Liebert APM: User Manual-15-90kVA, 120, 208, 480 and 600V, 50/60Hz

Download as pdf or txt
Download as pdf or txt
You are on page 1of 144

Liebert® APM™

User Manual–15-90kVA, 120, 208, 480 and 600V, 50/60Hz


TABLE OF CONTENTS
IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
GLOSSARY OF SYMBOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
1.0 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
1.1 Battery Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1.1 Battery Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.0 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
2.1 Initial Inspections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.1.1 Storing for Delayed Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.2 Preliminary Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.2.1 Identification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.3 UPS Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.3.1 Positioning the UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.3.2 Environmental Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.4 Considerations in Moving the Liebert APM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.5 Mechanical Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.5.1 Clearances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.5.2 Floor Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.5.3 Cable Entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.5.4 Special Considerations for Parallel Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.5.5 Special Considerations for 1+N Parallel Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.6 45kVA and 90kVA UPS Frames—Auxiliary Cabinets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.6.1 Optional Cabinets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.7 Optional Seismic Brackets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.8 Liebert FlexPower™ Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.9 Static Bypass Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.0 ELECTRICAL CONNECTIONS—UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
3.1 Power Cabling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.1.1 Cable Rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.2 External Protective Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.2.1 Rectifier and Bypass Input Supply of the UPS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.2.2 External Battery. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.2.3 UPS Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.2.4 UPS Input Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.2.5 UPS Input Configuration with Transformers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.2.6 Cabling Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.2.7 Cable Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.2.8 Accessory Fuses and Backfeed Breaker Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3.2.9 Safety Ground . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
3.2.10 Protective Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
3.2.11 Cabling Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
3.3 Control Cables Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
3.3.1 Static Bypass Assembly Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

i
3.4 Dry Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
3.4.1 Input Dry Contacts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
3.4.2 Output Dry Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
3.4.3 Liebert BDC Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
3.4.4 Battery Cabinet Interface Connectors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
3.4.5 EPO Input—Optional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
4.0 PARALLEL SYSTEM AND LBS SYSTEM INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
4.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
4.2 System Installation Procedures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
4.2.1 Preliminary Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
4.2.2 Cabinet Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
4.2.3 External Protective Device. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
4.2.4 Power Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
4.2.5 Input Breaker Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
4.2.6 Output Breaker Control Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
4.2.7 Parallel Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
4.2.8 Key Interlock System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
4.2.9 Remote EPO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
4.3 LBS System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
4.3.1 Cabinet Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
4.3.2 External Protective Device. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
4.3.3 Power Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
4.3.4 Control Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
5.0 BATTERY INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
5.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
5.2 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
5.3 UPS Batteries—Liebert APM 45kVA Frame Only. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
5.3.1 Internal Battery Breaker Component Locations and Control Wiring. . . . . . . . . . . . . . . . . . . 47
5.4 External Battery Cabinet Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
5.4.1 Matching Battery Cabinets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
5.4.2 Connecting the Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
5.4.3 Installation Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
5.4.4 Connecting the Battery Cabinet to the UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
5.5 Non-Standard Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
5.6 Battery Ground Fault Detection Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
6.0 LIEBERT BDC™ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57
6.1 Normal (UPS) Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
6.2 UPS Static Bypass Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
6.3 Maintenance Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
6.4 Locating the Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
6.5 Cable Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
6.5.1 Wiring Preparation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
6.5.2 Power Cable Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
6.5.3 Input/Output Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
6.6 Bolting Cabinets Together . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61

ii
7.0 INSTALLATION DRAWINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .62
8.0 LIEBERT INTELLISLOT® INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
8.1 Liebert IntelliSlot Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
8.2 Liebert IntelliSlot Web Card—SNMP/HTTP Network Interface Card . . . . . . . . . . . . . . . . . 78
8.2.1 Liebert IntelliSlot® Unity Cards—IS-UNITY-LIFE, IS-UNITY-S, IS-UNITY-DP . . . . . . . . 79
8.3 Liebert IntelliSlot Card Web Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
8.4 Liebert IntelliSlot® Relay Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
8.4.1 Liebert IntelliSlot Relay Card Pin Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
8.4.2 Liebert IntelliSlot® Relay Card Jumper Setup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
8.5 Liebert IntelliSlot™ MultiPort Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
8.6 Alber® BDSi™ Battery Monitoring System—Optional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
8.7 Battery Temperature Compensation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
9.0 OPERATOR CONTROL AND DISPLAY PANEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
9.1 Operator Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
9.2 Mimic Display Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
9.3 Control Buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
9.4 Alarm Buzzer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
9.5 LCD Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
9.6 Navigation Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
9.7 LCD Menus and Data Items . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
9.8 Language Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
9.9 Current Date and Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
9.10 UPS History Log. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
9.11 Types of LCD Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
9.11.1 Opening Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
9.11.2 Default Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
9.11.3 UPS Help Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
9.11.4 Screen Saver Window. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
9.12 Pop-Up Windows . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
9.12.1 From Bypass to Inverter Mode With Power Interruption . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
9.12.2 From Inverter to Bypass Mode With Interruption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
9.12.3 System Self-Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
9.12.4 Battery Capacity Test Confirmation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
9.12.5 Battery Self-Test Aborted, Condition Not Met . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
9.12.6 Battery Equalize Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
9.12.7 Battery Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
9.12.8 Battery Refresh Charge Aborted, Condition Not Met . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
9.12.9 Enter Control Password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
10.0 OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .98
10.1 Liebert APM Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
10.2 UPS Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
10.2.1 Startup Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
10.2.2 Startup in ECO Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
10.2.3 Switching Between UPS Operation Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102

iii
10.3 UPS Battery Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
10.4 Switching the UPS from Normal Operation to Maintenance Bypass . . . . . . . . . . . . . . . . . 103
10.5 Switching the UPS from Maintenance Bypass to Normal Operation . . . . . . . . . . . . . . . . . 104
10.6 De-Energize Liebert APM with Maintenance Bypass Cabinet . . . . . . . . . . . . . . . . . . . . . . 105
10.7 De-Energize Liebert APM Without Maintenance Bypass Cabinet . . . . . . . . . . . . . . . . . . . 106
10.8 Operation of Two Liebert APM Units in Parallel Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
10.8.1 Procedure to Take UPS1 Offline While Leaving UPS2 Online . . . . . . . . . . . . . . . . . . . . . . . 108
10.8.2 Procedure to Put UPS1 Back Online . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
10.8.3 Procedure to Take UPS2 Offline While Leaving UPS1 Online . . . . . . . . . . . . . . . . . . . . . . . 108
10.8.4 Procedure to Put UPS2 Back Online . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
10.9 APM Procedure from Parallel Inverter Operation to Wrap-Around Bypass . . . . . . . . . . . 109
10.10 APM Procedure from Wrap-Around Bypass to Parallel Inverter Operation . . . . . . . . . . . 109
10.11 Parallel APM System Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
10.12 Parallel APM System Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
10.13 Emergency Shutdown With EPO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
10.14 Auto Restart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
10.15 Reset After Shutdown for Emergency Stop (EPO Action) or Other Conditions . . . . . . . . . 110
10.16 Battery Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
10.16.1 Battery Undervoltage Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
10.16.2 Battery End-of-Discharge (EOD) Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
10.17 Replacing Dust Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
10.18 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
10.19 Static Bypass Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
11.0 SPECIFICATIONS AND TECHNICAL DATA. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
11.1 Conformity and Standards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
11.2 UPS Environmental . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
11.3 Batteries Approved for Use in Liebert APM Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
11.4 UPS Electrical Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
12.0 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
12.1 Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
12.2 Limited Life Components. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
12.3 Routine Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
12.3.1 Record Log. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
12.3.2 Air Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
12.3.3 Battery Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
12.3.4 Battery Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
12.3.5 Torque Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
12.4 Detecting Trouble . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
12.5 Reporting a Problem. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
12.6 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
12.7 Recommended Test Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
APPENDIX A - HAZARDOUS SUBSTANCES OR ELEMENTS ANNOUNCEMENT . . . . . . . . . . . . . . . A129
APPENDIX B - UPS STATUS MESSAGES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A130

iv
FIGURES
Figure 1 Cabinet arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Figure 2 Liebert FlexPower assembly indicators and controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Figure 3 Static bypass assembly connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Figure 4 Single UPS block diagram—dual input single source configuration . . . . . . . . . . . . . . . . . . . . . . . 17
Figure 5 Liebert APM in a split bypass configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Figure 6 Control wiring for the dual input transformer configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Figure 7 Input busbars—Liebert APM 45kVA frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Figure 8 Input busbars—Liebert APM 90kVA frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Figure 9 Liebert BDC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Figure 10 Busbars—Liebert BDC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Figure 11 Busbars—External 600mm battery cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Figure 12 Busbars—External 900mm battery cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Figure 13 Accessory fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Figure 14 Dual input backfeed breaker wiring when bypass distribution cabinet not used . . . . . . . . . . . . . 27
Figure 15 Ground and neutral busbar connections—45kVA frame busbars . . . . . . . . . . . . . . . . . . . . . . . . . 29
Figure 16 Ground and neutral busbar connections—90kVA frame busbars . . . . . . . . . . . . . . . . . . . . . . . . . 30
Figure 17 Static bypass assembly connections to display cabinet and options . . . . . . . . . . . . . . . . . . . . . . . 33
Figure 18 Auxiliary terminal block detail (static switch assembly front panel) . . . . . . . . . . . . . . . . . . . . . . 33
Figure 19 Input dry contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Figure 20 Output dry contacts and EPO wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Figure 21 EPO wiring and signal names for J6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Figure 22 Single UPS Remote Emergency Power Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Figure 23 UPS system with external maintenance switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Figure 24 Input breaker control wiring for parallel systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Figure 25 Output breaker control wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Figure 26 Connection of parallel control cables of parallel system. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Figure 27 Key interlock system control wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Figure 28 Locations of ports J1, J2 and J3 on bypass module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Figure 29 Remote Emergency Power Off wiring for parallel UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Figure 30 Typical dual bus system (with STS and LBS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Figure 31 Connection of typical dual bus system of two parallel systems . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Figure 32 Connection of typical dual bus system of two single UPS’s without redundant LBS cable . . . . . 45
Figure 33 Connection of typical dual bus system of two single UPS’s with redundant LBS cable . . . . . . . . 45
Figure 34 Internal battery breaker component locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Figure 35 Internal battery control wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Figure 36 Bolting the battery cabinet to the Liebert APM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Figure 37 Battery cabinet, 600mm wide—details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Figure 38 Battery trays for 600mm battery cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Figure 39 Battery cabinet with trays for 900mm battery cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Figure 40 Battery cabinet connection to Liebert APM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Figure 41 Battery ground fault detection component location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Figure 42 Control wiring diagram for battery ground fault detection option . . . . . . . . . . . . . . . . . . . . . . . . 56
Figure 43 Single input UPS with external Liebert BDCwith optional internal transformer—typical
configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Figure 44 Liebert BDC—access plate removed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Figure 45 BDC connection to Liebert APM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Figure 46 Bolting Liebert APM to a Liebert BDC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Figure 47 UPS dimensions- front view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Figure 48 Lineup arrangement, Liebert APM with battery and Liebert BDCs . . . . . . . . . . . . . . . . . . . . . . . 62

v
Figure 49 UPS dimensions continued, center of gravity—side, top and bottom views . . . . . . . . . . . . . . . . . 63
Figure 50 Liebert APM with top fan kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Figure 51 UPS main components—typical unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Figure 52 UPS cable connections—45kVA and 90kVA frames . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Figure 53 Battery cabinet connection to UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Figure 54 Battery cabinet connection to UPS (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Figure 55 Battery cabinet outline drawing, weights and center of gravity, 600mm cabinet . . . . . . . . . . . . 72
Figure 56 Battery cabinet outline drawing, weights and center of gravity 900mm cabinet . . . . . . . . . . . . . 73
Figure 57 Outline drawing, Liebert BDC for Liebert APM, 15-45kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Figure 58 Outline drawing, Liebert BDC for Liebert APM, 15-90kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Figure 59 Liebert BDC connection to UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Figure 60 Acceptable hardware configuration for torque application. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Figure 61 Seismic mounting bracket details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Figure 62 Liebert IntelliSlot Web card display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Figure 63 Pin location and numbering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Figure 64 Jumper location and numbering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Figure 65 Liebert IntelliSlot MultiPort card pin assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Figure 66 Alber BDSi controller and input connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Figure 67 Multi-temperature sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Figure 68 Overview of control panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Figure 69 Mimic display indicators location. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Figure 70 Control button layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Figure 71 Alarm buzzer location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Figure 72 Sections of the LCD. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Figure 73 Menu tree . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Figure 74 Language selection screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Figure 75 Date and time screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Figure 76 History log records . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Figure 77 Opening display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Figure 78 Default screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Figure 79 Screen saver window. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Figure 80 Battery start button location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Figure 81 Typical configuration for single UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Figure 82 Liebert APM six-breaker buyout paralleling configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Figure 83 Dust filter replacement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Figure 84 Single module block diagram—Single input configuration with three-breaker Liebert
BDC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Figure 85 Single module block diagram—Dual input configuration with three-breaker Liebert
BDC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Figure 86 Block diagram—Single input configuration with four-breaker internal bypass . . . . . . . . . . . . . 114
Figure 87 Battery, circuit breaker and UPS wiring with external batteries with four connecting
wires. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Figure 88 Battery, circuit breaker and UPS wiring with external batteries with three connecting
wires. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122

vi
TABLES
Table 1 Battery voltage, nominal and float . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Table 2 Battery retorque values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Table 3 LED indications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Table 4 Description of dry contact input port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Table 5 Output dry contact relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Table 6 Liebert BDC interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Table 7 Battery cabinet interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Table 8 EPO input contact relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Table 9 Control wiring for Liebert APM to battery cabinet. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Table 10 Control wiring for Liebert APM UPS to Liebert BDC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Table 11 Center of gravity and weights for Liebert APM 90 kVA frame . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Table 12 Center of gravity and weights for Liebert APM 90 kVA frame with top fan option . . . . . . . . . . . 66
Table 13 Center of gravity and weights for Liebert APM 45 kVA frame . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Table 14 Center of gravity and weights for Liebert APM 45 kVA frame with top fan option . . . . . . . . . . . 67
Table 15 Interconnect wiring for Liebert APM to battery cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Table 16 Battery cabinet, center of gravity and weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Table 17 Interconnect wiring for Liebert APM to Liebert BDC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Table 18 Spring washer torque application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Table 19 Liebert APM communication options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Table 20 Relay card pin configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Table 21 Jumper connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Table 22 Descriptions of UPS operator control and display panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Table 23 Mimic display status indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Table 24 Control buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Table 25 Icons for navigation keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Table 26 UPS menus and data window items . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Table 27 Dip switch matrix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Table 28 Mimic indicators for normal mode operation with battery breaker open . . . . . . . . . . . . . . . . . . 101
Table 29 Mimic indicators for normal mode operation with battery breaker closed . . . . . . . . . . . . . . . . . 101
Table 30 Mimic indicators after initialization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Table 31 UPS operating modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Table 32 Environmental requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Table 33 UPS mechanical characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Table 34 45kVA Liebert BDC mechanical characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Table 35 90kVA Liebert BDC mechanical characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Table 36 600mm battery cabinet mechanical characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Table 37 Batteries approved for use in External Battery Cabinet, 600mm . . . . . . . . . . . . . . . . . . . . . . . . 117
Table 38 Batteries approved for use in External Battery Cabinet, 900mm . . . . . . . . . . . . . . . . . . . . . . . . 117
Table 39 Internal batteries approved for use with 45kVA frame Liebert APM . . . . . . . . . . . . . . . . . . . . . 117
Table 40 900mm battery cabinet mechanical characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Table 41 UPS currents and terminals—Input (for single-input unit, 208V operation) . . . . . . . . . . . . . . . 118
Table 42 UPS currents and terminals—Input (for dual-input unit only, 208V operation) . . . . . . . . . . . . 118
Table 43 UPS currents and terminals—Bypass input (for dual-input units, 208V operation) . . . . . . . . . 118
Table 44 UPS currents and terminals—Battery (288V string) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Table 45 AC/AC efficiency, loss and air exchange . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Table 46 UPS currents and terminals—Output 208V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Table 47 Battery DC intermediate circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Table 48 Rectifier input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Table 49 Bypass input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121

vii
Table 50 Inverter output to critical load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Table 51 Component service life . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Table 52 Battery voltage record . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Table 53 Terminal block with compression lugs (for control wiring) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Table 54 Battery retorque values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Table 55 Recommended test equipment and tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
Table 56 Hazardous substances or elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Table 57 UPS status messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130

viii
IMPORTANT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS


This manual contains important instructions that should be followed during installation of the
Liebert APM, Liebert Bypass Distribution Cabinet™ and batteries (where applicable).
Read this manual thoroughly, paying special attention to the sections that apply to your installation,
before working with the UPS. Retain this manual for use by installing personnel.
A properly trained and qualified electrical contractor should oversee the installation of the
equipment.
The Liebert APM cannot be put into operation until it is commissioned by the manufacturer or
authorized engineer. Otherwise, human safety may be endangered and damage to the UPS will not be
covered by the warranty.
The Liebert APM is designed for commercial and industrial uses and cannot be used as life support
equipment.

! WARNING
Risk of moving heavy equipment and electric shock. Can cause equipment damage, injury and
death.
Exercise extreme care when handling UPS cabinets to avoid equipment damage or injury to
personnel. The Liebert APM’s weight ranges from 800 to 3500 lb. (363 to 1590kg).
Determine unit weight and locate center of gravity symbols before handling the UPS.
Test lift and balance the cabinet before transporting it. Never tilt equipment more
than 15 degrees from vertical.
Battery manufacturers supply details of the necessary precautions to be observed when
working on, or in the vicinity of, a large bank of battery cells. These precautions should be
followed at all times.
Follow all battery safety precautions when installing, charging or servicing batteries. In
addition to the hazard of electric shock, gas produced by batteries can be explosive and
sulfuric acid can cause severe burns. When connected, the nominal battery voltage is 288VDC
and is potentially lethal.
In case of fire involving electrical equipment, use only carbon dioxide fire extinguishers or
those approved for use in fighting electrical fires.
Extreme caution is required when performing maintenance.
Be constantly aware that the UPS system contains high DC as well as AC voltages.
Check for voltage with both AC and DC voltmeters prior to making contact.

! WARNING
Risk of moving electric shock. Can cause equipment damage, injury and death.
As with other types of high power equipment, dangerous voltages are present within the UPS
and battery enclosure even after input power has been disconnected. The risk of contact with
these voltages is minimized as the live component parts are housed behind a metal panel.
Further internal safety screens make the equipment protected to IP20 standards. Never
remove panels or covers or open doors that will expose internal components to contact.
Read and follow all warnings, cautions and safety and operating instructions to avoid serious
injury or death from electric shock. No risk exists to any personnel when operating the
equipment in the normal manner, following the recommended operating procedures.
All equipment maintenance and servicing procedures involve internal access and should be
carried out only by trained personnel.

1 Liebert® APM™
Ground Leakage Currents

! CAUTION
Risk of electric shock from high leakage current. Can cause injury, property damage and
death.
EARTH CONNECTION IS ESSENTIAL BEFORE CONNECTING THE INPUT SUPPLY.
Earth leakage current exceeds 3.5 mA and is less than 1000 mA.
Transient and steady-state earth leakage currents, which may occur when starting the
equipment, should be taken into account when selecting instantaneous RCCB or RCD devices.
Residual Current Circuit Breakers (RCCBs) must be selected sensitive to DC unidirectional
pulses (Class A) and insensitive to transient current pulses.
Note also that the earth leakage currents of the load will be carried by this RCCB or RCD.
This equipment must be earthed in accordance with the local electrical code of practice.

! WARNING
Risk of electric shock. Can cause injury, property damage and death.
Under typical operation and with all UPS doors closed, only normal safety precautions are
necessary. The area around the UPS system should be kept free of puddles of water, excess
moisture and debris.
Special safety precautions are required for procedures involving handling, installation and
maintenance of the UPS system and the internal batteries (internal batteries accommodated
by 45kVA frame only). Observe all safety precautions in this manual before handling or
installing the UPS system as well as during all maintenance procedures. Observe all battery
safety precautions before working on or near the battery.
This equipment contains several circuits that are energized with high voltage. Only
test equipment designed for troubleshooting should be used. This is particularly true for
oscilloscopes. Always check with AC and DC voltmeters to ensure safety before making
contact or using tools. Even when the power is turned Off, dangerously high electric charges
may exist within the UPS.
All power and control wiring should be installed by a qualified electrician. All power
and control wiring must comply with the NEC and applicable local codes.
ONLY qualified service personnel should perform maintenance on the UPS system.
When performing maintenance with any part of the equipment under power, service
personnel and test equipment should be standing on rubber mats. The service personnel
should wear insulating shoes for isolation from direct contact with the floor (earth ground).
Never work alone, even if all power is removed from the equipment. A second person should
be standing by to assist and summon help in case an accident should occur.

NOTICE
Risk of improper ground connection. Can cause equipment damage.
Ground connection is essential before connecting the input supply. This equipment must be
grounded in accordance with local electrical codes. Maximum load must not exceed that
shown on the UPS rating label.

NOTICE
Risk of improper improper electromagnetic shielding. Can cause radio communication
interference.
This unit complies with the limits for a Class A digital device, pursuant to Part 15 Subpart J
of the FCC rules. These limits provide reasonable protection against harmful interference in a
commercial environment. This unit generates, uses and radiates radio frequency energy and,
if not installed and used in accordance with this instruction manual, may cause harmful
interference to radio communications. This unit is not designed for use in a residential area.
Operation of this unit in a residential area may cause harmful interference that the user is
solely responsible for correcting.

Liebert® APM™ 2
Battery Cabinet Precautions
The following warning applies to all battery cabinets supplied with UPS systems. Additional
warnings and cautions applicable to battery cabinets may be found in 5.0 - Battery Installation.

! WARNING
Risk of improper handling. Can cause injury, property damage and death.
Internal battery strapping must be verified by manufacturer prior to moving a battery cabinet
(after initial installation).
• Battery cabinets contain non-spillable batteries.
• Keep units upright.
• Do not stack.
• Do not tilt.
Failure to heed this warning could result in smoke, fire or electric hazard.
Call 1-800-LIEBERT before moving battery cabinets (after initial installation).

Battery Hazards

! WARNING
Risk of electric shock. Can cause injury, property damage and death.
Special care should be taken when working with the batteries associated with this equipment.
Batteries are always live. Battery terminal voltage will exceed 300VDC and is potentially
lethal.
In addition to the hazard of electric shock, gas produced by batteries can be explosive and
sulfuric acid can cause severe burns.
Batteries should be installed, serviced and replaced only by properly trained and qualified
service personnel trained in safe battery handling methods and who have the correct PPE
(Personal Protection Equipment) and tools.
The following precautions should be observed when working with the batteries:
• Eye protection should be worn to prevent injury from electrical arcs.
• Remove rings, watches and all other metal objects.
• Use only tools with insulated handles.
• Wear rubber gloves and boots.
• When replacing batteries, replace them with the same type and number of batteries or bat-
tery packs.
• Do not dispose of batteries in a fire. The batteries may explode.
• Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It is
toxic.
• Never lay metal objects of any type on top of the batteries.
• Disconnect the charging source before connecting or disconnecting battery terminals.
• Determine whether the battery is grounded. If the battery is grounded, remove source of
the ground. Contact with any part of a grounded battery can result in electrical shock. The
likelihood of such shock can be reduced if such grounds are removed during installation and
maintenance.

If a battery leaks electrolyte, or is otherwise physically damaged, it must be replaced, stored in a


container resistant to sulfuric acid and disposed of in accordance with local regulations.
If electrolyte comes into contact with skin, the affected area should be washed immediately with large
amounts of water.

3 Liebert® APM™
GLOSSARY OF SYMBOLS

Risk of electrical shock

! Indicates caution followed by important instructions

AC input

AC output

i Requests the user to consult the manual

- +
Indicates the unit contains a valve-regulated lead acid battery
PbH2SO4

R Recycle

DC voltage

AC voltage

Equipment grounding conductor

Bonded to ground

Liebert® APM™ 4
Introduction

1.0 INTRODUCTION
The Liebert APM UPS is a transformer-free, hardware-scalable, online uninterruptible power system
with 208/120V input and 208/120V output capability. The Liebert APM can operate with either a 50
or 60Hz input and provide a matching output frequency conversion. The rack-mounted 15kVA/kW
modules allow scaling the UPS’s capacity in 15kVA increments from 15kVA to a maximum of 90kVA
in a single frame.
Optional transformers are available to add 208V Isolation or 480V or 600V input capability to the
Liebert APM in both the UPS, 90kVA/kW frame only, or the Bypass Distribution Cabinet (BDC) in
either the 45kVA/kW or the 90kVA/kW frame.
The Liebert APM UPS is a SmartAisle™ technology, appropriate for use with the SmartAisle design
approach.
The Liebert APM provides continuous, high-quality AC power to business-critical equipment, such as
telecommunications and data processing equipment. The Liebert APM supplies power free of the
disturbances and variations in voltage and frequency common to utility power, which is subject to
brownouts, blackouts, surges and sags.
The Liebert APM utilizes the latest in high-frequency, double-conversion pulse width modulation
(PWM) technology and fully digital controls to enhance its reliability and increase the ease of use.
Two frame sizes are available: 45kVA/kW and 90kVA/kW. The 45kVA/kW frame is designed to accept
internal batteries; the 90kVA/kW frame does not. The 90kVA frame is, however, designed to accept
Internal Transformers and a four-breaker bypass.
Output Voltage Adjustment
This feature allows a Liebert Customer Engineer to adjust the output voltage over a range of -5% to
+16% of nominal. This permits compensation for any IR drop when the UPS is a significant distance
from the protected load. Output voltage adjustment can optimize the UPS output voltage for loads
that operate more efficiently at a UPS output voltage different from the Liebert APM’s standard
output voltage.

1.1 Battery Maintenance

! WARNING
Risk of electrical shock and high short circuit current. Can cause equipment damage, personal
injury and death.
These maintenance procedures will expose hazardous live parts. Refer servicing to properly
trained and qualified personnel working in accordance with applicable regulations as well as
with manufacturers’ specifications.

1.1.1 Battery Safety Precautions


Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and
the required precautions. Keep unauthorized personnel away from batteries.
When replacing batteries, use the same number and type of batteries.

! WARNING
Risk of electric shock, explosive reaction, hazardous chemicals and fire. Can cause equipment
damage, personal injury and death.
Lead-acid batteries contain hazardous materials. Batteries must be handled, transported and
recycled or discarded in accordance with federal, state and local regulations. Because lead is a
toxic substance, lead-acid batteries must be recycled rather than discarded.
Do not dispose of battery or batteries in a fire. The battery may explode.
Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin
and eyes. It is toxic.

5 Liebert® APM™
Introduction

! WARNING
Risk of electrical shock and high short circuit current. Can cause equipment damage, personal
injury and death.
The following precautions must be observed when working on batteries:
• Remove watches, rings and other metal objects.
• Use tools with insulated handles.
• Wear rubber gloves and boots.
• Do not lay tools or metal parts on top of batteries.
• Disconnect charging source prior to connecting or disconnecting battery terminals.
• Determine whether the battery is grounded. If it is grounded, remove source of ground.
Contact with any part of a grounded battery can result in electrical shock. The likelihood of
such shock will be reduced if such grounds are removed during installation and
maintenance.

Lead-acid batteries can present a risk of fire because they generate hydrogen gas. In addition, the
electrical connections must be protected against accidental short circuits which can cause sparks. The
following procedures should be followed:
• DO NOT SMOKE when near batteries.
• DO NOT cause flame or spark in battery area.
• Discharge static electricity from body before touching batteries by first touching a grounded metal
surface.
• After replacing battery jars in a battery cabinet, replace the retaining straps that hold the jars in
place on the shelves. This will limit accidental movement of the jars and connectors should the
cabinet ever need to be repositioned or relocated.
Regular maintenance of the battery module is an absolute necessity. Periodic inspections of battery
and terminal voltages, specific gravity and connection resistance should be made. Strictly follow the
procedures outlined in the battery manufacturer’s manual, available on the manufacturer’s Web site.
Valve-regulated lead-acid (sealed-cell) batteries do require periodic maintenance. Although
maintenance of electrolyte levels is not required, visual inspections and checks of battery voltage and
connection resistance should be made.

NOTICE
Risk of equipment damage. Batteries should be cleaned with a dry cloth or a cloth lightly
moistened with water. Do not use cleaners on the batteries. Solvents can make the battery
cases brittle.
Because individual battery characteristics are not identical and may change over time, the UPS
module is equipped with circuitry to equalize battery cell voltages. This circuit increases charging
voltage to maintain flooded type battery cells at full capacity.

! WARNING
Risk of electric shock, explosive reaction, hazardous chemicals and fire. Can cause equipment
damage, personal injury and death.
Do not use equalize charging with valve-regulated, lead-acid batteries, such as those in
Liebert Battery Cabinets. Refer to the battery manufacturer’s manual, available on the
manufacturer’s Web site, for specific information about equalize charging.

Liebert® APM™ 6
Introduction

Matching Battery Cabinets—Optional


Although the individual battery cells are sealed (valve-regulated) and require only minimal
maintenance, the Battery Cabinets should be given a periodic inspection and electrical check. Checks
should be performed at least annually to ensure years of trouble-free service.
Voltage Records: With the Battery Cabinet DC circuit breaker closed and the connected UPS
operating, measure and record battery float voltage. With the DC circuit breaker open, measure and
record the nominal (open circuit) voltage. Both these measurements should be made across the final
positive and negative terminal lugs. Compare these values with those shown below. The recorded
nominal voltage should be no less than the value shown; while the recorded float voltage should be
within the range shown. If a discrepancy is found, contact Liebert Services.
Table 1 Battery voltage, nominal and float
Battery Voltage, VDC
Nominal/
Number of Cells Open Cell Float
144 288 324

Power Connections: Check for corrosion and connection integrity. Inspect wiring for discolored or
cracked insulation. Clean and/or retighten as required. Refer to torque specifications in Table 2.
Battery Cell Terminals: Check for discoloration, corrosion and connection integrity. Clean and
tighten if necessary. Note that when installing a new battery, the initial torque value is 5 lb.-in. more
than the retorque value. Table 2 shows battery retorque values.
Table 2 Battery retorque values
Battery Mfr. Battery Model # Retorque Value
HX205-FR 65 in-lb
HX300-FR 65 in-lb
HX330-FR 65 in-lb
HX400-FR 65 in-lb
Enersys
HX500-FR 65 in-lb
HX540-FR 65 in-lb
16HX800F 100 in-lb
16HX925F 100 in-lb

If the system uses a different model battery, contact Liebert Services for the required torque value.
To access battery cell terminals, disconnect the inter-tier cable and two shelf retaining screws. Once
disconnected, insulate (with protective boot or electrical tape) the cables to prevent accidental shorts.
The battery shelf can now be pulled out. Tighten each terminal connection to the retorque value.
When replacing a battery, the terminal connections must be cleaned and tightened. Disconnect and
insulate the cables connected to the battery. Secure each battery shelf with retaining screws when
maintenance is complete.

Other DC Sources
If the UPS system uses a DC source other than a factory-supplied Matching Battery Cabinet, perform
maintenance on the DC source as recommended in the DC source manufacturer’s maintenance
manual, available on the manufacturer’s Web site.

7 Liebert® APM™
Installation

2.0 INSTALLATION
This section describes the Liebert APM’s environmental requirements and mechanical considerations
that must be taken into account when planning the positioning and cabling of the UPS equipment.
Because each site is unique, this section presents a guide to general procedures and practices that
should be observed by the installing engineer, rather than step-by-step installation instructions.

