JSW Protection Settings-SIEMENS
JSW Protection Settings-SIEMENS
上海威能电力科技有限公司
印度金达电厂一期
JSW ENERGY(VIJAYANAGAR)LIMITED
GENERATOR PROTECTION
保 护 定 值 计 算(参考)
Protection Setting Calculation(Reference)
Author:
Page 1 of 41
上海威能电力科技有限公司
上海威能电力科技有限公司
Table of contents
1. Introduction 4
2. Technical Data 5
2.1 Generator 5
2.1.1 Generator 5
2.1.2 Current transformer 5
2.1.3 Voltage transformer 5
2.2 Generator Neutral (Grounding-) transformer 5
2.3 Main Transformer 5
2.4 Unit AUX Transformer 6
3. Parameter Settings for Cubicle 10CHA01 (Prot. System A) 7
3.1 Parameter Settings 7UT635 –F10 7
3.1.1 Device Configuration Parameters 7
3.1.2 Power System data 1 7
3.1.3 (
Settings for Differential Protection 87G-M ) 8
3.2 Parameter Settings 7UM622 -F11 9
3.2.1 Device Configuration Parameters 9
3.2.2 Power System data 1 10
3.2.3 Settings for generator differential protection – (87G-A) 10
3.2.4 Settings for generator stator 90% ground protection Uo> (64G1-A) 11
3.2.5 Settings for underexcitation (loss of field) protection – (40G-A) 12
3.2.6 Settings for reverse power protection – (32R2-A) 13
3.2.7 Settings for forward power protection – (32F-A) 13
3.2.8 Settings for negative sequence protection – (46G-A) 15
3.2.9 Settings for generator impedance protection – (21G-A) 15
3.2.10 Settings for out of step protection – (78G-A) 17
3.2.11 Settings for generator (thermal) overload protection – (49G-A) 18
3.2.12 Settings for overvoltage protection – (59G-A) 19
3.2.13 Settings for underoltage protection – (27G-A) 19
3.2.14 Settings for overexcitation (Volt /Hz) protection – (24G-A) 20
3.2.15 Settings for frequency protection– (81-A) 21
3.2.16 Settings for Inadvertent Energization protection– (50/27-A) 22
3.2.17 Settings for External Trip Function 22
3.3 Parameter Settings 7UM611 –F12 23
3.3.1 Device Configuration Parameters 23
3.3.2 Power System data 1 23
3.3.3 Settings for reverse power protection – (32R1-A) 24
3.3.4 Settings for ( Interturn Protection) stator 90% ground protection Uo> (59N(IN)-A) 24
4. Parameter Settings for Cubicle 10CHA02 (Prot. System B) 24
4.1 Parameter Settings 7UM622 –F21 24
4.1.1 Device Configuration Parameters 24
4.1.2 Power System data 1 26
4.1.3 Settings for generator differential protection – (87G-B) 26
4.1.4 Settings for stator earth fault 100 % protection – (64G2-B) 27
4.1.5 Settings for underexcitation (loss of field) protection – (40G-B) 29
4.1.6 Settings for reverse power protection – (32R2-B) 30
4.1.7 Settings for forward power protection – (32F-B) 30
4.1.8 Settings for negative sequence protection – (46G-B) 32
4.1.9 Settings for generator impedance protection – (21G-B) 32
page 2 of 41
上海威能电力科技有限公司
上海威能电力科技有限公司
4.1.10 Settings for out of step protection – (78G-B) 34
4.1.11 Settings for generator (thermal) overload protection – (49G-B) 35
4.1.12 Settings for overvoltage protection – (59G-B) 36
4.1.13 Settings for underoltage protection – (27G-B) 36
4.1.14 Settings for overexcitation (Volt /Hz) protection – (24G-B) 37
4.1.15 Settings for frequency protection– (81-B) 38
4.1.16 Settings for Inadvertent Energization protection– (50/27-B) 39
4.1.17 Settings for External Trip Function 39
4.2 Parameter Settings 7UM611 –F22 39
4.2.1 Device Configuration Parameters 39
4.2.2 Power System data 1 40
4.2.3 Settings for reverse power protection – (32R1-B) 40
4.2.4 Settings for ( Interturn Protection) stator 90% ground protection Uo> (59N(IN)-B) 41
page 3 of 41
上海威能电力科技有限公司
1. Introduction
This report gives the draft functional settings of the protection relays necessary for the operation of
the protection system and for selective clearance of faults.
