User Manual: Devicenet ™ Communication
User Manual: Devicenet ™ Communication
Communication User
Module
Manual
Catalog Number
0160-DN2
Firmware 3.xxx
TM
CONFORMANCE TESTED
READY
FAULT
COMM
Important User Information Because of the variety of uses for the products described in this publi-
cation, those responsible for the application and use of this control
equipment must satisfy themselves that all necessary steps have been
taken to assure that each application and use meets all performance
and safety requirements, including any applicable laws, regulations,
codes and standards.
• Identify a hazard.
• Avoid the hazard.
• Recognize the consequences.
Important: Identifies information that is critical for successful appli-
cation and understanding of the product.
Summary of Changes
Summary of Changes
Bulletin 160-DN2 version 3.xxx Features and enhancements in the 160-DN2 module that are different
Software Enhancements than those in the 160-DN1 module include:
Compatibility with Bulletin 160 drives Bulletin 160 (Series A, B, and C) drives can be connected to a
(Series A, B, and C) DeviceNet network.
Ability to Create Electronic Data Sheets Configuration tools, such as DeviceNet Manager, can create an
Electronic Data Sheet (EDS file) for the 160 SSC drive and 160-DN2
module.
Added Parameter Object This object describes the parameters in the 160 SSC drive and
160-DN2 module.
Added Parameter Group Object This object describes the parameter groups associated with the
160 SSC drive and 160-DN2 module.
New and Revised Chapters to The bulletin 160-DN2 DeviceNet Communication Module User
this Manual Manual, Publication 0160-5.18, is a new manual. It is, however,
similar to the 160 DeviceNet Communication Module User Manual,
Publication 0160-5.5. The main differences can be found in the
following chapters:
Troubleshooting Chapter 7
Understanding the COMM LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
Understanding the FAULT LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-3
Specifications Appendix A
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Environmental . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Mechanical. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Index
Notes:
Who Should Use This Manual? This manual is intended for qualified personnel. To make efficient use
of the Communication Module, you must be able to program and
operate serial communications devices, as well as have an under-
standing of the parameter settings and functions of the Bulletin 160
SSC drive.
Conventions Parameter numbers and names are shown in bold typeface and follow
the format PXX - [*] where P denotes parameter, XX denotes the
parameter number, and * represents the parameter name. For exam-
ple, P01 - [Output Frequency].
Places to the right of the decimal do not affect content of this manual.
Manual Organization
Chapter Title Contents
Manual objectives, audience, vocabulary,
Preface Using This Manual manual conventions and organization, safety
precautions, and DeviceNet compatibility.
Module description, LEDs, DIP switches, and
1 Product Overview
DeviceNet compatibility.
Quick Start for Experienced Communication Module features, configura-
2
Users tion, and diagnostics.
Installation, switch configuration, cabling, and
3 Installation and Wiring
removal.
4 Modes of Operation Power-up and modes of operation.
DeviceNet Parameter EDS file parameters, Bulletin 160 SSC inter-
5
Descriptions face, product codes.
Mac IDs, Manager software, configuration,
Using 160-DN2 with
6 input/output assemblies, network control,
DeviceNet Scanner
scan list, ladder program, explicit messaging.
7 Troubleshooting LED indications and fault descriptions.
Environmental, electrical, and communica-
Appendix A Specifications
tion specifications.
Appendix B DeviceNet Information DeviceNet message types and object classes.
Safety Precautions
DeviceNet Compatibility The 160-DN2 Communication Module is intended for use only with
Bulletin 160 SSC Series A, Bulletin 160 SSC Series B, and Bulletin
160 SSC Series C (FRN 7.03 and later) devices. Bulletin 160 SSC
(Series C) devices must use a 160-DN2 Communication Module to
connect to a DeviceNet network. Bulletin 160 SSC (Series A and B)
devices can use either a 160-DN2 or 160-DN1 Communication Mod-
ule to connect to a DeviceNet network.
Replacing a 160-DN1 with a You can replace a 160-DN1 Communication Module with a 160-DN2
160-DN2 Communication Module on any 160 SSC (Series A and Series B)
drive. To do so, you will need to create an EDS file for the new 160-
DN2 Communication Module and map the module to the network.
Chapter 6, Using 160-DN2 with DeviceNet Scanner, provides detailed
instructions on how to perform these tasks.
CONFORMANCE TESTED
TM Ready LED - GREEN when drive is powered up ➀
➀ See Chapter 4, Modes of Operation, and Chapter 7, Troubleshooting, for detailed operation.
The Communication Module has one eight position DIP switch for setting the
DeviceNet Node Address and Baud Rate. DIP switches are located on the
rear of the module and are only accessible when the module is removed
from the Bulletin 160 SSC drive.
If you have any questions or are unfamiliar with the terms used or
concepts presented in the procedural steps, always read the refer-
enced chapters and other recommended documentation before trying
to apply the information.
Required Tools and Equipment Have the following tools and equipment ready:
Procedures
# Steps Reference
1. Review Attention statements in the Preface.
2. Check the contents of shipping box.
Unpack the shipping box making sure that the contents include:
• Bulletin 160 DeviceNet module (Catalog Number 160-DN2).
• 10-pin linear plug with probe holes and jack screws.
• Bulletin 160 DeviceNet Communication Module User Manual.
If the contents are incomplete, call your local Allen-Bradley representative for assistance.
Ensure that the drive is correctly installed and wired. Publication
3. (Stop Input (TB3-7, TB3-8) must be jumpered together 160-SSC
to start drive.) User Manual
DeviceNet
Ensure that the DeviceNet master and network are
Cable System Planning
4. installed and functioning in accordance with
and Installation Manual
DeviceNet standards.
(Pub. 1485-6.7.1)
Remove Program Keypad Module or Ready/Fault Indi- Chapter 3
5.
cating Panel from the drive. (Installation)
Set the DeviceNet Module’s node address and baud Chapter 3
6.
rate. (Installation)
Set the DIP Switches at the back of the module. Switches 1
through 6 control node address and switches 7 and 8 control baud
rate.
Chapter 3
7. Install the DeviceNet module on the drive.
(Installation)
Wire the DeviceNet connector and plug it into the Chapter 3
8.
drive. (Installation)
Chapter 3
9. Power up the drive and the network.
(Installation)
Important: When power-up occurs, the COMM (communication Chapter 4
status) LED flashes green for 1/4 second, red for 1/4 second, and (Modes of Operation)
then goes blank while the Communication Module finishes its ini- Chapter 7
tialization. If the COMM LED goes red, there is a problem. (Troubleshooting)
Chapter 6
(Using 160-DN2 with
10. Create the Electronic Data Sheet (EDS) file.
DeviceNet Scanner, page
6-3)
Create the EDS file in accordance with the DeviceNet software or DeviceNet Software
hardware configurator that you are using to configure the Commu- or Hardware
nication Module (see Chapter 5 for EDS file descriptions). Configurator Manual
Chapter 6
Configure the Bulletin 160 SSC drive for DeviceNet so
(Using 160-DN2 with
11. the drive can accept speed reference and control logic
DeviceNet Scanner, page
via the network.
6-3 to 6-9)
Use configuration software such as DeviceNet Manager or hard-
ware such as DeviceView Hand Held DeviceNet Configurator.
Chapter 6
Configure the DeviceNet Scanner to recognize the (Using 160-DN2 with
12.
