DC90D MK2 Genset Controller User Manual Ver1.1
DC90D MK2 Genset Controller User Manual Ver1.1
DC90D MK2 Genset Controller User Manual Ver1.1
GENSET CONTROLLER
USER MANUAL
DC90D MK2
DC92D MK2
DC9xD MK2 GENSET CONTROLLER USER MANUAL
Software Version
No. Version Date Note
1 V1.0 2020-09-30 Original release.
2 V1.1 2021-01-30 Name of unified input and output port.
1
DC9xD MK2 GENSET CONTROLLER USER MANUAL
Symbol Description
Symbol Description
2
DC9xD MK2 GENSET CONTROLLER USER MANUAL
Warning
1. The installation of this equipment must be carried out by professionals.
2. When installing and operating the controller, please read the entire instruction
manual first.
3. Any maintenance and commissioning of the equipment must be familiar with all the
equipment.
4. t, safety standards and precautions in advance, otherwise it may cause personal
injury or damage to related equipment.
5. The engine must have an overspeed protection device independent of the
controller system to avoid casualties or other damage caused by engine out of
control.
6. After the installation of the controller is completed, please verify that all protection
functions are valid.
Be Care
1. Please keep the good connection of the power supply of the controller. Do not
share the connection lines of the positive and negative electrodes of the battery
with the floating charger.
2. During the operation of the engine, do not disconnect the battery, otherwise it may
cause damage to the controller.
3
DC9xD MK2 GENSET CONTROLLER USER MANUAL
Catalogue
1、 Summary............................................................................................................................ 5
2、 Main Features....................................................................................................................5
3、 Parameters Display.......................................................................................................... 6
4、 Parameters.........................................................................................................................8
6、 Installation instruction.....................................................................................................16
Notes:
1. All rights reserved. No part of this duplication may be reproduced in any material
form (including photocopying or storing in any medium by electronic means or others)
without the written permission of the copyright holder.
2. MEBAY Technology reserves the rights to change the contents of this document
without prior notice.
4
DC9xD MK2 GENSET CONTROLLER USER MANUAL
1、 Summary
This series controller is specialized for Diesel / Gasoline / Gas Genset Start,
Stop, Parameters monitoring, faults-checking as well as data setting.
4.3inch colorful LCD screen display with brand new UI design is adapted in this
controller that the relative failures can be displayed directly. All the parameters can
be displayed by simulated indicators and words. Besides, LCD screen can display
various faults in the same time that the genset will be stopped once it can’t work
smoothly.
There are Chinese/English interface options, more language can be set
according to user’s request. All the parameters can be configured through the front
face buttons or use programmable interface by RS485 or USB to adjust via PC. It can
be widely applied for all kinds of auto control system of gensets.
2、 Main Features
There are four Models under DC9xD MK2 series.
DC90D MK2: used for single machine automation. Start/Stop through remote
start signal.
DC92D MK2: Based on DC90D MK2, it adds Mains monitoring and AMF
(Mains/Generator automatic switching control), especially suitable for the automation
system composed by mains and genset.
DC90DR MK2: Based on DC90D MK2, it adds RS485 port.
DC92DR MK2: Based on DC92D MK2, it adds RS485 port.
Dual core 32bit high performance single chip microcomputer.
4.3inch TFT colorful big screen LCD, Available in 5 languages, user’s language set
if necessary.
Indicator and number display through UI surface.
Acrylic material is adapted to protect the screen.
Silicone panels;
USB Port: parameters can be set even without power through USD port to monitor
in real time.
With RS485 communication port, can achieve “Three Remote” functions via
MODBUS protocol.
Standard CAN communication port, built-in J1939 protocol, has matched more
than 30 kinds of engines;
Various kinds of parameters display.
Input/output function, status can be shown directly.
More categories of surface setting.
Real time clock inside: preset time operate and auto maintenance is available.
Genset working plan can be set as per week or month.
Three class protection countdown function, which can set the maintenance time or
date.
The black box function can save the relevant parameters of the unit when the fault
alarm occurs in real time, and it is convenient to find the cause of the fault.