! WARNING
Risk of electric shock. Can cause injury, property damage and death.
Special care should be taken when working with the batteries associated with this equipment.
When connected together, the nominal battery voltage is 288VDC and is potentially lethal.
• Eye protection should be worn to prevent injury from accidental electrical arcs.
• Remove rings, watches and all metal objects.
• Only use tools with insulated handles.
• Wear rubber gloves.
If a battery leaks electrolyte or is otherwise physically damaged, it must be replaced, stored in
a container resistant to sulfuric acid and disposed of in accordance with local regulations.
If electrolyte comes into contact with skin, the affected area should be washed immediately
with large amounts of water.

NOTICE
Risk of improper installation. Can cause equipment damage.
Do not apply electrical power to the UPS equipment before the commissioning engineer
arrives at the installation site.
The UPS must be installed by a properly trained and qualified engineer in accordance with
the information contained in this chapter. All the equipment not referred to in this manual is
shipped with details of its own mechanical and electrical installation information.
NOTE
Three-phase, four-wire input power is required.
NOTE
Input power must be supplied to the Liebert APM from a properly grounded Wye or Delta
source. The Liebert APM is not for use with impedance grounded systems, corner-grounded
systems or high-leg Delta systems. For these applications, an isolation transformer must be
installed between the input power and the Liebert APM.

Liebert® APM™ 8
Installation

2.1 Initial Inspections


1. While the Liebert APM and ancillary cabinets are still on the truck, inspect the equipment and
shipping container for any signs of damage or mishandling. Do not attempt to install the system if
damage is apparent. If any damage is noted, file a damage claim with the shipping agency
immediately and contact Liebert Services at 1-800-LIEBERT to inform them of the damage claim
and the condition of the equipment.
2. Compare the contents of the shipment with the bill of lading. Report any missing items to the
carrier and your local Emerson representative immediately.
3. Check the product label on the back of front door and confirm the contents match the UPS model,
capacity and main parameters that were ordered.

2.1.1 Storing for Delayed Installation


If the equipment will not be installed immediately, it must be stored indoors where the humidity is no
higher than 90% and the temperature is no higher than 104°F (40°C). The storage area must protect
the Liebert APM from excessive moisture (see 11.2 - UPS Environmental).

! CAUTION
If the UPS must remain disconnected from power for more than six (6) months, the batteries
(if so equipped) must be recharged before use. To charge the batteries, the unit must be
connected to utility power and started up—the charger operates only while the Liebert APM
is operating.

! CAUTION
When batteries are installed in the UPS or are cabinet-mounted adjacent to the UPS, the
battery—not the UPS—dictates the designed maximum ambient temperature.

2.2 Preliminary Checks


2.2.1 Identification
The equipment supplied has an identification tag on the back of the main door listing the type and
size of the UPS.

2.3 UPS Location


2.3.1 Positioning the UPS
Choose a location for the UPS that offers:
• Easy connection to inputs, outputs and auxiliary equipment
• Enough space to service the UPS
• Air circulation sufficient to expel heat produced by UPS
• Protection against moisture and excessive humidity
• Protection against dust and other particulate matter
• Compliance with fire prevention regulations and practices
• Operating environment temperature of 74-80°F (23-27°C) for maximum battery efficiency

9 Liebert® APM™
Installation

2.3.2 Environmental Considerations


Before installing the Liebert APM, verify that the UPS room satisfies the environmental conditions
stipulated in 11.2 - UPS Environmental, paying particular attention to the ambient temperature
and air exchange system.
The UPS unit should be installed in a cool, dry, clean-air environment with adequate ventilation to
keep the ambient temperature within the specified operating range 32°F to 104°F (0°C to 40°C).
For optimal UPS and battery system performance and service life, maintain the operating
temperature within the range of 74-80°F, (23-27°C).
The Liebert APM is cooled by internal fans. Cooling air enters the unit through the front of the unit
and is exhausted out the back. To permit proper air flow and prevent overheating, do NOT block or
cover the ventilation openings or blow air down onto the unit. The UPS requires 24 in. (610mm)
ventilation clearance above the unit and 12" (305mm) behind the UPS.
See Table 46 for details on heat dissipation.
Battery Location
Temperature is a major factor in determining battery life and capacity. Battery manufacturers
recommend an operating temperature of 77°F (25°C). Ambient temperatures warmer than this reduce
battery life; temperatures below this reduces battery capacityv. In a typical installation, battery
temperature should be maintained between 74°F and 80°F (23-27°C). Batteries should be placed
where there are no main heat sources or air inlets to prevent portions of batteries from being either
much warmer or much cooler than other parts of the batteries.
2.4 Considerations in Moving the Liebert APM
Ensure that the UPS weight is within the designated surface weight loading (lb./ft2 or kg/cm2) of any
handling equipment. See Table 33 for weights of various units.
The Liebert APM may be rolled on its casters for short distances only. For longer distances, move the
UPS with a forklift or similar equipment to ease the relocation and to reduce vibration.
The optional battery cabinets should be moved with a forklift or similar equipment.

! WARNING
Risk of moving heavy unit. Can cause property damage, injury and death.
Ensure that any equipment that will be used to move the Liebert APM has sufficient lifting
capacity. The Liebert APM’s weight ranges from 800 to 3500 lb. (363 to 1590kg). See Table 33
for details.
The UPS presents a tipping hazard. Do not tilt the Liebert APM more than 15 degrees from
vertical.
The UPS is fitted with casters—Take care to prevent movement when unbolting the
equipment from its shipping pallet. Ensure adequate personnel and lifting equipment are
available when taking the Liebert APM off its shipping pallet.

! WARNING
Risk of heavy unit tipping over while being moved. Can cause property damage, injury and
death.
The casters are strong enough for movement across even surfaces only. Casters may fail if
they are subjected to shock loading, such as being dropped or rolled over holes in the floor or
obstructions. Such failure may cause the unit to tip over, injuring personnel and damaging
the equipment.
Care must be taken when maneuvering units fitted with batteries. Keep such moves to a
minimum. For further information, see Battery Cabinet Precautions on page 3.
Final Positioning
When the equipment has been finally positioned, ensure that the adjustable stops are set so that the
UPS will remain stationary and stable (see 7.0 - Installation Drawings).
The Liebert APM and its auxiliary cabinets must be installed on a concrete or equivalent, non-
resilient floor.

Liebert® APM™ 10
Installation

2.5 Mechanical Considerations


The Liebert APM is constructed with a steel frame and removable panels. Top and side panels are
secured to the chassis by screws. The doors may be opened for access to power connections bars,
auxiliary terminals blocks and power switches.
The UPS comes with an Operator Control Panel that provides basic operational status and alarm
information. The cabinet houses both the power components and the internal batteries. Cooling is
provided by internal fans. The unit sits on four casters. Adjustable stops are provided to prevent the
UPS from moving once it has been moved to its final position.

! WARNING
Risk of heavy units tipping over while being moved. Can cause property damage, injury and
death.
The Liebert BDC™ and battery cabinets must be properly prepared and secured for lifting.
Improper lifting may cause the cabinets to fall, causing personal injury or death and
equipment damage.
Emerson recommends lifting the units with one of the following methods:
• Installing four eyebolts in the factory-fabricated holes, one at each corner of the unit,
attaching cables or similar strapping to the eyebolts and lifting with a suitable mechanism.
• Placing suitable straps on the Liebert BDC™ or battery cabinet. The straps must go under
the unit to be lifted.

2.5.1 Clearances
There are no ventilation grilles on the sides of the UPS. The sides must be accessible during
installation. After installation, the unit must have a clearance of 12 in. (305mm) in the rear to permit
adequate circulation of air exhausted from the UPS. The Top Fan option eliminates the 12" (305mm)
rear clearance requirement, but it increases the Liebert APM’s height by 7.63" (194mm).
To enable routine tightening of power terminations within the UPS, make sure there is sufficient
clearance in front of the Liebert APM to permit free passage of personnel with the door fully opened.
Leave a minimum of 24 in. (610mm) between the top of the UPS frame and the ceiling to permit
adequate air circulation above the unit. Emerson recommends against using air conditioning or other
systems that blow air onto the top of the unit.

2.5.2 Floor Installation


If the Liebert APM, Liebert BDC or battery cabinet is to be placed on a raised floor, the UPS should be
mounted on a pedestal that will support the equipment point loading. Refer to the bottom view in
Figures 49, 55 or 58 to design this pedestal.

2.5.3 Cable Entry


Cables can enter the Liebert APM, Liebert BDC and battery cabinets from the top or bottom through
removable metal plates.
Some plates have factory-punched holes and others are designed to allow the personnel to punch
holes for fitting and securing the conduit. Once the conduit holes are punched, these plates should be
reattached to the UPS. The conduit size and wiring method must be in accordance with all local,
regional and national codes and regulations, including NEC ANSI/NFPA 70.
The UPS must be accessible from the right side to allow personnel to complete the cable connections
and make necessary adjustments. After installation is complete, the Liebert APM may be serviced
from the front.
NOTE
When installing the UPS, the customer must provide a disconnect with overcurrent protection
at the output of the UPS.

11 Liebert® APM™
Installation

2.5.4 Special Considerations for Parallel Systems


1. Consider the grounding configuration of the UPS system before finalizing module placement. For
optimal ground performance, the Liebert APM modules should be close together. See 3.2.6 -
Cabling Guidelines.
2. For optimal load-sharing performance, the UPS bypass input cables and output cables should be
approximately the same length, ±10 percent.
3. Position modules in such a way as to minimize the length of power cables and control wiring
between UPS modules and the paralleling cabinet.
Refer to 4.0 - Parallel System and LBS System Installation for further information on
installing a parallel system.

2.5.5 Special Considerations for 1+N Parallel Systems


Consider the grounding configuration of the UPS system before finalizing module placement. See
3.2.6 - Cabling Guidelines.
Emerson recommends matching the impedance in the bypass path of paralleled systems as closely as
possible.
The impedance mismatch can be minimized by controlling the wiring length of each unit. The design
and the layout of the UPS system and associated panels and cabling should be examined closely to
ensure that cable lengths and impedances are closely matched. The Liebert 1+N UPS module is
supplied with a sharing reactor to minimize the impact of cable impedance mismatch. The cabling
impedance must be carefully controlled to ensure good bypass current sharing.
For Liebert APM systems, the cabling impedances must be within 10% from maximum to minimum.
If the cabling impedances must be greater than 10%, contact your Emerson representative to
calculate whether the system will result in an overload condition when operating on bypass.
When bringing the 1+N system online for the first time or after removing one unit, Emerson
recommends checking the bypass current mismatch. To check the bypass current mismatch:
1. Place a load on the bypass of each UPS module.
2. View the output current of each unit.
The accuracy of the currents displayed on the UPS module is sufficient for this check. If the mismatch
is greater than 10%, the bypass impedances must be balanced or the load must be limited to less than
the maximum rating.

2.6 45kVA and 90kVA UPS Frames—Auxiliary Cabinets


The 45kVA frame consists of a single cabinet housing the UPS components and the internal battery
string. The 90kVA frame, also a single cabinet, does not accommodate internal batteries, but does
provide for an internal four-breaker bypass or an internal transformer. The internal transformers are
available with 480V:208V; 600V:208V; or 208V:208V isolation input primaries.
Optional battery cabinets are available for each Liebert APM model to provide extended run time.
Each battery cabinet houses a single string of batteries per cabinet that operate in parallel with the
Liebert APM’s internal batteries (45kVA frame only). The battery cabinets are designed to be bolted
to the left side of the UPS (see Figure 1). Refer to 5.4 - External Battery Cabinet Installation for
details.
Optional Liebert BDC™ units are available. These cabinets house the components necessary to
provide an external wraparound maintenance bypass switch for servicing the UPS.
Liebert BDCs are designed to be bolted to the right side of the UPS (see Figure 1). Refer to 6.4 -
Locating the Cabinet for further details.
System Composition
A UPS system can comprise a number of equipment cabinets, depending on the system design
requirements—e.g., UPS cabinet, External Battery Cabinet and External Bypass Cabinet. All
cabinets used will be the same height and will be designed to be positioned side-by-side to form an
aesthetically appealing equipment suite.

Liebert® APM™ 12
Installation

2.6.1 Optional Cabinets


If the Liebert APM installation includes a Liebert BDC, the UPS must be positioned to allow the
Liebert BDC to be bolted to right side of the Liebert APM (see Figure 1).
The Liebert BDC must be cabled and bolted to the Liebert APM before the UPS and bypass cabinet
are moved into their final position. Connect the input wiring to the Liebert BDC ONLY after the units
are connected and positioned.
Battery cabinets may be bolted only to the left side of the Liebert APM; see Figure 1.
Figure 1 Cabinet arrangement
ALL UNITS VIEWED FROM ABOVE

Liebert Liebert
APM Bypass APM
Distribution Battery
Cabinet Cabinet

Liebert APM connected only to Liebert BDC


(BDC must be on right side of the Liebert APM) Liebert APM connected to Battery Cabinet (Battery Cabinets
must be on the left side of the Liebert APM)

Liebert
APM Bypass
Battery Battery Distribution
Cabinet Cabinet Cabinet

Liebert APM connected to Liebert BDC and Battery Cabinets


(BDC must be on right side of the Liebert APM)
(Battery Cabinets must be on the left side of the Liebert APM)

2.7 Optional Seismic Brackets


Optional seismic mounting brackets to anchor the Liebert APM, Liebert BDC™ and battery cabinet
to the floor are available. Refer to Figure 61 for mounting details.

13 Liebert® APM™
Installation

2.8 Liebert FlexPower™ Assembly


Figure 2 Liebert FlexPower assembly indicators and controls
Fault LED

Run LED

DIP Switches

Battery Start Button

Ready Switch

The Battery start button allows starting of UPS on battery; refer to 10.3 - UPS Battery Start.
The Run LED is illuminated Green when the Liebert FlexPower assembly is operating normally.
The Fault LED will illuminate red when the Liebert FlexPower assembly has a problem.
Table 3 LED indications
LED Status Indication
Run LED (Green)
Flashing Green The inverter is starting, but has no output yet.
Constant Green The inverter has started to supply power.
OFF The inverter has not started up.
Fault LED (Red)
Auxiliary power failure (15V or 24V), rectifier overtemperature, rectifier failure (including battery
SCR short circuit), battery converter failure, soft start failure, main circuit back feed, abnormal
Constant Red input current, inverter failure, output short circuit, bypass SCR short circuit fault, inverter relay
short circuit fault, abnormal bus voltage under non-sleep mode, module not ready, module ID
out of range and duplicated module ID.
Charger failure, abnormal main circuit voltage, abnormal main circuit frequency, main circuit
undervoltage, main circuit reverse phase, battery unavailable, reverse battery, input zero-loss,
Flashing Red
current sharing failure, module overload, inverter relay disconnection fault, bypass SCR
disconnection fault and input fuse blown.
OFF No above failures or alarms.

2.9 Static Bypass Assembly


Figure 3 Static bypass assembly connections
J1 J5 J4
J10
J7 J8 J11
J2
Input/output dry contact and EPO/BCB/MBC interface
J1 ~ J3 port can’t connect to phone!

J1 J4 J7 J10

INTELLISLOT1 INTELLISLOT2 INTELLISLOT3


MFP_C
INPUT_1
+12V
GND

GND
BAT-OUT

BAT-IN

INPUT_2

MFP_S

MFP_O
OUT

J2 PARA J5 J8 J11
ONLINE
EXT-OUT

BFP_C
GND

Q3BP
Q2BP

DRIVER
GND

BFP_O
BFP_S
BCB_IN

J3 PARA J6 J9 J12
ENV_DET
EPO-NO

BAT_READY

BAT_GND
+12V
EPO-NC

INV_C

INV_S
+12V

+12V

INV_O

MONITOR RS485-1 RS485-2 RS232


LBS

J6 J9 J12 Liebert IntelliSlot


J3 Monitor RS-485 RS-232 Bays 1, 2, 3

The Static bypass assembly has three Liebert IntelliSlot interface card bays and connections for
ancillary cabinets (Liebert BDC and battery) and for options.

Liebert® APM™ 14
Electrical Connections—UPS

3.0 ELECTRICAL CONNECTIONS—UPS


The UPS requires both power and control cabling once it has been mechanically installed. All control
cables must run separate from power cables in metal conduits or metal ducts that are electrically
bonded to the metalwork of the cabinets to which they are connected.

! WARNING
Risk of electric shock. Can cause property damage, injury and death.
Before connecting input power to the Liebert APM, ensure that you are aware of the location
and operation of the overcurrent protection devices that connect the UPS input/bypass supply
to the power distribution panel.
De-energize and lockout or tagout all incoming high- and low-voltage power circuits before
installing cables or making any electrical connections.

3.1 Power Cabling


3.1.1 Cable Rating
The main factors affecting the choice and size of cable are voltage, current (also taking into account
overcurrent), room temperature and conditions of installation of the cable. Refer to ANSI/NFPA 70.
The power cables of the system must be sized with respect to the following description:
• UPS input cables - The UPS input cables must be sized for the maximum input current,
including the maximum battery recharge current, given in Table 41, with respect to the unit
rating and the input AC voltage.
• UPS bypass and output cables - The bypass and output cables must be sized for the nominal
output current, given in Table 41, with respect to the unit rating and the output AC voltage.
• Battery cables - Each UPS unit has its own internal batteries factory-wired. If connecting an
external battery cabinet, the battery cables must be sized for the battery discharge current at the
end-of-discharge voltage, as given in Table 41, with respect to the unit rating.
NOTE
Table 41 gives nominal currents for determining the size of UPS power cables. Other
important factors to consider include cable route length and coordination with protective
devices.
The power cables can be sized to suit the UPS unit rating according to Table 41.
Lug Size and Torque Requirements
Refer to Table 41 for lug size and torque requirements and to Table 18 and Figure 60.

3.2 External Protective Devices


For safety concerns, it is necessary to install external circuit breakers or other protective devices for
the input AC supply of the UPS system. This section provides generic practical information for
qualified installation engineers. The installation engineers should be knowledgeable about regulatory
wiring standards and the equipment to be installed.
To reduce the risk of fire, connect only to a circuit provided with branch circuit overcurrent protection
in accordance with NEC ANSI/NFPA 70.

15 Liebert® APM™
Electrical Connections—UPS

3.2.1 Rectifier and Bypass Input Supply of the UPS


Overcurrents
Install suitable protective devices in the distribution unit of the incoming mains supply, considering
the power cable current-carrying capacity and overload capacity of the system. Generally, the
magnetic circuit breaker with IEC60947-2 tripping curve C (normal) at the 125% of the nominal
current listed in Table 41 is recommended.
Split bypass: In case a split bypass is used, separate protective devices should be installed for the
rectifier input and bypass input in the incoming mains distribution panel.
NOTE
The rectifier input and bypass input must use the same neutral line.
For an IT power network system, a 4-pole protective device must be installed on the external
input distribution and external output distribution of the UPS.
Earth Leakage, RCD Devices
Any residual current detector (RCD) installed upstream of the UPS input supply:
• Must be sensitive to DC unidirectional pulses (Class A)
• Must be insensitive to transient current pulses, and
• Must have an average sensitivity, adjustable between 0.3 and 1A.
To avoid false alarms, earth leakage monitoring devices when used in systems with split bypass input
or when used in paralleled UPS configurations, must be located upstream of the common neutral
sinking point. Alternatively, the device must monitor the combined four-wire rectifier and split
bypass input currents.
The residual earth current introduced by the RFI suppression filter inside the UPS is greater than
3.5mA and less than 300mA. Liebert recommends verifying the selectivity with all other differential
devices both upstream of the input distribution board and downstream (toward the load).

3.2.2 External Battery


The DC-compatible circuit breaker provides overcurrent protection for UPS system and battery,
which is provided by the external battery cabinet.

3.2.3 UPS Output


If an external distribution panel is used for load distribution, the selection of protective devices must
provide discrimination with those that are used at the input to the UPS (see Table 47).

Liebert® APM™ 16
Electrical Connections—UPS

3.2.4 UPS Input Configuration


By default, the Liebert APM ships with internal links installed between the bypass input and main
(rectifier) input (single input configuration see Figure 84).
Figure 4 shows the Liebert APM in a split bypass (single source dual-input) configuration. In this
configuration, the static bypass and the maintenance bypass lines are supplied by the same source
using separate feeds. Both feeds must be protected externally with properly sized protective devices.
To wire the Liebert APM as a single source dual-input UPS, remove the links and wire the bypass
feed to the bypass busbars, then wire the main feed to the main busbars (see Figure 8).
Figure 4 Single UPS block diagram—dual input single source configuration

Bypass Distribution Cabinet

* Bypass MBB Optional AC Output


AC Input BIB MIB 54-Pole 208V
4-Wire + GND See Note 6 4-Wire + GND

Static Bypass

* Rectifier
AC Input
4-Wire + GND
UPS Cabinet
See Note 7
Battery

NOTES
BIB - Bypass Isolation Breaker
1. Install in accordance with national and local electrical codes.
MBB - Maintenance Bypass Breaker
2. Input and bypass must share the same single source.
MIB - Maintenance Isolation Breaker
3. A neutral is required from the system AC input source. A full
* External Overcurrent Protection
capacity neutral conductor is recommended. Grounding
by others
conductors are recommended.
4. Bypass and rectifier inputs and output cables must be run Field-Supplied Wiring
in separate conduits.
5. Control wiring must be run in separate conduits. UAM01023
6. Optional 54-pole, 225A for 45kVA frame only or optional 54-pole, Rev. 3
400A for 90kVA frame only.
7. Customer must supply shunt trip breaker with 120V coil.

17 Liebert® APM™
Electrical Connections—UPS

3.2.5 UPS Input Configuration with Transformers


Figure 5 shows the Liebert APM in a split bypass (single-source, dual-input) configuration using two
transformers. One transformer is inside the Bypass Distribution Cabinet and the other inside the
UPS.
In this configuration, the static bypass and the maintenance bypass lines are supplied by the same
source using separate feeds. Both feeds must be protected externally with properly sized protective
devices.
Figure 6 shows the control wiring for the dual input transformer configuration.

Figure 5 Liebert APM in a split bypass configuration

Bypass Distribution Cabinet

* Bypass MBB (Optional) AC Output


AC Input BIB MIB 54 Pole 208V
4-Wire + GRD See Note 6 4 Wire + GRD

Static Bypass

* Rectifier
AC Input
4 Wire + GRD
See Note 7 UPS Cabinet
Battery

NOTES:
1. Install in accordance with national and local electrical codes. 5. Control wiring must be run in separate conduits.
2. Input and bypass must share the same single source. 6. Optional 54 pole, 225A for 45kVA frame only or
3. A neutral is required from the system AC input source. A full optional 54 pole 400A for 90kVA frame only.
capacity neutral conductor is recommended. Grounding 7. Customer must supply shunt trip breaker with 120V coil.
conductors are recommended. 8. Input voltage options of the isolation
4. Bypass and rectifier inputs and output cables must be run in transformer: 600V, 480V, 220V and 208V.
separate conduits.

BIB - Bypass Isolation Breaker * External Overcurrent Field-Supplied Wiring


UAM01024
MBB - Maintenance Bypass Breaker Protection by Others
Rev. 0
MIB - Maintenance Isolation Breaker

Liebert® APM™ 18
Bypass Distribution Cabinet

Output
Figure 6

W91
Neutral

MBB
ØA AC Output
ØB W04
Utility ØC W05
W06 (Optional)

transformer.
GRD Customer Liebert 54 Pole
Main Input APM UPS N MIB
Kirk A W88 See Note 3
Busbars
Key K1 B W89 Output
C W90 Ground
To
Bypass
Input UPS AC Kirk
Output Ground
Key K2
Bypass Input To Unit
4
Frame
BIB 3
W07 W85 4
W08 W86 2 Fuses, 2A
W09 W87 3
1
W83 3
2 3
1432 3 4
RIB PE 2
TB1

19
N
ØA
Ø to A
ØB
* Utility Rect. B
ØC
Input C
Rect. Input 1

SKRU
Input Neutral K0
Control wiring for the dual input transformer configuration

* Customer
must supply
Main Ground Busbar W84
shunt trip to
AC 120V

See Note 1
rectifier
input breaker AC 120V
with 120V coil Ground Inner Door
To Unit
Frame
NOTES SKRU - SOLENOID
1. Customer-furnished electrode conductor to be installed in KEY RELEASE UNIT
accordance with national and local electrical codes. KO - KEY OPERATOR
2. See installation manual for additional connection information. Field-Supplied Wiring
3. Optional 54 pole, 225A for 45kVA frame only or optional 54 pole Factory-Supplied Wiring
400A for 90kVA frame only.

The external maintenance bypass is available with a 480V, 600V or 208V optional internal
4. Transformer available: 208V, 220V, 480V and 600V input. UAM04047
5. Overcurrent protection is based on 80% rated devices.
6. Ensure that the jumper bars between input and rectifier input
Rev. 0
are removed before starting the unit for the first time.
7. See Drawing UAM02022.

internal transformer. Internal batteries are not available for a 45kVA frame that has an the internal
transformer. Each UPS frame size (45kVA or 90 kVA) is available with a 480V, 600V or 208V optional
Electrical Connections—UPS

Liebert® APM™
Electrical Connections—UPS

3.2.6 Cabling Guidelines


The following are guidelines only and are superseded by local regulations and codes of practice where
applicable. Use wiring rated at 75°C or greater.
1. Take special care when determining the size of the neutral cable, as current circulating on the
neutral cable may be greater than nominal current in the case of non-linear loads. Refer to the
values in 11.4 - UPS Electrical Characteristics.
2. The ground conductor should be sized according to such factors as the fault rating, cable lengths
and type of protection. The ground cable connecting the UPS to the main ground system must
follow the most direct route possible. Control wiring and power wiring must be run in separate
conduit. Output and input cables must be run in separate conduit.
3. Consider using paralleled smaller cables for heavy currents—this can ease installation.
4. When sizing battery cables, a maximum voltage drop of 4VDC is permissible at the current
ratings in Table 43. For terminal connection sizing, see Tables 41 through 43.
5. In most installations, the load equipment is connected to a distribution network of individually
protected busbars fed by the UPS output, rather than connected directly to the UPS itself. When
this is the case, the UPS output cables can be rated to suit the individual distribution network
demands rather than being fully load-rated.
NOTE
If more load is added to the distribution panel, the unit’s cabling must be resized.
6. When laying power cables, do not form coils; this will help avoid increasing formation of
electromagnetic interference.
NOTE
Right-side access may be required when making power connections. Cable connections should
be made before a cabinet is attached to the right side of the Liebert APM or before the UPS is
placed where another obstruction, such as a wall, is against the Liebert APM’s right side.

3.2.7 Cable Connections


The rectifier input, bypass output and battery are easily accessible from the right side of the unit for
installation. All require lug type terminations. They are connected to busbars on the right side of the
Liebert APM, as shown in Figures 7 and 8. These busbars are accessible when the right side panel is
removed.

NOTICE
Risk of improper installation. Can cause equipment damage.
When wiring a single-input only system, connect only the power wiring to the input busbars.

Liebert® APM™ 20
Electrical Connections—UPS

Figure 7 Input busbars—Liebert APM 45kVA frame


1.75" (44mm)
1.75" (44mm) (Typ.) 1.52" (39mm)
(Typ.)
1.65"
(42mm) ø .50" (13mm) ø .55" (14mm)
1.65" 4 places
2 places
(42mm) .8" (20mm)
3.54" (90mm) (Typ.)
.8" (20mm) 1.6" (41mm)
.7" (18mm)
DETAIL D
Top View DC Busbars DETAIL C
Top View Ground
ø .50" (13mm)
Typ.

Main Input Busbars


Same for Bypass and
Output Busbars

See
Detail D
TOP VIEW BOTTOM VIEW 1.75" (44mm) Typ.

31.5" (800mm) 37.5" (953mm) DETAIL A

Links for Main


to Bypass
(Single Input Only)

2.2" (56mm)
Typ. 6 Places Main Input
Busbars

Bypass
78.7" Battery Busbars
(2000mm) Breaker

Ground
1.97" (50mm) See Detail A
Typ. 3 Places

See Output
Detail B Busbars
DC Busbars
2.36" See Detail A
(60mm)
Typ. 2
Places
FRONT VIEW DETAIL B
RIGHT SIDE VIEW
Door Removed Panel Removed
NOTES
1. All dimensions are in inches (mm).
2. Control wiring and power wiring must be run in separate conduits.
3. Copper cables only are recommended.
4. All wiring must be in accordance with national and local electrical codes.

21 Liebert® APM™
Electrical Connections—UPS

Figure 8 Input busbars—Liebert APM 90kVA frame

NOTES
1. Dimensions are in inches [mm].
2. Control wiring and power wiring must be run in separate conduits. UAM02021
3. Emerson recommends using only copper cables. Rev. 3
4. All wiring must be in accordance with national and local electrical codes.

Liebert® APM™ 22
Electrical Connections—UPS

Figure 9 Liebert BDC

1. All dimensions are in inches (mm).


2. Control wiring and power wiring must be run
in separate conduits.
3. Only copper cables are recommended.
4. All wiring is to be in accordance with national
and local electrical codes.
5. If bypass distribution cabinet is attached
TOP VIEW to the UPS, Emerson will supply the
interconnection cables.
BOTTOM VIEW 6. See UAM06020B, Pg. 2 of 2.

23.6" (600mm) 37.5" (953mm)

LDB

78.7"
(2000mm)

MBB MIB
BIB

Input/Output
System Neutral Bus
Input Ground
Bus Bus
See Detail A and
Isometric View
Detail B, Pg. 2
LEFT SIDE VIEW (Note 6)
FRONT VIEW
Panel Removed RIGHT SIDE VIEW
Door Removed
Panel Removed

UAM06020A
Rev. 2

23 Liebert® APM™
Electrical Connections—UPS

Figure 10 Busbars—Liebert BDC

UPS Bus
Ø .44"
(11mm)
Typical Neutral Bus
5" x 8.9"
(127 x 227mm)
Ø .44" 1.75"
System
(11mm) (44.5mm)
Input Bus
Typical Typical
See Detail B
All
Busbars
Ø .56"
1.38" (35mm) 1.38" (35mm) (14mm)
1.38" (35mm) DETAIL A 1.38" (35mm) Typical Ground Bus
2.44" (62mm) 5" x 4"
(127 x 102mm)
2.44" (62mm) Ø .56"
(14mm)
Typical

Input/Outout
Bus Typical
Input 1.5" x 8.9"
Breaker (38 x 227mm)

Ø .44"
(11mm)
Input Typical
Ground
Bus Ø .56"
(14mm)
System
Typical
Input
Busbar
Located at
Rear, Typ.

System Neutral
Input Input/Output
Connections Connections

1. See UAM06020A, Pg. 1 of 2


(2) 225A or 400A panelboard.
2. See UAM06021A, Pg. 1 of 2
(2) 225A or (2) 150A subfeed breakers.
3. See UAM06022A, Pg. 1 of 2
without distribution.