Bulletin 160 SSC drive. DeviceNet Scanner, page
6-10 to 6-16)
Use DeviceNet Manager to configure the DeviceNet Scanner’s
“Scan List” to recognize the Bulletin 160 SSC drive.
Required Tools and Equipment Before installing and configuring the 160-DN2 Communication Mod-
ule, ensure that the contents of the shipping box include:
• Bulletin 160-DN2 module (Catalog Number 160-DN2).
• 10 pin linear Plug (Part Number 1787-PLUG10R).
• Bulletin 160-DN2 DeviceNet Communication Module User Man-
ual (Part Number 193557).
In addition, you will need to supply the following:
• A small blade screwdriver.
• DeviceNet configuration software or hardware device.
• DeviceNet thick cable or thin cable. Refer to the DeviceNet Prod-
uct Overview, Publication DN-2.5, for details and part numbers.
EMC Directive 89/336/EEC This product complies with Electromagnetic Compatibility (EMC)
Compliance Directive 89/336/EEC when conforming with the following installa-
tion requirements:
Low Voltage Directive 73/23/EEC This product complies with Low Voltage Directive 73/23/EEC when
Compliance conforming with the following installation requirements:
Removing Program Keypad Module Before installing the Communication Module, it may be necessary to
or Ready/Fault Panel remove a previously installed module such as a Program Keypad
Module or Ready/Fault panel.
Figure 3.1
Removing Program Keypad Module
Insert a small screw driver into slot, pry Program Keypad Module
back, and pivot module out. Avoid bending
or twisting the contact pins located
underneath the center portion of the
Understanding Module The DeviceNet Communication module’s DIP switch settings deter-
Configuration Switches mine:
Figure 3.2
DIP Switches on Rear of Module
DIP Switch ON = 1
Factory Settings OFF = 0
1 2 3 4 5 6 7 8
NO
Setting the DeviceNet Node DIP switches 6 through 1 set the module’s node address using binary
Address addressing. The factory default setting is DeviceNet address 63.
Figure 3.3
Setting the Node Address
DeviceNet Address
8 7 6 4 5 3 2 1 000000 - 111111 (0 to 63)
ON = 1
OFF = 0
N O
DeviceNet Switch Settings DeviceNet Switch Settings DeviceNet Switch Settings DeviceNet Switch Settings
Address➀ 6 <---- 1 Address 6 <---- 1 Address 6 <---- 1 Address 6 <---- 1
Setting the Baud Rate Dip switches 7 and 8 set the baud rate at which the Communication
Module communicates on the network. The factory default setting for
baud rate is 125K BPS.
Figure 3.4
Setting the Baud Rate
ON = 1
OFF = 0
N O
125 kBPS 0 0
250 kBPS 0 1
500 kBPS 1 0
Set by DeviceNet 1 1
Parameter 104
Installing the Communication After setting the DIP switches, secure the Communication Module to
Module the drive by following these steps:
1. Insert the module, ensuring that the pins on the back of the mod-
ule line up with the drive’s expansion port.
2. Press down on the module until it is fully seated. The module is
fully seated when its sides are resting on the drive’s face.
3. Press down on the latch until it snaps into place.
Figure 3.5
Installing the Communication Module
Expansion Port
Drive’s
Face
Wiring the DeviceNet Connector Follow these recommendations for communications wiring:
The Communication Module receives power and communications through the DeviceNet connector.
DeviceNet cable wires connect to the DeviceNet plug as shown in the following table.
Red
5
White
4
Bare
3
Blue
2
Black
1
Connecting the DeviceNet Drop Follow these steps to connect your module DeviceNet drop line:
Line to the Module
1. Turn off the network power supply.
Removing Communication Module If you need to reconfigure the Communication Module DIP switches,
From a Drive you must remove the Communication Module from the drive.
Powering Up the Drive After you have installed the Communication Module, apply power to
the drive and to the Network. The COMM LED should flash green or
turn solid green. If it does not, refer to Chapter 7, Troubleshooting.
1. When power-up occurs, the COMM LED flashes green for 1/4
second, red for 1/4 second, and then goes blank while the Com-
munication Module finishes its initialization.
2. Performs power-up initialization.
3. Reads and stores the DIP switch settings.
4. Performs a duplicate node address check to verify that another
node is not assigned the same DeviceNet address as the Commu-
nication Module.
If the power-up or reset is successful, the Communication Module
enters the run mode and the LED flashes green or turns solid green.
Run Mode
After a successful power-up or reset, the Communication Module
enters the run mode and operates as a slave device to a master device.
In run mode, the Communication Module:
Error Mode
If the Communication Module detects an error, the COMM LED is
affected. Errors are critical or noncritical, and are summarized below
DeviceNet Parameters The communication module contains a set of parameters that are used
to define how the module will interact with the Bulletin 160 SSC and
with the DeviceNet network. These parameters may be used to set the
module’s address, baud rate, or I/O data format. Parameters may also
be read to attain status from the module.
Electronic Data Sheet Electronic Data Sheet (EDS) files are specially formatted ASCII files
that provide all of the information necessary for a configuration tool
such as the DeviceNet Manager (Cat. No. 1787-MGR), to access and
alter the parameters of a device. The EDS file contains information on
the number of parameters in a device and how those parameters are
grouped together. Information about each parameter is contained in
this file such as parameter min, max, and default values, parameter
data format and scaling, and the parameter name and units.
Parameters and EDS File Users create EDS files for the Bulletin 160 using software applica-
tions such as DeviceNet Manager. (See Chapter 6, Using 160-DN2
with DeviceNet Scanner, for instructons on creating an EDS file.) An
EDS file is used to define all the parameters in the Bulletin 160 and in
the Communication Module. This EDS file is used to create a public
interface to the drive via DeviceNet. Configuration tools such as
DeviceNet Manager use EDS files to present parameters to the user.
Through DeviceNet Manager, operators can perform configuration
functions on the 160 SSC drive via DeviceNet by changing the values
associated with individual parameters.
Parameters and EDS File Parameter values may be read or written via DeviceNet. Writing a
(Continued) value to a parameter may configure drive operations such as the accel-
eration or deceleration rates. Writing a value to a parameter may also
configure DeviceNet operations such as which input or output assem-
blies are to be used for polled I/O communications with a master.
Reading a parameter value gives you status information.
Bulletin 160 SSC Interface This parameter set contains all of the parameters described in the Bul-
letin 160 SSC User Manual, plus a few extra parameters to configure
the operation of the Communication Module on the DeviceNet net-
work.
Product Codes and EDS Files Bulletin 160 SSC drives are available in Analog Signal Follower and
Preset Speed models. Each model supports a slightly different set of
parameters (in general the Preset Speed model contains extra parame-
ters for setting up preset speeds). Therefore each drive model uses an
EDS file specific to that model. Configuration tools such as
DeviceNet Manager use “product codes” to identify which EDS file
to use for a given drive model. Table 6 summarizes the various prod-
uct codes. Note that each product code is based on the model, horse-
power, voltage, and the firmware version of the drive.
Table 6: EDS Files for Bulletin 160 using a 160-DN2 version 3.000 or later
Drive Rating
Product Code Drive Model Voltage EDS File Name
kW (HP)
Drive Rating
Product Code Drive Model Voltage EDS File Name
kW (HP)
Examples:
4.eds refers to Bulletin 160 with firmware version 4.04 or 4.07
5.eds refers to Bulletin 160 with firmware version 5.00 to 5.99
6.eds refers to Bulletin 160 with firmware version 6.00 to 6.99
7.eds refers to Bulletin 160 with firmware version 7.00 or later
It is important that the correct EDS file for the drive model, horse-
power, and voltage be used. If an incorrect one is used, the configura-
tion tool may be unable to set up the drive.
