Generator Exciter & Voltage Exciter
Generator Exciter & Voltage Exciter
Generator Exciter & Voltage Exciter
9.0 GENERATOR, EXCITER, AND through a magnetic field. Figure 9-1 shows
VOLTAGE REGULATION the principles being discussed in this
section. As the conductor passes through
This chapter presents the major the magnetic field, in this case downward, it
components of the electrical generator, the cuts each of the lines of magnetic force
exciter, and the voltage regulator and (flux) which causes a current to be
explains how they relate to the "induced" in the conductor. Because the
development of power by the diesel engine conductor has a resistance, it is known
driven generator unit. from 'ohms law' that the voltage is equal to
the current times the resistance.
Learning Objectives Therefore, a voltage is also 'induced'
between the two ends of the conductor. If
As a result of this lesson, you will be able to: the conductor is connected to a closed
electrical circuit, this voltage would cause a
1. Describe the functions of the generator, current to flow. The amount of current flow
exciter, and voltage regulator. is a function of the voltage induced and the
electrical resistance of the load in the
2. Identify the major components of the circuit.
generator and how they inter-relate.
9.1.2 Induced Voltage
3. Describe how diesel engine output
power relates to the power demands of The actual voltage induced in the conductor
the generator. is determined by the number of lines of flux
cut per unit of time. Two key factors affect
4. Describe the function of the excitation the magnitude of voltage induced.
system and the associated voltage
regulator. • The speed at which the conductor
moves through the fixed magnetic field
5. Identity the major components of the and the strength of the magnetic field
exciter and voltage regulator system. determine the output voltage. This
speed is a function of the rotational
9.1 Generator Principles speed (RPM) of the generator /engine.
As the speed of the engine the
The following is a brief discussion of generator increases, the voltage
generator operation and its relationship to produced also increases.
the mechanical load placed on the diesel
engine. Since the operating speed of the engine
and generator is constant in order to
9.1.1 Electromagnetic Induction maintain the desired frequency, another
method of voltage control must be
Electromagnetic induction, the basic employed.
principle of generator operation, involves
the movement of an electrical conductor • Generator output voltage is most often
controlled by regulating the strength This is shown in the part of the diagram
(flux intensity) of the magnetic field. labeled 'Start.' As the armature is turned to
This is accomplished by the generator a position 90 degrees from the first, the two
excitation system. The excitation ends of the loop is acted upon in a manner
system monitors the generator output wherein the voltages generated at each
and regulates the magnetic field to end of the loop are additive, as shown in
maintain the desired voltage. As the the '1/4-cycle' diagram. Peak output
load on the generator is increased, an voltage is generated at each cycle point.
increase in current flow causes the As the armature continues to rotate, it
voltage to drop. The excitation system again gets to a position of no voltage
senses this decrease in voltage and generation, shown in the ‘½-cycle diagram’.
increases the strength of the magnetic As the rotation continues, a voltage is again
field to return the voltage to the desired generated. A close examination of the
level. wiring out of the armature reveals that the
connections have become inverted. This
9.1.3 How the generator works results in the opposite polarity of voltage.
Figure 9-2 shows the principles discussed The diagram at the bottom of the figure
above implemented into a machine to shows the resulting build-up and decay and
produce a voltage. In this implementation, opposite polarity build up and decay again
a ‘U’ shaped form is provided with a ‘gap’ through two cycles (two rotations of the
between the open ends of the ‘U’. A coil of armature). The resulting voltage build-up
wire is wrapped about the legs of this form and decay forms a sinusoidal wave that is
to produce a magnetic field across the gap. defined as 'Alternating Current' or AC.