DETAIL B UAM06020B
Iso View Front Left
with Corner Post Not Shown Rev. 2

Liebert® APM™ 24
Electrical Connections—UPS

Figure 11 Busbars—External 600mm battery cabinet

3.66"
3.66"
(93mm)
(93mm)
1.75" 1.75"
(45mm) (45mm)
.56" Dia.(14.3mm)

TERMINAL SPECIFICATIONS .44" Dia. (11.1mm)


Unit Rating: 15-90kVA
Bolt Shaft Size: M10 1.75"
Torque: 240 lb-In (27Nm) (45mm)
1.75"
(45mm)

1.65"
(42mm)
1.75"
(45mm) 1.65"
3.66" (42mm)
Bottom View (93mm) 4.96"
Top View 23.6" (126mm)

(600mm) DETAIL A
Alber Battery 37.5"
Monitoring (953mm)
DC Connection
Busbars

Ground
Bus

78.7" See
(2000mm) Detail A

Left Side View Front View


Panel Removed Door Removed
Right Side View
1. All dimensions are in inches (mm). Panel Removed
2. Control wiring and power wiring must be run in separate conduits.
3. Copper cables onlyare recommended.
4. All wiring is to be in accordance with national and local electrical codes. UAM05020
5. If battery cabinet is attached to UPS, Emerson will supply interconnect cables. Rev. 1

25 Liebert® APM™
Electrical Connections—UPS

Figure 12 Busbars—External 900mm battery cabinet


3.31" 3.31"
(84mm) (84mm)

1.65" 1.65"
(42mm) (42mm)

.56" Dia.
(14.3mm)

1.75" 1.75"
(45mm) (45mm)

1.75"
(45mm)

TOP VIEW
Alber Battery .44" Dia.
BOTTOM VIEW (11.1mm)
Monitoring
35.4" (900mm)

DETAIL A
37.5" (953mm)

DC Connection
Busbars

Ground
78.7" Bus
(2000mm)

See
Detail A

Front View Left Side View


Door Removed Panel Removed
NOTES
1. Dimensions are in inches [mm].
2. Control wiring and power wiring must be run in separate conduits. Right Side View
3. Emerson recommends using only copper cables. Panel Removed
4. All wiring must be in accordance with national and local electrical codes.
5. If the battery cabinet is attached to the UPS, Emerson will UAM05022
supply the interconnect cables.
Rev. 0
3.2.8 Accessory Fuses and Backfeed Breaker Wiring
Two fuse blocks provide power for the backfeed breakers (standard) and the BDSi (optional). The fuse
blocks are at the lower right of the front of the Liebert APM UPS. Refer to Figure 24 for additional
details. See for fuse holder locations.
The backfeed breaker fuse block provides 120V nominal provided from the UPS output (L-N) and the
fuse is rated for 8 amps. Figure 14 shows the backfeed breaker wiring.
The BDSi fuse block provides 208V nominal from the UPS output (L-L) and the fuse is rated at 8A.
The BDSi power wiring is shown in Figures 40 and 66.

Liebert® APM™ 26
Electrical Connections—UPS

Figure 13 Accessory fuses

Backfeed BDSi Fuse


Breaker Block
Fuse Block (optional)

Figure 14 Dual input backfeed breaker wiring when bypass distribution cabinet not used
1. Auxiliary contacts not needed for backfeed breaker operation. Upstream Bypass
2. A 120V shunt trip coil is required for proper operation. Input Breaker
Upstream System Dual Input Control Wiring
Input Breaker Single Input Control Wiring

AUX MX Backfeed Breaker AUX MX Backfeed Breaker


C2 C1 C2 C1
J10 Fuse Block (FH1) J10 Fuse Block (FH1)
2 3 2 3

PH B PH B
J11
2 3 N N

UHRF3S67X2 (J10, J11) Upstream Rectifier


Input Breaker

J10
AUX MX
C2 C1
J11
2 3
J11

UAM04030
APM Bypass Module Rev. 3

NOTE
Shunt trips are required in upstream breakers to allow backfeed protection to function
properly.

27 Liebert® APM™
Electrical Connections—UPS

3.2.9 Safety Ground


The safety ground busbar is below the neutral input and output busbars as shown in Figure 15
below. The safety ground cable must be connected to the ground busbar and bonded to each cabinet in
the system. This ground busbar is then connected to the ground electrode conductor (GEC).
All cabinets and cable conduit should be grounded in accordance with local regulations.

! WARNING
Risk of electrical shock and arc flash. Can cause property damage, injury anddeath.
Failure to follow proper grounding procedures can result in electric shock hazard to personnel
or the risk of fire, should a ground fault occur.

NOTE
Proper grounding significantly reduces problems caused by electromagnetic interference.

NOTE
The ground and neutral busbars are easily accessible when the right side panel is removed.
Cable connections should be made before a cabinet is attached to the right side of the Liebert
APM or before the UPS is placed where another obstruction, such as a wall, is against the
Liebert APM’s the right side.

Liebert® APM™ 28
Electrical Connections—UPS

Figure 15 Ground and neutral busbar connections—45kVA frame busbars


1.75" (44mm)
1.75" (44mm) (Typ.) 1.52" (39mm)
(Typ.)
1.65"
(42mm) ø .50" (13mm) ø .55" (14mm)
1.65" 4 places
2 places
(42mm) .8" (20mm)
3.54" (90mm) (Typ.)
.8" (20mm) 1.6" (41mm)
.7" (18mm)
DETAIL D
Top View DC Busbars DETAIL C
Top View Ground
ø .50" (13mm)
Typ.

Main Input Busbars


Same for Bypass and
Output Busbars

See
Detail D
TOP VIEW BOTTOM VIEW 1.75" (44mm) Typ.

31.5" (800mm) 37.5" (953mm) DETAIL A

Links for Main


to Bypass
(Single Input Only)

2.2" (56mm)
Typ. 6 Places Main Input
Busbars

Bypass
78.7" Battery Busbars
(2000mm) Breaker

Ground
1.97" (50mm) See Detail A
Typ. 3 Places

See Output
Detail B Busbars
DC Busbars
2.36" See Detail A
(60mm)
Typ. 2
Places
FRONT VIEW DETAIL B
RIGHT SIDE VIEW
Door Removed Panel Removed
NOTES
1. All dimensions are in inches (mm).
2. Control wiring and power wiring must be run in separate conduits.
3. Copper cables only are recommended.
4. All wiring must be in accordance with national and local electrical codes.

29 Liebert® APM™
Electrical Connections—UPS

Figure 16 Ground and neutral busbar connections—90kVA frame busbars

NOTES
1. Dimensions are in inches [mm].
2. Control wiring and power wiring must be run in separate conduits. UAM02021
3. Emerson recommends using only copper cables. Rev. 3
4. All wiring must be in accordance with national and local electrical codes.

Liebert® APM™ 30
Electrical Connections—UPS

3.2.10 Protective Devices


For safety, it is necessary to install circuit breakers in the input AC supply external to the UPS
system. Given that every installation has its own characteristics, this section provides guidelines for
qualified installation engineers with knowledge of operating practices, regulatory standards and the
equipment to be installed.
UPS Rectifier and Bypass Input Supply
Protection from excessive overcurrents and short circuits in power supply input
External overcurrent protection for the AC output circuit is to be provided. See 11.4 - UPS Elec-
trical Characteristics and Table 47 for overload capacity.
A breaker is used for internal battery circuit overcurrent protection. When an external battery
supply is used, overcurrent protection for the battery circuit is to be provided by the customer.
• Dual Input Single Source
When wiring the UPS with dual inputs but with a single input source, the Rectifier input and the
Bypass input must be protected separately. Size the breakers according to the input currents
shown in Table 41.
NOTE
For single or dual input, a 120V shunt trip coil(s) is required when a breaker is supplied by the
customer. See Figures 4 and 5 for details.
Fuses
The Liebert APM’s main input and bypass input busbars are equipped with fuses (six locations; see
Figure 51). The type is Bussman 170M4465, rated at 550A and 700V.
System Output
When using an external distribution panel for load distribution, the output neutral and input neutral
must be separated at the input to the UPS.

3.2.11 Cabling Procedure

! CAUTION
The operations described in this section must be performed by authorized electricians or
qualified technical personnel. If you have any difficulties, contact your local Emerson
representative or Liebert Services.
NOTE
Hydraulic pressure pliers, combinative tools and piston ring pliers should be used to connect
AC wiring.
Once the equipment has been positioned and secured for operation, and the battery and ground lugs
have been connected (see 3.2.7 - Cable Connections), connect the power cables as described below.
(Study the reference drawing in 7.0 - Installation Drawings.)
1. Verify that all incoming high and low voltage power circuits are de-energized and locked out or
tagged out before installing cables or making any electrical connections.
2. Remove the right side panel to gain easier access to the connections busbars.
3. Connect the safety ground and any easier bonding ground bus cables to the copper ground busbar
located in the middle of the Liebert APM below the Input and Bypass connections. All cabinets in
the UPS system must be connected to the user’s ground connection.
NOTE
The grounding and neutral bonding arrangement must comply with the National Electrical
Code and all applicable local codes.
4. Identify and make power connections with incoming cables according to Steps 5 through 8.

31 Liebert® APM™
Electrical Connections—UPS

Common Input Connections


5. For common bypass and main inputs, connect the AC input supply cables to the UPS input
terminals (A2-B2-C2-N1) and tighten the connections to 240lb-in. (27N-m) (M10 Bolt). Ensure
correct phase rotation.
NOTE
For common bypass and main inputs, the AC input cables must be connected to the bypass
terminal (A2-B2-C2-N1) but not the main input terminal (A2-B2-C2).
Split Bypass Connections
6. If a split bypass configuration is used, connect the AC input supply cables to the rectifier input
terminals (A1-B1-C1-N1) and the AC bypass supply cables to the bypass input terminals
(A2-B2-C2-N1) and tighten the connections to 240lb-in. (27N-m) (M10 Bolt). Ensure correct phase
rotation.
NOTE
For split bypass operation, ensure that the busbars between bypass and rectifier inputs are
removed. The neutral line of the bypass input must be connected to that of the rectifier input.
Output System Connections—Ensure Correct Phase Rotation
7. Connect the system output cables between the UPS output busbars (A-B-C-N terminals) and the
critical load and tighten the connections to 240lb-in. (27N-m) (M10 bolt).

! WARNING
Risk of electrical shock and arc flash. Can cause property damage, injury and death.
If the load equipment will not be ready to accept power when the commissioning engineer
arrives, ensure that the system output cables are safely isolated.
Internal UPS Battery Connections
The UPS internal batteries will be connected at the factory, EXCEPT the connections between the
shelves and to the breaker.

! WARNING
Risk of electrical shock and arc flash. Can cause property damage, injury and death.
The DC bus is live when this internal battery connection is made. This connection is to be
performed ONLY by Emerson Network Power® Liebert Services at startup.
Observe the battery cable polarity. Be sure that the battery connection is made with the cor-
rect polarity.
8. Refit all protective covers removed for cable installation.

3.3 Control Cables Details


3.3.1 Static Bypass Assembly Features
Based on your site’s specific needs, the UPS may require auxiliary connections to manage the battery
system (external battery circuit breaker, battery temperature sensor), communicate with a personal
computer or provide alarm signaling to external devices or for Remote Emergency Power Off (REPO).
Terminations for these functions are located at the front of the static bypass module. The main
features are:
• Input and output dry contacts signal (one pair of contacts of relay)
• Emergency Power Off control (EPO)
• Environmental parameter input interface
• User communication (for data setting and user background monitor)
• Liebert IntelliSlot® interface
• Temperature detect interface

Liebert® APM™ 32
Electrical Connections—UPS

Figure 17 Static bypass assembly connections to display cabinet and options

Monitor
Operator Control Panel

J4
Battery Cabinet
J8

J5
Bypass Distribution Cabinet
J12
Static
Bypass Backfeed Protection J11 Bypass
Mains Backfeed Protection J10 Assembly

Temp Sensor (optional) and J4


BCB Control Board

Ground Fault (optional)


Sensor & BCB Control Board J9
On Generator (optional)

Figure 18 Auxiliary terminal block detail (static switch assembly front panel)

Input /output dry contact and EPO /BCB/MBC interface


J1~J3 port can’t connect to hone !

Auxiliary
Terminal
J7
J1 J4 J10 Block
GND

MFP_C
+12V

MFP_S

MFP_O
BAT-OUT

OUT
BAT -IN

GND

INPUT_2

INPUT_1

J2 PARA J5 J8 J11
GND

EXT-OUT

GND

DRIVER

BFP_C
Q2BP

Q3BP

ONLINE

BFP_S

BFP_O
BCB_IN

PARA
J3 J6 J9 J12
+12V

+12V

+12V

BAT-READY

ENV_DB

INV_S

INV_O
EPO-NC

EPO-NC

BAT-GND

INV_C

LBS

NOTE
Terminal block connectors are on the left side of the static bypass assembly.

33 Liebert® APM™
Electrical Connections—UPS

3.4 Dry Contacts


The UPS provides input dry contacts and output dry contacts on the Auxiliary Terminal Block (ATB).

3.4.1 Input Dry Contacts


External input dry contacts are connected via the ATB. Dry contacts are available for environment
detection, battery ground fault detection, etc.
The UPS accepts external signal from zero-voltage (dry) contacts connected through external dry
contact terminals produced, and these terminals are on the static bypass assembly. Through software
programming, these signals become active when these contacts connect to +12V to ground (in the
most left side). The cables connected to the monitor board must be separated from power cables.
Moreover, these cables should be double-insulated with a typical cross-section of 0.5 to 1mm2 for a
maximum connection length between 82 and 165ft. (25-50m). The ATB has several input dry contacts.
Figure 19 Input dry contacts

12V 12V

12V
+12V

J9 J4 J5 J8
+12V

+12V

Q2BP

Q3BP

ONLINE
BAT_GND

GND

BAT_IN

GND

GND

BCB_IN

DRIVER
ENV_DET

BAT_OUT

EXT_OUT
BAT_READY-

NOTE: The black square () on each connector indicates Pin 1.


Refer to Figure 18 for the location of connectors J4, J5, J8 and J9.
Table 4 Description of dry contact input port
Position Name Description
J9.1 ENV_DET Detection of battery room environment (normally closed); On Generator; EVN
J9.2 BAT_GND Battery short to ground detection; BtG; On Generator
J9.3 BAT_READY Not Used
J9.4 +12V +12V power supply
J4.1 BAT_IN Internal battery temperature detection
J4.2 +12V +12V power supply
J4.3 BAT_OUT External battery temperature detection
J4.4 GND Power supply GND
J5.1 Q3BP Input circuit breaker status of external Liebert BDC
J5.2 Q2BP Output circuit breaker status of external Liebert BDC
J5.3 EXT_OUT Input circuit breaker status of internal Liebert BDC
J5.4 GND Power supply GND
J8.1 DRIVER BCB Driver Signal
J8.2 BCB_IN BCB Contact State
J8.3 GND Power Ground
BCB On-Line - Input (N.O.) - This pin will become active when the BCB
J8.4 ONLINE
interface is connected.

Liebert® APM™ 34
Electrical Connections—UPS

3.4.2 Output Dry Contacts


The Auxiliary Terminal Block has three output dry contact relays (see Figure 20 and Table 5).

Figure 20 Output dry contacts and EPO wiring

J11 J12 J10


BFP_S

INV_S

MFP_S
BFP_C

INV_C

MFP_C
BFP_O

INV_O

MFP_O
NOTE: The black square () on each connector indicates Pin 1.
Refer to Figure 18 for the location of connectors J10, J11 and J12.

Table 5 Output dry contact relays


Position Name Description
J11.2 BFP_O Bypass feedback protection relay. Normally open. Closed when bypass SCR is shorted.
J11.3 BFP_S Bypass feedback protection relay center
J11.4 BFP_C Bypass feedback protection relay. Normally closed. Open when bypass SCR is shorted.
J12.2 INV_O Inverter mode relay. Normally open. Closed when UPS is in inverter mode.
J12.3 INV_S Inverter mode relay common
J12.4 INV_C Inverter mode relay. Normally closed. Open when UPS is in inverter mode.
J10.2 MFP_O Main feedback protection relay. Normally open. Closed when bypass SCR is shorted.
J10.3 MFP_S Main feedback protection relay common
J10.4 MFP_C Main feedback protection relay. Normally closed. Open when bypass SCR is shorted.

NOTE
All auxiliary cables of terminal must be double-insulated. Wire should be 20-16AWG stranded
for maximum runs between 80 and 200 feet (25-60m), respectively.
3.4.3 Liebert BDC Interface
The Liebert BDC interface is on the Auxiliary Terminal Block at J5. Refer to Figure 18 for the
location of connector J5 and to Figure 19 for circuit details.
Table 6 Liebert BDC interface
Position Name Description
J5.1 Q3BP Input circuit breaker status of external Liebert BDC
J5.2 Q2BP Output circuit breaker status of external Liebert BDC
J5.3 EXT_OUT Input circuit breaker status of internal Liebert BDC
J5.4 GND Power supply GND
These contacts cannot be active unless they are set via software.

NOTE
All auxiliary cables of terminal must be double-insulated. Wire should be 20-16AWG stranded
for maximum runs between 80 and 200 feet (25-60m), respectively.
NOTE
Refer to Table 10 and Figure 45 for the Liebert BDC wiring.

35 Liebert® APM™
Electrical Connections—UPS

3.4.4 Battery Cabinet Interface Connectors


The battery cabinet interface is on the Auxiliary Terminal Block at J8 and J4. Refer to Figure 18 for
the location of connectors J4 and J8 and to Figure 19 for circuit details.
Table 7 Battery cabinet interface
Position Name Description
J4.1 BAT_IN Internal Battery Temperature Detection
J4.2 +12V +12V Power Supply
J4.3 BAT_OUT External Battery Temperature Detection
J4.4 GND Power Ground
J8.1 DRIVER BCB Driver Signal
J8.2 BCB_IN BCB Contact State
J8.3 GND Power Ground
BCB On-Line - Input (N.O.) - This pin will become
J8.4 ONLINE
active when the BCB interface is connected.

NOTE
All auxiliary cables of terminal must be double-insulated. Wire should be 20-16AWG stranded
for maximum runs between 80 and 200 feet (25-60m), respectively.
NOTE
Refer to Table 9 and Figure 40 for battery cabinet wiring.

3.4.5 EPO Input—Optional

NOTICE
Risk of exceeding internal voltage limits. Can cause equipment damage.
Do not apply more than 12V to the Emergency Power Off (EPO) input. Exceeding 12V on this
input can damage the Liebert APM’s internal circuitry and control boards. Exceeding 12V will
also put the Liebert APM in an EPO state, and the unit will not reset, making it non-
functional.
The UPS has an Emergency Power Off (EPO) function operated by a button on the control panel or by
a remote contact provided by the user. The EPO button is under a hinged, clear plastic shield.
The J6 connector, shown in Figure 21, is the remote EPO input interface. The EPO has NO/NC
contacts that become active when shorting terminals J6: 3 and 4 or open terminal connection J6: 2
and 1.
If an external Emergency Stop capability is required, it is connected at terminals J6: 1 and 2 and at
J6: 3 and 4 on the monitor board. It also is connected to the Normally Open or Normally Closed
remote stop switch between these two terminals using shielded cable (see Figure 21 and Table 8). If
this function is not used, terminals J6:3 and 4 must be opened and J6:1 and 2 must be closed.

Figure 21 EPO wiring and signal names for J6


+12V +12V

J6 J6

NOTE: The black square () on each


EPO-NC
EPO-NO

+12V

+12V

connector indicates Pin 1.


EPO-NO EPO-NC Refer to Figure 18 for the location of
connector J6.

Liebert® APM™ 36
Electrical Connections—UPS

Table 8 EPO input contact relays


Position Name Description
J6.1 EPO_NC EPO Activated when opened to J6.2
J6.2 +12V EPO Activated when opened to J6.1
J6.3 +12V EPO Activated when shorted to J6.4
J6.4 EPO_NO EPO Activated when shorted to J6.3

NOTE
The Emergency Stop action within the UPS shuts down the rectifier, inverter and static
bypass. It does not internally disconnect the input power supply. To disconnect ALL power to
the UPS, open the upstream feeder breaker(s) when the remote EPO is activated.
NOTE
Normally Closed EPO – J6: 1, 2, these terminals are supplied factory-linked on the Bypass
Module on the UPS and must remain installed if using NO contacts.
NOTE
All auxiliary cables of terminal must be double-insulated. Wire should be 20-16AWG stranded
for maximum runs between 80 and 200 feet (25-60m), respectively.

Figure 22 Single UPS Remote Emergency Power Off


Single Liebert APM Module
Liebert APM
Bypass Module

Remote EPO X2_J6


(Customer- UHRF3S67X2
Supplied)

UHRF3S67X2 (J6)

Liebert APM UAM04031-00


Bypass Module Field-Supplied Wiring Rev. 1

37 Liebert® APM™
Parallel System and LBS System Installation

4.0 PARALLEL SYSTEM AND LBS SYSTEM INSTALLATION


This chapter gives details on the installation of a parallel system and an LBS system.

4.1 General
A parallel Liebert APM system can consist of two Liebert APM cabinets connected in parallel without
a main system static bypass. Instead, the bypass static switches of each UPS share the load when the
system transfers to the utility bypass supply. A third-party APM paralleling switchboard may be used
to provide external maintenance capability. See Figure 23 for details.
From a power viewpoint, each module is internally identical to the single-module configuration. A
parallel system requires intermodule control signals to manage the load sharing, synchronizing and
bypass switching. The control signals are connected through parallel communication cables, which
provide bi-directional communication between the two Liebert APM units of the system. A second
parallel cable is provided to establish redundancy.
When Liebert APM units are to be connected in parallel, a sharing inductor assembly is required and
must be installed inside the Liebert APM cabinet. The inductor may be installed at the factory or
field-installed.

4.2 System Installation Procedures


The installation of a parallel UPS should follow the procedures for a single UPS module with the
additional requirements detailed in this section.

4.2.1 Preliminary Checks


Be sure that the options of the parallel cables are correct and that the modules are of the same rating,
model and with the same software and hardware release.

! WARNING
To achieve coordinated operation of the modules in the parallel system, it is required to
configure each module separately using Emerson configuration software. This must be done
by Emerson service personnel.

4.2.2 Cabinet Installation


Position the UPS modules and make connections as shown in Figure 23. The output distribution
consisting of external UPS output switches and maintenance bypass must be installed, as shown in
Figure 23, to facilitate maintenance and system testing.

Liebert® APM™ 38
Parallel System and LBS System Installation

Figure 23 UPS system with external maintenance switch

MBB
Buyout Liebert APM Paralleling Switchboard

* System AC Output
AC Input UIB UIB Opt. K MIB 4-Wire+GND
4 Wire +GND See
Note 7

MOB1
Output
Liebert APM #1 Busbar
UPS Cabinet

Static Bypass

Output MOB2
Liebert APM #2 Busbar
UPS Cabinet
Field-Supplied Wiring
Battery
* External overcurrent protection by others
LEGEND
UIB - UPS Input Breaker
NOTES: MOB - Module Output Breaker
1. Install in accordance with national and local 6. The 90kVA frame has a capacity of up to six MIB - Maintenance Isolation Breaker
electrical codes. Flex Power assemblies and the 45kVA frame has a MBB - Maintenance Bypass Breaker
2. Input and bypass must share the same single source. capacity of up to three Flex Power assemblies.
3. A neutral is required from the system AC input source. 7. Paralleling switchboard requires shunt trip UIB breakers
A full capacity neutral conductor is recommended. with 120V coils.
Grounding conductors are recommended. 8. See drawings UAM01080B, UAM01080C, UAM01080D,
4. Bypass and rectifier inputs and output cables must be UAM01080E and UAM01080F. Refer to the following
run in separate conduits. battery cabinet control wiring drawings:
5. Control wiring must be run in separate conduits. UAM04000
UAM4001A,B UAM01060A
UAM4002A,B D) Rev. 0

NOTE
For parallel system installations, an external bypass rated for the total system load must be
installed.
For parallel systems, Emerson recommends installing bypass load sharing inductors to optimize
current sharing during static bypass operation.

4.2.3 External Protective Device


Refer to 3.2 - External Protective Devices.

39 Liebert® APM™
Parallel System and LBS System Installation

4.2.4 Power Cable


The power cable wiring is similar to that of the UPS module. Refer to 3.1 - Power Cabling.
The bypass and rectifier input supplies must use the same neutral line input terminal. If the input
has a current leakage protective device, the current leakage protective device must be fitted upstream
of the neutral line input terminal.
NOTE
The length and specification of power cables including the bypass input cables and UPS output
cables should be the same. This facilitates load sharing in bypass mode.

4.2.5 Input Breaker Control Wiring


Figure 24 Input breaker control wiring for parallel systems

UIB Liebert APM 1


Backfeed Breaker
Paralleling
Fuse Block (FH1)
Switchboard Liebert APM #1

ØA
ØB
BDSi ØC
Fuse Block (FH2) Input Neutral Liebert APM
(Optional) Bypass
TB1 J10
1 2
Liebert APM Detail View
with Door Open 2 3

3 J11
2
4
3
5
Phase
6
Neutral
Backfeed
J10 Breaker
Fuses, (2) 8
UHRF3S67X2 UIB Liebert APM 2
(J10, J11) Paralleling
J11 Switchboard Liebert APM #2

ØA
ØB
ØC
Input Neutral Liebert APM
TB1 J10 Bypass
7 2

Liebert APM Bypass Module 8 3


Only One Shown
9 J11
Notes
1. See drawings UAM01080A, UAM01080B, 2
UAM01080D, UAM01080E and UAM01080F. 10
2. Paralleling switchboard requires shunt trip 3
UIB breakers with 120V coils. 11
Phase
12 Neutral
Field-Supplied Wiring Backfeed
Breaker UAM1080C
Fuses, (2) 8
Pg. 3, Rev. 1

4.2.6 Output Breaker Control Wiring


Auxiliary wiring must be installed as shown in Figure 25 to protect the system and enable a single
UPS to be isolated and tested during service.

Liebert® APM™ 40
Parallel System and LBS System Installation

Figure 25 Output breaker control wiring


Buyout Liebert APM Paralleling Switchboard
MBB

System AC Output
AC Input MIB 4-Wire + GND
4-Wire + GND
UIB MOB1 See Note 2
UHRF3S67X2 (J5) Liebert
APM #1
TB2
1 1
See Note 3
2
3 2
4 3
X2 J5
J5

MOB2
UIB
Liebert
APM #2

1 4
Liebert APM Bypass Module 2 See Note 3
Only One Shown 3 5
4 6
Notes
1. See drawings UAM01080A, UAM01080B,
UAM01080C, UAM01080E and UAM01080F.
2. MBB auxiliary switch connections are on the normally
closed and common positions.
3. MOBs auxiliary switch connections are on the normally
Field-Supplied Wiring UAM0180D
open and common positions. Rev. 1

4.2.7 Parallel Cables


Shielded and double-insulated parallel control cables available in lengths of 16.4ft. and 32.8ft. (5m
and 10m) must be interconnected in a ring configuration between the UPS modules, as shown in
Figure 26. The parallel ports J1 and J2 are provided on the front panel of the bypass module, as
shown in Figure 28. The ring connection ensures the reliability of the control of the parallel system.
Be sure to verify the reliable cable connection before starting up the system!
NOTE
Use the shortest parallel control cables possible for the application . Do not coil excess cable.
Meanwhile, separate the parallel control cables from the power cables to prevent electrical
inteferences.
Figure 26 Connection of parallel control cables of parallel system
UHRF3S67X2 (J1, J2)

Liebert APM 1 Liebert APM 2

J1 J1

J1

J2
J2 J2

Liebert APM Bypass Module


Notes Only One Shown Parallel Control Cables
1. See drawings UAM01080A, UAM01080C,
UAM01080D, UAM01080E and UAM01080F. Factory-Supplied Wiring UAM1080B
2. Load Bus Sync cable not used with parallel system. Pg. 2, Rev. 0

41 Liebert® APM™
Parallel System and LBS System Installation

4.2.8 Key Interlock System


Figure 27 Key interlock system control wiring
Buyout Liebert APM Paralleling Switchboard
AC Input MBB AC Output
ØA ØA
ØB ØB
ØC ØC
See Note 2 Neu

UHRF3S67X2 (J5, J12) Kirk Key


K1
MOB1 MIB

Liebert
APM #1
*See Note 4 TB3
3 1
4 2 See Note 3 Kirk Key
X2 J12 TB2 K2
J5
1 1
2
3 2
4 3
2 Fuses
X2 J5 2A

SKRU
MOB2

Liebert APM Bypass Module Liebert


APM #2 KO
Only One Shown
*See Note 4 TB3
Notes 3 See Note 3
3
1. See drawings UAM01080A, UAM01080B,
4 4
UAM01080C, UAM01080D and UAM01080F.
X2 J12 Push
2. MBB auxiliary switch connections are on the normally TB2
closed and common positions. Button
1 4
3. MOBs auxiliary switch connections are on the normally 2
open and common positions. 3 5
4. Contact closes when UPS is on internal bypass. 4 6
X2 J5 Inner Door SWBRD
Field-Supplied Wiring

UAM0180E
Rev. 0

Transfer Parallel Liebert APM Units to System Bypass Mode


1. Verify that all Liebert APM units are in internal maintenance bypass mode. The light in the
SKRU push button will turn On when all units are in bypass.
2. Hold the push button in and rotate the key in K0 to remove key.
3. Insert key in MBB interlock K1 and rotate to withdraw interlock. Key will remain in interlock.
4. Close the MBB.
5. Open the MIB and rotate thekey in K2 to extend interlock.
6. Remove key from MIB interlock K2 and place in K0.
7. Rotate key in K0 to lock key.
Return Parallel Liebert APM Units to Normal Mode
1. Verify that all Liebert APM units are in internal maintenance bypass mode. The light in the
SKRU push button will turn On when all units are in bypass.
2. Hold the push button in and rotate the key in K0 to remove the key.
3. Insert the key in the MIB interlock and rotate the the key in K2 to withdraw interlock.
4. Close the MIB.
5. Open the MBB and rotate the key in K1 to extend interlock.
6. Remove the key from the MBB interlock K1 and place it in K0.
7. Rotate the key in K0 to lock the key.

Liebert® APM™ 42
Parallel System and LBS System Installation

Figure 28 Locations of ports J1, J2 and J3 on bypass module

Input/output dry contact and EPO/BCB/MBC interface


J1 ~ J3 port can’t connect to phone!

J1 J4 J7 J10

J1 INTELLISLOT1 INTELLISLOT2 INTELLISLOT3

MFP_C
INPUT_1
+12V
GND

GND
BAT-OUT

BAT-IN

INPUT_2

MFP_S

MFP_O
OUT
J2 PARA J5 J8 J11

J2

ONLINE
EXT-OUT

BFP_C
GND

Q3BP
Q2BP

DRIVER
GND

BFP_O
BFP_S
BCB_IN
J3 PARA J6 J9 J12

J3

ENV_DET
EPO-NO

BAT_READY

BAT_GND
+12V
EPO-NC

INV_C

INV_S
+12V

+12V

INV_O
MONITOR RS485-1 RS485-2 RS232
LBS

4.2.9 Remote EPO


In addition to the EPO switch provided on the operator control and display panel of each UPS module
for controlling the EPO of each module respectively, the parallel system also provides remote EPO
function for controlling all UPS modules to shut down simultaneously from a remote terminal, as
shown in Figure 29.
NOTE
1. The remote EPO switch must provide a dry contact signal, which is normally open or
closed.
2. The open circuit voltage provided is 5VDC, <20mA.
3. The external EPO device can be composed of another control system that can disconnect the
UPS mains supply or the bypass input.
4. Pins 1 and 2 of the normally closed EPO-J6 port on the bypass module are connected at the
factory.

Figure 29 Remote Emergency Power Off wiring for parallel UPS


Two Liebert APM
Modules in Parallel
Liebert APM
Bypass Module 1

X2_J6
UHRF3S67X2

Remote EPO
(Customer-
Supplied) Liebert APM
Bypass Module 2

UHRF3S67X2 (J6)

X2_J6
UHRF3S67X2

Liebert APM UAM04031-00


Bypass Module Field-Supplied Wiring Rev. 1

43 Liebert® APM™
Parallel System and LBS System Installation

4.3 LBS System


4.3.1 Cabinet Installation
A dual bus system consists of two independent UPS systems, each containing one or more parallel
UPS modules, as shown in Figure 30. The dual bus system has high reliability and is suitable for
loads with multiple input terminals. For a single-input load, an optional static transfer switch can be
fitted to achieve the transfer between the two outputs of the dual bus system.