This report includes the protective functions for the following components:
• Generator
• Generator neutral point
page 4 of 41
上海威能电力科技有限公司
2. Technical Data
2.1 Generator
2.1.1 Generator
Rated voltage UN 20 kV
Rated apparent power SN 353 MVA
Power factor p.f. 0.85
Rated active power PN 300 MW
Rated current IN 10189 A
Rated frequency fN 50 Hz
page 5 of 41
上海威能电力科技有限公司
page 6 of 41
上海威能电力科技有限公司
page 7 of 41
上海威能电力科技有限公司
0522 CT Rated Primary Current Meas. Loc. 2 2500 A
0523 CT Rated Secondary Current Meas. Loc. 2 1 A
0531 CT-Strpnt. Meas. Loc.3 in Dir. of Object YES
0532 CT Rated Primary Current Meas. Loc. 3 15000 A
0533 CT Rated Secondary Current Meas. Loc. 3 5 A
0541 CT-Strpnt. Meas. Loc.4 in Dir. of Object YES
0542 CT Rated Primary Current Meas. Loc. 4 2500 A
0543 CT Rated Secondary Current Meas. Loc. 4 1 A
CB
0851A Minimum TRIP Command Duration 0.15 sec
Device Configuration:
Address Parameter/Comment Setting Note
Setting Group A:
Address Parameter/Comment Setting Note
General
1201 Differential Protection ON
1205 Increase of Trip Char. During Start OFF
1206 Inrush with 2. Harmonic Restraint ON
1207 n-th Harmonic Restraint OFF
I-Diff
1221 Pickup value of Differential current 0.30 I/In0
1226A T I-Diff> Time Delay 0.00 sec
1231 Pickup value of High set Trip 5.0 I/In0
1236A T I-Diff>> Time Delay 0.00
Characteristic
1241A Slope 1 of Tripping Characteristic 0.25
1242A Base Point for Slope 1 of Characteristic 0.00 I/In0
1243A Slope 2 f Tripping Characteristic 0.50
1244A Base Point for Slope 2 of Characteristic 2.50 I/In0
page 8 of 41
上海威能电力科技有限公司
1251A I-RESTRAINT for Start Detection 0.10 I/In0
1252A Factor for Increasing of Characteristic at Start 1.0
1253 Maximum permissible Starting Time 5.0 sec
1261A Pickup for Add-on Stabilization 4.00 I/In0
1262A Duration for Add-on Stabilization 15 cycle
1263A Time for Cross-block Add-on Stabilization 15 cycle
Inrush 2.HM
1271 2nd Harmonic Content in I-Diff 20 %
1272A Time for Cross-blocking 2nd Harm. 5 cycle
Restr. n. HM
1276 n-th Harmonic Content in I-DIFF 30 %
1277A Time for Cross-blocking n-th Harm. 20 cycle
1278A Limit IDIFFmax of n-th Harm. Restraint 1.5 I/In0
page 9 of 41
上海威能电力科技有限公司
0181 Measured Value Supervision Enabled
0182 Trip Circuit Supervision Disabled
0185 Threshold Supervision Enabled
0186 External Trip Function 1 Enabled I&C trip
0187 External Trip Function 2 Enabled Cooling water
0188 External Trip Function 3 Enabled SWT high
0189 External Trip Function 4 Enabled SWT high-high
3.2.2 Power System data 1
Address Parameter/Comment Setting Note
Power System
0270 Rated Frequency 50 Hz
0271 Phase Sequence L1 L2 L3
0272 Scheme Configuration Unit transformer
connected
Generator / Motor
0251 Rated Primary Voltage Generator/Motor 20.0 kV
0252 Rated apparent power of the generator 353.00 MVA
0242 Starpoint Side 1 Isolated
0244 Starpoint Side 2 Isolated
CT’s
0201 CT-Starpoint Side 1 in direction of Object * YES
0202 CT Rated Primary Current Side 1 15000 A
0203 CT Rated Secondary Current Side 1 5 A
0204 Correction Angle CT W0 0.00 °
0205 CT Ratio Prim./Sec. IEE1 [not used] 60.0
0210 CT-Starpoint Side 2 in direction of Object * YES
0211 CT Rated Primary Current Side 2 15000 A
0212 CT Rated Secondary Current Side 2 5 A
0213 CT Ratio Prim./Sec. IEE2 [not used] 60.0
0214 Grounded terminal CT IEE2 [not used] Terminal Q7
VT’s
0221 Rated Primary Voltage 20.00 kV
0222 Rated Secondary Voltage (Ph-Ph) 110 V
0223 UE Connection VN connect. to broken delta
winding
0224 VT Ratio Prim./Sec. Ue [20kV/√3 / 0.11/3kV] 314.9
0225A Matching Ratio Phase–VT to Broken Delta-VT 1.73
Breaker
0280 Minimum TRIP Command Duration 0.15 sec
0281 Closed Breaker Min. Current Threshord 0.20 A
Transducer
0295 Transducer 1 [not used] 10 V
0296 Transducer 2 [not used] 10 V
0297 Transducer 3 [not used] with filter
page 10 of 41
上海威能电力科技有限公司
K cc ——style factor, 1
K er ——CT error, 10%
b) The differential speedy value:
1
I Diff >>= I Nobj = 5 I Nobj → address 1231
Uk %
c) The tripping characteristic:
We use the default settings of the slope 1 and slope 2, also the default settings of BP1 and BP2.
