Optimal Charge Amount For Different Refrigerants in Air-to-Water Heat Pumps
Optimal Charge Amount For Different Refrigerants in Air-to-Water Heat Pumps
Optimal Charge Amount For Different Refrigerants in Air-to-Water Heat Pumps
DOI 10.1007/s40997-016-0028-2
RESEARCH PAPER
Received: 27 January 2016 / Accepted: 10 July 2016 / Published online: 19 July 2016
Shiraz University 2016
123
326 Iran J Sci Technol Trans Mech Eng (2016) 40:325–335
123
Iran J Sci Technol Trans Mech Eng (2016) 40:325–335 327
compressor, water-cooled copper pipe body-type con- COP, enthalpy, pressure ratio and other related functions
denser, air source copper pipe with aluminum fins evapo- were calculated and compared for all three gases at each
rator, and an expansion device. The condenser was used to gas level.
exchange heat between the refrigerant and water. Air was
selected as a heat source and water acted as a heat sink in
the thermodynamic cycle of constructed heat pump. 3 Calculations
Moreover, used refrigerants were R134a, R404a and R22
(Table 1). Temperatures in the test setup were monitored The heat transfer rate of the condenser and the evaporator
using T-types thermocouples to measure essential points can be calculated from the following equation:
and surface of the condenser, and refrigerant pressures
Q_ evap ¼ m_ a;e cp;a Tin;a Tout;a ð1Þ
were also measured at the selected locations with bourdon
pressure gauges shown in Fig. 1. In order to reduce heat Q_ cond ¼ m_ w;c cp;w Tout;w Tin;w ð2Þ
transfer to the environment, all parts of the system
including pipes, water tank, condenser and other compo- In the laboratory heat pump apparatus, three-phase elec-
nents were insulated. The evaporator is installed inside a trical motor has been used as a driving force of the com-
wind tunnel and both speed and temperature of the air pressor. In this state, electrical power consumption of the
inside can be controlled by a fan and an electrical heater. A motor–compressor unit can be calculated as Cakır et al.
volumetric flow meter was installed to measure condenser (2013):
pffiffiffi
cooling water flow rate. Each sensor was calibrated to W_ comp ¼ 3 cos ; U:I ð3Þ
reduce experimental uncertainties (Karagoz 2002).
The first step of the test procedure was a 2000 g charge where the cos ; is power factor and was taken as 0.8 in the
under the certain condition. Subsequently, the refrigerant calculation.
was added into the heat pump unit in 200–300 g incre- Considering the air fan in the wind tunnel, overall power
ments until the maximum COP was obtained. Charging consumption and the total coefficient of performance
was carried out from 2000 up to 7300 g for R134a, and (COPT) of the heat pump device are as follows:
6000 and 7000 g for R404a and R22 refrigerants, respec- W_ total ¼ W_ comp þ W_ electric fan ð4Þ
tively. Totally, 7 tests were performed in each stage (4 tests
for different condenser water flow rates and 3 tests for Q_ cond
COPT ¼ ð5Þ
different evaporator air temperature). Heating capacity, W_ total
123
328 Iran J Sci Technol Trans Mech Eng (2016) 40:325–335
123
Iran J Sci Technol Trans Mech Eng (2016) 40:325–335 329
sffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi
2 2 2 highest point on the chart. After passing through the
oY oY oY
uc ð y Þ ¼ uð x 1 Þ þ uðx2 Þ þ þ uð x n Þ peak point, additional gas causes a performance reduc-
oX1 oX2 oXn tion and COP value drops in next steps. Furthermore,
ð16Þ these diagrams show that how the different water flow
rates (0.05, 0.06, 0.10 and 0.1314 kg s-1) impact on the
In this case, COP is a function of mass flow rate, water
COP. It is clearly observed that with increasing in flow
input and output temperatures and power consumption of
rate, heat provided from the system increases, which
compressor as shown in Eq. (5).
means a higher performance of the unit.