Figure 30 Typical dual bus system (with STS and LBS)


Bypass Bypass

Main Input Main Input Main Input Main Input


UPS1A UPS1B UPS2A UPS2B

Parallel Parallel
Control Control
Cable Cable
LBS

STS

To Load
The dual bus system uses the LBS to keep the output of the two independent UPS systems (or parallel
systems) in synchronization. One system is designated as the master, the other is designated as the
slave. The operation modes of the parallel system comprise master and/or slave operation in normal
or bypass mode.
Place the UPS modules side by side and interconnect the UPS modules according to the following
instructions.

4.3.2 External Protective Device


Refer to 3.2 - External Protective Devices.

4.3.3 Power Cable


The power cable wiring is similar to that of the UPS module. Refer to 3.1 - Power Cabling.
The bypass and rectifier input supplies must use the same neutral line input terminal. If the input
has a current leakage protective device, the current leakage protective device must be fitted upstream
of the neutral line input terminal.

4.3.4 Control Cable


For Liebert APM-to-Liebert APM dual bus system, connect the optional LBS cables between the two
UPS systems as shown in Figures 31 to 33. The J3 and J4 ports are provided on the front panel of
the bypass module, as shown in Figures 28.
NOTE
Use the shortest LBS cable that will be functional for the application and do not coil excess
cable. Separate the LBS cable from the power cables to prevent electrical inteferences.

Liebert® APM™ 44
Parallel System and LBS System Installation

Figure 31 Connection of typical dual bus system of two parallel systems

UPS 1 UPS 2 UPS 3 UPS 4


Bypass Module Bypass Module Bypass Module Bypass Module
J1 J1 J1 J1

J2 J2 J2 J2

J3 J3 J3 J3

LBS Cable
LBS Cable

Figure 32 Connection of typical dual bus system of two single UPS’s without redundant LBS cable

UPS 1 UPS 2
Bypass Module Bypass Module
J1 J1

J2 J2

J3 J3

LBS Cable

Figure 33 Connection of typical dual bus system of two single UPS’s with redundant LBS cable

UPS 1 UPS 2
Bypass Module Bypass Module
J1 J1

J2 J2
LBS
Cab
le
J3 J3
le
Cab
LBS

45 Liebert® APM™
Battery Installation

5.0 BATTERY INSTALLATION

5.1 Introduction
Emerson recommends that the batteries in external cabinets be the same type and made by the same
manufacturer as the internal batteries in the Liebert APM.
If multiple sets of batteries connected in parallel are used to provide the required battery backup run
times, fit each set with an isolating device to permit working on one of the battery sets while leaving
the others in service and providing backup protection.

5.2 Safety
Special care should be taken when working with the batteries associated with the Liebert APM
system equipment.

! WARNING
Risk of electrical shock and arc flash. Can cause property damage, injury and death.
The Liebert APM’s internal batteries are connected and energized even if the UPS is turned
Off. To minimize the risk of injury, a properly trained and qualified service person should
disconnect internal batteries before any maintenance is performed on the unit.
When all batteries are connected together, the battery terminal voltage may exceed 324V and
is potentially lethal.
The center of the battery is connected to the neutral of the UPS and is grounded.
A battery can present a risk of electrical shock and high short circuit current. The following
precautions should be observed when working on batteries:
• Remove watches, rings and other metal objects.
• Use tools with insulated handles.
• Wear rubber gloves and boots.
• Do not lay tools or metal parts on top of batteries.
• Disconnect charging source prior to connecting or disconnecting battery terminals.
• Determine whether the battery is grounded. If the battery is grounded, remove source of
the ground. Contact with any part of a grounded battery can result in electrical shock. The
likelihood of such shock can be reduced if such grounds are removed during installation and
maintenance.

When replacing batteries, replace with batteries of the same type and manufacturer, or equivalent.
Refer to 11.2 - UPS Environmental for a list of approved batteries or contact your Emerson
representative.

! CAUTION
Batteries used in the Liebert APM and its auxiliary cabinets must be of an approved type.
Replacing batteries with an incorrect type can cause an explosion and fire. Refer to Tables 38
and 40 for acceptable batteries.
Do not dispose of batteries in a fire. The batteries may explode. Do not open or mutilate
batteries. Released electrolyte is harmful to the skin and eyes. It is toxic.

Liebert® APM™ 46
Battery Installation

5.3 UPS Batteries—Liebert APM 45kVA Frame Only


The Liebert APM’s internal batteries are fully charged before the unit is shipped. During storage and
transportation, some charge is lost. All batteries should be recharged before use. The battery charger
works only when the Liebert APM is connected to input power and turned On.
NOTE
Full safety instructions concerning the use and maintenance of UPS batteries are provided in
the appropriate battery manufacturer's manuals, available on the manufacturer’s Web site.
The battery safety information contained in this section relates to key considerations that must
be taken into account during the installation design process and might affect the design
outcome, depending on your installation.

5.3.1 Internal Battery Breaker Component Locations and Control Wiring


The Liebert APM 45kVA frame contains internal batteries. The batteries are protected by an internal
battery breaker. Figure 34 shows the component location; Figure 35 shows the control wiring.

Figure 34 Internal battery breaker component locations

UHRF3S67X2
Liebert APM
Bypass Module
TB1

Battery Battery
Temperature Breaker
Sensor UHW241C2
Location UH8351A8 BIB Board
Capacitor
Board

See
Detail A

UAM04052A
See Figure 35 Detail A
FRONT Pg. 1, Rev. 0

47 Liebert® APM™
Battery Installation

Figure 35 Internal battery control wiring

Battery
Breaker
Liebert APM
W61 DC Bus
Positive (+)

W62
Neutral (Neg. Midpoint)
Neg. Midpoint
W63
Negative (-)
Liebert APM
Aux. MX
Internal
Battery W1 X107
Red 3
Black 2
W2 1
TB1 Red Black
Black J4 X101 Detail A
Black Capacitor BIB
See Note 2
Board Board
Striped Com White
UH8351A8 UHW241C2
Yellow NO White J3 See Detail A
Black Black
220VDC 220VDC
Brown Brown X107
White White Liebert APM
Green Green J2 X100 Bypass Module
DRV
AUX X108 1
Black BAT IN
See Figure 34 GND1
USE
1
2
White
Red
2 +12V
Red White
X102 3 3 BAT-OUT
W3 Black
X104 X106 4 GND
X103 X105 X2 J4
UHRF3S67X2
W4 Black Driver
1
Brown 2 BCB_IN
Internal Battery Temperature Sensor White
3 GND
Green
4 Online
X2 J8
NOTES
1. All service and initial battery connections 2. Jumper X107 must short circuit Pin 1 and Pin 2.
must be performed by properly trained and 3. The circuit breaker auxiliary blue wire #12 is not used. UAM04052B
qualified service personel. 4. Shunt trip drive is 220VDC @ 2.4A. Pg. 2, Rev. 0

Liebert® APM™ 48
Battery Installation

5.4 External Battery Cabinet Installation


5.4.1 Matching Battery Cabinets
A matching battery cabinet is available. Refer to Figure 37. The same model battery cabinet may be
installed in parallel in multiple cabinet strings for additional capacity. Battery run time depends on
the cabinet model, the number of cabinets and the load on the UPS.
Handling—The battery cabinet has casters to facilitate movement over short distances. The bottoms
of the battery cabinets are reinforced to permit movement by forklift over longer distances.
Inspection—Remove all panels and visually inspect the batteries, bus connections, and cabinet for
any damage. Exercise caution; voltage is present within the battery cabinet even before installation.
If there are signs of damage, do not proceed. Call Liebert Services at 1-800-542-2378.
Storage—The batteries can be stored for up to six months without appreciable deterioration. If
planning to store a battery cabinet for longer than six months or at temperatures higher than 77°F
(25°C), contact Liebert Services for recommended precautions.
The following notes, in conjunction with the diagrams (Figure 37), illustrate the broad principles to
be followed when fitting and connecting the majority of battery cabinet installations.

! CAUTION
Any battery system should be installed by properly trained and qualified personnel.

When installing an external battery cabinet that is NOT a Liebert APM battery cabinet, the customer
must provide overcurrent protection. See Table 43 for sizing of protection devices.
NOTE
When using an external battery supply that is not provided with the UPS, please make
reference to the battery manufacturer’s installation manual for battery installation and
maintenance instructions, available on the manufacturer’s Web site. When replacing batteries,
Emerson recommends that the batteries in external cabinets be the same type used internally in
the Liebert APM. See Tables 38 and 40 for batteries that are approved for use with the Liebert
APM.

Figure 36 Bolting the battery cabinet to the Liebert APM

Washer
Washer Split, M10
2 Split, M10 3

B
1
Hex Head
Bolt, M10

DETAIL B
Liebert Battery
APM Cabinet

49 Liebert® APM™
Battery Installation

5.4.2 Connecting the Batteries


If the Liebert APM battery cabinets are installed on a raised floor, the battery power cables and
circuit breaker control cables may be routed to the UPS cabinet through the bottom of the cabinet.
If the Liebert APM battery cabinets are installed adjacent to one another on a solid floor, these cables
may be passed between the cabinets through slots in the lower sides of the cabinets.
Intertray connections must be made before the battery cabinet may be used.

Figure 37 Battery cabinet, 600mm wide—details

12
X8

Tray 1 B

Tray 2

34
Tray 3 40
42

Tray 4

2X 32

603705G2 ASSY BATT NXRA 600 BATT CAB HX330


603705G4 ASSY BATT NXRA 600 BATT CAB HX300 39
603705
603705G5 ASSY BATT NXRA 600 BATT CAB HX205
DETAIL B Pg. 1, Rev. 1
603705G10 ASSY BATT NXRA 600 BATT CAB HX150 4X

Liebert® APM™ 50
Battery Installation

Figure 38 Battery trays for 600mm battery cabinet


HX300
HX330

HX205
HX150

51 Liebert® APM™
Battery Installation

Figure 39 Battery cabinet with trays for 900mm battery cabinet

Page 1, Rev. 3
603797

Liebert® APM™ 52
Battery Installation

5.4.3 Installation Considerations


Position—Liebert battery cabinets come in versions specific to the left side of the UPS. If the system
includes a matching Liebert BDC, the cabinet should be mounted to the right of the UPS (nearest the
busbars) and the battery cabinet(s) should be installed to the left of the UPS.
The battery cabinet(s) are designed to be located conveniently next to each UPS module on the left
side only and are also available in stand-alone configurations with painted side panels. The front
access design eliminates side and rear service clearance requirements. Refer to Table 36 for battery
cabinet dimensions and weights.
Bolt-On Cabinets—Matching battery cabinets are designed to bolt only onto the left side of the UPS
module cabinet. Use bolts that ship with each unit to connect cabinet frames at posts, two places in
the front and two places in the rear.
Service Clearance—Allow front access to the battery cabinet at all times for maintenance and
servicing. Electrical codes require that the battery cabinet be installed with no less than 3 feet (1m) of
clearance at the front of the cabinet when operating. Side and rear panels do not require service
clearance.
Cables—Cables may be run between the cabinets through cutouts in the top of the cabinet,
eliminating the need for external conduit runs. Route cables before moving cabinets into final position
for bolting together. No top or bottom entry cables are required, except for remotely located cabinets
which require conduits.
Software—To allow the UPS to accurately display the battery run time, the number of battery
cabinets must be noted when performing initial startup and setup using the configuration software.
This is to be performed by the Liebert Services engineer when commissioning the unit.
Casters and Adjustable Stops—The adjustable stops are not designed to bear the full weight of the
cabinet. Lower the stops until they are finger-tight in contact with the floor. Then tighten a small
amount with a wrench (less than two turns) to give a good friction fit. When mounting the battery
cabinet on seismic stands, ensure that the casters are bearing the weight of the cabinet.

5.4.4 Connecting the Battery Cabinet to the UPS


After the battery cabinet equipment has been positioned and secured for operation and the batteries
have been connected, connect the power cables as described below (see Figure 40).
1. Verify that all incoming high and low voltage power circuits are de-energized and locked out or
tagged out before installing cables or making any electrical connections.
2. Remove the UPS right side panel to gain access to the ground and battery busbars.
3. Remove the battery cabinet front panel to gain access to the busbars.
4. Connect the safety ground and any necessary bonding ground cables to the copper ground busbar.
(example: UPS located on the bottom of the equipment below the power connections).
All cabinets in the UPS system must be connected to the user's ground connection.
NOTE
The grounding and neutral bonding arrangement must be in accordance with the National
Electrical Code and all applicable local codes.
5. Connect the system battery cables from the UPS battery terminals (+ N -) to battery cabinet
breaker BCB (+ N -) as shown in Figure 40. Be sure that the battery connections are made with
the right polarity, and tighten the connections to 240lb-in. (27N-m) (M10 bolt). Do not close the
battery circuit breaker before the equipment has been commissioned.
6. Connect TB1 from battery cabinet to J4 and J8 on the UPS according to Table 9.
NOTE
The shunt trip drive capability for the battery breaker is 220VDC at 2.4A.

53 Liebert® APM™
Battery Installation

Table 9 Control wiring for Liebert APM to battery cabinet


From To
Liebert APM UPS Bypass Battery Cabinet
Module (X2 J4 & J8) Terminal Strip (TB1)
J4-2 TB1-12
J4-3 TB1-11
J4-4 TB1-10
J8-1 TB1-6
J8-2 TB1-7
J8-3 TB1-8
J8-4 TB1-9

Figure 40 Battery cabinet connection to Liebert APM

GRD
W21 Positive Fault CT AC 120V
from UPS
W22 Neutral BDSi Fuse Block
Neg. Mid Pt.
W23 Negative

Aux. MX

Ground W24
Blue (Not Used)

Red
See
Note 3 Black TB2
UPS
Blue Brown
TB1
Red Blk Module
Orange W/R J4 X101 Yel/Grn
1
Black
2 W/Blk UH8351A8 BCB
3 BIB
Blue Com White Control
4
Violet NO
5 White
Board
J3
Red
Blk 6 Blk 220VDC Blk 220VDC
X107
Brn 7 Brn 3
Wht 8 Wht 2
1
Grn Grn
9 J2 X100
Blk Blk DRV
10 AUX X108 1 BAT IN
White 11 White GND1 1
Blk
White Red
USE 2 2 +12V
Red Red
12 X102 3
Red White
3 BAT-OUT AC 120V Power
X104 X106 Blk
4 GND to Optional BDSi
X103 X105 X2 J4 Controller
UHR93S6A1
Blk
X2
1 Driver
TEMP Brn
2 BCB_IN
Wht
3 GND
Grn
4 Online
X2 J8

External
1. All service and initial connectino of batteries 3. The auxilliary blue wire is not used. Cap and coil the Connections
must be performed by properly trained and wire and tie it to the bridge lance on the frame below
qualified service personnel. the breaker. UAM04000
2. The Jumper X107 must short circuit Pin 1 and Pin 2. 4. Shunt trip drive is 220VDC @ 2.4A. Rev. 0

Liebert® APM™ 54
Battery Installation

5.5 Non-Standard Batteries


When batteries other than a matching battery cabinet are used, a remote battery disconnect switch
with overcurrent protection is required per the National Electrical Code. Contact your local Emerson
sales representative about this option. Refer to Figures 87 and 88 for details.
Install battery racks, cabinets and batteries in accordance with the manufacturer's instructions.
Verify that the battery area has adequate ventilation and battery operating temperature complies
with the manufacturer's specifications and with all applicable national and local codes.
If you have any questions concerning batteries, battery racks or accessories, contact Liebert Services
at 1-800-543-2378.
NOTE
The user-supplied battery DC bypass breakers or fuses should have a minimum overload
rating of 8kA and 500V.

5.6 Battery Ground Fault Detection Option


An optional battery ground fault detection device can be added to detect leakage current in the
battery system. The residual current range monitored is 30mA ~ 3000mA. When a battery ground
fault is detected, an alarm will appear on the UPS display panel. The battery ground fault detection
set contains one current transformer (CT). Figures 41 and 42 show the connection of this set for the
Liebert APM.

Figure 41 Battery ground fault detection component location


UHW241M5 Auxiliary Power Board
ULC366SC1 Ground Fault Detect Board
CT

UHRF3S67X2
Liebert APM
Bypass
Module

Isometric View - Right Side


Battery
Breaker
UHR93S6A1ZA6 Battery
Output EMI Board Temperature
Sensor Location

Front
UAM04050A-00
Pg. 1, Rev. 0
Right Side

55 Liebert® APM™
Battery Installation

Figure 42 Control wiring diagram for battery ground fault detection option

W600
Red Blk
UHRF3S67X2 (J9) UHR93S6A1ZA6
Output EMI Board
Liebert APM
Output A Bypass Module

Output B

Output C

Output N X2_J4
UHRF3S67X2
J9
UHW241M5 Blk
Auxiliary Power Board
Red Red
Brn
Blk
X2_J9

W601 W603
Liebert APM Bypass Module
Red Brn Blk
Red Blk
J4 J7
Battery J1 J5

GND
12V
Breaker W602
CT
Blk Brn Blk Brn
Positive

Liebert ULC366SC1
Neutral
APM Ground Fault Detect Board
DC Bus
Negative
Liebert
APM
Internal Notes
Battery
1. All battery service and initial connections
must be performed by properly trained and UAM04050B
qualified personnel.
2. Refer to drawing # UAM04050A, Pg. 1. Pg. 2, Rev. 0

Liebert® APM™ 56
Liebert BDC™

6.0 LIEBERT BDC™


The Liebert BDC is designed to operate in UPS normal mode, static bypass mode and maintenance
mode. The Liebert BDC offers either 45kVA or 90kVA capacity to match the associated Liebert APM
frame offerings. Each of the Liebert BDC capacities offer optional input 208V, 480V and 600V
internal transformers as well as multiple output distribution selections.

Figure 43 Single input UPS with external Liebert BDCwith optional internal transformer—typical
configuration

Bypass Distribution Cabinet

* System MBB Optional AC Output


AC Input Optional
BIB MIB 54-Pole 208V
3-Wire + GRD Transformer
See Note 5 4-Wire + GRD

Local Grounding
Electrode
See Note 1
Static Bypass

UPS Cabinet
Battery

Notes BIB - Bypass Isolation Breaker


1. Install in accordance with national and local electrical codes. MBB - Maintenance Bypass Breaker
2. Input and bypass must share the same single source. MIB - Maintenance Isolation Breaker
3. UPS system input and output cables must be run in separate conduits. * External Overcurrent Protection by Others
4. Control wiring must be run in separate conduits. Field-Supplied Wiring
5. Optional 54-pole, 225A for 45kVA frame only or optional 54-pole, 400A
for 90kVA frame only. UAM01004
6. Transformer available: 480V or 600V input.
Rev. 3

6.1 Normal (UPS) Mode


While the Liebert BDC is in Normal mode (MBB open; BIB/MIB closed), the UPS is supplying the
connected load with continuous, high-quality AC power. In this mode of operation, the load is
protected by the UPS.

6.2 UPS Static Bypass Mode


When the Liebert APM is in Static Bypass mode, it provides an alternate path for power to the
connected equipment. Should the UPS need to be taken out of service for limited maintenance or
repair, manual activation of the Static Bypass will cause an immediate transfer of the equipment
from the UPS inverter to the bypass source. In this mode, power will still be supplied to the UPS;
however, the load is NOT protected by the UPS.

57 Liebert® APM™
Liebert BDC™

6.3 Maintenance Mode


When the Liebert BDC is in Maintenance mode (MBB closed; BIB/MIB open), it provides an alternate
path for power to the connected equipment should the UPS need to be taken out of service for limited
maintenance or repair. In this mode of operation, no power is supplied to the UPS and the load is
NOT protected by the UPS.

6.4 Locating the Cabinet


This Liebert BDC may be mounted to the left of the UPS or installed as a stand-alone unit. In either
case, ensure that the unit is in a well-ventilated area and that there is clearance for access to the
switches and cable connections as required by national and local codes.

6.5 Cable Installation


6.5.1 Wiring Preparation
Be sure that the unit is not connected to any AC utility power source or UPS before installing any
wiring to this unit. This Liebert BDC should be installed by a qualified / certified electrician.

! WARNING
Risk of electrical shock and arc flash. Can cause property damage, injury and death.
Read this section thoroughly before attempting to install wiring to this unit. Read and
comply with all warnings and cautions in this manual.

Removing the Cover Plates


Plates cover the input and output terminals on the front of the Liebert BDC (see Figure 44). Remove
these and keep the screws and plates for reinstallation.

Figure 44 Liebert BDC—access plate removed

6.5.2 Power Cable Installation


Refer to Table 43 when selecting cables.

NOTE
Transient and steady state earth leakage currents may occur when starting the equipment.
This should be taken into account when selecting ground current detection devices because
these will carry the earth leakage currents of both the UPS equipment and the load.

Liebert® APM™ 58
Liebert BDC™

6.5.3 Input/Output Wiring


Follow the steps below to connect the input wiring:

NOTE
Input wiring must be installed using conduit if cabinet is not mounted to the immediate right
of the UPS.
1. Locate the input wiring access (top or bottom access), remove the conduit landing plate and punch
the appropriate size hole for the size conduit being used. Pull the three/four input wires through
it, allowing some slack for installation. For cabinets that are located to the immediate left of the
UPS, the access plate is on the lower right of the cabinet. Remove the access plate and verify that
the edge guarding is installed and intact.
2. Secure the conduit to the access plate of the Liebert BDC.
3. Input power cables connect to the system input circuit breaker; refer to Figure 59 and to
Table 18.
4. Connect the ground (earth) wire to the earth busbar and tighten it to 240lb-in. (27N-m) (M10
bolt).
5. Locate UPS input and output cables and access panel to UPS on lower right side.
NOTE
If the Liebert BDC is not to be bolted to the UPS, use either top or bottom access plate.
6. Connect the system ground cable between the Liebert BDC and UPS and tighten the connections
to 240lb-in. (27N-m) (M10 bolt).
7. Connect the system input cables between the Liebert BDC “UPS Input” Busbars (A-B-C N
terminals) and UPS input busbars (A-B-C N terminals) and tighten the connections to 240lb-in.
(27N-m) (M10 bolt).
8. Connect the system output cables between the Liebert BDC 'UPS Output' Busbars (A-B-C N
terminals) and UPS output busbars (A-B-C N terminals) and tighten the connections to 240lb-in.
(27N-m) (M10 bolt).
9. Connect TB1 from the Liebert BDC to J5 and J12 on the Liebert APM.

NOTICE
Risk of improper wiring connection. Can cause equipment damage.
The control wire must be installed to ensure proper operation of the system and fully protect
the load when switching between bypass cabinet and UPS.
Table 10 Control wiring for Liebert APM UPS to Liebert BDC
From To
Liebert APM UPS Bypass
Module (X2 J5 & J12) Liebert BDC Terminal Strip (TB1)
J12-3 TB1-11
J12-4 TB1-12
J5-1 TB1-3
J5-3 TB1-6
J5-4 TB1-5
Jumper TB1-4 to TB1-5

59 Liebert® APM™
Liebert BDC™

Figure 45 BDC connection to Liebert APM

Output
W91 Neutral

MBB
ØA W04
ØB W05 AC
Utility ØC W06 Output

Kirk MIB
Key K1 W88
W89
W90

Kirk
AC Input Key K2
4 Output
BIB 3 Ground
W07 W85 4 (2)
A
W08 W86 B Fuses
W87 3 Ground
W09 2A
C 1 to Unit Frame
N
PE
3 SKRU
432 3 4
2
1 2 3 4 5 6 7 8 9 10 11 12
K0

Input Neutral Push


Button
See Note 1 To TB1
Main Ground Busbar
AC 120V
Ground Inner Door
SKRU - Solenoid
to Unit Frame
Key Release Unit
1. Customer-furnished electrode conductor to be KO - Key Operator
installed in accordance with national and Field-Supplied Wiring UAM04012
electrical codes. Factory-Supplied Wiring Rev. 4

NOTE
Install jumper on TB1 pins 4 and 5.
For startup procedure, see 10.2 - UPS Startup.

Liebert® APM™ 60
Liebert BDC™

6.6 Bolting Cabinets Together


NOTE
UPS wiring must be completed before the cabinets are bolted together.
1. Line up cabinets so that mounting holes are aligned.

Figure 46 Bolting Liebert APM to a Liebert BDC

Washer
Split, M10
2 3 Washer
Hex Head Flat, M10
Bolt, M10
1

Hardware for bolting units is in a bag attached to


the Liebert BDC. See form included with UPS.
Place cabinets so mounting holes are aligned.
A bolt from the adjacent cabinet may be screwed into the threaded DETAIL A
top hole, or a bolt may be inserted through the lower hole and
screwed into the threaded hole in the adjacent cabinet.
2. Using supplied hardware, bolt the cabinets together. The bolts may be inserted from either the
UPS side or from the Liebert BDC side, whichever is more convenient.

61 Liebert® APM™
Installation Drawings

7.0 INSTALLATION DRAWINGS


The diagrams in this section illustrate the key mechanical and electrical characteristics of the Liebert
APM UPS System cabinets (UPS, Liebert BDC and battery).
Figure 47 UPS dimensions- front view
55.4" (1408mm)
23.8" (604mm)

1. All dimensions are in inches (mm).


2. 24" (610) minimum clearance above unit;
36" (914) front access required for service.
3. Keep cabinet within 15 degrees of vertical.
4.Top and bottom cable entry available through
removable access plates.
Remove, punch to suit conduit size and replace.
5. Unit bottom is structurally adequate for forklift handling.
6. Control wiring and power wiring must be run in
separate conduits.
78.7" 7. Copper cables only are recommended.
(2000mm) 8. All wiring is to be in accordance with national
and local electrical codes.
9. All battery cabinets must be positioned on the
left side of the UPS.
Total Width with Additional Battery Cabinets

Number of Total Width


Battery Cabinets In. (mm)
2 79.1 (2008)
3 102.7 (2608)
4 126.3 (3208)

Battery UPS UAM03000


Cabinet #1
FRONT VIEW Rev. 0

Figure 48 Lineup arrangement, Liebert APM with battery and Liebert BDCs

UAM03001
Rev. 1

Liebert® APM™ 62
Installation Drawings

Figure 49 UPS dimensions continued, center of gravity—side, top and bottom views
23.4"
3"
(595mm)
(77mm)
See Detail A

9.2" Power
(235mm) 28.3" Cable Entry
(719mm) 21.26 x 7.87"
Bracket (540 x 200mm)
Centers
34.3" Vent Screen
Power (871mm) Mechanical
Caster
Cable Entry Stop
8.9"
21.26 x 7.87"
(226mm)
(540 x 200mm)
28.3"
(719mm) 1.4"
TOP VIEW 0.8" BOTTOM VIEW (36mm)
(21mm)
39-1/2" 31.5" (800mm) Detail A
(1000mm) without Side Panels

Vent Screen
Front and Back

Display
Center of Center of
Gravity Gravity
Front Front
78.7"
(2000mm)

Dimension
Y; See Pg. 2

1.56"
(40mm)

Dimension Dimension See


LEFT SIDE VIEW See Pg. 2
X Z Page 2
OVERALL RIGHT SIDE VIEW
31.8"
FRONT VIEW (808mm)

1. All dimensions are in inches (mm).


2. 24" (610) minimum clearance above unit and 12" (305) 8. All wiring is to be in accordance with national and local
rear clearance required for air exhaust and 36" (914) electrical codes.
front access required for service. 9. See page 2 of 5 drawing: UAM02010B for weight table
3. Keep cabinet within 15 degrees of vertical. and centers of gravity for UPS at 208V.
4. Top and bottom cable entry available through removable 10. See page 3 of 5 drawing: UAM02010C for weight table
access plates. Remove, punch to suit conduit size and replace. and centers of gravity for UPS at 480V.
5. Unit bottom is structurally adequate for forklift handling. 11. See page 4 of 5 drawing:UAM02010D for weight table and
6. Control wiring and power wiring must be run in separate centers of gravity for UPS at 600V.
conduits. 12. See page 5 of 5 drawing:UAM02010E for weight table and
7. Only copper cables are recommended. centers of gravity for UPS with internal maintenance bypass.

UAM2010A
Refer to Tables 11 and 13 for Dimensions X, Y and Z in each Liebert APM model. Rev. 2

63 Liebert® APM™
Installation Drawings

Figure 50 Liebert APM with top fan kit

Caster Mechanical
Stop

DETAIL A

23.4"
3" FRONT (595mm)
Top Fan (77mm)
20.7" (526mm) See Detail A
Flange to
Flange
9.2" Power Cable Entry
13.2" 12.1" 28.3"
(235mm) 21.26" x 7.87
(335mm) (308mm) (718mm) (540mm x 200)
Bracket
Centers
Vent Screen
34.3"
(871mm)
Power Cable 8.9"
Entry 21.26" x 7.87" (226mm)
(540x 200mm)

28.3" (719mm)
1.4"
0.8"
TOP VIEW (21mm) BOTTOM VIEW (36mm)

31.5" (800mm) Top


39.5" w/o Side Panels Fan
(1000mm) 07.6"
(194mm)

Vent Screen
Front and Back

Display
Center of Center of
Gravity Gravity

78.7"
(2000mm)

Dim. Y
See Pg. 2
FRONT FRONT

See Pg. 2 Dimension Dimension Z See Pg. 2


LEFT SIDE VIEW X
OVERALL 31.8" RIGHT SIDE VIEW
(808mm)
FRONT VIEW UAM0212A
Notes
1. All dimensions are in inches (mm). Pg. 1, Rev. 1
2. 24" (610) minimum clearance above unit and 36" (914) front access 7. Only copper cables are recommended.
required for service. 8. All wiring is to be in accordance with nationaland local electrical codes.
3. Keep cabinet within 15 degrees of vertical. 9. See Pg. 2 of 5 drawing: UAM02012B for weight table and centers of gravity for UPS at 208 V.
4. Top and bottom cable entry available through removable access plates. 10. See Pg. 3 of 5 drawing: UAM02012C for weight table and centers of gravity for UPS at 480 V.
Remove, punch to suit conduit size and replace. 11. See Pg. 4 of 5 drawing: UAM02012D for weight table and centers of gravity for UPS at 600 V.
5. Unit bottom is structurally adequate for forklift handling. 12. See Pg. 5 of 5 drawing: UAM02012E for weight table and centers of gravity for UPS with internal
6. Control wiring and power wiring must be run in separate conduits. maintenance bypass.

