General Specifications: YTA110 Temperature Transmitter

Download as pdf or txt
Download as pdf or txt
You are on page 1of 9

<<Contents>> <<Index>>

General YTA110
Specifications Temperature Transmitter

GS 01C50B01-00EN [Style: S3]

The YTA110 is the high performance temperature


transmitter that accepts Thermocouple, RTD, ohms or
DC milivolts inputs and converts it to a 4 to 20 mA DC
signal for transmission. The YTA110 supports either
BRAIN or HART communication protocol.
The YTA110 in it standard configuration is certified by
TÜV as complying with SIL2 for safety requirement.

 FEATURES
High performance
Microprocesser-based sensing technology ensures
long-term accuracy and high reliability.

High reliability
Dual-compartment housing realizes high resistance
capability to harsh environments, and YTA110 has
Stability
SIL2 capability for safety requirement.
RTD:
Variety of sensor inputs ± 0.1% of reading or ± 0.1°C per 2 years,
whichever is greater at 23±2°C.
The type of sensor input is user-selectable from T/C:
thermocouples (T/C), RTDs, ohms, or DC milivolts. ± 0.1% of reading or ± 0.1°C per year, whichever
is greater at 23±2°C.
Digital communication
5 Year Stability
BRAIN or HART® communication protocol is RTD:
available. The insturment configuration can be ± 0.2% of reading or ± 0.2°C, whichever is
changed by the user with using the BT200 or HART greater at 23±2°C.
communicator. T/sC:
± 0.4% of reading or ± 0.4°C, whichever is
Self-diagnostics function
greater at 23±2°C.
Continuous self-diagnostics capability ensures
Power Supply Effect
longterm performance and lower cost of ownership.
± 0.005% of calibration span per volt
LCD display with bargraph Vibration Effect
The LCD display provides both a digital readout and 10 to 60 Hz 0.21 mm peak displacement
percent bargraph simultaneously. 60 to 2000 Hz 3G
Position Effect
None
 STANDARD SPECIFICATIONS
■ FUNCTIONAL SPECIFICATIONS
■ PERFORMANCE SPECIFICATIONS
Input
Accuracy Input type is selectable: Thermocouples, 2-, 3-, and
(A/D accuracy/span + D/A accuracy) or ± 0.1 % of 4-wire RTDs, ohms and DC milivolts. See Table 1. on
calibrated span, whichever is greater. page 3.
See Table 1. on page 3.
Span & Range Limits
Cold Junction Compensation Accuracy See Table 1. on page 3.
(For T/C only)
± 0.5°C (± 0.9°F) Input signal source resistance (for T/C, mV)
1 kΩ or lower
Ambient Temperature Effect (per 10°C change)
± 0.1 % or ± (Temperature Coefficient /span), Input lead wire resistance (for RTD, ohm)
whichever is greater. See Table 2. for Temperature 10 Ω per wire or lower
Coefficient.