Here, s1=0.25, s2=0.50, BP1=0, BP2=2.5
Device Configuration:
Address Parameter/Comment Setting Note
Setting Group A:
Address Parameter/Comment Setting Note
General
2001 Differential Protection ON
2005 Increase of Trip Char. During Start OFF
I-Diff
2021 Pickup value of Differential current 0.30 I/In0
2026A T I-Diff> Time Delay 0.00 sec
2031 Pickup value of High set Trip [ > (1/x’d)⋅⋅In0 ] 5.0 I/In0
2036A T I-Diff>> Time Delay 0.00
Characteristic
2041A Slope 1 of Tripping Characteristic 0.25
2042A Base Point for Slope 1 of Characteristic 0.00 I/In0
2043A Slope 2 f Tripping Characteristic 0.50
2044A Base Point for Slope 2 f Characteristic 2.50 I/In0
2051A I-RESTRAINT for Start Detection 0.10 I/In0
2052A Factor for Increasing of Characteristic at Start 1.0
2053 Maximum permissible Starting Time 5.0 sec
2061A Pickup for Add-on Stabilization 4.00 I/In0
2062A Duration for Add-on Stabilization 15 Cycle
2063A Time for Cross-blocking Add-on Stabiliz. 15 Cycle
3.2.4 Settings for generator stator 90% ground protection Uo> (64G1-A)
Device Configuration:
Address Parameter/Comment Setting Note
Setting Group A:
Address Parameter/Comment (Secondary-)Setting Note
page 11 of 41
上海威能电力科技有限公司
5002 Uo> Pickup 11.0 V
5005 T S/E/F Time Delay 0.30 sec
Remark: Final setting during primary tests.
The rated machine data must refer to secondary values to enable setting. Furthermore it must be
noted, that rated current and rated voltage of the machine in general are not equal to the rated data
of the instrument transformers.
According 7UM62 manual, matching is performed according to the following formula:
1 1 UNsec INmach TRU 1 100 3.39 200
= ⋅ ⋅ ⋅ = ⋅ ⋅ ⋅ = 0.25
xdsec xdmach INsec UNmach TRI 0.18 5 100 3000
whereby
xdsec secondary per unit synchronous reactance
xdmach per unit synchronous reactance of machine
Unsec secondary rated voltage (CT and unit)
Insec secondary rated current (CT and unit)
INMach rated machine current
UNmach rated machine voltage
TRU transformation ratio of voltage transformers
TRI transformation ratio of current transformers
As a proposal in case when no exact data are available the settings below may be used
− The parameter 1/xdsec 1 is set to 1.1 times the formula value (safety factor), with an angle of
80 degree.
− The parameter 1/xdsec 2 is set to 90 % of λ1, with an angle of 90 degree.
− The parameter 1/xdsec 3 is set to 1.1 with an angle of 110 degree.
b) Rotor criteria
Instead of the excitation voltage acquisition, the signal of an AVR system failure has fed in via a
binary input.
Device Configuration:
Address Parameter/Comment Setting Note
Setting Group A:
Address Parameter/Comment (Secondary-)Setting Note
Underexcitation
3001 Underexcitation Protection ON
3011 T-Short Time Delay (char. & Uexc<) 2.00 sec
3012 State of Excitation Volt. Supervision ON
page 12 of 41
上海威能电力科技有限公司
3013 Excitation Voltage Superv. Pickup 8.00 V
3014A Undervoltage blocking Pickup 27.5 V
Characteristics
3002 Conductance Intersect Characteristic 1 0.25
3003 Inclination Angle of Characteristic 1 80 °
3004 Characteristic 1 Time Delay 10.00 sec
3005 Conductance Intersect Characteristic 2 0.28 I/In0
3006 Inclination Angle of Characteristic 2 90 °
3007 Characteristic 2 Time Delay 10.00 I/In0
3008 Conductance Intersect Characteristic 3 1.10 I/In0
3009 Inclination Angle of Characteristic 3 100 °
3010 Characteristic 3 Time Delay 0.50 sec
For steam turbines the reverse power has to be measured during reverse power operation of turbine
set with stop valves. The setting value has to be chosen with approx. 50% of the measured reverse
power. For measuring the protection relay has to be used.
Device Configuration:
Address Parameter/Comment Setting Note
page 13 of 41
上海威能电力科技有限公司
The forward power is set to the nominal active power of unit auxiliary transformer. The machine
output must therefore be referred to secondary values:
Assumed the nominal apparent power of unit auxiliary transformer is 40MVA, power factor is about
0.8, so
PUAT PUAT UNmach INmach PUAT
= ∗ * =
SNsec SNmach UNpri INpri 3 ⋅ UNpri ⋅ INpri
To avoid the low forward power protection mis-operating, System has an additional CFC logic to
control this protection, this logic has been proved effective in lots of projects including Yamunanagar
power plant generator protection.
Forward Power
Pf< Pickup 5128
& Pf< Trip
511
Block Pf<
511
Block Pf
BI
Msv tripped
NOT
PTFailure
OR
U<
Undervoltage CFC
For steam turbines the reverse power has to be measured during reverse power operation of turbine
set with stop valves. The setting value has to be chosen with approx. 50% of the measured reverse
power. For measuring the protection relay has to be used.
Device Configuration:
Address Parameter/Comment Setting Note
page 14 of 41
上海威能电力科技有限公司
0131 Reverse Forward Protection Enabled
Setting Group A:
Address Parameter/Comment (Secondary-)Setting Note
Forward Power
3201 Forward Power Supervision ON
3202 P-forw.< Supervision Pickup 7.7 %
3203 P-forw.> Supervision Pickup 17.0 %
3204 T-P-forw.< Time Delay 0.30 sec
3205 T-P-forw.> Time Delay oo sec
3206A Method of Operation Method Fast
Setting Group A:
Address Parameter/Comment (Secondary-)Setting Note
page 15 of 41
上海威能电力科技有限公司
The zone Z2 reach could be set slightly above the transformer reactance.
