Instrument Symbols - 1
Instrument Symbols - 1
7.4.2 Air supply. Identify air supply followed by air supply pressure.
7.4.3 Hydraulic fluid supply. Identify hydraulic fluid followed by the fluid supply pressure.
7.5 Identification of instrument action. Show the direction of the instrument signal by placing
appropriate letters close to the instrument bubble. Identify an instrument in which the value of the
output signal increases or changes to its maximum value, as input (measured variable) increases
by the letters "DIR." Identify an instrument in which the value of the output signal decreases or
changes to its minimum value, as the value, of the input (measured variable) increases by the
letters "REV." However, since most transmitters are direct-acting, the designation DIR is optional
for them.
4 Symbols
4.1 General
Standard instrumentation symbols as shown in ISA-S5.1 are retained as much as possible for
flow diagram use, but are supplemented as necessary by the new symbols in Sections 4.2
through 4.6. Symbol size should be consistent with ISA-S5.1, Section 3. The symbol descriptions
listed to the right of each symbol are intended as guidelines for applications, and are not intended
to be all inclusive. The symbol may be used if one or more of the descriptions apply. Shared
signal lines can be expressed by the symbol for a system link
ISA-S5.3-1983 11
4.2.3 Not normally accessible to operator
1) Shared blind controller.
2) Shared display installed in field.
3) Computation, signal conditioning in shared controller.
4) May be on communication link.
5) Normally blind operation.
6) May be altered by configuration
4.4.2 Distributed control interconnecting logic controller with binary or sequential logic functions.
1) Packaged programmable logic controller, or digital logic
controls integral to the distributed control equipment.
2) Not normally accessible by the operator.
4.4.3 Distributed control interconnecting logic controller with binary or sequential logic functions.
1) Packaged programmable logic controller, or digital logic
controls integral to the distributed control equipment.
2) Normally accessible to the operator.
4.7.3 Long term/mass storage of a process variable by digital memory means such as tape, disc,
etc., shall be depicted in accordance with 4.2 or 4.3 of this standard, depending on the location of
the device.
Table 5.1.1 — Instrumentation device and function symbols
Note: Numbers in parentheses refer to explanatory notes in Clause 5.3.1.
Shared display,
Shared control (1) C D
A B
Primary
Alternate
No. Choice Location & accessibility (6)
Choice Computer
or
or Systems
Basic Discrete
Safety and
Process (5)
Instrumented Software
Control
System (4)
System
(3)
(2)
--`,``,,,``,,,,,```,````,,,,```,-`-`,,`,,`,`,,`---
x Located in field.
1 x Not panel, cabinet, or console mounted.
x Visible at field location.
x Normally operator accessible.
x Pilot light.
7 x Circle shall be replaced with any symbol from column D in Table 5.1.1 if location and
accessibility needs to be shown.
--`,``,,,``,,,,,```,````,,,,```,-`-`,,`,,`,`,,`---
Table 5.2.1 — Measurement symbols: primary elements and transmitters
Note: Numbers in parentheses refer to explanatory notes in Clause 5.3.2.
No Symbol Description
(1a) (2) x Generic primary element, bubble format.
1 x Notation (*) from Table 5.2.2 should be used to identify type of element.
x Connect to process or other instruments by symbols from Tables 5.3.1 and 5.3.2.
?E x Insert in or on process flow line, vessel, or equipment.
(*)
(1a) ( (2) (3) x Transmitter with integral primary element, bubble format.
2 x Notation (*) from Table 5.2.2 should be used to identify type of element.
?T
x Connect to process or other instruments by symbols from Tables 5.3.1 and 5.3.2.
x Insert in or on process flow line, vessel, or equipment.
(*)
(1a) (2) (3) x Transmitter with close coupled primary element, bubble format
3 ?T x Notation (*) from Table 5.2.2 should be used to identify type of element.
x Connecting line shall be equal to or less than 0.25 inches (6 millimeters).
x Connect to process or other instruments by symbols from Tables 5.3.1 and 5.3.2.
x Insert element in or on process flow line, vessel, or equipment.
