RENR8091 Quick Start Guide
RENR8091 Quick Start Guide
Shutdown SIS
Previous Screen
Systems Operation
PL1000E Communication ECM
Media Number -RENR8091-03 Publication Date -01/09/2007 Date Updated -06/09/2007
i02794794
1. Verify the type of "Programmable Logic Controller" (PLC) that is being used.
2. Ensure that the PLC supports the native Modbus, NOT Modbus+.
3. Verify that the PLC is a Modbus Master that is capable of requesting registers 40,001 through 42,000.
4. Locate the protocol that is required for the Modbus. (TCP, RS-232, RS-485 (4 wire), RS-485 (2 wire),
and RS-422).
Note: The steps that are required in order to configure RS-485 (2 wire) are the same steps that are
required to configure RS-485 (4 wire). After the PCL file has been loaded on the PL1000E, the user will
need to go into Cat ET. Go to the "Modbus"configuration. Configure the parameter that is called "RS-
485 Mode". The selections will be 2 wire or 4 wire configuration.
6. Locate the Modbus slave address in the PL1000E that the "Master" will request the information from.
7. If applicable, locate the unused Modbus slave address for the internal housekeeping.
Note: The address type will be either "Dynamic Host Configuration Protocol" (DHCP) or "Static"
addressing.
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/s... 29/01/2008
Media Search - RENR8091 - PL1000E Communication ECM Page 2 of 6
Note: The ECM address depends on the type of engine that is being used. To locate the ECM address,
log onto Cat ET. Initially, ECM addresses may be in hexadecimal format, and will need to be converted
into decimal format for the Parameter Translation Editor.
2. Locate the data link that the information is on from each ECM and the starting registers.
1. Ensure that each Caterpillar ECM is defined. Ensure that each ECM has the correct address.
2. Verify all Modbus ECMs, and that each Modbus ECM has the correct Modbus slave ID.
Note: The PL1000E has two Modbus slave addresses. The Modbus slave address that is configured in
the PCL file is the address the Modbus Master uses in order to retrieve engine information. The Modbus
slave address that is configured in Cat ET, Caterpillar Communication Tool Kit, or through the web
server, is for the PL1000E's internal statistics.
3. Define all of the translation lines from the Caterpillar ECMs to the Modbus ECMs.
Note: The Modbus registers that are associated with each parameter are shown in the right hand column.
Note: All of the parameters that are in the General Parameter Translation Editor (PTE) files may not be
supported.
6. Save a ".CSV" file from each translation line. This will be given to the PLC integrator.
1. Wire the PL1000E for use with the PLC. Refer to "Caterpillar Dealer Questions" for instructions about
the required connections for the PLC.
2. Upload the PCL file into the PL1000E by use of FTP. Use the "IP" address or "Internet Host Name".
The "IP" address or "Internet Host Name" are both defined in the "Configuration" screen in Cat ET. The
default username and the password are both "admin". Check the ECM mapping screen for correct
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/s... 29/01/2008
Media Search - RENR8091 - PL1000E Communication ECM Page 3 of 6
4. Locate a parameter that is in a Cat ET status screen. Check for accuracy between the PCL file and Cat
ET.
5. Verify that there are no problems with the communications. Modify the PCL file in order to send the
data to a RS-232 port. Check to make sure the data is being sent by the PL1000E.
Illustration 1 g01395613
Sample System Block Diagram
Begin by making a sketch of the system diagram. The system diagram should identify each ECM that is in the
system. The system diagram should identify each ECM communication type.
Refer to the sample of a system diagram that is shown in Illustration 1. Illustration 1 provides an explanation
and a description of each electronic control that is used. There is certain information that is needed about each
device in order to perform the integration successfully.
The system diagram that is shown in Illustration 1 is a generic example that could be used for an application.
Each system may vary depending on the components and on the interfaces that the system contains.
The control numbers can represent an engine control, a combustion module, or other electronic devices that
exist in the Caterpillar application.
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/s... 29/01/2008
Media Search - RENR8091 - PL1000E Communication ECM Page 4 of 6
NOTICE
Do not connect multiple engine control modules onto the same datalink
network. Multiple engine control modules that are connected to the
same datalink network will cause faulty data or datalink failure.
Note: The PTE file should be located on same Compact Disc (CD) with the PL1000E information. If the PTE
file is not included, then contact local Caterpillar dealer.
Note: For "Data Link Addresses" information, refer to the System Operation Troubleshooting, Testing and
Adjusting, RENR8091, "Data Link Address of Caterpillar Electronic Control".
