This two-page report summarizes test results for a 33kV current transformer (CT) used at the Shantahar 33/11kV substation in Bangladesh. The CT was tested for primary injection, core allocation, and winding resistance. Test results showed the CT ratios and phases matched expected values with low errors. The core allocations and winding resistances were also within acceptable limits.
This two-page report summarizes test results for a 33kV current transformer (CT) used at the Shantahar 33/11kV substation in Bangladesh. The CT was tested for primary injection, core allocation, and winding resistance. Test results showed the CT ratios and phases matched expected values with low errors. The core allocations and winding resistances were also within acceptable limits.
This two-page report summarizes test results for a 33kV current transformer (CT) used at the Shantahar 33/11kV substation in Bangladesh. The CT was tested for primary injection, core allocation, and winding resistance. Test results showed the CT ratios and phases matched expected values with low errors. The core allocations and winding resistances were also within acceptable limits.
This two-page report summarizes test results for a 33kV current transformer (CT) used at the Shantahar 33/11kV substation in Bangladesh. The CT was tested for primary injection, core allocation, and winding resistance. Test results showed the CT ratios and phases matched expected values with low errors. The core allocations and winding resistances were also within acceptable limits.
Download as DOCX, PDF, TXT or read online from Scribd
Download as docx, pdf, or txt
You are on page 1of 2
33kV CT Test Report Page 1 of 2
Customer Bangladesh Power Development Board (BPDB)
Project DESIGN, SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF 33/11KV NEW 2X10/13.33MVA AT SANTAHAR AT BOGRA AIS SUB STATION, RAJSHAHI ZONE. (PACKAGE NO-AIS-3) Contract Contract No-10349,DTD-28.12 2017 Substation Shantahar 33/11kV Substation Location/Feeder T2 Transformer
Equipment Data
Manufacturer Mehru Electrical & Mechanical
Serials Engineers (P) Ltd., India Type Live Tank R OC-8644/6/1/19 Standard IEC 61869 Y OC-8879/6/2/19 Rated Current 400-200/5/5/5A B OC-8879/6/1/19 Insulation Level 70/170kV Short Time Current 25kA 3s
Core 1 Core 2 Core 3
Ratio 200-400/5A 200-400/5A 200-400/5A Burden VA 30 30 Output Class 0.2 5P20 PS
Core CT Ratio Error Phase Current Current Current R 400 A 4.86 5 0.14 1S1 – 1S3 Y 400 A 4.88 5 0.12 B 400 A 4.86 5 0.14 80 R 400 A 4.87 5 0.13 2S1 – 2S3 Y 400 A 4.84 5 0.16 B 400 A 4.88 5 0.12
Core Allocation Test
Core Allocation Setting core Star point
Core Phase Status R OK 1S1-1S3 1S3 1S1 – 1S3 Y OK For B OK METERING R OK 2S1-2S3 2S3 2S1 – 2S3 Y OK For For SEA/AKES B For SWPLOK For BPDB/NESCO Protection Date: 30/01/2020 3S1-3S3 SPARE 33kV CT Test Report Page 2 of 2
Customer Bangladesh Power Development Board (BPDB)
Project DESIGN, SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF 33/11KV NEW 2X10/13.33MVA AT SANTAHAR AT BOGRA AIS SUB STATION, RAJSHAHI ZONE. (PACKAGE NO-AIS-3) Contract Contract No-10349,DTD-28.12 2017 Substation Shantahar 33/11kV Substation Location/Feeder T2 Transformer
CT winding resistance test
Core Ratio Phase Resistance(Ω)
R .25 1S1 – 1S2 200 Y .25 B .26 R .5 1S1 – 1S3 400 Y .5 B .5 R .26 2S1 – 2S2 200 Y .25 B .25 R .80 2S1 – 2S3 400 Y .80 B .80