5
DC9xD MK2 GENSET CONTROLLER USER MANUAL
3、 Parameters Display
Engine RPM
Engine oil pressure
Engine water temperature
Engine fuel temperature
Engine cylinder temperature
Engine Tank temperature
Engine fuel level
Engine battery voltage
Charging voltage
Mains Frequency (only for DC92D MK2)
Mains phase voltage L-N (only for DC92D MK2)
Mains phase voltage L-L (only for DC92D MK2)
Generator 3 Phase voltage L-N
Generator 3 Phase voltage L-L
Generator 3 phase current A
Generator Frequency Hz
Generator Power Factor COS φ
Generator active power KW
Generator apparent power KVA
Generator reactive power KVar
Real-time load rate %
Current load rate %
Average loading rate %
Current consumption KWH
Total consumption KWH
Total Crank times
6
DC9xD MK2 GENSET CONTROLLER USER MANUAL
Protection
Over speed
Under speed
Low oil pressure
High water temperature
High Oil temperature
High Cylinder Temperature
High Tank temperature
Low fuel level
Low oil level
External instant unloading shutdown
External emergency alarm
RPM Lost
Sensor Open
Over Frequency
Under Frequency
Over voltage
Under voltage
Over current
Non-balance of current
Over power
Gen load failure
Gen unload failure
Mains Load failure
Mains unload failure
Primary maintenance expire
Secondary maintenance expire
Third maintenance expire
ECU alarm failure
ECU communication Failure
Low water level alarm
Louver opening exception
Emergency Stop
Crank failure
Stop Failure
7
DC9xD MK2 GENSET CONTROLLER USER MANUAL
4、 Parameters
Options Parameters
Working voltage DC9V----36V Continuous
Standby:24V:MAX 1W
Power consumption
Working:24V:MAX 7W
1P2W 30VAC-276VAC (ph-N)
AC Voltage Input 2P3W 30VAC-276VAC (ph-N)
3P4W 30VAC-276VAC (ph-N)
Rotate speed sensor
200-10000Hz
Frequency
MAX Accumulating Time 99999.9Hours(Min Store time:6min)
Fuel Relay Output Max 16Amp DC+VE Supply voltage
Start Relay Output Max 16Amp DC+VE Supply voltage
AUX. Output 1 Max 16Amp DC+VE Supply voltage
AUX. Output 2 Max 16Amp DC+VE Supply voltage
AUX. Output 3 Max 5Amp DC+VE Supply voltage
AUX. Output 4 Max 5Amp DC+VE Supply voltage
AUX. Output 5 Max 5Amp DC+VE Supply voltage
AUX. Output 6 Max 5Amp DC+VE Supply voltage
AUX. Output 7 Max 5Amp DC+VE Supply voltage
AUX. Output 8 Max 5Amp DC+VE Supply voltage
Excitation output Max 0.9AMP DC+VE supply voltage
Switch value input Available if connecting with Battery -
Working condition -25-65℃
Storage condition -40-85℃
IP54:when waterproof rubber gasket is added
Protection Level
between controller and its panel
Apply AC1.5kV voltage between high voltage terminal
Insulation strength and low voltage terminal; The leakage current is not
more than 3mA within 1min.
Overall dimension 241mm*177mm*45mm
Panel cutout 220mm*160mm
Weight 1Kg
8
DC9xD MK2 GENSET CONTROLLER USER MANUAL
241
177
241
45
177
45
9
DC9xD MK2 GENSET CONTROLLER USER MANUAL
Cable
cross
No. Function Description
sectional
area
1 Battery Negative Input B- Controller power supply input B-. 2.5mm2
2 Battery Negative Input B+ Controller power supply input B+. 2.5mm2
B+ voltage input is active, and connected to
3 Emergency Stop Input 2.5mm2
emergency stop normal closed button.
4 Fuel Output Active output, Max 16Amp 1.5mm2
5 Crank Output Active output, Max 16Amp. 1.5mm2
6 Charging excitation output Active output, Max 0.9Amp. 1.0mm2
7 Common GND Connect the battery negative or outer casing. 1.5mm2
8 Aux. Ouput 3 Active output, Max 5Amp. 1.5mm2
9 Aux. Ouput 4 Active output, Max 5Amp. 1.5mm2
10 Aux. Ouput 5 Active output, Max 5Amp. 1.5mm2
11 Aux. Ouput 6 Active output, Max 5Amp. 1.5mm2
12 Aux. Ouput 7 Active output, Max 5Amp. 1.5mm2
13 Aux. Ouput 8 Active output, Max 5Amp. 1.5mm2
14 Sensor common GND Connect the battery negative or outer. 1.5mm2
15 Aux. Sensor 1_OP 1.0mm2
16 Aux. Sensor 2_WT Sensor input types can be configured as: 1.0mm2
17 Aux. Sensor 3_FL disabled, oil pressure sensor, water 1.0mm2
18 Aux. Sensor 4 temperature sensor, oil temperature sensor, 1.0mm2
19 Aux. Sensor 5 cylinder temperature sensor, oil level sensor. 1.0mm2
20 Aux. Sensor 6 1.0mm2
10
DC9xD MK2 GENSET CONTROLLER USER MANUAL
11
DC9xD MK2 GENSET CONTROLLER USER MANUAL
TO LOAD SWITCHING
FROM GENERATOR
U P1 P2
S1 S2
V P1 P2
DEVICE
S1 S2
W P1 P2
S1 S2
N2
FUSE 2A
H L SCR B A SCR +5V
OUTPUT
42 43 44 45 46 47 34 35 36 37 33 32 31 30 38 39 40 41 24 25 26 27 28 29 56
IA IB IC ICOM U V W N2 R S T N1
GEN CURRENT GEN VOLTS AUX. OUTPUT 2 AUX. OUTPUT 1 MAIN VOLTS CAN RS485
(AC0-5A) (AC0-300V) MAX 16A MAX 16A (AC0-300V)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 48 49 50 51 52 53 54 55 21 22 23
FUSE 10A
FUSE 20A
SCR
HIGH COOLANT TEMP ALARM
+ -
AUX. S2 COOLANT TEMP
OUTPUT 3
OUTPUT 4
OUTPUT 5
OUTPUT 6
OUTPUT 7
OUTPUT 8
FUEL
REMOTE START
4
5
6
7
8
STOP
INPUT
INPUT
INPUT
INPUT
INPUT
+
BATTERY
AUX. S4
AUX. S5
AUX. S6
ALT D+
AUX.
