. tIref,neg>EXT 040 102 Fig. 3-136
IDMT1: Block. tIref,N> EXT 040 103 Fig. 3-138
IDMT1: Enabled 040 100 Fig. 3-128
IDMT1: Starting Iref,P> 040 080 Fig. 3-133
IDMT1: tIref,P> elapsed 040 082 Fig. 3-133
IDMT1: Trip signal tIref,P> 040 084 Fig. 3-134
IDMT1: Hold time P running 040 053 Fig. 3-133
IDMT1: Memory P clear 040 110 Fig. 3-133
IDMT1: Starting Iref,neg> 040 107 Fig. 3-136
IDMT1: tIref,neg> elapsed 040 109 Fig. 3-136
IDMT1: Trip sig. tIref,neg> 040 108 Fig. 3-136
IDMT1: Hold time neg runn. 040 113 Fig. 3-136
IDMT1: Memory neg clear 040 111 Fig. 3-136
IDMT1: Starting Iref,N> 040 081 Fig. 3-138
IDMT1: tIref,N> elapsed 040 083 Fig. 3-138
IDMT1: Trip signal tIref,N> 040 085 Fig. 3-139
IDMT1: Hold time N running 040 054 Fig. 3-138
IDMT1: Memory N clear 040 112 Fig. 3-138
IDMT2: Block. tIref,P> EXT 040 136
Switch on to fault protection SOTF: Par. ARC running EXT 039 063 Fig. 3-152
SOTF: Enabled 040 069 Fig. 3-152
SOTF: tManual-close runn. 036 063 Fig. 3-152
SOTF: Trip signal 036 064 Fig. 3-152
Auto-reclosing control ARC: Reset counters EXT 005 244 Fig: 3-175,
Fig.*: 3-86
ARC: Enable EXT 037 010 Fig. 3-159
ARC: Disable EXT 037 011 Fig. 3-159
ARC: Test HSR A-B-C EXT 037 017 Fig. 3-173
ARC: Blocking EXT 036 050 Fig. 3-160
ARC: CB drive ready EXT 004 066 Fig. 3-161
ARC: Ext./user enabled 037 013 Fig. 3-159
ARC: Enabled 015 064 Fig. 3-159
ARC: Test HSR A-B-C 034 023 Fig. 3-173
ARC: Blocked 004 069 Fig. 3-160
ARC: Blocking trip 042 000 Fig. 3-170
ARC: Ready 004 068 Fig. 3-161
ARC: Not ready 037 008 Fig. 3-161
ARC: Reject test HSR 036 055 Fig. 3-173
ARC: Block. time running 037 004 Fig. 3-160
Automatic synchronism check ASC: Ext./user enabled 037 092 Fig. 3-177
ASC: Reset counters EXT 006 074 Fig.*: 3-86
ASC: Enable EXT 037 049 Fig. 3-177
ASC: Disable EXT 037 061 Fig. 3-177
ASC: Blocking EXT 037 048 Fig. 3-178
ASC: Test close requ. EXT 037 064 Fig. 3-179
ASC: Enabl.close requ.EXT 037 063 Fig. 3-179
ASC: Close request EXT 037 062 Fig. 3-179
ASC: Enabled 018 024 Fig. 3-177
ASC: Blocked 038 018 Fig. 3-178
ASC: Ready 037 079 Fig. 3-178
ASC: Not ready 037 082 Fig. 3-178
ASC: Test close request 034 019 Fig. 3-179
ASC: Close request 034 018 Fig. 3-179
ASC: Cycle running 038 019 Fig. 3-183
ASC: Operat.time running 037 093 Fig. 3-183
ASC: Close enable 037 083 Fig: 3-69,
3-181
ASC: Close enable,volt.ch 037 085 Fig. 3-181
ASC: Close enable,sync.ch 037 084 Fig. 3-182
ASC: Close rejection 037 086 Fig. 3-183
Ground fault direction GFDSS: Reset counters EXT 005 245 Fig.*: 3-86
determination using
steady-state values
GFDSS: GF (curr.) eval. EXT 038 020 Fig. 3-188
GFDSS: Enabled 042 096 Fig. 3-188
GFDSS: GF (pow.) ready 038 026 Fig. 3-188
GFDSS: GF (pow.) not ready 038 027 Fig. 3-188
GFDSS: GF (curr.) evaluat. 039 071 Fig. 3-188
GFDSS: GF (curr.) ready 038 028 Fig. 3-188
GFDSS: GF (curr.) not ready 038 029 Fig. 3-188
GFDSS: Admittance ready 038 167 Fig. 3-188
GFDSS: Admittance not ready 038 168 Fig. 3-188
GFDSS: Grd. fault pow./adm. 009 037 Fig: 3-190,
3-196
GFDSS: Forward / LS 009 035 Fig: 3-193,
3-199
GFDSS: Direct. backward/BS 009 036 Fig: 3-193,
3-199
GFDSS: Starting forward/LS 009 040 Fig: 3-193,
3-199
Transient ground fault TGFD: Blocking EXT 004 034 Fig. 3-202
direction determination
TGFD: Reset counters EXT 005 246 Fig. 3-208
TGFD: Reset signal EXT 004 140 Fig. 3-206
TGFD: Enabled 037 100 Fig. 3-202
TGFD: Ready 037 080 Fig. 3-202
TGFD: Not ready 037 081 Fig. 3-202
TGFD: Ground fault 004 033 Fig. 3-204
TGFD: Direct. determined 004 030 Fig. 3-205
TGFD: Forward / LS 004 031 Fig. 3-205
TGFD: Direct. backward/BS 004 032 Fig. 3-205
TGFD: Signals reset 004 141 Fig. 3-206
Thermal overload protection THERM: Therm.repl.block EXT 041 074 Fig. 3-223
THERM: Reset replica EXT 038 061 Fig. 3-224
THERM: Enabled 040 068 Fig. 3-219
THERM: Reset therm. replica 039 061 Fig. 3-224
THERM: Starting k*Iref> 041 108 Fig. 3-223
THERM: CTA error EXT 038 062 Fig. 3-221
THERM: Warning 039 025 Fig. 3-223
THERM: Trip signal 039 020 Fig. 3-223
THERM: Not ready 040 035 Fig. 3-220
THERM: Reclosure blocked 039 024
Time-voltage protection V<>: Blocking tV> EXT 041 068 Fig. 3-229
V<>: Blocking tV>> EXT 041 069 Fig. 3-229
V<>: Blocking tV< EXT 041 070 Fig. 3-230
V<>: Blocking tV<< EXT 041 071 Fig. 3-230
V<>: Blocking tVpos> EXT 041 090 Fig. 3-232
V<>: Blocking tVpos>> EXT 041 091 Fig. 3-232
V<>: Blocking tVpos< EXT 041 092 Fig. 3-232
V<>: Blocking tVpos<< EXT 041 093 Fig. 3-232
V<>: Blocking tVneg> EXT 041 094 Fig. 3-233
V<>: Blocking tVneg>> EXT 041 095 Fig. 3-233
V<>: Blocking tVNG> EXT 041 072 Fig. 3-235
V<>: Blocking tVNG>> EXT 041 073 Fig. 3-235
V<>: Enabled 040 066 Fig. 3-227
V<>: Ready 042 003 Fig. 3-227
V<>: Not ready 042 004 Fig. 3-227
V<>: Starting V>/>> A(-B) 041 031 Fig. 3-229