Yokogawa Electric Corporation GS 01C50B01-00EN


2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan ©Copyright June 1998
Tel.: 81-422-52-5690 Fax.: 81-422-52-2018 28th Edition June 2017 (KP)
<<Contents>> <<Index>> 2
Output Supply & Load Requirements
Two wire 4 to 20 mA DC. Output range: 3.68 mA to Supply Voltage
20.8 mA 10.5 to 42 V DC for general use and flameproof type
BRAIN or HART® protocol is superimposed on the 4 10.5 to 32 CV DC for lightning protector (Optional
to 20 mA signal. code /A)
Any single value from the followings can be selected 10.5 to 30 V DC for intrinsically safe, Type n,
as the analog output signal. nonincendive, or non-sparking type
Sensor 1, Terminal Temperature. Minimum voltage limited at 16.4 V DC for digital
Also, up to three of the above values can be communications, BRAIN and HART® protocols
displayed on LCD display or read via communication.
Load
Isolation 0 to 1335 Ω for operation
Input/Output/GND isolated to 500 V DC 250 to 600 Ω for digital communication
Sensor Burnout See Figure 1. on page 4.
High (21.6 mA DC) or Low (3.6 mA DC), Communication Requirements
userselectable.
BRAIN:
Output in Transmitter Failure
Up-scale: 110%, 21.6 mA DC or more (Standard or Communication Distance
Optional code /C3) Up to 2 km (1.25 miles) when using CEV
Down-scale: –5%, 3.2 mA DC or less (Optional code polyethylene-insulated PVC-sheathed cables.
/C1 or /C2) Communication distance varies depending on type of
cable used.
Update Time
Approximately 0.5 seconds Load Capacitance
0.22 µF or less
Turn-on Time
Approximately 5 seconds Load Inductance
3.3 mH or less
Damping Time Constant
Selectable from 0 to 99 seconds Input Impedance of communicating device
10 kΩ or more at 2.4 kHz.
Ambient Temperature Limits
Option code may affect limits. ■ PHYSICAL SPECIFICATIONS
-40 to 85°C (-40 to 185°F)
-30 to 80°C (-22 to 176°F) with Integral Indicator Enclosure
Ambient Humidity Limits Material
5 to 100% RH at 40°C (104°F) Low copper cast-aluminum alloy or SCS14A stainless
steel (option, equivalent to SUS316 cast stainless
EMC Conformity Standards
steel and ASTM CF-8M)
EN61326-1 Class A, Table2
EN61326-2-3 Coating
CE Marking is not conformed. Polyurethan resin baked finish
Color: Deep-sea moss green (Munsell 0.6GY3.1/2.0)
SIL Certification
YTA110 temperature transmitter is certified by TÜV Degrees of Protection
NORD CERT GmbH in compliance with the following IP66/IP67, NEMA4X
standards; Data and tag plate
IEC 61508: 2000; Part1 to Part 7 Functional Safety of SUS304 stainless steel or SUS316 stainless steel
Electrical/electronic/programmable electronic related (option)
systems; Mounting
SIL 2 capability for single transmitter use, SIL 3 Optional mounting brackets can be used either for
capability for dual transmitter use. two-inch pipe or flat panel mounting.
Self-calibration Terminal Screws
The analog-to-digital measurement circuitry M4 screws
automatically self-calibrates for temperature update
by comparing the dynamic measurement to extremely Integral Indicator
stable and accurate internal reference elements. Optional LCD digital indicator includes 5-digit
numerical dispaly with °C, K, °F, °R, % and mV, 0 to
Self-diagnostics 100 % bargraph and dot-matrix display.
Loss of input error, ambient temperature error,
EEPROM error, and CPU error. Up to four error Weight
history can be stored in the memory. 1.2 kg(2.6 lb) without Integral indicator and Mounting
bracket. Integral indicator weights 0.2 kg(0.4 lb).
Manual Output Function Bracket for horizontal pipe: 0.3 kg
The output value can be set manually. Bracket for vertical pipe: 1.0 kg
Electrical Connections
Refer to ‘MODEL AND SUFFIX CODES’ on page 5.