AUX.
AUX.
AUX.
AUX.
AUX.
GND
GND
AUX.
AUX.
AUX.
AUX.
AUX.
Note: Please don’t move battery during running status or it may cause the
controller broken!
12
DC9xD MK2 GENSET CONTROLLER USER MANUAL
MECHANICAL INTERLOCK
TO LOAD SWITCHING
DEVICE
L1 L2 L3 N
CTs MUST BE 5 AMP SECONDARY
FROM GENERATOR
U P1 P2 R
S1 S2
FROM MAINS
V P1 P2 S
S1 S2
W P1 P2 T
S1 S2
N2 N1
ELECTRICAL
INTERLOCK
G M
FUSE 2A FUSE 2A
H L SCR B A SCR +5V
OUTPUT
42 43 44 45 46 47 34 35 36 37 33 32 31 30 38 39 40 41 24 25 26 27 28 29 56
IA IB IC ICOM U V W N2 R S T N1
GEN CURRENT GEN VOLTS AUX. OUTPUT 2 AUX. OUTPUT 1 MAIN VOLTS CAN RS485
(AC0-5A) (AC0-300V) MAX 16A MAX 16A (AC0-300V)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 48 49 50 51 52 53 54 55 21 22 23
FUSE 10A
FUSE 20A
SCR
HIGH COOLANT TEMP ALARM
AUX. S2 COOLANT TEMP
+ -
LOW OIL PRESSURE ALARM
AUX. S1 OIL PRESSURE
CRANK
EMERGENCY
OUTPUT 3
OUTPUT 4
OUTPUT 5
OUTPUT 6
OUTPUT 7
OUTPUT 8
FUEL
REMOTE START
4
5
6
7
8
STOP
INPUT
INPUT
INPUT
INPUT
INPUT
+
BATTERY
AUX. S4
AUX. S5
AUX. S6
ALT D+
AUX.
AUX.
AUX.
AUX.
AUX.
AUX.
GND
GND
AUX.
AUX.
AUX.
AUX.
AUX.
Note: Please don’t move during running status or it may cause the
controller broken!
13
DC9xD MK2 GENSET CONTROLLER USER MANUAL
TO LOAD SWITCHING
FROM GENERATOR
U P1 P2
S1 S2
DEVICE
N2
FUSE 2A
H L SCR B A SCR +5V
OUTPUT
42 43 44 45 46 47 34 35 36 37 33 32 31 30 38 39 40 41 24 25 26 27 28 29 56
IA IB IC ICOM U V W N2 R S T N1
GEN CURRENT GEN VOLTS AUX. OUTPUT 2 AUX. OUTPUT 1 MAIN VOLTS CAN RS485
(AC0-5A) (AC0-300V) MAX 16A MAX 16A (AC0-300V)
TO LOAD SWITCHING
FROM GENERATOR
U P1 P2
S1 S2
V P1 P2 DEVICE
S1 S2
N2
FUSE 2A
H L SCR B A SCR +5V
OUTPUT
42 43 44 45 46 47 34 35 36 37 33 32 31 30 38 39 40 41 24 25 26 27 28 29 56
IA IB IC ICOM U V W N2 R S T N1
GEN CURRENT GEN VOLTS AUX. OUTPUT 2 AUX. OUTPUT 1 MAIN VOLTS CAN RS485
(AC0-5A) (AC0-300V) MAX 16A MAX 16A (AC0-300V)
14
DC9xD MK2 GENSET CONTROLLER USER MANUAL
TO LOAD SWITCHING
DEVICE
L1 L2 N
CTs MUST BE 5 AMP SECONDARY
FROM GENERATOR
U P1 P2 R
S1 S2
FROM MAINS
V P1 P2 S
S1 S2
N2 N1
ELECTRICAL
INTERLOCK
G M
FUSE 2A FUSE 2A
H L SCR B A SCR +5V
OUTPUT
42 43 44 45 46 47 34 35 36 37 33 32 31 30 38 39 40 41 24 25 26 27 28 29 56
IA IB IC ICOM U V W N2 R S T N1
GEN CURRENT GEN VOLTS AUX. OUTPUT 2 AUX. OUTPUT 1 MAIN VOLTS CAN RS485
(AC0-5A) (AC0-300V) MAX 16A MAX 16A (AC0-300V)
MECHANICAL INTERLOCK
TO LOAD SWITCHING
DEVICE
L1 N
CTs MUST BE 5 AMP SECONDARY
FROM GENERATOR
U P1 P2 R
S1 S2
FROM MAINS
N2 N1
ELECTRICAL
INTERLOCK
G M
FUSE 2A FUSE 2A
H L SCR B A SCR +5V
OUTPUT
42 43 44 45 46 47 34 35 36 37 33 32 31 30 38 39 40 41 24 25 26 27 28 29 56
IA IB IC ICOM U V W N2 R S T N1
GEN CURRENT GEN VOLTS AUX. OUTPUT 2 AUX. OUTPUT 1 MAIN VOLTS CAN RS485
(AC0-5A) (AC0-300V) MAX 16A MAX 16A (AC0-300V)
15
DC9xD MK2 GENSET CONTROLLER USER MANUAL
6、 Installation instruction
The controller is fixed by four special fixing members and screws, and the screws
of the metal fasteners cannot be too tight.
Panel Cutout: W220mm*H160mm.
220
160
Note: If the controller is installed directly in the genset shell or other fluctuated
equipment, the rubber pad must be installed.
Battery Voltage Input
DC9xD MK2 controller is suitable for 8-36V DC battery voltage. Battery negative