Primary impedance:
k R uR U2N
Zprim = ⋅ ⋅
100 100 SN.Tfr
where kR zone reach of zone Z. in %
uK percent impedance voltage of the Main transformer
SN,Tfr rated apparent power of the Main transformer
UN rated voltage of the Main transformer (Generator side)
Calculation:
Main transformer: uk = 14.5 %
SN,Tfr = 370 MVA
UN = 20 kV
Z1sec = (70%/100%) x (14.5%/100%) x (202 kV2/ 370MVA) x (110V/20kV) x (15000A/5A) = 1.81 Ω
address 3306
Zone Z1B is only active in case of open Gen. C.B.! Zone Z1B will be activated by C.B. aux. contact
via binary input. The zone reach should be: 100% transformer reactance+ the reactance from
transformer to Gen. C.B. Example: 120% transformer reactance
Z1Bsec = (100%/100%) x (14.5%/100%) x (202 kV2 / 370MVA) x (110V/20kV) x (15000A/5A) = 2.59Ω
address 3308
Similarly to Z1, zone reach of the second stage Z2 can be determined from e.g. 100% transformer
reactance. If zone 2 was activated, the settings of the distance protection at the grid side would have
to be considered.
Z2sec = (120%/100%) x (14.5%/100%) x (202 kV2 / 370MVA) x (110V/20kV) x (15000A/5A) = 3.10Ω
address 3310
The power swing block is mostly used for impedance stage1 because the delay time T1 for this
stage is set low.
A compromise has to be found for the distance between power swing polygon and the trip polygon
(P/SPOL-TPOL address 3314) and for the rate of changing of the impedance vector (dZ/dt address
3315):
In 7UM62 Manual, the default setting for dZ/dt is 60Ω/s (In=5A) which is adequate for most
applications. This is also the basis for the minimum distance P/PSOL-TPOL assuming that for
detection of a power swing there must be one impedance value between P/PSOL-TPOL.
Setting condition: P/PSOL-TPOL > dZ/dt x ∆ t.
Fault detection current pickup:
Set I> pickup=1.2Ign=4.08A address 3302
Device Configuration:
Address Parameter/Comment Setting Note
UN.Gen
X′ds = ⋅ xds′ Calculation with generator data:
3 ⋅ IN.Gen
where:
Xds’ transient reactance of the machine
xds’ transient per unit reactance xds’ = 20.2 %
UN,Gen rated machine voltage UN = 20 kV
IN,Gen rated machine current IN = 10189 A
Thus, the primary transient reactance:
Zb ≈ X’ds = [20000V / (√3 x 10189A)] ⋅ 0.2 = 0.227Ω
Zbsec=0.227 x (110V/20kV) x (15000A/5A)=3.75Ω address 3505
page 17 of 41
上海威能电力科技有限公司
Zasec=0.102 x (110V/20kV) x (15000A/5A)=1.68Ω address 3504
Assuming that the remaining transformer reactance and the covered system reactance should be
0.312 Ω (primary), the setting of 3507 results in:
Zd-ZC = 0.188 Ω
Zdsec-Zcsec=0.188 x (110V/20kV) x (15000A/5A)=3.10Ω address 3507
The holding time (address 3511) determines how long time a detected out-of-step condition (passing
through) is maintained so that the counter is incremented with the next passing through. This time
should be set higher than the longest expected slip period (i.e. the smallest slip frequency).
Conventional values lie between 20s and 30s.
Device Configuration:
Address Parameter/Comment Setting Note
Setting Group A:
Address Parameter/Comment (Secondary-)Setting Note
Out-of-step
3501 Out of Step Protection ON
3502 Pickup Current for Measuring Release I1> 101.9 %
3503 Pickup Current for Measuring Release I2< 17.0 %
3504 Resistance Za of the Polygon (width) 1.68 Ω
3505 Resistance Zb of the Polygon (reverse) 3.75 Ω
3506 Resistance Zc of Polygon (forward char.1) 2.04 Ω
3507 Reactance Dif. Char.1 – Char. 2 (forward) 3.10 Ω
3508 Angle of Inclination of the Polygon 90.0 °
3509 Number of Powerswing (Characteristic 1) 1
3510 Number of Powerswing (Characteristic 2) 4
3511 Holding Time of Fault Detection 20.00 sec
3512 Min. Signal Time for Annun. Char. 1/2 0.05 sec
The thermal time constant τ is decisive for the time to reach the limit temperature and thus for the
time trip (address 1603). The actual percentage of the temperature is calculated from the stator
current using the thermal replica.
