SL Power Electronics GPFM250 User Manual

The document provides installation instructions for Condor DC Power Supply models GPFM250-X. It lists the input and output ratings for the power supplies, which can provide up to 250W of power with ambient cooling or a cover/fan option. Safety certifications and classifications are also summarized, along with connection details, overvoltage protection information, and warnings about dangerous voltages and fuse replacement.

Uploaded by

mohammed
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
153 views2 pages

SL Power Electronics GPFM250 User Manual

The document provides installation instructions for Condor DC Power Supply models GPFM250-X. It lists the input and output ratings for the power supplies, which can provide up to 250W of power with ambient cooling or a cover/fan option. Safety certifications and classifications are also summarized, along with connection details, overvoltage protection information, and warnings about dangerous voltages and fuse replacement.

Uploaded by

mohammed
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

GPFM250 SERIES

CONDOR DC POWER SUPPLIES INC. INSTALLATION INSTRUCTIONS


2311 STATHAM PKWY
OXNARD, CA 93033 + 805-486-4565
Internet: www.condorpower.com

MODEL NUMBERS: GPFM250-X where X represents the output voltage, which may be any number
from 3.3 thru 48. Models may or may not be followed by suffix –C, which indicates optional cover/fan,
suffix –H, which indicates the Neutral fuseholder/fuse removed and replaced with a jumper on the PWB,
suffix –YYY and/or G, where YYY may be any number from 001 thru 999. The –YYY suffix are used
for value added configurations that have no impact on safety and suffix G indicates compliance to
RoHS.
RATINGS:
Input: 100-240 V ac, 6 A, 50/60 Hz
Output: Maximum volts = 48 V dc
Maximum current = 50 A
Maximum watts = 180 W convection cooled,
250 W with cover/fan option or minimum 150 LFM airflow.
Notes: 1. Maximum ambient temperature for rated output power is 50 °C.
2. Maximum Operating Relative Humidity 96 %, no condensation.
3. Storage: -40 to +85 °C. Units should be allowed to warm-up under non-condensing conditions before
application of power.
CERTIFICATION: All models are Certified to be in compliance with the applicable requirements of
UL 60601-1, CSA 22.2 No. 601.1, IEC/EN 60601-1.
CLASSIFICATION: (5.1) Protection against electric shock = Class I
(In accordance with (5.2) Degree of protection against electric shock = Signal output or intermediate
clause 5 of (5.3) Protection against harmful ingress of water = Ordinary (no protection)
IEC 60601-1) (5.5) Have not been evaluated for use in the presence of a flammable anaesthetic
mixture with air, oxygen, or nitrous oxide. This evaluation is to be made on the
end equipment by the OEM.
(5.6) Mode of operation = Continuous

SAFETY DECLARATION: Condor DC Power Supplies, Inc. declares under our sole
responsibility that all models listed above are in conformity with the applicable requirements
of EN 60950-1 following the provisions of the Low Voltage Directive 73/23/EEC.
GROUNDING: Protection Class I requires that the chassis and/or TB1-3 be bonded to Protective Earth
in the end application. Using TB1-3 for the end product’s protective earthing terminal is not
recommended. A separate dedicated protective earthing point should be used.
OUTPUTS: Output common or return should be connected to Protective Earth in the end application.
The output is intended for Protectively Earthed Signal Output and Intermediate Circuits only. The
output is not acceptable for patient connection without additional isolation. The DC output is SELV
under normal and single fault conditions.

41-34880-0001 Rev. G 12/06/05 Page 1 of 2


OVERVOLTAGE PROTECTION: The output is monitored for an overvoltage condition. In some
applications where an overvoltage condition could result in a hazard as defined in applicable safety
standards, redundant or additional overvoltage protection may be required. Consult factory for details.
CAUTION: When performing Dielectric Strength Tests, catastrophic failure of the unit may result if a
Dielectric Strength test voltage greater than 1800 V ac is applied between primary and secondary
circuits. The components providing isolation from primary to secondary cannot be tested while installed
in the power supply without overstressing basic (primary to ground) insulation. All isolating
components are individually 100 % tested at 4800 V ac prior to installation.
TEMPERATURES: The maximum operating temperatures of certain safety components, as defined in
the applicable safety standards, must not be exceeded after installation to preserve the intended safety.
The output power, ambient air temperature and the availability, amount, direction and/or restriction of
airflow influence the temperatures of these components.
EXPLANATION OF SYMBOLS
FUSING: Fuses for both Line and Neutral are provided in the power Alternating Current
supply on all models except models with –H suffix.
Direct Current
WARNING! RISK OF FIRE! A blown internal fuse is an
Attention, Consult
indication of catastrophic failure of circuit component(s). Refer to Accompanying Documents
fuse marking on the supply for rating. Repair must be performed by
Attention, Dangerous Voltages
Condor authorized personnel.
Earth (Ground)
WARNING! SHOCK HAZARD! Dangerous voltages are present
on some components, printed wiring traces and heatsinks.

CONNECTIONS
TB1 AC Input TB2 DC Output J2 Signal Out FAN MATING CONNECTORS
L AC Line 1 Output (+) 1 DC Good 1 12 V (-) J2 and FAN: Amp MTA-100 Receptacle
N AC Neutral 2 Output (+) 2 Power Fail 2 12 V (+)
Earth 3 Return 3 Ext Off
4 Return 4 + Sense CAUTION: Do not exceed 20 A per terminal on terminal
5 - Sense Block TB2; 60 A peak on buss bars (3.3 & 5 V models).

Condor DC Power Supplies Inc. will not be liable for the safety, reliability or performance of these power supplies if a) any changes, modifications or repairs are carried out by other
than authorized agents of Condor DC Power Supplies Inc., or b) the installation of the supply is not in accordance with these installation instructions and the applicable UL, CSA,
and EN/IEC safety standards.

41-34880-0001 Rev. G 12/06/05 Page 2 of 2