Bulletin 160 SSC Interface The Bulletin 160 SSC Interface parameters are grouped together logi-
Parameters cally. The following sections provide information about the Bulletin
160 SSC Interface parameter groups:
• DeviceNet Parameters.
• Drive Display Parameters.
• Drive Program Parameters.
The following tables summarize the Bulletin 160 SSC Interface. For
more detailed information on the Display Group and Program Group
parameters, refer to the Bulletin 160 SSC User Manual.
DeviceNet Parameters Use the following parameters to configure and monitor the DeviceNet
Network Interface. These parameters are unique to drives equipped
with the DeviceNet Communication Module.
Object Mapping
Parameter Min./Max. Factory
Name and Description (Class-Instance-
Number Range Default
Attribute)
Drive Display Parameters Below is a brief description of the Bulletin 160 SSC Interface Display
(Read Only) Group parameters. Refer to the Bulletin 160 SSC User Manual for
more detailed information on these parameters.
Object Mapping
Parameter
Parameter Name (Class-Instance- Description Units
Number
Attribute)
01 [Output Frequency] 0xB3-1-1 Frequency at TB2 terminals T1, T2, T3. 0.1 Hz
02 [Output Voltage] 0xB3-1-2 Voltage at TB2 terminals T1, T2, T3. 1 Volt
03 [Output Current] 0xB3-1-3 Current at TB2 terminals T1, T2, T3. 0.01 Amperes
04 [Output Power] 0xB3-1-4 Power at TB2 terminals T1, T2, T3. 0.01 kW
05 [Bus Voltage] 0xB3-1-5 DC Bus voltage level. 1 Volt
06 [Cmd Frequency] 0xB3-1-6 Commanded Frequency. 0.1 Hz
07 [Present Fault] 0xB3-1-7 Coded last fault number. Numeric Value
08 [Heatsink Temp] 0xB3-1-8 Temperature of the drive heatsink. 1 degree C
09 [Drive Status] 0xB3-1-9 Status of drive in binary coded format. Important: Parameter 9 Binary Number
shown below does not match what is published in the Bulletin 160
SSC User Manual. The DeviceNet binary code for Parameter 9 is:
Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Running
Forward
Accel
Decel
Drive
Faulted
Reverse
Latched
A-B Internal
Use Only
At
Frequency
Reference
10 [Drive Type] 0xB3-1-10 Used by Allen-Bradley field service personnel. Numeric Value
11 [Firmware Version] 0xB3-1-11 Version of drive firmware used. Numeric Value
12 [Input Status] ➀ 0xB3-1-12 Open (0) Closed (1) state of Drive’s discrete inputs. Binary Number
Important: Parameter 12 shown below does not match what is pub-
lished in the Bulletin 160 SSC User Manual. The DeviceNet binary
code for Parameter 12 is:
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Preset 1
Input
Preset 2
Input
Preset 3
Input
Unused
Reverse
Stop
Start
Not Used
13 [Power Factor Ang] 0xB3-1-13 Angle (electrical degrees) between V and I. 0.1 degree C
14 [Memory Probe] 0xB3-1-14 Used by Allen-Bradley service personnel. Numeric Value
➀ For preset speed model, this parameter contains the data from parameter 15 in the SSC drive due to conflicting parameter numbers with DeviceNet
specific parameters.
SW2
SW3
Unused
16 [Analog Input] 0xB3-1-16 The analog input as a percent of full scale. 0.1%
17 [Fault Buffer 0] 0xB3-1-17 Most recent fault. Numeric Value
18 [Fault Buffer 1] 0xB3-1-18 Second most recent fault. Numeric Value
19 [Fault Buffer 2] 0xB3-1-19 Third most recent fault. Numeric Value
Drive Program Parameters Below is a brief description of the Bulletin 160 SSC Interface Pro-
gram Group parameters. Refer to the Bulletin 160 SSC User Manual
for more detailed information on these parameters.
Object Mapping
Parameter
Parameter Name (Class-Instance- Description Units
Number
Attribute)
30 [Accel Time 1] 0xB3-1-30 Time to ramp from 0 Hz to maximum frequency. 0.1 Seconds
31 [Decel Time 1] 0xB3-1-31 Time to ramp from maximum frequency to 0 Hz. 0.1 Seconds
32 [Minimum Frequency] 0xB3-1-32 Lowest continuous output frequency. 1 Hz
33 [Maximum Frequency] 0xB3-1-33 Highest continuous output frequency. 1 Hz
34 [Stop Mode Select] 0xB3-1-34 Determines stop mode used. Numeric Value
47 [Output Configure] 0xB3-1-47 Configures TB3 output relay functionality. Numeric Value
48 [Output Threshold] 0xB3-1-48 Used in conjunction with P47 - [Output Configure]. Numeric Value
49 [PWM Frequency] 0xB3-1-49 Carrier frequency for PWM output waveform. 0.1 kHz
50 [Restart Tries] 0xB3-1-50 Times drive will attempt to reset a fault. Numeric Value
51 [Restart Time] 0xB3-1-51 Time between restart attempts. 0.1 Seconds
52 [DB Enable] 0xB3-1-52 Enables/disables dynamic braking. Numeric Value
53 [S-Curve] 0xB3-1-53 Enables a fixed shape S-curve. Numeric Value
80 [Stall Disable] 0xB3-1-80 Amount of time that the drive must be in a stall condition Numeric Value
before it causes a stall fault.
81 [Proc Kp Gain] 0xB3-1-81 Proportional gain used by the PI regulator. This parameter is Numeric Value
active when P46 - [Input Mode] setting 9 is used.
82 [Proc Ki Gain] 0xB3-1-82 Integral gain used by the PI regulator. This parameter is Numeric Value
active when P46 - [Input Mode] setting 9 is used.
83 [Proc Reference] 0xB3-1-83 Set point value to which PI control will regulate. This parame- Numeric Value
ter is active when P46 - [Input Mode] setting 9 is used.
84 [PI Dead Band] 0xB3-1-84 The PI control will ignore errors less than this value. This Numeric Value
parameter is active when P46 - [Input Mode] setting 9 is
used.
Notes:
The 1747-SDN Scanner for the SLC 500 is used in the examples in
this manual, but the concepts demonstrated in the examples apply to
the 1771-SDN Scanner for the PLC 5 as well.
Needed Tools The following tools are needed to complete this chapter:
Example Network This chapter will illustrate the steps needed to configure the following
simple DeviceNet network.
Set Device MAC ID’s Every device on a DeviceNet network must have a unique MAC ID
between 0 and 63. Setting the MAC ID on the 1747-SDN is done via
the network using the DeviceNet Manager Software. Setting the
MAC ID for the 160-DN2 may be done via DIP switches or via the
network using the DeviceNet Manager Software. For directions on
setting the 160-DN2 MAC ID, refer to Chapter 3.
Invoke Manager Software and “Go Choose “Set Up Online Connection” from the “Utilities” menu. The
Online” following screen appears:
Click the “OK” button to establish a connection to the network for the
DeviceNet Manager software.
Create the EDS File After invoking the DeviceNet Manager Software, choose “Create
EDS Stub” from the “Utilities” menu. The following screen appears:
Create the EDS File (Continued) Click the “Load from Device” button. The following screen appears:
Type the node address of the 160-DN2, and then click the “OK” but-
ton. DeviceNet Manager creates the EDS file. When it finishes the
EDS file, the “Create EDS Stub” screen reappears.