Assumed,
τ = 37s address 1603
Device Configuration:
Address Parameter/Comment Setting Note
page 18 of 41
上海威能电力科技有限公司
Setting Group A:
Address Parameter/Comment (Secondary-)Setting Note
Thermal Overload
1601 Thermal overload protection ON
1602 K-Factor 0.71
1603 Thermal Time Constant 37 sec
1604 Thermal Alarm Stage 90 %
1610A Current Overload Alarm Setpoint 3.55 A
1612A Kt-Factor when Motor Stops 1
1615A Maximum Current for Thermal Replica 10.19 A
1616A Emergency Time [not relevant] 100 sec
Temperature Input
1605 Temperature at rated sec. Current [not used] 100 °C
1607 Temperature Input [not used Disabled
1608 Temperature for scaling [not used 100 °C
The U>> stage as a short-time stage should be set such that the transients after full-load rejection
do not initiate tripping. A common setting is, 130% UN with a delay of 0.1s
Device Configuration:
Address Parameter/Comment Setting Note
Setting Group A:
Address Parameter/Comment (Secondary-)Setting Note
Overvoltage
4101 Overvoltage protection ON
4102 U> Pickup 121 V
4103 T U> Time Delay 5.00 sec
4104 U>> Pickup 143 V
4105A T U>> Time Delay 0,50 sec
4106A U> Drop Out Ratio 0,95
4107A Measurement Values for U> Voltage Protection with U Phase-Phase
Setting Group A:
Address Parameter/Comment (Secondary-)Stting Note
Overvoltage
page 19 of 41
上海威能电力科技有限公司
4001 Overvoltage protection ON
4002 U< Pickup 88 V
4003 T U< Time Delay 1.50 sec
4004 U<< Pickup 110 V
4005 T U<< Time Delay oo sec
4006A U< Drop Out Ratio 1.05
2.1
2.0
1.9
1.8
( U/U0 ) RATIO OF ACTUAL VOLTAGE TO RATED VOLTAGE
1.7
1.6
1.5
1.4
1.3
1.2
1.1
1.0
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.0
-4 -2 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64
WITHSTAND TIME IN SECONDS
According the overfluxing curve supplied by owner, the overfluxing protection setting values are as
following:
Device Configuration:
Address Parameter/Comment Setting Note
Setting Group A:
Address Parameter/Comment (Secondary-) Setting Note
Overexcitation
page 20 of 41
上海威能电力科技有限公司
4301 Overexcitation Protection U/f ON
4302 U/f> Pickup 1.20
4303 T U/f> Time Delay 5.00 sec
4304 U/f>> Pickup 1.40
4305 T U/f>> Time Delay 2.00 sec
Characteristics *)
4306 U/f = 1.05 Time Delay 20000 sec
4307 U/f = 1.10 Time Delay 20000 sec
4308 U/f = 1.15 Time Delay 20000 sec
4309 U/f = 1.20 Time Delay 20000 sec
4310 U/f = 1.25 Time Delay 60 sec
4311 U/f = 1.30 Time Delay 38 sec
4312 U/f = 1.35 Time Delay 18 sec
4313 U/f = 1.40 Time Delay 5 sec
4314 Time for Cooling Down 37 sec
*) Values could be chosen directly by using the overexcitation curve of generator or main
transformer.
The frequency protection function is acting as back up protection to the turbine speed monitoring
protection. As a matter of principle, the setting values for frequency and delay times depend on the
values supplied by the turbine manufacturer.
In this project, this function has 2 stages of under-frequency and 2 stages of over-frequency:
In F11 7UM622 relay,
81U-1: stage-1, f<48.5Hz, t=5.0s ⇒ TRIP
81U-2: stage-2, f<47.5Hz, t=3.0s ⇒ TRIP
81U-3: stage-3, f>51.5Hz, t=5.0s ⇒ TRIP
81O-1: stage-1, f>52.5Hz, t=3.0s ⇒ TRIP
Device Configuration:
Address Parameter/Comment Setting Note
Setting Group A:
Address Parameter/Comment (Secondary)- Note
Setting
Frequency Prot.
4201 Over/Under Frequency Protection ON
4202 (50Hz) f1 Pick-up 48.50 Hz
4204 Time Delay f1 5.0 sec
4205 (50Hz) f2 Pick-up 47.50 Hz
4207 Time Delay f2 3.0 sec
4208 (50Hz) f3 Pick-up 51.50 Hz
4210 Time Delay f3 5.0 sec
4211 (50Hz) F4 Pick-up 52.50 Hz
page 21 of 41
上海威能电力科技有限公司
4213 Time Delay f4 3.0 sec
4214 Handling of Threshold f4 Freq. prot. stage
overfrequency
4215 Minimum operating voltage, below which frequency 66 V
measurement f>< is blocked
Device Configuration:
Address Parameter/Comment Setting Note
Setting Group A:
Address Parameter/Comment (Secondary-)Setting Note
Inadvert. En.
7101 Inadvertent Energisation ON
7102 I Stage Pickup 1.50 A
7103 Release Threshold U1< 55.0 V
7104 Pickup Time Delay T U1< 3.00 sec
7105 Drop Out Time Delay T U1< 3.00 sec
Device Configuration:
Address Parameter/Comment Setting Note
0186 External Trip Function 1 Enabled
(BI 1: “I&C trip ")
0187 External Trip Function 2 Enabled
(BI 2: “Cooling water loss")
0188 External Trip Function 3 Enabled
(BI 6: “Stator-winding temp high")
0189 External Trip Function 4 Enabled
(BI 7: “Stator-winding temp high-high")
Setting Group A: *)
Address Parameter/Comment (Secondary-)Setting Note
External Trip
8601 External Trip Function 1 ON
8602 External Trip 1 Time Delay 0.00 sec
8701 External Trip Function 2 ON
8702 External Trip 2 Time Delay 0.00 sec
8801 External Trip Function 3 ON
8802 External Trip 3 Time Delay 0.00 sec
page 22 of 41
上海威能电力科技有限公司
8901 External Trip Function 4 ON
8902 External Trip 4 Time Delay 0.00 sec
3.3.4 Settings for ( Interturn Protection) stator 90% ground protection Uo> (59N(IN)-A)
The interturn fault protection detects faults between turns within a generator winding (phase).
