Gsov25 HT: Applications
Gsov25 HT: Applications
Gsov25 HT: Applications
GSOV25 HT
Fuel Isolation Valve
• Rated at <10 psi
Applications (69 kPa) pressure
drop at flow of
The Woodward 25 000 lb/h
GSOV25 HT fuel (11 340 kg/h)
isolation valve is
• Fuel temperature
designed to provide
range –4 to +350 °F
extremely fast
(–20 to +177 °C)
shutoff of gaseous
fuel flow to an • Closes in <0.100
industrial gas seconds at 900 psig
turbine engine. Gas (6200 kPa)
flow is stopped
when the valve is • Better than Class VI
closed, with zero shutoff
leakage from inlet • 100 to 900 psig
to outlet. The HT (690 to 6200 kPa)
version can operating pressure
withstand higher
fuel temperatures • 500 psig (3448 kPa)
and higher back reverse pressure
pressures than the capable
standard version. It
• Certified for North
is suitable for American Hazardous
operation with gas
Locations
temperatures between –4 and +350 °F (–20 and +177 °C). The valve can achieve
ANSI Class VI shut-off capability in the reverse flow direction with a pressure • Compliant with
differential of 500 psi (3448 kPa). applicable CE
Directives—ATEX,
The normally-closed valve may be used for emergency and normal shutdown
Pressure Equipment,
operation. The special seal design in the main piston valve allows long life and
Machinery, Low
prevents leakage. Stainless steel construction assures availability of the valve in
Voltage, and EMC
spite of corrosive service conditions.
• Certified for use in
This product is suitable for use on industrial turbines in the 10 to 50 MW power
explosive
output range with single or multiple combustion fuel manifold systems.
atmospheres within
the Russian
Description Federation
The GSOV25 HT fuel isolation valve provides shutdown on a gas turbine by rapidly • Designed for natural
halting the flow of gaseous fuel. The supply pressure is used to move a spring- gas, propane, ethane,
loaded piston in the valve. When the valve is energized, gas pressure drives the or methane
spring-loaded piston open, admitting fuel to the turbine. When the current signal to
• Operates from line
the electrical solenoid is interrupted, the spring loaded second-stage piston changes
pressure with no
states to vent off primary control pressure. The main spring then forces the primary
external connections
piston to the seal, stopping all flow.
required or with
external pilot pressure
Released
Woodward 03286 p.2
Specifications
Performance Closing Time Within 0.100 second at 900 psi (6200 kPa) supply pressure
Within 0.085 second at 600 psi (4137 kPa) supply pressure
Opening Time 0.300 second maximum at 100 psi (690 kPa) minimum supply pressure
Pressure Drop <10 psi (69 kPa) at 25 000 lb/hr (11 340 kg/hr) (see graph)
Main Seat Forward Leakage ANSI/FCI 70-2, Class VI
Main Seat Reverse Leakage ANSI/FCI 70-2 Class VI up to 500 psid (3448 kPa) reverse pressure differential
Maximum Effective Area 2.4 in² (15.5 cm²)
Cycle Life 20 000 cycles
Pilot Valve Vent Shall not exceed 400 SCCM
Operating Chemical Compatibility NACE Compliant for all typical gas fuels; call Woodward for special applications
Conditions/ Fuel Temperature –4 to +350 °F (–20 to +177 °C)
Environment Ambient Temperature –4 to +250 °F (–20 to +121 °C) [–4 to +221 °F (–20 to +105 °C) for dual coil version]
Fuel Types Natural gas, propane, ethane, methane
Fuel Supply Pressure Normal operation 100 to 900 psig (690 to 6205 kPa)
Proof Pressure 1350 psig (9308 kPa)
Burst Pressure 5000 psig (34 475 kPa)
Fuel Solid Particle Contaminant Less than 10 µm diameter, 30 ppm by volume maximum
Greater than 10 µm diameter, 0.3 ppm by volume maximum
Pilot Filtration 40 µm
External Pilot Pressure (optional) 200 to 900 psig (1380 to 6200 kPa) [valve operates from 100 to 200 psig, however,
opening slew time may exceed stated value]
Electrical Voltages Available Nominal 24 Vdc, 125 Vdc
Specifications Power Consumption 10 W nominal
Resistance to Ground 50 MΩ minimum at 500 Vdc
Wiring Interface Electrical 1/2-14 NPT for electrical conduit; interface 12-foot (3.7 m) leads on solenoid
and on proximity switch
Proximity Switch SPDT switch or switches, each with Normally Open and Closed contacts. Options include
a closed position switch (standard), Open position switch, or both.
Mechanical Installation Flange per ANSI B16.5; 600 lb (272 kg) rating dimension, 2 inch (51 mm) nominal
Specifications pipe size (6.500 dia. flange with eight 0.625-11 UNC taps through on 5.000 bolt circle on
inlet end; 6.500 diameter flange with eight 0.688 holes through on a 5.000 bolt circle on
outlet end)
Seal Overboard/Vent Connection 0.562-18 UNJF (-06) straight thread
Weight 75 pounds (34 kg)
Line Pressure Tap (removable plug) 0.438-20 UNJF (-04) straight thread
External Pilot Connection 0.438-20 UNJF (-04) straight thread
Construction Stainless steel housing; precipitation-hardened stainless steel internal components
Ingress Protection IP54 per EN60529
Regulatory Compliance
European Compliance for CE Marking:
ATEX Directive: Suitability is the result of the compliance of the individual components. Zone 1: Ex d IIB T3 or Zone 2: Ex nA
IIC T3.
EMC Directive: Declared to 2004/108/EC COUNCIL DIRECTIVE of 31 December 2004 on the approximation of the laws of
the Member States relating to electromagnetic compatibility.
Low Voltage Declared to 2006/95/EC COUNCIL DIRECTIVE of 12 December 2006 on the harmonization of the laws
Directive: of the Member States relating to electrical equipment designed for use within certain voltage limits.
Pressure Certified to Pressure Equipment Directive 97/23/EC of 29 May 1997 on the approximation of the laws of
Equipment Directive: the Member States concerning pressure equipment, Category # II.