V<>: Starting V>/>> B(-C) 041 032 Fig. 3-229
V<>: Starting V>/>> C(-A) 041 033 Fig. 3-229
V<>: Starting V> 041 030 Fig. 3-229
V<>: Starting V> 3-pole 041 097 Fig. 3-229
V<>: Starting V>> 041 096 Fig. 3-229
V<>: tV> elapsed 041 034 Fig. 3-229
V<>: tV> 3-pole elapsed 041 098 Fig. 3-229
V<>: tV>> elapsed 041 035 Fig. 3-229
V<>: Starting V</<< A(-B) 041 038 Fig. 3-230
V<>: Starting V</<< B(-C) 041 039 Fig. 3-230
V<>: Starting V</<< C(-A) 041 040 Fig. 3-230
V<>: Starting V< 041 037 Fig. 3-230
V<>: Starting V< 3-pole 042 005 Fig. 3-230
V<>: Starting V<< 041 099 Fig. 3-230
V<>: tV< elapsed 041 041 Fig. 3-230
V<>: tV< elaps. transient 042 023 Fig. 3-230
V<>: Fault V< 041 110 Fig. 3-230
V<>: tV< 3-pole elapsed 042 006 Fig. 3-230
V<>: tV< 3p elaps. trans. 042 024 Fig. 3-230
V<>: Fault V< 3-pole 041 111 Fig. 3-230
V<>: tV<< elapsed 041 042 Fig. 3-230
V<>: tV<< elapsed trans. 042 025 Fig. 3-230
V<>: tV</<< elaps. trans. 042 007 Fig. 3-230
V<>: Fault V<< 041 112 Fig. 3-230
V<>: Starting Vpos> 042 010 Fig. 3-232
V<>: Starting Vpos>> 042 011 Fig. 3-232
V<>: tVpos> elapsed 042 012 Fig. 3-232
Circuit Breaker Failure f<>: Reset meas.val. EXT 006 075 Fig.*: 3-86
Protection
f<>: Blocking f1 EXT 042 103 Fig. 3-240
f<>: Blocking f2 EXT 042 104
Power directional protection P<>: Blocking tP> EXT 035 082 Fig. 3-243
P<>: Blocking tP>> EXT 035 083 Fig. 3-243
P<>: Blocking tQ> EXT 035 084 Fig. 3-245
P<>: Blocking tQ>> EXT 035 085 Fig. 3-245
P<>: Blocking tP< EXT 035 050 Fig. 3-247
P<>: Blocking tP<< EXT 035 051 Fig. 3-247
P<>: Blocking tQ< EXT 035 052 Fig. 3-250
P<>: Blocking tQ<< EXT 035 053 Fig. 3-250
P<>: Enabled 036 250 Fig. 3-241
P<>: Starting P> 035 086 Fig: 3-243, 3-
253
P<>: Starting P>> 035 089 Fig: 3-243,
3-253
P<>: Signal P> delayed 035 087 Fig. 3-243
P<>: Signal P>> delayed 035 090 Fig. 3-243
P<>: Trip signal P> 035 088 Fig. 3-244
P<>: Trip signal P>> 035 091 Fig. 3-244
P<>: Starting Q> 035 092 Fig: 3-245, 3-
254
P<>: Starting Q>> 035 095 Fig: 3-245,
3-254
P<>: Signal Q> delayed 035 093 Fig. 3-245
P<>: Signal Q>> delayed 035 096 Fig. 3-245
P<>: Trip signal Q> 035 094 Fig. 3-246
P<>: Trip signal Q>> 035 097 Fig. 3-246
P<>: Starting P< 035 054 Fig: 3-247,
3-248,3-253
P<>: Starting P<< 035 060 Fig: 3-247,
3-248,3-253
P<>: Signal P< delayed 035 055 Fig: 3-247,
3-248
P<>: Signal P<< delayed 035 061 Fig: 3-247,
3-248
P<>: tP< elapsed trans. 035 056 Fig: 3-247,
3-248
P<>: tP<< elapsed trans. 035 062 Fig: 3-247,
3-248
P<>: tP</tP<< elaps.trans 035 178 Fig. 3-247
P<>: Fault P< 035 057 Fig: 3-247,
3-249
P<>: Fault P<< 035 063 Fig. 3-247
P<>: Trip signal P< 035 058 Fig. 3-248
P<>: Trip signal P<< 035 064 Fig. 3-248
P<>: Trip signal P< trans 035 059 Fig. 3-248
P<>: Trip sig. P<< trans. 035 065 Fig. 3-248
P<>: Starting Q< 035 066 Fig: 3-250,
3-251,3-254
P<>: Starting Q<< 035 010 Fig: 3-250,
3-251,3-254
P<>: Signal Q< delayed 035 067 Fig: 3-250,
3-251
P<>: Signal Q<< delayed 035 011 Fig: 3-250,
3-251
P<>: tQ< elapsed trans. 035 068 Fig: 3-250,
3-251
P<>: tQ<< elapsed trans. 035 016 Fig: 3-250,
3-251
P<>: tQ</tQ<< elaps.trans 035 179 Fig. 3-250
P<>: Fault Q< 035 069 Fig: 3-250,
3-252
P<>: Fault Q<< 035 049 Fig. 3-250
Circuit Breaker Monitoring CBM: Reset meas.val. EXT 005 247 Fig.*: 3-86
CBM: Blocking EXT 044 128 Fig. 3-273
CBM: Enabled 044 130 Fig. 3-265
CBM: Cycle running A 044 205
External devices 01 to 10 DEV01: Open signal EXT 210 030 Fig: 3-296,
3-302
DEV02: Open signal EXT 210 080
Single-pole signals SIG_1: Signal S001 EXT 226 004 Fig. 3-310
SIG_1: Signal S002 EXT 226 012
Binary counts COUNT: Set counter 1 EXT 217 130 Fig. 3-312
COUNT: Transmit counts EXT 217 009 Fig. 3-312
COUNT: Reset EXT 217 004 Fig. 3-312
COUNT: Enabled 217 001 Fig. 3-312
COUNT: Transmit counts 217 010 Fig. 3-312
COUNT: Reset 217 005 Fig. 3-312
Setting the enable for changing values from the local control panel.
Status Events
Command to reset monitoring counters as listed below.
GSSE: Enroll. IEDs flags L 105 160
Bar with state bits for all GSSE inputs, showing if the respective GSSE
sending device has logged-on and is transmitting free of fault (input 1 to 16).
GSSE: Enroll. IEDs flags H 105 161
Bar with state bits for all GSSE inputs, showing if the respective GSSE
sending device has logged-on and is transmitting free of fault (input 17 to
32).
GSSE: Tx message counter 105 162
State of the continuous counter sequence for the message counter sent
with each GSSE.
GSSE: Tx last message 105 166
State of the continuous counter sequence for state changes sent with each
GSSE.
GSSE: No. reject. messages 105 167
Setting for which GSSE sending device the following statistics information is
to be displayed.
GSSE: IED receiv. messages 105 172
State of the continuous counter sequence for the message counter received
with each GSSE.
