PLC Cpu215
PLC Cpu215
General information
Engineering with
● Programming package STEP 7 V13 SP1 or higher
Display
with display No
Supply voltage
Rated value (DC)
● 24 V DC Yes
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Load voltage L+
● Rated value (DC) 24 V
● permissible range, lower limit (DC) 5 V
● permissible range, upper limit (DC) 250 V
Input current
Current consumption (rated value) 500 mA
Current consumption, max. 1 500 mA
Inrush current, max. 12 A; at 28.8 V DC
Encoder supply
24 V encoder supply
● 24 V L+ minus 4 V DC min.
Power losses
Power loss, typ. 12 W
CPU-blocks
Number of blocks (total) DBs, FCs, FBs, counters and timers. The maximum number of
addressable blocks ranges from 1 to 65535. There is no
restriction, the entire working memory can be used
OB
● Number, max. Limited only by RAM for code
Hardware configuration
Number of modules per system, max. 3 comm. modules, 1 signal board, 8 signal modules
Time of day
Clock
● Hardware clock (real-time clock) Yes
● Deviation per day, max. +/- 60 s/month at 25 °C
● Backup time 480 h; Typical
Digital inputs
Number of digital inputs 14; Integrated
● of which, inputs usable for technological 6; HSC (High Speed Counting)
functions
Digital outputs
Number of digital outputs 10; Relays
integrated channels (DO) 10
short-circuit protection No; to be provided externally
Switching capacity of the outputs
● with resistive load, max. 2 A
● on lamp load, max. 30 W with DC, 200 W with AC
Output delay with resistive load
● "0" to "1", max. 10 ms; max.
● "1" to "0", max. 10 ms; max.
Switching frequency
● of the pulse outputs, with resistive load, max. 1 Hz
Relay outputs
● Number of relay outputs, integrated 10
● Number of relay outputs 10
● Number of operating cycles, max. mechanically 10 million, at rated load voltage 100,000
Cable length
Analog inputs
Number of analog inputs 2
Integrated channels (AI) 2; 0 to 10 V
Input ranges
● Voltage Yes
Input ranges (rated values), voltages
● 0 to +10 V Yes
● Input resistance (0 to 10 V) ≥100k ohms
Cable length
● shielded, max. 100 m; twisted and shielded
Analog outputs
Number of analog outputs 2
Integrated channels (AO) 2; 0 to 20 mA
Output ranges, current
● 0 to 20 mA Yes
Cable length
● shielded, max. 100 m; shielded, twisted pair
Encoder
Connectable encoders
● 2-wire sensor Yes
1st interface
Interface type PROFINET
Physics Ethernet
Isolated Yes
Automatic detection of transmission speed Yes
Autonegotiation Yes
Autocrossing Yes
Functionality
● PROFINET IO Device Yes
● PROFINET IO Controller Yes
PROFINET IO Controller
● Transmission rate, max. 100 Mbit/s
Communication functions
S7 communication
● supported Yes
● as server Yes
● As client Yes
Open IE communication
● TCP/IP Yes
● ISO-on-TCP (RFC1006) Yes
● UDP Yes
Web server
● supported Yes
● User-defined websites Yes
Number of connections
● overall 16; dynamically
Integrated Functions
Number of counters 6
Counter frequency (counter) max. 100 kHz
Frequency meter Yes
controlled positioning Yes
PID controller Yes
Number of alarm inputs 4
Galvanic isolation
EMC
Interference immunity against discharge of static electricity
● Interference immunity against discharge of Yes
static electricity acc. to IEC 61000-4-2
— Test voltage at air discharge 8 kV
— Test voltage at contact discharge 6 kV
Interference immunity to cable-borne interference
● Interference immunity on supply lines acc. to Yes
IEC 61000-4-4
● Interference immunity on signal lines acc. to Yes
IEC 61000-4-4
Surge immunity
● on the supply lines acc. to IEC 61000-4-5 Yes
Immunity against conducted interference induced by high-frequency fields
● Interference immunity against high-frequency Yes
radiation acc. to IEC 61000-4-6
Emission of radio interference acc. to EN 55 011
● Limit class A, for use in industrial areas Yes; Group 1
● Limit class B, for use in residential areas Yes; When appropriate measures are used to ensure compliance
with the limits for Class B according to EN 55011
Ambient conditions
Dimensions
Width 130 mm
Height 100 mm
Depth 75 mm