Liebert® APM™ 64
Installation Drawings

Table 11 Center of gravity and weights for Liebert APM 90 kVA frame
Center of Gravity
Weight, lb (kg)
Dimension X Dimension Y Dimension Z
KVA Rating in. (mm) in. (mm) in. (mm) Unit Shipping
No Internal Options
15 16.65 (423) 37.64 (956) 18.78 (477) 796 (362) 896 (407)
30 16.18 (411) 38.66 (982) 18.54 (471) 872 (396) 972 (442)
45 15.79 (401) 39.88 (1013) 18.35 (466) 948 (431) 1048 (476)
60 15.47 (393) 41.30 (1049) 18.15 (461) 1024 (465) 1124 (511)
75 15.16 (385) 42.87 (1089) 17.99 (457) 1100 (500) 1200 (545)
90 14.88 (378) 44.57 (1132) 17.83 (453) 1176 (535) 1276 (580)
480V Internal Transformer
15 13.78 (350) 29.72 (755) 20.43 (519) 1728 (785) 1828 (831)
30 13.66 (347) 30.94 (786) 20.67 (525) 1804 (820) 1904 (865)
45 13.43 (341) 32.32 (821) 20.87 (530) 1880 (855) 1980 (900)
60 13.23 (336) 33.43 (849) 21.06 (535) 1956 (889) 2056 (934)
75 13.15 (334) 34.96 (888) 21.26 (540) 2032 (924) 2132 (969)
90 13.03 (331) 36.26 (921) 21.50 (546) 2108 (958) 2208 (1004)
600V Internal Transformer
15 14.37 (365) 32.40 (823) 19.80 (503) 1743 (792) 1843 (838)
30 14.25 (362) 33.70 (856) 19.96 (507) 1819 (827) 1919 (872)
45 14.02(356) 35.16 (893) 20.16 (512) 1895 (861) 1995 (907)
60 13.86 (352) 36.73 (933) 20.35 (517) 1971 (896) 2071 (941)
75 13.70 (348) 38.43 (976) 20.59 (523) 2047 (930) 2147 (976)
90 13.50 (343) 40.20 (1021) 20.91 (531) 2123 (965) 2223 (1010)
Internal Maintenance Bypass
15 16.02 (407) 43.94 (1116) 21.89 (556) 985 (448) 1085 (493)
30 15.55 (395) 44.96 (1142) 22.13 (562) 1061 (482) 1161 (528)
45 15.16 (385) 46.22 (1174) 22.32 (567) 1137 (517) 1237 (562)
60 14.80 (376) 47.64 (1210) 22.52 (572) 1213 (551) 1313 (597)
75 14.57 (370) 49.21 (1250) 22.68 (576) 1289 (586) 1389 (631)
90 14.33 (364) 50.91 (1293) 22.80 (579) 1365 (620) 1465 (666)

65 Liebert® APM™
Installation Drawings

Table 12 Center of gravity and weights for Liebert APM 90 kVA frame with top fan option
Center of Gravity
Weight, lb (kg)
Dimension X Dimension Y Dimension Z
KVA Rating in. (mm) in. (mm) in. (mm) Unit Shipping
Top Fan Option Only
15 17.99 (457) 37.83 (961) 18.70 (475) 827 (376) 927 (421)
30 16.34 (415) 38.90 (988) 18.43 (468) 903 (410) 1003 (456)
45 15.94 (405) 40.08 (1018) 18.23 (463) 979 (445) 1097 (498)
60 15.63 (397) 41.54 (1055) 18.03 (458) 1055 (480) 1155 (525)
75 15.31 (389) 43.11 (1095) 17.91 (455) 1131 (514) 1231 (560)
90 15.04 (382) 44.72 (1136) 17.72 (450) 1027 (549) 1127 (512)
480V Internal Transformer
15 13.94 (354) 29.92 (760) 20.31(516) 1759 (800) 1859 (845)
30 13.82 (351) 31.14(791) 20.55 (522) 1835 (834) 1935 (880)
45 13.58 (345) 32.52 (826) 20.79 (528) 1911 (869) 2011 (914)
60 13.39 (340) 33.66 (855) 20.94 (532) 1987 (903) 2087 (949)
75 13.27 (337) 35.16 (893) 21.14 (537) 2063 (938) 2163 (983)
90 13. 19(335) 36.46 (926) 21.38(543) 2139 (972) 2239 (1018)
600V Internal Transformer
15 14.53 (369) 32.60 (828) 19.69 (500) 1774 (806) 1874 (852)
30 14.41 (366) 33.86 (860) 19.84 (504) 1850 (841) 1950 (887)
45 14.17 (360) 35.35 (898) 20.04 (509) 1926 (875) 2026 (921)
60 14.02 (356) 36.93 (938) 20.24 (514) 2002 (910) 2102 (955)
75 13.86 (352) 38.58 (980) 20.47 (520) 2078 (945) 2178 (990)
90 13.58 (345) 40.39 (1026) 20.79 (528) 2154 (979) 2254 (1025)
Internal Maintenance Bypass
15 16.18 (411) 44.13 (1121) 21.77 (553) 1016 (462) 1116 (507)
30 15.67 (398) 45.20 (1148) 21.97 (558) 1092 (496) 1192 (542)
45 15.31 (389) 46.38 (1178) 22.20 (564) 1168 (531) 1268 (576)
60 14.96 (380) 47.83 (1215) 22.36 (568) 1244 (565) 1344 (611)
75 14.72 (374) 49.41 (1255) 22.56 (573) 1320 (600) 1420 (645)
90 14.49 (368) 51.02 (1296) 22.64 (575) 1396 (635) 1496 (680)

Liebert® APM™ 66
Installation Drawings

Table 13 Center of gravity and weights for Liebert APM 45 kVA frame
Center of Gravity Weight, lb (kg)
Dimension X Dimension Y Dimension Z
kVA Rating in. (mm) in. (mm) in. (mm) Unit Shipping
12HX100 Batteries
15 14.29 (363) 31.50 (800) 21.30 (541) 1922 (874) 2022 (919)
30 13.94 (354) 33.46 (850) 21.59 (548.4) 1998 (908) 2098 (954)
45 13.62 (346) 35.04 (890) 21.73 (552) 2074 (943) 2174 (988)
12HX150 Batteries
15 14.25 (362) 30.91 (785) 21.54 (547) 2114 (961) 2214 (1006)
30 13.78 (350) 32.87 (835) 21.81 (554) 2190 (995) 2290 (1041)
45 13.39 (340) 34.72 (882) 22.05 (560) 2260 (1030) 2360 (1073)

Table 14 Center of gravity and weights for Liebert APM 45 kVA frame with top fan option
Center of Gravity Weight, lb (kg)
Dimension X Dimension Y Dimension Z
kVA Rating in. (mm) in. (mm) in. (mm) Unit Shipping
12HX100 Batteries
15 14.45 (367) 31.69 (805) 21.18 (538) 1953 (888) 2053 (933)
30 14.09 (358) 33.66 (855) 22.83 (580) 2029 (922) 2129 (968)
45 13.78 (350) 35.24 (895) 21.61 (549) 2105 (957) 2205 (1002)
12HX150 Batteries
15 14.41 (366) 31.10 (790) 21.42 (544) 2145 (975) 2245 (1020)
30 13.94 (354) 33.07 (840) 21.65 (550) 2221 (1010) 2321 (1055)
45 13.58 (345) 34.92 (887) 21.93 (557) 2297 (1044) 2397 (1090)

67 Liebert® APM™
Installation Drawings

Figure 51 UPS main components—typical unit

UAM02000
Rev. 2 Liebert APM 45kVA Frame UAM02000
Rev. 2

Liebert APM 90kVA Frame

Liebert® APM™ 68
Installation Drawings

Figure 52 UPS cable connections—45kVA and 90kVA frames

45kVA frame

90kVA frame

69 Liebert® APM™
Installation Drawings

Figure 53 Battery cabinet connection to UPS

Refer to Table 15
for interconnect
wiring

NOTES
1. Dimensions are in inches [mm].
2. Control wiring and power wiring must be run in separate conduits. UAM02021
3. Emerson recommends using only copper cables. Rev. 3
4. All wiring must be in accordance with national and local electrical codes.

Liebert® APM™ 70
Installation Drawings

Figure 54 Battery cabinet connection to UPS (continued)

600mm
Battery Cabinet

900mm
Battery Cabinet

Table 15 Interconnect wiring for Liebert APM to battery cabinet


Run From To Conductors
A UPS Battery Busbar External Battery Cabinet Busbar Positive, DC Neutral, Negative
UPS Static Bypass Assembly
B Battery Cabinet Terminal Block TB1 Battery Breaker Shunt and Aux Contacts
J4 and J8
See Figure 40 for additional details.
NOTE
Wiring is supplied when the UPS and external battery cabinet are ordered as a system.

71 Liebert® APM™
Installation Drawings

Figure 55 Battery cabinet outline drawing, weights and center of gravity, 600mm cabinet
3.75" (95mm) Cable Entry Area
Outside Panel 8.2" x 8.7" (210 x 220mm)
2 Places
FRONT
Cable Entry Area
2.5" (65mm) 14.6" x 7.6"
Outside Panel (370 x 190mm) 7.9" (200mm)
Outside Frame

13" (300mm)
Outside Frame
34.3"
(872mm)
28.3"
(719mm)
Bracket
Centers
23.7" Cable Entry Area
(602mm) 7.9" x 23.6"
(200 x 600mm)
TOP VIEW
Maximum 5.6"
BOTTOM VIEW
(142mm)
Door Swing - 120°
39.5" (1000mm)
23.6" (600mm) Door Closed
1. All dimensions are in inches (mm). X
2. 24" (610) minimum clearance above unit; Z See
Table
36" (914) front access required for service.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through
removable access plates. Remove, punch Battery
to suit conduit size and replace. and
Tray
5. Control wiring and power wiring must be run
in separate conduits.
6. Only copper cables are recommended. 78.7" Center
7. All wiring is to be in accordance with national (2000mm) of Gravity
and local electrical codes.
See
Table

24" Center Leveling


(609mm) of Gravity RIGHT SIDE VIEW
Feet
FRONT VIEW
Without Covers UAM05010
Rev. 2
Table 16 Battery cabinet, center of gravity and weights
Center of gravity
Battery
X Y Z Weights *
Battery Model in (mm) in (mm) in (mm) lb (kg)
12HX150-FR 300 580 900 1490 (677)
12HX205-FR 300 570 890 1755 (798)
12HX300-FR 290 550 870 2213 (1006)
12HX330-FR 280 550 860 2477 (1126)
* For shipping weight, add 100 lb. (45 kg).
Source: UAM05010, Rev. 2

Liebert® APM™ 72
Installation Drawings

Figure 56 Battery cabinet outline drawing, weights and center of gravity 900mm cabinet

4" (101mm)
Outside Panel

Cable Entry Area


14.6" x 7.6" 17.1" (434mm)
(370 x 190mm) Outside Panel
FRONT 7.5" (190mm)
Outside Frame

Cable Entry Area


8.2" x 8.7"
12.6" (320mm)
(210 x 220mm)
14.1" Outside Frame
2 Places
(359mm)
Bracket Centers
34.3"
(782mm) Cable Entry Area
14.1"
7.9" x 23.6"
(359mm)
(200 x 600mm)
20" 18.2" Bracket
(507mm) (464mm) Centers

TOP VIEW 5.5" BOTTOM VIEW


Maximum Door Swing - 120° (140mm)

Center of Gravity, In. (mm) 35.8" (908mm)


X 39.5" (1003mm)
Battery Type X Y Z Door Closed
12HX400-FR 17.3 (440) 35 (890) 20 (510) Z
12HX505-FR 17.3 (440) 33 (840) 20.9 (530)
12HX540-FR 17.3 (440) 33 (840) 20.9 (530)

Approximate Weights *
Battery Type Weight, Lb. (kg) Battery
12HX400-FR 2693 (1224) and
Tray
12HX505-FR 3245 (1475
12HX540-FR 3345 (1520) 78.8" Center
(2000mm) of Gravity
* For shipping weights, add 100 lb. (45 kg)
1. All dimensions are in inches (mm).
2. 24" (610) minimum clearance above
unit; 36" (914) front access required
for service.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through
removable access plates.
Remove, punch to suit conduit size and replace.
5. Control wiring and power wiring must be run in 35.2" (895mm)
Center
of Gravity
separate conduits.
6. Only copper cables are recommended. FRONT VIEW RIGHT SIDE VIEW Leveling
Without Covers Feet
7. All wiring is to be in accordance with national
and local electrical codes. UAM05012
Rev. 1

73 Liebert® APM™
Installation Drawings

Figure 57 Outline drawing, Liebert BDC for Liebert APM, 15-45kVA


11.5"
(292mm) Cable Entry Area 23.6"
Outside 6.2" x 13.2" (600mm) 39.5" (1000mm)
Panel (57 x 335mm) X Z
Cable Entry
Area
Cable Entry Area
11.4" x 13.2"
6.5" 11.4" x 13.2"
(290 x 335mm)
(164mm) (290 x 335mm)
Outside
Panel Cable Entry
Area
34.6" 6.2" x 13.2"
(870mm) (57 x 335mm)
28.3"
(719mm)
78.7"
Bracket
(200mm)
Centers 6.5"
(164mm)
Outside Panel
23.7"
Center
(602mm)
of Gravity
5.5" 6.4"
TOP VIEW (140mm) (162mm)
Outside Panel Y
Maximum
BOTTOM VIEW
Door Swing - 120°
1. All dimensions are in inches (mm).
2. 24" (610) minimum clearance above unit;
36" (914) front access required for service.
3. Keep cabinet within 15 degrees of vertical. 24"
4. Top and bottom cable entry available through (609mm) Leveling
removable access plates. Remove, punch FRONT VIEW Feet RIGHT SIDE VIEW
to suit conduit size and replace. Dimension, in. (mm)
5. Control wiring and power wiring must be run Liebert BDC Weight,*
with Distribution Type X Y Z lb (kg)
in separate conduits.
6. Only copper cables are recommended. 39.4"
Without Panelboard 11.8" (300) 14.9" (379) 525 (239)
7. All wiring is to be in accordance with national (1000)
and local electrical codes. UAM06008 39.4"
With Panelboard 11.8" (300) (1000) 14.9" (379) 625 (284)
Rev. 5
* Shipping weight, add 100 lb. (45kg)

Figure 58 Outline drawing, Liebert BDC for Liebert APM, 15-90kVA


11.5"
(292mm) Cable Entry 23.6" (600mm)
Outside Area 39.5" (1000mm)
X
Panel 6.2" x 13.2"
Z
(57 x 335mm)

6.5" Cable Entry Area


11.4" x 13.2" Cable Entry
(164mm)
(290 x 335mm) Area
Outside
11.4" x 13.2"
Panel
(290 x 335mm)

Cable Entry Area


6.2" x 13.2"
34.6" (57 x 335mm)
(870mm)
28.3" 78.7"
(719mm) (200mm)
Bracket
Centers 6.5"
23.7" TOP VIEW (164mm)
Outside Panel Center
(602mm)
Maximum of Gravity
Door Swing - 120°
5.5" 6.4" Y
(140mm) (162mm)
BOTTOM VIEW Outside Panel

1. All dimensions are in inches (mm).


2. 24" (610) minimum clearance above unit;
36" (914) front access required for service.
24" Leveling
3. Keep cabinet within 15 degrees of vertical. (609mm) Feet RIGHT SIDE VIEW
4. Top and bottom cable entry available through FRONT VIEW
removable access plates. Remove, punch
to suit conduit size and replace.
5. Control wiring and power wiring must be run Dimension, in. (mm)
in separate conduits. Liebert BDC
6. Only copper cables are recommended. with Distribution Type X Y Z Weight,* lb (kg)
7. All wiring is to be in accordance with national No Distribution 11.8" (300) 39.4" (1000) 14.9" (379) 550 (250)
and local electrical codes. With 2-225A Subfeed Breakers 11.8" (300) 39.4" (1000) 14.9" (379) 660 (300)
UAM06010 With 400A Panelboard 11.8" (300) 39.4" (1000) 14.9" (379) 660 (300)
Rev. 5 * Shipping weight, add 100 lb. (45kg)

Liebert® APM™ 74
Installation Drawings

Figure 59 Liebert BDC connection to UPS

37.5" (953mm)

Links for Main


to Bypass
(Single Input Only)

2.2" (56mm)
Typ. 6 Places Main Input
Busbars

Bypass
Busbars

1.97" (50mm) Ground


Typ. 3 See Detail C
Places
See
Detail B
Output
Busbars

DC Busbars
2.36" See Detail D
(60mm)
Typ. 2
RIGHT SIDE Places UAM02021
(Panel Removed) DETAIL B Rev. 3
23.6" (600mm)

Input
Breaker
LDB

Input
Ground
Bus
System Input
78.7" Busbar
(2000mm) Located at
Rear, Typ.
MBB MIB

BIB
System Input
Connections

Neutral Input
System Connections
Input
Bus
See Detail A and
Isometric View
UAM06020A Detail B, Page 2 DETAIL B
FRONT Iso View, Front Left UAM06020B
Rev. 0 (See Note 6)
(Door Removed) Corner Post Removed Rev. 0

NOTES
1. All Emerson-supplied cable must be repositioned prior to and while the cabinets are being placed
in their final installed location.
2. All interconnection hardware supplied by Emerson.
3. AC connections must be made to the UPS module before attaching Liebert BDC to UPS module.
4. All cabling will be field-supplied when a Liebert BDC is configured as a stand-alone cabinet.
5. Liebert BDCs must attach to the right side only of the Liebert APM.
6. Refer to the individual drawing of each piece of equipment for additional details.

75 Liebert® APM™
Installation Drawings

Table 17 Interconnect wiring for Liebert APM to Liebert BDC


Run From To Conductors
A Utility AC source BDC System Input Bus Phase A, B, C
B Utility AC Source BDC System Input Bus Neutral
C BDC Bypass Isolation Breaker UPS Main Input Phase A, B, C
D BDC Bypass Isolation Breaker UPS Main Input Neutral
E UPS Output MBC Maintenance Isolation Breaker Phase A, B, C
F UPS Output MBC Maintenance Isolation Breaker Neutral
G BDC Panelboard Load AC Connection Phase A, B, C
H BDC Panelboard Load AC Connection Neutral
I Utility AC Source All Ground Connections Ground
J BDC Terminal Block TB1 UPS Static Bypass Module J5 and J12 Wiring for KO on MBC
See Figure 45 and Table 10 for additional details.
NOTE
Wiring is supplied when the UPS and Liebert BDC are ordered as a system.
Table 18 Spring washer torque application
Hardware Two Belleville Washers
M10 (3/8") 240 lb-in. (27 N-m)

Figure 60 Acceptable hardware configuration for torque application

Liebert® APM™ 76
Rear Base 4.3" 4.3"
Bracket 17.7" (450mm) (110mm)
6.9" (110mm) 6.5" 9.8" 6.9" 6.5" 3.5"
See Detail A 9.8" 6.9" 4.3" 6.5" (165mm)
(175mm) (165mm) (250mm) (175mm) (89mm)
2.7" (250mm) (175mm) (110mm) (165mm)
(69mm)

(REAR)

Cabinet
BYPASS Rear Door
BATTERY UPS DISTRIBUTION
CABINET 15-90KVA CABINET

Rear
Rear Anchor Wall
39.2" Hardware
(997mm) .5
(Not Supplied)
(13mm)

Rear Cabinet FLOOR Rear Cabinet


Floor Bracket Base Bracket
.75
Detail A
Figure 61 Seismic mounting bracket details

(19mm)
Minimum
(FRONT)
Cabinet
Front Door
Front Cabinet

77
3.7" 5.5" 5.5" 5.5" 11.0" 5.5" 5.5" 5.5" 11.0" 5.5" 5.5" 5.5" 3.7"
(94mm) (140mm) (140mm) (140mm) (280mm) (140mm) (140mm) (140mm) (280mm) (140mm) (140mm) (140mm) (94mm) Base Bracket
16.5" (420mm) Front Cabinet
SLOT 16mm Base Bracket Anchor
RAD 7mm, Typical (See Detail B)
SEISMIC ANCHORING
Bottom Of Units
(Viewed From Top Looking Down)
NOTES FLOOR

1. Recommended floor anchor: 1/2" ITW ramset/red head 5. Move cabinet into position with rear tabs into slots of
self-drilling anchor, ICBO #ER-1372 or equivalent (not floor bracket. Tabs to extend at least 1/2" through floor Detail B
supplied). Follow manufacturer’s instructions. bracket (Detail A). Then attach front floor brackets to front
2. Position rear floor brackets on floor at least .75" cabinet base bracket but do not fully tighten hardware.
from rear wall. Mark location and drill holes (Detail A) 6. Mark hole locations and remove brackets. Drill and install
to a minimum depth of 4.12" (104.6mm) into the concrete. floor brackets. Unit door can be removed for better access.
3. Install rear cabinet base bracket (Detail A) to existing Reinstall front floor brackets to front cabinet brackets with
holes on underside of unit with tabs facing rear wall. supplied hardware and torque to 235 lb-in (26.5 Nm).
Use supplied hardware and torque to 365 lb-inch (41.2 Nm). 7. After all cabinets are moved into place and secured to the
Loosen leveling bolt locking nut and tighten after floor, multiple cabinet configurations are then bolted together.
bracket is secured. 8. If side walls are present, 1.0" (25.4mm) minimum distance from either
4. Install front cabinet base bracket (Detail B) to existing side wall is required.
holes on underside of unit with bent flange facing front. UAM08020
Use supplied hardware and torque to 365 lb-inch (41.2 Nm). Rev. 2
Loosen leveling bolt locking nut and tighten after
bracket is secured.

Liebert® APM™
Installation Drawings
Liebert IntelliSlot® Installation

8.0 LIEBERT INTELLISLOT® INSTALLATION

8.1 Liebert IntelliSlot Communication


The Liebert APM has three Liebert IntelliSlot ports to allow installation of optional communication
cards. Liebert IntelliSlot cards communicate via Liebert’s proprietary Velocity protocol to cards that
translate the information into such protocols as SNMP and Modbus. Other cards provide dry contact
signals for external signaling of operating status.
The Liebert IntelliSlot communication ports may be installed or removed while the Liebert APM is
operating.

8.2 Liebert IntelliSlot Web Card—SNMP/HTTP Network Interface Card


This network interface card provides all real-time data and status information as SNMPv1 traps for
connection to a 10/100-baseT Ethernet connection. The same card also will transmit the same status
information and all measured parameters for display via a Web browser. The Liebert IntelliSlot bays
are on the right side of the control module and labeled as IntelliSlot1, IntelliSlot2 and IntelliSlot3.
Table 19 Liebert APM communication options
Port Type and Labeled ID Monitoring
Location Name of Port Devices Supported
IS-MultiPort
Left Liebert
IntelliSlot 1 IS-Relay
IntelliSlot
IS-485EXI
IS-MultiPort
IS-Relay
Center Liebert
IntelliSlot 2 IS-Unity-DP
IntelliSlot
IS-Unity-LIFE
IS-485EXI
IS-MultiPort
IS-Relay
Right Liebert
IntelliSlot 3 IS-Unity-DP
IntelliSlot
IS-Unity-LIFE
IS-485EXI

Liebert® APM™ 78
Liebert IntelliSlot® Installation

8.2.1 Liebert IntelliSlot® Unity Cards—IS-UNITY-LIFE, IS-UNITY-S, IS-UNITY-DP


• IS-UNITY-LIFE (Included): Offers a web interface to manage and configure the Emerson
Life.net and Emerson proprietary protocols for use with the Emerson Life Station™, Liebert
Nform® and Emerson® Trellis™.
• IS-UNITY-DP: Offers a web interface to monitor and configure the Life.net and Emerson
Network Power proprietary protocols for use with the Emerson Life Station, Liebert Nform and
Emerson Trellis. It allows selection and configuration of two of the available third-party
protocols—SNMP, Modbus or BACnet—for operation with building management systems.
• Liebert IntelliSlot® Dry Contact Card (IS-RELAY): Provides dry contact alarm information,
including: On Battery, On Bypass, Low Battery, Summary Alarm, UPS Fault and On UPS signals
for communication to a remote monitoring system or for use with Liebert MultiLink® software.
• Liebert IntelliSlot MultiPort Card (IS-MULTIPORT) Provides dry contact alarm
information, including: On Battery, Low Battery signals for communication to four servers for use
with Liebert MultiLink software.
• IS-485EXI: The Liebert IntelliSlot 485 EXI Card provides connection to a Liebert SiteLink-E™
allowing Liebert SiteScan® Web 4.0 monitoring and control of your Liebert equipment.

8.3 Liebert IntelliSlot Card Web Interface


The IS-Unity-Life and IS-Unity-DP IntelliSlot cards offer a Web interface, yielding a wide variety of
status and summary information through an Ethernet connection. Liebert’s IS-Unity-DP also
provides e-mail and text notification.

Figure 62 Liebert IntelliSlot Web card display

79 Liebert® APM™
Liebert IntelliSlot® Installation

8.4 Liebert IntelliSlot® Relay Card


The Liebert IntelliSlot Relay card (IS-RELAY) provides voltage-free contact closures for remote
monitoring of alarm conditions.
Delivering On Battery, On Bypass, Low Battery, Summary Alarm, UPS Fault and On UPS
signals, the easy-to-install card integrates with AS/400 computers (additional cable required) and
other relay contact monitoring systems.
The relay card is rated for 24 VAC/DC at 1A. and supported in any of the three Liebert IntelliSlot
bays on the Liebert APM.

8.4.1 Liebert IntelliSlot Relay Card Pin Configuration


The card has two terminals blocks, TB1 (green, numbered 1-9) and TB2 (black, 10-18), as shown in
Figure 63.
Figure 63 Pin location and numbering

9 18

TB1 TB2
green black

1 10

Refer to your Liebert product user manual for the pin configuration for the terminal blocks.
Table 20 Relay card pin configuration
Pin Function Operation
1 Common - Low Battery
2 Low Battery Closed if Low Battery point occurs.
3 Low Battery Closed if battery is OK
4 Common - UPS Fault
5 UPS Fault Closed if UPS fault occurs
6 UPS Fault Closed if no UPS failure
7 Common - On Battery
8 On Battery Closed if On Battery power (Utility failure)
9 On Battery Closed if not On Battery power (Utility OK)
10 Not Used
11 Not Used
12 Not Used
13 Summary Alarm* Closed if no alarm conditions are present
14 Summary Alarm* Closed if Summary Alarm occurs
15 Common - Summary Alarm*
16 On UPS Closed if On UPS (inverter) power
17 On Bypass Closed if On Bypass
18 Common - On Bypass

Liebert® APM™ 80
Liebert IntelliSlot® Installation

8.4.2 Liebert IntelliSlot® Relay Card Jumper Setup


The Liebert IntelliSlot Relay Card has five jumpers, P3 through P7, as shown in Figure 64. Each
jumper connects two pins.
Figure 64 Jumper location and numbering

Front
of
Card
Jumper
P6

Jumper
P5

Jumper
P4

Jumper
P3

Jumper
P7

By default all five jumpers have shunts installed. The two pins are shunted together to provide the
functions shown in Table 21, allowing relay commons to be tied together.
The jumpers should be removed if there is any external voltage source that may intentionally or
inadvertently be connected to the relay.
Removing the shunt from any two pins breaks the connection between the relay commons so they are
not tied together.
Table 21 Jumper connections
Jumper Relay
P6 On Battery
P5 UPS Fault
P4 Low Battery
P3 On Bypass
P7 Summary Alarm

NOTE
Refer to the Liebert IntelliSlot Relay Card manual, SL-23211 for additional details. the
document is available at the Liebert Web site, www.liebert.com

81 Liebert® APM™
Liebert IntelliSlot® Installation

8.5 Liebert IntelliSlot™ MultiPort Card


The Liebert IntelliSlot MultiPort card provides four sets of voltage-free contact closures for remote
monitoring of alarm conditions UPS operation On Battery and battery low condition. A typical
application is to allow a maximum of four computer systems to simultaneously monitor the status
(e.g., utility power failure-low battery) of a single UPS.
This card is supported in any of the three Liebert IntelliSlot bays on the Liebert APM.

Figure 65 Liebert IntelliSlot MultiPort card pin assignment

UPS IS-MULTIPORT Pin Description


Liebert 1 Low Battery
MultiLink 2 Utility Fail
computers
3 NOT USED
4 NOT USED
5 NOT USED
AS/400 6 NOT USED
system 7 Low Battery Common
units
8 Utility Fail Common

8.6 Alber® BDSi™ Battery Monitoring System—Optional


The matching Liebert battery cabinets allow installing an optional Alber BDSi battery monitoring
system inside the cabinet. The Alber BDSi by Emerson continuously checks all critical battery
parameters, such as cell voltage, overall string voltage, current and temperature. Automatic periodic
tests of internal resistance of each battery will verify the battery's operating integrity. Additional
capabilities include automatic internal DC resistance tests and trend analysis providing the ability to
analyze performance and aid in troubleshooting.
The Alber BDSi system is installed inside the battery cabinet as shown in Figures 11 and 12. The
monitoring system power inlet is wired to the Alber BDSi Fuse Block on the UPS (see ,Figures 13
and 66). The Alber BDSI fuse block supplies 120VAC and has an 8A fuse.
If required, power can be supplied from the output terminals of the UPS, a distribution panel or
another UPS-protected source.
For details about operating the Alber system, refer to the Alber unit’s documentation, available at
http://www.alber.com/

Liebert® APM™ 82
Liebert IntelliSlot® Installation

Figure 66 Alber BDSi controller and input connection

Rear Panel

120VAC 50/60Hz

! INPUT
XXXXXXXXXXXXXAXA
XXXXXXXXXXXA
OUTPUT
POWER X
XXXXXXA

Input

83 Liebert® APM™
Liebert IntelliSlot® Installation

8.7 Battery Temperature Compensation


For a UPS with external batteries, an optional battery temperature interface optimizes the external
battery management by connecting up to four external temperature sensors from the battery cabinets
to a control unit inside the UPS.

Figure 67 Multi-temperature sensors

Temperature
Sensor

+ NC X103
IN 12V
- OUT
GND
TMP-2

Temperature
Sensor

+ NC X104
IN 12V
- OUT
GND
TMP-2 Monitor
Board
– X2
X108
Temperature 12V +12V
Sensor OUT BAT_OUT
GND GND
J4 Static
NC X105 Bypass
+
12V Module
IN OUT
- GND
TMP-2

BCB Control
Temperature Board
Sensor

NC X106
+
IN 12V
OUT
- GND
TMP-2

Liebert® APM™ 84
Operator Control and Display Panel

9.0 OPERATOR CONTROL AND DISPLAY PANEL


9.1 Operator Control Panel
The control panel and LCD on the front of the Liebert APM lets the operator:
• Turn the UPS On or Off.
• Transfer into the various operating modes.
• Silence alarms.
• Check the status of the UPS and its batteries, including all measured parameters, events and
alarms.
The main areas of the control panel are shown below in Figure 68 and explained in Table 22.
• Mimic Display - view the status of the Liebert APM in single-line diagram format—indicators
show status by changing color when ON, flashing or OFF
• Liquid Crystal Display (LCD) and Navigation keys - view status and operational data from
the Liebert APM in tabular format
• Control buttons - turn the Liebert APM on or off, silence alarms
Figure 68 Overview of control panel

E ME R S O N TM

Network Power 8

Mimic 3
1 4 5 Control
current EPO

buttons
path 2 INV E RTE R OFF FAULT CLE AR

6
STATUS S ILE NCE ON/ OFF

7 F1 F2 F3 F4 HELP INV E RTE R ON

LCD and Menu Buttons

Table 22 Descriptions of UPS operator control and display panel


Mimic Current Path Control Buttons
Item # Function Button Function
1 Rectifier indicator (AC to DC) EPO EPO switch
2 Battery indicator (backup DC power) INVERTER ON Inverter start button
3 Bypass input indicator INVERTER OFF Inverter shutdown button
4 Inverter indicator (DC to AC) FAULT CLEAR Fault reset button
5 Load indicator (AC output) SILENCE ON/OFF Alarm mute button
6 UPS status and alarm indicator Menu Buttons
7 Audible alarm (buzzer) Button Function
8 Protective cover for EPO button F1 through F4 and HELP LCD menu keys

NOTE
Help button menus are not active. Future units will ship with an F5 legend in place of the
HELP legend.

85 Liebert® APM™
Operator Control and Display Panel

9.2 Mimic Display Indicators


Figure 69 Mimic display indicators location

E ME R S O N TM 3
Network Power
Mimic indicators
1. Rectifier indicator 4
2. Battery indicator 5
3. Bypass indicator
4. Inverter indicator
2
5. Load indicator
6. Status indicator 6
STATUS

Mimic indicators show the operational status of the Liebert APM by their color—green, amber or
red—and whether they are ON (solid), flashing or OFF. Table 23 provides a guide to interpreting the
various states of the indicators.
Table 23 Mimic display status indicators
Indicator
(see Figure 69) Green Flashing Green / Amber Red Off
Flashing Green: Utility normal, Rectifier is normal, but utility
1. Rectifier Load on Rectifier Rectifier fault
but rectifier not operating is abnormal
Battery and converter are
Battery Powering Flashing Green: Battery Battery or battery
2. Battery normal, and battery is not
the Load pre-warning (low battery) converter abnormal*
discharging
Load on Bypass Bypass out of
3. Bypass — Bypass Normal
Power normal range
Inverter Powering Flashing Green: Inverter on
4. Inverter Inverter fault Inverter normal but Off
the Load Normally standby
5. Load UPS output On — UPS output overloaded UPS has no output power
No Alarms—UPS Amber: UPS has a general
6. Status UPS has a serious alarm —
Working Normally alarm
* Battery or battery converter abnormal events include these event messages (see Table 57): No Battery, Battery Replaced, Battery
Reverse, Batt. Conv. Over. Curr., Batt. Converter Fault, Batt. Converter Overtemp.