To reduces the risk of overfunction, the time delay is 0.50 sec. address 5005
Setting Address 5002 : 10%
Device Configuration:
Address Parameter/Comment Setting Note
page 24 of 41
上海威能电力科技有限公司
0117 Unbalanced Load ( Negative sequence) Enabled
0118 Start-up O/C Protection Disabled
0120 Differential Protection Generator/Motor
0121 Restricted Earth Fault Protection Disabled
0130 Underexcitation Protection Enabled
0131 Reverse Power Protection Enabled
0132 Forward Power Protection Enabled
0133 Impedance Protection Enabled
0135 Out of Step Protection Enabled
0140 Undervoltage Protection Enabled
0141 Overvoltage Protection Enabled
0142 Frequency Protection Enabled
0143 Overexcitation Protection Enabled
0144 Inverse Undervoltage Protection Up< Disabled
0150 Stator Earth Fault Protection Disabled
0151 Sensitive Earth Current Protection Disabled
0152 Stator Earth Fault Prot. 3rd Harmonic Disabled
0153 100% Stator Earth Fault Protection Enabled
0154 Sensitive Earth Current Prot. B Disabled
0155 Interturn Protection Disabled
0160 Rotor Earth Fault Protection (R, fn) Disabled
0161 Rotor Earth Fault Protection (1-3Hz) Disabled
0165 Motor Starting Time Supervision Disabled
0166 Restart Inhibit for Motors Disabled
0170 Breaker Failure Protection Disabled
0171 Inadvertent Energisation Enabled
0172 DC Voltage/Current Protection Disabled
0180 Fuse Failure Monitor Enabled
0181 Measured Value Supervision Enabled
0182 Trip Circuit Supervision Disabled
0185 Threshold Supervision Enabled
0186 External Trip Function 1 Enabled I&C trip
0187 External Trip Function 2 Enabled Cooling water
0188 External Trip Function 3 Enabled SEF detect
0189 External Trip Function 4 Disabled
page 25 of 41
上海威能电力科技有限公司
page 26 of 41
上海威能电力科技有限公司
1
I Diff >>= I Nobj = 5 I Nobj → address 1231
Uk %
c) The tripping characteristic:
We use the default settings of the slope 1 and slope 2, also the default settings of BP1 and BP2.
Here, s1=0.25, s2=0.50, BP1=0, BP2=2.5
Device Configuration:
Address Parameter/Comment Setting Note
page 27 of 41
上海威能电力科技有限公司
Requirement:
- through the low level signal the cables must be twisted or shielded.
- the impedance from the bandpass to the load resistor must be low ohmic.
- at long distances the 20-Hz-equipment must be located direct on NT cell.
Band- 20Hz
pass
Gen.
1 RLoad
RE=
0.651Ω
ω ⋅C < 5kΩ
<< 1kΩ 600/5A
U20Hz(R) 100%
Fourier
-Filter
I20Hz(R) Gr.-
20Hz Fault
2
k VT 20kV 1
RSEF = K 2Trans = ⋅ = 57.9 address 0275
kICT 0.24kV 600 / 5
Rsec = Rsef = RPrim / R SEF
Rsef< = 5000Ω / 57.9 ≈ 86.4Ω address 5302
Rsef<< = 1000Ω / 57.9 ≈ 17.3Ω (settings at least 20 Ohm) address 5303
The pick-up value of the current tripping stage should be chosen such that this stage covers
approximately 90% of the stator winding. This results in the following suggestion:
⋅240V 1 ⋅240V 1
I.SEF = 0.1* * = 0.1* * = 0.31 A address. 5306
RLoad kICT 0.651Ω 600A / 5A
RLoad Load resistor at the Grounding transformer 0.651 Ω
KICT transformation ratio of the intermediate current transformer 600A/5A
Device Configuration:
Address Parameter/Comment Setting Note
page 28 of 41
上海威能电力科技有限公司
5309 Correction Angle for I SEF 100% *) 0 °
5310A Resistance Rps *) 0.0 Ω
5311A Parallel Load Resistance *) oo Ω
*) To be measured during commissioning!!
whereby
xdsec secondary per unit synchronous reactance
xdmach per unit synchronous reactance of machine
Unsec secondary rated voltage (CT and unit)
Insec secondary rated current (CT and unit)
INMach rated machine current
UNmach rated machine voltage
TRU transformation ratio of voltage transformers
TRI transformation ratio of current transformers
As a proposal in case when no exact data are available the settings below may be used
− The parameter 1/xdsec 1 is set to 1.1 times the formula value (safety factor), with an angle of
80 degree.
− The parameter 1/xdsec 2 is set to 90 % of λ1, with an angle of 90 degree.
− The parameter 1/xdsec 3 is set to 1.1 with an angle of 110 degree.
b) Rotor criteria
Instead of the excitation voltage acquisition, the signal of an AVR system failure has fed in via a
binary input.