The PL1000E Communication ECM is designed specifically for communication translations from Caterpillar
electronic controls.
This device may be any industry available Modbus communications device so long as it meets the following
criteria:
Capable of Modbus communications over RS-232, RS-422, RS-485 (4 wire) and RS-485 (2 wire) or
Ethernet
Capable of requesting single and multiple Modbus registers in the range of 40,001 through 42,000
Use the Caterpillar Communications Tool Kit or Caterpillar Electronic Technician (Cat ET) in order to prepare
the PCL file as described in this document.
Refer to the System Operation Troubleshooting Testing and Adjusting, RENR8091, "PL1000E
Communication ECM", "Parameter Translation Configuration" section.
Refer also to the System Operation Troubleshooting Testing and Adjusting, RENR8091, "PL1000E
Communication ECM", "Create Parameter Translation Design" section.
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/s... 29/01/2008
Media Search - RENR8091 - PL1000E Communication ECM Page 5 of 6
In the PCL design window, each Caterpillar electronic control from the system block diagram would be
represented by a CDL or a J1939 ECM Object. Each Caterpillar electronic control from the system block
diagram will require a PTE file association. The PL1000E Modbus interface would be represented by a
Modbus ECM. The translations are defined by the "Translation Lines". The "Translation Lines" are defined by
the CDL or J1939 ECM, and by the Modbus ECM.
Each network is different. Each network requires slightly different configurations. The configuration is
dependant upon the hardware and the software that is used in order to configure, manage, and maintain the
system's servers.
If the embedded web server of the PL1000E Communication ECM's is to be accessible over a local network,
then the local network administrator should be contacted in order to obtain the appropriate configurations. The
factory default setting for the PL1000E is "Dynamic Host Configuration Protocol" (DHCP).
In order to change from the DHCP setting, refer to the System Operation Troubleshooting Testing and
Adjusting, RENR8091, "PL1000E Communication ECM", "Internet Protocol Configuration" section.
The Modbus communications must be configured in the PCL file. The Modbus communications must also be
configured separately in the configuration screen of Cat ET.
Refer to the "Modbus Configuration" section of this document in order to determine the appropriate
configurations for the system. The ethernet port is used to transfer the PCL file to the PL1000E. The ethernet
port can be configured with Cat ET or Caterpillar Communication Toolkit.
If the embedded web server is to be used, then the embedded web server must also be initially configured
using Cat ET. Refer to System Operation Troubleshooting Testing and Adjusting, RENR8091, "PL1000E
Communication ECM", "Internet Protocol Configuration" for the appropriate configurations for the system.
Note: Configuration of the PL1000E Communication ECM and preparation of the PCL file may be completed
prior to the actual installation at the system site. The PL1000E Communication ECM does not need to be
connected to the Caterpillar electronic controls in the system in order to allow proper configurations, PCL file
creation, or PCL file installation.
Note: The PL1000E must be configured before installation of the PCL file.
There are several different methods that can be used in order to install the PCL file, however, all of the
methods must be executed using "File Transfer Protocol" FTP over the ECM's ethernet connection. After the
PCL file has been successfully installed on the ECM, the module is ready for installation. Also, the module is
ready for integration with the other Caterpillar electronic controls and the Modbus master.
Refer to the "LAN Network Ethernet Connection" section and to the "PL1000E Communication ECM" section
of this document for information about connection methods.
Also, refer to System Operation Troubleshooting Testing and Adjusting, RENR8091, "PL1000E
Communication ECM", "Direct Crossover Ethernet Connection" section.
Refer to Special Instruction, REHS2362 for installation and wiring requirements of the PL1000E
Communication ECM.
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/s... 29/01/2008
Media Search - RENR8091 - PL1000E Communication ECM Page 6 of 6
Using either the embedded communication adapter of the ECM or other external communication adapters,
verify that the service tool can successfully detect all Caterpillar electronic controls in the system.
Configure or program the Modbus master to request any or all of the status and statistics Modbus registers
from the ECM. In order to retrieve the standard and statistics Modbus register data, the ECM Modbus slave
address that is defined in the Modbus configuration through the Cat ET, Caterpillar Communication Toolkit
(the ECM configuration), or embedded web pages must be used.
Alternately, configure or program the Modbus master in order to request any of the Modbus registers that are
defined in the PCL file for one of the Caterpillar electronic controls in the system. In order to retrieve the
Modbus registers from the other Caterpillar electronic controls in the system, the ECM Modbus slave address
that is defined in the PCL file must be used.