must be reliably connected to the enclosure of the engine. The controller power
supply B+ and B- must be connected to battery positive and negative, and the wire
size must not be less than 2.5mm2.
NOTE:
In case of floating charger connect charger output to battery positive and negative
directly, then, connect battery positive and negative poles to controller positive and
negative power supply.
Output and relay expansion
Note: All outputs of the controller are relay contacts. The maximum current
capacity is described in the "Parameters" in this manual. Please use it in the relay
current capacity. If an extended relay is needed, add a continuous current diode
(when the extended relay coil is DC) or a resistance-capacitance loop (when the
extended relay coil is AC) to both ends of the coil to prevent interference with the
controller or other equipment.
AC current input
Current transformer with rated secondary current 5A must be externally connected
to the controller current input.
If withstanding voltage test is conducted after the controller has already been
installed onto the control panel, please unplug all controller terminal connections in
order to prevent high voltage from damaging it.
7、 Panel and display
DC90D MK2
LCD Left Up
OK/UI Change
Alarm Right
Warning Down
Running Manual
On load Manual Start
Gens status Stop
Load transfer Auto
On MAN mode
LCD Left Up
OK/UI Change
Alarm Right
Warning Down
Running
Manual
Gens on load Manual Start
Gens status Stop
Close/On Auto
Mains Status
17
DC9xD MK2 GENSET CONTROLLER USER MANUAL
Manual Pressing this key will set the module into manual mode.
Auto Pressing this key will set the module into auto mode.
DC90D MK2 Pressing this key to check the alarm records under stop
Records mode.
Pressing this key to come into manual testing mode.
DC92D MK2 Under testing mode, pressing MANUAL can start the
Test genset and transfer to normal loading after running which
is to test if the auto start is in normal status.
Test if all LED lights are ok, pressing this key to test if all
lighted, all off when loosen it.
Under warning, pressing this key can clear warning and
LED Test/
controller will re-check warning.
Warning clear
Under alarm, pressing this key can clear the buzzer call.
Pressing this key in 3 seconds can clear the buzzer call,
pressing it again in 3 seconds can recover the buzzer call.
Gens/ Mains Under manual mode, pressing this key can transfer load
Close/On to genset/mains.
2) When the generator frequency and engine speed are not zero, press
and for more than 0.5 seconds, the controller will automatically calculate
and save the number of flywheel teeth according to the generation frequency and
generator poles.
3) After calculating and saving the number of flywheel teeth successfully, the
controller shows: " Flywheel xxx teeth, saved successfully!"
choose the record you need. Press to confirm the record and come into
history records checking page.
3) Press to turn lower records under records checking page. Press to
turn upper records and press to revert back to alarm history records page.
4) Exit from records page: In the history records page and checking page, press
to exit.