In the gap, an armature is formed by a loop
of wire. The loop exits the armature onto This is the basis for a single phase
two slip rings. The slip rings are contacted alternator. Two other sets of coils offset by
by brushes that connect the generator to 120 degrees and connected to slip rings
the outside electric circuit. An engine or would form a machine to generate 3-phase
some other prime mover is connected to AC power. This is the basis for all AC 3-
the armature causing it to rotate inside the phase generation.
gap. When the ‘field’ coil is energized to
establish a magnetic field/flux in the gap If instead of using two slip rings a single
and the armature is then rotated, a voltage ring that is split into two segments were
is generated in the armature. The slip rings used, as the armature rotated, there would
and brushes conduct this voltage out to be a buildup and decay of voltage as
some load "A." before; but the split slip ring would reverse
the connection on each half revolution.
Figure 9-3 shows a blowup of the armature The split slip ring configuration is commonly
in the gap. As the armature is rotated in its referred to as a 'commutator.' This would
initial position, no voltage is created result in a machine that puts out a pulsating
because the magnetic flux is equal but DC current. By combining a great many
opposite on both branches of the loop. poles and the same number of segments
on the armature commutator, an almost voltage. This is the case when the power
steady DC output would be produced. This factor is 1.0 (unity). The real power (KW) in
is the principle of the DC generator or that case is equal to the apparent power
motor. (KVA). These terms will be discussed later.
When the current is not in phase with the
The AC alternator described above has a voltage, there is a lesser power factor, and
number of problems. The armature and its the KW is less than the KVA. The KW is
slip rings have to handle all the load current still in phase with the voltage, but the KVA
that is produced by this generator. The has shifted slightly due to the shift in the
brushes and slip rings restrict the amount current. This introduced KVAR, and will be
of current that can be handled. To explained later.
eliminate this problem, design and
construction were changed such that the 9.2 Generator Construction
small excitation current now goes through
the brushes and slip rings to the rotating Figure 9-5 shows a cutaway of a typical
armature field. The large AC current generator. The generator consists of a
induced into the stationary stator windings shaft on which is mounted a hub, more
is transmitted to the loads by solid often called the spider. The spider may be
connections. This same principle also attached to the shaft by a press fit, with or
applies to AC synchronous motors as there without keys, or by a flange and bolting.
is little difference between an AC generator The spider has slots into which the field
and an AC synchronous motor. It is a pole pieces are attached. Together, this
matter of what is driving the system – an makes up the ‘rotor’. The rotor assembly
electric motor or an engine-driven usually also includes slip rings used to
generator. convey the field current into the field
windings. These windings are wrapped
This also simplifies the construction of the around the pole pieces. A view of a rotor
generator. These machines very often also and shaft assembly is shown in Figure 9.7.
are called 'alternators' in as much as the
voltage and current are alternating. A The stator core consists of a special steel
three-phase generator/alternator is simply stampings, called laminations, with slots to
three single phase machines interlaced hold the stator windings. The stator core
with one another, sharing the same rotor has spaces between some of the
assembly, with wiring brought out to laminations through which air is force by
connect each phase into the electrical fans on the rotor assembly. This is to
system. The result of the interlacing of the provide cooling for the stator core and the
alternator windings is shown on the voltage windings. A steel framework supports and
trace shown at the bottom of Figure 9-4. aligns the stator core assembly. The steel
framework also usually supports the
The upper part of Figure 9-4 shows how bearings of the generator. Some
the current of each/any phase acts to generators are supplied with two dedicated
produce the power. The left-most diagram bearings, one at each end of the generator
shows the current in phase with the rotor assembly. Others are supplied with
The wiring in the stator slots is grouped in As a short cut, for 60 Hz power generators,
sections. The number for each phase N = 7,200 / P and, therefore, P = 7,200 / N
matches the number of poles on the rotor.
These various sections are wired together All generators have an even number of
around the periphery of the stator. The end poles. An engine running at 900 rpm would
of these groups are gathered together and have 8 poles on its generator to produce 60
brought out to the generator electrical Hz power.
connection box.
