ANIT-REVERSE
[email protected] [email protected]
CURRENT SOLUTIONS
[email protected] [email protected]
www.goodwe.com
FOR ONE PIECE
WHAT IS
GRID-TIED INVERTER
ANTI-REVERSE
CURRENT SINGLE PHASE THREE PHASE 1KW ~ 70KW
Pl
Grid
CT
Pi Pg
Load
Pl
Pl: Loads power Anti-Reverse solution for a single phase inverter ( NS & DNS series )
1 Limit Pg to 0 Pg: Power from/feed to grid 1, Purchase a CT from GoodWe 2, Put CT on the main L line, and connect CT cable to inverter
2 Limit Pg to a certain value 3, Press 'Enter' button on the inverter to 'Set Power Limit'
HOW ANTI-REVERSE FUNCTION WORKS SINGLE PHASE HOW ANTI-REVERSE FUNCTION WORKS THREE PHASE
Logic: Logic:
CT detects is there any or how much current stream flowing to/from the grid, then it sends signal to tell 3-phase EzMeter communicates with the inverter and detects (on each phase) if there is any or how much
inverter to reduce or increase output power accordingly. current stream flowing to/from grid, then feedbacks the data to the inverter, which will know how much power
(in total) it should produce after calculation.
Based on power limit value set on inverter display
Only works with goodwe CT
GOODWE EZMETER -
Example: (Power Limit 0W)
THREE-PHASE INVERTER FROM GOODWE
Total Loads: 6KW
(DT / SDT SERIES) (80A) L1: 1KW / L2: 3KW / L3: 2KW
Inverter output: 6KW (2KW on each phase)
ANTI-REVERSE WIRING A B
MT SERIES INVERTER
STEPS 1 Finish wiring 2 Configure CT ratio on EzMeter 3 Set power limit value on inverter display
RS485 Cable
EZMETER
Main
Breaker
Load
B A
Anti-Reverse solution for a three phase inverter ( SDT & DT series ) GOODWE THREE-PHASE INVERTER CT *3 EZMETER - FROM GOODWE
1, Purchase an EzMeter from GoodWe 2, Cut the Main L lines and then connect to EzMeter (MT SERIES) 100A/250A/1000A/500A : 5A
3, A RS485 cable is used to communicate between inverter and EzMeter
Warning:
For the connection, CT1 (connected on Ia & Ia*)
must be connected to the same phase line with
Ua, same for CT2 & Ub, CT3 & Uc.
N L1 L3
Wrong wiring will cause inaccurate data detection
which further lead to malfunction of solar system
ANTI-REVERSE WIRING
A B
HOW ANTI-REVERSE FUNCTION WORKS
Logic:
3-phase EzMeter communicates with inverter and CT detects (on each phase) is there any or how much current
stream flowing to/from grid, then feedbacks data to the inverter, which tells how much power (in total) it should
produce after calculation.
RS485 Cable
EZMETER
CT
CT
Main Breaker L1: 2KW 1KW
L2: 2KW 1KW
L3: 2KW 0KW
B
A
Load
STEPS 1 Finish wiring 2 Set power limit value and CT ratio on EzLogger Pro
EZMETER
Router
RS485 Cable
RS485 Cable
CT Power Meter Grid
CT
CT
Main Breaker
1, Purchase EzMeter and EzLogger Pro from GoodWe, CTs can be purchased from GoodWe or anywhere else
2, Put CTs on the main L lines and connect CT cables to EzMeter CT ports 5, Connect inverters to EzLogger Pro COM1/COM2/COM3
EZMETER & CT CONNECTION 3, Connect L lines and Neutral line from anywhere to EzMeter power ports
4, An RS485 cable is used to communicate between EzLogger Pro COM4 and EzMeter
6, Connect a laptop to EzLogger Pro net port and run ‘ProMate’
CONFIGURATION 1
2
Warning:
ON PROMATE 4
For the connection, CT1 (connected on Ia & Ia*) 1. Choose “EzLogger Pro”
must be connected to the same phase line with a,b
2. Wait untill it shows “Connection Succeed” and
Ua, same for CT2 & Ub, CT3 & Uc. serial No. & Version
N L1 L3 c
3. Click ‘Refresh’ to check inverter SN connected
Wrong wiring will cause inaccurate data detection
to this EzLogger Pro
which further lead to malfunction of solar system 3
4. Here to configure monitoring
a. set system parameters and CT ratio
b. choose “Export Enab”
L2 c. Phase current & power display here
CT1 CT2 CT3
HOW ANTI-REVERSE FUNCTION WORKS HYBRID INVERTER SERIES
Logic: (ES & EM)
EzMeter + CT detect curent flow and communicate with Ezlogger Pro,
then EzLogger Pro sends commands to inverters to drop output power. STEPS 1 Finish wiring
2 Configure Power Limit Value on GoodWe APP
RS485 Cable
Example:
(Power Limit 0W;
L1: 15KW / L2: 25KW / L3: 20KW GOODWE HYBRID INVERTER SMART METER - FROM GOODWE
Total Loads: 60KW)
(ES / EM SERIES) (120A)
RS485 Cable
GOODWE CT SPECIFICATION inverter, then inverter will keep extra power charging battery or ->Export Power Limit & Power Value
drop inverter production to achieve power export limit.
Model Ratio (A) W / H / D (mm) a /e (mm)