19
DC9xD MK2 GENSET CONTROLLER USER MANUAL
Press “ ” and the test file indicator is on. At this time, it is detected whether the
connection of each sensor is normal. If the sensor is open, the sensor opens an
alarm. If it is normal, the unit start process is executed in the following sequence after
pressing the " ". automatically switch to Generator provide the power when the
unit is running normally. Press “ ” The controller performs the parking process at
the following timing:
Longest
Longest Longest
voltage
speed temperature
built/ rated
increasing increasing warming Cooling
increasing up time runn-
time time running time
time ing
Start Stop
Rated speed idle
Safe idle
Crank time time time
test
time ETS
Long- solen-
est oid
Idle hold
Pre- pre-oil Start
heat supply Crank
Wait
delay delay delay Stop
Start Stop
Rated speed idle
Safe idle
Crank time time time
test
time ETS
Long- solen-
est oid
Idle hold
Pre- pre-oil Start
heat supply Crank
Wait
delay delay delay Stop
20
DC9xD MK2 GENSET CONTROLLER USER MANUAL
After the manual start is successful, pressing the "automatic key" can be
converted into an automatic file. The specific working time is as follows:
Longest
Longest Longest
voltage
speed temperature
built/
rated Transfer
increasing increasing warming Cooling
increasing up time runn- back to
time time running time
time ing mains delay
Start Stop
Rated speed idle
Safe idle
Crank time time time
test
time ETS
Long- solen-
est oid
Idle hold
Pre- pre-oil Start
heat supply Crank
Wait
delay delay delay Stop
Start Stop
Rated speed idle
Safe idle
Crank time time time
test
time ETS
Long- solen-
Crank oid
Idle est
Auto Pre- pre-oil Start test Crank hold
Start heat supply Crank time rest Wait
delay delay delay delay time Stop
Note 1: During the Cranking time, the controller automatically detects the speed
signal, frequency signal and oil pressure value or the charging voltage (according to
the parameter setting) to reach the judgment condition of successful start, then the
judgment is that the start is successful and the motor relay is closed.
Note 2: Within the safety delay, only respond to emergency stop, immediate
21
DC9xD MK2 GENSET CONTROLLER USER MANUAL
stop, over speed, over frequency, Over voltage, ECU communication Failure,shutter
open abnormal, other alarms are not responded to.
Note 8: After entering rated operation, the Gens load relay output.
Note 10: If the stop key is pressed again during idle time, the idle time will be
canceled and the stop operation will be executed directly.
Notes: Warning is a non-serious failure state, which will not harm the gensets
system for the time being. It only reminds operators to pay attention to the situation
that does not meet the requirements and solve it in time to ensure the continuous
operation of the system. When the warning occurs, the gensets does not stop. Once
the fault is removed, the warning is automatically canceled.
warning”, Then start warning delay and the duration (Normal warning delay) have
not returned to normal, the warning of under speed is reported. "WARNING" lights
will light up, Generators will not stop, displays " Under speed " on the current fault
screen.
screen.
24
DC9xD MK2 GENSET CONTROLLER USER MANUAL
25
DC9xD MK2 GENSET CONTROLLER USER MANUAL
When the controller detects that the generator power is higher than “Over total
power warning”, Then start warning delay and the duration (Normal warning delay)
have not returned to normal, the warning of over power is reported. "WARNING"
lights will light up, Generators will not stop, displays " Over power " on the current
fault screen.
28
DC9xD MK2 GENSET CONTROLLER USER MANUAL
When the gap between D+ and B+ is over than this value, and there is charging
failure but still high(normal warning delay), then charge failure warns. "WARNING"
lights will light up, Generators will not stop, displays "Charger fault" on the current
fault screen.Once the gap is lower than the value, warns clear.
Starting fault
Fail to Start
If the number of cranks exceeds the predetermined number of cranks, the failure of
start-up will be reported if the start-up of the generating unit is still unsuccessful.
"ALARM" lights on, without stopping the engine, and displays " Crank failure " on
the current fault screen.
Shutdown Alarms
Warning: After the Shutdown Alarm occurs, the system will be locked
immediately and the generator set will be stopped. Only after troubleshooting, press
key to clear the alarm, can it be re-operated.
Notes:When the shutdown alarm failure occurs, the "ALARM" lights will light
up and the generator unit automatically stops.
Over Speed Alarm
When the controller detects that the engine speed is higher than “Over speed alarm”,
Then start alarm delay and the duration (Emergency delay) have not lower than”Over
speed revert”, the alarm of over speed is reported. "ALARM" lights will light up,
Generator stops running, and displays " Over speed " on the current fault screen.
switch" is valid. Then the alarm, the public alarm light "ALARM" lights will light up,
stop the unit operation, and display "High CT switch" on the current fault screen.
31
DC9xD MK2 GENSET CONTROLLER USER MANUAL
delay is delayed for a period of time “Normal alarm delay” AUX. Input port
“External instant alarm input” switch When it is valid, it will alarm, the public alarm
light "ALARM" lights will light up,Generator stops running, and display "Instant
parking" on the current fault screen.