All Rights Reserved. Copyright © 1998, Yokogawa Electric Corporation GS 01C50B01-00EN June 1, 2017-00
<<Contents>> <<Index>> 3
Table 1. Sensor type, measurement range, and accuracy
Minimum Accuracy
Reference Measurement Range
Sensor Type Span Input range A/D Accuracy D/A
Standard
°C °F (Recommended) °C °F °C °F Accuracy
100 to 300 212 to 572 ±3.0 ±5.4
B 100 to 1820 212 to 3308 300 to 400 572 to 752 ±1.0 ±1.8
400 to 1820 752 to 3308 ±0.75 ±1.35
-200 to -50 -328 to -58 ±0.35 ±0.63
E -200 to 1000 -328 to 1832
-50 to 1000 -58 to 1832 ±0.16 ±0.29
-200 to -50 -328 to -58 ±0.40 ±0.72
J -200 to 1200 -328 to 2192
-50 to 1200 -58 to 2192 ±0.20 ±0.36
-200 to -50 -328 to -58 ±0.50 ±0.90
K -200 to 1372 -328 to 2502
-50 to 1372 -58 to 2502 ±0.25 ±0.45
-200 to -50 -328 to -58 ±0.80 ±1.44
N IEC584 -200 to 1300 -328 to 2372
-50 to 1300 -58 to 2372 ±0.35 ±0.63
-50 to 0 -58 to 32 ±1.0 ±1.8
0 to 100 32 to 212 ±0.80 ±1.44
R -50 to 1768 -58 to 3214
100 to 600 212 to 1112 ±0.60 ±1.08
600 to 1768 1112 to 3214 ±0.40 ±0.72
25°C -50 to 0 -58 to 32 ±1.0 ±1.8
Y/C 0 to 100 32 to 212 ±0.80 ±1.44
S -50 to 1768 -58 to 3214 (45°F)
100 to 600 212 to 1112 ±0.60 ±1.08
600 to 1768 1112 to 3214 ±0.40 ±0.72
-200 to -50 -328 to -58 ±0.25 ±0.45
T -200 to 400 -328 to 752 ±0.02%
-50 to 400 -58 to 752 ±0.14 ±0.25
of span
0 to 400 32 to 752 ±0.80 ±1.44
400 to 1400 752 to 2552 ±0.50 ±0.90
W3 0 to 2300 32 to 4172
1400 to 2000 2552 to 3632 ±0.60 ±1.08
ASTM 2000 to 2300 3632 to 4172 ±0.90 ±1.62
E988 0 to 400 32 to 752 ±0.70 ±1.26
400 to 1400 752 to 2552 ±0.50 ±0.90
W5 0 to 2300 32 to 4172
1400 to 2000 2552 to 3632 ±0.70 ±1.26
2000 to 2300 3632 to 4172 ±0.90 ±1.62
-200 to -50 -328 to -58 ±0.30 ±0.54
L -200 to 900 -328 to 1652
-50 to 900 -58 to 1652 ±0.20 ±0.36
DIN43710
-200 to -50 -328 to -58 ±0.50 ±0.90
U -200 to 600 -328 to 1112
-50 to 600 -58 to 1112 ±0.25 ±0.45
Pt100 -200 to 850 -328 to 1562 -200 to 850 -328 to 1562 ±0.14 ±0.25
Pt200 IEC751 -200 to 850 -328 to 1562 -200 to 850 -328 to 1562 ±0.30 ±0.54
Pt500 -200 to 850 -328 to 1562 10°C -200 to 850 -328 to 1562 ±0.20 ±0.36
RTD JPt100 -200 to 500 -328 to 932 -200 to 500 -328 to 932 ±0.16 ±0.29
JIS C1604 (18°F)
SAMA -70 to -40 -94 to -40 ±1.35 ±2.43
Cu -70 to 150 -94 to 302
RC21-4 -40 to 150 -40 to 302 ±1.0 ±1.8
mV -10 to 100 [mV] 3 [mV] ±12 [µV]
— —
ohm 0 to 2000 [Ω] 20 [Ω] ±0.35 [Ω]
Total Accuracy = (A/D Accuracy / Span + D/A Accuracy) or (± 0.1% of calibrated span), whichever is greater.
For T/C input, add Cold Junction Compensation Accuracy (± 0.5 °C) to the total accuracy.
Example; when selecting Pt100 with measurement range of 0 to 200 °C.
0.14°C
× 100% of span +0.02% of span = 0.09% of span
200°C
Since the value is smaller than ± 0.1% of span, the total accuracy is ± 0.1%.