?E
(*)
(1a) (3) x Transmitter with remote primary element, bubble format.
4 ?T x Notation (*) from Table 5.2.2 should be used to identify type of element.
x Connecting line shall be equal to or greater than 0.5 inches (12 millimeters).
x Connect to process or other instruments by symbols from Tables 5.3.1 and 5.3.2.
?E
x Insert element in or on process flow line, vessel, or equipment.
--`,``,,,``,,,,,```,````,,,,```,-`-`,,`,,`,`,,`---
(*)
(1b) (3) x Transmitter with integral primary element inserted in or on process flow line, vessel,
5 ?T or equipment, bubble/graphic format.
x Insert primary element symbol from Table 5.2.3 at #.
x Connect to other instruments by symbols from Table 5.3.2.
#
(1b) (3) x Transmitter with close-coupled primary element inserted in or on process flow line,
6 ?T vessel, or equipment, bubble/graphic format.
x Insert primary element symbol from Table 5.2.3 at #.
x Connecting line shall be equal to or less than 0.25 inches (6 millimeters).
x Connect to other instruments by symbols from Table 5.3.2.
#
(1b) (3) x Transmitter with remote primary element inserted in or on process flow line, vessel,
7 or equipment, bubble/graphic format.
?E x Insert primary element symbol from Table 5.2.3 at #.
x Connecting line may be any signal line from Table 5.2.3.
x Connecting line shall be equal to or greater than 0.5 inches (12 millimeters).
# x Connect to other instruments by symbols from Table 5.3.2.
Table 5.2.2 — Measurement symbols: measurement notations (4)
Note: Numbers in parentheses refer to explanatory notes in Clause 5.3.2
Analysis
AIR = Excess air H2O = Water O2 = Oxygen UV = Ultraviolet
CO = Carbon monoxide H2S = Hydrogen sulfide OP = Opacity VIS = Visible light
CO2 = Carbon dioxide HUM = Humidity ORP = Oxidation reduction VISC = Viscosity
COL = Color IR = Infrared pH = Hydrogen ion =
COMB = Combustibles LC = Liquid chromatograph REF = Refractometer =
COND = Elec. conductivity MOIST = Moisture RI = Refractive index =
DEN = Density MS = Mass spectrometer TC = Thermal conductivity =
GC = Gas chromatograph NIR = Near infrared TDL = Tunable diode laser =
Flow
CFR = Constant flow regulator OP = Orifice plate PT = Pitot tube VENT = Venturi tube
CONE = Cone OP-CT = Corner taps PV = Pitot venturi VOR = Vortex Shedding
COR = Coriollis OP-CQ = Circle quadrant SNR = Sonar WDG = Wedge
DOP = Doppler OP-E = Eccentric SON Sonic =
DSON = Doppler sonic OP-FT = Flange taps TAR = Target
FLN = Flow nozzle OP-MH = Multi-hole THER = Thermal =
FLT = Flow tube OP-P = Pipe taps TTS = Transit time sonic =
LAM = Laminar OP-VC = Vena contracta taps TUR = Turbine =
MAG = Magnetic PD = Positive displacement US = Ultrasonic =
Level
CAP = Capacitance GWR = Guided wave radar NUC = Nuclear US = Ultrasonic
d/p = Differential pressure LSR = Laser RAD = Radar =
DI = Dielectric constant MAG = Magnetic RES = Resistance =
DP = Differential pressure MS = Magnetostrictive SON = Sonic =
Pressure
ABS = Absolute MAN = Manometer VAC = Vacuum
AVG = Average P-V = Pressure-vacuum =
DRF = Draft SG = Strain gage = =
Temperature
BM = Bi-metallic RTD = Resistance temp detector TCK = Thermocouple type K TRAN = Transistor
IR = Infrared TC = Thermocouple TCT = Thermocouple type T =
RAD = Radiation TCE = Thermocouple type E THRM = Thermistor =
RP = Radiation pyrometer TCJ = Thermocouple type J TMP = Thermopile =
Miscellaneous
Burner, Combustion Position Quantity Radiation
FR = Flame rod CAP = Capacitance PE = Photoelectric Į = Alpha radiation
IGN = Igniter EC = Eddy current TOG = Toggle ȕ = Beta radiation
IR = Infrared IND = Inductive = Ȗ = Gamma radiation
TV = Television LAS = Laser = n = Neutron radiation
UV = Ultraviolet MAG = Magnetic = =
= MECH = Mechanical = =
--`,``,,,``,,,,,```,````,,,,```,-`-`,,`,,`,`,,`---
= OPT = Optical = =
= RAD = Radar = =
= = = =
Speed Weight, Force
ACC = Acceleration LC = Load cell = =
EC = Eddy current SG = Strain gauge = =
PROX = Proximity WS = Weigh scale = =
VEL = Velocity = = =
= = = =
Table 5.2.3 — Measurement symbols: primary elements
Note: Numbers in parentheses refer to explanatory notes in Clause 5.3.2.
