Anit-Reverse: Current Solutions

The document provides contact information for GoodWe locations around the world and describes their anti-reverse current solutions for single phase and three phase inverters. For single phase, a current transformer is installed on the main line and connected to the inverter to limit power exported to the grid. For three phase, an EzMeter communicates with the inverter to detect current flow on each phase and limit total output power accordingly based on a set limit value.

Uploaded by

Dan Dep
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
171 views6 pages

Anit-Reverse: Current Solutions

The document provides contact information for GoodWe locations around the world and describes their anti-reverse current solutions for single phase and three phase inverters. For single phase, a current transformer is installed on the main line and connected to the inverter to limit power exported to the grid. For three phase, an EzMeter communicates with the inverter to detect current flow on each phase and limit total output power accordingly based on a set limit value.

Uploaded by

Dan Dep
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

GoodWe (China) GoodWe (Germany)

No.189 Kunlunshan Rd., SND, Suzhou, 215163, China Fuerstenriederstr. 279A, 81377 Munich
T: +86 512 6239 6771 T: +49 (0) 800 998 1212
[email protected] [email protected]
[email protected] [email protected]

GoodWe (Italy) GoodWe (Australia)


No. 17 Via Galimberti, Biella 13900, Italy Level 14, 380 St. Kilda Rd, Melbourne, VIC, 3004, Australia
T: +39 (0) 15 4191921 T: +61 3 9324 0559
[email protected] [email protected]
[email protected] [email protected]

GoodWe (India) GoodWe (UK)


1202, G-Square Business Park,Sector 30A,Opp. Sanpada 6 Dunhams Court, Dunhams Lane,
Railway Stn.,Vashi, Navi Mumbai- 400703 Letchworth Garden City, SG6 1WB UK
T: +91(0)9769 3475 60 T:+ 44 (0) 333 358 3184
[email protected] [email protected]
[email protected] [email protected]

GoodWe (Netherlands)
Franciscusdreef 42C, 3565AC Utrecht, the Netherlands
T: +31 (0) 30 737 1140
GoodWe (Turkey)
Adalet Mah. Megapol Tower K: 9 No: 110 Bayraklı - Izmir
T: +90 (232) 935 68 18
ANIT-REVERSE
[email protected] [email protected]

CURRENT SOLUTIONS
[email protected] [email protected]

www.goodwe.com
FOR ONE PIECE
WHAT IS
GRID-TIED INVERTER
ANTI-REVERSE
CURRENT SINGLE PHASE THREE PHASE 1KW ~ 70KW

Limit the max power exporting to grid


from solar system after feeding loads SINGLE PHASE INVERTER
STEPS 1 Finish wiring 2 Configure on inverter display

GOODWE CT - FROM GOODWE


Pi Pg SINGLE-PHASE INVERTER 1000 / 1, 90A
(NS / DNS SERIES)

Pl

Scenario A: Pl = Pi + Pg Pi: Inverter output power


Pl: Loads power
× No need to use anti-reverse function Pg: Power from/feed to grid ANTI-REVERSE WIRING
House
Meter

Grid

CT

Pi Pg
Load

Pl

Scenario B: Pg = Pi – Pl Pi: Inverter output power B A

Pl: Loads power Anti-Reverse solution for a single phase inverter ( NS & DNS series )
1 Limit Pg to 0 Pg: Power from/feed to grid 1, Purchase a CT from GoodWe 2, Put CT on the main L line, and connect CT cable to inverter
2 Limit Pg to a certain value 3, Press 'Enter' button on the inverter to 'Set Power Limit'
HOW ANTI-REVERSE FUNCTION WORKS SINGLE PHASE HOW ANTI-REVERSE FUNCTION WORKS THREE PHASE

Logic: Logic:
CT detects is there any or how much current stream flowing to/from the grid, then it sends signal to tell 3-phase EzMeter communicates with the inverter and detects (on each phase) if there is any or how much
inverter to reduce or increase output power accordingly. current stream flowing to/from grid, then feedbacks the data to the inverter, which will know how much power
(in total) it should produce after calculation.
Based on power limit value set on inverter display
Only works with goodwe CT

L1: 2KW 1KW

THREE PHASE INVERTER L2: 2KW 1KW


L3: 2KW 0KW

STEPS 1 Finish wiring 2 Configure on inverter display

GOODWE EZMETER -
Example: (Power Limit 0W)
THREE-PHASE INVERTER FROM GOODWE
Total Loads: 6KW
(DT / SDT SERIES) (80A) L1: 1KW / L2: 3KW / L3: 2KW
Inverter output: 6KW (2KW on each phase)

ANTI-REVERSE WIRING A B
MT SERIES INVERTER
STEPS 1 Finish wiring 2 Configure CT ratio on EzMeter 3 Set power limit value on inverter display
RS485 Cable

EZMETER

Power Meter Grid

Main
Breaker

Load

B A
Anti-Reverse solution for a three phase inverter ( SDT & DT series ) GOODWE THREE-PHASE INVERTER CT *3 EZMETER - FROM GOODWE
1, Purchase an EzMeter from GoodWe 2, Cut the Main L lines and then connect to EzMeter (MT SERIES) 100A/250A/1000A/500A : 5A
3, A RS485 cable is used to communicate between inverter and EzMeter

4, Press inverter button to set the limit ON and Ratio


EZMETER & CT CONNECTION CT RATIO CONFIGURATION
Note: CT is available from GoodWe or from external vendor (Ratio: ***/5A)

Warning:
For the connection, CT1 (connected on Ia & Ia*)
must be connected to the same phase line with
Ua, same for CT2 & Ub, CT3 & Uc.
N L1 L3
Wrong wiring will cause inaccurate data detection
which further lead to malfunction of solar system