So the uncertainty of heat pump performance is obtained
There are several factors to evaluate COP, heat
by the following equation (Pan et al. 2011), from which the
capacity and even the optimal charge amount of the
calculated uncertainty for COP (UCOP,HP) was ±5.53 %.
system including inlet temperature, secondary fluids flow
ffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi
s
2
2
2
123
330 Iran J Sci Technol Trans Mech Eng (2016) 40:325–335
11.2 C 19, 20 and 24 C 0.05, 0.06, 0.10 and 0.1314 kg s-1 0.80 kg s-1
R134a R22
3 3
2.5
2.5
2
2
COP
1.5
COP
2800
R404 2700 R134a
2.5
2600 R404a
power consumpon (wa)
2 2500 R22
2400
1.5 2300
COP
2200
0,05 kg/s
1
2100
0,06 kg/s
2000
0.5 0,10 kg/s
1900
0,13 kg/s
0
1800
2000 3000 4000 5000 6000 7000
2000 2500 3000 3500 4000 4500 5000 5500 6000
gas amount (gr) gas amount (gr)
Fig. 4 COP variations according to the gas amount and water flow Fig. 6 Compressor work variation with respect to the charge amount
rate for R404a refrigerant
123
Iran J Sci Technol Trans Mech Eng (2016) 40:325–335 331
8000 450
super
7000 R134a R22
6000 400
R404a R134a
Enthalpy (kj/kg)
5000
Qh (wa)
R22
350 R404a
4000
3000
300
2000 liquid
1000 250
0
2000 3000 4000 5000 6000 7000 200
gas amount (gr) 2000 3000 4000 5000 6000 7000
gas amount (gr)
Fig. 7 Variation of heating capacity with gas amount for all three
refrigerants Fig. 10 Condenser outlet enthalpy (h3) with respect to the gas
amount
cop Qh power consumpon
4 6000
2500 gr R22
3.5 14
5000 3200 gr
3 12
6600 gr
Qh , w (wa)
4000
2.5 10
Pressure (Bar)
COP
2 3000
8
1.5
2000 6
1
1000 4
0.5
2
0 0
2000 3000 4000 5000 6000 7000 0
gas amount (gr) 100 150 200 250 300 350 400 450 500
enthalpy (kj/kg)
Fig. 8 Heating capacity, COP and power consumption with respect
to the gas amount Fig. 11 Heat pump cycle in P–h diagram for different charge amount
123
332 Iran J Sci Technol Trans Mech Eng (2016) 40:325–335
1.5 400
in other hand, power consumption increases due to the
300
1 elevated pressure so there must be an optimal gas charge
200 amount to find highest COP, and finding a relationship
0.5
100
between the charge amount and pressure is one of the aims
of this study. Figures 12, 13 and 14 show relations between
0 0 suction line pressure and COP value, which vary with the
2000 2800 3400 4000 4600 5200 5800 6400 7000
R22- gas amount (gr) gas amount of different gases. This proportion can be
considered to find out needed pressure and a way toward
Fig. 12 Pcomp,in versus COP for R22 refrigerant (Ta,in = 19 C, determining the optimal charge amount in heat pumps.
Tw,in = 11.2, m_ a = 0.8025 kg s-1, m_ w = 0.13 kg s-1) Based on results from the tests, it was found that the full
charge of R134a, R404a and R22 refrigerants of the heat
3 500
COP pump unit was almost 5800–6000, 5200–5400 and 6200 g
compressor inlet pressure (kpa)
2.5 pressure 400
and maximum value obtained for COP was 2.91, 2.40 and
2.78, respectively. In the case of R404a, charging of the
2 system has been performed less than other gases because
300
the compressor power consumption rate has increased
COP
1.5
200 rapidly. The maximum obtained COP values according to
1 the gas amount collected in Table 3, and related com-
100 pressor inlet pressures and charge amount have been listed
0.5
for comparison.
0 0 Compressor working condition varies due to different
2000 2800 3400 4000 4600 5200 5800 6700 parameters including the type of refrigerant and its prop-
R134a - gas amount (gr) erty and also charge amount which effect on inlet and
outlet pressures and temperatures of the compressor.