9.3.2 Mechanical Loading
Figure 9-6 shows an assembled generator,
ready for installation to an engine. This As the electrical conductors move through
particular machine has a shaft driven the magnetic field of the generator, an
exciter unit, the smaller diameter cylinder opposing magnetic field is created around
shown on the end of the generator. the conductors. This opposing field resists
Figures 9-6 through Figure 9-22 show the movement of the conductors through
various parts and aspects of the assembly the generator magnetic field. The physical
of the parts of the generator. force, or power, provided by the diesel
engine must be sufficient to overcome the
9.3 Generator Terminology resistance of the opposing field in order to
achieve the desired voltage and frequency.
9.3.1 Generator Frequency
As the load on the generator increases in
Another key element in the output of the the form of an increase in current demand,
generator is the frequency. Frequency is a the excitation system increases the density
function of the rotational speed (RPM) of of the magnetic flux by increasing the
the engine and the number of poles current in the generator field. This
(magnetic fields) in the generator as shown increases the resistance to movement of
in the following equation. As the operating the conductors through the field. As a
speed of the engine and generator is result, the generator induced voltage
reduced, the number of poles must be decreases momentarily until the excitation
increased to achieve 60 hertz. An EDG system compensates to return the voltage
operating at 450 RPM would require twice to its previous level. Since the load was
as many poles as a unit operating at 900 increased with relatively constant voltage,
RPM. Once designed, the number of poles the output current (and hence, output
in an alternating current (AC) machine is power) of the generator must increase.
fixed. This power demand is also felt on the
diesel engine which is trying to maintain the
· speed constant as the load from the
120 generator increases.
Real power in an alternating current (AC) 1000 for KA or 1,000,000 for MVA.
system refers to the true electrical power
that is converted to mechanical energy 9.4.3.4 Power Factor
such as a motor driving a pump. This
power is measured in watts or kilowatts Power factor is the ratio of Real Power
(kW) (or mega-watts - MW) for large (KW) to Apparent Power (KVA). It is a
electrical systems. measure of the utilization of the input power
of a system or equipment. A typical power
9.4.3.2 Reactive Power -- KVAR factor for the rating of the generator, per
NEMA standards, is for a power factor of
Most electrical systems that undergo 0.8 (80%).
changes of voltage or current have either
capacitance or inductance. In a DC For example, the generic plant FSAR
system, these are only important during a specifies that the standby EDG be rated at
significant change. Because AC power is 4000 KW. To provide this real power input
continually changing (the voltage is and generate enough 'magnetizing' power
sinusoidal), the inductance and/or for the generator rotor and stator, the
capacitance become more important. generator is rated at an apparent power of
Electrical power is needed in AC machinery 5000 KVA.
(motors, generators, and transformers) to
create the magnetic fields and voltage 9.4.3.5 Relationship between KW, KVA,
induction that enable these machines to KVAR, and Power Factor
operate. This ‘magnetizing’ power, which is
‘stored’ energy in the AC system, is There is a relationship between the KW,
reactive power. The current component of KVA, KVAR, and Power Factor that allows
this power acts at 90 degrees from the real us to calculate any one, knowing at least
power (KW). Reactive power is measured two others. That relationship is described
in volt-amperes-reactive or VARs. For high by the following formulae:
voltage systems, reactive power may be
measured in kilo-VARs or mega-VARs
(KVAR or MVAR)
As its name implies, apparent power is the For power factor in percent, multiply the
power that is ‘apparently’ required to be decimal value by 100.
input or drawn from the AC system.