No Symbol (4) Description
Analysis Analysis Analysis
6 x Restriction orifice.
8 x Restriction orifice.
--`,``,,,``,,,,,```,````,,,,```,-`-`,,`,,`,`,,`---
x Circle quadrant orifice plate.
Flow
10
11
12 x Notation from Table 5.2.2 required at (*) if used for more than one type.
(*)
x Venturi tube.
Flow
13
x Flow nozzle.
Flow
14
x Flow tube.
Flow
15
Table 5.2.3 — Measurement symbols: primary elements
Note: Numbers in parentheses refer to explanatory notes in Clause 5.3.2.
No Symbol (4) Description
16
17
18
x Turbine flowmeter.
Flow
19 x Propeller flowmeter.
20
x Target flowmeter.
Flow
21
22 a) M b)
23 a) ǻT b)
--`,``,,,``,,,,,```,````,,,,```,-`-`,,`,,`,`,,`---
24
x Cone meter.
Flow
x Wedge meter.
Flow
26
x Coriollis flowmeter.
Flow
27
x Sonic flowmeter.
Flow
28 x Ultrasonic flowmeter.
29
30
Table 5.2.3 — Measurement symbols: primary elements
Note: Numbers in parentheses refer to explanatory notes in Clause 5.3.2.
No Symbol (4) Description
31
ladder.
x Guide wires may be omitted.
x Insert probe.
38 x May be through top of vessel.
Level
x Radar.
39
Level
PE x Notation (*) from Table 5.2.2 should be used to identify type of element.
40
x Connection symbols 6, 7, 8, or 9 in Table 5.3.1 are used if connection type is to
(*) be shown.
x Bubble may be omitted if connected to another instrument.
--`,``,,,``,,,,,```,````,,,,```,-`-`,,`,,`,`,,`---
Table 5.2.3 — Measurement symbols: primary elements
Note: Numbers in parentheses refer to explanatory notes in Clause 5.3.2.
No Symbol (4) Description
Temperature
x Sight glass.
Flow
1 FG
x Pressure gage.
Pressure
x Thermometer.
TG x Use connection 6, 7, 8, or 9 in Table 5.3.1 if connection type is to be shown.
5
--`,``,,,``,,,,,```,````,,,,```,-`-`,,`,,`,`,,`---
Table 5.2.5 — Measurement symbols: auxiliary and accessory devices
Note: Numbers in parentheses refer to explanatory notes in Clause 5.3.2.
No Symbol (4) Description
x Thermowell, flanged.
--`,``,,,``,,,,,```,````,,,,```,-`-`,,`,,`,`,,`---
--`,``,,,``,,,,,```,````,,,,```,-`-`,,`,,`,`,,`---
Table 5.3.2 — Line symbols: instrument-to-instrument connections
(3) a) x Unguided electromagnetic signals, light, radiation, radio, sound, wireless, etc.
11 x Wireless instrumentation signal.
b) x Wireless communication link.