Liebert® APM™ 86
Operator Control and Display Panel

9.3 Control Buttons


The Control Buttons on the front panel may be used to shut down the UPS completely, turn the
inverter on or off, restart the UPS after a fault and silence the alarm, as shown in Figure 70. The
function of each button is described in Table 24.
NOTE
To activate a button properly, press and hold until you hear a short beep—about two seconds.
Figure 70 Control button layout

EPO Button Cover

EPO Button
E MER SO N
Network Power
TM
Inverter Off Button

EPO

Fault Clear Button


INV E RTE R OFF FAULT CLE AR

Silence On/Off Button


STATUS S ILE NCE ON/ OFF

F1 F2 F3 F4 HELP INV E RTE R ON

Inverter On Button

LCD Navigation Keys


Table 24 Control buttons
Button
(see Figure 70) Function
Completely shuts down the UPS, including the static switch.
EPO CAUTION: Use caution before pressing the Emergency Power Off (EPO) button. This button
completely shuts down the unit and the critical load.
Press this button to start the inverter and transfer from static bypass to inverter.
INVERTER ON
NOTE: If the inverter is not ready, this will not activate the UPS.
Press this button to shut down the inverter during operation. The load will be transferred to
INVERTER OFF
static bypass.
After the UPS shuts down due to a fault and the alarm condition has been resolved, press this
FAULT CLEAR
button to clear the fault and restart the UPS.
Press this button once to silence the alarm buzzer when an alarm is active. Any new fault will
SILENCE ON/OFF sound the buzzer again.
If the alarm buzzer is not beeping, press this button to test the alarm sound.

9.4 Alarm Buzzer


The alarm buzzer produces three types of sounds:
• Single beep—When any Control button is pressed
• Single beep repeating every two seconds—The system has a general alarm
• Continuous—The system has a serious fault
If the alarm buzzer makes no sound, the system may be operating properly or the alarm may have
been silenced manually.
Figure 71 Alarm buzzer location

E ME R S O N TM

Network Power

EPO

INV E RTE R OFF FAULT CLE AR

STATUS S ILE NCE ON/ OFF

F1 F2 F3 F4 HELP INV E RTE R ON

Buzzer

87 Liebert® APM™
Operator Control and Display Panel

9.5 LCD Overview


The LCD on the front panel has five main sections, as shown in Figure 72. Press the F1 key below
the LCD to scroll through these sections.
• UPS system information - view UPS name and model, date and time, overall status.
• LCD Menu - choose a category of data items to appear below the menus (see Table 26).
• Data and settings - view data items for the selected menu (see Table 26).
• Current status messages - check the most recent UPS event and alarm messages (see
Table 57).
• Navigation key icons - look at the icon above each navigation key to determine how the key
operates when pressed (see 9.6 - Navigation Keys).
The LCD displays alarm information in real time. After appearing in the current status section of the
LCD, status messages are stored in the history log—512 records can be stored and retrieved.
Figure 72 Sections of the LCD
UPS System Information Time Alarms

Single APM 090 kVA 02:17:47 E-Mail


Notification
L1-N/L2 L2- N/L3 L3-N/L1 Icon

L-N voltage (V) 121.4 122.7 121.7


Current status
L-N current (A) 12.2 14.2 13.5
Frequency (Hz) 59.96 59.96 59.96
L-L voltage (V) 211.3 211.6 210.5
Power factor 0.00 0.00 0.00
Current menu Mains
Menu icons

Return to Output
Menu Move to
Next Menu
F1 F2 F3 F4 HELP

Liebert® APM™ 88
Operator Control and Display Panel

9.6 Navigation Keys


The navigation keys on the front panel—F1 through F4 and Help—are used to access the LCD to view
the current status and other information about the Liebert APM.
Navigation key icons on the LCD appear above each key to indicate its operation (see Table 25). The
keys are “soft keys” that can change functions according to the icon.
• Use F1 to move to the home portion of the LCD.
• Use F3 and F4 as cursor keys to move left and right or up and down, depending on the icons
displayed above the keys.
• Use F3 and F4 on the display simultaneously to view individual Module information such as
Input and Output conditions and individual Module Firmware versions
• Use F2 as an ESC key.
• Use HELP to access help information on the LCD or to enter a choice.
Table 25 Icons for navigation keys
Key F1 F2 F3 F4 HELP

Functions ESC Left Right Enter


Available

Home
Exit
?
Up Down Help

9.7 LCD Menus and Data Items


The LCD menus provide access to the following categories of information and settings for the UPS.
Selecting a menu changes the information displayed in the UPS data items portion of the LCD. The
menu choices are listed below and described in detail in Table 26.
• Mains - view utility power input data: voltage, current, frequency and power factor
• Bypass - view bypass data: voltage and frequency
• Output - view output data: voltage, current, frequency and power factor
• Load - view load data: load percent, output current, output power and crest factor (CF)
• System - view system data
• Battery - view battery characteristics—voltage, current, temperature, remaining time and
capacity—and messages when the battery is boost/float charging or disconnected
• Events - view the events log—displays all recent events added to the log (new records added at
end)
• Records - access the history log—displays all records in the log (new records added at end)
• Language - select a language for LCD text (choices appear in the native language)
• Settings - configure UPS settings: adjust the display contrast, choose a format for date display,
set the date and time, set up the UPS for modem communications (baud rate, address, mode and
phone numbers to dial for alarm notifications) and change the password
• Command - start or stop a battery maintenance test, battery capacity test or system test
• Run Time - view available backup time for the UPS and bypass
• Version - view firmware versions for the inverter, rectifier and software display board and the
model information for the UPS
Figure 73 shows a menu tree of the options available from the LCD menus.

89 Liebert® APM™
Operator Control and Display Panel

Figure 73 Menu tree

Mains (input) Bypass Output Load System


L-N voltage (V) L-N voltage (V) L-N voltage (V) Sout (kVA) Sout (kVA)
L-N current (A) Frequency (Hz) L-N current (A) Pout (kW) Pout (kW)
Frequency (Hz) L-L voltage (V) Frequency (Hz) Qout (kVAR) Qout (kVAR)
L-L voltage (V) L-L voltage (V) Load level %
Power factor Power factor Crest factor

Battery Events Records Language


Battery voltage (V) (events log) (history log) (Choices for
Battery current (A) display)
Battery temperature (°C)
Remain Time Min.
Battery capacity (%)
Battery boost charging
Battery float charging
Battery disconnected

Settings Command Run Time Version


Display contrast Battery maintenance test UPS Run Time Monitor version
Date format set Battery capacity test Byp Run Time Rectifier version
Date & time System test Inverter version
Comm1 baud rate Stop testing Bypass version
Comm2 baud rate Freshening Charge UPS model
Comm3 baud rate Stop Freshening Charge
Communication address Modem Auto-answer enable
Communication mode Battery Reset
Callback times
Phone No.1
Phone No.2
Phone No.3
Command password
Protocol
ECO Mode
Battery Equalize Charge

9.8 Language Selection


The LCD menus and data display are available in 12 languages (Chinese, Dutch, English, French,
German, Italian, Japanese, Polish, Portuguese, Russian, Spanish and Swedish). To select a different
language:
1. From the main menu, press the F4 (shift) key to move the cursor to the Language menu at the
bottom of the screen.
2. Press HELP to access the language choices.
3. Press F3 and F4 (left and right arrows) as needed to highlight the desired language.
4. Use HELP to select the required language.
5. Return to the main menu by repeatedly pressing F2 (ESC) and F1.
All text on the LCD will now be displayed in the selected language.

Liebert® APM™ 90
Operator Control and Display Panel

Figure 74 Language selection screen

Single APM 090 kVA 02:17:47

ENGLISH DEUTSCH
POLSKI FRANCAIS ITALIANO
ESPANOL NEDERLANDS SVENSKA
PORTUGUES

Language

F1 F2 F3 F4 HELP

9.9 Current Date and Time


To change the system date and time:
1. From the main menu, press the F4 (shift) key to move the cursor to the Settings menu at the
bottom of the screen.
2. Press HELP to select the Settings menu.
3. Use F3 and F4 (up and down) to select the Date & Time option, then press HELP (enter).
4. Use F4 to position the cursor on the row where the date and time are displayed, then press
HELP (enter).
5. Using the F3 (up), enter the current time and date information.
6. Press HELP (enter) to save the settings.
7. Press F2 (ESC), then F1 to return to the main screen.
Figure 75 Date and time screen

Single APM 090 kVA 02:17: 47


D is p la y c o n t r a s t

D a t e f o r ma t s e t Y/ M/ D
D / M/ Y M/ D / Y Y/ M/ D
D a t e & t ime
2 0 1 0-0 7 - 1 5 0 2: 1 7 : 4 5

Settings

F1 F2 F3 F4 HELP

91 Liebert® APM™
Operator Control and Display Panel

9.10 UPS History Log


The Liebert APM displays status changes as they occur and stores that data in the history log, as
shown in Figure 76.
• History Log: When a record moves to the history log, the time the status changed is recorded.
The history log can hold up to 512 records. History log records may be viewed by accessing the
Records menu.
Figure 76 History log records

Single APM 090 kVA 02:17:47

1 Ma in s v o lt . a b n o r ma l
2 0 1 0-0 6 - 0 7 0 9 : 4 8: 1 0
2 0 1 0-0 6 - 0 7 0 9 : 4 8: 1 0
3 Ma in s v o lt . a b n o r ma l
2 0 1 0-0 6 - 0 7 0 9 : 4 8: 1 0
2 0 1 0-0 6 - 0 7 History log
0 9 : 4 8: 1 0 (records menu)
6 Ma in s v o lt . a b n o r ma l
2 0 1 0-0 6 - 0 7 0 9 : 4 8: 1 0
2 0 1 0-0 6 - 0 7 0 9 : 4 8: 1 0
Records

F1 F2 F3 F4 HELP

See Table 57 for a complete list of status messages, along with a description and any recommended
actions.

9.11 Types of LCD Screens


This section provides a quick guide to the main types of LCD screens.

9.11.1 Opening Display


As the UPS begins powering up, the opening display appears, as shown in Figure 77.

Liebert® APM™ 92
Operator Control and Display Panel

Figure 77 Opening display

Single APM 090kVA 0 2 :1 7 : 4 7

EMERSON™
Network Power

Press any key back to main menu

F1 F2 F3 F4 HELP

9.11.2 Default Screen


After the UPS has powered up and completed a self-test, the output screen appears, as shown in
Figure 78. This window is the default screen.
Figure 78 Default screen

Single APM 090 kVA 02:17:47

L1-N/L2 L2- N/L3 L3-N/L1


L-N voltage (V) 118.4 119.2 121.6
L-N current (A) 0.0 0.0 13.5
Frequency (Hz) 59.97 59.97 59.97
L-L voltage (V) 205.7 208.4 207.9
Power factor 0.00 0.00 0.00
Output

F1 F2 F3 F4 HELP

9.11.3 UPS Help Screen


Press the HELP key below the LCD to display the Help window. (Press the HELP key again to exit
the Help window.)

93 Liebert® APM™
Operator Control and Display Panel

9.11.4 Screen Saver Window


If there has been no interaction with the Liebert APM’s LCD for 2 minutes, the screen saver window
appears. It remains on the LCD for 2 minutes, then the screen will go dark. The LCD will become
active again when any key is pressed.
Figure 79 Screen saver window

Single APM 090kVA 0 2 :1 7 : 4 7

EMERSON™
Network Power

Press any key back to main menu

F1 F2 F3 F4 HELP
F1 F2 F3 F4 HELP

9.12 Pop-Up Windows


Pop-up prompt windows appear when the user must confirm a choice or perform an operation. This
section describes the pop-up windows. Some operations require entering a password; refer to 9.12.9 -
Enter Control Password for help.

9.12.1 From Bypass to Inverter Mode With Power Interruption


If the bypass voltage or frequency exceeds the synchronized range and
utility voltage or frequency is normal, the inverter cannot be in Transfer with Interrupt,
synchronization with the bypass, and the output can only transfer to please confirm or cancel
inverter after an interruption of about 15ms when the user presses the
INVERTER ON button. Before transferring, the system will let the
user confirm whether the interruption can be accepted, as shown at right. If the bypass voltage
returns to normal before the user makes confirmation, the UPS will transfer to inverter mode
automatically. At the same time, the prompt window will close.

9.12.2 From Inverter to Bypass Mode With Interruption


If the bypass voltage or frequency exceeds the synchronized range and
the UPS is in inverter mode, the system must let the user confirm and This operation leads to
accept the power interruption danger before pressing the INVERTER output shutdown,
OFF button to shut down the output of the inverter. The user can also Confirm or cancel
cancel the shutdown operation, as shown at right. If the bypass voltage
returns to normal before the user makes the confirmation, the UPS
will transfer to bypass operation mode automatically, and at the same time the prompt window will
disappear soon.

Liebert® APM™ 94
Operator Control and Display Panel

9.12.3 System Self-Test


When a system self-test is completed, a pop-up window reports the
results of the test, as shown at right. System Self-Test finished.
Please check the current
• Press the Help (Enter) key and the pop-up window closes. warnings

9.12.4 Battery Capacity Test Confirmation


When a battery capacity test is started from the Command menu, the
battery will be discharged to low-battery warning level. The Liebert Battery will be depleted,
APM asks for confirmation before the test is started, as shown at right. Confirm or cancel

• To confirm the choice and begin the battery capacity test, press the
Help (Enter) key and the pop-up window disappears.
• To cancel the test, press the F2 (ESC) key. The pop-up window disappears.
NOTE
For a battery capacity test to function properly, the load must be between 20% and 100%.

9.12.5 Battery Self-Test Aborted, Condition Not Met


When a battery capacity test is started from the Command menu and
the battery self-test condition is inadequate, the Liebert APM will not Battery Self-Test aborted,
perform a battery test. User should check whether the battery state is Conditions not met
boost charging and whether the load level is greater than 20 percent.
• Press the Help (Enter) key and the pop-up window closes.

9.12.6 Battery Equalize Charge


Battery equalize charge
The user can Enable or Disable the Battery Equalize Charge of the enabled
batteries. Use the F3 or F4 button to Enable or Disable the Battery
Equalize feature.
Battery equalize charge
• Press the Help (Enter) key and the pop-up window closes.
disabled
9.12.7 Battery Reset
The user can reset the battery statistics to a new battery state. Use the
F3 or F4 button to select Battery Reset
Battery reset
• Press the Help (Enter) key and the pop-up window closes.

9.12.8 Battery Refresh Charge Aborted, Condition Not Met


When a battery refreshening charge is started from the Command
menu and battery refreshening condition fails to meet requirements, Battery Refresh Charge
the Liebert APM will not perform a battery refreshening charge. User aborted,
should check if boost charging condition is not enough, such as (No Conditions not met
battery, charger failed, etc.).
• Press the Help (Enter) key and the pop-up window closes.

9.12.9 Enter Control Password


When a UPS control operation requires a password, the pop-up at
right will be displayed. The password is 12345. Enter Control Password
Use the Right or Left arrow to move the cursor along the password *****
field. Then use the Up and Down arrows to advance until the desired
number is displayed. Enter the password one digit at a time.

95 Liebert® APM™
Operator Control and Display Panel

Table 26 UPS menus and data window items


Menu Type Item Type Explanation
L-N voltage (V) Phase voltage
L-N current (A) Phase current
Mains
Frequency (Hz) Input frequency
(input)
L-L voltage (V) Line-line voltage
Power factor Power factor
L-N voltage (V) Phase voltage
Bypass Frequency (Hz) Bypass frequency
L-L voltage (A) Line-line voltage
L-N voltage (V) Phase voltage
L-N current (A) Phase current
Output Frequency (Hz) Output frequency
L-L voltage (V) Line-line voltage
Power factor Power factor
Sout (kVA) Sout: Apparent power
Pout (kW) Pout: Active power
Load Qout (kVAR) Qout: Reactive power
Loadlevel % The percent of the UPS rating load
Crest factor Output current Crest Factor
Sout (kVA) Sout: Apparent power
Pout (kW) Pout: Active power
System Qout (kVAR) Qout: Reactive power
When configured as a single unit, UPS displays only native load, no system
Single unit
load.
Battery voltage (V) Battery bus voltage
Battery current (A) Battery bus current
Battery temperature (°C) Internal battery temperature °C
Remain Time Min. Battery run time remaining
Battery
Battery boost charging Battery is boost charging
Battery float charging Battery is float charging
Battery equalize charging Battery charge is equalized
Battery disconnected Battery is not connected
Events (event log) Displays recent events
Records (history log) Displays all records in the history log
Language (choices for text displayed) User may select any of 12 languages for LCD text.

Liebert® APM™ 96
Operator Control and Display Panel

Table 26 UPS menus and data window items (continued)


Menu Type Item Type Explanation
Display contrast Adjust the LCD display contrast
Choose the format for date display: YYYY MM DD, DD MM YYYY and MM DD
Date format set
YYYY
Date & time Set the date and time
Comm1 baud rate Communication baud rate setting for Liebert IntelliSlot 1
Comm2 baud rate Communication baud rate setting for Liebert IntelliSlot 2
Comm3 baud rate Communication baud rate setting for Liebert IntelliSlot 3
Communication address This setting is applicable to RS485 communication mode
Communication mode Communication Mode Setting
When Liebert IntelliSlot 1 Communication mode is Modem, this parameter sets
Settings Callback times
the number of times a number is redialed to send an alarm notification.
When Liebert IntelliSlot 1 Communication mode is Modem, this is the first
Phone No.1
phone number to be dialed (to send an alarm notification).
When Liebert IntelliSlot 1 Communication mode is Modem, this is the second
Phone No.2
phone number to be dialed (to send an alarm notification).
When Liebert IntelliSlot 1 Communication mode is Modem, this is the third
Phone No.3
phone number to be dialed (to send an alarm notification).
Command password User can modify the command password.
Protocol System protocol
ECO Mode Configures UPS for ECO mode
Battery Equalize Charge Configures UPS for equalize charge
This test performs a partial discharge of the battery to obtain a rough estimate
Battery maintenance test
of the battery capacity. Load must be between 20% and 80%.
This test performs a full discharge of the battery to obtain a precise measure of
Battery capacity test
the battery capacity. Load must be between 20% and 80%.
This is a self-test of the UPS. When the user activates this function, a pop-up
System test
Command window appears about 5 seconds later to show the results.
(start / stop Manually stops a battery maintenance test, battery capacity test or system
battery & Stop testing
test.
system
tests) Allows a temporary Equalize charge for the batteries. This charge is
Freshening Charge
configurable for 1 to 36 hours.
Stop Freshening Charge Manually stops a Freshening Charge.
Modem Auto-answer
Manually enable the modem's auto-answer function.
enabled
Battery Reset Resets battery statistics
UPS Run Time UPS Run Time
Run Time
Byp Run Time Bypass Run Time
UPS model Provides UPS model information—for example, 208V-60Hz.
Monitor Version Monitor Firmware Version
Version Rectifier Version Rectifier Firmware Version
Inverter Version Inverter Firmware Version
Bypass Version Bypass Firmware Version

97 Liebert® APM™
Operation

10.0 OPERATION
10.1 Liebert APM Operating Modes
The UPS is designed to operate as an on-line, double-conversion, reverse-transfer system in the
following modes:
• Normal Mode
• Battery Mode
• Auto-Restart Mode
• ECO Mode
• Bypass Mode
• Battery Start Mode
• Maintenance Mode (Manual Bypass)
• Sleep Mode
• Paralleling Mode
• Output Voltage Adjustment
• Generator Mode
NOTE
1. The user controls and indicators mentioned in these procedures are identified in 9.0 -
Operator Control and Display Panel.
2. The audible alarm may sound at various points during these procedures. It can be canceled
at any time by pressing the SILENCE ON/OFF push button.
NOTE
This unit refers to some modes and conditions that are set or adjusted using proprietary service
software. To take advantage of all the available features for the Liebert APM, the unit must be
commissioned by an Emerson-authorized engineer.
Normal Mode
Operating in normal mode, the Liebert APM’s rectifier derives power from a utility AC source and
supplies regulated DC power to the inverter, which regenerates precise AC power to supply the
connected equipment. The rectifier also uses the utility source power to charge the batteries.
Battery Mode
When utility AC power fails, the Liebert APM protects the critical load by instantaneously channeling
battery power to the inverter which continues supporting the critical load without interruption. When
utility power returns and is within acceptable limits, the Liebert APM automatically shifts back to
Normal mode, with the rectifier powering the critical load.
Auto-Restart Mode
The battery may become exhausted following an extended AC utility failure. The inverter shuts down
when the battery reaches the End of Discharge voltage (EOD). The UPS may be programmed to "Auto
Recovery after EOD" after a delay time if the AC utility recovers. This mode and any delay time may
be programmed by the commissioning engineer.
Bypass Mode
When the Liebert APM is in bypass mode, the load is directly supported by utility power and is
without battery backup protection.
The Liebert APM’s static transfer switch will shift the load from the inverter to bypass mode without
interruption in AC power if the inverter is synchronous with the bypass and any of the following occurs:
• inverter fails
• inverter overload capacity is exceeded
• inverter is manually turned off by user
NOTE
If the inverter is asynchronous with the bypass, the static switch will transfer the load from the
inverter to the bypass WITH interruption in AC power to the critical load. This interruption
will be less than 15ms (in 50Hz), or less than 13.33ms (in 60Hz). This interruption time may be
altered by modifying the Output transfer interrupt time setting.

Liebert® APM™ 98
Operation

ECO Mode (Single-Module UPS System Only)


When ECO mode is selected, the Liebert APM switches inverter power from the UPS input to the
bypass input to save energy by improving UPS efficiency. In this mode, the bypass is the preferred
source. If the bypass voltage or frequency becomes outside preset limits, the UPS load is transferred
back to the inverter.
Battery Start Mode
The battery start option permits starting the Liebert APM with power supplied only by the batteries
(at charged condition).
Maintenance Mode
For maintenance or repair, the Liebert APM may be operated in maintenance mode. To place the
Liebert APM in maintenance mode, follow the instructions in 10.4 - Switching the UPS from
Normal Operation to Maintenance Bypass.

! WARNING
Risk of arc flash and electric shock. Can cause equipment damage, injury and death
The UPS input and output must be protected with external overcurrent protection devices. In
maintenance mode, the input and output busbars remain energized and present an electric
shock hazard.
Sleep Mode
Sleep mode allows equal run time on all power modules. The modules will put themselves offline for a
programmable period of 0-30 days. As a module goes offline, another module comes online. Each
module will rotate being online and offline.
Sleep Mode must be enabled by an Emerson Customer Engineer. A minimum of three power modules
are required for Sleep Mode to be activated. Once enabled, Sleep Mode requires no further action.
Any Power Modules that are not supporting the load will automatically enter sleep mode. During
sleep mode the system maintains one extra active power module in addition to those supporting the
load. Sleep mode can handle configurations with redundant power modules. When a power module is
in Sleep Mode, both LED indicators will turn Off. During extended periods of Sleep Mode, the
inactive power module is cycled through at regular intervals
Common Battery
Common Battery feature permits two Liebert APM’s to be connected to one battery cabinet. The
UPS’s may be separate systems or may be in a parallel system. LBS cannot be used while common
battery is enabled.
Paralleling Mode
This option is available only on 208V Input Parallel. This mode requires the buyout panelboard
paralleling gear. It can parallel the following:
• two APM’s
• 45kW or 90kW frames in any module capacity
• redundant
• can allow up to 180kW of load capacity
A sharing inductor is required for parallel units.
NOTE
To parallel non-208 input voltages, an upstream transformer must drop the input voltage to
208V before the paralleling gear.
Output Voltage Adjustment
This feature allows a Liebert Customer Engineer to adjust the APM’s output voltage over a range of
-5% to +16% of nominal. The output voltage adjustment can be used to compensate for any drop in
line voltage that may occur when the UPS is a significant distance from the protected load. In
addition, it can be used to optimize the UPS output voltage for loads that operate more efficiently at a
voltage different from the nominal Liebert APM output voltage.

99 Liebert® APM™
Operation

Generator Mode
The Liebert APM UPS can be set up for operation in Generator Mode by an Emerson Network Power
Liebert Services engineer. The setup requires connecting J9 Pin 1 to Pin 4 or connecting J9 Pin 2 to
Pin 4. The software must be configured to reflect the connection points as attached.

10.2 UPS Startup


The Liebert APM must be fully installed and commissioned before startup, and external power
isolators must be closed. Once those general conditions are met, the UPS may be started.

! WARNING
Risk of electrical shock and arc flash. Can cause property damage, injury and death.
During this procedure the output terminals will become live.
If any load equipment is connected to the UPS output terminals, please check with the load
user and ascertain whether it is safe to apply power to the load. If the load is not ready to
receive power, then ensure that it is safely isolated from the UPS output terminals.

10.2.1 Startup Procedure


To start the UPS from a fully powered-down condition:
1. Open the external power switch.
2. Open the UPS door.
3. Connect the power supply cables.
4. Ensure the correct phase rotation.
5. Confirm that the address DIP switch of the main Liebert FlexPower assemblies are different from
each other, and they are within 1 to 6. If they are the same, adjust them to create different Liebert
FlexPower assembly addresses.
Table 27 Dip switch matrix
FlexPower Assembly Address

Flex Power Assembly DIP Switch Number Left to Right


Address Top to Bottom 1 2 3 4 5
6 Down Up Up Down Down
5 Up Down Up Down Down
4 Down Down Up Down Down
3 Up Up Down Down Down
2 Down Up Down Down Down
1 Up Down Down Down Down

NOTE
For standardization, if the quantity of modules in system is less than 6, for example 45kVA
system, Emerson recommends setting the address bits of the modules as 1, 2, 3 respectively.
6. Close the external input circuit breaker and connect input power.
The LCD activates. The rectifier indicator flashes while the rectifier is starting. The rectifier
enters normal operation state, and after about 30 seconds, the rectifier indicator stops blinking
and is illuminated in a steady green. After initialization, the bypass static switch turns on. The
mimic LEDs appear as shown Table 28.

Liebert® APM™ 100


Operation

Table 28 Mimic indicators after initialization


LED Status
Rectifier Indicator Green
Battery Indicator Red
Bypass Indicator Green
Inverter Indicator Off
Load Indicator Green
Status Indicator Amber
7. Ensure that the Liebert FlexPower assembly ready switches are latched (in Down position).
8. Close the external output circuit breaker.
9. Press the INVERTER ON button for 2 seconds. The inverter indicator flashes while the inverter
is starting. After the inverter is ready, the UPS transfers from bypass to inverter, the bypass
indicator turns Off, and the inverter indicator turns On. The UPS is in Normal Mode. The mimic
LEDs will appear as shown below.
Table 29 Mimic indicators for normal mode operation with battery breaker open
LED Status
Rectifier Indicator Green
Battery Indicator Red
Bypass Indicator Off
Inverter Indicator Green
Load Indicator Green
Status Indicator Amber

10. Close the battery breaker.


Table 30 Mimic indicators for normal mode operation with battery breaker closed
LED Status
Rectifier Indicator Green
Battery Indicator Off
Bypass Indicator Off
Inverter Indicator Green
Load Indicator Green
Status Indicator Green

10.2.2 Startup in ECO Mode


ECO Mode is available only on a single-module Liebert APM.
1. Verify that input power is available.
2. Select ECO Mode on the Control Panel.
3. Verify that the Bypass indicator remains green to indicate that the load is supplied by the bypass
input. The UPS is now operating in ECO Mode.

101 Liebert® APM™


Operation

10.2.3 Switching Between UPS Operation Modes


To switch from Normal Mode to Static Bypass Mode—Press the INVERTER OFF button to
switch to Bypass Mode (see Figure 70).
NOTE
In Static Bypass Mode, the load is being powered by the utility and is not protected from
fluctuations in input power: spikes, sags and failure.
To Switch From Bypass Mode To Normal mode—When the UPS is in Bypass Mode, press the
INVERTER ON button. After the inverter enters normal operation, the UPS transfers to Normal
Mode.
To switch from Normal Mode to ECO Mode—Select ECO Mode using the Liebert APM control
panel. After a 5-minute qualification of the bypass voltage, the UPS will transfer to bypass.
The Bypass indicator on the MIMIC display will illuminate Green to indicate that the UPS is
operating properly with input power form the bypass input. The Inverter indicator will flash Green to
indicate that the Inverter is on standby operating in ECO mode.
NOTE
In ECO Mode, the load is being powered by the utility as long as the bypass source remains
within set limits.
To switch from ECO mode to Normal Mode—When the UPS is in ECO Mode, press the
INVERTER ON button. After the inverter enters normal operation, the UPS transfers to Normal Mode.

10.3 UPS Battery Start


The battery start option permits starting the Liebert APM with power supplied only by the batteries
(at charged condition).

! CAUTION
Before attempting to start the UPS without utility power present, ensure that the batteries
are fully charged—over 2.1V per cell—and will supply adequate run time to the load.

1. Verify that the battery cabinet is properly connected (see Figure 40) and that the battery breaker
is closed.
2. Press the battery start button on the front panel of any Liebert FlexPower assembly for two
seconds (see Figure 80 for the button’s location).
The LCD displays the start screen, and the battery indicator flashes green. It stops flashing and
becomes solid green about 30 seconds after the rectifiers enter normal operation.
3. Press and hold the INVERTER ON key for two seconds, and the UPS will begin operating in
battery mode.
Figure 80 Battery start button location

Battery Start Button on Right


Side of the Liebert FlexPower
assembly

Liebert® APM™ 102


Operation

10.4 Switching the UPS from Normal Operation to Maintenance Bypass


Follow the procedure below to transfer the load from the UPS inverter output to the Maintenance
Bypass system.

! CAUTION
This procedure must be performed by properly trained and qualified personnel who are
knowledgeable about the operation of this system. Failure to follow these instructions will
result in loss of power and possible damage to critical equipment.
Before performing this operation, read any messages on the LCD to be sure that bypass
supply is regular and the inverter is synchronous with it. If those conditions are not present,
there is a risk of a short interruption in powering the load.

This procedure assumes that UPS is operating normally.


1. Press the INVERTER OFF button on the right side of the Operator Control Panel for longer than
2 seconds.
The Inverter indicator will turn Off, the status indicator will turn amber and an audible alarm
will sound. The load will transfer to static bypass (internal) and the inverter will shut off.
NOTE
Pressing the Alarm Silence Switch cancels the audible alarm, but leaves the warning message
displayed until the appropriate condition is rectified.
2. Open the Liebert BDC door to gain access to the bypass isolation breaker (BIB), maintenance
bypass breaker (MBB) and maintenance isolation breaker (MIB).
3. When the lamp indicator on the BDC is illuminated, press and hold the adjacent push button and
remove the Key from the lock (K0).
4. Insert the Key into the lock on the MBB and turn the Key.
5. Close the MBB.
6. Verify the MBB is closed. Failure to close the MBB will interrupt power to the load.
7. Open the MIB.
8. Remove the key from the lock on the MIB. Insert the key into the lock (K0) and turn the key.
9. The UPS system is now isolated from the critical load.
10. For a single-input system, the bypass isolation breaker (BIB) remains closed; this allows power to
remain present at the UPS input; refer to Figure 84.
11. For a single-source, dual-input system, the bypass isolation breaker (BIB) can be opened to
further isolate the UPS from input power; refer to Figure 81.