GSSE: IED Rx last message 105 174
State of the continuous counter sequence for state changes received with
each GSSE.
GSSE: IED missed messages 105 175
Number of GSSE received after the validity time period has elapsed. This
counter is reset by GSSE: Res e t counters .
Binary outputs OUTP: Reset latch. USER 021 009 Fig. 3-33
The output relay selected for testing is triggered for the duration of the set
time ( O U T P : H o l d - t i m e f o r t e s t ).
Setting the time period for which the selected output relay is triggered
during functional testing.
Measured data output MEASO: Reset output USER 037 116 Fig. 3-37
Main function MAIN: General reset USER 003 002 Fig. 3-85
The counters for counting close and trip commands are reset.
The display of active and reactive energy output and input is reset.
MAIN: Group reset 1 USER 005 253 Fig. 3-86
A 100 ms trip command is issued from the local control panel. This setting is
password-protected (see section entitled 'Password-Protected Control
Operations' in Chapter 6).
Note:
The command is only executed if the manual trip command has been
configured as trip command 1 or 2.
MAIN: Man. close cmd. USER 018 033 Fig. 3-69
A close command is issued from the local control panel for the set reclose
command time. This setting is password-protected (see section entitled
'Password-Protected Control Operations' in Chapter 6).
MAIN: Warm restart 003 039
A warm restart is carried out. The device functions as it does when the
power supply is turned on.
MAIN: Cold restart 000 085
Operating data recording OP_RC: Reset record. USER 100 001 Fig. 3-91
The operating data memory and the counter for operation signals are reset.
Monitoring signal recording MT_RC: Reset record. USER 003 008 Fig. 3-92
Overload recording OL_RC: Reset record. USER 100 003 Fig. 3-97
Ground fault recording GF_RC: Reset record. USER 100 000 Fig. 3-106
Fault recording is enabled from the local control panel for 500 ms.
FT_RC: Reset record. USER 003 006 Fig. 3-115
The auto-reclosing control function is enabled from the local control panel.
ARC: Disable USER 003 133 Fig. 3-159
The auto-reclosing control function is disabled from the local control panel.
ARC: Reset counters USER 003 005 Fig. 3-175
Automatic synchronism check ASC: Enable USER 003 136 Fig. 3-177
A close request is issued from the integrated local control panel. This will
trigger the ASC functional operation. No close command is transmitted to
the CB if the check of the ASC is positive. Only a signal is issued.
A close request is issued from the integrated local control panel. This will
trigger the ASC functional operation. A close command is transmitted to the
CB if the ASC check is positive.
This control action is password-protected (see section entitled 'Password-
Protected Control Operations' in Chapter 6).
Ground fault direction GFDSS: Reset counters USER 003 004 Fig: 3-195,
determination using 3-201
steady-state values
The counters for the ground fault direction determination function using
steady-state values are reset.
Transient ground fault TGFD: Reset signal USER 003 009 Fig. 3-206
direction determination
The direction decisions can be reset while the buffer time is elapsing.
TGFD: Reset counters USER 003 022 Fig. 3-208
The counters for the transient ground fault direction determination function
are reset.
Motor protection MP: Reset replica USER 022 073 Fig. 3-217
In order to set the default value for the operating hours, this parameter
should be set to 'execute'.
MP: Init. val. Hours_Run 025 154
Thermal overload protection THERM: Reset replica USER 022 061 Fig. 3-224
protection
Resetting the measured event values f<> : m a x. fre qu . for f> and
f < > : m in . f r e qu . for f< .
Protection
Circuit breaker failure protection is enabled from the local control panel.
CBF: Disable USER 003 015 Fig. 3-255
Circuit breaker failure protection is disabled from the local control panel.
Circuit Breaker Monitoring CBM: Initialize values 003 011 Fig. 3-270
Set the limit values for the ruptured currents and their squares. (An alarm is
displayed if these limit values are exceeded.)
Binary counts COUNT: Transmit counts USER 217 008 Fig. 3-312
Count transmission.
COUNT: Reset USER 217 003 Fig. 3-312
Count reset.
Operating data recording OP_RC: Operat. data record. 003 024 Fig. 3-91
Monitoring signal recording MT_RC: Mon. signal record. 003 001 Fig. 3-92
8.2 Events
Main function MAIN: No. general start. 004 000 Fig. 3-74
Setting the maximum number of CB operations for an ARC cycle (or for a
limited time period).
MAIN: No. gen.trip cmds. 1 004 006 Fig. 3-78
Number of times external devices with direct motor control are activated
during the monitoring time.
MAIN: No.overfl.act.en.out 009 090 Fig. 3-59
Counter for the number of times the measuring range of the active energy
output was exceeded.
MAIN: No.overfl.act.en.inp 009 091 Fig. 3-59
Counter for the number of times the measuring range of the active energy
input was exceeded.
MAIN: No.ov/fl.reac.en.out 009 092 Fig. 3-59
Counter for the number of times the measuring range of the reactive energy
output was exceeded.
MAIN: No.ov/fl.reac.en.inp 009 093 Fig. 3-59
Counter for the number of times the measuring range of the reactive energy
input was exceeded.
Operating data recording OP_RC: No. oper. data sig. 100 002 Fig. 3-91
Monitoring signal recording MT_RC: No. monit. signals 004 019 Fig. 3-92
Ground fault recording GF_RC: No. ground faults 004 100 Fig. 3-105
Number of faults.
FT_RC: No. system disturb. 004 010 Fig. 3-114
Auto-reclosing control ARC: Number HSR A-B-C 004 007 Fig. 3-175
Automatic synchronism check ASC: No. RC aft. man.clos 004 009 Fig. 3-187
Ground fault direction GFDSS: No. GF power/admitt. 009 002 Fig. 3-201
determination using
steady-state values
Number of ground faults detected by steady-state power evaluation.
GFDSS: No. GF (curr. meas) 009 003 Fig. 3-195
Circuit Breaker Monitoring CBM: No. of CB oper. A 008 011 Fig. 3-270
CBM: No. of CB oper. B 008 012 Fig. 3-272
CBM: No. of CB oper. C 008 013 Fig. 3-272
Overload data acquisition OL_DA: Overload duration 004 102 Fig. 3-93
Display of the load current used by the thermal overload protection function
to calculate the tripping time.
If, on the other hand, the coolant temperature and the maximum permissible
coolant temperature have been set to the same value, then the coolant
temperature is not taken into account and the characteristic is a function of
the current only. The additional reserve amounts to zero in this case.
Ground fault data acquisition GF_DA: Ground flt. duration 009 100 Fig. 3-98
Display of the ground fault duration of the most recent ground fault.
GF_DA: GF duration pow.meas 009 024 Fig. 3-99
Display of the ground fault duration of the most recent ground fault as
determined by the steady-state power evaluation feature of the ground fault
direction determination function.
GF_DA: Voltage VNG p.u. 009 020 Fig: 3-100,
3-104
Display of the neutral-point displacement voltage of the most recent ground
fault referred to Vnom.
Note:
This display is only active when the steady-state power evaluation mode of
the GFDSS ground fault direction determination function is enabled.
GF_DA: Current IN p.u. 009 021 Fig: 3-100, 3-
102,3-104
Display of the residual current of the most recent ground fault referred to
IN,nom.