(4) x Communication link and system bus, between devices and functions of a shared
12 display, shared control system.
x DCS, PLC, or PC communication link and system bus.
(6) x Communication link and system bus, between devices and functions of a fieldbus
14 system.
x Link from and to “intelligent” devices.
(7) x Communication link between a device and a remote calibration adjustment device or
15 system.
x Link from and to “smart” devices.
Table 5.3.2 — Line symbols: instrument-to-instrument connections
--`,``,,,``,,,,,```,````,,,,```,-`-`,,`,,`,`,,`---
(#)
a)
(##)
17
b) (#)
(##)
(#)
b)
(##)
--`,``,,,``,,,,,```,````,,,,```,-`-`,,`,,`,`,,`---
Table 5.4.1 — Final control element symbols
--`,``,,,``,,,,,```,````,,,,```,-`-`,,`,,`,`,,`---
Table 5.4.2 — Final control element actuator symbols
Note: Numbers in parentheses refer to explanatory notes in Clause 5.3.4
No Symbol Description
15
(1) (2) x Variable area flowmeter with integral manual adjusting valve.
2 FICV x Instrument tag bubble required with (b).
(a)
(b)
x Level regulator.
7 x Ball float and mechanical linkage.
TANK
x Backpressure regulator.
8 x Internal pressure tap.
x Backpressure regulator.
9 x External pressure tap.
--`,``,,,``,,,,,```,````,,,,```,-`-`,,`,,`,`,,`---
Table 5.4.3 — Self-actuated final control element symbol
Note: Numbers in parentheses refer to explanatory notes in Clause 5.3.4.
No Symbol Description
x Pressure-reducing regulator.
10 x Internal pressure tap.
x Pressure-reducing regulator.
11 x External pressure tap.
x Vacuum relief.
Table 5.4.3 — Self-actuated final control element symbol
Note: Numbers in parentheses refer to explanatory notes in Clause 5.3.4.
No Symbol Description
x Temperature regulator.
20 x Filled thermal system.
--`,``,,,``,,,,,```,````,,,,```,-`-`,,`,,`,`,,`---
Table 5.4.4 — Control valve failure and de-energized position indications
Note: Numbers in parentheses refer to explanatory notes in Clause 5.3.4.
No Method A (1) (10) Method B (1) (10) Definition
FO
FC
--`,``,,,``,,,,,```,````,,,,```,-`-`,,`,,`,`,,`---
FL
FL/DO
FL/DC
Table 5.5 — Functional diagramming symbols
Note: Numbers in parentheses refer to explanatory notes in Clause 5.3.5.
No Symbol (1) (2) Description
(*)
--`,``,,,``,,,,,```,````,,,,```,-`-`,,`,,`,`,,`---
6
(*)
(*)
Table 5.6 — Signal processing function block symbols
Note: Numbers in parentheses refer to explanatory notes in Clause 5.3.6.
Function Equation
No Definition
Symbol (1) (2) Graph
Ȉ X M
Xn
X2
X1
Ȉ
t t
--`,``,,,``,,,,,```,````,,,,```,-`-`,,`,,`,`,,`---
Average M = X1 + X2 }+ Xn /n x Output equals algebraic sum of
2 inputs divided by number of inputs.
X M
Ȉ/n Xn
X2
X1
Ȉ/n
t t
X M
¨
X1
X2
t t
X X X1 M
X2
t1 t t1 t
Table 5.6 — Signal processing function block symbols
Note: Numbers in parentheses refer to explanatory notes in Clause 5.3.6.
Function Equation
No Definition
Symbol (1) (2) Graph
y X X1 M
X2
y
t1 t t1 t
n
Exponential x Output equals nth power of input.
M=X
6
n
X X M
n
X
t t
Root extraction n
M = X x Output equals nth root of input.