Apparent power is volt-amperes, kilovolt- Note that the relationships between KW,
amperes, or megavolt-amperes (VA, KVA KVAR, and KVA is the same as that for any
or MVA). It is determined by multiplying the right triangle – The Pythagorean theorem.
voltage times the amperes times the
square root of three for 3-phase electrical Also, note that the triangular relationship
systems and then dividing the result by between the three factors can be solved if
any two are known. This also includes the result of generator, exciter, and voltage
power factor in as much as the power regulator characteristics and response.
factor gives the relationship (ratio) between The frequency dip is a result of engine and
the KW and KVA. So knowing KW or KVA governor characteristics and response.
and the Power Factor, one can get the The engine knows nothing of the KVAR
other and from that the third. loading except as that may influence the
efficiency of the generator and its
KW is usually measured and displayed on relationship to the engine.
a meter. KVA can be obtained by taking
the voltage (average for the 3 phases) and The KW loading on the generator is
the current (average for the 3 phases), converted to the engine Horsepower
multiplying them together, and then required using the following relationship:
multiplying that result by the square root of
3 (1.73) for a three-phase power system,
then dividing by 1000 to get the kilo-VA. ·
. %
KVAR may be displayed on a meter as well
as Power Factor being displayed.
9.5 Excitation and Voltage Regulation
There is no means of directly measuring
Every power generation system requires
KVAR or PF other than special meters for
some means of controlling the voltage
that purpose or by calculation using the
and/or current produced by the machine.
above formulas. The Power factor meter is
The output of a generator is normally
the least accurate of any of the electrical
controlled by controlling the current in the
parameter meters. It is far more accurate to
field of the generator, the speed being
solve the triangular relationship between
constant for a set frequency. Various
KW and KVA as shown in paragraph
excitation systems are possible and all
9.4.3.4.
usually include some system of sensing
and controlling the generator output
It is convenient at this point to emphasize a
voltage.
principle that applies to all engine driven
generator systems.
9.5.1 Types of Excitation Systems
• THE GOVERNOR ON THE ENGINE
Excitation systems vary from the very
CONTROLS OR RESPONDS TO THE
simplest to rather complex systems. The
KW LOADING ON THE GENERATOR.
simplest would consist of a battery to
supply excitation power to the generator
• THE VOLTAGE REGULATOR AND
field along with a rheostat to control the
EXCITER SYSTEM CONTROLS OR
amount of excitation current, that being
RESPONDS TO THE KVA and
managed manually by an operator. This
thereby the KVAR loading.
system is generally not acceptable;
therefore, some means of automatic
The two control devices are quite
control is desired. It may consist of
independent otherwise. Voltage dip is a
automating the rheostat such as the old
Westinghouse rocking arm Silver Stat Most excitation systems used at nuclear
design. It worked; it wasn’t fast and had power stations are either the Series Boost
droop in the voltage regulation, but it was (SB) or the fully electronic Static Exciter
simple. Voltage Regulator (SEVR) system. These
are more similar than they are different in
Most modern excitation systems involve most cases, and they will be explained by
electronics in the voltage sensing and explaining the excitation system shown in
regulation and are relatively fast and Figure 9-23.
accurate. Many exciter systems consist of
an excitation generator driven by the The exciter output DC voltage type is fed
engine either directly or by a system of through bundles of slip rings into the main
pulleys and belts. The excitation generator generator field windings.
puts out the power, and a voltage regulator
controls that generator’s field in such a way
that the main generator’s field is under 9.5.2 Explanation of Elements of the
control. Electronic (Static) Type Excitation
System
Many commercial systems use what is
termed a brushless exciter. With a Figure 9-23 shows the elements in the
brushless excitation system, an typical modern electronic excitation system.
alternator/generator is mounted on the end While there are differences between the
of the generator shaft and is driven along Series Boost (SB) and the Static Exciter-
with the main generator. A permanent Voltage Regulator (SEVR) systems, the
magnet field excites the alternator as it basic elements are the same in both
rotates. The alternator output goes through systems. Their differences will be
a diode bridge which converts it into DC explained as each section of the systems is
that is fed into the generator field through explained.
wires running along the shaft between the
alternator’s output section and the main Figure 9-23 shows the generator on the far
generator field. There are no brushes in left with its load lines going to the right, until
this type system, thus the term ‘brushless they finally pass through the generator
exciter’. A control winding is included in the output circuit breaker and on to the loads.
permanent magnet field to control the As each load line exits the generator, it
output of the exciter alternator, and thereby goes through the primary side of a Power
the main generator’s field. There are a few Current Transformer (PCT). The
of these systems at nuclear stations. They secondary side of these transformers feed
are not as fast and responsive as the fully power for excitation into the exciter
electronic system that is discussed below. package. Most of the modern exciter
They are limited in power capability, and systems have these Power Current
their overall response is slow because the Transformers to supply some of the
system has to operate through two sets of excitation current required by the generator
magnetics the exciter alternator and the field.
main generator field.
