SP3.6 Array Voltage Considerations
SP3.6 Array Voltage Considerations
9ROWDJH
formance, in some cases negatively. Low dc array voltage, for
example, is a common cause of substandard performance
that occurs when open-circuit or operating voltages for an
array persistently fail to meet minimum inverter dc input
voltage thresholds over time. In this situation, the system
design does not take into account the cumulative effects of
a variety of real-world circumstances, including high ac grid
voltage, array degradation, module-to-module voltage toler-
ance and high ambient temperatures. Fortunately, low dc
array voltage is avoidable.
In this article, I detail array design best practices for deter-
mining the maximum number of modules in a source circuit.
My approach is slightly less conservative than the industry
standard and is supported by changes to the National Electri-
cal Code that are introduced in the 2011 cycle. I also present
recommendations for determining the minimum number of
modules per source circuit. While these may be more conser-
vative than current design standards, my opinions are based
on years of experience. They are not influenced by the desire
to sell more or less of any specific product but rather by the
general desire to propagate well-designed PV systems that
perform optimally for decades.
68 S O L A R P R O | October/November 2010
\H&RQVLGHUDWLRQV By Bill Brooks, PE
5HGXFHXSIURQWV\VWHPFRVWDQGRSWLPL]H
ORQJWHUPSHUIRUPDQFHE\DYRLGLQJWKHSLWIDOOVRI
VWULQJVL]LQJRQDXWRSLORW
C o u r te sy S P G S o l ar an d X an te r ra Par k s & Re so r t s
solarprofessional.com | S O L A R PR O 69
Array Voltage Considerations
*\YYLU[(
a utility disturbance, it will not restart until the late after-
>T
noon when the Voc increases. This can reduce the system’s
operating availability by several percentage points annually
if utility disturbances are common in the summer, such as >T
when utilities switch in distribution capacitors around noon
on hot days to accommodate high air conditioning loads. To >T
design a PV array that is well-matched to an inverter’s oper-
ating window, system designers need to pay attention to the
low end of the inverter operating voltage range, as well as to
the maximum voltage allowed.
70 S O L A R P R O | October/November 2010
Array Voltage Considerations
/RZ'HVLJQ7HPSHUDWXUH
T o find the record low temperature for any location in the US,
go to Weather.com’s Monthly Climatology web page at the
following URL and specify the desired zip code:
weather.com/weather/climatology/monthly/zipcode.
For design purposes, however, a location’s record low
temperature is very conservative, generally lower than the
minimum expected ambient temperature at peak irradiance.
C o u r tes y S t eve P ro eh l
72 S O L A R P R O | October/November 2010
Array Voltage Considerations
/RZ$UUD\9ROWDJH
LOW DC VOLTAGE
Inverter specification sheets seem
simple enough to use, but some knowl-
=TW
age. For residential systems, the nomi-
(TWLYHNL
(: /
(:
U
KHYK
9(,
LZ[JV
SV^[LT
the ac voltage varies above nominal, the
[LT
UKP[PV
=VJ
UZ
74 S O L A R P R O | October/November 2010
5+H\FR[/D\RXW$03DJH
solarprofessional.com | S O L A R PR O 75
Array Voltage Considerations
arrays, especially those under 10 kW, can be heavily influenced considering array mounting (typically 20°C to 30°C), and
by a desire to fully exploit the available inverter capacity. This βVMP is the temperature coefficient of Vmp.
often leads to array voltage compromises that are unnecessary
in larger systems. The inverter in this case is large enough that VMIN = 29.5 V + ((34°C + 20°C − 25°C) x -0.133 V/°C)
its capacity does not drive array voltage design. The relevant = 29.5 V + (29°C x -0.133 V/°C)
design details for this case study are as follows. = 29.5 V − 3.9 V
= 25.6 V
Location: Raleigh, NC
Low design temperature: -13°C, per ASHRAE Extreme Annual Select and apply a multiplier to account for the com-
Mean Minimum Design Dry Bulb Temperature bined effects of high ac grid voltage, array degradation and
Record low temperature: -21°C, per Weather.com module voltage tolerance. 0.85 is used in this case:
High design temperature: 34°C, per ASHRAE 2% Annual Design
Dry Bulb Temperature VMIN = 25.6 V x 0.85
PV module: Yingli YL230P-29b, 230 W STC, 29.5 Vmp, 7.8 Imp, = 21.8 V
37.0 Voc, 8.4 Isc, -0.137 V/°C temperature coefficient of Voc
(-0.37%/°C x 37.0 Voc), -0.133 V/°C temperature coefficient of Divide the minimum MPPT voltage by the minimum
Vmp (based on the published temperature coefficient for Pmp, voltage per module and round up to the nearest whole num-
-0.45%/°C x 29.5 Vmp) ber to determine the minimum number of modules in series:
Inverter: Satcon PVS-50, 50 kW, 600 Vdc maximum input,
305–600 Vdc MPPT range NMIN = 305 V / 21.8 V = 13.99
= 14 module in series
Maximum modules in series. To determine the maximum
number of modules in series, first calculate the per-module Comparison of results. It is now possible to recalculate
maximum voltage as follows: the acceptable source-circuit configurations using standard
assumptions for a string-sizing program. There are two main
VMAX = VOC + ((TLOW − TREF) × αVOC) differences in the calculations.