Device Configuration:
Address Parameter/Comment Setting Note
Setting Group A:
Address Parameter/Comment (Secondary-)Setting Note
Underexcitation
3001 Underexcitation Protection ON
3011 T-Short Time Delay (char. & Uexc<) 2.00 sec
3012 State of Excitation Volt. Supervision ON
page 29 of 41
上海威能电力科技有限公司
3013 Excitation Voltage Superv. Pickup 8.00 V
3014A Undervoltage blocking Pickup 27.5 V
Characteristics
3002 Conductance Intersect Characteristic 1 0.25
3003 Inclination Angle of Characteristic 1 80 °
3004 Characteristic 1 Time Delay 10.00 sec
3005 Conductance Intersect Characteristic 2 0.28 I/In0
3006 Inclination Angle of Characteristic 2 90 °
3007 Characteristic 2 Time Delay 10.00 I/In0
3008 Conductance Intersect Characteristic 3 1.10 I/In0
3009 Inclination Angle of Characteristic 3 100 °
3010 Characteristic 3 Time Delay 0.50 sec
For steam turbines the reverse power has to be measured during reverse power operation of turbine
set with stop valves. The setting value has to be chosen with approx. 50% of the measured reverse
power. For measuring the protection relay has to be used.
Device Configuration:
Address Parameter/Comment Setting Note
page 30 of 41
上海威能电力科技有限公司
The forward power is set to the nominal active power of unit auxiliary transformer. The machine
output must therefore be referred to secondary values:
Assumed the nominal apparent power of unit auxiliary transformer is 40MVA, power factor is about
0.8, so
PUAT PUAT UNmach INmach PUAT
= ∗ * =
SNsec SNmach UNpri INpri 3 ⋅ UNpri ⋅ INpri
To avoid the low forward power protection mis-operating, System has an additional CFC logic to
control this protection, this logic has been proved effective in lots of projects including Yamunanagar
power plant generator protection.
Forward Power
Pf< Pickup 5128
& Pf< Trip
511
Block Pf<
511
Block Pf
BI
Msv tripped
NOT
PTFailure
OR
U<
Undervoltage CFC
For steam turbines the reverse power has to be measured during reverse power operation of turbine
set with stop valves. The setting value has to be chosen with approx. 50% of the measured reverse
power. For measuring the protection relay has to be used.
Device Configuration:
Address Parameter/Comment Setting Note
page 31 of 41
上海威能电力科技有限公司
0131 Reverse Forward Protection Enabled
Setting Group A:
Address Parameter/Comment (Secondary-)Setting Note
Forward Power
3201 Forward Power Supervision ON
3202 P-forw.< Supervision Pickup 7.7 %
3203 P-forw.> Supervision Pickup 17.0 %
3204 T-P-forw.< Time Delay 0.30 sec
3205 T-P-forw.> Time Delay oo sec
3206A Method of Operation Method Fast
Setting Group A:
Address Parameter/Comment (Secondary-)Setting Note
page 32 of 41
上海威能电力科技有限公司
The zone Z2 reach could be set slightly above the transformer reactance.
Primary impedance:
k R uR U2N
Zprim = ⋅ ⋅
100 100 SN.Tfr
where kR zone reach of zone Z. in %
uK percent impedance voltage of the Main transformer
SN,Tfr rated apparent power of the Main transformer
UN rated voltage of the Main transformer (Generator side)
Calculation:
Main transformer: uk = 14.5 %
SN,Tfr = 370 MVA
UN = 20 kV
Z1sec = (70%/100%) x (14.5%/100%) x (202 kV2/ 370MVA) x (110V/20kV) x (15000A/5A) = 1.81 Ω
address 3306
Zone Z1B is only active in case of open Gen. C.B.! Zone Z1B will be activated by C.B. aux. contact
via binary input. The zone reach should be: 100% transformer reactance+ the reactance from
transformer to Gen. C.B. Example: 120% transformer reactance
Z1Bsec = (100%/100%) x (14.5%/100%) x (202 kV2 / 370MVA) x (110V/20kV) x (15000A/5A) = 2.59Ω
address 3308
Similarly to Z1, zone reach of the second stage Z2 can be determined from e.g. 100% transformer
reactance. If zone 2 was activated, the settings of the distance protection at the grid side would have
to be considered.
Z2sec = (120%/100%) x (14.5%/100%) x (202 kV2 / 370MVA) x (110V/20kV) x (15000A/5A) = 3.10Ω
address 3310
The power swing block is mostly used for impedance stage1 because the delay time T1 for this
stage is set low.
A compromise has to be found for the distance between power swing polygon and the trip polygon
(P/SPOL-TPOL address 3314) and for the rate of changing of the impedance vector (dZ/dt address
3315):
In 7UM62 Manual, the default setting for dZ/dt is 60Ω/s (In=5A) which is adequate for most
applications. This is also the basis for the minimum distance P/PSOL-TPOL assuming that for
detection of a power swing there must be one impedance value between P/PSOL-TPOL.
Setting condition: P/PSOL-TPOL > dZ/dt x ∆ t.