7 x If ‘n’ omitted, square root is
assumed.
n
¥Ǧ X M
n
¥Ǧ
t t
(3)
a) K
--`,``,,,``,,,,,```,````,,,,```,-`-`,,`,,`,`,,`---
b) P
t1 t t1 t
Table 5.6 — Signal processing function block symbols
Note: Numbers in parentheses refer to explanatory notes in Clause 5.3.6.
Function Equation
No Definition
Symbol (1) (2) Graph
(3)
a) -K
M
b) -P
t1 t
10
(3) x Output proportional to time
integral of input.
a) b) I x TI = Integral time constant.
X M
(3)
a)
b) I
t1 t2 t t1 t2 t
(3)
a) d/dt
b) D t1 t t1 t
g(x)
t t
Table 5.6 — Signal processing function block symbols
Note: Numbers in parentheses refer to explanatory notes in Clause 5.3.6.
Function Equation
No Definition
Symbol (1) (2) Graph
g(t)
t1 t t1 t
t t
--`,``,,,``,,,,,```,````,,,,```,-`-`,,`,,`,`,,`---
! X
X1
M
X2
!
t1 t t1 t
M = X1 for X2 >X1 >X3 or X3 >X1 >X2 Output equals middle value of three or
16 Middle signal select M = X2 for X1 >X2 >X3 or X3 >X2 >X1 more inputs.
M = X3 for X1 >X3 >X2 or X2 >X3 >X1
M X X2 M
X1
X3
M
t t
Table 5.6 — Signal processing function block symbols
Note: Numbers in parentheses refer to explanatory notes in Clause 5.3.6.
Function Equation
No Definition
Symbol (1) (2) Graph
X M
X1
X2
t1 t t1 t
X M
!
H
!
t1 t t1 t
--`,``,,,``,,,,,```,````,,,,```,-`-`,,`,,`,`,,`---
X M
L
t1 t t1 t
X X2 X1 M
t1 t2 t t1 t2 t
Table 5.6 — Signal processing function block symbols
Note: Numbers in parentheses refer to explanatory notes in Clause 5.3.6.
Function Equation
No Definition
Symbol (1) (2) Graph
X
X2 X1
M
--`,``,,,``,,,,,```,````,,,,```,-`-`,,`,,`,`,,`---
t1 t2 t t1 t2 t
(3)
a)
b) ! t1 t2,3 t t1 t2 t3 t
t t1 t
t1
(State 1) M = 1 @ X L x Output state is dependent on
Low signal monitor
24 (State 2) M = 0 @ X > L value of input.
x Output changes state when input
is equal to or lower than an
arbitrary low limit.
L X M
State State
L
L
t1 t t1 t
Table 5.6 — Signal processing function block symbols
Note: Numbers in parentheses refer to explanatory notes in Clause 5.3.6.
Function Equation
No Definition
Symbol (1) (2) Graph
L
HL
t1 t2 t t1 t2 t
B a. .Automatically and is
not adjustable by operator.
No graph
b. Manually and is adjustable
B by operator.
--`,``,,,``,,,,,```,````,,,,```,-`-`,,`,,`,`,,`---
X2 State
T State
t1 t t1 t
Analog signal transfer
X M
X1
X2
State State
T
t1 t t1 t
Binary signal transfer
Table 5.7 — Binary logic symbols
Note: Numbers in parentheses refer to explanatory notes in Clause 5.3.7.
Function Definition (1)
No
Symbol
A B C X O
1 0 0 0 0 0
2 1 0 0 0 0 1
3 0 1 0 0 0 A 0
4 0 0 1 0 0
5 0 0 0 1 0 B
6 1 1 0 0 0
7 1 0 1 0 0 C
8 1 0 0 1 0
9 0 1 1 0 0 X
10 0 1 0 1 0
11 0 0 1 1 0
12 1 1 1 0 0 O
13 1 1 0 1 0
14 1 0 1 1 0 t
15 0 1 1 1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
16 1 1 1 1 1
A A
B B
C OR O C O O
X X
A B C X O
1 0 0 0 0 0
2 1 0 0 0 1 1
3 0 1 0 0 1 A 0
4 0 0 1 0 1
5 0 0 0 1 1 B
6 1 1 0 0 1
7 1 0 1 0 1 C
8 1 0 0 1 1
9 0 1 1 0 1 X
10 0 1 0 1 1
11 0 0 1 1 1
12 1 1 1 0 1 O
13 1 1 0 1 1 t
14 1 0 1 1 1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
15 0 1 1 1 1
16 1 1 1 1 1
--`,``,,,``,,,,,```,````,,,,```,-`-`,,`,,`,`,,`---
Table 5.7 — Binary logic symbols
Note: Numbers in parentheses refer to explanatory notes in Clause 5.3.7.
