Schneider Electric - Altivar Easy 310 - Catalogue

Download as pdf or txt
Download as pdf or txt
You are on page 1of 13

Variable speed drives

Altivar Easy 310


For applications from 0.37 to 11 kW / 0.5 to 15 HP

Catalog
September 2017
General contents

Altivar Easy 310 variable speed drives


bb Variable speed drives................................................................................ page 2
vv Presentation................................................................................................ page 2
vv Applications................................................................................................. page 2
vv Functions..................................................................................................... page 2
vv An optimized offer........................................................................................ page 3
vv References.................................................................................................. page 5
bb Configuration tools................................................................................... page 6
vv Simple Loader and Multi-Loader.................................................................. page 6
vv Remote display terminals............................................................................ page 6
bb Options....................................................................................................... page 7
vv Line chokes, motor chokes and LR filter cells.............................................. page 7
vv Braking resistors.......................................................................................... page 8
vv Modbus serial link........................................................................................ page 8
bb Motor starters............................................................................................ page 9
bb Product reference index.......................................................................... page 10

1
Presentation Variable speed drives
AltivarTM Easy 310

Presentation
The AltivarTM Easy 310 drive is a frequency inverter for three-phase 380…460 V
asynchronous motors rated from 0.37 kW/0.5 HP to 11 kW/15 HP.

The compact size of this drive, its robust design, its ease of installation, based on the
principle of Plug & Play, its integrated functions and macro configuration make it
particularly suitable for applications involving industrial machines and certain
consumer machines.
By taking account of the constraints governing installation and use at the product
design stage, we have been able to offer a reliable, cost-effective solution to
manufacturers of compact machines (OEMs).
The Altivar Easy 310 has been developed with no compromise on quality : the
components are designed to last 10 years.

Textile machine Applications


The Altivar Easy 310 drive incorporates functions that are suitable for the most
common applications, including:
bb Textile machine
bb Machine tools
bb Wood making machine
bb Material handling
bb Packaging and printing machines
bb Ceramic machine

Functions
In addition to the functions usually available on this type of drive, the Altivar Easy 310
drive also features the following:

Motor control functions (1)


bb Motor control profiles: standard, performance and pump/fan
bb Cooling fan thermal control
bb Switching frequency management
bb Boost torque
bb Motor noise reduction
bb Current limitation
bb Auto DC injection

Application functions (1)


bb Frequency skip
Packaging machine bb Preset speeds
bb PID regulator
bb S ramp, U ramp, ramp switching
bb Jog operation
bb +/- speed around reference
bb Freewheel stop, fast stop
bb Automatic catching a spinning load with speed detection and automatic restart

Control functions (1)


bb Channel configuration - separate mode or not
bb Reference channel selection
bb Reverse inhibition
bb Force local control
bb Store customer parameter settings

Protection and maintenance functions (1)


bb Protection of the installation by means of underload and overload detection
bb Maintenance functions:
vv HMI password
vv Configuring the logic and analog I/O
vv Configuring how the parameters are displayed
vv Viewing the state of the logic inputs on the drive display
vv Key parameters display (drive power on / Fan time / Process elapsed time)
vv The last 4 fault display, error log, etc.
Printing machine (1) For the implementation of functions, please consult the user manual on our local
website.

Drives: Configuration tools: Options: Modbus serial link: Motor starters:


page 5 page 6 page 7 page 8 page 9

2
Presentation (continued) Variable speed drives
Altivar Easy 310

An optimized offer
Environment
The entire range conforms to international standards IEC/EN 61800-5-1 and
IEC/EN 61800-3 and has been developed to meet the requirements of directives
regarding the protection of the environment (RoHS, WEEE).
Owing to its innovated air flow design and to its thicker coating which avoids
polluting PCB, the range can be used in the harshest environments. It can withstand
a 55 °C/131 °F ambiant air temperature around the device without derating (1).
Its degree of protection is IP 20 (IP 41 on top of the product).