All Rights Reserved. Copyright © 1998, Yokogawa Electric Corporation GS 01C50B01-00EN Sep. 15, 2016-00
<<Contents>> <<Index>> 4
Table 2. Temperature Coefficient

Sensor Type Temperature Coefficient


Thermocouples E, J, K, N, T, L, U 0.08°C + 0.02% of abs.reading
Thermocouples R, S, W3, W5 0.25°C + 0.02% of abs.reading
T/C B 100°C ≤ Reading < 300°C 1°C + 0.02% of abs.reading
300°C ≤ Reading 0.5°C + 0.02% of abs.reading
RTD 0.08°C + 0.02% of abs.reading
mV 0.002 mV + 0.02% of abs.reading
ohm 0.1 Ω + 0.02% of abs.reading
Note 1: Ambient Temperature Effect per 10°C change is ±0.1% or ±(temperature coefficient/span), whichever is greater.
Note 2: The “abs.reading” on Table2 means the absolute value of the reading in °C.
Example of abs reading;
When the temperature value is 250 Kelvin, abs reading is 23.15, absolute (250−273.15).
Example of Ambient Temperature Effect;
Conditions;
1) Input Sensor: Pt100
2) Calibration Range: −100 to 100°C
3) Reading value: −50°C
Ambient Temperature Effect per 10°C;
Temperature Coefficient/Span=(0.08°C+0.02/100×|−50°C|)/{100°C−(−100°C)}= 0.00045 → 0.045%
Therefore, Ambient Temperature Effect is ±0.1%/10°C

600
E-10.5
R=
0.0236 Digital
External Communication
load range
BRAIN and HART
resistance
250

R (Ω)

10.5 16.4 24.7 42


Power supply voltage E (V DC)
F01E.ai

Figure 1. Relationship Between Power Supply


Voltage and External Load Resistance.

F02E.ai

Figure 2. Integral Indicator Display Example.

All Rights Reserved. Copyright © 1998, Yokogawa Electric Corporation GS 01C50B01-00EN Oct. 31, 2014-00
<<Contents>> <<Index>> 5
 MODEL AND SUFFIX CODES
Model Suffix Codes Descriptions
YTA110 . . . . . . . . . . . . . . . . . . . . Temperature Transmitter
Output Signal -D. . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital commnuication (BRAIN protocol)
-E. . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication (HART protocol, refer to GS 01C50T01-00EN)
— A. . . . . . . . . . . . . . . . Always A
Electrical Connection 0 . . . . . . . . . . . . . G1/2 female
2 . . . . . . . . . . . . . 1/2 NPT female
3 . . . . . . . . . . . . . Pg 13.5 female
4 . . . . . . . . . . . . . M20 female
Integral Indicator D. . . . . . . . . . with digital indicator
N. . . . . . . . . . None
Mounting Bracket B. . . . . . . . SUS304 Stainless steel 2-inch horizontal pipe mounting *1
D. . . . . . . . SUS304 Stainless steel 2-inch vertical pipe mounting *1
J . . . . . . . . SUS316 Stainless steel 2-inch horizontal pipe mounting *1
K. . . . . . . . SUS316 Stainless steel 2-inch vertical pipe mounting *1
N. . . . . . . . None
Option codes / Optional specifications
*1: For flat-panel mounting, please prepare bolts and nuts.

