Troubleshooting Sheet For Electric Trouble of The Generators

1) The troubleshooting sheet lists possible causes of electric trouble for generators in parallel operation, including defects in the control module, thyristors, voltage regulators, and measuring transformers. 2) Some specific issues mentioned are excessive or insufficient voltage/current, voltage hunting, improper power factor or reactive current, and failure of wiring links or blocking circuits. 3) The sheet indicates where on the chart each potential problem could cause low voltage, high voltage, voltage fluctuations, or incorrect power output.

Uploaded by

Allen Anyayahan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
119 views2 pages

Troubleshooting Sheet For Electric Trouble of The Generators

1) The troubleshooting sheet lists possible causes of electric trouble for generators in parallel operation, including defects in the control module, thyristors, voltage regulators, and measuring transformers. 2) Some specific issues mentioned are excessive or insufficient voltage/current, voltage hunting, improper power factor or reactive current, and failure of wiring links or blocking circuits. 3) The sheet indicates where on the chart each potential problem could cause low voltage, high voltage, voltage fluctuations, or incorrect power output.

Uploaded by

Allen Anyayahan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 2

Troubleshooting sheet for electric trouble of the generators

parallel operation

excessive voltage drop with load


narrow voltage control range
defect with control module
circulation current under lower

voltage control impossible

voltage increase with load


voltage & current hunting

higher droop & PF drop


excessive reactive current

defect with thyristor

lower max. voltage

no voltage built up
lower reactive current

voltage hunting
high voltage

half voltage
low voltage

KVAr hunting

different P.F
KW hunting
fault--------

load
possible cause

no wiring link 0 0 0
wiring link wrong point 0 0 0 0 0 0 @ 0
AVR Usoll wrong setting 0 0 0 0 0 @ 0 0
Vr.TN wrong setting 0 0 0
internal defect @ 0 0 0 0 0 0
discontinuity 0 @ 0 0
power
blocking fail 0 0
thyrister
gate electrode fail 0 0 0

measuring discontinuity 0 0
transformer internal defect 0 0 0 0 0 0
[T7.T8]
wiring link wrong point 0 0 0
discontinuity @ 0 0 0

reference wiring link wrong point 0 @ 0 0


value setter incorrect no-load setting @ @ @ 0
[VR]
short cicuit in leads 0 0
improper contact at T/B 0 0 0
discontinuity 0 0 0
series resister
excessive resitance @ 0 0
[R1]
lower resistance @ 0 0 0 0

intermidiate discontinuity 0 0 0 0
transformer short cicuit in leads 0 0
[T4.T5]
wiring link wrong point 0 0 0 0 0 0
discontinuity 0 0 0 0 0
excessive resitance 0 0 0 0
tandem
potentiamete lower resistance 0 0
r [R2]
different resistances @
wiring link wrong point 0 0 0 0 0 0 @ @

reactor discontinuity @ 0
[L]1 smaller reactor gap @ 0
rectifier discontinuity 0 0 0
transformer
[T6] improper tap setting @ @ 0 @ @ @ 0 0

steady rectifier discontinuity @


[V1] burnt or internal defect @

rotating discontinuity 0 0 0 0
rectifier [V2] burnt or internal defect @
varistor internal short circuit 0
discontinuity @ 0
currrent
transformers wiring link wrong point 0 0 0
internal defect 0 0
[T1,T2,T3]
setting to lower power @ @ 0
+F1 & -F2 wrong polarity 0
note : @ -- with high possibility, check first
Troubleshooting sheet for electric trouble of the generators
parallel operation

excessive voltage drop with load


narrow voltage control range
defect with control module
circulation current under lower

voltage control impossible

voltage increase with load


voltage & current hunting

higher droop & PF drop


excessive reactive current

defect with thyristor

lower max. voltage

no voltage built up
lower reactive current

voltage hunting
high voltage

half voltage
low voltage

KVAr hunting

different P.F
KW hunting
fault--------

load
possible cause

no wiring link 0 0 0
wiring link wrong point 0 0 0 0 0 0 @ 0
AVR U wrong setting 0 0 0 0 0 @ 0 0
K,T,R47 wrong setting 0 0 0
internal defect @ 0 0 0 0 0 0
discontinuity 0 @ 0 0
power
blocking fail 0 0
thyrister
gate electrode fail 0 0 0

measuring discontinuity 0 0
transformer internal defect 0 0 0 0 0 0
(AVR inside) wiring link wrong point 0 0 0
discontinuity @ 0 0 0

reference wiring link wrong point 0 @ 0 0


value setter incorrect no-load setting @ @ @ 0
[VR] short cicuit in leads 0 0
improper contact at T/B 0 0 0
discontinuity 0 0 0
series resister
excessive resitance @ 0 0
[R48]
lower resistance @ 0 0 0 0
discontinuity 0 0 0 0
intermidiate
transformer short cicuit in leads 0 0
[T4] wiring link wrong point 0 0 0 0 0 0
discontinuity 0 0 0 0 0

potentiomete excessive resitance 0 0 0 0


r (AVR inside) lower resistance 0 0
[S] different resistances @
wiring link wrong point 0 0 0 0 0 0 @ @

reactor discontinuity @ 0
[L1] smaller reactor gap @ 0
rectifier discontinuity 0 0 0
transformer
[T6] improper tap setting @ @ 0 @ @ @ 0 0
rotating discontinuity 0 0 0 0
rectifier
V2 burnt or internal defect @
varistor internal short circuit 0
discontinuity @ 0
currrent
transformers wiring link wrong point 0 0 0
internal defect 0 0
[T1,T2,T3]
setting to lower power @ @ 0
+F1 & -F2 wrong polarity 0
note : @ -- with high possibility, check first