Fig. 13 Pcomp,in versus COP for R134a refrigerant (Ta,in = 19 C,
Figure 15 shows inlet pressures of the compressor in dif-
Tw,in = 11.2, m_ a = 0.8025 kg s-1, m_ w = 0.13 kg s-1)
ferent conditions, and Fig. 16 shows discharge to inlet
pressure (pressure ratio) variations which decreases with
3 700 increasing in the amount of refrigerant. Among the gases,
COP R404a has less liquid density than others, since it has
600
compressor inlet pressure (kPa)
123
Iran J Sci Technol Trans Mech Eng (2016) 40:325–335 333
Table 3 Optimum COP due to gas amount and compressor inlet pressure for all gases
Refrigerant m_ w = 0.05 kg s-1 m_ w = 0.06 kg s-1 m_ w = 0.10 kg s-1 m_ w = 0.13 kg s-1
COP P1 (kPa) Charge (g) COP P1 (kPa) Charge (g) COP P1 (kPa) Charge (g) COP P1 (kPa) Charge (g)
500 2.2
2.1
400
COP
2
300
1.9
200 1.8
100 1.7
1.6
0
2000 3000 4000 5000 6000 7000 1.5
gas amount (gr) 0.04 0.06 0.08 0.1 0.12 0.14
water flow rate (kg/s)
Fig. 15 Variation of Pcomp,in with charge amount
Fig. 17 COP variation with respect to condenser water flow rate for
R22 and R404a refrigerants (charge amount 4800, 5000 and 5200 g)
7
R134a
R404a
In the heat pump system, heat transfer rate increases as a
6
R22 consequence of the difference between the temperature of
secondary fluid and condensing temperature. Additionally,
5
pressure rao
123
334 Iran J Sci Technol Trans Mech Eng (2016) 40:325–335
22 compression rao
3.5 0.035
3.3 gas flow rate
compressor inlet temperature (°C)
20 0.03
3.1
compression rao
0.025
90 35 15
R22
85 33
13 R404 a
31
Outlet temperature (°C)
R134a
80
pressure (bar)
29 11
Inlet temperature (°C)
T,comp,out- 0.05kg/s
75 0.06 kg/s 27
0.1 kg/s 9
70 0.13 kg/s 25
T,comp,in- 0.05kg/s
0.06 kg/s 7
65 23
0.10 kg/s
0.13 kg/s
21
60 5
19
55 17 3
200 250 300 350 400 450
50 15
2000 3000 4000 5000 6000 enthalpy (kj/kg)
Gas amount (gr)
Fig. 21 Charge effect (5400, 5600 and 5800 g) on the heat pump
Fig. 19 Compressor inlet and outlet temperature with respect to the cycle in the P–h diagram (Ta,in = 19 C, Tw,in = 11.2,
gas amount in different water flow rates (kg s-1) at the condenser m_ a = 0.8025 kg s-1, m_ w = 0.13 kg s-1)
(purple and yellow lines indicate inlet and outlet results, respectively)
123
Iran J Sci Technol Trans Mech Eng (2016) 40:325–335 335
2. It was determined that the maximum COP of the Cho H, Ryu C, Kim Y, Kim H (2005) Effects of refrigerant charge
system strongly depends on the charge amount and amount on the performance of a transcritical CO2 heat pump. Int
J Refrig 28:1266–1273
refrigerant type. On the other side, performance of the Choi H, Cho H, Choi J (2012) Refrigerant amount detection algorithm for
system decreases in overcharge condition. a ground source heat pump unit. Int J Renew Energy 42:111–117
3. This study revealed that in the low gas levels whole Choia J, Kim Y (2004) Influence of the expansion device on the
cycle is in the superheat region in the P–h diagram. performance of a heat pump using R407C under a range of
charging conditions. Int J Refrig 27:378–384
With additional charge, the cycle passes through two- Comaklı O, Bayramoglu M, Kaygusuz K (1996) A thermodynamic
phase region at first and then reaches rapidly liquid model of a solar assisted heat pump system with energy storage.