 OPTIONAL SPECIFICATION
Item Description Code
Lightning protector Power supply voltage: 10.5 to 32 V DC
A
Allowable current: Max. 6000 A (1×40µs), repeating 1000 A (1×40µs) 100 times
Painting Coating change Epoxy resin coating X1
Color change Amplifier cover only Munsell code: N1.5 Black P1
Munsell code: 7.5BG4/1.5, Jade green P2
Metallic silver P7
Amplifier and terminal Covers Munsell code: 7.5 R4/14 Red PR
SUS316 exterior parts Exterior parts on the amplifier housing (name plates, tag plate, screws) will become
HC
SUS316 stainless steel *2
Calibration Unit Degree F/Degree R unit D2
Output signal low-side in Output signal low-side: -5%, 3.2 mA DC or less.
C1
Transmitter failure Sensor burnout is also set to 'LOW': -2.5%, 3.6 mA DC.
NAMUR NE43 Compliant Output signal limits: Failure alarm down-scale: output status at CPU failure and
3.8 mA to 20.5 mA hardware error is -5%, 3.2 mA or less. C2
Sensor burnout is also set to LOW: -2.5%, 3.6 mA DC.
Failure alarm up-scale: output status at CPU failure and
hardware error is 110%, 21.6 mA or more. C3
In this case Sensor burnout is High: 110%, 21.6 mA DC.
Data Configuration Description into “Descriptor” parameter of HART protocol (max. 16 characters) CA
Stainless steel housing *1 Housing Material: SCS14A stainless steel (equivalent to SUS316 cast stainless steel and
E1
ASTM CF-8M)
Wired tag plate SUS304 stainless steel tag plate wired onto transmitter *3 N4
*1: Not applicable for optional code JF3, G12, P1, P2, P7, PR, and X1.
*2: This specification is not included in option code E1. Select HC for SUS316 exterior parts regardless of E1.
*3: When HC is selected, the material is SUS316 stainless steel.

All Rights Reserved. Copyright © 1998, Yokogawa Electric Corporation GS 01C50B01-00EN Oct. 31, 2014-00
<<Contents>> <<Index>> 6
 OPTIONAL SPECIFICATION (For Explosion Protected type)
Item Description Code
Canadian Standards CSA Intrinsically safe, non-incendive and Explosionproof approval combination
Association (CSA) [Intrinsically safe/non-incendive approval]
Applicable standard: C22.2 No0, C22.2 No0.4, C22.2 No25, C22.2 No94, C22.2 No142,
C22.2 No157, C22.2 No213
Certificate: 172608-0001053837
Intrinsically safe for Class I, Division 1, Groups A, B, C and D; Class II, Division 1,
Groups E, F and G; Class III, Division 1:
Non-incendive for Class I, Division 2, Groups A, B, C and D; Class II, Division 2,
Groups E, F and G; Class III, Division 1:
Enclosure Type 4X Temperature Class: T4, Ambient Temperature: -40 to 60°C
Supply: Vmax=30 V, Imax=165 mA, Pmax=0.9W, Ci=18nF, Li=730µH CU1
Sensor input: Voc=9 V, Isc=40 mA, Po=0.09W, Ca=1µF, La=10 mH
Electrical Connection: 1/2 NPT female*2
[Explosionproof approval]
Applicable standard: C22.2 No0, C22.2 No0.4, C22.2 No25, C22.2 No30, C22.2 No94,