Adaptability and performances


The Altivar Easy 310 has been designed with an increased adaptability to different
motors and various tough loads.
One of its main quality is its torque capacity for starting and braking:
bb Braking capacity:
vv over 80 % of the rated motor torque without braking resistor
vv 150 % of the rated motor torque with braking resistor (see page 8)
bb Torque capacity
vv starting torque 150 % at 3 Hz
vv over torque : 150 to 170 %, depending on model (2).
Altivar Easy 310 range
Easy to integrate in system
The Altivar Easy 310 drive integrates as standard the Modbus communication
5 protocol, which can be accessed via the RJ45 connector located on the underside of
the drive 1 with a 2-wire RS 485 physical interface. To communicate on the network,
the Altivar Easy 310 speed drive uses the Modbus RTU transmission mode. For
more information on the complementary characteristics of the Modbus port
(transmission speed, address, messaging...), please consult our local website.
2 Logic input can be configured as source or sink by software, compatible with
many PLCs.
3
4 Easy to install
The Altivar Easy 310 drives can easily and quickly be installed as:
bb they are easy and quick to wire due to their Plug & Play concept
bb they can be identified on the front panel.
1
bb they can be mounted side by side to save cabinet space.
bb power terminal and connection labels are easily identified and differenciated
ATV310H037N4E with door bb a connection guideline is shown inside the front door.
on front panel open

Easy to commission
Human-Machine Interface (integrated keypad)
The 4-digit display 2 can be used to display states and faults, access parameters
and modify them via the navigation button 3.
The RUN and STOP buttons 4 can be made accessible on the front panel by removing
the blanking plate 5 from the door; they must be configured in order to be active.
Remote display terminal
The Altivar Easy 310 drive can be connected to a remote display terminal, available
as an option. This terminal can be mounted on an enclosure door with IP 54 or IP 65
Remote terminal Remote terminal with cover
with cover closed open: RUN, FWD/REV and degree of protection. The maximum operating temperature is 50 °C/122 °F. It
STOP buttons accessible provides access to the same functions as the Human-Machine interface.
Simple Loader and Multi-Loader configuration tools
The Simple Loader tool enables one powered-up drive's configuration to be
duplicated on another powered-up drive. Operation is very simple.
The Multi-Loader tool enables configurations from a PC or drive to be copied and
duplicated on another drive; the drives do not need to be powered up. The
configuration can be loaded onto the drive without taking it out of its packaging.

Easy to maintain
A warning is sent by the drive to the user when it is necessary to clean heat sink or
replace cooling fan. This fan, which is the only wearing part, can be changed without
the need for any tool.
The security of the system is ensured by an access code allowing authorized people
to configure applications and settings in Configuration mode. Simple users are only
allowed to use the Monitoring mode (parameters display).
Multi-Loader
configuration tool (1) Over this temperature, see the derating curves in the User Manual, available on our website.
(2) For more information, please refer to our local website.

Drives: Configuration tools: Options: Modbus serial link: Motor starters:


page 5 page 6 page 7 page 8 page 9

3
Presentation (continued) Variable speed drives
Altivar Easy 310

Main characteristics
Analog input AI1
1 software-configurable voltage or current analog input:
bb Voltage analog input: 0...5 V c (internal power supply only) or 0...10 V c ,
impedance 30 kΩ
bb Analog current input: X-Y mA by programming X and Y from 0–20 mA,
Impedance 250 W
Sampling time: < 20 ms
Resolution: 10 bits
Accuracy: ± 1% at 25 °C/77 °F
Linearity: ± 0.3% of the maximum scale value
Factory setting: Input configured as voltage type

Analog output AO1


1 software-configurable voltage or current analog output:
bb Analog voltage output: 0…10 V c , minimum load impedance 470 W
bb Analog current output: 0–20 mA, maximum load impedance 800 W
Sampling time: < 10 ms
Resolution: 8 bits
Accuracy: ± 1% at 25 °C/77 °F

Relay outputs R1A, R1B, R1C


1 protected relay output, 1 N/O contact and 1 N/C contact with common point
Response time: 30 ms maximum
Minimum switching capacity: 5 mA for 24 V c
Maximum switching capacity:
bb On resistive load (cos j = 1 and L/R = 0 ms): 3 A at 250 V a or 4 A at 30 V c
bb On inductive load (cos j = 0.4 and L/R = 7 ms): 2 A at 250 V a or 30 V c

Logic inputs LI1...LI4


4 programmable logic inputs, compatible with PLC level 1, standard IEC/EN 61131-2
24 V ⎓ internal power supply or 24 V ⎓ external power supply (min. 18 V,
max. 30 V)
Sampling time: < 20 ms
Sampling time tolerance: ± 1 ms
Factory-set with 2-wire control in "transition" mode for machine safety reasons:
bb LI1: forward
bb LI2…LI4: not assigned
Multiple assignment makes it possible to configure several functions on one input
(for example: LI1 assigned to forward and preset speed 2, LI3 assigned to reverse
and preset speed 3)
Impedance 3.5 kW