Properly sized PCTs, supply power for the unit. This is not desirable in the
excitation in direct proportion to the load on isolated 'emergency mode'. The terms
the generator. The generator exciter used on the switching this control function
system requires about 1 to 2 percent are usually referred to as 'unit' (without
generator’s output power. current compensation) and 'parallel' (with
current compensation).
As the load lines continue beyond the PCT
connections, there are connections to a The voltage regulator receives a reference
Power Potential Transformer (PPT). Since signal from the operator or system which
there is no generator output current when tells it the voltage to maintain. This voltage
there is ‘no load’ on the generator, there may be modified by the current
must be some other source of power for compensation circuit if the exciter is set up
generating excitation when there is no load. for ‘parallel’ operation. In this case, the
The PPTs supply the power for generator reference input of the regulator is
excitation when the generator is not loaded. compared to the sensed voltage input. The
voltage regulator’s output is changed to
As the load lines continue beyond the PPT restore the generator output voltage back
connection, there is another PT connection to the reference voltage input.
for sensing the generator output. This is
fed into the Voltage Regulator section as a The output signal from the voltage regulator
sense of the generator output voltage. controls elements in the Power Section of
the exciter system. This section is attached
Beyond the sensing PT connection, there is to the Power Potential Transformers.
another Current Transformer (CT) for Properly sized PTs control the output
sensing the amount of load (via the current, voltage without the need for current
assuming the voltage is constant). This is compensation.
used to adjust the voltage regulator’s
output when the unit is being paralleled to Generally there are two methods of
the grid (infinite bus). In order to control controlling the power section. In the case
the reactive power component of the load of the Series Boost (SB) exciter, the
current when paralleled, the voltage transformers (PPTs) have a third (tertiary)
regulator has to receive some sense of the winding. The PPTs are like normal
load on the system. This is equivalent to transformers if the tertiary winding is not
the droop function in the governing system. turned on. However, if there is current in
This principle is variously called 'current the tertiary winding, it causes the
compensation,' 'load compensation,' transformers to become saturated to the
‘paralleling load sensing’ or ‘voltage droop’. point that the current transfer from the
The function is usually switched out primary of the PPT to the secondary is (can
automatically when the diesel generator is be) restricted; thus, the output current can
in the 'emergency mode.' It is required only be controlled. These transformers are
in parallel operation. If the circuit were left therefore often called 'saturable reactors'.
active in ‘emergency mode’, there would be
a slight change in voltage as load is put on In the case of the SEVR type exciter, the
amount of current out of the power section regulator. That is, all of the power
is controlled by turning on or holding off the generated in the exciter goes to the
firing of silicone controlled rectifiers (SCRs) generator field circuit. There are SCRs that
or similar electronic elements. If a large are connected in parallel with the generator
amount of power is required, the SCRs are field that shunt the proper amount of
fired early in the voltage cycle. If less current around the field in order to control
power is required, the SCRs are fired later. the current that goes through the field.
If no power is required (in the voltage
overshoot situation), the SCRs are not Other than these differences, most exciter
turned on. This is the means of controlling systems are more alike than different, and
the no-load excitation power in such a all contain the basic elements shown in
system. Figure 9-24.