Select “160CTRL.BMP” and then click the “OK” button. The “Cre-
ate EDS Stub” screen reappears. Click the “OK” button to save the
EDS file, and then click the “OK” button in the DeviceNet Manager
prompt that appears to ask if you want to write the EDS file to the
EDS library. The following screen then appears:
If desired, enter a description for the EDS file. Click the “OK” button
to save the description and the new EDS file.
Perform Network Who Choose “Network Who” from the “Who” menu. The following screen
appears:
Invoke 160 Configuration Screen Choose the Bulletin 160 by double clicking on the Bulletin 160
Image. This invokes the 160 configuration screen and allows you to
change setup parameters in the drive. The following screen appears:
Pick Input and Output Assemblies The DeviceNet Specification defines Assembly Objects as objects
for the Bulletin 160 that “bind attributes of multiple objects to allow data to or from each
object to be sent over a single connection.” The Bulletin 160 uses
Assembly Objects to send data to and from a Scanner over an IO con-
nection. The terms “Input” and “Output” are defined from the scan-
ner’s point of view. Bulletin 160 Output Assemblies are defined as the
information that is “output” by the scanner and consumed by the Bul-
letin 160. Input Assemblies are the status information that is con-
sumed by the scanner or are the scanner’s “input.”
The Bulletin 160 allows the user to choose between various Input and
Output Assemblies, thereby choosing the data format of the messages
that are passed back and forth between the 160 and the scanner on the
IO connection. The Assemblies that are supported are numbered and
are part of a DeviceNet defined “Motor Control Hierarchy.” This
allows drives to directly replace motor starters or contactors on a net-
work without the need to reprogram the scanner. Information on the
data format of all Bulletin 160 Assemblies is given in Appendix B,
page B-23 to B-28.
DeviceNet parameters P107 - [Output Assembly] and P108 - [Input
Assembly] must be programmed with the proper output or input
assembly. Refer to page 5-5 for possible selections.
The choice of which Input and Output Assembly to use should be
based on what sort of information is appropriate in a particular sys-
tem. See Appendix B for a description of the various Input and Output
assemblies. In the example system, we use Output Assembly 21 and
Input Assembly 71. The data formats for these Assemblies are given
below:
Table 1: Assembly 21 Data Format
(Reversing Speed Control Output Assembly)
Pick Input and Output Assemblies To choose these Assemblies, first select the “DNet Config” parameter
for the Bulletin 160 (Continued) group as shown below:
➊ ➋
Enter Assembly Number “21” and click the “Save to Device” button.
Repeat the above steps for the P108 - [Input Assembly] except set
the value to “71.”
Enable Network Control The Bulletin 160 must be configured to accept commands from the
network. This is done by configuring the “Input Mode” parameter. To
do this, select the “Program” parameter group as shown below:
➊
➋
Enable Network Control For the new input mode to take effect, P56 - [Reset Functions] must
(Continued) be modified. Double click on P56 - [Reset Functions]. The following
screen appears:
➊
➋
Select “Reset Input Mode” and click the “Save to Device” button.
When the save is done, close the window by clicking the “OK” but-
ton.
Configure the 160 to Accept Speed The Bulletin 160 must be configured to accept its speed commands
Commands From the Network from the network. This is done by changing P59 - [Frequency
Select]. Double click on the P59 - [Frequency Select] parameter.
The following screen appears:
➋
➊
Select “Internal Freq” and click the “Save to Device” button. When
the save is done, close the window by clicking the “OK” button.
Invoke Scanner Configuration Double Click on the 1747-SDN Scanner in the “Network Who”
Screens screen to configure the SDN Scanner. The following Scanner configu-
ration screen appears:
Set Up the Scan List Click the “Edit Scan List...” button. The following screen appears:
Set Up the Scan List (Continued) To add the Bulletin 160 onto the 1747-SDN scan list, click the “Who”
button in the “Add Devices From” box. The following screen appears:
➌
In this screen, click the Bulletin 160 and drag it onto the 1747-SDN
image. Click the “OK” button and the Bulletin 160 appears in the
1747-SDN scan list:
Set Up the Scan List (Continued) Edit the I/O data by either clicking Bulletin 160 in the scan list and
clicking the “Edit I/O Parameters” button or by double clicking on the
Bulletin 160 in the scan list. The following screen appears:
➋ ➌
➊
Polled: Enabled
Poll Rx Size: “4 Byte”
Poll Tx Size: “4 Byte”
Poll Rate: “Every Scan”
Set Up the Scan List (Continued) Now the scan list window should appear as follows:
Map Each Device in the Scan List Data from IO messages may be mapped to the SLC’s discrete I/O area
or to an I/O area located in the “M0” and “M1” files. This mapping
determines where a ladder program can find the data that is passed
over the network. We use the discrete area in our example.
To map the data, click the “Datatable Map...” button under the Scan
List Tools window. The following Datatable Map screen appears:
Map Each Device in the Scan List Select “Data Entry” for the display mode. Since we are mapping to
(Continued) the discrete area, choose “Discrete” from the “Map Data To:” list box
as shown below:
➍
➐
➌
➎ ➏
➋
Map Each Device in the Scan List Next map 32 bits of the Bulletin 160 output message to O:1.1. First
(Continued) click the “Output” radio button in the Data Map section of the win-
dow. Then choose “Discrete” from the “Map Data From:” list. From
the “Map Data To:” list choose “Poll message”. In the “Map Data
To:” section of the window, choose O:1.1, Bit 0, 32 bits of data, then
click the “Apply Segment” button. The Datatable map should appear
as follows:
➊ ➏
➌
➋
➐ ➍ ➎
Map Each Device in the Scan List Finally, we must save the scan list and datatable map to the scanner.
(Continued) This is done by clicking the “Save To SDN...” button. The following
screen appears:
Choose the “All Records” button, and click “OK”. When the scan list
and datatable map have been loaded, you are informed that the scan-
ner will be unavailable for a brief period of time following the down-
load as follows:
Program the Ladder The example ladder program in Figure 6.1 on page 6-17 accomplishes
Run Forward/Run Reverse control and speed command of the Bulle-
tin 160.
This example SLC program will control the Bulletin 160 to run for-
ward to 60Hz, once it reaches 60 Hz, the SLC will reverse the Bulle-
tin 160 to 60Hz, once running in reverse at 60Hz the SLC will start
this sequence over.
This rung sends a run reverse command to the drive when the drive is running forward and is at speed.
0005 END
Important: The 1747-SDN scanner card is located in slot 2 of the SLC rack for this example.
Important: The Bulletin 160SSC drive Stop Input (TB3-7, TB3-8) must be jumpered together to start
the drive.
Explicit Messaging Explicit Messaging is a way of allowing the user to configure and
monitor a slave device’s parameters on the DeviceNet network. This
form of messaging is performed by copying data to and from the SLC
processor M0 and M1 file. Explicit Messaging can only be done by
the SLC processor to slave devices that are mapped in the scanner
module’s scan list.
How it Works
There are five steps to the Explicit Messaging process. The following
is a brief description of what happens during this process.
How to Format the Explicit There are ten 32-word transaction blocks within the scanner module
Message Transaction Block reserved for Explicit Message Program Control. These transaction
blocks accommodate both downloading of Explicit Message
Requests and the uploading of Explicit Message Responses. The
scanner module can accommodate one request or response for each
transaction block. Each transaction block must be formatted as shown
below.