Logic outputs LO1


One 24 V c logic output assignable as positive logic (Source) or negative logic
(Sink) open collector type, compatible with level 1 PLC, standard IEC/EN 61131-2
Maximum voltage: 30 V
Linearity: ± 1%
Maximum current: 10 mA (100 mA with external power supply)
Impedance: 1 kW
Update time: < 20 ms

Drives: Configuration tools: Options: Modbus serial link: Motor starters:


page 5 page 6 page 7 page 8 page 9

4
References Variable speed drives
Altivar Easy 310
Drives

Drives
PF142119

Motor Line supply Altivar Easy 310


Power Max. line Apparent Max. Maximum Maximum Dissipated Reference Weight
indicated on current power prospec- continuous transient power at (3)
rating plate (2) tive line output current for maximum
(1) Isc current 60 s output
(In) (1) current (In)
(1)
ATV310H037N4E 380 V 460 V 460 V 380 V
kW HP A A kVA kA A A W kg/
lb
Three-phase supply voltage: 380…460 V 50/60 Hz
0.37 0.5 2.1 1.8 1.4 5 1.5 2.3 19.63 ATV310H037N4E 0.800/
PF142121

1.760
0.75 1 3.5 3.1 2.5 5 2.3 3.5 28.83 ATV310H075N4E 0.800/
1.760
1.5 2 6.5 5.4 4.3 5 4.1 6.2 51.82 ATV310HU15N4E 1.100/
2.430
2.2 3 8.8 7.2 5.7 5 5.5 8.3 66.32 ATV310HU22N4E 1.100/
2.430
ATV310HU15N4E 3 4 11.1 9.2 7.3 5 7.1 10.7 80.24 ATV310HU30N4E 1.800/
3.970
4 5 13.7 11.4 9.1 5 9.5 14.3 102.72 ATV310HU40N4E 1.800/
3.970
PF142123

5.5 7.5 21.3 14.3 11.4 22 12.6 18.9 141.54 ATV310HU55N4E 1.800/
3.970
7.5 10 26.6 22.4 17.8 22 17 25.5 203.87 ATV310HU75N4E 3.700/
8.160
11 15 36.1 30.4 24.2 22 24 36 294.70 ATV310HD11N4E 3.700/
8.160

ATV310HU30N4E

Dimensions (overall)
Drives with heatsinks WxHxD
PF142126

mm in.
ATV310H037N4E 72 x 143 x 130 2.83 x 5.63 x 5.12
ATV310H075N4E 72 x 143 x 140 2.83 x 5.63 x 5.51
ATV310HU15N4E, HU22N4E 105 x 143 x 151 4.13 x 5.63 x 5.94
ATV310HU30N4E…HU55N4E 140 x 184 x 151 5.51 x 7.24 x 5.94
ATV310HU75N4E, HD11N4E 150 x 232 x 171 5.91 x 9.13 x 6.73
(1) These values are given for a nominal switching frequency of 4 kHz, for use in continuous operation.
If operation above 4 kHz needs to be continuous, the nominal drive current should be derated by 10% for 8 kHz and
20% for 12 kHz.
The switching frequency can be set between 2 and 12 kHz for all ratings.
Above 4 kHz, the drive will reduce the switching frequency automatically in the event of an excessive temperature rise.
See the derating curves in the User Manual, available on our local website.
(2) Typical value for the indicated motor power and for the maximum prospective line Isc.
ATV310HU75N4E
(3) Weight of product without packaging.

Presentation: Configuration tools: Options: Modbus serial link: Motor starters:


page 2 page 6 page 7 page 8 page 9

5
References (continued) Variable speed drives
Altivar Easy 310
Configuration tools

Configuration tools
Description For drives Reference Weight
kg/
lb
Simple Loader, Multi-Loader configuration tools and associated cable
Simple Loader tool ATV310HpppN4E VW3A8120 –
For duplicating one drive configuration on another drive.
The drives must be powered-up.
The tool is supplied with a cordset equipped with 2 RJ45
connectors.