The power from the power section is sent There is generally some feedback from the
over to the rectifier section where it is exciter output section to the voltage
joined with the power from the PCTs. This regulator section so that the voltage
is rectified (converted) from AC to DC regulator can anticipate what it needs to do
(direct current) and sent on to the generator next or if it needs to help stabilize the
field as shown. There is usually a voltage regulator. In most regulation systems
meter and an amperage meter in the field without feedback, the systems tend to turn
circuit so that the field conditions can be all the way 'on' or all the way 'off' and this is
monitored. The generator field can accept not desirable. Therefore, feedback helps
only a direct current supply. The generator the regulator know how much excitation is
acts as a fixed resistance, changed only being put out so it can gauge that against
slightly by its temperature. Therefore, the the error and anticipate that the problem is
field voltage and current are proportional. nearly resolved, et.al.
This is helpful in troubleshooting some
types of exciter/generator problems such These exciters are self-sustaining. That is,
as detecting a short or ground in the they take the power they need from the
generator field. generator output. They require no external
power for normal operation. But that also
There are a number of differences in some means that they will probably not start
excitation techniques that are worth themselves up when required. Therefore, a
mentioning. In the Westinghouse and GE means of starting the excitation process
exciters, the power section output, and the has to be provided. This is done with the
PCT, contributions are rectified separately 'Field Flashing' circuit, also shown on
and joined together in the DC field circuit. Figure 9-23. That circuit consists of a
In the Basler and Portec systems, the battery (maybe the station batteries) and a
power section and PCT contributions are switch. The switch is closed when the
joined on the AC side and rectified after system is signaled to start up (usually upon
they are joined. the engine achieving a certain speed), and
the switch is opened when the voltage
The Portec exciter is a 'shunt' type regulator senses that the generator voltage
has built up to a certain value (usually side of the exciter rotor. It serves to
about 65 to 75% of rated voltage). Inside change the AC exciter output to DC. The
the rectifier section this circuit usually output is fed through a hole in the exciter
includes a diode to block reverse current shaft to the main generator. It exits after
from the exciter back into the batteries. passing through the rear of the generator
Usually, some resistors are included to limit housing and connects to the rotating main
the current available from the batteries generator field windings. There are no slip
because only a small current is needed into rings or brushes.
the generator field to get generation
started. The field of the exciter generator is
stationary. Its housing is mounted onto the
Most of the modern excitation systems rear end of the main generator.
have the capability of putting out an
immense amount of power if needed. To Another alternator may be mounted
sustain rated load may not take much outboard of the exciter generator. This unit
power, but to start a large motor load may would have a permanent magnet rotor,
tax the generator and exciter system. Most usually mounted on the back of the
of the modern exciters are capable of generator shaft. The stator winding of this
putting out about 3 to 5 times (300 to alternator puts out an AC current/voltage to
500%) of the generator’s normal full load a voltage regulator. The voltage regulator
excitation current. This is called ‘field turns that AC input into a DC output which
forcing’. The voltage dip caused by starting is controlled so as to ultimately control the
a large motor is primarily a function of the current into the main generator field.
generator characteristics (specifically the
transient and sub-transient reactances). If the unit does not have this permanent
However, the rate of recovery and a few magnet alternator (PMA), another source of
percent of the voltage dip can be influenced voltage for the voltage regulator must be
by the response and the field forcing provided. In a number of cases, that may
capability of the excitation system. be from a battery. In other cases, it is from
the main generator output (reduced in
9.5.3 Brushless Excitation Systems voltage by a transformer). In this last case,
since the voltage source is not available
A brushless excitation system has the when the EDG is being started, a battery is
advantage of not having brushes to used to ‘flash’ the system until the
transmit the current to the generator field generator voltage has built up to a near
through slip rings and brushes. Figure 9-24 rated voltage condition, similar to flashing
shows a schematic diagram of the typical the field on the static exciter systems
brushless exciter system. discussed above.
voltage regulator. While there are some and output. When it comes to response to
advantages to digitizing the voltage the voltage dip caused by starting large
regulator for the purpose of better voltage motors, that is primarily influenced by the
stability during isolated operation (powering characteristics of the generator and would
the emergency bus), and of controlling not be appreciably influenced by having a
reactive power (power factor) a little tighter faster and more complicated voltage
when in parallel with the offsite power regulator. The more components in a
system, the effect would be small in a system, the less reliable the system
comparison to the existing analog systems. becomes.