! WARNING
Risk of electrical shock and arc flash. Can cause property damage, injury and death.
Wait 5 minutes for the internal DC busbar capacitors to discharge before attempting
to remove the internal protective barriers.

! WARNING
Risk of electrical shock and arc flash. Can cause property damage, injury and death.
Even with the UPS in maintenance bypass and Off, portions of the Liebert APM system are
still energized. Service must be performed by properly trained and qualified personnel only.

NOTICE
Risk of power loss to connected load. Can cause damageto equipment.
The load equipment is not protected from normal supply aberrations when the Liebert APM is
operating in the maintenance bypass mode.

103 Liebert® APM™


Operation

10.5 Switching the UPS from Maintenance Bypass to Normal Operation


Follow the procedure below to transfer the load from the Maintenance Bypass system to the UPS
inverter output.
These conditions must be met for this operation to proceed:
• the UPS must be operating normally
• the BIB breaker must be closed
• the UPS system must be in the Maintenance Bypass mode of operation.

! CAUTION
Risk of electrical shock and arc flash. Can cause property damage, injury and death.
This procedure must be performed by properly trained and qualified personnel who are
knowledgeable about the operation of this system. Failure to follow these instructions will
result in loss of power and possible damage to critical equipment.
Before performing this operation, read any messages on the LCD to be sure that bypass
supply is regular and the inverter is synchronous with it. If those conditions are not present,
there is a risk of a short interruption in powering the load.

1. Verify that the Liebert APM is in Maintenance Bypass mode.


NOTE
Pressing the Alarm Silence Switch cancels the audible alarm, but leaves the warning message
displayed until the appropriate condition is rectified.
2. Open the Liebert BDC door to gain access to the bypass isolation breaker (BIB), maintenance
bypass breaker (MBB) and the maintenance isolation breaker (MIB).
3. When the Lamp indicator on the BDC is illuminated, press and hold the adjacent push button and
remove the key from the lock (K0).
4. Insert the key into the lock on the MIB, and turn the key.
5. Close the MIB.
6. Verify the MIB is closed. Failure to close the MIB will interrupt power to the load.
7. Open MBB.
8. Remove the key from the lock on the MBB.
9. Insert the key into the lock (K0) and turn the key.
The UPS system is now supplying power to the critical load.
10. Press the INVERTER ON button on the right side of the Operator Control Panel for longer than
2 seconds.
The Inverter indicator flashes while the inverter is starting.
After the inverter is ready, the UPS transfers from static bypass to inverter, the bypass indicator
turns Off and the inverter indicator turns On. The UPS is in Normal Mode. The indicator will
appear as shown in Table 30.

Liebert® APM™ 104


Operation

10.6 De-Energize Liebert APM with Maintenance Bypass Cabinet

! CAUTION
This procedure will remove power from the critical bus.

To de-energize the system:


1. On the UPS control panel, press and hold the INVERTER OFF button for 2 seconds.
2. Open all battery circuit breakers(s) including internal battery breaker (if applicable).

! CAUTION
Performing the next step will shut down the critical load.

3. If the MBC is an Emerson cabinet, open the Maintenance Isolation Circuit Breaker (MIB). If the
MBC is a customer-issued switchgear or a non-Emerson cabinet, open the breaker(s) that supply
power to the critical bus.
4. Open the Rectifier Input Circuit Breaker and Bypass Input Breaker (if dual input). If the MBC is
a customer-issued switchgear or a non-Emerson cabinet, open the breaker(s) that supply power to
the UPS input and bypass input (if dual input).
5. Allow 5 minutes for all DC circuits and capacitors to fully discharge.
6. Open the external feeder breaker to the MBC or bypass switchgear.
7. Install a Lockout/Tagout on the external feeder breaker to the MBC or bypass switchgear.
8. Use a digital multimeter to verify there is no AC or DC voltage present at the UPS input, output
and bypass bus bars.
9. Use a digital multimeter to verify there is no AC or DC voltage present at the MBC BIB, MIB and
MBB breakers.

105 Liebert® APM™


Operation

10.7 De-Energize Liebert APM Without Maintenance Bypass Cabinet

! CAUTION
This procedure will remove power from the critical bus.

To de-energize the APM:


1. On the UPS control panel, press and hold the INVERTER OFF button for 2 seconds.
2. Open all battery circuit breakers(s) including internal battery breaker (if applicable).

! CAUTION
Performing the next step will shut down the critical load.

3. Open the UPS output circuit breaker(s).


4. Open the UPS input circuit breaker and bypass circuit breaker (dual input systems only).
5. Allow 5 minutes for all DC circuits and capacitors to fully discharge.
6. Use a digital multimeter to verify there is no AC or DC voltage present at the UPS input, output
and bypass bus bars.
Figure 81 Typical configuration for single UPS

Static Bypass

* System AC Input Output


Busbar
AC Output
4-Wire + GRD 208V
See Note 5 UPS Cabinet 4-Wire + GRD
Battery

Notes Field-Supplied Wiring


1. Install in accordance with national and local electrical codes. * External Overcurrent
2. A neutral is required from the system AC input source. Protection by Others
A full-capacity neutral conductor and grounding conductors
are recommended.
3. UPS system input and output cables must be run in separate conduits.
4. Control wiring must be run in separate conduits. UAM01000
5. Customer must supply shunt trip breaker with 120V coil. Rev. 2
10.8 Operation of Two Liebert APM Units in Parallel Setup
This section describes a variety of operations for two Liebert APM units wired for parallel operation.
Figure 82 shows the one line diagram, and subsequent sections provide detailed steps for parallel
operation of the parallel units.

Liebert® APM™ 106


Operation

Figure 82 Liebert APM six-breaker buyout paralleling configuration

MBB
Buyout Liebert APM Paralleling Switchboard

* System AC Output
AC Input UIB UIB Opt. K MIB 4-Wire+GND
4 Wire +GND See
Note 7

MOB1
Output
Liebert APM #1 Busbar
UPS Cabinet

Static Bypass

Output MOB2
Liebert APM #2 Busbar
UPS Cabinet
Field-Supplied Wiring
Battery
* External overcurrent protection by others
LEGEND
UIB - UPS Input Breaker
NOTES: MOB - Module Output Breaker
1. Install in accordance with national and local 6. The 90kVA frame has a capacity of up to six MIB - Maintenance Isolation Breaker
electrical codes. Flex Power assemblies and the 45kVA frame has a MBB - Maintenance Bypass Breaker
2. Input and bypass must share the same single source. capacity of up to three Flex Power assemblies.
3. A neutral is required from the system AC input source. 7. Paralleling switchboard requires shunt trip UIB breakers
A full capacity neutral conductor is recommended. with 120V coils.
Grounding conductors are recommended. 8. See drawings UAM01080B, UAM01080C, UAM01080D,
4. Bypass and rectifier inputs and output cables must be UAM01080E and UAM01080F. Refer to the following
run in separate conduits. battery cabinet control wiring drawings:
5. Control wiring must be run in separate conduits. UAM04000
UAM4001A,B UAM01060A
UAM4002A,B D) Rev. 0

107 Liebert® APM™


Operation

10.8.1 Procedure to Take UPS1 Offline While Leaving UPS2 Online


The procedure below is used to switch the system from parallel to single UPS operation.

NOTICE
Risk of improper switching. Can cause damage to connected load.
Verify that removal of UPS1 from the system bus will NOT overload UPS2 and cause the load
to drop.
1. Turn OFF the inverter on UPS1 (see Figure 82).
2. Verify that UPS1 is now in Static Bypass Mode.
3. Open Battery Breaker(s) for UPS1.
4. Verify that the Battery Status Light on UPS1 turns Red.
5. Open UIB1.
6. Open MOB1.
7. Verify that UPS1 is now completely OFFLINE.

10.8.2 Procedure to Put UPS1 Back Online


1. Close MOB1 (see Figure 82).
2. Close UIB1.
3. Verify that the Liebert APM UPS turns On.
4. Close the battery breaker for UPS1.
5. Verify that the battery status light on UPS1 turns Off.
6. Verify that UPS1 is now in Static Bypass Mode.
7. Turn on the Inverter on UPS1.

10.8.3 Procedure to Take UPS2 Offline While Leaving UPS1 Online

NOTICE
Risk of improper switching. Can cause damage to connected load.
Verify that removal of UPS2 from the system bus will NOT overload UPS1 and cause the load
to drop.
1. Turn OFF the inverter on UPS2 (see Figure 82).
2. Verify that UPS2 is now in Static Bypass Mode.
3. Open Battery Breaker(s) for UPS2.
4. Verify that the Battery Status Light on UPS2 turns Red.
5. Open UIB2.
6. Open MOB2.
7. Verify that UPS2 is now completely OFFLINE.

10.8.4 Procedure to Put UPS2 Back Online


1. Close MOB2 (see Figure 82).
2. Close UIB2.
3. Verify that the Liebert APM UPS turns On.
4. Close the battery breaker for UPS2.
5. Verify that the battery status light on UPS2 turns Off.
6. Verify that UPS2 is now in Static Bypass Mode.
7. Turn on the Inverter on UPS2.

Liebert® APM™ 108


Operation

10.9 APM Procedure from Parallel Inverter Operation to Wrap-Around Bypass


Note: MBB is OPEN.
1. Turn OFF the Inverter on UPS1 (see Figure 82).
2. Turn OFF the Inverter on UPS2.
3. Verify that each UPS is now in Static Bypass Mode.
4. Open Battery Breaker(s) for UPS1.
5. Open Battery Breaker(s) for UPS2.
6. Verify that the Battery Status Light on UPS1 and UPS2 turns Red.
7. Close MBB - Bypass Breaker for System.
8. Open UIB1.
9. Open MOB1.
10. Verify that UPS1 is now completely OFFLINE.
11. Open UIB2.
12. Open MOB2.
13. Verify that UPS2 is now completely OFFLINE.

10.10 APM Procedure from Wrap-Around Bypass to Parallel Inverter Operation


Note: MBB is CLOSED.
1. Close UIB1 - Feed breaker to UPS1 (see Figure 82).
2. Close UIB2 - Feed breaker to UPS2.
3. Allow each UPS to qualify the Input and Bypass Feeds.
4. Close Battery Breaker(s) for UPS1.
5. Close Battery Breaker(s) for UPS2.
6. Close MOB1 - Output Breaker for UPS1.
7. Close MOB2 - Output Breaker for UPS2.
8. Verify that each UPS is now registering that it is in Static Bypass Mode and that the Battery
Status Light is not lit.
9. Open MBB.
10. Both UPS units should now be in static bypass mode.
11. Engage the Inverter on UPS1.
12. Engage the Inverter on UPS2.
13. Verify that there is a successful transfer from Static Bypass to Inverter (Normal Mode).
14. UPS1 and UPS2 are now both ONLINE.

10.11 Parallel APM System Startup


1. Close circuit breakers UIB1 and UIB2.
2. Close the battery breaker for each UPS.
3. Verify that the APM units are operating in Normal Mode.
4. Close circuit breakers MOB1 and MOB2.
5. Close circuit breaker MIB.

10.12 Parallel APM System Shutdown


1. Shutdown connected loads.
2. Open circuit breaker MIB.
3. Open circuit breakers MOB1 and MOB2.
4. Open circuit breakers UIB1 and UIB2.
5. Open the battery breaker for each UPS.

109 Liebert® APM™


Operation

10.13 Emergency Shutdown With EPO


This circuit has been designed to switch off the UPS in emergency conditions (i.e., fire, flood, etc.). The
system will turn off the rectifier, inverter and stop powering the load immediately (including the
inverter and bypass), and the battery stops charging or discharging.
If the input utility is present, the UPS’s controls will remain active; however, the output will be
turned off. To remove all power from the UPS, the external feeder breaker should be opened. (Refer to
Figure 68).

10.14 Auto Restart


When the main and bypass sources fail, the UPS draws power from the battery system to supply the
load until the batteries are depleted. When the UPS reaches its end of discharge (EOD) threshold, it
will shut down.
The UPS will automatically restart and enable output power:
• after utility power is restored
• if “Auto Recovery after EOD Enabling” is enabled in the UPS configuration (set by factory or by
Liebert Services)
• after the “Auto Recovery after EOD Delay Time” expires (the default delay is 10 minutes)
During the auto recovery delay, the Liebert APM will be charging its batteries to provide a safety
margin for equipment shutdown if input power fails again.
If the “Auto Recovery after EOD Enabling” feature is disabled, the system must be restarted manually.

10.15 Reset After Shutdown for Emergency Stop (EPO Action) or Other Conditions
Once all appropriate measures have been taken to correct the problem indicated by the alarm
message appearing on the Operator Control Panel , carry out this procedure to restore the UPS to
regular operation following an EPO action or for the following reasons: Inverter Overtemperature,
Cut-off Overload, Battery Overvoltage, excessive switching (BYP: XFER COUNT BLOCK), etc.
When the user confirms that the fault is cleared:
1. Press the FAULT CLEAR button to let the system exit the emergency off state.
2. Press the INVERTER ON button on the right side of the Operator Control Panel for longer than
2 seconds (after the rectifier has qualified).
NOTE
The rectifier will start automatically 5 minutes after the of overtemperature fault is cleared.
After the EPO button is pressed, if the input utility is removed, the UPS will shut down completely.
When input utility is restored, the EPO condition will clear, and the UPS will enable the static bypass
and restore the output.

10.16 Battery Protection


10.16.1 Battery Undervoltage Warning
Before the end of discharge, the Liebert APM displays a low battery warning. After this warning, the
battery has the capacity for 5 minutes discharging with full load (default time). The Liebert APM can
be user-configured to display this warning from 3 to 60 minutes before end-of-discharge.

10.16.2 Battery End-of-Discharge (EOD) Protection


If the battery voltage is lower than the end-of-discharge voltage, the battery converter will be shut
down.

Liebert® APM™ 110


Operation

10.17 Replacing Dust Filters


Installing the two dust filter sizes in a Liebert APM requires only a Phillips screwdriver. Each filter is
held in place by a bracket on either side of each filter. Each UPS is shipped from the factory with two
sets of washable and reusable dust filters. Refer to 12.3.2 - Air Filters for details about filter
maintenance.
To replace each filter:
1. Open the UPS front door and locate the filters on the back side of the front door (see Figure 83).
2. Remove one bracket and loosen the screw on the second bracket. The second bracket need not be
removed.
3. Remove the dust filter to be replaced.
4. Insert the clean filter.
5. Reinstall the bracket, tightening the screw securely.
6. Tighten the screw on the second bracket.

Figure 83 Dust filter replacement

111 Liebert® APM™


Operation

10.18 Operation

! WARNING
Risk of electrical shock and arc flash. Can cause property damage, injury and death.
The Liebert APM contains high voltages internally. Components that can only be accessed by
opening the protective cover with tools cannot be serviced or replaced by the user.
Only properly trained and qualified service personnel are authorized to remove the protective
covers.
The Liebert APM operates in the modes shown in Table 31. This section describes various kinds of
operating procedures under each operating mode, including transfer between operating modes, UPS
setting and procedures for turning on/off inverter.
Table 31 UPS operating modes
Operating mode Descriptions
Normal mode NORMAL UPS powers the load
The load power supply is provided by the static bypass. This mode can be regarded
Bypass mode BYPASS as a temporary transition mode between the normal mode and maintenance bypass
mode, or a temporary abnormal operating status.
Maintenance UPS shuts down, the load is connects to the mains through the Liebert BDC. In this
MAINT
Mode mode the load is not protected against abnormal input utility power.
As shown in Figure 84, the AC utility source is supplied through the input breaker, and the rectifier
converts the alternating current into DC power. The inverter converts the AC power from the
utility—or DC power from the batteries—into AC power for the load. The batteries power the load
through the inverter in the event of a power failure. The utility source can also power the load
through the static bypass.
If maintenance or repair of the UPS is necessary, the load can be switched without interruption in
service using the Liebert BDC.
Figure 84 Single module block diagram—Single input configuration with three-breaker Liebert BDC
Bypass Distribution Cabinet

* System MBB AC Output


Optional
AC Input 208V
BIB MIB 54-Pole
4-Wire + GND 4-Wire + GND
See Note 6

Static Bypass

UPS Cabinet
Battery

NOTES
1. Install in accordance with national and local electrical codes. BIB - Bypass Isolation Breaker
2. Input and bypass must share the same single source. MBB - Maintenance Bypass Breaker
3. A neutral is required from the system AC input source. A full MIB - Maintenance Isolation Breaker
capacity neutral conductor is recommended. Grounding * External Overcurrent Protection
conductors are recommended. by others
4. UPS system input and output cables must be run in separate conduits. Field-Supplied Wiring
5. Control wiring must be run in separate conduits.
6. Optional 54-pole, 225A for 45kVA frame only or optional 54-pole, UAM01003
400A for 90kVA frame only. Rev. 2

Liebert® APM™ 112


Operation

Figure 85 Single module block diagram—Dual input configuration with three-breaker Liebert BDC

Bypass Distribution Cabinet

* Bypass MBB Optional AC Output


AC Input BIB MIB 54-Pole 208V
4-Wire + GND See Note 6 4-Wire + GND

Static Bypass

* Rectifier
AC Input
4-Wire + GND
UPS Cabinet
See Note 7
Battery

NOTES
BIB - Bypass Isolation Breaker
1. Install in accordance with national and local electrical codes.
MBB - Maintenance Bypass Breaker
2. Input and bypass must share the same single source.
MIB - Maintenance Isolation Breaker
3. A neutral is required from the system AC input source. A full
* External Overcurrent Protection
capacity neutral conductor is recommended. Grounding
by others
conductors are recommended.
4. Bypass and rectifier inputs and output cables must be run Field-Supplied Wiring
in separate conduits.
5. Control wiring must be run in separate conduits. UAM01023
6. Optional 54-pole, 225A for 45kVA frame only or optional 54-pole, Rev. 3
400A for 90kVA frame only.
7. Customer must supply shunt trip breaker with 120V coil.

113 Liebert® APM™


Operation

Figure 86 Block diagram—Single input configuration with four-breaker internal bypass

UPS Cabinet

System * MBB Output AC Output


AC Input Busbar 208V
RIB BIB MIB
4-Wire + GND 4-Wire + GND

Static Bypass

Battery

1. Install in accordance with national and local electrical codes. RIB - Rectifier Input Breaker
2. A neutral is required from the system AC source. Emerson BIB - Bypass Isolation Breaker
recommends a full-capacity neutral conductor and grounding conductors. MBB - Maintenance Bypass Breaker
3. System AC input and output cables must be run in separate conduits. MIB - Maintenance Isolation Breaker
4. Contol wiring must be run in separate conduits. * Eternal Overcurrent protection by others
Field-Supplied Wiring
UAM01070
Rev. 2
10.19 Static Bypass Switch
The circuit block labeled “Static Bypass” in Figure 84 contains an electronically controlled switching
circuit that enables the critical load to be connected to either the inverter output or to a bypass power
source via the static bypass line. During normal system operation, the load is connected to the
inverter and the inverter contactor is closed; but in the event of a UPS overload or inverter failure,
the load is automatically transferred to the static bypass line.
To provide a clean (no-break) load transfer between the inverter output and static bypass line, the
static switch activates, connecting the load to bypass. To achieve this, the inverter output and bypass
supply must be fully synchronized during normal operating conditions. This is achieved through the
inverter control electronics, which make the inverter frequency track that of the static bypass supply,
provided that the bypass remains within an acceptable frequency window.
NOTE
When the UPS is operating in static bypass mode or on maintenance bypass, the connected
equipment is not protected from power failures or surges and sags.

Liebert® APM™ 114


Specifications and Technical Data

11.0 SPECIFICATIONS AND TECHNICAL DATA

11.1 Conformity and Standards


The Liebert APM has been designed to conform to the following standards:
Safety UL 1778, CSA 22.2 107.3, 4th Edition
Surge ANSI 62.41 Cat A3 and B3
Harmonics IEC 61000-3-4
Electrical Fast Transient IEC 61000-4-4 Level 4, Criteria A
ESD IEC 61000-4-2 Level 4, Criteria A
FCC Part 15, Class A
Radiated Immunity IEC 61000-4-3 Level 3, Criteria A
Conducted Immunity IEC 61000-4-6 Level 4, Criteria A
Low-Frequency Signals IEC 61000-2-2 Criteria A
Transportation ISTA Procedure 1H
ISO 9001
Misc OSHA, ASME, NEMA PE-1

The Liebert APM has UL and c-UL approval.

11.2 UPS Environmental


The Liebert APM is designed to operate under the following environmental conditions without
damage or degradation in electrical operating characteristics:
Table 32 Environmental requirements
Item Requirements
Acoustical Noise, dBA, at 55 in. (1.4m) 57 (45kVA); 60 (90kVA)
With Top Fan Kit 69 (45kVA); 70 (90kVA)
3300 ft. (1000m) above sea level; derate power by 1% per 330 ft.
Operating Altitude
(100m) between 3300 and 6000 ft. (1000m and 2000m)
Relative Humidity 0 to 95% non condensing
32 to 104 (0 to 40)*
Operating Temperature, °F (°C)
Battery life is halved for every 18°F (10°C) increase above 68 (20)
UPS Storage/Transport Temperature, °F (°C) -4 to 158 (-20 to 70)
Recommended Battery Storage -4 to 86 (-20 to 30)
Temperature, °F (°C) 68 (20) for optimum battery storage

Table 33 UPS mechanical characteristics


Rated Power, kVA 15 - 90
Dimensions, W x D x H, in (mm) 31-1/2 x 39-1/2 x 78-3/4 (800 x 1000 x 2000)
Weight, without batteries, lb (kg) 796 - 2154 (362 - 979)
Color Black
Protection Degree IEC (60529) IP20 (finger-proof with front doors open or closed)

115 Liebert® APM™


Specifications and Technical Data

Table 34 45kVA Liebert BDC mechanical characteristics


Rated Power, kVA 15-45
23-5/8 x 39-1/2 x 78-3/4
Dimensions, W x D x H, in (mm)
(600 x 1000 x 2000)
Weight, lb (kg)
No Distribution 525 (239)
225A Panelboard 625 (284)
No Distribution & 480V Transformer 1070 (486)
No Distribution & 600V Transformer 1085 (493)
225A Panelboard & 480V Transformer 1170 (532)
225A Panelboard & 600V Transformer 1085 (493)
Color Black
Protection Degree IEC (60529) IP20 (finger-proof with front doors open or closed)
Table 35 90kVA Liebert BDC mechanical characteristics
Rated Power, kVA 15-90
23-5/8 x 39-1/2 x 78-3/4
Dimensions, W x D x H, in (mm)
(600 x 1000 x 2000)
Weight, lb (kg)
No Distribution 550 (250)
Two 225A Subfeed Breakers 660 (300)
400A Panelboard 660 (300)
No Distribution & 480V Transformer 1482 (674)
No Distribution & 600V Transformer 1497 (680
Two 225A Subfeed Breakers & 480V Transformer 1592 (724)
Two 225A Subfeed Breakers & 600V Transformer 1607 (730)
400A Panelboard & 480V Transformer 1592 (724)
400A Panelboard & 600V Transformer 1607 (730)
Color Black
Protection Degree IEC (60529) IP20 (finger-proof with front doors open or closed)
Table 36 600mm battery cabinet mechanical characteristics
Rated Power, kVA 15 - 90
23-5/8 x 39-1/2 x 78-3/4
Dimensions, W x D x H, in (mm)
(600 x 1000 x 2000)
Weight, lb (kg)
with HX150 batteries 1490 (677)
with HX205 batteries 1755 (798)
with HX300 batteries 2213 (1006)
with HX330 batteries 2477 (1126)
Color Black
Protection Degree IEC (60529) IP20 (finger-proof with front doors open or closed)

Liebert® APM™ 116


Specifications and Technical Data

Table 37 900mm battery cabinet mechanical characteristics


Rated Power, kVA 15 - 90
35-1/2 x 39-1/2 x 78-3/4
Dimensions, W x D x H, in (mm)
(900 x 1000 x 2000)
Weight, lb (kg)
with HX400 batteries 2693 (1224)
with HX505 batteries 3245 (1475)
with HX540 batteries 3345 (1520)
Color Black
Protection Degree IEC (60529) IP20 (finger-proof with front doors open or closed)

11.3 Batteries Approved for Use in Liebert APM Systems


Table 38 Batteries approved for use in External Battery Cabinet, 600mm
Supplier Part Number
Enersys 12HX150-FR
Enersys 12HX205-FR
Enersys 12HX300-FR
Enersys 12HX330-FR

Table 39 Batteries approved for use in External Battery Cabinet, 900mm


Supplier Part Number
Enersys 12HX400-FR
Enersys 12HX505-FR
Enersys 12HX540-FR

Table 40 Internal batteries approved for use with 45kVA frame Liebert APM
Supplier Part Number
12HX100-FR
Enersys
12HX150-FR

117 Liebert® APM™


Specifications and Technical Data

11.4 UPS Electrical Characteristics


Refer to additional circuit breaker notes in 3.2.8 - Accessory Fuses and Backfeed Breaker
Wiring.
NOTE
The breakers and cables used must be in accordance with NEC ANSI/NFPA 70. A disconnect
breaker must be provided for AC input, DC input and AC output. Recommended cable sizes are
suitable for operation at a maximum temperature of 86°F (30°C). For continuous operation at
temperatures above 86°F (30°C), the site design should include cables that meet requirements
for 104°F (40°C) installations.
Table 41 UPS currents and terminals—Input (for single-input unit, 208V operation)
Maximum Recommended Lug (T&B)

Nominal Maximum OCP Compression Mechanical


Unit Input Input Device 75°C Wire Lug Two Hole Lug Two Hole
Rating Current Current Rating Bolt Size Current, tot Wire 3/8" Bolt 3/8" Bolt
15 45 56 70 M10 (3/8") 130 (1) #1 54857BE 32209
30 90 112 125 M10 (3/8") 150 (1) 1/0 54860BE 32209
45 134 167 200 M10 (3/8") 200 (1) 3/0 54864BE 32211
60 179 223 250 M10 (3/8") 300 (2) 1/0 54860BE 32209
75 224 279 350 M10 (3/8") 350 (2) 2/0 54862BE 32209
90 268 334 400 M10 (3/8") 460 (2) 4/0 54866BE 32211

Table 42 UPS currents and terminals—Input (for dual-input unit only, 208V operation)
Maximum Recommended Lug (T&B)

Nominal Maximum OCP Compression Mechanical


Unit Input Input Device 75°C Wire Lug Two Hole Lug Two Hole
Rating Current Current Rating Bolt Size Current, tot Wire 3/8" Bolt 3/8" Bolt
15 45 56 70 M10 (3/8") 130 (1) #1 54857BE 32209
30 90 112 125 M10 (3/8") 150 (1) 1/0 54860BE 32209
45 134 167 200 M10 (3/8") 200 (1) 3/0 54864BE 32211
60 179 223 250 M10 (3/8") 300 (2) 1/0 54860BE 32209
75 224 279 350 M10 (3/8") 350 (2) 2/0 54862BE 32209
90 268 334 400 M10 (3/8") 460 (2) 4/0 54866BE 32211

Table 43 UPS currents and terminals—Bypass input (for dual-input units, 208V operation)
Maximum Recommended Lug (T&B)

Nominal Compression Mechanical


Unit Input OCP Device 75°C Wire Lug Two Hole Lug Two Hole
Rating Current Rating Bolt Size Current, tot Wire 3/8" Bolt 3/8" Bolt
15 42 60 M10 (3/8") 130 (1) #1 54857BE 32209
30 84 110 M10 (3/8") 150 (1) 1/0 54860BE 32209
45 126 175 M10 (3/8") 175 (1) 2/0 54862BE 32209
60 168 225 M10 (3/8") 230 (1) 4/0 54866BE 32211
75 210 300 M10 (3/8") 300 (2) 1/0 54860BE 32209
90 252 350 M10 (3/8") 350 (2) 2/0 54862BE 32209

Liebert® APM™ 118


Specifications and Technical Data

Table 44 UPS currents and terminals—Output 208V


Maximum Recommended Lug (T&B)

Nominal Compression Mechanical


Unit Output OCP Device 75°C Wire Lug Two Hole Lug Two Hole
Rating Current Rating Bolt Size Current, tot Wire 3/8" Bolt 3/8" Bolt
15 42 60 M10 (3/8") 130 (1) #1 54857BE 32209
30 83 125 M10 (3/8") 150 (1) 1/0 54860BE 32209
45 125 200 M10 (3/8") 175 (1) 2/0 54862BE 32209
60 167 225 M10 (3/8") 230 (1) 4/0 54866BE 32211
75 208 300 M10 (3/8") 300 (2) 1/0 54860BE 32209
90 250 350 M10 (3/8") 350 (2) 2/0 54862BE 32209

Table 45 UPS currents and terminals—Battery (288V string)


Maximum Recommended Lug (T&B)

Compression Mechanical
Unit Battery OCP Device 75°C Wire Lug Two Hole Lug Two Hole
Rating Current Rating Bolt Size Current, tot Wire 3/8" Bolt 3/8" Bolt
15 67 80 M10 (3/8") 130 (1) #1 54857BE 32209
30 135 150 M10 (3/8") 175 (1) 2/0 54862BE 32209
45 202 225 M10 (3/8") 230 (1) 4/0 54866BE 32211
60 269 300 M10 (3/8") 300 (2) 1/0 54860BE 32209
75 335 350 M10 (3/8") 400 (2) 3/0 54864BE 32211
90 404 450 M10 (3/8") 460 (2) 4/0 54866BE 32211
Table 46 AC/AC efficiency, loss and air exchange
AC/AC Efficiency Data
Normal Mode (dual
94 maximum
conversion), %
ECO Mode, % Up 98
Inverter Efficiency (DC/AC) (Battery at Nominal Voltage 288VDC and Full-Rated Linear Load)
Rated Power, kVA 15-90
Battery Mode, % 94
Heat Losses and Air Exchange
Rated Power, kVA 15 30 45 60 75 90
Normal Mode, kW 0.9 1.8 2.7 3.6 4.5 5.4
No Load, kW 0.3 0.6 0.9 1.2 1.5 1.8
Maximum forced air cooling
(front intake, rear exhaust), 102 (173) 204 (346) 306 (519) 408 (692) 510 (865) 612 (1038)
L/sec (m3/hr)
Heat Dissipation, BTU/Hr (kWH)
Without Transformer 3074 (0.9) 6147 (1.8) 9220 (2.7) 12,295 (3.6) 15,368 (4.5) 18,442 (5.4)
With Transformer, 480V 9352 (2.7) 12,425 (3.6) 15,498 (4.5) 23,149 (6.8) 26,222 (7.7) 29,296 (8.6)
With Transformer, 600V 9393 (2.8) 12,466 (3.7) 15,539 (4.6) 22,920 (6.7) 25,993 (7.6) 29,067 (8.5)
With Transformer, 208V 9021 (2.6) 12,094 (3.5) 15,167 (4.5) 18,996 (5.6) 22,069 (6.5) 25,143 (7.4)
Top Fan Forced Air Cooling, 45kVA Frame - 566 L/sec (2040 m3/hr)
Total: 2 Fans 90kVA Frame - 744 L/sec (2680 m3/hr)

119 Liebert® APM™


Specifications and Technical Data

Table 47 Rectifier input


Parameter 15-90kVA
Rated AC Input Voltage 1 208/120V or 220/127V, 60Hz, 3-Phase, 4-Wire Plus Ground
Input Voltage Range, Startup/Operating 96-138V or 102-146V or -20%, +15% (Full Load)
Input Voltage Range, Operating 72-138V or 76-146V or -40%, +15% (<80% Load)
Frequency 50 or 60Hz (40-70Hz Range)
Power Factor 0.99 Full Load, 0.98 Half Load
THD 3% THDI Full Load
1. Three-phase, four-wire and shared neutral with the bypass input.