1 2 Multi-Loader tool 1 ATV310HpppN4E VW3A8121 –


For copying a configuration on a PC or drive and duplicating it
on another drive.
The drives do not need to be powered-up.
Supplied with the tool:
bb 1 cordset equipped with 2 RJ45 connectors
bb 1 cordset equipped with a USB type A connector and a USB
Mini-B type connector
bb 1 x 2 GB SD memory card
bb 1 female/female RJ45 adaptor
Configuring the drive bb 4 AA/LR6 1.5 V batteries
in its packaging with
the Multi-Loader tool
VW3A8121+ cordset Cordset for Multi-Loader tool 2 ATV310HpppN4E in VW3A8126 –
VW3A8126  For connecting the Multi-Loader tool to the Altivar Easy 310 drive its packaging
in its packaging. Equipped with a non-locking RJ45 connector
with special mechanical catch on the drive end and an RJ45
connector on the Multi-Loader end.

Remote display terminals and associated cordsets


Description Degree of For drives Reference Weight
protection kg/
lb
Remote display terminals IP 54 ATV310HpppN4E VW3A1006 0.250/
PF080659

For fixing the Human-Machine interface on an 0.550


enclosure door with IP 54 or IP 65 degree of
IP 65 ATV310HpppN4E VW3A1007 0.275/
protection.
0.610
A remote-fixing cordset VW3A1104Rpp is also
required.

VW3A1006 with cover open:


RUN, FWD/REV and STOP Remote-fixing cordsets Length: ATV310HpppN4E VW3A1104R10 0.050/
buttons accessible equipped with 2 RJ45 connectors. 1 m/3.28 ft 0.110
For connecting the VW3 A1 006 or VW3A1007
Length: ATV310HpppN4E VW3A1104R30 0.150/
remote display terminal to the Altivar Easy 310
3 m/9.84 ft 0.330
drive.

Dimensions (overall)
Remote display terminal WxHxD
mm in.
VW3A1006 50 x 70 x 22.7 1.97 x 2.76 x 0.89
VW3A1007 66 x 106 x 26.7 2.6 x 4.17 x 1.05

Presentation: Options: Modbus serial link: Motor starters:


page 2 page 7 page 8 page 9

6
References (continued) Variable speed drives
Altivar Easy 310
Options: line chokes, motor chokes and LR filter cells

Presentation
Line chokes
A line choke can be used to provide improved protection against overvoltages on the line supply and to reduce
harmonic distortion of the current produced by the drive. They are recommended for ATV310…N4E drives.
The recommended chokes limit the line current. They have been developed in line with standard EN 50178
(VDE 0160 level 1 high energy overvoltages on the line supply).
The choke values are defined for a voltage drop between phases of between 3% and 5% of the nominal supply
voltage. Values higher than this will cause loss of torque.
These chokes should be installed upstream of the drive.

The use of line chokes is recommended in particular under the following circumstances:
bb Close connection of several drives in parallel
bb Line supply with significant disturbance from other equipment (interference, overvoltages)
bb Line supply with voltage imbalance between phases above 1.8% of the nominal voltage
bb Drive supplied by a line with very low impedance (in the vicinity of a power transformer 10 times more powerful than
the drive rating)
bb Installation of a large number of frequency inverters on the same line
bb Reducing overloads on the cosϕ correction capacitors, if the installation includes a power factor correction unit.

M1
Motor chokes and LR filter cell
3 Motor chokes are required:
bb When connecting more than 2 motors in parallel
M1
3 bb When the motor cable length (L), including tap-offs, is:
vv 25 m/82.2 ft maximum for a shielded motor cable (1),
M1 vv 50 m/164.4 ft maximum for an unshielded motor cable (1).
3
L LR filter cell comprises 3 high-frequency chokes and 3 resistors.
VW3A455p
Motor choke References
Line chokes
For drives Choke
Line current without choke Line current with choke Reference Weight
380 V 460 V 380 V 460 V
A A A A kg/
lb
ATV310H037N4E 2.1 1.8 1.1 1 VW3A4551 1.500/
ATV310H075N4E 3.5 3.1 1.9 1.7 3.310
ATV310HU15N4E 6.5 5.4 3.5 2.9 VW3A4552 3.700/
PF142110