33
DC9xD MK2 GENSET CONTROLLER USER MANUAL
higher than the "Non-balance current ratio alarm".Then start alarm delay and the
duration (Normal alarm delay) have not returned to normal, the alarm of Non-balance
current ratio is reported. "ALARM" lights will light up, Generator stops running,
displays " Unbalance of AMP " on the current fault screen.
the digit into right, press to turn the digit into left, press once done. Then
system comes into menu after confirmation of password setting. The screen will
display error if password is wrong. The correct password should be put after
pressing any button.
3) Press to turn the digit into upper position, press to turn the digit into
lower position, press to get into parameters setting page.
4) Press to shift up the parameters, press to shift down the parameters,
press to get into parameter changing page.
digit into right and press to turn the digit into left, press once done. If the
36
DC9xD MK2 GENSET CONTROLLER USER MANUAL
parameters setting is in the valid setting range, then it can be saved, if not, it can’t
be saved.
6) Press and to save the parameters and exit from edition page.
7) Press to revert back to last class if in any setting position.
Revert back to default: put password “97011” when coming into parameters
setting, then all the parameters can be set as defaults.
Note: the data can’t be saved if the user didn’t press OK and STOP to confirm
the setting.
Parameter list.
1)Basic setting
No Parameter Range (default) Notes
0-English
1-简体中文
1 Language 2-繁体中文 Language option.
3-español
4-русский
When the flywheel teeth are set as 0, the
RPM will be resulted by frequency.
Pole 2: 50Hz---3000RPM.
2 Gens poles 2/4/6/8(4)
Pole 4: 50Hz---1500RPM.
Pole 6: 50Hz---1000RPM.
Pole 8: 50Hz---750RPM
Disable
Gens phases:
1 phase 2 wire
No gens parameters can be displayed if
3 Gens AC system 2 phase 3 wire
setting as disable, which is applied to water
3 phase 3 wire
pump genset.
3 phase 4 wire
5-6000A/5A Used for setting genset CT primary current,
4 CT rate
(500A/5A) secondary rated current 5A.
Setting generator rated frequency to choose
40.0-80.0Hz
5 Rated frequency the meter range and calculate the alarm
(50.0Hz)
value.
Rated phase Setting generator phase voltage to choose the
6 80-360V(230V)
voltage meter range and calculate the alarm value.
Rated phase Setting generator phase current to choose the
7 5-6000A(500A)
current meter range and calculate the alarm value.
5-2000Kw Set total power of generator to choose the
8 Rated total power meter range and calculate the average
(276Kw)
loading rate and alarm value.
Rated battery Choose the meter range and calculate the
9 8.0-36.0V (24.0V)
voltage alarm value.
500-4500RPM Choose the meter range and calculate the
10 Rated RPM
(1500) alarm value.
If the setting is 0, (RPM sensor Disabled),
11 Flywheel teeth 0-300(0)
then RPM is resulted by Hz.
Warning If the system is set as trip stop, then the
Action if over
12 Alarm and stop unloading procession shall be acted and then
current
Trip stop stop with alarm.
37
DC9xD MK2 GENSET CONTROLLER USER MANUAL
38
DC9xD MK2 GENSET CONTROLLER USER MANUAL
delay
AC Voltage
22 abnormal 2.0-20.0s (10.0s) Over / under voltage delay.
delay
Over phase When this parameter is set to 0, the over current
23 current 0-3600.0s(30s) delay is the inverse time; if not, the over current
delay delay is the time set for this parameter.
When this parameter is set to 0, the over power
Over total power
24 0-3600.0s(30s) delay is the inverse time; if not, the over current
delay
delay is the time set for this parameter.
This option will not take effect until the [23-Over
Over current phase current delay] is set to 0. The over
25 0.1-36.0(36.0)
【inverse time】 current delay is inverse time, and the formula is
T=t/((IA/IT) -1)^2.
This option will not take effect until the [24-Over
Over power total power delay] is set to 0. The over power
26 0.1-36.0(36.0)
【inverse time】 delay is inverse time, and the formula is
T=t/((IA/IT) -1)^2.
Transfer switch
27 0-3600.0s (5.0s) The time from Mains to Gens.
delay
Mains and Gens loading and unloading pulse
Load / unload
28 1.0-10.0s (10.0s) width, when it is 10s, it is regarded as continuous
pulse width
output.
29 Choke close delay 0-200.0s (3.0s) Choke close delay.
Pulse speed up The interval time of the pulse speed up relay
30 0.1-60.0s(0.1s)
delay change.
Pulse speed down The interval time of the pulse speed down relay
31 0.1-60.0s(0.1s)
delay change.