Note:
This display is only active when the ground fault direction determination
function using steady state values (GFDSS) is enabled.
GF_DA: Current IN,act p.u. 009 022 Fig. 3-100
Display of the active component of the residual current of the most recent
ground fault referred to IN,nom.
Note:
This display is only active when the steady-state power evaluation mode of
the GFDSS ground fault direction determination function is enabled.
Display of the reactive component of the residual current of the most recent
ground fault referred to IN,nom.
Note:
This display is only active when the steady-state power evaluation mode of
the GFDSS ground fault direction determination function is enabled.
GF_DA: GF durat. curr.meas. 009 026 Fig. 3-101
Display of the ground fault duration of the most recent ground fault as
determined by the steady-state current evaluation feature of the ground fault
direction determination function.
GF_DA: Curr. IN filt. p.u. 009 025 Fig. 3-102
Display of the residual current component having the set filter frequency for
the most recent ground fault (referred to IN,nom).
GF_DA: GF duration admitt. 009 068 Fig. 3-103
Display of the ground fault duration of the most recent ground fault as
determined by the admittance evaluation mode of the ground fault direction
determination function.
GF_DA: Admittance Y(N) p.u. 009 065 Fig. 3-104
Fault data acquisition FT_DA: Fault duration 008 010 Fig. 3-107
Display of the load impedance (in Ω) after the general starting condition of
time-overcurrent protection has ended.
The display only appears if the fault has been detected by the fault data
acquisition function of the P139.
FT_DA: Load angle post-flt. 004 038 Fig. 3-113
Display of the load angle (in degrees) after the general starting condition of
time-overcurrent protection has ended.
The display only appears if the fault has been detected by the fault data
acquisition function of the P139.
FT_DA: Resid.curr. post-flt 004 039 Fig. 3-113
Display of the residual current referred to Inom after the general starting
condition of time-overcurrent protection has ended.
The display only appears if the fault has been detected by the fault data
acquisition function of the P139.
Automatic synchronism check ASC: Voltage Vref 004 087 Fig. 3-186
ASC: Volt. sel. meas.loop 004 088 Fig. 3-186
ASC: Volt. magnit. diff. 004 091 Fig: 3-182,
3-186
Display of the difference between amplitudes of the measurement loop
voltage and the reference voltage during a close request, referred to Vnom.
The display only appears if ASC is operating.
ASC: Angle difference 004 089 Fig: 3-182,
3-186
Display of the difference between angles (in degrees) of the measurement
loop voltage and the reference voltage during a close request.
The display only appears if ASC is operating.
ASC: Frequ. difference 004 090 Fig: 3-182,
3-186
Display of the difference between frequencies (in Hz) of the measurement
loop voltage and the reference voltage during a close request.
The display only appears if ASC is operating.
protection
Maximum frequency during an overfrequency condition.
f<>: Min. frequ. for f< 005 001
Ground fault recording GF_RC: Ground flt.record. 1 033 010 Fig. 3-106
GF_RC: Ground flt.record. 2 033 011 Fig. 3-106
GF_RC: Ground flt.record. 3 033 012 Fig. 3-106
GF_RC: Ground flt.record. 4 033 013 Fig. 3-106
GF_RC: Ground flt.record. 5 033 014 Fig. 3-106
GF_RC: Ground flt.record. 6 033 015 Fig. 3-106
GF_RC: Ground flt.record. 7 033 016 Fig. 3-106
GF_RC: Ground flt.record. 8 033 017 Fig. 3-106
9 Commissioning
Only qualified personnel, familiar with the "Warning" page at the beginning of this
manual, may work on or operate this device.
When installing and connecting the device the warning notices at the beginning of
Chapter 5 must be observed.
The device must be reliably grounded before auxiliary voltage is turned on.
The surface-mounted case is grounded using the bolt and nut, appropriately marked, as
the ground connection. The flush-mounted case must be grounded in the area of the
rear sidepieces at the location provided. The cross-section of the ground conductor must
conform to applicable national standards. A minimum cross section of 2.5 mm2 is
required.
In addition, a protective ground connection at the terminal contact on the power supply
module (identified by the letters "PE" on the terminal connection diagram) is also
required for proper operation of the device. The cross-section of this ground conductor
must also conform to applicable national standards. A minimum cross section of
1.5 mm2 is required.
Before working on the device itself or in the space where the device is connected, always
disconnect the device from the supply.
The secondary circuit of live system current transformers must not be opened! If the
secondary circuit of a live CT is opened, there is the danger that the resulting voltages
will endanger personnel and damage the insulation.
The threaded terminal block for connection to the current transformers is not a shorting
block. Therefore always short-circuit current transformers before loosening the threaded
terminals.
The power supply must be turned off for at least 5 s before power supply module V is
removed. Otherwise there is the danger of an electric shock.
When increased-safety machinery is located in a hazardous area the P139 must always
be installed outside of this hazardous area.
The fiber-optic interface may only be connected or disconnected when the supply voltage
for the device is shut off.
The PC interface is not designed for permanent connection. Consequently, the female
connector does not have the extra insulation from circuits connected to the system that is
required per VDE 0106 Part 101. Therefore, when connecting the prescribed connecting
cable be careful not to touch the socket contacts.
Application of analog signals to the measuring inputs must be in compliance with the
maximum permissible rating of the measuring inputs (see chapter entitled 'Technical
Data')
When using the programmable logic (function group LOGIC), the user must carry out a
functional type test to conform to the requirements of the relevant protection/control
application. In particular, it is necessary to verify that the requirements for the
implementation of logic linking (by setting) as well as the time performance during device
startup, during operation and when there is a fault (device blocking) are fulfilled.
Preparation
After the P139 has been installed and connected as described in Chapter 5, the
commissioning procedure can begin.
Before turning on the power supply voltage, the following items must be checked again:
After the wiring work is completed, check the system to make sure it is properly isolated.
The conditions given in VDE 0100 must be satisfied.
Once all checks have been made, the power supply voltage may be turned on. After
voltage has been applied, the device starts up. During startup, various startup tests are
carried out (see Chapter 3, ‘Self-Monitoring’). The LED indicators for ‘Operation’ (H1)
and ‘Blocked/Faulty’ (H2) will light up. After approximately 15 s, the P139 is ready for
operation. By default (factory setting) or after a cold restart, the device type “P139 ” and
the time are displayed on the first line of the LCD after the device has started up. If a
bay type has already been selected this bay will then be shown as a single-pole display.
Once the change enabling command has been issued (see Chapter 6, ‘Enabling
Parameter Changes’), all settings can be entered. The procedure for entering settings
from the integrated local control panel is described in Chapter 6.
After pressing the ENTER key to confirm the setting parameter 'Type of bay'
the signal 'Bay initialization' is displayed on the LCD for a time duration of
20 s. The LED indicator labeled EDIT MODE will light up. A control action is
not possible during this time period.
If either the PC interface or the communication interface will be used for setting the P139
and reading out event records, then the following settings must first be made from the
integrated local control panel.