Request Response
15 0 15 0
TXID command TXID status
port size port size
service MAC ID service MAC ID
class
instance service response
attribute data
service data
Program the SLC to Run Explicit The example ladder program (Figure 6.2, page 6-21) can be used to
Messaging do explicit programing from the SLC 500. This ladder program will
allow the SLC 500 to use Explicit Messaging to read and write
parameters to a Bulletin 160 drive. There are three steps to executing
this program:
Program the SLC to Run Explicit Data Format for a Read and Write of a Parameter
Messaging (Continued)
Request Data for Read of Parameter 30 (Accel Time)
N10 address
address 0 1 2 3 4 5 6 7 8 9
N10:0 0101 0006 0E01 00B3 0001 001E 0000 0000 0000 0000
N10:10 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000
N10:20 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000
N10:30 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000
Response Data for Read of Parameter 30
N11 address
address 0 1 2 3 4 5 6 7 8 9
N11:0 0101 0002 8E01 00B3 0000 0000 0000 0000 0000 0000
N11:10 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000
N11:20 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000
N11:30 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000
Request Data for Write to Parameter 30
N10 address
address 0 1 2 3 4 5 6 7 8 9
N10:0 0101 0008 1001 00B3 0001 001E 0001 0000 0000 0000
N10:10 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000
N10:20 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000
N10:30 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000
Response Data for Write to Parameter 30
N11 address
address 0 1 2 3 4 5 6 7 8 9
N11:0 0101 0000 9001 0000 0000 0000 0000 0000 0000 0000
N11:10 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000
N11:20 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000
N11:30 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000
This rung moves the Explicit Message Request data from the SLC500 processor to the 1747-SDN.
Copy Request data from
Explicit Msg Request Generate Explicit the SLC to the SDN Scanner
enable bit Request Only Once. COP
N7:0 B3:0
Copy File
0000 OSR
0 0 Source #N10:0
Dest #M0:2.224
Length 32
This rung moves the response data from the 1747-SDN to the SLC500 processor when it is available.
Then a delete transaction from response queue is sent.
Copy Response data from
SDN Scanner to SLC
Explicit Msg Request Status Word - Explicit
enable bit Msg Available COP
N7:0 I:2
Copy File
0001 Source
0 15 #M1:2.224
Dest #N11:0
1747-SDN Length 32
Notes:
Figure 7.1
Module Front View
TM
CONFORMANCE TESTED
COMM LED
Description
Color State
None No DeviceNet power or initializing.
Red Solid Unrecoverable fault.
Red Flashing I/O connection has timed out.
Green Solid Normal operating state.
Device is allocated to a master.
Green Flashing Device is on-line but not allocated to a
master.
Understanding the COMM LED The COMM LED provides status information on Communication
Module operations. The table below shows how to use the LED to
detect and correct common operation problems.
None The Communication module is not receiving power from the Check DeviceNet power and cable connections and the
network. power connection on the DeviceNet terminal block.
Red Solid Diagnostics test failed on power-up/reset. Internal fault Cycle power to the drive and network. If the fault still exists,
exists. return the Communication Module for repair.
Red Solid Duplicate DeviceNet node address. Two nodes cannot have Reset DIP switches 1 through 6 using a valid address and
the same address. reset device.
OR
OR
Understanding the FAULT LED When the FAULT LED is Red, a drive fault is present. To view the
fault code, you must either view P7 - [Present Fault] or read the
value of Class 0x29 (Control Supervisor Object) Instance 1 Attribute
13 (Fault Code).
Fault
Fault Code Description Corrective Action
Indication
Fault
Fault Code Description Corrective Action
Indication
50 No DeviceNet 24 volt network power is not detected. Check DeviceNet connector at Communication Module.
Power Also, check network’s power supply.
51 DeviceNet Module DeviceNet Module EEPROM has invalid data. Reset to factory defaults P56 - [Reset Functions].
EEPROM Fault
52 DeviceNet Lost Polled I/O connection timed out. Check DeviceNet Master for correct operation (i.e., pow-
I/O Connection ered up, scanner online, etc.).
53 DeviceNet Unre- No communication is occurring. Fault occurs when dupli- Check DIP switch settings for proper baud rate and node
coverable Fault cate node address exists or wrong baud rate is set. address.
54 DeviceNet Trans- A transmit timeout occurred. Power drive off and then cycle power on.
mit Fault
55 Forced Fault Control Supervisor Object (Class Code 0x29) attribute 17 Clear fault.
was set to 1.
56 Drive The 160-DN2 is not compatible with the 160 SSC firm- Replace the drive.
Incompatibility ware version (e.g., Series C FRN 7.02)
Fault
1100 Max Retries Fault Drive failed to reset fault within the max retries specified. Repair system fault.
2213 Power Test Fault detected during initial start sequence. Check drive wiring. Check motor wiring. Reset drive to
factory defaults.
2220 Over Current Overcurrent detected in hardware trip circuit. Check short circuit at the drive output or excessive load
conditions at the motor.
2331 Phase U Phase to ground fault detected between drive and motor Check wiring between drive and motor. Check motor for
phase U. grounded phase.
2332 Phase V Phase to ground fault detected between drive and motor Check wiring between drive and motor. Check motor for
phase V. grounded phase.
2333 Phase W Phase to ground fault detected between drive and motor Check wiring between drive and motor. Check motor for
phase W. grounded phase.
2341 UV Short Excessive current has been detected between these two Check the motor and external wiring to the drive output
drive output terminals. terminals for a shorted condition.
2342 UW Short Excessive current has been detected between these two Check the motor and external wiring to the drive output
drive output terminals. terminals for a shorted condition.
2343 VW Short Excessive current has been detected between these two Check the motor and external wiring to the drive output
drive output terminals. terminals for a shorted condition.
3120 Power Loss DC Bus voltage remains below 85% nominal on power up Monitor incoming AC line for low voltage or line power
for longer than 5 seconds. interruption.
Fault
Fault Code Description Corrective Action
Indication
3210 Over Voltage DC Bus maximum voltage exceeded. Bus overvoltage caused by motor regeneration. Extend
the decel time, or install dynamic brake option or external
capacitor module. Check for high line voltage.
3220 Under Voltage DC Bus voltage fell below the minimum value while the Monitor incoming AC line for low voltage or line power
motor was running. interruption.
4310 Over Temperature Excessive heat detected. Clear blocked or dirty heat sink fins. Check ambient tem-
perature. Check for blocked or non-operating fan.
5300 Drive Reset Stop input not present. Check stop input at TB3 terminal 8.
6310 EEPROM Fault EEPROM has invalid data. Reset EEPROM.
6311 DeviceNet DevicNet Module EEPROM has invalid data. Reset to factory defaults using P56 - [Reset Defaults].
Module EEPROM
Fault
7121 Motor Stalled Motor has stalled. Motor load is excessive. Longer accel time or reduced load required.
7122 Motor Overload Internal electronic overload trip. Excessive motor load Reduce motor load.
exists.
7421 Reprogramming Occurs when drive parameters are reset to defaults. Clear fault.
Fault
7500 No DeviceNet 24 volt network power is not detected. Check DeviceNet connector at Communication Module.
Power Also, check network’s power supply.
7501 DeviceNet Lost Polled I/O connection timed out. Check DeviceNet Master for correct operation (i.e., pow-
I/O Connection ered up, scanner online, etc.).