33 Fuel output delay 1.0-60.0s(2.0s) The output time of fuel valve relay before crank.
4)Engine Alarm setting
Range
No Parameter Notes
(defaults)
Rated RPM multiplying by this value is regarded as over
speed warning value. When the RPM is higher than the
Over speed 0-200%
1 warning value and comes into over speed delay but still
warning (107%)
higher, then over speed warns. if the value is set as 200,
then the over speed alarm is disabled.
Rated RPM multiplying by this value is regarded as over
speed alarm value. When the RPM is higher than the
Over speed 0-200% alarm value and comes into over speed delay but still
2
alarm (114%) higher(emergency faults delay), then over speed
alarms. if the value is set as 200, then the over speed
alarm is disabled.
Over speed 0-200% Rated RPM multiplying by this value is regarded as over
3
revert (108%) speed alarm revert value.
Rated RPM multiplying by this value is regarded as
under speed warning value. When the RPM is lower
Under speed 0-200%
4 than the warning value and comes into under speed
warning (90%)
delay but still lower (normal warning delay), then under
speed warns. if the value is set as 0, then the over
43
DC9xD MK2 GENSET CONTROLLER USER MANUAL
44
DC9xD MK2 GENSET CONTROLLER USER MANUAL
is disabled.
When the temperature is higher than the value and
comes into high temperature warning delay but still
High genset box
20-200℃ higher (normal warning delay), then high temperature
15 temperature
(65 ℃ ) warns. If it is lower than the value then warning clears. If
warning
the value is set as 200, then the high temperature
warning is disabled.
When the temperature is higher than the alarm value
High genset box 20-200℃ and comes into high temperature delay but still higher
16 temperature (normal faults delay), then high temperature alarms. if
(85℃)
alarm the value is set as 200, then the high temperature alarm
is disabled.
When the fuel level is lower than the value and comes
into low fuel level warning delay but still lower (normal
Low fuel level 0-100%
17 warning delay), then low fuel level warns. If it is higher
warning (20%)
than the value then warning clears. If the value is set as
0, then the low fuel level warning is disabled.
When the fuel level is lower than the alarm value and
Low fuel level 0-100% comes into low fuel level delay but still lower (normal
18
alarm (0%) faults delay), then low fuel level alarms. if the value is
set as 0, then the under speed alarm is disabled.
Rated battery voltage multiplying by this value is
regarded as over battery voltage warning value. When
the battery input is higher than the warning value and
Over battery 0-200%
19 comes into over battery voltage delay but still higher
voltage warning (135%)
(normal faults delay), then over battery voltage warns. if
the value is set as 200, then the over battery voltage is
disabled.
Rated battery voltage multiplying by this value is
regarded as under battery voltage warn value. When the
battery input is lower than the warning value and comes
Under battery 0-200%
20 into under battery voltage delay but still lower (normal
voltage warning (67%)
faults delay), then under battery voltage warns. if the
value is set as 0, then the under battery voltage is
disabled.
When the gap between D+ and B+ is over than this
value, and there is charging failure but still high (normal
1.0-30.0V
21 Charger warning warning delay), then charge failure warns. Once the gap
(30.0V)
is lower than the value, warns clear. If the value is set as
300, then the charge failure is disabled.
5)Generator alarm parameters
No Parameter Range(defaults) Notes
Rated frequency multiplying by this value is
regarded as under over frequency warn value.
When the Freq is higher than the value and comes
1 Over freq warning 0-200% (110%) into over freq warning delay but still higher (normal
warn delay), then over frequency warns. If it is
lower than the value then warning clears. If the
value is set as 200, then the warning is disabled.
2 Over freq alarm 0-200% (114%) Rated frequency multiplying by this value is
45
DC9xD MK2 GENSET CONTROLLER USER MANUAL
temperature 2. VDO 40-120℃ the sensor used by the user is not the
sensor 3. MEBAY-001B commonly used type, it can be User-defined.
4. SGH
5. SGD
6. SGX
7. CURTIS
8. DATCON
9. VOLVO-EC
10. 3015238
11.PT100
12. MEBAY-Mier
13. WEICHAI 40-120℃
14. GENCON 40-120℃
33 Oil 1. User-defined Choose the usual oil temperature sensor, If
temperature 2. VDO 40-120℃ the sensor used by the user is not the
sensor 3. MEBAY-001B commonly used type, it can be User-defined.
4. SGH
5. SGD
6. SGX
7. CURTIS
8. DATCON
9. VOLVO-EC
10. 3015238
11.PT100
12. MEBAY-Mier
13. WEICHAI 40-120℃
14. GENCON 40-120℃
34 Cylinder 1. User-defined If the sensor used by the user is not the
temperature 2. MEBAY-Mier commonly used type, it can be User-defined.
sensor 3. PT100
4-15: Reserved
35 Genset box 1. User-defined If the sensor used by the user is not the
temperature 2. MEBAY-Mier commonly used type, it can be User-defined.
sensor 3. PT100
4-15: Reserved
36 Fuel level 1. User-defined If the sensor used by the user is not the
sensor 2. 0-100Ω commonly used type, it can be User-defined.