L2 CT1 CT2 CT3


Here to set CT ratio:
Press to change the value
Press to jump to another character

ANTI-REVERSE WIRING

A B
HOW ANTI-REVERSE FUNCTION WORKS
Logic:
3-phase EzMeter communicates with inverter and CT detects (on each phase) is there any or how much current
stream flowing to/from grid, then feedbacks data to the inverter, which tells how much power (in total) it should
produce after calculation.
RS485 Cable

EZMETER

CT Power Meter Grid

CT

CT
Main Breaker L1: 2KW 1KW
L2: 2KW 1KW
L3: 2KW 0KW

B
A

Load

Anti-Reverse solution for a three phase inverter ( MT series )


1, Purchase an EzMeter from GoodWe and CTs from GoodWe or anywhere else 2, Put CTs on main L lines and connect CT cables to EzMeter CT ports
Example: (Power Limit 0W)
3, Connect L lines and Neutral line from anywhere to EzMeter power ports 4, An RS485 cable is used to communicate between inverter and EzMeter Total Loads: 6KW
L1: 1KW / L2: 3KW / L3: 2KW
5, Press EzMeter button to set CT ratio 6, Press inverter button to set the limit ON and Ratio Inverter output: 6KW (2KW on each phase)
FOR MULTI-PIECES
GRID-TIED INVERTERS
SINGLE PHASE THREE PHASE LARGE SCALE PROJECTS

FOR MULTI INVERTERS


A B A B

STEPS 1 Finish wiring 2 Set power limit value and CT ratio on EzLogger Pro

EZMETER
Router
RS485 Cable

RS485 Cable
CT Power Meter Grid
CT

CT

Main Breaker

GOODWE 3-PHASE INVERTERS EZLOGGER PRO 3-PHASE EZMETER CT * 3


* 60 (MAX) *1 *1 250A/1000A/5000A Anti-Reverse solution for multiple three phase inverters Load

1, Purchase EzMeter and EzLogger Pro from GoodWe, CTs can be purchased from GoodWe or anywhere else

2, Put CTs on the main L lines and connect CT cables to EzMeter CT ports 5, Connect inverters to EzLogger Pro COM1/COM2/COM3

EZMETER & CT CONNECTION 3, Connect L lines and Neutral line from anywhere to EzMeter power ports

4, An RS485 cable is used to communicate between EzLogger Pro COM4 and EzMeter
6, Connect a laptop to EzLogger Pro net port and run ‘ProMate’

7, Set power/current limit in the ‘ProMate’

CONFIGURATION 1
2

Warning:
ON PROMATE 4

For the connection, CT1 (connected on Ia & Ia*) 1. Choose “EzLogger Pro”
must be connected to the same phase line with a,b
2. Wait untill it shows “Connection Succeed” and
Ua, same for CT2 & Ub, CT3 & Uc. serial No. & Version
N L1 L3 c
3. Click ‘Refresh’ to check inverter SN connected
Wrong wiring will cause inaccurate data detection
to this EzLogger Pro
which further lead to malfunction of solar system 3
4. Here to configure monitoring
a. set system parameters and CT ratio
b. choose “Export Enab”
L2 c. Phase current & power display here
CT1 CT2 CT3
HOW ANTI-REVERSE FUNCTION WORKS HYBRID INVERTER SERIES
Logic: (ES & EM)
EzMeter + CT detect curent flow and communicate with Ezlogger Pro,
then EzLogger Pro sends commands to inverters to drop output power. STEPS 1 Finish wiring
2 Configure Power Limit Value on GoodWe APP

L1: 20KW 5KW


L2: 20KW 5KW
L3: 20KW 0KW

RS485 Cable
Example:
(Power Limit 0W;
L1: 15KW / L2: 25KW / L3: 20KW GOODWE HYBRID INVERTER SMART METER - FROM GOODWE
Total Loads: 60KW)
(ES / EM SERIES) (120A)
RS485 Cable

CT SPECIFICATION & SELECTION EZMETER & CT CONNECTION


Note: CT is available from GoodWe or from external vendor (Ratio: **/5A) Logic: CONFIGURE POWER LIMIT ON APP
EzMeter + CT detect curent flow and communicate with hybrid APP -> Set ->Advanced Setting

GOODWE CT SPECIFICATION inverter, then inverter will keep extra power charging battery or ->Export Power Limit & Power Value
drop inverter production to achieve power export limit.
Model Ratio (A) W / H / D (mm) a /e (mm)

K-30X20 250/5A 90 / 114 / 40 22 / 32 2.Export Power Limit


& Power Value
K-60X40 250/5A , 1000/5A 114 / 140 / 36 42 / 62

K-80X40 1000/5A 122 / 162 /40 42 / 82

K-80X80 1000/5A 144 / 159 / 36 82 / 82

K-140X60 5000/5A 164 / 234 / 52 62 / 142


9 10

K-160X80 5000/5A 184 / 254 / 52 82 / 162

Support Information for CT selection


Anti-Reverse solution for one hybrid inverter ( ES, EM and BP series )
*The min space between AC
Max total current 1, Purchase a CT & EzMeter unit from GoodWe
cable or copper bars
stream through AC 2, Put CT on the main L line, and connect Ethernet cable from inverter to EzMeter
* The sizes of your cable or 1.Advanced Setting
cable or copper bar 3, Connect inverter wireless signal ‘Solar-WiFi’ with a phone and run PV Master app
copper bars
4, Switch ‘Export Power Limit’ to ON and set ‘Power Value’