Function Definition (1)
No
Symbol
A B C X O
1 0 0 0 0 1
2 1 0 0 0 0
3 0 1 0 0 0 1
4 0 0 1 0 0 A 0
5 0 0 0 1 0
6 1 1 0 0 0 B
7 1 0 1 0 0
C
8 1 0 0 1 0
9 0 1 1 0 0
X
10 0 1 0 1 0
11 0 0 1 1 0
12 1 1 1 0 0
O
13 1 1 0 1 0
14 1 0 1 1 0 t
15 0 1 1 1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
16 1 1 1 1 0
A B C X O
1 0 0 0 0 1
2 1 0 0 0 1
1
3 0 1 0 0 1
A 0
4 0 0 1 0 1
5 0 0 0 1 1
B
6 1 1 0 0 1
7 1 0 1 0 1
C
8 1 0 0 1 1
9 0 1 1 0 1
X
10 0 1 0 1 1
11 0 0 1 1 1
12 1 1 1 0 1 O
13 1 1 0 1 1
14 1 0 1 1 1 t
15 0 1 1 1 1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
16 1 1 1 1 0
--`,``,,,``,,,,,```,````,,,,```,-`-`,,`,,`,`,,`---
Table 5.7 — Binary logic symbols
Note: Numbers in parentheses refer to explanatory notes in Clause 5.3.7.
Function Definition (1)
No
Symbol
Qualified OR gate x Output true if number of true inputs is greater than or equal to ‘n’.
Greater or equal to ‘n’ x Truth table and graph are for n = 2.
5
A
B
C tn O
A B C X O
1 0 0 0 0 0
2 1 0 0 0 0 1
3 0 1 0 0 0 A 0
4 0 0 1 0 0
5 0 0 0 1 0 B
6 1 1 0 0 1
7 1 0 1 0 1 C
8 1 0 0 1 1
9 0 1 1 0 1 X
10 0 1 0 1 1
11 0 0 1 1 1
12 1 1 1 0 1 O
13 1 1 0 1 1 t
14 1 0 1 1 1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
15 0 1 1 1 1
16 1 1 1 1 1
Qualified OR gate x Output true if number of true inputs is greater than ‘n’.
Greater than ‘n’ x Truth table and graph are for n = 2.
6
A
B
C !n O
A B C X O
1 0 0 0 0 0
2 1 0 0 0 0 1
3 0 1 0 0 0 A 0
4 0 0 1 0 0
5 0 0 0 1 0 B
6 1 1 0 0 0
7 1 0 1 0 0 C
8 1 0 0 1 0
9 0 1 1 0 0 X
10 0 1 0 1 0
11 0 0 1 1 0
12 1 1 1 0 1 O
13 1 1 0 1 1
14 1 0 1 1 1 t
15 0 1 1 1 1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
16 1 1 1 1 1
--`,``,,,``,,,,,```,````,,,,```,-`-`,,`,,`,`,,`---
Table 5.7 — Binary logic symbols
Note: Numbers in parentheses refer to explanatory notes in Clause 5.3.7.
Function Definition (1)
No
Symbol
Qualified OR gate x Output true if number of true inputs is less than or equal to ‘n’.
Less or equal to ‘n’ x Truth table and graph are for n = 2.