C22.2 No142, C22.2 No157, C22.2 No213, C22.2 No1010.1
Certificate: 1089576
Explosionproof Class I, Div.1, Groups B, C and D, Class II, Groups E, F and G, Class III.
For Class I, Div.2 Locations “FACTORY SEALED, CONDUIT SEAL NOT REQUIRED”
Enclosure TYPE 4X Temperature Class: T6 Ambient Temperature: -40 to 60°C
Electrical Connection: 1/2 NPT female*2
Factory Mutual (FM) FM Intrinsically safe, non-incendive and Explosionproof approval combination
[Intrinsically safe/non-incendive approval]
Applicable standard: FM 3600, FM 3610, FM 3611, FM 3810
Intrinsically safe for Class I, II, III Division 1 Groups A, B, C, D, E, F and G.
Non-incendive for Class I, II, Division 2 Groups A, B, C, D, F and G Class III, Division 1.
Enclosure Type: 4X Temperature Class: T4 Ambient Temperature: -40 to 60°C (-40 to 140°F)
Supply: Vmax=30 V, Imax=165 mA, Pmax=0.9W, Ci=18nF, Li=730µH
Sensor: Voc=9 V, Isc=40 mA, Po=0.09W, Ca=1µF, La=10 mH FU1
[Explosionproof approval]
Applicable standard: FM 3600, FM 3615, FM 3810, ANSI/NEMA 250
Class I, Division 1, Groups A, B, C and D.;
Dust-ignitionproof for Class II/III, Division 1, Groups E, F and G.
"FACTORY SEALD, CONDUIT SEAL NOT REQUIRED." Enclosure Ratings: TYPE 4X
Temperature Class: T6 Ambient Temperature: -40 to 60°C (-40 to 140°F)
Electrical Connection: 1/2NPT female*2
FM Explosionproof approval
Applicable standard: FM 3600, FM 3615, FM 3810, ANSI/NEMA 250
Explosionproof Class I, Division 1, Groups A, B, C and D;
Dust-ignitionproof for Class II/III, Division 1, Groups E, F and G. FF1
“FACTORY SEALED, CONDUIT SEAL NOT REQUIRED.” Enclosure Rating: TYPE 4X
Temperature Class: T6 Ambient Temperature: -40 to 60°C (-40 to 140°F)
Electrical Connection: 1/2 NPT female*2
IECEx IECEx Intrinsically safe, Flameproof and Dust ignition proof Approval
[Intrinsically safe approval]
Applicable standard: IEC 60079-11:2011, IEC 60079-0:2011, IEC 60079-26:2006
Certificate No.: IECEx KEM 09.0032X
Ex ia IIC T4...T5 Ga, Ex ic IIC T4...T5 Gc
Ambient Temperature: -40 to 70°C for T4, -40 to 50°C for T5
Enclosure: IP66/IP67
Supply circuit : Ui = 30 V, Ii = 165 mA, Pi = 900 mW, Ci = 20nF, Li = 730μH (Ex ia IIC T4...T5 Ga)
: Ui = 30 V, Ci = 20nF, Li = 730μH (Ex ic IIC T4...T5 Gc)
Sensor circuit: Uo = 9 V, Io = 40 mA, Po = 90 mW, Co = 0.7μF, Lo = 10 mH
SU2
[Flameproof and Dust ignition proof]
Applicable Standard: IEC 60079-0: 2011, IEC 60079-1: 2014-06, IEC 60079-31:2013
Certificate: IECEx KEM 07.0044
Ex db IIC T6/T5 Gb, Ex tb IIIC T70°C/T90°C Db
Ambient Temperature for Gas Atmospheres: -40 to 75°C (-40 to 167°F) for T6,
-40 to 80°C (-40 to 176°F) for T5
Ambient Temperature for Dust Atmospheres: -30 to 65°C (-22 to 149°F) for T70°C,
-30 to 80°C (-22 to 176°F) for T90°C
Enclosure: IP66/IP67
Electrical Connection: 1/2 NPT female and M20 female*1

