Vav-Sd: Features and Highlights

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

VAV-SD

Features and highlights


• Capable
Four 10-bit inputs and five binary
outputs.

• Interoperable
Fully BACnet-compliant on MS/TP
LAN at up to 76.8 Kbps.

BACnet is a registered trademark of ASHRAE. ASHRAE does not endorse,


approve or test products for compliance with ASHRAE standards. Compliance of

� listed products to requirements of ASHRAE Standard 135 is the responsibility of


the BACnet Manufacturers Association (BMA). BTL is a registered trademark of
the BMA.

• Versatile
Downloadable operating code
to allow for future software
improvements.

• Reliable
Extensive on-board filtering, with
all program data backed up in
nonvolatile flash memory.

• Accurate
Factory calibrated at multiple
velocity points and field-adjustable The Alerton® BACtalk® VAV-SD controller is a versatile BACnet-compliant
during balancing. field controller that provides pressure-independent control of any single-
duct variable air volume (VAV) box. As a native BACnet controller, the VAV-
SD integrates seamlessly with your BACnet system, communicating at up
to 76.8 Kbps on a BACnet MS/TP LAN. The VAV-SD-F includes a filter to
reduce dust contamination.

The BACtalk VAV-SD contains an integral airflow sensor to provide


pressure-independent operation of the VAV box. Each airflow sensor is
factory-calibrated at multiple velocity points. Minimum, maximum, and
reheat airflows can be entered either at an Alerton Microset™ wall unit or
an operator workstation. A technician can adjust the calibration in the field
during balancing to compensate for slight variations in box installation and
type.

All control algorithms are factory-loaded into nonvolatile flash memory


and can be field-modified. The VAV-SD can execute control algorithms
independently of other equipment. All calibration, programming, and
operator-entered setup data is stored in flash memory for further assurance
of stable, reliable, and independent operation.

The BACtalk VAV-SD is your complete answer to control of all single-


duct VAV boxes in a BACnet environment. With its integral airflow sensor
and programming flexibility, the VAV-SD provides every option for precision
VAV box control.
6670 185th Avenue Northeast, Redmond, WA 98052 USA • Tel: 425.869.8400 • Fax: 425.869.8445 • www.alerton.com
2 of 2 LTBT-VAV-SD Rev. 0004
© Honeywell International Inc. All rights reserved. Alerton is a registered trademark of Honeywell.
VAV-SD
Technical Data
• Power  24 VAC @ 5 VA min., plus binary output loads (65 VA max). Utilizes
a half-wave rectifier, which allows a single transformer to power multiple
VLCs. One leg of 24 VAC connects to earth (panel) ground.

• Inputs 4 universal inputs with 10-bit resolution. Input 0 can be used for a
BACtalk Microset. Inputs 1–3 support thermistor/dry contact.

• Binary outputs 5 outputs, each rated at 24 VAC, 0.5 A. Three outputs


utilize hot-switched triacs. Two outputs utilize ground switching triacs for
damper motor control. All outputs have a common connection to the fused 24
VAC supply.

• Pressure sensor 0–1.25 inches water column differential pressure sensor.

• Processor & Memory Motorola AZ60 processor with on-board flash


memory. Flash memory provides nonvolatile program and data storage and
allows for encrypted updates to the program for future product enhancements.

• Max. Dimensions 5.20” (132mm)H x 3.30” (84mm)W x 1.40”


(36mm)D.

• Terminations Removable header-type screw terminals accept 14–24


AWG wire. An additional header is provided for easy connection to MS/TP for
testing.

• Environmental 0–158 deg. F (-17–70 deg. C). 0–95% RH, non-


condensing.

• Communications BACnet MS/TP LAN up to 76.8 Kbps.

• BACnet conformance An application specific controller


(ASC); tested and approved by BTL. See Protocol


Implementation Conformance Statement (PICS). �
BACnet is a registered trademark of ASHRAE. ASHRAE does not endorse,
approve or test products for compliance with ASHRAE standards. Compliance of
listed products to requirements of ASHRAE Standard 135 is the responsibility of
the BACnet Manufacturers Association (BMA). BTL is a registered trademark of
the BMA.

• Ratings

Listed Underwriters Laboratory for Open Energy Management Equipment


(PAZX) under the UL Standard for Safety 916; listing includes both U.S. and
Canadian certification

EMC Directive 89/336/EEC (European CE Mark)

FCC Part 15, Subpart J, Class A

Ordering information
Item number Description

VAV-SD Single-duct variable air volume controller

VAV-SD-C VAV-SD field controller with available custom DDC


Specifications subject to change without notice

6670 185th Avenue Northeast, Redmond, WA 98052 USA • Tel: 425.869.8400 • Fax: 425.869.8445 • www.alerton.com


2 of 2 LTBT-VAV-SD Rev. 0004
© Honeywell International Inc. All rights reserved. Alerton is a registered trademark of Honeywell.