region which the cycle will be finally completed in last Int J Pergamon 56:485–492
stage. Comaklı K, Yuksel B, Comaklı O (2004) Evaluation of energy and
exergy losses in district heating network. Int J Appl Therm Eng
4. The effects of gas type and charging level on the 24:1009–1017
pressure and temperature of the compressor were Comaklı O, Comakli K, Ozdemir N, Yilmaz M (2010) Analysis of
characterized in suction and discharge lines. heat pumps with zeotropic refrigerant mixtures by Taguchi
5. Obtained results show that compression ratio is very method. J Therm Sci Technol 30(2):113–122
Corberan J, Martinez I, Gonzalvez J (2008) Charge optimization
variable parameter and strongly depends on gas study of a reversible water-to-water propane heat pump. Int J
properties and charge level. Refrig 31:716–726
6. It was specified that refrigerant property is a significant Corberan J, Martinez I, Martinez-Ballester S, Gonzalvez-Macia J,
parameter for working condition of a heat pump; Royo-Pastor R (2011) Influence of the source and sink temper-
atures on the optimal refrigerant charge of a water-to-water heat
especially, gas density has a major role in temperature pump. Int J Refrig 34:881–892
and pressure of the system and also pressure ratio in Fernando P, Palm B, Lundqvist P, Granryd E (2004) Propane heat
the condenser. Some refrigerants cause an increase in pump with low refrigerant charge: design and laboratory tests.
temperature and pressure of compressor that leads us to Int J Refrig 27:761–773
Holman JP (1986) Heat transfer, 6th edn. ISBN: 0-07-029620-0
select a proper compressor and even lubrication oil in Karagoz S (2002) Utilization of refrigerant mixtures in heat pumps,
heat pumps. MSc thesis
Kim D, Park H, Kim M (2014) The effect of the refrigerant charge
The scientific method and obtained results presented in amount on single and cascade cycle heat pump systems. Int J
this study can be used for industrial process improvement Refrig 40:254–268
of heat pumps and refrigerants. Kong X, Zhang D, Li Y, Yang Q (2011) Thermal performance
analysis of a direct-expansion solar-assisted heat pump water
heater. Int J Energy 36:6830–6838
Acknowledgments This project was supported by the Research
Palm B (2007) Refrigeration systems with minimum charge of
Project Foundation of the Ataturk University (Project No. BAP-2013/
refrigerant. Int J Appl Therm Eng 27:1693–1701
105). The authors gratefully acknowledge the support of this study.
Pan L, Wang H, Chen Q, Chen C (2011) Theoretical and experimental
study on several refrigerants of moderately high temperature
heat pump. Int J Appl Therm Eng 31:1886–1893
Poggi F, Macchi-Tejeda H, Leducq D, Bontemps A (2008) Refrig-
References erant charge in refrigerating systems and strategies of charge
reduction. Int J Refrig 31:353–370
Afshari F, Comakli O, Adiguzel N, Ghasemi Zavaragh H (2016) Poppi S et al (2016) Analysis of system improvements in solar
Influence of refrigerant properties and charge amount on thermal and air source heat pump combisystems. Appl Energy
performance of reciprocating, compressor in air source heat 173:606–623
pump. J Energy Eng. doi:10.1061/(ASCE)EY.1943-7897.0000377, Tahavvor AR, Hosseini S (2014) The effects of humidity, compressor
04016025 operation time and ambient temperature on frost formation in an
Bakirci K, Ozyurt O, Comakli K, Comakli O (2011) Energy analysis industrial fridge, iranian journal of science and technology.
of a solar-ground source heat pump system with vertical closed- Trans Mech Eng 39:197–203
loop for heating applications. Int J Energy 36:3224–3232 Tahavvor AR, Zakeri E, Moezi SA (2014) Modeling of frost growth
Bjork E, Palm B (2006) Refrigerant mass charge distribution in a on a horizontal circular cylinder under natural convection using
domestic refrigerator. Part I: transient conditions. Int J Appl fractal geometry analysis. Iran J Sci Technol Trans Mech Eng
Therm Eng 26:829–837 38:1–8
Caglar A, Yamali C (2012) Performance analysis of a solar-assisted Yan G, Bai T, Yu J (2016) Energy and exergy efficiency analysis of
heat pump with an evacuated tubular collector for domestic solar driven ejector–compressor heat pump cycle. Sol Energy
heating. Int J Energy Build 54:22–28 125:243–255
Cakır U, Comaklı K, Comaklı O, Karsli S (2013) An experimental Zhang D, Wu QB, Li JP, Kong XQ (2014) Effects of refrigerant
exergetic comparison of four different heat pump systems charge and structural parameters on the performance of a direct-
working at same conditions: as air to air, air to water, water to expansion solar-assisted heat pump system. Int J Appl Therm
water and water to air. Int J Energy 58:210–219 Eng 73:520–526
123