‘Par/DvID/’ folder:
DVICE: Device password 1
DVICE: Device password 2
‘Par/Conf/’ folder:
PC: Name of manufacturer
PC: Bay address
PC: Device address
PC: Baud rate
PC: Parity bit
COMM1: Function group COMM1
COMM1: General enable USER
COMM1: Name of manufacturer
COMM1: Line idle state
COMM1: Baud rate
COMM1: Parity bit
COMM1: Communicat. protocol
COMM1: Octet comm. address
COMM1: Octet address ASDU
COMM2: Function group COMM2
COMM2: General enable USER
COMM2: Name of manufacturer
COMM2: Line idle state
COMM2: Baud rate
COMM2: Parity bit
COMM2: Octet comm. address
COMM2: Octet address ASDU
COMM3: Function group COMM3
COMM3: General enable USER
COMM3: Baud rate
‘Par/Func/Glob/’ folder:
PC: Command blocking
PC: Sig./meas.val.block.
COMM1: Command blocking
COMM1: Sig./meas.block.USER
COMM2: Command blocking
COMM2: Sig./meas.block.USER
Note: The settings given above apply to the IEC 60870-5-103 communication
protocol. If another protocol is being used for the communication interface,
additional settings may be necessary. See Chapter 7 for further details.
After the settings have been made, the following checks should be carried out again
before the blocking is cancelled:
M A I N : D e v i c e o n - l i n e 'Yes' (on)'
Tests
By using the signals and displays generated by the P139, it is possible to determine
whether the P139 is correctly set and properly interconnected with the station. Signals
are signaled by output relays and LED indicators and entered into the event memory. In
addition, the signals can be checked by selecting the appropriate signal in the menu
tree.
If the user does not wish the circuit breaker to operate during protection testing, the trip
commands can be blocked through M A I N : T r i p c m d . b l o c k . U S E R
('Par/Func/Glob' folder) or an appropriately configured binary signal input. If circuit
breaker testing is desired, it is possible to issue a trip command for 100 ms through
M A I N : M a n . T r i p c m d . U S E R (‘Oper/CtrlTest’ folder) or an appropriately
configured binary signal input. Selection of the trip command from the integrated local
control panel is password-protected (see Chapter 6, "Password-Protected Control
Operations").
Note: The manual trip command is only executed if it has been configured for trip
command 1 or trip command 2.
If the P139 is connected at substation control level, the user is advised to activate the
test mode via M A I N : T e s t m o d e U S E R (folder ‘Par/Func/Glob’) or an
appropriately configured binary signal input. The telegrams are then identified
accordingly (reason for transmission: test mode).
This display appears regardless of the binary signal input mode selected.
Before starting the test, open any triggering circuits for external devices so that no
inadvertent switching operations will take place.
Application of analog test values to the measuring inputs must be in compliance with the
maximum permissible rating of the measuring inputs (see Chapter 'Technical Data').
When checking the time-overcurrent protection function with a testing device the
measuring-circuit monitoring function must be disabled at
(M C M O N : G e n e r a l e n a b l e U S E R , ‘Par/Func/Main’ folder), as this protection will
always be triggered – depending on the setting – and error messages will be issued.
Checking the correct
phase connection of
current and voltage
transformers with load
current
The user can check to make sure connection to the system’s current and voltage
transformers involves the correct phase by consulting the operating data displays for
load angle (M A I N : L o a d a n g l e p h i A , M A I N : L o a d a n g l e p h i B , and
M A I N : L o a d a n g l e p h i C in the ‘Oper/Cycl/Meas/’ folder). In this test it is required
that the connection 'Standard' has been made according to the standard schematic
connection diagram shown in Chapter 'Installation and Connection' and that the
parameter at M A I N : C o n n . m e a s . c i r c . I P (‘Par/Funk/Glob’ folder) is set to
'Standard'. If there is only an ohmic (resistive) load then the load angles for all three
phases toward the line must come to approximately 0°. The load angles are only
determined if at least 5% of the nominal device current is flowing.
The selected phase sequence (alternative terminology: Rotary field) must match the
actual phase sequence. If there is only an ohmic (resistive) load then angle ϕN must
take on the following values (depending whether the energy flow is towards the line or
towards the busbar):
The DTOC function is activated. This can be determined by checking logic state
signal D T O C : E n a b l e d (‘Oper/Cycl/Log/’ folder).
The function at M A I N : B l o c k t i m . s t . I N , n e g must be set to 'No'
(‘Par/Func/Main/’ folder).
The function at M A I N : G e n . s t a r t i n g m o d e is to be set to 'with start. IN, Ineg'
(‘Par/Func/Main/’ folder).
The short-circuit direction determination function must be disabled.
S C D D : G e n e r a l e n a b l e U S E R is to be set to ‘No’ (‘Par/Func/Main/’ folder).
By injecting appropriate analog test values at the current measuring inputs it is possible
to check the overcurrent stages and their associated timer stages.
Application of analog test values to the measuring inputs must be in compliance with the
maximum permissible rating of the measuring inputs (see Chapter 'Technical Data').
The IDMT function is activated. This can be determined by checking logic state
signal I D M T : E n a b l e d (‘Oper/Cycl/Log/’ folder).
The function at M A I N : B l o c k t i m . s t . I N , n e g must be set to 'No'
(‘Par/Func/Main/’ folder).
The function at M A I N : G e n . s t a r t i n g m o d e is to be set to 'with start. IN, Ineg'
(‘Par/Func/Main/’ folder).
The short-circuit direction determination function must be disabled.
S C D D : G e n e r a l e n a b l e U S E R is to be set to ‘No’ (‘Par/Func/Main/’ folder).
By injecting appropriate analog test values at the current measuring inputs it is possible
to check the overcurrent stages and their associated timer stages.
Application of analog test values to the measuring inputs must be in compliance with the
maximum permissible rating of the measuring inputs (see Chapter 'Technical Data').
Tripping times issued by the inverse-time maximum current protection, and dependant
on the tripping characteristic selected, are given in the following table:
The short-circuit direction determination function must be activated (see Chapter 3).
All phase currents exceed 0.1 Inom.
At least two phase-to-phase voltages exceed 200 mV.
The directions for short-circuit direction determination are set to ‘forward'.
When the connection 'Standard' has been made according to the standard schematic
connection diagram shown in Chapter 'Installation and Connection' and the parameter at
M A I N : C o n n . m e a s . c i r c . I N is also set to 'Standard', then measurement of the
short-circuit direction determination is towards the line. The selected phase sequence
(alternative terminology: Rotary field) must match the actual phase sequence. Now the
various fault types may simulated with the appropriate starting by the DTOC and IDMT
protection by connecting different short-circuit wiring (e.g. Phase A to N). Trip signals
issued by the phase current stages are now directional.
Short-Circuit Direction
Determination: Checking
the direction of the residual
current stages
A test of the residual current stages, used with short-circuit direction determination, can
only be carried out when the following conditions are met:
The short-circuit direction determination function must be activated (see Chapter 3).
The residual current calculated must exceed 0.01 Inom.
The neutral-point displacement voltage must exceed the trigger value set at
SCDD: VNG>.