First, use the record low temperature for the location in
where TLOW is the ASHRAE Extreme Annual Mean Mini- place of the ASHRAE Extreme Annual Mean Minimum Design
mum Design Dry Bulb Temperature; TREF is the cell tempera- Dry Bulb Temperature for the VMAX and NMAX calculations:
ture at STC; and αVOC is the temperature coefficient of Voc.
VMAX = 37.0 V + ((-21°C - 25°C) x -0.137 V/°C)
VMAX = 37.0 V + ((-13°C − 25°C) x -0.137 V/°C) = 37.0 V + (-46°C x -0.137 V/°C)
= 37.0 V + (-38°C x -0.137 V/°C) = 37.0 V + 6.3 V
= 37.0 V + 5.2 V = 43.3 V
= 42.2 V
NMAX = 600 Vdc / 43.3 V = 13.9
Divide the maximum inverter input voltage by the = 13 modules in series
temperature-corrected open-circuit voltage and round
down to the nearest whole number to determine the maxi- Second, do not apply a 0.85 multiplier as part of the VMIN
mum number of modules in series: calculations. This means that the minimum number of mod-
ules per source circuit is calculated using a Vmp of 25.6 Vdc:
NMAX = 600 Vdc / 42.2 V = 14.2
= 14 modules in series NMIN = 305 V / 25.6 V = 11.9
= 12 module in series
Minimum modules in series. To determine the minimum
number of modules in series, first calculate the per module The best array design for this case study calls for 14 mod-
minimum voltage as follows: ules per source circuit. However, the simplest string-sizing
program specifies 12 to 13 modules per source circuit. More
VMIN = (VMP + ((THI + TRISE − TREF) × βVMP)) sophisticated string-sizing programs apply a margin of
safety to the minimum expected dc voltage to account for
where THI is the ASHRAE 2% Annual Design Dry Bulb high ac grid voltage, array degradation and module-to-module
Temperature, TRISE is the rise in cell temperature expected voltage mismatch. Using PVSelect.com, for C O N T I N U E D O N P A G E 7 8
76 S O L A R P R O | October/November 2010
Array Voltage Considerations
example, to calculate the acceptable string sizes for this case conductors. Longer strings also increase the array voltage,
study disqualifies source circuits of 12 modules. However, if the which has voltage drop benefits when cables are sized. Get-
designer is not using ASHRAE low design temperature data, ting the array voltage up also provides insurance when it is
even PVSelect.com cannot identify the best design option. needed most against insidious low dc voltage problems that
Assuring the best design requires both accurate calculations result in poor system performance precisely when the solar
and proper data. resource is greatest. On 5 kW or 50 kW net-metered projects,
the difference in performance between having 14 modules
SIZING THINGS UP in series or 12 or 13 modules in series might not register with
I am not suggesting that inverter manufacturers do not pro- the customer. However, on 500 kW or 5 MW projects that are
vide a valuable service with their string-sizing tools. With- PPA financed, this will make a world of difference in both
out these resources, the number of array design mistakes the installed costs and the revenue generated over the life of
would undoubtedly be many times what it is today. Never- the systems.
theless, system designers routinely make mistakes, in spite
of the fact that they have ready access to many easy-to-use g C O N TAC T
string-sizing tools. The results of the low voltage mistakes Bill Brooks / Brooks Engineering / Vacaville, CA / [email protected] /
described here are not dangerous; they do not pose a hazard brooksolar.com
to persons or property; they do not violate Code. They simply Resources
miss the mark of reducing up-front system cost and optimiz- American Society of Heating, Refrigeration, and Air-Conditioning
ing long-term performance. Designers need to keep in mind Engineers / ashrae.org
that all “approved” string sizes are not created equal. Blue Oak PV Selection Tool / pvselect.com
From an installed cost point of view, it is always better to
Solar America Board for Codes and Standards (Solar ABCs) /
put the maximum number of modules in series. This deliv-
solarabcs.org/permitting
ers the greatest amount of power per pair of source-circuit
78 S O L A R P R O | October/November 2010