The voltage regulator operates basically
from analog inputs and in the case of the 9.6 Generator Output Breaker
Basler Series Boost systems (used at most
plants), the output is also analog, there is Figure 9-23 also shows the main generator
little advantage to inserting digital output beaker at the right end of the
components in between the input and diagram. The generator output breaker
output. When it comes to response to the connects the generator to its Class 1E
voltage dip caused by starting large motors, emergency bus. When an emergency
that is primarily influenced by the start signal is received, the EDG starts and
characteristics of the generator and would comes up to rated speed and voltage. The
not be appreciably influenced by having a output circuit breaker is closed
faster and more complicated voltage automatically. An auxiliary contact on the
regulator. The more components in a circuit breaker provides a signal to the load
system, the less reliable the system sequencer to connect the emergency load
becomes. in proper sequence within a time period of
approximately 30 seconds.
9.5.4 Digital Voltage Regulation
In the event of the unit being started for
The only section of the excitation system surveillance testing, the output breaker is
that lends itself to digital control is the closed manually by the plant operators
voltage regulator. While there are some after bringing the unit into synchronizism
advantages to digitizing the voltage with the offsite power system. The
regulator for the purpose of better voltage operator must closely match the frequency
stability during isolated operation (powering of the generator to that of the off- site
the emergency bus), and of controlling power, with the generator slightly higher
reactive power (power factor) a little tighter than the offsite frequency so that the unit
when in parallel with the offsite power will assume some load when the output
system, the effect would be small in a breaker is closed. The voltage must also
comparison to the existing analog systems. be closely matched but slightly high so that
The voltage regulator operates basically the KVAR loading will be outbound rather
from analog inputs and in the case of the than inbound. A synchroscope is typically
Series Boost systems, the output is also used to bring the unit into synchronizism,
analog, there is little advantage to inserting and the system may also include sync-
digital components in between the input check relays to protect the generator output
breaker from being closed with the unit not phase of this system. There is a like device
synchronized properly. and circuit for each phase, A, B and C.
between the cheeks of the crankshaft at the have the crankshaft straight in the
throws to determine that the crankshaft is horizontal plane.
straight. This procedure for crank
alignment is commonly known as crank Once the generator bearing and the rotor
web deflection or crank alignment. are properly set up to relieve the crank
stress/strain, then the generator stator must
The crank pin journal can be considered to be positioned with respect to the rotor
be of fixed length. If the crankshaft is not position so as to equalize the air gap
straight through the throw, as the between the stator and the rotor. This is
crankshaft rotates, the crankshaft webs go usually done by shifting the generator on
through a bending to accommodate the jack screws and then installing shims under
bend in the crank. This causes the crank the generator feet before tightening the
cheeks to go from being more open to generator to the foundation or the skid.
being more closed, as shown in the lower
left portion of the diagram. The crankshaft The details of how to perform a crankshaft
is attempting to bend in that section shown alignment will be covered in the hands-on
with as 'AREA OF HIGHEST STRESS'. If the exercise.
crank continued to bend or deflect during
each rotation, it could induce high enough
stress to fail over time. It is necessary to
change this situation to minimize the
bending and flexing of the crankshaft
particularly through the last throw.
LOAD
Figure
e 9-4 Three-Phase Generation
Figure 9-1
12 Field Pole with Amortiser
Figure 9-19
9 Complete Stator Assembly
Figure 9-20 Rotor Installed within Stator (note fan assembly & sllip ring
Figure 9-22
2 Brush Rigging and Slip Rings
Figure 9-2
26 Engine-Generator Alignment