When the connection 'Standard' has been made according to the standard schematic
connection diagram shown in Chapter 'Installation and Connection' and the parameter at
M A I N : C o n n . m e a s . c i r c . I N is also set to 'Standard', then measurement of the
short-circuit direction determination is towards the line. The selected phase sequence
(alternative terminology: Rotary field) must match the actual phase sequence. Now the
various fault types may simulated as described above in the paragraph 'Checking
direction of the phase current stages'. Trip signals issued by the residual current stages
are now directional.
Checking protective
signaling
The protective signaling function can only be tested if protective signaling is ready. This
can be determined by checking logic state signal P S I G : R e a d y (‘Oper/Cycl/Log/’
folder).
If protective signaling is not ready, this may be due to the following reasons:
If conditions for a test are met it is possible to generate, for testing purposes, a 'test
send' signal from the integrated local control panel (P S I G : T e s t t e l e c o m . U S E R )
This pulse will be present for 1 s and is extended for the set reset time. The generated
'test send' signal may be checked at the logic state signal
PSIG: Send (transm.relay).
If the ARC function is not ready, this may be due to the following reasons:
A test HSR can be executed for testing purposes from the integrated local control panel
or by triggering a binary signal input. The test HSR function first issues a trip command
and then issues a reclose command after the set dead time has elapsed.
Application of analog test values to the measuring inputs must be in compliance with the
maximum permissible rating of the measuring inputs (see Chapter 'Technical Data').
Before the motor protection can be tested the thermal replica must always be cleared.
Clearing the thermal replica is done by short term disabling of the protection by setting
M A I N : D e v i c e o n - l i n e to 'No' (off) ('Par/FuncGlob/’ folder). The actual status of
the thermal replica may be read out from the operating data display at
M P : T h e r m . r e p l . b u f f e r M P ('Oper/Cycl/Meas/' folder). Because the
characteristic curve is settable, there can be different tripping times:
With the thermal replica cleared an applied test current is abruptly changed from 0
(≡ machine stopped) to a value ≥ to the setting of M P : t I S t U p > P S x , in the
'Par/Func/Main/' folder (≡ machine starting up):
36
reciprocally squared characteristic curve: t = t 6 I ⋅
ref
(I I ref )2
Application of analog test values to the measuring inputs must be in compliance with the
maximum permissible rating of the measuring inputs (see Chapter 'Technical Data').
Before the thermal overload protection can be tested the thermal replica must always be
cleared. Clearing the thermal replica is done by short term disabling of the protection by
setting M A I N : D e v i c e o n - l i n e to 'No' (off) ('Par/FuncGlob/’ folder). The actual
status of the thermal replica may be read out from the operating data display at
T H E R M : S t a t u s T H E R M r e p l i c a ('Oper/Cycl/Meas/' folder). The tripping time
may be checked:
With the thermal replica cleared an applied test current is abruptly changed from 0 to the
value ≥ 0.1 Iref
2
⎛ I ⎞
⎜⎜ ⎟ − ΘP
⎝ Iref ⎟⎠
t = τ ⋅ ln 2
⎛ I ⎞ ⎛ Θa − Θa,max ⎞
⎜⎜ ⎟⎟ − Θoff ⋅ ⎜1 − ⎟
⎜ ⎟
⎝ I ref ⎠ ⎝ Θmax − Θa,max ⎠
Application of analog test values to the measuring inputs must be in compliance with the
maximum permissible rating of the measuring inputs (see Chapter 'Technical Data').
By injecting appropriate analog test values at the voltage measuring inputs it is possible
to check the overvoltage and undervoltage stages as well as their associated timer
stages.
The P139 calculates the neutral-point displacement voltage from the analog test values
at the voltage measuring inputs according to below formula:
1
V N −G = ⋅ V A −G + V B−G + V C −G
3
In the case of a single-phase test setup using |VB-G| = |VC-G| = 0, the result of the
calculation formula for VN-G given above is that the triggers VN G > and VN G > > operate
when the test voltage exceeds the following value:
Vnom
V test = 3 ⋅ VNG > ⋅
3
VNG > : Setting V<>: VNG> and U<>: VNG>>
Application of analog test values to the measuring inputs must be in compliance with the
maximum permissible rating of the measuring inputs (see Chapter 'Technical Data').
Should the system permit such operation a ground fault on the busbar side (BS) or on
the line side (LS) may be simulated by wiring a short circuit. Then the P139 must issue
the respective signal. With the operating mode for ground faults set to 'Steady-state
power' it is assumed that threshold values for residual current (set at
G F D S S : I N , a c t > / r e a c > B S P S x and G F D S S : I N , a c t > / r e a c > L S P S x )
and the neutral-point displacement voltage with 'Steady-state admittance' evaluation (set
at G F D S S : V N G > ) or G F D S S : I N are exceeded. With the operating mode set
to 'Steady-state admittance' the set threshold values for conductance / susceptance (set
at G F D S S : G ( N ) > / B ( N ) > B S and G F D S S : G ( N ) > / B ( N ) > L S ) and the
neutral-point displacement voltage (G F D S S : V N G > ) or the admittance
(G F D S S : Y ( N ) > must be exceeded.
A ground fault functional test by wiring a short circuit is, in most cases, not possible as
there is the danger of a double ground fault occurring. As an alternative it is possible to
wire the system’s CTs and VTs such that a functional test is possible without causing a
ground fault.
The residual current and the neutral-point displacement voltage measured by the P139
are displayed as measured operating values in primary quantities referred to the nominal
quantities of the Protection & Control device (see 'Measured Operating Data').
If current is measured at a Holmgreen group the secondary side of the phase A line
current transformer must be disconnected and shorted (see figure 9-2).
9-2 Ancillary circuit for systems with ground fault compensation and Holmgreen group, ground fault towards BS
A test-wire is inserted through the core balance current transformer to obtain a current
flow from the phase B line (see figure 9-3). The ancillary circuit figures include vector
diagrams displaying the position of current and voltage vectors.
A simulated ground fault on the busbar is displayed in the example. The current
connections or the voltage connections must be exchanged to test a ground fault on the
line side.
A
B BS
C
VNG
VA-G
VC-G VB-G
V -G
VB-G
19Z5291A_EN
9-3 Ancillary circuit for systems with ground fault compensation and core balance current transformer, ground fault towards BS
9-4 Ancillary circuit for isolated neutral-point systems and Holmgreen group, ground fault towards LS
A test-wire is inserted through the core balance current transformer to obtain current flow
from the phase B and C lines (see figure 9-5). The ancillary circuit figures include vector
diagrams displaying the position of current and voltage vectors.
A simulated ground fault on the line side is displayed in the example. The current
connections or the voltage connections must be exchanged to test a ground fault on the
busbar side.
A
B BS
C
VNG
VA-G
B-C N
VC-G VB-G
VN-G
VB-G
19Z5292A_EN
9-5 Ancillary circuit for isolated neutral-point systems and core balance current transformers, ground fault towards LS
Checking Control
Functions
The selected bay type is displayed on the Bay Panel. The selection of the Bay Panel is
described in the Chapter 6. The current switching state of the switchgear units is
displayed on the Bay Panel if state signals from such switching devices are connected
properly to binary signal inputs on the P139. Should the switching state not be displayed
correctly then it can be determined by checking the physical state of binary signal inputs
whether the state signals are presented correctly to the P139 (check at parameter
I N P : S t a t e U x x x x ‘Oper/Cycl/Phys’ folder).