7502 DeviceNet Unre- No communication is occurring. Fault occurs when dupli- Check DIP switch settings for proper baud rate and node
coverable Fault cate node address exists or wrong baud rate is set. address.
7503 DeviceNet Trans- A transmit timeout occurred. Power drive off, and then cycle power on.
mit Fault
7504 DN Forced Fault DeviceNet module forced a fault. Clear fault.
Notes:
Environmental
Ambient Temperature
Operating 0 to 50° C (32 to 122° F)
Storage -40 to 85° C (-40 to 185° F)
Relative Humidity 0 to 95% non-condensing
1.0 G Operational
Vibration
2.5 G Non-operational
15.0 G Operational
Shock
30.0 G Non-operational
Altitude 1,000 m (3,300 ft.) without derating
Communications
DeviceNet
Baud Rates 125, 250, 500 k BPS
Distance maximum 500 m (1640 ft.) @ 125 k BPS
200 m (820 ft.) @ 250 k BPS
100 m (328 ft.) @ 500 k BPS
Mechanical
Dimensions in Millimeters (inches)
Height 67.54 (2.68)
Width 70.0 (2.76)
Depth➁ 45.36 (1.79)
➀ Use this value to size the network current draw from the power supply.
➁ When installed on the 160 SSC drive, the communication module adds
approximately 21.40 mm (0.85 in.) to the overall depth.
DeviceNet Message Types As a group 2 slave device, the Communication Module supports the
following message types.
➀ Dip switches 7 and 8 must be set to “ON” position to enable Group 4 messaging (see pages
3-4 and 3-5).
Object Classes The Communication Module supports the following object classes.
Number of Instances: 2
3 Get Product Code UINT (Refer to tables on page 5-2 for product
codes.)
Revision Structure of: xxxxxxxxxx
4 Get Major Revision USINT X➀
Minor Revision USINT X➀
0 = Not owned
5 Get Status WORD
1 = Owned by master
6 Get Serial Number UDINT unique number
Product Name Structure of:
7 Get String Length USINT 32
ASCII String STRING “Bulletin 160 Preset 0.37kW 230V”
9 Get Configuration Consistency UINT Checksum
➀ E.g., firmware revision 5.01 would have a major revision of “5” and a minor revision of “1”.
Common Services
Implemented for:
Service Service
Code Name
Class Instance
Instance 1 Attributes:
➀ Allocation_byte
Bit 0 Explicit Messaging
Bit 1 Polled I/O
Bit 4 Change of state
Bit 5 Cyclic
Common Services
Implemented for:
Service Service
Code Name
Class Instance
0 = Nonexistant
1 = Configuring
1 Get State USINT 3 = Established
4 = Timed out
5 = Deferred delete
2 Get Instance Type USINT 0 = Explicit Message
3 Get Transport Class Trigger USINT 0x83
4 Get Produced Connection ID UINT 10xxxxxx100 xxxxxx = Node address
5 Get Consumed Connection ID UINT 10xxxxxx100 xxxxxx = Node address
6 Get Initial Comm. Characteristics USINT 0x22
7 Get Produced Connection Size UINT 7
8 Get Consumed Connection Size UINT 7
9 Get/Set Expected Packet Rate UINT Timer resolution of 10 msec.
1 = Auto delete
12 Get/Set Watchdog Action USINT
3 = Deferred delete
13 Get Produced Connection Path Length UINT 0
14 Get Produced Connection Path Null (no data)
15 Get Consumed Connection Path Length UINT 0
16 Get Consumed Connection Path Null (no data)
0 = Nonexistant
1 = Configuring
1 Get State USINT
3 = Established
4 = Timed out
2 Get Instance Type USINT 1 = I/O Message
3 Get Transport Class Trigger USINT 0x82
4 Get Produced Connection ID UINT 10xxxxxx100 xxxxxx = Node address
5 Get Consumed Connection ID UINT 10xxxxxx101 xxxxxx = Node address
6 Get Initial Comm Characteristics USINT 0x21
7 Get Produced Connection Size UINT 0 to 8
8 Get Consumed Connection Size UINT 0 to 4
9 Get/Set Expected Packet Rate UINT Timer resolution of 10 msec.
0 = Transition to timed out
12 Get/Set Watchdog Action USINT 1 = Auto delete
2 = Auto reset
13 Get Produced Connection Path Length UINT 3
[63hex][hex string] where [hex string] is the
14 Get/Set Produced Connection Path
input assembly number in hex
15 Get Consumed Connection Path Length UINT 3
[63hex][hex string] where [hex string] is the
16 Get/Set Consumed Connection Path
output assembly number in hex
0 = Nonexistant
1 = Configuring
1 Get State USINT
3 = Established
4 = Timed out
2 Get Instance Type USINT 1 = I/O Message
3 Get Transport Class Trigger USINT 0x82
4 Get Produced Connection ID UINT 10xxxxxx100 xxxxxx = Node address
5 Get Consumed Connection ID UINT 10xxxxxx101 xxxxxx = Node address
6 Get Initial Comm Characteristics USINT 0x21
7 Get Produced Connection Size UINT 0 to 8
8 Get Consumed Connection Size UINT 0 to 4
9 Get/Set Expected Packet Rate UINT timer resolution of 10 msec.
0 = transition to timed out
12 Get/Set Watchdog Action USINT 1 = auto delete
2 = auto reset
13 Get Produced Connection Path Length UINT 3
[63hex][hex string] where [hex string] is the
14 Get/Set Produced Connection Path
input assembly number in hex
15 Get Consumed Connection Path Length UINT 3
[63hex][hex string] where [hex string] is the
16 Get/Set Consumed Connection Path
output assembly number in hex
17 Get/Set Production Inhibit Time UINT 0
Common Services
Implemented for:
Service Service
Code Name
Class Instance
ARRAY of DeviceNet
Link Path
path
3 Get Segment type/port 6
Byte
Segment Address “20 B3 24 01 30 01”➀
path
4 Get Descriptor WORD ➀
Common Services
Implemented for:
Service Service
Code Name
Class Instance
Number of Instances: 3
Common Services
Implemented for:
Service Service
Code Name
Class Instance
Instance 1 Attributes
Access
Attribute ID Name Data Type Min/Max Units Default Description
Rule
Common Services
Implemented for:
Service Service
Code Name
Class Instance
Instance 1 Attributes:
Access
Attribute ID Name Data Type Min/Max Default Description
Rule
Figure B.6
State Transition Diagram
0 0 Stop NA
0 -> 1 0 Run RunFwd
0 0 -> 1 Run RunRev
0 -> 1 0 -> 1 No Action NA
1 1 No Action NA
1->0 1 Run RunRev
1 1->0 Run RunFwd
Instance 1 Attributes:
Common Services
Implemented for:
Service Service
Code Name
Class Instance
Instance 1 Attributes:
Common Services
Implemented for:
Service Service
Code Name
Class Instance
Instance 1 Attributes:
Access Data
Attribute ID Parameter Name Units Description
Rule Type
This Bulletin 160 SSC specific object implements all of the parameters in the 160 SSC parameter table as instance attributes of the object. For example,
attribute #1 corresponds to P01 - [Output Frequency]. This give you the ability to configure a drive via DeviceNet using attribute numbers that are pub-
lished as parameter numbers in the Bulletin 160 SSC User Manual. Important: Attributes 9 and 12 shown below do not match what is published in the
Bulletin 160 SSC User Manual.