3. 100-0Ω
4. 0-107Ω
5. 107-0Ω
6. 0-180Ω
7. 180-0Ω
8. 180-10Ω
9. 10-180Ω
10. 120-10Ω
11.10-120Ω
12. 90-0Ω
13. 0-90Ω
14. 0-30Ω
15. 73-10Ω
55
DC9xD MK2 GENSET CONTROLLER USER MANUAL
16. 240-33Ω
17. 33-100Ω
18. 0-200Ω
19. 200-0Ω
7) Working plan and maintenance setting
No Parameter Range(defaults) Notes
This mode must be under auto mode.
Working plan is disabled once setting as
disable.
Disable The working plan will be executed
1 Working plan format Every month according the chosen date when setting as
Every week every month.
The working plan will be executed
according the chosen date when setting as
every week.
From 1st to 31st
Maintenance date per
2 Default: the first The date chosen for every month.
month
day
Maintenance date per Monday to Sunday
3 The date chosen for every week.
week Default: Sunday
Maintenance with load To choose if the genset starts with load or
4 Disabled/with load
or not not.
5 Maintenance start time 00:00-23:59(00:00) Maintenance start time setting.
Maintenance running
6 1-120m(5m) Maintenance running time setting.
time
8)Mains protection
No Parameter Range(defaults) Notes
Disable
1 Phase 2 Wire
Choose the input, there is no display if
1 Phase 2 Phase 3 Wire
setting as disable.
3 Phase 3 Wire
3 Phase 4 Wire
2 Mains under volt 55-330V(184V) When the mains voltage is lower than the
"low voltage crank threshold" and comes
into mains low voltage delay (normal failure
delay) but still lower, then mains becomes
3 Revert under volt 55-330V(207V)
invalid. If the voltage become higher than
"low voltage revert threshold" during normal
failure delay time, then it will not alarm.
4 Mains over volt 55-330V(276V) When the mains voltage is higher than the"
high voltage crank threshold" and comes
into mains high voltage delay (normal
failure delay) but still higher, then mains
5 Revert over volt 55-330V(253V) becomes invalid. If the voltage become
lower than "low voltage revert threshold"
during normal failure delay time, then it will
not alarm.
6 Mains normal delay 0.0-3600.0S(10.0s) The time from abnormal to normal, which is
7 Mains abnormal delay 0.0-3600.0S(5.0s) used for ATS transfer.
9)LCD setting
56
DC9xD MK2 GENSET CONTROLLER USER MANUAL
23: GTSC1
24: MTSC1
25: YUCHAI-YCECU
26: Y&C ENGINE-YC6K
27: WEICHAI-WISE15
28: CHANGCHAI-ECU15
29: YUCHAI-LMB
30: MAN
31: J1939-C
32: SDEC-H/D
33: SDEC-E
34:YTO
35:DEUTZ EMR2-2001
36:DEUTZ EMR2-2012
37:DEUTZ EMR3
38:DEUTZ EMR4
39:NEVED-ECU13
40:Cummins-CM2150
3 ECU warning Disable/Enable ECU warnings enable.
4 ECU alarm Disable/Enable ECU alarms enable.
5 Mask SPN 00000000 Up to 12 sets of alarm codes can be input,
and the controller will not respond to the
input alarm codes.
6 Rated idle 500-4500RPM(750RPM) CAN send idling speed.
speed
7 Slow rise time 0.0-120.0s(5.0s) The delay time from ECU generating idle
speed to high speed.
c) working plan
No Parameter Range(default) Notes
Disable
Enable 1: remote start
Working
1 Enable 2: mains failure Working plan start condition.
plan
Enable 3: the above 1 or 2
Enable4: running always
2 Start time 00:00-23:59 The start time allowed.
3 End time 00:00-23:59 The end time allowed (the next day is valid).
Multiple choices according to the reality. The
4 Dates 1-31
longest running time is 24 hours.
d) Data/time setting
No Parameter Range(defaults) Notes
1 Date/Time 2016/01/01-2099/12/31
Internal calendar, please calibrate
2 Current time 00:00:00-23:59:59
regularly.
3 Current week Monday to Sunday
e) Self-define curve
NO Parameter Notes
1 Self-define oil pressure resistance curve Sensor curve can be User-defined by
2 Self-define oil pressure voltage curve panel buttons, resistance and
3 Self-define water temperature curve according value should be input,MAX
4 Self-define oil temperature curve 15 groups ,MIN 2 groups.
5 Self-define cylinder temperature curve
58
DC9xD MK2 GENSET CONTROLLER USER MANUAL
59