Local/Remote selection
Controlling switchgear units may be carried out from keys on the local control panel,
remotely via the communication interface or through appropriately configured binary
signal inputs. The control site – Local or Remote – is selected by the L/R key on the
local control panel or by an appropriately configured binary signal input. The L/R key
has no effect when a binary signal input has been configured. Using the L/R key on the
local control panel to switch from 'Remote' to 'Local' is only possible after the 'Password
L/R' was entered (see Chapter 6 for further information). The Bay Panel display will
show which control site has been selected.
Local control
The switchgear unit to be controlled is selected by pressing the selection key on the local
control panel, and pressing the 'Open' or 'Close' key will generate a switching request.
When control is carried out with binary signal inputs the respective binary signal input is
to be triggered.
Remote control
Remote control of switchgear units may be carried out via the communication interface
or with appropriately configured binary signal inputs.
Completing
commissioning
Before the P139 is released for operation, the user should make sure that the following
steps have been taken:
After completion of commissioning, only the green LED indicator signaling ‘Operation’
(H1) should be on.
10 Troubleshooting
This chapter describes problems that might be encountered, their causes, and possible
methods for eliminating them. It is intended as a general orientation only, and in cases
of doubt it is better to return the P139 to the manufacturer. Please follow the packaging
instructions in the section entitled "Unpacking and Packing" in Chapter 5 when returning
equipment to the manufacturer.
Problem:
Only qualified personnel, familiar with the "Warning" page at the beginning of this
manual, may work on or operate this device.
Before checking further, disconnect the P139 from the power supply.
Check to make sure that fuse F1 on power supply module V is not fused.
If the fuse is defective, it should not be replaced without determining the cause of
failure. If a fuse is replaced without eliminating the problem, there is the danger
that the damage will spread.
Required fuses:
Identify the specific problem by reading out the monitoring signal memory (see
section "Monitoring Signal Memory Readout" in Chapter 6). The table below lists
possible monitoring or warning indications (provided that a configuration setting has
been entered at S F M O N : F c t . a s s i g n . w a r n i n g ) , the faulty area, the P139's
response, and the mode of the output relay configured for 'Warning' and
'Blocked/faulty'.
SFMON: Warning (LED) 036 070
Key:
-: No reaction and/or no output relay triggered.
Updating: The output relay configured for 'Warning' starts only if the monitoring
signal is still present.
1)
: The 'Blocked/faulty' output relay only operates if the signal has been
configured at M A I N : F c t . a s s i g n m . w a r n i n g .
2)
: The 'Warning' output relay only operates if the signal has been
configured at S F M O N : F c t . a s s i g n m . w a r n i n g .
SFMON: Cold restart 093 024
A cold restart has been carried out on account of a checksum error in the
memory (NOVRAM).
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay: Yes / Yes
'Blocked/faulty' output relay: Yes / Yes
SFMON: Cold rest./SW update 093 025
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay: Yes / Yes
'Blocked/faulty' output relay: Yes / Yes
SFMON: Blocking/ HW failure 090 019
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay: Yes / Yes
'Blocked/faulty' output relay: Yes / Yes
SFMON: Invalid type of bay 096 122
If the user has selected a bay type that requires a P139 hardware
configuration that is not actually fitted, then this signal is generated.
The +15 V internal supply voltage has dropped below a minimum value.
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay: Yes / Yes
'Blocked/faulty' output relay: Yes / Yes
SFMON: +24V supply faulty 093 082
The +24 V internal supply voltage has dropped below a minimum value.
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay: Yes / Yes
'Blocked/faulty' output relay: Yes / Yes
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay: Yes / Yes
'Blocked/faulty' output relay: Yes / Yes
SFMON: Wrong module slot 1 096 100
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay: Yes / Yes
'Blocked/faulty' output relay: Yes / Yes
SFMON: Defect.module slot 1 097 000
The +15 V internal supply voltage of the transient ground fault evaluation
module has dropped below a minimum value.
The -15 V internal supply voltage of the transient ground fault evaluation
module has dropped below a minimum value.
The checksum feature of the transient ground fault evaluation module has
detected a fault in the data transmission of the Dual-Port-RAM.
Fault in the program or data memory of the transient ground fault evaluation
module.
The checksum feature of analog I/O module Y has detected a fault in the
data transmission of the Dual-Port-RAM.
The checksum feature of analog module (RTD) has detected a fault in the
data transmission of the Dual-Port-RAM.
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay: Yes / Yes
'Blocked/faulty' output relay: Yes / Yes
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay: Yes / Yes
'Blocked/faulty' output relay: Yes / Yes
SFMON: Undefined interrupt 093 012
Undefined interrupt.
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay: Yes / Yes
'Blocked/faulty' output relay: Yes / Yes
SFMON: Exception oper.syst. 093 013
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay: Yes / Yes
'Blocked/faulty' output relay: Yes / Yes
SFMON: Protection failure 090 021
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay: Yes / Yes
'Blocked/faulty' output relay: Yes / Yes
SFMON: Checksum error param 090 003
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay: Yes / Yes
'Blocked/faulty' output relay: Yes / Yes
SFMON: Clock sync. error 093 041
Faulty test pattern in the RAM. This can occur, for example, if the processor
module or the power supply module is removed from the bus module
(digital). This fault is only detected during device startup. After the fault is
detected, the software initializes the RAM. This means that all records are
deleted.
Software overloaded.
Incorrect or invalid software for transient ground fault evaluation module has
been downloaded.
Incorrect or invalid software for analog I/O module Y has been downloaded.
Watchdog is monitoring the periodic status signal of the analog I/O module
Y. It has detected an error.
The fuse failure monitoring function has detected a fault in the reference
voltage-measuring circuit.
The maximum sum of the disconnection current values to the second power
has been exceeded.
The maximum duration for the opening of a CB pole has been exceeded.
Disconnection is not determined for this CB pole.
The plausibility logic was triggered during the acquisition of the circuit
breaker's (CB) status signals.
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay: Yes / Yes
'Blocked/faulty' output relay: Yes / Yes
SFMON: Invalid SW vers. DSP 093 128
Incorrect or invalid software has been downloaded for the DSP co-
processor.
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay: Yes / Yes
'Blocked/faulty' output relay: Yes / Yes
SFMON: Fcts.not perm.f.60Hz 093 098
A protective function has been activated that is not permitted for operation
at a system frequency of 60 Hz.
An invalid characteristic has been set for the BCD output channel of analog
I/O module Y.
An invalid characteristic has been set for one of the analog output channels
of analog I/O module Y.
An invalid characteristic has been set for the analog input channel of analog
I/O module Y.
The P139 has detected an open circuit in the connection of the resistance
thermometer "PT100" to the analog I/O module Y.
The P139 has detected an open circuit in the connection of the 20 mA input.
The function was configured to a binary signal input on the analog I/O
module Y. Such a configuration is not permitted for this function.
11 Maintenance
Only qualified personnel, familiar with the "Warning" page at the beginning of this
manual, may work on or operate this device.
The P139 is a low-maintenance device. The components used in the units are selected
to meet exacting requirements. Recalibration is not necessary.