7
A
B
C dn O
A B C X O
1 0 0 0 0 1
2 1 0 0 0 1
3 0 1 0 0 1 1
4 0 0 1 0 1 A 0
5 0 0 0 1 1
6 1 1 0 0 1 B
7 1 0 1 0 1
8 1 0 0 1 1 C
9 0 1 1 0 1
10 0 1 0 1 1 X
11 0 0 1 1 1
12 1 1 1 0 0
13 1 1 0 1 0 O
14 1 0 1 1 0 t
15 0 1 1 1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
16 1 1 1 1 0
Qualified OR gate x Output true if number of true inputs is less than ‘n’.
Less than ‘n’ Truth table and graph are for n = 2.
8
A
B
C n O
x
A B C X O
--`,``,,,``,,,,,```,````,,,,```,-`-`,,`,,`,`,,`---
1 0 0 0 0 1
2 1 0 0 0 1 1
3 0 1 0 0 1 A 0
4 0 0 1 0 1
5 0 0 0 1 1 B
6 1 1 0 0 0
7 1 0 1 0 0 C
8 1 0 0 1 0
9 0 1 1 0 0 X
10 0 1 0 1 0
11 0 0 1 1 0
12 1 1 1 0 0 O
13 1 1 0 1 0
14 1 0 1 1 0 t
15 0 1 1 1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
16 1 1 1 1 0
Table 5.7 — Binary logic symbols
Note: Numbers in parentheses refer to explanatory notes in Clause 5.3.7.
Function Definition (1)
No
Symbol
A
B
C n O
A B C X O
1 0 0 0 0 0
2 1 0 0 0 0
1
3 0 1 0 0 0
A 0
4 0 0 1 0 0
5 0 0 0 1 0
B
6 1 1 0 0 1
7 1 0 1 0 1
C
8 1 0 0 1 1
9 0 1 1 0 1
X
10 0 1 0 1 1
11 0 0 1 1 1
12 1 1 1 0 0 O
13 1 1 0 1 0
14 1 0 1 1 0 t
15 0 1 1 1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
16 1 1 1 1 0
Qualified OR gate x Output true if number of true inputs is not equal to ‘n’.
Not equal to ‘n’ x Truth table and graph are for n = 2.
10
A
B
C zn O
A B C X O
1 0 0 0 0 1
2 1 0 0 0 1
3 0 1 0 0 1 1
4 0 0 1 0 1 A 0
5 0 0 0 1 1
--`,``,,,``,,,,,```,````,,,,```,-`-`,,`,,`,`,,`---
6 1 1 0 0 0 B
7 1 0 1 0 0
8 1 0 0 1 0 C
9 0 1 1 0 0
10 0 1 0 1 0 X
11 0 0 1 1 0
12 1 1 1 0 1
13 1 1 0 1 1 O
14 1 0 1 1 1
t
15 0 1 1 1 1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
16 1 1 1 1 1
Table 5.7 — Binary logic symbols
Note: Numbers in parentheses refer to explanatory notes in Clause 5.3.7.
Function Definition (1)
No
Symbol
1
A O A 0
1 0
O 1
0 1
0
t
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1
A B C D A 0
1 0 0 0 1
2 1 0 1 0 B
3 0 0 1 0
4 0 1 0 1 C
5 0 0 0 1
6 1 1 1 0 D
7 0 0 1 0
8 1 1 0 1 t
1 2 3 4 5 6 7 8
Set dominant memory x Outputs [C] and [D] are always opposite.
x If input [A] equals (1) then output [C] equals (1) and output [D] equals (0).
13 x If input [A] changes to (0) output [C] remains (1) until input [B] equals (1) then output [C]
equals (1) and output [D] equals (0).
A So C x If input [B] equals (1) then output [D] equals (1) and output [C] equals (0).
x If input [B] changes to (0) output [D] remains (1) until input [A] equals (1), then output [D]
B R D equals (1) and output [C] equals (0).
x If inputs [A] and [B] are simultaneously equal to (1) then output [C] equals (1) and output
[D] equals (0).