01 Get [Output Frequency] UINT 0.1 Hz Frequency at TB2 terminals T1, T2, T3.
02 Get [Output Voltage] UINT 1 Volt Voltage at TB2 terminals T1, T2, T3.
03 Get [Output Current] UINT 0.01 Amperes Current at TB2 terminals T1, T2, T3.
04 Get [Output Power] UINT 0.01 kW Power at TB2 terminals T1, T2, T3.
05 Get [Bus Voltage] UINT 1 Volt DC Bus voltage level.
06 Get [Cmd Frequency] UINT 0.1 Hz Commanded frequency.
07 Get [Present Fault] USINT Numeric Value Coded last fault number.
08 Get [Heatsink Temp] USINT 1C Temperature of the drive heatsink.
09 Get [Drive Status] USINT Binary Number Status of drive in binary coded format.
10 Get [Drive Type] UINT Numeric Value Used by Allen-Bradley field service personnel.
11 Get [Control Version] UINT Numeric Value version of drive firmware used.
12 Get [Input Status] USINT Binary Number Open (0) Closed (1) state of drive’s discrete inputs.
13 Get [Power Factor Ang] UINT 0.1 Angle (electrical degrees) between V and I.
14 Get [Memory Probe] UINT Numeric Value Used by Allen-Bradley service personnel.
15 Get [Preset Status] USINT Binary Number Displays state of TB3 inputs.
16 Get [Analog Input] INT 0.1% The analog input as a percent of full scale.
17 Get [Fault Buffer 0] USINT Numeric Value Stores the most recent fault.
18 Get [Fault Buffer 1] USINT Numeric Value Stores the second most recent fault.
19 Get [Fault Buffer 2] USINT Numeric Value Stores the third most recent fault.
30 Get/Set [Accel Time 1] UINT 0.1 Seconds Time to ramp from 0 Hz to maximum frequency.
31 Get/Set [Decel Time 1] UINT 0.1 Seconds Time to ramp from maximum frequency to 0 Hz.
32 Get/Set [Minimum Freq] USINT 1 Hz Lowest continuous output frequency.
33 Get/Set [Maximum Freq] USINT 1 Hz Highest continuous output frequency.
34 Get/Set [Stop Mode Select] USINT Numeric Value Determines stop mode used.
47 Get/Set [Output Configure] USINT Numeric Value Configures TB3 output relay functionality.
48 Get/Set [Output Threshold] UINT Numeric Value Used in conjunction with P47 - [Output Configure].
49 Get/Set [PWM Frequency] USINT 0.1 kHz Carrier Frequency for PWM output waveform.
50 Get/Set [Restart Tries] USINT Numeric Value Times drive will attempt to reset a fault.
51 Get/Set [Restart Time] UINT 0.1 Seconds Time between restart attempts.
52 Get/Set [DB Enable] USINT Numeric Value Enables/Disables dynamic braking.
53 Get/Set [S-Curve] USINT Numeric Value Enables a fixed shape S-curve.
54 Get/Set [Clear Fault] BOOL Numeric Value Setting to 1 performs a fault reset.
55 Get/Set [Probe Address] UINT Numeric Value Used by Allen-Bradley service personnel.
56 Get/Set [Reset Functions] USINT Numeric Value Sets all parameters to their factory default.
57 Get/Set [Program Lock] BOOL Numeric Value Locks all program group parameters.
58 Get/Set [Internal Freq] UINT 0.1 Hz Digital Frequency setpoint.
59 Get/Set [Freq Select] BOOL Numeric Value Selects source of frequency command.
60 Get/Set [Zero Offset] INT Numeric Value Add or subtracts an offset to the analog input.
60 Get/Set [DN Preset Cmd] USINT Numeric Value Network preset command.
61 Get/Set [Preset Freq 0] UINT 0.1 Hz Sets command frequency when selected.
62 Get/Set [Preset Freq1] UINT 0.1 Hz Sets command frequency when selected.
63 Get/Set [Preset Freq 2] UINT 0.1 Hz Sets command frequency when selected.
64 Get/Set [Preset Freq 3] UINT 0.1 Hz Sets command frequency when selected.
65 Get/Set [Preset Freq 4] UINT 0.1 Hz Sets command frequency when selected.
66 Get/Set [Preset Freq 5] UINT 0.1 Hz Sets command frequency when selected.
67 Get/Set [Preset Freq 6] UINT 0.1 Hz Sets command frequency when selected.
68 Get/Set [Preset Freq 7] UINT 0.1 Hz Sets command frequency when selected.
69 Get/Set [Accel Time 2] UINT 0.1 Seconds Sets acceleration rate for presets 4 to 7.
70 Get/Set [Decel Time 2] UINT 0.1 Seconds Sets deceleration rate for presets 4 to 7.
71 Get/Set [IR Compensation] USINT 1% Adds a voltage to the output based on the torque current.
72 Get/Set [Slip Comp] USINT 0.1 Hz Compensates for the inherent slip of the motor.
73 Get/Set [Reverse Disable] BOOL Numeric Value Setting to 1 disables the reverse.
74 Get/Set [Analog Select] BOOL Numeric Value Selects between unipolar and bipolar analog input.
75 Get/Set [Analog Minimum] INT 0.1% Sets the percent of the analog input used to represent
P32 - [Minimum Freq].
76 Get/Set [Analog Maximum] INT 0.1% Sets the percent of the analog input used to represent
P33 - [Maximum Freq].
78 Get/Set [Compensation] BOOL Numeric Value Setting to 1 enables the compensation.
79 Get/Set [Current Trip] USINT 1% Percent above P43 - [Current Limit] at which the drive trips
immediately.
80 Get/Set [Stall Disable] USINT Numeric Value Time drive is in stall condition before causing a stall fault.
81 Get/Set [Proc Kp Gain] UINT Numeric Value Proportional gain used by the PI regulator.
82 Get/Set [Proc Ki Gain] UINT Numeric Value Integral gain used by the PI regulator.
83 Get/Set [Proc Reference] UINT Numeric Value Set point value to which PI control will regulate.
84 Get/Set [Proc Invert] USINT Numeric Value The PI control will ignore errors less than this value.
Instance 1 Attributes:
Access Data
Attribute ID Name Min/Max Default Description
Rule Type
➀ If set to a “9” P9 - [Drive Status] (of the SSC Interface Profile) goes in the low byte of the assembly field and P12 - [Input Status] (of the SSC Interface
Profile) goes in the high byte of assembly field.
Common Services
Implemented for:
Service Service
Code Name
Class Instance
Access
Attribute ID Name Data Type Min/Max Default Description
Rule
3 Get Data See instance data format for individual I/O assemblies on page B-24 through page B-28.
Access
Attribute ID Name Data Type Min/Max Default Description
Rule
See configuration assembly data formats for individual configuration assemblies on page B-29 through
3 Get/Set Data
page B-36.
Common Services
Implemented for:
Service Service
Code Name
Class Instance
Instance 100 Data Format (Reversing Speed Control Output Assembly (Hz)
This output assembly type is only available for use when Parameter #15 (Interface Select) is set to “0=Bulletin 160 SSC Interface.”
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Fault Reset RunRev RunFwd
1
2➀ Internal Frequency (0.1 Hz) (Low Byte)➂
3➀ Internal Frequency (0.1 Hz) (High Byte)➂
➀ If speed references are outside of their min/max limits, the the drive ignores them and previous speed reference will be maintained.