Maintenance procedures in
the power supply area
Electrolytic capacitors are installed in the power supply area because of dimensioning
requirements. The useful life of these capacitors is significant from a maintenance
standpoint. When the equipment is operated continuously at the upper limit of the
recommended temperature range (+55°C or 131°F), the useful life of these components
is 80,000 hours, or more than 9 years. Under these conditions, replacement of the
electrolytic capacitors is recommended after a period of 8 to 10 years. When the
operating temperatures are approx. +45°C inside the devices, the required maintenance
interval can be increased by about 1 year.
The P139 is equipped with a lithium battery for non-volatile storage of fault data and for
keeping the internal clock running in the event of failure of the auxiliary power supply.
Loss of capacity due to module-internal self-discharging amounts to less than 1% per
year over a period of availability of 10 years. Since the terminal voltage remains virtually
constant until capacity is exhausted, usefulness is maintained until a very low residual
capacity is reached. With a nominal capacity of 850 mAh and discharge currents of only
a few µA during device storage or in the range of the self-discharge current during
device operation, the result is a correspondingly long service life. It is therefore
recommended that the lithium battery only be replaced after the maintenance interval
cited above.
Always turn off the power (supply voltage) before removing a hardware module.
The power supply must be turned off for at least 5 s before power supply module V is
removed. Otherwise there is the danger of an electric shock.
Electrolytic capacitor:
on power supply module V.
Lithium battery:
on power supply module V.
There is a danger of explosion if the electrolytic capacitor and battery are not properly
replaced. Always check to make sure that the polarity of the electrolytic capacitor and
the battery is correct.
After the maintenance procedures described above have been completed, new
commissioning tests as described in Chapter 9 must be carried out.
The P139 incorporates in its system a very extensive self-monitoring function for
hardware and software. The internal structure guarantees, for example, that
communication within the processor system will be checked on a continuing basis.
Nonetheless, there are a number of subfunctions that cannot be checked by the self-
monitoring feature without injection testing from the device terminals. The respective
device-specific properties and settings must be observed in such cases.
In particular, none of the control and signaling circuits that are run to the device from the
outside are checked by the self-monitoring function.
The best way to carry out a static test of the analog input circuits is to check the primary
measured operating data using the operating data measurement function or to use a
suitable testing instrument. A "small" measured value (such as the nominal current in
the current path) and a "large" measured value (such as the nominal voltage in the
voltage path) should be used to check the measuring range of the A/D converter. This
makes it possible to check the entire dynamic range.
In addition, a dynamic test can be used to check transmission performance and the
phase relation of the current transformers and the anti-aliasing filter. This can best be
done by measuring the trigger point of the first zone when there is a two-phase
ungrounded fault. For this test, the value of the short-circuit current should be such that
a loop voltage of approximately 2 V is obtained at the device's terminals with the set
impedance. Furthermore, a suitable testing instrument that correctly replicates the two-
phase ungrounded fault should be used for this purpose.
This dynamic test is not absolutely necessary, since it only checks the stability of a few
less passive components. Based on reliability analysis, the statistical expectation is that
only one component in 10 years in 1000 devices will be outside the tolerance range.
Additional analog testing of such factors as the impedance characteristic or the starting
characteristic is not necessary, in our opinion, since information processing is completely
digital and is based on the measured analog current and voltage values. Proper
operation was checked in conjunction with type testing.
Binary outputs
With respect to binary outputs, the integrated self-monitoring function includes even two-
phase triggering of the relay coils of all the relays. There is no monitoring function for
the external contact circuit. In this case, the all-or-nothing relays must be triggered by
way of device functions or integrated test functions. For these testing purposes,
triggering of the output circuits is integrated into the software through a special control
function (‘Oper/CtrlTest/’ folder).
!
Before starting the test, open any triggering circuits for external devices so that no
inadvertent switching operations will take place.
Serial Interfaces
The integrated self-monitoring function for the PC or communication interface also
includes the communication module. The complete communication system, including
connecting link and fiber-optic module (if applicable), is always totally monitored as long
as a link is established through the control program or the communication protocol.
12 Storage
If the units are stored without being connected to auxiliary voltage, then the electrolytic
capacitors in the power supply area need to be recharged every 4 years. Recharge the
capacitors by connecting auxiliary voltage to the P139 for approximately 10 minutes.
If the units are stored during a longer time, the battery of the power supply module is
used for the continuous buffering of the event data in the working memory of the
processor module. Therefore the battery is permanently required and discharges
rapidly. In order to avoid this continuous discharge, it is recommended to remove the
power supply module from the mounting rack during long storage periods. The contents
of the event memory should be previously read out and stored separately!
The P139 is supplied with standard labeling for the LED indicators. LED indicators that
are not already configured and labeled can be labeled using the label strips supplied.
Affix the label strips to the front of the unit at the appropriate location.
The label strips can be filled in using a Stabilo brand pen containing water-resistant ink
(Type OH Pen 196 PS).
14 Order Information
MiCOM P139
Feeder Management and Bay Control P139 P139- 9 0 -307 -4xx -614 -7xx -46x -9x x -9x x -8xx
Basic device:
Basic device 40TE, pin-terminal connection, 3 -411
Basic device 40TE, CT/VT ring-, I/O pin-terminal connection, 5 -412
Basic device 84TE, ring-terminal connection, 8 -413
basic complement with 4 binary inputs and 8 output relays
and 6 binary inputs and 6 output relays for the
control of 3 switchgear units
Current transformer:
2)
Inom = 1 A / 5 A (T1...T4) resp. 22.5mV at 50A for NCIT 9
Voltage transformer:
Without 0
Vnom = 50 ... 130 V (4-pole) 4
Vnom = 50 ... 130 V (5-pole) f. Automatic Synchronism Check 5
9)
CT/VT-Boards with NCIT:
Variant 1: 22.5 mV at 50 A, 3.25 V at Vnom 9
Language:
English (German)
4) Without order extension no.
Px40 English (English)
4) Not yet available -800
German (English)
4) -801
French (English)
4) -802
Spanish (English)
4) Not yet available -803
Polish (English)
4) Not yet available -804
Russian (English)
4) 7) Not yet available -805
Language version
In order to display the Russian data model, the corresponding order extension number
(-805) must be added upon ordering so that the hardware option supporting Cyrillic
characters is integrated. With this ordering option, reference menu texts (English) will be
available for display. However, other Western European languages containing extra
characters will not be fully supported. Consequently, selecting the "Russian / English"
ordering option means that it will not be possible to download Western European data
models into the device.
Schneider Electric
35 rue Joseph Monier
92506 Rueil-Malmaison
FRANCE
Phone: +33 (0) 1 41 29 70 00
Fax: +33 (0) 1 41 29 71 00
www.schneider-electric.com Publishing: Schneider Electric
Publication: P139/EN M/Ea8 Version: -614 11/2010
Customer Care Centre
http://www.schneider-electric.com/CCC
Schneider Electric
35 rue Joseph Monier
92506 Rueil-Malmaison
FRANCE
Phone: +33 (0) 1 41 29 70 00
Fax: +33 (0) 1 41 29 71 00
www.schneider-electric.com Publishing: Schneider Electric
Publication: P139/EN M/Ana Version: -614 -630 -615 -616 -631 -617 -632 -618 -633, Vol. 1 06/2011