1
A B C D A 0
1 0 0 0 1
2 1 0 1 0 B
3 0 0 1 0
4 0 1 0 1 C
5 0 0 0 1
6 1 1 1 0 D
7 0 0 1 0
8 1 1 1 0 t
1 2 3 4 5 6 7 8
--`,``,,,``,,,,,```,````,,,,```,-`-`,,`,,`,`,,`---
Table 5.7 — Binary logic symbols
Note: Numbers in parentheses refer to explanatory notes in Clause 5.3.7.
Function Definition (1)
No
Symbol
Reset dominant memory x Outputs [C] and [D] are always opposite.
x If input [A] equals (1) then output [C] equals (1) and output [D] equals (0).
14 x If input [A] changes to (0) output [C] remains (1) until input [B] equals (1) then output [C]
equals (1) and output [D] equals (0).
S x If input [B] equals (1) then output [D] equals (1) and output [C] equals (0).
A C
x If input [B] changes to (0) output [D] remains (1) until input [A] equals (1), then output [D]
B Ro D equals (1) and output [C] equals (0).
x If inputs [A] and [B] are simultaneously equal to (1) then output [C] equals (0) and output
[D] equals (1).
1
A B C D A 0
1 0 0 0 1
2 1 0 1 0 B
3 0 0 1 0
4 0 1 0 1 C
5 0 0 0 1
--`,``,,,``,,,,,```,````,,,,```,-`-`,,`,,`,`,,`---
6 1 1 0 1 D
7 0 0 0 1
8 1 1 0 1 t
1 2 3 4 5 6 7 8
Pulse duration - fixed x Output [O] changes from (0) to (1) and remains (1) for prescribed time duration (t) when
input [I] changes from (0) to (1).
15
I t PD O
1
I 0
O
NONE
t t
Time delay - off x Output [O] changes from (0) to (1) when input [I] changes from (0) to (1).
x Output [O] changes from (1) to (0) after input [I] changes from (1) to (0) and has been
16 equal to (0) for time duration (’t).
I t DT O
1
I 0
O
NONE
t t
t
Table 5.7 — Binary logic symbols
Note: Numbers in parentheses refer to explanatory notes in Clause 5.3.7.
Function Definition (1)
No
Symbol
Time delay - on x Output [O] changes from (0) to (1) after input [I] changes from (0) to (1) and [I] remains (1)
for prescribed time duration (t).
17 x Output [O] remains (1) until Input [I] changes to (0) or optional Reset [R] changes to (1).
I t GT O
1
I 0
NONE O
t t t
R
t
Pulse duration - variable x Output [O] changes from (0) to (1) when input [I] changes from (0) to (1).
x Output [O] changes from (1) to (0) when Input [I] has been equal to (1) for time duration (t),
18 Input [I] changes from (1) to (0), or optional Reset [R] changes to (1).
I t LT O
1
I 0
NONE O
t t t
--`,``,,,``,,,,,```,````,,,,```,-`-`,,`,,`,`,,`---
t
Table 5.8 — Electrical schematic symbols
Note: Numbers in parentheses refer to explanatory notes in Clause 5.3.8.
No Symbol (1) Description
--`,``,,,``,,,,,```,````,,,,```,-`-`,,`,,`,`,,`---
Table 5.8 — Electrical schematic symbols
Note: Numbers in parentheses refer to explanatory notes in Clause 5.3.8.
No Symbol (1) Description
x On time delay.
21 x Moves after relay coil is energized and set time has elapsed.
(*) x (*) = Set time.
x Transformer.
23 x (*) = Rating, 220/120 Vac or Vdc, etc.
(*)
x Thermal overload.
--`,``,,,``,,,,,```,````,,,,```,-`-`,,`,,`,`,,`---
25
x Bell.
30
Table 5.8 — Electrical schematic symbols
Note: Numbers in parentheses refer to explanatory notes in Clause 5.3.8.
No Symbol (1) Description
x Horn or siren.
31
x Buzzer.
32
x Solenoid coil.
33
x Pilot light.
34
x Battery
35
x Ground
36
b)