643331F Master Clock Mic Sigma M GB

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

Technical leaflet

Modular master clock Sigma Mod


Rack version Wall-mounted version

Wire or wireless time distribution and relay programming.

Master clock with programmable circuits, control of clock network, relays


and bells, NTP time reference.
PC software programming and USB key transfer.

Description:
 Synchronisable via GPS, FI or DCF antenna or NTP.
1U rack version
 3 programming circuits with week mode, holiday or special day mode for the activation of
bells and other systems such as heater, air conditioning, lighting, alarms access control,
etc.
 Automatic resetting of time distribution after power shortage.
 Clock synchronisation with wired or DHF wireless coded time signals.
 Programming though PC software and data transferring tough USB key.
 Automatic summer/winter changeover.
 Time distribution and relay/bell activation through radio DHF signal.

Weight : 2.8 Kg
Technical features:
 ABS casing for wall-mounted or aluminum casing for 19 ″ rack (1U height).
 Power and alarm led indicators.
 Keyboard with sensitive keys.
 Quartz: TCXO (Temperature compensated crystal oscillator).
 Accuracy: ± 0.1 s/day typical (adjustable drift compensation). Wall mounted version
 Absolute accuracy with GPS or radio antenna. 22
 Operating temperature: 0 to +50°C. 0
 Retro illuminated display with 2 lines of 24 characters each readable at one meter.
 LCD display: hour - minute - second - date.
 Permanent saving of programming and time.
 Programming protected by access code.
 Circuits with 3 relays, power cut: 1A / 240V.
 Clock output protected against short-circuits and overloads.
83
322

 Protection level: IP41.


 Drilling indications:

Norms:
 Applicable norms: EN 60950 - EN 55022 - EN 55024 –
EN 301-489-3 – EN 300 -220-3.
 FI/DCF signal norm: NFC 90002.
Weight: 2.4 Kg
 IRIG.B / AFNOR norm: NFS 87500A. Wall mount through 2 screws
 AFNOR/DHF norm: NF S 87-500 C (fixed channel, 869.525 MHz at 500 mW).

References: wall rack


Réf. 643331 F

 Sigma Mod 120/240V 907 451 907 453


 Sigma Mod 24VDC 907 452 907 454
 Sigma Mod 36/72VDC 907 456
 DCF radio antenna 907 026
 GPS antenna 907 037
 DHF transmitter 907 511
 DHF repeater 927 240
Technical leaflet
Modular master clock Sigma Mod
Electrical connections:
 Power: 24V DC or 240V ±10% 50/60Hz, 35W.
 Inputs/Output s on Sigma Mod:
- 1 polarised impulse output (24V // minute / ½ minute / second, 0.5A) or TBT 24V,
- 1 DHF output for DHF transmitter,
- 1 AFNOR coded time output,
- 1 external contact input,
- 1 USB slot,
- 1 NTP client/server on RJ45 plug,
- 3 relays for D1D2 impulses (tower clock control) and alarm or for circuit programming.
 Optional Input/Output (2 possible option cards for wall version, 4 for rack version) :
- Option card with 3 AFNOR outputs,
- Option card with 2 RS232/RS422/RS485 serial outputs,
- Option card with 1 polarised impulse output (24V // minute / ½ minute / second, 0.5A)
- Option card with 3 relays
- Option card melody

DHF transmitter
Wiring :
Option card 1 Option card 2

Melodys sounder DHF

 The C1 and C2 circuits (SPNO relays) control the D1D2 impulses or heater, air conditioning…
 The C3 circuit (SPDT relay) is assigned to alarm output or controls heater, air conditioning…
 The settable time output (14-15) allow time distribution in minute, ½ minute or second 24 V // (0,5A)
Wireless relay controller DHF
or a TBT power generator 24V.
 The AFNOR output (16-17) allows the synchronisation of approximately 50 clocks over 30km.
 The DHF output (18-19) when connected to a DHF transmitter can control the wireless relay
controllers for lighting, air conditioning, etc, the wireless chimes and the wireless clocks.
 The contact input (20-21) allows remote control of the C1, C2 or C3 circuit from an external contact.
 The NTP output allows control of slave clocks and is a NTP time reference (time server) for
computers connected to the LAN network.
 Optional outputs can increase the area of applications by controlling different types of slave clocks Reference:
1-relay indoor controller 907523
or to connect the Sigma to a computer. 1-relay outdoor controller 907524
 Alarm notification by SNMP trap. 1-relay embedded controller 907525

 Alarm notification by Email.

Option cards :
 Impulse output card 907 531
 AFNOR output card 907 533
 Serial output card 907 534
 Relay card (1 SPDT and 2 SPNO relays) 907 535
 Melody card 907 537
Technical Leaflet

Modular master clock Sigma Mod

You might also like