Table 48 Battery DC intermediate circuit


Parameter 15 - 90kVA
Battery Bus Voltage Nominal: 288VDC (VRLA Float charge is 324V) 24 jars of 12V VRLA
Number of Lead-Acid Cells 144 = [24 x 6 cell (12V) blocks], nominal
2.25V/cell, selectable from 2.2 - 2.3V/cell
Float Voltage
Constant current and constant voltage charge mode
Temperature Compensation -3.0mV/°C, selectable from 0 to -5.0mV/°C around 77°F (25°C) or 86°F (30°C) or inhibit
Ripple Voltage ≤1%
Ripple Current, ~ C10 ≤5%
Boost Charge 2.35 V/cell (selectable from 2.30-2.40V/cell)
Voltage Constant current and constant voltage charge mode
• Float-boost current trigger 0.050 C10 (selectable 0.030-0.070)
• Boost-float current trigger 0.010 C10 (selectable 0.005-0.025)
Boost Control
24 hr safety time-out (selectable 8-30 hr)
Boost charge mode inhibit also selectable
1.63 V/cell (selectable from 1.60-1.750V/cell)
End of Discharge Auto Inverse EOD voltage x discharge current mode
(The end of discharge voltage increases at low discharge currents)
2.4 V/cell (selectable from 2.3-2.4V/cell)
Battery Charge Constant current and constant voltage charge mode
Programmable auto trigger or inhibit of boost mode
UPS (kVA) 15 30 45 60 75 90
Battery Charging Power1
Battery Charging Power (kW) 2.25 4.5 6.75 9 11.25 13.25
Max Current (Adjustable)2
Max Charging Current (A) 11 22 33 44 55 66
1. At low input voltage, the UPS recharge capability increases with load decrease (up to the maximum capacity indicated).
2. Maximum currents listed are for end of discharge voltage of 1.67 V/cell for 144 cells.

Liebert® APM™ 120


Specifications and Technical Data

Table 49 Inverter output to critical load


Parameter 15 - 90kVA
Rated AC Voltage 1 208/120, 220/127VAC, 60Hz, 3-phase, 3- or 4-wire plus ground
2
Frequency 60Hz
110% load, 60 min
Overload Capacity 125% load, 10 min
150% load, 60 sec
Fault Current Short circuit for 200 ms
3
Non-Linear Load Capability 100%
Neutral Current Capability 170%
Steady State Voltage Stability ±1% (balanced load)
±1% for balanced load
Voltage Regulation
±5% for 100% unbalanced load
120° ±1° for balanced load
Phase Balance
120° ±15°± for 100 unbalanced load
Transient Voltage Response 4 ±5%
THD < 1% (linear load), <4% (non linear load 3)
Sync Frequency Range Rated frequency ± 2Hz (selectable ± 0.5 to ± 3Hz)
Frequency Slew Rate 0.2 to 3Hz/sec
±0.1% (single Liebert FlexPower Assembly)
Frequency Regulation
±0.25% (six Liebert FlexPower Assemblies)
Voltage Adjustment Range -5% to +16% of nominal
1. Factory set to 208V or 220V selectable by commissioning engineer.
2. Factory set to 60Hz; 50Hz selectable by commissioning engineer. Frequency converter operation also selectable.
3. EN50091-3 (1.4.58) crest factor: 3:1
4. IEC62040-3/ EN 50091-3 also for 0-100-0% load transient. Transient recovery time: return to within 5% of steady state output voltage
within half a cycle.
5. Three-phase, 4 wire and shared neutral with the bypass input.

Table 50 Bypass input


Parameter 15 - 90kVA
Rated AC Voltage 1 2 208/220V 3-phase
208V 252A
Rated current
220V
240A
Overload 135% load, long term

Upstream protection, bypass line Thermomagnetic circuit-breaker, rated up to 125% of nominal output
current. IEC 60947-2 curve C.
Current rating of neutral cable, A 1.7×In
Frequency, Hz 60
Synchronous transfer: 0ms
Transfer time between Bypass and Inverter, ms Asynchronous transfer (default): 15 ms (50 Hz), 13.3 ms (60 Hz)
or 40, 60, 80, 100 ms selectable
Upper limit: +10, +15 or +20, default +15
Bypass voltage tolerance,%VAC Lower limit: -10, -20, -30 or -40; default: -20 (delay time to accept steady
bypass voltage: 10 sec)
Bypass frequency tolerance,% ±10 or ±20; default ±10
Synchronization - Window Rated frequency ± 2Hz (selectable ± 0.5 to ± 3Hz)
1. Factory-set to 208 or 220V selectable by commissioning engineer.
2. Three-phase, 4 wire and shared neutral with the rectifier input. Neutral referenced to the output.

121 Liebert® APM™


Specifications and Technical Data

Figure 87 Battery, circuit breaker and UPS wiring with external batteries with four connecting wires

N U
N P
N S

-
Figure 88 Battery, circuit breaker and UPS wiring with external batteries with three connecting wires

+
N
N
-
-

Liebert® APM™ 122


Maintenance

12.0 MAINTENANCE

12.1 Safety Precautions


Observe the safety precautions in Important Safety Instructions on page 1.
Only properly trained and qualified personnel should perform maintenance on the UPS system.
Observe all of the warnings and cautions below before performing any maintenance on the UPS
system and associated equipment. Also observe the manufacturer's safety precautions pertaining to
the battery, along with the battery safety precautions in this section.

! WARNING
Risk of electrical shock and arc flash. Can cause property damage, injury and death.
Only Emerson or Emerson-trained service personnel should work on this equipment. Both AC
and DC high voltages are present in lethal amounts within this equipment. Extreme care
should be taken when working around UPS equipment.
Always identify the source of connecting wiring prior to disconnecting. Mark any disconnected
wires, so they can be properly reconnected.
Do not substitute parts except as authorized by Emerson.
Maintain the UPS cabinets free of foreign materials such as solder, wire cuttings, etc.
Call Liebert Services if you are not sure of the procedures to follow or if you are not familiar
with the design or operation of the equipment.

! WARNING
Risk of electrical shock and arc flash. Can cause property damage, injury and death.
Extreme caution is required when performing maintenance.
Be constantly aware that the UPS system contains high DC as well as AC voltages. With
input power off and the battery disconnected, high voltage at filter capacitors and power
circuits should be discharged within 30 seconds. However, if a power circuit failure has
occurred, you should assume that high voltage may still exist after shutdown. Check with a
voltmeter before making contact.
AC voltage will remain on the bypass and output contactors and the static bypass switch,
unless associated external circuit breakers are opened.
Check for voltage with both AC and DC voltmeters prior to making contact.
When the UPS system is under power, both the operator and any test equipment must be
isolated from direct contact with earth ground and the UPS chassis frame by using rubber
mats.
Some components within the cabinets are not connected to chassis ground.
Any contact between floating circuits and the chassis is a lethal shock hazard. use differential
oscilloscopes when measuring a floating circuit. The differential input should have at least
800 vrms common mode input rating and a common mode rejection ratio of at least 8odb.
Exercise caution that the test instrument exterior does not make contact either physically or
electrically with earth ground.
In case of fire involving electrical equipment, use only carbon dioxide fire extinguishers, or
others approved for use in electrical fire fighting.

123 Liebert® APM™


Maintenance

12.2 Limited Life Components


The Liebert APM UPS has a design life well in excess of 10 years. Well-maintained units can continue
to provide economic benefits for 20 years or more. Long-life components are used in the UPS wherever
practical and cost-effective. However, due to the currently available component material,
manufacturing technology limitations and the general function and use of the component, a few
components in your Liebert UPS will have a shorter life cycle and require replacement in less than 10
years.
The following components utilized in your UPS system have a limited life cycle and are specifically
exempt from warranty. To prevent a wear-out failure of one of these components affecting your
critical load operations, Liebert recommends these components be periodically inspected and replaced
before the expected expiration of their life cycle. The expected life of each component listed below is
simply an estimate and is not a guarantee. Individual users may have site-specific requirements,
maintenance and other environmental conditions that affect the length of the component's useful life
cycle.
Table 51 Component service life
Component Expected Life Replace in:
Air filters 5 years Check four times per year
Valve-regulated, lead-acid (VRLA) 10 years 6 to 8 years

In most cases, replacement components must exactly match the original component specifications.
These replacement components are not readily available from third-party component distributors.
For assistance with your specific component specifications, replacement component selection and
sourcing, call 1-800-LIEBERT. For customers using Emerson Network Power Liebert Services’
preventive maintenance services, periodic inspection of these components is part of this service, as
well as recommending component replacement intervals to customers to avoid unanticipated
interruptions in critical load operations.

12.3 Routine Maintenance


Become thoroughly familiar with the equipment, but at no time go beyond the specific procedures in
this manual while performing maintenance or correcting a malfunction. If you have any doubt as to
what must be done, call Emerson® Network Power Liebert Services at 1-800-LIEBERT for further
instructions. The UPS is designed for unattended operation, but does require some common sense
maintenance.
• Keep good records—Troubleshooting is easier if you maintain historical service records.
• Keep the UPS free of dust and any moisture.
• Keep the UPS cool:
• Battery systems must be kept in the range of 72-77°F (22-25°C) in order to meet design speci-
fications for capacity and longevity.
• The UPS will reliably meet all performance specifications at temperatures up to 104°F (40°C),
and can be slightly derated for operation at even higher temperatures. However, performance
and longevity will be optimized when the UPS is operated at the same temperature as the
batteries.
• Keep connections tight.
• Tighten all connections at installation and at least annually thereafter. (See 12.3.5 - Torque
Requirements).

12.3.1 Record Log


Set up a maintenance log to record scheduled checks and any abnormal conditions.
The log should have space for all metered data including phase readings, alarm messages, UPS mode
of operation, air filter replacement date, and observation notes. A second log should be maintained for
the battery module as directed by the battery manufacturer.
Emerson recommends a periodic walk-through inspection of the UPS and battery rooms to check for
visible and audible indications of problems. Log the inspection, metered parameter indications and
any discrepancies.

Liebert® APM™ 124


Maintenance

12.3.2 Air Filters


The air filters must be inspected and serviced on a regular schedule. The period between inspections
will depend upon environmental conditions. Under normal conditions, the air filters will require
cleaning or replacement approximately every two months.
All Liebert APM models have replaceable filter elements behind the grille in the front of the unit.
This element can be changed with the UPS operating, by opening the outer door for access. The
Liebert APM air filters are washable and reusable. Two sets of air filters are are shipped with the
Liebert APM.
Abnormal or dusty conditions will require more frequent cleaning and replacement of air filters.
Inspect installations in new buildings more often, then extend the inspection period as experience
dictates.

12.3.3 Battery Maintenance

! WARNING
Risk of electrical shock and arc flash. Can cause property damage, injury and death.
These maintenance procedures will expose hazardous live parts. Refer servicing to qualified
personnel.

12.3.4 Battery Safety Precautions


Servicing of batteries should be performed or supervised by personnel experienced with batteries and
the required precautions. Keep unauthorized personnel away from batteries.

125 Liebert® APM™


Maintenance

When replacing batteries, use the same number and type of batteries.

! WARNING
Risk of electric shock, explosive reaction, hazardous chemicals and fire. Can cause property
damage, injury and deth.
Lead-acid batteries contain hazardous materials. Batteries must be handled, transported,
and recycled or discarded in accordance with federal, state, and local regulations. Because
lead is a toxic substance, lead-acid batteries should be recycled rather than discarded.
Do not dispose of battery or batteries in a fire. The battery may explode.
Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin
and eyes. It is poisonous.
A battery can present a risk of electrical shock and high short circuit current. The following
precautions should be observed when working on batteries:
• Remove watches, rings and other metal objects.
• Use tools with insulated handles.
• Wear rubber gloves and boots.
• Do not lay tools or metal parts on top of batteries.
• Disconnect charging source prior to connecting or disconnecting battery terminals.
• Determine if battery is inadvertently grounded. If inadvertently grounded, remove source
of ground. Contact with any part of a grounded battery can result in electrical shock. The
likelihood of such shock will be reduced if such grounds are removed during installation
and maintenance.
• Lead-acid batteries can present a risk of fire because they generate hydrogen gas. In addi-
tion, the electrical connections must be protected against accidental short circuits which
can cause sparks. The following procedures should be followed:
• DO NOT SMOKE when near batteries.
• DO NOT cause flame or spark in battery area.
• Discharge static electricity from body before touching batteries by first touching a grounded
metal surface.
• After replacing battery jars in a battery cabinet, replace the retaining straps that hold the
jars in place on the shelves. This will limit accidental movement of the jars and connectors
should the cabinet ever need to be repositioned or relocated.

Regular maintenance of the battery module is an absolute necessity. Periodic inspections of battery
and terminal voltages, specific gravity, and connection resistance should be made. Strictly follow the
procedures outlined in the battery manufacturer's manual. (See battery manufacturer’s web site.)
Valve-regulated lead-acid batteries do require periodic maintenance. Although they do not require
maintenance of electrolyte levels, visual inspections and checks of battery voltage and connection
resistance should be made.

NOTICE
Do not use cleaners on the batteries. Solvents can make the battery cases brittle. Use only a
dry cloth or a cloth moistened in water
Since individual battery characteristics are not identical and may change over time, the UPS module
is equipped with circuitry to equalize battery cell voltages. This circuit temporarily increases
charging voltage to maintain flooded type battery cells at full capacity.

Liebert® APM™ 126


Maintenance

! WARNING
Risk of electric shock, explosive reaction, hazardous chemicals and fire. Can cause equipment
damage, personal injury and death.
Do not use equalize charging with valve-regulated, lead-acid batteries, such as those used in
Liebert battery cabinets. Refer to the battery manufacturer’s manual, available on the
manufacturer’s Web site, for specific information about equalize charging.

Table 52 Battery voltage record

Float Voltage Nominal Voltage


Date (Volts DC) (Volts DC) Ambient Temp. (°F)

* To be completed by Liebert Services customer engineer at time of startup.

12.3.5 Torque Requirements


All electrical connections must be tight. Refer to Table 18 and Figure 60.
Tables 53 and 54 provide the torque values for the connections in the UPS and batteries. Use these
values unless the equipment is labeled otherwise.

Table 53 Terminal block with compression lugs (for control wiring)


AWG Wire Size
or Range Lb-in Nm
#22 - #14 3.5 to 5.3 0.4 to 0.6
Table 54 Battery retorque values
Battery Mfr. Battery Model # Retorque Value
12HX100-FR 40 in-lb (4.5N-m)
12HX150FR 40 in-lb (4.5N-m
12HX205-FR 58 in-lb (6.5N-m)
12HX300-FR 58 in-lb (6.5N-m)
Enersys
12HX330-FR 58 in-lb (6.5N-m)
12HX400-FR 58 in-lb (6.5N-m)
12HX505-FR 58 in-lb (6.5N-m)
12HX540-FR 58 in-lb (6.5N-m)

127 Liebert® APM™


Maintenance

12.4 Detecting Trouble


It is important that the operator check the instrument readings if abnormal equipment performance
is suspected. Any metered value that differs appreciably from normal could mean an impending
malfunction, and should be investigated.
Items to check on the various UPS display screens include:
1. Output voltage of all phases should be within 2% of normal voltage. Output currents on each
phase should not normally differ by more than 20%. If a greater difference is noted, the load is
unbalanced and corrective action should be taken to redistribute the load, if possible.
2. If the UPS has not operated on battery power during the last 10 hours, the batteries should
require little charging current. Battery mimic should indicate normal DC voltage with relatively
little battery charge current.
3. Input current on each phase should be within 10% of the average input current. Alarm messages
indicate malfunction or impending malfunction. A daily check of the Operator Control Panel will
help to provide an early detection of problems. Refer to Appendix B - UPS Status Messages to
interpret alarm messages.
4. Tracing a problem to a particular section is facilitated by alarm messages and the metered
parameter indications. These are stored in the Status Reports and can be displayed at the
Operator Control Panel or at an optional terminal.

NOTE
If the UPS system has a blown fuse, the cause should be determined before you replace the fuse.
Contact Liebert Global Services.

12.5 Reporting a Problem


If a problem occurs within the UPS, review all alarm messages along with other pertinent data. This
information should be given via telephone to the Liebert Service dispatcher. This information can also
be automatically sent by telephone modem. Call 1-800-LIEBERT to report a problem or to request
assistance.

12.6 Corrective Actions


For each alarm message on the Operator Control Panel and the Remote Alarm Status Panel, you can
find the recommended corrective action in Appendix B - UPS Status Messages.

12.7 Recommended Test Equipment


A list of recommended test equipment and tools required to maintain, troubleshoot, and repair the
UPS module is given in Table 55. You may substitute instruments of equivalent range and accuracy.
All instruments should be calibrated and be within the current calibration cycle. Calibration data for
the instruments should be maintained in equipment-history files and the instruments labeled for
audit and verification.

Table 55 Recommended test equipment and tools


Qty Test Equipment Manufacturer Model or Type
1 Oscilloscope Tektronix, H-P or Fluke DC to 50 MHz
2 Voltage Probes Tektronix, H-P or Fluke 10X, with 10 ft. Cable
2 Voltage Probes Tektronix, H-P or Fluke 100X, with 10 ft. Cable
1 Digital Multi-meter Fluke 8060, with Test Leads
1 Tool Kit N/A Standard electrical contractor tools

Liebert® APM™ 128


Maintenance

APPENDIX A HAZARDOUS SUBSTANCES OR ELEMENTS ANNOUNCEMENT


Table 56 Hazardous substances or elements
Hazardous Substances
Polybrominated Polybrominated
Lead Mercury Cadmium Chrome Biphenyl Diphenyl Ethers
Part Name (Pb) (Hg) (Cd) (Cr6+) (PBB) (PBDE)
Hex copper stud X ✔ ✔ ✔ ✔ ✔
PCBA X ✔ ✔ ✔ ✔ ✔
AC capacitor X ✔ ✔ ✔ ✔ ✔
DC capacitor X ✔ ✔ ✔ ✔ ✔
Fan X ✔ ✔ ✔ ✔ ✔
Cables X ✔ ✔ ✔ ✔ ✔
LCD X X ✔ ✔ ✔ ✔
Sensors X ✔ ✔ ✔ ✔ ✔
Large-medium power magnetic
components
X ✔ ✔ ✔ ✔ ✔

Circuit breaker / rotating switch X ✔ ✔ ✔ ✔ ✔


Semiconductors X ✔ ✔ ✔ ✔ ✔
Battery (when applicable) X ✔ ✔ ✔ ✔ ✔
Insulation monitoring device
(when applicable)
X ✔ ✔ ✔ ✔ X

? = Means the content of the hazardous substances in all the average quality materials of the part is within the limits specified in SJ/T-
11363-2006
X = Means the content of the hazardous substances in at least one of the average quality materials of the part is outside the limits specified
in SJ/T11363-2006
Emerson Network Power Co., Ltd. has been committed to the design and manufacturing of environment-friendly products. It will reduce and
eventually eliminate the hazardous substances in the products through unremitting efforts in research. However, limited by the current
technical level, the following parts still contain hazardous substances due to the lack of reliable substitute or mature solution:
1. All solders in the products contain lead.
2. Copper alloy contains lead.
3. Backlight bulb contains mercury.
4. The ceramic materials of the ceramic capacitor, the copper terminals and copper leads of metallic film capacity contain lead.
5. The glass of resistor contains lead.
6. The glass of LCD contains lead, and the backlight lamp contains mercury.
7. The lead in the battery is determined by the battery feature and technical levels.
8. The insulation monitoring device contains lead and PBDE.
About Environment Protection Period: The Environment Protection Period of the product is marked on the product. Under normal working
conditions and normal use of the products observing relevant safety precautions, the hazardous substances in the product will not seriously
affect the environment, human safety or property in the Environment Protection Period starting from the manufacturing date.
About battery: The battery life is dependent on the ambient temperature and charging / discharging times. The battery life will be shortened
if the battery is used under high temperature or in deep discharging status. Refer to the manufacturer’s product literature for details.
Applicable scope: Liebert APM 90kVA UPS

129 Liebert® APM™


Maintenance

APPENDIX B UPS STATUS MESSAGES


Table 57 shows all event messages as they appear in the current status area of the LCD or the
history log, along with a description and recommended actions, if any. For further information on the
current status area and the history log, see 9.10 - UPS History Log.
Table 57 UPS status messages
Event Message Description / Suggested Action (if any)
The CAN communication between internal monitor and rectifier/inverter/bypass fails. Contact
Comm. Fail
Liebert Services at 800-543-2378 for assistance.
Battery Overtemp. The Battery temperature is over limit. Check the battery temperature and ventilation.
Ambient Overtemp. The Ambient temperature is over limit. Check the ventilation of UPS room.
Replace Battery Battery should be replaced. Contact Liebert Services at 800-543-2378 for assistance.
Before the end of discharging, battery under-voltage pre-warning should occur. After this pre-
warning, battery should have the capacity for 3 minutes discharging with full load. The time is
Battery Low Pre-warning
user configured from 3 to 60 minutes.
Shut down the load in time.
Inverter turned off due to low battery voltage.
Battery End of Discharge
Check the utility failure and try to fix it.
Mains Voltage exceeds the upper or lower limit and results in rectifier shutdown.
Mains Volt. Abnormal
Check the input line-to-neutral voltage amplitude of rectifier.
Mains Voltage is undervoltage (120v~132V).
Mains Undervoltage
Check the input line-to-line voltage amplitude of rectifier.
Mains frequency is out of limit range and results in rectifier shutdown.
Mains Freq. Abnormal
Check the rectifier’s input voltage frequency.
Rectifier Fault Rectifier Fault; Contact Liebert Services at 800-543-2378 for assistance.
The temperature of heat sink is too high to keep the rectifier running.
Rectifier Overtemp.
The UPS can recover automatically. Check the environment and ventilation.
Charger Fault The Charger has failed. Contact Liebert Services at 800-543-2378 for assistance.
Input Fuse Fail Input fuse is open. Contact Liebert Services at 800-543-2378 for assistance.
Control Power 1 has failed or has been lost. Contact Liebert Services at 800-543-2378 for
Control Power 1 Fail
assistance.
Mains Phase Reversed Input phase sequence is reversed. Contact Liebert Services at 800-543-2378 for assistance.
Rectifier could not start due to low DC bus voltage. Contact Liebert Services at 800-543-2378 for
Soft Start Fail
assistance.
This alarm is triggered by an inverter software routine when the amplitude or frequency of bypass
voltage is beyond the normal range.
The amplitude threshold is fixed for positive and negative 10% rating.
This alarm automatically resets once the bypass voltage goes normal.
1. First verify that the bypass voltage and frequency displayed on the panel is within the selected
Bypass Unable to Trace
range. Note here the rated voltage and frequency are specified by “Output voltage level” and
“Output frequency level” respectively.
2. If the displayed voltage is believed to be abnormal, then verify the bypass voltage and
frequency presented to the UPS. Check the external supply if it is found to be faulty.
Contact Liebert Services at 800-543-2378 for assistance.
This alarm is triggered by an inverter software routine when the amplitude or frequency of bypass
voltage exceeds the limit.
This alarm automatically resets once the bypass voltage goes normal.
First check if there are some relevant alarms such as “Bypass disconnect open”, “Bypass phase
reverse” and “Mains neutral lost”. If they appear, solve them first.
1. Then verify that the bypass voltage and frequency displayed on the panel is within the bypass
Bypass Abnormal limit. Note here the rated voltage and frequency are specified by “Output voltage level” and
“Output frequency level” respectively.
2. If the displayed voltage is believed to be abnormal, then verify the bypass voltage and
frequency presented to the UPS. Check the external bypass supply if it is found to be faulty. If
the utility is likely to trigger this alarm frequently, the bypass limit can be changed a little larger
through the configuration software according to the customer’s agreement.
Contact Liebert Services at 800-543-2378 for assistance.

Liebert® APM™ 130


Maintenance

Table 57 UPS status messages (continued)


Event Message Description / Suggested Action (if any)
This alarm is triggered by an inverter software routine when the inverter and bypass waveforms
are misaligned by more than 6 degrees in phase. This alarm resets automatically once the
condition is no longer true.
1. First check if the alarm “Bypass unable to trace” or “Bypass abnormal” occurs. If so, solve it
Inverter Asynchronous
first.
2. Verify the waveform of the bypass voltage. If it is too distorted, ask the customer to verify and
seek any possible measurements.
Contact Liebert Services at 800-543-2378 for assistance.
This alarm indicates a fault condition exists within the inverter.
Inverter Fault
Contact Liebert Services at 800-543-2378 for assistance.
Fan Fault At least one of the cooling fans failed. Contact Liebert Services at 800-543-2378 for assistance.
At least one of the static switches of inverter side is open or short circuit. This fault is locked until
Inverter STS (relay) Fail
power off. Contact Liebert Services for assistance at 800-543-2378 for assistance.
At least one of the static switches of bypass side is open or short circuit. This fault is locked until
Bypass STS Fail power off.
Contact Liebert Services at 800-543-2378 for assistance.
Output Fuse Fail At least one of the output fuses is open. Contact Liebert Services at 800-543-2378 for assistance.
Control Power 2 Fail Control Power 2 is abnormal or lost. Contact Liebert Services at 800-543-2378 for assistance.
The UPS is confirmed to be overload when the load arises above 105% nominal rating.
The alarm automatically resets once the overload condition is removed.
1. Confirm that the alarm is true by checking the load percent indicated on the LCD panel to
determine which phase is being overloaded.
Unit Overload
2. If the alarm is true, measure the actual output current to verify that the indications are valid.
Disconnect unnecessary load and ensure the safety. In a parallel system, a severe load
sharing error can also leads to the alarm.
Contact Liebert Services at 800-543-2378 for assistance.
The UPS parallel system is confirmed to overload when the total load arises above 105% nominal
rating for the set basic number of UPSs. The alarm automatically resets once the overload
condition is removed.
1. Confirm that the alarm is true by checking the system load percent indicated on the LCD
System Overload
panel to determine which phase is being overloaded.
2. If the alarm is true, measure the actual output current to verify that the indications are valid.
Disconnect unnecessary load and ensure the safety. In a parallel system, a severe load
sharing error can also leads to the alarm.
The UPS is confirmed to overload and the overload times out.
Note 1: The highest loaded phase will indicate overload timing-out first.
Note 2: When the timer is active, then alarm “unit overload” should also be active as the load is
above nominal.
Note 3: When the timer has expired, the inverter Static Switch is opened and the load transferred
Unit Overload Timeout to bypass. The inverter shutdown and will restart after 10 seconds.
Note 4: If the load decreases lower than 95% after 5 minutes, the system will transfer back to
inverter mode.
Confirm that the alarm is genuine by checking the load percent indicated on the LCD. If an
overload is indicated then check the load, and investigate any additional load connected prior to
the alarm (if applicable).
The phase sequence direction of bypass voltage is reversed.
Normally, the phase of Phase B lags 120 degrees behind Phase A, and the phase of Phase C
Bypass Phase Reversed lags 120 degrees behind Phase B.
Verify that the phase rotation of the bypass supply presented to the UPS is correct, and rectify it if
it is found to be in error. Contact Liebert Services at 800-543-2378 for assistance.
A transfer to bypass occurred due to a large step load. The UPS should recover automatically.
Load Impact Transfer
Turn on connected equipment in sequential order to reduce the step loading of the inverter.
The load is on bypass power due to excessive number of transfers that occurred within the last
hour.
Transfer Timeout
The UPS will recover automatically and will transfer the load back to inverter power within an
hour.
UPS working within a parallel system are not sharing load current correctly. Contact Liebert
Load Sharing Fault
Services at 800-543-2378 for assistance.

131 Liebert® APM™


Maintenance

Table 57 UPS status messages (continued)


Event Message Description / Suggested Action (if any)
Shut off inverter due to abnormal DC bus voltage.
DC Bus Abnormal
Contact Liebert Services at 800-543-2378 for assistance.
The whole paralleled UPS system transferred to bypass at the same time. This message will
System Transfer
appear on the UPS which passive transfer to bypass.
Rectifier, inverter and battery converter were shutdown because DC bus voltage is too high.
Check whether there is a fault in rectifier side. If no, then check whether overload occurs.
DC Bus Overvoltage
Restart the inverter after resetting the fault. If fault does not clear, contact Liebert Services at 800-
543-2378 for assistance.
The LBS setting is active. The UPS is acting as an LBS master or slave in a dual bus
LBS Active
configuration.
Battery ground fault from dry contact signal. Contact Liebert Services at 800-543-2378 for
Battery ground fault
assistance.
Inverter turned On
Manual Turn On via front panel
manually
Inverter turned Off
Manual Turn Off via front panel
manually
EPO Emergency Power Off
Transfer Confirm Interrupted Transfer Confirm
Transfer Cancel Interrupted Transfer is cancel
Unit Off Confirm Unit Turned Off Confirm
System Off Confirm System Turned Off Confirm
Fault Reset Fault Reset
Alarm Silence Alarm Silence
Turn On Fail Turn On Fail
Alarm Reset Audible Alarm Reset
Bypass Mode UPS in Bypass Mode
Normal Mode UPS in Normal Mode
Battery Mode UPS in Battery Mode
Output Disabled UPS Output Disabled
Maint. Disconnect Closed Maintenance Disconnect Closed
Reserved
Output Disconnect Open Output Disconnect Open
Battery Reverse Connect the battery again and check the wiring of batteries.
No Battery Check the battery and the wiring of batteries.
Auto start After UPS was shutdown at EOD, inverter auto starts when utility is restored.
BCB closed BCB closed from dry contact signal.
BCB open BCB open from dry contact signal.
Battery Float Charging Battery is float charging.
Battery Boost Charging Battery is boost charging.
Battery Discharging Battery is discharging.
Battery Period Testing Battery is period self-testing.
Batt. Capacity Testing Battery is capacity self-testing.
Batt. Maint. Testing Battery is maintenance self-testing.
Inverter in Setting Inverter is in parameter setting.
Rectifier in Setting Rectifier is in parameter setting.
Battery converter output voltage beyond limits or battery fuse failed. Battery converter shuts
Batt. Converter Fault
down. Battery backup not available.
Operation Invalid This record is registered following an incorrect operation.

Liebert® APM™ 132


Maintenance

Table 57 UPS status messages (continued)


Event Message Description / Suggested Action (if any)
Byp. Abnormal Shutdown Both bypass and inverter voltages unavailable. Load interruption.
Mains Neutral Lost AC Input mains reference neutral not detected.
Battery Room Alarm Environment in battery room needs attention.
Rec Flash Update Rectifier firmware is being updated.
Inv Flash Update Inverter firmware is being updated.
Monitor Flash Update Monitor firmware is being updated.
LBS abnormal LBS is abnormal.

133 Liebert® APM™


Technical Support / Service
Web Site
www.liebert.com
Monitoring
[email protected]
800-222-5877
Outside North America: +00800 1155 4499
Single-Phase UPS & Server Cabinets
[email protected]
800-222-5877
Outside North America: +00800 1155 4499
Three-Phase UPS & Power Systems
800-543-2378
Outside North America: 614-841-6598
Environmental Systems
800-543-2778
Outside the United States: 614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
While every precaution has been taken to ensure the accuracy Fax: +39 049 5841 257
and completeness of this literature, Liebert Corporation assumes no Asia
responsibility and disclaims all liability for damages resulting from use of
this information or for any errors or omissions.
29/F, The Orient Square Building
© 2014 Liebert Corporation F. Ortigas Jr. Road, Ortigas Center
All rights reserved throughout the world. Specifications subject to change Pasig City 1605
without notice. Philippines
® Liebert is a registered trademark of Liebert Corporation.
All names referred to are trademarks +63 2 687 6615
or registered trademarks of their respective owners. Fax: +63 2 730 9572
SL-25615_REV9_09-14

Emerson Network Power


Liebert
www.emerson.com

www.EmersonNetworkPower.com

You might also like