All Rights Reserved. Copyright © 1998, Yokogawa Electric Corporation GS 01C50B01-00EN June 1, 2017-00
<<Contents>> <<Index>> 7
Item Description Code
TIIS Certification*3 TIIS Flameproof approval
Ex ds IIC T6 X JF3
Amb. Temp.: -20 to 60°C
Attached flameproof Electrical connection: G1/2 female
2 pc. G12
packing adapter*4 Applicable cable: O.D. 8.5 to 11 mm
*1: Applicable for Electrical Connection Code 2 and 4.
*2: Applicable for Electrical Connection Code 2.
*3: Not applicable for /HC and /E1.
*4: If cable wiring is to be used to a TIIS flameproof type transmitter, do not fail to add the YOKOGAWA-assured flameproof
packing adapter.

All Rights Reserved. Copyright © 1998, Yokogawa Electric Corporation GS 01C50B01-00EN June 1, 2017-00
<<Contents>> <<Index>> 8
 DIMENSIONS
Unit: mm (Approx. inch)
 2-inch horizontal pipe mounting
65.4(2.57)
111(4.37) 47(1.85) 66(2.60)
Electrical Connection 18.5
(Input signal) Terminal Cover
Electrical Connection (0.73)
(Output signal) With Indicator
(Optional)

ø93(3.66)
102(4.02)

164(6.46)
Shrouding Bolt Ground Terminal

(1.57)
40
(For Explosionproof type)
Tag Plate

Horizontal Pipe

(0.98)
Mounting Bracket

25
(Optional)

56(2.21) 2-inch pipe, ø60.5(ø2.38)


70(2.76)
90(3.54)

 2-inch vertical pipe or horizontal mounting 65.4(2.57)


47(1.85) 66(2.60)
111(4.37) Electrical Connection 18.5
(Input signal) Terminal Cover
(0.73)
Electrical Connection
(Output signal) With Indicator
(Optional)

ø93(3.66)
Shrouding Bolt
(For Explosionproof type)
209.5(8.25)
191.5(7.54)

Ground Terminal
Tag Plate
Vertical Pipe
Mounting Bracket
46(1.81)

(Optional)

2-inch pipe, 64(2.52)


ø60.5 (ø2.38) 101(3.98)
70(2.76)
98(3.86)
F03E.ai

All Rights Reserved. Copyright © 1998, Yokogawa Electric Corporation GS 01C50B01-00EN Oct. 31, 2014-00
<<Contents>> <<Index>> 9
Terminals
Terminal Configuration
Power Supply and output terminal
Communication
Terminals (BT200 etc.) External Indicator (ammeter) terminal *1
Connection hook
Ground terminal
*1: When using an external indicator or check meter, the
CHECK METER internal resistance must be 10Ω or less.
Connection hook *1 This hook is not available for Fieldbus communication
type(output signal code F).
M10×1.5 12-deep female
for mounting bracket
F04E.ai

Input Wiring

Single input (YTA110)


(A) (A) (A)
1 1 1 1
(+) (B) (A)
2 2 2 2
(B) (B) (B)
3 (–)
3 3 3
(B)
4 4 4 4
5 5 5 5

T/C or DC milivolts two-wire three-wire four-wire


RTD or ohm RTD or ohm RTD
F05E.ai

< Ordering Information > Table A. Settings upon shipment


Specify the following when ordering Model, suffix
codes, and optional codes. Input sensor type Pt100 three-wire system, or
as specified
The instrument is shipped with the settings shown in
Calibration range lower limit "0" or as specified
Table A. Specify the following when necessary.
Calibration range upper limit "100" or as specified
1. Sensor type.
For RTD and resistance input, specify the number of Calibration unit "°C" or as specified
wire as well. (Example; Pt200 3-wire system) Damping time constant 2 seconds
2. Calibration range and unit Sensor burnout *1 High (110%, 21.6 mA DC)
1) Calibration range can be specified within the Output in Transmitter failure *1 High (110%, 21.6 mA DC or
measurement range shown in Table 1. on page more)
3. Integral Indicator *2 PV
2) Specify one range from °C, K, °F or °R for Output type Sensor 1
temperature input. °F and °R are available when Tag number As specified in order
Optional code D2 is specified. It is not necessary
to specify the unit of mV and ohm inputs, for *1: Except when Optional code C1 or C2 is specified.
these units automatically will be mV or Ω. *2: When Integral indicator is specified.
3. Tag Number
4. Other Items related with options < Related Instruments >
/CA option allows specifying the setting Descriptor for Power Distributor:
HART protocol type at factory. Refer to GS 01B04T01-02E or GS 01B04T02-00E
Specify upto 16 characters to be entered in the BRAIN TERMINAL: Refer to GS 01C00A11-00E
Descriptor parameter.
< Reference >
HART; Trademark of The HART Communiation
Foundation. (USA)
Material Cross Reference Table

SUS304 AISI 304


SUS316 AISI 316

All Rights Reserved. Copyright © 1998, Yokogawa Electric Corporation GS 01C50B01-00EN Oct. 31, 2014-00
Subject to change without notice.