ATV310HU22N4E 8.8 7.2 5.1 4.4 8.160


ATV310HU30N4E 11.1 9.2 6.6 5.6
ATV310HU40N4E 13.7 11.4 8.5 7.1 VW3A4553 4.100/
ATV310HU55N4E 21.3 14.3 11.6 9.9 9.040
ATV310HU75N4E 26.6 22.4 15.2 12.8 VW3A4554 6.150/
ATV310HD11N4E 36.1 30.4 22 18.9 13.230
VW3A455p
Motor chokes and LR filter cell
For drives Losses Nominal current Reference Weight
W A kg/
lb
ATV310H037N4E…HU15N4E 150 10 VW3A58451 (2) 7.400/
16.310
ATV310HU22N4E...HU40N4E 65 10 VW3A4552 3.700/
8.160
ATV310HU55N4E 75 16 VW3A4553 4.100/
9.040
ATV310HU75N4E...HD11N4E 90 30 VW3A4554 6.150/
13.230
Dimensions (overall)
Line chokes or WxHxD
motor chokes,
LR filter cell
mm in.
VW3A4551 100 x 135 x 60 3.94 x 5.31 x 2.36
VW3A4552, A4553 130 x 155 x 90 5.12 x 6.1 x 3.54
VW3A4554 155 x 170 x 135 6.1 x 6.69 x 5.31
VW3A58451 169.5 x 340 x 123 6.67 x 13.39 x 4.84
(1) Motor cable length given for a switching frequency of 4 kHz.
(2) LR filter cell

7
References (continued) Variable speed drives
Altivar Easy 310
Options: braking resistors, Modbus serial link

Braking resistors
For drives Minimum Ohmic value at Power available at Reference Weight
Ohmic value 20° C/68 °F 50° C/122 °F (1)
W W kW kg/
lb
Not protected resistor (IP00) (2)
PF151245A

ATV310HU15N4E 80 100 0.028 VW3A7723 0.600/


ATV310HU22N4E 60 1.320

ATV310HU30N4E 36 100 0.035 VW3A7725 0.850/


ATV310HU40N4E 36 1.870

Protected resistor (IP20 or 23)


ATV310HU15N4E 80 100 0.1 VW3A7730 1.500/
ATV310HU22N4E 60 3.307

ATV310HU30N4E 36
ATV310HU40N4E 36
ATV310HU55N4E 28 60 0.16 VW3A7731 2.000/
ATV310HU75N4E 28 4.409

VW3A7730 ATV310HD11N4E 28 28 0.3 VW3A7732 3.000/


6.614
Dimensions (overall)
Braking resistors WxHxD
mm in.
VW3A7723 60 x 170 x 30 2.36 x 6.659x 1.18

VW3A7725 62 x 212 x 36 2.44 x 8.35 x 1.42

VW3A7730 105 x 295 x 100 4.13 x 11.61 x 3.94

VW3A7731 105 x 345 x 100 4.13 x 13.58 x 3.94

VW3A7732 175 x 345 x 100 6.89 x 13.58 x 3.94

Modbus serial link


Description Item no. Length Unit reference Weight
m/ft kg/
lb
Connection via splitter box and RJ45 connectors
Programmable Modbus splitter box – LU9GC3 0.500/
controller (3) 10 RJ45 connectors and 1 screw terminal 1.100
Cordsets for Modbus serial link 2 0.3/0.98 VW3A8306R03 0.025/
Modbus serial link (4)

equipped with 2 RJ45 connectors 0.060


1 2 3 4 1/3.28 VW3A8306R10 0.060/
0.060
3/9.84 VW3A8306R30 0.130/
0.290
4 2 3
Modbus T-junction boxes 3 0.3/0.98 VW3A8306TF03 0.190/
2 (with integrated cable) 0.420
1/3.28 VW3A8306TF10 0.210/
0.460
Line terminators (5) (6) R = 120 W 4 – VW3A8306RC 0.010/
ATV310 For RJ45 connector C = 1 nf 0.020
Example of Modbus diagram R = 150 W 4 – VW3A8306R 0.010/
with connection via splitter box 0.020
and RJ45 connectors (1) Load factor for resistors: the value of the average power that can be dissipated at 50 °C from the resistor into the casing is
determined for a load factor during braking that corresponds to the majority of normal applications.
For VW3A7730...732:
- 2 s braking with a 0.6 Tn braking torque for a 40 s cycle
- 0.8 s braking with a 1.5 Tn braking torque for a 40 s cycle
(2) For not protected resistors, add a thermal overload device.
(3) Please refer to the programmable controller catalogue on our local website.
(4) Cable depends on the type of controller or PLC.
(5) Order in multiples of 2.
(6) Depends on the bus architecture.