➁ 0 – 32000 RPM. RPM value is limited by the value programmed into P33 - [Maximum Frequency].
➂ 0 = 0 Hz, 2400 = 240.0 Hz. Frequency value is limited by the value programmed into P33 - [Maximum Frequency].
➀ Net Ref has higher priority than Net Control. Therefore, if Net Ref is set, presets are ignored.
➁ For Preset Speed Units: Net Ref determines if speed reference comes from the network or preset speeds.
The following table indicates the I/O Assembly Data Attribute map-
ping for Output Assemblies.
Word Byte
0 Value of parameter pointed to by Parameter Number 109 (Low Byte)
0
1 Value of parameter pointed to by Parameter Number 109 (High Byte)
2 Value of parameter pointed to by Parameter Number 110 (Low Byte)
1
3 Value of parameter pointed to by Parameter Number 110 (High Byte)
4 Value of parameter pointed to by Parameter Number 111 (Low Byte)
2
5 Value of parameter pointed to by Parameter Number 111 (High Byte)
6 Value of parameter pointed to by Parameter Number 112 (Low Byte)
3
7 Value of parameter pointed to by Parameter Number 112 (High Byte)
➀ 1 = forward, 0 = reverse
Word Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
1 0 Fault N/A Decel Accel Rot Dir➀ Cmd Dir➀ Running Enabled
1 Freq Source➂ Freq Source➂ Freq Source➂ Freq Source➂ Local➁ Local➁ Local➁ At Speed
2 2 Actual Speed Scale 0-32767➃
3 Actual Speed Scale 0-32767➃
3 4 Value of parameter pointed to by Parameter Number 111 (Low Byte)
5 Value of parameter pointed to by Parameter Number 111 (High Byte)
4 6 Value of parameter pointed to by Parameter Number 112 (Low Byte)
7 Value of parameter pointed to by Parameter Number 112 (High Byte)
➀ 1 = forward, 0 = reverse
Parameter Parameter
Config Num. Description Size Config Num. Description Size
Number Number
! ATTENTION: Changing this parameter value may cause unpredictable network conditions, resulting in equipment damage, personal injury, or death.
Ensure that you understand how changing this parameter affects your application.
Parameter Parameter
Config Num. Description Size Config Num. Description Size
Number Number
! ATTENTION: Changing this parameter value may cause unpredictable network conditions, resulting in equipment damage, personal injury, or death.
Ensure that you understand how changing this parameter affects your application.
Parameter Parameter
Config Num. Description Size Config Num. Description Size
Number Number
! ATTENTION: Changing this parameter value may cause unpredictable network conditions, resulting in equipment damage, personal injury, or death.
Ensure that you understand how changing this parameter affects your application.
Parameter Parameter
Config Num. Description Size Config Num. Description Size
Number Number
! ATTENTION: Changing this parameter value may cause unpredictable network conditions, resulting in equipment damage, personal injury, or death.
Ensure that you understand how changing this parameter affects your application.
Parameter Parameter
Config Num. Description Size Config Num. Description Size
Number Number
! ATTENTION: Changing this parameter value may cause unpredictable network conditions, resulting in equipment damage, personal injury, or death.
Ensure that you understand how changing this parameter affects your application.
Parameter Parameter
Config Num. Description Size Config Num. Description Size
Number Number
! ATTENTION: Changing this parameter value may cause unpredictable network conditions, resulting in equipment damage, personal injury, or death.
Ensure that you understand how changing this parameter affects your application.
Parameter Parameter
Config Num. Description Size Config Num. Description Size
Number Number
1 30 Accel Time 1 2 18 47 Output Configuration 1
2 31 Decel Time 1 2 19 48 Output Threshold 2
3 32 Minimum Freq 1 20 49 PWM Frequency 1
4 33 Maximum Freq 2 21 50 Restart Tries 1
5 34 Stop Mode Select !
1 22 51 Restart Time 2
Instance 192 Data Format (Fixed Configuration Assembly – All Signal Follower Models)
Parameter Parameter
Config Num. Description Size Config Num. Description Size
Number Number
1 30 Accel Time 1 2 13 42 Motor Overload 2
2 31 Decel Time 1 2 14 43 Current Limit 1
3 32 Minimum Frequency 1 15 44 DC Hold Time 1
4 33 Maximum Frequency 2 16 45 DC Hold Voltage 1
5 34 Stop Mode Select !
1 17 46 Input Mode !
1
! ATTENTION: Changing this parameter value may cause unpredictable network conditions, resulting in equipment damage, personal injury, or death.
Ensure that you understand how changing this parameter affects your application.
1 None Reserved 1
2 114 Motor Base RPM 2
3 113 DN Fault Mode 1
4 107 Output Assembly 1
5 108 Input Assembly 1
6 103 NV MAC ID 1
7 104 NV Baud 1
8 109 Assembly Word 0 1
9 110 Assembly Word 1 1
10 111 Assembly Word 2 1
11 112 Assembly Word 3 1
12 115 DN Idle Mode 1
13 117 COS 2
14 118 Local Return Md 1
15 105 Bus Off Error 1
C E
COMM LED EDS files
color 7-2 creating 6-3
description 7-2 description 5-1
state 7-2 Electronic Data Sheets, see EDS files
troubleshooting 7-2
equipment 3-1
communication module
error
installing 3-6, 3-8
description 4-2
powerup 4-1
LED state 4-2
removing 3-8
mode 4-2
wiring 1-1, 3-7
type 4-2
configuration
explicit messaging 6-18
switches 3-3
F
D
factory default
data rate
baud rate 3-5
factory default 3-5
data rate 3-5
settings 3-5
fault
DeviceNet wiring 1-1, 3-7
codes 7-4
DIP switches corrective action 7-4
1 through 6 3-4 description 7-4
7 and 8 3-4 LED 7-4
baud rate 3-5
data rate 3-5
DeviceNet address 3-4 G
node address 3-4 getting started 2-1
procedures 2-2
I Q
input assemblies 6-7, B-26 quick start
installation for experienced users 2-1
getting started 2-1
installing R
communication module 3-6, 3-8 removal
installing module 3-1 communication module 3-8
removing keypad 3-1
L removing Read/Fault panel 3-1
LED required equipment 3-1
COMM 1-1
description 1-1, 3-7
S
FAULT 1-1
READY 1-1 specifications
status 1-1, 3-7 communications A-1
electrical A-1
environmental A-1
M mechanical A-1
modes of operation startup 2-1
error mode 4-2
start-up instructions 2-1
Powerup Reset 4-1
run mode 4-2 status LED 1-1, 3-7
module switches
installation 3-1 configuration 3-3
setting 3-3
O
T
output assemblies 6-7, B-24–B-25
tools 3-1
troubleshooting 7-1
P
LEDs 7-1
parameters 5-3–5-11
powerup 4-1
W
powerup mode 4-1
wiring
procedures DeviceNet connection 1-1, 3-7
quick start 2-1
Americas Headquarters, 1201 South Second Street, Milwaukee, WI 53204, USA, Tel: (1) 414 382-2000, Fax: (1) 414 382-4444
European Headquarters SA/NV, avenue Herrmann Debroux, 46, 1160 Brussels, Belgium, Tel: (32) 2 663 06 00, Fax: (32) 2 663 06 40
Asia Pacific Headquarters, 27/F Citicorp Centre, 18 Whitfield Road, Causeway Bay, Hong Kong, Tel: (852) 2887 4788, Fax: (852) 2508 1846