Fault detection current pickup:
Set I> pickup=1.2Ign=4.08A address 3302
Device Configuration:
Address Parameter/Comment Setting Note
page 34 of 41
上海威能电力科技有限公司
Zasec=0.102 x (110V/20kV) x (15000A/5A)=1.68Ω address 3504
Assuming that the remaining transformer reactance and the covered system reactance should be
0.312 Ω (primary), the setting of 3507 results in:
Zd-ZC = 0.188 Ω
Zdsec-Zcsec=0.188 x (110V/20kV) x (15000A/5A)=3.10Ω address 3507
The holding time (address 3511) determines how long time a detected out-of-step condition (passing
through) is maintained so that the counter is incremented with the next passing through. This time
should be set higher than the longest expected slip period (i.e. the smallest slip frequency).
Conventional values lie between 20s and 30s.
Device Configuration:
Address Parameter/Comment Setting Note
page 35 of 41
上海威能电力科技有限公司
Thermal Overload
1601 Thermal overload protection ON
1602 K-Factor 0.71
1603 Thermal Time Constant 37 sec
1604 Thermal Alarm Stage 90 %
1610A Current Overload Alarm Setpoint 3.55 A
1612A Kt-Factor when Motor Stops 1
1615A Maximum Current for Thermal Replica 10.19 A
1616A Emergency Time [not relevant] 100 sec
Temperature Input
1605 Temperature at rated sec. Current [not used] 100 °C
1607 Temperature Input [not used Disabled
1608 Temperature for scaling [not used 100 °C
The U>> stage as a short-time stage should be set such that the transients after full-load rejection
do not initiate tripping. A common setting is, 130% UN with a delay of 0.1s
Device Configuration:
Address Parameter/Comment Setting Note
page 36 of 41
上海威能电力科技有限公司
4.1.14 Settings for overexcitation (Volt /Hz) protection – (24G-B)
2.1
2.0
1.9
1.8
( U/U0 ) RATIO OF ACTUAL VOLTAGE TO RATED VOLTAGE
1.7
1.6
1.5
1.4
1.3
1.2
1.1
1.0
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.0
-4 -2 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64
WITHSTAND TIME IN SECONDS
According the overfluxing curve supplied by owner, the overfluxing protection setting values are as
following:
Device Configuration:
Address Parameter/Comment Setting Note
page 37 of 41
上海威能电力科技有限公司
4308 U/f = 1.15 Time Delay 20000 sec
4309 U/f = 1.20 Time Delay 20000 sec
4310 U/f = 1.25 Time Delay 60 sec
4311 U/f = 1.30 Time Delay 38 sec
4312 U/f = 1.35 Time Delay 18 sec
4313 U/f = 1.40 Time Delay 5 sec
4314 Time for Cooling Down 37 sec
*) Values could be chosen directly by using the overexcitation curve of generator or main
transformer.
The frequency protection function is acting as back up protection to the turbine speed monitoring
protection. As a matter of principle, the setting values for frequency and delay times depend on the
values supplied by the turbine manufacturer.
In this project, this function has 2 stages of under-frequency and 2 stages of over-frequency:
In F11 7UM622 relay,
81U-1: stage-1, f<48.5Hz, t=5.0s ⇒ TRIP
81U-2: stage-2, f<47.5Hz, t=3.0s ⇒ TRIP
81U-3: stage-3, f>51.5Hz, t=5.0s ⇒ TRIP
81O-1: stage-1, f>52.5Hz, t=3.0s ⇒ TRIP
Device Configuration:
Address Parameter/Comment Setting Note
page 38 of 41
上海威能电力科技有限公司
4.1.16 Settings for Inadvertent Energization protection– (50/27-B)
The inadvertent energizing protection serves to limit damage by accidental connection of the
stationary or already started, but not yet synchronized generator, by fast actuation of the mains
breaker.
IPickup = 30%*In= 0.3*5.0 = 1.5 A
U1release = (50~70)%*Un= 0.5*110 = 55 V
Device Configuration:
Address Parameter/Comment Setting Note
page 39 of 41
上海威能电力科技有限公司
0114 Inverse O/C Time Protection Disabled
0116 Thermal Overload Protection Disabled
0131 Reverse Power Protection Enabled
0140 Undervoltage Protection Disabled
0141 Overvoltage Protection Disabled
0142 Frequency Protection Disabled
0143 Overexcitation Protection Disabled
0150 Stator Earth Fault Protection Non-Directional only U0
0151 Sensitive Earth Current Protection Disabled
0180 Fuse Failure Monitor Enabled
0181 Measured Value Supervision Enabled
0185 Threshold Supervision Disabled
0186 External Trip Function 1 Disabled
0187 External Trip Function 2 Disabled
page 40 of 41
上海威能电力科技有限公司
Reverse Power
3101 Reverse power protection ON
3102 P> Reverse Pick-up -0.85 %
3103 Time Delay Long (without Stop value) 1.00 sec
3104 Time Delay Long (with Stop value) oo sec
3105A Pickup Holding Time 0.00 sec
4.2.4 Settings for ( Interturn Protection) stator 90% ground protection Uo> (59N(IN)-B)
The interturn fault protection detects faults between turns within a generator winding (phase).
To reduces the risk of overfunction, the time delay is 0.50 sec. address 5005
Setting Address 5002 : 10%
Device Configuration:
Address Parameter/Comment Setting Note
page 41 of 41