Presentation: Configuration tools: Options: Motor starters:


page 2 page 6 page 7 page 9

8
Combinations for Variable speed drives
customer assembly Altivar Easy 310
Motor starters

Applications
The proposed combinations can:
bb Protect people and equipment (when a short-circuit occurs)
bb Maintain protection upstream of the drive in the event of a short-circuit on the
power stage
Two types of combination are possible:
bb Drive + circuit-breaker: Minimum combination
bb Drive + circuit-breaker + contactor: Minimum combination with contactor when a
control circuit is needed

Motor starters
Standard Variable speed Combination with control circuit
power drive (circuit-breaker + contactor)
ratings of Minimum combination TeSys
three- (circuit-breaker only) contactor
phase (1)
4-pole TeSys motor Operating
50/60 Hz circuit-breaker range or
motors (3) rating
(2)
kW HP A
M1 A1 Q1 KM1
Three-phase supply voltage: 380…460 V 50/60 Hz (4)
5
1

Q1:
GV2pppp 0.37 0.5 ATV310H037N4E GV2P07 2.5 LC1D09
GV2L07 2.5
2

0.75 1 ATV310H075N4E GV2P08 4 LC1D09


GV2L08 4
1.5 2 ATV310HU15N4E GV2P14 10 LC1D09
GV2L14 10
KM1:
1

TeSys LC1pppp 2.2 3 ATV310HU22N4E GV2P14 10 LC1D09


(if control circuit) GV2L14 10
3 ATV310HU30N4E GV2P16 14 LC1D09
2

4
GV2L16 14
A1:
4 5.4 ATV310HU40N4E GV2P16 14 LC1D09
R/L1

S/L2

T/L3

ATV310HpppN4E
GV2L16 14
5.5 7.4 ATV310HU55N4E GV2P22 25 LC1D09
W/T3
U/T1

V/T2

GV2L22 25
7.5 10 ATV310HU75N4E GV2P32 32 LC1D18
GV2L32 32
W1
U1

V1

M1: 11 15 ATV310HD11N4E GV2P40 40 LC1D25


380..460 V three-phase M1 GV2L40 40
asynchronous motor 3
(1) For a complete list of references for TeSys contactors, please visit our local website.
(2) Motor power indicated for combination with an ATV310HpppN4E drive with the same rating.
Motor starter with three-phase power supply (3) TeSys motor circuit-breakers:
- GV2 Ppp: Thermal magnetic motor circuit-breakers with pushbutton control
- GV2 Lpp: Magnetic motor circuit-breakers with control by rotary knob.

Presentation: Configuration tools: Options: Modbus serial link:


page 2 page 6 page 7 page 8

9
Index Product reference index

A
ATV310H037N4E 5
ATV310H075N4E 5
ATV310HD11N4E 5
ATV310HU15N4E 5
ATV310HU22N4E 5
ATV310HU30N4E 5
ATV310HU40N4E 5
ATV310HU55N4E 5
ATV310HU75N4E 5

L
LU9GC3 8

V
VW3A1006 6
VW3A1007 6
VW3A1104R10 6
VW3A1104R30 6
VW3A4551 7
VW3A4552 7
VW3A4553 7
VW3A4554 7
VW3A7723 8
VW3A7725 8
VW3A7730 8
VW3A7731 8
VW3A7732 8
VW3A8120 6
VW3A8121 6
VW3A8126 6
VW3A8306R 8
VW3A8306R03 8
VW3A8306R10 8
VW3A8306R30 8
VW3A8306RC 8
VW3A8306TF03 8
VW3A8306TF10 8
VW3A58451 7

10
Schneider Electric Industries SAS www.schneider-electric.com
Head Office The information provided in this documentation contains general descriptions and/or technical
35, rue Joseph Monier characteristics of the performance of the products contained herein. This documentation is
F-92500 Rueil-Malmaison not intended as a substitute for and is not to be used for determining suitability or reliability of
France these products for specific user applications. It is the duty of any such user or integrator to
perform the appropriate and complete risk analysis, evaluation and testing of the products with
respect to the relevant specific application or use thereof. Neither Schneider Electric nor any
of its affiliates or subsidiaries shall be responsible or liable for misuse of the information
contained herein.

Design: Schneider Electric


DIA2ED2140701EN

Photos: Schneider Electric

September 2017 - V2.0

You might also like